Installation Instructions USB-to-Data Highway Plus Cable Catalog Number 1784-U2DHP About the Cable The 1784-U2DHP USB-to-Data Highway Plus Cable lets you connect a computer to a Data Highway Plus (DH+) network via an unused USB port on the computer. You can also use the cable to connect the computer to PLC-5 processors (except for Classic PLC-5 processors, such as PLC-5/10, PLC-5/12, PLC-5/15, and PLC-5/25) or SLC 5/04 processors. Communication on the DH+ link requires the RSLinx Classic software DF1 serial 1770-KF2/1785-KE drive. Topic Page Important User Information 2 Environment and Enclosure 3 Install the Cable 5 Configure the DH+ Node Address 11 Consider the Traffic Analyzer Software 11 About Using Multiple Cables 12 Status Indicators 13 Specifications 15 Additional Resources 18

Upload: truongmien

Post on 13-Apr-2018

215 views

Category:

Documents


2 download

TRANSCRIPT

  • Installation Instructions

    USB-to-Data Highway Plus CableCatalog Number 1784-U2DHP

    About the CableThe 1784-U2DHP USB-to-Data Highway Plus Cable lets you connect a computer to a Data Highway Plus (DH+) network via an unused USB port on the computer. You can also use the cable to connect the computer to PLC-5 processors (except for Classic PLC-5 processors, such as PLC-5/10, PLC-5/12, PLC-5/15, and PLC-5/25) or SLC 5/04 processors. Communication on the DH+ link requires the RSLinx Classic software DF1 serial 1770-KF2/1785-KE drive.

    Topic Page

    Important User Information 2

    Environment and Enclosure 3

    Install the Cable 5

    Configure the DH+ Node Address 11

    Consider the Traffic Analyzer Software 11

    About Using Multiple Cables 12

    Status Indicators 13

    Specifications 15

    Additional Resources 18

  • 2 USB-to-Data Highway Plus Cable

    Important User Information

    Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.

    In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.

    The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.

    No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.

    Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.

    Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

    WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

    ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.

    SHOCK HAZARD: Labels may be on or inside the equipment, for example, drive or motor, to alert people that dangerous voltage may be present.

    BURN HAZARD: Labels may be on or inside the equipment, for example, drive or motor, to alert people that surfaces may reach dangerous temperatures.

    IMPORTANT Identifies information that is critical for successful application and understanding of the product.

    Rockwell Automation Publication 1784-IN045C-EN-P - May 2010

    http://literature.rockwellautomation.com/idc/groups/literature/documents/in/sgi-in001_-en-p.pdfhttp://www.rockwellautomation.com/literature/

  • USB-to-Data Highway Plus Cable 3

    Environment and Enclosure

    Preventing Electrostatic Discharge

    ATTENTION: This equipment is intended for use in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.

    This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated disturbances.

    This equipment is supplied as enclosed equipment. It should not require additional system enclosure when used in locations consistent with the enclosure type ratings stated in the Specifications section of this publication. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings, beyond what this product provides, that are required to comply with certain product safety certifications.

    In addition to this publication, see:

    Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication 1770-4.1, for additional installation requirements. NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure.

    ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: Touch a grounded object to discharge potential static. Do not touch connectors or pins on component boards. Store the equipment in appropriate static-safe packaging when not

    in use.

    Rockwell Automation Publication 1784-IN045C-EN-P - May 2010

    http://literature.rockwellautomation.com/idc/groups/literature/documents/in/1770-in041_-en-p.pdf

  • 4 USB-to-Data Highway Plus Cable

    At the end of its life, this equipment should be collected separately from any unsorted municipal waste.

    The 1784-U2DHP cable replaces both the 1784-PCMK communication card and 1784-PCM6 cable (for computers without PCMCIA slots).

    IMPORTANT The cable will not connect to Classic PLC-5 processors, such as PLC-5/10, PLC-5/12, PLC-5/15, and PLC-5/25, without an adapter. An adapter can be purchased separately from third-party companies.

    To comply with the CE Low Voltage Directive (LVD), this equipment must be powered from a source compliant with safety extra low voltage (SELV) or protected extra low voltage (PELV).

    USB Cable0.61 m (2 ft)

    8-pin DIN Cable2.44 m (8 ft)

    Communication Rate Switch

    Status Indicators

    Rockwell Automation Publication 1784-IN045C-EN-P - May 2010

  • USB-to-Data Highway Plus Cable 5

    The cable operates at DH+ communication rates of 57.6 Kbps, 115.2 Kbps, and 230.4 Kbps.

    The 1784-U2DHP cable supports these DH+ network cable lengths.

    Install the CableFollow the procedures on the following pages to install the cable.

    Obtain the Device Driver for the CableFollow these steps to download the device driver for the cable.

    1. Visit http://www.rockwellautomation.com/support/pccards.

    2. Click the 1784_u2dhp.inf file.

    3. Save the file to a directory on the computer on which you want to install the cable.

    IMPORTANT The DH+ communication rate is read only when power is applied. To change the communication rate, you must disconnect the cable from the USB port, use the Communication Rate switch to change the communication rate setting, then reconnect the cable to the USB port.

    DH+ Communication Rate Max. DH+ Network Cable Length

    57.6 Kbps 3048 m (10,000 ft)

    115.2 Kbps 1524 m (5000 ft)

    230.4 Kbps 762 m (2500 ft)

    IMPORTANT If RSLinx Classic software, version 2.53 or later, is installed on the computer, the device driver is already installed on the computer. Skip this section.

    Rockwell Automation Publication 1784-IN045C-EN-P - May 2010

    http://www.rockwellautomation.com/support/pccards

  • 6 USB-to-Data Highway Plus Cable

    Connect and Configure the Cable

    1. Insert the end of the cable having the USB connector into an unused USB port on a computer.

    The Found New Hardware wizard appears.

    If you do not see the Found New Hardware wizard, proceed tostep 9. Otherwise, continue with the next step.

    2. Select No, not this time and click Next.

    3. Select Install from a list or specific location and click Next.

    4. Select Search for the best driver.

    5. Check only the Include this location checkbox.

    6. Browse to the location where you saved the 1784_u2dhp.inf file and click OK.

    7. Click Next.

    8. Click Finish.

    TIP If you do not see the Found New Hardware wizard, the drivers have already been installed. If RSLinx Classic software, version 2.53 or later, is installed on the computer, the device driver was installed at C:\Program Files\Rockwell Software\RSLINX\PnP_Drivers\1784-U2DHP.

    TIP If you see a Microsoft Windows error message that displayscode 10, disconnect the cable from the USB port, then reconnect the cable to the USB port, so that the Windows operating system recognizes the device.

    Rockwell Automation Publication 1784-IN045C-EN-P - May 2010

  • USB-to-Data Highway Plus Cable 7

    9. Insert the other end of the cable having the 8-pin mini DIN connector to a device on your Data Highway Plus network.

    10. Verify which computer COM port the cable is using.

    a. Right-click My Computer and choose Manage.b. Select Device Manager.c. Click the + to the left of Ports.d. Make note of the port (for example, COM3) for the 1784-U2DHP

    cable.

    Configure the RSLinx Classic Software Driver for the CableConfigure the cable driver for use with your DH+ networked device.

    ATTENTION: The USB cable is not to exceed 3.0 m (9.84 ft).

    TIP The operating system of the computer you are using assigns a COM port to the cable.

    USB Connector

    8-pin DIN Connector

    Rockwell Automation Publication 1784-IN045C-EN-P - May 2010

  • 8 USB-to-Data Highway Plus Cable

    RSLinx Classic Software, Version 2.52 and Earlier

    Do these steps to configure the cable device driver by using RSLinx Classic software, version 2.52 and earlier.

    1. Open RSLinx Classic software and then, from the Communication menu, choose Configure Drivers.

    2. From the Available Driver Types pull-down menu, choose RS-232 DF1 Devices.

    3. Click Add New.

    4. Enter a name for the driver you just added and click OK.

    The Configure RS-232 DF1 Devices dialog box appears.

    Rockwell Automation Publication 1784-IN045C-EN-P - May 2010

  • USB-to-Data Highway Plus Cable 9

    5. Enter configuration information in each field.

    6. Click OK.

    RSLinx Classic Software, Version 2.53 and Later

    Do these steps to configure the cable device driver by using RSLinx Classic software, version 2.53 and later.

    1. Open RSLinx Classic software and then ,from the Communication menu, choose Configure Drivers.

    2. From the Available Driver Types pull-down menu, choose 1784-U2DHP for DH+ devices.

    3. Click Add New.

    4. Enter a name for the driver you just added and then click OK.

    In this field Do this

    Comm Port Select the COM port you verified in step 10 on page 7.

    Device Select 1770-KF2/1785-KE/SCANport.

    Station Number (node address)

    Enter the DH+ Station Number for this cable. The defaultis 0.The 1784-U2DHP cable can use any DH+ network address from 0...77 octal. The first packet sent from RSLinx Classic software to the 1784-U2DHP cable sets the DH+ network address the first time that RSLinx Classic software communicates through the 1784-U2DHP cable after power is applied. See Configure the DH+ Node Address on page 11.

    Error Checking Select CRC.

    Protocol Select Full Duplex.

    Baud Rate Not used.

    Parity Not used.

    Stop Bits Not used.

    Rockwell Automation Publication 1784-IN045C-EN-P - May 2010

  • 10 USB-to-Data Highway Plus Cable

    The Configure 1784-U2DHP dialog box appears.

    5. Enter configuration information in each field.

    6. Click OK.

    In this field Do this

    Comm Port Select the COM port you verified in step 10 on page 7.

    Station Number (node address)

    Enter the DH+ Station Number for this cable. The default is 0.The 1784-U2DHP cable can use any DH+ network address from 077 octal. The first packet sent from RSLinx Classic software to the 1784-U2DHP cable sets the DH+ network address the first time that RSLinx Classic software communicates through the 1784-U2DHP cable after power is applied. See Configure the DH+ Node Address on page 11.

    IMPORTANT Do not disconnect the cable without first using RSLinx Classic software to stop the driver. Disconnecting the cable without stopping the driver can shut down or cause RSLinx Classic software to become unresponsive.

    Rockwell Automation Publication 1784-IN045C-EN-P - May 2010

  • USB-to-Data Highway Plus Cable 11

    Configure the DH+ Node AddressThe cable DH+ node address (station number) is automatically set the first time the cable sees traffic from RSLinx software to the DH+ network.

    To change the node address of the cable, you must do these steps.

    1. In RSLinx Classic software, from the Communication menu, choose Configure Drivers.

    2. Choose the driver and click Stop.

    3. Click Configure.

    4. Enter the new node address and click OK.

    5. Cycle power to the cable by disconnecting the 1784-U2DHP cable USB connector from the USB port, then reconnecting it.

    6. Verify the driver is still selected and click Start.

    7. Initiate traffic from RSLinx Classic software to the DH+ network.a. From the Communication menu, choose RSWho.b. Choose the driver from the list.

    Consider the Traffic Analyzer SoftwareThe 1784-U2DHP cable is designed to work with Frontlines NetDecoder traffic analyzer software. For more information on Frontlines product, go to http://www.rockwellautomation.com/encompass or http://www.fte.com.

    Rockwell Automation Publication 1784-IN045C-EN-P - May 2010

    http://www.rockwellautomation.com/encompass/http://www.fte.com/

  • 12 USB-to-Data Highway Plus Cable

    About Using Multiple Cables

    Once you have installed the device driver for a 1784-U2DHP cable, a unique COM port will be created and associated with that module (for example, COM9). If you connect a different 1784-U2DHP cable to the same computer, a new COM port will be created and associated with the new cable(for example, COM10).

    Each time you connect a new 1784-U2DHP cable to the computer, refer tostep 10 on page 7 to determine the correct COM port for the additional cables.

    When you are using multiple 1784-U2DHP cables on the same computer, you must do one of these procedures.

    Change the RSLinx Classic software driver settings to specify the appropriate COM port for the connected cable.

    Configure multiple RSLinx Classic software drivers.

    Product DimensionsThe following illustration shows the product dimensions.

    USB Cable Length 0.61 m (2 ft)

    8-pin DIN Cable Length 2.44 m (8 ft)

    EnclosureLength: 7.62 cm (3 in.)Width: 5.08 cm (2 in.)Thickness: 2.54 cm (1 in.)

    Rockwell Automation Publication 1784-IN045C-EN-P - May 2010

  • USB-to-Data Highway Plus Cable 13

    Status IndicatorsThe following table describes the cable status indicators.

    Cable Status Indicators

    Indicator State Description

    USB Solid green The cable is configured, but no network traffic is present.

    Blinking green Network traffic is present.

    Off Unable to transfer data. Disconnected from host. In one of the following states:

    Default Powered Address Suspend

    Power Solid green The cable is powered.

    Off No power to the cable.

    DH+ NetworkPower

    USB

    Rockwell Automation Publication 1784-IN045C-EN-P - May 2010

  • 14 USB-to-Data Highway Plus Cable

    DH+ Network Off Node address not present.

    Blinking green Not connected to the DH+ network.Incorrect DH+ communication rate selected.Break or short in wiring.

    Solid green Communicating with the DH+ network.

    Blinking red Duplicate node detected.

    Solid red Internal diagnostic test failed.

    Cable Status Indicators

    Indicator State Description

    Rockwell Automation Publication 1784-IN045C-EN-P - May 2010

  • USB-to-Data Highway Plus Cable 15

    Specifications

    Technical Specifications - 1784-U2DHP

    Attribute Value

    Enclosure type rating Meets IP30

    Power dissipation, max 1.575 W max

    Supply voltage 5.00V DC5.25V DC, max

    Supply current 125 mA

    Power consumption, max 1.575 W

    Isolation voltage 30V (continuous), Basic Insulation TypeDH+ to USB, Type tested at 500V AC for 60 s

    Wiring category 2 - on communication ports(1)

    (1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

    Rockwell Automation Publication 1784-IN045C-EN-P - May 2010

    http://literature.rockwellautomation.com/idc/groups/literature/documents/in/1770-in041_-en-p.pdf

  • 16 USB-to-Data Highway Plus Cable

    Environmental Specifications - 1784-U2DHP

    Attribute Value

    Temperature, operatingIEC 60068-2-1 (Test Ad, Operating Cold),IEC 60068-2-2 (Test Bd, Operating Dry Heat),IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

    055 C (32131 F)

    Temperature, nonoperatingIEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

    -1085 C (14185 F)

    Relative humidityIEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

    595% noncondensing

    Shock, nonoperatingIEC 60068-2-27 (Test Ed, Unpackaged Shock)

    1000 mm (3.28 ft)

    EmissionsCISPR 11

    Group 1, Class A

    ESD immunityIEC 61000-4-2

    8 kV air discharges

    Radiated RF immunityIEC 61000-4-3

    10V/m with 1 kHz sine-wave 80% AM from 802000 MHz10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz10V/m with 1 kHz sine-wave 80% AM from 20002700 MHz

    Rockwell Automation Publication 1784-IN045C-EN-P - May 2010

  • USB-to-Data Highway Plus Cable 17

    EFT/B immunityIEC 61000-4-4

    2 kV at 5 kHz on DH+ port

    Surge transient immunityIEC 61000-4-5

    2 kV line-earth (CM) on DH+ port

    Conducted RF immunityIEC 61000-4-6

    10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on DH+ port

    Certifications - 1784-U2DHP

    Certification(1) Value

    c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.

    CE European Union 2004/108/EC EMC Directive, compliant with:EN 61326; Meas./Control/Lab., Industrial RequirementsEN 61000-6-2; Industrial ImmunityEN 61000-6-4; Industrial EmissionsEN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

    C-Tick AS/NZS CISPR 11; Industrial Emissions

    (1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

    Environmental Specifications - 1784-U2DHP

    Attribute Value

    Rockwell Automation Publication 1784-IN045C-EN-P - May 2010

    http://www.ab.com/

  • 18 USB-to-Data Highway Plus Cable

    Additional ResourcesThese documents contain additional information concerning related Rockwell Automation products.

    Resource Description

    Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1

    Provides general guidelines for installing a Rockwell Automation industrial system.

    Product Certifications website, http://www.ab.com

    Provides declarations of conformity, certificates, and other certification details.

    Rockwell Automation Publication 1784-IN045C-EN-P - May 2010

    http://literature.rockwellautomation.com/idc/groups/literature/documents/in/1770-in041_-en-p.pdfhttp://www.ab.com

  • USB-to-Data Highway Plus Cable 19

    Notes:

    Rockwell Automation Publication 1784-IN045C-EN-P - May 2010

  • Rockwell Automation Support

    Rockwell Otomasyon Ticaret A.., Kar Plaza Merkezi E Blok Kat:6 34752 erenky, stanbul, Tel: +90 (216) 5698400

    Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.

    For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/.

    Installation AssistanceIf you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running.

    New Product Satisfaction ReturnRockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.

    Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature,

    United States or Canada 1.440.646.3434

    Outside United States or Canada

    Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell Automation representative.

    United StatesContact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process.

    Outside United States Please contact your local Rockwell Automation representative for the return procedure.

    Publication 1784-IN045C-EN-P - May 2010 PN-76634

    Allen-Bradley, Rockwell Software, Rockwell Automation, Data Highway Plus, RSLinx Classic, PLC-5, SLC, and TechConnect are trademarks of Rockwell Automation, Inc.

    Trademarks not belonging to Rockwell Automation are property of their respective companies.

    Supersedes Publication 1784-IN045B-EN-P - March 2009 Copyright 2010 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

    http://www.rockwellautomation.com/support/http://www.rockwellautomation.com/support/http://www.rockwellautomation.com/support/http://www.rockwellautomation.com/support/http://www.rockwellautomation.com/locations/http://www.rockwellautomation.com/support/americas/phone_en.htmlhttp://www.rockwellautomation.com/literature/

    1784-IN045C-EN-P, USB-to-Data Highway Plus Cable Installation InstructionsAbout the Cable

    Important User InformationEnvironment and EnclosurePreventing Electrostatic Discharge

    Install the CableObtain the Device Driver for the CableConnect and Configure the CableConfigure the RSLinx Classic Software Driver for the Cable

    Configure the DH+ Node AddressConsider the Traffic Analyzer SoftwareAbout Using Multiple CablesProduct Dimensions

    Status IndicatorsSpecificationsAdditional ResourcesBack Cover

    /ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /CropGrayImages true /GrayImageMinResolution 300 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Average /GrayImageResolution 300 /GrayImageDepth 8 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 2.00000 /EncodeGrayImages true /GrayImageFilter /FlateEncode /AutoFilterGrayImages false /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /CropMonoImages true /MonoImageMinResolution 1200 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Average /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects false /CheckCompliance [ /None ] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile (None) /PDFXOutputConditionIdentifier () /PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped /False

    /CreateJDFFile false /Description > /Namespace [ (Adobe) (Common) (1.0) ] /OtherNamespaces [ > /FormElements false /GenerateStructure true /IncludeBookmarks false /IncludeHyperlinks false /IncludeInteractive false /IncludeLayers false /IncludeProfiles true /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe) (CreativeSuite) (2.0) ] /PDFXOutputIntentProfileSelector /NA /PreserveEditing true /UntaggedCMYKHandling /LeaveUntagged /UntaggedRGBHandling /LeaveUntagged /UseDocumentBleed false >> ]>> setdistillerparams> setpagedevice

    Introduction_Catagory Types

    This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards. It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printing.Find your publication type in the first section below. Use the assigned Printing Category information to determine the standard print specifications for that document type. The Printing Categories are defined below the Publication Type section. Note there may be slightly different print specifications for the categories, depending on the region (EMEA or Americas).For more information on Global Sales and Marketing Printing Standards, see publication RA-CO004 in DocMan.

    Publication Type and Print Category

    Publication TypeOff Set Print Category Spec. (See table below)JIT Spec. (See table below)DescriptionOrder MinOrder MaxLife Cycle Usage / Release Option

    ADNA - PuttmanNAAdvertisement Reprint ColourNANAPresale / Internal

    APA3D2Application Solution or Customer Success Story5100Presale / External

    ARNANAArticle/Editorial/BylineNANAPresale / Internal

    /News Release (press releases should not be checked into DocMan or printed)

    ATB3, B4D5Application Techniques5100Presale / External

    BRA2 Primary, A1NABrochures5100Presale / External

    CAC2 Primary, C1NACatalogue150Presale / External

    CGNANACatalogue Guide150Presale / External

    CLNANACollection550Presale / External

    COA5, A6, A9D5Company Confidential InformationNANANA / Confidential

    CPE-onlyE-only, D5Competitive Information550NA / Confidential

    DCE-onlyE-onlyDiscount SchedulesNANAPresale / Internal

    DIA1, A3NADirect Mail5100Presale / Internal

    DMNANAProduct Demo550Presale / Internal

    DSB3D5Dimensions Sheet15Post / External

    DUB3D5Document Update15Post / External

    GRB2D6Getting Results15Post / External

    INB3D5Installation instructions15Post / External

    LMNANALaunch KitMaterials550Presale / Internal

    PCB3D5Packaging Contents

    PLE-only Primary, B3E-onlyPrice List550Presale / Internal

    PMB2D6Programming Manual15Post / External

    PPA3D1Product Profile NOTE: Application Solutions are to be assigned the AP pub type.5100Presale / External

    QRB2 Primary, B3, B5D5, D6Quick Reference15Post / External

    QSB2 Primary, B3, B5D5, D6Quick Start15Post / External

    RMB2D5, D6Reference Manual15Post / External

    RNB3D5Release Notes15Post / External

    SGB1 Primary, B4D5, D6Selection Guide Colour5100Presale / External

    SGB2D5, D6Selection Guide B/W5100Presale / External

    SPA1, A2, A3, A4NAService ProfileSales Promotion NOTE: Service profiles are to be assigned the PP pub type.5100Presale / Internal

    SRB2, B3D5, D6Specification Rating Sheet5100Presale / External

    TDB2 Primary B3, B4, B5D5, D6Technical Data5100Presale / External

    TGB2, B3D6Troubleshooting Guide15Post / External

    UMB2 Primary, B4D6User Manual B/W15Post / External

    WDB3D5Wiring Diagrams / Dwgs15Post / Internal

    WPB3 Primary, B5D5White Paper5100Presale / External

    Pre-sale / MarketingAll paper in this category is White Brightness, 85% or better. Opacity 87% or better

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    A14 color170gsm 2pp100# gloss cover, 100# gloss text

    A24 color170gsm, folded, 4pp100# gloss cover, 80# gloss text

    A34 colorCover 170gsm with Body 120gsm, > 4pp80# gloss cover, 80# gloss text

    A42 color80# gloss cover, 80# gloss text

    170gsm Silk 120gsm Silk

    A52 color80# gloss cover, 80# matt sheet text

    170gsm Silk 120gsm Silk

    A61 color170gsm Silk 120gsm Silk80# gloss cover, 80# matt sheet text

    A74 color cover10 Point Cover C2S

    2 color textCategory being deleted50# matte sheet text

    Selection Guide

    A84 color coverCategory being deleted50# matte sheet text, self cover

    2 color text

    Selection Guide

    A92 color100gsm bond50# matte sheet text, self cover

    Selection Guide

    Post Sale / Technical Communication

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    B14 color cover270gsm Gloss 100gsm bond10 Point Cover C2S

    2 color text50# matte sheet text

    B21 color60# Cover

    160gsm Colortech & 100gsm Bond50# matte sheet text

    B31 color50# matte sheet text, self cover

    100gsm bond

    B42 color60# Cover

    160gsm Colortech & 100gsm Bond50# matte sheet text

    B52 color50# matte sheet text, self cover

    100gsm bond

    Catalogs

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    C14 color cover270gsm Gloss 90gsm silk10 Point Cover C2S

    4 color text45# Coated Sheet

    C24 color cover270gsm Gloss 80gsm silk10 Point Cover C2S

    2 color text32#-33# Coated Sheet

    JIT / POD

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    D14 color170gsm white silk80# gloss cover, coated 2 sides

    D24 color120gsm white silk80# gloss text, coated 2 sides, self cover

    D34 colorCover 170gsm with Body 120gsm80# gloss cover, 80# gloss text coated 2 sides

    D41 color160gsm tab90# index

    D51 color80gsm bond20# bond, self cover

    D61 colorCover 160gsm tab with Body 80gsm bond90# index, 20# bond

    D72 color160gsm tab90# index

    D82 color80gsm bond20# bond, self cover

    D92 colorCover 160gsm tab with Body 80gsm bond90# index, 20# bond

    D10Combination: 4 color cover, with 2 color bodyCover 160gsm with Body 80gsm90# index, 20# bond

    Print Spec Sheet

    JIT Printing SpecificationsRA-QR005D-EN-P - 4/03/2009

    Printing SpecificationYOUR DATA HEREInstructionsNO

    (required) Category:D5Select Print Category A,B,C or D from category list, on "Introduction_Catagory Types" tab11 x 17LOOSE -Loose LeafYESPre-sale / MarketingTOP

    (required) Finished Trim Size Width:4.75 x 7 (slightly smaller half-size)8.5 x 11PERFECT - Perfect BoundA1LEFT

    (required) Publication Number :1784-IN045C-EN-PSample: 2030-SP001B-EN-P3 x 5SADDLE - Saddle StitchA2RIGHTCORNER

    Use Legacy NumberYES or NO18 x 24 PosterPLASTCOIL - Plastic Coil (Coil Bound)A4BOTTOMSIDE

    Legacy Number if applicable:Sample Legacy Number: 0160-5.3324 x 36 PosterSTAPLED1 -1 positionA3

    Publication Title:USB-to-Data Highway Plus Cable Installation InstructionsSample: ElectroGuard Selling Brief36 x 24 PosterSTAPLED1B - bottom 1 positionA5

    (required) Business Group:Marketing CommercialAs entered in DocMan4 x 6STAPLED2 - 2 positionsA6

    (required) Cost Center:19021As entered in DocMan - enter number only, no description. Example - 19021CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 191054.75 x 7 (slightly smaller half-size)THERMAL - Thermal bound (Tape bound)A7

    Binding/Stitching:SADDLE - Saddle StitchReview key on right...Saddle-Stitch Items All page quantities must be divisible by 4.20 sheets max. on 20# (text and cover); 20 sheets = 80-page pub16 sheets max. on 20# (text) and 90# (cover); 16 sheets = 64-page pub

    Perfect Bound Items475 sheets max. on 20# no cover; 475 sheets = 950-page pub470 sheets max. w/cover / 90# index unless indicated otherwise); 470 sheets = 940-page pub

    Coil Bound Items400 sheets max. of 20# (if adding cover deduct equivalent number of pages to equal cover thickness) (90# index unless indicated otherwise); 400 sheets = 800-page pub

    Tape Bound Items125 sheets max. on 20# no cover; 125 sheets = 250-page pub120 sheets max. w/cover (90# index unless indicated otherwise); 120 sheets = 240-page pub

    Double Wire Bound Items250 sheets max. on 20# (if adding cover deduct equivalent number of pages to equal cover thickness) (90# index unless indicated otherwise); 250 sheets = 500-page pub4.75 x 7.75THERMALO - Thermal Bound (Tape bound - offline)A8

    (required) Page Count of Publication:20Total page count including cover5.5 x 8.5 (half-size)Wire O - Double Wire Bound (offline)A9

    Paper Stock Color:White is assumed. For color options contact your vendor.6 x 4Post Sale / Technical Communication

    Number of Tabs Needed:5 tab in stock at RR Donnelley7.385 x 9 (RSI Std)B1

    Stitching Location:SIDEBlank, Corner or Side8.25 x 10.875B2

    Drill Hole YES/NONOAll drilled publications use the 5-hole standard, 5/16 inch-size hole and a minimum of inch from the inner page border.8.25 x 11 (RA product profile std)B3

    Glue Location on Pad:Glue location on pads8.375 x 10.875B4

    Number of Pages per Pad:Average sheets of paper.. 25, 50 75,100 Max9 x 12 (Folder)B5

    Ink ColorOne color assumes BLACK / 4 color assume CMYK / Indicate PMS number hereA4 (8 x 11 ) (210 x 297 mm)Catalogs

    Used in Manufacturing:YESA5 (5.83 x 8.26) (148 x 210 mm)C1

    Comments:C2

    Part Number:PN-76634JIT / POD

    D1

    D2

    D3

    D4

    D5

    D6

    D7

    D8

    D9