T200A Hardware Operation Manual
1
PONOVO POWER CO., LTD2F, 4Cell, Tower C, In.Do Mansion
No.48A Zhichun Road, Haidian District
Beijing, China (Post Code 100098)
OfficeTEL. +86 (10) 82755151 ext. 8887
FAX +86 (10) 82755257
E-Mail [email protected]
Website www.relaytest.com
T200A
OPERATION MANUAL
VERSION: T200A-AE-3.04
DATE: 08/01/2013
This manual is the publisher of PONOVO POWER CO., LTD. To make any kind of copy of
this manual please contact PONOVO POWER CO., LTD in advance.
This manual represents the technical status for the moment of publishing. The product
information, description and specifications mentioned in the manual do not have any
contact binding force and PONOVO POWER CO., LTD remains the right to make
modifications to the technical specifications and configurations without prior notice.
PONOVO POWER does not take responsibility to the possible error/mistakes in this
manual.
-
8/9/2019 User Manual T200A en V3.04
2/55
T200A Hardware Operation Manual
2
Notes
In order to prevent accumulation of static electricity inside the running tester,
make reliable ground connection via its ground terminal before the test.
Be caution when output voltage is over 36V, this might cause some electric
accident. Keep safety and avoid this situation occurring.
When high current is being outputted, avoid personal injury and the equipment
damage, which is under test.
Never add external voltage and current onto the voltage/current output
terminals of the tester.
Since the tester is a kind of precision electronic equipment, keep a water-proof
and damp-proof environment for it.
Find any abnormal signs during the installation of the tester, please inform
factory immediately and dont fix it by yourself.
-
8/9/2019 User Manual T200A en V3.04
3/55
T200A Hardware Operation Manual
3
Content
1. General Introduction ................................................................................................. 5
2. Panel introduction ..................................................................................................... 8
3. Technique parameters ............................................................................................ 104. Operation guide ...................................................................................................... 14
4.1 How to select test item .................................................................................. 14
4.2 How to select variable ................................................................................... 15
4.3 How to set parameters .................................................................................. 15
4.4 How to control output .................................................................................... 15
4.5 Reports view and save ................................................................................. 16
4.5.1 Report view ......................................................................................... 16
4.5.2 Report save ......................................................................................... 16
4.6 System setting ............................................................................................... 17
5. Introduction to test function .................................................................................... 18
5.1. Aux DC ......................................................................................................... 18
5.2. Any test ......................................................................................................... 19
5.2.1 Manual &Meter .................................................................................... 19
5.2.2 ShotLinear RampPulses Ramp ................................................... 19
5.3 Relay test ...................................................................................................... 22
5.3.1 Trip time test, Trip time + pulse length test with I2 ............................. 22
5.3.2 Pick up test ......................................................................................... 24
5.3.3 Reclosing ............................................................................................ 25
5.3.4 Under freq test .................................................................................... 265.3.5 Differential test .................................................................................... 28
5.3.6 Harmonic ............................................................................................. 30
5.3.7 Synchronism test ................................................................................ 32
5.3.8 Directional test .................................................................................... 33
5.3.9 DC relay, mA level; AC & DC test ....................................................... 34
5.3.10 Motor overload test ........................................................................... 35
5.4 CT Test....................................................................................................... 36
5.4.1 Primary side injection .......................................................................... 36
5.4.2 Ratio test ............................................................................................. 37
5.4.3 Polarity test ......................................................................................... 38
5.4.4 Winding resistance test ....................................................................... 39
5.4.5 Excitation curve test ............................................................................ 40
5.4.6 Secondary impedance test ................................................................. 41
5.5 DC test of operating loop .............................................................................. 42
-
8/9/2019 User Manual T200A en V3.04
4/55
T200A Hardware Operation Manual
4
5.6 Timer.............................................................................................................. 43
5.7 Voltage/current measuring function .............................................................. 44
6. T200A Accessories ................................................................................................. 45
6.1 Soft Bag for Test Leads ................................................................................. 46
6.2 Transportation Case ................................................................................. - 51 -7. Appendix ............................................................................................................ - 53 -
-
8/9/2019 User Manual T200A en V3.04
5/55
T200A Hardware Operation Manual
5
1. General Introduct ion
The T500 series single phase relay test kits are designed for easy and safe test of
different type of relays. The powerful 250A/2000VA current source can be used to test all
kinds of current relays, including high burden relay and CT. The AC/DC current and/or
voltage sources allow phase angle and frequency to be adjusted smoothly. This makes it
possible to precisely test directional and frequency relay. The kit uses advanced switching
power amplifier to replace the traditional transformer, thus avoiding the dangerous high
voltage across the current output.
T500 series universal tester offers 2 types of products: T200A/T1000.
The following is the introduction of T200A.
Hardware configuration
High power AC current I1 0.2-250A
High power AC voltage U1 10-500V
High power DC voltage Udc 10-300V
High precision AC/DC current I2 0-20A
High precision AC/DC voltage U2 0-120V
High precision AC/DC low current I3 0-200mA
Auxiliary DC power supply 20-240V/55W110V/110W(220V)
AC/DC voltmeter 0-600V
AC/DC ammeter 0-6A
Binary input 2
Binary output 1
-
8/9/2019 User Manual T200A en V3.04
6/55
T200A Hardware Operation Manual
6
T200A Test Functions
SN. Module
type
Functions Application relay types
1. Relay test Users can select any of thefollowing test content to operate.
Trip time test, trip time and
pulse length test with I1, U1, I2,
U2, I3, Udc
Pick up test
Reclosing
Under frequency test
Differential test
Harmonics test
Synchronism test
Directional test
DC relay, mA level; AC & DC
test
Motor overload test
Overcurrent relaysUndercurrent relays
Overvoltage relays
Undervoltage relays
Motor overload protection (I2)
Automatic reclosing devices
Thermal relays
df/dt relay(U2&I2)
Time-delay relays (U2&I2)
Timer(Binary input)
Harmonic brake test
Differential relay
Synchronism relay
2. Any Test Manually control the amplitude,
phase of AC variables and also
high power Udc.
Shot, linear ramp, pulse ramp
start relay device test when
Udc being the power supply
low voltage operate test on trip
coil of intermedia\high voltagebreaker when Udc being the
control power resource
3. Timer Automatically test Action time measurement
4. CT test Primary/secondary side
injectionUse manual control
Ratio test
Polarity test
Winding resistance test
Excitation curve test
Basic test functions for CT
-
8/9/2019 User Manual T200A en V3.04
7/55
T200A Hardware Operation Manual
7
5. Report Reviewing the report 30 reports can be saved and 10
reports can be displayed in each
page.
6. System
setting
Set rated voltage and frequency of
the system being tested
/
7. Aux DC Provide power supply Provide power supply to relay or
other equipment
8. PC control The test results can be transferred
to external PC via USB port.
Optional
-
8/9/2019 User Manual T200A en V3.04
8/55
T200A Hardware Operation Manual
8
2. Panel introduct ion
1) High power output (I1): its mainly applied for CT test and primary side injection.
2) High power output(UDC): 10300V, its mainly applied for DC act time testing
and low voltage operation test to the tripping coil on intermedia/high voltage
breaker.
3) High power output (U1): its mainly applied for CT test and primary side injection.
4) AC/DC voltmeter: they can be applied for measuring both internal and external
outputs. used for realizing the DC resistance and impedance measurement,
excitation characteristic test etc.
5) AC/DC ammeter: they can be applied for measuring both internal and external
outputs. used for realizing the DC resistance and impedance measurement,
excitation characteristic test etc.
6) Binary output: one pair, relay contacts
Binary input: two pairs with no polarity. It can not only receive protection actingcontacts, but be applied for timer test, pick up value test, with single channel and
double channels for options.
7) CT polarity test
8) Running lamp: its used for the equipment to output indications.
-
8/9/2019 User Manual T200A en V3.04
9/55
T200A Hardware Operation Manual
9
Overheat lamp: it will turn on the lamp, alarm and close the output, if the
operation temperature of the power module inside the equipment exceeds 80.
Overload lamp: it will turn on the lamp and close the output when an overload of
current and/or voltage occurs.
Open-circuit lamp: it will flame if an open circuit is detected at the current output .9) Menu selection, parameter setting and adjustments output control areas.
10) USB port: it is applied for reading report and debugging the computer in high
level.
11) High precision voltage and current output: it gives high precision, adjusted angle
and frequency, good waveform and transient characteristic and is mainly applied
for protection tests, auto reclosing, under frequency, and directional power relay
etc.
12) Auxiliary DC power supply: its mainly used to provide power supply to protection
or relay with the load of 0.5A continuously.
13) High precision current AC/DC I3: DC relay, mA level, AC & DC test
14) Power socket: used for connecting the power supply cable, and with one
spared fuse
15) Earthed terminal: this is used for connecting the T series instrument to the rigid
grounded point
16) Breaker: used for controlling the power supply
-
8/9/2019 User Manual T200A en V3.04
10/55
T200A Hardware Operation Manual
10
3. Technique parameters
High power AC current output (I1)
Range 0.2A~20A 10A~250A
Accuracy 0.5%
Output voltage 130V~100V 10V~8V
Power 2000VA(20A) 2000VA(250A)
Output current 250A 100A 50A
-
8/9/2019 User Manual T200A en V3.04
11/55
T200A Hardware Operation Manual
11
Auxi liary DC voltage output (Aux Udc)
AC/DC current output (I2)
AC/DC vol tage output (U2)
Range 20~240V
Accuracy 1%
Power 55W at 110V/110W at 220VLoad time continuous at 0.5A
Mode AC output DC output
Range 0~20A 0~20A
0.2~0.5A 0.5-20A 0.2-0.5A 0.5~20A
Accuracy 2.5mA 0.5% 2.5mA 0.5%
Power(20A) 200VA 300WFrequency 20~100Hz
Phase angle 0~360
Phase angle accuracy 0.5
Distortion 1A~20A
-
8/9/2019 User Manual T200A en V3.04
12/55
T200A Hardware Operation Manual
12
High precision AC/DC current output (I3)
Ammeter & Vol tmeter
Binary inputs
Binary output
Mode AC output DC output
Range 0~200mA 0~200mA
Accuracy 0.5% 0.5%
Power(200mA) 3VA 3W
Frequency 20~100Hz
Type Ammeter Voltmeter
Range 0~6A AC/DC 0~600V AC/DC
Accuracy 1% 1%
Number 2
Input characteristics 30-250VDC, or dry contact
Time resolution 1 ms (0.01~1s) 0.1%
(1~9999.999s)
Max. measuring time 9999.999s
Number 1
Type Potential free relay contacts
Break capacity AC Vmax :250V /Imax : 8A/ Pmax : 2000VA
Break capacity DC Vmax : 250V /Imax : 8A/ Pmax :150W
-
8/9/2019 User Manual T200A en V3.04
13/55
T200A Hardware Operation Manual
13
Power supply
Others
Nominal input voltage 110/220Vac
Permissible tolerance -20%~+15%
Nominal frequency 50/60Hz
Permissible frequency 45~65Hz
Operation temperature -5~+50C
Operation humidity 5~95%, non-condensing
Weight 23kg
Dimension (W*H*D) 440*255*255mm
PC connection USBGround Socket 4 mm banana socket; front side
-
8/9/2019 User Manual T200A en V3.04
14/55
T200A Hardware Operation Manual
14
4. Operation guide
4.1 How to select test item
The tester has a test unit selection area on the right bottom of the equipment panel, where
gets 4 buttons: F1, F2, F3 and the menu. Press the MENUbutton in the area, you will
enter into the main menu directly.
In the main menu, rotate the ENTERbutton to select certain test item, and then press the
ENTER button to go into the interface of the test item you selected.
For sub-menu, you may press the F1 button to go back to last level menu.
-
8/9/2019 User Manual T200A en V3.04
15/55
T200A Hardware Operation Manual
15
4.2 How to select variable
In the test item interface, rotate the ENTER button (clockwise or counter clockwise) to
select the variable. The variable you selected will be displayed in white characters with
black background.
4.3 How to set parameters
When the variable was selected, press the ENTER button and rotate it clockwise or
counter-clockwise to change the magnitude of the variable. Select the step of parameter
changing by using theFast/Fineadjustment button. You may switch the step between0.001, 0.1, 1 and 10 by pressing the button.
The parameter setting of action unit and manual unit:
Both before and after test, you may select certain variable to set corresponding
parameters
Both before and after test, you may press the Fast/Fine adjustment button to
change the variable output.
Other units cant be changed with their parameters as soon as the test starts.
4.4 How to control output
The Run and Stopbuttons are applied to control the tester of its output, or to stop it.
-
8/9/2019 User Manual T200A en V3.04
16/55
T200A Hardware Operation Manual
16
4.5 Reports view and save
4.5.1 Report view
Select the view option in the main menu to go into the report view interface, where you
may view all saved reports. Here, each page can display 10 reports. With total 3 pages, it
can save 30 reports at most. 1/3 denotes there have 3 pages and the current page is the
first page.
The report with cursor below has test items whose names are listed as following figure in
their item names.
4.5.2 Report save
After the test, you may save current item following the guide on the screen. Both date and
time will be saved in the report.
-
8/9/2019 User Manual T200A en V3.04
17/55
T200A Hardware Operation Manual
17
4.6 System sett ing
Select the system setting option in the main menu, and then go to its interface, where you
can set time, volt, freq., off delay.
Time can be represented by second or cycles.
Off delayWhen the tester receive a trip or reclose signal from the relay under test, the
tester will generate the voltage and current continually, until the delay time end.
Voltdenotes rated voltage value.
Freq: denotes rated frequency of high precision AC/DC I2, U2, according to rated
frequency setting codes of electric network.
-
8/9/2019 User Manual T200A en V3.04
18/55
T200A Hardware Operation Manual
18
5. Introduction to test function
5.1. Aux DC
Mainly provide power supply for protection or relay
Select theAux DCmenu as above figure shown.
Set the output voltage valuepress the Run button to output
The ON/OFFbutton on the panel can control the output voltage,
Note: a. The aux DC output can be controlled by the ON/OFFbutton, and be outputted
with other terminals at the same time.
b. The maximum output current is 0.5A.
-
8/9/2019 User Manual T200A en V3.04
19/55
T200A Hardware Operation Manual
19
5.2. Any test
5.2.1 Manual &Meter
This unit can output high power AC voltage/current, high power DC voltage, high
precision voltage/current and display the reading values of voltmeter and ammeter. It can
realize manual control on the amplitude, phase of AC variables or amplitude of DC
variables by the step.
5.2.2 ShotLinear RampPulses Ramp
It can output high power AC voltage/current, high power DC voltage, high precision
voltage/current, realize automatic control on amplitude, phase of AC variables andamplitude of DC variables by the step, and record action values, action time automatically.
There have 3 test methods for your selection.
Shot
-
8/9/2019 User Manual T200A en V3.04
20/55
T200A Hardware Operation Manual
20
Select output variables from the menu: AC-I1 -250A, AC-I1-20A, AC-U1,
Udc-2.5A, Udc-0.5A, AC/DC-I2, AC/DC-U2, AC/DC-I3
Set the start value and duration time of variables.
Press the Run button to output. When the tester receives the binary input of
protection acting signal and finish recording the action time, the test will stop.
Linear ramp
Select output variables from the menu: Udc-0.5A , AC-I2, AC-U2, DC-I2, DC-U2,
AC-I3, DC-I3
Set variable, start value, stop value, step and step time.
Press the Run button to start output, shown as figure. The variable will gradually
increase on the step from the start value to the stop value. When the tester
receives the binary input of protection acting signal and finish recording the
action time, the test will stop.
-
8/9/2019 User Manual T200A en V3.04
21/55
T200A Hardware Operation Manual
21
Pulse ramp
Select output variables from the menu: AC-I2, DC-I2, AC-I3, DC-I3, AC-U2,
DC-U2 Set start value, stop value, step, step time and interval time.
Press the Run button to output as above figure shown. The variable will
gradually increase in the mode of pulse on the step from the start value to the
stop value. When the tester receives the binary input of protection acting signal
and finish recording the action time, the test will stop.
-
8/9/2019 User Manual T200A en V3.04
22/55
T200A Hardware Operation Manual
22
5.3 Relay test
5.3.1 Trip time test, Trip time + pulse length test with I2
There have two states for setting. You can set amplitude and phase for these two
states, and the tester will count time when entering into the 2nd state.
Perform tests on the action time in all kinds of over-voltage/current and
under-voltage/current relays.
Test process
1) Select test item.2) Set voltage, current and current harmonics values.
Set the variable of offset to relay but no-action.
Set the variable of Test to reliable action of relay undertest.
Set the values of current harmonics (The 2nd
and 3rd
current
-
8/9/2019 User Manual T200A en V3.04
23/55
T200A Hardware Operation Manual
23
harmonics)
3) Test:
Press theRun button, the tester will start to output under theAC Test. Press the ENTER
button into the Test and start time counting at the same time. As soon as the tester
receives the binary input of protection acting signal, the tester will start to record theaction timepulse time.
This module can also test high power Udc-0.5A and high accuracy of Udc. The testing
method is the same.
Example: Time test of DC relay
1. Wiring
2. Test process
Select item Udc-0.5ASet parameterTest starts
-
8/9/2019 User Manual T200A en V3.04
24/55
T200A Hardware Operation Manual
24
5.3.2 Pick up test
a) For high power output, you can manually control the amplitude to change on the
step.
b) Nominal voltage and current can manually control the amplitude, phase and
frequency of AC variables and amplitude of DC variables to change on the step.
Test process:
1) Select test item and then go into the action value test unit.
2) Set voltage and current values.
3) Press the Run button the tester starts to output based on the setting rotate
the ENTER button to control the output of the variable you selected as soon
as the tester receives the binary input of relay acting signal, the tester will start to
record the action time change the variable to make the relay equipment return
the record values, and automatically calculate the return coefficient at the sametime, and finally stop the test.
-
8/9/2019 User Manual T200A en V3.04
25/55
T200A Hardware Operation Manual
25
5.3.3 Reclosing
This unit can perform reclosing test .
There are two states for setting. You can set amplitude and phase for these two
states.
During test, you must connect the relays acting contacts and reclosing contacts
to the binary input terminals of the tester to make sure the correct logic for
output.
Time counting definition: pick up, denotes the time of first time tripping; reclosing,
denotes the time between binary input aand bafter each fault;acctrip, denotes
the time of second time tripping.
Test process
1) Select test item, go into the reclosing unit..
2) Set voltage and current values of the two states.
3) Test:
Press theRunbutton, the tester will start to output under the Constant Fault. Press theENTER button into the Test and start time counting at the same time. As soon as the
tester receives the binary input of relay acting signal, it will record the acting timepulse
timeacc trip time
-
8/9/2019 User Manual T200A en V3.04
26/55
T200A Hardware Operation Manual
26
5.3.4 Under freq test
You can set end frequency, df/dt, frequency setting.
You can have a test on action value, action time, df/dt, under-voltage blocking
value in under-cycle load-shedding device:
1) Parameter setting
Voltage amplitude: it should be larger than the voltage blocking value of
the relay, unless the voltage blocking value of the protection is under
test.
Current amplitude: it should be larger than the current blocking value of
the relay, unless the current blocking value of the protection is under
test.
End frequency: it should be larger than the under-frequency blocking
value and is suggested to be no less than 45Hz;
df/dt: it should be less than the df/dt of the protection unless the df/dt of
relay is under test.
Frequency setting: it could be settled under-cycle action value, also
could be actual measuring action frequency.
2) Description of test process Press the Run button, the tester will output the settled voltage and
current values with frequency of 50Hz of 5 seconds.
When the 5s end, the voltage and current frequencies will drop from
50Hz at df/dt to the end frequency. At the same time, the tester will start
-
8/9/2019 User Manual T200A en V3.04
27/55
T200A Hardware Operation Manual
27
to count time when the frequency has dropped to the frequency setting:
If the relay acts, while the action contacts are connected to the binary
inputs of tripping, the tester will stop to count time and show the action
time.
If the relay doesnt work, it will drop to the end frequency, hold for 30sand then stop the test.
-
8/9/2019 User Manual T200A en V3.04
28/55
T200A Hardware Operation Manual
28
5.3.5 Differential test
This function is designed to test differential relay with independent restraint coil and
differential coil. The items, such as the trip value, time and differential current tripping
value under different restraint current, can be tested. Test results can be recorded.
Test process:
1) Action value:
Select test item, and then go into the differential test unit;
Set the amplitude and phase of I1 and I2. For example:
I1 for differential current; I2 for restraining current;
Press theRun button, the tester will start to output based on the settled I1, I2. Rotate the
ENTER button to change the magnitude of I1 (Id). As soon as the tester receives thebinary input of relay acting signal, press the Stopbutton to stop the test.
2) Action time:
Select test item, and then go into the differential test unit.
Set the amplitude and phase of I1 and I2 that can trigger the relay action.
-
8/9/2019 User Manual T200A en V3.04
29/55
T200A Hardware Operation Manual
29
Press the Run button, the tester will start to output based on the settled I1, I2. When the
tester receives the binary input of relay acting signal and finish recording the action time,
the test will stop.
-
8/9/2019 User Manual T200A en V3.04
30/55
T200A Hardware Operation Manual
30
5.3.6 Harmonic
This unit can have superposition of 2nd, 3rd, 5th,7th harmonics on the fundamental toexecute the harmonic surge blocking test and harmonic overflux blocking test of
transformers,
1) Select test item, and then go into the harmonic restrained unit;
2) Set parameters.
Rotate the ENTERbutton to set the amplitudes of fundamental current and
harmonic current.
Harmonic coefficienteffective value of harmonic/effective value of
fundamental100;
Set U2 values of amplitude and phase
3) Test process
Press theRun button, and then the tester will output the recombination current of I2
fundamental and harmonic. Here, the ratio of harmonic to fundamental is larger than
the protections settled harmonic restrained coefficient, so the differential protection
wont work.
-
8/9/2019 User Manual T200A en V3.04
31/55
T200A Hardware Operation Manual
31
Rotate the ENTERbutton to decrease the harmonic currents amplitude value till the
differential relay act.
The tester will display the harmonic coefficient of acting moment.
-
8/9/2019 User Manual T200A en V3.04
32/55
T200A Hardware Operation Manual
32
5.3.7 Synchronism test
This function is for checking the performance of synchronism relay
Condition: power supply frequency, 50Hz or 60Hz.
Connect wires as above figure shown.
Select the synchronizing test menu as above figure shown.
Set amplitude and phase of voltages from the menu.
Press theRun button to output the voltage value, change the phase of voltage, if
the relay trips, record the corresponding phase angle difference.
-
8/9/2019 User Manual T200A en V3.04
33/55
T200A Hardware Operation Manual
33
5.3.8 Directional test
This function can be realized in the AC test of Pick Up.
This unit can make the boundary for power direction relay.
Connect wires as above figure shown.
Select high precision AC test menu as above figure shown.
Set amplitude and phase of voltage/current in the non-action zone of power
direction relay.
Press the Run button to output voltage and current values. Change the phase to
make the phase angle of voltage/current move from the non-action zone to the
action zone. During the protection acting period, mark the boundary I; then
change the moving direction of phase, which is also moving from non-action
zone to action zone, then marks the boundary II during the protection acting
period. Thus, calculate the sensitive angle with these measuring boundaries I
and II by the software automatically.
-
8/9/2019 User Manual T200A en V3.04
34/55
T200A Hardware Operation Manual
34
5.3.9 DC relay, mA level; AC & DC test
Connect wires as above figure.
Select Relay testPickupHighprecision DC-I3test menu, shown as above
figure.
Set DC current value from the menu.
Press the Run button to output DC current, adjust DC current, and record
corresponding DC current values during protection acting.
-
8/9/2019 User Manual T200A en V3.04
35/55
T200A Hardware Operation Manual
35
5.3.10 Motor overload test
This unit can test trip time of motor.
The output current values can be set in two states, the tester will count time
when press the ENTER button.
There are two ways to record the action time. Firstly, as soon as the tester
receives a single from the relay under test; secondly, the current stop to output,
In this unit, the max output time of max output current is 120s.
Test process
1) Select test item.
2) Set current values.
3) The first state output current value should be smaller than trip current value of relay.
4) The second state output current value should be bigger than trip value of relay, and
makes the relay act.Press the Run button, the tester will start to output the first state current value. Press
the ENTERbutton, the state will change into the second state and start time counting at
the same time. As soon as the tester receives the acting signal from relay or stops to
output, the tester will record the action time.
-
8/9/2019 User Manual T200A en V3.04
36/55
T200A Hardware Operation Manual
36
5.4 CT Test
5.4.1 Primary side injection
Connect wires as above figure, and connect the I1 output into the CT primary
side
Select high power AC current menu, shown as above figure.
Select a appropriate current output range
Set the current value for output
Press the Run button to output current, check the sampling of protection, or
action behaviors of relay and switching.
If the output current has insufficient power, the overload lamp will flame and the
output will be shut down at the same time.
-
8/9/2019 User Manual T200A en V3.04
37/55
T200A Hardware Operation Manual
37
5.4.2 Ratio test
Connect I1 output to the CT primary side and CT secondary side to the current
measuring terminal, shown as above figure. Dont make open circuit.
Select the Ratio 250A menu, shown as above figure.
Set the current for output, and CT secondary current rating. The software will
calculate the ratio by the CT secondary current rating automatically.
Press theRunbutton to output current. The tester will display the current it has
measured and the ratio that has been calculated.
-
8/9/2019 User Manual T200A en V3.04
38/55
T200A Hardware Operation Manual
38
5.4.3 Polarity test
Employ the method of inputting the pulse voltage at CT primary side to have the
CT polarity test.
Connect wires as above figure shown. Please connect the polarity terminals of
CT primary and secondary sides correctly.
Press the function button, then the tester will output a voltage pulse. Its not
necessary to press the function button for a longer time.
The positive and negative lamps will tell us the TA polarity. If the report is needed to be saved, go to the CT Polarity menu and select the
CT polarity that has been measured out to save, shown as above figure.
-
8/9/2019 User Manual T200A en V3.04
39/55
T200A Hardware Operation Manual
39
5.4.4 Winding resistance test
Connect wires as above figure shown
Select the secondary DC Resistance test menu, shown as above figure.
Set the DC current values for output, and environment temperature.
Press the Run button to output the DC current, the tester will display the DC
voltage that has been measured and the secondary DC resistance that has been
calculated at 75
-
8/9/2019 User Manual T200A en V3.04
40/55
T200A Hardware Operation Manual
40
5.4.5 Excitation curve test
Connect wires as above figure shown
Select theExcitation Curve test menu, shown as above figure.
Set the start current value for output
Press theRun button to output the start current, elevate the current gradually
and record the corresponding voltages that have been measured and
corresponding series of test points.
Note: During the test, the current should be rise gradually and cant be swing up
and down, which might cause remanence. The existence of remanence will have
great effects on the measuring results. Once this situation happens, you shouldre-elevate the current to be higher than the original value and then decrease it
gradually to zero. Repeat foregoing process for one or two times, thus the effect of
CT remanence can be cured.
-
8/9/2019 User Manual T200A en V3.04
41/55
T200A Hardware Operation Manual
41
5.4.6 Secondary impedance test
Connect wires as above figure shown. Disconnect the connecting sheet inside
the CT terminal box heading to CT winding.
Select theManual&Meter menu, shown as above figure.
Set the current value for output, which is normally the secondary current rating.
Press the Run button to output current, and the tester will display the voltage
and secondary impedance value that have been measured.
-
8/9/2019 User Manual T200A en V3.04
42/55
T200A Hardware Operation Manual
42
5.5 DC test of operating loop
Connect wires as above figure shown.
Select the Manual&Metermenu, shown as above figure.
Select the DC voltage value from the menu.
Press the Run button to output the DC voltage, adjust DC voltage value, and
record the corresponding DC current value at the same time.
Operation loop test include 2 tests, one is the start performance test to
relay device, another is the low voltage operating test to trip coil of the
medium/high voltage breaker,
-
8/9/2019 User Manual T200A en V3.04
43/55
T200A Hardware Operation Manual
43
5.6 Timer
Single channel test
Double channels test
Connect wires as above figure shown Select the Timer menu, shown as above figure.
Set single channel and/or double channels from the menu.
Press the Run button to start the test. The action time will be measured
automatically before the test has ended.
-
8/9/2019 User Manual T200A en V3.04
44/55
T200A Hardware Operation Manual
44
5.7 Voltage/current measuring function
Select theManual& Meter menu, shown as above figure.
This unit could measure internal or external voltage and current, and when youmeasure DC resistance or secondary impedance and CT ratio/excitation curve,
this measure part have to be in series with/ in parallel with the output
variable(current or voltage), or take it as a measurement tool to measure
external variable.
Press the Run button to start the test, and the test results will be displayed on
the screen directly.
-
8/9/2019 User Manual T200A en V3.04
45/55
T200A Hardware Operation Manual
45
6. T200A Accessories
This chapter describes the optional equipments and accessories for the T200A test set.
Please visit the PONOVO Web site www.relaytest.com for up-to-date information.
Standard accessories
Item Part No.
Color coded current cables SAW0001
Color coded voltage cables SAW0002
Signal cables SAW0003/4
Crocodile clips SAW0005/6
U clamps SAW0007
Pin clamps SAW0008
Power cord SAW0009
Earthing lead SAW0018
Data cable (USB) SAW0011
Transportation case SAC0106
Color coded high current plier SAW0023
-
8/9/2019 User Manual T200A en V3.04
46/55
T200A Hardware Operation Manual
46
6.1 Soft Bag for Test Leads
The T200A Wiring Accessory Package contains the following articles:
1. Colour coded current cables
SAW0001 colour coded current cable
Amount: 1xred, 1xblack
The current cables to connect the T200A output to other safety sockets of, generally thecurrent parts, voltage and signal tripping.
-
8/9/2019 User Manual T200A en V3.04
47/55
T200A Hardware Operation Manual
47
2. Color coded voltage cables
SAW0002 Colour coded voltage cable
Amount: 1x red, 1x yellow, 1x green, 1x black
The voltage cables to connect the T200A output to other safety sockets of, generally the
voltage parts, current and signal tripping.
3. Signal Cable
SAW0003 Signal cables
Amount: 1xred, 1x yellow, 1x green, 1x blue, 1x brown, 1x purpleIt connects the T200A with other different sockets, generally with signal tripping and
current/voltage testing.
-
8/9/2019 User Manual T200A en V3.04
48/55
T200A Hardware Operation Manual
48
4. Crocodile Clips
SAW0005 Crocodile clips 10mm SAW0006 Crocodile clips 20mm
Amount: 2xred, 2xblack, 2xyellow, 2xblue 1xred, 1xblack, 1xyellow, 1xblue
Crocodile clips for secondary side to connect to pins or screw types.
5. U Clamps
SAW0007 U clamps
Amount: 1x red, 1x black
It is used to connect test leads with screw type terminals.
----------------------------------------------------------------------------------
Notes:One end of the adapters have no
insulator, users should make sure there is
no output during connecting the adapters.
Users insert the non-safety into the
terminals and screw it firmly, then connect
the test lead with the other end.
-----------------------------------------------------------------------------------
-
8/9/2019 User Manual T200A en V3.04
49/55
T200A Hardware Operation Manual
49
6. Pin clamps
SAW0008 Pin clamps
Amount: 2xred, 2xblack, 2x yellow, 2x green
It is used to connect test leads with screw type terminals.
7. Power Cord
SAW0009 Power code
Amount: 1 piece
Power cord connects the T200A with power supply socket. PONOVO will provide relevant
plug socket according to different countries. For the plug socket information, please check
the Chapter 11. Appendix.
-
8/9/2019 User Manual T200A en V3.04
50/55
T200A Hardware Operation Manual
50
8. Earthing Lead
T200A
SAW0018 Earthing lead
Specification: 2.5mm4m
Amount: 1 piece
Earthing lead connects the T200A with ground to ensure kit safety.
-------------------------------------------------------------------------------
Notes:In order to avoid static induction,
users should connect the T200A with
ground reliably before testing.
-------------------------------------------------------------------------------
-
8/9/2019 User Manual T200A en V3.04
51/55
T200A Hardware Operation Manual
- 51 -
9. Data cable (USB)
SAW0011 Data cable (USB)
Amount: 1 piece
The data cable connects the T200A with PC for communications.
10. Color coded high current plier
SAW0023 Color coded high current plier
Amount: 1x red, 1x black
It is used to connect CT primary with T200A to make CT test.
6.2 Transportation Case
-
8/9/2019 User Manual T200A en V3.04
52/55
T200A Hardware Operation Manual
- 52 -
The large-size case with wheels is designed for heavy transport stress with folding hand it
is made of fireproof materials and smooth rolling rubber tires.
SAC0106 Transportation case
Dimension: 550x360x380mm (WxHxD)
Weight: 10Kg
-
8/9/2019 User Manual T200A en V3.04
53/55
T200A Hardware Operation Manual
- 53 -
7. Appendix
In order to assure PONOVO sockets are used smoothly in foreign countries, PONOVO
provides the plug sockets to our customers in different countries.
The followings are the sockets used in different countries.
1. Plug Type B
Type B adapter is mainly used in America, Canada and Taiwan etc.
-
8/9/2019 User Manual T200A en V3.04
54/55
T200A Hardware Operation Manual
- 54 -
2. Plug Type I Adapter
The UK type plug is mainly used in United Kingdom, India, Pakistan, Thailand, Malaysia,
Singapore, New Zealand and Hong Kong etc.
3. Plug Type L Adapter
Type L Adapter is mainly used in South Africa and British Standard 15A.
-
8/9/2019 User Manual T200A en V3.04
55/55
T200A Hardware Operation Manual
4. Plug Type N Adapter
This adapter is mainly used in Italy.
5. Type G Adapter