7/27/2020 1 © buildingscience.com Unvented Roofs Without Spray Foam: The Rest of the Story Kohta Ueno August 14, 2020 1 2

Upload: others

Post on 13-Oct-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

1

© buildingscience.com

Unvented Roofs Without Spray Foam:

The Rest of the Story

Kohta Ueno

August 14, 2020

1

2

Page 2: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

2

NESEA BE20: Unvented Roofs Without Spray Foam3

© buildingscience.com

Background

NESEA BE20: Unvented Roofs Without Spray Foam4

© buildingscience.com

Ventilated Attics—Best Choice

Roof sheathing dries to ventilated attic-moisture safe

Interior moisture (air leaks) ventilated away in winter

Air sealing at ceiling critical for best performance (e.g., spray foam air barrier,

detail with sealant)

3

4

Page 3: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

3

NESEA BE20: Unvented Roofs Without Spray Foam5

© buildingscience.com

Then Why Unvented Roofs?

Living space built into roof

Vented cathedral assemblies—often poor performance

Complicated rooflines, hip geometries—how to vent?

Unworkable air barrier at ceiling line

Blown-in rain (coastal)

Hurricane tear-off

HVAC in vented attic

NESEA BE20: Unvented Roofs Without Spray Foam6

© buildingscience.com

Ducts in unconditioned attic = energy losses Industry reluctant to move ducts out of attic

Ice dam issues due to duct losses

Solution: bring ducts into conditioned space

Unvented/conditioned attic—keeps ductwork in conditioned space, duct leak issues eliminated

Unvented Roofs & HVAC Placement

5

6

Page 4: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

4

NESEA BE20: Unvented Roofs Without Spray Foam7

© buildingscience.com

Fibrous Insulation Unvented Roofs Dense pack insulation of unvented roofs common

in cold-climate retrofits Moisture risks (see BSI-043 “Don't Be Dense—

Cellulose and Dense-Pack Insulation”)—2 in 10 failure?

Violates I-codes (see IRC§R806.4/R806.5)

“Ridge rot”—localized problems (SIPS same problem)

NESEA BE20: Unvented Roofs Without Spray Foam8

© buildingscience.com

Fibrous Insulation Unvented Roofs

The BS* + Beer Show: Unvented Roofs and Fluffy Insulation (with Bill Hulstrunk/NatureTech), May 2020

Moisture buffering from cellulose storage

Critical role of density

https://www.youtube.com/watch?v=xZlnpQYdsuM&t=1551s

7

8

Page 5: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

5

NESEA BE20: Unvented Roofs Without Spray Foam9

© buildingscience.com

Why Unvented + Fibrous Risky? Different than walls?

Moisture risks at sheathing Interior-sourced air leakage

Vapor contributing too?

Zero-perm exterior (“wrong side perfect vapor barrier”)

Night sky radiation cooling

Stack effect in winter

“Ridge rot” (thermal and moisture buoyancy)

NESEA BE20: Unvented Roofs Without Spray Foam10

© buildingscience.com

Why Unvented + Loose Fill Risky? Risk reduced by: Airtightness of ceiling

Dense insulations that suppress airflow

Solar drive But white roofs, shading

Lower interior RH (winter) Why many of them work?

Lower permeance interior Assumes good airtightness—

vapor retarder not bypassed

Moisture accumulation: what gets in vs. gets out

9

10

Page 6: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

6

NESEA BE20: Unvented Roofs Without Spray Foam11

© buildingscience.com

Spray Foam/Exterior Insulation Roofs

2006 IRC: R806.4 Unvented attic assemblies

Minimum R-value of “air impermeable insulation” Actually ratio of R-values (BSI-100 Hybrid Assemblies)

Nail base needed with rigid foam on roof deck

NESEA BE20: Unvented Roofs Without Spray Foam12

© buildingscience.com

Why Fibrous Fill Unvented Roofs?

Unvented roofs without spray/board foams could reduce costs and increase market penetration… IF moisture damage risks are addressed

Retrofit opportunities (existing uninsulated living space at roof line, without removing finishes)

11

12

Page 7: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

7

NESEA BE20: Unvented Roofs Without Spray Foam13

© buildingscience.com

Previous Building America Research

NESEA BE20: Unvented Roofs Without Spray Foam14

© buildingscience.com

Previous Building America Research Chicago (CZ 5A): One winter, 50% RH

Unvented roofs-high risk

Cellulose lower risk than FG batt

Vented compact roof (chute) safe-but poor air leakage

Houston/Orlando (CZ 2A): 2 attics, multiple seasons

Diffusion vents allow greater drying, avoid moisture problems

5 Top Vent Fiberglass-GWB

4 Top Vent Fiberglass

2 Top Vent Cellulose-GW

3 Top Vent Cellulose

7 Unvented Cellulose

6 Diffusion Vent Cellulose

1 Vented

Chicagoroof disassembly

Houston roof w. diffusion vent

13

14

Page 8: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

8

NESEA BE20: Unvented Roofs Without Spray Foam15

© buildingscience.com

Diffusion Vent Prototype (Orlando-Tile)200+ perms diffusion ventAir barrier closed

NESEA BE20: Unvented Roofs Without Spray Foam16

© buildingscience.com

Houston/Orlando Results

Diffusion vent avoids wintertime ridge accumulation problems (ridge peak RHs/MCs)

No failures at low interior RH, bigger difference at higher RH (interior humidification)

Airtightness disappointing in some cases-no SPF

0

10

20

30

40

50

60

70

80

90

100

0

5

10

15

20

25

30

35

40

45

50

10/1/14 1/9/15 4/19/15 7/28/15 11/5/15 2/13/16

Relative Humidity (%

)

Moisture Content (%

)

DVR1 Peak Wafer UVR1 Peak Wafer

DVR1 Peak RH UVR1 Peak RH

Unvented

Dif. Vent.

Dif. Vent.Unvented

Summer WinterWinter

15

16

Page 9: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

9

NESEA BE20: Unvented Roofs Without Spray Foam17

© buildingscience.com

“Ridge Rot” and Moisture Buoyancy

NESEA BE20: Unvented Roofs Without Spray Foam18

© buildingscience.com

Houston and Jacksonville (CZ 2A) 2001

17

18

Page 10: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

10

NESEA BE20: Unvented Roofs Without Spray Foam19

© buildingscience.com

Moisture Buoyancy Moisture concentrated at highest point in

conditioned attic (ridge)

Not a simple one-dimensional problem

Not a straight-up air leakage problem

Problem with open-cell spray foam (ocSPF) unvented roofs (high RHs in attic)-many climates But not ccSPF—lower vapor permeance

Concentration of interior-sourced moisture

Moist air is lower density (“lighter”) than dry air

Others: “system in equilibrium has same dewpoint in connected air space”

NESEA BE20: Unvented Roofs Without Spray Foam20

© buildingscience.com

“Ping Pong” Water

See BSI-016: Ping Pong Water and The Chemical Engineer

19

20

Page 11: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

11

NESEA BE20: Unvented Roofs Without Spray Foam21

© buildingscience.com

“Ping Pong” Water

See BSI-016: Ping Pong Water and The Chemical Engineer

NESEA BE20: Unvented Roofs Without Spray Foam22

© buildingscience.com

“Ping Pong” Water

“Gas separation process similar to pressure swing adsorption”

Solar-powered moisture concentration machine

21

22

Page 12: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

12

NESEA BE20: Unvented Roofs Without Spray Foam23

© buildingscience.com

Orlando Decommissioning

NESEA BE20: Unvented Roofs Without Spray Foam24

© buildingscience.com

Orlando Decommissioning

‐10

0

10

20

30

40

50

60

70

80

90

50 60 70 80 90

Heigh

t (in.)

Temperature/Dewpoint  (F)

Temperature (F)

Dewpoint (F)

‐10

0

10

20

30

40

50

60

70

80

90

50 60 70 80 90

Heigh

t (in.)

Temperature/Dewpoint  (F)

Temperature (F)

Dewpoint (F)

Temperature and dewpoint stratification directly measured

90%+ RH near ridge

System is not in equilibrium

23

24

Page 13: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

13

NESEA BE20: Unvented Roofs Without Spray Foam25

© buildingscience.com

Test Hut Approach & Construction

NESEA BE20: Unvented Roofs Without Spray Foam26

© buildingscience.com

Test Hut Experimental Approach Climate Zone 5A test hut

Eight north-south roof bays; guard bays

±R-50 (14-¾” framing, 2012 IECC)

Test variables (changed year-to-year):

Vapor retarder: variable perm vs. fixed perm, various permeance curves

Diffusion vent at ridge: full size, none, “small,” or “tight”

Fiberglass vs. cellulose

“Control” comparison §R806.4 spray foam + fibrous

Varying interior boundary conditions

Winter 1: “Normal” interior conditions

Winter 2: Elevated RH (50% constant)

Winter 3: Air leakage into rafter bays

Test Hut South Elevation

25

26

Page 14: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

14

NESEA BE20: Unvented Roofs Without Spray Foam27

© buildingscience.com

Test Hut Construction

Flash and blow bays (ccSPF shown) ccSPF completes air barrier between bays, wiring holes

Insulation netted & blown

NESEA BE20: Unvented Roofs Without Spray Foam28

© buildingscience.com

Test Hut Construction

Interior air barrier & vapor retarder membrane

Adhesive spray + double tape seal (double-sided tape + housewrap tape) plus mechanical fasteners

27

28

Page 15: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

15

NESEA BE20: Unvented Roofs Without Spray Foam29

© buildingscience.com

Test Hut Construction

Instrumentation completion

NESEA BE20: Unvented Roofs Without Spray Foam30

© buildingscience.com

Test Hut Construction

ccSPF in guard bays and walls

29

30

Page 16: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

16

NESEA BE20: Unvented Roofs Without Spray Foam31

© buildingscience.com

Test Hut Construction

Fibrous insulation installed

NESEA BE20: Unvented Roofs Without Spray Foam32

© buildingscience.com

Test Hut Construction

Interior air/vapor control installed

31

32

Page 17: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

17

NESEA BE20: Unvented Roofs Without Spray Foam33

© buildingscience.com

Experimental Approach: Diffusion Vent

~6 in. opening (fits under typical ridge cap)

Dörken Delta-Foxx membrane 214 perms dry cup, 550 perms wet cup

NESEA BE20: Unvented Roofs Without Spray Foam34

© buildingscience.com

Research Findings

33

34

Page 18: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

18

NESEA BE20: Unvented Roofs Without Spray Foam35

© buildingscience.com

Year 1 Findings (“Normal” Conditions)

Non-diffusion vent roofs worst; high moisture levels at ridge

Roofs with diffusion vent & variable-perm vapor retarder safest

Viitanen mold index values below risk thresholds (3.0 MI); meets ASHRAE Standard 160

Visible settling of insulation (when cutting new ridge openings from above)

Summertime inward drive at fixed-perm VR roofs

Eliminated non-diffusion vent roofs for Year 2 (added “small” & “tight” DVs)

NESEA BE20: Unvented Roofs Without Spray Foam36

© buildingscience.com

Roof Insulation Settling (Fiberglass)

Insulation settling noted during diffusion vent retrofit

Fiberglass roof shown above

35

36

Page 19: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

19

NESEA BE20: Unvented Roofs Without Spray Foam37

© buildingscience.com

Retrofit Work, Cellulose Settling

NESEA BE20: Unvented Roofs Without Spray Foam38

© buildingscience.com

Retrofit Work, Cellulose Settling

Settling along entire roof length only occurred on north side

Roofs left as-is for Winter 2: realistic settling of insulation? Also, damage to instruments when retrofitting insulation

37

38

Page 20: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

20

NESEA BE20: Unvented Roofs Without Spray Foam39

© buildingscience.com

Summertime Inward Drive

1 perm vapor barrier 1 perm vapor barrier

NESEA BE20: Unvented Roofs Without Spray Foam40

© buildingscience.com

Summertime Inward Drive

Inward vapor drive does matter—we were just measuring in the wrong location!

1 perm vapor barrier 1 perm vapor barrier

39

40

Page 21: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

21

NESEA BE20: Unvented Roofs Without Spray Foam41

© buildingscience.com

“Small” and “Tight” Diffusion Vents

“Small” DV = ~2 inches

“Tight” DV = 25 perm

NESEA BE20: Unvented Roofs Without Spray Foam42

© buildingscience.com

Year 2 Findings (50% RH Constant)

Interior at 50% RH creates much more challenging conditions: many pushing edge of risk

Many MCs over 20% to 30%, sustained high RH

Mold Index #s remain below 3.0

Mold growth occurred on framing & sheathing

“Tight” diffusion vent did not work acceptably

Code-compliant ccSPF roof acceptable

Repacked insulation after disassembly; filling all voids

Replaced all ridge sensors (data failures)

41

42

Page 22: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

22

NESEA BE20: Unvented Roofs Without Spray Foam43

© buildingscience.com

Summer 2 Ridge Disassembly Work• Fiberglass: staining, rundown, some mold spotting

NESEA BE20: Unvented Roofs Without Spray Foam44

© buildingscience.com

Summer 2 Ridge Disassembly Work• Cellulose: worst mold, settling (greater at north)

43

44

Page 23: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

23

NESEA BE20: Unvented Roofs Without Spray Foam45

© buildingscience.com

Year 3 Setup & Findings (Air Injection)

Early winter 50% RH, no air leak

February onward-add air leak

Air injection system Interior-to-interior leak

Very small air leak, 0.5 CFM per bay

Comparable to very airtight construction

Before air injection: much drier than Year 2 Repacking insulation suppresses convection?

Air injection: severe spike in sheathing MC Localized to injection site

Disassembly in summer: no visible damage

NESEA BE20: Unvented Roofs Without Spray Foam46

© buildingscience.com

Air Injection System

0.5 CFM air injection rate

North side roof

45

46

Page 24: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

24

NESEA BE20: Unvented Roofs Without Spray Foam47

© buildingscience.com

Disassembly

No indication of moisture issues (mold, staining, packy insulation

NESEA BE20: Unvented Roofs Without Spray Foam48

© buildingscience.com

Miscellaneous Measurements

47

48

Page 25: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

25

NESEA BE20: Unvented Roofs Without Spray Foam49

© buildingscience.com

Air Leakage Testing

Duct Blaster™ attached to exhaust opening

Pressurization & depressurization

~50 CFM 50 (0.02 CFM 50/sf enclosure)

Sliding door seal effect on airtightness

NESEA BE20: Unvented Roofs Without Spray Foam50

© buildingscience.com

Air Leakage Testing: Infrared w. ΔP

Air leakage at 3-way intersection

At guard bay, not test bay

49

50

Page 26: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

26

NESEA BE20: Unvented Roofs Without Spray Foam51

© buildingscience.com

Air Leakage Testing During Disassembly

Depressurized to -75 Pascals

No detectable air leakage

No indication of tape seam failure

NESEA BE20: Unvented Roofs Without Spray Foam52

© buildingscience.com

Water Leakage Testing

Insulation removed from interior

-75 Pascal depressurization, 10 minutes water spraying each side

No sign of water leakage

51

52

Page 27: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

27

NESEA BE20: Unvented Roofs Without Spray Foam53

© buildingscience.com

Density Measurements

Insulation weighed, density calc

Average 1.5 PCF (fiberglass) & 4.0 PCF (cellulose)

Higher density @ FG ridgeRoof Total  Lbs Cubic Ft PCF

1 FG‐VB‐DV 5.8 4.6 1.3

2 FG‐SVR‐DV 6.2 4.6 1.3

3 FG‐VB‐nDV (Low) 6.6 4.6 1.4

3 FG‐VB‐nDV (Hi) 5.0 2.3 2.2

4 FG‐SVR‐nDV 6.4 4.6 1.4

5 Cell‐VB‐nDV (Low) 19.2 4.6 4.1

5 Cell‐VB‐nDV (Hi) 10.0 2.3 4.3

6 Cell‐SVR‐nDV 10.6 2.3 4.6

7 Cell‐SVR‐DV 8.6 2.3 3.7

NESEA BE20: Unvented Roofs Without Spray Foam54

© buildingscience.com

Data Results (Fiberglass Roofs)

53

54

Page 28: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

28

NESEA BE20: Unvented Roofs Without Spray Foam55

© buildingscience.com

Instrumentation Design: Fibrous Insulation

NESEA BE20: Unvented Roofs Without Spray Foam56

© buildingscience.com

Instrumentation Design: Fibrous Insulation

55

56

Page 29: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

29

NESEA BE20: Unvented Roofs Without Spray Foam57

© buildingscience.com

Instrumentation Design: Fibrous Insulation

NESEA BE20: Unvented Roofs Without Spray Foam58

© buildingscience.com

Instrumentation Design: Fibrous Insulation

57

58

Page 30: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

30

NESEA BE20: Unvented Roofs Without Spray Foam59

© buildingscience.com

Fiberglass Roofs: Ridge RH 24 hr Average

24 hr. averaging for readability

Winter 1 compares DV vs. non-DV

Winter 2 wetter than Winter 1

Winter 3 much drier than Winter 2

Winter 1 Winter 2 Winter 3

Roof Short Name

1 FG‐VB‐DV

2 FG‐SVR‐DV

3 FG‐tVR‐DV

4 FG‐SVR‐sDV

NESEA BE20: Unvented Roofs Without Spray Foam60

© buildingscience.com

Fiberglass Roofs: Ridge Wafers

Winter 1 Roof 3 & Roof 4 no DV

Winter 1 vs Winter 2 (50% RH)

Winter 3 also 50% RH-but low moisture And wafer sensor replaced

Winter 1 Winter 2 Winter 3

Roof Short Name

1 FG‐VB‐DV

2 FG‐SVR‐DV

3 FG‐tVR‐DV

4 FG‐SVR‐sDV

59

60

Page 31: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

31

NESEA BE20: Unvented Roofs Without Spray Foam61

© buildingscience.com

Winter 1 DV roofsvs. non-DV roofs

Much higher MCs in Winter 2 (50% RH)

Winter 3 drier “trajectory” (same 50% RH)

After air injection: MCs increase

30-40% MC @ lower & mid sheathings

Fiberglass Roofs: N Sheathing MCsWinter 1 Winter 2 Winter 3

NESEA BE20: Unvented Roofs Without Spray Foam62

© buildingscience.com

Fiberglass Roofs: Inward Drive Sensors

South side wafer sensors

Summer 2018/2019: Roofs 1 worst (fixed VB)

All below 40-45% MC condensation level Roof Short Name

1 FG‐VB‐DV

2 FG‐SVR‐DV

3 FG‐tVR‐DV

4 FG‐SVR‐sDV

Summer 2017 Summer 2018 Summer 2019

61

62

Page 32: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

32

NESEA BE20: Unvented Roofs Without Spray Foam63

© buildingscience.com

Data Results (Cellulose Roofs)

NESEA BE20: Unvented Roofs Without Spray Foam64

© buildingscience.com

Cellulose Roofs: Ridge Wafer

50%+ MC unrealistic: condensation, borate migration

Winter 3 much drier than Winter 2

Roof 8 (hybrid) condensation-range MCs? Not replaced between Winters 2/3

Roof Short Name

5 Cell‐tVR‐DV

6 Cell‐SVR‐sDV

7 Cell‐SVR‐DV

8 ccSPF‐Cell

Winter 1 Winter 2 Winter 3

63

64

Page 33: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

33

NESEA BE20: Unvented Roofs Without Spray Foam65

© buildingscience.com

North sheathing MCs

Upper: condensation & borate migration

Winter 3 starts out drier than Winter 2

Air injection: rise in MCs low & mid

Peak MCs lower than fiberglass: storage

Cellulose Roofs: N Sheathing MCs

Roof Short Name

5 Cell‐tVR‐DV

6 Cell‐SVR‐sDV

7 Cell‐SVR‐DV

8 ccSPF‐Cell

Winter 1 Winter 2 Winter 3

NESEA BE20: Unvented Roofs Without Spray Foam66

© buildingscience.com

Cellulose Roofs: Inward Drives

Inward drive wafer, south

All well below 15% MC (safe)

Roof Short Name

5 Cell‐tVR‐DV

6 Cell‐SVR‐sDV

7 Cell‐SVR‐DV

8 ccSPF‐Cell

Summer 2017 Summer 2018 Summer 2019

65

66

Page 34: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

34

NESEA BE20: Unvented Roofs Without Spray Foam67

© buildingscience.com

Hybrid Roofs(ccSPF & cellulose)

NESEA BE20: Unvented Roofs Without Spray Foam68

© buildingscience.com

Rising RH Conditions @ Ridge

Sensor at sheathing showed safe behavior

Interface (ccSPF to cellulose) likely condensing surface

67

68

Page 35: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

35

NESEA BE20: Unvented Roofs Without Spray Foam69

© buildingscience.com

Hybrid Roof Interface: RH

Winter 1: excursions to 90-95% RH

Winters 2 & 3 (50% RH): 95-100% RH all winter

No visible issues from interior (cellulose storage)

Winter 1 Winter 2 Winter 3

NESEA BE20: Unvented Roofs Without Spray Foam70

© buildingscience.com

Hybrid Roof Interface: Disassembly

No indications of caked or “packy”/adhered insulation on ccSPF

Hybrid assembly ‘insulation ratios’ not intended for ‘flatline’ 50% RH in winter

69

70

Page 36: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

36

NESEA BE20: Unvented Roofs Without Spray Foam71

© buildingscience.com

Conclusions and Recommendations

NESEA BE20: Unvented Roofs Without Spray Foam72

© buildingscience.com

Recommendations and Further Work Unvented fibrous insulation roofs can work, BUT Ensure complete packing of insulation/density

Still vulnerable to small (0.5 CFM) air leaks

Mold found after Winter 2, despite mold index < 3.0 Vulnerability to moisture damage at ridge

Difficult to recommend for widespread use and acceptance in building codes High indoor RHs more likely w. tighter construction and

high occupant density/multifamily

Retrofit solution for failing assemblies? Demolition + spray foam not possible?

No place in code to allow

71

72

Page 37: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

37

NESEA BE20: Unvented Roofs Without Spray Foam73

© buildingscience.com

Foam-free Unvented Roof Options Fibrous + continuous exterior insulation outside air

barrier, per§R806.5 Mineral fiber, wood fiber board, etc.

Ventilated cavity outboard of vapor-permeable air/water control membrane

NESEA BE20: Unvented Roofs Without Spray Foam74

© buildingscience.com

Recommendations and Further Work If implementing unvented fibrous insulation roofs Keep interior RH low for life of building

Airtightness of interior air/vapor control layer

Variable-perm vapor retarder (allows downward drying)

Large 300 perm diffusion vent recommended

Fibrous insulation without voids or empty cavities

Light colored roofs & shading increase risks

Future work? Moisture risks demonstrated; not sure if additional

research useful

“Story and a Half Geometry” (Cape Cod short slope)

73

74

Page 38: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

38

NESEA BE20: Unvented Roofs Without Spray Foam75

© buildingscience.com

Story and a Half (Cape Cod Short Slope)

Possible application to retrofitting “short slope” of kneewall attic geometry

Eliminates “chute,” possible to retrofit longer runs

“Short slope” portion of roof“Short slope” portion of roof

LIVING SPACE

“Warm storage,” insulation at roofline. Air-vapor retarder required interior to insulation. Recommended approach for air barrier continuity

“Warm storage,” insulation at roofline. Air-vapor retarder required interior to insulation. Recommended approach for air barrier continuity

“Cold storage,” insulation at kneewall, across ceiling of first floor. Wind washing/air

barrier recommended at exposed kneewall insulation.

“Cold storage,” insulation at kneewall, across ceiling of first floor. Wind washing/air

barrier recommended at exposed kneewall insulation.

Blocking and air barrier required at floor framing cavities in “cold storage” approachBlocking and air barrier required at floor framing cavities in “cold storage” approach

NESEA BE20: Unvented Roofs Without Spray Foam76

© buildingscience.com

Story and a Half (Cape Cod Short Slope)

Higher R-value in limited cavity

Not proven by this research, but this is “lower half of roof” geometry (low risk portion)

Rafter bay has “full-size diffusion vent” to vented attic above

Common practice in weatherization NE/Midwest

State code change proposals in process

75

76

Page 39: Unvented Roofs Without Spray Foam: The Rest of the Story · 8/14/2020  · NESEA BE20: Unvented Roofs Without Spray Foam 3 ... Actually ratioof R-values (BSI-100 Hybrid Assemblies)

7/27/2020

39

NESEA BE20: Unvented Roofs Without Spray Foam77

© buildingscience.com

Questions?Kohta Uenokohta [at] buildingscience [dot] com