university of connecticut telecommunications design guide ......bicsi - business industry consulting...
TRANSCRIPT
University of Connecticut Telecommunications Design Guide & Standards
January 2004 University Information Technology Services
369 Fairfield Way, Unit 1209 Storrs, Connecticut
University of Connecticut
Table of Contents
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.1 Definitions and Acronyms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.2 Turn-key Solution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
1.3 UCONN Specific Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
1.4 Regulatory Requirements, Codes and Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
1.5 Certification Requirements and Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2. Telecommunication Rooms and Pathways . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 2.1 Telecommunication Rooms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2.2 Telecommunication Pathways . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
3. Cabling, Terminations and Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9 3.1 Backbone (Riser) Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
3.2 Horizontal Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
4. Work Area Outlets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13 4.1 Typical WAO Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
4.2 Program Space WAO Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
4.3 WAO Faceplates and Labeling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
5. Voice System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16 5.1 Passive Voice Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
5.2 Active Voice Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
6. LAN System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
6.1 Passive LAN Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
6.2 Active LAN Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
6.3 Wireless LAN (WLAN) System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
7. SMATV Video System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 7.1 SMATV Video System Performance Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
7.2 Academic and Administrative Buildings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
7.3 Student Housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Telecommunications Design Guide & Standards January 2004 i
University of Connecticut
8. Building Automation Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
8.1 Building Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
8.2 Point-of-service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
8.3 Public Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
9. Close-out Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25 9.1 Test Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
9.2 As-builts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
9.3 Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
10. Outside Plant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27 10.1 Pathways . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
10.2 Maintenance Holes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
10.3 Outside Plant As-Built Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Appendix A Parts List
B TR Layout and Rack Elevation for LAN Equipment
C WAO Symbols, Configurations, Faceplate & TR Termination Labeling
D Logical LAN Diagrams
E Code Blue Base Template for Pedestal Telephone
F Binding Post Information and LAN Switch Audit Form
G Reference Resources
Telecommunications Design Guide & Standards January 2004 ii
University of Connecticut
1. Introduction
The purpose of this document is to establish a strategic direction for the physical and logical
connectivity of telecommunications systems at the University of Connecticut. A properly designed
and constructed telecommunications systems based on industry standards will promote an efficient,
long-lasting and cost-effective telecommunications system. The University of Connecticut recognizes
and adopts for itself the Telecommunication's industry standards and practices as defined and/or
interpreted by those agencies listed in section 1.4. As such, the intent of this document is to identify
and define those requirements specific to the needs and practices of the university. The
implementation of this design guide and standards will ensure a flexible, uniform telecommunications
environment that will allow for the growth of high speed, high bandwidth required by specialized
applications used in a higher education environment.
This design guide is a living document and as such, the criteria contained within are subject to
revisions and updates as needed due to technological advances within the telecommunications
industry.
1.1 Definitions and Acronyms
To establish a common understanding, this document and the University of Connecticut use the
following definitions, terms and acronyms.
UCONN, the University of Connecticut, is the owner of all property and completed projects,
unless otherwise specified in the project. As the owner, UCONN has the right to enforce or
modify all applicable codes, standards, and UCONN specific requirements.
UNIVERSITY ITS, University Information Technology Services, is the department that is
responsible for maintaining all of UCONN’s telecommunications systems. As such, UNIVERSITY
ITS shall be entitled to final approval of the design, parts, and equipment proposed for UCONN’s
telecommunications infrastructure and systems.
UCIMT, University Center for Instructional Media and Technology, is the department that is
responsible for maintaining all audio/visual systems (AV) for UCONN’s Hi-tech Classrooms. As
such, UCIMT shall be entitled to final approval of all AV designs proposed for UCONN’s Hi-tech
Classrooms.
The term “shall” is used to denote requirements set forth by UCONN that are not negotiable or
arbitrary.
The term “should” is used where UCONN strongly recommends certain guidelines or practices.
Telecommunications Design Guide & Standards January 2004 1
University of Connecticut
AFF – Above Finished Floor AOR – Area of Refuge/Rescue AV – Audio Visual BAS – Building Automation Systems BDF – Building Distribution Frame CATV – Cable Television EF – Entrance Facility ER – Equipment Room HVAC – Heating, Ventilating, and Air-conditioning IDF – Intermediary Distribution Frame LAN – Local Area Network MDF – Main Distribution Frame MH – Maintenance Hole OEM – Original Equipment Manufacturer OTDR – Optical Time Domain Reflectometer RCDD – Registered Communications Distribution Designer RF – Radio Frequency RMU – Rack Mount Unit RPS – Redundant Power Supply SMATV – Satellite Master Antennae Television TLT – Telecommunications Infrastructure Layout Technician TR – Telecommunications Room UPS – Uninterruptible Power Supply UTP – Unshielded Twisted Pair VMIU – Video Mask Interdiction Unit WAO – Work Area Outlet WI-FI – Wireless Fidelity WLAN – Wireless Local Area Network Refer to section 1.4 for abbreviations or acronyms of regulatory and industry agencies.
1.2 Turn-key Solution
All telecommunication designs and installations for UCONN administrative, academic, residence
halls and apartment buildings shall be such that at the completion of the project, UCONN is
provided with complete and operational voice, LAN and SMATV video systems consistent with
the guidelines set forth in this document. Designs and installations shall incorporate existing
systems to ensure a seamless co-existence of newly installed and existing systems. Certified
personnel as specified in section 1.5 shall perform all designs and installations.
Telecommunications drawings shall be identified as T-series in the approved construction
drawings. The telecommunications section of the specification manual shall be numbered
separately and distinctly from other sections as proposed by the Construction Specifications
Institute for the MasterFormat™.
Telecommunications Design Guide & Standards January 2004 2
University of Connecticut
Designs for TRs, cable pathways, voice, LAN and SMATV video systems shall be provided to
UNIVERSITY ITS for approval prior to bid. Submittals of all parts and equipment shall be
provided to UNIVERSITY ITS for approval prior to purchase.
1.3 UCONN Specific Materials
UCONN has standardized on specific brands and warranties for telecommunications cabling and
system requirements. Refer to section 9.3 to ensure compliance with required warranties. All
design specifications and bids submitted shall be based on materials and equipment as specified,
without substitution. UCONN’s parts and materials list will be updated continually to amend
discontinued items or technological changes. As such, modifications to the parts and materials
specified in the bid package may be required.
The parts and materials list should not be considered a complete list as additional parts may be
required to provide complete solutions. All materials, equipment, hardware, and components
shall be new and free from defects in materials, composition, and installed workmanship.
Materials and equipment shall be installed, placed, terminated, tested, handled, and processed in
a manner consistent with manufacturer’s instructions, prevailing codes, ordinances, regulations,
standards or UCONN specific requirements, whichever is more stringent.
1.4 Regulatory Requirements, Codes and Standards All work on UCONN campuses shall be in compliance with the following industry codes,
standards, and practices, as well as, UCONN specific requirements. It is the responsibility of all
trades to know and comply with the most current revisions of all codes, standards, and practices
set forth by the following agencies.
ANSI - American National Standards Institute ASME - American Society of Mechanical Engineers ASTM - American Society for Testing and Materials BICSI - Business Industry Consulting Services International EIA - Electronic Industries Alliance FCC - Federal Communications Commission IEEE - Institute of Electrical and Electronics Engineers Inc. NEC - National Electrical Code NEMA - National Electrical Manufactures Association NFPA - National Fire Protection Association OSHA - Occupational Safety and Health Administration SCTE - Society of Cable Television Engineers State of Connecticut and Local Building Codes TIA - Telecommunications Industry Association UL - Underwriters Laboratories
Telecommunications Design Guide & Standards January 2004 3
University of Connecticut
All code requirements, industry standards and practices, and UCONN specific requirements shall
be enforced, however, where they differ, the more stringent or UCONN specific requirements
shall be applied.
1.5 Certification Requirements and Documentation A TLT, who is also a BICSI certified RCDD, shall approve and stamp all drawings and documents
relating to the telecommunications infrastructure design. This includes, but is not limited to, all
TRs, riser diagrams identifying cable counts and sizes, WAO locations, and logical designs.
Current certifications shall be provided to UCONN/UNIVERSITY ITS in conjunction with print
and/or design submittals.
The cabling vendor shall provide documentation supporting their active status as a qualified
certified installer prior to award of the bid and/or installation of cabling components. Copies of the
certificates shall be provided to UNIVERSITY ITS prior to installation.
All SMATV video systems shall be designed and engineered by an SCTE Broadband
Communications Engineer. All SMATV video systems shall be installed and tested by SCTE
Broadband Communications Technician(s).
All trades working on the installation of the telecommunications infrastructure, voice, LAN, and
SMATV video systems shall provide licenses and/or certifications as required for manufacturers’
warranties.
Telecommunications Design Guide & Standards January 2004 4
University of Connecticut
2. Telecommunication Rooms and Pathways
Telecommunication rooms are designed specifically to house telecommunications equipment and
wiring. These rooms have specific requirements due to the nature, size and complexity of the
equipment and wiring housed in the room and shall not be combined with other occupants or building
support systems. All TRs shall be locked and keyed per UCONN specifications.
Telecommunication pathways provide a means of distributing cabling within a building. Pathways
include, but are not limited to, conduits, trays, sleeves and ducts between TRs, and between TRs and
WAOs.
Fire safety codes and regulations shall be met. Where applicable, plenum spaces shall be identified
on drawings and plenum rated cabling and materials shall be specified. 2.1 Telecommunication Rooms / Equipment Rooms
All UCONN TRs house active equipment and shall follow the design requirements for ERs.
Design considerations include, but are not limited to, location, size, lighting, ceiling, flooring,
HVAC, grounding, power, doors, equipment racks, clearances, and pathways required to
complete the voice, LAN and SMATV video systems. Modifications may be necessary due to
University and/or specific needs of the building. TRs should be rectangular in shape and shall
have a minimum of 80 square feet of useable floor space free from overhead obstructions and
ductwork to a height of 8’.
Detailed layouts for equipment racks, cable management, backboards, termination fields, power
outlets and appropriate clearances shall be shown on the T-drawings. Flame retardant plywood
backboards shall be installed on all walls from floor to ceiling. One wall shall be designated for
the voice system and one wall for the SMATV video system.
UCONN’s LAN system requires a minimum of two floor-mounted, equipment racks per TR. Rack
usage shall be dedicated for either active electronic equipment (active rack) or passive cable
terminations (passive rack). The designed rack fill for active and passive racks shall not exceed
32 RMUs. The active rack design shall include LAN switches (not to exceed 288 LAN
connections), horizontal wire management, power strip, and if necessary LAN and video
distribution equipment. Where needed, a UPS shall be installed at the bottom of the active rack.
The UPS shall not be included as part of the above specified limit of 32 RMUs. The passive rack
design shall include patch panels (not to exceed 288 connections), horizontal wire management,
optical fiber termination box, and optical fiber management. Additional active and passive racks
shall be required if the LAN connections should exceed the above specified limits. These
specifications may require room sizes to be larger than those previously specified.
Telecommunications Design Guide & Standards January 2004 5
University of Connecticut
Equipment racks shall be installed side-by-side in a single row. Equipment racks shall have
vertical cable management troughs (minimum 6" wide) installed between the racks and on each
end of the row. Equipment racks shall have a minimum clearance of 3' to the front and rear and
at least one end of the row. These clearances shall be measured from the edge of any
equipment installed in the racks to the surface of any equipment installed on the walls. For
design purposes a 2' by 2' footprint with the centerline located 7.5" from the front can be
estimated per rack, for vertical management, use 6” between the racks and on the end of each
row as specified above.
Note: The use of one rack may be appropriate in installations where
LAN counts are minimal and future growth is limited. However, this is
not a standard design and any deviation from UCONN’s standard
requirements is subject to approval by UNIVERSITY ITS.
All TRs shall have ladder rack around the perimeter and over the equipment racks to provide a
cable pathway. The width of the ladder rack shall be designed to accommodate and support the
volume of the cables including service loops. The ladder rack and support system shall be
sufficiently strong and well secured to building structure to bear the weight of the cables and any
splice enclosures. Each equipment rack shall be securely fastened to the ladder rack to provide
seismic bracing.
All TRs shall have a minimum of three 20-amp, dedicated, duplex power outlets, one for each
area of voice, LAN and SMATV video terminations. One duplex power outlet box should be
placed in close proximity to the voice termination field and one for the SMATV video field. One
duplex power outlet box should be mounted high on the wall near the location of the active rack,
or if the racks are located in the center of the room, the outlet box should be mounted on the
ladder rack or active rack.
2.2 Telecommunication Pathways
Design considerations for pathways shall include, but are not limited to, conduits, cable trays,
sleeves, ducts, pull boxes, conduit fill, building layout, and other utilities. Due to University and/or
building specific needs, modifications may be necessary. All pathways shall be bonded and
grounded as required by those agencies listed in section 1.4.
Detailed layouts of pathways shall be shown and labeled on T-drawings. UNIVERSITY ITS shall
approve design of all cable pathways before the release of the bid package. All pathway
conduits, trays, sleeves, ducts, pull boxes, etc. shall be sized to accommodate proper cable bend
radii, current cable counts, maintenance, future growth and adequate fire stopping where needed.
Telecommunications Design Guide & Standards January 2004 6
University of Connecticut
2.2.1 Backbone (Riser) Pathways
Backbone pathways shall have a minimum of three 4” trade size conduits or sleeves for
cabling between TRs. Vertical ladder rack shall be installed from floor to ceiling to establish a
cable pathway between riser sleeves. Upon completion, there shall be a minimum of one
spare conduit or sleeve for future use. Where possible, a pathway should extend to the roof
to accommodate future cabling needs.
2.2.2 Horizontal Pathways
All penetrations shall be sleeved with metallic conduit or equivalent. All sleeves shall be
reamed, have a plastic bushing installed on each end, and extend 4” beyond the wall or
ceiling on each side. Sleeves shall be of sufficient size to accommodate cabling and fire
stopping plus 40% spare capacity to allow for future cabling. Cable pathways shall be accessible and follow the corridors of the building. Where cable tray
or conduit is not specified, a continuous pathway of independent cable supports shall be
provided. The distance between supports shall not exceed 48” and shall be fastened to the
building structure.
Conduits shall provide a pathway from each WAO box to an accessible common cable
pathway. Conduits shall be sized to accommodate the number of cables specified for
installation with room for additional fill. Conduits shall be a minimum of 1” in diameter. All
conduits used for WAOs shall stub into an outlet box. Box-connectors and plastic bushings
shall be installed on all conduits.
2.2.2.1 Outlet Boxes
All concealed outlet boxes shall be a minimum of 4-11/16” x 4-11/16” x 2-1/8” with a
single gang plaster ring. Each outlet box shall have a minimum of 1” diameter conduit
stubbed to an accessible cable pathway system
2.2.2.2 Surface Mounted Raceway
Raceway shall be metallic and sized to accommodate the number of cables specified for
installation with proper cable bend radii and room for additional fill. Split or dual channel
raceway shall be specified for installations that require both power and
telecommunication services to share raceway.
Telecommunications Design Guide & Standards January 2004 7
University of Connecticut
All surface-mounted raceway shall be identified and labeled on the print set with the
contents and the from-to locations.
2.2.2.3 Modular Furniture and Paneling
Furniture and paneling shall accommodate UCONN specific materials. UNIVERISTY ITS
shall be consulted to ensure compliance with University telecommunications needs.
Telecommunications Design Guide & Standards January 2004 8
University of Connecticut
3. Cabling, Terminations, and Testing
This section pertains to the inside plant cabling as UCONN provides and installs all outside plant
cabling and terminations. All installations shall be such that cables are labeled and routed neatly
for ease of identification. Only test results with passable readings shall be accepted. All failed
readings shall be corrected and retested prior to submittal. See section 1.3. UCONN Specific
Materials
3.1 Backbone (Riser) Cabling
Each horizontal cross-connect shall have a direct backbone to the main cross-connect.
3.1.1 Optical Fiber Backbone Cabling and Termination Requirements
The minimum strand count for optical fiber backbone cable is 12 strands of singlemode and
12 strands of multimode optical fiber cable. A maintenance loop of at least 20' of cable shall
be neatly stored within the TR for each optical fiber cable.
Singlemode optical fiber shall be 9/125-micron. UCONN uses FC/APC-type connector
pigtails fusion spliced to backbone singlemode optical fiber. Mechanical splices are not
acceptable.
Multimode optical fiber shall be 62.5/125-micron. UCONN uses ST-type, ceramic tip,
epoxy/heat-cure connectors.
3.1.1.1 Optical Fiber Testing Specifications
All singlemode optical fiber strands shall be tested using a light source and power meter
in one direction and per manufacturer’s extended warranty specifications. Strands shall
be tested at the 1310nm and 1550nm wavelengths. No loss shall exceed the sum of
.75db per mated connector pair plus .3db per splice plus the calculated cable length
insertion loss.
All multimode optical fiber strands shall be tested using a light source and power meter in
one direction and per manufacturer’s extended warranty specifications. Strands shall be
tested at the 850nm and 1300nm wavelengths. No loss shall exceed the sum of .75db
per mated connector pair plus .3db per splice plus the calculated cable length insertion
loss.
Telecommunications Design Guide & Standards January 2004 9
University of Connecticut
Testing shall be done with the 1-jumper referencing method. In addition, all spliced
multimode and singlemode optical fiber strands (other than pigtail splices) shall be tested
with an OTDR. OTDR traces shall be provided at the 850nm wavelength for multimode
and the 1310nm wavelength for singlemode. Traces shall be in one direction only.
Test results shall be electronic and include each strand labeled with from-to locations,
test speed, test date and time, and certification of the operator(s) performing the tests.
3.1.2 UTP Backbone Cabling and Termination Requirements
Backbone cabling shall be sized to have a minimum of 2 pairs for every voice port plus 40%
growth capacity to each TR. Size accordingly in 100 pair increments. All backbone cabling
shall terminate on 110-type connector blocks using C-5 connectors.
A binding post spreadsheet shall be provided to UNIVERSITY ITS for cross-connect
identification purposes. UNIVERSITY ITS shall receive this information in order to activate
dial tone at least two weeks prior to building automation system needs or four weeks prior
occupancy which ever comes first.
3.1.2.1 UTP Backbone Testing Specifications
Each cable and pair shall be tested for point-to-point continuity. This includes testing to
verify binding post locations and to insure there are no opens, shorts, crosses, or
grounds. All testing shall be performed using certified calibrated testers and shall be
done in accordance to OEM requirements for warranty.
Documentation shall include the testing equipment make, model, and setting(s) used, as
well as, cable identification numbers, from-to locations of each cable, and test date and
times.
3.1.3 Coaxial Backbone Cabling and Termination Requirements
Specify Parameter III .500 hard-line coaxial CATV-R distribution cable to be installed
between TRs. No kinks or damage to the outer sheath are allowable. All connectors shall be
terminated with OEM specified tools. At least 10 feet of slack shall be left neatly routed
around the perimeter of the termination area in each TR. Minimum bend radius restrictions
shall be observed for all coaxial backbone cable.
Power supply voltage (60 VAC) shall not be run through F-connectors in the backbone.
Telecommunications Design Guide & Standards January 2004 10
University of Connecticut
3.1.3.1 Coaxial Backbone Testing Specifications
Each cable shall be tested for point-to-point continuity. Testing shall be done in
accordance to OEM requirements for warranty. All testing shall be performed using
certified calibrated testers.
Documentation shall include the testing equipment make, model, and setting(s) used, as
well as, cable identification numbers, from-to locations of each cable, test date and times.
3.2 Horizontal Cabling
All cables shall be continuous and without interruption from the WAO to the termination point in
the TR. In-line splices, splits, taps or bridges are not acceptable in horizontal station cabling
runs.
3.2.1 UTP Horizontal Cabling and Termination Requirements
Unshielded twisted pair cabling shall be 4-pair, Category 5e, and green in color. Cable shall
be in accordance with OEM manufacturer’s requirements for warranty as specified in section
1.3.
The TR end of the cable shall terminate onto 110-type connector blocks using C-4
connectors for voice and 48-port patch panels using 8-pin, 8-conductor, T568B modular
connectors for LAN. The WAO end of the cable shall terminate on an 8-pin, 8-conductor,
T568B modular connector. Connectors for Category 5e shall match the color of the faceplate
for voice and green for LAN.
Both ends of each cable shall be labeled with the 5-digit WAO number followed by the 1-digit
port number using machine printed labels.
3.2.1.1 UTP Horizontal Testing Specifications
Testing shall be done in accordance to OEM manufacturer’s requirements as specified to
meet the appropriate end-to-end solution for warranty. All testing shall be performed
using certified calibrated testers.
Test results shall include the testing equipment make, model, and setting(s) used, as well
as, cable identification numbers (5-digit WAO number plus the 1-digit port number), from-
to locations of each cable, and test date and times.
Telecommunications Design Guide & Standards January 2004 11
University of Connecticut
3.2.2 Coaxial Horizontal Cabling and Termination Requirements
Each end of the coaxial cable shall be terminated with F-style compression fittings. Positive
compression type connectors with minimal signal leakage characteristics shall be installed
with OEM installation tool. Hex crimp connectors are not acceptable.
The TR end of the cable shall be connected to either a ground block F-81, splitter, or VMIU,
mounted neatly and securely to the termination backboard. The WAO end of the cable shall
be connected to an F-style insert.
Both ends of each cable shall be labeled with the 5-digit WAO number using machine printed
labels. Alternatively, in the TR only, each coaxial cable shall be labeled with the
corresponding 5-digit WAO faceplate number on the tab of a cable tie identifier, using a fine
point indelible marker. For student housing locations, the cable shall have an additional
cable tie identifier, on the cable between the splitter and the interdiction unit, near the
interdiction output port that is labeled with the 3-digit room number. All labels shall be legible
and identifiable.
3.2.2.1 Coaxial Horizontal Testing Specifications
All coaxial cable shall be tested with a TDR for length, impedance and continuity.
All coaxial cables shall be tested to assure compliance with FCC standards for
broadband CATV systems. A frequency response sweep of the building distribution
system shall be performed. The response shall meet the minimum FCC requirements
for frequency response and ripple.
Test results shall include the testing equipment make, model, and setting(s) used, as well
as, cable identification numbers (5-digit WAO number), from-to locations of each cable,
and test date and times
Telecommunications Design Guide & Standards January 2004 12
University of Connecticut
4. Work Area Outlets
Work area outlets consist of voice, LAN and/or SMATV services. Voice and LAN services use 4-pair
UTP cables terminated on 8-pin, 8-conductor, T568B modular connector jacks. SMATV services use
RG-6 coaxial cables terminated on F-type modular connector jacks. UCONN uses typical variations
of WAOs. UCONN has established minimum WAO requirements based on program space. Work
area outlets are typically 18” AFF unless otherwise noted. Refer to section 8 for building automation
systems requirements.
4.1 WAO Configurations
The following descriptions are for typical WAO configurations. Other configurations may be needed
to meet specific application requirements.
Standard Two 4-pair UTP cables terminated on 8-pin, 8-conductor, T568B modular connector jacks, one for
a voice connection and one for a LAN connection.
Wall Phone
One 4-pair UTP cable terminated on 8-pin, 8-conductor, T568B modular connector jacks for a
voice connection, 48”AFF.
LAN Two 4-pair UTP cables terminated on 8-pin, 8-conductor, T568B modular connector jacks for LAN
connections.
SMATV One RG-6 coaxial cable terminated on F-type modular connector jack.
Multi-media Two 4-pair UTP cables terminated on 8-pin, 8-conductor, T568B modular connector jacks, one for
a voice connection and one for a LAN connection and one RG-6 coaxial cable terminated on an
F-type modular connector jack.
Telecommunications Design Guide & Standards January 2004 13
University of Connecticut
4.2 Program Space WAO Requirements
The following are minimal WAO requirements based on typical program spaces. Additional
WAOs may be required for ancillary devices (printers, fax machines, etc.), specific needs of the
occupant(s), and size or intended use of the room.
Faculty/Staff Offices
Two standard WAO located on opposite walls.
Dean/Director Offices One standard WAO and one multi-media WAO located on opposite walls. Clerical Staff/Graduate Student Offices and Work Areas One standard WAO shall be provided for each desk or workspace.
Conference Rooms One standard WAO and one multi-media WAO located on opposite walls.
Lounges/Break Rooms One multi-media WAO.
Computer Labs
One LAN WAO for every two computers, one SMATV or multi-media WAO, one wall phone WAO
located near the door.
Classrooms
One multi-media WAO located near the teaching station and one wall phone WAO located near
the door.
Hi-tech Classrooms
UCIMT maintains all Hi-tech Classrooms and shall be consulted for specific WAOs and AV
requirements. Cabling specifically for AV shall use pathways designed specifically for the AV
system and shall at no time be located in pathways designed for cabling of UCONN’s voice, LAN,
and SMATV video systems.
Student Housing Double occupancy bedrooms shall have one standard WAO and one multi-media WAO located
on opposite walls. Single occupancy bedrooms shall have one multi-media WAO.
Common areas, such as living rooms, in apartments or suites shall have one SMATV WAO.
Study rooms and lounges shall have one standard WAO and one multi-media WAO located on
opposite walls.
Telecommunications Design Guide & Standards January 2004 14
University of Connecticut
4.3 WAO Faceplates and Labeling
All faceplates shall be flush-mounted, single gang and specified to match electrical faceplate in
quality and finish.
UCONN uses colored jacks in addition to location in the faceplate to identify the jack application.
A jack that matches the faceplate shall identify voice applications and a green jack shall identify
LAN applications. Where applicable, the top position of the faceplate shall be used for voice, the
bottom or middle position for LAN and the bottom position for SMATV video.
Work area outlet faceplates shall be numbered from left to right around the room when entering
through the door. Faceplates shall be labeled with a black on white printed label. Handwritten
labels will not be accepted. Each faceplate shall be identified with a 5-digit label. This format
shall identify the room number and the outlet location within the room separated by a dot. For
example: 101.02 would be room 101 (101.02), outlet location 2 (101.02).
Student housing applications may differ if room numbers include alpha designations. For
example: 101.A1 would be room 101 (101.A1), bedroom A (101.A1), outlet location 1 (101.A1).
T-drawings should include an example of each type of WAO configuration, a WAO numbering
submittal of each floor based on the room numbering scheme provided by UCONN and a
summary of all WAO faceplate counts.
Telecommunications Design Guide & Standards January 2004 15
University of Connecticut
5. Voice System
UCONN owns a Centrex System and provides and maintains all dial tone for the University. As such,
UNIVERITY ITS performs all end-user service requests, including adds, moves and changes.
5.1 Passive Voice Equipment
The voice system shall be terminated on 110-type connector blocks with jumper troughs.
Distribution rings for cable management shall be installed on the backboard for voice cabling.
The voice backbone 110-type connector blocks shall be placed together on the backboard in the
left-most position to allow room for expansion. The voice station 110-type connector blocks shall
be placed in the right-most position with room for expansion.
All building automation systems requiring voice circuits such as, fire alarm and elevator shall be
terminated on a separate 110-type connector block. Typically the building automation systems
110-type connector block should be located to the right of the voice station 110-type connector
block field.
Every row on the 110-type connector blocks shall be labeled with designation strips including a
printed label with the identification number of backbone or station cable. Backbone 110 field
labels shall be white and station 110 field labels shall be blue. Building automation system 110
field labels shall be red.
Each station label on the 110-type connector block shall consist of the corresponding 5-digit WAO
faceplate label, followed by the 1-digit port number separated by a dot. For example, WAO
faceplate label 101.02, port 1 shall be labeled 101.02.1. Building automation systems shall be
labeled accordingly as “FIRE.1”, “FIRE.2”, or “ELEV.1”, “ELEV.2”, etc.
5.2 Active Voice Equipment
UNIVERSITY ITS performs all horizontal voice cross-connects needed for dial tone.
Telecommunications Design Guide & Standards January 2004 16
University of Connecticut
6. LAN System
UCONN owns and maintains the LAN system and provides core connectivity to all buildings. As
such, UNIVERSITY ITS will determine all core and distribution needs including configuration of all
LAN hardware. No external links or gateways to other networking resources shall be installed on the
UCONN network.
The building LAN shall be designed to provide a turn-key solution which includes at a minimum, LAN
switches, patch cables, optical fiber cables, station cables and any ancillary materials necessary for
the activation of the network for the project. UNIVERSITY ITS shall approve LAN designs prior to
release of the bid package.
The LAN design shall provide one Ethernet switch port for every LAN jack with a minimum of twelve
spare ports per TR for future growth. UNIVERSITY ITS and the University occupants of the building
shall be consulted regarding special networking requirements.
All LAN hardware shall be delivered to UNIVERSITY ITS for configuration approximately six weeks
prior to installation. Prior to core connectivity of the LAN system, UNIVERSITY ITS shall receive the
LAN system cross-connect spreadsheet detailing the switch port to LAN jack location.
6.1 Passive LAN Equipment
The LAN system shall be terminated on 48-port patch panels, wired for T568B with rear wire
management and installed in the equipment rack designated for passive use. Horizontal cable
managers shall be installed above and below each patch panel for LAN cabling.
Building automation systems requiring a LAN connection, such as HVAC or power monitoring,
shall be terminated on patch panels and follow the LAN WAO configuration.
Each port on the patch panel shall be labeled on the front with printed labels. Labels on the patch
panel shall consist of the corresponding 5-digit WAO faceplate label, followed by the 1-digit port
number separated by a dot. For example, WAO faceplate label 101.02, port 2 shall be labeled
101.02.2. 6.2 Active LAN Equipment
All LAN hardware and interconnect cabling needed to provide a turn-key solution shall be
included in the design. LAN hardware shall consist of aggregate and edge switches and
associated components as needed to complete the LAN system for the project. All LAN switches
shall be installed in the equipment rack designated for active use with cable managers above and
Telecommunications Design Guide & Standards January 2004 17
University of Connecticut
below each switch. In addition, one power-strip with surge suppression is required per active
rack.
The LAN design shall accommodate all necessary connections between the core and aggregate
layers and the edge switch stack(s). All LAN switches shall be connected using the appropriate
module. All optical fiber used for the LAN system interconnects shall be duplex OEM assembled
cables. If a building consists of only one TR, please consult UNIVERSITY ITS, as an aggregate
switch may not be required.
A star configuration shall be used for TR and building aggregation design. At least one port on
the aggregate switch is required for UNIVERSITY ITS to provide a core connection. Each
aggregation point shall be connected to an UPS. Where an aggregation point serves more than
one building, a redundant power supply (RPS) is also required.
A cascade configuration shall be used for each TR edge stack design. Each edge switch stack
requires a minimum of one port on the aggregation switch for uplink connection(s). Each stack
shall not exceed 288 LAN connections. -
6.3 Wireless LAN System
A WLAN system has not been approved for release. UCONN is in the process of defining
policies and usage requirements for all WLAN systems. These policies and requirements will be
specified in a UCONN WLAN White Paper.
UNIVERSITY ITS authorizes and manages the use of all Industrial, Scientific, and Medical (ISM)
bands on University premises defined by the FCC for use with unlicensed devices including: 902-
928 MHz (26 MHz), 2.4-2.4835 GHz (83.5 MHz) and 5.725-5.85 GHz (125MHz) frequencies. All
unlicensed ISM band devices shall comply with UCONN’s application of these bands for use on
the University premises.
UNIVERSITY ITS shall approve all WLAN designs prior to release of the bid package in addition
to submittals before installation of the system. Unauthorized installations are not permitted and
are subject to removal from UCONN’s network.
6.3.1 WLAN Design Requirements
UCONN’s proposed WLAN system is based on the IEEE 802.11b (802.11g, once ratified)
standard. All WLAN designs shall include: clearly defined projected areas of contained
coverage, access point quantities, locations, antenna type and placement, and appropriate
Telecommunications Design Guide & Standards January 2004 18
University of Connecticut
channel selection. An in-line Power over Ethernet (PoE) LAN switch and termination of LAN
jacks for access points on a separate patch panel may be required for larger installations.
One LAN WAO shall be provided for each access point location. All access points and
accessories shall be accessible for service and protected from theft and damage. The design
should note the exact location of the access point in relation to the finished ceiling.
All WLAN hardware shall be delivered to UNIVERSITY ITS for configuration approximately
six weeks prior to installation. In designs that include wireless network interface cards (NIC),
UNIVERSITY ITS shall be provided with all MAC addresses and corresponding user names.
This information is required for authentication and access to the WLAN system.
6.3.2 WLAN Testing and Documentation
All installations shall be field tested with a WI-FI certified device for signal strength and
coverage. As-built documentation of floor layouts shall illustrate all RF radiation patterns
emitted from each access point. RF leakage outside the scope of the project shall be
included in the diagram.
Telecommunications Design Guide & Standards January 2004 19
University of Connecticut
7. SMATV Video System
UCONN owns and maintains the SMATV video system and provides core connections to all
buildings. As such, UNIVERSITY ITS will determine and provide all core and distribution needs to the
demarcation of each building.
The SMATV video distribution system shall be designed to provide a turn-key solution that includes
video hardware, cables and any ancillary materials necessary for the delivery of video from the
building demarcation point to each WAO. UNIVERSITY ITS shall approve the design of the SMATV
video system before the release of the bid package.
Student housing video distribution systems differ from academic video distribution systems as they
utilize addressable interdiction systems, where academic systems employ traditional passive
equipment.
All splitters, directional couplers, taps or other active or passive devices are to be confined within
TRs. No equipment shall be mounted above ceilings, within walls or in any other locations. Passive
equipment and materials shall be 1,000 MHz. 7.1 SMATV Video System Performance Requirements
Distribution of the SMATV video system shall be balanced to provide each video WAO location
with the minimum acceptable carrier signal level for any CATV channel between 2 and 80 is 3
dBmV. No visual carrier shall differ from an adjacent carrier by more than 3dB. The maximum
difference between the highest and lowest visual carrier levels shall not exceed 13dB. At each
video WAO location 15 dBmV at channel 80 and 12 dBmV at channel 2 will be the maximum
allowed output. The minimum level at any output is 4 dBmV at channel 80 and 1 dBmV at
channel 2.
Minimum C/N ratio shall be 45 dB at the end of the horizontal run. Composite Second Order
(CSO) shall not exceed 55 dB at the end of the horizontal run. Composite Triple Beat (CTB)
shall not exceed 55 dB at the end of the horizontal run. Hum to Carrier shall not exceed 3% at
the end of the horizontal run.
7.1.1 Amplifier and Tap Levels
Levels entering any amplifier between the lowest and highest channel shall meet the
manufacturer’s specifications.
Telecommunications Design Guide & Standards January 2004 20
University of Connecticut
7.1.2 Return Path
Each amplifier shall have return capability between 5-42 Mhz installed, activated and
balanced to manufacturer’s specifications.
7.2 Academic and Administrative Buildings
UCONN’s SMATV video system in academic and administrative buildings requires amplifiers and
passive electronics. The design of the SMATV video system in these locations is required to
meet the specified performance levels for signal at each video WAO location.
7.3 Student Housing
UCONN’s SMATV video system in residence halls or apartment buildings require interdiction taps
to provide service to all video WAO locations. UNIVERSITY ITS controls interdiction units using
an automated system.
Interdiction units require line-powered 60VAC for operation, and require additional internal
directional couplers, pads and equalizers to be correctly configured and installed for operation.
Interdiction units have specific, manufacturer recommended operational windows for input and
output levels for proper operation.
In cases where one residence unit may require multiple drops, a splitter may be installed in the
TR, in close proximity to the VMIU. Layout of splitter and cable management shall be presented
prior to installation and approved by UNIVERSITY ITS. Drop amplifiers are not permitted to
extend horizontal coaxial lengths unless approved by UNIVERSITY ITS in writing.
Power passing taps shall be used to provide signal and power to each VMIU. In cases where a
single VMIU port feeds multiple horizontal runs, all performance requirements at the WAO
locations shall be met. Length of the cable runs shall be considered in the design due to the
limited output levels of the interdiction devices. Determining maximum horizontal cable length by
calculating the output levels of taps to accommodate multiple locations within each residence unit
is the responsibility of the system designer/engineer.
7.3.1 Testing Interdiction in Student Housing
UNIVERSITY ITS shall be provided with a document identifying the VMIU port-to-room
assignments. This information is used to map the specific interdiction port address used to
serve a specific room and shall include: interdiction unit serial and digital numbers from the
barcode label on the housing, building name as identified by UCONN, and the corresponding
Telecommunications Design Guide & Standards January 2004 21
University of Connecticut
room/suite numbers as assigned by UCONN. UNIVERSITY ITS shall receive this information
at least five days prior to testing. For installations of more than 12 interdiction units,
additional time will be required to input the data into the interdiction system controller prior to
operational testing.
Two operational tests will be used to verify interdiction unit configuration and operation. One
test is a visual inspection of each output port. This test is performed with a cable ready
television at the WAO. Video service is turned on and off using the management system.
The other test checks the interdiction units. Each port shall be shown to jam channels 49-53.
Both of these tests require a coordinated effort. UNIVERSITY ITS will work with the installer
and assist in controlling the video signal from the head end. Both UNIVERSITY ITS and the
installer will perform the inspections at the WAOs.
7.3.2 Leakage Testing
UNIVERSITY ITS will conduct a cumulative signal leakage survey of the SMATV video
system and coaxial cable plant after installation and prior to building occupancy. The project
schedule shall accommodate time for UNIVERSITY ITS to perform leakage testing and for
the installer to correct and repair all leaks exceeding FCC regulation. UNIVERSITY ITS will
require a minimum of 3 days notice to schedule and prepare for testing and a minimum of 1
working day for every 48 horizontal coaxial drops to perform inspections and system testing.
UNIVERSITY ITS will provide a list of all leaks exceeding the FCC stated maximum of 20
µV/m measured at 3 meters. The contractor shall be responsible for repairing any signal leak
beyond 20 µV/m as required to be within compliance of FCC regulations. The reported leaks
shall be repaired and documentation of the repairs shall be submitted to UNIVERSITY ITS
before UCONN will accept the system as complete.
Telecommunications Design Guide & Standards January 2004 22
University of Connecticut
8. Building Automation Systems
Building automation systems refer to building monitoring, point-of-service, public safety systems
including Code Blue Emergency Phones, and any other building specific systems. Completion and
activation of telecommunications infrastructure and systems need to be included in the project
schedule based upon requirements for BAS testing and/or activation. UNIVERSITY ITS requires two
weeks notice prior to activation of service.
Building automation systems WAO requirements shall be identified on the T-drawings to ensure that
UCONN voice and/or LAN system requirements are included in the telecommunications design.
UCONN shall be consulted to determine which BAS are required.
Work area outlets for BAS requiring network or dial-up access shall be located within 3 meters of the
control unit. Building automation system WAOs that are located in publicly accessible areas shall be
located within millwork or a secured box specifically for the WAO. A secure pathway shall be run
between the box for the WAO and the building system control unit. Work area outlets shall not be co-
located in a box with building system equipment. Boxes for WAOs shall be visible and accessible
without moving furniture or equipment. In all instances where a WAO is concealed within a box, the
box shall be identified with the WAO number. Submittals of the box, along with shop drawings for
each WAO location shall be provided with the telecommunications submittal package.
8.1 Building Monitoring
Building monitoring systems include HVAC, power monitoring, intrusion detection and any other
monitoring system that may be required.
8.2 Point-of-service
Point-of-service systems include any systems that use card reader technology. These systems
are currently used for building access, point-of-sale transactions, and any other system UCONN
may use to provide these types of services to the University community.
8.3 Public Safety
Public safety systems include emergency and/or needs compliance systems for ADA
requirements. These systems comprise of fire alarm/AOR control systems, elevator monitoring
and phones, building access phones, and ride phones.
Telecommunications Design Guide & Standards January 2004 23
University of Connecticut
8.3.1 Code Blue Emergency Phones
UCONN Public Safety specifies Code Blue Emergency phone locations and UNIVERISTY
ITS provides the phone and cabling. Provisions for foundations and conduit pathways for all
Code Blue Emergency Phones need to be provided by the project.
Each Code Blue Emergency Phone requires two one-inch conduits, one for voice service and
one for electrical service. The telecommunications conduit shall terminate in the main TR of
the building from where service will be provided. This conduit will have a pull string installed,
tied off at both ends, and will be labeled in the TR as “Code Blue”. The electrical conduit
shall terminate in the electrical panel to provide 110VAC power on a dedicated 15-amp circuit
with emergency power backup for each Code Blue phone.
UNIVERSITY ITS shall be provided with as-built drawings that include conduit locations,
electrical panel number and breaker information.
Telecommunications Design Guide & Standards January 2004 24
University of Connecticut
9. Close-out Documentation
UNIVERSITY ITS shall be provided with all test results, as-builts, and warranty information in
electronic format no later than thirty days from completion of project.
9.1 Test Results
All test results shall be submitted to UNIVERSITY ITS in an electronic format. Test results shall
include a reader for the software to ensure that UNIVERSITY ITS will be able to open and view
the results.
9.2 As-builts
UNIVERSITY ITS shall be provided with an electronic copy in AutoCAD of all documentation for
telecommunications. As-built documents shall consist of the bid/construction package including
all addendums and modifications from the original scope. All changes shall be highlighted, noted,
or written in red. This package should include diagrams showing all risers, cable pathways, floor
layouts, and TR diagrams.
Riser diagrams shall include:
1. One-line diagrams for UTP copper cabling with cable counts.
2. One-line diagrams for optical fiber cabling with cable counts.
3. One-line diagrams for coaxial cabling with cable sizes.
Floor diagrams shall include:
1. TR locations and room numbers.
2. WAO locations and faceplate labels.
3. TR wiring zones, which identify WAOs, served.
4. Horizontal cabling pathways including penetrations and fire stopping.
TR diagrams shall include:
1. Butterfly layouts.
2. TR room numbers.
3. Backboard layouts for voice and video systems.
4. Rack elevations for LAN system.
5. Other systems (HVAC, Building automation systems, etc.).
All voice system 110-binding post information, LAN system cross-connects, and student housing
SMATV video system VMIU port-to-jack information shall be entered in Microsoft Excel
Telecommunications Design Guide & Standards January 2004 25
University of Connecticut
spreadsheets. UNIVERSITY ITS shall receive these spreadsheets as either a hardcopy or an
electronic file prior to testing and/or activation of the systems.
9.3 Warranty
UNIVERSITY ITS shall be provided with copies of all OEM system and equipment warranties.
UCONN requires manufacturer’s extended system warranties on all cabling. The approved
manufacturer warranties for structured cabling are NetClear by Ortronics, and ClearBIT or
SureBIT by Hubbell for copper cabling and Corning LANscape Extended Warranty Program for
optical fiber.
All warranty registrations for LAN and SMATV system equipment shall be provided to
UNIVERSITY ITS.
Telecommunications Design Guide & Standards January 2004 26
University of Connecticut
10. Outside Plant
This section pertains to outside plant structure as UCONN provides and installs all outside plant
cabling and terminations. As such, UNIVERSITY ITS shall be consulted regarding outside plant
pathways. UCONN uses an underground conduit system to provide pathways for
telecommunications cabling. Contact UCONN Architectural and Engineering Services for specific
guidelines and requirements for installation of maintenance holes and conduits. UCONN
Architectural and Engineering Services and agencies such as “Call Before You Dig” shall be
contacted prior to breaking ground.
Outside plant pathways include, but are not limited to, conduits, maintenance holes, hand-holes, and
pull-boxes. All outside plant pathways will become property of UCONN upon completion of the
project.
10.1 Pathways
UCONN buildings are fed with a minimum of one 4” conduit and one multi-cell from a
telecommunications maintenance hole. Multi-cell conduits shall be type C with a minimum of four
cells. A minimum of one 4” conduit shall be included in the design as spare to accommodate
future growth to the building.
Duct banks between maintenance holes shall be designed to include a minimum of six 4”
conduits. A minimum of three 4” conduits shall be noted in the design for spare to accommodate
future growth.
Conduits shall be encased in concrete. Conduit runs shall not exceed a maximum distance of
400 feet for installations with a combined bend radius of 180 degrees between any two pulling
spaces. Any changes in direction between pulling spaces shall be included in the maximum
combined bend radius of 180 degrees. For straight installations between pulling spaces, the
maximum distance shall not exceed 600 feet. Where sharp bends or turns are unavoidable,
prefabricated fittings, joint boxes and/or pull boxes may be required. All joints shall be watertight.
A positive drain slope shall be maintained and all unused conduits shall be capped to prevent
water accumulation.
Installation of conduits and duct banks shall include provisions of all necessary accessories
including, but not limited to, couplings, bends, universal terminators at maintenance holes and
each building, slip couplings, and adapters fitting PVC to rigid duct, pull strings, etc. Steel and
PVC ducts shall be encased in a concrete envelope with duct separators. Conduits and duct
banks shall have a warning ribbon at least 12 in. above the underground installation.
Telecommunications Design Guide & Standards January 2004 27
University of Connecticut
10.2 Maintenance Holes
UCONN telecommunication maintenance holes shall be pre-cast with splay entrance and 6 feet
by 12 feet by 7 feet high. Minimum depth from ground surface to top of manhole roof shall be
one foot. Standard hardware required for construction and utilization of maintenance holes shall
be provided. This includes rocking bolt assemblies, vertical support brackets, pulling irons, ladder
support hooks, covers, etc. The cover shall be labeled “telephone” or “communications.”
All conduits shall enter and exit on opposite pre-cored end walls only. Conduits shall be neatly
stacked and splayed into pre-cored knockouts starting on the bottom to allow for future
expansion. All splays shall be outside the maintenance hole to allow for maximum workable
space inside the maintenance hole. At no time shall conduits enter on the sidewall of the
manholes. A water barrier shall be installed at each construction joint
10.3 Outside Plant As-Built Documentation
As-built drawings shall identify and label all conduits, duct banks, maintenance holes, pull-boxes,
hand-holes and junction boxes. Documentation shall include cross sectional diagrams of duct
banks and butterfly diagrams of all maintenance holes, pull-boxes, hand-holes, and junction
boxes.
Telecommunications Design Guide & Standards January 2004 28
University of Connecticut Appendix A
Parts List
OUTSIDE PLANT
Solution Description Manufacturer Part # Detail/Specific Requirements
* Maintenance Hole Rotondo & Son 38Y-4046-1 Telephone Maintenance Hole
* Multi-cell Conduit Carlon MX-4way PVC/Rigid Multi-Gard
VOICE SYSTEM TERMINATIONS
Solution Description Manufacturer Part # Detail/Specific Requirements
Hubbell 110 Wiring Block Hubbell 110BLK100FTK4 100-pair Field Termination Kit with 4-pair Connecting Blocks
Hubbell 110 Wiring Block Hubbell 110BLK100FTK5 100-pair Field Termination Kit with 5-pair Connecting Blocks
Hubbell 110 Wiring Block Hubbell 110BLK300FTK4 300-pair Field Termination Kit with 4-pair Connecting Blocks
Hubbell 110 Wiring Block Hubbell 110BLK300FTK5 300-pair Field Termination Kit with 5-pair Connecting Blocks
Hubbell 110 Wiring Block Hubbell 110TRA Cable Management Trough with Legs
Ortronics 110 Wiring Block Ortronics OR-30200145 110 Wiring Blocks with Legs, 100pr
Ortronics 110 Wiring Block Ortronics OR-30200007 110 Wiring Blocks with Legs, 300pr
Ortronics 110 Wiring Block Ortronics OR-30200109 110C Connecting Blocks, 4 Pair
Ortronics 110 Wiring Block Ortronics OR-30200110 110C Connecting Blocks, 5 Pair
Ortronics 110 Wiring Block Ortronics OR-30200140 Cable Management Trough w/Legs
Ortronics 110 Wiring Block Ortronics OR-70400272 110 Designation Kit (Labeling Kit)
BACKBONE CABLING
Solution Description Manufacturer Part # Detail/Specific Requirements
Hubbell Copper Cable General Cable 2133144 100pr Cat 3 UTP, CMR, Gray
Hubbell Copper Cable General Cable 2133373 300pr Cat 3 UTP, CMR, Gray
Hubbell Copper Cable General Cable 2131377 100pr Cat 3 UTP, CMP, Gray, Plenum Rated
Telecommunications Design Guide & Standards January 2004 1
University of Connecticut Appendix A
BACKBONE CABLING (Continued)
Solution Description Manufacturer Part # Detail/Specific Requirements
Hubbell Copper Cable General Cable 2131474 300pr Cat 3 UTP, CMP, Gray, Plenum Rated
Hubbell Copper Cable Mohawk M55211 100pr Cat 3 UTP, CMR, Gray
Hubbell Copper Cable Mohawk M57098 300pr Cat 3 UTP, CMR, Gray
Hubbell Copper Cable Mohawk M56128 100pr Cat 3 UTP, CMP, Gray, Plenum Rated
Hubbell Copper Cable Mohawk M57211 300pr Cat 3 UTP, CMP, Gray, Plenum Rated
Ortronics Copper Cable Berk-Tek 10032472 100pr Cat 3 UTP, CMR, Gray
Ortronics Copper Cable Berk-Tek 10032494 300pr Cat 3 UTP, CMR, Gray
Ortronics Copper Cable Berk-Tek 10032113 100pr Cat 3 UTP, CMP, Gray, Plenum Rated
Ortronics Copper Cable Berk-Tek 10032124 300pr Cat 3 UTP, CMP, Gray, Plenum Rated
Corning Optical Fiber Corning 0xxK81-33130-24 MIC Riser, Multimode (xx = Number of Strands)
Corning Optical Fiber Corning 0xxR81-33131-24 MIC Riser, Singlemode (xx = Number of Strands)
Corning Optical Fiber Corning 0xxK88-33130-29 MIC Plenum Riser, Multimode (xx = Number of Strands)
Corning Optical Fiber Corning 0xxR88-33131-29 MIC Plenum Riser, Singlemode (xx = Number of Strands)
Corning Optical Fiber Corning 0xxK61-31230-24 Fan-Out Riser, Multimode, Exposed Tray (xx = Number of Strands)
Corning Optical Fiber Corning 0xxR61-31231-24 Fan-Out Riser, Singlemode, Exposed Tray (xx = Number of Strands)
Corning Optical Fiber Corning 0xxK68-31230-29 Fan-Out Plenum Riser, Multimode, Exposed Tray (xx = Number of Strands)
Corning Optical Fiber Corning 0xxR68-31231-29 Fan-Out Plenum Riser, Singlemode, Exposed Tray (xx = Number of Strands)
* Coaxial Cable CommScope P3-500 JCAR Parameter III .500 Riser
* Coaxial Cable CommScope P3-500 JCAP Parameter III .500 Riser, Plenum Rated
* Connector Gilbert GRS-500-CH-DU-03 Pin Connector .500
Telecommunications Design Guide & Standards January 2004 2
University of Connecticut Appendix A
FIBER TERMINATIONS
Solution Description Manufacturer Part # Detail/Specific Requirements
* Optical Fiber, Patch Cords Corning 2121-02R5131-xxxM FC/APC to FC/APC, Singlemode (xxx = Length in
Meters)
* Optical Fiber, Patch Cords Corning 2158-02R5131-xxxM FC/APC to SC, Singlemode (xxx = Length in Meters)
* Optical Fiber, Patch Cords Corning 5050-02K5141-xxxM ST to ST 62.5/125, Multimode (xxx = Length in Meters)
* Optical Fiber, Patch Cords Corning 5039-02K5141-xxxM ST to SC 62.5/125, Multimode (xxx = Length in Meters)
* Optical Fiber, Patch Cords Corning 3939-02K5141-xxxM SC to SC 62.5/125, Multimode (xxx = Length in Meters)
Corning Optical Fiber, Pigtail Corning CCH-CP06-21-P03RH 6 Fiber FC Pigtail, Singlemode (Includes Panel)
Corning Connector Corning 95-100-44BP ST Multimode Epoxy & Polish Connector
Corning Housing Panel Corning CCH-CP06-15 LANscape ST Multimode
Corning Closet Connector Housing Corning CCH-04U LANscape 4U (Accepts 12 Housing Panels)
Corning Closet Connector Housing Corning CCH-02U LANscape 2U (Accepts 4 Housing Panels)
Corning Cable Mgmt. Component Corning CJP-01U LANscape 1U Jumper Management Panel
Corning Cable Mgmt. Component Corning CJP-02U LANscape 2U Jumper Management Panel
Corning Closet Connector & Splice Housing Corning CCS-03U LANscape 3U (Accepts 4 Housing Panels and 4 Splice
Trays)
Corning Closet Splice Housing Corning CJH-02U LANscape 2U, Used with CJP-02U (Accepts 4 Splice Trays)
Corning Closet Splice Housing Corning CSH-03U LANscape 3U (Accepts 12 Splice Trays)
Corning Closet Splice Tray Corning M67-048 LANscape (Accepts 12 Singlemode Splices)
Corning Closet Splice Tray Corning M67-068 LANscape (Accepts 6 Singlemode splices)
Telecommunications Design Guide & Standards January 2004 3
University of Connecticut Appendix A
HORIZONTAL CABLING & ACCESSORIES
Solution Description Manufacturer Part # Detail/Specific Requirements
Hubbell Copper Cable, Horizontal General Cable 6133512 PlatinumPlus 350 Cat 5e UTP, CMR, Green
Hubbell Copper Cable, Horizontal General Cable 6131547 PlatinumPlus 350 Cat 5e UTP, CMP, Green, Plenum
Rated
Hubbell Copper Cable, Horizontal Mohawk M56165 MegaLAN 400 Cat 5e UTP, CMR, Green
Hubbell Copper Cable, Horizontal Mohawk M56166 MegaLAN 400 Cat 5e UTP, CMP, Green, Plenum
Rated
Hubbell Faceplate, Single Gang Hubbell IFP Series Plastic (Standard Configurations are 2, 3 or 4 Ports)
Hubbell Faceplate, Single Gang Hubbell P630S1GJ8 Stainless Steel Wall Phone Plate (RJ45, T568B Jack)
Hubbell Faceplate, Single Gang Hubbell SSF series Stainless Steel (Standard Configurations are 2, 3 or 4
Ports)
Hubbell Jack Hubbell HXJ5EGN RJ45, T568B, Cat 5e, Green (LAN Applications)
Hubbell Jack Hubbell HXJ5EOW RJ45, T568B, Cat 5e, Office white (Voice Applications)
Hubbell Jack Hubbell SFB10 Blank, 10/pack, Office white
Hubbell Jack Hubbell SFFX Snap-fit F-Connector, Office white
Hubbell Outlet Box Hubbell AMO Multimedia Outlet (Accepts 6 Brackets)
Hubbell Outlet Box Hubbell OFPPL Multimedia Outlet (4-port and Fiber Brackets)
Hubbell Patch Panel Hubbell P5E48UE 48-port 2U Patch Panel, Universal (T568B Wiring)
Hubbell Wire Management Hubbell PCBLMGT Rear Wire Management Bar for P5E48UE
Hubbell Wire Management Hubbell HC219ME3N 19" 2U 3.50"x3.50" Cable Management
Hubbell Copper Cable, Patch Cords Hubbell PCX5EGNxx Speedgain PCX Cat 5e, Green
(xx = Length in Feet)
Ortronics Copper Cable, Horizontal Berk-Tek 10032428 LANMark 350 Cat 5e UTP, CMR, Green
Ortronics Copper Cable, Horizontal Berk-Tek 10032086 LANMark 350 Cat 5e UTP, CMP, Green, Plenum Rated
Ortronics Faceplate, Single Gang Ortronics OR-403005xx Plastic TracJack Series (xx = Port Configuration)
Telecommunications Design Guide & Standards January 2004 4
University of Connecticut Appendix A
HORIZONTAL CABLING & ACCESSORIES (Continued)
Solution Description Manufacturer Part # Detail/Specific Requirements
Ortronics Faceplate, Single Gang Ortronics OR-403004xx Stainless Steel TracJack Series (xx = Port
Configuration)
Ortronics Faceplate, Single Gang Ortronics OR-854045212 Stainless Steel Wall Phone Plate (TracJack T568B
Wiring)
Ortronics Jack Ortronics OR-42100002 Blank, 10/pack, Fog White
Ortronics Jack Ortronics OR-63700006 F-Connector, Fog White
Ortronics Jack Ortronics OR-TJ5E00-25 RJ45, T568B, Clarity Cat 5e, Green (LAN Applications)
Ortronics Jack Ortronics OR-TJ5E00 RJ45, T568B, Clarity Cat 5e, Fog White (Voice Applications)
Ortronics Outlet Box Ortronics OR-40400056 6-port Surface Mount Box
Ortronics Patch Panel Ortronics OR-808004818 Cable Management Panel
Ortronics Patch Panel Ortronics OR-PHD5E6U48 Clarity 5E 48-port 2U Patch Panel, High Density (T568B Wiring)
Ortronics Wire Management Ortronics OR-60400057 5 Metal Rings 3" x 4", 2U
Ortronics Copper Cable, Patch Cords Ortronics OR-MC5Exx-05 Clarity 5E, 4 Pair, 24 AWG, Stranded, GTP. Green
(xx = Length in Feet)
* Coaxial Cable, Horizontal CommScope 5740 RG-6 Quad Shield, 75 Ohm, Non-plenum
* Coaxial Cable, Horizontal CommScope 2227V RG-6 Quad Shield, 75 Ohm, Plenum
* Connector Gilbert GF325CHT F-to-pin Connector
* Connector Gilbert GKSKSM Housing-to-housing Connector
* Connector Gilbert GTRMT Housing Terminator
* Connector Thomas&Betts SNS6PB Snap-n-seal RG 6 Quad Shield F-series, Plenum (Requires OEM Compression Tool)
* Connector Thomas&Betts SNS6QS Snap-n-seal RG 6 Quad Shield F-series, Non-plenum (Requires OEM Compression Tool)
* Cable Identifier Thomas&Betts TY551M Ty-Rap Cable Identifier (Required on Coaxial Cable for Student Housing)
* Compression Tool Thomas&Betts IT1000 Includes Compression Tool with Cable Prep
Telecommunications Design Guide & Standards January 2004 5
University of Connecticut Appendix A
HORIZONTAL CABLING & ACCESSORIES (Continued)
Solution Description Manufacturer Part # Detail/Specific Requirements
* Compression Tool Thomas&Betts SNSIT Requires Cable Prep T&B CPT-6590
* Cable Prep Thomas&Betts CPT-6590 For use with Compression Tool T&B SNSIT
LAN SYSTEM EQUIPMENT
Solution Description Manufacturer Part # Detail/Specific Requirements
* GBIC Module Cisco WS-G5483 1000BASE-T GBIC
* GBIC Module Cisco WS-G5484 1000BASE-SX Short Wavelength GBIC (Multimode Only)
* GBIC Module Cisco WS-G5486 1000BASE-LX/LH Long Haul GBIC (Singlemode or Multimode)
* Ethernet Switch Cisco WS-C2950G-24-EI 24-port 10/100 with 2 GBIC Slots, Enhanced Image (Requires SNTE-C2950-G24 8x5x4 Warranty)
* Ethernet Switch Cisco WS-C2950G-48-EI 48-port 10/100 with 2 GBIC Slots, Enhanced Image (Requires SNTE-C2950-G48 8x5x4 Warranty)
* Ethernet Switch Cisco WS-C3550-12G 10-port 1000BaseX plus 2-port 10/100/1000BaseT (Requires SNTE-C3550-12G 8x5x4 Warranty)
* Ethernet Switch Cisco WS-C3550-12T 10-port 10/100/1000BaseT plus 2-port 1000BaseX (Requires SNTE-C3550-12T 8x5x4 Warranty)
* Redundant Power System (RPS) Cisco PWR675-AC-RPS-
N1= Cisco RPS 675 with 1 connector cable (Requires SNTE-PWR675-AC-RPS-N1 8x5x4 Warranty)
* RPS Cable Cisco CAB-RPS-1614= 1.2 Meter Cable for Cisco RPS 675
SMATV SYSTEM EQUIPMENT
Solution Description Manufacturer Part # Detail/Specific Requirements
* Fiber Receiver C-Cor HX8L13 series Optiworx Fiber Optical Forward Path Receiver (SC/UPC Connector)
* Fiber Transmitter C-Cor 1074320 Optiworx Shelf and Power Supply Manual
* Fiber Transmitter C-Cor HX2281EC Optiworx Fiber Shelf
* Fiber Transmitter C-Cor/ Optiworx HX8L13 series Fiber Optic Transmitter (Connector SC/UPC, APC)
* Fiber Transmitter C-Cor/ Optiworx HXFAN110 Shelf and Power Supply Fan Assembly
Telecommunications Design Guide & Standards January 2004 6
University of Connecticut Appendix A
SMATV SYSTEM EQUIPMENT (Continued)
Solution Description Manufacturer Part # Detail/Specific Requirements
* Splitter Fiberdyne Labs FTSCAPC Optical Splitter Terminators
* Splitter Fiberdyne Labs Per Design Optical Splitter (SC/APC Only)
* Tap Motorola FFT8-N/PE series Starline 2000 Power Extracting Tap
PATHWAYS & SPACES
Solution Description Manufacturer Part # Detail/Specific Requirements
* Ladder Rack Hubbell HLSxx12G NextFrame 12" Wide Cable Runway, Gray (xx = Length in Feet, 06 or 10)
* Ladder Rack Accessory Hubbell HLCD12 NextFrame 12" Wide Cable Radius Drop
* Ladder Rack Accessory Hubbell HLCD06 NextFrame 6" Wide Cable Radius Drop for Stringer
* Ladder Rack Hubbell HLI1290G NextFrame 12" Wide Inside Radius Bend
* Ladder Rack Hubbell HLF1290G NextFrame 12" Wide Flat Turns Bend
* Ladder Rack Hubbell HLO1290G NextFrame 12" Wide Outside Radius Bend
* Ladder Rack Chatsworth 10250-x12 12" Wide Universal Cable Runway (Gray)
* Ladder Rack Accessory Chatsworth 12100-x12 12" Wide Cross-member Radius Drop
* Ladder Rack Accessory Chatsworth 12101-x01 10.25" Wide Cross-member Stringer Radius Drop
* Ladder Rack Chatsworth 10724-x12 12" Wide Inside Radius Bend
* Ladder Rack Chatsworth 10822-x12 12" Wide E-Bend
* Ladder Rack Chatsworth 10723-x12 12" Wide Outside Radius Bend
* Relay Rack Corning CDF-ER-7A-19 LANscape Closet Distribution Frame (Requires (2) CDF-ISB-7)
* Vertical Manager Corning CDF-ISB-7 LANscape Interbay Storage
Telecommunications Design Guide & Standards January 2004 7
University of Connecticut Appendix A
PATHWAYS & SPACES (Continued)
Solution Description Manufacturer Part # Detail/Specific Requirements
* Power Strip Middle Atlantic PD-915R Rack Power Distribution Panel
* Uninterruptible Power Supply (UPS) APC SU2200RM3U Smart-UPS 2200VA RM 3U 120V
* Uninterruptible Power Supply (UPS) APC SU2200RMXLNET Smart-UPS XL 2200VA RM 5U 120V
* UPS Backplate APC SU029RM3U Backplate for Smart-UPS SU220RM3U (20A Alternate to Standard Plate)
* UPS Backplate APC SU029RM Backplate for Smart-UPS SU2200RMXLNET (20A Alternate to Standard Plate)
* UPS Management Card APC AP9617 SNMP Card with Ethernet Interface
* UPS Management Card APC AP9618 SNMP Card with Ethernet Interface, Enviromentals and
Out-of-Band
* UPS Management Card APC AP9619 SNMP Card with Ethernet Interface and Enviromentals
SURFACE MOUNT RACEWAY & SPECIALTY PLATES
Solution Description Manufacturer Part # Detail/Specific Requirements
* Raceway Wiremold V700 series Steel Surface Mount (Accommodates up to (4) Cat 5e Cables)
* Raceway Wiremold V4000 series Steel Surface Mount (Accommodates up to (66) Cat 5e Cables)
* Raceway Wiremold ALA4800 series Aluminum Surface Mount (Accommodates up to (62) Cat 5e Cables)
* Raceway Wiremold V4050/G4050 Bracket For Wiremold 4000 Series
* Raceway Wiremold CM-ARA Angled Adapter for Wiremold 4000 Series
* Raceway Wiremold CM2-U2TJ Bezel for Wiremold 4000 & 4800 Series (Accepts 2 Ortronics TracJack Jacks)
* Raceway Wiremold ALA-2A Cover Plate for Wiremold 4800 Series (Accepts CM2 & HWM2 Bezels)
Hubbell Bezel Hubbell HWM2KI10 Bezel for Wiremold 4000 & 4800 Series (Accepts 2 Hubbell HXJ Jacks)
Telecommunications Design Guide & Standards January 2004 8
University of Connecticut Appendix A
SURFACE MOUNT RACEWAY & SPECIALTY PLATES (Continued)
Solution Description Manufacturer Part # Detail/Specific Requirements
Hubbell Furniture Bezel Hubbell FP2GY Bezel for Steelcase Furniture (Accepts 2 Hubbell HXJ Jacks)
Hubbell Furniture Bezel Hubbell FP4GY Bezel for Steelcase Furniture (Accepts 4 Hubbell HXJ Jacks)
Hubbell Furniture Bezel Hubbell FP4BGY Bezel for Steelcase Furniture (Accepts 4 Hubbell HXJ Jacks)
Ortronics Furniture Bezel Ortronics OR-40300633 Fog White for Steelcase Furniture (Accepts 4 Ortronics TracJack Jacks)
Ortronics Furniture Plate Ortronics OR-40700072 .625" D Modular Furniture Plate
Ortronics Furniture Adapter Ortronics OR-42100009 Adapter for OR-40700072 (Accepts 3 Ortronics TracJack Jacks)
Telecommunications Design Guide & Standards January 2004 9
University of Connecticut Appendix B
TR Layout
���
��
��
��
�
����������
��������
������
Doo
r3'
-0" X
7'-0
"Sw
ing
Out
10'-0
"
8'0"
3/4"
ply
woo
d pa
inte
dbo
th s
ides
with
an
intu
mes
cent
pai
nt.
From
floo
r to
8'-0
" AFF
.Ty
pica
l of a
ll w
alls
.
120
volt
20 a
mp
dupl
exou
tlet.
Typ
ical
of t
hree
.
(4) 4
" con
duit
slee
ves.
Typi
cal t
o th
ete
leco
mm
unic
atio
ns ro
omab
ove,
bel
ow, a
nd to
the
cabl
e pa
thw
ays
outs
ide
the
room
.
Cab
le tr
ay:
A ne
twor
k of
12"
ladd
er ra
ckin
g to
cre
ate
a pa
thw
ay fr
om th
e po
int w
here
the
cabl
es e
nter
the
tele
com
mun
icat
ions
room
to o
ver t
hete
leco
mm
unic
atio
ns b
ackb
oard
s an
d eq
uipm
ent r
acks
. It
will
be s
ecur
ely
fast
ened
to e
ach
wal
l and
to th
e to
p of
eac
h eq
uipm
ent r
ack.
Tele
com
mun
icat
ions
Gro
undi
ng B
usba
r
Activ
eEq
uipm
ent R
ack
Pass
ive
Equi
pmen
t Rac
k
Futu
reEq
uipm
ent R
ack
Voic
e R
iser
Term
inat
ion
Fiel
d
Voic
e H
oriz
onal
Term
inat
ion
Fiel
d
Voic
e Eq
uipm
ent
Term
inat
ion
Fiel
d
HU
SKYv
isio
n-Te
rmin
atio
nFi
eld
DAT
E
12/3
1/20
03
SCAL
E
NTS
TITL
E TYPI
CAL
TR
RO
OM
BUTT
ERFL
Y D
RAW
ING
5'-0"
�
�
����������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������
�������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������
����������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������
���������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������
���������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������
Telecommunications Design Guide & Standards January 2004 1
University of Connecticut Appendix B
Telecommunications Design Guide & Standards 2
Rack Elevation for LAN Equipment
2
1
4
3
6
5
8
7
10
9
UTILSTAT
DUPLXSPEED
SYST EMRPS
MODE 11 12
CATALYST 3550
SDS D
SD
SD
SD
26 27 28 29 30 31 3225 34 35 36 37 38 39 4033 42 43 44 45 46 47 4841
5 61 2 3 4 7 8 9 10 11 12 13 14 15 16 18 19 20 21 22 23 2417
Ortronics
SD
SD
26 27 28 29 30 31 3225 34 35 36 37 38 39 4033 42 43 44 45 46 47 4841
5 61 2 3 4 7 8 9 10 11 12 13 14 15 16 18 19 20 21 22 23 2417
Ortronics
SD
SD
26 27 28 29 30 31 3225 34 35 36 37 38 39 4033 42 43 44 45 46 47 4841
5 61 2 3 4 7 8 9 10 11 12 13 14 15 16 18 19 20 21 22 23 2417
Ortronics
SD
SD
26 27 28 29 30 31 3225 34 35 36 37 38 39 4033 42 43 44 45 46 47 4841
5 61 2 3 4 7 8 9 10 11 12 13 14 15 16 18 19 20 21 22 23 2417
Ortronics
SD
SD
26 27 28 29 30 31 3225 34 35 36 37 38 39 4033 42 43 44 45 46 47 4841
5 61 2 3 4 7 8 9 10 11 12 13 14 15 16 18 19 20 21 22 23 2417
Ortronics
SD
SD
26 27 28 29 30 31 3225 34 35 36 37 38 39 4033 42 43 44 45 46 47 4841
5 61 2 3 4 7 8 9 10 11 12 13 14 15 16 18 19 20 21 22 23 2417
Ortronics
SD
SD
A B C D E F G H J K L M
SD
1
2
3
4
5
6
SIECOR
SD
1
2
3
4
5
6
SIECOR
SD
1
2
3
4
5
6
SIECOR
SD
1
2
3
4
5
6
SIECOR
SD
1
2
3
4
5
6
SIECOR
SD
1
2
3
4
5
6
SIECOR
SD
1
2
3
4
5
6
SIECOR
SD
1
2
3
4
5
6
SIECOR
SD
1
2
3
4
5
6
SIECOR
SD
1
2
3
4
5
6
SIECOR
SD
1
2
3
4
5
6
SIECOR
SD
1
2
3
4
5
6
SIECOR
S D
SD
SD
Smart-UPS
2 2 0 0
Test
AMERICAN POWER CONVERSION
SD
SD
SD
SD
SD
SD
SD
SD
SD
Passive Active
48-PortPatch Panel
Rack Mount UPS(If Needed)
LAN Switch
Horizontal WireManagement
Video DistributionEquipment(If Needed)
LAN DistributionSwitch
Optical FiberPanel Housing
Horizontal WireManagement
Optical FiberManagement
Vertical WireManagement
Rack MountPower Strip
January 2004
University of Connecticut Appendix C
WAO Symbols & Configurations
The following diagrams represent the most common symbols and configurations for WAOs. Other
configurations may be required to meet specific application requirements.
101.05101.02 101.03 101.04
101.01
(1) SMATV
C(1) Voice(1) LAN
2
(2) Voice
2
(2) LAN
(1) Voice(1) LAN(1) SMATV
C
(1) Voice(2) LAN
2
(2) Voice(1) LAN
2
3
(3) Voice
3
(3) LAN
(2) Voice(2) LAN
22
(1) Voice(3) LAN
3
4
(4) LAN
(1) Voice(2) LAN(1) SMATV
C 2
TV (1) SMATV
Wall Mount(1) Voice
Note: Either symbol isacceptable for SMATV
W
1 1
2
1
2
3
1
2
3
4
1
UCONN uses colored jacks in addition to location in the faceplate to identify the jack application. A jack
that matches the faceplate shall identify voice applications and a green jack shall identify LAN applications.
Where applicable, the top position of the faceplate shall be used for voice, the bottom or middle position for
LAN and the bottom position for SMATV video.
Each faceplate shall be identified with a 5-digit label. This format shall identify the room number and the
outlet location within the room. For example: 101.02 would be room 101 (101.02), outlet location 2
(101.02).
To denote outlet locations for building automation systems, use the appropriate symbol shown above for
denoting the requirements. In addition, include the intended use for the outlet. Some examples for
building automation systems WAO symbols are as follows. 2HVAC
2PowerMonitoring
2Elevator
2Fire
2POS
Telecommunications Design Guide & Standards January 2004 1
University of Connecticut Appendix C
WAO Faceplate Labeling
Work area outlets (WAO) shall be labeled with a 5-digit number. The number shall consist of the 3-digit
room number and the 2-digit faceplate number within the room. WAO shall be numbered starting on the
left when entering a room and continue numbering clockwise around the room. In instances where rooms
are nested within another room and denoted with a letter (see Room 106), drop the letter and continue
numbering with the left most WAO (in the subset room) and continue clockwise until the room, or suite of
rooms, is complete.
Room 102
Room 104Room 106
Room 106BRoom 106A
Room 105Room 103Room 101
Corridor
102.01
106.02
106.03
106.05
106.04
106.07
106.06106.01
106.08
105.01
105.02103.02101.01
101.02 103.01
104.02
104.01
102.02
Telecommunications Design Guide & Standards January 2004 2
University of Connecticut Appendix C
Telecommunications Design Guide & Standards January 2004
TR Termination Labeling
110 Field Terminations Each station label on the 110-type connector
block shall consist of the corresponding 5-digit
WAO faceplate label, followed by the 1-digit port
number. For example, WAO faceplate label
101.02, port 1 shall be labeled 101.02.1. Building
automation systems shall be labeled accordingly
as "FIRE.1" or "ELEV.1", "ELEV.2", etc.
110AW4 - 100
101.01.1 101.02.1 101.03.1 101.07.1 101.07.2 101.08.1101.08.2 101.09.1
Patch Panel Terminations
Each port on the patch panel shall be labeled on the front with printed labels. Labels on the patch panel
shall consist of the corresponding 5-digit WAO faceplate label, followed by the 1-digit port number. For
example, WAO faceplate label 101.02, port 2 shall be labeled 101.02.2. Building automation systems shall
be labeled accordingly as "HVAC.1" or "PWR.1", "PWR.2", etc. SD
C
OR
TRO
NIC
S
43 44 45 46 47 4837 38 39 40 41 4231 32 33 34 35 3625 26 27 28 29 30
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
AT5e
101.01.2 101.02.2 101.02.3 101.03.2 101.03.3 101.03.4 101.04.1 101.04.2 101.05.1 101.05.2 101.05.3 101.06.1 101.06.2 101.06.3 101.06.4 101.07.3 101.08.3 101.08.4
SMATV Terminations
201.01201
For administrative and academic installations, each cable shall be labeled with the corresponding 5-digit
WAO faceplate label and connected to a wall-mounted F-81. An additional label tag (Thomas & Betts
TY551M) identifying the 3-digit room number shall be
fastened on the cable near the F-81 connector.
UNIVERSITY ITS will perform connections to the tap.
201
From Splitter to VMIU
201.01
From WAO to Splitter
In student housing, each cable shall be labeled with the
corresponding 5-digit WAO faceplate label and connected to a VMIU. An additional label tag (Thomas &
Betts TY551M) identifying the 3-digit room number shall be fastened on the cable near the VMIU. Where
multiple drops from one apartment are connected to a splitter, only the cable from the splitter to the VMIU
needs to have the additional 3-digit room number tag.
3
University of Connecticut Appendix D
Logical LAN Diagrams
SYST RPS
STRT DUPLXSPEEDUT IL
MODE
Catalyst 2950 SER IES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
43
44
45
46
47
48
2
1
SYST RPS
STRT DUPLXSPEEDUT IL
MODE
Catalyst 2950 SER IES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
43
44
45
46
47
48
2
1
SYST RPS
STRT DUPLXSPEEDUT IL
MODE
Catalyst 2950 SER IES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
43
44
45
46
47
48
2
1
SYST RPS
STRT DUPLXSPEEDUT IL
MODE
Catalyst 2950 SER IES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
43
44
45
46
47
48
2
1
TR #3Edge Switch Stack
SYST RPS
STRT DUPLXSPEEDUT IL
MODE
Catalyst 2950 SER IES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
43
44
45
46
47
48
2
1
SYST RPS
STRT DUPLXSPEEDUT IL
MODE
Catalyst 2950 SER IES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
43
44
45
46
47
48
2
1
SYST RPS
STRT DUPLXSPEEDUT IL
MODE
Catalyst 2950 SER IES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
43
44
45
46
47
48
2
1
SYST RPS
STRT DUPLXSPEEDUT IL
MODE
Catalyst 2950 SER IES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
43
44
45
46
47
48
2
1
TR #2Edge Switch Stack
SYST RPS
STRT DUPLXSPEEDUT IL
MODE
Catalyst 2950 SER IES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
43
44
45
46
47
48
2
1
SYST RPS
STRT DUPLXSPEEDUT IL
MODE
Catalyst 2950 SER IES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
43
44
45
46
47
48
2
1
SYST RPS
STRT DUPLXSPEEDUT IL
MODE
Catalyst 2950 SER IES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
43
44
45
46
47
48
2
1
TR #1Edge Switch Stack
TX GBIC
Mul
timod
e Fi
ber
SX G
BICTX GBIC
TX GBIC
Aggregate
UPS
TX GBIC
TX GBIC
TX GBIC
TX GBIC
TX GBIC
TX GBIC
Singlmode FiberLX GBIC
SYST RPS
STRT DUPLXSPEEDUT IL
MODE
Catalyst 2950 SER IES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
43
44
45
46
47
48
2
1
SYST RPS
STRT DUPLXSPEEDUT IL
MODE
Catalyst 2950 SER IES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
43
44
45
46
47
48
2
1
SYST RPS
STRT DUPLXSPEEDUT IL
MODE
Catalyst 2950 SER IES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
43
44
45
46
47
48
2
1
TREdge Switch Stack
TX GBIC
TX GBIC
TX GBIC
Sing
lem
ode
Fibe
rLX
GBI
C
(1) Building withMultiple TRs
(1) Building with(1) TR
Aggregate
UPS
POWERFAULT DATA ALARMRPS
TRAggregate Switch
(1) Building ServingMultiple Buildings
Sing
lem
ode
Fibe
rLX
GBI
C
Sing
lem
ode
Fibe
rLX
GBI
C
S D
S m a rt - U P S
1 4 0 0
T es t
A M ER IC A N PO W E R C ON V E R S IO N
2
1
4
3
6
5
8
7
10
9
UTILSTAT
DUPLXSPEED
SYSTEMRPS
MODE11 12
CATALYST 3550
S D
S m a r t- U P S
1 4 0 0
T e s t
AM E RI CA N P O W E R C O N VE RS I ON
2
1
4
3
6
5
8
7
10
9
UTILSTAT
DUPLXSPEED
SYSTEMRPS
MODE 11 12
CATALYST 3550
SYST RPS
STRT DUPLXSPEEDUT IL
MODE
Catalyst 2950 SER IES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
43
44
45
46
47
48
2
1
SYST RPS
STRT DUPLXSPEEDUT IL
MODE
Catalyst 2950 SER IES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
43
44
45
46
47
48
2
1
UConn LAN Core
Telecommunications Design Guide & Standards January 2004 1
University of Connecticut Appendix E
Code Blue Base Template For Pedestal Telephone
8" DIAMETER BOLT CIRCLE(TEMPLATE PROVIDEDWITH J-BOLTS)
1" CONDUITS STUBBEDUP IN CENTER OF BASEFOR VOICE ANDELECTRIC WIRING
DIAMOND PATTERNINSTALLATION OF J-BOLTS
SIDEWALK LINEINSTALL PHONE BASE FLUSHAGAINST SIDEWALK FORWHEELCHAIR ACCESSIBILITY�����������
�����������
CODE BLUE PEDESTALFOOTPRINT
����������������������������������������������������������������������������������
��������������������������������������������������������������������������������������������������������������������������������������������
��������������
����������������
��������������������������������������������������������������������������������������������������������������������������������������������������������������������
��������������������������������
��������������������������������������������������������������������������������������������������������
������������������������������������������������������������������������������������������������������������������������
������������������ ��������
������������������������
��������������������������������������������������������������������
������������������������������������������������������������
������������������������������������������������������������
��������������������������������������������������������
������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������
����������������������������������������������������������������
������������������������������������������������������������������������������������������������������������������������������
LONG RADIUS BENDS ONCONDUITS IS MANDATORY
NO LOOPING (DAISY CHAIN)OF MULTIPLE BASES
�����������������������
�������������������������
����������������
��������������
��������������
���������� �����������
ELECTRICAL CONDUIT1" CONDUIT FOR ELECTRIC 110VACINSTALLED ON DEDICATED 15 AMP CIRCUITWITH EMERGENCY POWER BACKUP
VOICE CONDUIT1" CONDUIT WITH BUSHINGS AND PULLSTRING TO MAIN TELECOMMUNICATIONSROOM FOR TELEPHONE WIRING
J-BOLTS (3/4" X 24") WITH AMINIMUM OF 6" THREADEXPOSED ABOVECONCRETE PAD
6" EXPOSED THREAD
CONCRETE FOUNDATION24" IN DIAMETER,MINIMUM 1" ABOVEGROUND LEVEL,CROWNED TO ALLOWFOR DRAINAGE, POUREDTO A DEPTH OF 42"
Telecommunications Design Guide & Standards January 2004 1
University of Connecticut Appendix F
Binding Post Information Form
For a printable version of this form, please go to http://telecom.uconn.edu/DGS/Forms603.zip.
Telecommunications Design Guide & Standards January 2004 1
University of Connecticut Appendix F
LAN Switch Audit Form
For a printable version of this form, please go to
http://telecom.uconn.edu/DGS/Forms603.zip.
Telecommunications Design Guide & Standards January 2004 2
University of Connecticut Appendix G
Reference Resources
Regulatory Requirements, Codes & Standards www.ansi.org
www.asme.org
www.astm.org
www.bicsi.org
www.eia.org
www.fcc.gov
www.ieee.org
www.nema.org
www.nfpa.org
www.osha.org
www.scte.org
www.state.ct.us/dps
www.tiaonline.org
www.ul.com
UConn telecom.uconn.edu
www.aes.uconn.edu
www.police.uconn.edu
www.ucimt.uconn.edu
Manufacturers www.ortronics.com
www.hubbell-premise.com
www.corning.com/opticalfiber
www.wiremold.com
Telecommunications Design Guide & Standards June 2003 1