User ManualmyGEKKO RIO modules

V 0.24

Page 2: User manual myGEKKO RIO modules

2

®®

Latest Update: August 2015All software-related descriptions refer to the V3320-07 software. An update is recommended for older versions of the system. Small deviations of the descriptions are possible and due to changes in the software. All brands and logos are registered trademarks and are the property of the respective holders of the rights

Copyright

All rights reserved. No parts of this document may be reproduced or transmitted in any form by any means, electronic or mechanical, without the prior written authorization of its legal owner.

If this publication is made available on Ekon GmbH media, Ekon gives its consent to downloading and printing copies of the content provided in this file only for private use and not for redistribution. No part of this publication may be modified, altered or used for commercial purposes. Ekon GmbH is not liable for the damages which arise from the use of an illegal modified or altered publication.

All products correspond to the directly applicable EU regulations and guidelines.

Page 3: User manual myGEKKO RIO modules

3

Table of Contents 1. Introduction

1.1 General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.2 Sub-Bus configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

2. Technical specifications 2.1 Rio 292.1.1 General technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62.1.2 Digital inputs X4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72.1.3 Analog inputs X5, X6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82.1.4 Digital outputs X7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82.1.5 Analog outputs X5, X6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92.1.6 Aux1 / RS-485 X3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92.1.7 MBus X3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92.1.8 Aux2 / RS-485 or RS-232 X3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 2.1.9 Screw terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 2.1.10 Spring clamp terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102.1.11 Installation specifications RIO 29 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112.1.12 Functional description Dip switch RIO 29 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

2.2. Aux-8 2.2.1 General technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142.2.2 Digital PWM inputs X100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152.2.3 Analog outputs X101 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152.2.4 Connection example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162.2.5 Installation specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 2.2.6 Spring clamp terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 2.3. Rio 16 2.3.1 General technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182.3.2 Digital inputs X4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192.3.3 Digital outputs X5, X6, X7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 2.3.4 Screw terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 2.3.5 Spring clamp terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212.3.6 Installation specifications RIO 16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222.3.7 Functional description Dip switch RIO 16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232.3.7 RIO-16 in single mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 2.4 Functional description LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262.5 Buswiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 272.6 Configurations example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 282.7 Schematic example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

3. Installation manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

4. Software activation at myGEKKO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

5. Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 353

Page 4: User manual myGEKKO RIO modules

4

1. Introduction

1.2 Sub-Bus configuration

1.1 General Information

The maximum number of modules which can be connected to a RIO-29 bus coupler is 16 modules includ-ing bus coupler. Rio 16 or Rio 29 modules may be attached also in combination at will. The sub-bus modules may also be mounted on several distributors distinctively.

The basic function of the RIO-modules consists of data acquisition (digital and analogue inputs) and the triggering of digital and analogue outputs respectively. RIO-modules are controlled via a RS-485 connection. The devices themselves have no intelligence.

Solely, the operating status of the digital outputs can be determined in case of communication failure. The modules are built-in appliances and may be installed only by qualified personnel. The necessary covers must be in place (see section installation instruction).

A maximum of 8 bus lines can be operated on a myGEKKO Slide (Bus coupler RIO29 or RIO16 in single mode).

WARNING: Read all safety information and instructions before using the RIO modules in order to avoid injuries.!

Connections at the myGEKKO Slide Connections at the RIO29 bus coupler

to the Sub-Busmodulesrecommended cable typeProfibus L2FIP 1x2x0,65

RS485

RS485 Rio-29

Example myGEKKO with one bus line divided among several distributors

Rio-29 Rio-29

Rio-16

Rio-16 Rio-16 Rio-16

120

Ohm

Page 5: User manual myGEKKO RIO modules

5

Note that the supply of the modules must be fused with 3A. If the power consumption exceeds 3A the mod-ules have to be supplied separately.

The bus must be wired accordingly to X1 or X2 (sub-bus). Therefore, the following connections are required:

+24VDC do not connect, but supply separatelyRxTx+ connect to previous moduleRxTx- connect to previous moduleGND connect to previous module

RS485

RS485

16 modules

...

...

Example con�guration with 4 Bus-lines

Rio-29

Rio-29

Rio-29 Rio-29 Rio-29 Rio-29 Rio-16

Rio-29

Rio-16

(from V.0.17)

Rio-16

Bus coupler(1st module of the busline)

Sub-Busmodule(more modules)

max. 3 Amax. 3 A

!

+24V

DC

GN

D

+24V

DC

GN

D

3A 3A

Page 6: User manual myGEKKO RIO modules

6

2. Technical specifications

2.1 RIO 29

Page 7: User manual myGEKKO RIO modules

7

2.1.1 General technical specifications

2.1.2 Digital Inputs X4

Parameters ValueInput type Optically separated /

opto-couplersIsolation voltage 400VSwitch point On >9VDCSwitch point Off <5VDCMaximum input voltage 24VDC +30%Current consumption / Input @ 10V 2mACurrent consumption / Input @ 18V 3.8mACurrent consumption / Input @ 24V 5.5mACurrent consumption / Input @ 28V 6.2mA

There is a galvanic isolation to the modules of all inputs via opto-couplers.

Parameters Value NotesSupply voltage 24VDC -25% / +30%Current consumption (internal) max. 250mA Typ. 100mA @ 24VDCTemperature range during operation

- 20-50°C

Storage temperature - 40-85°COperating time 100% ED designed for continuous

operationDegree of protection IP20 established via appropriate

installationContamination level 2Protection class IIPrinciple of operation Type 1 EN60730-1Humidity max. 75% r.H. without condensation, during

operationSoftware class Class ADimensions 162mm x 110mm x 62mm L x W x HWeight 280gEMV CE according to 2004/108/EGRated surge voltage 0,5kVOutput PV at 24 VDC 3 W

Page 8: User manual myGEKKO RIO modules

8

2.1.4 Digital Outputs X7 Parameters Value/Notes

Type of output PWM outputs / galv. non-insulated

Output current 0,5A / Short-circuit-proofPower supply Separate feeding

(Supply must be fused exter-nally with 5A) 24VDC -25% / +30%

2.1.3 Analog inputs X5, X6

Parameters ValueUI-x input range 0-10V voltage input

1mV (16 Bit ADC)0 – 10’000

II-x input range 0-20mA current input10uA (12 Bit ADC)0 – 2’000 uA

TI-x input range PT1000 0,1 Grad-500 – 2’500

TI-x temperature range -50 – 250°C

PT 1.0000-10 VDC0-20 mA

Page 9: User manual myGEKKO RIO modules

9

2.1.5 Analog outputs X5, X6

2.1.6 Aux1 / RS-485 X3

2.1.7 M-Bus X3

2.1.8 Aux2 / RS-485 oder RS-232 X3

Parameters Value NotesUO-X Output 0-10V 12-bit resolution

0 – 4’096UO-X Max. load 10mA short-circuit-proofIO-X Output 0-20mA 12-bit resolution coupled with

UO-XIO-X Max. load 500 Ohm pen-circuit-proof

Parameters ValueInterface type RS-485

Baud rate 1200, 2400, 4800, 9600, 19’200 and 38’400 baudParity adjustable

Parameters Value/NotesInterface type M-Bus /

+/-30VDC max. 60mABaud rate 1200, 2400, 4800, 9600, 19’200 and

38’400 baudParity adjustable

Parameters ValueInterface type RS-485 oder RS-232

Baud rate 1200, 2400, 4800, 9600, 19’200 and 38’400 baud

Parity adjustable

The module acts as bus master for a maximum of 3 M-bus slaves.

Aux2 can either be operated as an RS-485 or RS-232 interface.

848586878889

80818283

31

90

79

91011121314

1920

15161718

222324252627282930

21

32333435363738

40394142434445464748

69

49

5152535455565758

6059

6162636465666768

my-G

EKKO RIO

-29w

ww

.my-gekko.com

Analog-IO

AI-1 .. A

I-4, AO

-1A

nalog-IO A

I-5 .. AI-8, A

O-2

Digital O

utputs DO

-1 .. DO

-8

M-Bus +M-Bus -

1314

848586878889

80818283

31

90

79

91011121314

1920

15161718

222324252627282930

21

32333435363738

40394142434445464748

69

49

5152535455565758

6059

6162636465666768

my-G

EKKO RIO

-29w

ww

.my-gekko.com

Digital O

utputs DO

-1 .. DO

-8

AUX1

: RS4

85AU

X2: R

S485

/RS2

32

9101112

1920

15161718

RxTx+

RxTx-

+24VDC

GND

RxTx+RxTx-

+24VDC

GNDRxDTxD

848586878889

80818283

31

90

79

91011121314

1920

15161718

222324252627282930

21

32333435363738

40394142434445464748

69

49

5152535455565758

6059

6162636465666768

my-G

EKKO RIO

-29w

ww

.my-gekko.com

Analog-IO

AI-1 .. A

I-4, AO

-1A

nalog-IO A

I-5 .. AI-8, A

O-2

Digital O

utputs DO

-1 .. DO

-8

Gnd

UI-3II-3

TI-3

AI-7

UI-1II-1

TI-1Gnd

AI-5

UI-2II-2

TI-2Gnd

AI-6

UI-4II-4

TI-4Gnd

AI-8

UO-1IO-1GND

AO-2

U: Voltage 0..10V D

CI: Current 0..20m

A

0,25 ..0,50,14 ..0,5

Gnd

UI-3II-3

TI-3

AI-3

UI-1II-1

TI-1Gnd

AI-1

UI-2II-2

TI-2Gnd

AI-2

UI-4II-4

TI-4Gnd

AI-4

UO-1IO-1GND

AO-1

U: Voltage 0..10V D

CI: Current 0..20m

A

11

4748

69

49

1

6768

848586878889

80818283

31

90

79

91011121314

1920

15161718

222324252627282930

21

32333435363738

40394142434445464748

69

49

5152535455565758

6059

6162636465666768

my-G

EKKO RIO

-29w

ww

.my-gekko.com

Digital O

utputs DO

-1 .. DO

-8

AUX1

: RS4

85AU

X2: R

S485

/RS2

32

9101112

1920

15161718

RxTx+

RxTx-

+24VDC

GND

RxTx+RxTx-

+24VDC

GNDRxDTxD

Page 10: User manual myGEKKO RIO modules

10

2.1.9 Screw terminals

2.1.10 Spring clamp terminals

Stripping length 7 mmConnection dataConductor cross section rigid min 0,14 mm²

Conductor cross section rigid max 1,5 mm²Conductor cross section flexible min 0,14 mm²Conductor cross section flexible max 1,5 mm²Conductor cross section flexible with ferrule without plastic sleeve min 0,25 mm²Conductor cross section flexible with ferrule without plastic sleeve max 1,5 mm²

Conductor cross section flexible with ferrule and plastic sleeve min 0,25 mm²Conductor cross section flexible with ferrule and plastic sleeve max 0,5 mm²Conductor cross section AWG/kcmil min 28Conductor cross section AWG/kcmil max 162 cables of the same cross section rigid min 0,08 mm²2 cables of the same cross section rigid max 0,5 mm²2 cables of the same cross section flexible min 0,08 mm²2 cables of the same cross section flexible max 0,75 mm²2 cables of the same cross section flexible with CES without plastic sleeve min 0,25 mm²2 cables of the same cross section flexible with CES without plastic sleeve max 0,34 mm²2 cables of the same cross section flexible with TWIN-CES with plastic sleeve min 0,5 mm²2 cables of the same cross section flexible with TWIN-CES with plastic sleeve max 0,5 mm²

Stripping length 8,5 mmConnection dataConductor cross section rigid min 0,2 mm²

Conductor cross section rigid max 1,5 mm²Conductor cross section flexible min 0,2 mm²Conductor cross section flexible max 1,5 mm²Conductor cross section AWG/kcmil min 20Conductor cross section AWG/kcmil max 16

X1, X2: type MCV1.5 / 4-St-3,81

X3, X4, X7 type 250-210

Page 11: User manual myGEKKO RIO modules

11

Stripping length 8,5 mmConnection dataConductor cross section rigid min 0,14 mm²

Conductor cross section rigid max 0,5 mm² Conductor cross section flexible min 0,2 mm²Conductor cross section flexible max 0,5 mm²Conductor cross section AWG/kcmil min 24Conductor cross section AWG/kcmil max 20

X5, X6 type 250-1419

2.1.11 Installation specifiactions RIO-29

Please note: The ground (GND) of the power supply unit must be earthed.The cable screens for the analogue inputs and outputs must be grounded on the module-side.

!

Page 12: User manual myGEKKO RIO modules

12

2.1.12 Functional description Dip switch RIO 29

The DIP-switches are activated when the corresponding switches are pushed upwards.

Parameters Values

Manual operation switch1..8

State of the corresponding output in manual mode or at bus timeout.

ON = Output ONOFF = Output OFF

A

Behaviour of outputs in case of communication interruption.

ON = Outputs retain current state (not remanent)OFF = Outputs attain the set manual mode.

B Reserve (without functionality)

LED

State of the status LED on the module.

ON = All LEDs are switched offOFF=All LEDs show the current module state

Manual

Manual operation

ON = Switches all outputs to manual operation modeOFF=Automatic mode

Page 13: User manual myGEKKO RIO modules

13

The concealed switches which are located underneath the module cover have the following functions:

The valid address range is as follows:For a module connected to the sub-bus an address in the range 2 .. 99 may be assigned.A RIO-29 module connected directly to the myGEKKO bus an address of 1..99 may be assigned.

Parameters Values

Config 1

Baud Uart1

ON: 115.200kBOFF: 57.600kB

Config 2

RIO29 master mode

ON: Module acts as sub-bus master (bus coupler)OFF: Module acts as slave module, such as a RIO16

Config 3

Locking of straight/odd outputs 1-4

ON: 1 and 2, 3 and 4 interlockedOFF: No locking function activated

Config 4

Locking of straight/odd outputs 5-8

ON: 5 and 6, 7 and 8 interlockedOFF: No locking function activated

AdressModule address on the bus.

CAUTION: Address 0 is not permissible for operation

Page 14: User manual myGEKKO RIO modules

14

2.2 AX-8

2.2.1 General technical specifications

Parameters Value NotesSupply voltage 24VDC -25% / +30%Current consumption (internal) max. 50mA Typ. 20mA @ 24VDCTemperature range during op-eration

- 20 - 50°

Storage temperature - 40 - 85°Operating time 100% ED designed for continuous opera-

tionDegree of protection IP20 established via appropriate

installationContamination level 2Protection class IIPrinciple of operation Type 1 EN60730-1

Page 15: User manual myGEKKO RIO modules

15

2.2.2 Digital PWM inputs X100

2.2.3 Analog outputs X101

Parameters ValueInput type PWM inputs, only from Rio 29Maximum input voltage 24VDC +30%Input frequency 500 Hz

The PWM inputs translate the PWM outputs of the RIO-29 into a 0-10V signal. The module can only be oper-ated on a RIO-29.

Parameters Value NotesHumidity max. 75% r.H. without condensation, during

operationSoftware class no softwareDimensions 54 mm x 110mm x 62mm L x W x HWeight 80 gEMV CE according to 2004/108/EGRated surge voltage 0,5kVTypical thermal power at 24VDC 0,5 W

Parameters Value NotesUO - X Output 0-10 V 12-bit resolution 0 - 4.096UO - X max. load 10mA short-circuit-proof

Page 16: User manual myGEKKO RIO modules

16

2.2.4 Connection example

2.2.5 Installation instruction AX-8

Page 17: User manual myGEKKO RIO modules

17

2.2.6 Spring clamp terminals

Stripping length 8,5 mmConnection data

Conductor cross section rigid min 0,2 mm²

Conductor cross section rigid max 1,5 mm²Conductor cross section flexible min 0,2 mm²Conductor cross section flexible max 1,5 mm²Conductor cross section AWG/kcmil min 20Conductor cross section AWG/kcmil max 16

X100, X101 type 250-210

Page 18: User manual myGEKKO RIO modules

18

2.3 RIO 16

The power current outputs DO-1 to DO-8 must be externally protected with 1*16A each.!

2.3.1 General technical specifications

Page 19: User manual myGEKKO RIO modules

19

2.3.2 Digital inputs X4

Parameters ValueInput type Optically separated /

opto-couplersIsolation voltage 400VSwitch point On >9VDCSwitch point Off <5VDC

Maximum input voltage 24VDC +30%

Current consumption / Input @ 10V 2mA

Current consumption / Input @ 18V 3.8mA

Current consumption / Input @ 24V 5.5mA

Current consumption / Input @ 28V 6.2mA

There is a galvanic isolation to the modules of all inputs via opto-couplers.

Parameters Value NotesSupply voltage 24VDC -25% / +30%Current consumption (inter-nal)

Max. 250mA Typ. 100mA @ 24VDC

Temperature range during operation

-20 - 50°C

Storage temperature -40 - 85°COperating time 100% ED designed for continuous

operationDegree of protection IP20 established via appropriate

installationContamination level 2Protection class IIPrinciple of operation Type 1 EN60730-1Humidity max. 75% r.H. without condensation, dur-

ing operationSoftware class Class ADimensions 162mm x 110mm x 62mm L x W x HWeight 380gEMV CE according to 2004/108/EGRated surge voltage 0,5kVOutput PV at 24 VDC 2 W

Page 20: User manual myGEKKO RIO modules

20

2.3.3 Digital outputs X5, X6, X7

Parameters Values NotesOutput type relay 16A/230VAC per output

External fusing Each output has to be fused exter-nally with 1*16A.

Inrush current factor 10%

25A Max. 4 seconds duty

Max. continuous current 16A DC or COS(phi) = 1Max. switching capacity AC 4000VAMax. operation cycles 50’000

The relay outputs can be realized with “high-current relay.” In order to realize the module possible energy saving, the relay only 1 second can be driven with the nominal coil voltage. If the relay is defined attracted, thus lowering the voltage, the relay module to reduce power consumption.

2.3.4 Screw terminals

Stripping length 7 mmConnection dataConductor cross section rigid min 0,14 mm²

Conductor cross section rigid max 1,5 mm²Conductor cross section flexible min 0,14 mm²Conductor cross section flexible max 1,5 mm²Conductor cross section flexible with ferrule without plastic sleeve min 0,25 mm²Conductor cross section flexible with ferrule without plastic sleeve max 1,5 mm²Conductor cross section flexible with ferrule and plastic sleeve min 0,25 mm²Conductor cross section flexible with ferrule and plastic sleeve max 0,5 mm²Conductor cross section AWG/kcmil min 28Conductor cross section AWG/kcmil max 162 cables of the same cross section rigid min 0,08 mm²2 cables of the same cross section rigid max 0,5 mm²2 cables of the same cross section flexible min 0,08 mm²2 cables of the same cross section flexible max 0,75 mm²2 cables of the same cross section flexible with CES without plastic sleeve min 0,25 mm²2 cables of the same cross section flexible with CES without plastic sleeve max 0,34 mm²2 cables of the same cross section flexible whit TWIN-CES with plastic sleeve min 0,5 mm²2 cables of the same cross section flexible whit TWIN-CES with plastic sleeve max 0,5 mm²

X2: type MCV1.5/4-ST-3,81

222324252627282930

21

101

102

103

104

105

106

113

114

115

116

117

118

107

108

109

110

111

112

5678

ww

w.m

y-gekko.com

DO

-1D

O-2

DO

-5D

O-3

DO

-4D

O-7

DO

-8D

O-6

NC

NC

101

102

103

104

105

106

107

108

109

110

111

112

113

114

115

116

117

118

my-G

EKKO RIO

-16

101

102

103

104

105

106

113

114

115

116

117

118

107

108

109

110

111

112

L

DO1

L

DO2

L

DO3Contact ratings load Switching cycles

12 A, 250V~, cosφ=1TV8 2500 W, 230V~, halogen lamps1000 W, 250V~, incandescent lamps3000 W, 250V~, incandescent lamps1500 VA, fluorescent tubes 163 µF

3x105

25x103

>104 2,3x105 3,6x104

104

Page 21: User manual myGEKKO RIO modules

21

Stripping length 6,5 mmConnection dataConductor cross section rigid min 0,5 mm²

Conductor cross section rigid max 4 mm² Conductor cross section flexible min 0,5 mm² Conductor cross section flexible max 4 mm² Conductor cross section flexible with ferrule without plastic sleeve min 0,5 mm² Conductor cross section flexible with ferrule without plastic sleeve min 2,5 mm² Conductor cross section flexible with ferrule without plastic sleeve min 0,5 mm² Conductor cross section flexible with ferrule without plastic sleeve min 2,5 mm² Conductor cross section AWG/kcmil min 20 Conductor cross section AWG/kcmil max 102 cables of the same cross section rigid min 0,5 mm²2 cables of the same cross section rigid max 1,5 mm²2 cables of the same cross section flexible min 0,5 mm²2 cables of the same cross section flexible max 1,5 mm²2 cables of the same cross section flexible with CES without plastic sleeve min 0,25 mm²2 cables of the same cross section flexible with CES without plastic sleeve max 0,75 mm²2 cables of the same cross section flexible with TWIN-CES with plastic sleeve min 0,5 mm²2 cables of the same cross section flexible with TWIN-CES with plastic sleeve max 1,5 mm²

Stripping length 8,5 mmConnection dataConductor cross section rigid min 0,2 mm²

Conductor cross section rigid max 1,5 mm² Conductor cross section flexibel min 0,2 mm² Conductor cross section flexibel max 1,5 mm² Conductor cross section AWG/kcmil min 20 Conductor cross section AWG/kcmil max 16

X5, X6, X7 type PT2.5/6-7.5H

2.3.5 Spring clamp terminals

X4 type 250-210

Page 22: User manual myGEKKO RIO modules

22

2.3.6 Installation specifiactions RIO-16

Note that the module linking via the connectors X10 and X11 is only permissible up to a current of 3A. If the 3A are exceeded, separate supply at X1 or X2 (sub-bus) has to be established.

!

Page 23: User manual myGEKKO RIO modules

23

The DIP-switches are activated when the corresponding switches are pushed upwards.

Parameters Value

Manual operation switch1..8

State of the corresponding output in manual mode or at bus time-out.

ON = Output ONOFF = Output OFF

A

Behaviour of outputs in case of communication interruption.

ON = Outputs retain current state (not remanent)OFF = Outputs attain the set manual mode.

B ON = the module acts like an independent module (without RIO 29)OFF = the module acts like a slave module

LED

State of the status LED on the module.

ON = All LEDs are switched offOFF=All LEDs show the current module state

Manual

Manual operation

ON = Switches all outputs to manual operation modeOFF=Automatic mode

2.3.7 Functional description Dip switch RIO 16

Page 24: User manual myGEKKO RIO modules

24

The concealed switches which are located underneath the module cover have the following functions:

The valid address range is as follows:For a module connected to the sub-bus an address in the range 2 .. 99 may be assigned.A RIO-29 module connected directly to the myGEKKO bus an address of 1..99 may be assigned.

Parameters Value

Config 1 Emergency control system

Config 2 Emergency control system

Config 3

Locking of straight/odd outputs 1-4

ON: 1 and 2, 3 and 4 interlockedOFF: No locking function activated

Config 4

Locking of straight/odd outputs 5-8

ON: 5 and 6, 7 and 8 interlockedOFF: No locking function activated

AdressModule address on the bus.

CAUTION: Address 0 is not permissible for operation

Emergency control system RIO-16

Config 1 Config 2 User A (Fail-mode)

Description

0 0 0 Outputs switch to the state of the manual switches

0 0 1 Outputs maintain the last state received from myGEKKO1 0 X SR-Light direct mode (DI->DO toggle)0 1 X Rollo mode1 1 X Reserve. At the moment: Outputs switch to the state of the

manual switches (if fail mode ‘0’)

Page 25: User manual myGEKKO RIO modules

25

SR-Light direct mode (DI->DO toggle)

Rollo-Mode

• Outputs are switched as pushbutton function of inputs. Impulse at input x toggled state on output x (relay closed / relay opened).

• 1.Input switches as pushbutton function of 1.output (same for all 8 inputs and outputs)

• short keystroke -> short operation

• long keystroke (>1s) -> output switched for 5 min. or until keystroke on input 1 (or key-stroke on input 2 in case of activated locking)

• The Odd-Even-Lock of the outputs must be activated via Config 3 and Config 4.

2.3.7 Functional description Dip switch RIO 16

The myGEKKO RIO-16 can be operated in single mode and therefore it can be connected independently to the myGEKKO (from software version myGEKKO RIO-16 V.0.17). Please note that the RIO-16 module cannot be used as bus coupler and is not suitable for the connection of other RIO modules.

To select the single mode for the myGEKKO RIO-16, the DIP switch B has to be switched to ON. The address can be entered with the address switch as usual.

Page 26: User manual myGEKKO RIO modules

26

Parameters ValueRun LED on, module active no fault condition

Info LED blinking, Odd/Even Lock active, i.e. 2 outputs mutually activeManual LED on, outputs manual operation, i.e. such as switch position

„ON“Auto LED on, outputs are set via busMaster LED blinking, if interface is currently communicatingSlave LED blinking, if interface is currently communicatingAux LED blinking, if interface is currently communicatingInputs LED on, corresponding input activeOutputs LED on, corresponding output active

2.4 Functional description LED’s

Page 27: User manual myGEKKO RIO modules

27

2.5 Bus wiring

It is of high importance that the bus cabling is linear, i.e. the bus has a start and an end point. Star-shaped bus wiring as well as ring wiring have to be avoided to prevent interferences.

Recommended cable type for data connection: Profibus L2FIP 1x2x0,65

Note:Install bus terminating resistors at the start and end points of the bus in case of communication problems or long connection lines to myGEKKO (> 20 meters). The resistor must be connected as follows:For slave bus:1 resistor on the master RIO-29 at the slave bus connector and 1 resistor on the last RIO-16 or RIO-29 at the slave connector wired in series.For master bus:1 resistor on myGEKKO Slide and 1 resistor at the last master connector wired in series.

no star wiring!!

no ring wiring!!

Bus wiring

120O

hm

120O

hm

120O

hm

myGEKKO Slide last RIO29 bus coupler last RIO16

120

Ohm

Page 28: User manual myGEKKO RIO modules

28

2.6 Configuration example setting of bus addresses

Page 29: User manual myGEKKO RIO modules

29

2.6 Configuration example setting of bus addresses

Page 30: User manual myGEKKO RIO modules

30

2.7 Schematic example: Protection of the 24VDC circuits with circuit breaker or extra fuse

power supply TRACOTBL 150 / 6,25A

RIO 29module no. 1

RIO 29module no. 2

RIO 16module no. 9

to module no. 3...8

DISTRIBUTOR

FIELD

myGEKKO Touch

push-button, contacts,...

DISTRIBUTOR

FIELD

Thermo valve drives

Circuit breakereg: ABB S201-Z2 and S201-Z41P 2/4A Car. Z

2A 2A 2A 2A 2/4A 2/4A

to module no. 10...16

Temperature probesPT1000

TIG

ND UI

GN

D

humidity sensors0-10V

Thermo valve drives

Fuse circuits:1) myGEKKO Touch 2) Devices in the �eld like push-buttons, contacts, sensors, ..3) feed-in modules RIO 1..84) feed-in modules RIO 9..16 5) Thermal valve drives �rst RIO296) Thermal valve drives second RIO29

Page 31: User manual myGEKKO RIO modules

31

2.7 Schematic example: Protection of the 24VDC circuits with circuit breaker or extra fuse

power supply TRACOTBL 150 / 6,25A

RIO 29module no. 1

RIO 29module no. 2

RIO 16module no. 9

to module no. 3...8

DISTRIBUTOR

FIELD

myGEKKO Touch

push-button, contacts,...

DISTRIBUTOR

FIELD

Thermo valve drives

Circuit breakereg: ABB S201-Z2 and S201-Z41P 2/4A Car. Z

2A 2A 2A 2A 2/4A 2/4A

to module no. 10...16

Temperature probesPT1000

TIG

ND UI

GN

D

humidity sensors0-10V

Thermo valve drives

Fuse circuits:1) myGEKKO Touch 2) Devices in the �eld like push-buttons, contacts, sensors, ..3) feed-in modules RIO 1..84) feed-in modules RIO 9..16 5) Thermal valve drives �rst RIO296) Thermal valve drives second RIO29

Page 32: User manual myGEKKO RIO modules

32

3. Installation manual

3.1 User-circle

3.2 General safety information

3.3 Installation procedure

Installation and assembly of electrical equipment may only be performed by a qualified electrician. Non-observance of this manual could cause damage to the device and cause fire or other hazards.

This manual is part of the product and has to remain with the end user.

The applicable electrical regulations for domestic installation are to be respected.

There are live parts inside the housing. Touching terminals may be fatal if the system is not discon-nected from the mains. There are no serviceable parts inside the device. The opening of the hous-ing is thus only allowed to employees of the manufacturer.

Caution! External voltage on the RIO !For the performance of service work on RIO modules or the connected peripherals all connections must be disconnected from the main supply. Include all circuit breakers which provide dangerous voltages to the device.

Power supply must not be applied to the terminals as long as the earth connector is not earthed properly according to instructions.Basically, the valid electrical installation regulations must be observed for household and observed.

The devices are designed for stationary operation and must be mounted that the touching of the energized terminals in normal operation is impossible.

In general, the RIO modules are installed under covers. During installation, ensure particular that the devices are protected from environmental influences like water, humidity and dirt.

The units may be connected in the supply voltage condition. Depending on the installation the modules can either snapped onto DIN-rails (C-35) or screwed (surface) on a mounting panel. The cable relief of the connecting cables must made during installation. The modules have no cable relief.

!

!

!

Page 33: User manual myGEKKO RIO modules

33

3.4 External fuseThe 24VDC power supply of the RIO modules must be secured externally according to the cross section of the connection wires and the maximum current consumption of the device.

It has to be ensured that for each output DO-1 to DO-8 of the RIO-16 current is limited by external protection to a maximum of 16A.

All connecting wire cross sections have to be chosen in regard of the maximum current.

!

4. Software activation at myGEKKOThe modules are ready for use if all modules are connected and configured.

1. Go to main settings and select IO configuration (green/blue arrows)2. At IO Station 1 select –> “myGEKKO RIO”. If you use several bus lines you need to select “myGEKKO RIO”

also at the other stations 2 to 8 according to the number of bus lines used.3. Select next to “myGEKKO RIO” the port on which you have connected the RIOs. By default, it is the COM

PORT 2 directly on the Touch. If you use several bus lines (IO stations) choose from there as well the par-ticular port on which the bus line is connected.

4. Tap “Configure>>” then select the connected modules according to the bus line. Now tap “Scan”. All con-nected RIO modules should now be detected and listed. If the RIOs are correctly identified an “OK” will appear next to each detected RIO. Now press “>>” on the RIO 29 modules to open the overview of the analogue inputs. Select the connected analogue inputs manually (0..10V; 0..20mA; PT1000; NC) With RIO-16 in single mode: The IO configuration is identical. Select the type for “RIO 1” in the submenu “Configuration >>”.

5. Tap “Save”. 6. Done! You can now use the RIO modules in the single system menus.

Selection of the RIOs at the Com Port 2

Page 34: User manual myGEKKO RIO modules

34

Scanning the RIO modules

Scanning the RIO 16 module

Defineing the analog inputs of the RIO modules

RIO 16 in single mode

Page 35: User manual myGEKKO RIO modules

35

5. Notes

Page 36: User manual myGEKKO RIO modules

36