vacuum circuit-breaker 3ah3 7.2kv to 36kv 真空断路器 3ah3 operating instr engl-chn... ·...

27
Operating Instruction Siemens 3AH3 / 西门子 3AH3 真空断路器使用手册 Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 7.2kV 36kV Operating Instructions/操作手册 Order-No:/订货号: 9229 9860 174 0D-SLC PTD MC All right reserved / 版权所有 © Siemens AG 1996 & SLC PTD MC 2005

Upload: buiminh

Post on 21-Jul-2018

230 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 Operating Instr Engl-Chn... · Operating Instruction Siemens 3AH3 / 西门子3AH3 真空断路器使用手册. Standard

Operating Instruction Siemens 3AH3 / 西门子 3AH3 真空断路器使用手册

Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 7.2kV 至 36kV Operating Instructions/操作手册 Order-No:/订货号: 9229 9860 174 0D-SLC PTD MC

All right reserved / 版权所有 © Siemens AG 1996 & SLC PTD MC 2005

Administrator
文本框
上海锐杰电器有限公司提供
Page 2: Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 Operating Instr Engl-Chn... · Operating Instruction Siemens 3AH3 / 西门子3AH3 真空断路器使用手册. Standard

Operating Instruction Siemens 3AH3 / 西门子 3AH3 真空断路器使用手册

主要零部件说明 13. Checking marking 触头磨损标记指示 15. Pole plate 16.1 Upper post insulator 上绝缘子 16.2 Lower post insulator 下绝缘子 19. Pole assembly, complete

相极柱装配

20. Upper interrupter support

上极帽

27. Upper terminal 上接线排 28. Strut 绝缘支撑杆 28.1 Centering piece 衬垫 29. Lower terminal 下接线排 29.1 Flexible connector 软连接导电带 29.2 Clamp 导电夹 30. Vacuum interrupter 真空泡 31. Fixed contact piece 静触头 31.1 Connection surface 接触面 32. Insulator 绝缘外壳 33. Arcing chamber 灭弧室 34. Metal bellows 金属波纹管 35. Guide 导向管 36. Moving contact piece 动触头 36.1 Drive and terminal bolt

动触杆

40. Lower interrupter support

下极帽

48. Insulating operate rod

绝缘拉杆

48.6 Angled lever 拐臂 49. Contact pressure spring

触头压力弹簧

50. Hand crank 手柄 50.1 Opening for fitting hand crank

手柄储能操作孔

50.2 (Charging) gearing 减速箱 50.4 Motor M1 电动机 M1 50.4.1Position switch 位置开关 50.5 Hand crank coupling 手柄耦合杆 50.6 Adapter for hand crank

手柄适配头

51. Rating plate 铭牌 51.1 Opening for rating plate

铭牌面板开孔

53. ″Close″pushbutton 合闸按钮 53.1 Closing solenoid Y9 合闸线圈 Y9 54. ″Open″pushbutton 分闸按钮 54.1 Shunt release Y1 一级分励脱扣器 Y1 54.2 Shunt release Y2 二级分励脱扣器 Y1 54.3 Current transformer- operated release Y4

电流互感器驱动型脱扣

器 Y4 54.4 Undervoltage release Y7

欠电压脱扣器 Y7

55. ″Closing spring charged″ indicator

″合闸弹簧储能″ 指示器

55.1. Opening for indicator ″Closing spring charged″

″合闸弹簧储能″ 指示器面板开孔

58. Operating cycle counter

操作计数器

58.1 Opening for operating-cycle counter

操作计数器面板开孔

59. ON-OFF indicator 合分闸指示器 59.1 Opening for ″closed/open″ indicator

合分闸指示器面板开孔

60. Mechanism housing 操动机构箱 60.1 Cover 机构箱面板 60.2 Transport hole 运输起吊孔 60.3 Crane hook symbol 起吊标志 61. Dashpot 分闸缓冲器 62. Closing spring 合闸弹簧 63. Breaker shaft 主轴 64. Opening spring 分闸弹簧 66. Closing damper 合闸缓冲 68. Auxiliary switch S1

(6NO+6NC) 辅助开关 S1 (6 常开+6 常闭)

68.0.1.Extended auxiliary switch S1 (12NO+12NC)

延长型辅助开关 S1 (12 常开+12 常闭)

68.1 Operating rod (for auxiliary switch S1)

操动杆 (针对辅助开关 S1)

68.7.1 Low voltage plug connector X0 (64- pole)

64 针低压接插件 X0

69. Contactor 防跳接触器 70. Earthing bolt M12 接地螺栓 90. Mechanical interlocking

机械联锁

Administrator
文本框
上海锐杰电器有限公司提供
Page 3: Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 Operating Instr Engl-Chn... · Operating Instruction Siemens 3AH3 / 西门子3AH3 真空断路器使用手册. Standard

Operating Instruction Siemens 3AH3 / 西门子 3AH3 真空断路器使用手册

Contents Page General 1/1 Technical data 1/2~1/9

Type designation 1/2 Rating plate 1/2 Standards and specification 1/3 Ambient temperature/humidity loadability 1/3 Site altitude 1/4 Electrical data 1/5 Operating times 1/6 Switching duties 1/6 Motor operating mechanism 1/6 Auxiliary switch 1/7 Low-voltage plug connector 1/7 Shunt closing release 1/7 Shunt release 1/7~1/8 Undervoltage release 1/8 CT-operated release 1/8 Breaker tripping signal, cut-out Switches (S6 and S7) 1/9 Varistor module (V1 to V3) 1/9 Electrical local closing/ Electrical interlocking 1/9 Mechanical interlocking 1/9 Dimensions and weights 1/9

Description 2/1~2/5

Construction 2/1~2/3 Vacuum interrupters 2/4 Complement 2/5

Installation 3/1~3/4

Installing in cubicle or on truck 3/1 Flat bar connection 3/1~3/2 Control leads 3/2 Earthing 3/2 Circuit documents 3/2 Function schematic diagram 3/3~3/4

Operation 4/1~4/2

Commissioning 4/1~4/2 Charging and closing spring 4/2 Closing 4/2 Tripping 4/2

Maintenance 5/1~5/4

Safety measures 5/1 Servicing 5/1 Cleaning 5/1 Abnormal operating conditions 5/2 Checking the contact systems 5/2 Checking the vacuum 5/2 Service life 5/3 Accessories and spare parts 5/4

Note: The items illustrated in the Figures are enumerated in the fold–out central legend. When ordering the operating instructions please quote the order No.9229 9860 174 0D- SLC PTD MC.

内容 页码 概述 1/1 技术数据 1/2~1/9

型号表达方式 1/2 铭牌 1/2 适用标准 1/3 环境温度,湿度与负载能力 1/3

安装场所高度 1/4 电气数据 1/5 额定操作次数 1/6 切合负载范围 1/6 马达操动机构 1/6 辅助开关 1/7 低压接插件 1/7 合闸线圈 1/7 分励脱扣器 1/7~1/8 欠电压脱扣器 1/8 电流互感器驱动型脱扣器 1/8 断路器脱扣信号及消除开关(S6 和 S7) 1/9 压敏电阻模块 (V1 至 V3) 1/9 电气就地合闸/电气联锁 1/9 机械联锁 1/9 尺寸及重量 1/9

说明 2/1~2/5

结构 2/1~2/3 真空灭弧室 2/4 补充 2/5

安装 3/1~3/4 安装于柜内或 手车上 3/1 平滑母排连接 3/1~3/2 二次控制引线 3/2 接地 3/2 二次文件 3/2 二次控制线路图 3/3~3/4

操作 4/1~4/2 使用 4/1~4/2 储能及合闸弹簧 4/2 合闸 4/2 脱扣 4/2

维护 5/1~5/4 安全措施 5/1 维护 5/1 清理 5/1 非正常使用环境 5/2 检查触头磨损情况 5/2 检查灭弧室的真空度 5/2 使用寿命 5/3 附件及备件 5/4

注意: 图例中的标项详见主要零部件说明表. 如需定购操作手册请咨询订货号 9229 9860 174 0D SLC PTD MC.

Administrator
文本框
上海锐杰电器有限公司提供
Page 4: Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 Operating Instr Engl-Chn... · Operating Instruction Siemens 3AH3 / 西门子3AH3 真空断路器使用手册. Standard

Operating Instruction Siemens 3AH3 / 西门子 3AH3 真空断路器使用手册

! WARNING This equipment contains hazardous volt- ages and mechanical parts which move at high speed and may be controlled remotely. Non-observance of the safety instructions can result in severe personal injury or property damage. Only qualified personnel should work on or around this equipment after becoming thoroughly familiar with all warnings, safety notices, and maintenance procedu- res contained herein. The successful and safe operation of this equipment is dependent on proper handling, installation, operation and maintenance. General: Siemens 3AH3 vacuum circuit-breakers (V-breaker) are of the triple-pole indoor type for rated voltages between 7.2 and 36kV. The vacuum circuit-breaker consists of the mechanism housing complete with stored-energy mechanism and control elements, the three poles with vacuum interrupters, cast-resin insulators and operating rods. The mounting position (relative to the vacuum interrupters) is vertical. Under certain conditions horizontal mounting position is possible. Horizontal mounting position needs to be indicated when ordering. Please contact your Siemens representative. The vacuum circuit-breaker can be used in practically any system design. Under normal operating conditions, the vacuum circuit-breaker is maintenance free.

! 警告 本设备在运行时带有危险电压, 以及

可以通过远控实现高速运动的机械部

件. 违反正确安全操作说明有可能导致操

作人员受伤或破坏性损失. 只有完全熟悉本书所有警告,安全条例

以及产品维护程序的人员才可以使用

维护本设备. 本设备成功和安全的运行取决与正确

的搬运, 安装, 操作以及维护. 概述: 西门子 3AH3 真空断路器是三相户内型, 额定电压

从 7.2kV 至 36kV. 真空断路器由带有储能机构的操动机构箱, 控制元 件, 带灭弧室的三相极柱装配, 环氧浇注绝缘子以及 绝缘拉杆. 断路器安装位置为垂直 (相对于灭弧室). 在某些情

况下,水平安装位置是可能的,但需要在订货时注明,并与西门子办事处联系.断路器适用于各种电力系统

场合. 在正常使用条件下, 本断路器是完全免维护的. - 1/1 -

Administrator
文本框
上海锐杰电器有限公司提供
Page 5: Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 Operating Instr Engl-Chn... · Operating Instruction Siemens 3AH3 / 西门子3AH3 真空断路器使用手册. Standard

Operating Instruction Siemens 3AH3 / 西门子 3AH3 真空断路器使用手册

Technical data Type designation 3AH3 vacuum circuit-breakers are identified by a machine-readable product designation made up of a series of figures and letters.

3 A H 3 1 1 7 - 7 (See catalog HG11 for selection and ordering data of the respective circuit-breaker) Rating plate The rating plate which can be read in the operating position, contains the following information: 1 Manufacturer 7 Rated short-circuit duration 2 Type designation 8 Weight 3 Serial number 9 Rated operation sequence 4 Design code 10 Rated frequency 5 Year of manufacture 11 Rated lightning impulse 6 Rated normal current withstand voltage 12 Rated short-circuit

breaking current 13 Rated voltage Fig.1/1 Rating plate Note: in the event of any queries state the type designation(2), designation code(4) and the serial number(3).

技术数据 型号表达方式 3AH3 真空断路器按照下述一系列数字及字母代码组成

的表达式来标注. Basic type 基本型号 Rated voltage 额定电压 Rated short circuit breaking current 额定开断电流 Rated normal current 额定电流 (断路器具体订货选型参数见样本 11) 铭牌 铭牌可以从操作位置看到, 包括以下参数: 1 制造商 7 热稳定时间 2 型号 8 重量 3 系列号 9 额定操作顺序 4 设计编号 10 额定频率 5 制造年月 11 额定雷冲击耐受电压 6 额定电流 12 额定短路开断电流 13 额定电压 图.1/1 铭牌 注意: 如有任何询问请表明型号(2), 设计编号(4), 系列号(3).

- 1/2 -

503150

3117-7 2Y 3117-7

3150

2Y

50

O- O-

Administrator
文本框
上海锐杰电器有限公司提供
Page 6: Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 Operating Instr Engl-Chn... · Operating Instruction Siemens 3AH3 / 西门子3AH3 真空断路器使用手册. Standard

Operating Instruction Siemens 3AH3 / 西门子 3AH3 真空断路器使用手册

Standard specifications The 3AH3 vacuum circuit-breaker comply with the standards of IEC62 271-100, IEC60 694, BS 5311 and DIN VDE 0670. The V-breakers 3AH3 for 15kV rated voltage meet the requirements of the American standards ANSI C37 with respect to their insulating capacity. Ambient temperature/humidity and loadability The 3AH3 V-breakers are designed for the normal operating conditions laid down in the standards. Permissible ambient temperatures: Maximum value =+40 C Average over a period of 24 hours =+35 C Minimum value = -5 C Permissible atmospheric humidity: Relative humidity, 24 hours mean <95% Relative humidity, 1month mean <90% Under these conditions condensation may occasionally occur. The rated normal currents listed in Fig. 1/4 were laid down for 40°C ambience in accordance with DIN VDE/IEC. Use under conditions other than normal is possible with certain measures that can be implemen- ted on request. The maximum permissible load current as a function of the 3AH3 V-breaker ambient temperature has been plotted in Fig.1/2. The load currents indicated apply to open-type switchgear. Metal-enclosed switchgear must be derated as specified by switchgear manufacturer. Determination of the load characteristic number 负载特性曲线号的确定 Rated normal current load characteristic number 额定电流 负载特性曲线号 1250A 2 2000A 4 2500A 5 3150A 6 4000A 7

适用技术标准 西门子 3AH3 真空断路器完全符合 IEC 62 271-100, IEC 60 694, BS 5311 以及 DIN VDE 0670 的所有条款, 而且

对于 15kV 产品 还满足 ANSI C37 中的绝缘部分. 环境温度,湿度与负载能力 3AH3 真空断路器按正常使用条件设计可在以下温度和

湿度时正常工作. 最高温度 =+40 C 24 小时平均温度 =+35 C 最低温度 = -5 C 允许大气湿度: 24 小时相对平均湿度 <95% 1 个月中相对平均湿度 <90% 在上述湿度时,可能会出现凝露.图 1/4 是依照 DIN VDE/IEC 标准环境温度为 40°C 时额定电流函数曲线. 采取一定措施后断路器可在超标环境运行. 3AH3 最大允许负载电流是环境温度的函数, 图 1 示出了 这些曲线. 它们适用于断路器安装在敞开式的开关柜中. 如装于金属封闭式的开关柜中,则额定电流将有所减小, 应有开关柜制造厂重新确定.

-1/3 -

Load current A 负载电流

Fig.1/2 Maximum permissible load current as a function of the switch ambient temperature 图. 1/2 最大允许负载电流与开关环境温度的函数关系

Ambient temperature °C 环境温度

Administrator
文本框
上海锐杰电器有限公司提供
Page 7: Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 Operating Instr Engl-Chn... · Operating Instruction Siemens 3AH3 / 西门子3AH3 真空断路器使用手册. Standard

Operating Instruction Siemens 3AH3 / 西门子 3AH3 真空断路器使用手册

安装场所的高度 断路器的额定绝缘水平(额定冲击耐受电压, 额定工频耐 受电压) 1)是根据 VDE 标准 0111 和 IEC-71 基于标准状 态(大气压 1013 h Pa, 温度 20 °C 和相对湿度 11g/m 3) 制定的, 即在海平面处的大气标准条件.随着海拔高度的

升高, 空气密度变小, 绝缘体的空气绝缘水平下降.从海平

面升高到 1000m,上述的额定绝缘水平略下降 9%, 对此, VDE,IEC 以及其他标准都认为是允许的. 这些标准中没有对海拔高度大于 1000m 时的绝缘水平

作出规定, 应由客户和制造商根据具体情况达成协议解

决. 对此,我们有如下建议: 既然海拔 1000m 以下的绝缘水平机算方法被认为是有

效的, 它同样应适用于更高海拔的情况. 海拔修正系数 a 应 以 1000m 处的绝缘水平为基准,比海平面绝缘水平大约

下降 9%(相对应于 0.91 或 1/1.1). 以下公式可用于设备选择参考: 额定耐受电压选择值 2)

要求额定耐受电压 2) > (1.1xa)

例如: 安装场所海拔高度 3000 m 要求额定冲击耐受电压 95kV (对于 15kV 等级按照 ANSI 标准) 修正系数 a 0.73 (参照图 1/3) 额定冲击耐受电压选择值:

95kV 1.1x0.73 =118kV

额定电压为 24kV, 标准 2(额定雷冲击耐压 125 kV)的开

关设备可以满足要求. 于是安装场所实际绝缘水平 耐受电压 3)=a* 被选择开关设备的额定耐受电压 2) 图.1/3 Relationship between the correction factor a and the site altitude. 修正系数 a 与海拔高度的函数关系.

以下为适用定义: 1) 额定耐受电压

2)=根据 DIN,VDE,IEC 标准所提供的海 拔为零时的要求值 耐受电压

3 )=给定海拔高度的实际值. 2)

额定雷冲击耐受电压 额定工频耐受电压 3) 雷冲击耐受电压 工频耐受电压 -1/4 -

Altitude of site above sea level/海拔高度

Correction factor/修正系数

Administrator
文本框
上海锐杰电器有限公司提供
Page 8: Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 Operating Instr Engl-Chn... · Operating Instruction Siemens 3AH3 / 西门子3AH3 真空断路器使用手册. Standard

Operating Instruction Siemens 3AH3 / 西门子 3AH3 真空断路器使用手册

Electrical data 3AH3 vacuum circuit-breaker

电气参数 3AH3 真空断路器

U

(kV)

UW

(kV)

Us

(kV)

ISC

(kA)

tth

(s)

1250A

2000A

2500A

3150A

4000A

Ima

(kA)

D.C.

(%)

PA

(mm)

(11)

50 3 125 36 210 EU 3AH3 057-2*

EU 3AH3 057-6*

EU 3AH3 057-7*

275 EU 3AH3 077-8*

63 3 160 36 275 EU 3AH3 078-2*

EU 3AH3 078-6*

EU 3AH3 078-7*

7.2

60 20

EU 3AH3 078-8*

50 3 125 36 210 EU 3AH3 117-2

EU 3AH3 117-6

EU 3AH3 117-7

275 EU 3AH3 127-8

63 3 160 36 275 EU 3AH3 128-2**

EU 3AH3 128-6**

EU 3AH3 128-7**

12

75 28

EU 3AH3 128-8**

50 3 125 36 210 EU 3AH3 167-2**

EU 3AH3 167-6**

EU 3AH3 167-7**

275 EU 3AH3 177-8**

63 3 160 36 275 EU 3AH3 178-2**

EU 3AH3 178-6**

EU 3AH3 178-7**

15 95 36

EU 3AH3 178-8**

50 3 125 36 210 EU 3AH3 217-2**

EU 3AH3 217-6**

EU 3AH3 217-7**

275 EU 3AH3 227-8**

63 3 160 36 275 EU 3AH3 228-2**

EU 3AH3 228-6**

EU 3AH3 228-7**

17.5 95 38

EU 3AH3 228-8** 24 125 50 40 3 100 36 275 EU 3AH3 266-6 110 50 50 3 137 36 275 EU 3AH3 267-7

31.5 3 80 36 350 EK 3AH3 305-2***

EK 3AH3 305-4***

EK 3AH3 305-6***

36 170 70

40 3 100 36 350 EU 3AH3 306-6***

*Us=32kV; **Us=42kV;***Us=85/95kV,Uw=185/195kV. Note: available 1. Rated voltage (maximum permissible system voltage) at 50/60Hz. 2. Rated lightning impulse withstand voltage (peak value) 3. Rated power frequency withstand voltage (RMS value) 4. Rated short-circuit current 5. Rated short-circuit duration 6. Type designation 7. Rated normal current 8. Rated short-circuit making current 9. DC component of rated short-circuit breaking current 10. Pole center distance 11. Switching duties U= Rapid load transfer K= rapid auto-reclosure +U E= electrical operating energy Fig.1/4 electrical data for 3AH3 vacuum circuit-breaker

标注 : 可提供 1. 额定电压 (系统最高电压) 频率 50-60Hz 2. 额定雷冲击耐受电压 (峰值) 3. 额定工频耐受电压 (有效值) 4. 额定短路电流 5. 热稳定时间 6. 型号 7. 额定电流 8. 额定关合电流 9. 额定短路开断电流时的直流分量 10. 相中心距 11. 操作功能 U= 快速负荷转移 K= 快速自动重合闸 +U E= 电动储能机构 图.1/4 3AH3 真空断路器的电气参数 - 1/5 -

Administrator
文本框
上海锐杰电器有限公司提供
Page 9: Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 Operating Instr Engl-Chn... · Operating Instruction Siemens 3AH3 / 西门子3AH3 真空断路器使用手册. Standard

Operating Instruction Siemens 3AH3 / 西门子 3AH3 真空断路器使用手册

Operating times 动作时间

Closing time/合闸时间 Spring charging time/ 弹簧储能时间 Opening time/分闸时间 Shunt release/ 分励脱扣器 (Y1) Supplementary release 3AX11/ (Y2,Y4,Y7) 辅助脱扣器 3AX11 Arcing time/燃弧时间 Break time/开断时间 Shunt release/分励脱扣器 (Y1) Supplementary release 3AX11/ (Y2,Y4,Y7) 辅助脱扣器 3AX11 Dead time/断电时间 Close-open-time/金属短接时间 Shunt release/分励脱扣器 (Y1) Supplementary release 3AX11/ (Y2,Y4,Y7) 辅助脱扣器 3AX11 Minimum pulse duration/指令的最短时间 ″Close″/″合闸″ Closing solenoid/合闸线圈 (Y9) ″Trip″ / ″脱扣″ Shunt release/分励脱扣器 (Y1) ″Trip″ / ″脱扣″ Supplementary release 3AX11 (Y2,Y4,Y7) 辅助脱扣器 3AX11 Shortest pulse duration of breaker tripping signal for 1st shunt release /一级分励脱扣器最小脱扣脉冲信号时间 Shortest pulse duration of breaker tripping signal for 2nd and 3rd shunt release /2 级和 3 级分励脱扣器最小脱扣

脉冲信号时间

ms s

ms ms

ms ms ms

ms ms ms

ms ms ms

ms ms

<80 <15 <65 <45

<15 <80 <60

300 <90 <70

45 40 20

>15 >10

Fig.1/5 operating times/ 图.1/5 动作时间

Closing time = the interval of time between the initiation of the closing operation and the instant when the contacts touch in all poles. Opening time = the interval of time between the initiation of the opening operation and the instant when the contacts separate in all poles. Arc time = the interval of time between the instant of the first initiation of an arc and the instant of final arc extinction in all poles. Breaking time = the interval of time between the beginning of the opening time of a circuit breaker and the end of the arcing time. Close-open-time = the interval of time (in a make-break operation cycle) between the instant when the contacts touch in the first pole in the closing process, and the instant when the arcing contacts separate in all poles in the subsequent opening process Switching duties The operating mechanisms of the 3AH3 circuit-breakers are suitable for rapid auto-reclosure. Breakers for a rated short-circuit breaking current of ≥40kA are, at rated data levels, suitable for rapid load transfer and till 31.5kA for rapid auto-reclosure. Motor operating mechanism The maximum DC power input is 500 W (approx.) the maximum AC power input is 650VA (approx.). During part of the short spring charging time the motor operate in the overload range. The recommended rating for motion protection devices are shown in Fig.1/6 (the protection devices are not supplied with the vacuum breakers and must be ordered separately) *) MCB with G characteristic Fig.1/6 Rated currents of motor protection device. The supply voltage may deviate from the rated value by -15% to +10%.

合闸时间 =从合闸操作开始到三相触头全部接触这一瞬间该 段时间间隔. 分闸时间 = 从分闸操作开始到三相触头全部分离这一瞬间的 该段时间间隔. 燃弧时间 = 从燃弧初始到各相电弧全部熄灭瞬间的时间间隔. 开断时间 = 从断路器开始分闸到燃弧结束的时间间隔. 合-分时间 = 在合闸过程中当第一相触头接触瞬间到紧接着的 分闸操作中三相燃弧触头全部分离瞬间的时间间隔. 切合负载 3AH3 的操动机构适用于快速自动重合闸.对于额定开

断电流为 40kA 及以上的断路器具有快速负荷转移功能; 对于 31.5kA 及以下则同时具有快速重合闸功能 电动机操动机构 最大直流输入功率为 500W. 最大交流输入功率约为 650VA. 在弹簧储能的部分时间中电动机处于过负荷状态. 表.1/6 出示

了我们推荐的电动机保护装置.(不随断路器一起供货, 如用户

需要则另外定购) *) 具有 G 特性的低压朔壳开关 图.1/6 电动机保护设备的额定电流 操作电压可在额定电压-15%至+10%的范围内波动. - 1/6 -

Rated supply voltage 额定电压

DC24V DC48V DC60V DC/AC 110V 50/60HZ

DC220V/AC230V 50/60HZ

Recommended rating of protection device* 保护装置推荐等级*

16A 8A 6A 3A 1.6A

Administrator
文本框
上海锐杰电器有限公司提供
Page 10: Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 Operating Instr Engl-Chn... · Operating Instruction Siemens 3AH3 / 西门子3AH3 真空断路器使用手册. Standard

Operating Instruction Siemens 3AH3 / 西门子 3AH3 真空断路器使用手册

Auxiliary switch (S1) 3SV92 辅助开关(S1) 3SV92Two versions of the auxiliary switch can be supplied. The standard version is fitted with 6 NO contacts and 6 NC contacts. The extended version is fitted with 12NO contacts and 12NC contracts. Rated insulation voltage: AC/DC 250 V Insulation class: C acc. to DIN VDE 0110 Current: 10A Making capacity: 50A

本产品提供两种型号的辅助开关. 标准型号是 6 常开 6常闭. 延长型为 12 常开 12 常闭. 额定电压: AC/DC 250V 绝缘等级: C 级 符合德国标准 DIN VDE 0110 电流: 10A 额定关合电流: 50A

Breaking capacity/ 切断能力 AC 40 to 60 Hz/交流 40~60Hz DC/直流

Operational current/操作电流 I (A)

Voltage 电压 U (V)

Operational current 操作电流

I (A)

Voltage 电压 U (V) Resistive load/阻性负载 Inductive load/感性负载

(T=20ms) <230V 10 24

48 60 110 220

10 10 9 5

2.5

10 9 7 4 2

Fig.1/7 Breaking capacity of 3SV92 auxiliary switch Low-voltage plug connector (X0) The control elements of the 3AH3 vacuum circuit-breaker provided in the mechanism housing are wired for external connection to the plug connector(X0). The standard version is provided with a 64-pole plug connector. Shunt closing release (Y9) 3AY1510 The closing solenoid unlatches the charged closing spring and thus closes the circuit-breaker electrically It is available for both AC and DC operation. After completion of a closing operation, the closing solenoid is de-energized internally. Power consumption approx. 140 W/VA

图.1/7 辅助开关 3SV92 的开断能力 低压二次接插件(X0) 3AH3 断路器机构箱内的控制单元所有接线被引至低压

接插件(X0), 标准型号提供的是 64 针接插件. 合闸线圈(Y9) 3AY1510 合闸线圈通电动作使合闸弹簧释放能量, 这就是电气合 闸. 交直流操作均可, 合闸完成后,合闸线圈失电. 功率消耗约 140 W/VA

Shunt releases (shunt opening releases) The shunt releases are used for automatic tripping of circuit-breakers by means of appropriate protective relays and for deliberate tripping by other electrical means. They are designed for connection to external voltage (DC or AC voltage). In special cases, for deliberate tripping, they can also be connected to a voltage transformer. Shunt releases based on two different operating principles are used. Shunt release (Y1) 3AY1510 The 3AY1510 shunt release is used as standard in the basic circuit-breaker version, with this design, the electrically supplied tripping pulse is passed to the ″open″ latching mechanism by means of a direct-action solenoid armature and the circuit-breaker is thus opened. It is available for both AC and DC operation. After completion of an opening operation, the AY1510 shunt release is de-energized internally. In operation with AC voltage, a rectifier module 3AX1525-1F is installed in the circuit-breaker. Power consumption approx. 140 W/VA

分励脱扣器 (分闸线圈) 分励脱扣器是用于经由相应的保护继电器来实现断路器

自动脱扣的装置,还可用于其他的电气措施来实现某些特

定的脱扣动作.分励脱扣器由直流或交流电源供电, 在特 殊情况下, 它们也可接在电压互感器上 分励脱扣器有两种不同的脱扣原理. 分励脱扣器 (Y1) 3AY1510 3AY1510 分励脱扣器是断路器基本结构的标准脱扣器. 该脱扣器可以直接用线圈的铁芯"打开"锁扣机构, 于是断 路器分闸. 交直流操作均可, 分闸完成后,分励脱扣器失电. 交流操作时,断路器加装 3AX1525-1F 整流模块. 功率消耗约 140 W/VA

- 1/7 -

Administrator
文本框
上海锐杰电器有限公司提供
Page 11: Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 Operating Instr Engl-Chn... · Operating Instruction Siemens 3AH3 / 西门子3AH3 真空断路器使用手册. Standard

Operating Instruction Siemens 3AH3 / 西门子 3AH3 真空断路器使用手册

Shunt release (Y2) 3AX1101 1)

The 3AX1101 shunt release is fitted if more than one shunt release is required. With its design, the electrical opening command is transferred in boosted form to the ″Open″ latching mechanism via a solenoid armature through unlatching of a energy store and thus the circuit-breaker is opened. Any varistors and rectifiers required are integrated in the release. Power consumption: <60W or <55VA Undervoltage release (Y7) 3AX1103 1)

Undervoltage release consist of a stored-energy mechanism, an unlatching mechanism and an electromagnet system which is connected continuously to the supply when the circuit-breaker is in the close state. If this voltage drops to below a certain value the unlatching mechanism is released and opening of the circuit-breaker is thus initiated via the stored-energy mechanism. The deliberate tripping of undervoltage release generally takes place via an NC contact in the tripping circuit. But it can also be carried out via an NO contact by short-circuiting of the magnet coil. With this type of tripping, the short-circuit current is limited by the built-in resistors (see circuit diagram Fig.3/4) Under voltage releases can also be connected to voltage transformers. When the operating voltage drops to impermissibly low levels, the circuit-breaker is tripped automatically. Power consumption: <6.5 W or <7.5 VA CT-Operated release (Y4) 3AX1102 1)

CT-operated releases consist of a stored-energy mechanism, an unlatching mechanism and an electromagnet system. When the tripping current is exceeded (90% of the CT-operated release rated current) the unlatching device of the stored-energy mechanism is released and thus opening of the circuit-breaker is initiated. In addition to the primary current transformer, matching transformers are required for application of the CT-operated releases. Power consumption for 0.5A and 1A<6VA at 90% of the rated current and with open armature. CT-operated release (Y6) 3AX11041) (Low-energy release 0.1Ws) In connection with a solid-state release (7SJ41 overcurrent time protection or similar) and low-power primary current transformers (window-type transformers), it is possible with the 3AX1104 to create a CT-operated release without additional supply voltage. The 3AX1104 is of similar design as the 3AX1101 /1102 releases. With its coil data and its low energy requirement of < 0.1Ws, its designend to be directly actuated by a release impulse provided by a capacitor of the above-mentioned electronic release systems.

1) Can be ordered on request, retrofitting possible.

分励脱扣器 (Y2) 3AX1101 1).

当需用不止一个脱扣器时, 则安装 3AX1101 分励脱扣器. 使用该脱扣器时, 电气分闸指令以放大形式传给线铁芯, 然后打开储能元件的锁扣系统, 将断路器分闸.所有必需

的变阻器和整流模块在分励脱扣器中被集成化. 功率消耗最大值: <60W 或<55VA 欠电压脱扣器 (Y7) 3AX1103 1)

欠电压脱扣器由一套储能机构, 解锁机构以及电磁系统 构成, 当断路器处于闭合状态时, 该电磁系统与电源相连 接. 当电源电压降低至某一树值时, 解锁机构释放, 通过 弹簧储能机构将断路器分断. 这种精巧的欠电压脱扣器装置通常通过接在脱扣回路中

的一个常闭触点来动作. 但是也可以用短接其电磁线圈的 方式使用一常开触点, 短路电流由装置内的电阻限制( 见图 3/4) 欠电压脱扣器还可以安装在电压互感器上, 当工作电压 降到允许值以下时, 断路器自动脱扣. 功率消耗约: <6.5 W 或<7.5 VA 电流互感器驱动型脱扣器 (Y4) 3AX1102 1)

电流互感器驱动型脱扣器由一套储能机构, 解锁 机构以及电磁系统构成. 当脱扣电流超过脱扣器额 定脱扣电流的 90%时, 储能机构的解锁装置脱扣, 然后断

路器实现分闸. 除了电流互感器之外, 这种脱扣器还需配

用一个耦合变压器. 对于 0.5A 和 1A 两种规格, 当脱扣电流为 90%额定脱扣 电流时, 且脱扣器带有运动铁芯时, 功率消耗为<6VA 电流互感器驱动型脱扣器 (Y6) 3AX11041) (低能脱扣器 0.1Ws) 把电子脱扣器 (类似 7SJ41 过流时间保护或其他)和 低功率初级电流互感器(窗式互感器)相连, 就可以和 3AX1104 形成一个无需附加电源的电流互感器驱动 型脱扣器. 3AX1104 与 3AX1101/3AX1102 脱扣器的设计非常 相似. 根据线圈参数以及<0.1Ws 的低能耗要求, 它可以 由上述电子脱扣系统中的一个电容所提供的脱扣脉冲信

号直接动作. 1) 可按需定购, 改装也可能实现.

- 1/8 -

Administrator
文本框
上海锐杰电器有限公司提供
Page 12: Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 Operating Instr Engl-Chn... · Operating Instruction Siemens 3AH3 / 西门子3AH3 真空断路器使用手册. Standard

Operating Instruction Siemens 3AH3 / 西门子 3AH3 真空断路器使用手册

Breaker tripping signal, cut-out switches (S6 and S7)

When the vacuum circuit-breaker is tripped by means of a release, the position switch S6 briefly makes contact. This contact making can be used for signalling. In the event of intentional mechanical tripping, the cut-out switch S7 breaks this contact. Varistor module (V1 to V3) 3AX1526 1) The disconnection of inductive loads in DC circuits may cause switching overvoltage which pose a risk to electronic control units. In order to prevent this, the inductances of the circuit-breaker mechanism and control (motor, closing solenoid, shunt release and auxiliary contactor) can be connected to varistor (with DC operation). For rated operating voltage of 60V to 220V DC the varistor module 3AX1526 is available as an accessory; it limits the overvoltage to about 500V. The module contains 2 separate varistor circuits. Electrical local closing/electrical interlocking1)

In the basic version, the closing spring must be released mechanically if the breaker is to be closed locally. A version with electrical local closing can also be supplied. In this version, the making circuit of the circuit-breaker is activated electrically via a push-button. In this way, allowance can also be made for station-specific interlocks, and undesired making operations prevented. For example, interlocking of the circuit-breaker is possible via the auxiliary contact of a disconnector. Circuit-breaker with electrical local closing cannot be closed mechanical. Mechanical interlocking1) Operating mechanism of disconnectors can be fitted with a mechanical switchgear interlocking facility. The disconnector and the associated circuit-breaker are in this case interlocked mechanically. The sensing parts check the switch position of the circuit-breaker and prevent if from closing mechanically and electrically if the associated disconnector is not in a position to allow safe operation. On the other hand, the disconnector is prevented from being operated when the circuit-breaker is closed. The mechanical interlocking facility can also be used to interlock breaker trucks or draw-out breaker parts. Adjustment instruction: 3G 460 00127 (3AX 1520-3C) Dimensions and weight The dimensions and weights of the vacuum circuit-breaker are shown in the relevant drawings. For planning purposes, the drawings showing detailed overall dimensions, can be ordered through the appropriate Siemens agency. The weight is also stated on the breaker rating plate.

1) Can be ordered on request, retrofitting possible.

分闸脱扣信号 S6 和信号消除开关 S7

当断路器分闸是由于脱扣装置引起时, 位置开关 S6 会短 时闭合, 这可以作为脱扣跳闸信号. 在正常机械分闸时, 信号消除开关 S7 首先断开. 压敏电阻模块 (V1 to V3) 3AX1526 1) 切断直流感性负荷时可能会产生危害控制线路中电子元

件的操作过电压. 为防止这一危害, 断路器机械和控制部 分中的感性元件 (电动机, 合闸线圈, 分励脱扣器以及辅 助接触器可以接有压敏电阻 (直流操作时). 3AX1526 压敏电阻模块可用于直流 60V-220V; 它可以把过电压 限制在 500V 左右.该模块由两个独立的压敏电阻回路组

成. 电气就地合闸/电气联锁 1)

在基本配置中, 如要求断路器就地合闸, 则必须运用机械 合闸. 本产品还可以提供电气就地合闸装置. 这个装置 利用一个按钮以实现断路器电气合闸. 通过这个装置还可 以实现电站的某些特殊联锁. 例如, 通过隔离开关的辅助 触点完成断路器与其的联锁. 带有电气就地合闸的断路器不具有机械合闸功能. 机械联锁 1) 隔离开关的操动机构可以装有一套机械联锁装置. 这套 装置将隔离开关与其相关的断路器用机械方法加以联锁. 机械联锁的探头部分可以辨别断路器的合,分位置, 如果 与断路器相关的隔离开关的闸刀处于不能确保安全操作

的位置时, 断路器就不能闭合. 另一方面, 当断路器处于 合闸状态, 联锁装置可阻止操作隔离开关. 机械联锁装置还可用于断路器手车或可移开部分的联锁. 调节指示: 3G 460 00127 (3AX 1520-3C) 外形尺寸及重量 真空断路器的外形尺寸及重量可以在相应图中查到. 考虑布置方案时, 可以向西门子公司的合法代理商定购 详细的总体外形尺寸图. 重量可在断路器铭牌上查到. 1) 可按需定购, 改装也可能实现. - 1/9 -

Administrator
文本框
上海锐杰电器有限公司提供
Page 13: Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 Operating Instr Engl-Chn... · Operating Instruction Siemens 3AH3 / 西门子3AH3 真空断路器使用手册. Standard

Operating Instruction Siemens 3AH3 / 西门子 3AH3 真空断路器使用手册

Description Construction The vacuum circuit-breaker consists of the mechanism housing (60.), the 3-pole assemblies (19.) with vacuum interrupter (30.), cast-resin post insulators (16.1and 16.2), struts (28.) and of the operating rods (48.) with contact pressure springs (49). Each of three pole assemblies (19.) is supported by two cast-resin post insulators (16.1and 16.2), which are bolted to the pole plate (15) respectively. The main feature of the 3AH3 vacuum circuit-breaker are shown in Fig.2/1. The mechanism housing (60.) accommodates all electrical and mechanical elements required for opening and closing the vacuum circuit-breaker. Fig. 2/2 shows the arrangement of the individual modules in the mechanism housing. The mechanism housing has a detachable cover 60.1(Fig.2/3). This cover (60.1) has cutouts for the actuating and indicating devices. The vacuum circuit-breaker is closed by means of the pushbutton (53.). The motor (50.4) immediately recharges the closing spring (62.). In the event of motor power supply failure, the closing spring can be charged by means of a hand crank (50.). The cover includes an opening (50.1) for the hand crank, behind which the hand crank coupling (50.5) of the gearing (50.2) is located. The stored-energy mechanism state is shown by the indicator (55.). The indicator (59.) shows the breaker state (ON-OFF). The operating cycle counter (58.) indicates the number of charging operations. The rating plate (51.) is attached to the mechanism housing but visible through an opening (51.1) in the cover. The movement is transmitted to the pole assemblies via moulded-plastic operating rods (48.).

说明 结构 真空断路器由机构箱 (60.), 3 相极柱装配 (19.) 真空 灭弧室 (30.), 环氧浇注绝缘子 (16.1 和 16.2), 绝缘支杆 (28.) 和带有触头压力弹簧 (49)的绝缘拉杆(48.). 每相极柱装配 (19.) 由两个环氧浇注绝缘子 (16.1 和 16.2) 所支撑, 绝缘子是通过螺栓连接分别固定在支撑板 上 (15). 3AH3 真空断路器的主要特征见图 2/1. 机构箱 (60.) 包含了用于合分断路器 的所有机械和电气 单元. 图.2/2 显示了机构箱中各个独立的模块单元. 机构箱有一块可拆卸的面板 60.1(图.2/3). 面板 (60.1) 有操作和指示设备的开孔. 真空断路器通过按钮 (53.) 合闸后. 马达 (50.4) 立即对 合闸弹簧 (62.) 储能. 在电动储能失败的情况下,合闸弹 簧可通过手柄 (50.) 进行手动储能. 面板上有一个手动 储能的开孔(50.1), 它的后面是齿轮箱 (50.2) 的 手柄储 能机构 (50.5). 储能机构状态通过储能指示器 (55.) 显 示. 指示器 (59.) 显示断路器状态 (合-分). 操作计数器 (58.) 显示了储能操作次数. 铭牌 (51.) 安放于机构箱中 但是可以通过面板上的开孔 (51.1) 看到. 合分操作通过绝缘拉杆 (48.) 传送到极柱装配.

- 2/1 -

Fig.2/1 3AH3 vacuum circuit-breaker 图.2/1 3AH3 真空断路器

Administrator
文本框
上海锐杰电器有限公司提供
Page 14: Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 Operating Instr Engl-Chn... · Operating Instruction Siemens 3AH3 / 西门子3AH3 真空断路器使用手册. Standard

Operating Instruction Siemens 3AH3 / 西门子 3AH3 真空断路器使用手册

Fig. 2/2 View of an open mechanism housing 图. 2/2 卸去面板的机构箱主视图 Fig. 2/3 Actuating and indicating devices 图. 2/3 操作和指示设备

- 2/2 -

Tightening torque:10Nm 紧固力矩: 10Nm

Administrator
文本框
上海锐杰电器有限公司提供
Page 15: Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 Operating Instr Engl-Chn... · Operating Instruction Siemens 3AH3 / 西门子3AH3 真空断路器使用手册. Standard

Operating Instruction Siemens 3AH3 / 西门子 3AH3 真空断路器使用手册

The pole assembly (19.) consists of the upper interrupter support (20.) with the upper terminal (27.), the vacuum interrupter (30.), the lower interrupter support (40.) with the lower terminal (29.), the clamp (29.2) with the flexible connector (29.1) and angled lever (48.6). The centering piece (28.1) and the struts (28.) relieve the vacuum interrupters of external forces see (Fig. 2/4). Fig. 2/4 3AH3 pole assembly 图. 2/4 3AH3 极柱装配

真空断路器极柱装配 (19.) 包括带有上接线终端 (30.) 上极帽 (27.), 带有下接线终端 (29.) 下极帽, 以及连接于 软连接 (29.1) 的导电夹 (29.2) 和拐臂 (48.6). 衬垫 (28.1) 和 绝缘支撑杆 (28.) 减弱了施加于真空灭弧室的 外部压力(见图.2/4).

- 2/3 -

Administrator
文本框
上海锐杰电器有限公司提供
Page 16: Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 Operating Instr Engl-Chn... · Operating Instruction Siemens 3AH3 / 西门子3AH3 真空断路器使用手册. Standard

Operating Instruction Siemens 3AH3 / 西门子 3AH3 真空断路器使用手册

Vacuum interrupters The basic construction of the vacuum interrupters for the 3AH3 vacuum circuit-breaker is shown in the sectional view in Fig.2/5. Depending on its type, the vacuum interrupter (30.) is fixed to the upper interrupter support (20.). The arcing chamber (33.) is located between two ceramic insulator (32.). The fixed contact piece (31.) is connected directly with the housing. The moving contact piece (36.) is fixed to the terminal bolt (36.1) and is located centrally in the guide (35.). The metal bellows (34.) forms the vacuum-proof connection to the interrupter housing. Fig.2/5 vacuum interrupter 图. 2/5 真空灭弧室 The vacuum interrupters fitted in the 3AH3 vacuum circuit-breaker are type-approved in accordance with the X-ray regulations of the Federal Republic of Germany. They conform to the requirements of the X-ray regulations of January 8, 1987 (Federal LAW Gazette Page 144) § 8 and annex Ш section 5 up to rated short-time AC voltage stipulated in accordance with DIN VDE/IEC.

真空灭弧室 3AH3 真空断路器灭弧室的基本结构的剖面如图 2/6. 依照这种结构, 真空灭弧室 (30) 由上支撑(上极帽) (20.)固定. 金属灭弧室 (33.) 位于上下瓷绝缘外罩 之间.静触头 (31.) 与灭弧室外壳固定在一起. 动触头 (36.) 与动触头杆 (36.1) 相连并且位于导向管 (35.) 中央玻纹管 (34.) 与灭弧室形成密封保护连接. 装于 3AH3 真空断路器的灭弧室是经过型式试验考核的, 符合德国对于 X 射线计量的规定. 并满足 (联邦法律公报 144 页) 第 5 章第Ш部分第 8 款关于按照 DIN VDE/IEC 标准中规定在额定短时交流电压下 X 射线的要求.

- 2/4 -

Administrator
文本框
上海锐杰电器有限公司提供
Page 17: Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 Operating Instr Engl-Chn... · Operating Instruction Siemens 3AH3 / 西门子3AH3 真空断路器使用手册. Standard

Operating Instruction Siemens 3AH3 / 西门子 3AH3 真空断路器使用手册

Complement The basic version of the vacuum circuit-breaker comprises: Electrical operating mechanism (charging motor) With mechanical and electrical anti-pumping feature (M1) Closing solenoid (Y9) Shunt release (Y1) Low-voltage plug connector, 64-pole (X0) with grommet sleeve housing Auxiliary switch 6NO+6NC (S1) Position switch for signaling "Closing spring charged" (S41, S42) Breaker tripping signal, cut-out switch (S6, S7) Operating cycle counter Each 3AH3 vacuum circuit-breaker can be equipped with the following supplementary devices: Terminal block (X0) Extended auxiliary switch 12NO+12NC (S1) Shunt release 3AX1101 (Y2) Current transformer-operated release 3AX1102 (Y4, Y5) Current transformer-operated release 3AX1104(0.1Ws) (Y6) Undervoltage release 3AX1103 (Y7) Electrical manual closing (S14, S15) Mechanical interlock In addition to the standard shunt release Y1, the 3AH3 vacuum circuit-breaker can be fitted with a maximum of two release of type 3AX 11 The permissible combination of supplementary equipment and special versions are stated in catalogue HG 11.

完整单元 标准型断路器包含以下: 电动机构 (储能马达) 带有机械及电气防跳 (M1) 合闸线圈 (Y9) 1 级分励脱扣 (Y1) 64 针低压接插件 (X0) 辅助开关 6 常开+6 常闭 (S1) "合闸弹簧储能"位置信号开关 (S41, S42) 脱扣信号及消除脱扣信号开关 (S6, S7) 操作计数器 3AH3 真空断路器还可加装以下附加设备: 二次接线端子排 (X0) 延长型辅助开关 12 常开+12 常闭 (S1) 2 级分励脱扣器 3AX1101 (Y2) 电流互感器驱动型脱扣器 3AX1102 (Y4, Y5) 电流互感器驱动型脱扣器 3AX1104(0.1Ws) (Y6) 欠电压脱扣器 3AX1103 (Y7) 电气手动合闸 (S14, S15) 机械联锁 除了标准分励脱扣器 Y1 外, 每台 3AH3 断路器最多还可 加装两个附加脱扣器 3AX 11. 允许的附加设备组合和特殊型号可参阅样本 HG 11. - 2/5 -

Administrator
文本框
上海锐杰电器有限公司提供
Page 18: Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 Operating Instr Engl-Chn... · Operating Instruction Siemens 3AH3 / 西门子3AH3 真空断路器使用手册. Standard

Operating Instruction Siemens 3AH3 / 西门子 3AH3 真空断路器使用手册

Installation Installing in cubicle or on truck The 3AH3 vacuum circuit-breaker are supplied in the open state with the ″closing spring discharged″ indication (55.) visible. Before installing the 3AH3 V-breaker, remove the transport device (skids and spacers). Mount face loose supplied phase barrier in accordance with the supplied drawings. Before installing the 3AH3 vacuum circuit-breaker in a cubicle or a truck check its rating plate data (to avoid confusion) and compare the rated voltage indicated in the delivery papers with the power supply voltage available at the site. On the vacuum circuit-breaker with undervoltage release (Y7) 3AX1103, the arresting screw of the hammer must be moved from position A to B (see annex to operating instructions for release or note card in mechanism housing [60.] of vacuum circuit-breaker). On the pole plate (15.) and on the mechanism housing (60.) there are a total of 14 fixing holes – to suit the various types of installation (Fig.3/1). For installation of vacuum circuit breakers with rated short circuit breaking current > 50kA we recommend to only the pole plate. Use M12 fixing bolts - strength class 8 – making reference to the mandatory dimension drawings. The rack or frame must be adapted to the operating conditions and have adequate load bearing capacity and stability. Flat bar connection Prior to fitting the conductors fix them so as to ensure smooth contact with their connecting parts and with the holes in full alignment. Rub the contact faces to be bolted together with criss-crossing strokes using a wire brush until bright metal shows and wipe then with a clean rag. Note! Copper-sprayed and spray silver-plated surfaces should be cleaned a rag and not brushed.

安装 安装在开关柜中或手车上 3AH 真空断路器出厂时处于分闸状态并 可看到″合闸弹 簧未储能″指示 (55.). 在安装 3AH3 断路器以前, 首先除 去运输装备 (垫木及固定铁板). 根据所提供的图纸安装 固定相间隔板 在把断路器安装于开关柜或手车之前, 核对铭牌数据 (以防混淆)并且比较断路器额定电压是否与现场电压一致. 对于带有欠电压脱扣器 (Y7) 3AX1103 的断路器, 脱扣器

上的调节螺栓必须从 A 位调整到 B 位 (详见附录 脱扣器使用说明或断路器机构箱 (60.) 的说明卡). 在极柱安装板 (15.) 和机构箱上 (60.) 共有 14 个固定孔 – 适用于不同的安装 (图.3/1). 当安装额定短路电流大于

50kA 时的断路器时我们建议使用极柱安装板图的安装孔. 应用 M1 固定螺栓 - 强度等级为 8 级 - 参照指示尺寸图. 支架或外框架必须适合于操作条件并且具有足够的承载

能力和稳定性. . 平滑母排连接 预先安装之前, 检查连接导体是否光滑接触并且安装孔 完全匹配. 用金属丝刷上下左右擦抹将要用螺栓对接的接触面直到 金属发亮然后用干净抹布擦净. 注意! 喷铜或镀银表面应用抹布清洁切勿用刷子. - 3/1 -

View Y/ Y 向

View Z/ Z 向 Fig.3/1 Means of fixing 3AH3 vacuum circuit-breaker图.3/1 3AH3 真空断路器的固定方法

* Holes for M12 bolts * M12 螺栓孔

Administrator
文本框
上海锐杰电器有限公司提供
Page 19: Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 Operating Instr Engl-Chn... · Operating Instruction Siemens 3AH3 / 西门子3AH3 真空断路器使用手册. Standard

Operating Instruction Siemens 3AH3 / 西门子 3AH3 真空断路器使用手册

Differing contact materials (AL/CU) must not be worked with the same cleaning tool. Thinly grease the bright contact faces with acid-free Vaseline (e.g. Shell Vaseline 8420) or equivalent anti-corrosion agent and bolt them together immediately 1). Note: Silver-plated parts must not be bolted together with aluminium bars. Use the appropriate M12 nuts and bolts of strength class 8 and corresponding spring elements and plain washers. Note! When tightening the terminal screws, counteract the torque (70Nm~7mkp) by resisting it with a suitable spanner or socket wrench. Control leads Vacuum circuit-breaker of standard design are provided with a 64-pole low-voltage plug connector X0 (68.7.1). The corresponding plug for external connection is designed for crimp connection of control leads with a nominal section area of 1.5mm2. Use only crimping tools (e.g. Amphenol crimp tongs TA 0500 with positioning sleeve TA 0000141 and TA 0007 146 0003) 2). Make reference to the circuit diagram supplied. Earthing Connect the vacuum circuit-breaker to the appropriate high voltage protective earth by means of the suitable marked M12 (70.)(see Fig.3/3) terminal on the top of the mechanism housing (60.) using flat copper, copper cable or hot galvanized steel strip (DIN VDE 0141/7.76 Item 5.3). If the V-breaker with the mechanism housing are installed in an earth metal rack so that firm electrical contact is established, the mechanism housing need not be earthed separately. When installing the switch externally, toothed serrated washers (DIN 6789) must then be placed under the bolt heads. Circuit documents The wiring and connection of circuit-breaker is shown in the circuit diagram supplied, depending on the particular model and complement. Typical circuit diagram for circuit-breaker are shown in Fig. 3/3 and 3/5.

不同的连接导体 (铝/铜) 不允许用同样的清洁工具, 用 无酸凡士林 (如 Shell 凡士林 8420) 或同等的防腐剂薄薄 地涂抹于接触表面,然后立即用螺栓加以连接 1). 注意: 镀银部件绝对不允许与铝排固定连接. 使用强度等级 8 级的 M12 螺栓和螺母以及适当的平垫圈,弹簧垫圈. 注意! 当最终拧紧时, 须使用适当的扭矩扳手,扭矩为 70Nm~7mkp. 二次控制引线 标准型的断路器提供 64 针低压插座 X0 (68.7.1). 相应 用于外部连接的插头可连接截面积为 1.5mm2的成束二 次控制引线, 在连接时应使用恰当的束线工具. (例如 Amphenol 束线钳 TA 0500 带有位置出套 TA0000141 加 TA 0007 146 0003) 2). 参照本书所提供的二次线路图. 接地 对于断路器高压接地保护可使用位于机构箱 (60.) 顶部

的带有接地标志的接地终端 M12 (70.)(见图.3/3) 可使用

扁平铜排, 铜芯电缆或经热度锌处理的钢条 (DIN VDE 0141/7.76 目录 5.3). 当真空断路器机构箱安装于接地金属支架时, 机构箱无 须再单独接地. 但连接时需采用带齿形的接地垫圈 ( DIN 6789). 二次线路图 断路器的二次线路接线见所提供的二次线路图, 根据特

殊型号及补充. 断路器的典型二次线路图参阅 图. 3/3 和 3/5.

- 3/2 -

70Fig.3/2 图 .3/2

Administrator
文本框
上海锐杰电器有限公司提供
Page 20: Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 Operating Instr Engl-Chn... · Operating Instruction Siemens 3AH3 / 西门子3AH3 真空断路器使用手册. Standard

Operating Instruction Siemens 3AH3 / 西门子 3AH3 真空断路器使用手册

Function schematic diagram 功能示意图

HA Manual tripping/手动脱扣 HE Manual closing/手动合闸 K1 Anti-pumping contactor 防跳接触器 M1 Motor operating mechanism/马达储能机构 P Energy store/能量储存 R1 Resistor/电阻 S1 Auxiliary switch/辅助开关 S21, S22 Position switches (cut-out motor after charging) 位置开关 (储能后切断马达回路) S3 Position switches (open when closing spring charged ) 位置开关(合闸弹簧储能后断开) S41, S42 Position switch (signals charged state) 位置开关 (合闸弹簧储能信号) S6, S7 Position switches (for switch tripped signal) 位置开关 (脱扣信号) X0 Low-voltage plug connector 二次插座

Y1 1st shunt release/一级分励脱扣器 Y2 2nd shunt release/二级分励脱扣器 Y4, Y5, Y6 CT operated release/电流互感器驱动型脱扣器 Y7 Undervoltage release/欠电压脱扣器 Y9 Closing solenoid/合闸线圈 S10, S11 Position switches (mech. pumping prevention) 位置开关 (机械防跳) - 3/3 -

Fig.3/3 V circuit-breaker 3AH3 with manual and electrical closing with 64-way plug connector 图.3/3 带手动合闸, 电动合闸以及 64 针低压插座的 3AH3 真空断路器

Motor drive 马达驱动

Closing and anti- pumping device 合闸及防跳装置

1st shunt release 一级分励脱扣

Switch tripping signal 脱扣信号

closing spring charged signal 合闸弹簧储能信号

System wiring 系统接线

Tripping via NC contact 跳闸回路常闭触

Tripping via NC contact 跳闸回路

常闭触点

Breaker wiring 断路器接线

System wiring 系统接线

Release "off" 脱扣器 "脱离"

-Y6 -Y5 -Y7

Fig.3/4 typical circuit for connection of the undervoltage release Y7 图.3/4 欠电压脱扣器 Y7 的典型接线图

Administrator
文本框
上海锐杰电器有限公司提供
Page 21: Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 Operating Instr Engl-Chn... · Operating Instruction Siemens 3AH3 / 西门子3AH3 真空断路器使用手册. Standard

Operating Instruction Siemens 3AH3 / 西门子 3AH3 真空断路器使用手册

Function schematic diagram 功能示意图

-Y6 -Y5

- 3/4 -

Motor drive 马达驱动

Closing and anti- pumping device 合闸及防跳装置

1st shuntrelease 一级分 励脱扣

Switch tripping signal 脱扣信号

Closing spring charged signal 合闸弹簧储能信号

1st CT operated release 一级电流互感器

驱动型脱扣器

Electrical manual closing 手动电气

合闸

Fig.3/5 V circuit-breaker 3AH3 with electrical manual closing with 64-way plug connector

Example for extended fitting with Y4 and varistor circuit for DC 图.3/5 带电气手动合闸以及 64 针低压插座的 3AH3 真空断路器

图例中带电流互感器型脱扣器 Y4 和直流电路过电压吸收装置

HA Manual tripping/手动脱扣 HE Manual closing/手动合闸 K1 Anti-pumping contactor 防跳接触器 M1 Motor operating mechanism/马达储能机构 P Energy store/能量储存 R1 Resistor/电阻 S1 Auxiliary switch/辅助开关 S21, S22 Position switches (cut-out motor after charging) 位置开关 (储能后切断马达回路) S3 Position switches (open when closing spring charged ) 位置开关 (合闸弹簧储能后断开) S41, S42 Position switches (signals charged state) 位置开关 (合闸弹簧储能信号) S6, S7 Position switches (for switch tripped signal) 位置开关 (脱扣信号) X0 Low-voltage plug connector 二次插座

Y1 1st shunt release/一级分励脱扣器 Y2 2nd shunt release/二级分励脱扣器 Y4, Y5, Y6 CT operated release/电流互感器驱动型脱扣器 Y7 Undervoltage release/欠电压脱扣器

Y9 Closing solenoid/合闸线圈

With this model, the auxiliary switch terminals are wired to the plug connector as illustrated 在这种模式下,辅助开关的终端通常连接至二次接插件如下图所示

Auxiliary switch standard 标准型辅助开关

Auxiliary switch extended 延长型辅助开关

Wiring not applicable if B Y2 (2nd shunt release) fitted E Y7 (undervoltage release) fitted

接线不适用如果 B 配 2 级分励脱扣器 Y2 E 配欠电压脱扣器 Y7

Release "off" 脱扣器“"脱离”

Extended auxiliary switch 辅助开关延长部分

D7 B3 B8 C5 D8 D9 B9 C9

-Y7

Administrator
文本框
上海锐杰电器有限公司提供
Page 22: Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 Operating Instr Engl-Chn... · Operating Instruction Siemens 3AH3 / 西门子3AH3 真空断路器使用手册. Standard

Operating Instruction Siemens 3AH3 / 西门子 3AH3 真空断路器使用手册

! DANGER High voltage! Touching of live will result in death or severe personal injury. This equipment shall be operated only by qualified personnel after becoming thoroughly familiar with the respective instruction manual and in particular all safety instructions. ! WARNING This equipment contains hazardous voltages and mechanical parts which move at high speed and may be control remotely. Non-observance of the safety instructions can result in severe personal injury or property damage. In particular: Do not remove the cover (60.1). Do not reach inside any openings in the operating mecha- nism. Dot not touch pole assemblies(19.) and operating rods (48.). Commissioning Prior to commissioning, check the V-breaker in accordance with the following points: 1. Clean them as applicable (for details refer to ″cleaning″

page 5/1.). 2. Check all fixing and terminal screws for tightness. 3. Examine the circuit-breaker for any external damage,

especially to the control leads, post insulators and interrupters.

! CAUTION The V-breaker may be operated only with the original hand crank (50.), in order to avoid injures as a result of the motor suddenly starting up. 4. Charge the closing spring (62.) with the hand crank (50.)

(see Fig.4/1), press the ″close″ push-button (53.) and after closing, trip the breaker by pressing the ″open″ push-button (54.).

On the 3AH3 V-breaker with undervoltage release

(Y7) 3AX1103, the arresting screw of the hammer must be moved from position A to B (see note card in mechanism housing [60.] of 3AH3 vacuum circuit-breaker)

! 危险 高压! 接触导电部分会导致死亡或严重人身伤害. 只有完全熟悉操作手册特别是安全规程的人员 才可操作本设备. ! 警告 本设备在运行时带有危险电压, 以及可以 通过远控实现高速运动的机械部件. 违反操作规程可能导致人员伤亡或设备损坏. 特别注意: 不要随便移去机构箱面板 (60.1). 不要触 摸打开面板机构箱内部. 不要触摸极柱装 配部分 (19.) 以及绝缘操动杆 (48.). 使用 使用前请按以下项目检查断路器: 1. 合理清洁断路器 (详阅″清理″章节 5/1.). 2. 检查所有紧固部位. 3. 检查断路器是否有外部损伤, 特别对于二次引线, 环氧绝缘

子以及灭弧室. ! 注意 为防止马达突然启动所造成的不必要伤害, 手动储能操作时请使用原配手柄 (50.). 4. 利用手柄 (50.) 对闸弹簧储能 (62.) (见图.4/1), 按 ″合闸″

按钮 (53.), 合闸之后, 按 ″分闸″ 按钮 (54.) 使断路器跳闸.

对于装有欠电压脱扣器 (Y7) 3AX1103 的 3AH3 断路器, 调

节螺钉的位置必须从位 A 移到 B 位(见 3AH3 真空断路器中

的注意卡).

- 4/1 -

Administrator
文本框
上海锐杰电器有限公司提供
Page 23: Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 Operating Instr Engl-Chn... · Operating Instruction Siemens 3AH3 / 西门子3AH3 真空断路器使用手册. Standard

Operating Instruction Siemens 3AH3 / 西门子 3AH3 真空断路器使用手册

5. For test operations with the motor mechanism switch on the supply voltage. The motor will start immediately and charge the closing spring (62.). check the mechanical and electrical indication of the charging state of the closing spring. Actuate the mechanism as indicated under 4. And check the mechanical and electrical state indication.

6. Check the auxiliary switch S1 (68.) and position switches

(50.4.1) electrically in both end positions by actuating the 3AH3 vacuum circuit-breaker.

7. Also check-by electrical actuation – the function of the

closing solenoid Y9 (53.1) and all fitted shunt release. When correct functioning of the 3AH3 V-breaker has been ascertained it can be put into service. Charging the closing spring When the supply voltage is applied the motor (50.4) automatically charges the closing spring (62.). Should the supply fail the closing spring (62.) can also be charged by hand crank (50.). In the lattercase, as shown in Fig.4/1,the hand crank(50.) is inserted with the forwards pushed adapter (50.6) through the opening (50.1) onto hand crank coupling (50.5) and turned clockwise, until the symbol "closing spring discharged” shown in the indicator opening (55.3) is changed to "closing spring charged” (Fig. 4/2). The adapter (50.6) is designed so that the hand crank (50.) is decoupled on the recovery of the motor supply. Closing If operation is not blocked by the mechanical interlock, press the close push-button (53.) or the corresponding control switch until the 3AH3 vacuum circuit-breaker closes and both indicates and signals this state. After closing (and, if applicable, releasing of the close push-button (53.) the closing spring (62.) is immediately and automatically recharged the "closing spring charged” (55.) and indication becomes visible once again. Tripping The opening spring (64.) is charged during closing. To trip the breaker press the open push-button (54.) or corresponding control switch until the V-breaker trips and both indicates and signals this state.

5. 进行测试时接通马达机构电源, 此时马达立即启动 并对合闸弹簧 (62.) 储能. 检查合闸弹簧在储能状 态时的电气和机械指示. 然后按第 4 点所述操作, 再 检查此状态时的电气及机械指示. 6. 通过操作 3AH3 断路器, 检查辅助开关 S1 (68.) 和 位置开

关 (50.4.1) 在合分位置的电气状态. 7. 通过电气手段检查合闸线圈 Y9 (53.1) 以及所有脱

扣线圈. 当 3AH3 断路器以上功能都得到验证后, 可以投入使用. 合闸弹簧储能 当电源接通后,马达 (50.4) 自动对合闸弹簧 (62.) 储能. 如电源

有故障时, 可通过手柄 (50.) 进行储能. 对于后者,如 图.4/1 所示, 手柄 (50) 的适配头 (50.6) 通过面板开孔 (50.1) 插入手柄耦合杆 (50.5) 顺时针转动, 直到面板开孔 (55.3)上 的标志”合闸弹簧未储能”转换为”合闸弹簧已储能”(图.4/2). 手柄适配头 (50.6) 经专门设计保证在马达电源恢复时 手柄顺利从耦合杆退出. 合闸 在机械联锁处于防松状态时, 按″合闸″按钮 (53.)或相应 控制开关使 3AH3 断路器合闸并且面板指示和电气信号 都处于对应状态. 合闸后 ( 合闸 按钮 (53.) 释放后), 合闸弹簧 (62.) 立即自动再

储能, 储能状态指示重新为”合闸弹簧已 储能” (55.). 分闸 分闸弹簧 (64.) 在合闸的过程中被压缩储能. 按”分闸”按钮 (54.) 或相应控制开关使断路器分闸并且 面板指示和电气信号都处于对应状态.

- 4/2 -

Fig.4/1 Charging the closing spring with the hand crank 图 4/1 利用手柄对合闸弹簧储能

Fig.4/2 Closing spring discharged ″合闸弹簧未储能”

Fig.4/2 Closing spring charged ″合闸弹簧已储能”

Administrator
文本框
上海锐杰电器有限公司提供
Page 24: Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 Operating Instr Engl-Chn... · Operating Instruction Siemens 3AH3 / 西门子3AH3 真空断路器使用手册. Standard

Operating Instruction Siemens 3AH3 / 西门子 3AH3 真空断路器使用手册

Maintenance Safety measure ! DANGER Maintenance, repair and subsequent conver- sion work may be carried out only by specially trained personnel in accordance with the operating instructions and/or special conversions instructions. Training and information sessions for personnel can be provided by the competent Siemens department before starting any work on V-breakers, reference must be made to the local safety regulations for high-voltage switchgear, e.g. the five safety rules (DIN VDE 0105/07.83 Part 1, Item 9). Switch off the power supply and then close and open the V-breaker by hand ( V-breaker in open state "closing spring discharged" indication visible). Non-observation can result in death, severe personal injure or substantial property damage.

维护 安全措施 ! 危险 维护, 修理及以后的更换工作 必须由熟悉操作 手册的经过培训的专业人员来完成.人员培训 可以西门子专业部门提供 投入使用前, 必须参照当地的高压开关柜的 安全准则, 例如五防标准 (DIN VDE 0105/07.83 第 9 章,第 1 节). 断开二次电源然后通过手动关

合断路器 ( 真空断路器处于分闸状态 "合闸弹

簧未储能" 标志可见). 违章操作会导致严重的人员伤亡和设备损害.

Servicing Under normal operating conditions, the 3AH3 vacuum circuit-breaker is maintenance-free. We recommend nonetheless a regular visual inspection. Cleaning To ensure the insulating capacity, it is necessary that the insulating components are clean. Insulating components and external breaker parts must be wiped with a damp cloth. Use only warm water with the addition of a mild liquid household detergent as cleaning agent. ! WARNING Windings and terminals must not be touched if the power supply has not been disconnect- ed. Non-observance can result in death or serious personnel injury. ! CAUTION All springs of the operating mechanism must be relaxed and the vacuum circuit-breaker be brought into the open state, "closing spring discharged" indication visible. Non-observance can result in personnel injury.

检修 在正常条件下, 3AH3 真空断路器是免维护的, 我们建 议定期作一次常规视觉检查. 清理 为了确保绝缘水平. 因此绝缘件应保持处于清洁状态. 绝缘件以及断路器的外露部分必须用湿布擦抹. 清洗 请使用纯净的温水添加入柔和的家用清洗液进行清洗. ! 警告 如二次电源没切断, 切不可触及线圈及二次 终端. 违章操作会导致严重的人员伤亡 ! 注意 机械操动机构的所有弹簧必须处于松弛状态, 同时断路器应处于分闸状态, "合闸弹簧未 储能" 标志应可见. 违章操作会导致严重的人员伤亡.

- 5/1 -

Administrator
文本框
上海锐杰电器有限公司提供
Page 25: Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 Operating Instr Engl-Chn... · Operating Instruction Siemens 3AH3 / 西门子3AH3 真空断路器使用手册. Standard

Operating Instruction Siemens 3AH3 / 西门子 3AH3 真空断路器使用手册

Abnormal conditions If the 3AH3 vacuum circuit-breaker is used in abnormally unfavourable indoor conditions (e.g. frequent heavy condensation, dust-ridden air etc). We recommend regular cleaning of the breaker external components and, if necessary, renewal of the anti-corrosion protection. Only the following products may be used for the respective working parts of the VCB. Bearing, sliding surface: Isoflex Topas L32 Kl ber- Lubrication KG Geisenhausener Stra e 7 Postfach 70 10 47 81379 Munich Federal Republic of Germany Bearings inaccessible to grease and bearings of the auxiliary switch S1: SHELL Tellus Oil 32 SHELL Oil trade company GmbH Zitadellenstra e 5 P.O.Box 900915 21079 Humburg Federal Republic of Germany Joints and bearings which cannot be dismantled must not be treated with a cleaning agent prior to reapplication of anti-corrosives. After renewal of the anti-corrosion protection, several mechanical test-switching operations should be performed on the vacuum circuit-breaker. Lubricants (for special conditions) are available from the Siemens agent responsible: Order No 180 g Kl ber-Isoflex Topas L32 3AX1133-3A and 50 g SHELL Tellus Oil 32 180 g Kl ber-Isoflex Topas L32 3AX1133-3H 50 g SHELL Tellus Oil 32 3AX1133-2G 1kg SHELL Tellus Oil 32 3AX1133-2D 1kg Kl ber-Isoflex Topas L32 3AX1133-3E Checking the contact system In the course of the service life of an interrupter, the contact travel may move out of true. This is caused by mechanical deformation (compression) and/or erosion. We have taken measures in design to ensure that such minor changes in the travel do not affect the switching performance of our circuit breakers. Checking the vacuum Such a check should be made if there is any risk of an interrupter having developed a leak. Busbar and cable connections must be split. The check is performed with an HV test unit. If necessary, further information may be obtained from the appropriate Siemens Regional Office.

非正常运行工况 如果 3AH3 断路器被用于在非正常,不利的户内环境中 (例如 频繁的严重污秽条件下等).我们建议定期对断 路器外露部件清洗, 在必要时还应更新防污保护. 以下 产品可用于断路器的独立活动部件. 轴承, 滑动表面: Isoflex Topas L32 Kl ber- Lubrication KG Geisenhausener Stra e 7 Postfach 70 10 47 81379 Munich Federal Republic of Germany 油脂润滑难以接近的轴承以及辅助开关 S1 的轴承: SHELL Tellus Oil 32 SHELL Oil trade company GmbH Zitadellenstra e 5 P.O.Box 900915 21079 Humburg Federal Republic of Germany 不能拆卸的轴承和连接处在用防蚀剂处理前绝对不允许 用清洁剂擦洗. 重新更换防腐蚀保护后, 应对断路器进行几次机械操作 测试. 润滑剂 (用于特殊条件下) 可以通过西门子代理商或办事 处获得: 订货号 180 g Kl ber-Isoflex Topas L32 3AX1133-3A and 50 g SHELL Tellus Oil 32 180 g Kl ber-Isoflex Topas L32 3AX1133-3H 50 g SHELL Tellus Oil 32 3AX1133-2G 1kg SHELL Tellus Oil 32 3AX1133-2D 1kg Kl ber-Isoflex Topas L32 3AX1133-3E 检查触头系统 在真空泡的电寿命期内触头开距可能有变化,这是机械变

形(触头间压力)或腐蚀造成的. 我们在设计上已采取了措

施确保了这种较小的变化不会影响断路器的开断性能. 检查真空度 当怀疑灭弧室有漏气现象时, 应该作真空度检查. 母排 和电缆连接应拆除. 检查方法是对灭弧室施加高压. 如 有必要可向西门子办事处获取更多信息.

- 5/2 -

Administrator
文本框
上海锐杰电器有限公司提供
Page 26: Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 Operating Instr Engl-Chn... · Operating Instruction Siemens 3AH3 / 西门子3AH3 真空断路器使用手册. Standard

Operating Instruction Siemens 3AH3 / 西门子 3AH3 真空断路器使用手册

Service life of vacuum interrupter The maximum permissible number of mechanical operating cycles is 10,000. The permissible number of operating cycles as a function of the breaking current is shown in Fig.5/2. When this permissible maximum has been attained, the interrupters or the complete pole assemblies must be renewed. Detailed instructions are supplied with the replacement interrupters/pole assemblies. When ordering replacement interrupters or pole assemblies, state the circuit-breaker type, design code and serial number (see name plate)

真空灭弧室运行寿命 断路器最高机械寿命为 10,000 次. 断路器允许操作次 数是开断电流的函数如图.5/2. 当达到最高操作次数 时, 灭弧室或整个极柱装配 必须更换 具体说明随 灭弧室/极柱装配更换件一起提供. 如需定购灭弧室/极柱装配更换件时, 请注明断路器型号, 设计编号和系列号 (见铭牌).

Fig.5/2 Permissible number of operating cycle as a function of breaking current Ia 图 5/2 断路器允许开断次数是开断电流 Ia 的函数 - 5/3 -

Determination of the load characteristic number/ 负载开断特性函数号的确定

Load characteristic number at rated normal current

额定电流下负载特性曲线号 Rated voltage

额定电压 kV

Rated short-circuit breaking current 额定短路电流

kA 1250A 2000A 2500A 3150A 4000A 50 1 - 1 1 - 7.2 63 2 - 2 2 2 50 1 1 1 - 12 63 2 2 2 2 50 1 - 1 1 - 15 63 2 - 2 2 2 50 3 - 3 3 3 17.5 63 4 - 4 4 4 40 - - 5 - 24 50 3

31.5 6 6 6 - - 36 40 5 5 5 -

Num

ber o

f bre

akin

g op

erat

ions

/开断次数

Breaking current I (kA)/开断电流 (kA)

Administrator
文本框
上海锐杰电器有限公司提供
Page 27: Vacuum Circuit-Breaker 3AH3 7.2kV to 36kV 真空断路器 3AH3 Operating Instr Engl-Chn... · Operating Instruction Siemens 3AH3 / 西门子3AH3 真空断路器使用手册. Standard

Operating Instruction Siemens 3AH3 / 西门子 3AH3 真空断路器使用手册

Accessories and spare parts A hand crank 3AX 1530-2B for charging the closing spring can be supplied as an accessory: Owing to the fact that all parts of this breaker type have been optimized to the last the normal service life, it is not possible to recommend particular spare parts for keeping in stock. When ordering spare part state the following: 1. Type designation, design code and serial number

of the 3AH3 vacuum circuit-breaker (see rating plate)

2. The designation and part number, making reference to illustrations in these operating instructions or to a photograph or sketch as applicable. Alternatively, a sample may be submitted.

Published by the Power Transmission and Distribution Group Schaltwerk Berlin Translated by SLC PTD MC Edition 1/Oct. 2005 Subject to change

附备件 用于合闸储能的手柄 3AX 1530-2B 可以作为附件提供: 针对于整个寿命周期, 本断路器所有零部件已经过最优 化设计, 因此我们建议用户无须考虑特殊零部件的备件 存. 定购备件时请注明: 1. 3AH3 断路器的型号, 设计编号和系列号 (见铭牌 ). 2. 备件名称及编号, 参阅本手册的图例说明或运用照片

和草图加以说明, 二者可选其一. 出版者 西门子输配电部 Schaltwerk 柏林 校译 西门子中国有限公司 中压开关部件部 日期 1/10 2005 保留更改权力

- 5/4 -

Order No. / 订货号: 9229 9860 174 0D –SLC PTD MC Place of order / 订货地址: SLC PTD MC ShangHai

Administrator
文本框
上海锐杰电器有限公司提供