  • User Manual V4.2

    User Manual -Installation -Operation

    Omniksol-1k-TL Omniksol-1.5k-TL Omniksol-2k-TL

    Omnik New Energy Co.,ltd

  • User Manual V4.2

    1

    Catalog 1. Notes on this manual ....................................................................................................................................... 3

    1.1 Scope of Validation ...................................................................................................................................... 3

    1.2 Symbols Used ............................................................................................................................................. 3

    1.3 Target Group ............................................................................................................................................... 4

    2. Preparation ........................................................................................................................................................ 5

    2.1 Safety Instructions ....................................................................................................................................... 5

    2.2 Explanations of Symbols on Inverter ........................................................................................................... 6

    3. Product Information ......................................................................................................................................... 8

    3.1 Overview ...................................................................................................................................................... 8

    3.2 Major Characteristics ................................................................................................................................... 9

    3.3 Datasheet ..................................................................................................................................................10

    4. Packing checklist ............................................................................................................................................13

    4.1 Assembly parts ..........................................................................................................................................13

    4.2 Product Appearance ..................................................................................................................................14

    4.3 Product Identification .................................................................................................................................15

    4.4 Further Information ....................................................................................................................................15

    5. Installation .......................................................................................................................................................16

    5.1 Safety.........................................................................................................................................................16

    5.2 Mounting Instructions ................................................................................................................................16

    5.3 Safety Clearance .......................................................................................................................................17

    5.4 Mounting Procedure ..................................................................................................................................18

    5.4.1 Mounting with bracket ........................................................................................................................18

    5.4.2 Mounting without bracket ...................................................................................................................20

    5.5 Safety lock .................................................................................................................................................22

    5.5.1 Safety lock with the wall mounting bracket .................................................................................22

    5.5.2 Safety lock without the wall mounting bracket ............................................................................22

    6. Electrical Connection .....................................................................................................................................23

    6.1 Safety.........................................................................................................................................................23

    6.2 Overview of Connection Area ....................................................................................................................24

    6.3 AC Side Connection ..................................................................................................................................25

    6.4 DC Side Connection ..................................................................................................................................27

    6.5 Communication and Monitoring Device .....................................................................................................32

    7. Display .............................................................................................................................................................33

    7.1 LCD Panel .................................................................................................................................................33

    7.2 LCD Display ...............................................................................................................................................34

    7.3 Set Language ............................................................................................................................................36

    7.4 Instructions of Safety Standard selection when power-up ........................................................................37

    7.5 State Information .......................................................................................................................................39

  • User Manual V4.2

    2

    8. Recycling and Disposal .................................................................................................................................40

    9. Troubleshooting .............................................................................................................................................41

    10. Abbreviation ....................................................................................................................................................42

    11. Contact .............................................................................................................................................................43

  • User Manual V4.2

    3

    1. Notes on this manual

    1.1 Scope of Validation The main purpose of this Users Manual is to provide instructions and detailed procedures for

    installing, operating, maintaining, and troubleshooting the following three types of Omnik New

    Energy-Solar Inverters:

    Omniksol-1k-TL

    Omniksol-1.5k-TL

    Omniksol-2k-TL

    Please keep this user manual all time available in case of emergency.

    1.2 Symbols Used

    DANGER

    DANGER indicates a hazardous situation which, if not

    avoided, will result in death or serious injury.

    WARNING

    WARNING indicates a hazardous situation which, if not avoided, can result in death or serious injury or moderate injury.

    CAUTION

    CAUTION indicates a hazardous condition which, if not

    avoided, can result in minor or moderate injury.

    or moderate injury.

    NOTICE

    NOTICE indicates a situation that can result in property

    damage, if not avoided.

  • User Manual V4.2

    4

    1.3 Target Group Chapter 1, 2, 3, 4, 7, 8, 9, 10 and Chapter 11 are intended for anyone who is

    intended to use Omnik Grid Tie Solar Inverter. Before any further action, the operators

    must first read all safety regulations and be aware of the potential danger to operate high-

    voltage devices. Operators must also have a complete understanding of this devices

    features and functions.

    Chapter 5 and Chapter 6 are only for qualified personnel who are intended to install

    or uninstall the Omnik Grid Tie Solar Inverter.

    WARNING

    Do not use this product unless it has been successfully installed

    by qualified personnel in accordance with the instructions in

    Chapter 5, Installation.

    NOTICE

    Hereby qualified personnel means he/she has the valid license from the local authority in:

    Installing electrical equipment and PV power systems

    (up to 1000 V).

    Applying all applicable installation codes.

    Analyzing and reducing the hazards involved in

    performing electrical work.

    Selecting and using Personal Protective Equipment

    (PPE).

  • User Manual V4.2

    5

    2. Preparation 2.1 Safety Instructions

    DANGER

    DANGER due to electrical shock and high voltage DO NOT touch the operating component of the inverter, it

    might result in burning or death.TO prevent risk of electric shock during installation and

    maintenance, please make sure that all AC and DC terminals are plugged out.DO NOT stay close to the instruments while there is severe

    weather conditions including storm, lighting etc.

    WARNING

    The installationservice recycling and disposal of the

    inverters must be performed by qualified personnel only in

    compliance with national and local standards and

    regulations. Please contact your dealer to get the

    information of authorized repair facility for any maintenance

    or repairmen.

    Any unauthorized actions including modification of product

    functionality of any form will affect the validation of warranty

    service; Omnik may deny the obligation of warranty service

    accordingly.

    NOTICE

    Public utility only The PV inverter designed to feed AC power directly into the

    public utility power griddo not connect AC output of the device to any private AC equipment.

  • User Manual V4.2

    6

    2.2 Explanations of Symbols on Inverter

    Symbol Description

    Dangerous electrical voltage This device is directly connected to public grid, thus all work to the inverter shall only be carried out by qualified personnel.

    DANGER to life due to high electrical voltage! There might be residual currents in inverter because of large capacitors. Wait 10 MINUTES before you remove the front lid.

    NOTICE, danger! This device directly connected with electricity generators and public grid.

    Danger of hot surface The components inside the inverter will release a log of heat during operation, DO NOT touch aluminum housing during operating.

    An error has occurred Please go to Chapter 9 Trouble Shooting to remedy the error.

    This device SHALL NOT be disposed of in residential waste Please go to Chapter 8 Recycling and Disposal for proper treatments.

    CAUTION

    The PV inverter will become hot during operation; please

    dont touch the heat sink or peripheral surface during or

    shortly after operation

    Risk of damage due to improper modications.

    Never modify or manipulate the inverter or other components

    of the system.

  • User Manual V4.2

    7

    Without Transformer This inverter does not use transformer for the isolation function.

    German mark of conformity The inverter complies with the requirement of the German Grid Regulations.

    Certified Safety The inverter complies with the requirements of the Equipment and Product Safety Act in Europe.

    Standards Association of Australian The inverter complies with the requirement of the AS4777.

    CE Mark Equipment with the CE mark fulfils the basic requirements of the Guideline Governing Low-Voltage and Electromagnetic Compatibility.

    No unauthorized perforations or modifications Any unauthorized perforations or modifications are strictly forbidden, if any defect or damage (device/person) is occurred, Omnik shall not take any responsibility for it.

  • User Manual V4.2

    8

    3. Product Information

    3.1 Overview

    Industrial Layout

    Excellent Heat Elimination

  • User Manual V4.2

    9

    Effective Shield For DC/AC/Communication Connections

    3.2 Major Characteristics Omnik inverter has following characteristics which make Omnik inverter High Efficiency, High

    Reliability, High Cost Effective Ratio

    Wide DC input voltage and current ranges, enables more PV panels connected.

    Wide MPP voltage range ensure high yield under various weather conditions.

    High MPP tracking accuracy, ensure the minimum power loses during converting.

    Complete set of protection methods.

    Also, following protection methods are integrated in Omnik inverter:

    Internal overvoltage

    DC insulation monitoring

    Ground fault protection

    Grid monitoring

    Ground fault current monitoring

    DC current monitoring

    Integrated DC switch (Optional)

  • User Manual V4.2

    10

    3.3 Datasheet

    Omniksol-1k-TL

    Type Omniksol-1k-TL

    Input (DC)

    Max. PV-generator power Ppv [W] 1300

    Max DC voltage Vmax(DC) [V] 500

    MPPT DC voltage range Vmppt [V] 80- 300

    Turn off DC Voltage Vmin(DC) [V] 80

    Max. DC current Imax(DC) [A] 16

    Nominal DC current IN(DC) [A] 8.5

    Number of DC connection 1

    DC-connection MC4

    Number of MPP trackers 1

    Turn on power Pmin(DC) [W] 10

    Output (AC)

    Max. AC Power Pmax(AC) [V] 1100

    Nominal AC power PN(AC) [W] 1000

    Max. AC current Imax(AC) [A] 5.8

    Nominal AC current IN(AC) [A] 4.3

    Power connection Single phase

    Grid voltage range According to VDE 0126-1-1, RD1663, ENEL2010,C10/11,

    G83/1 AS4777

    Grid frequency range According to VDE 0126-1-1, RD1663, ENEL2010,C10/11,

    G83/1, AS4777

    Power factor 0.99 (>30% of Full Load)

    Harmonic distortion (THD) at nominal output

  • User Manual V4.2

    11

    Dimensions and weight

    Dimensions (WxHxD) [mm] 330x425x130

    Weight [kg] 13

    Environmental limits

    IP protection type IP 65 according to IEC 60529

    Operating temperature range -20C to +60C

    Relative humidity 0% to 98%, no condensation

    Maximum altitude (above sea level) [m] 2000

    Noise level [dBA] < 40

    General data

    Isolation type Transformerless

    Cooling concept Convection

    Housing Stainless steel housing for inside and outside installation

    Mounting information Wall bracket

    LED display 3

    LCD display Backlight, 16 x 2 Character LCD

    Data logger RS485, Optional (Wi-Fi, GPRS, Ethernet)

    Data communication interfaces

    Computer Communication RS232 as Option

    Standard warranty 5 years (optional 10 years)

    Omniksol-1.5k/2k-TL

    Type Omniksol-1.5k-TL Omniksol-2k-TL

    Input (DC)

    Max. PV-generator power Ppv [W] 1750 2300

    Max DC voltage Vmax(DC) [V] 500

    MPPT DC voltage range Vmppt [V] 120 - 450

    Turn off DC Voltage Vmin(DC) [V] 120

    Max. DC current Imax(DC) [A] 18

    Nominal DC current IN(DC) [A] 14 16.5

    Number of DC connection 1

    DC-connection MC4

    Number of MPP trackers 1

    Turn on power Pmin(DC) [W] 10

    Output (AC)

    Max. AC Power Pmax(AC) [V] 1650 2200

    Nominal AC power PN(AC) [W] 1500 2000

    Max. AC current Imax(AC) [A] 9.0 12.0

    Nominal AC current IN(AC) [A] 6.5 8.5

    Power connection Single phase Single phase

    Grid voltage range According to VDE 0126-1-1, RD1663, ENEL2010,C10/11,

    G83/1 AS4777

    Grid frequency range According to VDE 0126-1-1, RD1663, ENEL2010,C10/11,

    G83/1, AS4777

    Power factor 0.99 (>30% of Full Load)

    Harmonic distortion (THD) at nominal output

  • User Manual V4.2

    12

    Power consumption at night Pnig(AC) [W] 0

    Power consumption at standby Pstd(AC) [W] 6

    Efficiency

    Max. Efficiency (at 360VDC) 97.5%

    Euro efficiency (at 360VDC) 96.6%

    MPPT efficiency 99.9%

    Safety and protection

    Internal overvoltage protection Yes

    DC Insulation monitoring Yes

    Earth fault protection Yes

    Grid monitoring According to VDE 0126-1-1, RD1663, ENEL2010,C10/11

    G83/1, AS4777

    Earth fault current monitoring According to VDE 0126-1-1, RD1663, ENEL2010,C10/11

    G83/1, AS4777

    DC current monitoring According to VDE 0126-1-1, RD1663, ENEL2010,C10/11

    G83/1, AS4777

    Islanding protection According to VDE 0126-1-1, RD1663, G83/1, AS4777

    Normative reference

    CE- compliant according to

    EN 62109, EN 61000-6-1, EN 61000-6-3, EN 61000-6-2, EN 61000-6-4

    EN61000-3-2, EN61000-3-3, EN61000-3-12, EN61000-3-11

    Dimensions and weight

    Dimensions (WxHxD) [mm] 330x425x130

    Weight [kg] 13

    Environmental limits

    IP protection type IP 65 according to IEC 60529

    Operating temperature range -20C to +60C

    Relative humidity 0% to 98%, no condensation

    Maximum altitude (above sea level) [m] 2000

    Noise level [dBA] < 40

    General data

    Isolation type Transformerless

    Cooling concept Convection

    Housing Metal housing for inside and outside installation

    Mounting information Wall bracket

    LED display 3

    LCD display Backlight, 16 x 2 Character LCD

    Data logger RS485, Optional (Wi-Fi, GPRS, Ethernet)

    Data communication interfaces

    Computer Communication RS232 as Option

    Standard warranty 5 years (optional 10 years)

  • User Manual V4.2

    13

    4. Packing checklist

    4.1 Assembly parts After you receive the Omnik inverter, please check if there is any damage on the carton, and then check the inside completeness for any visible external damage on the inverter or any accessories. Contact your dealer if anything is damaged or missing.

    A B C D

    E F G H

    Object Quantity Description

    A 1 Omnik inverter

    B 1 pair DC connector

    C 1 AC connector

    D 1 Mounting bracket

    E 4 Screw (ST650)

    F 4 Expansion tube

    G 1 Installation and operating instructions

    H 1 DC Switch (Optional)

  • User Manual V4.2

    14

    4.2 Product Appearance Front

    Bottom

    Object Description

    A Removable front shield

    B LED light(Green) RUN

    C LED light(Red) FAULT

    D LED light(Yellow) COM

    E Function key for displays and choice of language

    F Monitoring LCD with backlighting

    AA

    FF

    EE DD CC BB

    A B C

  • User Manual V4.2

    15

    Object Description

    A Plug connectors for DC input.

    B RS232/RS485 interface

    C Terminal for grid connection (AC output)

    4.3 Product Identification You can identify the inverter by the side nameplate. Information such as serial number (SN.), type of the inverter, as well as inverter specifications are specified on the side name plate. The name plate is on the middle part of the right side of the inverter housing. And the following figure is the side name plate example as on Omniksol-1.5k-TL.

    4.4 Further Information If you have any further questions concerning the type of accessories or installation, please

    check our website www.omnik-solar.com or contact our service hotline.

  • User Manual V4.2

    16

    5. Installation

    5.1 Safety

    5.2 Mounting Instructions

    DANGER

    DANGER to life due to potential fire or electricity shock.

    DO NOT install the inverter near any inflammable or

    explosive items.

    This inverter will be directly connected with HIGH

    VOLTAGE power generation device, the installation must

    be performed by qualified personnel only in compliance with

    national and local standards and regulations.

    NOTICE

    NOTICE due to the inappropriate or the harmonized

    installation environment may jeopardize the life span

    of the inverter.

    Installation directly expose under intensive sunshine is not

    recommended.

    The installation site MUST have good ventilation condition.

    MMaaxx 1155

  • User Manual V4.2

    17

    Omnik inverter is designed for indoors and outdoors installation

    Please mount the inverter in the direction as illustrated above

    Install the inverter in the vertical direction is recommended, with a max.15 degrees

    backwards.

    For the convenience of checking the LCD display and possible maintenance

    activities, please install the inverter at eye level.

    Make sure the wall you selected is strong enough to handle the screws and bear the

    weight of the inverter

    Ensure the device is properly fixed to the wall

    It is not recommended that the inverter is exposed to the strong sunshine, because

    the excess heating might lead to power reduction

    The ambient temperature of installation site should be between -20 C and +60 C

    ( between -4 F and 140 F )

    Make sure the ventilation of the installation spot, not sufficient ventilation may reduce

    the performance of the electronic components inside the inverter and shorten the life

    of the inverter

    5.3 Safety Clearance Observe the following minimum clearances to walls, other devices or objects to guarantee

    sufficient heat dissipation and enough space for pulling the electronic solar switch handle.

    10 CM 10 CM

    30 C

    M

    30 C

    M

  • User Manual V4.2

    18

    Direction Minimum clearance

    Above 30 cm

    Below 30 cm

    Sides 10 cm

    5.4 Mounting Procedure

    5.4.1 Mounting with bracket

    1) Mark 4 positions of the drill holes on the wall according to the wall mounting bracket in

    the carton box.

    Depth 50mm

    25

    0

    213

    First, according to the marks, drill 4 holes in the wall. Then, place four expansion tubes

    in the holes using a rubber hammer. Next, make 4 screws through the mounting holes in

    the bracket, then tighten the screws into the expansion tubes. So far, the wall mounting

    bracket is fixed already.

  • User Manual V4.2

    19

    2) First check the 4 holes in the backside of the inverter. Then, lift the inverter carefully,

    align the 4 holes in the inverter and the 4 hooks on the bracket, and finally attach the

    inverter to the hooks slightly.

  • User Manual V4.2

    20

    5.4.2 Mounting without bracket

    1) Mark 4 positions of the drill holes on the wall according to the paper installation position

    scale packed in the carton box.

    2) First, according to the marks, drill 4 holes in the wall. Then, place four expansion tubes

    in the holes using a rubber hammer. Next, wring 4 screws into the expansion tubes.

    44--1122 22554411

    3322

    00

    22

  • User Manual V4.2

    21

    3) First check the 4 holes in the backside of the inverter. Then, lift the inverter carefully,

    align the 4 holes in the inverter and the 4 screws in the wall, and finally attach the

    inverter to the screws slightly.

    4) Please carefully check the accessories and original carton to make sure every

    necessary part is used and nothing is missing during installation.

  • User Manual V4.2

    22

    5.5 Safety lock

    5.5.1 Safety lock with the wall mounting bracket After the inverter is hang up on the bracketlock up the device and the bracket together at the

    Lower Right Corner of the inverter (as the picture showed below),

    Recommended padlock dimension:

    5.5.2 Safety lock without the wall mounting bracket After the inverter is hang up on the wall, install the lock bracket on the aluminium radiator at

    the Lower Right Corner of the inverter (as the picture showed below),make sure the round hole

    of the lock bracket aim at the hole of the inverter, after that lock up the device.

    The lock bracket

    padlock

  • User Manual V4.2

    23

    AShackle Diameter 5~7 mm

    BVertical Clearance 8~15 mm

    CHorizontal Clearance 12~20 mm

    Stainless, solid hanger and secured lock cylinder

    6. Electrical Connection

    6.1 Safety

    NOTICE

    For further maintenance and possible repair, please keep the key of the padlock in a safe place.

    DANGER

    DANGER to life due to potential fire or electricity shock. With

    the inverter powered, comply with all prevailing national

    regulations on accidents prevention. This inverter

    will be directly connected with HIGH VOLTAGE power

    generation device, the installation must be performed by

    qualified personnel only in compliance with national and local

    standards and regulations.

    A

    B C

  • User Manual V4.2

    24

    6.2 Overview of Connection Area

    Object Description

    A Plug connectors for DC input.

    B RS232/RS485 interface

    C Terminal for grid connection (AC output)

    NOTICE

    Electrical connections shall be carried out in

    accordance with the applicable regulations, such as

    conductor sections, fuses, PE connection.

    A B C

  • User Manual V4.2

    25

    6.3 AC Side Connection

    1) Integrated RCD and RCM

    The Omniksol inverter is equipped with integrated RCD (Residual Current Protective Device)

    and RCM (Residual Current Operated Monitor). The current sensor will detect the volume of

    the leakage current and compare it with the pre-set value, if the leakage current exceeds the

    permitted range, the RCD will disconnect the inverter from the AC load.

    2) Assembly Instructions

    a. Strip the cable with the length 0.276 inches (9/32) - (7mm) and please be careful NOT

    to nick conductors.

    b. Screw off and separate each component of AC connector as follows.

    c. Pass the cable through each component from left to the right as follows.

    DANGER

    DANGER to life due to potential fire or electricity shock.

    NEVER connect or disconnect the connectors under load.

  • User Manual V4.2

    26

    d. Use a screw driver and loose the three screws at the side of the straight plug. Then

    insert the stripped N, L and PE cable accordingly to the corresponding position and

    fully tighten the screws.

    e. Aim the terminals on the straight plug to the holes of the grommet, and then compress

    them together.

    f. Finally connect the straight plug to the AC terminal on inverter. Pay attention to the

    polarity of the terminals to avoid wrong connecting.

  • User Manual V4.2

    27

    6.4 DC Side Connection

    For Omniksol-1k/1.5k/2k-TL, there is only one MPP Tracker, and the DC characteristics

    of them are illustrated as the following table.

    Inverter Type MPP

    Tracker

    Max. DC

    Power

    Max. DC

    Voltage

    Max. DC

    Current

    Omniksol-1k-TL

    1

    1300W

    500V

    16A

    Omniksol-1.5k-TL 1750W 18A

    Omniksol-2k-TL 2300W 18A

    MC4 Assembly instructions

    If, during self assembly, parts and tools other than those stated by MC are used or

    if the preparation and assembly instructions described here are disregarded then neither

    safety nor compliance with the technical data can be guaranteed.

    For protection against electric shock, PV-connectors must be isolated from the

    power supply while being assembled or disassembled.

    The end product must provide protection from electric shock.

    The use of PVC cables is not recommended.

    NOTICE

    DC Switch (Optional) may be integrated or external to

    Inverter, and it can be used to connect or disconnect the

    DC source from Inverter.

    DANGER

    DANGER to life due to potential fire or electricity shock.

    NEVER connect or disconnect the connectors under load.

  • User Manual V4.2

    28

    Unplugging under load: PV plug connections must not be unplugged while under

    load. They can be placed in a no load state by switching off the DC/AC converter or

    breaking the DC circuit interrupter. Plugging and unplugging while under voltage is

    permitted.

    It is unadvisable to use non-tinned cables of type H07RN-F, since with oxidised

    copper wires the contact resistances of the crimp connection may exceed the permitted

    limits.

    Disconnected connectors should be protected from dirt and water with sealing

    caps.

    Plugged parts are watertight IP67. They can not be used permanently under

    water. Do not lay the MC-PV connectors on the roof surface.

    See the MC catalogue 2 Solar line for technical data and assembled parts.

    PV-Female cable coupler PV-Male cable coupler Optional

    PV-KBT4/ PV-KST4/ PV-SSH4

    Touch protection,

    mated/unmated

    IP67/IP2X

    Rated current 17A(1,5mm2/14AWG)

    22A(2,5mm2/ 12AWG)

    30A(4mm2,6mm2/ 10AWG)

    Ambient

    temperature

    range

    -40 ...90C(IEC/CEI)

    -40 ...75C(UL)

    -40 ...70C(UL/AWG14)

    Rated voltage 1000V (IEC/CEI) 600V (UL)

    Upper limiting

    temperature

    105C (IEC/CEI) Safety class II

    Tools required

    (ill.1) Crimping tool incl. locator and

    built-in crimping insert.

    Type: PV-ES-CZM-18100

    PV-ES-CZM-19100

  • User Manual V4.2

    29

    (ill.2) Interchangeable crimping

    inserts incl. hexagonal screwdriver A/F

    2,5.

    Type: PV-ES-CZM-18100

    PV-ES-CZM-19100

    (ill.3) Open-end spanner PV-MS 1 set =

    2 pieces Order No. 32.6024

    (ill.4) PV-WZ-AD/GWD socket wrench

    insert to tighten, Order No. 32.6006

    (ill.5) PV-SSE-AD4 socket wrench insert

    to secure PV-SSE-AD4, Order No.

    32.6026

    (ill.6) Open-end spanner A/F 15 mm

    (ill.7) Torque screwdriver A/F 12 mm

    (ill.8) Test plug PV-PST

    Order No.: 32.6028

  • User Manual V4.2

    30

    Cable preparation

    (ill.9) Important: Cables with class 2, 5

    or 6 construction can be connected. It is

    advantageous to use tinned conductors.

    It is unadvisable to use non-tinned cables

    of type H07RN-F, since with oxidised

    copper wires the contact resistances of

    the crimp connection may exceed the

    permitted limits.

    Check dimension b according to the

    following table:

    (ill.10) Strip cable insulation. L = 6-7, 5

    mm. Take care not to cut individual

    strands.

    Recommended tool:

    Stripping pliers PV-AZM,Order

    No.32.6027

    Crimping

    (ill.11) Notes to the operation ofthe

    crimping pliers, seeMA251-def

    (www.multicontact.com)

    (ill.12) Push the crimped contact into the

    socket resp. plug insulator until it

    engages. Pull lightly on the lead to check

    that the metal part has engaged.

  • User Manual V4.2

    31

    Assembly control

    (ill.13) Insert the test pin with the

    corresponding side into the socket or plug

    to the end position. If the contact is

    correctly assembled, the white marking

    on the test pin must be still visible.

    (ill.14) Screw on the cable gland, hand-

    tight, with the tools PV-MS. Or

    Screw on the cable gland, with the tools

    PV-WZ-AD/GWD and PV-SSE-AD4

    In any case:

    The tightening torque must be adapted to

    the solar cables used in each specific

    case. Typical values lie in a range

    between 2,5 Nm to 3 Nm.

    Plugging and unplugging the cable

    coupler without safety lock clip PV-SSH4

    Plugging

    (ill.15)Plug the coupling together until

    they engage. Check correct engagement

    by pulling on the coupling.

    Unplugging

    (ill.16)Compress the two snap-in springs

    (X) by hand or with the PV-MS tool and

    separate the coupling.

    Plugging and unplugging the cable

    coupler without safety lock clip PV-SSH4

    Refer to cable manufactures specification for minimum bending radius.

  • User Manual V4.2

    32

    6.5 Communication and Monitoring Device There are 2 plugs in the bottom side of the Omnik inverter as the following figure:

    These 2 plugs are used for multipoint communications, that is, up to 50 Omnik inverters can be

    connected one by one through these 2 plugs and the cables, the upper computer can

    communicate with these inverters via a single signal cable at the same time, and maximum

    length of the cable is 1000m. Through these plugs, the user can get the data from these

    inverters, and can also configure parameters of them.

  • User Manual V4.2

    33

    7. Display

    7.1 LCD Panel

    Object Description

    A LED light(Green) RUN

    B LED light(Red) FAULT

    C LED light(Yellow) COM

    D Function key for displays and choice of language

    E Monitoring LCD with backlighting

    The LCD panel is integrated in the front lid of the inverter, so it is easy for user to check and

    set the data. In addition, the user can press the function key to illuminate the LCD screen.

    NOTICE

    Omnik inverter is not an aligned measuring instrument

    for current, voltage or power consumption. A slight

    deviation of a few percent points is intrinsic to the

    system, the results from the inverter cannot be used f or

    grid balance calculations. An aligned meter will be

    required to make calculations for the utility company.

    EE

    AA BB CC DD

  • User Manual V4.2

    34

    7.2 LCD Display

    The display content consists of 2 lines. The bottom line (Line 2) always displays the output

    power (Pac = xxxx W). The top line (Line 1) shows current state information by default, and by

    pressing function key it will display different operating information as the following flow chart

    and table.

    NOTICE

    Make sure the DC switch(Optional) is switched to On

    position, otherwise the inverter cannot work due to power

    shortage.

  • User Manual V4.2

    35

    State information

    Pac = xxxx W

    Iac

    Pac = xxxx W

    E-total

    Pac = xxxx W

    Vpv

    Pac = xxxx W

    Ipv

    Pac = xxxx W

    E-today

    Pac = xxxx W

    Vac

    Pac = xxxx W

    Model

    Pac = xxxx W

    Ver

    Pac = xxxx W

    Set language

    Pac = xxxx W

    Frequency

    Pac = xxxx W

    S/N(WiFi)

    Pac = xxxx W

    IP Address

    Pac = xxxx W

  • User Manual V4.2

    36

    Line 1 Description

    State

    information

    Current state information: all possible content shows in the following

    table, reference to 7.4 for further information

    E-today The energy generated today in kilo watt hours (kWh)

    E-total The energy generated since starting up the inverter (kWh)

    Vpv The present voltage of the solar generator

    Ipv The present current of the solar generator

    Iac The present grid current

    Frequency The grid frequency

    Model The type of the inverter

    Ver The Firmware version

    Set Language Several languages are provided for users, reference to 7.3 for further

    information

    Vac The grid voltage

    S/N(WiFi) Displays the serial number of the WiFi card (such as no WiFi card

    shows 00000000)

    IP Address Displays the IP address of the WiFi (such as don't connect WiFi card

    shows 0.0.0.0)

    7.3 Set Language The Omnik inverter provides several languages for users to use. At the entry of Set

    Language, press the key for approx. 5 seconds, you can enter the language selection menu.

    Choose the language which you need with the function key, and keep this state without any

    operation. When it returns to the main menu automatically, the setting has been saved.

  • User Manual V4.2

    37

    7.4 Instructions of Safety Standard selection when power-up

    1) Attentions before the operation:

    Only perform this operation when the voltage value displayed on Omnik inverters LCD falls

    between 80V and 300V for 1.0kW inverter or between 150V and 450V for 1.5kW/2.0kW

    inverters.

    Only perform this operation when the accumulative generated electricity is less than 1KWh.

    2) Operation steps are as following:

    a. Power on the inverter with only DC side connected, while disconnecting cables of AC

    side.

    b. Press the Function button until the LCD displays inverters model and hold the button for

    5 seconds or more when the LCD displays the current Safety Standard. Change the

    standard by pressing the Function button one at a time.

    Function button

  • User Manual V4.2

    38

    c. When the LCD displays your desired Safety Standard, hold the Function button for 5

    seconds or more until it shows Safety Standard OK.

    d. The Safety Standard setup is now completed.

  • User Manual V4.2

    39

    7.5 State Information

    State Display State information

    Wait

    Waiting Initialization & waiting

    Reconnect s Reconnect

    Checking s Checking

    Normal Normal Normal state

    Fault

    Ground I Fault GFCI failure oversized leakage current

    Fac Failure Grid frequency failure

    Vac Failure Grid voltage failure

    Utility Loss No Utility&Island

    PV Over Voltage Input voltage too high

    Over Temperature Temperature abnormal

    Isolation Fault Isolation failure

    Relay-Check Fail Output relay failure

    DC INJ High Output DC injection too high

    EEPROM R/W Fail EEPROM problem

    SCI Failure Serial communication interface failure

    AC HCT Failure Output AC sensor abnormal

    GFCI Failure GFCI testing device abnormal

    Flash F/W Updating Update

    About the further information for each fault, please reference to Chapter

    9.TROUBLESHOOTING.

  • User Manual V4.2

    40

    8. Recycling and Disposal To comply with European Directive 2002/96/EC on waste Electrical and Electronic Equipment

    and its implementation as national law, electrical equipment that has reached the end of its life

    must be collected separately and returned to an approved recycling facility. Any device that

    you no longer required must be returned to your dealer or you must find an approved collection

    and recycling facility in your area.

    Ignoring this EU Directive may have severe affects on the environment and your health.

    WARNING

    This device SHALL NOT be disposed of in

    residential waste.

  • User Manual V4.2

    41

    9. Troubleshooting

    LCD display Possible actions

    Resumable

    Fault

    Isolation Fault

    1. Check the impedance between PV (+) & PV (-) and the inverter is earthed. The impedance must be greater

    than 2M. 2. Check whether the AC-side has contacts with earth.

    Ground I Fault

    1. The ground current is too high. 2. After cut off the AC side connection, unplug the inputs

    from the PV generator and check the peripheral AC system.

    3. After the cause is cleared, re-plug the PV panel and AC connection, and check PV-Inverter status.

    Grid Fault Fac Over Range

    Vac Over Range

    1. Wait for a moment, if the grid returns to normal, PV-Inverter automatically restarts.

    2. Make sure grid voltage and frequency meet the specifications.

    Utility Loss

    1. Grid is not connected. 2. Check grid connection cables. 3. Check grid usability. 4. If grid is ok, and the problem persists, maybe the fuse

    in the inverter is open, please call service.

    Over Temperature

    1. The internal temperature is higher than specified normal value.

    2. Find a way to reduce the ambient temperature. 3. Or move the inverter to a cooler environment.

    PV over Voltage

    1. Check the open PV voltage, see if it is greater than or too close to 500VDC (for Omniksol-1k/1.5k2k-TL).

    2. If PV voltage is less than 500VDC, and the problem still occurs, please call local service.

    Permanent

    Fault

    Consistent Fault Disconnect PV (+) or PV (-) from the input, restart the

    inverter.

    Relay-Check Fail

    1. Disconnect ALL PV (+) or PV (-). 2. Wait for a few seconds. 3. After the LCD switches off, reconnect and check again. 4. If the problems remain please call local service.

    DC INJ High

    EEPROM R/W Fail

    SCI Failure

    AC HCT Fault

    GFCI Failure

  • User Manual V4.2

    42

    10. Abbreviation

    LCD Liquid Crystal Display

    LED Light Emitting Diode

    MPPT Maximum Power Point Tracking

    PV Photovoltaic

    Vdc Voltage at the DC side

    Vac Voltage at the AC side

    Vmpp Voltage at the Maximum Power Point

    Impp Amperage at Maximum Power Point

    AC Alternating Current ( Form of electricity supplied by Utility

    Company )

    DC Direct Current ( Form of electricity generated by PV modules )

    VDE 0126-1-1 German standards for establishing suitability for Grid

    Connection of the Inverter.

    DC Switch Switch in the DC Circuit. Disconnects DC source from Inverter.

    May be integrated or external to Inverter.

  • User Manual V4.2

    43

    11. Contact Suzhou Headquarter

    Xinghu Road No.218 bioBAY Park A4-414 215123 Suzhou China

    Tel: +86 512 6295 6676

    Fax: +86 512 6295 6682

    Email: [email protected]

    www.omnik-solar.com

    Omnik German Service Center

    Omnik GmbH

    Forsthausstr.8A

    65479 Raunheim

    Tel+49 (179) 9762 654

    Service line

    Tel: +86 512 6295 6676

    Fax: +86 512 6295 6682

    Email: [email protected]