    T200A Hardware Operation Manual

    1

    PONOVO POWER CO., LTD2F, 4Cell, Tower C, In.Do Mansion

    No.48A Zhichun Road, Haidian District

    Beijing, China (Post Code 100098)

    OfficeTEL. +86 (10) 82755151 ext. 8887

    FAX +86 (10) 82755257

    E-Mail [email protected]

    Website www.relaytest.com

    T200A

    OPERATION MANUAL

    VERSION: T200A-AE-3.04

    DATE: 08/01/2013

    This manual is the publisher of PONOVO POWER CO., LTD. To make any kind of copy of

    this manual please contact PONOVO POWER CO., LTD in advance.

    This manual represents the technical status for the moment of publishing. The product

    information, description and specifications mentioned in the manual do not have any

    contact binding force and PONOVO POWER CO., LTD remains the right to make

    modifications to the technical specifications and configurations without prior notice.

    PONOVO POWER does not take responsibility to the possible error/mistakes in this

    manual.

  • 8/9/2019 User Manual T200A en V3.04

    2/55

    T200A Hardware Operation Manual

    2

    Notes

    In order to prevent accumulation of static electricity inside the running tester,

    make reliable ground connection via its ground terminal before the test.

    Be caution when output voltage is over 36V, this might cause some electric

    accident. Keep safety and avoid this situation occurring.

    When high current is being outputted, avoid personal injury and the equipment

    damage, which is under test.

    Never add external voltage and current onto the voltage/current output

    terminals of the tester.

    Since the tester is a kind of precision electronic equipment, keep a water-proof

    and damp-proof environment for it.

    Find any abnormal signs during the installation of the tester, please inform

    factory immediately and dont fix it by yourself.

  • 8/9/2019 User Manual T200A en V3.04

    3/55

    T200A Hardware Operation Manual

    3

    Content

    1. General Introduction ................................................................................................. 5

    2. Panel introduction ..................................................................................................... 8

    3. Technique parameters ............................................................................................ 104. Operation guide ...................................................................................................... 14

    4.1 How to select test item .................................................................................. 14

    4.2 How to select variable ................................................................................... 15

    4.3 How to set parameters .................................................................................. 15

    4.4 How to control output .................................................................................... 15

    4.5 Reports view and save ................................................................................. 16

    4.5.1 Report view ......................................................................................... 16

    4.5.2 Report save ......................................................................................... 16

    4.6 System setting ............................................................................................... 17

    5. Introduction to test function .................................................................................... 18

    5.1. Aux DC ......................................................................................................... 18

    5.2. Any test ......................................................................................................... 19

    5.2.1 Manual &Meter .................................................................................... 19

    5.2.2 ShotLinear RampPulses Ramp ................................................... 19

    5.3 Relay test ...................................................................................................... 22

    5.3.1 Trip time test, Trip time + pulse length test with I2 ............................. 22

    5.3.2 Pick up test ......................................................................................... 24

    5.3.3 Reclosing ............................................................................................ 25

    5.3.4 Under freq test .................................................................................... 265.3.5 Differential test .................................................................................... 28

    5.3.6 Harmonic ............................................................................................. 30

    5.3.7 Synchronism test ................................................................................ 32

    5.3.8 Directional test .................................................................................... 33

    5.3.9 DC relay, mA level; AC & DC test ....................................................... 34

    5.3.10 Motor overload test ........................................................................... 35

    5.4 CT Test....................................................................................................... 36

    5.4.1 Primary side injection .......................................................................... 36

    5.4.2 Ratio test ............................................................................................. 37

    5.4.3 Polarity test ......................................................................................... 38

    5.4.4 Winding resistance test ....................................................................... 39

    5.4.5 Excitation curve test ............................................................................ 40

    5.4.6 Secondary impedance test ................................................................. 41

    5.5 DC test of operating loop .............................................................................. 42

  • 8/9/2019 User Manual T200A en V3.04

    4/55

    T200A Hardware Operation Manual

    4

    5.6 Timer.............................................................................................................. 43

    5.7 Voltage/current measuring function .............................................................. 44

    6. T200A Accessories ................................................................................................. 45

    6.1 Soft Bag for Test Leads ................................................................................. 46

    6.2 Transportation Case ................................................................................. - 51 -7. Appendix ............................................................................................................ - 53 -

  • 8/9/2019 User Manual T200A en V3.04

    5/55

    T200A Hardware Operation Manual

    5

    1. General Introduct ion

    The T500 series single phase relay test kits are designed for easy and safe test of

    different type of relays. The powerful 250A/2000VA current source can be used to test all

    kinds of current relays, including high burden relay and CT. The AC/DC current and/or

    voltage sources allow phase angle and frequency to be adjusted smoothly. This makes it

    possible to precisely test directional and frequency relay. The kit uses advanced switching

    power amplifier to replace the traditional transformer, thus avoiding the dangerous high

    voltage across the current output.

    T500 series universal tester offers 2 types of products: T200A/T1000.

    The following is the introduction of T200A.

    Hardware configuration

    High power AC current I1 0.2-250A

    High power AC voltage U1 10-500V

    High power DC voltage Udc 10-300V

    High precision AC/DC current I2 0-20A

    High precision AC/DC voltage U2 0-120V

    High precision AC/DC low current I3 0-200mA

    Auxiliary DC power supply 20-240V/55W110V/110W(220V)

    AC/DC voltmeter 0-600V

    AC/DC ammeter 0-6A

    Binary input 2

    Binary output 1

  • 8/9/2019 User Manual T200A en V3.04

    6/55

    T200A Hardware Operation Manual

    6

    T200A Test Functions

    SN. Module

    type

    Functions Application relay types

    1. Relay test Users can select any of thefollowing test content to operate.

    Trip time test, trip time and

    pulse length test with I1, U1, I2,

    U2, I3, Udc

    Pick up test

    Reclosing

    Under frequency test

    Differential test

    Harmonics test

    Synchronism test

    Directional test

    DC relay, mA level; AC & DC

    test

    Motor overload test

    Overcurrent relaysUndercurrent relays

    Overvoltage relays

    Undervoltage relays

    Motor overload protection (I2)

    Automatic reclosing devices

    Thermal relays

    df/dt relay(U2&I2)

    Time-delay relays (U2&I2)

    Timer(Binary input)

    Harmonic brake test

    Differential relay

    Synchronism relay

    2. Any Test Manually control the amplitude,

    phase of AC variables and also

    high power Udc.

    Shot, linear ramp, pulse ramp

    start relay device test when

    Udc being the power supply

    low voltage operate test on trip

    coil of intermedia\high voltagebreaker when Udc being the

    control power resource

    3. Timer Automatically test Action time measurement

    4. CT test Primary/secondary side

    injectionUse manual control

    Ratio test

    Polarity test

    Winding resistance test

    Excitation curve test

    Basic test functions for CT

  • 8/9/2019 User Manual T200A en V3.04

    7/55

    T200A Hardware Operation Manual

    7

    5. Report Reviewing the report 30 reports can be saved and 10

    reports can be displayed in each

    page.

    6. System

    setting

    Set rated voltage and frequency of

    the system being tested

    /

    7. Aux DC Provide power supply Provide power supply to relay or

    other equipment

    8. PC control The test results can be transferred

    to external PC via USB port.

    Optional

  • 8/9/2019 User Manual T200A en V3.04

    8/55

    T200A Hardware Operation Manual

    8

    2. Panel introduct ion

    1) High power output (I1): its mainly applied for CT test and primary side injection.

    2) High power output(UDC): 10300V, its mainly applied for DC act time testing

    and low voltage operation test to the tripping coil on intermedia/high voltage

    breaker.

    3) High power output (U1): its mainly applied for CT test and primary side injection.

    4) AC/DC voltmeter: they can be applied for measuring both internal and external

    outputs. used for realizing the DC resistance and impedance measurement,

    excitation characteristic test etc.

    5) AC/DC ammeter: they can be applied for measuring both internal and external

    outputs. used for realizing the DC resistance and impedance measurement,

    excitation characteristic test etc.

    6) Binary output: one pair, relay contacts

    Binary input: two pairs with no polarity. It can not only receive protection actingcontacts, but be applied for timer test, pick up value test, with single channel and

    double channels for options.

    7) CT polarity test

    8) Running lamp: its used for the equipment to output indications.

  • 8/9/2019 User Manual T200A en V3.04

    9/55

    T200A Hardware Operation Manual

    9

    Overheat lamp: it will turn on the lamp, alarm and close the output, if the

    operation temperature of the power module inside the equipment exceeds 80.

    Overload lamp: it will turn on the lamp and close the output when an overload of

    current and/or voltage occurs.

    Open-circuit lamp: it will flame if an open circuit is detected at the current output .9) Menu selection, parameter setting and adjustments output control areas.

    10) USB port: it is applied for reading report and debugging the computer in high

    level.

    11) High precision voltage and current output: it gives high precision, adjusted angle

    and frequency, good waveform and transient characteristic and is mainly applied

    for protection tests, auto reclosing, under frequency, and directional power relay

    etc.

    12) Auxiliary DC power supply: its mainly used to provide power supply to protection

    or relay with the load of 0.5A continuously.

    13) High precision current AC/DC I3: DC relay, mA level, AC & DC test

    14) Power socket: used for connecting the power supply cable, and with one

    spared fuse

    15) Earthed terminal: this is used for connecting the T series instrument to the rigid

    grounded point

    16) Breaker: used for controlling the power supply

  • 8/9/2019 User Manual T200A en V3.04

    10/55

    T200A Hardware Operation Manual

    10

    3. Technique parameters

    High power AC current output (I1)

    Range 0.2A~20A 10A~250A

    Accuracy 0.5%

    Output voltage 130V~100V 10V~8V

    Power 2000VA(20A) 2000VA(250A)

    Output current 250A 100A 50A

  • 8/9/2019 User Manual T200A en V3.04

    11/55

    T200A Hardware Operation Manual

    11

    Auxi liary DC voltage output (Aux Udc)

    AC/DC current output (I2)

    AC/DC vol tage output (U2)

    Range 20~240V

    Accuracy 1%

    Power 55W at 110V/110W at 220VLoad time continuous at 0.5A

    Mode AC output DC output

    Range 0~20A 0~20A

    0.2~0.5A 0.5-20A 0.2-0.5A 0.5~20A

    Accuracy 2.5mA 0.5% 2.5mA 0.5%

    Power(20A) 200VA 300WFrequency 20~100Hz

    Phase angle 0~360

    Phase angle accuracy 0.5

    Distortion 1A~20A

  • 8/9/2019 User Manual T200A en V3.04

    12/55

    T200A Hardware Operation Manual

    12

    High precision AC/DC current output (I3)

    Ammeter & Vol tmeter

    Binary inputs

    Binary output

    Mode AC output DC output

    Range 0~200mA 0~200mA

    Accuracy 0.5% 0.5%

    Power(200mA) 3VA 3W

    Frequency 20~100Hz

    Type Ammeter Voltmeter

    Range 0~6A AC/DC 0~600V AC/DC

    Accuracy 1% 1%

    Number 2

    Input characteristics 30-250VDC, or dry contact

    Time resolution 1 ms (0.01~1s) 0.1%

    (1~9999.999s)

    Max. measuring time 9999.999s

    Number 1

    Type Potential free relay contacts

    Break capacity AC Vmax :250V /Imax : 8A/ Pmax : 2000VA

    Break capacity DC Vmax : 250V /Imax : 8A/ Pmax :150W

  • 8/9/2019 User Manual T200A en V3.04

    13/55

    T200A Hardware Operation Manual

    13

    Power supply

    Others

    Nominal input voltage 110/220Vac

    Permissible tolerance -20%~+15%

    Nominal frequency 50/60Hz

    Permissible frequency 45~65Hz

    Operation temperature -5~+50C

    Operation humidity 5~95%, non-condensing

    Weight 23kg

    Dimension (W*H*D) 440*255*255mm

    PC connection USBGround Socket 4 mm banana socket; front side

  • 8/9/2019 User Manual T200A en V3.04

    14/55

    T200A Hardware Operation Manual

    14

    4. Operation guide

    4.1 How to select test item

    The tester has a test unit selection area on the right bottom of the equipment panel, where

    gets 4 buttons: F1, F2, F3 and the menu. Press the MENUbutton in the area, you will

    enter into the main menu directly.

    In the main menu, rotate the ENTERbutton to select certain test item, and then press the

    ENTER button to go into the interface of the test item you selected.

    For sub-menu, you may press the F1 button to go back to last level menu.

  • 8/9/2019 User Manual T200A en V3.04

    15/55

    T200A Hardware Operation Manual

    15

    4.2 How to select variable

    In the test item interface, rotate the ENTER button (clockwise or counter clockwise) to

    select the variable. The variable you selected will be displayed in white characters with

    black background.

    4.3 How to set parameters

    When the variable was selected, press the ENTER button and rotate it clockwise or

    counter-clockwise to change the magnitude of the variable. Select the step of parameter

    changing by using theFast/Fineadjustment button. You may switch the step between0.001, 0.1, 1 and 10 by pressing the button.

    The parameter setting of action unit and manual unit:

    Both before and after test, you may select certain variable to set corresponding

    parameters

    Both before and after test, you may press the Fast/Fine adjustment button to

    change the variable output.

    Other units cant be changed with their parameters as soon as the test starts.

    4.4 How to control output

    The Run and Stopbuttons are applied to control the tester of its output, or to stop it.

  • 8/9/2019 User Manual T200A en V3.04

    16/55

    T200A Hardware Operation Manual

    16

    4.5 Reports view and save

    4.5.1 Report view

    Select the view option in the main menu to go into the report view interface, where you

    may view all saved reports. Here, each page can display 10 reports. With total 3 pages, it

    can save 30 reports at most. 1/3 denotes there have 3 pages and the current page is the

    first page.

    The report with cursor below has test items whose names are listed as following figure in

    their item names.

    4.5.2 Report save

    After the test, you may save current item following the guide on the screen. Both date and

    time will be saved in the report.

  • 8/9/2019 User Manual T200A en V3.04

    17/55

    T200A Hardware Operation Manual

    17

    4.6 System sett ing

    Select the system setting option in the main menu, and then go to its interface, where you

    can set time, volt, freq., off delay.

    Time can be represented by second or cycles.

    Off delayWhen the tester receive a trip or reclose signal from the relay under test, the

    tester will generate the voltage and current continually, until the delay time end.

    Voltdenotes rated voltage value.

    Freq: denotes rated frequency of high precision AC/DC I2, U2, according to rated

    frequency setting codes of electric network.

  • 8/9/2019 User Manual T200A en V3.04

    18/55

    T200A Hardware Operation Manual

    18

    5. Introduction to test function

    5.1. Aux DC

    Mainly provide power supply for protection or relay

    Select theAux DCmenu as above figure shown.

    Set the output voltage valuepress the Run button to output

    The ON/OFFbutton on the panel can control the output voltage,

    Note: a. The aux DC output can be controlled by the ON/OFFbutton, and be outputted

    with other terminals at the same time.

    b. The maximum output current is 0.5A.

  • 8/9/2019 User Manual T200A en V3.04

    19/55

    T200A Hardware Operation Manual

    19

    5.2. Any test

    5.2.1 Manual &Meter

    This unit can output high power AC voltage/current, high power DC voltage, high

    precision voltage/current and display the reading values of voltmeter and ammeter. It can

    realize manual control on the amplitude, phase of AC variables or amplitude of DC

    variables by the step.

    5.2.2 ShotLinear RampPulses Ramp

    It can output high power AC voltage/current, high power DC voltage, high precision

    voltage/current, realize automatic control on amplitude, phase of AC variables andamplitude of DC variables by the step, and record action values, action time automatically.

    There have 3 test methods for your selection.

    Shot

  • 8/9/2019 User Manual T200A en V3.04

    20/55

    T200A Hardware Operation Manual

    20

    Select output variables from the menu: AC-I1 -250A, AC-I1-20A, AC-U1,

    Udc-2.5A, Udc-0.5A, AC/DC-I2, AC/DC-U2, AC/DC-I3

    Set the start value and duration time of variables.

    Press the Run button to output. When the tester receives the binary input of

    protection acting signal and finish recording the action time, the test will stop.

    Linear ramp

    Select output variables from the menu: Udc-0.5A , AC-I2, AC-U2, DC-I2, DC-U2,

    AC-I3, DC-I3

    Set variable, start value, stop value, step and step time.

    Press the Run button to start output, shown as figure. The variable will gradually

    increase on the step from the start value to the stop value. When the tester

    receives the binary input of protection acting signal and finish recording the

    action time, the test will stop.

  • 8/9/2019 User Manual T200A en V3.04

    21/55

    T200A Hardware Operation Manual

    21

    Pulse ramp

    Select output variables from the menu: AC-I2, DC-I2, AC-I3, DC-I3, AC-U2,

    DC-U2 Set start value, stop value, step, step time and interval time.

    Press the Run button to output as above figure shown. The variable will

    gradually increase in the mode of pulse on the step from the start value to the

    stop value. When the tester receives the binary input of protection acting signal

    and finish recording the action time, the test will stop.

  • 8/9/2019 User Manual T200A en V3.04

    22/55

    T200A Hardware Operation Manual

    22

    5.3 Relay test

    5.3.1 Trip time test, Trip time + pulse length test with I2

    There have two states for setting. You can set amplitude and phase for these two

    states, and the tester will count time when entering into the 2nd state.

    Perform tests on the action time in all kinds of over-voltage/current and

    under-voltage/current relays.

    Test process

    1) Select test item.2) Set voltage, current and current harmonics values.

    Set the variable of offset to relay but no-action.

    Set the variable of Test to reliable action of relay undertest.

    Set the values of current harmonics (The 2nd

    and 3rd

    current

  • 8/9/2019 User Manual T200A en V3.04

    23/55

    T200A Hardware Operation Manual

    23

    harmonics)

    3) Test:

    Press theRun button, the tester will start to output under theAC Test. Press the ENTER

    button into the Test and start time counting at the same time. As soon as the tester

    receives the binary input of protection acting signal, the tester will start to record theaction timepulse time.

    This module can also test high power Udc-0.5A and high accuracy of Udc. The testing

    method is the same.

    Example: Time test of DC relay

    1. Wiring

    2. Test process

    Select item Udc-0.5ASet parameterTest starts

  • 8/9/2019 User Manual T200A en V3.04

    24/55

    T200A Hardware Operation Manual

    24

    5.3.2 Pick up test

    a) For high power output, you can manually control the amplitude to change on the

    step.

    b) Nominal voltage and current can manually control the amplitude, phase and

    frequency of AC variables and amplitude of DC variables to change on the step.

    Test process:

    1) Select test item and then go into the action value test unit.

    2) Set voltage and current values.

    3) Press the Run button the tester starts to output based on the setting rotate

    the ENTER button to control the output of the variable you selected as soon

    as the tester receives the binary input of relay acting signal, the tester will start to

    record the action time change the variable to make the relay equipment return

    the record values, and automatically calculate the return coefficient at the sametime, and finally stop the test.

  • 8/9/2019 User Manual T200A en V3.04

    25/55

    T200A Hardware Operation Manual

    25

    5.3.3 Reclosing

    This unit can perform reclosing test .

    There are two states for setting. You can set amplitude and phase for these two

    states.

    During test, you must connect the relays acting contacts and reclosing contacts

    to the binary input terminals of the tester to make sure the correct logic for

    output.

    Time counting definition: pick up, denotes the time of first time tripping; reclosing,

    denotes the time between binary input aand bafter each fault;acctrip, denotes

    the time of second time tripping.

    Test process

    1) Select test item, go into the reclosing unit..

    2) Set voltage and current values of the two states.

    3) Test:

    Press theRunbutton, the tester will start to output under the Constant Fault. Press theENTER button into the Test and start time counting at the same time. As soon as the

    tester receives the binary input of relay acting signal, it will record the acting timepulse

    timeacc trip time

  • 8/9/2019 User Manual T200A en V3.04

    26/55

    T200A Hardware Operation Manual

    26

    5.3.4 Under freq test

    You can set end frequency, df/dt, frequency setting.

    You can have a test on action value, action time, df/dt, under-voltage blocking

    value in under-cycle load-shedding device:

    1) Parameter setting

    Voltage amplitude: it should be larger than the voltage blocking value of

    the relay, unless the voltage blocking value of the protection is under

    test.

    Current amplitude: it should be larger than the current blocking value of

    the relay, unless the current blocking value of the protection is under

    test.

    End frequency: it should be larger than the under-frequency blocking

    value and is suggested to be no less than 45Hz;

    df/dt: it should be less than the df/dt of the protection unless the df/dt of

    relay is under test.

    Frequency setting: it could be settled under-cycle action value, also

    could be actual measuring action frequency.

    2) Description of test process Press the Run button, the tester will output the settled voltage and

    current values with frequency of 50Hz of 5 seconds.

    When the 5s end, the voltage and current frequencies will drop from

    50Hz at df/dt to the end frequency. At the same time, the tester will start

  • 8/9/2019 User Manual T200A en V3.04

    27/55

    T200A Hardware Operation Manual

    27

    to count time when the frequency has dropped to the frequency setting:

    If the relay acts, while the action contacts are connected to the binary

    inputs of tripping, the tester will stop to count time and show the action

    time.

    If the relay doesnt work, it will drop to the end frequency, hold for 30sand then stop the test.

  • 8/9/2019 User Manual T200A en V3.04

    28/55

    T200A Hardware Operation Manual

    28

    5.3.5 Differential test

    This function is designed to test differential relay with independent restraint coil and

    differential coil. The items, such as the trip value, time and differential current tripping

    value under different restraint current, can be tested. Test results can be recorded.

    Test process:

    1) Action value:

    Select test item, and then go into the differential test unit;

    Set the amplitude and phase of I1 and I2. For example:

    I1 for differential current; I2 for restraining current;

    Press theRun button, the tester will start to output based on the settled I1, I2. Rotate the

    ENTER button to change the magnitude of I1 (Id). As soon as the tester receives thebinary input of relay acting signal, press the Stopbutton to stop the test.

    2) Action time:

    Select test item, and then go into the differential test unit.

    Set the amplitude and phase of I1 and I2 that can trigger the relay action.

  • 8/9/2019 User Manual T200A en V3.04

    29/55

    T200A Hardware Operation Manual

    29

    Press the Run button, the tester will start to output based on the settled I1, I2. When the

    tester receives the binary input of relay acting signal and finish recording the action time,

    the test will stop.

  • 8/9/2019 User Manual T200A en V3.04

    30/55

    T200A Hardware Operation Manual

    30

    5.3.6 Harmonic

    This unit can have superposition of 2nd, 3rd, 5th,7th harmonics on the fundamental toexecute the harmonic surge blocking test and harmonic overflux blocking test of

    transformers,

    1) Select test item, and then go into the harmonic restrained unit;

    2) Set parameters.

    Rotate the ENTERbutton to set the amplitudes of fundamental current and

    harmonic current.

    Harmonic coefficienteffective value of harmonic/effective value of

    fundamental100;

    Set U2 values of amplitude and phase

    3) Test process

    Press theRun button, and then the tester will output the recombination current of I2

    fundamental and harmonic. Here, the ratio of harmonic to fundamental is larger than

    the protections settled harmonic restrained coefficient, so the differential protection

    wont work.

  • 8/9/2019 User Manual T200A en V3.04

    31/55

    T200A Hardware Operation Manual

    31

    Rotate the ENTERbutton to decrease the harmonic currents amplitude value till the

    differential relay act.

    The tester will display the harmonic coefficient of acting moment.

  • 8/9/2019 User Manual T200A en V3.04

    32/55

    T200A Hardware Operation Manual

    32

    5.3.7 Synchronism test

    This function is for checking the performance of synchronism relay

    Condition: power supply frequency, 50Hz or 60Hz.

    Connect wires as above figure shown.

    Select the synchronizing test menu as above figure shown.

    Set amplitude and phase of voltages from the menu.

    Press theRun button to output the voltage value, change the phase of voltage, if

    the relay trips, record the corresponding phase angle difference.

  • 8/9/2019 User Manual T200A en V3.04

    33/55

    T200A Hardware Operation Manual

    33

    5.3.8 Directional test

    This function can be realized in the AC test of Pick Up.

    This unit can make the boundary for power direction relay.

    Connect wires as above figure shown.

    Select high precision AC test menu as above figure shown.

    Set amplitude and phase of voltage/current in the non-action zone of power

    direction relay.

    Press the Run button to output voltage and current values. Change the phase to

    make the phase angle of voltage/current move from the non-action zone to the

    action zone. During the protection acting period, mark the boundary I; then

    change the moving direction of phase, which is also moving from non-action

    zone to action zone, then marks the boundary II during the protection acting

    period. Thus, calculate the sensitive angle with these measuring boundaries I

    and II by the software automatically.

  • 8/9/2019 User Manual T200A en V3.04

    34/55

    T200A Hardware Operation Manual

    34

    5.3.9 DC relay, mA level; AC & DC test

    Connect wires as above figure.

    Select Relay testPickupHighprecision DC-I3test menu, shown as above

    figure.

    Set DC current value from the menu.

    Press the Run button to output DC current, adjust DC current, and record

    corresponding DC current values during protection acting.

  • 8/9/2019 User Manual T200A en V3.04

    35/55

    T200A Hardware Operation Manual

    35

    5.3.10 Motor overload test

    This unit can test trip time of motor.

    The output current values can be set in two states, the tester will count time

    when press the ENTER button.

    There are two ways to record the action time. Firstly, as soon as the tester

    receives a single from the relay under test; secondly, the current stop to output,

    In this unit, the max output time of max output current is 120s.

    Test process

    1) Select test item.

    2) Set current values.

    3) The first state output current value should be smaller than trip current value of relay.

    4) The second state output current value should be bigger than trip value of relay, and

    makes the relay act.Press the Run button, the tester will start to output the first state current value. Press

    the ENTERbutton, the state will change into the second state and start time counting at

    the same time. As soon as the tester receives the acting signal from relay or stops to

    output, the tester will record the action time.

  • 8/9/2019 User Manual T200A en V3.04

    36/55

    T200A Hardware Operation Manual

    36

    5.4 CT Test

    5.4.1 Primary side injection

    Connect wires as above figure, and connect the I1 output into the CT primary

    side

    Select high power AC current menu, shown as above figure.

    Select a appropriate current output range

    Set the current value for output

    Press the Run button to output current, check the sampling of protection, or

    action behaviors of relay and switching.

    If the output current has insufficient power, the overload lamp will flame and the

    output will be shut down at the same time.

  • 8/9/2019 User Manual T200A en V3.04

    37/55

    T200A Hardware Operation Manual

    37

    5.4.2 Ratio test

    Connect I1 output to the CT primary side and CT secondary side to the current

    measuring terminal, shown as above figure. Dont make open circuit.

    Select the Ratio 250A menu, shown as above figure.

    Set the current for output, and CT secondary current rating. The software will

    calculate the ratio by the CT secondary current rating automatically.

    Press theRunbutton to output current. The tester will display the current it has

    measured and the ratio that has been calculated.

  • 8/9/2019 User Manual T200A en V3.04

    38/55

    T200A Hardware Operation Manual

    38

    5.4.3 Polarity test

    Employ the method of inputting the pulse voltage at CT primary side to have the

    CT polarity test.

    Connect wires as above figure shown. Please connect the polarity terminals of

    CT primary and secondary sides correctly.

    Press the function button, then the tester will output a voltage pulse. Its not

    necessary to press the function button for a longer time.

    The positive and negative lamps will tell us the TA polarity. If the report is needed to be saved, go to the CT Polarity menu and select the

    CT polarity that has been measured out to save, shown as above figure.

  • 8/9/2019 User Manual T200A en V3.04

    39/55

    T200A Hardware Operation Manual

    39

    5.4.4 Winding resistance test

    Connect wires as above figure shown

    Select the secondary DC Resistance test menu, shown as above figure.

    Set the DC current values for output, and environment temperature.

    Press the Run button to output the DC current, the tester will display the DC

    voltage that has been measured and the secondary DC resistance that has been

    calculated at 75

  • 8/9/2019 User Manual T200A en V3.04

    40/55

    T200A Hardware Operation Manual

    40

    5.4.5 Excitation curve test

    Connect wires as above figure shown

    Select theExcitation Curve test menu, shown as above figure.

    Set the start current value for output

    Press theRun button to output the start current, elevate the current gradually

    and record the corresponding voltages that have been measured and

    corresponding series of test points.

    Note: During the test, the current should be rise gradually and cant be swing up

    and down, which might cause remanence. The existence of remanence will have

    great effects on the measuring results. Once this situation happens, you shouldre-elevate the current to be higher than the original value and then decrease it

    gradually to zero. Repeat foregoing process for one or two times, thus the effect of

    CT remanence can be cured.

  • 8/9/2019 User Manual T200A en V3.04

    41/55

    T200A Hardware Operation Manual

    41

    5.4.6 Secondary impedance test

    Connect wires as above figure shown. Disconnect the connecting sheet inside

    the CT terminal box heading to CT winding.

    Select theManual&Meter menu, shown as above figure.

    Set the current value for output, which is normally the secondary current rating.

    Press the Run button to output current, and the tester will display the voltage

    and secondary impedance value that have been measured.

  • 8/9/2019 User Manual T200A en V3.04

    42/55

    T200A Hardware Operation Manual

    42

    5.5 DC test of operating loop

    Connect wires as above figure shown.

    Select the Manual&Metermenu, shown as above figure.

    Select the DC voltage value from the menu.

    Press the Run button to output the DC voltage, adjust DC voltage value, and

    record the corresponding DC current value at the same time.

    Operation loop test include 2 tests, one is the start performance test to

    relay device, another is the low voltage operating test to trip coil of the

    medium/high voltage breaker,

  • 8/9/2019 User Manual T200A en V3.04

    43/55

    T200A Hardware Operation Manual

    43

    5.6 Timer

    Single channel test

    Double channels test

    Connect wires as above figure shown Select the Timer menu, shown as above figure.

    Set single channel and/or double channels from the menu.

    Press the Run button to start the test. The action time will be measured

    automatically before the test has ended.

  • 8/9/2019 User Manual T200A en V3.04

    44/55

    T200A Hardware Operation Manual

    44

    5.7 Voltage/current measuring function

    Select theManual& Meter menu, shown as above figure.

    This unit could measure internal or external voltage and current, and when youmeasure DC resistance or secondary impedance and CT ratio/excitation curve,

    this measure part have to be in series with/ in parallel with the output

    variable(current or voltage), or take it as a measurement tool to measure

    external variable.

    Press the Run button to start the test, and the test results will be displayed on

    the screen directly.

  • 8/9/2019 User Manual T200A en V3.04

    45/55

    T200A Hardware Operation Manual

    45

    6. T200A Accessories

    This chapter describes the optional equipments and accessories for the T200A test set.

    Please visit the PONOVO Web site www.relaytest.com for up-to-date information.

    Standard accessories

    Item Part No.

    Color coded current cables SAW0001

    Color coded voltage cables SAW0002

    Signal cables SAW0003/4

    Crocodile clips SAW0005/6

    U clamps SAW0007

    Pin clamps SAW0008

    Power cord SAW0009

    Earthing lead SAW0018

    Data cable (USB) SAW0011

    Transportation case SAC0106

    Color coded high current plier SAW0023

  • 8/9/2019 User Manual T200A en V3.04

    46/55

    T200A Hardware Operation Manual

    46

    6.1 Soft Bag for Test Leads

    The T200A Wiring Accessory Package contains the following articles:

    1. Colour coded current cables

    SAW0001 colour coded current cable

    Amount: 1xred, 1xblack

    The current cables to connect the T200A output to other safety sockets of, generally thecurrent parts, voltage and signal tripping.

  • 8/9/2019 User Manual T200A en V3.04

    47/55

    T200A Hardware Operation Manual

    47

    2. Color coded voltage cables

    SAW0002 Colour coded voltage cable

    Amount: 1x red, 1x yellow, 1x green, 1x black

    The voltage cables to connect the T200A output to other safety sockets of, generally the

    voltage parts, current and signal tripping.

    3. Signal Cable

    SAW0003 Signal cables

    Amount: 1xred, 1x yellow, 1x green, 1x blue, 1x brown, 1x purpleIt connects the T200A with other different sockets, generally with signal tripping and

    current/voltage testing.

  • 8/9/2019 User Manual T200A en V3.04

    48/55

    T200A Hardware Operation Manual

    48

    4. Crocodile Clips

    SAW0005 Crocodile clips 10mm SAW0006 Crocodile clips 20mm

    Amount: 2xred, 2xblack, 2xyellow, 2xblue 1xred, 1xblack, 1xyellow, 1xblue

    Crocodile clips for secondary side to connect to pins or screw types.

    5. U Clamps

    SAW0007 U clamps

    Amount: 1x red, 1x black

    It is used to connect test leads with screw type terminals.

    ----------------------------------------------------------------------------------

    Notes:One end of the adapters have no

    insulator, users should make sure there is

    no output during connecting the adapters.

    Users insert the non-safety into the

    terminals and screw it firmly, then connect

    the test lead with the other end.

    -----------------------------------------------------------------------------------

  • 8/9/2019 User Manual T200A en V3.04

    49/55

    T200A Hardware Operation Manual

    49

    6. Pin clamps

    SAW0008 Pin clamps

    Amount: 2xred, 2xblack, 2x yellow, 2x green

    It is used to connect test leads with screw type terminals.

    7. Power Cord

    SAW0009 Power code

    Amount: 1 piece

    Power cord connects the T200A with power supply socket. PONOVO will provide relevant

    plug socket according to different countries. For the plug socket information, please check

    the Chapter 11. Appendix.

  • 8/9/2019 User Manual T200A en V3.04

    50/55

    T200A Hardware Operation Manual

    50

    8. Earthing Lead

    T200A

    SAW0018 Earthing lead

    Specification: 2.5mm4m

    Amount: 1 piece

    Earthing lead connects the T200A with ground to ensure kit safety.

    -------------------------------------------------------------------------------

    Notes:In order to avoid static induction,

    users should connect the T200A with

    ground reliably before testing.

    -------------------------------------------------------------------------------

  • 8/9/2019 User Manual T200A en V3.04

    51/55

    T200A Hardware Operation Manual

    - 51 -

    9. Data cable (USB)

    SAW0011 Data cable (USB)

    Amount: 1 piece

    The data cable connects the T200A with PC for communications.

    10. Color coded high current plier

    SAW0023 Color coded high current plier

    Amount: 1x red, 1x black

    It is used to connect CT primary with T200A to make CT test.

    6.2 Transportation Case

  • 8/9/2019 User Manual T200A en V3.04

    52/55

    T200A Hardware Operation Manual

    - 52 -

    The large-size case with wheels is designed for heavy transport stress with folding hand it

    is made of fireproof materials and smooth rolling rubber tires.

    SAC0106 Transportation case

    Dimension: 550x360x380mm (WxHxD)

    Weight: 10Kg

  • 8/9/2019 User Manual T200A en V3.04

    53/55

    T200A Hardware Operation Manual

    - 53 -

    7. Appendix

    In order to assure PONOVO sockets are used smoothly in foreign countries, PONOVO

    provides the plug sockets to our customers in different countries.

    The followings are the sockets used in different countries.

    1. Plug Type B

    Type B adapter is mainly used in America, Canada and Taiwan etc.

  • 8/9/2019 User Manual T200A en V3.04

    54/55

    T200A Hardware Operation Manual

    - 54 -

    2. Plug Type I Adapter

    The UK type plug is mainly used in United Kingdom, India, Pakistan, Thailand, Malaysia,

    Singapore, New Zealand and Hong Kong etc.

    3. Plug Type L Adapter

    Type L Adapter is mainly used in South Africa and British Standard 15A.