VEGA CONTROL PANEL

Technical

Page 2: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Applications

• Hotels

• Factories / Manufacturing Environments

• Shopping Centres

• Underground Stations

• Airports

• Office Complexes

• Commercial Buildings

Page 3: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

24 Zone Vega Panel

FIRE PROTECTION

ZONE 1

ZONE 9

ZONE 17

ZONE 2

ZONE 10

ZONE 18

ZONE 3

ALARM DEVICEFAULT

TEST POWER ONP.S.U.FAULT

COMMONFAULT

COMMONISOLATE

SYSTEMFAULT

EARTHFAULT

SOUNDERFAULT

DEVICEISOLATE

OUTPUTDELAYED

PRE ALARM

SILENCE BUZZER

6 7 8 9 0

1 2 3 4 5

OUTPUTISOLATE

SCROLL

DELAY OVERRIDE

SILENCE ALARMS

EVACUATERESET

ZONE 11

ZONE 19

ZONE 4

ZONE 12

ZONE 20 ZONE 21

ZONE 13

ZONE 5

ZONE 22

ZONE 14

ZONE 6

ZONE 23

ZONE 15

ZONE 7

ZONE 24

ZONE 16

ZONE 8

FIRE PROTECTION

Page 4: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Control Panel - Features

• Expandable from 1 to 16 loops

• 16 status LED indications

• Expandable from 24 to 120 Zone Fire Indications

• 8 Line x 40 Character Liquid Crystal Display

• Compatible with Apollo S90, XP95 Discovery, Explorer & Hochiki ESP Protocol

• Membrane Zone / Status Text Slide Inserts

• Integral Fast Action Event Printer (option)

• Programmable Sounder Circuits & Relay Contacts

• Alarm Management features

Page 5: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Control Panel - Features

• Integral Power Supply Units

• Space for Batteries

• P.C. Programming via Viper software package

• Complies with key international standards, BS EN-54

• Plant Indications provide non-fire related Alarms

• 10 Priority Level Alarm Structure

• Custom Device Type & Alarm Header Text Message Facility

• Motherboard Plug in Option Cards

Page 6: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Control Panel - Features

• Multi Serial Data Communications Outputs

• Network to Graphics System

• 64 x Repeater Panels - 15 Active (Full Control)

• Fully Programmable via Panel Fascia or P.C. software

• Menu Driven Operation complete with User Guidance Text

• Selective Event Log

• Remote System Control Inputs & Outputs

• Engineers Functions - loop current, forward\reverse scan, fault codes

• One Man Test Mode

Page 7: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Fascia Layouts

Page 8: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Membrane Control Key Operation

• Silence Buzzer - deactivates panel buzzer. While timer T1 is counting down, operation will cause T1 to be accepted and initiate timer T2. While T2 is counting down, each operation will extend the countdown by 10s increments to a maximum of 600s.

• Scroll - When more than one activation is indicated on the control panel, operation of SCROLL will allow all activations to be viewed on the display. Each operation of the Scroll key will step through to the next activation in sequence of operation, for the selected area only.

• Silence Alarms - Will silence any audible alarms, deactivate any outputs which may have been programmed, and cancel the operation of timers T1 and T2. Will also cause the pulsing alarm and relevant zonal LED’s to operate in constant mode.

Page 9: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Membrane Control Key Operation

• Delay Override - Overrides the operation of any programmed time delays (timers T0, T1 & T2)

• Evacuate - Activates sounder circuits and other outputs. When in evacuate mode, the output operation will remain until Silence Alarms has been operated.

• Enter Key - Used for acceptance of numeric data, access of menu selection and accepting the setting of system information. During activation of priority alarms the key is used for viewing device information.

• Cancel Key - Operation of the cancel key will cancel/deselect the pre-set access menu selections and continued operation will eventually return the display to access level 1.If the printer is operating it will be stopped.

Page 10: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Membrane Control Key Operation

• Numeric Keys - Used to select access level password codes, to select menu level options and inputting system data.

• Arrow Keys - Used for selection of access level menus, viewing activations, pending priority activations and for programming the control panel. When multiple priority alarms are displayed the Left and Right arrow keys will enable the user to scroll between priorities.

Page 11: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Membrane

• 8 lines x 40 character LCD display

• Text & graphical capability

• Option to have LCD back light switched off in quiescent mode

• Shows 1st & last zones in alarm and option to scroll through intermediate zones

• Option to view devices in alarm in each zone

• On-screen prompts for ease of control

• Membrane pocket allows insertion of customer’s logo

• Membrane insert allows different language control functions to be incorporated

Page 12: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Membrane

• Controls:- Access level 1

- Silence buzzer- Delay override- Scroll

- Access level 2- Silence alarms- Reset- Evacuate

Page 13: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Membrane

• Up - down - left - right keys:- used to drive through menu options

• Numeric Keys:- password selection- menu options- programming

• Cancel/Enter keys:- Selection/de-selection of menu options

Page 14: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Membrane

• Status LED’s:All LED’s are grouped together in relevant sections (alarm, fault & disable) & meet the requirements of EN54-2

Status LED Colour FunctionAlarm Red Illuminates in conjunction with

any zonal alarm LED'sPre-alarm Yellow Detection device alarm

threshold has raised above normalCommon Fault Yellow Illuminates in conjunction with

any faultSystem Fault Yellow Illuminates in conjunction with

any processor faultDevice Fault Yellow Illuminates in conjunction with

any input or output fault

Page 15: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Membrane

• Status LED’s

Note: Fault can also be used to indicate disablement of sounder circuit. In this case, it will be illuminated in a constant mode.

Status LED Colour FunctionPSU Fault Yellow Illuminates in conjunction with

any PSU faultSounder Fault/ Yellow Illuminates in conjunction withdisablement any sounder circuit fault or

sounder circuit isolationDevice Isolated Yellow Indicates isolation of any

input or output deviceCommon Yellow Illuminates in conjunction withIsolate any disablement

Page 16: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Membrane

• Status LED’s

Status LED Colour FunctionOutput Yellow Illuminates when anyIsolated sounder or VFCO isolatedOutput Yellow Illuminates when anydelayed delay is programmedTest Yellow Illuminates when the panel

is in test mode, in conjunctionwith zonal fault LED's

Power On Green Remains illuminated whilstIsolate power is supplied to the panel

Page 17: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Membrane

• Status LED’s

Note: 2 spare yellow LED’s available for future use.

Status LED Colour FunctionZonal LED's Red Alarm indication per zoneZonal LED's Yellow Fault indication per zone (pulsed)

Disablement indication per zone (constant)Test indication per zone (slow pulse)

Page 18: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega - Passwords

Default Password

• End User Access Level 2 = 7179

• Engineers Access Level 3 = 7134

User Definable

• Access Level 2 = any four digit number except 7134

• Access Level 3 = any four digit number except 7179

Page 19: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Menu Time Out Sequence

120sec

Sub MenuHigh Level

Sub MenuLow Level

Main Menu

Status Menu

Time Out Alert

Access LevelOne 90

sec60

sec30

sec10

sec0

sec

Note: Any key operation extends time out period by 30 seconds

Page 20: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega - Top Level Menu Structure

Feature Select Option Level 1 Level 2 Level 3 Level 4Silence Buzzer Yes Yes Yes YesScroll Yes Yes Yes YesSilence Alarms No Yes Yes Yes

Panel Reset No Yes Yes YesDelay Override Yes Yes Yes Yes

Controls Evacuate No Yes Yes YesEnter Yes Yes Yes YesCancel Yes Yes Yes YesNumeric Keys (0 - 9) Yes Yes Yes YesArrow Keys N/A N/A N/A N/A

Page 21: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega - Top Level Menu Structure

Feature Select Option Level 1 Level 2 Level 3 Level 4Zones No Yes Yes YesLoop Devices No Yes Yes Yes

Isolate (De) Output Groups No Yes Yes YesMenu Panel Functions No Yes Yes Yes

Plant Alarms No Yes Yes YesLocal Buzzer No No Yes Yes

Page 22: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega - Top Level Menu Structure

Select Option Level 1 Level 2 Level 3 Level 4Zones No Yes Yes YesLoop No Yes Yes YesDevices No Yes Yes YesOutput Groups No Yes Yes YesPanel Functions No Yes Yes YesPlant Alarms No Yes Yes YesIsolations No Yes Yes YesEvent Log No Yes Yes YesEngineer information No No Yes Yes

Page 23: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega - Top Level Menu Structure

Feature Select Option Level 1 Level 2 Level 3 Level 4Time & Date No Yes Yes YesPrinter Status No Yes Yes Yes

Set Activate Day Mode No Yes Yes YesStandard Features No No Yes Yes

Menu Custom Features No No Yes YesClear Memory No No Yes YesUser Passwords No No Yes YesLoop Configuration No No Yes Yes

Test Panel LED Test No No Yes YesDevice Test No No Yes Yes

Menu Output Group Test No No Yes YesAlarm Simulation Test No No Yes YesMembrane Keypad Test No No Yes YesTest Mode No No Yes Yes

Page 24: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega - Priority Level Alarm Structure

Priority Level Latch Non- Scroll LCD Buzzer Print Program LED's Status

latching Display Out Outputs Zone/Plant LED's

Evacuate 0 Yes No Yes Yes Constant Yes Yes Zone Alarm

Fire 1 Yes No Yes Yes Constant Yes Yes Zone Alarm

Alert 2 Optional Optional Yes Yes Constant Yes Yes Zone No

Pre-alarm 3 No Yes Yes Yes Pulse Yes No Zone Pre-alarm

Fault 4 No Yes Yes Yes Pulse Yes No Zone Common & Device

Unassigned 5 Optional Optional Yes Yes Pulse Yes Yes Zone/Plant No

Unassigned 6 Optional Optional Yes Yes Pulse Yes Yes Zone/Plant No

Unassigned 7 No Yes No No No No Yes Plant No

Unassigned 8 No Yes No No No No Yes Plant No

Unassigned 9 No Yes No No No No Yes Plant No

Note: 1. All events are displayed time & priority order 2. All events are recorded in the panel event log 3. Priority alarm text can be customized for display purpose (0-2 & 5-9 only) 4. Zone, Plant & Status LED’s operate as cause & effect programming

Page 25: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Fire Condition Display

FIRETotal 003

Access Level 1

Priority alarm pending

tot 001/001Stationery storeroomOptical

Loop 01 dev 043:1 Zone 011

Last Z024 Main Building

002 Z011 First Floor West Block

1st Z010 Ground Floor Main Office

Priority header text

Total Qty of fires

Zone text 24 characters

Device type 24 characters of device text

Total fireswithin zone

Access level

TIMERS EXTENDED

Control Key operated

Device 43Sub address No 1

Page 26: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

FAULTTotal 003

Access Level 1

001/001Loop 1 short - circMaster BLC

First floor sounder cctsGrp 005

Zone 001

System fault

Priority header text

Total Qty of faults

Zone text 24 characters

Fault conditionText position

System fault location

Main building reception

System fault description

Displayed upon operation of Enter key

tot 001/001

tot 001/001

tot 001/001

Fault Qty for this position

Vega Fault Condition Display

Page 27: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

FAULTTotal 003

Access Level 1

Main purchasing office 02Ionisation

First floor sounder cctsGrp 005

Zone 001

System fault

Priority header text

Total Qty of faults

Zone text 24 characters

Fault conditionText position

Device information displayed upon operationof Enter key upon zone position

Main building reception

Device fault code

tot 001/001

tot 001/001

tot 001/001

Fault Qty for this position

Loop 01 dev 047.1 zone 000 tot 001/001

Vega Fault Condition Display

Page 28: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Access Level 3 Standard features

Device 031.1 loop 01

Text Main office sounder

Type sounder cct Custom 00: Unassigned

Group 000

Select option using&

Zone text 24 characters

Device typedescription

Allocated groupnumber

Custom devicetype

Device address, sub address & loop number

Vega Membrane Device Programming

Page 29: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Access Level 3 Standard features

Device 031.1 loop 01

Text Goods inwards office

Type Ionisation Custom 00: Unassigned

Zone 001 Priority Fire

Sens STD Day mode Isolated

Non latch NO BGU Flag NO

Zone text 24 characters

Device typedescription

Allocated zonenumber

Custom devicetype

Device address, sub address & loop number

Device priorityselection

Day mode setting

Flag for quick responseof fire condition

Device sensitivitysetting

Device sensitivityflag

Vega Membrane Device Programming

Page 30: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Access Level 3 Standard features

Edit group 001 information

Text O/P’s assigned to 1st floor

Timer T3 020 sec BGU override NO

Timer T4 01 mins BGU override Yes

Action on program Evacuate NO

Deactivate on silence alarms

Select option using &

Time delayto intermittentmode

Time delay toevacuate mode

Group programmingparameter options

Groups 24 characters of text

Device address, sub address & loop number

Relevant timeroverrides

Output to operateon sound alarmsOutput to deactivate

on silence alarmsUser operating text

Vega Membrane Output Programming

Page 31: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Control Panel - 24 Zone 1 Loop Hardware Schematic

Page 32: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Control Panel - 120 Zone 16 Loop Possible System Hardware Schematic

Page 33: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega - MCP & BLC Internal Switch Setting

Card No Main Control Processor Board44782-K071SW1 Processor RestartSW2 System Fault Reset (watchdog)SW3 Config EnableSW4 Not usedLink 1 Config Enable

Card No Master Basic Loop Controller44782-K073SW1 BLC RestartSW2 Bit 1 On = BLC sounder circuit 4 disabled during failsafe operation

Bit 2 On = BLC relay contact 4 disabled during failsafe operation

Card No Repeater Output Driver Card44782-K076SW1 On = One radial output cable used

Off = Two radial output cable used

Page 34: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega - MCP & BLC Internal Switch Setting

Card No Slave Basic Loop Controller44782-K084SW1SW2 End of Line On = Last slave BLC address within panel

Off = Intermediate slave BLC within panelSW3 End of Line On = Intermediate slave BLC within panel

Off = Last slave BLC address within panelSW4 Bit 1 On = Loops 5 to 8

Board Address Bit 2 On = Loops 9 to 12Bit 3 On = Loops 13 to 16

SW5 Failsafe settings as for MBLC card 44782-K073

BLC Restart

Page 35: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega - M.B.L.C. Digital Inputs & Outputs

Input No Operation1 Remote Alert priority alarm (latching)2 Remote Evacuate priority alarm (latching)3 Remote Silence Alarms4 Remote System Reset5 External Fault Input6 Access Level 2 Override7 Class Change (non-latching evac)8 Day Mode Stop/Start (non-latching)

Output No Operation1 Alarm Repeat2 Auxiliary Repeat3 Alert Repeat4 Pre-alarm Repeat5 Fault Repeat6 Membrane Manual Evacuate7 System Reset8 Silence Alarms Repeat

Inputs will operate by applying 0 volts

w.r.t. power supplyOpen Collector Outputs switch from 28 v to 0 v

Page 36: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Motherboard plug-in Options

2 KM

1 - 4

5 - 8

9 - 12

13 - 16

MOTHERBOARD2 core FIRE PROTECTION

ZONE 1

ZONE 9

ZONE 17

ZONE 2

ZONE 10

ZONE 18

ZONE 3

ALARM DEVICEFAULT

TEST POWER ONP.S.U.FAULT

COMMONFAULT

COMMONISOLATE

SYSTEMFAULT

EARTHFAULT

SOUNDERFAULT

DEVICEISOLATE

OUTPUTDELAYED

PRE ALARM

SILENCE BUZZER

6 7 8 9 0

1 2 3 4 5

OUTPUTISOLATE

SCROLL

DELAY OVERRIDE

SILENCE ALARMS

EVACUATERESET

ZONE 11

ZONE 19

ZONE 4

ZONE 12

ZONE 20 ZONE 21

ZONE 13

ZONE 5

ZONE 22

ZONE 14

ZONE 6

ZONE 23

ZONE 15

ZONE 7

ZONE 24

ZONE 16

ZONE 8

FIRE PROTECTION

Page 37: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega 4 Way Motherboard

Page 38: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega 4 Way Motherboard Description:

The motherboard can be installed within the Vega control panel, space

permitting, to allow site specific customer requirements to be met. A range

of input/output option cards can then be inserted using Plg 2 to 5.

Terminations to external field cables are made direct to the motherboard at

TB 1 to 4 & should be restricted to switching a maximum load of 1 amp @

28 volts d.c. depending upon option cards installed. The maximum current

available, PSU rating permitting, when power is derived through the

motherboard is 9 amps @ 28 volts. The I/O cards receive site specific

programming data from the Vega MCP via the MBLC connection to

TB 5 using RS 485 signals.

Page 39: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega 4 Way Motherboard Description (Cont’d):

A processor fail safe is incorporated connecting the MCP, MBLC and I/O

cards using the “F” terminal. This guards against any possible processor

failure during an alarm condition & will operate fail safe configured outputs.

A maximum of 4 fully populated motherboards can be connected together

in a daisy chain format using TB 5 & 6 to enable a total of 16 I/O cards to

be installed within the system.

The motherboard can also be used within a Repeater panel with

connection being made to the Repeater output driver card 44782-K076.

No fail safe connection should be made when used external to the

control panel enclosure.

Page 40: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega 4 Way Motherboard Connection Details:

The Vega control panel should be powered down before making the

following connections:

a) Connect 24 volt d.c. supply to TB 7, 28v & 0v using suitable 1mm cable

b) Connect TB 5 to Vega MBLC card 44782-K073 at TB 9, F- + terminals using suitable 0.5mm cable

c) Set the plug in option card switches & insert into slots plg 2 to 5, refer option card data sheet for switch info

Page 41: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega 4 Way Motherboard Connection Details (Cont’d):

d) Set SW 1 - bit 1 & 2 to ON on the last or only motherboard installed. Set to OFF on intermediate cards

e) Set SW 2 - bit 1 & 2 to ON when used with integral panel PSU. Set to OFF when using a separate PSU

f) When a separate PSU is used connect the fault monitoring output to

TB 7 Flt terminal, Plg 2 requires an option card installation in order to signal the fault

Refer to plug in option card data sheets for definition of output terminals obtained at TB 1 to 4

Note: Plg 1 & TB 7 Aux 5v terminals are NOT used in Vega panels

Page 42: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega 8 Way Relay Card

Page 43: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega 8 Way Relay CardDescription:

The 8 way relay card provides 8 independently driven volt free change

over contacts (V.F.C.O.) Each relay has a maximum contact current

rating of 1 Amp at 28 volts d.c. The relays are independently controlled by

the on-board processor located in I.C. 1. The card receives programming

instructions from the Vega main control processor (MCP) using the RS 485

signal connection. The relay card has a unique address switch to enable

full monitoring & operation to be maintained. Each relay output responds

to a separate sub-address. Location text to define each output function can

be programmed on the Vega control panel to help the end user during

isolations & maintenance engineers during service visits. Programming

functions such as Evacuate, Alert, Double knock & Delays can all be

assigned to the relay outputs using the Vega control panel.

Page 44: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega 8 Way Relay CardConnection Details:

The Vega control panel should be powered down before making the following

connections & motherboard part no 44782-K091 should have been installed as

detailed on data sheet DS-K091.

a) Configure the 8 relay contacts as either normally open “NO” or normally closed “NC” contacts in non alarm condition using switches SW 1 to SW 8

b) Set SW 9 to required motherboard address, address 0 = MB 01,

address 1 = MB 02, etc. Duplicate addressing is not permitted

c) Set SW 10 as required, bit 1 & 2 ON provides fail safe operation of all relay outputs during an alarm condition & a MCP processor failure. Set bit 1 & 2 to OFF when fail safe operation is not desired.

Page 45: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega 8 Way Relay CardConnection Details (Cont’d):

d) With control panel powered down insert the relay card into the motherboard at Plg 2 to 5

e) The relay V.F.C.O. contact terminal outputs located on the motherboard are:

Relay Output RL1 RL2 RL3 RL4 RL5 RL6 RL7 RL8Common Contact 1 3 5 7 9 11 13 15N/O - N/O Contact 2 4 6 8 10 12 14 16

A regular flash rate shown by LED D1 indicates healthy communications with the MCP. D1 OFF indicates lost communications

Page 46: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega 8 Way Sounder Card

Page 47: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega 8 Way Sounder CardDescription:

The 8 way sounder card provides 8 independently driven reverse polarity monitored

outputs. Each output has a maximum current drive rating of 1 Amp at 28 volts d.c,

with on-board fuses for over current protection F 1 to 8. However, the total load

taken from each card should be restricted within the system design to 4 Amps Max.

The monitored outputs are independently controlled by the on-board processor

located in I.C.1 The card receives programming instructions from the Vega main

control processor (MCP) using the RS 485 signal connection. The sounder card

has a unique address switch to enable full monitoring & operation to be maintained.

Each sounder output responds to a separate sub-address. Location text to define

each output function can be programmed on the Vega control panel to help the

end user during isolations & maintenance engineers during service visits.

Programming functions such as Evacuate, Alert, Double knock & Delays can

all be assigned to the relay outputs using the Vega control panel.

Page 48: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega 8 Way Sounder CardConnection Details:

The Vega control panel should be powered down before making the following

connections & motherboard part no 44782-K091 should have been installed as

detailed on data sheet DS-K091.

a) Set SW 1 to required motherboard address, address 0 = MB 01, address 1 = MB 02, etc. Duplicate addressing is not permitted

b) With control panel powered down insert the sounder output card into the motherboard at Plg 2 to 5

c) Install 8 x end of line 10k resisters in the motherboard between odd & even terminals

Page 49: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega 8 Way Sounder CardConnection Details:

d) The sounder terminal outputs located on the motherboard are:

A regular flash rate shown by LED D22 indicates healthy communications with

the MCP. D22 OFF indicates lost communications. LED ON indicates a

short/open circuit fault to one or more sounder circuit outputs.

Relay Output Snd1 Snd2 Snd3 Snd4 Snd5 Snd6 Snd7 Snd8Positive (+Ve) 1 3 5 7 9 11 13 15Negative (-Ve) 2 4 6 8 10 12 14 16

Page 50: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega 16 Way Non-monitored Input Card

Page 51: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega 16 Way Non-monitored Input CardDescription:

The 16 way input card provides 16 independent non-monitored inputs. The inputs

are initiated by applying or removing a zero volt signal with respect to the power

supply connected to the motherboard. I.e. switched +28 volt to 0 volts. The inputs

can be configured as either a normally closed, initiating an input signal when the 0 v

is applied. The inputs are independently monitored by the on-board processor

located in I.C.1 The card continuously monitors the state of the inputs passing any

changes to the Vega main control processor (MCP) using the RS 485 signal

connection. The input card has a unique address switch to enable full monitoring

to be maintained with each individual input responding to a separate sub-address.

Location text to define each input action can be programmed on the Vega control

panel to help the end user during isolations or maintenance engineers during

service visits. Programming of the inputs Zone or Plant alarm indications

can be achieved, along with output Group & Priority assignments using the

Vega control panel.

Page 52: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega 16 Way Non-monitored Input CardConnection Details:

The Vega control panel should be powered down before making the following

connections & motherboard part no 44782-K091 should have been installed as

detailed on data sheet DS-K091.

a) Configure the 16 input channels for “N/O” or “N/C” operation.

SW 2 bit 1 to 8 relate to inputs 1 to 8, SW 3 bit 1 to 8 relate to inputs 9 to 16.

OFF = “N/O” & ON = “N/C

b) Set SW 1 to the required motherboard address, address 0 = MB 01, address 1 = MB 02, etc. Duplicate addressing is not permitted.

c) With control panel powered down insert the input card into the motherboard at Plg 2 to 5 A regular flash rate shown by LED D1 indicates healthy

communications with the MCP. D1 OFF indicates lost communications

Page 53: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega 16 Way Open Collector Output Card

Page 54: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega 16 Way Open Collector Output CardDescription:

The 16 way output card provides 16 independently driven open collector switched

to zero volt outputs. Each output has a maximum current drive capability of 50mA.

The outputs are independently controlled by the on-board processor located in I.C.1

The card receives programming instructions from the Vega main control processor

(MCP) using the RS 485 signal connection. The output card has a unique address

switch to enable full monitoring & operation to be maintained. Each open collector

output responds to a separate sub-address. Location text to define each output

function can be programmed onto the Vega control panel to help the end user

during isolations & maintenance engineers during service visits. Programming

functions such as Evacuate, Alert, Double knock & Delays can all be assigned to

the relay outputs using the Vega control panel. The card can be used to

interface to additional relay & sounder output cards or can be used to drive

LED indications located on geographic mimic plates. The open collector

outputs are for internal panel use only.

Page 55: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega 16 Way Open Collector Output CardConnection Details:

The Vega control panel should be powered down before making the following

connections & motherboard part no 44782-K091 should have been installed as

detailed on data sheet DS-K091.

a) Set SW 1 to the required motherboard address, address 0 = MB 01, address

1 = MB 02, etc. Duplicate addressing is not permitted.

b) Set SW 2 as required, bit 1 & 2 ON provides fail safe operation of all relay outputs during an alarm condition & a MCP processor failure. Set bit 1 & 2 OFF when fail safe operation is not desired.

c) With control panel powered down insert the relay card into the motherboard at Plg 2 to 5A regular flash rate shown by LED D12 indicates healthy

communications with the MCP. D12 OFF indicates lost communications

Page 56: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega 8 Way Monitored Input Card

Page 57: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega 8 Way Monitored Input CardDescription:

The 8 way input card provides 8 independently monitored input circuits. The

inputs are initiated by applying a 470 to 680 ohm resistor in parallel with the

monitored circuit. Each input channel is monitored for open & short circuit condition

using an end of line (EOL) monitoring resistor. The inputs are independently

monitored by the on-board processor located in I.C.1 The card continuously

monitors the state of the inputs passing any changes to the Vega main control

processor (MCP) using the RS 485 signal connection. The input card has a unique

address switch to enable full monitoring to be maintained with each individual input

responding to a separate sub-address. Location text to define each inputs action

can be programmed on the Vega control panel to help the end user during

isolations or maintenance engineers during service visits. Programming of the

inputs to Zone or Plant alarm indications can be achieved, along with output

Group & Priority assignments using the Vega control panel.

Page 58: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega 8 Way Monitored Input CardConnection Details:

The Vega control panel should be powered down before making the following

connections & motherboard part no 44782-K091 should have been installed as

detailed on data sheet DS-K091.

a) Set SW 1 to the required motherboard address, address 0 = MB 01, address

1 = MB 02, etc. Within Viper programming software package. Duplicate addressing is not permitted.

b) Set SW 2 = bit 1 ON failsafe operation enabled, OFF failsafe line disabled

= bit 2 ON for use with zener bases & 6K8 EOL, OFF for use with standard base & 3K9 EOL or diode base & active EOL device

c) With control panel powered down insert the relay card into the motherboard at Plg 2 to 5 & connect EOL resistors

Page 59: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega 8 Way Monitored Input CardConnection Details (Cont’d):

d) The monitored zone terminal inputs located on the motherboard are:

Zone Input Z1 Z2 Z3 Z4 Z5 Z6 Z7 Z8Negative (-Ve) 1 3 5 7 9 11 13 15Positive (+Ve) 2 4 6 8 10 12 14 16

A regular flash rate shown by LED D18 indicates healthy communications with the MCP. LED off indicates lost communications. LED on constant indicates 1 or more circuits are in fault condition (open or short circuit)

Page 60: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Software Features

• Device alarm test

• Alarm simulation test

• Blink Control (Discovery & ESP only)

• Loop Integrity Test

• Device Sub Address Programming

Page 61: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Software Features

• Time delays to zonal inputs

- T1

- T2

• Time delays to output devices

- T3

- T4

Page 62: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega - Delay to Output Group Operation

Input devices are assigned to Zones Output devices are assigned to Groups

T1 & T2 are assigned to each input - Zone T3 & T4 are assigned to the Output GroupT1 = Alarm Accept Time delay T3 = Delay to the operation of the GroupT2 = Alarm Investigation Time Period T4 = Alert period (pulsing sounders) delay

Page 63: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega – Output Group ProgrammingZone of origin to provide alarm accept delay for 1 min with investigation time of 3 mins. Constant alarm to follow after time out or BGU is activated or delay override button is pressed. Adjacent zones delayed for 2 mins then pulsed (Alert) for 2 mins followed by constant alarm until system silenced then reset.

Page 64: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Engineers Functions

• Isolate local buzzer

• Detector fault codes complete with menu look up chart

• Loop drive capability forwards and backwards

• Read loop quiescent current value

• Alarm simulation test

• Text allocation to all inputs and outputs

• Self resetting over current protection devices

on sounder circuits

Page 65: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Engineers Functions

• Fully programmable via membrane

• Selective event log

• Menu driven operation complete with guidance text

• Common hardware for Apollo and Hochiki

Page 66: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Alarm Management

• Day / Night mode

• Delay timers T1, T2, T3 & T4

• BGU & co-incidence override per zone

• Sensitivity level adjustment

• Latching & non-latching alarms

Page 67: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Alarm Management

• Priority levels

• Output group selection & control

• Output group override for BGU’s

• Output group styles A, E, 1-6

• Plant alarms

Page 68: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Device Fault CodesDevice fault code reference

No Description No Description01 Test Failed 17 Illegal Type02 Device Missing 18 Sounder Short Circuit03 Memory Failure 19 Sounder Open Circuit04 Type Changed 20 I/O Output Short Circuit05 Contamination Fault 21 I/O Output Open Circuit06 Local PSU Fault 22 I/O Input Short Circuit07 Loop Output Short Circuit 23 I/O Input Open Circuit08 Loop Output Open Circuit 24 Extra Device09 Loop Input Short Circuit 25 Remote PSU AC Fault10 Loop Input Open Circuit 26 Remote PSU Battery Fault11 Power Failure 27 Remote PSU Charger Fault12 Device Low Level 28 Frift Fault13 Device High Level 29 Invalid Approval Code14 Sub Address Fault 30 Invalid Site Address15 Address Fault 31 Sensitivity Fault16 Unspecified Error 32 Discovery Write Failure

Page 69: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega - One Man Test Mode

• Zone based

• Auto reset after 30s

• Multiple device tests recorded to event log & printer

• All outputs suppressed

• All the zones fully functional

• Reduced cost of ownership

Page 70: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Operational FlowchartPANEL NORMAL

DEVICETYPE

CHANGE

AccessLevel 3Set loop config auto learn loop x

AccessLevel 3Set loop config accept logon

STATUS LED’sCommon faultDevice faultZone faultLCDZone faultSystem faultDevice missingUnregistered deviceBuzzerPulsed

STATUS LED’sCommon faultDevice faultZone faultLCDZone faultSystem faultDevice missingUnregistered deviceBuzzerPulsed

Affect

Affect

Action

Affect

Action

Action

Page 71: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Operational Flowchart

PANEL NORMAL

ADD NEWDevice

AccessLevel 3Set loop config auto learn loop x

AccessLevel 3Set loop config accept logon

STATUS LED’sCommon faultDevice faultLCDZone faultUnregistered deviceBuzzerPulsed

STATUS LED’sCommon faultDevice faultNew device in zone 000LCDUnregistered deviceLogon faultBuzzerPulsed

Affect

Affect

Action

Affect

Action

Action

Page 72: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Operational Flowchart

PANEL NORMAL

REMOVEDevice

AccessLevel 3Set loop config auto learn loop x

AccessLevel 3Set loop config accept logon

STATUS LED’sCommon faultDevice faultZonal faultLCDZone faultDevice missing (code 2)BuzzerPulsed

STATUS LED’sCommon faultDevice faultZonal LEDLCDSystem faultLogon faultBuzzerPulsedAffect

Affect

Action

Affect

Action

Action

Page 73: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Power Supply

• 110V - 220V AC input sensing

• 2.5, 4/2 & 8/4 Amp PSU’s

• EN54-4 (Power supply section)

• Battery monitoring thermistor for temperaturecompensated charging

• Fault indications - Battery charge

- Battery low

- Stand by power loss

- Mains failure

Page 74: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Power Supply

• Screw terminals for cable connections

• Fully enclosed

• All PSU’s are interchangeable

• Self resetting current limiting devices to protect outputs

Page 75: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega - Repeater Control Panels

• LCD, 24, 56, 88 & 120 Zone Format

• Optional Event Printer

• Up to 64 Repeaters can be connected to a control panel

• Up to 15 Active Repeaters available (Full Control over main panel user functions)

• Integral Sounder Circuit & VFCO relay (Programmable on active repeaters)

• Access level 2 override input for optional key switch

• Active Repeaters have unique address & user text allocation

• Alarm accept & delay override control on active repeaters

• RS 485 two core data cable connection to main control panel

Page 76: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Repeater Panel Schematic

FIRE PROTECTION

ZONE 1

ZONE 9

ZONE 17

ZONE 2

ZONE 10

ZONE 18

ZONE 3

ALARM DEVICEFAULT

TEST POWER ONP.S.U.FAULT

COMMONFAULT

COMMONISOLATE

SYSTEMFAULT

EARTHFAULT

SOUNDERFAULT

DEVICEISOLATE

OUTPUTDELAYED

PRE ALARM

SILENCE BUZZER

6 7 8 9 0

1 2 3 4 5

OUTPUTISOLATE

SCROLL

DELAY OVERRIDE

SILENCE ALARMS

EVACUATERESET

ZONE 11

ZONE 19

ZONE 4

ZONE 12

ZONE 20 ZONE 21

ZONE 13

ZONE 5

ZONE 22

ZONE 14

ZONE 6

ZONE 23

ZONE 15

ZONE 7

ZONE 24

ZONE 16

ZONE 8

FIRE PROTECTION

FIRE PROTECTION

ZONE 1

ZONE 9

ZONE 17

ZONE 2

ZONE 10

ZONE 18

ZONE 3

ALARM DEVICEFAULT

TEST POWER ONP.S.U.FAULT

COMMONFAULT

COMMONISOLATE

SYSTEMFAULT

EARTHFAULT

SOUNDERFAULT

DEVICEISOLATE

OUTPUTDELAYED

PRE ALARM

SILENCE BUZZER

6 7 8 9 0

1 2 3 4 5

OUTPUTISOLATE

SCROLL

DELAY OVERRIDE

SILENCE ALARMS

EVACUATERESET

ZONE 11

ZONE 19

ZONE 4

ZONE 12

ZONE 20 ZONE 21

ZONE 13

ZONE 5

ZONE 22

ZONE 14

ZONE 6

ZONE 23

ZONE 15

ZONE 7

ZONE 24

ZONE 16

ZONE 8

FIRE PROTECTION

FIRE PROTECTION

ZONE 1

ZONE 9

ZONE 17

ZONE 2

ZONE 10

ZONE 18

ZONE 3

ALARM DEVICEFAULT

TEST POWER ONP.S.U.FAULT

COMMONFAULT

COMMONISOLATE

SYSTEMFAULT

EARTHFAULT

SOUNDERFAULT

DEVICEISOLATE

OUTPUTDELAYED

PRE ALARM

SILENCE BUZZER

6 7 8 9 0

1 2 3 4 5

OUTPUTISOLATE

SCROLL

DELAY OVERRIDE

SILENCE ALARMS

EVACUATERESET

ZONE 11

ZONE 19

ZONE 4

ZONE 12

ZONE 20 ZONE 21

ZONE 13

ZONE 5

ZONE 22

ZONE 14

ZONE 6

ZONE 23

ZONE 15

ZONE 7

ZONE 24

ZONE 16

ZONE 8

FIRE PROTECTION

FIRE PROTECTION

ZONE 1

ZONE 9

ZONE 17

ZONE 2

ZONE 10

ZONE 18

ZONE 3

ALARM DEVICEFAULT

TEST POWER ONP.S.U.FAULT

COMMONFAULT

COMMONISOLATE

SYSTEMFAULT

EARTHFAULT

SOUNDERFAULT

DEVICEISOLATE

OUTPUTDELAYED

PRE ALARM

SILENCE BUZZER

6 7 8 9 0

1 2 3 4 5

OUTPUTISOLATE

SCROLL

DELAY OVERRIDE

SILENCE ALARMS

EVACUATERESET

ZONE 11

ZONE 19

ZONE 4

ZONE 12

ZONE 20 ZONE 21

ZONE 13

ZONE 5

ZONE 22

ZONE 14

ZONE 6

ZONE 23

ZONE 15

ZONE 7

ZONE 24

ZONE 16

ZONE 8

FIRE PROTECTION

FIRE PROTECTION

ZONE 1

ZONE 9

ZONE 17

ZONE 2

ZONE 10

ZONE 18

ZONE 3

ALARM DEVICEFAULT

TEST POWER ONP.S.U.FAULT

COMMONFAULT

COMMONISOLATE

SYSTEMFAULT

EARTHFAULT

SOUNDERFAULT

DEVICEISOLATE

OUTPUTDELAYED

PRE ALARM

SILENCE BUZZER

6 7 8 9 0

1 2 3 4 5

OUTPUTISOLATE

SCROLL

DELAY OVERRIDE

SILENCE ALARMS

EVACUATERESET

ZONE 11

ZONE 19

ZONE 4

ZONE 12

ZONE 20 ZONE 21

ZONE 13

ZONE 5

ZONE 22

ZONE 14

ZONE 6

ZONE 23

ZONE 15

ZONE 7

ZONE 24

ZONE 16

ZONE 8

FIRE PROTECTION

2 core 2 core

Page 77: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Repeaters

• Type 1 - Receive Only

• Type 2 - Full access level 2 controls

Page 78: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Repeaters

How to install - software:

• Vega panel set up - Membrane & Viper

• Install repeater - will install Type 1 & 2

• Number of active repeaters

• Enable repeater printer

Page 79: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Repeaters

How to install hardware:

• Install repeater drive pcb 44792-K076 into PLG 2 on the MBLC 44782-K073

• SW1 - leaves 1 & 2 on = repeater driving is one direction- leaves 1 & 2 off = repeater driving in both

directions

Page 80: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Repeaters

Interface Cable

• Twisted pair data cable

• 2L1.5 MICC

• FP200 2 core 1.0mm

Page 81: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Repeater Hardware

Connection to Vega via TB4 “Repeater In” on the

repeater terminal board 44782-K078.

SW1 - leaves 1 & 2 on - last repeater

- leaves 1 & 2 off - intermediate repeater

Page 82: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Repeater Hardware

Repeater Processor Board 44782-K077

SW1 - Processor reset

SW2 - (0) Type 1 repeater (no controls)

SW2 - (1-F) Type 2 repeater (with controls)

Page 83: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Repeater Hardware Repeater Processor Board 44782-K077 (cont’d)

SW3 Bit 1 ON local printer enable

OFF local printer disable

Bit 2 ON silence local buzzer only

OFF global buzzer silence

Bit 3 ON back light on constant

OFF back light timed to off

Bit 4 ON silence buzzer & local sounder

OFF silence buzzer only

SW4 Processor re-start

Page 84: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Battery Calculations

Calculation approved by the British Fire

Protection Systems Association (BFPSA)

Quiescent current (QI) x Battery degradation

factor (1.25)x 24 hours + half hour alarm load

(AI) x battery degradation factor (1.25)

QI x 1.25 x 24 + 0.5 x AI x 1.25

Page 85: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Standard Battery Sizes

12v - 0.8 A/h 18.0 A/h

1.2 A/h 24.0 A/h

2.0 A/h 26.0 A/h

3.0 A/h 33.0 A/h

4.5 A/h 38.0 A/h

7.0 A/h 40.0 A/h

12.0 A/h 70.0 A/h

17.0 A/h 75.0 A/h

Page 86: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Current Values

Single Loop Four LoopCurrent Current

Quiescent LCD Backlight Off 350mA 570mAcondition LCD Backlight On 410mA 630mA

1030mA 1260mAAlarm No Outputs Operational 470mA 670mAcondition BLC Sounders & VFCO's 730mA 940mAwithout printer BLC O/P's & Loop Devices 1380mA 1770mAAlarm No Outputs Operational 620mA 800mAcondition BLC Sounders & VFCO's 880mA 1080mAwith printer BLC O/P's & Loop Devices 1480mA 1900mA

Operation Description

LED Test

Page 87: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Approved Cables

• Conventional Detection- MICC (BS6207 Part 1)- FP200

• Conventional Sounders- MICC (BS6207 Part 1)- FP200

Vega

Page 88: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega

Approved Cables

• Addressable Detection Loops- MICC (BS6207 Part 1) up to 1km 1.5mm2

- FP200 up to 2 km 2.5mm2

• Sounders- MICC (BS6207 Part 1)- FP200

Page 89: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega

Approved Cables

• Repeaters / Motherboards- BELDEN 9729 (UL STYLE 2493) - MICC (BS6207 Part 1) 1mm 2 core- FP200

Page 90: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

EMC

• European Directive for Electro Magnetic Compatibility (EMC) 89/336/EEC

• Compliance to directive by type testing or construction file

• To ensure products are not affected or affect other electrical products

Page 91: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

EMC

• Tests include: radiated susceptibilityconducted susceptibilityradiated emissionsESDfast transientssurge test

• Compliance is indicated by the CE mark on products, data sheets, etc.

Page 92: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

EMC

• Generic standard has two sections:

- Industrial emissions & susceptibility- Domestic emissions & susceptibility

• Product specific standard for Fire & Security products uses the industrial levels for susceptibility & the domestic levels for emissions

Page 93: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

EMC

• Guidance for installation:

- earthing of cable glands- routing of cables inside the panel- routing of mains cable- use of screened cable

Page 94: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Specials

Special Metalwork

• Enclosure including 19” rack mounted

• IP65 enclosure

• Glazed outer doors

• Stainless steel fascia

Page 95: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Specials

Geographic Mimics with LED Indications

• Mosaic

• Rear engraved, multi-colour

• Silk screen on to door

Page 96: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Specials

Wiring

• Termination chambers

• Isolating terminals for external wiring

Software

• Unique changes to standard software

Page 97: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Specials

Specials Cell

• Dedicated project engineer

• Dedicated draughtsman

• Software engineering

• Verification engineer

Page 98: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Specials

Major Projects

• London Underground Limited

• Istanbul Metro Project

• Heathrow Airport

• Pfizers

• Kerteh Tankage Terminal Facility – Petronas

Page 99: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Part Numbers

Number configuration: (LL)/(B)/(ZZZ)/(D)/(S)/(P)

LL = No of loops 01 - 16B = Box size 1 - 16ZZZ = No of zonesD = Detector protocol

A = Apollo Series 90/XP95/DiscoveryE = Hochiki ESP

S = Power Supply2 = 2.5A switch mode4 = 4/2A switch mode8 = 8/4A switch mode

P = Printer

Page 100: VEGA CONTROL PANEL Technical. Applications Hotels Factories / Manufacturing Environments Shopping Centres Underground Stations Airports Office Complexes

Vega Part Numbers

Examples:

V01/1/024/A/2 = 1 loop, box size 1 (500w x 400h x 140d) 24 zonal LED’s, Apollo protocol, integral 2.5A PSU, without printer

V04/2/088/E/4/P = 4 loop, box size 2 (500w x 550h x 140d) 88 zonal LED’s, Hochiki protocol, integral 4/2 A PSU, with printer