uv disinfection for drinking water - va awwa operations... · uv disinfection system design ups...
TRANSCRIPT
Wa
ter JA
M 2
01
0
UV Disinfection for Drinking Water
David S. Briley, PE
Virginia AWWA 2015 Operators Conference
Virginia Beach, VA
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
Principles of UV Disinfection
Applications of UV Disinfection for Drinking Water
Design Considerations
Validation Testing
Case Study – City of Raleigh, NC
Obtaining Giardia/Crypto Credit for UV
Agenda
Wa
ter JA
M 2
01
0
Principles of UV Disinfection
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
Physical process using electromagnetic energy to
prevent DNA and RNA from further replication
Germicidal UV irradiation range - 200 to 300
UV produces no residual
Principle of Ultraviolet (UV) Disinfection
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
Dimerization of DNA (thymine bases)
Inability to Reproduce Bug is Non-infective
Dark repair has been observed in some bacteria
5
Dimer
Dimer
Disinfection Mechanism
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
Disinfection Effectiveness vs. Wavelength
6
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
Adapted from Linden and Mofidi, 1999; Wright and Cairns, 1998; and Kolch, 1999
Characteristic
Low-Pressure,
High OutputMediumPressure Pulsed-UV
Spectral Emission Polychromatic
(185 – 1,387 nm)
Polychromatic
(185 – 800 nm)
Operating Temperature (°C) 100-200 500 – 850 7,000 – 15,000
Lamp life (hr) 8,000 – 12,000 2,000 – 8,000 925 @ 30 Hz
Efficiency (200-300 nm) 35 – 40% 15 – 25% <20%
Relative Light Intensity Low Medium High
Relative Footprint Required Medium Small Small
Nearly
monochromatic
Comparison of UV Lamps
7
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
UV Equipment
Germicidal Output by UV Lamps
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
Typical Municipal UV Disinfection Systems
Most prevalent UV technologies
Low-Pressure, High Output (LPHO)
Medium-Pressure, High Output (MPHO)
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
Ratio of light at a specific wavelength (typically 254 nm)
exiting the water to that entering the water
Related to UV absorbance:
%UVT = 100 x 10-A
As UV absorbance increases,
UV transmittance decreases
Typical UVT Values:
DI / RO Water = 99%
Municipal Tap Water = 85-95%
Secondary Effluent = 60-70%
UV Transmittance (UVT)
10
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
UV Transmittance in Water
11
High UVT = High Dose
Low UVT = Lower Dose for same energy
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
UV Dose = Intensity x Time
[mW-sec/cm²] = [mW/cm²] x [sec]
UV Dose
Dose – the energy per unit area incident on a surface (mJ/cm2)
No residual that can be measured, so must measure impacts Bioassay
Chemical Actinometry
Dyed Microspheres
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
UV Intensity Sensor
UV Intensity is a function of:
Lamp output
Lamp age
Quartz sleeve transmissivity
Water quality (UV
transmittance)
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
UV Disinfection Guidance Manual
US EPA published UVDGM in 2006
http://water.epa.gov/lawsregs/sdwa/lt2/compliance.cfm
UVDGM provides guidance for:
Design of UV facilities
Validation testing of UV equipment
Monitoring and operation of UV facility
Includes UV dose requirements for
Giardia, Crypto, and viruses to meet
LT2ESWTR
14
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
Log Inactivation
0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0
Cryptosporidium 1.6 2.5 3.9 5.8 8.5 12 -- --
Giardia 1.5 2.1 3.0 5.2 7.7 11 -- --
Virus 39 58 79 100 121 143 163 186
UV Dose Requirements
LT2ESWTR and UVDGM 2006
15
UV dose in mJ/cm2
Wa
ter JA
M 2
01
0
Applications of UV Disinfection
for Drinking Water
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
UV Disinfection Applications
Multiple barrier disinfection
Urbanized watershed
Source water quality variability
LT2ESWTR Compliance
Water system is classified as Bin 2 or higher
Receive inactivation credit for Crypto
DBP Compliance Strategy
Receive inactivation credit for Giardia and Crypto.
Reduce free chlorine contact in WTP
Can be effective if in combination with chloramines
UV produces no regulated DBPs
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
UV Disinfection Treatment Objectives
Source: UV Disinfection Knowledge Base, WaterRF Report No. 3117 (2012)
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
Example States Granting Credit for UV
Arizona
California
North Carolina
New York
Tennessee
Utah
Washington
Wisconsin
Virginia – coming soon
Wa
ter JA
M 2
01
0
Design Considerations
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
Water Quality Factors
21
Parameter Influence/Effect LimitsUV Transmittance Absorption of UV light > 85% UVT
Turbidity Shields pathogens < 1 NTU
Hardness Cause scaling on quartz sleeves reducing UV intensity
< 200 mg/L CaCO3
pH Affect solubility of metals, potentially affecting UVT and
fouling
6.0 - 9.0
Iron Fouling of lamp sleeves Perform pilot test for lamp sleeve fouling
Suspended Solids Absorption of UV light and shielding of pathogens
< 10 ppm
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
UV Transmittance (UVT)
Most critical design parameter
Need large dataset to properly select design value
(95th percentile)
Typical UVT Values for municipal WTPs: 85-95%
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
Site and Layout Considerations
Recommended location for UV system is post-filter
Reduces solids which can shield pathogens
Maximize WQ to achieve best UV performance and minimize fouling
Optimal location is between filters and clearwell
Layout considerations
Sufficient straight pipe
upstream of UV reactors
Flowmeter for each UV train
Ensure UV unit remains full
under all conditions
Motorized isolation valves
May require relocation of
post-filter chemical feeds
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
Hydraulic Head Requirements
Existing WTPs have limited head b/w filters and clearwell
Need to identify available head in your WTP
Critical to understand headloss through UV to avoid
impacting filter operations or clearwell volume
Headloss not directly related to UV technology
Ways to reduce headloss
Locate UV Facility close to filters and clearwell
Install larger reactors or more reactors ($$)
Typical Headloss
UV Reactors 2 to 24 inches
UV Facility 36 to 48 inches
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
Hydraulic Considerations
Hydraulic design to allow for even distribution b/w units
Ensure UV unit does not exceed validated flowrate
Ensure steady flow through UV units
Avoid rapid fluctuations in flow or pressure
Some UV units equipped with baffles to
distribute flow through reactor
More complex for pumped systems
Ensure UV units flooded at all times
Lamps can result in rapid heat buildup and
damage components
In large LPHO units, provided air release/vacuum valves
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
UV System Section
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
Electrical Design Considerations
Power Supply
Varies significantly by UV technology
Recommend pre-selecting UV equip. or
design bid alternates
LPHO Systems: 0.5 to 1.4 kW/mgd
MPHO systems: 2.0 to 2.4 kW/mgd
Uninterruptible Power Supply
Power conditioning (electronic
ballasts sensitive to power spikes)
Ensures UV operation (and continued
disinfection) until standby power
starts up
In event of generator failure, allows for
controlled UV shutdown to prevent flow
entering clearwell
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
On-Site vs Offsite Validation
Significant challenges with on-site testing
Operational limitations with online WTP
Limited available water for test matrix
May require partial or full WTP shutdowns
Capacity of backwash handling facilities to handle test water
Consistency of water quality and UVT during testing
Issues with chlorine in UV influent
Offsite Validation Testing allows
for better control of test
parameters
UV manufacturers have validated
reactors for most applications
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
Validation Testing
• Cannot directly measure UV
residual or inactivation
• Validation testing required to
confirm performance
• Validation testing should
cover design conditions
(max flow, min UVT, etc)
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
UV Dose Response Curves
30
0
0.5
1
1.5
2
2.5
0 10 20 30 40 50 60
MS
-2 R
ed
ucti
on
[L
og
(N
o/N
)]
UV Dose (mJ/cm2)
MS-2 - low pressure
MS-2 - 255 nm UV-LEDS
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
UV Definitions - UV Dose
Reduction Equivalent Dose (RED) – Inactivation
measured during full-scale reactor testing correlated to
UV dose-response curve from collimated beam testing.
Required Dose (Dreq) – UV dose specified in LT2ESWTR
to achieve target log inactivation for target pathogen.
Validated Dose (Dval) – UV dose delivered by UV reactor
as determined through validation testing. Compared to
the required dose to determine log inactivation credit.
Calculated Dose – The RED calculated using the dose-
monitoring equation that was developed through
validation testing.
31
reqval DVF
REDD
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
UVDGM Requirements for UV Design
Relate UV facility design to
validation system setup
UVDGM Option 1
Straight pipe upstream of
UV unit during validation testing (X)
+5 pipe diameters
Requires coordination with UV
suppliers during concept design
X
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
Relating Validation Setup to Installation
Option 2 – Site Specific Validation Test
Identical piping layout for 10D
upstream and 5 D downstream
Costly!!
Option 3 –Velocity Profiles
CFD modeling to demonstrate velocity
profile is similar or better than during
validation testing
Validated Reactor Installed Reactor
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
Regulatory Approval for UV Disinfection
UV systems have been granted inactivation credit for
Crypto. and Giardia in:
Arizona
California
Tennessee
Utah
Washington
Wisconsin
NC: Granted credit to UV system at D.E. Benton WTP
(City of Raleigh) in Oct. 2013.
Other States are currently developing guidance or
protocols such as New York.
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
Case Study: Raleigh, NC
Dempsey E. Benton WTP
Permitted Capacity: 16 mgd
Design Capacity: 20 mgd WTP
WTP online May 2010
Constructed to provide reliability in City’s water system
EM Johnson WTP
Capacity = 86 mgd
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
Raleigh’s Goals for UV Disinfection
To provide multiple barrier disinfection
Urbanized watershed
Source water quality variability
Some Crypto. hits but still Bin 1
To lower DBPs – simultaneous compliance with
LT2ESWTR and Stage 2 DBPR
Receive inactivation credit for Crypto. and Giardia
DBP Compliance Strategy
Reduce free chlorine contact in WTP
Can be effective if in combination with chloramines
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
UV Disinfection System Design
Three 10-mgd UV reactors
N+1 redundancy
Design Flowrate = 20 mgd
Design dose = 40 mJ/cm2
Design UV
Transmittance = 90%
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
UV Disinfection System Design
LPHO Reactors (Wedeco K Series)
Space for 2 future reactors
UV Reactor
5 lamp rows
12 lamps per row
60 lamps total
Splitter weirs upstream
of each UV unit
36” mag flowmeter
upstream of each UV unit
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
UV Disinfection System Design
UPS
Operate 2 UV reactors for 15 mins
Generator w/ ATS
Effluent valves on each UV reactor powered by UPS
Complete shutdown if standby generators do not
start to prevent plant flow without UV disinfection
Clean-in-place system for periodic cleaning of UV
lamp sleeves
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
Key Issues for Approval for Inactivation Credit
Most States are following UVDGM
Off-Spec operations
UV Lamp Breakage Risks and Response Plan
Combined lamp aging/fouling factor (CAF)
Monitoring and controls to ensure disinfection
Backup plan in the event of UV system failure
Monitoring and reporting forms
Validation Testing
Low wavelength action spectra (applies to MPHO)
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
Off-Spec Operations
EPA UVDGM: at least 95% of water delivered
through UV reactors operating within validated
conditions
UV System controls can limit off-spec operations
Some regulators don’t like 5% if UV is for primary
disinfection
Off-spec for no more than 15 mins at a time (NC, UT, WA)
Off-spec for no more than 0.1% (WI)
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
UV Off-Spec Operations
• 58 off-spec events in 20 months
• Each event < 5 mins
• Most were due to faulty UVT analyzer at the time
• UVT analyzer issues have been since corrected
0.00%
0.02%
0.04%
0.06%
0.08%
0.10%
0.12%
0.14%
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
J F M A M J J A S O N D J F M A M J J A S
Pe
rce
nt
of
Tre
ate
d F
low
Off
-Sp
ec
Vo
lum
e (
MG
)
Total Off-Spec Flow (MG) Total Off-Spec Flow (%)
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
UV Transmittance Analyzer
90
91
92
93
94
95
96
97
98
99
100
N F J S D A J O J
UV
Tra
nsm
itta
nce (
%)
UV Transmit (%) Minimun UV Transmit (%) Average
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
Mercury Release Findings - LPHO
Following a lamp break, the concentrations of mercury
in the water passing through the reactor will be an order
of magnitude or more less than the regulatory MCL of 2
μg/L.
With amalgam lamps, the majority of the mercury will be
within the solid amalgam.
Liquid or amalgam mercury will settle to the bottom of
the reactor.
Mercury and quartz shards can be captured using
isolation valves and low velocity zones downstream of
reactor.
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
Lamp Breakage Risks
Regulators concerned about lamp breakage and potential
mercury release
Identified lamp breakage risks and demonstrate how design and
operation will mitigate these risks
Debris:
Downstream of filters, and splitter weirs
Baffle at UV reactor inlet
Water Hammer:
Free water surface upstream and downstream
Partially full reactor:
Downstream weir set to keep reactor flooded
Level switch at top of reactor shuts down reactor when activated
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
Lamp Breakage
Hg has high density and low solubility
LPHO lamps have order of
magnitude less Hg than MP lamps
WRF Research showed much of Hg
will be trapped in reactor and Hg
release << MCL
Only a release if quartz sleeve breaks as
well
Experience shows that most lamp break
events occur during lamp changeout –
outside of UV reactor
Developed a Lamp Breakage
Response Plan
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
Lamp Fouling/Aging Factor
Lamp output measured by intensity sensors
Intensity affected by: Lamp aging
Quartz sleeve fouling
UVT
Lamp Aging Factor: 88-92%
Lamp Fouling Factor: 68-80%
Combined Aging Fouling Factor (CAF)
WRF Report (3117) found that CAF not monitored closely
NC PWS requires close monitoring of CAF to monitor when lamps require replacement or cleaning.
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
UV Systems Control Sequences
Significant effort in reviewing control system logic with NC PWS
Developed UV Operations and Maintenance Manual
Fully automated controls for UV dose pacing
Unusual Conditions
If UVT > MAX VALIDATED UVT, UV dose calc will clamp at MAX VALIDATED UVT
If UVT < 90% [DESIGN UVT], all rows on at 100%, UV dose calc will clamp at 90%
If low intensity is detected, new lamp row will start
Flowmeter failure, design flow (10 MGD) used in UV dose calc.
If off-spec condition is detected
Auto start standby reactor
Approx 5 mins to start new reactor and achieve 100% power
Power Loss Standby generators called to start
UPS can power UV system for up to 15 mins
If generators fail to start, PLC will close effluent valves and shutdown UV system after set delay (~10 mins)
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
Contingency Planning
NC PWS very focused on contingency planning
Recommend focus on redundancy and reliability during
design and development of control logic
Minimize under-disinfected water (off-spec) from entering
distribution system
City of Raleigh developed Plan for Total UV System Failure
Convert back to meeting Giardia CT via free chlorine disinfection
Requires moving point of ammonia feed and converting clearwell
from chloramines back to free chlorine
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
Monitoring and Reporting
Date UVT
UV Reactor 1 UV Reactor 2 UV Reactor 3
Runtim
e (Hrs)
Flow
(MG)
Off-
Spec
Flow
(MG)
Min.
RED
(mJ/cm2
)
Runtim
e (Hrs)
Flow
(MG)
Off-
Spec
Flow
(MG)
Min. RED
(mJ/cm2)
Runtim
e (Hrs)
Flow
(MG)
Off-
Spec
Flow
(MG)
Min.
RED
(mJ/cm2
)
Runtim
e (Hrs)
1/1/11 24.11 4.38 0.00 82.04 24.04 4.34 0.00 82.00 0.00 0.00 0.00 0.00 N/A
1/2/11 24.04 4.41 0.00 82.06 24.04 4.34 0.00 82.00 0.00 0.00 0.00 0.00 N/A
1/3/11 24.12 4.41 0.00 82.04 24.10 4.34 0.00 82.00 0.00 0.00 0.00 0.00 N/A
1/4/11 24.06 4.44 0.00 82.05 24.06 4.38 0.00 82.00 0.00 0.00 0.00 0.00 N/A
1/5/11 24.05 3.84 0.00 82.06 24.04 3.80 0.00 82.00 0.00 0.00 0.00 0.00 N/A
1/6/11 24.02 3.94 0.00 82.06 24.05 3.87 0.00 82.00 0.00 0.00 0.00 0.00 N/A
1/7/11 24.00 4.44 0.00 82.26 24.05 4.34 0.00 82.00 0.00 0.00 0.00 0.00 N/A
1/8/11 23.90 4.34 0.00 82.04 23.90 4.28 0.00 82.00 0.00 0.00 0.00 0.00 N/A
1/9/11 24.02 4.28 0.00 82.06 24.02 4.28 0.00 82.00 0.00 0.00 0.00 0.00 N/A
1/10/11 24.03 4.69 0.00 82.05 17.03 2.91 0.00 82.00 0.00 0.00 0.00 0.00 N/A
1/11/11 24.08 4.28 0.00 82.05 24.03 4.19 0.00 82.00 0.00 0.00 0.00 0.00 N/A
1/12/11 21.89 3.19 0.00 82.07 24.01 3.72 0.01 82.00 0.00 0.00 0.00 0.00 N/A
1/13/11 24.09 3.05 0.00 82.06 24.01 2.89 0.00 82.00 0.00 0.00 0.00 0.00 N/A
1/14/11 24.03 3.41 0.00 82.07 24.01 3.28 0.00 82.00 0.00 0.00 0.00 0.00 N/A
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
Summary
UV Disinfection can be effective for LT2 and Stage 2
DBP Rule Compliance
UV has been approved for log inactivation credit in
several states. With more installations, regulatory
agencies are developing a comfort level with
reliability of UV
Talk to regulatory agency early in the process and
about your unique design/circumstances
If you want to reduce chemical CT,
Don’t expect it to be a quick process
Prepare to dive into the details with regulatory agenday
Prepare to develop more in-depth SOPs and more elaborate
controls to ensure CONTINUED DISINFECTION
Wa
ter JA
M 2
01
0N
C A
WW
A W
EA
20
11
David S. Briley, P.E.
(919) 833-7152
Questions