DRAWING INDEX SAFETY x PERSONAL PROTECTIVE EQUIPMENT SHALL BE WORN AS REQUIRED IN ALL APPLICABLE AREAS. LIMIT ACCESS BY UNAPPROVED PERSONNEL TO APPLICABLE AREAS x IF WORK IS BEING DONE IN AN AREA WHERE PEDESTRIANS MAY WALK THROUGH, MAKE SURE THE AREA IS BARRICADED OR CONED OFF APPROPRIATELY. x IF WORKING NEAR DOORS OF OFFICE SUITES MAKE SURE SIGNS ARE PLACED ON OTHER SIDE OF DOOR INDICATING WORKERS NEAR DOORWAY x PERMITS MUST BE OBTAINED FROM THE AHJ FOR ENERGIZED ELECTRICAL, HOT WORK, CONFINED SPACE ENTRY AS WELL AS LIFE SAFETY WORK ARE OBTAINED PRIOR TO BEGINNING WORK. x $// (03/2<((6 :25.,1* 21 ´/2&.(' 287 ´(48,30(17 6+$// +$9( 7+(,5 /2&. $1' 7$* 21 7+( 6285&( 2) (1(5*< x FOLLOW ALL OTHER APPLICABLE FEDERAL, STATE AND LOCAL ENVIRONMENTAL HEALTH AND SAFETY REGULATIONS. x PROJECT MANAGERS, CONTRACTORS, EHS SHOULD CONFIRM THAT ASBESTOS/HAZARDOUS MATERIALS HAVE BEEN IDENTIFIED, TESTED AND ABATED PRIOR TO ALL WORK. REDLINES CONTRACTOR SHALL SUBMIT PROJECT REDLINES MERGED TO ONE CLEAN SET OF DRAWINGS STAMPED REDLINES. DRAWINGS WILL BE MARKED: CHANGE - RED PENCIL / REMOVAL - RED PENCIL HATCH / NOTE TO DESIGNER - GRAY PENCIL. SUBMITTALS SCOPE OF WORK US-34 & US-18 REPLACEMENT PROJECT THIS PROJECT CONTAINS ASBESTOS, ABATEMENT REQUIRED. THIS PROJECT CONTAINS HAZARDOUS MATERIALS, SPECIAL PRECAUTIONS REQUIRED. YES NO GENERAL INFORMATION 1 G-001 COVER (INDEX) SHEET CIVIL ARCHITECTURAL STRUCTURAL MECHANICAL PLUMBING FIRE PROTECTION ELECTRICAL 2 E-001 ELECTRICAL NOTES, SYMBOLS AND LEGEND 3 E-002 ONE-LINE SYMBOLS CONT'D & ELECTRICAL ABBREVATIONS 4 E-101 ELECTRICAL SITE PLAN - DEMOLITION 5 E-201 ELECTRICAL SITE PLAN - NEW WORK 6 E-202 ELECTRICAL FLOOR PLAN - NEW WORK 7 E-501 ELECTRICAL SWITCHGEARS & SWITCHBOARDS ELEVATION 8 E-601 PARTIAL ELECTRICAL ONE-LINE DIAGRAM - DEMOLITION 9 E-602 PARTIAL ELECTRICAL ONE-LINE DIAGRAM - NEW WORK TELECOMMUNICATIONS SECURITY/IT G-001 COVER (INDEX) SHEET STATUS: DESIGNER: PROJECT INFORMATION DESCRIPTION REVISIONS: REV. SHEET TITLE PROJECT #: DATE DRAWN BY: ENGINEERED BY: CHECKED BY: EntCadStd-v2.1 3/10/15 WORK # : DRAWING NUMBER CONSTRUCTION KEY PLAN: PROJ MGR: LOCATION: APPROVALS: DESIGN MGR: ISSUE FOR IFC US-34 & US-18 REPLACEMENT PROJECT 10/17/17 80046953 4630141873 SUTTHARA L. SUTTHARA L. DAVE K. MARK McKINNEY FT. BELVOIR, VA 7900 BLOCK, TELEGRAPH ROAD RECOMMENDED PHASING PLAN CONTRACTOR IS REQUIRED TO SUBMIT A PHASING PLAN FOR REVIEW/APPROVAL. PHASING PLAN CAN BE SIMILAR TO THIS RECOMMENDED PLAN OR BETTER. 1. INSTALL NEW ALTERNATE FEEDER CABLES FROM WTA TO US-18 LOAD INTERRUPTER SWITCH. 2. FOR US-18: PRIOR TO DEMOLISHING LOAD INTERRUPTER SWITCH, TRANSFORMER, AND DISTRIBUTION SWITCHBOARD, CONTRACTOR SHALL PROVIDE THREE RENTAL GENERATORS WITH ALL REQUIRED TEMPORARY POWER CABLES TO FEED: x PANEL PP-SA WITH A 20KW, 480/277V, 3PH, 4W GENERATOR x PANEL HAB WITH A 20KW, 480/277V, 3PH, 4W GENERATOR x HEAT PUMP WITH A 40KW, 480/277V, 3PH, 4W GENERATOR 3. ONCE THE NEW ALTERNATE FEEDER CABLE FROM WTA TO US-18 LOAD INTERRUPTER SWITCH IS COMPLETELY INSTALLED AND ALL US-18 LOAD INTERRUPTER SWITCH, PAD MOUNTED TRANSFORMER, AND DISTRIBUTION SWITCHBOARD ARE COMPLETELY REPLACED AND COMMISSIONED, TURN ON BREAKER WTA-D11A TO POWER US-18. AFTER THAT, CONTRACTOR MAY PROCEED WITH US-34 REPLACEMENT. 2. FOR US-34: PRIOR TO DEMOLISHING LOAD INTERRUPTER SWITCH, TRANSFORMER, AND DISTRIBUTION SWITCHBOARD, CONTRACTOR SHALL PROVIDE A RENTAL GENERATOR WITH ALL REQUIRED TEMPORARY POWER CABLES TO FEED: x PANEL MDP1 AT US-34 LOCATION WITH A 40KW, 480/277V, 3PH, 4W GENERATOR 3. ONCE US-34 LOAD INTERRUPTER SWITCH, PAD MOUNTED TRANSFORMER, AND DISTRIBUTION SWITCHBOARD ARE COMPLETELY REPLACED AND COMMISSIONING, TURN ON BREAKER WTB-D6A TO POWER US-34.

Upload: others

Post on 25-Apr-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: US-34 & US-18 REPLACEMENT PROJECT€¦ · drawing index safety xpersonal protective equipment shall be worn as required in all applicable areas. limit access by unapproved personnel

DRAWING INDEX

SAFETY

PERSONAL PROTECTIVE EQUIPMENT SHALL BE WORN AS REQUIRED IN ALL APPLICABLE AREAS.

LIMIT ACCESS BY UNAPPROVED PERSONNEL TO APPLICABLEAREAS

IF WORK IS BEING DONE IN AN AREA WHERE PEDESTRIANS MAY WALK THROUGH, MAKE SURE THE AREA IS BARRICADED OR CONED OFF APPROPRIATELY.

IF WORKING NEAR DOORS OF OFFICE SUITES MAKE SURE SIGNS ARE PLACED ON OTHER SIDE OF DOOR INDICATING WORKERS NEAR DOORWAY

PERMITS MUST BE OBTAINED FROM THE AHJ FOR ENERGIZED ELECTRICAL, HOT WORK, CONFINED SPACE ENTRY AS WELL AS LIFE SAFETY WORK ARE OBTAINED PRIORTO BEGINNING WORK.

ALL EMPLOYEES WORKING ON “LOCKED OUT “EQUIPMENT SHALL HAVE THEIR LOCK AND TAG ON THE SOURCE OF ENERGY.

FOLLOW ALL OTHER APPLICABLE FEDERAL, STATE AND LOCAL ENVIRONMENTAL HEALTH AND SAFETY REGULATIONS.

PROJECT MANAGERS, CONTRACTORS, EHS SHOULD CONFIRM THAT ASBESTOS/HAZARDOUS MATERIALS HAVE BEEN IDENTIFIED, TESTED AND ABATED PRIOR TO ALLWORK.

REDLINESCONTRACTOR SHALL SUBMIT PROJECT REDLINES MERGED TO ONE CLEAN SET OF DRAWINGS STAMPED REDLINES. DRAWINGS WILL BE MARKED: CHANGE - RED PENCIL / REMOVAL -

RED PENCIL HATCH / NOTE TO DESIGNER - GRAY PENCIL.

SUBMITTALS

SCOPE OF WORK

US-34 & US-18REPLACEMENT PROJECT

THIS PROJECT CONTAINS ASBESTOS, ABATEMENT REQUIRED.

THIS PROJECT CONTAINS HAZARDOUS MATERIALS, SPECIAL PRECAUTIONS REQUIRED.

YES NO

GENERAL INFORMATION1 G-001 COVER (INDEX) SHEET

CIVIL

ARCHITECTURAL

STRUCTURAL

MECHANICAL

PLUMBING

FIRE PROTECTION

ELECTRICAL2 E-001 ELECTRICAL NOTES, SYMBOLS AND LEGEND

3 E-002 ONE-LINE SYMBOLS CONT'D & ELECTRICAL ABBREVATIONS

4 E-101 ELECTRICAL SITE PLAN - DEMOLITION

5 E-201 ELECTRICAL SITE PLAN - NEW WORK

6 E-202 ELECTRICAL FLOOR PLAN - NEW WORK

7 E-501 ELECTRICAL SWITCHGEARS & SWITCHBOARDS ELEVATION

8 E-601 PARTIAL ELECTRICAL ONE-LINE DIAGRAM - DEMOLITION

9 E-602 PARTIAL ELECTRICAL ONE-LINE DIAGRAM - NEW WORK

TELECOMMUNICATIONS

SECURITY/IT

G-001

COVER(INDEX)SHEET

STATUS:

DESIGNER:

PROJECT INFORMATION

DESCRIPTION

REVISIONS:

REV.

SHEET TITLE

PROJECT #:

DATE

DRAWN BY:ENGINEERED BY:

CHECKED BY:

EntCadStd-v2.1 3/10/15

WORK # :

DRAWING NUMBER

CONSTRUCTION

KEY PLAN:

PROJ MGR:

LOCATION:

APPROVALS:

DESIGN MGR:

ISSUE FOR

IFC

US-34 & US-18REPLACEMENT

PROJECT

10/17/17

80046953

4630141873

SUTTHARA L.SUTTHARA L.

DAVE K.

MARK McKINNEY

FT. BELVOIR, VA7900 BLOCK, TELEGRAPH ROAD

RECOMMENDED PHASING PLANCONTRACTOR IS REQUIRED TO SUBMIT A PHASING PLAN FOR REVIEW/APPROVAL. PHASING PLAN CAN BE SIMILAR TO THIS RECOMMENDED PLAN OR BETTER.

1. INSTALL NEW ALTERNATE FEEDER CABLES FROM WTA TO US-18 LOAD INTERRUPTER SWITCH.

2. FOR US-18: PRIOR TO DEMOLISHING LOAD INTERRUPTER SWITCH, TRANSFORMER, AND DISTRIBUTION SWITCHBOARD, CONTRACTOR SHALL PROVIDE THREE RENTALGENERATORS WITH ALL REQUIRED TEMPORARY POWER CABLES TO FEED:

PANEL PP-SA WITH A 20KW, 480/277V, 3PH, 4W GENERATOR PANEL HAB WITH A 20KW, 480/277V, 3PH, 4W GENERATOR HEAT PUMP WITH A 40KW, 480/277V, 3PH, 4W GENERATOR

3. ONCE THE NEW ALTERNATE FEEDER CABLE FROM WTA TO US-18 LOAD INTERRUPTER SWITCH IS COMPLETELY INSTALLED AND ALL US-18 LOAD INTERRUPTER SWITCH,PAD MOUNTED TRANSFORMER, AND DISTRIBUTION SWITCHBOARD ARE COMPLETELY REPLACED AND COMMISSIONED, TURN ON BREAKER WTA-D11A TO POWER US-18.AFTER THAT, CONTRACTOR MAY PROCEED WITH US-34 REPLACEMENT.

2. FOR US-34: PRIOR TO DEMOLISHING LOAD INTERRUPTER SWITCH, TRANSFORMER, AND DISTRIBUTION SWITCHBOARD, CONTRACTOR SHALL PROVIDE A RENTALGENERATOR WITH ALL REQUIRED TEMPORARY POWER CABLES TO FEED:

PANEL MDP1 AT US-34 LOCATION WITH A 40KW, 480/277V, 3PH, 4W GENERATOR

3. ONCE US-34 LOAD INTERRUPTER SWITCH, PAD MOUNTED TRANSFORMER, AND DISTRIBUTION SWITCHBOARD ARE COMPLETELY REPLACED AND COMMISSIONING, TURNON BREAKER WTB-D6A TO POWER US-34.

Page 2: US-34 & US-18 REPLACEMENT PROJECT€¦ · drawing index safety xpersonal protective equipment shall be worn as required in all applicable areas. limit access by unapproved personnel

EQUIPMENT RECEPTACLE WALL MTD 6" BELOW SUSPENDED CEILING.

EQUIPMENT RECEPTACLE WALL MTD 12" AFF (UON)

EQUIPMENT RECEPTACLE MTD BELOW RAISED FLOOR

CONDUIT EMBEDDED IN OR BELOW CONCRETE SLAB OR UNDERGROUND

LOCAL CONTROL STATION, TYPE AS INDICATED ON DRAWINGS

EXISTING ELECTRICAL DUCT BANK/GROUND CONDUCTOR AS INDICATED

SV = SOLENOID VALVE, TS = TEMPERATURE SWITCH/TIME SWITCH

MOTOR OPERATED VALVE

TRANSFORMER

MAGNETIC MOTOR STARTER, MH AS INDICATED ON PLANS

HOMERUN TO SOURCE, SOURCE AND CIRCUIT NO.(S) SHOWN

FLUORESCENT LIGHT FIXTURE, STRIP OR INDUSTRIAL TYPE

COMBINATION MOTOR STARTER & CKT BKR, AS INDICATED ON PLANS

FLUORESCENT LIGHT FIXTURE, STRIP OR INDUSTRIAL TYPE,

INCANDESCENT OR HID LIGHT FIXTURE, UNSWITCHED ON EMERG/NL CKT

PANELBOARD, 208Y/120V, SURFACE MOUNTED

GROUND WIRE SYSTEM (DASHED=EXPOSED), WIRE SIZE SHOWN.

FLEXIBLE CONNECTION, SIZE AS INDICATED ON PLANS

MANUAL MOTOR SWITCH, WITH THERMAL OVERLOAD, MH + 4'-0" AFF UON

PANELBOARD, 480/277V, SURFACE MOUNTED

CONDUIT RUN, EXPOSED

CONDUIT RUN, CONCEALED

MECHANICAL UNIT IDENTIFICATION (TYPICAL). UH/4 INDICATES UNIT HEATER #4

2' x 4' FLUORESCENT LIGHT FIXTURE

UNSWITCHED ON EMERG/NL CKT (UON)

JUNCTION BOX, CEILING MOUNTED (SIZE PER 2005 NEC REQUIREMENTS)

PULL BOX OR ENCLOSURE.

J

PLAN SYMBOLSPANELBOARD, 208/120V FLUSH MOUNTED

PANELBOARD, 480/277V, FLUSH MOUNTED

TRACK LIGHTING CEILING MTD, NUMBER OF FIXTURES AS INDICATED

2' x 2' FLUORESCENT LIGHT FIXTURE

1' x 4' FLUORESCENT LIGHT FIXTURE

DASH AND BOLD MARK INDICATES ITEMS TO BE REMOVED

JUNCTION BOX, WALL MOUNTED, MH AS INDICATED ON PLAN DWGS

DEMOLITION NOTES

ONE-LINE SYMBOLS

CONDUIT TURNING UP

CONDUIT TURNING DOWN

UNDERFLOOR BOX FOR UTILITY POWER. POINT OF DISTRIBUTION.

UNDERFLOOR BOX FOR TECHNICAL POWERPOINT OF DISTRIBUTION.

MH + 6'-0"AFF TOHIGHEST BREAKER

CONDUIT HASH MARKS INDICATE NO. OF #12 IN CODE SIZE CONDUIT,3/4"C MIN. LONG MARK INDICATES NEUTRAL CONDUCTOR; GREENGROUND CONDUCTOR IS NOT SHOWN BUT SHALL BE PROVIDED.

JUNCTION BOX, MOUNTED ON SLAB UNDERFLOOR (SIZE PER 2005 NEC REQUIREMENTS)J

J JUNCTION BOX, MOUNTED ON SLAB UNDERFLOOR

TYPE 5-20R.

OVERLOAD ELEMENTS, NO. INDICATED, MOTOR CONTROLLER

SELECTOR SWITCH (SPDT), THREE POSITION

SOLENOID OPERATED VALVE COIL

SELECTOR SWITCH (SPST), TWO POSITION

TOGGLE SWITCH (SPST)

ONE-LINE SYMBOLS

AS = AMMETER SWITCH, VS = VOLTMETER SWITCH

MOTOR WITH HORSEPOWER INDICATED

CIRCUIT BREAKER, 3P, FRAME & TRIP RATING AS INDICATED

TS=CKT BKR TEST SWITCH, CS=CKT BKR CONTROL SWITCH

120 VAC SHUNT TRIP, SOLID IS NEW, DASHED IS FUTURE

CONTROL TRANSFORMER, 1Ø, WINDING VOLTAGES AS INDICATED

CONDUCTORS CONNECTED

CONDUCTORS NOT CONNECTED

A= AMMETER V= VOLTMETER

INTERLOCK CIRCUIT

INDICATES FEEDER No.

KEY INTERLOCK

AUTOMATIC TRANSFER SWITCH

EMERGENCY/STANDBY GENERATOR SET

GROUND CONNECTION

BATTERY, DC VOLTAGE AS INDICATED

HIGH VOLTAGE LOAD INTERRUPTER SWITCH, NON-FUSED

POWER TRANSFORMER, RATINGS AS PER SINGLE LINE

POWER TRANSFORMER WITH ELECTROSTATIC SHIELD

GROUNDING RESISTOR, RESISTANCE AS INDICATED

LOW VOLTAGE DRAWOUT CIRCUIT BREAKER

FUSE, TYPE AS INDICATED

DRAW-OUT STAB CONNECTOR

E.O. = ELECTRICALLY OPERATED

S

HARDWIRE CONNECTION TO EQUIPMENT AS INDICATED ON DRAWINGS.

PLUG STRIP

SERVICE OUTLET BOX, (1) SINGLE 5-20R ON TECHNICAL POWERAND (1) DUPLEX 5-20R ON UTILITY POWER.

VIDEO INTERFACE BOXV

FLASHING LIGHT

OCCUPANCY SENSOR, PASSIVE DUAL TECHNOLOGY, WIDE VIEW, WALL MTD,MH 8'-6"AFF. INFRARED/MICROPHONIC TECHNOLOGIES, a = SWITCHCONTROLLING LIGHTING FIXTURES WITH DESIGNATIONS SHADED PORTIONS OFSYMBOL INDICATE SENSOR INSTALLATION DIRECTION FOR MAXIMUM AREACOVERAGE, 6-DESIGNATES CONTROLLED CIRCUIT (OPEN OFFICE AREAS).

HEAVY LINE IS NEW WORK BY THE CONTRACTOR UON.

LIGHT LINE IS EXISTING WORK AND IS SHOWN FOR REFERENCE ONLY UON.

CONDUIT HASH MARKS INDICATE NO. OF #12 IN CODE SIZECONDUIT, 3/4"C MIN. LIGHT HASH MARKS INDICATE EXISTING 2WIRES; BOLD HASH MARKS INDICATE NEW WIRES, SIZE ASINDICATED.

ACCESS CONTROL REMOTE RELEASE BUTTON

LIGHTNING PROTECTION AIR TERMINAL

EMERGENCY POWER SWITCH ("EPO" BUTTON) ANNUCIATOR PANEL.

EQUIPMENT DISCONNECT SWITCH.

PUBLIC ANNOUNCER SYSTEM SPEAKER

M

M5

1. SOME SYMBOLS SHOWN ON THIS DRAWING ARE NOT BEING USED.

2. ENSURE POWER OUTAGE AUTHORIZATION IS APPROVED PRIOR TOSHUTTING ANY POWER SOURCE.  COORDINATE ALL POWEROUTAGES WITH GOVERNMENT AT LEAST ONE WEEK IN ADVANCE.

3. THE CONDUIT SYSTEM SHALL NOT BE USED AS EQUIPMENTGROUNDING. FOR SYSTEMS 600 VOLTS AND BELOW, ALL POWER ANDCONTROL/INSTRUMENTATION FEEDERS SHALL HAVE A GREENGROUND CONDUCTOR. ALL NON-CURRENT CARRYING PARTS OFSUCH EQUIPMENT, LIGHTING FIXTURES, RECEPTACLES, ETC SHALLBE GROUNDED BY MEANS OF A GREEN INSULATED GROUNDCONDUCTOR RUN IN THE RACEWAY WITH PHASE CONDUCTORSSIZED PER 2017 NEC (OR MOST CURRENT VERSION) UNLESSOTHERWISE INDICATED ON THE DRAWING.

4. ALL "SPARE" CONDUITS AND "CONDUIT ONLY" SHALL BE PROVIDEDWITH A 200 POUND NYLON PULLCORD.

5. ALL NOTES ON DRAWINGS WITHOUT OR ARE GENERALNOTES.

6. ALL CONDUIT ABOVE CEILING SPACE SHALL BE INSTALLED ABOVEMECHANICAL PIPING/DUCT WORK.

7. OCCUPANCY SENSORS SHALL BE OF THE TWO-WAY TYPE, WHICHDETECT CHANGES IN LOW INTENSITY, INAUDIBLE SOUND WAVES.SENSORS SHALL HAVE ADJUSTABLE SENSITIVITY AND TIME DELAY (15SEC. TO 30 MINUTES), AND MANUAL OVERRIDE SWITCH. SET SENSORTIME DELAY AT 10 MINUTES. ADJUST SENSITIVITY AS REQUIRED.SENSORS SHALL HAVE MULTIPLE FREQUENCIES TO ENABLESEPARATE CONTROL OF ADJACENT AREAS. THREE AREAS WHEREOCCUPANCY SENSORS SHALL BE PROVIDED ARE: OPEN OFFICESPACES, RESTROOMS, AND CORRIDORS. OCCUPANCY SENSORSSHALL BE CAPABLE OF OPERATION IN OPEN OFFICE SPACE WITHMODULAR OFFICE WALLS AT 84 INCHES HIGH.

8. FOR ALL TRANSFORMERS, THE SECONDARY NEUTRAL CONDUCTORSHALL BE GROUNDED IN ACCORDANCE WITH THE 2017 NEC (ORMOST CURRENT VERSION).

9. ALL CONTROL/POWER WIRING REQUIRED BUT NOT SHOWN FORTHERMOSTATS, CONTROLLERS, VARIABLE FREQUENCY DRIVECONTROL, MANUFACTURE EQUIPMENT CONTROL PANEL, DAMPERMOTORS, VARIABLE VOLUME CONTROLS, MOTORS, SMOKE DAMPERS,SENSING DEVICES SUCH AS TEMPERATURE, PRESSURE, HUMIDITY,LEVEL, FLOW, AND VOLUME ETC. SHALL BE PROVIDED BYCONTRACTOR AS PART OF INSTALLATION PACKAGE.

10. CONTRACTOR SHALL MAKE FINAL CONNECTION TO FLOOR BOXESAND LAN FDF RACKS FOR A COMPLETE FUNCTIONAL SYSTEM.

11. FIELD VERIFY AND UPDATE ALL POWER PANEL SCHEDULES.

12. ALL WORK SHALL BE IN ACCORDANCE TO STANDARD SPECIFICATION2000 (CURRENT VERSION).

13. CONTRACTOR SHALL NOT USE METAL CLAD CABLE UNLESS NOTEDON DRAWINGS.

14. ALL CONDUIT RUNS SHOWN ARE FOR ILLUSTRATION ONLY.CONTRACTOR SHALL FIELD VERIFY FOR EXACT CONDUIT ROUTINGPATHS. PROJECT MANAGER SHALL BE NOTIFIED IMMEDIATELY OFANY DEVIATIONS FROM THE DRAWINGS.

15. AREA SHALL BE CLEAN AND LEFT IN SAFE WORKING CONDITIONS PEROSHA REQUIREMENTS UPON COMPLETION OF PROJECT.

16. EACH NEW RECEPTACLE FEEDING A SERVER RACK IN DATA CENTERSHALL BE FED FROM A DEDICATED CIRCUIT.  MULTIPLERECEPTACLES FED FROM THE SAME CIRCUIT SHALL NOT BEPERMITTED.

NOTICE:ALL WORK WITHIN PDU'S/ELECTRICAL PANELSSHALL BE PERFORMED BY FSB APPROVEDPERSONNEL. THIS IS TO INCLUDEENERGIZING AND DE-ENERGIZING OFDISCONNECTS AND BREAKERS.

1. THE CONTRACTOR SHALL VERIFY ALL EXISTING EQUIPMENT SHOWNON THE DEMOLITION DRAWINGS TO BE REMOVED/RELOCATEDDURING THE JOB WALK.

2. WHERE EXISTING CIRCUITS FEED DEVICES TO BE REMOVED AND TOBE RELOCATED, CONTRACTOR SHALL MAINTAIN EXISTING CIRCUITCONTINUITY TO THE PORTION OF THE CIRCUIT REQUIRED TOREMAIN IN SERVICE.

3. CONTRACTOR SHALL REMOVE ALL DEMOLISHED ELECTRICALEQUIPMENT FROM THE SITE UNLESS OTHERWISE NOTED. WORKAREAS SHALL BE CLEAR PRIOR TO STARTING NEW ELECTRICALWORK.

4. ALL HOLES AND DAMAGE CAUSED BY ELECTRICAL DEMOLITION ANDMODIFICATIONS SHALL BE REPAIRED AND PAINTED TO MATCHADJACENT AREA AND EXISTING CONDITIONS.

5. THE CONTRACTOR SHALL COORDINATE ANY ELECTRICALDEMOLITION WITH THE GOVERNMENT BEFORE STARTING ANYWORK.

6. THE CONTRACTOR SHALL RETURN TO THE GOVERNMENT, ORPROVIDE THE GOVERNMENT WITH COMPENSATION FOR ANYTHINGSALVAGED.

7. PRIOR TO DE-ENERGIZING POWER SOURCE OF ANY EXISTINGRECEPTACLE IN A DATA CENTER, CONTRACTOR SHALL FIELD VERIFYTO ENSURE THE DEMOLISHED RECEPTACLE HAS NO POWER CORDPLUGGED INTO IT.  IF A POWER CORD IS STILL PLUGGED IN THERECEPTACLE TO BE DEMOLISHED, CONTRACTOR SHALL NOTIFYPROJECT MANAGER IMMEDIATELY.  ONLY END USER ISAUTHORIZED TO UNPLUG THE POWER CORD.

8. UNLESS OTHERWISE NOTED, WHEN MULTIPLE CIRCUITS RUN IN THESAME RACEWAY TO FEED MULTIPLE RECEPTACLES AND ONE OFTHOSE RECEPTACLES IS NOT IN USE.  THE UNUSED RECEPTACLESHALL NOT BE DEMOLISHED AND IT SHALL REMAIN IN PLACE. LABEL CIRCUIT FEEDING THE UNUSED RECEPTACLE AS “U/F SPAREREC @ XXYY.”  XXYY IS THE ACTUAL GRID LOCATION.

MEDIUM VOLTAGE DRAW-OUT VACUUM CIRCUIT BREAKER,SIZE AND CAPACITY AS INDICATED

ELECTRICAL CONNECTION

WINDOW TYPE CURRENT TRANSFORMER. 1-INDICATESNUMBER OF CT'S AND 50/5-INDICATES TURN RATIO

CURRENT TRANSFORMER. 3-INDICATES NUMBER OF CT'S AND2000/5-INDICATES CURRENT RATIO

COMBINATION STARTER FULL VOLTAGE NONREVERSING; 1 = NEMA STARTER SIZE

COMBINATION CONTACTOR, 1 = NEMA CONTACTOR SIZE

CONTACTOR, 1 = NEMA CONTACTOR SIZE

LIGHTING FIXTURE TYPE, SEE LIGHTING FIXTURE SCHEDULE MOUNTINGHEIGHT AFF IS AS INDICATED. FIXTURE IS SURFACE OR RECESSED MOUNTEDWHEN MOUNTING HEIGHT IS OMITTED.

FLUORESCENT LIGHT FIXTURE, LETTER a INDICATES ONE HALF ON NORMALPOWER SWITCHED LEG AND THE OTHER HALF UNSWITCHED ON EMERG/NLCIRCUIT. ABSENCE OF CONTROL SW LETTER INDICATES ENTIRE FIXTURE ISUNSWITCHED ON EMERG/NL CKT.

INCANDESCENT, COMPACT FLUORESCENT OR HID LIGHT FIXTURE, CEILING MOUNTED,UON

EXIT LIGHT, CEILING MTD, SINGLE OR DOUBLE FACE AS INDICATED BY THE NUMBER OFDIRECTIONAL ARROWS SHOWN. SHADED AREA INDICATES FACE OF THE EXIT SIGN.

INCANDESCENT OR HID LTG FIXTURE WALL MTD UON, MOUNTINGHEIGHT AS NOTED ON LIGHTING PLAN

EXIT LIGHT, BACK WALL MOUNTED, WITH OR WITHOUT DIRECTIONALARROW AS INDICATED. SHADED AREA INDICATES FACE OF THE EXITSIGN.

LIGHT SWITCH, WALL MTD 42" AFF., LETTERS AND NUMBERS INDICATE: a = SWITCHCONTROLLING LTG FIXTURES W/DESIGNATION; 3 = THREE WAY SWITCH; 2 =DOUBLE POLE, SINGLE THROW; D = DIMMER (20A, 120-277VAC)

OCCUPANCY SENSOR, PASSIVE DUAL TECHNOLOGY, WIDE VIEW, WALL MTD, MH42"AFF. INFRARED/MICROPHONIC TECHNOLOGIES, a = SWITCH CONTROLLINGLIGHTING FIXTURES WITH DESIGNATIONS SHADED PORTIONS OF SYMBOL INDICATESENSOR INSTALLATION DIRECTION FOR MAXIMUM AREA COVERAGE. (PRIVATEOFFICES). PROVIDE IVORY COLORED DECORATOR STYLE AND FIT INTO A SINGLEGANG SWITCH BOX.

OCCUPANCY SENSOR (INFRARED TECHNOLOGY), WIDE VIEW, WALL MTD, MH 6"BELOW CEILING, a = SWITCH CONTROLLING LIGHTING FIXTURES WITHDESIGNATION, SHADED PORTIONS OF SYMBOL INDICATE SENSOR INSTALLATIONDIRECTION FOR MAXIMUM AREA COVERAGE (CORRIDORS).

20A, 120V, 1 PHASE POWER-PACK: a = IDENTIFIES CONTROLLINGOCCUPANCY SENSOR(S). CIRCUIT NUMBER ON THE LIGHTING FIXTURESALSO FEEDS THE POWER PACK NEAREST TO THE FIXTURE.

EMERGENCY POWER OFF "EPO" BUTTON MOUNTED 42" AFF. BUTTON SHALL BE REDMUSHROOM TYPE, SPRING ACTION MOMENTARY CONTACT, AND 40MM CLEARHINGED LOCKOUT LIP.

QUADRUPLEX RECEPTACLE, (2)20A, 125V, 2P-3W, NEMA 5-20R, 18"AFF (UON).MOUNTED IN DOUBLE GANG UTILITY BOX

FLOOR UTILITY ACCESS BOX WITH NEMA TYPE RECEPTACLES AS INDICATED ONDRAWINGS.

DUPLEX CONVENIENCE RECEPTACLE, 20A, 125V, 2P-3W, NEMA 5-20R, 18"AFF (UON).GFCI INDICATES GROUND FAULT CURRENT INTERRUPTER.

SINGLE RECEPTACLE, 20A, 125V, 2P-3W, NEMA 5-20R, 54" AFF (UON).

DUPLEX CONVENIENCE RECEPTACLE ON EMERGENCY CIRCUIT, 20A, 125V, 2P-3W,NEMA 5-20R, 18" AFF (UON). RECEPTACLES SHOWN ON SYSTEMS FURNITUREPARTITION PANELS ARE LOCATED IN BASE OF PANELS. GFCI INDICATES GROUNDFAULT CURRENT INTERRUPTER

DUPLEX CONVENIENCE RECEPTACLE, 20A, 125V, 2P-3W, NEMA 5-20R, MOUNTEDAT CEILING.

DUPLEX CONVENIENCE RECEPTACLE, 15A, 125V, 2P-3W, NEMA 5-15R, MOUNTEDUNDER RAISED FLOOR

SINGLE RECEPTACLE, 20A, 125V, 2P-3W, NEMA 5-20R, MOUNTED UNDERRAISED FLOOR

TWIST LOCK RECEPTACLE, AMPACITY AND VOLTAGE AS INDICATED ONRENOVATION PACKAGE.

TWIST LOCK SINGLE RECEPTACLE, 20A, 125V, 2P-3W, NEMA L5-20R, MOUNTEDUNDER RAISED FLOOR

TWIST LOCK SINGLE RECEPTACLE, 30A, 125V, 1P-3W, NEMA L5-30R, MOUNTEDUNDER RAISED FLOOR

TWIST LOCK SINGLE RECEPTACLE, 30A, 250V, 2P-3W, NEMA L6-30R, MOUNTEDUNDER RAISED FLOOR

TWIST LOCK SINGLE RECEPTACLE, 20A, 208/120V, 4P-5W, NEMA L21-20R,MOUNTED UNDER RAISED FLOOR

TWIST LOCK SINGLE RECEPTACLE, 20A, 250V, 2P-3W, NEMA L6-20R, MOUNTEDUNDER RAISED FLOOR

TWIST LOCK SINGLE RECEPTACLE, 30A, 120/208V, 3Ø, 4P-5W, NEMA L21-30R,MOUNTED UNDER RAISED FLOOR

SYSTEMS FURNITURE PARTITION POWER ENTRY (UTILITYPOWER)

CLOCK OUTLET, WALLMOUNTED

POWER DISTRIBUTION UNIT. K RATEDISOLATION TRANSFORMER WITH THREESECTION, 126 POLE PANELBOARD.

EMERGENCY POWER OFF (EPO) SWITCH FOROPERATION OF SHUNT TRIP BREAKER.

WALL OR CEILING MOUNTED EMERGENCYLIGHTING UNITS MAINTENANCE FREE WITHLEAD-CALCIUM BATTERIES

STREET LIGHT, 277AC, ON 25' (VON) POLE AND METAL HALIDE SOURCE.

AREA/WALKWAY LIGHT, 277AC, ON 10' (VON) AND METAL HALIDE SOURCE.

DIRECT BURIED PULL BOX FOR ELECTRICAL POWER FEEDS. (MANHOLE)

ELECTRICAL MOTOR. SIZE, CONDUIT, ANDCONDUCTORS AS INDICATED ON ONE-LINE DIAGRAM

COMBINATION HIGH VOLTAGE SELECTOR AND LOADINTERRUPTER WITH MECHANICAL INTERLOCK

POTENTIAL OR CONTROL POWER TRANSFORMER WITHFUSES QUANTITY AND WINDING VOLTAGES AS INDICATED

SURGE ARRESTER, VOLTAGE RATING AND QUANTITY ASINDICATED

MAGNETIC ONLY CIRCUIT BREAKER WITH MOTOR CIRCUITPROTECTOR

LOW VOLTAGE DISCONNECT SWITCH NON FUSED, 30A/3P UON

LOW VOLTAGE FUSED DISCONNECT SWITCH, 3 POLE SIZE ASSHOWN 60A INDICATES SWITCH SIZE (50A) INDICATES FUSESIZE

COIL, R=RELAY, D=DAMPER MTR, M=MOTOR STARTER COIL,TC=TRIP COIL, TS=TIME SWITCH

STARTER RELAY CONTACT, NORMALLY OPEN, R-1=DEVICECONTACT NO.1CIRCUIT BREAKER AUXILIARY CONTACT, b = NORMALLYCLOSED.

TEMPERATURE SWITCH, NORMALLY OPEN, CLOSES ON INCREASINGTEMP

TEMPERATURE SWITCH, NORMALLY CLOSED, OPENS ON INCREASINGTEMPTIMER CONTACT, NORMALLY OPEN, TIME DELAY CLOSE ATENERGIZING

TIMER CONTACT, NORMALLY CLOSED, TIME DELAY OPEN ATENERGIZINGINSTANTANEOUS CLOSE WHEN RELAY IS ENERGIZED. TIMEDELAY OPEN WHEN RELAY IS DEENERGIZED.

INSTANTANEOUS OPEN WHEN RELAY IS ENERGIZED. TIMEDELAY CLOSE WHEN RELAY IS DEENERGIZED.

PILOT LIGHT, A-AMBER, B-BLUE, G-GREEN, R-RED, W-WHITE,Y-YELLOW

E-001

ELECTRICAL NOTES,SYMBOLS AND

LEGEND

GENERAL NOTES

PLO

T D

ATE

: 1

0/1

9/2

01

7, FIL

E N

AM

E: S

R 8

00

46

95

3_U

S-3

4_E

-00

1.d

wg

PLO

T S

CA

LE

: 4

41

/64

" =

1'-0

", P

LO

T T

AB

LE

: --

-- L

TS

CA

LE

: 0

.20

00

00

STATUS:

DESIGNER:

PROJECT INFORMATION

DESCRIPTION

REVISIONS:

REV.

SHEET TITLE

PROJECT #:

DATE

DRAWN BY:ENGINEERED BY:

CHECKED BY:

EntCadStd-v2.1 3/10/15

WORK # :

DRAWING NUMBER

CONSTRUCTION

KEY PLAN:

PROJ MGR:

LOCATION:

APPROVALS:

DESIGN MGR:

ISSUE FOR

IFC

US-34 & US-18REPLACEMENT

PROJECT

10/17/17

80046953

4630141873

SUTTHARA L.SUTTHARA L.

DAVE K.

MARK McKINNEY

FT. BELVOIR, VA7900 BLOCK, TELEGRAPH ROAD

Page 3: US-34 & US-18 REPLACEMENT PROJECT€¦ · drawing index safety xpersonal protective equipment shall be worn as required in all applicable areas. limit access by unapproved personnel

ONE-LINE SYMBOLS (CONT'D)

STARTER TERMINAL

RELAY PANEL TERMINAL

DEVICE TERMINAL

FIELD TERMINATION POINT

3 POSITION SELECTOR SWITCH, HAND-OFF-AUTOMATIC

PUSH BUTTON SWITCH, MOMENTARY CONTACT, NORMALLY OPEN

PUSH BUTTON SWITCH, MOMENTARY BREAK, NORMALLY CLOSED

TRIPPING AUXILIARY RELAY

CLOSED BREAKER TRIP COIL

CLOSED IN TRIP POSITION

KILOWATT/KILOVAR METER

WHD = WATTHOUR DEMAND METER PF = POWER FACTOR METER

TA = CURRENT TRANSDUCER TV = VOLTAGE TRANSDUCER

GROUND FAULT RELAY

GROUND PROTECTIVE RELAY

FREQUENCY RELAY, GENERATOR BUS

CONTACT IN AUTOMATIC SYNCHRONIZER

SELECTOR SWITCH, VP 488-788

SELECTOR SWITCH, AUTO TRANSFER, ON-OFF

SELECTOR SWITCH, TWO POSITION MAINTAINED CONTACT

LOAD CONTROL SELECTOR SWITCH

LOAD CONTROL CONTACT

CLOSING AUXILIARY RELAY

AUXILIARY POWER CONTROL SWITCH

CLOSED IN CLOSED POSITION

CIRCUIT BREAKER TEST SWITCH

CIRCUIT BREAKER STATIONARY AUX CONTACT

GENERATOR LOCKOUT RELAY

(VP) LOCKOUT RELAY FOR XFMR T1

DIFFERENTIAL PROTECTIVE RELAY

LOCKOUT RELAY FOR TIE BREAKER

GENERATOR BUS GROUND AUXILIARY RELAY

LOCKOUT RELAY, MAIN BUS SOURCE 1, 2

GENERATOR BUS GROUND LOCKOUT RELAY

CIRCUIT BREAKER TRUCK OPERATED CONTACT

64

LOCK OUT RELAY

86GG

86GGX

86TIE

86T1

87

86B1,B2

86

86G

81G

OVERVOLTAGE RELAY59

52/TOC

52STA

52TS

T

TC

TX

CS30A,B

C

CXA

LC

LCS

SS

SSA

SSB

SYN

TW = WATT TRANSDUCER

AC CIRCUIT BREAKER

CIRCUIT BREAKER AUXILIARY CONTACTS

CIRCUIT BREAKER CONTROL SWITCH52CS

52a,b

52

UNDERVOLTAGE TIME DELAY RELAY, GEN BUS

MANUAL TRANSFER OR SELECTOR DEVICE

DEVICE, QUANTITY AS INDICATED, LEGEND AS INDICATED BELOW:

UNDERVOLTAGE AUXILIARY RELAY, GEN BUS

NEUTRAL TIME OVERCURRENT RELAY

VOLTAGE RESTRAINED TIME OVERCURRENT RELAY

COMBINATION INSTANTANEOUS AND TIME OVERCURRENT RELAY

GROUND INSTANTANEOUS OVERCURRENT RELAY

NEUTRAL INSTANTANEOUS OVERCURRENT RELAY

GENERATOR BUS GROUND AC OVERCURRENT RELAY

GROUND TIME OVERCURRENT RELAY

FIELD (OVER/UNDER EXCITATION) RELAY

51V

INSTANTANEOUS OVERCURRENT RELAY

REVERSE PHASE OR PHASE BALANCE CURRENT RELAY

AC TIME OVERCURRENT RELAY

51G

51N

51GG

50/51

51

50

5ON

5OG

43

46

40

27G/TD

SYNCHRONISM CHECK RELAY

TIME DELAY STARTING OR CLOSING RELAY

DEVICE PROVIDED BY OTHERS, LEGEND AS INDICATED BELOW:

UNDERVOLTAGE RELAY, GEN BUS

UNDERVOLTAGE RELAY

DIRECTIONAL POWER RELAY

25

32

27GX

27G

27

02

OR 3

GENERAL ELECTRIC POWER LOGIC MODBUS MONITOR

GENERAL ELECTRIC MICRO VERSA TRIP PM UNIT WITH COMMUNICATIONS CAPABILITY.

ELECTRICAL ABBREVIATIONS

CATALOGCAT

FDF FIBER DISTRIBUTION FRAME

CR CONTROL RELAY

CONTROL SWITCH

CURRENT TRANSFORMER/COOLING

(X DENOTES # OF CONDUCTORS)

SINGLE CONDUCTOR CABLE

MULTICONDUCTOR CABLE

COOL WHITE/CHILLED WATER

CHILLED WATER PUMP

CABLE TERMINATION CABINET

COOLING TOWER WATER SUPPLY

COOLING TOWER WATER RETURN

TOWER/CONTROL TRAY

CWP

1/C

X/C

CU

CW

COPPER

CTC

CTWR

CTWS

CS

CT

CHILLED WATER SUPPLY

COMMUNICATION MANHOLE/HANDHOLE

CONTINUOUS LOAD

CONDUIT ONLY

CONTROL POWER TRANSFORMER

CONDUCTOR,CONDITIONING

CONTROL/CONTINUATION

COMMUNICATION

CONT

CORR

CPT

CONN

COND

CORRIDOR

CONNECTION

CL

CMH

CO

COMM

CKT

CHWS

CIRCUIT

COMPRESSED AIR UNIT

CHILLED WATER RETURN

CONTRACTOR FURNISHED EQUIPMENT/

CHILLER CONTROL PANEL

CHILLED WATER PUMP

CHILLER MOTOR STARTER

CENTRAL HOUSE VACUUM

CONTRACTOR INSTALLED

CONTROL BUILDING

COAXIAL CABLE UTILITY RACK

CIRCUIT BREAKER/CHILLER BUILDING/

CHWP

CHV

CHWR

CHCP

CH

CHMS

CHILLER

CCUR

CFE/CI

CAU

CB

GOVERNMENT FURNISHED EQUIPMENT/

GOVERNMENT FURNISHED EQUIPMENT/

GROUND

GOVERNMENT FURNISHED EQUIPMENT

GROUND FAULT RELAY

GOVERNMENT INSTALLED

CONTRACTOR INSTALLED

G

GND

GF

GFE

GFE/CI

GFE/GI

FIRE PROTECTION

FUTURE

FEET/FOOT

FLOW SWITCH

FULL VOLTAGE

FORWARD

GENERATOR

GROUND FAULT INTERRUPTER

FULL VOLTAGE NON-REVERSING

GRAPHIC ANNUNCIATOR PANEL

FULL VOLTAGE REVERSING

GAP

GEN

GFI

FWD

FVR

FUT

FV

FVNR

FP

FS

FT(')

FIBER OPTIC CABLE

FINISHED

FIXTURE

FULL LOAD AMPS

CONTROL SYSTEM

FLUORESCENT

FLEXIBLE

FEEDER/FIBER DISTRIBUTION RACK

FIBER OPTIC CABLE UTILITY RACK

FIBER OPTIC CABLE TRAY

FACILITIES MONITORING AND

FO

FOCT

FOCUR

FMCS

FLUOR

FLA

FIXT

FLEX

FDR

FIN

BALANCED MAGNETIC SWITCH

CONDUIT/ CONDUCTOR/ COMMON

BOTTOM OF BOX

BELOW FINISH FLOOR

BOTTOM OF STEEL

BOTTOM OF CONDUIT

BOTTOM OF TRAY

BADGE TERMINAL CABINET

C

BTC

BOC

BOS

BOT

BMS

BOB

BLDG

BC

BFF

BKR

BUILDING

BARE COPPER

BREAKER

APPROXIMATELY

ARCHITECTURAL

AIR HANDLING UNIT

AMPS INTERRUPTING CAPACITY

AUTOMATIC TRANSFER SWITCH

AMERICAN WIRE GAUGE

AMMETER SWITCH

ABOVE RAISED FLOOR

AWG

BATT

AS

AT

ATS

BATTERY

AMPERE TRIP

APPROX

ARCH

ARF

AHU

AIC

AL ALUMINUM

4" SQUARE, 2 1/8" DEEP JUNCTION BOX

ACCESS CONTROL SECURITY SYSTEM

AMPERES/AMMETER/AUTO

AMPERE FRAME

ALTERNATING CURRENT/AIR COMPRESSOR

ABOVE FINISH FLOOR

AIR CONDITIONING UNIT

AIR CONDITIONING

ABOVE CONCRETE FLOOR

AIR CIRCUIT BREAKER

ACSS

AF

AFF

A/C

ACF

A

AC

ACB

4SD

DWG DRAWING

EQ

ELECTRICAL ROOM

FIRE ALARM

FAN COIL UNIT

FILTER/FAST FORWARD CONTACTOR

FIBER DISTRIBUTION CENTER

FIRE ALARM CONTROL PANEL

EQUIPMENT

ELECTRICAL WATER HEATER

ELECTRIC WATER COOLER

EXISTING

FACP

FCU

FDC

FA

F

(E), EXIST

EWC

EWH

ER

EQUIP

ELECTRICAL

EXHAUST FAN

EMERGENCY

ENCLOSURE

ELECTRIC METALLIC TUBING

ELECTRICALLY OPERATED

ELECTRICAL MANHOLE/HANDHOLE

EMERGENCY POWER OFF

ELEVATION

ENCL

EO

EPO

EMERG

EMT

EL

EMH

ELEV

EF

ELECT

DIRECT CURRENT

DISCONNECT

DISTRIBUTE/DISTRIBUTION

DOOR SWITCH

DIRECT BURIAL/ DUCT BANK

DOUBLE POLE, SINGLE THROW

DOUBLE POLE, DOUBLE THROW

DIAMETER

DETAIL

DATA

DIA

DPDT

DPST

DS

DISC

DISTR

DB

DC

DET

D

MULTIMODE TYPE FIBER CABLE

AND ELECTRONIC ENGINEERS

MOTORIZED CONTROL DAMPER

LOW VOLTAGE POWER & CONTROL

MOUNTING HEIGHT/ MANHOLE

MM

MS

MPU

MOV

MTD

MTG

MTR

MVA

MOTOR

MEGAVOLT-AMPERE

MOTORIZED SCREEN

MAIN PROCESSOR UNIT

MOTOR OPERATED VALVE

MOUNTED

MOUNTING

MCD

MICRO

MCB

MCC

MAX

MH

MIN

MFG

MFGR

MECH

MISC

MLO

MANUFACTURER

MAIN LUGS ONLY

MISCELLANEOUS

MINIMUM

MICROWAVE

MANUFACTURING

MOTOR CONTROL CENTER

MAIN CIRCUIT BREAKER

MECHANICAL

MAXIMUM

LVL

LIS

LV

LCS

LFACP

LDCP

LTG

LTC

LVPC

MA

LOW VOLTAGE

METER/MANUAL

MILLIAMPS

M

LEVEL

LOAD INTERRUPTER SWITCH

LIGHT/LIGHTING

LOAD TAP CHANGER

LOAD CONTROL SYSTEM

LC

JB

J-BOX

KV

kcmil

KVA

KW

KVAR

LIGHTING CONTACTOR

KILOVOLT-AMPERES

LINEL

KILOVAR

KILOWATT

THOUSAND/KILO

JUNCTION BOX

THOUSAND CIRCULAR MIL

KILOVOLT

k

ICI

IEEE

IG

IFC

INCAND

INTLK

IND

ISC

ISOLATED GROUND

INCANDESCENT

SHORT CIRCUIT CURRENT

INTERLOCK

INDICATION

ISSUED FOR CONSTRUCTION

INSTITUTE OF ELECTRICAL

HERTZHZ

HID

HHWP

HOA

HP

HPF

HPS

HVAC

HW

HORSEPOWER

HIGH VOLTAGE

HIGH POWER FACTOR

HIGH PRESSURE SODIUM

HOT WATER

HV

HOT/HUMIDIFIER/HIGH

HAND OFF AUTOMATIC

HEATING HOT WATER PUMP

HIGH INTENSITY DISCHARGE

H

SINGLEMODE TYPE FIBER CABLE

SHUNT TRIP/ FO CABLE CONNECTOR

SPLICE POINT/SPARE

SINGLE POLE SINGLE THROW

SMOKE PURGE CONTROL PANEL

SINGLE POLE DOUBLE THROW

SV SECURE VOICE

SECONDARY STRING

SUBSTATION

STARTER

STANDARDSTD

STR

SUB

SPST

SS

ST

SIGNAL MANHOLE

SPECIFICATIONS

SPCP

SPECS

SPDT

SM

SMH

SP

RADIO FREQUENCY INTERFERENCE

RIGID GALVANIZED STEEL CONDUIT

RADIO FREQUENCY FILTER ASSEMBLY

ROOT MEAN SQUARE

REDUCED VOLTAGE REVERSING

REDUCED VOLTAGE NON-REVERSING

SECONDARY/SECOND

POLYVINYL CHLORIDE

POTENTIAL TRANSFORMER

PRESSURE SWITCH/PRIMARY STRING

SQUARE DEEP

SELECTOR

SCHEDULE

SHEET

SHIELDED

SEC

SEL

SH

SHT

SCH

SD

ROOM

REDUCED VOLTAGE

RVR

RVNR

RV

RGS

RM

RMS

BADGE READERRDR

REVISION/REVERSE

REFERENCE

RECEPTACLE

REV

RFI

RFFA

REF

RUN CONTACTOR

POWERPWR

R

PS

PT

PVC

POST INDICATOR VALVE

PERSONAL COMPUTER

PERSONNEL ACCESS CONTROL

PACSS EQUIP CLOSET

OVERLOAD RELAY CONTACTS

POINT OF CONNECTION

POWER DISTRIBUTION UNIT

PULL BOX/PUSHBUTTON

PATCH PANEL

PAIR

PANEL

POWER PULL BOX

PRIMARYPRI

PPB

PR

P/P

PNL

POC

POWER FACTOR

PIV

PF

PDU

PC

PCL

PB

OL

SECURITY SYSTEM

OPTICAL TURNSTILE

POLE/POWER

PUBLIC ADDRESS

P

PACSS

PA

OT

OVERCURRENT

NOT TO SCALE

PHASE/DIAMETER

NON SECURE VOICE

NON-AUTOMATIC

Ø

OC

NTS

NSV

NEUTRAL/NEUTRAL CONTACTOR

NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NATIONAL ELECTRICAL CODE

NORMALLY CLOSED/NEXT COMPUTER

NORMALLY OPEN

NIGHT LIGHT

NOT IN CONTRACT

NON-FUSED

NUMBER

NL

NO

No./#

NF

NIC

NC

NEC

NEMA

N

BADGE MAKING WORKSTATION

VIDEO DISPLAY TUBE TERMINAL

WATTS/WIRE/WIDTH/WIDE

VOLTAGE REGULATOR

VOLT-AMPERE

WATT HOUR DEMAND METER

VARIABLE SPEED/VOLTMETER SWITCH

VOLTAGE DROP

WEATHERPROOF

IMPEDANCE

TRANSFORMER

VOLTAGE DISTURBANCE MONITOR

VOLT/VOLTMETER

WORK STATION

XFMR

Z

W/

W/O

W/S

WS

WITH

WITHOUT

WP

VESTIBULEVEST

VR

VS

WHD

VP

W

VDT

VA

VD

VDM

V

TWISTED PAIR

UNINTERRUPTIBLE POWER SUPPLY

WATT TRANSDUCER/TWISTED

SWITCHBOARD

TIME DELAY ON ENERGIZATION

CURRENT TRANSDUCER

TELEPHONE BACKBOARD

TO BE DETERMINED

TIME DELAY ON DEENERGIZATION

TEMPERATURE

UNLESS OTHERWISE NOTED

UNIT HEATER

UNDERGROUND

UTILITY BLDG TRAY

VOLTAGE TRANSDUCER/TELEVISION

TELEPHONE/POWER POLE

TOP OF BOX

TRANSFORMER T1-T2

TECHNICAL/TRAY/TRANSFORMER

SYNCHROSCOPE

SYMMETRICAL

SWITCHGEAR

UNIT SUBSTATION

UNIT VENTILATOR

UTILITY MANAGEMENT SYSTEM

TWSP

UPS

UON

UMS

US

UV

UH

TYP

UBT

USER BOXUB

UG

TYPICAL

UTILITY U

TVCN

TOB

TW

TV

TP

TBD

TEL

TDOD

TDOE

TERM

TEMP

TERMINAL

TELEPHONE

SYN

SYS

TA

T1/T2

TB

SYSTEM

T

SW

SYMM

SWGR

SWBD

SWITCH

UNSECURED LOCAL AREA NETWORKULAN

LAN LOCAL AREA NETWORK

FSB FACILITY SERVICE BRANCH

VBN VIDEO BROADBAND NETWORK

PROVIDEFURNISH, INSTALL, AND CONNECT

COMPLETE.

ABOVE COUNTER TOPACT

AUTHORITY HAVING JURISDICTION

ARC FAULT CIRCUIT INTERRUPTERAFCI

AHS

GROUND FAULT CIRCUIT INTERRUPTGFCI

E-002

ONE LINE SYMBOLSCONT'D

ELECTRICALABBREVIATIONS

STATUS:

DESIGNER:

PROJECT INFORMATION

DESCRIPTION

REVISIONS:

REV.

SHEET TITLE

PROJECT #:

DATE

DRAWN BY:ENGINEERED BY:

CHECKED BY:

EntCadStd-v2.1 3/10/15

WORK # :

DRAWING NUMBER

CONSTRUCTION

KEY PLAN:

PROJ MGR:

LOCATION:

APPROVALS:

DESIGN MGR:

ISSUE FOR

IFC

US-34 & US-18REPLACEMENT

PROJECT

10/17/17

80046953

4630141873

SUTTHARA L.SUTTHARA L.

DAVE K.

MARK McKINNEY

FT. BELVOIR, VA7900 BLOCK, TELEGRAPH ROAD

Page 4: US-34 & US-18 REPLACEMENT PROJECT€¦ · drawing index safety xpersonal protective equipment shall be worn as required in all applicable areas. limit access by unapproved personnel

PROJECT NORTH

E-101

ELECTRICALSITE PLAN

DEMOLITION

GENERAL NOTES:1. REFER TO SHEETS E-001 & E-002 FOR SYMBOLS, ABBREVIATIONS, AND

GENERAL NOTES.

2. UNLESS OTHERWISE NOTED, ALL WORK SHALL BE IN ACCORDANCETO NEC 2017 AND SPECIFICATION 2000.

3. CONTRACTOR TO FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TOSTARTING CONSTRUCTION AND NOTIFY FSB DESIGN PROJECTMANAGER IN WRITING WHERE DISCREPANCIES OCCUR.

4. ALL WORK SHALL BE PHASED TO MINIMIZE OPERATIONAL IMPACT.PHASING PLAN SHALL BE SUBMITTED FOR REVIEW AND APPROVAL.SEE SHEET G-001 FOR RECOMMENDED PHASING PLAN.

5. ONLY APPROVED MATERIALS ARE USED ON THIS PROJECT. ALLOUTDOOR ELECTRICAL EQUIPMENT ENCLOSURES ARE NEMA 3RRATED. PRODUCT CUT SHEET SUBMITTALS ARE REQUIRED FORREVIEW/APPROVAL.

6. FEEDER CONDUIT ROUTING PATHS SHOWN ARE FOR ILLUSTRATIONONLY. FIELD VERIFICATION IS REQUIRED FOR EXACT FEEDER ROUTINGPATHS.

7. REFER TO ELECTRICAL ONE-LINE DIAGRAM FOR ALL FEEDER CABLEAND CONDUIT SIZES.

8. ENSURE POWER OUTAGE AUTHORIZATION IS OBTAINED PRIOR TOSHUTTING DOWN POWER. POWER OUTAGE REQUEST SHALL BESUBMITTED TO PROJECT MANAGER AT LEAST ONE WEEK IN ADVANCE.

SCALE: REF.

ELECTRICAL SITE PLAN - DEMOLITION1E-101 201 1" = 64'-0"

PRIOR TO DEMOLISHING ANY ELECTRICAL EQUIPMENT, CONTRACTORSHALL PROVIDE A TEMPORARY GENERATOR, FUEL, AND CABLES TO POWERALL EXISTING LOADS FOR ENTIRE WORK DURATION. A PHASING PLANSUBMITTAL IS ALSO REQUIRED FOR REVIEW/APPROVAL. RECOMMENDEDPHASING PLAN IS SHOWN ON SHEET G-001.

DEMOLISH EXISTING SWITCHBOARD WITH ASSOCIATED FEEDER CABLESCONNECTED FROM SWITCHBOARD TO PAD MOUNTED TRANSFORMER.ABANDON EXISTING FEEDER CONDUIT IN PLACE.

DEMOLISH EXISTING PAD MOUNTED TRANSFORMER. RETAIN EXISTINGFEEDER CONDUIT & CABLES FROM TRANSFORMER TO LOAD INTERRUPTERSWITCH FOR REUSE.

DEMOLISH EXISTING PAD MOUNTED LOAD INTERRUPTER SWITCH. RETAINEXISTING FEEDER CONDUIT & CABLES FOR REUSE.

DEMOLISH EXISTING GENERATOR RECEPTACLE WITH ASSOCIATED FEEDERCABLES AND CONDUIT.

DEMOLITION KEY NOTES:1

2

2

STATUS:

DESIGNER:

PROJECT INFORMATION

DESCRIPTION

REVISIONS:

REV.

SHEET TITLE

PROJECT #:

DATE

DRAWN BY:ENGINEERED BY:

CHECKED BY:

EntCadStd-v2.1 3/10/15

WORK # :

DRAWING NUMBER

CONSTRUCTION

KEY PLAN:

PROJ MGR:

LOCATION:

APPROVALS:

DESIGN MGR:

ISSUE FOR

IFC

US-34 & US-18REPLACEMENT

PROJECT

10/17/17

80046953

4630141873

SUTTHARA L.SUTTHARA L.

DAVE K.

MARK McKINNEY

FT. BELVOIR, VA7900 BLOCK, TELEGRAPH ROAD

3

5

3

2

SEE DETAIL 2BELOW FORDEMOLITION

SEE DETAIL 3BELOW FORDEMOLITION

SCALE: REF. 3/32" = 1'-0"

US-34 DEMOLITION2E-101 SCALE: REF. 3/32" = 1'-0"

US-18 - DEMOLITION3E-101 201

SEE DETAIL 4BELOW FORDEMOLITION

4

SCALE: REF. 3/32" = 1'-0"

US-18 - DEMOLITION 4E-101 201

4

3

4

5

1

1

11

1

1

1

Page 5: US-34 & US-18 REPLACEMENT PROJECT€¦ · drawing index safety xpersonal protective equipment shall be worn as required in all applicable areas. limit access by unapproved personnel

PROJECT NORTH

E-201

ELECTRICALSITE PLAN

NEW WORK

GENERAL NOTES:1. REFER TO SHEETS E-001 & E-002 FOR SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES.

2. UNLESS OTHERWISE NOTED, ALL WORK SHALL BE IN ACCORDANCE TO NEC 2017 ANDSPECIFICATION 2000.

3. CONTRACTOR TO FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO STARTINGCONSTRUCTION AND NOTIFY FSB DESIGN PROJECT MANAGER IN WRITING WHEREDISCREPANCIES OCCUR.

4. ALL WORK SHALL BE PHASED TO MINIMIZE OPERATIONAL IMPACT. PHASING PLAN SHALLBE SUBMITTED FOR REVIEW AND APPROVAL. SEE SHEET G-001 FOR RECOMMENDEDPHASING PLAN.

5. ONLY APPROVED MATERIALS ARE USED ON THIS PROJECT. ALL OUTDOOR ELECTRICALEQUIPMENT ENCLOSURES ARE NEMA 3R RATED. PRODUCT CUT SHEETS ARE REQUIREDTO SUBMIT FOR REVIEW/APPROVAL.

6. FEEDER CONDUIT ROUTING PATHS SHOWN ARE FOR ILLUSTRATION ONLY. FIELDVERIFICATION IS REQUIRED FOR EXACT FEEDER CONDUIT ROUTING PATHS.

7. REFER TO ELECTRICAL ONE-LINE DIAGRAM FOR ALL FEEDER CABLE AND CONDUIT SIZES.

8. ENSURE POWER OUTAGE AUTHORIZATION IS OBTAINED PRIOR TO SHUTTING DOWNPOWER. POWER OUTAGE REQUEST SHALL BE SUBMITTED TO PROJECT MANAGER ATLEAST ONE WEEK IN ADVANCE.

SCALE: REF.

ELECTRICAL SITE PLAN - NEW WORK1E-201 1/64" = 1'-0"

CONSTRUCT A NEW 2-WAY DUCT BANK FROM EXISTING MANHOLE EMH5-09 TO A NEW PULLBOX OUTSIDE BUILDING 2851. PROVIDE PULL A STRING IN SPARE CONDUIT. SEE DETAIL 5 ONSHEET E-501 FOR MORE INFORMATION.

PROVIDE AND INSTALL (2) NEW NEMA 4 RATED ELECTRICAL PULL BOXES, SIZE 24" X 24" X 20".

PROVIDE AND INSTALL (3) #4/0 5KV SHIELDED CABLES & (1) #4 GND IN A EXISTING 4" SPARECONDUIT FROM WTA TO US-18 SWITCH VIA NEW PULL BOX AND NEW DUCT BANK. NEW FEEDERCABLES SHALL BE TYPE EPR WITH 133% INSULATION.

PROVIDE NEW NEMA 3R RATED ENCLOSURE LOAD SELECTOR INTERRUPTER SWITCH ASSEMBLY,S&C PME-6 OR APPROVED EQUAL.

PROVIDE AND INSTALL A NEMA 3R RATED ENCLOSURE, PAD MOUNTED TRANSFORMER, 300KVA,4160V PRIMARY, 480/277V SECONDARY, MINERAL OIL FILLED, COPPER WINDING, ABBMANUFACTURE OR APPROVED EQUAL.

NEMA 3R RATED ENCLOSURE 400A, 480/277V, 3PH, 4W, NON-FUSE MANUAL TRANSFER SWITCHWITH MALE CAM-LOKS ON THE RIGHT HAND SIDE, PSI CONTROL SOLUTIONS MODELSTS400N3RNF4CR OR APPROVED EQUAL.

PROVIDE AND INSTALL NEW NEMA 3R RATED ENCLOSURE SWITCHBOARD, EATON PRL4B ORAPPROVED EQUAL, 400A, 480/277V, 3PH, 4W PANEBOARD. LABEL NEW PANEL BOARD ASSHOWN.

PROVIDE AND INSTALL (4) 600 KCMIL + (1) #2 GND IN 3.5" RGS CONDUIT.

NEW WORK KEY NOTES:1

2

STATUS:

DESIGNER:

PROJECT INFORMATION

DESCRIPTION

REVISIONS:

REV.

SHEET TITLE

PROJECT #:

DATE

DRAWN BY:ENGINEERED BY:

CHECKED BY:

EntCadStd-v2.1 3/10/15

WORK # :

DRAWING NUMBER

CONSTRUCTION

KEY PLAN:

PROJ MGR:

LOCATION:

APPROVALS:

DESIGN MGR:

ISSUE FOR

IFC

US-34 & US-18REPLACEMENT

PROJECT

10/17/17

80046953

4630141873

SUTTHARA L.SUTTHARA L.

DAVE K.

MARK McKINNEY

FT. BELVOIR, VA7900 BLOCK, TELEGRAPH ROAD

1

3

SEE DETAIL 2BELOW FORNEW WORK

SEE DETAIL 3BELOW FORNEW WORK

3 3 3 3

3

4

5

6

32

7

75

8

7

SCALE: REF. 3/32" = 1'-0"

US-34 - NEW WORK2E-201 SCALE: REF. 3/32" = 1'-0"

US-18 - NEW WORK3E-201

4

SCALE: REF. 1/8" = 1'-0"

US-18 - NEW WORK4E-201

4

8

SEE DETAIL 4BELOW FORNEW WORK

6

8

8

SEE SHEET E-202FOR NEW WORK

6

5

Page 6: US-34 & US-18 REPLACEMENT PROJECT€¦ · drawing index safety xpersonal protective equipment shall be worn as required in all applicable areas. limit access by unapproved personnel

SUBSTATION

SWGR BUILDING

CHILLER ROOM

ELECTRICAL

EQUIPMENT

AREA

SUBSTATION

SWGR BUILDING

GENERAL NOTES:1. REFER TO SHEETS E-001 & E-002 FOR SYMBOLS,

ABBREVIATIONS, AND GENERAL NOTES.

2. UNLESS OTHERWISE NOTED, ALL WORK SHALL BE INACCORDANCE TO NEC 2017 AND SPECIFICATION 2000.

3. CONTRACTOR TO FIELD VERIFY ALL EXISTINGCONDITIONS PRIOR TO STARTING CONSTRUCTION ANDNOTIFY FSB DESIGN PROJECT MANAGER IN WRITINGWHERE DISCREPANCIES OCCUR.

4. ALL WORK SHALL BE PHASED TO MINIMIZEOPERATIONAL IMPACT. PHASING PLAN SHALL BESUBMITTED FOR REVIEW AND APPROVAL. SEE SHEETG-001 FOR RECOMMENDED PHASING PLAN.

5. ONLY APPROVED MATERIALS ARE USED ON THISPROJECT. ALL OUTDOOR ELECTRICAL EQUIPMENTENCLOSURES ARE NEMA 3R RATED. PRODUCT CUTSHEETS ARE REQUIRED TO SUBMIT FORREVIEW/APPROVAL.

6. FEEDER CONDUIT ROUTING PATHS SHOWN ARE FORILLUSTRATION ONLY. FIELD VERIFICATION IS REQUIREDFOR EXACT FEEDER CONDUIT ROUTING PATHS.

7. REFER TO ELECTRICAL ONE-LINE DIAGRAM FOR ALLFEEDER CABLE AND CONDUIT SIZES.

8. ENSURE POWER OUTAGE AUTHORIZATION IS OBTAINEDPRIOR TO SHUTTING DOWN POWER. POWER OUTAGEREQUEST SHALL BE SUBMITTED TO PROJECT MANAGERAT LEAST ONE WEEK IN ADVANCE.

SCALE: REF. 1/8" = 1'-0"

ELECTRICAL FLOOR PLAN - NEW WORK1E-202

PROVIDE AND INSTALL (2) NEW NEMA 4 RATED ELECTRICALPULL BOXES, SIZE 24" X 24" X 20". SEE DETAIL 2 BELOW FORMORE INFORMATION.

PROVIDE AND INSTALL (3) #4/0 5KV SHIELDED CABLES & (1)#4 GND IN 4" EMT CONDUIT FROM THE NEWLY INSTALLEDPULL BOX OUTSIDE BUILDING 2851 TO WTA. NEW FEEDERCABLES SHALL BE TYPE EPR WITH 133% INSULATION.

CONDUIT PENETRATIONS SHALL BE SEALED USING HILTIFS-ONE INTUMESCENT FIRE STOP SEALANT. FIRE RATEDASSEMBLIES ARE IDENTIFIED ON STATION LIFE SAFETY PLAN.CONSULT WITH STATION ARCHITECT IF THERE IS ANYCONFUSION AS TO WHAT SHOULD BE DONE.

PATCH AND PAINT EXTERIOR WALL & CONDUIT TO MATCHEXISTING.

NEW WORK KEY NOTES:1

2

E-202

ELECTRICALFLOOR PLANNEW WORK

EXISTING 4" CONDUIT

1

2

EXISTING ELECTRICALMANHOLE EMH5-09

BU

ILD

ING

28

51

BU

ILD

ING

28

50

PROJECT NORTH

3

D11A

STATUS:

DESIGNER:

PROJECT INFORMATION

DESCRIPTION

REVISIONS:

REV.

SHEET TITLE

PROJECT #:

DATE

DRAWN BY:ENGINEERED BY:

CHECKED BY:

EntCadStd-v2.1 3/10/15

WORK # :

DRAWING NUMBER

CONSTRUCTION

KEY PLAN:

PROJ MGR:

LOCATION:

APPROVALS:

DESIGN MGR:

ISSUE FOR

IFC

US-34 & US-18REPLACEMENT

PROJECT

10/17/17

80046953

4630141873

SUTTHARA L.SUTTHARA L.

DAVE K.

MARK McKINNEY

FT. BELVOIR, VA7900 BLOCK, TELEGRAPH ROAD

3

3

SCALE: REF. 1/8" = 1'-0"

ELEVATION VIEW DETAILS2E-202

(1) 4" RGS CONDUITSWITH PULL STRING INA SPARE CONDUIT

(1) 4" EMT CONDUIT

BUILDING WALL

FLOOR SLAB 2-WAYDUCTBANK

TO EXISTINGELECTRICALMANHOLEEMH5-09

FASTEN CONDUIT TOMOUNTING SUPPORTPER NEC REQUIREMENT

PULL BOX SIZE24" X 24" X 20"NEMA 4

FINISHEDGRADE

EXISTING FLOOD LIGHT

4

4

3

(2) 4" RGS CONDUITS WITH PULLSTRING IN A SPARE CONDUIT

Page 7: US-34 & US-18 REPLACEMENT PROJECT€¦ · drawing index safety xpersonal protective equipment shall be worn as required in all applicable areas. limit access by unapproved personnel

E-501

ELECTRICAL SWITCHGEARELEVATION

GENERAL NOTES:1. UNLESS OTHERWISE NOTED, ALL WORK SHALL BE IN ACCORDANCE TO NEC 2017 AND

SPECIFICATION 2000.

2. CONTRACTOR TO FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO STARTINGCONSTRUCTION AND NOTIFY FSB DESIGN PROJECT MANAGER IN WRITING WHEREDISCREPANCIES OCCUR.

4. ALL WORK SHALL BE PHASED TO MINIMIZE OPERATIONAL IMPACT. PHASING PLAN SHALLBE SUBMITTED FOR REVIEW AND APPROVAL. SEE SHEET G-001 FOR RECOMMENDEDPHASING PLAN.

5. ONLY APPROVED MATERIALS ARE USED ON THIS PROJECT. ALL OUTDOOR ELECTRICALEQUIPMENT ENCLOSURES ARE NEMA 3R RATED. PRODUCT CUT SHEETS ARE REQUIREDTO SUBMIT FOR REVIEW/APPROVAL.

6. FEEDER CONDUIT ROUTING PATHS SHOWN ARE FOR ILLUSTRATION ONLY. FIELDVERIFICATION IS REQUIRED FOR EXACT FEEDER CONDUIT ROUTING PATHS.

7. REFER TO ELECTRICAL ONE-LINE DIAGRAM FOR ALL FEEDER CABLE AND CONDUIT SIZES.

8. ENSURE POWER OUTAGE AUTHORIZATION IS OBTAINED PRIOR TO SHUTTING DOWNPOWER. POWER OUTAGE REQUEST SHALL BE SUBMITTED TO PROJECT MANAGER ATLEAST ONE WEEK IN ADVANCE.

SCALE: REF.

WTB SWITCHGEAR - EXISTING1E-501 N.T.S

SCALE: REF.

WTA SWITCHGEAR - NEW WORK2E-501 N.T.S

PROVIDE A NEW PHENOLIC LABEL, 1/2" BLACK LETTERS ON WHITE BACKGROUND.

PRIOR TO ORDERING PANELBOARD, CONTRACTOR SHALL FIELD VERIFY ALL EXISTINGBREAKERS' HEIGHTS TO ENSURE EXISTING CABLES ARE LONG ENOUGH TO REACH UPTO THE NEW BREAKER POSITIONS IN THE NEW PANELBOARDS.

NEW WORK KEY NOTES:

STATUS:

DESIGNER:

PROJECT INFORMATION

DESCRIPTION

REVISIONS:

REV.

SHEET TITLE

PROJECT #:

DATE

DRAWN BY:ENGINEERED BY:

CHECKED BY:

EntCadStd-v2.1 3/10/15

WORK # :

DRAWING NUMBER

CONSTRUCTION

KEY PLAN:

PROJ MGR:

LOCATION:

APPROVALS:

DESIGN MGR:

ISSUE FOR

IFC

US-34 & US-18REPLACEMENT

PROJECT

10/17/17

80046953

4630141873

SUTTHARA L.SUTTHARA L.

DAVE K.

MARK McKINNEY

FT. BELVOIR, VA7900 BLOCK, TELEGRAPH ROAD

1

1

SCALE: REF.

SWITCHBOARD US-34 ELEVATION - NEW WORK3

E-501 N.T.S SCALE: REF.

SWITCHBOARD US-18 ELEVATION - NEW WORK4

E-501 N.T.S

22

2

2

2

2

SCALE: REF.

2-WAY ELECTRICAL DUCT BANK - NEW WORK5

E-501 N.T.S

Page 8: US-34 & US-18 REPLACEMENT PROJECT€¦ · drawing index safety xpersonal protective equipment shall be worn as required in all applicable areas. limit access by unapproved personnel

STATUS:

DESIGNER:

PROJECT INFORMATION

DESCRIPTION

REVISIONS:

REV.

SHEET TITLE

PROJECT #:

DATE

DRAWN BY:ENGINEERED BY:

CHECKED BY:

EntCadStd-v2.1 3/10/15

WORK # :

DRAWING NUMBER

CONSTRUCTION

KEY PLAN:

PROJ MGR:

LOCATION:

APPROVALS:

DESIGN MGR:

ISSUE FOR

IFC

US-34 & US-18REPLACEMENT

PROJECT

10/17/17

80046953

4630141873

SUTTHARA L.SUTTHARA L.

DAVE K.

MARK McKINNEY

FT. BELVOIR, VA7900 BLOCK, TELEGRAPH ROAD

E-601

PARTIAL ONE-LINE DIAGRAM

DEMOLITION

GENERAL NOTES:1. REFER TO SHEETS E-001 & E-002 FOR SYMBOLS,

ABBREVIATIONS, AND GENERAL NOTES.2. UNLESS OTHERWISE NOTED, ALL WORK SHALL BE IN

ACCORDANCE TO NEC 2017 AND SPECIFICATION 2000.3. CONTRACTOR TO FIELD VERIFY ALL EXISTING CONDITIONS

PRIOR TO STARTING CONSTRUCTION AND NOTIFY FSB DESIGNPROJECT MANAGER IN WRITING WHERE DISCREPANCIESOCCUR.

4. ALL WORK SHALL BE PHASED TO MINIMIZE OPERATIONALIMPACT. PHASING PLAN SHALL BE SUBMITTED FOR REVIEWAND APPROVAL. SEE SHEET G-001 FOR RECOMMENDEDPHASING PLAN.

5. ONLY APPROVED MATERIALS ARE USED ON THIS PROJECT.ALL OUTDOOR ELECTRICAL EQUIPMENT ENCLOSURES ARENEMA 4X RATED. PAD MOUNTED TRANSFORMER ENCLOSUREIS NEMA 3R. PRODUCT CUT SHEETS ARE REQUIRED TO SUBMITFOR REVIEW/APPROVAL.

6. ENSURE POWER OUTAGE AUTHORIZATION IS OBTAINED PRIORTO SHUTTING DOWN POWER. POWER OUTAGE REQUESTSHALL BE SUBMITTED TO PROJECT MANAGER AT LEAST ONEWEEK IN ADVANCE.

DEMOLISH EXISTING SWITCHBOARD WITH ASSOCIATED FEEDERCABLES CONNECTED FROM SWITCHBOARD TO PAD MOUNTEDTRANSFORMER. ABANDON EXISTING FEEDER CONDUIT IN PLACE.

DEMOLISH EXISTING PAD MOUNTED TRANSFORMER. RETAINEXISTING FEEDER CONDUIT & CABLES FROM TRANSFORMER TOLOAD INTERRUPTER SWITCH FOR REUSE.

DEMOLISH EXISTING PAD MOUNTED LOAD INTERRUPTER SWITCH.RETAIN EXISTING FEEDER CONDUIT & CABLES FOR REUSE.

DEMOLISH EXISTING GENERATOR RECEPTACLE WITH ASSOCIATEDFEEDER CABLES AND CONDUIT.

DEMOLITION KEY NOTES:

1

SCALE: REF.

PARTIAL ONE-LINE DIAGRAM - DEMOLITION1E-601 E-101 N.T.S

2

1

2

3

3 3

1

2

4

4

Page 9: US-34 & US-18 REPLACEMENT PROJECT€¦ · drawing index safety xpersonal protective equipment shall be worn as required in all applicable areas. limit access by unapproved personnel

STATUS:

DESIGNER:

PROJECT INFORMATION

DESCRIPTION

REVISIONS:

REV.

SHEET TITLE

PROJECT #:

DATE

DRAWN BY:ENGINEERED BY:

CHECKED BY:

EntCadStd-v2.1 3/10/15

WORK # :

DRAWING NUMBER

CONSTRUCTION

KEY PLAN:

PROJ MGR:

LOCATION:

APPROVALS:

DESIGN MGR:

ISSUE FOR

IFC

US-34 & US-18REPLACEMENT

PROJECT

10/17/17

80046953

4630141873

SUTTHARA L.SUTTHARA L.

DAVE K.

MARK McKINNEY

FT. BELVOIR, VA7900 BLOCK, TELEGRAPH ROAD

E-602

PARTIAL ONE-LINE DIAGRAM

NEW WORK

GENERAL NOTES:1. REFER TO SHEETS E-001 & E-002 FOR SYMBOLS,

ABBREVIATIONS, AND GENERAL NOTES.2. UNLESS OTHERWISE NOTED, ALL WORK SHALL BE IN

ACCORDANCE TO NEC 2017 AND SPECIFICATION 2000.3. CONTRACTOR TO FIELD VERIFY ALL EXISTING CONDITIONS

PRIOR TO STARTING CONSTRUCTION AND NOTIFY FSB DESIGNPROJECT MANAGER IN WRITING WHERE DISCREPANCIESOCCUR.

4. ALL WORK SHALL BE PHASED TO MINIMIZE OPERATIONALIMPACT. PHASING PLAN SHALL BE SUBMITTED FOR REVIEWAND APPROVAL. SEE SHEET G-001 FOR RECOMMENDEDPHASING PLAN.

5. ONLY APPROVED MATERIALS ARE USED ON THIS PROJECT.ALL OUTDOOR ELECTRICAL EQUIPMENT ENCLOSURES ARENEMA 3R RATED. PRODUCT CUT SHEETS ARE REQUIRED TOSUBMIT FOR REVIEW/APPROVAL.

6. FEEDER CONDUIT ROUTING PATHS SHOWN ARE FORILLUSTRATION ONLY. FIELD VERIFICATION IS REQUIRED FOREXACT FEEDER CONDUIT ROUTING PATHS.

7. REFER TO ELECTRICAL ONE-LINE DIAGRAM FOR ALL FEEDERCABLE AND CONDUIT SIZES.

8. ENSURE POWER OUTAGE AUTHORIZATION IS OBTAINED PRIORTO SHUTTING DOWN POWER. POWER OUTAGE REQUESTSHALL BE SUBMITTED TO PROJECT MANAGER AT LEAST ONEWEEK IN ADVANCE.

(3) #4/0 5KV SHIELDED CABLES & (1) #4 GND IN EXISTINGSPARE 4" CONDUIT FROM WTA TO US-18 SWITCH.

PAD MOUNTED TRANSFORMER, 300KVA, 4160V PRIMARY,480/277V SECONDARY, OIL FILLED, COPPER WINDING.

NEMA 3R RATED ENCLOSURE 400A, 480/277V, 3PH, 4W,MANUAL TRANSFER SWITCH WITH MALE CAM-LOKS ON THERIGHT HAND SIDE.

NEMA 3R RATED ENCLOSURE SWITCHBOARD, 480/277V, 3PH,4W. LABEL NEW PANEL BOARD AS SHOWN.

(4) 600 KCMIL + (1) #2 GND IN 3.5" RGS CONDUIT.

ADJUST THIS BREAKER SETTINGS TO MATCH BREAKERWTB-D6A.

PROVIDE AND INSTALL NEW 5KV SWITCH, 200A CONTINUOUS& LOAD INTERRUPTING OUTDOOR RATED ENCLOSURE, S&CPME-6 OR APPROVED EQUAL.

PROVIDE AND INSTALL KIRK-KEY INTERLOCK TO PREVENTACCIDENTALLY PARALLELING THE TWO 5KV POWERSOURCES. ONLY 3 KEYS ARE HELD IN POSITION.

PROVIDE (10) 4/0 AWG FLEXIBLE CABLES, TYPE DLO, AT 100FEET EACH WITH FEMALE CAM-LOK AT ONE END & MALECAM-LOK AT THE OTHER END. ALSO, PROVIDE (10) 4/0 AWGPIGTAILS, TYPE DLO, AT 3 FEET EACH WITH CAM-LOK FEMALEAT ONE END & CRIMPED CABLE LUG AT THE OTHER END. SEEDETAIL 2 BELOW. ALL CABLES SHALL BE PROPERLY COLORCODED FOR 480/277V SYSTEM (BROWN, ORANGE, YELLOW,GRAY, & GREEN)

NOT IN SCOPE. PORTABLE GENERATOR IS SHOWN FORREFERENCE INFORMATION ONLY.

NEW WORK KEY NOTES:

1

SCALE: REF.

PARTIAL ONE-LINE DIAGRAM - NEW WORK1E-602 201 N.T.S

2

2

1

3

4

4

3

5

5

5

2

4

3

5

5

6

10

1

7

6

8

88

9

7 7

8

9

9

SCALE: REF.

GENERATOR POWER CABLES2E-602 201 N.T.S

9

9

10

10

8

10