I-100 FIELD INSTALLATION HANDBOOK For NPS and Metric Carbon Steel, Stainless Steel, and Aluminum Products I-100 FIELD INSTALLATION HANDBOOK attempting to install, remove, adjust, or maintain any Victaulic products. attempting to install, remove, adjust, or maintain any Victaulic products. and hearing protection. serious personal injury and/or property damage. Victaulic products, contact Victaulic.

Upload: limin-zhang

Post on 13-Apr-2015

256 views

Category:

Documents


1 download

DESCRIPTION

Victaulic I-100 Field Installation Handbook

TRANSCRIPT

Page 1: Victaulic I-100 Field Installation Handbook.pdf

I-100FIELD INSTALLATION HANDBOOK

For NPS and Metric Carbon Steel, Stainless Steel, and Aluminum Products

I-100FIELD INSTALLATION HANDBOOK

attempting to install, remove, adjust, or maintain any Victaulic products.

attempting to install, remove, adjust, or maintain any Victaulic products.

and hearing protection.

serious personal injury and/or property damage.

Victaulic products, contact Victaulic.

Page 2: Victaulic I-100 Field Installation Handbook.pdf

I-100_i

NOTICE®

.......................................................... 1 ........................................................

Introduction .....................................................................

....................................................... 3

...................................

Pipe Preparation .............................................................. 5

..................................................................... 5

.................................... 6

..................................................................... 8

Roll Grooving Tool Capacities ............................................... 8

Cut Grooving Tool Capacities ...............................................18

.................................19

Roll Groove Specifications for Steel Pipe and All Materials Grooved with Standard and RX Rolls ...............21

Standard Cut Groove Specifications for Steel and Other NPS Pipe .......................................................... 26

Roll Groove Specifications for Standard-Wall Pipe or Plastic-Coated Pipe Joined with Style HP-70ES EndSeal Couplings ..............................................................31

Cut Groove Specifications for Standard or Heavier-Wall Pipe or Plastic-Coated Pipe Joined with Style HP-70ES EndSeal Couplings ...................................... 32

Standard Radius Cut Grooving Specifications for Schedule 80 or Schedule 40 PVC Plastic Pipe (ASTM D-1785-70) .... 33

................................................35

Advanced Groove System (AGS) Roll Grooving Specifications for Carbon Steel and Stainless Steel Pipe ......37

............................................................ 39

Standard NPS Gaskets ....................................................... 39

Special NPS Gaskets ......................................................... 40

Lubrication ....................................................................

......................................

Page 3: Victaulic I-100 Field Installation Handbook.pdf

I-100_ii

Dry Pipe Fire Protection System Notes .............................

............

Recommended Minimum Pipe Spacing .............................. 45

External Clearance Allowance ............................................ 45

Installation to Achieve Maximum Linear Movement ....................................

...................

......................................

Flexible Systems - Hanger Spacing ................................... 50

Hanger Spacing ...........................................................51

........................................ 53

.............

® ........... 55

Angle-Bolt-Pad Couplings............................................. 56

.......................

..........59

® ........................................................... 60

.....................................61

............................ 63

.....................................

Installation Inspection .................................................... 65

....................................... 69

Style 009H FireLock EZ™ Rigid Coupling ................................70

Style 107H Quick-Vic™ Rigid Coupling for Steel Pipe ...............74

Style 177 Quick-Vic™ Flexible Coupling for Steel Pipe ............. 79

Page 4: Victaulic I-100 Field Installation Handbook.pdf

I-100_iii

....................................... 85

Preparatory Steps for Coupling Installation ............................. 86

Style 005 FireLock® Rigid Coupling ....................................... 88

Style 07 Zero-Flex® Rigid Coupling (12-inch/323.9-mm and Smaller Sizes) ............................................................. 88

Style 489 Rigid Stainless Steel Coupling for Stainless Steel Pipe (4-inch/114.3-mm and Smaller Sizes) ................ 88

Style 07 (Non-AGS) Zero-Flex Rigid Coupling (14-inch/355.6-mm and Larger Sizes) .................................91

Style HP-70 Rigid Coupling (12-inch/323.9-mm and Smaller Sizes) .................................................................... 93

Style 89 Rigid Coupling for Stainless Steel Pipe ..................... 93

Style 489 Rigid Stainless Steel Coupling for Stainless Steel Pipe (139.7-mm and Larger Sizes) .............. 93

Style 489DX Rigid Stainless Steel Coupling for Duplex and Super Duplex Pipe .......................................... 93

Style HP-70 Rigid Coupling (14-inch/355.6-mm and Larger Sizes) ...................................................................... 96

Style HP-70ES EndSeal® Rigid Coupling ................................ 98

Style 72 Outlet Coupling ...................................................... 100

Style 75 Flexible Coupling .....................................................103

Style 77 Flexible Coupling – Two Segments for 24-inch/610-mm and Smaller Sizes ..................................103

Style 77A Flexible Aluminum Coupling ..................................103

Style 77S Flexible Stainless Steel Coupling............................103

Style 77DX Flexible Stainless Steel Coupling for Duplex and Super Duplex Pipe .........................................103

Style 475 Flexible Stainless Steel Coupling ............................103

Style 475DX Flexible Stainless Steel Coupling for Duplex and Super Duplex Pipe .........................................103

Style 77 (Non-AGS) Flexible Coupling – Four or Six Segments for 14-inch/355.6-mm and Larger Sizes ............................106

Style 78 Snap-Joint® Coupling ..............................................108

Style 78A Snap-Joint Aluminum Coupling .............................108

Style 750 Reducing Coupling ................................................110

Style 770 Large Diameter Coupling .......................................112

Style 791 Vic-Boltless Coupling ............................................114

Style 707-IJ ANSI and ISO 4200-to-JIS Transition Coupling ...........................................................117

Page 5: Victaulic I-100 Field Installation Handbook.pdf

I-100_iv

® APPLICATIONS

..............................................119Pipe End Inspection for AGS Couplings - All Sizes ............... 120

Pipe Preparation for AGS Couplings (Direct-Grooved Applications) - All Sizes ........................... 120

AGS Vic-Ring® Application Information .................................121

Pipe Preparation for Styles W07, W77, and W89 AGS Couplings (AGS Vic-Ring® Applications) - All Sizes ............121

Style W07 AGS Rigid Coupling (24-inch/610-mm and Smaller Sizes) ........................................................... 122

Style W77 AGS Flexible Coupling (24-inch/610-mm and Smaller Sizes) ........................................................... 122

Style W07 AGS Rigid Coupling (26-inch/660-mm and Larger Sizes) ..............................................................125

Style W77 AGS Flexible Coupling (26-inch/660-mm and Larger Sizes) ..............................................................125

Style W89 AGS Rigid Coupling for Direct-Grooved Stainless Steel Pipe or Carbon Steel Pipe Prepared with AGS Vic-Rings (24-inch/610-mm and Smaller Sizes) ............................... 129

............................................. 133

Style 441 Stainless Steel Vic-Flange® Adapter Notes ............ 134

Style 441 Stainless Steel Vic-Flange Adapter........................ 135

Victaulic Flange Adapter Notes for 12-inch/323.9-mm and Smaller Sizes – Style 741, Style 744, and Style 743 .......... 138

Victaulic Flange Washer Notes for 12-inch/323.9-mm and Smaller Sizes – Style 741, Style 744, and Style 743 .......... 139

Style 741 Vic-Flange Adapter (12-inch/323.9-mm and Smaller Sizes) – ANSI Class 125, 150/DIN PN10 Class, or DIN PN16 Class ............................................................140

Style 743 Vic-Flange Adapter – ANSI Class 300 ...................140

Style 744 FireLock Flange Adapter – ANSI Class 150 ...........140

Victaulic Flange Adapter Notes for 14-inch/355.6-mm and Larger Sizes (Non-AGS) – Style 741............................146

Victaulic Flange Washer Notes for 14-inch/355.6-mm and Larger Sizes (Non-AGS) – Style 741............................147

Style 741 (Non-AGS) Vic-Flange Adapter (14-inch/ 355.6-mm and Larger Sizes) – ANSI Class 150 .................148

Page 6: Victaulic I-100 Field Installation Handbook.pdf

I-100_v

.......151

Style W741 AGS Vic-Flange Adapter Notes for 24-inch/ 610-mm and Smaller Sizes ...............................................152

Style W741 AGS Vic-Flange Washer Notes for 24-inch/ 610-mm and Smaller Sizes .............................................. 153

Pipe End Inspection for AGS Vic-Flange Adapters - All Sizes ........................................................................... 154

Pipe Preparation for AGS Vic-Flange Adapters ..................... 154

Style W741 AGS Vic-Flange Adapter (ANSI Class 150) ..........155

............................................. 159

Style 99 Roust-A-Bout® Coupling (12-inch/323.9-mm and Smaller Sizes) ............................................................160

Style 99 Roust-A-Bout Coupling (14-inch/355.6-mm and Larger Sizes) ............................................................. 164

.......... 169Style 912 FireLock Low-Profile Sprinkler-Tee

(Available in Europe Only) .................................................170

Style 920 Mechanical-T® Bolted Branch Outlet .....................173

Style 920N Mechanical-T Bolted Branch Outlet ....................173

Style 922 FireLock Outlet-T ..................................................178

Style 923 Vic-Let™ Strapless Outlet ...................................... 180

Style 924 Vic-O-Well™ Strapless Thermometer Outlet ........... 180

.......... 183

........................

Series 700 Butterfly Valve ................................................... 185

Series 761 Vic-300 MasterSeal Butterfly Valve ..................... 185

Series W761 AGS Vic-300 Butterfly Valve ............................ 185

Series 765, 705, 766, and 707C Butterfly Valves ................. 185

Series 763 Stainless Steel Butterfly Valve ............................ 185

..........................................185

Adjusting the Gear Operator’s Closed Travel Limit Stops for Series 761 Vic-300 MasterSeal, Series W761 AGS Vic-300, and Series 763 Stainless Steel Butterfly Valves ................ 186

Adjusting the Gear Operator’s Open Travel Limit Stops for Series 761 Vic-300 MasterSeal, Series W761 AGS Vic-300, and Series 763 Stainless Steel Butterfly Valves .................187

Adjusting the Gear Operator’s Closed Travel Limit Stops for 10 – 12-inch/273.0 – 323.9-mm Series 765, 705, 766, and 707C Butterfly Valves ................................................ 188

Page 7: Victaulic I-100 Field Installation Handbook.pdf

I-100_vi

Adjusting the Gear Operator’s Open Travel Limit Stops for 10 – 12-inch/273.0 – 323.9-mm Series 765, 705, 766, and 707C Butterfly Valves ................................................ 189

............................190

Series 712, 712S, and 713 Swinger Check Valves ................ 190

Series W715 AGS Dual-Disc Vic-Check® Valve ..................... 190

Series 716/716H Vic-Check Valves ...................................... 190

Series 717, 717H, 717R, and 717HR FireLock Check Valves ....................................................................191

Series 779 Venturi Check Valve ............................................191

Ball Valve Installation and Operation ...............................191

Series 722 Threaded Ball Valve ............................................191

Series 723 Diverter Ball Valve ...............................................191

Series 726 Vic-Ball Valve ......................................................191

Series 728 FireLock Ball Valve ..............................................191

Plug Valve Installation and Operation ..............................

Series 365 Vic-Plug™ AWWA Plug Valve ............................... 192

Series 377 Vic-Plug Balancing Valve .................................... 192

.... 193Style 735 Fire Pump Test Meter .......................................... 194

...................................................... 195English and Metric Conversion Chart ................................... 195

ANSI Commercial Pipe Sizes ............................................... 196

Decimal Equivalents of Fractions ......................................... 199

Minutes Converted to Decimals of a Degree ......................... 199

Water Pressure to Feet-of-Head ........................................... 200

Feet-of-Head of Water to Pressure ....................................... 200

Where to Find Installation Instructions for Additional Products ...........................................................201

...................................................................

...........................FACILITIES LOCATIONS ......................................................... B/C

Page 8: Victaulic I-100 Field Installation Handbook.pdf

I-100_1

Page 9: Victaulic I-100 Field Installation Handbook.pdf

This safety alert symbol indicates important safety messages. When you

see this symbol, be alert to the possibility of personal injury. Carefully read

and fully understand the message that follows.

including recommended

result in death or serious personal

recommended precautions, are not

in personal injury and product or

including recommended

NOTICE

are important but not related to hazards.

This field assembly and installation handbook is a basic field reference guide for Victaulic

mechanical piping products for NPS and metric carbon steel, stainless steel, and

aluminum pipe. This handbook provides easy reference to proper installation information.

In addition to this handbook, Victaulic offers the following handbooks for other products/

materials:

Stainless Steel Products

Additional copies of installation information are available from Victaulic, or Victaulic

stocking distributors, upon request.

Always follow good piping practices. Specified pressures, temperatures, external loads,

internal loads, performance standards, and tolerances must never be exceeded.

Many applications require recognition of special conditions, code requirements, and the

use of safety factors. Qualified engineers should reference Section 26 of the Victaulic

General Catalog (G-100) and Victaulic publication 05.01, “Gasket Selection Guide,” when

determining requirements for special applications.

Page 10: Victaulic I-100 Field Installation Handbook.pdf

I-100_3

NOTICE

obligation.

Victaulic grooved pipe couplings are designed for use only with pipe that is grooved to

meet Victaulic specifications. In addition, Victaulic grooved pipe couplings are for use

only with Victaulic grooved-end fittings, valves, and related grooved-end components.

Victaulic grooved pipe couplings are not intended for use with plain-end pipe and/or

fittings.

Victaulic plain-end pipe couplings are designed for use only with plain-end or beveled-

end steel pipe and Victaulic plain-end fittings, unless indicated otherwise. Victaulic plain-

end pipe couplings must not be used with grooved-end or threaded pipe and/or fittings.

Gaskets for Victaulic grooved and plain-end pipe couplings must be lubricated for proper

assembly. Lubrication prevents gasket pinching and assists installation. A thin coat

of Victaulic Lubricant or another compatible material, such as silicone or soap-based

lubricants, is required. Always refer to the specific coupling installation instructions for

complete lubrication requirements.

Victaulic gaskets are designed to perform in a wide range of temperatures and operating

conditions. As with all installations, there is a direct relationship between temperature,

continuity of service, and gasket life. Victaulic publication 05.01, “Gasket Selection

Guide,” must be referenced to determine gasket grade recommendations for each

application.

For piping

applications that fall under the jurisdiction of the Provincial Boilers and Pressure Vessels

Acts, intended users should obtain Victaulic Technical Sheet TS-226, which outlines

approved services, products, pressure ratings, and temperature ratings.

Page 11: Victaulic I-100 Field Installation Handbook.pdf

NOTICE

1. tool. Read the supplied manual carefully before operating or performing maintenance

on any tool. Become familiar with the tool’s features, operations, applications, and

limitations. Be particularly aware of its specific hazards. Store the operator’s manual

in a readily available location. If you require additional copies of any literature, contact

Victaulic.

Make sure that the tool and power

drive are fastened securely to the floor.

3. Prevent accidental start-ups. Place any power switches in the “OFF” position

before plugging the tool into the electrical system. Always use a safety foot switch for the

power source.

Make sure the power source is connected to an

internally grounded electrical system.

5. Operating environment. Do not operate tools in damp locations. Wear hearing

protection in noisy shop operations. Ensure that the work area is well lit.

6. Wear proper clothing. Do not wear unbuttoned jackets, loose sleeve cuffs, neckties,

or anything else that can become tangled in moving parts. Always wear safety glasses

and foot protection.

Stay alert. Do not operate tools if you are drowsy from medication or fatigue. Avoid

horseplay around the equipment, and keep bystanders a safe distance away from the

equipment.

8. Inspect the equipment. Before starting the tool, check all moveable parts for any

obstructions. Make sure the guards and tool parts are installed and secured properly.

9. Keep the work area around the tool clear of obstructions

that could limit the movement of the operator. Clean up all oil and coolant spills. Remove

shavings from the tool to maintain proper operation.

10. For long sections of pipe and heavier work, use floor-mounted

pipe stands. Make sure that the work is secured properly in a pipe vise that is fastened

securely to the floor.

11. Operate tools with a safety foot switch

located at an easily accessible area. Never reach across moving parts or material being

worked on. The safety foot switch must always be accessible to the operator.

Do not misuse tools. Perform only the functions for which the tool was designed.

Do not force the tool. Do not operate the tool at speeds exceeding those specified in the

operating and maintenance instructions manual.

13. Only authorized personnel should

attempt to service tools. Always disconnect the power source before servicing or making

any adjustments.

Keep tools clean and cutting tools sharp for safe,

dependable operation. Follow all lubricating instructions. Report any unsafe conditions to

authorized personnel for immediate correction.

Page 12: Victaulic I-100 Field Installation Handbook.pdf

I-100_5

The grooved piping method is based upon the proper preparation of grooves to receive

the housings’ keys. The groove serves as a recess in the pipe, which allows ample depth

for secure engagement of the housings, yet ample wall thickness for full published

Victaulic pressure ratings.

Victaulic cut grooving tools are designed for use on standard, heavy-wall metallic; cast

gray iron; ductile iron; or plastic pipe. Roll grooving tools accommodate standard-wall

pipe, light-wall pipe, and some X-Strong pipe.

preparation tools, read and understand the operating and

Learn the operation, applications, and potential hazards peculiar to the tool.

product installation, resulting in serious personal injury and/or property damage.

Pipe must be prepared to Victaulic specifications outlined for each product style.

Preparation may vary according to pipe material, wall thickness, outside dimensions,

and other factors. Refer to all pipe preparation and groove specification sections of this

manual for detailed information.

Victaulic recommends square-cut pipe for use with grooved-end and plain-end pipe

products. Square-cut pipe MUST be used with Victaulic FlushSeal® and EndSeal®

gaskets. Beveled-end pipe may be used, provided that the wall thickness is standard

wall (ANSI B36.10) or less and that the bevel meets ANSI B16.25 (37 ½°) or ASTM A-53

(30°). Roll grooving beveled-end pipe may result in unacceptable flare.

For AGS products, beveled carbon steel pipe may be used, provided the wall thickness is

standard wall (0.375 inch/9.5 mm) and the bevel meets ASTM A53 and/or API 5L

(30˚ +5˚/-0˚). Roll grooving beveled-end pipe may result in unacceptable flare.

NOTICE

The “Tool Ratings” tables featured in this manual contain general information about

tool capacities. Certain tools are designed for high-use shop fabrication, while others

are designed for field fabrication. For detailed information on tools, refer to Victaulic

publication 24.01. For information about maintenance and operation of tools, refer to the

applicable operating and maintenance instructions manual for the tool. Victaulic

cut grooving tools are designed for use on AWWA ductile iron pipe as well as NPS steel

and other NPS materials.

Page 13: Victaulic I-100 Field Installation Handbook.pdf

I-100_6

The table below identifies the minimum pipe lengths that can be grooved safely by using

Victaulic Grooving Tools. In addition, this table identifies the maximum pipe lengths

that can be grooved without the use of a pipe stand. Pipe that exceeds the maximum

lengths listed in this table requires the use of a pipe stand. Always refer to the operating

and maintenance manual for the applicable grooving tool for proper setup and grooving

techniques.

Size

Nominal Sizeinches or mm

Actual Pipe Outside Diameter inches/mm Minimum Maximum

¾1.050 8 3626.9 205 915

11.315 8 3633.7 205 915

1 ¼1.660 8 3642.4 205 915

1 ½1.900 8 3648.3 205 915

22.375 8 3660.3 205 915

2 ½2.875 8 3673.0 205 915

76.1 mm3.000 8 3676.1 205 915

33.500 8 3688.9 205 915

3 ½4.000 8 36101.6 205 915

108.0 mm4.250 8 36108.0 205 915

44.500 8 36114.3 205 915

4 ½5.000 8 32127.0 205 815

133.0 mm5.250 8 32133.0 205 815

139.7 mm5.500 8 32139.7 205 815

55.563 8 32141.3 205 815

152.4 mm6.000 10 30152.4 255 765

159.0 mm6.250 10 30159.0 255 765

165.1 mm6.500 10 30165.1 255 765

66.625 10 28168.3 255 715

203.2 mm8.000 10 24203.2 255 610

216.3 mm8.500 10 24216.3 255 610

88.625 10 24219.1 255 610

254.0 mm10.000 10 20254.0 255 510

267.4 mm10.500 10 20267.4 255 510

1010.750 10 20273.0 255 510

304.8 mm12.000 12 18304.8 305 460

318.5 mm12.500 12 18318.5 305 460

1212.750 12 18323.9 305 460

Page 14: Victaulic I-100 Field Installation Handbook.pdf

Size

Nominal Sizeinches or mm

Actual Pipe Outside Diameter inches/mm Minimum Maximum

14 OD14.000 12 16355.6 305 410

377.0 mm14.843 12 16377.0 305 410

15 OD15.000 12 16381.0 305 410

16 OD16.000 12 16406.4 305 410

426.0 mm16.772 12 16426.0 305 410

18 OD18.000

NOTE: Always use a pipe stand when roll grooving

pipe in these sizes. DO NOT roll groove pipe lengths

shorter than 18 inches/457 mm

in these sizes.

457

480.0 mm18.898

480

20 OD20.000

508

530.0 mm20.866

530

22 OD22.000

559

24 OD24.000

610

650.0 mm25.591

650

26 OD26.000

660

28 OD28.000

711

30 OD30.000

762

32 OD32.000

813

36 OD36.000

914

40 OD40.000

1016

42 OD42.0001067

46 OD46.000

1168

48 OD48.000

1219

54 OD54.0001372

56 OD56.0001422

60 OD60.0001524

72 OD72.0001829

If pipe is required that is shorter than the minimum length listed in this table, shorten the next-to-last piece so that the last piece is as long (or longer) than the minimum length specified.

A 20-foot, 4-inch/6.2-m length of 10-inch/273.0-mm diameter steel pipe is required to finish a section and only 20-foot/6.1-m lengths are available. Instead of roll grooving a 20-foot/6.1-m length of steel pipe and a 4-inch/102-mm length of steel pipe, follow these steps:

1. Refer to the table above, and note that for 10-inch/273.0-mm diameter steel pipe, the minimum length that should be roll grooved is 10 inches/255 mm.

2. Roll groove a 19-foot, 6-inch/5.9-m length of pipe and a 10-inch/255-mm length of pipe.

Page 15: Victaulic I-100 Field Installation Handbook.pdf

I-100_8

Tool

Mod

elP

ipe

Mat

eria

l

inch

es/m

m

¾1

1 ¼

1 ½

60.

38

8.9

3 ½

101.

56

168

.38

1035

5.6

16

VE1

2

Ste

el

5 –

10

5 –

40

Sta

inle

ss

40

S O

nly

Alu

min

um

†5

– 1

05

– 4

0

PV

C P

last

ic4

0

VE

26

SS

tee

l5

– 4

05

– 1

0

Sta

inle

ss4

0S

On

ly

VE

26

CC

op

pe

rK

, L, M

, & D

WV

VE

26

PA

lum

inu

m †

5 –

40

5 –

10

PV

C P

last

ic4

0

VE

26

SS

Lt. W

all

SS

5S

– 1

0S

VE

46

Ste

el

5 –

40

Sta

inle

ss4

0S

On

ly

VE

46

PA

lum

inu

m †

5 –

40

PV

C P

last

ic4

04

0 –

80

VE1

06

V

E10

8H

(Gro

ov

e-N

-Go

)

Ste

el

◊5

– 4

0 S

td. R

olls

Sta

inle

ss4

0S

Std

. Ro

lls

Lt. W

all

SS

5S

– 1

0S

RX

Ro

lls

Co

pp

er

K, L

, M, &

DW

V C

op

pe

r R

olls

See n

ote

s on P

age 1

6.

Page 16: Victaulic I-100 Field Installation Handbook.pdf

I-100_9

Tool

Mod

elP

ipe

Mat

eria

l

inch

es/m

m

¾1

1 ¼

1 ½

60.

38

8.9

3 ½

101.

56

168

.38

1035

5.6

16

VE

22

6S

Ste

el

5 –

40

5 –

10

Sta

inle

ss

40

S O

nly

VE

22

6B

Ste

el

5 –

40

Sta

inle

ss4

0S

On

ly

Alu

min

um

†5

– 4

0

PV

C P

last

ic4

04

0 –

80

VE

22

6M

Ste

el

5 –

40

5 –

10

Sta

inle

ss4

0S

On

ly

VE

22

6C

Co

pp

er

K, L

, M, &

DW

V

VE

22

6B

SS

Lt. W

all

SS

5S

10

S

VE

22

6M

SS

LT. W

all

SS

5S

– 1

0S

VE

22

6P

Alu

min

um

†5

– 4

05

– 1

0

PV

C P

last

ic4

0 –

80

40

VE

27

2F

S ‡

Ste

el

◊5

– 4

0 S

td. R

olls

5 –

20

Std

. Ro

lls

Sta

inle

ss4

0S

Std

. Ro

lls

Lt. W

all

SS

5S

– 1

0S

RX

Ro

lls

Alu

min

um

†*

5 –

40

RP

Ro

lls5

– 2

0R

P R

olls

PV

C P

last

ic *

40

* §

40

– 8

0 R

P R

olls

40

*

Co

pp

er

K, L

, M, &

DW

V C

op

pe

r R

olls

See n

ote

s on P

age 1

6.

Page 17: Victaulic I-100 Field Installation Handbook.pdf

I-100_10

Tool

Mod

elP

ipe

Mat

eria

l

inch

es/m

m

¾1

1 ¼

1 ½

60.

38

8.9

3 ½

101.

56

168

.38

1035

5.6

16

VE

26

8

VE

26

9

Ste

el

◊5

– 4

0 S

td. R

olls

5 –

20

Std

. Ro

lls

Sta

inle

ss4

0S

Std

. Ro

lls

Lt. W

all

SS

5S

– 1

0S

RX

Ro

lls

Alu

min

um

†*

5 –

40

RP

Ro

lls5

– 2

0R

P R

olls

PV

C P

last

ic *

40

* §

40

– 8

0 R

P R

olls

40

RP

Ro

lls

Co

pp

er

K, L

, M, &

DW

V C

op

pe

r R

olls

VE

27

0F

SD

V

E2

71F

SD

Ste

el

◊5

– 4

0 S

td. R

olls

5 –

20

Std

.R

olls

Sta

inle

ss4

0S

Std

. Ro

lls

Lt. W

all

SS

5S

– 1

0S

RX

Ro

lls

Alu

min

um

†*

5 –

40

RP

Ro

lls5

– 2

0 R

PR

olls

PV

C P

last

ic *

40

* §

40

– 8

0 R

P R

olls

40

*

Co

pp

er

K, L

, M, &

DW

V C

op

pe

r R

olls

See n

ote

s on P

age 1

6.

Page 18: Victaulic I-100 Field Installation Handbook.pdf

I-100_11

Tool

Mod

elP

ipe

Mat

eria

l

inch

es/m

m

¾1

1 ¼

1 ½

60.

38

8.9

3 ½

101.

56

168

.38

1035

5.6

16

VE

27

2S

FS

V

E2

66

FS

Ste

el

◊5

– 4

0 S

td. R

olls

5 –

20

Std

. Ro

lls

Sta

inle

ss4

0S

Std

. Ro

lls

LT. W

all

SS

5S

– 1

0S

RX

Ro

lls

Alu

min

um

†*

5 –

40

RP

Ro

lls5

– 2

0R

P R

olls

PV

C P

last

ic*

40

* §

4

0 –

80

RP

Ro

lls4

0 *

Co

pp

er

K, L

, M, &

DW

V C

op

pe

r R

olls

VE

274

Ste

el

◊5

– 4

0 S

td. R

olls

5 –

20

Std

. Ro

lls

Sta

inle

ss4

0S

Std

. Ro

lls

Lt. W

all

SS

5S

– 1

0S

RX

Ro

lls

Alu

min

um

†*

5 –

40

RP

Ro

lls5

– 2

0R

P R

olls

PV

C P

last

ic *

40

* §

40

– 8

0 R

P R

olls

40

*

Co

pp

er

K, L

, M, &

DW

V C

op

pe

r R

olls

See n

ote

s on P

age 1

6.

Page 19: Victaulic I-100 Field Installation Handbook.pdf

Tool

Mod

elP

ipe

Mat

eria

l

inch

es/m

m

¾1

1 ¼

1 ½

60.

38

8.9

3 ½

101.

56

168

.38

1035

5.6

16

VE

27

6F

SD

Ste

el

◊5

– 4

0 S

td. R

olls

5 –

20

Std

. Ro

lls

Sta

inle

ss4

0S

Std

. Ro

lls

LT. W

all

SS

5S

– 1

0S

RX

Ro

lls

Alu

min

um

†*

5 –

40

RP

Ro

lls5

– 2

0R

P R

olls

PV

C P

last

ic *

40

* §

40

– 8

0 R

P R

olls

40

*

Co

pp

er

K, L

, M, &

DW

V C

op

pe

r R

olls

VE

414

MC

V

E41

4

Ste

el

◊5

– 4

0 S

td. R

olls

5 –

Std

. Wa

ll

Sta

inle

ss4

0S

Std

. Ro

llsS

td. W

all

On

ly

Lt. W

all

SS

5S

– 1

0S

RX

Ro

lls5

S –

10

RX

R

olls

Alu

min

um

†*

5 –

40

RP

Ro

lls5

–S

td.

Wa

ll *

PV

C P

last

ic *

80

* §

40

– 8

0 R

P R

olls

40

*

Co

pp

er

K, L

, M, &

DW

V C

op

pe

r R

olls

AG

S S

tee

l.2

20

” –

.37

5”

Wa

ll, R

W R

olls

AG

S S

tain

less

Std

. Wa

ll, R

W

Ro

lls

AG

S L

t. W

all

SS

5S

– 1

0S

RW

X

Ro

lls #

See n

ote

s on P

age 1

6.

Page 20: Victaulic I-100 Field Installation Handbook.pdf

I-100_13

Tool

Mod

elP

ipe

Mat

eria

l

inch

es/m

m

¾1

1 ¼

1 ½

60.

38

8.9

3 ½

101.

56

168

.38

1035

5.6

16

VE

416

FS

VE

416

FS

D

Ste

el

◊5

– 4

0 S

td. R

olls

5 –

Std

. Wa

ll

Sta

inle

ss4

0S

Std

. Ro

llsS

td. W

all

On

ly

Lt. W

all

SS

5S

– 1

0S

RX

Ro

lls5

S –

10

RX

R

olls

Alu

min

um

†*

5 –

40

RP

Ro

lls5

– S

td.

Wa

ll*

PV

C P

last

ic *

80

* §

40

– 8

0 R

P R

olls

40

*

Co

pp

er

K, L

, M, &

DW

V C

op

pe

r R

olls

AG

S S

tee

l.2

20

” –

.37

5”

Wa

ll, R

W R

olls

AG

S S

tain

less

Std

. Wa

ll,

RW

Ro

lls

AG

S L

t. W

all

SS

5S

10

SR

WX

Ro

lls #

See n

ote

s on P

age 1

6.

Page 21: Victaulic I-100 Field Installation Handbook.pdf

Tool

Mod

elP

ipe

Mat

eria

l

inch

es/m

m

½5

616

8.3

810

355.6

1618

50

8559

610

VE

42

4M

C ‡

Ste

el

◊5

– 8

05

– S

td. W

all

Sta

inle

ss4

0S

Std

. Ro

llsS

td. W

all,

Std

. Ro

lls

Lt. W

all

SS

5S

– 1

0S

RX

Ro

lls5

S/1

0S

/10

RX

Ro

lls

Alu

min

um

†*

5 –

40

RP

Ro

lls

PV

C P

last

ic *

40

– 8

0 *

40

*

AG

S S

tee

l.2

20

” –

.37

5”

Wa

ll, R

W R

olls

AG

S S

tain

less

Std

. Wa

ll, R

W R

olls

AG

S L

t. W

all

SS

5S

– 1

0S

RW

X R

olls

#

VE

45

0F

SD

Ste

el

◊5

– 4

0S

ch

. 5 –

Std

. Wa

ll O

rig

ina

l G

roo

ve

On

ly

Sc

h. 1

0 &

Std

. Wa

ll R

W-A

GS

Sta

inle

ss4

0S

Std

. Ro

llsS

td. W

all,

Std

. Ro

lls

Std

. Wa

ll, R

W-A

GS

Lt. W

all

SS

5S

– 1

0S

RX

Ro

lls ∞

5S

/10

S/1

0 R

X R

olls

AG

S L

t. W

all

SS

10S

RW

X R

olls

#

Alu

min

um

†*

5 –

40

RP

Ro

lls

PV

C P

last

ic *

40

– 8

04

0

See n

ote

s on P

age 1

6.

Page 22: Victaulic I-100 Field Installation Handbook.pdf

I-100_15

Tool

Mod

elP

ipe

Mat

eria

l

inch

es/m

m

½5

616

8.3

810

355.6

1618

50

8559

610

VE

44

8M

C ‡

Ste

el

◊5

– 8

05

– 4

0 @

5 –

Ex

tra

Str

on

g (

0.5

00

in

ch

) @

Sta

inle

ss4

0S

Std

. Ro

llsS

td. W

all,

Std

. Ro

lls

Lt. W

all

SS

5S

– 1

0S

RX

Ro

lls5

S/1

0S

/10

RX

Ro

lls

Alu

min

um

†*

5 –

40

RP

Ro

lls

PV

C P

last

ic *

40

– 8

0 *

40

*

AG

S S

tee

lS

td. W

all,

RW

Ro

lls

AG

S S

tain

less

Std

. Wa

ll, R

W R

olls

AG

S L

t. W

all

SS

5S

– 1

0S

RW

X R

olls

See n

ote

s on P

age 1

6.

Page 23: Victaulic I-100 Field Installation Handbook.pdf

I-100_16

Tool

Mod

elP

ipe

Mat

eria

l

inch

es/m

m

56

168

.38

1035

5.6

1618

50

8559

610

66

030

813

36

VE

43

6M

C ‡

Ste

el

◊5

– 8

05

– 4

0 @

5 –

Ex

tra

Str

on

g (

0.5

00

in

ch

) @

Sta

inle

ss4

0S

Std

. Ro

llsS

td. W

all,

Std

. Ro

lls

Lt. W

all

SS

5S

– 1

0S

RX

Ro

lls5

S/1

0S

/10

RX

Ro

lls

Alu

min

um

†*

5 –

40

RP

Ro

lls

PV

C P

last

ic4

0 –

80

*4

0 *

AG

S S

tee

l.2

20

” –

.49

2”

Wa

ll, R

W R

olls

Δ

AG

S S

tain

less

Std

. Wa

ll, R

W R

olls

AG

S L

t. W

all

SS

5S

– 1

0S

RW

X R

olls

#

* U

se R

P R

olls.

† 6

061-T

4 o

r 6

06

3-T

4 m

ust

be u

sed.

RP

Rolls

mu

st

be u

sed.

‡ T

ool h

as

been d

iscon

tinu

ed.

# S

pecia

l ro

lls

for

gro

ovin

g t

rue S

ch

. 10 (

0.2

50 in

ch

/6.4

mm

) are

availab

le.

@ F

or

6 –

14

-in

ch

/16

8.3

– 3

55

.6-m

m s

izes,

specia

l to

olin

g is

availab

le f

or

gro

ovin

g e

xtr

a-s

tron

g p

ipe.

For

8 –

24

-in

ch

/219.1

– 6

10

-mm

siz

es,

the m

axim

um

wall

thic

kn

ess

is lim

ited t

o s

tan

dard

w

all

for

pip

e len

gth

s sh

ort

er

than

4 fe

et/

1.2

m

§ A

sp

ecia

l lo

wer

roll

exc

lusiv

ely

for

gro

ovin

g 2

-in

ch

/60

.3-m

m S

ch

. 8

0 P

VC

is

availab

le.

Δ T

he V

E4

36

MC

is

cap

ab

le o

f gro

ovin

g .

49

2-i

nch

/12

.5-m

m w

all

carb

on s

teel p

ipe t

o A

GS s

pecific

ation

s.

Pip

e h

ard

ness

is lim

ited t

o a

Bri

nell

Hard

ness

Nu

mb

er

(BH

N)

of

15

0 m

axim

um

.

∞ T

hese r

olls

are

not

inte

rch

an

geab

le w

ith r

oll

sets

fro

m o

ther

tool m

od

els

. C

on

tact

Vic

tau

lic f

or

ord

eri

ng in

form

ation

.

◊ E

nd

Seal (E

S)

rolls

are

availab

le.

Con

tact

Vic

tau

lic f

or

deta

ils.

Page 24: Victaulic I-100 Field Installation Handbook.pdf

Tool

Mod

elP

ipe

Mat

eria

l

inch

es/m

m

56

168

.38

1035

5.6

1618

50

8559

610

66

030

813

36

38

96

510

166

0

VE

46

0

Ste

el

5 -

80

5 -

Ex

tra

S

tro

ng

10 -

Ex

tra

Str

on

g (

.50

0)*

A

GS

Std

. (.3

75

- .5

00

)*

AG

S

Sta

inle

ssS

ch

. 40

On

ly.3

75

Std

. (.3

75

- .5

00

)*

AG

S

Lt. W

all

SS

5S

- 1

0S

RX

5S

- 1

0S

- 1

0 R

WX

Alu

min

um

‡ #

5 -

40

PV

C P

last

ic ‡

40

- 8

04

0

Ste

el

5 -

Ex

tra

Str

on

g (

.50

0)*

.25

0 -

.50

0*

Sta

inle

ssS

td. (

.37

5)

Lt. W

all

SS

5S

- 1

0S

- 1

0 R

X R

olls

* M

axim

um

ratin

gs

are

lim

ited t

o p

ipe t

hat

does

not

exc

eed t

he y

ield

str

en

gth

of

AP

I-5

L G

rad

e “

B”,

AS

TM

Gra

de “

B”,

15

0 B

rin

ell

Hard

ness

Nu

mb

er

(BH

N)

maxim

um

.

‡ R

P r

olls

mu

st

be u

sed

# A

lum

inu

m a

lloys

60

61-T

4 o

r 6

06

3-T

4 m

ust

be u

sed.

RP

rolls

mu

st

be u

sed.

Page 25: Victaulic I-100 Field Installation Handbook.pdf

I-100_18

Tool

Mod

elP

ipe

Mat

eria

l

inch

es/m

m

¾1

1 ¼

1 ½

60.

38

8.9

3 ½

101.

56

168

.38

1035

5.6

1618

50

8559

610

Vic

-Gro

ov

er

Ind

ivid

ua

l ‡

Ste

el

40

– 8

0

Sta

inle

ss4

0 –

80

Alu

min

um

40

– 8

0

PV

C4

0 –

80

Vic

-Gro

ov

er

Ad

just

ab

le ‡

Ste

el

40

– 8

0

Sta

inle

ss4

0 –

80

Alu

min

um

40

– 8

0

Vic

-Gro

ov

er

Du

cti

le I

ron

Cla

ss5

3C

lass

53

VG

28

GD

Ad

just

ab

le

Gro

ov

er

Ste

el

40

– 8

0

Sta

inle

ss4

0 –

80

Alu

min

um

40

– 8

0

Du

cti

le I

ron

Cla

ss 5

3

VG

82

4C

ut

Gro

ov

er

Ste

el

40

– 8

03

0 –

Std

. Wa

ll

Sta

inle

ss3

0 –

Std

. Wa

ll

Alu

min

um

30

– S

td. W

all

Du

cti

le I

ron

Cla

ss 5

3

VG

82

8A

GS

Cu

t G

roo

ve

rS

tee

l.5

00

– .7

50

VG

412

Ad

just

ab

le G

roo

ve

r

Ste

el

40

– 8

0

Du

cti

le I

ron

Cla

ss 5

3

VP

G2

6P

VC

40

– 8

0 P

VC

VP

G8

24

PV

C4

0 –

80

PV

C

‡ V

ic-G

roover

Indiv

idu

al an

d A

dju

sta

ble

Tools

are

siz

e a

nd m

ate

rial sp

ecific

.

Page 26: Victaulic I-100 Field Installation Handbook.pdf

I-100_19

personal injury and/or property damage.

A B

D

B

T

COD F

B

A B

OD C

D

T

Exaggerated for Clarity

A B

OD C

B

R T

Exaggerated for clarity

Illustrations are exaggerated for clarity

NOTICE

– The average pipe outside diameter must not vary from the

specifications listed in the tables on the following pages. Maximum allowable pipe ovality

should not vary by more than 1%. Greater variations between the major and minor

diameters will result in difficult coupling assembly.

1⁄32 inch/0.8 mm for ¾ – 3 ½-inch/26.9 – 101.6-mm

sizes; 1⁄16 inch/1.6 mm for 4 – 24-inch/114.3 – 610-mm sizes; and

3⁄32 inch/2.4 mm for 26-inch/660-mm and larger sizes. This is

measured from the true square line.

"S" Max.

Any internal and external weld beads or seams must be ground flush to the pipe surface.

The inside diameter of the pipe end must be cleaned to remove coarse scale, dirt, and

other foreign material that might interfere with or damage grooving rolls. The front edge

of the pipe end shall be uniform with no concave/convex surface features that will cause

improper grooving roll tracking and result in difficulties during coupling assembly.

The “A” dimension, or the distance from the pipe end to the groove,

identifies the gasket seating area. This area must be free from indentations, projections

(including weld seams), and roll marks from the pipe end to the groove to ensure a leak-

tight seal. All foreign material, such as loose paint, scale, oil, grease, chips, rust, and dirt

must be removed.

The “B” dimension, or groove width, controls expansion, contraction,

and angular deflection of flexible couplings by the distance it is located from the pipe and

its width in relation to the coupling housings’ “key” width. The bottom of the groove must

be free of all foreign material, such as dirt, chips, rust, and scale that may interfere with

proper coupling assembly.

Page 27: Victaulic I-100 Field Installation Handbook.pdf

The “C” dimension is the average diameter at the base of the groove.

This dimension must be within the diameter’s tolerance and concentric with the

OD for proper coupling fit. The groove must be of uniform depth for the entire pipe

circumference.

The “D” dimension is the normal depth of the groove and is a reference

for a “trial groove” only. Variations in pipe OD affect this dimension and must be altered,

if necessary, to keep the “C” dimension within tolerance. The groove diameter must

conform to the “C” dimension described above.

Maximum allowable pipe-end flare diameter is

measured at the extreme pipe-end diameter. This applies to average (pi tape) and

single-point readings.

The “T” dimension is the lightest grade (minimum nominal wall

thickness) of pipe that is suitable for cut or roll grooving. Pipe that is less than the

minimum nominal wall thickness for cut grooving may be suitable for roll grooving or

adapted for Victaulic couplings by using Vic-Ring® Adapters. Vic-Ring Adapters can be

used in the following situations (contact Victaulic for details):

The “R” dimension is the radius necessary at the bottom of the groove

to eliminate a point of stress concentration for cast pipe (gray and ductile) and PVC

plastic pipe.

NOTICE

Page 28: Victaulic I-100 Field Installation Handbook.pdf

Siz

e

Nom

inal

S

ize

inch

es o

r m

m

Act

ual

Pip

e O

utsi

de

Dia

met

er

inch

es/m

m

Pip

e O

utsi

de D

iam

eter

Dep

thW

all

Max

.

Flar

e D

ia.

Max

.M

in.

Bas

icM

ax.

Min

.B

asic

Max

.M

in.

Max

.M

in.

¾1.

05

01.

06

01.

04

00

.62

50

.65

60

.59

40

.28

10

.312

0.2

50

0.9

38

0.9

23

0.0

56

0.0

49

1.15

26

.92

6.9

26

.415

.916

.715

.17.

17.

96

.42

3.8

23

.41.

51.

22

9.2

11.

315

1.3

28

1.3

02

0.6

25

0.6

56

0.5

94

0.2

81

0.3

120

.25

01.

190

1.17

50

.06

30

.04

91.

43

33

.73

3.7

33

.115

.916

.715

.17.

17.

96

.43

0.2

29

.91.

61.

23

6.3

1 ¼

1.6

60

1.6

76

1.6

44

0.6

25

0.6

56

0.5

94

0.2

81

0.3

120

.25

01.

53

51.

52

00

.06

30

.04

91.

77

42

.44

2.6

41.8

15.9

16.7

15.1

7.1

7.9

6.4

39

.03

8.6

1.6

1.2

45

.0

1 ½

1.9

00

1.9

191.

88

10

.62

50

.65

60

.59

40

.28

10

.312

0.2

50

1.7

75

1.7

60

0.0

63

0.0

49

2.0

14

8.3

48

.74

7.8

15.9

16.7

15.1

7.1

7.9

6.4

45

.14

4.7

1.6

1.2

51.1

57.

0 m

m2

.24

42

.26

72

.22

20

.62

50

.65

60

.59

40

.34

40

.37

50

.313

2.1

182

.10

20

.06

30

.04

92

.35

57.

05

7.6

56

.415

.916

.715

.18

.79

.58

.05

3.8

53

.41.

61.

25

9.7

22

.37

52

.39

92

.351

0.6

25

0.6

56

0.5

94

0.3

44

0.3

75

0.3

132

.25

02

.23

50

.06

30

.04

92

.48

60

.36

0.9

59

.715

.916

.715

.18

.79

.58

.05

7.2

56

.81.

61.

26

3.0

2 ½

2.8

75

2.9

04

2.8

46

0.6

25

0.6

56

0.5

94

0.3

44

0.3

75

0.3

132

.72

02

.70

20

.07

80

.07

82

.98

73

.07

3.8

72

.315

.916

.715

.18

.79

.58

.06

9.1

68

.62

.02

.07

5.7

76

.1 m

m3

.00

03

.03

02

.97

00

.62

50

.65

60

.59

40

.34

40

.37

50

.313

2.8

45

2.8

27

0.0

78

0.0

78

3.1

07

6.1

77.

07

5.4

15.9

16.7

15.1

8.7

9.5

8.0

72

.37

1.8

2.0

2.0

78

.7

33

.50

03

.53

53

.46

90

.62

50

.65

60

.59

40

.34

40

.37

50

.313

3.3

44

3.3

26

0.0

78

0.0

78

3.6

08

8.9

89

.88

8.1

15.9

16.7

15.1

8.7

9.5

8.0

84

.98

4.5

2.0

2.0

91.

4

3 ½

4.0

00

4.0

40

3.9

69

0.6

25

0.6

56

0.5

94

0.3

44

0.3

75

0.3

133

.83

43

.814

0.0

83

0.0

78

4.1

010

1.6

102

.610

0.8

15.9

16.7

15.1

8.7

9.5

8.0

97.

49

6.9

2.2

2.0

104

.1

108

.0 m

m4

.25

04

.29

34

.219

0.6

25

0.6

56

0.5

94

0.3

44

0.3

75

0.3

134

.08

44

.06

40

.08

30

.07

84

.35

108

.010

9.0

107.

215

.916

.715

.18

.79

.58

.010

3.7

103

.22

.22

.011

0.5

† S

ee n

ote

on p

age 2

5.

Page 29: Victaulic I-100 Field Installation Handbook.pdf

Siz

e

Nom

inal

S

ize

inch

es o

r m

m

Act

ual

Pip

e O

utsi

de

Dia

met

er

inch

es/m

m

Pip

e O

utsi

de D

iam

eter

Dep

thW

all

Max

.

Flar

e D

ia.

Max

.M

in.

Bas

icM

ax.

Min

.B

asic

Max

.M

in.

Max

.M

in.

44

.50

04

.54

54

.46

90

.62

50

.65

60

.59

40

.34

40

.37

50

.313

4.3

34

4.3

140

.08

30

.07

84

.60

114

.311

5.4

113

.515

.916

.715

.18

.79

.58

.011

0.1

109

.62

.22

.011

6.8

4 ½

5.0

00

5.0

50

4.9

69

0.6

25

0.6

56

0.5

94

0.3

44

0.3

75

0.3

134

.83

44

.814

0.0

83

0.0

78

5.1

012

7.0

128

.312

6.2

15.9

16.7

15.1

8.7

9.5

8.0

122

.812

2.3

2.2

2.0

129

.5

133

.0 m

m5

.25

05

.30

35

.219

0.6

25

0.6

56

0.5

94

0.3

44

0.3

75

0.3

135

.08

45

.06

40

.08

30

.07

85

.35

133

.013

4.7

132

.615

.916

.715

.18

.79

.58

.012

9.1

128

.62

.22

.013

5.9

139

.7 m

m5

.50

05

.55

65

.46

90

.62

50

.65

60

.59

40

.34

40

.37

50

.313

5.3

34

5.3

140

.08

30

.07

85

.60

139

.714

1.1

138

.915

.916

.715

.18

.79

.58

.013

5.5

135

.02

.22

.014

2.2

55

.56

35

.619

5.5

32

0.6

25

0.6

56

0.5

94

0.3

44

0.3

75

0.3

135

.39

55

.37

30

.08

40

.07

85

.66

141.

314

2.7

140

.515

.916

.715

.18

.79

.58

.013

7.0

136

.52

.22

.014

3.8

152

.4 m

m6

.00

06

.05

65

.96

90

.62

50

.65

60

.59

40

.34

40

.37

50

.313

5.8

30

5.8

08

0.0

85

0.0

78

6.1

015

2.4

153

.815

1.6

15.9

16.7

15.1

8.7

9.5

8.0

148

.114

7.5

2.2

2.0

154

.9

159

.0 m

m6

.25

06

.313

6.2

190

.62

50

.65

60

.59

40

.34

40

.37

50

.313

6.0

32

6.0

02

0.1

09

0.1

09

6.3

515

9.0

160

.415

8.0

15.9

16.7

15.1

8.7

9.5

8.0

153

.215

2.5

2.8

2.8

161.

3

165

.1 m

m6

.50

06

.56

36

.46

90

.62

50

.65

60

.59

40

.34

40

.37

50

.313

6.3

30

6.3

08

0.0

85

0.0

78

6.6

016

5.1

166

.716

4.3

15.9

16.7

15.1

8.7

9.5

8.0

160

.816

0.2

2.2

2.8

167.

6

66

.62

56

.68

86

.59

40

.62

50

.65

60

.59

40

.34

40

.37

50

.313

6.4

55

6.4

33

0.0

85

0.0

78

6.7

316

8.3

169

.916

7.5

15.9

16.7

15.1

8.7

9.5

8.0

164

.016

3.4

2.2

2.8

170

.9

20

3.2

mm

8.0

00

8.0

63

7.9

69

0.7

50

0.7

81

0.7

190

.46

90

.50

00

.43

87.

816

7.7

91

0.0

92

0.1

09

8.1

72

03

.22

04

.82

02

.419

.119

.818

.311

.912

.711

.119

8.5

197.

92

.42

.82

07.

5

† S

ee n

ote

on p

age 2

5.

Page 30: Victaulic I-100 Field Installation Handbook.pdf

Siz

e

Nom

inal

S

ize

inch

es o

r m

m

Act

ual

Pip

e O

utsi

de

Dia

met

er

inch

es/m

m

Pip

e O

utsi

de D

iam

eter

Dep

thW

all

Max

.

Flar

e D

ia.

Max

.M

in.

Bas

icM

ax.

Min

.B

asic

Max

.M

in.

Max

.M

in.

216

.3 m

m8

.515

8.5

78

8.4

84

0.7

50

0.7

81

0.7

190

.46

90

.50

00

.43

88

.331

8.3

06

0.0

92

0.1

09

8.6

921

6.3

217.

921

5.5

19.1

19.8

18.3

11.9

12.7

11.1

211.

621

1.0

2.4

2.8

22

0.7

88

.62

58

.68

88

.59

40

.75

00

.78

10

.719

0.4

69

0.5

00

0.4

38

8.4

418

.416

0.0

92

0.1

09

8.8

021

9.1

22

0.7

218

.319

.119

.818

.311

.912

.711

.121

4.4

213

.82

.42

.82

23

.5

25

4.0

mm

10.0

00

10.0

63

9.9

69

0.7

50

0.7

81

0.7

190

.46

90

.50

00

.43

89

.812

9.7

85

0.0

94

0.1

34

10.1

72

54

.02

55

.62

53

.219

.119

.818

.311

.912

.711

.12

49

.22

48

.52

.43

.42

58

.3

26

7.4

mm

10.5

28

10.5

91

10.4

97

0.7

50

0.7

81

0.7

190

.46

90

.50

00

.43

810

.34

010

.313

0.0

94

0.1

34

10.7

02

67.

42

69

.02

66

.619

.119

.818

.311

.912

.711

.12

62

.62

62

.02

.43

.42

71.

8

1010

.75

010

.813

10.7

190

.75

00

.78

10

.719

0.4

69

0.5

00

0.4

38

10.5

62

10.5

35

0.0

94

0.1

34

10.9

22

73

.02

74.7

27

2.3

19.1

19.8

18.3

11.9

12.7

11.1

26

8.3

26

7.6

2.4

3.4

27

7.4

30

4.8

mm

12.0

00

12.0

63

11.9

69

0.7

50

0.7

81

0.7

190

.46

90

.50

00

.43

811

.78

111

.751

0.1

09

0.1

56

12.1

73

04

.83

06

.43

04

.019

.119

.818

.311

.912

.711

.12

99

.22

98

.52

.84

.03

09

.1

318

.5 m

m12

.53

912

.60

212

.50

80

.75

00

.78

10

.719

0.4

69

0.5

00

0.4

38

12.3

2112

.29

10

.10

90

.15

612

.71

318

.53

20

.131

7.7

19.1

19.8

18.3

11.9

12.7

11.1

313

.031

2.2

2.8

4.0

32

2.8

1212

.75

012

.813

12.7

190

.75

00

.78

10

.719

0.4

69

0.5

00

0.4

38

12.5

3112

.50

10

.10

90

.15

612

.92

32

3.9

32

5.5

32

3.1

19.1

19.8

18.3

11.9

12.7

11.1

318

.331

7.5

2.8

4.0

32

8.2

14 O

D *

14.0

00

14.0

63

13.9

69

0.9

38

0.9

69

0.9

07

0.4

69

0.5

00

0.4

38

13.7

81

13.7

510

.10

90

.15

614

.16

35

5.6

35

7.2

35

4.8

23

.82

4.6

23

.011

.912

.711

.13

50

.03

49

.32

.84

.03

59

.7

37

7.0

mm

14.8

43

14.9

37

14.8

110

.93

80

.96

90

.90

70

.46

90

.50

00

.43

814

.611

14.5

81

0.1

160

.17

715

.00

37

7.0

37

9.4

37

6.2

23

.82

4.6

23

.011

.912

.711

.13

71.

13

70

.42

.94

.53

81.

0

† S

ee n

ote

on p

age 2

5.

Page 31: Victaulic I-100 Field Installation Handbook.pdf

Siz

e

Nom

inal

S

ize

inch

es o

r m

m

Act

ual

Pip

e O

utsi

de

Dia

met

er

inch

es/m

m

Pip

e O

utsi

de D

iam

eter

Dep

thW

all

Max

.

Flar

e D

ia.

Max

.M

in.

Bas

icM

ax.

Min

.B

asic

Max

.M

in.

Max

.M

in.

15 O

D15

.00

015

.06

314

.96

90

.93

80

.96

90

.90

70

.46

90

.50

00

.43

814

.78

114

.751

0.1

09

0.1

65

15.1

63

81.

03

82

.63

80

.22

3.8

24

.62

3.0

11.9

12.7

11.1

37

5.4

374

.72

.84

.23

85

.1

16 O

D *

16.0

00

16.0

63

15.9

69

0.9

38

0.9

69

0.9

07

0.4

69

0.5

00

0.4

38

15.7

81

15.7

510

.10

90

.16

516

.16

40

6.4

40

8.0

40

5.6

23

.82

4.6

23

.011

.912

.711

.14

00

.84

00

.12

.84

.241

0.5

42

6 m

m16

.77

216

.86

616

.74

00

.93

80

.96

90

.90

70

.46

90

.50

00

.43

816

.514

16.4

79

0.1

29

0.1

77

16.9

34

26

42

8.4

42

5.2

23

.82

4.6

23

.011

.912

.711

.141

9.5

418

.63

.34

.54

30

.0

18 O

D *

18.0

00

18.0

63

17.9

69

1.0

00

1.0

310

.96

90

.46

90

.50

00

.43

817

.78

117

.751

0.1

09

0.1

65

18.1

64

57

45

8.8

45

6.4

25

.42

6.2

24

.611

.912

.711

.14

51.6

45

0.9

2.8

4.2

461

.3

48

0 m

m18

.89

818

.99

218

.86

71.

00

01.

031

0.9

69

0.4

69

0.5

00

0.4

38

18.6

26

18.5

91

0.1

36

0.2

36

19.0

64

80

48

2.4

47

9.2

25

.42

6.2

24

.611

.912

.711

.14

73

.14

72

.23

.56

.04

84

.1

20

OD

*

20

.00

02

0.0

63

19.9

69

1.0

00

1.0

310

.96

90

.46

90

.50

00

.43

819

.78

119

.751

0.1

09

0.1

88

20

.16

50

85

09

.65

07.

22

5.4

26

.22

4.6

11.9

12.7

11.1

50

2.4

50

1.7

2.8

4.8

512

.1

53

0 m

m2

0.8

66

20

.96

02

0.8

35

1.0

00

1.0

310

.96

90

.46

90

.50

00

.43

82

0.5

72

20

.53

70

.14

70

.23

621

.03

53

05

32

.45

29

.22

5.4

26

.22

4.6

11.9

12.7

11.1

52

2.5

521

.63

.76

.05

34

.2

22

OD

*2

2.0

00

22

.06

321

.96

91.

00

01.

031

0.9

69

0.5

00

0.5

310

.46

921

.65

621

.62

60

.17

20

.18

82

2.2

05

59

56

0.4

55

8.0

25

.42

6.2

24

.612

.713

.511

.95

50

.15

49

.34

.44

.85

63

.9

58

0 m

m2

2.8

35

22

.92

92

2.8

03

1.0

00

1.0

310

.96

90

.50

00

.531

0.4

69

22

.48

82

2.4

57

0.1

72

0.2

76

23

.03

58

05

82

.45

79

.22

5.4

26

.22

4.6

12.7

13.5

11.9

57

1.2

57

0.4

4.4

7.0

58

5.0

24

OD

*2

4.0

00

24

.06

32

3.9

69

1.0

00

1.0

310

.96

90

.50

00

.531

0.4

69

23

.65

62

3.6

26

0.1

72

0.2

182

4.2

061

061

1.2

60

8.8

25

.42

6.2

24

.612

.713

.511

.96

00

.96

00

.14

.45

.561

4.7

63

0 m

m2

4.8

03

24

.89

72

4.7

72

1.0

00

1.0

310

.96

90

.50

00

.531

0.4

69

24

.45

92

4.4

24

0.1

72

0.2

76

25

.00

63

06

32

.46

29

.22

5.4

26

.22

4.6

12.7

13.5

11.9

621

.36

20

.44

.47.

06

35

.0

† *

See n

ote

s on p

age 2

5.

Page 32: Victaulic I-100 Field Installation Handbook.pdf

Siz

e

Nom

inal

S

ize

inch

es

Act

ual

Pip

e O

utsi

de

Dia

met

er

inch

es/m

m

Pip

e O

utsi

de D

iam

eter

Dep

thW

all

Max

.

Flar

e D

ia.

Max

.M

in.

Bas

icM

ax.

Min

.B

asic

Max

.M

in.

Max

.M

in.

26

OD

*2

6.0

00

26

.09

32

5.9

69

1.7

50

1.7

81

1.6

87

0.6

25

0.6

56

0.5

94

25

.00

02

5.4

37

0.2

50

0.2

50

26

.20

66

06

62

.86

59

.64

4.5

45

.24

2.8

15.9

16.7

15.1

64

7.7

64

6.1

6.4

6.4

66

5.5

28

OD

*2

8.0

00

28

.09

32

7.9

69

1.7

50

1.7

81

1.6

87

0.6

25

0.6

56

0.5

94

27.

50

02

7.4

37

0.2

50

0.2

50

28

.20

711

713

.67

10.4

44

.54

5.2

42

.815

.916

.715

.16

98

.56

96

.96

.46

.47

16.3

30

OD

*3

0.0

00

30

.09

32

9.9

69

1.7

50

1.7

81

1.6

87

0.6

25

0.6

56

0.5

94

29

.50

02

9.4

37

0.2

50

0.2

50

30

.20

76

27

64

.47

61.2

44

.54

5.2

42

.815

.916

.715

.174

9.3

747.

76

.46

.47

67.

1

32

OD

*3

2.0

00

32

.09

331

.96

91.

75

01.

78

11.

68

70

.62

50

.65

60

.59

431

.50

031

.43

70

.25

00

.25

03

2.2

08

138

15.2

812

.04

4.5

45

.24

2.8

15.9

16.7

15.1

80

0.1

79

8.5

6.4

6.4

817

.9

36

OD

*3

6.0

00

36

.09

33

5.9

69

1.7

50

1.7

81

1.6

87

0.6

25

0.6

56

0.5

94

35

.50

03

5.4

37

0.2

50

0.2

50

36

.20

914

916

.89

13.6

44

.54

5.2

42

.815

.916

.715

.19

01.

79

00

.16

.46

.49

19.5

42

OD

*4

2.0

00

42

.09

341

.96

92

.00

02

.031

1.9

37

0.6

25

0.6

56

0.5

94

41.5

00

41.4

37

0.2

50

0.2

50

42

.20

106

710

69

.210

66

.05

0.8

51.6

49

.215

.916

.715

.110

54

.110

52

.56

.46

.410

71.

9

48

OD

*4

8.0

00

48

.09

34

7.9

69

2.0

00

2.0

311.

93

70

.62

50

.65

60

.59

44

7.5

00

47.

43

70

.25

00

.25

04

8.2

012

1912

21.6

1218

.45

0.8

51.6

49

.215

.916

.715

.112

06

.512

04

.96

.46

.412

24

.3

† C

oatin

gs

that

are

ap

plied

to t

he in

teri

or

surf

aces

of

Vic

tau

lic g

rooved

an

d p

lain

-en

d p

ipe c

ou

plin

gs

mu

st

not

exc

eed 0

.010

inch

/0.2

5 m

m.

Th

is in

clu

des

the b

olt p

ad m

atin

g s

urf

aces.

In

ad

ditio

n,

the c

oatin

g t

hic

kn

ess

ap

plied

to t

he g

ask

et-

sealin

g s

urf

ace a

nd

with

in t

he g

roove o

n t

he p

ipe e

xte

rior

mu

st

not

exc

eed

0.0

10

inch

/0.2

5 m

m..

* S

tan

dard

gro

ovin

g s

pecific

ation

s.

For

AG

S g

roovin

g s

pecific

ation

s in

th

ese s

izes,

refe

r to

pages

35 -

38

.

Page 33: Victaulic I-100 Field Installation Handbook.pdf

Siz

e

Nom

inal

S

ize

inch

es o

r m

m

Act

ual

Pip

e O

utsi

de

Dia

met

er

inch

es/m

m

Pip

e O

utsi

de D

iam

eter

Max

.M

in.

Bas

icM

ax.

Min

.B

asic

Max

.M

in.

Max

.M

in.

¾1.

05

01.

06

01.

04

00

.62

50

.65

60

.59

40

.313

0.3

44

0.2

82

0.9

38

0.9

23

0.0

56

0.1

132

6.9

26

.92

6.4

15.9

16.7

15.1

8.0

8.7

7.2

23

.82

3.4

1.5

2.9

11.

315

1.3

28

1.3

02

0.6

25

0.6

56

0.5

94

0.3

130

.34

40

.28

21.

190

1.17

50

.06

30

.13

33

3.7

33

.73

3.1

15.9

16.7

15.1

8.0

8.7

7.2

30

.22

9.9

1.6

3.4

1 ¼

1.6

60

1.6

76

1.6

44

0.6

25

0.6

56

0.5

94

0.3

130

.34

40

.28

21.

53

51.

52

00

.06

30

.14

04

2.4

42

.641

.815

.916

.715

.18

.08

.77.

23

9.0

38

.61.

63

.6

1 ½

1.9

00

1.9

191.

88

10

.62

50

.65

60

.59

40

.313

0.3

44

0.2

82

1.7

75

1.7

60

0.0

63

0.1

45

48

.34

8.7

47.

815

.916

.715

.18

.08

.77.

24

5.1

44

.71.

63

.7

22

.37

52

.39

92

.351

0.6

25

0.6

56

0.5

94

0.3

130

.34

40

.28

22

.25

02

.23

50

.06

30

.15

46

0.3

60

.95

9.7

15.9

16.7

15.1

8.0

8.7

7.2

57.

25

6.8

1.6

3.9

2 ½

2.8

75

2.9

04

2.8

46

0.6

25

0.6

56

0.5

94

0.3

130

.34

40

.28

22

.72

02

.70

20

.07

80

.18

87

3.0

73

.87

2.3

15.9

16.7

15.1

8.0

8.7

7.2

69

.16

8.6

2.0

4.8

76

.1 m

m3

.00

03

.03

02

.97

00

.62

50

.65

60

.59

40

.313

0.3

44

0.2

82

2.8

45

2.8

27

0.0

78

0.1

88

76

.17

7.0

75

.415

.916

.715

.18

.08

.77.

27

2.3

71.

82

.04

.8

33

.50

03

.53

53

.46

90

.62

50

.65

60

.59

40

.313

0.3

44

0.2

82

3.3

44

3.3

26

0.0

78

0.1

88

88

.98

9.8

88

.115

.916

.715

.18

.08

.77.

28

4.9

84

.52

.04

.8

3 ½

4.0

00

4.0

40

3.9

69

0.6

25

0.6

56

0.5

94

0.3

130

.34

40

.28

23

.83

43

.814

0.0

83

0.1

88

101.

610

2.6

100

.815

.916

.715

.18

.08

.77.

29

7.4

96

.92

.24

.8

108

.0 m

m4

.25

04

.29

34

.219

0.6

25

0.6

56

0.5

94

0.3

75

0.4

06

0.3

44

4.0

84

4.0

64

0.0

83

0.2

03

108

.010

9.0

107.

215

.916

.715

.19

.510

.38

.710

3.7

103

.22

.25

.2

† S

ee n

ote

on p

age 3

0.

Page 34: Victaulic I-100 Field Installation Handbook.pdf

Siz

e

Nom

inal

Siz

e in

ches

Act

ual

Pip

e O

utsi

de

Dia

met

er

inch

es/m

m

Pip

e O

utsi

de D

iam

eter

Max

.M

in.

Bas

icM

ax.

Min

.B

asic

Max

.M

in.

Max

.M

in.

44

.50

04

.54

54

.46

90

.62

50

.65

60

.59

40

.37

50

.40

60

.34

44

.33

44

.314

0.0

83

0.2

03

114

.311

5.4

113

.515

.916

.715

.19

.510

.38

.711

0.1

109

.62

.25

.2

4 ½

5.0

00

5.0

50

4.9

69

0.6

25

0.6

56

0.5

94

0.3

75

0.4

06

0.3

44

4.8

34

4.8

140

.08

30

.20

312

7.0

128

.312

6.2

15.9

16.7

15.1

9.5

10.3

8.7

122

.812

2.3

2.2

5.2

5 ¼

OD

5.2

50

5.3

03

5.2

190

.62

50

.65

60

.59

40

.37

50

.40

60

.34

45

.08

45

.06

40

.08

30

.20

313

3.0

134

.713

2.6

15..9

16.7

15.1

9.5

10.3

8.7

129

.112

8.6

2.2

5.2

5 ½

OD

5.5

00

5.5

56

5.4

69

0.6

25

0.6

56

0.5

94

0.3

75

0.4

06

0.3

44

5.3

34

5.3

140

.08

30

.20

313

9.7

141.

113

8.9

15.9

16.7

15.1

9.5

10.3

8.7

135

.513

5.0

2.2

5.2

55

.56

35

.619

5.5

32

0.6

25

0.6

56

0.5

94

0.3

75

0.4

06

0.3

44

5.3

95

5.3

73

0.0

84

0.2

03

141.

314

2.7

140

.515

.916

.715

.19

.510

.38

.713

7.0

136

.52

.25

.2

6 O

D6

.00

06

.05

65

.96

90

.62

50

.65

60

.59

40

.37

50

.40

60

.34

45

.83

05

.80

80

.08

50

.219

152

.415

3.8

151.

615

.916

.715

.19

.510

.38

.714

8.1

147.

52

.25

.6

6 ¼

OD

6.2

50

6.3

136

.219

0.6

25

0.6

56

0.5

94

0.3

75

0.4

06

0.3

44

6.0

32

6.0

02

0.1

09

0.2

49

159

.016

0.4

158

.015

.916

.715

.19

.510

.38

.715

3.2

152

.52

.86

.3

6 ½

OD

6.5

00

6.5

63

6.4

69

0.6

25

0.6

56

0.5

94

0.3

75

0.4

06

0.3

44

6.3

30

6.3

08

0.0

85

0.2

1916

5.1

166

.716

4.3

15.9

16.7

15.1

9.5

10.3

8.7

160

.816

0.2

2.2

5.6

66

.62

56

.68

86

.59

40

.62

50

.65

60

.59

40

.37

50

.40

60

.34

46

.45

56

.43

30

.08

50

.219

168

.316

9.9

167.

515

.916

.715

.19

.510

.38

.716

4.0

163

.42

.25

.6

8 O

D8

.00

08

.06

37.

96

90

.75

00

.78

10

.719

0.4

38

0.4

69

0.4

07

7.8

167.

79

10

.09

20

.23

82

03

.22

04

.82

02

.419

.119

.818

.311

.111

.910

.319

8.5

197.

92

.46

.1

† S

ee n

ote

on p

age 3

0.

Page 35: Victaulic I-100 Field Installation Handbook.pdf

Siz

e

Nom

inal

S

ize

inch

es o

r m

m

Act

ual

Pip

e O

utsi

de

Dia

met

er

inch

es/m

m

Pip

e O

utsi

de D

iam

eter

Max

.M

in.

Bas

icM

ax.

Min

.B

asic

Max

.M

in.

Max

.M

in.

216

.3 m

m8

.515

8.5

78

8.4

84

0.7

50

0.7

81

0.7

190

.43

80

.46

90

.40

78

.331

8.3

06

0.0

92

0.2

38

216

.321

7.9

215

.519

.119

.818

.311

.111

.910

.321

1.6

211.

02

.46

.1

88

.62

58

.68

88

.59

40

.75

00

.78

10

.719

0.4

38

0.4

69

0.4

07

8.4

418

.416

0.0

92

0.2

38

219

.12

20

.721

8.3

19.1

19.8

18.3

11.1

11.9

10.3

214

.421

3.8

2.4

6.1

10 O

D10

.00

010

.06

39

.96

90

.75

00

.78

10

.719

0.5

00

0.5

310

.46

99

.812

9.7

85

0.0

94

0.2

50

25

4.0

25

5.6

25

3.2

19.1

19.8

18.3

12.7

13.5

11.9

24

9.2

24

8.5

2.4

6.4

26

7.4

mm

10.5

28

10.5

91

10.4

97

0.7

50

0.7

81

0.7

190

.50

00

.531

0.4

69

10.3

40

10.3

130

.09

40

.25

02

67.

42

69

.02

66

.619

.119

.818

.312

.713

.511

.92

62

.62

62

.02

.46

.4

1010

.75

010

.813

10.7

190

.75

00

.78

10

.719

0.5

00

0.5

310

.46

910

.56

210

.53

50

.09

40

.25

02

73

.02

74.7

27

2.3

19.1

19.8

18.3

12.7

13.5

11.9

26

8.3

26

7.6

2.4

6.4

30

4.8

mm

12.0

00

12.0

63

11.9

69

0.7

50

0.7

81

0.7

190

.50

00

.531

0.4

69

11.7

81

11.7

510

.10

90

.27

93

04

.83

06

.43

04

.019

.119

.818

.312

.713

.511

.92

99

.22

98

.52

.87.

1

318

.5 m

m12

.53

912

.60

212

.50

80

.75

00

.78

10

.719

0.5

00

0.5

310

.46

912

.321

12.2

91

0.1

09

0.2

79

318

.53

20

.131

7.7

19.1

19.8

18.3

12.7

13.5

11..9

313

.031

2.2

2.8

7.1

1212

.75

012

.813

12.7

190

.75

00

.78

10

.719

0.5

00

0.5

310

.46

912

.531

12.5

01

0.1

09

0.2

79

32

3.9

32

5.5

32

3.1

19.1

19.8

18.3

12.7

13.5

11.9

318

.331

7.5

2.8

7.1

14 O

D14

.00

014

.06

313

.96

90

.93

80

.96

90

.90

70

.50

00

.531

0.4

69

13.7

81

13.7

510

.10

90

.28

13

55

.63

57.

23

54

.82

3.8

24

.62

3.0

12.7

13.5

11.9

35

0.0

34

9.3

2.8

7.1

37

7.0

mm

14.8

43

14.9

37

14.8

110

.93

80

.96

90

.90

70

.50

00

.531

0.4

69

14.6

1114

.58

10

.116

0.3

153

77.

03

79

.43

76

.22

3.8

24

.62

3.0

12.7

13.5

11.9

37

1.1

37

0.4

2.9

8.0

† S

ee n

ote

on p

age 3

0.

Page 36: Victaulic I-100 Field Installation Handbook.pdf

Siz

e

Nom

inal

S

ize

inch

es o

r m

m

Act

ual

Pip

e O

utsi

de

Dia

met

er

inch

es/m

m

Pip

e O

utsi

de D

iam

eter

Max

.M

in.

Bas

icM

ax.

Min

.B

asic

Max

.M

in.

Max

.M

in.

15 O

D15

.00

015

.06

314

.96

90

.93

80

.96

90

.90

70

.50

00

.531

0.4

69

14.7

81

14.7

510

.10

90

.312

38

1.0

38

2.6

38

0.2

23

.82

4.6

23

.012

.713

.511

.93

75

.43

74.7

2.8

7.9

16 O

D16

.00

016

.06

315

.96

90

.93

80

.96

90

.90

70

.50

00

.531

0.4

69

15.7

81

15.7

510

.10

90

.312

40

6.4

40

8.0

40

5.6

23

.82

4.6

23

.012

.713

.511

.94

00

.84

00

.12

.87.

9

42

6.0

mm

16.7

72

16.8

66

16.7

40

0.9

38

0.9

69

0.9

07

0.5

00

0.5

310

.46

916

.514

16.4

79

0.1

29

0.3

35

42

64

28

.44

25

.22

3.8

24

.62

3.0

12.7

13.5

11.9

419

.541

8.6

3.3

8.5

18 O

D18

.00

018

.06

317

.96

91.

00

01.

031

0.9

69

0.5

00

0.5

310

.46

917

.78

117

.751

0.1

09

0.3

124

57

45

8.8

45

6.4

25

.42

6.2

24

.612

.713

.511

.94

51.6

45

0.9

2.8

7.9

20

OD

20

.00

02

0.0

63

19.9

69

1.0

00

1.0

310

.96

90

.50

00

.531

0.4

69

19.7

81

19.7

510

.10

90

.312

50

85

09

.65

07.

22

5.4

26

.22

4.6

12.7

13.5

11.9

50

2.4

50

1.7

2.8

7.9

22

OD

22

.00

02

2.0

63

21.9

69

1.0

00

1.0

310

.96

90

.56

30

.59

40

.53

221

.65

621

.62

60

.17

20

.37

55

59

.05

60

.45

58

.02

5.4

26

.22

4.6

14.3

15.1

13.5

55

0.1

54

9.3

4.4

9.5

24

OD

24

.00

02

4.0

63

23

.96

91.

00

01.

031

0.9

69

0.5

63

0.5

94

0.5

32

23

.65

62

3.6

26

0.1

72

0.3

75

610

611.

26

08

.82

5.4

26

.22

4.6

14.3

15.1

13.5

60

0.9

60

0.1

4.4

9.5

26

OD

26

.00

02

6.0

93

25

.96

91.

75

01.

78

11.

68

70

.62

50

.65

60

.59

42

5.5

00

25

.43

70

.25

00

.62

56

60

66

2.8

65

9.6

44

.54

5.2

42

.815

.916

.715

.16

47.

76

46

.16

.415

.9

28

OD

28

.00

02

8.0

93

27.

96

91.

75

01.

78

11.

68

70

.62

50

.65

60

.59

42

7.5

00

27.

43

70

.25

00

.62

57

117

13.6

710

.44

4.5

45

.24

2.8

15.9

16.7

15.1

69

8.5

69

6.9

6.4

15.9

28

ID

28

.87

52

8.9

38

28

.84

41.

00

01.

031

0.9

69

0.6

25

0.6

56

0.5

94

28

.531

28

.50

10

.17

20

.43

77

33

.47

35

.07

32

.62

5.4

26

.22

4.6

15.9

16.7

15.1

72

4.7

72

3.9

4.4

11.1

† S

ee n

ote

on p

age 3

0.

Page 37: Victaulic I-100 Field Installation Handbook.pdf

I-100_30

Siz

e

Nom

inal

Siz

e in

ches

Act

ual

Pip

e O

utsi

de

Dia

met

er

inch

es/m

m

Pip

e O

utsi

de D

iam

eter

Max

.M

in.

Bas

icM

ax.

Min

.B

asic

Max

.M

in.

Max

.M

in.

30

OD

30

.00

03

0.0

93

29

.96

91.

75

01.

78

11.

68

70

.62

50

.65

60

.59

42

9.5

00

29

.43

70

.25

00

.62

57

62

76

4.4

761

.24

4.5

45

.24

2.8

15.9

16.7

15.1

749

.374

7.7

6.4

15.9

30

ID

31.0

00

31.0

63

30

.96

91.

25

01.

28

11.

219

0.6

25

0.6

56

0.5

94

30

.59

43

0.5

64

0.2

03

0.5

00

78

7.4

78

9.0

78

6.6

25

.43

2.5

31.0

15.9

16.7

15.1

77

7.1

77

6.3

5.2

12.7

32

OD

32

.00

03

2.0

93

31.9

69

1.7

50

1.7

81

1.6

87

0.6

25

0.6

56

0.5

94

31.5

00

31.4

37

0.2

50

0.6

25

813

815

.28

12.0

44

.54

5.2

42

.815

.916

.715

.18

00

.17

98

.56

.415

.9

36

OD

36

.00

03

6.0

93

35

.96

91.

75

01.

78

11.

68

70

.62

50

.65

60

.59

43

5.5

00

35

.43

70

.25

00

.62

59

149

16.8

913

.64

4.5

45

.24

2.8

15.9

16.7

15.1

90

1.7

90

0.1

6.4

15.9

42

OD

42

.00

04

2.0

93

41.9

69

2.0

00

2.0

311.

93

70

.62

50

.65

60

.59

441

.50

041

.43

70

.25

00

.62

510

67

106

9.2

106

6.0

50

.851

.64

9.2

15.9

16.7

15.1

105

4.1

105

2.5

6.4

15.9

48

OD

48

.00

04

8.0

93

47.

96

92

.00

02

.031

1.9

37

0.6

25

0.6

56

0.5

94

47.

50

04

7.4

37

0.2

50

0.6

25

1219

1221

.612

18.4

50

.851

.64

9.2

15.9

16.7

15.1

120

6.5

120

4.9

6.4

15.9

† C

oatin

gs

ap

plied

to t

he in

teri

or

surf

aces,

inclu

din

g b

olt p

ad

matin

g s

urf

aces,

mu

st

not

exc

eed 0

.010

inch

/0.3

mm

. In

ad

ditio

n,

the c

oatin

g t

hic

kn

ess

ap

plied

to t

he g

ask

et-

sealin

g s

urf

ace a

nd

w

ith

in t

he g

roove o

n t

he p

ipe e

xte

rior

mu

st

not

exc

eed 0

.010 in

ch

/0.3

mm

.

Page 38: Victaulic I-100 Field Installation Handbook.pdf

I-100_31

Siz

e

Nom

inal

Siz

e in

ches

Act

ual

Pip

e O

utsi

de

Dia

met

er

inch

es/m

m

Pip

e O

utsi

de D

iam

eter

Dep

thM

in.

Flar

e D

ia.

Max

.M

in.

Max

.M

in.

Max

.M

in.

Max

.M

in.

22

.37

52

.39

92

.351

0.5

72

0.5

52

0.2

65

0.2

50

2.2

50

2.2

35

0.0

63

0.1

54

2.4

80

60

.36

0.9

59

.714

.514

.06

.76

.45

7.2

56

.81.

63

.96

3.0

2 ½

2.8

75

2.9

04

2.8

46

0.5

72

0.5

52

0.2

65

0.2

50

2.7

20

2.7

02

0.0

78

0.2

03

2.9

80

73

.07

3.8

72

.314

.514

.06

.76

.46

9.1

68

.62

.05

.27

5.7

33

.50

03

.53

53

.46

90

.57

20

.55

20

.26

50

.25

03

.34

43

.32

60

.08

30

.216

3.6

00

88

.98

9.8

88

.114

.514

.06

.76

.48

4.9

84

.52

.15

.59

1.4

44

.50

04

.54

54

.46

90

.610

0.5

90

0.3

20

0.3

00

4.3

34

4.3

140

.08

30

.23

74

.60

011

4.3

115

.411

3.5

15.5

15.0

8.1

7.6

110

.110

9.6

2.1

6.0

116

.8

66

.62

56

.68

86

.59

40

.610

0.5

90

0.3

20

0.3

00

6.4

55

6.4

33

0.0

85

0.2

80

6.7

30

168

.316

9.9

167.

515

.515

.08

.17.

616

4.0

163

.42

.27.

117

0.9

88

.62

58

.68

88

.59

40

.719

0.6

99

0.4

100

.39

08

.441

8.4

160

.09

20

.32

28

.80

021

9.1

22

0.7

218

.318

.317

.810

.49

.921

4.4

213

.82

.38

.22

23

.5

1010

.75

010

.813

10.7

190

.719

0.6

99

0.4

100

.39

010

.56

210

.53

50

.09

40

.36

510

.92

02

73

.02

74.7

27

2.3

18.3

17.8

10.4

9.9

26

8.3

26

7.6

2.4

9.3

27

7.4

1212

.75

012

.813

12.7

190

.719

0.6

99

0.4

100

.39

012

.531

12.5

01

0.1

09

0.3

75

12.9

20

32

3.9

32

5.5

32

3.1

18.3

17.8

10.4

9.9

318

.331

7.5

2.8

9.5

32

8.2

† C

oatin

gs

ap

plied

to t

he in

teri

or

surf

aces,

inclu

din

g b

olt p

ad

matin

g s

urf

aces,

mu

st

not

exc

eed 0

.010

inch

/0.3

mm

. In

ad

ditio

n,

the c

oatin

g t

hic

kn

ess

ap

plied

to t

he g

ask

et-

sealin

g s

urf

ace a

nd

w

ith

in t

he g

roove o

n t

he p

ipe e

xte

rior

mu

st

not

exc

eed 0

.010 in

ch

/0.3

mm

.

Page 39: Victaulic I-100 Field Installation Handbook.pdf

Siz

e

Nom

inal

Siz

e in

ches

Act

ual

Pip

e O

utsi

de

Dia

met

er

inch

es/m

m

Pip

e O

utsi

de D

iam

eter

Dep

th

Min

.

Wal

l M

ax.

Min

.B

asic

Max

.M

in.

Bas

icM

ax.

Min

.M

ax.

Min

.

22

.37

52

.39

92

.351

0.5

62

0.5

72

0.5

52

0.2

55

0.2

65

0.2

50

2.2

50

2.2

35

0.0

63

0.1

54

60

.36

0.9

59

.714

.314

.514

.06

.56

.76

.45

7.2

56

.81.

63

.9

2 ½

2.8

75

2.9

04

2.8

46

0.5

62

0.5

72

0.5

52

0.2

55

0.2

65

0.2

50

2.7

20

2.7

02

0.0

78

0.2

03

73

.07

3.8

72

.314

.314

.514

.06

.56

.76

.46

9.1

68

.62

.05

.2

33

.50

03

.53

53

.46

90

.56

20

.57

20

.55

20

.25

50

.26

50

.25

03

.34

43

.32

60

.07

80

.216

88

.98

9.8

88

.114

.314

.514

.06

.56

.76

.48

4.9

84

.52

.05

.5

44

.50

04

.54

54

.46

90

.60

50

.62

00

.59

00

.30

50

.315

0.3

00

4.3

34

4.3

140

.08

30

.23

711

4.3

115

.411

3.5

15.4

15.7

15.0

7.7

8.0

7.6

110

.110

9.6

2.1

6.0

66

.62

56

.68

86

.59

40

.60

50

.62

00

.59

00

.30

50

.315

0.3

00

6.4

55

6.4

33

0.0

85

0.2

80

168

.316

9.9

167.

515

.415

.715

.07.

78

.07.

616

4.0

163

.42

.27.

1

88

.62

58

.68

88

.59

40

.714

0.7

29

0.6

99

0.4

00

0.4

100

.39

08

.441

8.4

160

.09

20

.32

221

9.1

22

0.7

218

.318

.118

.517

.810

.210

.49

.921

4.4

213

.82

.38

.2

1010

.75

010

.813

10.7

190

.714

0.7

29

0.6

99

0.4

00

0.4

100

.39

010

.56

210

.53

50

.09

40

.36

52

73

.02

74.7

27

2.3

18.1

18.5

17.8

10.2

10.4

9.9

26

8.3

26

7.6

2.4

9.3

1212

.75

012

.813

12.7

190

.714

0.7

29

0.6

99

0.4

00

0.4

100

.39

012

.531

12.5

01

0.1

09

0.3

75

32

3.9

32

5.5

32

3.1

18.1

18.5

17.8

10.2

10.4

9.9

318

.331

7.5

2.8

9.5

† C

oatin

gs

ap

plied

to t

he in

teri

or

surf

aces,

inclu

din

g b

olt p

ad

matin

g s

urf

aces,

mu

st

not

exc

eed 0

.010

inch

/0.3

mm

. In

ad

ditio

n,

the c

oatin

g t

hic

kn

ess

ap

plied

to t

he g

ask

et-

sealin

g s

urf

ace a

nd

w

ith

in t

he g

roove o

n t

he p

ipe e

xte

rior

mu

st

not

exc

eed 0

.010 in

ch

/0.3

mm

.

Page 40: Victaulic I-100 Field Installation Handbook.pdf

I-100_33

Siz

e

Nom

inal

Siz

e in

ches

Act

ual

Pip

e O

utsi

de

Dia

met

er

inch

es/m

m

Pip

e O

utsi

de D

iam

eter

Max

.M

in.

Max

.M

in.

Bas

icM

ax.

Min

.M

ax.

Min

.

¾1.

05

01.

06

21.

03

80

.65

60

.59

40

.312

0.3

43

0.2

81

0.9

38

0.9

23

0.0

56

26

.92

7.0

26

.416

.715

.17.

98

.77.

12

3.8

23

.41.

4

11.

315

1.3

27

1.3

03

0.6

56

0.5

94

0.3

120

.34

30

.28

11.

190

1.17

50

.06

23

3.7

33

.73

3.1

16.7

15.1

7.9

8.7

7.1

30

.22

9.8

1.6

1 ¼

1.6

60

1.6

72

1.6

48

0.6

56

0.5

94

0.3

120

.34

30

.28

11.

53

51.

52

00

.06

24

2.4

42

.541

.916

.715

.17.

98

.77.

13

9.0

38

.61.

6

1 ½

1.9

00

1.9

121.

88

80

.65

60

.59

40

.312

0.3

43

0.2

81

1.7

75

1.7

60

0.0

62

48

.34

8.6

48

.016

.715

.17.

98

.77.

14

5.1

44

.71.

6

22

.37

52

.38

72

.36

30

.65

60

.59

40

.312

0.3

43

0.2

81

2.2

50

2.2

35

0.0

62

60

.36

0.6

60

.016

.715

.17.

98

.77.

15

7.2

56

.81.

6

2 ½

2.8

75

2.8

87

2.8

63

0.6

56

0.5

94

0.3

120

.34

30

.28

12

.72

02

.70

20

.07

87

3.0

73

.37

2.7

16.7

15.1

7.9

8.7

7.1

69

.16

8.6

2.0

33

.50

03

.515

3.4

85

0.6

56

0.5

94

0.3

120

.34

30

.28

13

.34

43

.32

60

.07

88

8.9

89

.38

8.5

16.7

15.1

7.9

8.7

7.1

84

.98

4.5

2.0

44

.50

04

.52

04

.48

00

.65

60

.59

40

.37

50

.40

60

.34

44

.33

44

.314

0.0

83

114

.311

4.8

113

.816

.715

.19

.510

.38

.711

0.1

109

.62

.1

† S

ee n

ote

on p

age 3

4

R

igid

, an

gle

-bolt-p

ad c

oup

lings

are

not

recom

men

ded f

or

use w

ith P

VC

pla

stic p

ipe.

AB

D

OD

C

B

0.0

78

"R

ad

ius

Page 41: Victaulic I-100 Field Installation Handbook.pdf

Siz

e

Nom

inal

Siz

e in

ches

Act

ual

Pip

e O

utsi

de

Dia

met

er

inch

es/m

m

Pip

e O

utsi

de D

iam

eter

Max

.M

in.

Max

.M

in.

Bas

icM

ax.

Min

.M

ax.

Min

.

66

.62

56

.66

06

.59

00

.65

60

.59

40

.37

50

.40

60

.34

46

.45

56

.43

30

.08

516

8.3

169

.216

7.4

16.7

15.1

9.5

10.3

8.7

164

.016

3.4

2.2

88

.62

58

.68

78

.59

40

.78

10

.719

0.4

37

0.4

68

0.4

06

8.4

418

.416

0.0

92

219

.12

20

.621

8.3

19.8

18.3

11.1

11.9

10.3

214

.421

3.8

2.3

1010

.75

010

.812

10.7

190

.78

10

.719

0.5

00

0.5

310

.46

910

.56

210

.53

50

.09

42

73

.02

74.6

27

2.3

19.8

18.3

12.7

13.5

11.9

26

8.3

26

7.6

2.4

1212

.75

012

.812

12.7

190

.78

10

.719

0.5

00

0.5

310

.46

912

.531

12.5

01

0.1

09

32

3.9

32

5.4

32

3.1

19.8

18.3

12.7

13.5

11.9

318

.331

7.5

2.8

1414

.00

014

.06

213

.96

90

.96

90

.90

70

.50

00

.531

0.4

69

13.7

81

13.7

510

.10

93

55

.63

57.

23

54

.82

4.6

23

.012

.713

.511

.93

50

.03

49

.32

.8

1616

.00

016

.06

215

.96

90

.96

90

.90

70

.50

00

.531

0.4

69

15.7

81

15.7

510

.10

94

06

.44

08

.04

05

.62

4.6

23

.012

.713

.511

.94

00

.84

00

.12

.8

† P

VC

pla

stic p

ipe is

based u

pon m

odifie

d P

VC

pla

stic p

ipe t

hat

con

form

s to

AS

TM

D-1

78

5-7

0;

Typ

e 1

, G

rad

e 1

- P

VC

11

20

; or

Gra

de 1

1 -

PV

C 1

22

0 a

t op

era

tin

g t

em

pera

ture

s of

75

˚ F/2

4˚ C

m

axim

um

. For

oth

er

typ

es

of

PV

C p

ipe a

nd

oth

er

op

era

tin

g t

em

pera

ture

s,

con

tact

Vic

tau

lic.

Rig

id,

an

gle

-bolt-p

ad c

oup

lings

are

not

recom

men

ded f

or

use w

ith P

VC

pla

stic p

ipe.

AB

D

OD

C

B

0.0

78

"R

ad

ius

Page 42: Victaulic I-100 Field Installation Handbook.pdf

I-100_35

personal injury and/or property damage.

NOTICE

length by approximately 1⁄8

A

F OD C

B

– The average pipe outside diameter must not vary from the

specifications listed in the tables on the following pages (API 5L end tolerance).

Maximum allowable pipe ovality should not vary by more than 1%. Greater variations

between the major and minor diameters will result in difficult coupling assembly.

1⁄8 This is measured from the true square

line. Any internal and external weld beads or seams must be ground

flush to the pipe surface. The inside diameter of the pipe end must

be cleaned to remove coarse scale, dirt, and other foreign material

that might interfere with or damage grooving rolls. The front edge of

the pipe end shall be uniform with no concave/convex surface features that will cause

improper grooving roll tracking and result in difficulties during coupling assembly.

The “A” dimension, or the distance from the pipe end to the groove,

identifies the gasket seating area. This area must be free from indentations, projections

(including weld seams), and roll marks from the pipe end to the groove to ensure a leak-

tight seal. All foreign material, such as loose paint, scale, oil, grease, chips, rust, and dirt

must be removed.

The “B” dimension, or groove width, controls expansion, contraction,

and angular deflection of flexible couplings by the distance it is located from the pipe

and its width in relation to the coupling housings’ “key” width. The bottom of the groove

must be free of all foreign material, such as dirt, chips, rust, and scale that may interfere

with proper coupling assembly. The corners at the bottom of the groove must be

radiused R .094/R 2.39. The Groove Width “B” dimension will be achieved with properly

maintained Victaulic tools that are equipped with Victaulic AGS (RW or RWQ) roll sets

for carbon steel and standard-wall stainless steel pipe or Victaulic AGS (RWX or RWQX)

specifically for light-wall stainless steel pipe.

"S" Max.

Illustration is exaggerated for clarity

Page 43: Victaulic I-100 Field Installation Handbook.pdf

I-100_36

The “C” dimension is the average diameter at the base of the groove.

This dimension must be within the diameter’s tolerance and concentric with the

OD for proper coupling fit. The groove must be of uniform depth for the entire pipe

circumference. Victaulic RW roll sets must be used for carbon steel and standard-wall

stainless steel pipe. Victaulic RWX roll sets must be used for light-wall stainless steel

pipe.

The “D” dimension is the normal depth of the groove and is a reference

for a “trial groove” only. Variations in pipe OD affect this dimension and it must be

altered, if necessary, to keep the “C” dimension within tolerance. The groove diameter

must conform to the “C” dimension described above.

Maximum allowable pipe-end flare diameter is

measured at the extreme pipe-end diameter. This applies to average (pi tape) and

single-point readings.

The minimum nominal wall thickness is the lightest

grade of pipe that is suitable for cut or roll grooving. Pipe that is less than the minimum

nominal wall thickness for cut grooving may be suitable for roll grooving or adapted for

Victaulic AGS couplings by using AGS Vic-Ring® Adapters. AGS Vic-Ring Adapters can be

used in the following situations (contact Victaulic for details):

14-inch/355.6-mm minimum nominal wall thickness is 0.220 inch/5.6 mm

16 – 24-inch/406.4 – 610-mm minimum nominal wall thickness is 0.250 inch/6.3 mm

14-inch/355.6-mm minimum nominal wall thickness is 0.315 inch/8.0 mm

16-inch/406.4-mm minimum nominal wall thickness is 0.346 inch/8.8 mm

18 – 36-inch/457 – 914-mm minimum nominal wall thickness is 0.375 inch/9.5 mm

38 – 72-inch/965 – 1829-mm minimum nominal wall thickness is 0.500 inch/12.7 mm

For 14 – 72-inch/355.6 – 1829-mm carbon steel pipe being grooved to AGS

specifications the maximum ratings are limited to pipe that does not exceed the yield

strength of API-5L Grade “B”, ASTM Grade “B”, 150 Brinell Hardness Number (BHN)

maximum.

14-inch/355.6-mm minimum nominal wall thickness is 0.156 inch/4.0 mm

16 – 18-inch/406.4 – 457-mm minimum nominal wall thickness is 0.165 inch/4.2 mm

20 – 22-inch/508 – 559-mm minimum nominal wall thickness is 0.188 inch/4.8 mm

24-inch/610-mm minimum nominal wall thickness is 0.218 inch/5.5 mm

NOTICE

Page 44: Victaulic I-100 Field Installation Handbook.pdf

Nom

inal

N

PS

/B

asic

M

etri

c P

ipe

Siz

e

Act

ual

Pip

e O

utsi

de D

iam

eter

in

ches

/mm

in

ches

/mm

Dim

ensi

ons

inch

es/m

mC

arbo

n S

teel

and

Sta

ndar

d W

eigh

t Sta

inle

ss S

teel

Sta

inle

ss S

teel

S

ched

ules

5

S/1

0S

/10

Ext

ra-

Str

ong

Car

bon

Ste

elStd

.-

Wal

l Ste

el

Ligh

t-W

all

Car

bon

Ste

el

Ligh

t-W

all

Sta

inle

ss

Ste

el

Max

imum

Fl

are

Dia

met

er

Max

.M

in.

Max

.M

in.

Bas

icM

ax.

Min

.B

asic

Max

.M

in.

Max

.M

in.

1414

.09

413

.96

914

.09

413

.96

9—

0.3

150

.22

00

.15

61.

50

01.

531

1.4

37

0.4

55

0.4

60

0.4

50

13.5

00

13.4

55

14.2

33

55

.63

58

.03

54

.83

58

.03

54

.88

.05

.64

.03

8.1

38

.93

6.5

11.6

11.7

11.4

34

2.9

341

.83

61.4

1616

.09

415

.96

916

.09

415

.96

9—

0.3

46

0.2

50

0.1

65

1.5

00

1.5

311.

43

70

.45

50

.46

00

.45

015

.50

015

.45

516

.23

40

6.4

40

8.8

40

5.6

40

8.8

40

5.6

8.8

6.4

4.2

38

.13

8.9

36

.511

.611

.711

.43

93

.73

92

.641

2.2

1818

.09

417

.96

918

.09

417

.96

9—

0.3

75

0.2

50

0.1

65

1.5

00

1.5

311.

43

70

.45

50

.46

00

.45

017

.50

017

.45

518

.23

45

74

59

.64

56

.44

59

.64

56

.49

.56

.44

.23

8.1

38

.93

6.5

11.6

11.7

11.4

44

4.5

44

3.4

46

3.0

20

20

.09

419

.96

92

0.1

25

19.9

69

—0

.37

50

.25

00

.18

81.

50

01.

531

1.4

37

0.4

55

0.4

60

0.4

50

19.5

00

19.4

55

20

.23

50

8.0

510

.45

07.

251

1.2

50

7.2

9.5

6.4

4.8

38

.13

8.9

36

.511

.611

.711

.44

95

.34

94

.251

3.8

22

22

.09

421

.96

92

2.1

25

21.9

69

—0

.37

50

.25

00

.18

81.

50

01.

531

1.4

37

0.4

55

0.4

60

0.4

50

21.5

00

21.4

55

22

.23

55

95

61.2

55

8.0

56

2.0

55

8.0

9.5

6.4

4.8

38

.13

8.9

36

.511

.611

.711

.45

46

.15

45

.05

64

.6

24

24

.09

42

3.9

69

24

.12

52

3.9

69

—0

.37

50

.25

00

.218

1.5

00

1.5

311.

43

70

.45

50

.46

00

.45

02

3.5

00

23

.45

52

4.2

361

061

2.0

60

8.8

612

.86

08

.89

.56

.45

.53

8.1

38

.93

6.5

11.6

11.7

11.4

59

6.9

59

5.8

615

.4

26

26

.09

42

5.9

69

——

—0

.37

5—

—1.

75

01.

78

11.

68

70

.53

50

.54

00

.53

02

5.4

30

25

.37

02

6.3

06

60

66

2.8

65

9.6

9.5

44

.54

5.2

42

.813

.613

.713

.56

45

.96

44

.46

68

.0

28

28

.09

42

7.9

69

——

—0

.37

5—

—1.

75

01.

78

11.

68

70

.53

50

.54

00

.53

02

7.4

30

27.

37

02

8.3

07

117

13.6

710

.49

.54

4.5

45

.24

2.8

13.6

13.7

13.5

69

6.7

69

5.2

718

.8

30

30

.09

42

9.9

69

——

—0

.37

5—

—1.

75

01.

78

11.

68

70

.53

50

.54

00

.53

02

9.4

30

29

.37

03

0.3

07

62

76

4.4

761

.29

.54

4.5

45

.24

2.8

13.6

13.7

13.5

747.

574

6.0

76

9.6

32

32

.09

431

.96

9—

——

0.3

75

——

1.7

50

1.7

81

1.6

87

0.5

35

0.5

40

0.5

30

31.4

30

31.3

70

32

.30

813

815

.28

12.0

9.5

44

.54

5.2

42

.813

.613

.713

.57

98

.37

96

.88

20

.4

34

34

.09

43

3.9

69

——

—0

.37

5—

—1.

75

01.

78

11.

68

70

.53

50

.54

00

.53

03

3.4

30

33

.37

03

4.3

08

34

86

6.0

86

2.8

9.5

44

.54

5.2

42

.813

.613

.713

.58

49

.18

47.

68

71.

2

Page 45: Victaulic I-100 Field Installation Handbook.pdf

I-100_38

Nom

inal

N

PS

/B

asic

M

etri

c P

ipe

Siz

e

Act

ual

Pip

e O

utsi

de D

iam

eter

in

ches

/mm

in

ches

/mm

Dim

ensi

ons

inch

es/m

mC

arbo

n S

teel

and

Sta

ndar

d W

eigh

t Sta

inle

ss S

teel

Sta

inle

ss S

teel

S

ched

ules

5

S/1

0S

/10

Ext

ra-

Str

ong

Car

bon

Ste

elStd

.-

Wal

l Ste

el

Ligh

t-W

all

Car

bon

Ste

el

Ligh

t-W

all

Sta

inle

ss

Ste

el

Max

imum

Fl

are

Dia

met

er

Max

.M

in.

Max

.M

in.

Bas

icM

ax.

Min

.B

asic

Max

.M

in.

Max

.M

in.

36

36

.09

43

5.9

69

——

—0

.37

5—

—1.

75

01.

78

11.

68

70

.53

50

.54

00

.53

03

5.4

30

35

.37

03

6.3

09

149

16.8

913

.69

.54

4.5

45

.24

2.8

13.6

13.7

13.5

89

9.9

89

8.4

92

2.0

38

38

.09

43

7.9

69

——

0.5

00

——

—1.

75

01.

78

11.

68

70

.53

50

.54

00

.53

03

7.4

30

37.

37

03

8.3

09

65

96

7.6

96

4.4

12.7

44

.54

5.2

42

.813

.613

.713

.59

50

.79

49

.29

72

.8

40

40

.09

43

9.9

69

——

0.5

00

——

—2

.00

02

.031

1.9

37

0.5

62

0.5

67

0.5

57

39

.37

53

9.3

154

0.3

01

01

61

018

.41

015

.212

.75

0.8

51.6

49

.214

.314

.414

.110

00

.19

98

.610

23

.6

42

42

.09

441

.96

9—

—0

.50

0—

——

2.0

00

2.0

311.

93

70

.56

20

.56

70

.55

741

.37

541

.315

42

.30

106

710

69

.210

66

.012

.75

0.8

51.6

49

.214

.314

.414

.110

50

.910

49

.410

74.4

44

44

.09

44

3.9

69

——

0.5

00

——

—2

.00

02

.031

1.9

37

0.5

62

0.5

67

0.5

57

43

.37

54

3.3

154

4.3

011

1811

20

.011

16.8

12.7

50

.851

.64

9.2

14.3

14.4

14.1

110

1.7

110

0.2

112

5.2

46

46

.09

44

5.9

69

——

0.5

00

——

—2

.00

02

.031

1.9

37

0.5

62

0.5

67

0.5

57

45

.37

54

5.3

154

6.3

011

68

117

0.8

116

7.6

12.7

50

.851

.64

9.2

14.3

14.4

14.1

115

2.5

1151

.011

76

.0

48

48

.09

44

7.9

69

——

0.5

00

——

—2

.00

02

.031

1.9

37

0.5

62

0.5

67

0.5

57

47.

37

54

7.31

54

8.3

012

1912

21.6

1218

.412

.75

0.8

51.6

49

.214

.314

.414

.112

03

.312

01.

812

26

.8

54

54

.09

45

3.9

69

——

0.5

00

——

—2

.50

02

.531

2.4

37

0.5

62

0.5

67

0.5

57

53

.37

55

3.3

155

4.3

013

72

1374

.013

70

.812

.76

3.5

64

.361

.914

.314

.414

.113

55

.713

54

.213

79

.2

56

56

.09

45

5.9

69

——

0.5

00

——

—2

.50

02

.531

2.4

37

0.5

62

0.5

67

0.5

57

55

.37

55

5.3

155

6.3

014

22

142

4.8

1421

.612

.76

3.5

64

.361

.914

.314

.414

.114

06

.514

05

.014

30

.0

60

60

.09

45

9.9

69

——

0.5

00

——

—2

.50

02

.531

2.4

37

0.5

62

0.5

67

0.5

57

59

.37

55

9.3

156

0.3

015

24

152

6.4

152

3.2

12.7

63

.56

4.3

61.9

14.3

14.4

14.1

150

8.1

150

6.6

1531

.6

72

72

.09

47

1.9

69

——

0.5

00

——

—2

.50

02

.531

2.4

37

0.5

62

0.5

67

0.5

57

71.

37

57

1.31

57

2.3

018

29

1831

.218

28

.012

.76

3.5

64

.361

.914

.314

.414

.118

12.9

1811

.418

36

.4

Page 46: Victaulic I-100 Field Installation Handbook.pdf

I-100_39

in property damage.

Many factors must be considered for optimum gasket performance. Do not subject

gaskets to temperatures beyond the recommended limits, since excessive temperatures

will degrade gasket life and performance.

The services listed below are general service recommendations, and they apply only to

Victaulic gaskets. Recommendations for a particular service do not necessarily imply

compatibility of the coupling housings, related fittings, or other components for the same

service. Always refer to the latest Victaulic Gasket Selection Guide (05.01) for gasket

service recommendations.

These recommendations do not apply to rubber-lined valves or other rubber-

lined products. Refer to the applicable product literature, or contact Victaulic for

recommendations.

Temp.Compound

ColorCode

E –30°F to +230°F–34°C to +110°C

EPDMGreenStripe

Recommended for hot water service within the specified tem-perature range, plus a variety of dilute acids, oil-free air, and many chemical services. UL clas-sified in accordance with ANSI/NSF 61 for cold +73°F/+23°C and hot +180°F/+82°C potable water service. NOT RECOMMENDED FOR PETROLEUM SERVICES.

EHP@ –30°F to +250°F–34°C to +120°C

EPDMGreen

and Red Stripes

Recommended for hot water service within the specified temperature range. UL classi-fied in accordance with ANSI/NSF 61 for cold +73°F/+23°C and hot +180°F/+82°C potable water service. NOT RECOMMENDED FOR PETROLEUM SERVICES.

T –20°F to +180°F–29°C to +82°C

NitrileOrange Stripe

Recommended for petroleum products, hydrocarbons, air with oil vapors, vegetable oil, and mineral oil, within the specified temperature range. NOT RECOMMENDED FOR HOT WATER SERVICES OVER +150°F/ +66°C OR FOR HOT, DRY AIR OVER +140°F/+60°C.

E†

(Type A)

Ambient EPDMVioletStripe

Applicable for wet and dry (oil-free air) sprinkler services only. For dry services, Victaulic recom-mends the use of FlushSeal® gaskets. NOT RECOMMENDED FOR HOT WATER SERVICES.

@ The Grade EHP gasket is available only for Style 107, 177, and 607 Couplings. † Vic-Plus gasket. Refer to the “Lubrication” and “Dry Pipe Fire Protection System Notes” sections in this manual for additional information. * The information reflected in the table above defines general ranges for all compatible fluids. For specific chemical and temperature compatibility, refer to the “Gasket Selection and Chemical Services” sections in Submittal 05.01 (Gasket Selection Guide).

Page 47: Victaulic I-100 Field Installation Handbook.pdf

Temp.Compound

ColorCode

M-2 –40°F to +160°F–40°C to +71°C

Epichloro-hydrin

White Stripe

Specially compounded to provide superior service for common aromatic fuels at low temperatures. Also suitable for certain ambi-ent temperature water services.

V –30°F to +180°F–34°C to +82°C

NeopreneYellow Stripe

Recommended for hot lubricating oils and certain chemicals. Good oxidation resistance. Will not support combustion.

O +20°F to +300°F–7°C to +149°C

Fluoroelas-tomer

Blue Stripe

Recommended for many oxidizing acids, petroleum oils, halogenated hydrocar-bons, lubricants, hydraulic fluids, organic liquids, and air with hydrocarbons. NOT RECOMMENDED FOR HOT WATER SERVICES.

L –30°F to +350°F–34°C to +177°C

SiliconeRed

Gasket

Recommended for dry heat, air without hydro-carbons to +350°F/+177°C, and certain chemical services.

A +20°F to +180°F–7°C to +82°C

White Nitrile

White Gasket

No carbon black content. May be used for food services. Meets FDA requirements. Conforms to CFR Title 21 Part 177.2600. Not recommended for hot water services over +150°F/+66°C or for hot, dry air over +140°F/+60°C. NOT RECOMMENDED FOR HOT WATER SERVICES.

T(EndSeal)

–20°F to +150°F–29°C to +66°C

NitrileNo External

Identification

Specially compounded with excellent oil resistance and a high modulus for resistance to extrusion. Temperature Range –20°F/–29°C to +150°F/+66°C. Recommended for petro-leum products, air with oil vapors, vegetable oil, and mineral oil within the specified temperature range. Not recommended for hot water services over +150°F/+66°C or for hot, dry air over +140°F/+60°C. For maximum gasket life under pressure extremes, tem-perature should be limited to +120°F/+49°C.

Page 48: Victaulic I-100 Field Installation Handbook.pdf

Temp.Compound

ColorCode

EF –30°F to +230°F–34°C to +110°C

EPDMGreen

“X”

Recommended for hot and cold water service within the specified temperature range, plus a variety of dilute acids, oil-free air, and many chemical services. Meets hot and cold pota-ble water requirements. DVGW, KTW, ÖVGW, SVGW, and French ACS (Crecep) Approved for W534, EN681-1 Type WA cold potable water service and Type WB hot potable water service. NOT RECOMMENDED FOR PETROLEUM SERVICES

EW –30°F to +230°F–34°C to +110°C

EPDMGreen

“W”

Recommended for hot water service within the specified temperature range, plus a variety of dilute acids, oil-free air, and many chemical services. WRAS- approved material to BS 6920 for cold and hot potable water service up to +149°F/+65°C.NOT RECOMMENDED FOR PETROLEUM SERVICES.

ST-20°F to +210°F-29°C to +99°C HNBR

Two Orange Stripes

Recommended for vary-ing concentrations of hot petroleum/water mixtures; hydrocarbons; air with oil vapors; vegetable and min-eral oils; and automotive fluids, such as engine oil and transmission oil, within the specified temperature range.

HMT(Standard or

EndSeal)

-20° F to +180° F

(-29° C to +82° C)High-

Modulus Nitrile

T2

No Color Code

Identification

Specially compounded with excellent oil resis-tance and a high modulus for resistance to extrusion. Temperature range is -20° F to +180° F/-29° C to +82° C. Recommended for petroleum products, air with oil vapors, vegetable and mineral oils within the specified temperature range. Not recommended for hot water services over +150° F/+66° C or for hot, dry air over +140° F/+60° C. For maximum gasket life under pressure extremes, the temperature should be limited to +120° F/+49° C.

Page 49: Victaulic I-100 Field Installation Handbook.pdf

Lubrication of the gasket with a thin coating of Victaulic Lubricant or another compatible

material on the exterior/gasket sealing lips or the coupling housings’ interiors/pipe ends

is essential to prevent gasket pinching. In addition, lubrication eases installation of

the gasket onto the pipe end. Refer to the photos below for examples of properly and

improperly lubricated gaskets. Victaulic Lubricant is not recommended for use

with High-Density Polyethylene (HDPE) pipe. Refer to Victaulic publication 05.02 for the

Victaulic Lubricant MSDS sheet.

Much Victaulic Lubricant

Canadian customers should contact Victaulic Company of

Canada for a Victaulic Lubricant MSDS sheet that meets Canadian WHMIS requirements.

NOTICE

may not enhance sealing capabilities on all adverse pipe conditions. Pipe

the product installation instructions.

Page 50: Victaulic I-100 Field Installation Handbook.pdf

The following table provides approximations for the number of gaskets that can be lubri-

cated with a 4.5-ounce/127.5-gram tube or a 1-quart/32-ounce/907-gram container of

Victaulic Lubricant. These values have been calculated using a thin coating of Victaulic

Lubricant, as described in the “Lubrication” section on the previous page, and do not

take into account any overuse, spillage, etc.

Coupling Size

Nominal Sizeinches

Actual Pipe Outside Diameter inches/mm Per Tube Per Quart

22.375

140 112060.3

33.500

97 77388.9

44.500

71 558114.3

66.625

49 383168.3

88.625

31 252219.1

1010.750

25 202273.0

1212.750

21 171323.9

14 OD14.000

12 98355.6

16 OD16.000

11 86406.4

18 OD18.000

10 76457

20 OD20.000

9 69508

22 OD22.000

8 63559

24 OD24.000

7 57610

26 OD26.000

6 50660

28 OD28.000

6 46711

30 OD30.000

5 43762

32 OD32.000

5 36813

36 OD36.000

4 34914

40 OD40.000

4 321016

42 OD42.000

4 311067

46 OD46.000

4 281168

48 OD48.000

3 271219

54 OD54.000

3 241372

56 OD56.000

3 231422

60 OD60.000

3 221524

72 OD72.000

2 181829

Victaulic Lubricant has full WRAS approval (Approval No. 0507514) and ANSI/NSF 61 approval.

Page 51: Victaulic I-100 Field Installation Handbook.pdf

Victaulic Grade “E”, (Type A) FireLock gaskets are Factory Mutual (FM) Approved

and Underwriters Laboratories, Inc. (UL) Listed for dry pipe fire protection systems.

In freezers or systems subject to freezing temperatures, pipe end surface preparation

becomes critical. EPDM will harden as freezing temperatures approach the lower

temperature limitation of the gasket material (–40º F/–40º C). Therefore, all indentations,

projections, loose paint, scale, dirt, chips, grease, and rust must be removed from the

end of the pipe to the groove to provide a leak-tight seal for the gasket.

Victaulic recommends Grade “E” (Type A) FireLock FlushSeal® gaskets (or Style

009/009V gaskets) in systems subject to both freezing temperatures and hydrostatic

pressure tests. The center leg in the gasket cavity reduces the potential for ice formation

from residual water that can become trapped in the gasket cavity during hydrostatic

pressure testing.

As a practical alternative to strict adherence to Victaulic’s surface preparation

requirements, or where pipe joint flexibility may be required, Grade “L” (silicone) gaskets

are recommended. At low temperatures, Grade “L” gaskets remain soft and pliable,

which helps the gasket seal on pipe surfaces that are less than ideal. In addition, Grade

“L” gaskets adapt more readily to temperature swings that generate both linear and radial

expansion/contraction and increases reliability on joints subject to movement, such as

rack piping, etc.

It is the system designer’s, material specifier’s, and/or the installing contractor’s

responsibility to select the gasket grade that is suitable for the intended service.

Dry pipe fire protection systems are subject to the supplemental lubrication issues

mentioned above.

Page 52: Victaulic I-100 Field Installation Handbook.pdf

Since the grooved piping method incorporates externally mounted housings,

consideration must be given to external dimensions beyond the pipe OD.

Allowance for insulation, when necessary, is not included in the following

examples.

Y + 20%

Y

Y + 20%

Y

Facing Each Other

Facing Out

Illustrations are exaggerated for clarity

To allow for easy installation, insulation, and maintenance, consideration must be given to

proper spacing between pipelines. Since Victaulic grooved pipe couplings are externally

mounted housings that contain bolt pads, allow enough access space to tighten the

bolts. In addition, provide enough space to prevent interference between piping and

adjacent couplings.

The pipe centerline must be spaced with the width of the coupling housings (“Y”

dimension) for systems where couplings are staggered. Add an additional 20% to the

width (Y) when couplings are inline, as shown above.

Y The “Y” dimension is the maximum dimension

across the coupling. Bolt pads can be positioned in any

orientation to provide adequate clearance if the

orientation shown causes interference with other system

components.

When installing grooved piping systems in confined

areas, such as a pipe shaft, a tunnel, a narrow trench, or when joining riser pipe and

dropping it through riser holes, consideration must be given to the external clearance

of the housings. This clearance must be slightly greater than the “Y” dimension of the

widest point. The necessary clearance will vary depending upon installation procedures,

the proximity of other pipes, and other factors. When installing Style 791 Vic-

Boltless Couplings, sufficient room must be provided to allow clearance for the Style 792

Assembly Tool (refer to the Style 792 installation instructions in this manual for more

information).

Page 53: Victaulic I-100 Field Installation Handbook.pdf

To achieve maximum expansion/contraction allowance, pipe joints must be installed with

proper spacing between the pipe ends. The following is a brief overview of methods to

accommodate expansion/contraction. Refer to Section 26, Design Data, of the G-100

General Catalog for complete details.

For maximum expansion, pipe ends must be at their maximum gap

PROPER INSTALLATION FOR EXPANSION

Key

Exaggerated for Clarity

1. Vertical systems can be installed as the pipe is lowered by assembling the couplings

and using the weight of the pipe to pull the pipe ends open.

Anchor the system at one end, and install the couplings and proper guides. Cap the

system, pressurize it to fully open the pipe ends, then anchor the other end with the pipe

ends fully gapped.

3. Install the couplings. Use a “come-along” to pull the pipe for full end separation,

then secure the pipe to maintain the opening.

coupling.

PROPER INSTALLATION FOR CONTRACTION

Key

Exaggerated for Clarity

1. In vertical systems, stack the pipe by using the weight to butt the pipe ends, then

anchor the pipe to maintain the position.

In horizontal systems, install the joints with the pipe ends butted by using a “come-

along” to draw the pipe ends together, if necessary, then secure the pipe in position.

For Expansion and Contraction

1. Alternate the above procedures in proportion to the need for expansion and

contraction.

For expansion, visible gaps on either side of the coupling housings’ key section (between

the coupling housings’ key section and the rear edge of the groove) can be used to

ensure proper installation of most couplings for maximum movement. These gaps are

approximately equal to half the linear movement capability. Piping must be secured to

maintain the desired position.

For pipe contraction, virtually no gap should be visible between the coupling housings’

key section and the rear edge of the groove. Piping must be secured to maintain the

desired position.

Page 54: Victaulic I-100 Field Installation Handbook.pdf

Piping that is joined with grooved pipe couplings, like all other piping systems, requires

support to carry the weight of pipes, equipment, and fluid. The support or hanging

method must minimize stress on joints, piping, and other components. In addition, the

method of support must allow pipeline movement, where required, along with other

design requirements, such as drainage or venting. The designer must also consider

the special requirements of flexible couplings while designing a support system.

Valves with unbalanced loads, particularly ones installed in horizontal pipelines within

areas of high vibration, require support to resist external rotation.

The following tables list the suggested maximum span between pipe supports for

horizontal, straight runs of standard-weight steel pipe that carries water or similarly dense

liquids.

NOTICE

DO NOT attach supports directly to couplings. Attach supports only to adjoining pipe and equipment.

Page 55: Victaulic I-100 Field Installation Handbook.pdf

For Victaulic rigid couplings, refer to the chart below for maximum hanger spacing.

Size

Nominal Size inches

Actual Pipe Outside Diameter inches/mm

Water Service

* *

11.315 7 9 12 9 9 1233.7 2.1 2.7 3.7 2.7 2.7 3.7

1 ¼1.660 7 11 12 9 11 1242.4 2.1 3.4 3.7 2.7 3.4 3.7

1 ½1.900 7 12 15 9 13 1548.3 2.1 3.7 4.6 2.7 4.0 4.6

22.375 10 13 15 13 15 1560.3 3.1 4.0 4.6 4.0 4.6 4.6

33.500 12 16 15 15 17 1588.9 3.7 4.9 4.6 4.6 5.2 4.6

44.500 14 17 15 17 21 15114.3 4.3 5.2 4.6 5.2 6.4 4.6

66.625 17 20 15 21 25 15168.3 5.2 6.1 4.6 6.4 7.6 4.6

88.625 19 22 15 24 28 15219.1 5.8 6.7 4.6 7.3 8.5 4.6

1010.750 19 23 15 24 31 15273.0 5.8 7.0 4.6 7.3 9.5 4.6

1212.750 23 24 15 30 33 15323.9 7.0 7.3 4.6 9.1 10.1 4.6

1414.000 23 25 15 30 33 15355.6 7.0 7.6 4.6 9.1 10.1 4.6

1616.000 27 25 15 35 33 15406.4 8.2 7.6 4.6 10.7 10.1 4.6

1818.000 27 25 15 35 33 15

457 8.2 7.6 4.6 10.7 10.1 4.6

2020.000 30 25 15 39 33 15

508 9.1 7.6 4.6 11.9 10.1 4.6

2424.000 32 25 15 42 33 15

610 9.8 7.6 4.6 12.8 10.1 4.6

2626.000 30 – – – – –

660 9.1 – – – – –

2828.000 30 – – – – –

711 9.1 – – – – –

3030.000 30 – – – – –

762 9.1 – – – – –

3232.000 31 – – – – –

813 9.4 – – – – –

3636.000 31 – – – – –

914 9.4 – – – – –

4040.000 35 – – – – –

1016 10.7 – – – – –

4242.000 35 – – – – –1067 10.7 – – – – –

4646.000 35 – – – – –

1168 10.7 – – – – –

4848.000 36 – – – – –

1219 11.0 – – – – –

Table continued on following page Refer to notes on following page

Page 56: Victaulic I-100 Field Installation Handbook.pdf

Size

Nominal Size inches

Actual Pipe Outside Diameter inches/mm

Water Service

* *

5454.000 37 – – – – –1372 11.3 – – – – –

5656.000 37 – – – – –1422 11.3 – – – – –

6060.000 37 – – – – –1524 11.3 – – – – –

*Spacing corresponds to ASME B31.1 Power Piping Code †Spacing corresponds to ASME B31.9 Building Services Piping Code ‡Spacing corresponds to NFPA 13 Fire Sprinkler Systems

Page 57: Victaulic I-100 Field Installation Handbook.pdf

I-100_50

Size

NominalSize

inches

Actual Pipe Outside Diameter

inches/mm

103.0

156.1

309.1

35

¾ – 11.050 – 1.315

1 2 2 2 3 3 4 4 5 626.9 – 33.7

1 ¼ – 21.660 – 2.375

1 2 2 2 3 3 4 4 5 542.4 – 60.3

2 ½ – 42.875 – 4.500

1 1 2 2 2 2 2 3 4 473.0 – 114.3

5 – 85.563 – 8.625

1 1 1 2 2 2 2 3 3 3139.7 – 219.1

10 – 1210.750 – 12.750

1 1 1 2 2 2 2 3 3 3273.0 – 323.9

14 – 1614.000 – 16.000

1 1 1 2 2 2 2 3 3 3355.6 – 406.4

18 – 2418.000 – 24.000

1 1 1 2 2 2 2 3 3 3457 – 610

26 – 6026.000 – 60.000

1 1 1 1 2 2 2 3 3 3660 – 1524

*No pipe length should be left unsupported between any two couplings

SizeSuggested Maximum Span

Nominal Size inches

Actual Pipe Outside Diameter inches/mm

¾ – 11.050 – 1.315 826.9 – 33.7 2.4

1 ¼ – 21.660 – 2.375 10

42.4 – 60.3 3.0

2 ½ – 42.875 – 4.500 1273.0 – 114.3 3.7

5 – 85.563 – 8.625 14139.7 – 219.1 4.3

10 – 1210.750 – 12.750 16273.0 – 323.9 4.9

14 – 1614.000 – 16.000 18

355.6 – 406.4 5.5

18 – 2418.000 – 24.000 20

457 – 610 6.1

26 – 6026.000 – 60.000 21

660 – 1524 6.4

Page 58: Victaulic I-100 Field Installation Handbook.pdf

I-100_51

Light-wall, stainless steel piping requires hangers to meet the following spacing

requirements. For flexible systems, refer to the preceding tables under the “Flexible

System” section. For rigid systems, refer to the table below for maximum hanger spacing.

Size

Suggested Maximum Span

Nominal Size inches or mm

Actual Pipe Outside Diameter

inches/mm inches/mm Schedule

22.37560.3

0.0655S

91.65 2.7

0.079—

102.00 3.1

0.10910S

102.77 3.1

76.1 mm3.000 0.079

—10

76.1 2.00 3.1

33.50088.9

0.079—

102.00 3.1

0.0835S

102.11 3.1

0.12010S

123.05 3.7

44.500114.3

0.079—

112.00 3.4

0.0835S

112.11 3.4

0.12010S

123.05 3.7

139.7 mm5.500139.7

0.079—

132.00 4.0

0.102—

132.60 4.0

0.118—

153.00 4.6

66.625168.3

0.079—

132.00 4.0

0.102—

132.60 4.0

0.1095S

132.77 4.0

0.118—

153.00 4.6

0.13410S

143.40 4.3

88.625219.1

0.102—

132.60 4.0

0.1095S

132.77 4.0

0.118—

153.00 4.6

0.14810S

153.76 4.6

Table continued on the following page

Page 59: Victaulic I-100 Field Installation Handbook.pdf

Size

Suggested Maximum Span

Nominal Size inches or mm

Actual Pipe Outside Diameter

inches/mm inches/mm Schedule

1010.750273.0

0.118—

153.00 4.6

0.1345S

153.40 4.6

0.16510S

164.19 4.9

1212.750323.9

0.118—

153.00 4.6

0.1565S

163.96 4.9

0.18010S

174.57 5.2

14*14.000 0.188

10S21

355.6 4.78 6.4

16*16.000 0.188

10S22

406.4 4.78 6.7

18*18.00 0.188

10S22

457 4.78 6.7

20*20.000 0.218

10S24

508 5.54 7.3

24*24.000 0.250

10S25

610 6.35 7.6

* Hanger spacing for these sizes applies to AGS Rigid Couplings.

Page 60: Victaulic I-100 Field Installation Handbook.pdf

I-100_53

The maximum allowable pipe-end separation dimensions shown in the table below are

for system layout purposes only. Style 009H and Style 107H Couplings are considered

rigid joints that allow no angular deflection or linear movement. The design/allowable pipe

separation MUST be considered during assembly.

Size

inches/mm

Nominal Size inches or mm

Actual Pipe Outside Diameter inches/mm Style 009H

1 ¼1.660 0.10 –42.4 2.5 –

1 ½1.900 0.10 –48.3 2.5 –

22.375 0.12 0.1560.3 3.1 3.8

2 ½2.875 0.12 0.1573.0 3.1 3.8

76.1 mm3.000 0.12 0.1576.1 3.1 3.8

33.500 0.12 0.1588.9 3.1 3.8

44.500 0.17 0.15114.3 4.3 3.8

139.7 mm5.500 – 0.15139.7 – 3.8

55.563 – 0.15141.3 – 3.8

165.1 mm6.500 – 0.15165.1 – 3.8

66.625 – 0.15168.3 – 3.8

88.625 – 0.22219.1 – 5.6

Page 61: Victaulic I-100 Field Installation Handbook.pdf

Victaulic AGS rigid couplings contain flat bolt pads. The housings’ wedge-shaped key

profile increases the allowable pipe-end separation and eases initial assembly alignment

(refer to the table below).

Rigid couplings provide a rigid joint that allows no angular deflection or linear movement.

The design/allowable pipe separation MUST be considered during assembly.

Size

Pipe-End Separation

Nominal Sizeinches

Actual Pipe Outside Diameter

inches/mm inches/mm

14 *14.000 0.25355.6 6.4

16 *16.000 0.25406.4 6.4

18 *18.000 0.25

457 6.4

20 *20.000 0.25

508 6.4

24 *24.000 0.25

610 6.4

26 *26.000 0.38

660 9.6

28 *28.000 0.38

711 9.6

30 *30.000 0.38

762 9.6

32 *32.000 0.38

813 9.6

36 *36.000 0.38

914 9.6

40 *40.000 0.44

1016 11.1

42 *42.000 0.441067 11.1

46 *46.000 0.44

1168 11.1

48 *48.000 0.44

1219 11.1

54 *54.000 0.501372 12.7

56 *56.000 0.501422 12.7

60 *60.000 0.501524 12.7

* Applies only to for Style W07 AGS Rigid Couplings. For pipe roll or cut grooved to standard specifications, refer to the separate table on page 56.

Page 62: Victaulic I-100 Field Installation Handbook.pdf

I-100_55

®

Victaulic AGS rigid couplings contain flat bolt pads. The housings’ wedge-shaped key

profile increases the allowable pipe-end separation and eases initial assembly alignment

(refer to the table below).

Rigid couplings provide a rigid joint that allows no angular deflection or linear movement.

The design/allowable pipe separation MUST be considered during assembly.

Size

Pipe-End Separation

Nominal Pipe Sizeinches

Coupling/ ® Size

inches/mm inches/mm

12 *14.000 0.25355.6 6.4

14 *16.000 0.25406.4 6.4

16 *18.000 0.25

457 6.4

18 *20.000 0.25

508 6.4

20 *22.000 0.25

559 6.4

22 *24.000 0.25

610 6.4

24 *26.000 0.38

660 9.6

26 *28.000 0.38

711 9.6

28 *30.000 0.38

762 9.6

30 *32.000 0.38

813 9.6

32 *34.000 0.38

865 9.6

34 *36.000 0.38

914 9.6

36 *38.000 0.38

965 9.6

38 *40.000 0.44

1016 11.1

40 *42.000 0.441067 11.1

42 *44.000 0.44

1118 11.1

44 *46.000 0.44

1168 11.1

46 *48.000 0.44

1219 11.1

* Applies only to ® for Style W07 AGS Rigid Couplings.

Page 63: Victaulic I-100 Field Installation Handbook.pdf

I-100_56

Victaulic standard rigid couplings have an angle-bolt-pad design that constricts the

coupling housings’ keys into the groove around the entire pipe circumference. The

housings slide on the angle bolt pads, rather than mating squarely.

In addition, the sliding of the housings forces the key sections into opposed contact

on the inside and outside groove edges, which results in pipe-end separation during

assembly (refer to the table below).

Rigid couplings provide a rigid joint that allows no angular deflection or linear movement.

The design/allowable pipe separation MUST be considered during assembly.

Size

Nominal Size inches or mm

Actual Pipe Outside Diameter inches/mm inches/mm

11.315 0.0533.7 1.2

1 ¼1.660 0.0542.4 1.2

1 ½1.900 0.0548.3 1.2

22.375 0.0760.3 1.7

2 ½2.875 0.0773.0 1.7

76.1 mm3.000 0.0776.1 1.7

33.500 0.0788.9 1.7

44.500 0.16114.3 4.1

108.0 mm4.250 0.16108.0 4.1

55.563 0.16141.3 4.1

133.0 mm5.250 0.16133.0 4.1

139.7 mm5.500 0.16139.7 4.1

66.625 0.16168.3 4.1

159.0 mm6.250 0.16159.0 4.1

165.1 mm6.500 0.16165.1 4.1

88.625 0.19219.1 4.8

1010.750 0.13273.0 3.3

1212.750 0.13323.9 3.3

† Allowable pipe-end separation is different for Style 307 Transition Couplings. Refer to the I-300 Field Installation Handbook for details.

Page 64: Victaulic I-100 Field Installation Handbook.pdf

Allowable pipe-end separation and deflection values are the maximum nominal range of

movement available at each joint for standard roll-grooved or cut-grooved pipe. These

values are maximums. For design and installation purposes, these values should be

reduced by 50% for ¾ – 3 ½-inch/26.9 – 101.6-mm sizes and 25% for 4-inch/114.3-mm

and larger sizes.

Size

Nominal Size inches or mm

Actual Pipe Outside Diameter

inches/mm

Minimum

Maximum

Maximum

22.375 0.13 0.19 0.2560.3 3.2 4.8 6.4

2 ½2.875 0.13 0.19 0.2573.0 3.2 4.8 6.4

76.1 mm3.000 0.13 0.19 0.2576.1 3.2 4.8 6.4

33.500 0.13 0.19 0.2588.9 3.2 4.8 6.4

44.500 0.13 0.25 0.38114.3 3.2 6.4 9.5

139.7 mm5.500 0.13 0.25 0.38139.7 3.2 6.4 9.5

55.563 0.13 0.25 0.38141.3 3.2 6.4 9.5

66.625 0.13 0.25 0.38168.3 3.2 6.4 9.5

88.625 0.19 0.31 0.44219.1 4.8 7.9 11.2

(1) Minimum pipe-end separation, as required by the gasket center leg, for roll- or cut-grooved pipe. Refer to illustration (1) below.

(2 and 3) Maximum pipe-end separation to be used in determining overall piping system movement for roll-grooved (2) or cut-grooved (3) pipe. For design and installation purposes, the minimum and maximum pipe-end separations should be reduced to the values shown in the table on the following page. These design and installation considerations include thermal growth, settlement, installation misalignment, and offsets. Refer to illustrations (2 and 3) below.

Separation Separation Separation

Information continued on the following page

Page 65: Victaulic I-100 Field Installation Handbook.pdf

I-100_58

Size

Nominal Size

inches or mm

Actual Pipe Outside

Diameter inches/mm

Linear Movement inches/mm

Centerline

Linear Movement inches/mm

Centerline

Degrees Per

inches Per

Pipe/mm Per

One meter Degrees

Per

inches Per

Pipe/mm Per

One meter

22.375 0.06

1.52°0.32 0.13

3.04°0.64

60.3 1.5 26 3.3 52

2 ½2.875 0.06

1.25°0.26 0.13

2.50°0.52

73.0 1.5 22 3.3 44

76.1 mm3.000 0.06

1.20°0.26 0.13

2.40°0.52

76.1 1.5 22 3.3 44

33.500 0.06

1.03°0.22 0.13

2.06°0.44

88.9 1.5 18 3.3 36

44.500 0.13

1.60°0.34 0.25

3.20°0.68

114.3 3.3 28 6.4 56

139.7 mm5.500 0.13

1.30°0.28 0.25

2.60°0.54

139.7 3.3 24 6.4 45

55.563 0.13

1.30°0.27 0.25

2.60°0.54

141.3 3.3 22 6.4 45

66.625 0.13

1.08°0.23 0.25

2.16°0.46

168.3 3.3 18 6.4 36

88.625 0.13

0.83°0.18 0.25

1.66°0.35

219.1 3.3 15 6.4 29

Page 66: Victaulic I-100 Field Installation Handbook.pdf

I-100_59

Allowable pipe-end separation and deflection values are the maximum nominal range

of movement available at each joint for pipe that is roll grooved to AGS specifications.

These values are maximums. For design and installation purposes, these values should

be reduced by 25%.

Size

Nominal Size inches

Actual Pipe Outside Diameter

inches/mm

Maximum

Separationinches/mm

Degrees PerCoupling

inches Per One

mm Per One

14 *14.000 0.13 – 0.31

0.73°0.15

355.6 3.3 – 7.9 13

16 *16.000 0.13 – 0.31

0.63°0.13

406.4 3.3 – 7.9 11

18 *18.000 0.13 – 0.31

0.57°0.12

457 3.3 – 7.9 10

20 *20.000 0.13 – 0.31

0.50°0.10

508 3.3 – 7.9 9

24 *24.000 0.13 – 0.31

0.42°0.09

610 3.3 – 7.9 8

26 *26.000 0.15 – 0.53

0.83°0.18

660 3.8 – 13.5 15

28 *28.000 0.15 – 0.53

0.78°0.16

711 3.8 – 13.5 14

30 *30.000 0.15 – 0.53

0.73°0.16

762 3.8 – 13.5 14

32 *32.000 0.15 – 0.53

0.68°0.14

813 3.8 – 13.5 11

36 *36.000 0.15 – 0.53

0.60°0.13

914 3.8 – 13.5 11

40 *40.000 0.21 – 0.59

0.55°0.12

1016 5.3 – 15.0 10

42 *42.000 0.21 – 0.59

0.52°0.11

1067 5.3 – 15.0 9

46 *46.000 0.21 – 0.59

0.47°0.10

1168 5.3 – 15.0 8

48 *48.000 0.21 – 0.59

0.45°0.10

1219 5.3 – 15.0 8

54 *54.000 0.28 – 0.66

0.40°0.08

1372 7.1 – 16.8 7

56 *56.000 0.28 – 0.66

0.38°0.08

1422 7.1 – 16.8 7

60 *60.000 0.28 – 0.66

0.36°0.08

1524 7.1 – 16.8 7

* Applies only to pipe roll grooved to AGS specifications for Style W77 (AGS) Flexible Couplings. For pipe roll grooved to standard specifications, refer to the separate table on page 61.

Page 67: Victaulic I-100 Field Installation Handbook.pdf

I-100_60

®

Allowable pipe-end separation and deflection values are the maximum nominal range

of movement available at each joint. These values are maximums. For design and

installation purposes, these values should be reduced by 25%.

Size ®

Nominal Pipe Size inches

Coupling/ ® Size

inches/mm

Maximum

Separationinches/mm

Degrees PerCoupling

inches Per One

mm Per One

12 *14.000 0.13 – 0.31

0.73°0.15

355.6 3.3 – 7.9 13

14 *16.000 0.13 – 0.31

0.63°0.13

406.4 3.3 – 7.9 11

16 *18.000 0.13 – 0.31

0.57°0.12

457 3.3 – 7.9 10

18 *20.000 0.13 – 0.31

0.50°0.10

508 3.3 – 7.9 9

20 *22.000 0.13 – 0.31

0.50°0.10

559 3.3 – 7.9 9

22 *24.000 0.13 – 0.31

0.42°0.09

610 3.3 – 7.9 8

24 *26.000 0.15 – 0.53

0.83°0.18

660 3.8 – 13.5 15

26 *28.000 0.15 – 0.53

0.78°0.16

711 3.8 – 13.5 14

28 *30.000 0.15 – 0.53

0.73°0.16

762 3.8 – 13.5 14

30 *32.000 0.15 – 0.53

0.68°0.14

813 3.8 – 13.5 11

32 *34.000 0.15 – 0.53

0.69°0.13

865 3.8 – 13.5 11

34 *36.000 0.15 – 0.53

0.60°0.13

914 3.8 – 13.5 11

36 *38.000 0.15 – 0.53

0.60°0.13

965 3.8 – 13.5 11

38 *40.000 0.21 – 0.59

0.55°0.12

1016 5.3 – 15.0 10

40 *42.000 0.21 – 0.59

0.52°0.11

1067 5.3 – 15.0 9

42 *44.000 0.21 – 0.59

0.50°0.10

1118 5.3 – 15.0 8

44 *46.000 0.21 – 0.59

0.47°0.10

1168 5.3 – 15.0 8

46 *48.000 0.21 – 0.59

0.45°0.10

1219 5.3 – 15.0 8

52 *54.000 0.28 – 0.66

0.40°0.08

1372 7.1 – 16.8 7

54 *56.000 0.28 – 0.66

0.38°0.08

1422 7.1 – 16.8 7

58 *60.000 0.28 – 0.66

0.36°0.08

1524 7.1 – 16.8 7

* Applies only to pipe ® for Style W77 AGS Flexible Couplings.

Page 68: Victaulic I-100 Field Installation Handbook.pdf

I-100_61

Allowable pipe-end separation and deflection values are the maximum nominal range

of movement available at each joint for standard roll-grooved pipe.

grooved pipe may be doubled. These values are maximums. For design and installation

purposes, these values should be reduced by 50% for ¾ – 3 ½-inch/26.9 – 101.6-mm

sizes and 25% for 4-inch/114.3-mm and larger sizes.

Size

Nominal Sizeinches or mm

Actual Pipe Outside Diameter

inches/mm

Maximum

Separationinches/mm

Degrees PerCoupling

inches Per One

mm Per One

¾1.050 0 – 0.06

3.40°0.72

26.9 0 – 1.6 60

11.315 0 – 0.06

2.72°0.57

33.7 0 – 1.6 48

1 ¼1.660 0 – 0.06

2.17°0.45

42.4 0 – 1.6 38

1 ½1.900 0 – 0.06

1.93°0.40

48.3 0 – 1.6 33

22.375 0 – 0.06

1.52°0.32

60.3 0 – 1.6 26

2 ½2.875 0 – 0.06

1.25°0.26

73.0 0 – 1.6 22

76.1 mm3.000 0 – 0.06

1.20°0.26

76.1 0 – 1.6 22

33.500 0 – 0.06

1.03°0.22

88.9 0 – 1.6 18

3 ½4.000 0 – 0.06

0.90°0.19

101.6 0 – 1.6 16

44.500 0 – 0.13

1.60°0.34

114.3 0 – 3.2 28

108.0 mm4.250 0 – 0.13

1.68°0.35

108.0 0 – 3.2 29

55.563 0 – 0.13

1.30°0.27

141.3 0 – 3.2 23

133.0 mm5.250 0 – 0.13

1.35°0.28

133.0 0 – 3.2 24

139.7 mm5.500 0 – 0.13

1.30°0.28

139.7 0 – 3.2 24

66.625 0 – 0.13

1.08°0.23

168.3 0 – 3.2 18

159.0 mm6.250 0 – 0.13

1.15°0.24

159.0 0 – 3.2 20

165.1 mm6.500 0 – 0.13

1.10°0.23

165.1 0 – 3.2 19

88.625 0 – 0.13

0.83°0.18

219.1 0 – 3.2 14

1010.750 0 – 0.13

0.67°0.14

273.0 0 – 3.2 12

1212.750 0 – 0.13

0.57°0.12

323.9 0 – 3.2 9

† Refer to note on the following page.

Page 69: Victaulic I-100 Field Installation Handbook.pdf

Size

Nominal Sizeinches or mm

Actual Pipe Outside Diameter

inches/mm

Maximum

Separationinches/mm

Degrees PerCoupling

inches Per One

mm Per One

14 *14.000 0 – 0.13

0.52°0.11

355.6 0 – 3.2 9

15 *15.000 0 – 0.13

0.48°0.10

381.0 0 – 3.2 9

16 *16.000 0 – 0.13

0.45°0.10

406.4 0 – 3.2 9

18 *18.000 0 – 0.13

0.40°0.08

457 0 – 3.2 7

20 *20.000 0 – 0.13

0.37°0.08

508 0 – 3.2 7

22 *22.000 0 – 0.13

0.32°0.07

559 0 – 3.2 6

24 *24.000 0 – 0.13

0.30°0.07

610 0 – 3.2 6

26 §26.000 0 – 0.38

0.83°0.17

660 0 – 9.7 14

28 §28.000 0 – 0.38

0.77°0.16

711 0 – 9.7 13

30 §30.000 0 – 0.38

0.72°0.15

762 0 – 9.7 13

32 §32.000 0 – 0.38

0.67°0.14

813 0 – 9.7 12

36 §36.000 0 – 0.38

0.60°0.12

914 0 – 9.7 10

42 §42.000 0.31 – 0.69

0.52°0.20

1067 7.9 – 17.5 17

* Applies only to pipe roll grooved to standard specifications for Style 77 (non-AGS) Flexible Couplings. For pipe roll grooved to AGS specifications, refer to the separate table on the previous pages.

§ Applies only to pipe roll grooved for Style 770 Large Diameter Couplings.

Page 70: Victaulic I-100 Field Installation Handbook.pdf

I-100_63

attempting to install, remove, or adjust any Victaulic piping products.

DO NOT attach supports directly to couplings. Attach supports only to adjoining pipe and equipment.

personal injury, property damage, and product damage.

The following instructions are a general guideline for the installation of Victaulic piping

products. These instructions must be followed to ensure proper pipe-joint assembly.

1. Always check the supplied gasket to ensure it is suitable for the intended service.

Refer to the “Gasket Selection” section of this manual or Victaulic submittal 05.01.

Valve bodies, discs, and other wetted components must be compatible with the

material flowing through the system. Refer to the most current Victaulic literature, or

contact Victaulic for details.

3. Always read the operating and maintenance instruction manuals for the pipe

preparation tools.

The outside diameter and grooving dimensions of pipe must be within the current

specifications published by Victaulic.

5. For rigid, angle-bolt-pad couplings, the nuts must be tightened evenly by alternating

sides until metal-to-metal contact at the bolt pads is achieved. Equal, positive offsets are

necessary to ensure a rigid joint.

6. Rigid, angle-bolt-pad couplings are not recommended for use with PVC plastic pipe.

For flexible couplings with flat bolt pads, the nuts must be tightened evenly by

alternating sides until metal-to-metal contact at the bolt pads is achieved.

8. Couplings that contain a tongue-and-recess feature must be mated properly,

tongue-to-recess.

9. When a torque value is specified for coupling installation, this torque be

applied to the nuts in order to achieve proper installation. However, torque beyond

specified values will not improve sealing. Exceeding the specified torque by more than

25% may cause damage to the product, resulting in joint failure.

10. For Advanced Groove System (AGS™), FireLock EZ™, and QuickVic™ couplings,

deep well sockets are recommended for proper installation due to the longer bolt lengths

associated with these products. Deep well sockets provide the full nut engagement that is

necessary during tightening.

11. Placement of check valves too close to sources of unstable flow will shorten the life

of the valve and may potentially damage the system. To extend valve life, valves should

be installed a reasonable distance away from pumps, elbows, expanders, reducers, or

other similar devices. Piping practices dictate a minimum distance of five times the pipe

diameter for general use. Distances between three and five diameters are allowable,

provided the flow velocity is less than 8 feet per second/2.4 meters per second.

Distances of less than three diameters are not recommended.

Victaulic female threaded products are designed to accommodate standard ANSI

male pipe threads only. BSPT threads are available (specify upon ordering). Use

of male threaded products with special features, such as probes, dry-pendent sprinkler

heads, etc., must be checked for suitability with the Victaulic piping product being

installed. Failure to verify suitability in advance may result in difficult installation or joint

failure.

13. When joining pipe of the same size but different wall thicknesses/schedules, the

joint rating will be based on the thinner wall pipe.

Page 71: Victaulic I-100 Field Installation Handbook.pdf

Nuts must be tightened evenly by alternating sides until metal-to-metal contact

present at the bolt pads to obtain pipe-joint rigidity.

Due to the speed of assembly when using an impact wrench, the installer should take

extra care to ensure nuts are tightened evenly by alternating sides until proper assembly

is complete. Always refer to the specific product installation instructions for complete

installation requirements.

Impact wrenches do not provide the installer with direct “wrench feel” or torque to judge

nut tightness. Since some impact wrenches are capable of high output, it is important

to develop a familiarity with the impact wrench to avoid damaging or fracturing bolts or

coupling bolt pads during installation. DO NOT continue to use an impact wrench after

the visual installation guidelines for the coupling are achieved.

If the battery is drained or if the impact wrench is under-powered, a new impact wrench

must be used to ensure the visual installation guidelines for the coupling are achieved.

Perform trial assemblies with the impact wrench and socket or torque wrenches to help

determine the capability of the impact wrench. Using the same method, periodically

check additional nuts throughout the system installation.

For safe and proper use of impact wrenches, always refer to the impact wrench

manufacturer’s operating instructions. In addition, verify that proper impact grade

sockets are being used for coupling installation.

Page 72: Victaulic I-100 Field Installation Handbook.pdf

I-100_65

INSTALLATION INSPECTION

Proper pipe preparation and coupling installation is essential for maximum joint

performance.

1. The pipe OD and groove dimensions must be within the tolerance published in

current Victaulic grooving specifications.

Unless stated otherwise in specific product instructions, Victaulic grooved pipe

couplings be assembled properly with the bolt pads in firm, metal-to-metal

contact.

3. The housings’ keys must be engaged completely in both grooves.

The gasket must be slightly compressed, which adds to the strength of the seal.

Typical Angle Bolt Pad Typical Flat Bolt Pad

Page 73: Victaulic I-100 Field Installation Handbook.pdf

I-100_66

When the OD of the pipe or fitting is below tolerance, engagement of the housings’ key

sections is lowered considerably.

G

Key

Undersized Pipe/Fitting

Exaggerated for Clarity

Additionally, there is little or no added compression of the gasket. The increased gap “G”

between the pipe and the housing may also result in gasket extrusion. These factors can

contribute to reduced gasket life and joint leakage.

Oversized Pipe/Fitting

KeyShoulder

Exaggerated for Clarity

When the OD of the pipe or fitting exceeds the allowable tolerance, engagement of the

housings’ key sections is increased to the point that the shoulder can grip onto the pipe.

This can result in reduced linear or angular movement. Under these conditions, the

bolt pads may not join with metal-to-metal contact, the gasket can possibly extrude, the

working pressure of the joint can be reduced, and the life of the gasket can be reduced.

G

Shallow Groove

Key

Exaggerated for Clarity

A groove that is not deep enough will have the same effect as the conditions described

in the “Installations with Undersized Pipes/Fittings” section above. In addition, this

condition may prevent couplings from being fully assembled, leaving gaps between the

bolt pad connections.

Page 74: Victaulic I-100 Field Installation Handbook.pdf

SmallSpace

KeyShoulder

Pipe with Deep Grooves – Figure 1

Exaggerated for Clarity

G

Pipe with Deep Grooves – Figure 2

LargeSpace

Key

Exaggerated for Clarity

A groove that is too deep will allow the coupling to shift so that one housing will have full

key engagement (Figure 1 above) and the other housing will have significantly reduced

key engagement (Figure 2 above). This will have the same effect as the conditions

described in the “Installations with Undersized Pipe/Fittings” section. Additionally, roll

grooving pipe to an undersized dimension may overstress and weaken the pipe wall. Cut

grooving pipe to an undersized dimension will result in insufficient wall thickness under

the groove.

Eccentric Groove

Key

Exaggerated for Clarity

Eccentric grooves generally occur because of out-of-round pipe that is grooved with a

stationary tool bit (such as a lathe). Tools that rotate the pipe, rather than rotate around

the pipe, may affect this condition. In addition, this can occur when roll grooving pipe

with large wall thickness variations. An eccentric groove means that the groove is too

shallow on one side and too deep on the other. This may lead to a combination of the

conditions outlined in the “Installations with Oversized Pipes/Fittings” section and the

“Installations on Pipes with Shallow Grooves” section.

Page 75: Victaulic I-100 Field Installation Handbook.pdf

I-100_68

Gap is notallowable

Angle PadContact

Offsets

Offsets Equal offsetsat both pairsof bolt pads

(Illustrations are exaggerated for clarity)

Unless stated otherwise in specific product installation instructions, Victaulic grooved

pipe couplings be assembled with the bolt pads in firm metal-to-metal contact.

The only exceptions are couplings that have torque values specified. Any specified

torque values must be achieved; however, firm metal-to-metal contact may not occur

at the coupling bolt pads when the torque requirement is reached. Always refer to the

installation instructions for the specific product. Any questions regarding an installation

can be directed to Victaulic by calling 1-800-PICK VIC.

1. Make sure coupling keys are engaged in the grooves. Coupling keys must not rest

on the outside surface of the pipe.

Make sure the bolts have been tightened fully.

3. Make sure the gasket is not pinched. Pinched gaskets must be replaced

immediately. Gaskets must be lubricated to prevent gasket pinching. For complete

lubrication requirements, refer to the installation instructions for the specific coupling.

Make sure oversized pipe or fittings were not used.

5. Make sure the groove conforms to Victaulic specifications. If the groove is shallow,

groove the pipe to Victaulic specifications. If the groove is too deep, discard that section

of pipe, and groove another section to Victaulic specifications.

Always re-inspect joints before and after the field test to identify points of possible failure.

Look for gaps at the bolt pads and/or keys that ride up on the shoulders. If any of these

conditions exist, depressurize the system, and replace any questionable joints.

NOTICE

instructions.

critical to ensure maximum system reliability.

Page 76: Victaulic I-100 Field Installation Handbook.pdf

I-100_69

Installation Instructions

Coupling

Page 77: Victaulic I-100 Field Installation Handbook.pdf

Style 009H - FireLock EZ™ Rigid Coupling

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

1. DO NOT DISASSEMBLE THE Style 009H Couplings

are installation ready. These couplings

are designed so that the installer does

not need to remove the bolts and nuts

for installation. This design facilitates

installation by allowing the installer to

directly install the grooved end of pipe/

mating components into the coupling.

The outside surface of the pipe/

mating component, between the groove

and the pipe/mating component end, must

be smooth and free from indentations,

projections (including weld seams), and

roll marks to ensure a leak-tight seal. All

oil, grease, loose paint, dirt, and cutting

particles must be removed. Measurements

taken across grooved pipe/mating

component ends must not exceed the

maximum allowable flare diameter. Refer to

current Victaulic grooving specifications for

the maximum allowable flare diameter.

Check the

gasket to make sure it is suitable for

the intended service. The color code

identifies the gasket grade. Refer to the

on the following page for details

concerning operating temperatures and

other requirements. Refer to the “Gasket

Selection” section of this manual for the

color code chart.

Never leave a Style 009H Coupling partially assembled. A partially assembled Style 009H Coupling poses a drop h azard.

mating component ends and the

attempting to insert the grooved

into the coupling.

could cause serious personal injury and/or property damage.

Page 78: Victaulic I-100 Field Installation Handbook.pdf

Assemble

the joint by inserting the grooved end of a

pipe/mating component into each opening

of the coupling. The ends of the grooved

pipe/mating components must be inserted

into the coupling until contact with the

center leg of the gasket occurs. A visual

check is required to ensure the coupling

keys align with the grooves in the pipe/

mating components. The coupling

may be rotated to ensure the gasket is

seated properly.

When assembling Style 009H

Couplings onto end caps, take additional

care to ensure the end cap is seated

fully against the center leg of the gasket.

DO NOT use Non-Victaulic fittings with

Style 009H Couplings. Use only FireLock

No. 006 End Caps containing the “EZ”

marking on the inside face or No. 60 End

Caps containing the “QV EZ” marking on

the inside face.

For Victaulic rigid, angle-bolt-pad couplings, the nuts must be tightened evenly by alternating sides until metal-to-metal c ontact occurs at the bolt pads.For Victaulic rigid, angle-bolt-pad

present at the bolt pads.

openings during tightening.

personal injury, and property damage.

NOTICE

®

sheet.

only.

enhance sealing capabilities on all adverse pipe conditions. Pipe condition and

instructions.

Page 79: Victaulic I-100 Field Installation Handbook.pdf

Tighten the

nuts evenly by alternating sides until

metal-to-metal contact occurs at the

angle bolt pads. Make sure the housings’

keys completely engage the grooves and

the offsets are equal at the bolt pads. To

ensure a rigid joint, equal and positive

offsets are preferred. It is important

to tighten the nuts evenly to prevent gasket

pinching. An impact wrench or standard

socket wrench can be used to bring the

bolt pads into metal-to-metal contact.

Refer to the “Impact Wrench Usage

Guidelines” section in this manual.

GOOD

BAD

6. Visually inspect the bolt pads at each

joint to ensure metal-to-metal contact is

achieved.

NOTICE

critical. Improperly assembled joints

is placed in service.

POSITIVE OFFSET WITH BOLT PAD

CONTACT

WITH BOLT PAD CONTACT

BAD

OFFSET

BOLT PAD

tightened.

SizeNut Size

Size

Nominal Sizeinches or mm

Actual Pipe Outside

Diameterinches/mm

inches/Metric

inches/mm

1 ¼ – 41.660 – 4.500 3⁄8 11⁄1642.4 – 114.3 M10 17

76.1 – 108.0 mm

3.000 – 4.250 3⁄8 11⁄1676.1 – 108.0 M10 17

133.0 – 139.7 mm

5.250 – 5.500 ½ ¾133.0 – 139.7 M12 18

55.563 ½ ¾141.3 M12 18

159.0 – 165.1 mm

6.250 – 6.500 5⁄8 15⁄16159.0 – 165.1 M16 24

6 – 86.625 – 8.625 5⁄8 15⁄16168.3 – 219.1 M16 24

Page 80: Victaulic I-100 Field Installation Handbook.pdf

Style 009H Couplings

Since the coupling housings conform to

the outside diameter of the pipe/mating

component during an initial installation,

direct installation of the pipe/mating

components into the coupling may not

be possible upon re-installation. If this is

the case, refer to the following steps for

re-installing the coupling.

1. Make sure the system is

depressurized and drained completely

before attempting to disassemble any couplings.

Follow steps 2 – 3 on page 70.

Apply a thin coat of Victaulic lubricant or

silicone lubricant to the gasket sealing lips

and exterior. It is normal for the gasket

surface to have a hazy white appearance

after it has been in service.

Insert the grooved

end of a pipe/mating component into the

gasket until it contacts the center leg of the

gasket.

Align the two grooved ends of the pipe/

mating components. Insert the other pipe/

mating component end into the gasket

until it contacts the center leg of the

gasket. Make sure no portion of the

gasket extends into the groove of either

pipe/mating component.

One

bolt can be inserted into the housings

with the nut threaded loosely onto the bolt

to allow for the “swing-over” feature, as

shown above. The nut should be

backed off no further than flush with the

end of the bolt.

Install the

housings over the gasket. Make sure the

housings’ keys engage the grooves properly

on both pipes/mating components.

Install the remaining bolt, and thread the

nut finger-tight onto the bolt. Make

sure the oval neck of each bolt seats

properly in the bolt hole.

Follow steps 5 and

6 on the previous page to complete the

assembly.

Page 81: Victaulic I-100 Field Installation Handbook.pdf

1. DO NOT DISASSEMBLE THE Style 107H Couplings are

installation ready. The coupling is designed

so that the installer does not need to

remove the bolts and nuts for installation.

This design facilitates installation by

allowing the installer to directly install the

grooved end of pipe/mating components

into the coupling.

The outside surface of the pipe/

mating component, between the groove

and the pipe/mating component end, must

be smooth and free from indentations,

projections (including weld seams), and

roll marks to ensure a leak-tight seal. All

oil, grease, loose paint, dirt, and cutting

particles must be removed. Measurements

taken across grooved pipe/mating

component ends must not exceed the

maximum allowable flare diameter. Refer to

current Victaulic grooving specifications for

the maximum allowable flare diameter.

Check the gasket

to make sure it is suitable for the intended

service. The color code identifies the

gasket grade. Refer to the “Gasket

Selection” section of this manual for the

color code chart.

installation.

QuickVic™ Rigid Coupling for Steel Pipe

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

Page 82: Victaulic I-100 Field Installation Handbook.pdf

Apply a thin

coat of Victaulic Lubricant or silicone

lubricant only to the sealing lips of the

gasket interior. The gasket exterior

is supplied with a factory-applied lubricant,

so there is no need to remove the gasket

from the housings to apply additional

lubricant to the exterior surface.

partially assembled. A partially

poses a drop h azard.

mating component ends and the

attempting to insert the grooved

into the coupling.

could cause serious personal injury and/or property damage.

Assemble the

joint by inserting the grooved end of a

pipe/mating component into each opening

of the coupling. The ends of the grooved

pipe/mating components must be inserted

into the coupling until contact with the

center leg of the gasket occurs. A visual

check is required to ensure the coupling

keys align with the grooves in the pipe/

mating components. The coupling

may be rotated to ensure the gasket is

seated properly.

When assembling Style 107H

Couplings onto end caps, take additional

care to ensure the end cap is seated fully

against the center leg of the gasket. DO

NOT use non-Victaulic fittings with Style

107H Couplings. Use only Victaulic No.

60 end caps containing the “QV” or “QV/

EZ” markings on the inside face. Victaulic

No. 460-SS stainless steel end caps shall

not be used with Style 107H Couplings.

No. 460-SS end caps must be used only

with Style 89 Rigid Couplings for stainless

steel pipe.

For Victaulic rigid, angle-bolt-pad couplings, the nuts must be tightened evenly by alternating sides until metal-to-metal c ontact occurs at the bolt pads.For Victaulic rigid, angle-bolt-pad

present at the bolt pads.

openings during tightening.

personal injury, and property damage.

Page 83: Victaulic I-100 Field Installation Handbook.pdf

Tighten the nuts

evenly by alternating sides until metal-

to-metal contact occurs at the angle

bolt pads. Make sure the housings’ keys

completely engage the grooves and the

offsets are equal at the bolt pads. To

ensure a rigid joint, equal and positive

offsets are preferred. It is important

to tighten the nuts evenly to prevent gasket

pinching. An impact wrench or standard

socket wrench can be used to bring the

bolt pads into metal-to-metal contact.

Refer to the “Impact Wrench Usage

Guidelines” section.

GOOD

BAD

Visually inspect the bolt pads at each

joint to ensure metal-to-metal contact is

achieved.

NOTICE

critical. Improperly assembled joints

is placed in service.

POSITIVE OFFSET WITH BOLT PAD

CONTACT

WITH BOLT PAD CONTACT

BAD

OFFSET

BOLT PAD

tightened.

Page 84: Victaulic I-100 Field Installation Handbook.pdf

Since the coupling housings conform to

the outside diameter of the pipe/mating

component during an initial installation,

direct installation of the pipe/mating

components into the coupling may not

be possible upon re-installation. If this is

the case, refer to the following steps for

re-installing the coupling.

1. Make sure the system is

depressurized and drained completely

before attempting to disassemble any

couplings.

Follow steps 2 – 3 on page 74.

Apply a thin

coat of Victaulic Lubricant or silicone

lubricant to the gasket sealing lips and

exterior. It is normal for the gasket surface

to have a hazy white appearance after it

has been in service.

Pipe End

Center Leg of Gasket

Insert the grooved

end of a pipe/mating component into the

gasket until it contacts the center leg of the

gasket.

Align the two grooved ends of the pipe/

mating components. Insert the other pipe/

mating component end into the gasket

until it contacts the center leg of the

gasket. Make sure no portion of the

gasket extends into the groove of either

pipe/mating component.

Size Nut Size

Nominal Sizeinches or mm

Actual Pipe Outside Diameter

inches/mminches/Metric

inches/mm

2 - 2 ½2.375 - 2.875 3⁄8 11⁄16

60.3 - 73.0 M10 17

76.1 mm3.000 3⁄8 11⁄1676.1 M10 17

3 - 53.500 - 5.563 ½ 7⁄888.9 - 141.3 M12 22

139.7 mm5.500 ½ 7⁄8139.7 M12 22

165.1 mm6.500 5⁄8 1 1⁄16165.1 M16 27

6 - 86.625 - 8.625 5⁄8 1 1⁄16168.3 - 219.1 M16 27

Page 85: Victaulic I-100 Field Installation Handbook.pdf

One

bolt can be inserted into the housings

with the nut threaded loosely onto the bolt

to allow for the “swing-over” feature, as

shown above. The nut should be

backed off no further than flush with the

end of the bolt.

Install the

housings over the gasket. Make sure the

housings’ keys engage the grooves properly

on both pipes/mating components.

Install the remaining bolt, and thread the

nut finger-tight onto the bolt. Make

sure the oval neck of each bolt seats

properly in the bolt hole.

Follow steps 6 and

7 on page 76 to complete the assembly.

Page 86: Victaulic I-100 Field Installation Handbook.pdf

1. DO NOT DISASSEMBLE THE Style 177 Couplings are

installation ready. The coupling is designed

so that the installer does not need to

remove the bolts and nuts for installation.

This design facilitates installation by

allowing the installer to directly install the

grooved end of pipe/mating components

into the coupling.

The outside surface of the pipe/

mating component, between the groove

and the pipe/mating component end, must

be smooth and free from indentations,

projections (including weld seams), and

roll marks to ensure a leak-tight seal. All

oil, grease, loose paint, dirt, and cutting

particles must be removed. Measurements

taken across grooved pipe/mating

component ends must not exceed the

maximum allowable flare diameter. Refer to

current Victaulic grooving specifications for

the maximum allowable flare diameter.

Color Code

Check the gasket

to make sure it is suitable for the intended

service. The color code identifies the

gasket grade. Refer to the “Gasket

Selection” section of this manual for the

color code chart.

installation.

QuickVic™ Flexible Coupling for Steel Pipe

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

Page 87: Victaulic I-100 Field Installation Handbook.pdf

I-100_80

Apply a thin

coat of Victaulic Lubricant or silicone

lubricant only to the sealing lips of the

gasket interior. The gasket exterior

is supplied with a factory-applied lubricant,

so there is no need to remove the gasket

from the housings to apply additional

lubricant to the exterior surface.

partially assembled. A partially

poses a drop h azard.

mating component ends and the

attempting to insert the grooved

into the coupling.

could cause serious personal injury and/or property damage.

Assemble the

joint by inserting the grooved end of a

pipe/mating component into each opening

of the coupling. The ends of the grooved

pipe/mating components must be inserted

into the coupling until contact with the

center leg of the gasket occurs. A visual

check is required to ensure the coupling

keys align with the grooves in the pipe/

mating components. The coupling

may be rotated to ensure the gasket is

seated properly.

When assembling Style 177

Couplings onto end caps, take additional

care to ensure the end cap is seated fully

against the center leg of the gasket. DO

NOT use non-Victaulic fittings with Style

177 Couplings.

Couplings contain a centering

important to tighten the nuts evenly by alternating sides until metal-to-metal c ontact occurs at the bolt pads. The middle section

openings during tightening.

personal injury, and property damage.

Page 88: Victaulic I-100 Field Installation Handbook.pdf

I-100_81

Tighten the nuts

evenly by alternating sides until metal-

to-metal contact occurs at the bolt pads.

The middle section of the bolt pad mating

surfaces must be in full metal-to-metal

contact to ensure a properly assembled

joint. Make sure the housings’ keys engage

the grooves completely during tightening.

Middle Section of Bolt

Pad Mating Surface

It is possible to bring the outside

sections of the bolt pads into metal-to-

metal contact without having metal-to-

metal contact at the middle section of the

bolt pad mating surfaces. Even tightening

of the nuts is required to bring the entire

bolt pad sections into metal-to-metal

contact. Refer to the graphics on the

following page for details.

In addition, it is important to tighten the

nuts evenly by alternating sides to prevent

gasket pinching. An impact wrench or

standard socket wrench can be used to

bring the bolt pads into metal-to-metal

contact. Refer to the “Impact Wrench

Usage Guidelines” section.

GOOD

BAD

Visually inspect the bolt pads at each

joint to ensure metal-to-metal contact

is achieved across the entire bolt pad

section.

Page 89: Victaulic I-100 Field Installation Handbook.pdf

NOTICE

critical. Improperly assembled joints

is placed in service.

BAD

BOLT PAD

SECTION

Size Nut Size

Nominal Sizeinches/mm

Actual PipeOutside Diameter

inches/mminches/Metric

inches/mm

2 – 2 ½2.375 – 2.875 3⁄8 11⁄16

60.3 – 73.0 M10 17

76.1 mm3.000 3⁄8 11⁄1676.1 M10 17

3 – 53.500 – 5.563 ½ 7⁄888.9 – 141.3 M12 22

139.7 mm5.500 ½ 7⁄8139.7 M12 22

6 – 86.625 – 8.625 5⁄8 1 1⁄16168.3 – 219.1 M16 27

Page 90: Victaulic I-100 Field Installation Handbook.pdf

I-100_83

Since the coupling housings conform to

the outside diameter of the pipe/mating

component during an initial installation,

direct installation of the pipe/mating

components into the coupling may not

be possible upon re-installation. If this is

the case, refer to the following steps for

re-installing the coupling.

1. Make sure the system is

depressurized and drained completely

before attempting to disassemble any

couplings.

Follow steps 2 – 3 on page 79.

Apply a thin

coat of Victaulic Lubricant or silicone

lubricant to the gasket sealing lips and

exterior. It is normal for the gasket surface

to have a hazy white appearance after it

has been in service.

Insert the grooved

end of a pipe/mating component into the

gasket until it contacts the center leg of the

gasket.

Align the two grooved ends of the pipe/

mating components. Insert the other pipe/

mating component end into the gasket

until it contacts the center leg of the

gasket. Make sure no portion of the

gasket extends into the groove of either

pipe/mating component.

One

bolt can be inserted into the housings

with the nut threaded loosely onto the bolt

to allow for the “swing-over” feature, as

shown above. The nut should be

backed off no further than flush with the

end of the bolt.

Install the

housings over the gasket. Make sure the

housings’ keys engage the grooves properly

on both pipes/mating components.

Page 91: Victaulic I-100 Field Installation Handbook.pdf

Install the remaining bolt, and thread the

nut finger-tight onto the bolt. Make

sure the oval neck of each bolt seats

properly in the bolt hole.

Follow steps 6

and 7 of the “Instructions for the Initial

Installation of Style 177 Couplings” section

to complete the assembly.

Page 92: Victaulic I-100 Field Installation Handbook.pdf

I-100_85

Standard

Installation Instructions

Stainless Steel Pipe

Page 93: Victaulic I-100 Field Installation Handbook.pdf

I-100_86

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

The outside

surface of the pipe, between the groove

and the pipe end, must be smooth

and free from indentations, projections

(including weld seams), and roll marks

to ensure a leak-tight seal. All oil, grease,

loose paint, dirt, and cutting particles must

be removed.

NOTICE

system, additional lubrication

that are installed at or continuously

Check the gasket to make sure it is suitable

for the intended service. Apply a thin coat

of Victaulic Lubricant or silicone lubricant

to the gasket sealing lips and exterior.

pinching/tearing during installation.

Position the

gasket over the pipe end. Make sure the

gasket does not overhang the pipe end.

Page 94: Victaulic I-100 Field Installation Handbook.pdf

Pipe End

Exaggerated for Clarity

It may be easier to turn the gasket

inside out, then slide it over the pipe end.

Make sure the gasket does not overhang

the pipe end.

Align and bring

the two pipe ends together. Slide the

gasket into position and center it between

the groove in each pipe end. Make sure

no portion of the gasket extends into the

groove in either pipe end.

Roll the gasket into

position and center it between the groove

in each pipe end. Make sure no portion of

the gasket extends into the groove in either

pipe end.

Page 95: Victaulic I-100 Field Installation Handbook.pdf

I-100_88

Style 005 - FireLock® Rigid Coupling

Zero-Flex® Rigid Coupling (12-inch/323.9-mm and Smaller Sizes)

Rigid Stainless Steel Coupling for Stainless Steel Pipe (4-inch/114.3-mm

and Smaller Sizes)

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

NOTICE

Insert

one bolt into the housings, and thread the

nut loosely onto the bolt to allow for the

“swing-over” feature, as shown above.

The nut should be backed off no

further than flush with the end of the bolt.

installing the housings.

Using the

“swing-over” feature, install the housings

over the gasket. Make sure the housings’

keys engage the grooves completely on

both pipe ends.

NOTICE

Apply an anti-seize compound to

the nuts.

Page 96: Victaulic I-100 Field Installation Handbook.pdf

I-100_89

Install the remaining bolt, and

thread the nut finger-tight onto the bolt.

Make sure the oval neck of each

bolt seats properly in the bolt hole.

Angle PadContact

Offsets

Offsets

Equal offsetsat both pairsof bolt pads

Exaggerated for clarity

Tighten all nuts

evenly by alternating sides until metal-

to-metal contact occurs at the angle

bolt pads. Make sure the housings’ keys

engage the grooves completely on both

pipe ends and that the offsets are equal at

the bolt pads. Equal, positive offsets are

necessary to ensure a rigid joint (refer to

the example above). It is important

to tighten all nuts evenly to prevent gasket

pinching.

For Victaulic rigid, angle-bolt-pad couplings, the nuts must be tightened evenly by alternating sides until metal-to-metal c ontact occurs at the bolt pads.For Victaulic rigid, angle-bolt-pad

present at the bolt pads.

openings during tightening.

personal injury, and property damage.

GOOD

BAD

6. Visually inspect the bolt pads at each

joint to ensure metal-to-metal contact is

achieved.

The Style 489 coupling assembly

has a torque requirement (refer to the table

below).

SizeTorque

Nominal Sizeinches or mm

Actual Pipe Outside

Diameterinches/mm

1 ½ – 2 ½1.900 – 2.875 18

48.3 – 73.0 25

76.1 mm3.000 1876.1 25

3 – 43.500 – 4.500 4588.9 – 114.3 61

Page 97: Victaulic I-100 Field Installation Handbook.pdf

I-100_90

Size Style 005

NominalSize

inches or mm

Actual PipeOutside

Diameterinches/

mm

Nut Sizeinches/Metric

Sizeinches/

mm

Nut Sizeinches/Metric

Sizeinches/

mm

Nut Sizeinches/Metric

Sizeinches/

mm

11.315

— —3⁄8 11⁄16

— —33.7 M10 17

1 ¼1.660 3⁄8 9⁄16 3⁄8 11⁄16

— —42.4 M10 15 M10 17

1 ½1.900 3⁄8 9⁄16 3⁄8 11⁄16 3⁄8 11⁄1648.3 M10 15 M10 17 M10 17

22.375 3⁄8 9⁄16 ½ 7⁄8 3⁄8 11⁄1660.3 M10 15 M12 22 M10 17

2 ½2.875 3⁄8 9⁄16 ½ 7⁄8 3⁄8 11⁄1673.0 M10 15 M12 22 M10 17

76.1 mm3.000 3⁄8 9⁄16 ½ 7⁄8 3⁄8 11⁄1676.1 M10 15 M12 22 M10 17

33.500 3⁄8 9⁄16 ½ 7⁄8 ½ 7⁄888.9 M10 15 M12 22 M12 22

3 ½4.000

— —½ 7⁄8

— —101.6 M12 22

44.500 3⁄8 9⁄16 ½ 7⁄8 ½ 7⁄8114.3 M10 15 M12 22 M12 22

108.0 mm 4.250 3⁄8 9⁄16 ½ 7⁄8 — —108.0 M10 15 M12 22

55.563 ½ ¾ 5⁄8 1 1⁄16

— —141.3 M12 18 M16 27

133.0 mm5.250 ½ ¾ 5⁄8 1 1⁄16

— —133.0 M12 18 M16 27

139.7 mm5.500 ½ ¾ 5⁄8 1 1⁄16

— —139.7 M12 18 M16 27

66.625 ½ ¾ 5⁄8 1 1⁄16

— —168.3 M12 18 M16 27

159.0 mm6.250 ½ ¾ 5⁄8 1 1⁄16

— —159.0 M12 18 M16 27

165.1 mm6.500 ½ ¾ 5⁄8 1 1⁄16

— —165.1 M12 18 M16 27

88.625 ¾ 1 ¼ ¾ 1 ¼

— —219.1 M20 32 M20 32

8 (005H)8.625 5⁄8 15⁄16

— — — —219.1 M16 24

1010.750

— —7⁄8 1 7⁄16

— —273.0 M22 36

1212.750

— —7⁄8 1 7⁄16

— —323.9 M22 36

200A (JIS)— 5⁄8 15⁄16 ¾ 1 ¼

— —216.3 M16 24 M20 32

250A (JIS)—

— —7⁄8 1 7⁄16

— —267.4 M22 36

300A (JIS)—

— —7⁄8 1 7⁄16

— —318.5 M22 36

Page 98: Victaulic I-100 Field Installation Handbook.pdf

I-100_91

Zero-Flex Rigid Coupling (14-inch/355.6-mm and Larger

Sizes)

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

Assemble the segments loosely (nuts

should be flush with ends of bolts), leaving

one bolt and nut off to allow for the “swing-

over” feature, or assemble the segments

loosely into two equal halves (whichever

permits easier handling).

Using the

“swing-over” feature, install the housings

over the gasket. Make sure the housings’

keys engage the grooves completely on

both pipe ends.

Page 99: Victaulic I-100 Field Installation Handbook.pdf

installing the housings.

While supporting the weight of the

assembly, install the remaining bolt, and

thread the nut finger-tight onto the bolt.

Make sure the oval neck of each

bolt seats properly in the bolt hole.

Angle PadContact

Offsets

Offsets

Exaggerated for clarity

Tighten all

nuts evenly by alternating bolt pads until

metal-to-metal contact occurs at the angle

bolt pads. Make sure the housings’ keys

engage the grooves completely on both

pipe ends and that the offsets are equal at

the bolt pads. Equal, positive offsets are

necessary to ensure a rigid joint (refer to

the example above). It is important

to tighten all nuts evenly to prevent gasket

pinching.

Apply torque

to each nut with a torque wrench. Refer

to the following table for the torque

requirement. If the required torque

is achieved before metal-to-metal contact

occurs at the angle bolt pads, check the

assembly by referring to the requirements

in the “Installation Inspection” section.

6. Inspect the bolt pads of each

coupling to ensure proper assembly is

achieved.

SizeTorque

Nominal Size

inches

Actual Pipe Outside Diameter

inches/mm

14 – 1814.000 – 18.000 250

355.6 – 457 339

20 – 2420.000 – 24.000 300

508 – 610 407

the nuts must be tightened evenly by alternating sides until metal-to-metal c ontact occurs at the bolt pads and the required torque value is achieved.For Victaulic rigid, angle-bolt-pad

present at the bolt pads.

openings during tightening.

personal injury, and property damage.

Size

NominalSize

inches

Actual PipeOutside

Diameterinchesmm

Nut Sizeinches/Metric

Sizeinches/

mm

14 – 1814.000 – 18.000 7⁄8 1 7⁄16

355.6 – 457 M22 36

20 – 2420.000 – 24.000 1 1 5⁄8

508 – 610 M24 41

Page 100: Victaulic I-100 Field Installation Handbook.pdf

I-100_93

Rigid Coupling (12-inch/323.9-mm and Smaller Sizes)

Style 89 - Rigid Coupling for Stainless Steel Pipe

Rigid Stainless Steel Coupling for Stainless Steel Pipe (139.7-mm and

Larger Sizes)

Rigid Stainless Steel Coupling for Duplex and Super Duplex Pipe

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

NOTICE

NOTICE

® design, the

Tongue Recess Tongue

Exaggerated for clarity

Install

the housings over the gasket with the

tongue and recess features mated

properly (tongue in recess). Make sure

the housings’ keys engage the grooves

completely on both pipe ends.

installing the housings.

NOTICE

nuts, apply an anti-seize compound

the nuts.

Install

the bolts, and thread a nut finger-tight onto

each bolt. Make sure the oval neck

of each bolt seats properly in the bolt hole.

Page 101: Victaulic I-100 Field Installation Handbook.pdf

Tighten all nuts

evenly by alternating sides. Make sure

the housings’ keys engage the grooves

completely on both pipe ends. Apply

torque to each nut with a torque wrench.

Refer to the following table for the torque

requirement. It is important to

tighten the nuts evenly to prevent gasket

pinching.

NOTICE

nuts must be tightened evenly by alternating sides until metal-to-metal contact occurs at the bolt pads.

GOOD

BAD

5. Inspect the bolt pads at each joint to

ensure proper assembly is achieved.

assembly.

and property damage.

Page 102: Victaulic I-100 Field Installation Handbook.pdf

I-100_95

Size

NominalSize

inches or mm

Actual PipeOutside

Diameterinches/mm

Style 89

2 – 32.375 – 3.500 60 – 80 60 – 90

—60 – 90

60.3 – 88.9 81 – 109 80 – 120 80 – 120

76.1 mm3.000

—60 – 90

—60 – 90

76.1 80 – 120 80 – 120

44.500 60 – 80 85 – 125

—85 – 125

114.3 81 – 109 115 – 170 115 – 170

139.7 mm5.500

—175 – 250 75 – 100 75 – 100

139.7 240 – 340 100 – 137 100 – 135

55.563

—175 – 250 85 – 125

—141.3 240 – 340 115 – 170

165.1 mm6.500

—175 – 250 125 – 200 125 – 200

165.1 240 – 340 170 – 275 170 – 275

66.625

†175 – 250 125 – 200 125 – 200

168.3 240 – 340 170 – 275 170 – 275

216.3 mm8.515

—200 – 300 200 – 300

—216.3 275 – 400 275 – 400

88.625

†200 – 300 200 – 300 200 – 300

219.1 275 – 400 275 – 400 275 – 400

267.4 – 318.5 mm10.528 – 12.539

—250 – 350 200 – 300

—267.4 – 318.5 340 – 475 275 – 400

10 – 1210.750 – 12.750

†250 – 350 200 – 300 200 – 300

273.0 – 323.9 340 – 475 275 – 400 275 – 400

† For 6 – 12-inch/168.3 – 323.9-mm Style HP-70 Couplings, there is no torque requirement. However, the nuts must be tightened evenly by alternating sides until metal-to-metal contact occurs at the bolt pads. It is important to tighten all nuts evenly to prevent gasket pinching.

Size Style 89

NominalSize

inches or mm

Actual PipeOutside

Diameterinches/mm

Nut Size

inches/Metric

Sizeinches/

mm

Nut Size

inches/Metric

Sizeinches/

mm

Nut Size

inches/Metric

Sizeinches/

mm

Nut Size

inches/Metric

Sizeinches/

mm

2 – 32.375 – 3.500 5⁄8 1 1⁄16 5⁄8 1 1⁄16

— —5⁄8 1 1⁄16

60.3 – 88.9 M16 27 M16 27 M16 27

76.1 mm3.000

— —5⁄8 1 1⁄16

— —5⁄8 1 1⁄16

76.1 M16 27 M16 27

44.500 ¾ 1 ¼ ¾ 1 ¼

— —¾ 1 ¼

114.3 M20 32 M20 32 M20 32

139.7 mm5.500

— —¾ 1 ¼ ¾ 1 ¼ ¾ 1 ¼

139.7 M20 32 M20 32 M20 32

55.563

— —¾ 1 ¼ ¾ 1 ¼

— —141.3 M20 32 M20 32

165.1 mm6.500

— —7⁄8 1 7⁄16 7⁄8 1 7⁄16 7⁄8 1 7⁄16

165.1 M22 36 M22 36 M22 36

66.625 7⁄8 1 7⁄16 7⁄8 1 7⁄16 7⁄8 1 7⁄16 7⁄8 1 7⁄16168.3 M22 36 M22 36 M22 36 M22 36

216.3 mm8.515

— —1 1 5⁄8 1 1 5⁄8

— —216.3 M24 41 M24 41

88.625 1 1 5⁄8 1 1 5⁄8 1 1 5⁄8 1 1 5⁄8219.1 M24 41 M24 41 M24 41 M24 41

267.4 – 318.5 mm

10.528 – 12.539— —

1 1 5⁄8 1 1 5⁄8— —

267.4 – 318.5 M24 41 M24 41

10 – 1210.750 – 12.750 1 1 5⁄8 1 1 5⁄8 1 1 5⁄8 1 1 5⁄8273.0 – 323.9 M24 41 M24 41 M24 41 M24 41

Page 103: Victaulic I-100 Field Installation Handbook.pdf

I-100_96

Rigid Coupling (14-inch/355.6-mm and Larger Sizes)

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

handling.

NOTICE

® design, the

Assemble the segments loosely into two

equal halves, as shown above. Allow

clearance between the segments to ease

assembly onto the pipe.

installing the housings.

Install one of the pre-

assembled halves over the gasket. Make

sure the housings’ keys engage the

grooves completely on both pipe ends.

Page 104: Victaulic I-100 Field Installation Handbook.pdf

Install the

second assembly onto the pipe. Make sure

the housings’ keys engage the grooves

completely on both pipe ends. While

supporting the weight of the assembly,

install the remaining bolts, and thread the

nuts finger-tight onto the bolts.

Make sure the oval neck of each bolt seats

properly in the bolt hole.

Tighten all nuts

evenly by alternating sides until metal-

to-metal contact occurs at the bolt pads.

Make sure the housings’ keys engage the

grooves completely. It is important

to tighten all nuts evenly to prevent gasket

pinching.

Apply torque

to each nut with a torque wrench. Refer

to the following table for the torque

requirement. Due to the high torque

requirement, use of a geared torque

multiplier is recommended.

Inspect the bolt pads at each joint to

ensure proper assembly is achieved.

For proper assembly, the nuts must be tightened until metal-to-metal contact occurs at the bolt pads and the required torque values, listed in these instructions, are achieved.

openings during tightening.

personal injury, and property damage.

SizeTorque

NominalSize

inches

Actual PipeOutside

Diameterinches/mm

1414.000 600355.6 814

1616.000 700406.4 949

Size

NominalSize

inches

Actual PipeOutside

Diameterinches/mm

NutSize

inches/Metric

Sizeinches/

mm

14 – 1614.000 – 16.000 1 ¼ 2

355.6 – 406.4 M30 50

Page 105: Victaulic I-100 Field Installation Handbook.pdf

I-100_98

EndSeal® Rigid Coupling

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

EndSeal®

serious personal injury and/or property damage.

NOTICE

The outside

surface of the pipe, between the groove

and the pipe end, must be smooth

and free from indentations, projections

(including weld seams), and roll marks

to ensure a leak-tight seal. All oil, grease,

loose paint, dirt, and cutting particles must

be removed. Pipe must be roll grooved or

EndSeal®

this manual.

Check the gasket to make

sure it is suitable for the intended service.

The Style HP-70ES gasket is molded with a

center leg that fits between the pipe ends.

Apply a thin coat of Victaulic Lubricant or

silicone lubricant to the gasket sealing lips

and exterior.

pinching/tearing during installation.

Insert the

grooved pipe end into the gasket until it

contacts the center leg of the gasket.

Page 106: Victaulic I-100 Field Installation Handbook.pdf

I-100_99

Align and bring

the two pipe ends together. Insert the other

pipe end into the gasket until it contacts

the center leg of the gasket. Make

sure no portion of the gasket extends into

the groove of either pipe.

Tongue Recess Tongue

Exaggerated for clarity

Install

the housings over the gasket with the

tongue and recess features mated

properly (tongue in recess). Make sure

the housings’ keys engage the grooves

completely on both pipe ends.

installing the housings.

Install

the bolts, and thread a nut finger-tight onto

each bolt. Make sure the oval neck

of each bolt seats properly in the bolt hole.

Tighten the nuts

evenly by alternating sides until metal-

to-metal contact occurs at the bolt pads.

Make sure the housings’ keys engage the

grooves completely. It is important

to tighten the nuts evenly to prevent gasket

pinching.

Visually inspect the bolt pads at each

joint to ensure metal-to-metal contact is

achieved.

For proper assembly, the nuts must be tightened until metal-to-metal contact occurs at the bolt pads.

openings during tightening.

personal injury, and/or property damage.

Size

NominalSize

inches

Actual PipeOutside

Diameterinches/mm

NutSize

inches/Metric

Sizeinches/

mm

2 - 32.375 – 3.500 5⁄8 1 1⁄16

60.3 – 88.9 M16 27

44.500 ¾ 1 ¼114.3 M20 32

66.625 7⁄8 1 7⁄16168.3 M22 36

8 – 128.625 – 12.750 1 1 5⁄8219.1 – 323.9 M24 41

Page 107: Victaulic I-100 Field Installation Handbook.pdf

I-100_100

Outlet Coupling

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

NOTICE

In addition, Victaulic #60 End Caps

vacuums may develop.

DO NOT remove this ring, since

The outside

surface of the pipe, between the groove

and the pipe end, must be smooth

and free from indentations, projections

(including weld seams), and roll marks

to ensure a leak-tight seal. All oil, grease,

loose paint, dirt, and cutting particles must

be removed.

Check the gasket to make sure it is suitable

for the intended service. Apply a thin coat

of Victaulic Lubricant or silicone lubricant

to the gasket sealing lips and exterior.

pinching/tearing during installation.

Install the

gasket onto the pipe end so that the lips

on one side cover the area between the

groove and the pipe end. The pipe

end should not contact the reinforcement

ribs inside the gasket.

Page 108: Victaulic I-100 Field Installation Handbook.pdf

I-100_101

Align and bring

the two pipe ends together. Slide the

gasket into position and center it between

the groove in each pipe end. Make sure

no portion of the gasket extends into the

groove in either pipe end.

Install the lower housing (without the

outlet) around the lower portion of the

gasket. Make sure the housings’ keys

engage the grooves completely on both

pipe ends. Tabs are located on

the gasket, which are designed to rest in

the recesses on both the upper and lower

housings. These tabs ensure proper gasket

positioning within the housings.

Install the upper housing over the gasket.

Make sure the housings’ keys engage the

grooves completely on both pipe ends.

Inspect the outlet opening to make sure

the outlet neck of the gasket is positioned

properly in the housing.

Install

the bolts, and thread a nut finger-tight onto

each bolt. Make sure the oval neck

of each bolt seats properly in the bolt hole.

Tighten the nuts

evenly by alternating sides until metal-

to-metal contact occurs at the bolt pads.

Make sure the housings’ keys engage the

grooves completely. It is important

to tighten the nuts evenly to prevent gasket

pinching.

8a. Visually inspect the bolt pads at each

joint to ensure metal-to-metal contact is

achieved.

For proper assembly, the nuts must be tightened until metal-to-metal contact occurs at the bolt pads.

openings during tightening.

personal injury, and property damage.

Page 109: Victaulic I-100 Field Installation Handbook.pdf

Nominal Outlet Size

Nominal inchesActual mm Nut Size

FPTinches/Metric

inches/mm

1 ½ x

½ – 1—

3⁄8 11⁄1648.3 21.3 – 33.7 M10 17

2x

½ – 1 1 3⁄8 11⁄1660.3 21.3 – 33.7 33.7 M10 17

2 ½x

½ – 1—

½ 7⁄873.0 21.3 – 33.7 M12 22

1 ¼ 1 ½ 5⁄8 1 1⁄1642.4 48.3 M16 27

3x

¾ 1 ½ 7⁄888.9 26.9 33.7 M12 22

1 1 ½ 5⁄8 1 1⁄1633.7 48.3 M16 27

4x

¾ 1 ½ 7⁄8114.3 26.9 33.7 M12 22

1 ½ 2 5⁄8 1 1⁄1648.3 60.3 M16 27

6x

1 – 1 ½ 2 ¾ 1 ¼168.3 33.7 – 48.3 60.3 M20 32

Page 110: Victaulic I-100 Field Installation Handbook.pdf

I-100_103

Flexible Coupling

Flexible Coupling - Two Segments for 24-inch/610-mm and Smaller Sizes

Flexible Aluminum Coupling

Flexible Stainless Steel Coupling

Flexible Stainless Steel Coupling for Duplex and Super Duplex Pipe

Flexible Stainless Steel Coupling

Flexible Stainless Steel Coupling for Duplex and Super Duplex Pipe

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

NOTICE

installation steps apply to Styles

listed above.

NOTICE

Install

the housings over the gasket. Make sure

the housings’ keys engage the grooves

completely on both pipe ends. Refer to

the notice above for Styles 475/475DX

Couplings.

installing the housings.

Install

the bolts, and thread a nut finger-tight

onto each bolt. For couplings supplied with

stainless steel hardware, apply an anti-

sieze compound to the bolt threads.

Make sure the oval neck of each bolt seats

properly in the bolt hole.

NOTICEFor

Stainless Steel Couplings

under each nut.

Page 111: Victaulic I-100 Field Installation Handbook.pdf

Size

NominalSize

inches or mm

Actual PipeOutside

Diameterinchesmm

Nut Sizeinches/Metric

Sizeinches/

mm

Nut Sizeinches/Metric

Sizeinches/

mm

Nut Sizeinches/Metric

Sizeinches/

mm

Nut Sizeinches/Metric

Sizeinches/

mm

¾1.050

— —3⁄8 11⁄16 3⁄8 11⁄16

— —26.9 M10 17 M10 17

11.315 3⁄8 11⁄16 3⁄8 11⁄16 3⁄8 11⁄16 3⁄8 11⁄1633.7 M10 17 M10 17 M10 17 M10 17

1 ¼1.660 3⁄8 11⁄16 ½ 7⁄8 3⁄8 11⁄16 3⁄8 11⁄1642.4 M10 17 M12 22 M10 17 M10 17

1 ½1.900 3⁄8 11⁄16 ½ 7⁄8 3⁄8 11⁄16 3⁄8 11⁄1648.3 M10 17 M12 22 M10 17 M10 17

22.375 3⁄8 11⁄16 ½ 7⁄8 3⁄8 11⁄16 3⁄8 11⁄1660.3 M10 17 M12 22 M10 17 M10 17

2 ½2.875 3⁄8 11⁄16 ½ 7⁄8 3⁄8 11⁄16 3⁄8 11⁄1673.0 M10 17 M12 22 M10 17 M10 17

76.1 mm3.000 3⁄8 11⁄16 ½ 7⁄8

— —3⁄8 1 11⁄16

76.1 M10 17 M12 22 M10 17

33.500 ½ 7⁄8 ½ 7⁄8 ½ 7⁄8 ½ 7⁄888.9 M12 22 M12 22 M12 22 M12 22

3 ½4.000 ½ 7⁄8 5⁄8 11⁄16

— — — —101.6 M12 22 M16 27

44.500 ½ 7⁄8 5⁄8 1 1⁄16 5⁄8 1 1⁄16 ½ 7⁄8114.3 M12 22 M16 27 M16 27 M12 22

108.0 mm4.250 ½ 7⁄8 5⁄8 1 1⁄16

— — — —108.0 M12 22 M16 27

Tighten the nuts

evenly by alternating sides until metal-

to-metal contact occurs at the bolt pads.

Make sure the housings’ keys engage the

grooves completely. It is important

to tighten the nuts evenly to prevent gasket

pinching.

For proper assembly, the nuts must be tightened until metal-to-metal contact occurs at the bolt pads.

openings during tightening.

personal injury, and property damage.

GOOD

BAD

5. Visually inspect the bolt pads at each

joint to ensure metal-to-metal contact is

achieved.

Page 112: Victaulic I-100 Field Installation Handbook.pdf

I-100_105

Size

NominalSize

inches or mm

Actual Pipe

OutsideDiameterinchesmm

Nut Sizeinches/Metric

Sizeinches/

mm

Nut Sizeinches/Metric

Sizeinches/

mm

Nut Sizeinches/Metric

Sizeinches/

mm

Nut Sizeinches/Metric

Sizeinches/

mm

127.0 mm5.000 5⁄8 1 1⁄16

— — — — — —127.0 M16 27

55.563 5⁄8 1 1⁄16 ¾ 1 ¼

— — — —141.3 M16 27 M20 32

133.0 mm5.250 5⁄8 1 1⁄16 ¾ 1 ¼

— — — —133.0 M16 27 M20 32

139.7 mm*5.500 5⁄8 1 1⁄16 ¾ 1 ¼

— —½ 7⁄8

139.7 M16 27 M20 32 M12 22

152.4 mm6.000 5⁄8 1 1⁄16

— — — — — —152.4 M16 27

66.625 5⁄8 1 1⁄16 ¾ 1 ¼ 5⁄8# 1 1⁄16#

— —168.3 M16 27 M20 32 M16 27

159.0 mm6.250 5⁄8 1 1⁄16 ¾ 1 ¼

— — — —159.0 M16 27 M20 32

165.1 mm*6.500 5⁄8 1 1⁄16 ¾ 1 ¼

— —5⁄8 1 1⁄16

165.1 M16 27 M20 32 M16 27

203.2 mm8.000 ¾ 1 ¼

— — — — — —203.2 M20 32

8§8.625 ¾ 1 ¼ 7⁄8 1 7⁄16 7⁄8 1 7⁄16

— —219.1 M20 32 M22 36 M22 36

254.0 mm10.000 7⁄8 1 7⁄16

— — — — — —254.0 M22 36

10§10.750

— —1 1 5⁄8 1 1 5⁄8

— —273.0 M24 41 M24 41

304.8 mm12.000 7⁄8 1 7⁄16

— — — — — —304.8 M22 36

12§12.750

— —1 1 5⁄8 1 1 5⁄8

— —323.9 M24 41 M24 41

13½ OD13.000

— —1 1 5⁄8

— — — —342.9 M24 41

200A (JIS)— ¾ 1 ¼ 7⁄8 1 7⁄16

— — — —216.3 M20 32 M22 36

250A (JIS)—

— —1 1 5⁄8

— — — —267.4 M24 41

300A (JIS)—

— —1 1 5⁄8

— — — —318.5 M24 41

14§14.000

— —1 1 5⁄8 1 1 5⁄8

— —355.6 M24 41 M24 41

16§16.000

— —1 1 5⁄8 1 1 5⁄8

— —406.4 M24 41 M24 41

18§18.000

— —1 1⁄8 1 13⁄16 1 1 5⁄8

— —457 M27 46 M24 41

2020.000

— —1 1⁄8 1 13⁄16

— — — —508 M27 46

2424.000

— —1 1⁄8 1 13⁄16

— — — —610 M27 46

* Style 475DX Flexible Stainless Steel Couplings are not available in these sizes # The nut size for 6-inch/168.3-mm Style 77DX Couplings is ¾ inch/M20. The socket size is 1 ¼ inch/ 32 mm. § Style 77DX Couplings are not available in these sizes

Page 113: Victaulic I-100 Field Installation Handbook.pdf

I-100_106

Flexible Coupling - Four or Six Segments for

14-inch/355.6-mm and Larger Sizes

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

Assemble the segments loosely into two

equal halves, as shown above. Allow

clearance between the segments to ease

assembly onto the pipe. For bolt

pads that contain a tongue-and-recess

feature, make sure the housings are

mated, as shown above.

installing the housings.

Install one of the pre-

assembled halves over the gasket. Make

sure the housings’ keys engage the

grooves completely on both pipe ends.

Page 114: Victaulic I-100 Field Installation Handbook.pdf

Install the

second assembly onto the pipe. Make sure

the housings’ keys engage the grooves

completely on both pipe ends. While

supporting the weight of the assembly,

install the remaining bolts, and thread the

nuts finger-tight onto the bolts.

Make sure the oval neck of each bolt seats

properly in the bolt hole.

Tighten all nuts

evenly by alternating sides until metal-

to-metal contact occurs at the bolt pads.

Make sure the housings’ keys engage the

grooves completely. It is important

to tighten all nuts evenly to prevent gasket

pinching.

Visually inspect the bolt pads at each

joint to ensure metal-to-metal contact is

achieved.

For proper assembly, the nuts must be tightened until metal-to-metal contact occurs at the bolt pads.

openings during tightening.

personal injury, and property damage.

Size

NominalSize

inches or mm

Actual Pipe Outside

Diameterinches/mm

NutSize

inches/Metric

Sizeinches/

mm

14 – 1814.000 – 18.000 1 1 5⁄8

355.6 – 457 M24 41

20 – 2420.000 – 24.000 1 1⁄8 1 13⁄16

508 – 610 M27 46

28 – 3028.000 – 30.000 1 1 5⁄8

711 – 762 M24 41

377.0 mm14.842 1 1 5⁄8377.0 M24 41

426.0 mm16.771 1 1 5⁄8426.0 M24 41

480.0 mm18.897 1 1⁄8 1 13⁄16480.0 M27 46

530.0 mm20.866 1 1⁄8 1 13⁄16530.0 M27 46

630.0 mm24.803 1 1⁄8 1 13⁄16630.0 M27 46

Page 115: Victaulic I-100 Field Installation Handbook.pdf

I-100_108

Snap-Joint® Coupling

Snap-Joint® Aluminum Coupling

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

NOTICE

Couplings are used in concrete

design parameters.

pipe used in concrete pumping

the couplings.

loading. These couplings are not

Sound anchoring and lashing practices must be observed.

Install one

side of the hinged housing over the gasket,

making sure the keys engage the grooves.

Swing the other side of the housing into

position. Squeeze the housing to further

center the gasket and seat the housing.

Lift the locking handle to position the nose

in the cradle tab of the opposite housing.

3a. Push the locking handle down firmly

until the entire handle assembly contacts

the coupling housing. The entire handle

assembly must contact the coupling

housing to ensure a properly locked joint.

DO NOT use hammers/heavy

heavy instruments to close the

misalign components.

serious personal injury and/or property damage.

Page 116: Victaulic I-100 Field Installation Handbook.pdf

I-100_109

Size Dimensions inches/mm

Fully Extended

Partially

Asse

mbled

NominalSize

inches

Actual Pipe Outside

Diameterinches/mm

PartiallyAssembled

FullyExtended

11.315 3.38 4.5033.7 85.9 114.3

1 ¼1.660 3.80 4.8842.4 96.5 124.0

1 ½1.900 5.50 7.6348.3 139.7 193.8

22.375 6.25 7.7560.3 158.8 196.9

2 ½2.875 7.16 10.7273.0 181.9 272.3

33.500 7.88 10.2588.9 200.2 260.4

44.500 10.63 12.88114.3 270.0 327.2

55.563 13.66 16.88141.3 347.0 428.8

66.625 14.88 18.38168.3 378.0 466.9

88.625 15.38 18.91219.1 390.7 480.3

Aluminum Coupling

Size Dimensions inches/mm

Fully Extended

Partially

Asse

mbled

NominalSize

inches

Actual PipeOutside

Diameterinches/mm

PartiallyAssembled

FullyExtended

22.375 3.22 4.0660.3 81.8 103.1

1010.750 21.00 23.00273.0 533.4 584.2

attempting to remove any Victaulic piping products.

personal injury and/or property damage.

1. After depressurizing and draining

the piping system, slide a screwdriver or

similar pry tool underneath the locking

handle for leverage during disassembly.

Check the gasket to make sure it is

not damaged. If the gasket is damaged,

it must be replaced with a new, Victaulic-

supplied gasket of a grade that is suitable

for the intended service.

3. Check the housing hinge and locking

handle to make sure they have not become

loosened, distorted, bent, or damaged. If

there is any doubt about the condition of

the coupling, do not reuse.

Follow all installation instructions,

listed in this section, for re-assembly.

Check pipe and groove conditions,

lubricate the gasket, etc.

Page 117: Victaulic I-100 Field Installation Handbook.pdf

I-100_110

Reducing Coupling

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

NOTICEVictaulic #60 End Caps must not

Assembly Washer

telescoping inside larger pipe in

The outside

surface of the pipe, between the groove

and the pipe end, must be smooth

and free from indentations, projections

(including weld seams), and roll marks

to ensure a leak-tight seal. All oil, grease,

loose paint, dirt, and cutting particles must

be removed.

Check the gasket to make

sure it is suitable for the intended service.

Apply a thin coat of Victaulic Lubricant or

silicone lubricant to the gasket sealing lips

and exterior.

pinching/tearing during installation.

Install the

larger opening of the gasket over the larger

pipe end. Make sure no portion of the

gasket extends into the pipe groove.

Page 118: Victaulic I-100 Field Installation Handbook.pdf

I-100_111

Align the

centerlines of the pipes and insert the

smaller pipe end into the gasket. Make

sure no portion of the gasket extends into

the pipe groove.

Install the

housings over the gasket. Make sure the

larger openings of the housings face the

larger pipe and that the housings’ keys

engage the grooves completely on both

pipe ends.

installing the housings.

Install

the bolts, and thread a nut finger-tight onto

each bolt. Make sure the oval neck

of each bolt seats properly in the bolt hole.

Tighten the nuts

evenly by alternating sides until metal-

to-metal contact occurs at the bolt pads.

Make sure the housings’ keys engage the

grooves completely. It is important

to tighten the nuts evenly to prevent gasket

pinching.

Visually inspect the bolt pads at each

joint to ensure metal-to-metal contact is

achieved.

For proper assembly, the nuts must be tightened until metal-to-metal contact occurs at the bolt pads.

openings during tightening.

personal injury, and property damage.

SizeNutSize Size

Nominal Size inches/Actual mm

inches/Metric

inches/mm

2x

1 – 1 ½ 3⁄8 11⁄1660.3 33.7 – 48.3 M10 17

2½x

2 3⁄8 11⁄1673.0 60.3 M10 17

76.1 mm x2 ½ 7⁄860.3 M12 22

3x

2 – 2 ½ ½ 7⁄888.9 60.3 – 73.0 M12 22

76.1 mm½ 7⁄8

M12 22

4x

2 – 3 5⁄8 1 1⁄16114.3 60.3 – 88.9 M16 27

114.3 mm x 76.1 mm5⁄8 1 1⁄16

M16 27

5x

4 ¾ 1 ¼141.3 114.3 M20 32

6x

4 – 5 ¾ 1 ¼168.3 114.3 – 141.3 M20 32

165.1 mm x 114.3 mm¾ 1 ¼

M20 32

8x

6 7⁄8 1 7⁄16219.1 168.3 M22 36

10x

8 1 1 5⁄8273.0 219.1 M24 41

Page 119: Victaulic I-100 Field Installation Handbook.pdf

Large Diameter Coupling

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

NOTICE½ inch/13 mm must

¾

Assemble the segments loosely into two

equal halves, as shown above. Allow

clearance between the segments to ease

assembly onto the pipe.

installing the housings.

Install one of the pre-

assembled halves over the gasket. Make

sure the housings’ keys engage the

grooves completely on both pipe ends.

Install the

second assembly onto the pipe. Make sure

the housings’ keys engage the grooves

completely on both pipe ends. While

supporting the weight of the assembly,

install the remaining bolts, and thread the

nuts finger-tight onto the bolts.

Make sure the oval neck of each bolt seats

properly in the bolt hole.

Page 120: Victaulic I-100 Field Installation Handbook.pdf

I-100_113

Tighten all nuts

evenly by alternating sides until metal-

to-metal contact occurs at the bolt pads.

Make sure the housings’ keys engage the

grooves completely. It is important

to tighten all nuts evenly to prevent gasket

pinching.

Apply 600 ft-lbs/

torque wrench. Due to the high torque

requirement, use of a geared torque

multiplier is recommended.

5a. Visually inspect the bolt pads at

each joint to ensure proper assembly is

achieved.

For proper assembly, the nuts must be tightened until metal-to-metal contact occurs at the bolt pads

openings during tightening.

personal injury, and property damage.

Size

NominalSize

inches

ActualPipe Outside

Diameterinches/mm

NutSize

inches/Metric

Sizeinches/

mm

26 – 3626.000 – 36.000 1 ¼ 2

660.4 – 914 M30 50

4242.000 1 ½ 2 3⁄81067 M36 60

Page 121: Victaulic I-100 Field Installation Handbook.pdf

Vic-Boltless Coupling

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

Install one

side of the hinged housing over the gasket,

making sure the keys engage the grooves.

Swing the other side of the housing into

position. Squeeze the housings to further

center the gasket and seat the housing.

Style 792 Assembly Tool Clearance

13 inches(330 mm)

81⁄8 inches(206 mm)

Style 792 Assembly Tool

Engage the “T” bar of the Style 792

Assembly Tool into the cradles on one side

of the coupling housing. Engage the nose

of the assembly tool into the cradles on the

other side of the coupling housing.

For ease of installing 6-inch/

168.3-mm and larger size couplings,

an extension for the assembly tool

can be used. The extension can be

fabricated from standard ¾-inch/19-mm

steel or aluminum pipe (not to exceed

10-inches/254-mm in length) and can be

slipped over the handgrip of the assembly

tool.

Page 122: Victaulic I-100 Field Installation Handbook.pdf

I-100_115

the assembly tool resists closure or

DO NOT use hammers/heavy instruments to close the assembly

instruments to close the assembly

components.

each coupling.

in serious personal injury and/or property damage.

Push the assembly

tool down firmly to bring the housings

together and to align the holes for the

locking pin.

Make

sure the proper size locking pin is available

(refer to table on this page). Set the locking

pin by inserting the plain end of the pin

into the hole.

Using a

hammer, drive the pin through both holes

in the coupling housings, and set the fluted

notches into the hole. Pin position

should be similar to the permanent pin on

the opposite side of the coupling.

6a. Remove the assembly tool by lifting it

up and away from the coupling.

Size

NominalSize

inches

ActualPipe Outside

Diameterinches/mm

Size

inchesColorCode

22.375

5⁄16 x 1 7⁄8 White60.3

2 ½2.875

3⁄8 x 1 7⁄8 Red73.0

33.500

3⁄8 x 1 7⁄8 Red88.9

44.500

7⁄16 x 2 Yellow114.3

66.625

½ x 2 1⁄16 Green168.3

88.625

5⁄16 x 2 5⁄16 Blue219.1

†Extra Vic-Boltless Coupling locking pins are available in color-coded strips of 10 pins.

Page 123: Victaulic I-100 Field Installation Handbook.pdf

I-100_116

Couplings

attempting to remove any Victaulic piping products.

personal injury and/or property damage.

1. Engage the “T” bar of the Style 792

Assembly Tool into the machined cradles

with the longer pin (not “as-cast” side).

Engage the nose of the tool into the center

cradle. Press the tool down until it hits the

housing. Hold the tool in position.

Using a hammer and a drive pin

punch (or a similar device that is smaller

in diameter than the pin) on the plain end,

drive the locking pin out of the hole to

completely remove it from the coupling.

It may be necessary to rotate the

coupling to gain access to the pin when

the coupling is installed with certain valves

and fittings.

3. Lift the assembly tool up and away

from the coupling. Remove the housings

and the gasket.

Check the gasket to make sure it is

not damaged. If the gasket is damaged,

it must be replaced with a new, Victaulic-

supplied gasket of a grade that is suitable

for the intended service.

5. Check the housing hinge and locking

pin to make sure they have not become

loosened, distorted, bent, or damaged. If

there is any doubt about the condition of

the coupling, do not reuse.

6. Follow all installation instructions,

listed in this section, for re-assembly.

Check pipe and groove conditions,

lubricate the gasket, etc.

Page 124: Victaulic I-100 Field Installation Handbook.pdf

ANSI and ISO 4200-to-JIS Transition Coupling

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

The outside

surface of the pipe, between the groove

and the pipe end, must be smooth

and free from indentations, projections

(including weld seams), and roll marks

to ensure a leak-tight seal. All oil, grease,

loose paint, dirt, and cutting particles must

be removed.

Check the gasket to make

sure it is suitable for the intended service.

Apply a thin coat of Victaulic Lubricant or

silicone lubricant to the gasket sealing lips

and exterior.

pinching/tearing during installation.

Install the

larger opening of the gasket (marked NPS)

over the larger pipe end (NPS side). Make

sure the gasket does not overhang the pipe

end.

Align and bring

the NPS and JIS pipe ends together.

Slide the gasket into position and center

it between the groove in each pipe end. Make sure no portion of the gasket

extends into the groove in either pipe and

that the NPS side of the gasket is facing

the NPS pipe.

Page 125: Victaulic I-100 Field Installation Handbook.pdf

I-100_118

NOTICE

assembly lugs to ensure proper

assembly.

Install the

housings over the gasket. Make sure the

larger openings of the housings (marked

NPS) face the larger pipe (NPS side) and

that the housings’ keys engage the grooves

completely on both pipe ends.

installing the housings.

Install

the bolts, and thread a nut finger-tight onto

each bolt. Make sure the oval neck

of each bolt seats properly in the bolt hole.

Tighten all nuts

evenly by alternating sides until metal-

to-metal contact occurs at the bolt pads.

Make sure the housings’ keys engage the

grooves completely. It is important

to tighten all nuts evenly to prevent gasket

pinching.

Visually inspect the bolt pads at each

joint to ensure metal-to-metal contact is

achieved.

For proper assembly, the nuts must be tightened until metal-to-metal contact occurs at the bolt pads.

openings during tightening.

personal injury, and property damage.

Size Nut Size Size

Nom.Size NPS OD

Metric/inches

mm/inches

200A 219.1 216.3 M20 328 8.625 8.515 ¾ 1¼

250A 273.0 267.4 M22 3610 10.750 10.528 7⁄8 1 7⁄16

300A 323.9 318.5 M22 3612 12.750 12.539 7⁄8 1 7⁄16

Page 126: Victaulic I-100 Field Installation Handbook.pdf

I-100_119

System

® Applications

Installation Instructions

Page 127: Victaulic I-100 Field Installation Handbook.pdf

®

1. Pipe ends shall be visually inspected

in accordance with the requirements listed

in this section.

The front edge of the pipe end

shall be uniform with no concave/convex

surface features that will cause improper

grooving roll tracking and result in

difficulties during coupling assembly (refer

to drawing above).

3. If pipe cut-off is required, Victaulic

recommends the use of a mechanically-

guided pipe cutting tool for proper pipe

end preparation. Free-hand pipe end

cutting is not acceptable.

"S" Max.

Square cut the pipe ends (“S”

dimension shown above) within

1⁄8 inch/3.2 mm.

Photo Showing Pipe withWeld Seam Ground 6 inches/152 mm

Back from Pipe End

Gri

nd

ing

Dir

ec

tio

n

1. Prior to grooving, weld seams must

be ground flush to the pipe surface (inside

diameter and outside diameter). Grind

the weld seam from the pipe end to a

minimum distance of 6 inches/152 mm

back from the pipe end. This area must

be smooth and free from indentations,

projections, and roll marks to ensure a

leak-tight seal. Pipe with external, axial

weld seams can be supported with

Victaulic Adjustable Pipe Stands. However,

the weld seam must be smooth and

rounded and at least three times as wide

as it is high. The weld seam must not

exceed 1⁄8 inch/3 mm in height.

1a. Groove the pipe in accordance with

the Victaulic AGS grooving specifications

in this manual.

WALL STAINLESS STEEL PIPE.

1b. Clean the outside surface of the pipe,

from the groove to the pipe end, to remove

all oil, grease, loose paint, and dirt.

Page 128: Victaulic I-100 Field Installation Handbook.pdf

®

Photo Showing Pipe withWeld Seam Ground 6 inches/152 mm

Back from Pipe End

Gri

nd

ing

Dir

ec

tio

n

1. Prior to welding a Vic-Ring onto

the pipe end, weld seams must be

ground flush to the pipe surface (outside

diameter). Grind the weld seam from the

pipe end to a minimum distance of

6 inches/152 mm back from the pipe end.

This area must be smooth and free from

indentations, projections, and roll marks.

1a. Weld the Vic-Ring onto the pipe end

per the specifications in the applicable

Victaulic publication listed below:

16.11 for Style W07 Rigid Couplings

16.12 for Style W77 Flexible Couplings

16.15 for Style W89 Rigid Couplings.

1b. Clean the outside surface of the

Vic-Rings to remove dirt and other foreign

material.

®

®

Style W07 AGS Rigid Couplings, Style W77 AGS Flexible Couplings, and Style W89 Rigid

Couplings can be installed on carbon steel pipe that is prepared with AGS Vic-Rings. Vic-

Rings must be welded to the carbon steel pipe ends in accordance with current Victaulic

specifications (refer to pipe preparation requirements below). AGS Vic-Rings

CANNOT be welded to stainless steel pipe for use with Style W89 AGS Rigid Couplings.

Page 129: Victaulic I-100 Field Installation Handbook.pdf

®

Rigid Coupling (24-inch/610-mm and Smaller Sizes)

Flexible Coupling (24-inch/610-mm and Smaller Sizes)

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

NOTICE

DO NOT attempt to assemble Style

original-type grooving roll sets.

cause improper assembly and joint

injury and/or property damage.

STAINLESS STEEL PIPE.

Check the gasket

to make sure it is suitable for the intended

service. The color code identifies the

gasket grade. Apply a thin coat of Victaulic

lubricant or silicone lubricant to the gasket

lips, gasket exterior, and the interior

surface of both coupling housings.

Position the

gasket over the pipe end or AGS Vic-Ring.

Make sure the gasket does not overhang

the pipe end or AGS Vic-Ring.

Page 130: Victaulic I-100 Field Installation Handbook.pdf

®

Align and bring

the two pipe ends together. Slide the

gasket into position, and center it between

the groove in each pipe end or AGS Vic-

Ring.

Apply

a thin coat of Victaulic lubricant or silicone

lubricant to the bolt threads. If

stainless steel bolts and nuts are special

ordered, apply an anti-seize compound to

the bolt threads.

installing the housings.

6. Install the

housings over the gasket. Make sure

the housings’ keys engage the groove

completely in each pipe end or AGS

Vic-Ring. Support the segments while

preparing to install the bolts and nuts.

Install the

bolts, and thread a nut finger-tight onto

each bolt. Make sure the oval neck

of each bolt seats properly in the bolt hole.

A washer must be installed under each

nut.

Tighten the nuts

evenly by alternating sides. Make sure

the housings’ keys engage the groove

completely in each pipe end or AGS Vic-

Ring. Continue to tighten the nuts evenly by alternating sides until metal-to-metal

torque value are achieved. Refer to the

“Required Assembly Torques” table on the

following page.

It is important to tighten the nuts

evenly by alternating sides to prevent

gasket pinching. Deep well sockets are

recommended for proper installation due

to the longer bolt lengths associated with

these products. Deep well sockets provide

the full nut engagement that is necessary

during tightening.

PADS INTO METAL-TO-METAL CONTACT

Page 131: Victaulic I-100 Field Installation Handbook.pdf

®

For proper assembly, the nuts must be tightened evenly until metal-to-metal contact occurs at the bolt pads and the required torque values, listed in these instructions, are achieved.

and property damage.

Size

Nominal Size inches

Actual Pipe Outside Diameterinches/mm

14 – 1814.000 – 18.000 250

355.6 – 457 340

20 – 2420.000 – 24.000 375

508 – 610 500

Size

Bolts/Nuts

Nut Size

NominalSize

inches

Actual PipeOutside

Diameterinches/mm inches/Metric inches/mm

14 – 1814.000 – 18.000

21 1 5⁄8

355.6 – 457 M24 41

20 – 2420.000 – 24.000

21 1⁄8 1 13⁄16

508 – 610 M27 46

GOOD BAD

8. Visually inspect the bolt pads at each joint to ensure metal-to-metal contact is

achieved across the entire bolt pad section.

Page 132: Victaulic I-100 Field Installation Handbook.pdf

®

NOTICE

DO NOT attempt to assemble Style

original-type grooving roll sets.

cause improper assembly and joint

injury and/or property damage.

STAINLESS STEEL PIPE.

Check the gasket to make sure it is

suitable for the intended service. The color

code identifies the gasket grade. Apply a

thin coat of Victaulic lubricant or silicone

lubricant to the gasket lips, gasket exterior,

and the interior surface of the coupling

housings.

Position the

gasket over the pipe end or AGS Vic-Ring.

Make sure the gasket does not overhang

the pipe end or AGS Vic-Ring.

Rigid Coupling (26-inch/660-mm and Larger Sizes)

Flexible Coupling (26-inch/660-mm and Larger Sizes)

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

Page 133: Victaulic I-100 Field Installation Handbook.pdf

®

Align and bring

the two pipe ends together. Slide the

gasket into position, and center it between

the groove in each pipe end or AGS Vic-

Ring.

Apply

a thin coat of Victaulic lubricant or silicone

lubricant to the bolt threads. If

stainless steel bolts and nuts are special

ordered, apply an anti-seize compound to

the bolt threads.

NOTICE

the coupling housings to aid in

the coupling housings, mechanical

recommended.

installing the housings.

6. Using a

strapping method, similar to the one shown

in the photos above with the bolts installed

in the bolt holes, install the housings over

the gasket. Make sure the housings’ keys

engage the groove completely in each pipe

end or AGS Vic-Ring.

Page 134: Victaulic I-100 Field Installation Handbook.pdf

®

Install a flat washer (supplied with the

coupling) onto the end of each bolt, and

thread a nut finger-tight onto each bolt.

Make sure the oval neck of each

bolt seats properly in the bolt hole.

Repeat the tightening sequence shown above until the installation requirements in Step 7 are achieved.

Tighten the nuts

evenly by alternating sides (refer to the

graphics in the left column of this page

for the tightening sequence). Make sure

the housings’ keys engage the groove

completely in each pipe end or AGS Vic-

Ring. Continue to tighten the nuts evenly by alternating sides until metal-to-metal

torque value are achieved. Refer to the

“Required Assembly Torques” table on the

following page.

It is important to tighten the nuts

evenly by alternating sides to prevent

gasket pinching. Deep well sockets are

recommended for proper installation due

to the longer bolt lengths associated with

these products. Deep well sockets provide

the full nut engagement that is necessary

during tightening.

PADS INTO METAL-TO-METAL CONTACT

Page 135: Victaulic I-100 Field Installation Handbook.pdf

®

GOODBAD

Coupling Size

Nominal Size inches

Actual Pipe Outside Diameterinches/mm

26 – 2826.000 – 28.000 375

660 – 711 500

30 – 3830.000 – 38.000 500

762 – 965 678

40 – 6040.000 – 60.000 600

1016 – 1524 814

Size

Bolts/Nuts/

Washers

Bolt/Nut/ Washer Size

NominalSize

inches

Actual PipeOutside

Diameterinches/mm inches/Metric inches/mm

26 – 2826.000 – 28.000

41 1⁄8 1 13⁄16

660 – 711 M27 46

30 – 3830.000 – 38.000

41 ¼ 2

762 – 965 M30 50

40 – 6040.000 – 60.000

41 ½ 2 3⁄8

1016 – 1524 M36 60

personal injury and/or property damage.

8. Visually inspect the bolt pads at each joint to ensure metal-to-metal contact is

achieved across the entire bolt pad section.

Page 136: Victaulic I-100 Field Installation Handbook.pdf

®

Style W89 - Rigid Coupling for Direct-Grooved Stainless Steel Pipe or

Carbon Steel Pipe Prepared with AGS Vic-Rings (24-inch/610-mm and Smaller Sizes)

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

NOTICE

Style W89 Couplings must be used only on pipe that is direct-grooved to Victaulic Advanced

DO NOT attempt to assemble this product on pipe that is direct-

roll sets.

cause improper assembly and joint

injury and/or property damage.

.

Check the gasket to make sure it is

suitable for the intended service. The color

code identifies the gasket grade. Apply a

thin coat of Victaulic lubricant or silicone

lubricant to the gasket lips and exterior.

Position the

gasket over the pipe end or AGS Vic-Ring.

Make sure the gasket does not overhang

the pipe end or AGS Vic-Ring.

Page 137: Victaulic I-100 Field Installation Handbook.pdf

I-100_130

®

Align and bring

the two pipe ends together. Slide the

gasket into position, and center it between

the groove in each pipe end or AGS Vic-

Ring.

Apply a thin coat of Victaulic Lubricant

or silicone lubricant to the bolt threads.

If stainless steel bolts and nuts

are special ordered, apply an anti-seize

compound to the bolt threads.

installing the housings.

Install

the housings over the gasket. Make sure

the housings’ keys engage the groove

completely in each pipe end or AGS

Vic-Ring. Support the segments while

preparing to install the bolts and nuts.

Install

the bolts, and thread a nut finger-tight onto

each bolt. Make sure the oval neck

of each bolt seats properly in the bolt hole.

Nuts must be tightened evenly until

torque value are achieved.

metal-to-metal contact immediately

openings during tightening.

serious personal injury and/or property damage.

Tighten the nuts

evenly by alternating sides. Make sure

the housings’ keys engage the groove

completely in each pipe end or AGS Vic-

Ring. Continue to tighten the nuts evenly by alternating sides until metal-to-metal

Page 138: Victaulic I-100 Field Installation Handbook.pdf

I-100_131

®

It is important to tighten the nuts

evenly by alternating sides to prevent

gasket pinching. Deep well sockets are

recommended for proper installation due

to the longer bolt lengths associated with

this product. Deep well sockets provide

the full nut engagement that is necessary

during tightening.

PADS INTO METAL-TO-METAL CONTACT

SizeNutSize Size

NominalSize

inches

Actual PipeOutside

Diameterinches/mm

inches/Metric

inches/mm

14 – 2414.000 – 24.000 1 1⁄8 1 13⁄16

355.6 – 610 M27 46

Page 139: Victaulic I-100 Field Installation Handbook.pdf
Page 140: Victaulic I-100 Field Installation Handbook.pdf

I-100_133

Installation Instructions

Page 141: Victaulic I-100 Field Installation Handbook.pdf

®

Exaggerated for clarity

The Style 441 is designed for use with Class 150 raised-face flanges, in accordance

with ANSI B16.5. When a Style 441 is used with a flat-faced flange, the raised

projections on the outside edge and around the mating holes of the Style 441 must

be ground flush to the body. The shaded areas on the sketch above identify the

projections that must be ground flush on both segments.

The Style 441 must not be used in installations where it does not mount flush with the

mating flange. Flange washers, or anything else that prevents mounting the Style 441

flush with the mating flange, must not be used.

The Style 441 must not be used as anchor points for tie rods across non-restrained

joints.

The Style 441 must not be used against rubber coated surfaces or with wafer or lug-

type valves, or when it does not mount flush with the mating flange.

Because of the outside flange dimension, the Style 441 must not be used 90° to one

another on a standard fitting.

Page 142: Victaulic I-100 Field Installation Handbook.pdf

I-100_135

Stainless Steel Vic-Flange Adapter (Patented)

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

NOTICE

clearance behind the groove in the

the Vic-Flange Adapter.

The outside

surface of the pipe, between the groove

and the pipe end, must be smooth

and free from indentations, projections

(including weld seams), and roll marks

to ensure a leak-tight seal. All oil, grease,

loose paint, dirt, and cutting particles must

be removed.

Insert a standard, full-shank diameter assembly

bolt through a mating hole to act as a

hinge, as shown above.

Check the gasket supplied

to make sure it is suitable for the intended

service. The color code identifies the

gasket grade. Apply a thin coat of Victaulic

lubricant or silicone lubricant to the gasket

lips and exterior.

GasketPosition

GasketMarkings

(Exaggerated for clarity)

Install the

gasket onto the pipe end. Make sure the

gasket is positioned properly, as shown

above. The lettering on the outside

of the gasket must face the gasket seating

area of the Style 441 Vic-Flange Adapter.

Page 143: Victaulic I-100 Field Installation Handbook.pdf

I-100_136

Place the hinged flange

around the grooved pipe end. Make sure

the key section of the flange adapter

engages with the groove in the pipe end.

5a. Closure lugs are provided to ease

installation. Clamp both lugs with a wrench

or pliers, and pull the two segments

together until the bolt holes align.

NOTICEWhen using stainless steel bolts/nuts, an anti-seize lubricant must be applied to the bolt threads.

5b. When the bolt holes are aligned,

insert a standard, full-shank diameter

assembly bolt through the other mating

hole of the Vic-Flange Adapter.

5c. Make sure the gasket is still seated

properly in the flange adapter.

Join the Vic-

Flange Adapter with the mating flange by

aligning the two bolts with the holes in the

mating flange.

Thread a nut onto each mating

bolt. Tighten the nuts until they are finger-

tight.

Insert a standard, full-shank

diameter assembly bolt through each

remaining hole in the Vic-Flange Adapter

and the mating flange. Thread a nut onto

each bolt until they are finger-tight.

Page 144: Victaulic I-100 Field Installation Handbook.pdf

Insert a standard, full-shank

diameter assembly bolt through each

remaining hole in the Vic-Flange Adapter

and the mating flange. Thread a nut onto

each bolt until they are finger-tight.

Tighten all nuts

evenly in a crossing pattern, as with a

standard flange assembly. Continue to

tighten all nuts until the standard, flange-

bolt torque recommendation is achieved.

SizeAssembly Bolts/

Nuts

AssemblyBolt/Nut

Size x Length inches/mm

Nominal Sizeinches

Actual Pipe Outside Diameter

inches/mm Maximum Minimum

22.375

4 5⁄8 x 2¾ 2.38 3.41

60.3 61 87

2½2.875

4 5⁄8 x 32.88 3.91

73.0 73 99

33.500

4 5⁄8 x 33.50 4.53

88.9 89 11.5

44.500

8 5⁄8 x 34.50 5.53

114.3 114 141

66.625

8 ¾ x 3½6.63 7.78

168.3 168 198

† Victaulic does not supply assembly bolts/nuts. Bolt/nut sizes are for conventional flange-to-flange connections. Full-shank diameter assembly bolts are required for proper installation of Victaulic Flange Adapters.

A

B

Page 145: Victaulic I-100 Field Installation Handbook.pdf

I-100_138

The Victaulic Flange Adapter design incorporates small teeth on the ID of the key

section to resist rotation. These teeth must be removed when the Victaulic Flange

Adapter is used with grooved-end Victaulic Series 700 Butterfly Valves, Schedule 5

pipe, and plastic pipe.

Victaulic Flange Adapters must be assembled so there is no interference with mating

components.

Because of the outside flange dimension, Victaulic Flange Adapters must not be used

within 90° of one another on a standard fitting.

Victaulic Flange Adapters cannot be used on FireLock fittings.

When wafer or lug-type valves are used adjoining a Victaulic fitting, check disc

dimensions to ensure proper clearance.

Victaulic Flange Adapters shall not be used as anchor points for tie rods across non-

restrained joints.

Mating Victaulic Flange Adapters to rubber faced flanges, valves, etc. requires the use

of a Victaulic Flange Washer. Refer to the “Victaulic Flange Washer Notes” section on

the following page.

The face of the mating flange must be free from gouges, undulations, and deformities

of any type for proper sealing. Refer to the installation instructions for complete

information.

The lettering on the outside of the gasket must face the gasket pocket of the Victaulic

Flange Adapter. When installed correctly, the lettering on the gasket will not be visible.

The hinge points of Victaulic Flange Adapters must be oriented approximately 90° to

each other when mated.

Style 741 Vic-Flange Adapters can be used only on the side of Series 700 Butterfly

Valves that will not interfere with handle operation.

Style 741 Vic-Flange Adapters can be used on all sizes of Series 761 Vic-300

MasterSeal Butterfly Valves and Series 716/716H Vic-Check Valves.

Series 761 Vic-300 MasterSeal Butterfly Valves cannot be connected directly to

flanged components with Style 743 Vic-Flange Adapters. A No. 46 ANSI 300 groove-

by-flange adapter is required for this application.

Style 741 Vic-Flange Adapters can be used only on one side of 8-inch/219.1-mm and

smaller Series 765, 705, 766, and 707C Butterfly Valves that will not interfere with

mating components and handle operation.

Style 741 Vic-Flange Adapters cannot be used on 10-inch/273.0-mm Series 765 and

Series 705 Butterfly Valves.

Style 741 and Style 743 Vic-Flange Adapters can be installed on either end of a Series

717, 717H, 717R, and 717HR FireLock Check Valve.

Series 765, 705, 766, and 707C Butterfly Valves cannot be connected directly to

flanged components with Style 743 Vic-Flange Adapters. A No. 46 ANSI 300 groove-

by-flange adapter is required for this application.

Series 763 Stainless Steel Butterfly Valves cannot be connected directly to flanged

components with Style 743 Vic-Flange Adapters. A No. 46 ANSI 300 groove-by-flange

adapter is required for this application.

Style 743 Vic-Flange Adapters are designed to mate with raised-face flanges. For

connections to flat-faced flanges, the raised projections on the outside face of the

Style 743 Vic-Flange Adapter must be removed.

Style 743 Vic-Flange Adapters in 2, 2 ½, and 3-inch/60.3, 73.0, and 88.9-mm sizes

must be ordered as a factory assembly when connected to a Victaulic fitting or valve.

Contact Victaulic for details.

Page 146: Victaulic I-100 Field Installation Handbook.pdf

I-100_139

Victaulic Flange Adapters require a smooth, hard surface at the mating flange face for

proper sealing. Some applications, for which the Victaulic Flange Adapter is otherwise

well suited, do not provide an adequate mating surface. In such cases, a metal Victaulic

Flange Washer (Type F phenolic when joining to copper systems) is recommended for

insertion between the Victaulic Flange Adapter and the mating flange to provide the

necessary sealing surface. To ensure the proper Victaulic Flange Washer is supplied,

always specify the product style and size when ordering.

A. – a flange

gasket shall be used against the serrated flange. The Victaulic Flange Washer

should then be inserted between the Victaulic Flange Adapter and the flange

gasket.

B. – the Victaulic

Flange Washer shall be placed between the valve and the Victaulic Flange Adapter.

C. etc. – the Victaulic Flange Washer must be placed between the Victaulic Flange

Adapter and the rubber-faced flange.

D. – follow

the same arrangement as if the Victaulic Flange Adapter was being mated to a

serrated flange. Refer to application “A” above.

E. When mating Victaulic AWWA Flange Adapters to Victaulic NPS Flange Adapters – the Victaulic Flange Washer must be placed between the two Victaulic

Flange Adapters with the hinge points oriented 90° to each other. If one flange is

not a Victaulic Flange Adapter (i.e. flanged valve), a flange gasket must be placed

against the non-Victaulic Flange. The Victaulic Flange Washer must then be

inserted between the flange gasket and the Victaulic Flange gasket.

F.

Raised-Face Mating FlangeVic-Flange

Adapter

Vic-Flange GasketRaised-Face Flange GasketVic-Flange Washer

Exaggerated for Clarity

Page 147: Victaulic I-100 Field Installation Handbook.pdf

Vic-Flange Adapter (12-inch/323.9-mm and Smaller Sizes) –

ANSI 125, 150/DIN PN10 Class, or DIN PN16 Class

Vic-Flange Adapter – ANSI Class 300

FireLock Flange Adapter – ANSI Class 150

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

NOTICE

The outside

surface of the pipe, between the groove

and the pipe end, must be smooth

and free from indentations, projections

(including weld seams), and roll marks

to ensure a leak-tight seal. All oil, grease,

loose paint, dirt, and cutting particles must

be removed.

NOTICE

system, additional lubrication

that are installed at or continuously

Check the gasket supplied

to make sure it is suitable for the intended

service. The color code identifies the

gasket grade. Apply a thin coat of Victaulic

lubricant or silicone lubricant to the gasket

lips and exterior. This gasket is

designed to provide the sole seal. However,

reference should be made to the notes at

the beginning of this section for special

applications.

pinching/tearing during installation.

Page 148: Victaulic I-100 Field Installation Handbook.pdf

Vic-Flange

Proper Gasket Positioning

MatingFlange

Exaggerated for ClarityExaggerated for Clarity

GasketMarkings

GasketPosition

Install the

gasket over the pipe end. Make sure the

gasket is positioned properly, as shown

above. The lettering on the outside

of the gasket must face the flange-adapter

gasket pocket. When installed correctly,

the lettering on the gasket will not be

visible.

Open the hinged flange adapter fully, and

install the flange over the gasket. Make

sure the flange key section engages the

pipe groove properly.

Closure lugs are provided for ease of

installation. If necessary, use an adjustable

wrench to bring the flange holes into

alignment. This will ease insertion of the

standard flange bolts into the mating holes.

Insert

a standard, full-shank diameter assembly

bolt through each of the two mating holes

in the flange adapter. This will maintain the

position of the flange in the pipe groove.

5a. Make sure the gasket is seated

properly in the flange adapter.

Join the flange

adapter with the mating flange by aligning

the bolt holes.

Page 149: Victaulic I-100 Field Installation Handbook.pdf

6a. Thread standard flange nuts finger-

tight onto the two mating bolts.

Insert a standard, full-shank

diameter assembly bolt through each

remaining hole in the flange adapter/

mating flange. Thread standard flange nuts

finger-tight onto all bolts.

Tighten the nuts

evenly, as with a regular flange assembly.

Continue tightening until the flange faces

come into firm, metal-to-metal contact

or the standard, flange-bolt torque

requirement is achieved.

Page 150: Victaulic I-100 Field Installation Handbook.pdf

SizeAssembly Bolts/

Assembly Bolt/NutSize x Length

inches/mm

Nominal Size

inches or mm

Actual Pipe Outside

Diameterinches/mm

Style Style Style Style Style StyleMaximum Minimum

22.375

4 8 4 5⁄8 x 2¾ 5⁄8 x 3 5⁄8 x 2¾2.38 3.41

60.3 61 87

2 ½2.875

4 8 4 5⁄8 x 3 ¾ x 3¼ 5⁄8 x 32.88 3.91

73.0 73 99

33.500

4 8 4 5⁄8 x 3 ¾ x 3½ 5⁄8 x 33.50 4.53

88.9 89 115

44.500

8 8 8 5⁄8 x 3 ¾ x 3¾ 5⁄8 x 34.50 5.53

114.3 114 141

55.563

8 8 8 ¾ x 3½ ¾ x 4 ¾ x 3½5.56 6.71

141.3 141 170

66.625

8 12 8 ¾ x 3½ ¾ x 4½ ¾ x 3½6.63 7.78

168.3 168 198

165.1 mm ‡ *

6.5008 — — ¾ x 3½ — —

6.50 7.66165.1 165 195

88.625

8 12 8 ¾ x 3½ 7⁄8 x 4¾ ¾ x 3½8.63 9.94

219.1 219 253

10 *10.750

12 16 — 7⁄8 x 4 1 x 5¼ —10.75 12.31

273.0 273 313

12 *12.750

12 16 — 7⁄8 x 4 11⁄8 x 5¾ —12.75 14.31

323.9 324 364

† Victaulic does not supply assembly bolts/nuts. Bolt/nut sizes are for conventional flange-to-flange connections. Longer bolts are required when Victaulic Flange Adapters are used with wafer-type valves. Full-shank diameter assembly bolts are required for proper installation of Victaulic Flange Adapters.

‡ Style 743 Vic-Flange Adapters are not available in the 165.1-mm size.

* Style 744 FireLock Flange Adapters are not available in the 165.1-mm; 10-inch/273.0-mm; and 12-inch/323.9-mm sizes.

Style 741 and Style 743 Vic-Flange Adapters provide rigid joints when used on pipe that is standard cut or roll grooved to Victaulic specifications. Consequently, no linear or angular movement is allowed at the joint.

A

B

Page 151: Victaulic I-100 Field Installation Handbook.pdf

Size PN10 PN16 mm/inches

Nominal Sizemm

Actual Pipe Outside

Diametermm/inches

AssemblyBolts/Nuts

AssemblyBolt/Nut

SizeAssemblyBolts/Nuts

AssemblyBolt/Nut

SizeMaximum Minimum

5060.3

4 M16 4 M1660 87

2.375 2.38 3.41

6573.0

4 M16 4 M1676 103

2.875 3.00 4.05

76.176.1

4 M16 4 M1676 103

3.000 3.00 4.05

8088.9

8 M16 8 M1689 115

3.500 3.50 4.53

100114.3

8 M16 8 M16114 141

4.500 4.50 5.55

108.0108.0

8 M16 8 M16108 133

4.250 4.25 5.24

133.0133.0

8 M16 8 M16133 160

5.250 5.24 6.30

139.7139.7

8 M16 8 M16140 168

5.500 5.51 6.61

150168.3

8 M20 8 M20168 198

6.625 6.63 7.78

159.0159.0

8 M20 8 M20159 187

6.250 6.25 7.36

165.1165.1

8 M20 8 M20165 195

6.500 6.50 7.68

200219.1

8 M20 12 M20219 252

8.625 8.63 9.94

250273.0

12 M20 12 M24273 313

10.750 10.75 12.31

300323.9

12 M20 12 M24324 365

12.750 12.75 14.31

† Victaulic does not supply assembly bolts/nuts. Bolt/nut sizes are for conventional flange-to-flange connections. Longer bolts are required when Victaulic Flange Adapters are used with wafer-type valves. Full-shank diameter assembly bolts are required for proper installation of Victaulic Flange Adapters.

Style 741 Vic-Flange Adapters provide rigid joints when used on pipe that is standard cut or roll grooved to Victaulic specifications. Consequently, no linear or angular movement is allowed at the joint.

Contact Victaulic for information on AS2129 – Table E; ISO 2084 (PN10); DIN 2532 (PN10); and JIS B-2210 (10K) flanges.

A

B

Page 152: Victaulic I-100 Field Installation Handbook.pdf

Size

Nominal Sizemm

Actual Pipe Outside

Diametermm/inches

AssemblyBolts/Nuts

AssemblyBolt/Nut Size

Maximum Minimum

7373.0

4 M1673 99

2.880 2.88 3.91

6576.1

4 M1676 103

3.000 3.00 4.05

8088.9

8 M1689 115

3.500 3.50 4.53

100114.3

8 M16114 141

4.500 4.50 5.53

141.3141.3

8 M20141 171

5.560 5.56 6.71

165.1165.1

8 M20165 195

6.500 6.50 7.66

150168.3

8 M20168 198

6.625 6.63 7.78

† Victaulic does not supply assembly bolts/nuts. Bolt/nut sizes are for conventional flange-to-flange connections. Longer bolts are required when Victaulic Flange Adapters are used with wafer-type valves. Full-shank diameter assembly bolts are required for proper installation of Victaulic Flange Adapters.

Style 741 Vic-Flange Adapters provide rigid joints when used on pipe that is standard cut or roll grooved to Victaulic specifications. Consequently, no linear or angular movement is allowed at the joint.

Contact Victaulic for information on AS2129 – Table E; ISO 2084 (PN10); DIN 2532 (PN10); and JIS B-2210 (10K) flanges.

A

B

Page 153: Victaulic I-100 Field Installation Handbook.pdf

Victaulic Flange Adapters must be assembled so there is no interference with mating

components.

Because of the outside flange dimension, Victaulic Flange Adapters must not be used

within 90° of one another on a standard fitting.

When wafer or lug-type valves are used adjoining a Victaulic fitting, check disc

dimensions to ensure proper clearance.

Victaulic Flange Adapters shall not be used as anchor points for tie rods across non-

restrained joints.

Mating Victaulic Flange Adapters to rubber-faced flanges, valves, etc. requires the use

of a Victaulic Flange Washer. Refer to the “Victaulic Flange Washer Notes” section on

the following page.

The face of the mating flange must be free from gouges, undulations, and deformities

of any type for proper sealing. Refer to the installation instructions for complete

information.

The lettering on the outside of the gasket must face the gasket pocket of the Victaulic

Flange Adapter. When installed correctly, the lettering on the gasket will not be visible.

.

Page 154: Victaulic I-100 Field Installation Handbook.pdf

Victaulic Flange Adapters require a smooth, hard surface at the mating flange face for

proper sealing. Some applications, for which the Victaulic Flange Adapter is otherwise

well suited, do not provide an adequate mating surface. In such cases, a metal Victaulic

Flange Washer is recommended for insertion between the Victaulic Flange Adapter and

the mating flange to provide the necessary sealing surface. To ensure the proper Victaulic

Flange Washer is supplied, always specify the product style and size when ordering.

A. – a flange

gasket shall be used against the serrated flange. The Victaulic Flange Washer

should then be inserted between the Victaulic Flange Adapter and the flange

gasket.

B. – the Victaulic

Flange Washer should be placed between the valve and the Victaulic Flange

Adapter.

C. etc. – the Victaulic Flange Washer must be placed between the Victaulic Flange

Adapter and the rubber-faced flange.

D. – follow

the same arrangement as if the Victaulic Flange Adapter was being mated to a

serrated flange. Refer to application “A” above.

E. When mating Victaulic AWWA Flange Adapters to Victaulic NPS Flange Adapters – the Victaulic Flange Transition Ring must be placed between the two

Victaulic Flange Adapters with the draw bolt locations offset from each other. If one

flange is not a Victaulic Flange Adapter (i.e. flanged valve), a flange gasket must

be placed against the non-Victaulic flange. The Victaulic Flange Washer must then

be inserted between the flange gasket and the Victaulic Flange gasket. A

Victaulilc Transition Ring, rather than a Victaulic Flange Washer, must be used

when mating a Style 741 Vic-Flange Adapter to a Style 341 Vic-Flange Adapter in

14 – 24-inch/355.6 – 610-mm sizes.

Raised-Face Mating FlangeVic-Flange

Adapter

Vic-Flange GasketRaised-Face Flange GasketVic-Flange Washer

Exaggerated for Clarity

Page 155: Victaulic I-100 Field Installation Handbook.pdf

Vic-Flange Adapter (14-inch/355.6-mm and Larger Sizes)

ANSI Class 150

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

NOTICE

clearance behind the pipe groove to

Flange Adapter.

The outside

surface of the pipe, between the groove

and the pipe end, must be smooth

and free from indentations, projections

(including weld seams), and roll marks

to ensure a leak-tight seal. All oil, grease,

loose paint, dirt, and cutting particles must

be removed.

Place

the first segment onto the pipe, making

sure that the key engages in the groove

properly. On vertical pipe, the

segments must be held in place until

all segments are fastened together. For

horizontal pipe, the segments can be

balanced on top of the pipe, as shown

above.

Add each segment by inserting the draw

bolts (provided) into the flange adapter

with the nuts (provided) loosely and

uniformly tightened. This will permit the

flange adapter to be rotated for bolt hole

alignment in later steps.

Check the gasket to make

sure it is suitable for the intended service.

Apply a thin coat of Victaulic Lubricant or

silicone lubricant to the gasket lips and

exterior. This gasket is designed

to provide the sole seal. However,

reference should be made to the notes at

the beginning of this section for special

applications.

Page 156: Victaulic I-100 Field Installation Handbook.pdf

pinching/tearing during installation.

Vic-Flange

Proper Gasket Positioning

MatingFlange

Exaggerated for ClarityExaggerated for Clarity

GasketMarkings

GasketPosition

Install the

gasket into the cavity between the pipe

OD and the flange recess. Make sure the

gasket is positioned properly, as shown

above. The lettering on the outside

of the gasket must face the flange-adapter

gasket pocket of the Style 741 Vic-Flange

Adapter. When installed correctly, the

lettering on the gasket will not be visible.

Rotate the Vic-

Flange on the pipe end, as required, to

align the holes with the mating flange.

Insert a

standard, full-shank diameter assembly

bolt into each of the four lap joint holes.

It may be necessary to tighten the

draw bolts to line up the lap joint bolt holes

for insertion of the bolts.

After

the four assembly bolts are inserted into

the lap-joint bolt holes, torque the draw

It is normal to have a small amount

of shift as these bolts are being torqued.

Direct the four

assembly bolts, installed in step 7, into the

mating flange holes. Hand-tighten a nut

onto each of the four assembly bolts to

prevent the bolts from pulling out.

Page 157: Victaulic I-100 Field Installation Handbook.pdf

I-100_150

SizeAssembly

inches/mm

Nominal Size

inches

Actual Pipe

Outside Diameter

inches/mm

Number

Nuts

Bolt/NutSize XLengthinches

Number

Nuts

Bolt/NutSize XLengthinches

Sizeinches Maximum Minimum

14 14.000355.6

12 1 x 4 ½ 4 5⁄8 x 3 ½ 15⁄1614.00355.6

16.39416.3

1616.000406.4 16 1 x 4 ½ 4 5⁄8 x 3 ½ 15⁄16

16.00406.4

18.39467.1

1818.000

45716

1 1⁄8 x4 ¾ 4 ¾ x 4 ¼ 11⁄8

18.00457.2

20.00208.0

2020.000

50820

1 1⁄8 x5 ¼ 4 ¾ x 4 ¼ 1 1⁄8

20.00508.0

22.50571.5

2424.000

61020

1 ¼ x5 ¾ 4 ¾ x 4 ¼ 11⁄8

24.00610.0

27.75704.9

† Victaulic does not supply assembly bolts/nuts. Bolt/nut sizes are for conventional flange-to-flange connections. Longer bolts are required when Vic-Flange Adapters are used with wafer-type valves. Full-shank diameter assembly bolts are required for proper installation of Style 741 Vic-Flange Adapters.

§ Draw bolts/nuts are supplied with 14 – 24-inch/355.6 – 610-mm Style 741 Vic-Flange Adapters.

A

B

Insert a standard, full-shank

diameter assembly bolt through each

remaining hole in the Vic-Flange Adapter/

mating flange. Thread standard flange nuts

finger-tight onto all bolts.

Tighten all assembly bolts evenly until the

required torque value is achieved. Refer

to the “Style 741 Assembly Bolt Torque

Requirements” table below for the torque

requirement.

Size

Nominal Sizeinches

Actual Pipe Outside Diameter

inches/mm

14 – 1614.000 – 16.000 200 – 300

355.6 – 406.4 271 – 407

18 – 2018.000 – 20.000 300 – 400

457 – 508 407 – 542

2424.000 400 – 500

610 542 – 678

Page 158: Victaulic I-100 Field Installation Handbook.pdf

I-100_151

System Vic-Flange Adapter

PipeInstallation Instructions

Page 159: Victaulic I-100 Field Installation Handbook.pdf

When installing Style W741 AGS Vic-Flange Adapters, care must be taken to avoid

interference with mating components.

Because of the outside flange dimensions, Style W741 AGS Vic-Flange Adapters must

not be used within 90º of one another on an AGS fitting.

When wafer or lug-type valves are used adjoining a Victaulic AGS fitting, check the

disc dimensions to ensure proper clearance.

Series W761 AGS Vic-300 Butterfly Valves CAN be connected directly to flanged

components with Style W741 AGS Vic-Flange Adapters.

Style W741 AGS Vic-Flange Adapters can be installed on either end of a Series W715

AGS Dual-Disc Vic-Check Valve.

Style W741 AGS Vic-Flange Adapters must not be used as anchor points for tie rods

across non-restrained joints.

Mating Style W741 AGS Vic-Flange Adapters to rubber-faced flanges, valves, etc.

requires the use of an AGS Vic-Flange Washer. Refer to the “Style W741 AGS Vic-

Flange Washer Notes” section on the following page.

The face of the mating flange must be free from gouges, undulations, and deformities

of any type for proper sealing. Refer to the installation instructions for complete

information.

The lettering on the outside of the gasket must face the gasket pocket of the Style

W741 AGS Vic-Flange Adapter. When installed correctly, the lettering on the gasket

will not be visible.

When mating two Style W741 AGS Vic-Flange Adapters in 14 – 24-inch/

355.6 – 610-mm sizes, the draw bolt locations must be offset from each other, and a

transition ring must be used between the two Vic-Flange Adapters.

Page 160: Victaulic I-100 Field Installation Handbook.pdf

I-100_153

Style W741 AGS Vic-Flange Adapters require a smooth, hard surface at the mating flange

face for proper sealing. Some applications, for which the Style W741 AGS Vic-Flange

Adapter is otherwise well suited, do not provide an adequate mating surface. In such

cases, a metal AGS Vic-Flange Washer is recommended for insertion between the Style

W741 AGS Vic-Flange Adapter and the mating flange to provide the necessary sealing

surface.

A. a flange gasket shall be used against the serrated flange. The AGS Vic-

Flange Washer should then be inserted between the Style W741 AGS Vic-Flange

Adapter and the flange gasket.

B.

the AGS Vic-Flange Washer should be placed between the valve and the

Style W741 AGS Vic-Flange Adapter.

C. the AGS Vic-Flange Washer must be placed between the

Style W741 AGS Vic-Flange Adapter and the rubber-faced flange.

D.

insert follow the same arrangement as if the Style W741 AGS Vic-Flange Adapter

was being mated to a serrated flange. Refer to application “A” above.

E. When mating Victaulic AWWA Flange Adapters to Victaulic NPS Flange Adapters the Victaulic Flange Transition Ring must be placed between the two

Victaulic Flange Adapters with the draw bolt locations offset from each other. If one

flange is not a Victaulic Flange Adapter (i.e. flanged valve), a flange gasket must

be placed against the non-Victaulic flange. The Victaulic Flange Washer must then

be inserted between the flange gasket and the Victaulic Flange gasket. A

Victaulic Transition Ring, rather than a Victaulic Flange Washer, must be used when

mating a Style W741 AGS Vic-Flange Adapter to a Style 341 Vic-Flange Adapter in

14 – 24-inch/355.6 – 610-mm sizes.

Raised-Face Mating FlangeStyle W741

AGS Vic-Flange Adapter

AGS Vic-Flange Gasket Raised-Face Flange Gasket

AGS Vic-Flange Washer

Exaggerated for Clarity

Page 161: Victaulic I-100 Field Installation Handbook.pdf

1. Pipe ends shall be visually inspected

in accordance with the requirements listed

in this section.

The front edge of the pipe end

shall be uniform with no concave/convex

surface features that will cause improper

grooving roll tracking and result in

difficulties during coupling assembly (refer

to drawing above).

3. If pipe cut-off is required, Victaulic

recommends the use of a mechanically-

guided pipe cutting tool for proper pipe

end preparation. Free-hand pipe end

cutting is not acceptable.

"S" Max.

Square cut the pipe ends (“S”

dimension shown above) within

1⁄8 inch/3.2 mm.

Photo Showing Pipe withWeld Seam Ground 6 inches/152 mm

Back from Pipe End

Gri

nd

ing

Dir

ec

tio

n

1. Prior to grooving, weld seams must

be ground flush to the pipe surface (inside

diameter and outside diameter). Grind

the weld seam from the pipe end to a

minimum distance of 6 inches/152 mm

back from the pipe end. This area must

be smooth and free from indentations,

projections, and roll marks to ensure a

leak-tight seal. Pipe with external, axial

weld seams can be supported with

Victaulic Adjustable Pipe Stands. However,

the weld seam must be smooth and

rounded and at least three times as wide

as it is high. The weld seam must not

exceed 1⁄8 inch/3 mm in height.

1a. Groove the pipe in accordance with

the Victaulic AGS grooving specifications

in this manual.

1b. Clean the outside surface of the pipe,

from the groove to the pipe end, to remove

all oil, grease, loose paint, and dirt.

Page 162: Victaulic I-100 Field Installation Handbook.pdf

I-100_155

Vic-Flange Adapter (ANSI Class 150)

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

Adapters must be used only on pipe that is prepared to Victaulic

type grooving roll sets.

cause improper assembly and joint

injury and/or property damage.

NOTICE

clearance behind the pipe groove to

Flange Adapter.

Place the

first segment onto the pipe. Make sure

the key engages completely in the groove.

On vertical pipe, the first segment

must be held in place until the second

segment is installed and fastened to the

first segment. For horizontal pipe, the first

segment can be balanced on top of the

pipe, as shown above.

Add

the second segment by inserting the draw

bolts (provided) into the flange adapter

with the nuts (provided) loosely and

tightened uniformly. This will permit the

flange adapter to be rotated for bolt hole

alignment in later steps. Make sure the key

of both segments engages completely in

the groove.

Page 163: Victaulic I-100 Field Installation Handbook.pdf

I-100_156

Check the gasket

to make sure it is suitable for the intended

service. The color code identifies the

gasket grade. Apply a thin coat of Victaulic

lubricant or silicone lubricant to the gasket

lips and exterior. This gasket is

designed to provide the sole seal. However,

reference should be made to the notes at

the beginning of this section for special

applications.

Style W741 AGSVic-Flange Adapter

Proper Gasket Positioning

MatingFlange

GasketMarkings

GasketPosition

Exaggerated for Clarity

Install the

gasket into the cavity between the pipe

OD and the flange recess. Make sure the

gasket is positioned properly, as shown

above. The lettering on the outside

of the gasket must face the flange-adapter

gasket pocket of the Style W741 AGS Vic-

Flange Adapter. When installed correctly,

the lettering on the gasket will not be

visible.

Rotate the Style

W741 AGS Vic-Flange Adapter on the pipe

end, as required, to align the holes with the

mating flange.

Metal-to-Metal Contact Plus

150 ft-lbs/203 N m

Torque

the draw bolts to approximately 150 ft-lbs/

contact.

Insert a

standard, full-shank-diameter assembly

bolt into each of the lap-joint bolt

holes. Refer to the “Style W741 Helpful

Information” table on the following page.

Direct the

standard, full-shank-diameter assembly

bolts, installed in step 7, into the mating

flange holes. Hand-tighten a nut onto each

bolt to prevent the bolts from pulling out.

Page 164: Victaulic I-100 Field Installation Handbook.pdf

Insert standard,

full-shank-diameter assembly bolts into

the remaining holes in the Style W741

AGS Vic-Flange and mating flange. Hand-

tighten a nut onto each bolt.

Tighten all

standard, full-shank-diameter assembly

bolts evenly until the required torque value

is achieved. Refer to the “Style W741

Assembly Bolt Torque Requirements” table

below for the specific torque requirement.

SizeTorque

NominalSize

inches

Actual Pipe Outside

Diameterinches/mm

14 – 1614.000 – 16.000 200 – 300

355.6 – 406.4 271 – 407

18 – 2018.000 – 20.000 300 – 400

457 – 508 407 – 542

2424.000 400 – 500

610 542 – 678

Flange Size

Mating Face Sealing

inches/mm

NominalSize

inches

Actual Pipe Outside

Diameterinches/mm

Bolts/Nuts

Bolt/NutSize X Lengthinches

Bolts/Nuts

Bolt/NutSize X Lengthinches

Sizeinches

Max.

Min.

1414.000

12 1 x 4 ½ 2 5⁄8 x 3 ½ 15⁄1614.00 16.00

355.6 355.6 406.4

1616.000

16 1 x 4½ 2 5⁄8 x 3 ½ 15⁄1616.00 18.00

406.4 406.4 457.2

1818.000

16 1 1⁄8 x 4 ¾ 2 ¾ x 4 ¼ 1 1⁄818.00 20.00

457 457.2 508.0

2020.000

20 1 1⁄8 x 5 ¼ 2 ¾ x 4 ¼ 1 1⁄820.00 22.00

508 508.0 558.8

2424.000

20 1 ¼ x 5 ¾ 2 ¾ x 4 ¼ 1 1⁄824.00 26.00

610 610.0 660.4

† Victaulic does not supply assembly bolts/nuts. Bolt/nut sizes are for conventional flange-to-flange connections. Longer bolts are required when Vic-Flange Adapters are used with wafer-type valves. Standard, full-shank-diameter assembly bolts are required for proper installation of Style W741 AGS Vic-Flange Adapters.

§ Draw bolts/nuts are supplied with 14 – 24-inch/355.6 – 610-mm Style W741 AGS Vic-Flange Adapters.

A

B

Page 165: Victaulic I-100 Field Installation Handbook.pdf

I-100_158

Page 166: Victaulic I-100 Field Installation Handbook.pdf

I-100_159

Plain-End PipeInstallation Instructions

Style 99

Page 167: Victaulic I-100 Field Installation Handbook.pdf

I-100_160

Style 99 - Roust-A-Bout® Coupling (12-inch/323.9-mm and Smaller Sizes)

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

"S" Max.

Square

cut the pipe ends (“S” dimension shown)

within 1⁄32 inch/0.8 mm for 1 – 6-inch/

33.7 – 168.3-mm sizes and 1⁄16 inch/1.6 mm

for 8 – 12-inch/219.1 – 323.9-mm sizes.

Both pipe ends must be the same

outside diameter.

1a. Make sure pipe ends are clean and

free from damage and scratches within

1 ½ inches/38 mm from the ends. Remove

cutting particles.

Using a

measuring tape and a bright-colored pencil

or paint stick, place a mark 1 inch/25 mm

from the pipe ends. This mark will be

used for reference in centering the gasket

during installation. Make at least four of

these marks equally-spaced around the

circumference of the pipe ends.

Refer to the “Insertion Depth

Requirements” table below. Using a

measuring tape and a bright-colored pencil

or paint stick, make an additional mark on

the pipe ends at the measurement listed

in this table. This mark will be used for

visual inspection to make sure the pipe is

inserted properly in the coupling. Make at

least four of these marks equally-spaced

around the circumference of the pipe

ends.

SizeInsertion Depth

Nominal Size

inches or mm

Actual Pipe Outside

Diameter inches/mm

inchesmm

11.315 1 ¼33.7 32

1 ½1.900 1 ½48.3 38

2 – 32.375 – 3.500 1 ¾

60.3 – 88.9 45

76.1 mm3.000 1 ½76.1 38

3 ½4.000 1 7⁄8101.6 48

44.500 2 1⁄8114.3 54

139.7 mm5.500 1 ¾139.7 45

5 – 65.563 – 6.625 2 ¼141.3 – 168.3 57

165.1 mm6.500 2 ¼165.1 57

8 – 108.625 – 10.750 2 3⁄8219.1 – 273.0 61

1212.750 2 ¼323.9 57

Page 168: Victaulic I-100 Field Installation Handbook.pdf

I-100_161

Check the gasket to make

sure it is suitable for the intended service.

The color code identifies the gasket grade.

Apply a thin coat of Victaulic Lubricant or

silicone lubricant to the gasket lips and

exterior.

Install the

gasket over the pipe end. Make sure the

gasket does not overhang the pipe end.

Align and bring

the pipe ends together. Slide the gasket

into position by centering it between the

first set of pipe marks. The pipe

ends should be butted; however, if a gap

is present between the pipe ends, the gap

must not exceed ¼ inch/6.4 mm.

Tongue Recess Tongue

Exaggerated for clarity

Install the

housings over the gasket. Make sure the

tongue-and-recess features mate properly

(tongue in recess) and that the housings

are centered between the second set of

pipe marks. The second set of marks must

indicate full insertion into the coupling.

The 1-inch/33.7-mm; 76.1 mm;

1 ½-inch/48.3-mm; and 139.7-mm sizes

do not contain the tongue-and-recess

features.

installing the housings.

Insert the

bolts. Thread a nut onto each bolt finger-

tight. Make sure the oval neck of

the bolts seat properly in the bolt holes.

Page 169: Victaulic I-100 Field Installation Handbook.pdf

Tighten all

nuts evenly by alternating sides until

the required torque value is achieved at

each nut. Refer to the “Style 99 Torque

Requirements” table below for the required

torque value.

It is important to tighten

all nuts evenly to prevent gasket pinching

and to produce bolt pad gaps that are

equal on both sides of the coupling.

in these instructions, must be

installation.Bolt pad gaps must be equal on

openings during tightening.

personal injury, and/or property damage.

Style 99 Couplings can be

re-installed as long as the teeth inside the

coupling housings are clean and free from

any damage. If pipe ends contain damage

or scratches within 1 ½ inches/38 mm from

the ends, corrective action must be taken

by cutting off the ends and preparing them

in accordance with Step 1 on page 160.

SizeTorque

Nominal Sizeinches or mm

Actual Pipe Outside

Diameter inches/mm

11.315 3533.7 48

1 ½1.900 6048.3 81

2 – 2 ½2.375 – 2.875 150

60.3 – 73.0 203

76.1 mm3.000 9576.1 129

3 – 43.500 – 4.500 20088.9 – 114.3 271

139.7 mm5.500 160139.7 217

55.563 250141.3 339

165.1 mm6.500 250165.1 339

6 – 86.625 – 8.625 250168.3 – 219.1 339

1010.750 300273.0 407

1212.750 350323.9 475

Size Style 99

NominalSize

inches or mm

Actual Pipe Outside

Diameterinches/mm

Nut Sizeinches/Metric

Sizeinches/

mm

11.315 3⁄8 11⁄1633.7 M10 17

1 ½1.900 ½ 7⁄848.3 M12 22

2 – 2 ½2.375 – 2.875 5⁄8 1 1⁄16

60.3 – 73.0 M16 27

76.1 mm3.000 ½ 7⁄876.1 M12 22

3 – 43.500 – 4.500 ¾ 1 ¼88.9 – 114.3 M20 32

139.7 mm5.500 ¾ 1 ¼139.7 M20 32

55.563 7⁄8 1 7⁄16141.3 M22 36

165.1 mm6.500 1 1 5⁄8165.1 M24 41

66.625 1 1 5⁄8168.3 M24 41

8 – 108.625 – 10.750 7⁄8 1 7⁄16219.1 – 273.0 M22 36

1212.750 1 1 5⁄8323.9 M24 41

Page 170: Victaulic I-100 Field Installation Handbook.pdf

I-100_163

personal injury and/or property damage.

Style 99 Roust-A-Bout Couplings require sufficient tangent lengths for proper assembly

to fittings. The following table applies to all fittings for plain-end pipe used with Style 99

Roust-A-Bout Couplings (elbows, tees, laterals, wyes, crosses, bull plugs, and nipples).

T

T

T

T

Size

MinimumTangent

Nominal Sizeinches or mm

Actual PipeOutside

Diameterinches/mm inches/mm

1 ½1.900 1.5048.3 38.1

22.375 1.7560.3 44.5

2 ½2.875 1.7573.0 44.5

76.1 mm3.00 1.5076.1 38.1

33.500 1.7588.9 44.5

3 ½4.000 1.75101.6 44.5

44.500 2.00114.3 50.8

139.7 mm5.500 1.75139.7 44.5

55.563 2.13141.3 54.1

66.625 2.13168.3 54.1

165.1 mm6.500 2.13165.1 54.1

88.625 2.25219.1 57.2

1010.750 2.25273.0 57.2

1212.750 2.25323.9 57.2

Page 171: Victaulic I-100 Field Installation Handbook.pdf

Style 99 - Roust-A-Bout Coupling (14-inch/355.6-mm and Larger Sizes)

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

segments to ease handling.

"S" Max.

Exaggerated for clarity

Square

cut the pipe ends (“S” dimension shown)

within 1⁄16 inch/1.6 mm. Both pipe

ends must be the same outside diameter.

1a. Make sure pipe ends are clean and

free from damage and scratches within

1 ½ inches/38 mm from the ends. Remove

cutting particles.

Using a

measuring tape and a bright-colored pencil

or paint stick, place a mark 1 inch/25 mm

from the pipe ends. This mark will be

used for reference in centering the gasket

during installation. Make at least four of

these marks equally-spaced around the

circumference of the pipe ends.

Page 172: Victaulic I-100 Field Installation Handbook.pdf

I-100_165

Refer to the “Insertion Depth

Requirements” table below. Using a

measuring tape and a bright-colored

marking pencil or paint stick, make an

additional mark on the pipe ends at the

measurement listed in this table. This mark

will be used for visual inspection to make

sure the pipe is inserted properly in the

coupling. Make at least four of these marks

equally-spaced around the circumference

of the pipe ends.

SizeInsertion Depth

Nominal Size

inches

Actual PipeOutside

Diameterinches/mm

inchesmm

14 – 1814.000 – 18.000 23⁄8

355.6 – 457 61

Tongue Recess

Assemble the segments loosely into two

equal halves, as shown above. Make sure

the tongue and recess features mate

properly (tongue-to-recess). Allow slight

clearance between the segments to ease

assembly onto the pipe.

Check the gasket to make

sure it is suitable for the intended service.

The color code identifies the gasket grade.

Apply a thin coat of Victaulic Lubricant or

silicone lubricant to the gasket lips and

exterior.

pinching/tearing during installation.

PipeEnd

Exaggerated for clarity

For larger-size

couplings, it may be easier to turn the

gasket inside out, then slide it over the

pipe end. Make sure the gasket does not

overhang the pipe end.

Align and bring

the pipe ends together. Roll the gasket

into position by centering it between the

first set of pipe marks. The pipe

ends should be butted; however, if a gap

is present between the pipe ends, the gap

must not exceed ¼ inch/6.4 mm.

Page 173: Victaulic I-100 Field Installation Handbook.pdf

I-100_166

installing the housings.

Install one of the pre-

assembled halves over the gasket.

Tongue Recess

Install the

second assembly onto the pipe, making

sure the tongue-and-recess features

mate properly (tongue to recess) and

that the housings are centered between

the second set of pipe marks. While

supporting the weight of the assembly,

install the remaining bolts, and thread the

nuts finger-tight onto the bolts.

Make sure the oval neck of each bolt seats

properly in the bolt hole.

Tighten all

nuts evenly by alternating sides until

the required torque value is achieved at

each nut. Refer to the “Style 99 Torque

Requirements” table below for the required

torque value.

Couplings. It is important to tighten

all nuts evenly to prevent gasket pinching

and to produce bolt pad gaps that are

equal at each set of bolt pads.

in these instructions, must be

installation.Bolt pad gaps must be equal on

openings during tightening.

personal injury, and/or property damage.

SizeTorque

NominalSize

inches

Actual Pipe Outside

Diameterinches/mm

14 – 1814.000 – 18.000 350

475355.6 – 457

Size Style 99

NominalSize

inches

Actual Pipe Outside

Diameterinches/mm

NutSize

inches/Metric

Sizeinches/

mm

14 – 1814.000 – 18.000 1 1 5⁄8

355.6 – 457 M24 41

Page 174: Victaulic I-100 Field Installation Handbook.pdf

Style 99 Couplings can be re-installed

as long as the teeth inside the coupling housings are clean and free from any damage.

If pipe ends contain damage or scratches within 1 ½ inches/38 mm from the ends,

corrective action must be taken by cutting off the ends and preparing them in

accordance with Step 1 on page 164.

property damage.

Style 99 Roust-A-Bout Couplings require sufficient tangent lengths for proper assembly

to fittings. The following table applies to all fittings for plain-end pipe used with Style 99

Roust-A-Bout Couplings (elbows, tees, laterals, wyes, crosses, bull plugs, and nipples).

T

T

T

T

Size

Minimum Tangent

NominalSize

inches

Actual Pipe Outside

Diameterinches/mm inches/mm

14 – 1814.000 – 18.000 2.25

57.2355.6 – 457

Page 175: Victaulic I-100 Field Installation Handbook.pdf

I-100_168

Page 176: Victaulic I-100 Field Installation Handbook.pdf

I-100_169

Hole-Cut ProductsInstallation Instructions

Thermometer Outlet

Page 177: Victaulic I-100 Field Installation Handbook.pdf

FireLock® Low-Profile Sprinkler-Tee (Available in Europe Only)

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

The Style 912 FireLock® Low-Profile Sprinkler-Tee is designed for direct connection

of sprinkler heads and is FM Approved up to 300 psi/2068 kPa and VdS and LPCB

Approved up to 232 psi/16 Bar at ambient temperatures that are typical for fire protection

systems.

Pipe Preparation

NOTICE

Proper preparation of the hole is essential for sealing and performance.

Drill a 15⁄16-inch/24-mm minimum hole (1-inch/25-mm maximum hole) on the

centerline of the pipe. Holes MUST be drilled on the centerline of the pipe.

Style 912 Low-Profile Sprinkler-Tee products are designed with female threads to ISO

7-Rp 1/2 (Rp 1/2 BSPP per BS21) and can accommodate only male sprinkler threads.

Ensure that a ¼-inch/6-mm area around the hole is clean, smooth, and free from

indentations and/or projections that could affect gasket sealing (refer to the sketch

below). Remove any burrs and sharp or rough edges from the hole that might affect

assembly, proper seating of the locating collar, flow from the outlet, or gasket seating.

¼ inch/6 mm

Exaggerated for clarity

Page 178: Victaulic I-100 Field Installation Handbook.pdf

Installation

Make sure the

gasket is seated fully in the gasket pocket.

Remove

the flange nut and bolt from one side

of the Style 912 assembly. Thread the

remaining flange nut loosely onto the bolt

(flange nut should be flush with end of

bolt) to allow for the “swing-over” feature.

Install the

outlet housing onto the pipe by centering

the locating collar in the hole. To check

for proper engagement, slide the outlet

housing back and forth while pushing

down. A properly positioned outlet housing

can be moved only a small amount in any

direction.

3a. Rotate the lower housing around

the pipe, while holding the outlet housing

in place to make sure the locating collar

remains seated properly in the hole.

Insert the other track bolt

into the lower housing and outlet housing.

Thread the flange nut onto the bolt finger-

tight. Make sure the track heads of the

bolts seat properly in the bolt holes.

Tighten the flange nuts evenly to an

approximate torque value of 20 ft-lbs/27.1-

To avoid over-tightening the flange

nuts, use a wrench with a maximum length

of 8 inches/200 mm. DO NOT over-tighten

the flange nuts.

Page 179: Victaulic I-100 Field Installation Handbook.pdf

The

outlet housing, near the gasket, should

not make metal-to-metal contact with the

pipe. In addition, a small bolt pad gap is

expected between the outlet housing and

the lower housing, as shown above.

and distort the outlet housing and

serious personal injury and/or property damage.

FPTNut Size

inches/MetricSize

inches/mm

All Sizes3⁄8 9⁄16

M10 15

Page 180: Victaulic I-100 Field Installation Handbook.pdf

Mechanical-T® Bolted Branch Outlet

Mechanical-T Bolted Branch Outlet

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

Mechanical-T Cross Installation

NOTICE

Proper preparation of the hole is essential for sealing and performance. Make sure

the correct hole saw size is being used. Refer to the “Style 920/920N Mechanical-T

Outlet and Mechanical-T Cross Pipe Preparation Requirements” table for the proper

hole saw size.

Holes MUST be drilled on the centerline of the pipe. Holes for Mechanical-T Cross

assemblies must be cut on the centerline of the pipe at predetermined locations

for each branch. Holes for Mechanical-T Cross assemblies must be in line within

1⁄16 inch/1.6 mm of each other.

Ensure that a 5⁄8-inch/16-mm area around the hole is clean, smooth, and free from

indentations and/or projections that could affect gasket sealing (refer to the sketch

below). Remove any burrs and sharp or rough edges from the hole. Burrs and sharp

edges might affect assembly, proper seating of the locating collar, flow from the outlet,

or gasket sealing.

The pipe around the entire circumference, within the “A” dimension shown in the

sketch below, must be free from any dirt, scale, or projections that might prevent the

housing from seating fully on the pipe. Refer to the “Style 920/920N Mechanical-T

Outlet and Mechanical-T Cross Pipe Preparation Requirements” table on the following

page for the “A” dimension.

PVC PLASTIC PIPE.

A

5⁄8 inch/16 mm

Exaggerated for clarity

Page 181: Victaulic I-100 Field Installation Handbook.pdf

NOTICE

SizeHole Dimensions

inches/mmPreparation

NominalOutlet Size

inchesActual mm

Minimum HoleDiameter/Hole

Maximum

Diameterinchesmm

All ½-inch/ 1 ½ 1 5⁄8 3 ½21.3 Outlets 38 41 89

All ¾-inch/ 1 ½ 1 5⁄8 3 ½26.9 Outlets 38 41 89

All 1-inch/ 1 ½ 1 5⁄8 3 ½33.7 Outlets 38 41 89

All 1 ¼-inch/ 1 ¾ 1 7⁄8 442.4 Outlets 44 48 102

All 1 ½-inch/ 2† 2 1⁄8 448.3 Outlets 51 54 102

All 2-inch/ 2 ½‡ 2 5⁄8 4 ½60.3 Outlets 64 67 114

All 2 ½-inch/ 2 ¾ 2 7⁄8 573.0 Outlets 70 73 127

All 76.1-mm 2 ¾ 2 7⁄8 5 ½Outlets 70 73 140

All 3-inch/ 3 ½ 3 5⁄8 5 ½88.9 Outlets 89 92 140

All 4-inch/ 4 ½ 4 5⁄8 6 ½114.3 Outlets 114 118 165

All 108.0-mm 4 ½ 4 5⁄8 6 ½Outlets 114 118 165

† 2 x 1 ½-inch/60.3 x 48.3-mm Style 920N products require a 1 ¾-inch/44-mm hole.

‡ 8 x 2-inch/219.1 x 60.3-mm Style 920 products require a 2 ¾-inch/70-mm size hole.

Style 920 and Style 920N housings CANNOT be mated to each other to achieve cross connections.

A

5⁄8 inch/16 mm

Exaggerated for clarity

Page 182: Victaulic I-100 Field Installation Handbook.pdf

Mechanical-T Installation

Insert

a bolt into the two housings. Thread a nut

loosely onto the end of the bolt.

Inspect the sealing surface

of the gasket to make sure no debris is

present. For Style 920N Mechanical-T

Outlets, it is not necessary to remove

the gasket from the housing.

Lubricate the exposed sealing surface of the gasket

in accordance with the “Lubricant

Compatibility for Gaskets” table below.

Lubricate the exposed sealing surface of the gasket

in accordance with the “Lubricant

Compatibility for Gaskets” table below. DO NOT use Victaulic lubricant on HDPE pipe.

Always consult with the pipe manufacturer

for lubricant compatibility requirements.

Rotate

the lower housing so that it is positioned

approximately 90° to the upper (outlet)

housing, as shown above. Place the upper

(outlet) housing onto the face of the pipe in

line with the outlet hole cut into the pipe.

Rotate the lower housing around the pipe.

Lubricant

Victaulic Lubricant, Soap-Based Solutions, Glycerin, Silicone Oil, or Silicone Release Agent

Good Good

Corn Oil, Soybean Oil, Hydrocarbon-Based Oils, or Petroleum-Based Greases

Good Not Recommended

Due to variations in HDPE pipe, always consult with the pipe manufacturer for lubricant com-patibility requirements. DO NOT USE VICTAULIC LUBRICANT ON HDPE PIPE.

Page 183: Victaulic I-100 Field Installation Handbook.pdf

3a. Make sure the locating collar engages

the outlet hole properly. Check this

engagement by rocking the upper (outlet)

housing in the hole.

Insert the remaining bolt. Thread

a nut onto the bolt finger-tight.

Make sure the oval neck of each bolt seats

properly in the bolt hole.

Make sure the

locating collar is still positioned properly

in the outlet hole. Tighten the nuts evenly

by alternating sides until the upper (outlet)

housing contacts the pipe completely.

The nuts must be

between the bolt pads. DO NOT exceed

The nuts must

On HDPE pipe, it is normal for bolt pads

to contact when the nuts are tightened

DO NOT exceed

NOTICE

applicable coupling installation instructions.For threaded outlets, complete the assembly using standard threading practices.

torque on the nuts. Increased bolt

Failure to torque nuts properly could

serious personal injury and/or property damage.

Branch ConnectionsRUNCL

BRANCHCL

Mechanical-TUpper Housing

90°

Exaggerated for clarity

If a branch connection is made to the

upper housing before the Mechanical-T

is installed on the pipe, make sure the

branch connection is 90° to the pipe run

before completing the tightening sequence

of the Mechanical-T assembly.

a transition piece between two runs,

it must be assembled onto the runs

before the branch connection is

made.

are designed to accommodate

standard ANSI male pipe threads

only. Use of male threaded products

with special features, such as

probes, dry pendent sprinkler heads,

etc., should be verified as suitable

for use with this Victaulic product.

Failure to verify suitability in advance

may result in assembly problems or

leakage.

Page 184: Victaulic I-100 Field Installation Handbook.pdf

Cross connections can be made ON METAL by using two upper housings

of the same size. Different branch sizes are

allowable.

on HDPE pipe.

Install the cross connection in accordance

with the instructions in this section. Make

sure the locating collar on each side is

even gaps between the bolt pads, to ensure the cross assembly is rigid. DO NOT

assemblies.

Size Nut Size

Nominal Sizeinches or mm

Actual Pipe Outside

Diameterinches/mm

inches/Metric

inches/mm

76.1 mm3.000 ½ 7⁄876.1 M12 22

108.0 mm4.250 ½ 7⁄8108.0 M12 22

44.500 ½ 7⁄8114.3 M12 22

133.0 mm5.250 5⁄8 1 1⁄16133.0 M16 27

139.7 mm5.500 5⁄8 1 1⁄16139.7 M16 27

5 – 65.563 – 6.625 5⁄8 1 1⁄16141.3 – 168.3 M16 27

159.0 mm6.250 5⁄8 1 1⁄16159.0 M16 27

165.1 mm6.500 5⁄8 1 1⁄16165.1 M16 27

200A (JIS)— ¾ 1 ¼

216.3 M20 32

88.625 ¾ 1 ¼219.1 M20 32

Size Nut Size

Nominal Sizeinches or mm

Actual Pipe Outside

Diameterinches/mm

inches/Metric

inches/mm

2 – 62.375 – 6.625 ½ 7⁄860.3 – 168.3 M12 22

76.1 – 139.7 mm3.000 – 5.500 ½ 7⁄876.1 – 139.7 M12 22

159.0 mm6.250 5⁄8 1 1⁄16159.0 M16 27

165.1 mm6.500 ½ 7⁄8165.1 M12 22

Page 185: Victaulic I-100 Field Installation Handbook.pdf

FireLock Outlet-T

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

The Style 922 FireLock Outlet-T is UL Listed and FM Approved up to 300 psi/2068 kPa

and VdS approved up to 16 Bar at ambient temperatures that are typical for fire protection

systems.

The Style 922 FireLock Outlet-T is designed for direct connection of sprinkler heads,

drop nipples, sprigs, drains, gauges, and other outlet products.

NOTICE

Proper preparation of the hole is essential for sealing and performance.

Drill a 1 3⁄16-inch/30-mm minimum hole (1 ¼-inch/32-mm maximum hole) on the

centerline of the pipe. Holes MUST be drilled on the centerline of the pipe.

Victaulic female threaded products are designed to accommodate standard NPT or

BSPT (Optional) male pipe threads only. Use of male threaded products with special

features, such as probes, dry pendent sprinkler heads, etc., should be verified as

suitable for use with this Victaulic product. Failure to verify suitability in advance may

result in assembly problems or leakage.

Ensure that a ½-inch/13-mm area around the hole is clean, smooth, and free from

indentations and/or projections that could affect gasket sealing (refer to the sketch

below). Remove any burrs and sharp or rough edges from the hole. Burrs and sharp

edges might affect assembly, proper seating of the locating collar, flow from the outlet,

or gasket seating.

½ inch/13 mm

A

Exaggerated for clarity

Page 186: Victaulic I-100 Field Installation Handbook.pdf

Installation

Install the

gasket into the gasket pocket, as shown

above. Press the gasket along the full

circumference to ensure that it seats fully

in the gasket pocket.

Insert a

bolt into the two housings. Thread a flange

nut loosely onto the end of the bolt (nut

should be flush with end of bolt) to allow

for the “swing-over” feature.

Install the

outlet housing onto the pipe by centering

the locating collar in the hole. To check

for proper engagement, slide the outlet

housing back and forth while pushing

down. A properly positioned outlet housing

can be moved only a small amount in any

direction.

3a. While holding the outlet housing in

place, rotate the lower housing around the

pipe. Make sure the locating collar remains

seated properly in the hole.

Insert the remaining bolt into the

outlet housing and lower housing. Thread a

flange nut onto the bolt finger-tight.

Make sure the oval neck of each bolt seats

properly in the bolt hole.

Tighten the

flange nuts evenly by alternating sides to

an approximate torque value of 20 ft-lbs/

compression. To avoid over-

tightening the flange nuts, use a wrench

with a maximum length of 8 inches/

200 mm. DO NOT over-tighten the flange

nuts.

The

outlet housing, near the gasket, should

not make metal-to-metal contact with the

pipe. In addition, a small gap is should be

present between the outlet housing and

the lower housing, as shown above.

Nut Sizeinches/Metric

Sizeinches/mm

All Sizes3⁄8 9⁄16

M10 15

Page 187: Victaulic I-100 Field Installation Handbook.pdf

I-100_180

Vic-Let™ Strapless Outlet

Vic-O-Well™ Strapless Thermometer Outlet

piping products.

or adjust any Victaulic piping products.

product installation, and/or property damage.

Victaulic Style 923 Vic-Let Strapless Outlets are rated to 300-psi/2068-kPa working

pressure on standard-weight steel pipe in sizes 4 – 8 inches/114.3 – 219.1-mm

and Schedule 10 through 40 steel pipe in sizes 10-inches/273.0-mm and larger. In

addition, Style 923 Vic-Let Strapless Outlets are UL/ULC Listed for 175-psi/1206 kPa

fire protection service.

Victaulic Style 924 Vic-O-Well Strapless Thermometer Outlets are rated to 300-

psi/ 2068-kPa working pressure on standard weight steel pipe. In addition, Style 924

Vic-O-Well Strapless Thermometer Outlets contain 1 ¼ - 18 NEF extra-fine threads to

receive thermometers with a 6-inch/152-mm nominal bulb length only.

NOTICE

Proper preparation of the hole is essential for sealing and performance.

Drill a 1 ½-inch/38-mm minimum hole (1 9⁄16-inch/40-mm maximum hole) on the

centerline of the pipe. Holes MUST be drilled on the centerline of the pipe.

Ensure that a 5⁄8-inch/16-mm area around the hole is clean, smooth, and free from

indentations and/or projections that could affect gasket sealing (refer to the sketch

below). Remove any burrs and sharp or rough edges from the hole. Burrs and sharp

edges might affect assembly, flow from the outlet, or gasket seating.

The pipe, within the “A” dimension shown in the sketch below, must be free from any

dirt, scale, or projections that might prevent the strapless outlet from seating fully on

the pipe.

A

5⁄8 inch/16 mm

Exaggerated for clarity

Page 188: Victaulic I-100 Field Installation Handbook.pdf

I-100_181

Installation

NOTICE

Let Strapless Outlet. In addition,

Vic-O-Well Strapless Thermometer Outlets.

924

Exaggerated for Clarity

Make sure the

“923” or “924” marking on the top hex nut

is facing toward the curvature of the collar

(along pipe axis), as shown above.

Position the lettered face of the assembly

nut at the top of the threads, as shown

above. DO NOT remove the assembly nut.

Apply a

thin coat of Victaulic lubricant or silicone

lubricant to the exposed gasket sealing

lip to ensure proper sealing. DO NOT use

petroleum-based lubricants on the gasket.

FIGURE 1HEELTOE

Exaggerated for Clarity

Align the “foot” of

the outlet with the pipe. Tilt the “toe” into

the hole to insert the outlet (refer to Figure

1 above).

FIGURE 2

HEEL

Exaggerated for Clarity

Shift the

outlet to position the “heel” inside the

pipe, as shown in Figure 2 above.

The heel must be positioned, as shown

in Figure 2 above, to ensure proper

performance under operating conditions.

Page 189: Victaulic I-100 Field Installation Handbook.pdf

924

Exaggerated for Clarity

Hold the collar in position, and

hand-tighten the assembly nut. Check

for proper positioning after tightening by

attempting to tilt the outlet in the hole. The

outlet should not shift. If the outlet shifts,

loosen the assembly nut, re-position the

outlet, and hand-tighten the assembly

nut again. Make sure the “923” or

“924” marking on the top hex nut is still

facing toward the curvature of the collar

(along pipe axis), as shown above.

Wrench-tighten the assembly nut until

the collar deforms and contacts the pipe

evenly on all sides. Maintain collar/gasket

alignment to prevent gasket pinching. DO NOT

For 4 – 8-inch/114.3 – 219.1-mm size

outlets, a “ratcheting” motion will help

maintain alignment with the collar.

NOTICE

installation.

After wrench-

tightening the assembly nut, check to

make sure the curvature of the collar

conforms to the curvature of the pipe. In

addition, make sure the collar contacts the

pipe evenly on all sides and that no portion

of the gasket is exposed.

the pipe evenly on all sides.

during installation.DO NOT exceed 1 ½ times the

tests.

serious personal injury and/or property damage.

Make the

required connection by using a second

wrench on the top hex only. To prevent

loosening of the outlet in the hole, DO NOT

use the assembly nut for tightening this

connection.

NOTICE

¼ -

nominal bulb length only.

Page 190: Victaulic I-100 Field Installation Handbook.pdf

I-100_183

Valve Installation and Operation

Ball Valves, Plug Valves

Vic®-300 MasterSeal™

Valve Vic-Ball Valve Ball Valve

Vic-Plug Balancing Valve

Page 191: Victaulic I-100 Field Installation Handbook.pdf

VALVE INSTALLATION

When installing a Victaulic butterfly valve into a piping system, follow the instructions

supplied with the coupling. Refer to the notes below for applications/limitations.

When using butterfly valves for throttling service,

Victaulic recommends the disc to be positioned no

less than 30 degrees open. For best results, the

disc should be between 30 and 70 degrees open.

High pipeline velocities and/or throttling with the

disc less than 30 degrees open may result in noise,

vibration, cavitation, severe line erosion, and/or loss

of control. For details regarding throttling services,

contact Victaulic.

Victaulic recommends limiting the flow velocities for

water service to 20 feet per second/6.1 meters per

second. When higher flow velocities are necessary,

contact Victaulic. When dealing with flow media other than water, contact Victaulic.

When directly connecting an end cap to a butterfly valve, use only a tapped end cap for

pressure relief. If the butterfly valve is opened then closed unknowingly while the end

cap is attached, the space between the disc and end cap will be filled and pressurized.

A sudden release of energy can occur if the end cap is removed while the space

behind it is pressurized.

to remove the cap.

serious personal injury.

Victaulic Butterfly Valves are designed with grooved ends for use with grooved pipe

couplings. If flange connections are required, refer to the notes on the following page

regarding Vic-Flange Adapter restrictions.

NOTICE

DO NOT use plain-end NPS pipe or grooved cast ductile iron pipe.

Page 192: Victaulic I-100 Field Installation Handbook.pdf

I-100_185VALVE INSTALLATION

Victaulic recommends Style 07 Zero-Flex Rigid Couplings or Style 107 Quick-Vic Rigid

Couplings with the Series 700 Butterfly Valve to eliminate joint deflection or valve

rotation at the coupling connection to the piping system. For installation requirements,

follow the instructions supplied with the coupling.

For Series 761 Vic-300 MasterSeal Butterfly Valves, lubricated nitrile “T” seat seals

are recommended for dry or lubricated gas services.

Style 741 Vic-Flange Adapters can be used on all sizes of Series 761 Vic-300

MasterSeal Butterfly Valves.

Series 761 Vic-300 MasterSeal Butterfly Valves cannot be connected directly to

flanged components with Style 743 Vic-Flange Adapters. A No. 46 ANSI 300 groove-

by-flange adapter is required for this application.

Series W761 AGS Vic-300 Butterfly Valves CAN be connected directly to flanged

components with Style W741 AGS Vic-Flange Adapters.

When connecting a Series W761 AGS Vic-300 Butterfly Valve to a Series W715

AGS Dual-Disc Vic-Check® Valve, a pipe spool is required between the two valves to

prevent disc interference.

When a Series W715 AGS Dual-Disc Vic-Check Valve is placed near a Series W761

AGS Vic-300 Butterfly Valve, orient the center brace/disc shaft of the Series W715

at right angles to the butterfly valve stem. Failure to do so will cause uneven and

unstable flow through the Series W715, resulting in noise and reduced valve life.

Style 741 Vic-Flange Adapters can be used only on one side of 8-inch/219.1-mm and

smaller Series 765, 705, 766, and 707C Butterfly Valves that will not interfere with

mating components and handle operation.

Style 741 Vic-Flange Adapters cannot be used on 10-inch/273.0-mm Series 765 and

Series 705 Butterfly Valves.

Series 765, 705, 766, and 707C Butterfly Valves cannot be connected directly to

flanged components with Style 743 Vic-Flange Adapters. A No. 46 ANSI 300 groove-

by-flange adapter is required for this application.

Series 763 Stainless Steel Butterfly Valves CANNOT be connected directly to flanged

components with Style 743 Vic-Flange Adapters. A No. 46 ANSI 300 groove-by-flange

adapter is required for this application.

Adjustment of the travel limit stops for Victaulic Butterfly Valves with gear operators can

be performed while the system is operational. Cycling of the valve to test travel

limit stop adjustments may affect downstream equipment. Refer to the instructions on the

following pages for detailed instructions on how to adjust the travel limit stops.

Page 193: Victaulic I-100 Field Installation Handbook.pdf

I-100_186VALVE INSTALLATION

1. Turn the handwheel of the gear

operator counterclockwise to ensure the

valve disc is not in the fully closed position.

Remove the travel stop dust cap

from the right side of the gear operator, as

shown above.

3. Using an appropriately sized wrench,

loosen the hex lock nut (counterclockwise)

located on the right side of the gear

operator.

Using an appropriately sized allen

wrench, loosen the internal set screw

counterclockwise to increase the distance

for disc travel.

Using an appropriately sized allen

wrench, tighten the internal set screw

clockwise to decrease the distance for disc

travel.

5. Turn the handwheel of the gear

operator in the clockwise direction to

place the valve disc in the closed (shut)

position. Confirm that the valve is providing

shutoff service. Repeat steps 4 and 4a, as

necessary.

6. With the valve disc in the closed

(shut) position, tighten the internal set

screw (clockwise) with an appropriately

sized allen wrench.

NOTICE

Using an appropriately sized wrench,

tighten the hex lock nut (clockwise) located

on the right side of the gear operator.

8. Verify proper operation of the gear

operator by turning the handwheel.

9. Replace the travel stop dust cap.

10. Follow the “Adjusting the Gear

Operator’s Open Travel Limit Stops”

section on the following page.

Page 194: Victaulic I-100 Field Installation Handbook.pdf

VALVE INSTALLATION

1. Turn the handwheel of the gear

operator clockwise to place the valve disc

in the slightly open position.

Remove the travel stop dust cap from

the left side of the gear operator, as shown

above.

3. Using an appropriately sized wrench,

loosen the hex lock nut (counterclockwise)

located on the left side of the gear

operator.

Using an appropriately sized allen

wrench, loosen the internal set screw

counterclockwise.

5. Turn the handwheel of the gear

operator to place the valve disc in the

desired open position.

6. With the valve disc in the desired

open position, tighten the internal set

screw (clockwise) with an appropriately

sized allen wrench.

Using an appropriately sized wrench,

tighten the hex lock nut (clockwise) located

on the left side of the gear operator.

8. Verify proper operation of the gear

operator by turning the handwheel.

9. Replace the travel stop dust cap.

Page 195: Victaulic I-100 Field Installation Handbook.pdf

I-100_188VALVE INSTALLATION

1. Turn the handwheel of the gear

operator counterclockwise to ensure the

valve disc is not in the fully closed position.

Remove the travel stop dust cap

from the right side of the gear operator, as

shown above.

3. Using an appropriately sized allen

wrench, loosen the internal set screw

counterclockwise to increase the distance

for disc travel.

3a. Using an appropriately sized allen

wrench, tighten the internal set screw

clockwise to decrease the distance for disc

travel.

3b. Turn the handwheel of the gear

operator in the clockwise direction to

place the valve disc in the closed (shut)

position. Confirm that the valve is providing

shutoff service. Repeat steps 3 and 3a, as

necessary.

With the valve disc in the closed

(shut) position, tighten the internal set

screw (clockwise) with an appropriately

sized allen wrench.

NOTICE

5. Verify proper operation of the gear

operator by turning the handwheel.

6. Replace the travel stop dust cap.

Follow the “Adjusting the Gear

Operator’s Open Travel Limit Stops”

section on the following page.

Page 196: Victaulic I-100 Field Installation Handbook.pdf

I-100_189VALVE INSTALLATION

1. Turn the handwheel of the gear

operator clockwise to place the valve disc

in the slightly open position.

Remove the travel stop dust cap from

the left side of the gear operator, as shown

above.

3. Using an appropriately sized allen

wrench, loosen the internal set screw

counterclockwise.

3a. Turn the handwheel of the gear

operator to place the valve disc in the

desired open position.

With the valve disc in the desired

open position, tighten the internal set

screw (clockwise) with an appropriately

sized allen wrench.

5. Verify proper operation of the gear

operator by turning the handwheel.

6. Replace the travel stop dust cap.

Page 197: Victaulic I-100 Field Installation Handbook.pdf

I-100_190VALVE INSTALLATION

When installing a Victaulic check valve into a piping system, follow the instructions

supplied with the coupling. Refer to the notes below for applications/limitations.

Placement of check valves too close to sources of unstable flow will shorten the life of

the valve and may potentially damage the system. To extend valve life, valves should be

installed a reasonable distance downstream from pumps, elbows, expanders, reducers,

or other similar devices. Sound piping practices dictate a minimum of five times the pipe

diameter for general use. Distances between three and five diameters are allowable,

provided the flow velocity is less than 8 feet per second/2.4 meters per second. Distances

less than three diameters are not recommended and will violate the Victaulic product

warranty. These distances do not apply to fire protection installations.

Series 712, 712S, and 713 Swinger Check Valves must be installed with the arrow on

the body pointing in the correct direction of flow through the pipeline.

Series 712, 712S, and 713 Swinger Check Valves SHOULD NOT be installed vertically.

® Valve

xCenterBrace

Correct Orientation forHorizontal Installation

Horizontal Installation Incorrect Orientation forHorizontal Installation

Series W715 AGS Dual-Disc Vic-Check Valves can be installed either vertically (flow

up) or horizontally.

For horizontal installations, the center brace inside the Series W715 AGS Dual-Disc

Vic-Check Valve must be in the vertical position, as shown above.

Style W741 AGS Vic-Flange Adapters can be installed on either end of a Series W715

AGS Dual-Disc Vic-Check Valve.

When connecting a Series W715 AGS Dual-Disc Vic-Check Valve to a Series W761

AGS Vic-300 Butterfly Valve, a pipe spool is required between the two valves to

prevent disc interference.

When a Series W715 AGS Dual-Disc Vic-Check Valve is placed near a Series W761

AGS Vic-300 Butterfly Valve, orient the center brace/disc shaft of the Series W715

at right angles to the butterfly valve stem. Failure to do so will cause uneven and

unstable flow through the Series W715, resulting in noise and reduced valve life.

Series 716/716H Vic-Check Valves can be installed either vertically (flow up) or

horizontally with the arrow on the body pointing in the correct direction of flow through

the pipeline.

Style 741 Vic-Flange Adapters can be installed on either end of a Series 716/716H

Vic-Check Valve.

Page 198: Victaulic I-100 Field Installation Handbook.pdf

I-100_191VALVE INSTALLATION

Series 717, 717H, 717R, and 717HR FireLock Check Valves can be installed either

vertically (flow up) or horizontally with the arrow on the body pointing in the correct

direction of flow through the pipeline.

Style 741 and Style 744 Vic-Flange Adapters can be installed on either end of a Series

717, 717H, 717R, or 717HR FireLock Check Valve.

Series 779 Venturi Check Valves can be installed either vertically (flow up) or

horizontally with the arrow on the body pointing in the correct direction of flow through

the pipeline.

The bushing or pipe plug that retains the shaft/disc must be located at the top of the

valve in horizontal installations (refer to drawing below).

When installing a Victaulic ball valve into a piping system, follow the instructions supplied

with the coupling. For threaded valves, follow standard threading practices for proper

installation. Victaulic ball valves are intended for open/closed services only and

MUST NOT be used for throttling services.

When directly connecting an end cap to a ball valve, use only a tapped end cap for

pressure relief. If the ball valve is opened then closed unknowingly while the end cap

is attached, the space between the ball and end cap will be filled and pressurized. A

sudden release of energy can occur if the end cap is removed while the space behind

it is pressurized.

When directly connecting an end cap to a ball valve, use

to remove the cap.

serious personal injury.

Page 199: Victaulic I-100 Field Installation Handbook.pdf

VALVE INSTALLATION

When directly connecting an end cap to a plug valve, use only a tapped end cap for

pressure relief. If the plug valve is opened then closed unknowingly while the end cap

is attached, the space between the plug and end cap will be filled and pressurized. A

sudden release of energy can occur if the end cap is removed while the space behind

it is pressurized.

When directly connecting an end cap to a plug valve, use

to remove the cap.

serious personal injury.

Series 365 Vic-Plug™ AWWA Plug Valve

Refer to the operation and maintenance manual supplied with the Series 365 Plug

Valve for detailed information regarding valve installation, accessory installation, and

maintenance requirements.

Refer to the operation and maintenance manual supplied with the Series 377 Vic-

Plug Balancing Valve for detailed information regarding valve installation, accessory

installation, and maintenance requirements.

The Series 377 Vic-Plug Balancing Valve is an eccentric, grooved-end plug valve

designed specifically for throttling services.

For 3 – 12-inch/88.9 – 323.9-mm sizes, the Victaulic Style 307 Transition Coupling is

available to directly connect the Series 377 to grooved-end steel and other NPS pipe.

For installing these sizes of Vic-Plug valves into a piping system, follow the instructions

supplied for the Style 307 Transition Coupling.

R

SE

AT

EN

D

SEATEND

FLOWDIRECTION

Vic-PlugBalancing Valve

Pump

Page 200: Victaulic I-100 Field Installation Handbook.pdf

I-100_193

Product

Page 201: Victaulic I-100 Field Installation Handbook.pdf

Victaulic Style 735 Fire Pump Test Meters are designed specifically for monitoring fire

protection systems. The Style 735 contains grooved ends for easy installation with

Victaulic couplings that are FM Approved. The maximum working pressure for Model

“L” Style 735 Fire Pump Test Meters is 175 psi/1200 kPa, and the Model “S” is rated to

500 psi/3450 kPa.

To ensure proper installation and accurate flow readings, all sizes of Style 735 Fire Pump

Test Meters have a minimum straight-pipe requirement of five diameters upstream and

two diameters downstream from any valve or fitting (refer to the drawing below).

The Style 735 can be installed either horizontally or vertically.

VICTAULIC® FIRE PUMP TEST METER

THROTTLE VALVE "C"

AIR VENT

BYPASS VALVE "B"

FLOWTO RESERVOIR

OR WASTE

OPTIONAL TO

PUMP INLET

SUPPLY FROM

CITY MAIN OR

RESERVOIRFIRE PUMP

MIN. PIPE DIAMETERS FROM VALVE

VALVE

FLOW

VALVE "A"

TO SYSTEM

SUGGESTED

PIPING

DIAGRAM

(2) (5)

1. Close the system valve “A.”

Open the bypass valve “B,” and throttle valve “C.”

3. Purge the meter, which is located on the Style 735 Fire Pump Test Meter, as follows:

3a. Open the station shutoff valves (below meter), and vent the valves (above meter).

When a steady stream of water passes through each plastic hose, the meter is purged of

air. Close all valves after the air is purged.

Start the fire pump, and read the meter in gpm (m3 /hr).

5. Refer to the gpm requirement for the pump, and adjust the throttle valve to achieve

various flow readings. Record the gpm, suction pressure, and discharge pressures, etc.,

in accordance with requirements established by the local authority having jurisdiction.

Page 202: Victaulic I-100 Field Installation Handbook.pdf

I-100_195

English and Metric Conversion Chart

ANSI Commercial Pipe Sizes

25.4 X inches (in) = millimeters (mm) X 0.03937

0.3048 X feet (ft) = meter (m) X 3.281

0.4536 X pounds (lbs) = kilograms (kg) X 2.205

28.35 X ounces (oz) = grams (g) X 0.03527

6.894 X pressure (psi) = kilopascals (kPa) X 0.145

.069 X pressure = Bar X 14.5

4.45 X end load (lbs) = Newtons (N) X 0.2248

1.356 X torque (ft-lbs) = X 0.738

F – 32 ÷ 1.8 temperature (°F) = Celsius (°C) C ÷ 17.78 X 1.8

745.7 X horsepower (hp) = watts (W) X 1.341 X 10-3

3.785 X gallons per minute (gpm) = liters per minute (l/m) X 0.2642

3.7865 X10-3 gallons per minute (gpm)

=cubic meters per

minute (m3/m)X 264.2

Page 203: Victaulic I-100 Field Installation Handbook.pdf

I-100_196

Siz

e

Nom

inal

Siz

ein

ches

/mm

Act

ual

Out

side

Dia

met

erin

ches

/mm

Sch

. 5

SS

ch.

10S

Sch

. 10

Sch

. 30

Std

.S

ch.

60

Ext

raStr

ong

Sch

. 8

0S

ch.

100

Sch

.S

ch.

Sch

.16

0XX

Str

ong

1⁄80

.40

5—

0.0

49

——

—0

.06

80

.06

8—

0.0

95

0.0

95

——

——

—4

10.3

1.2

1.7

1.7

2.4

2.4

¼0

.54

0—

0.0

65

——

—0

.08

80

.08

8—

0.1

190

.119

——

——

—8

13.7

1.7

2.2

2.2

3.0

3.0

3⁄80

.67

5—

0.0

65

——

—0

.09

10

.09

1—

0.1

26

0.1

26

——

——

—10

17.1

1.7

2.3

2.3

3.2

3.2

½0

.84

00

.06

50

.08

3—

——

0.1

09

0.1

09

—0

.14

70

.14

7—

——

0.1

88

0.2

94

1521

.31.

72

.12

.82

.83

.73

.74

.87.

5

¾1.

05

00

.06

50

.08

3—

——

0.1

130

.113

—0

.15

40

.15

4—

——

0.2

190

.30

82

02

6.9

1.7

2.1

2.9

2.9

3.9

3.9

5.6

7.8

11.

315

0.0

65

0.1

09

——

—0

.13

30

.13

3—

0.1

79

0.1

79

——

—0

.25

00

.35

82

53

3.7

1.7

2.8

3.4

3.4

4.5

4.5

6.4

9.1

1 ¼

1.6

60

0.0

65

0.1

09

——

—0

.14

00

.14

0—

0.1

91

0.1

91

——

—0

.25

00

.38

23

24

2.4

1.7

2.8

3.6

3.6

4.9

4.9

6.4

9.7

1 ½

1.9

00

0.0

65

0.1

09

——

—0

.14

50

.14

5—

0.2

00

0.2

00

——

—0

.28

10

.40

04

04

8.3

1.7

2.8

3.7

3.7

5.1

5.1

7.1

10.2

22

.37

50

.06

50

.10

9—

——

0.1

54

0.1

54

—0

.218

0.2

18—

——

0.3

44

0.4

36

50

60

.31.

72

.83

.93

.95

.55

.58

.711

.1

2 ½

2.8

75

0.0

83

0.1

20

——

—0

.20

30

.20

3—

0.2

76

0.2

76

——

—0

.37

50

.55

26

57

3.0

2.1

3.0

5.2

5.2

7.0

7.0

9.5

14.0

33

.50

00

.08

30

.12

0—

——

0.2

160

.216

—0

.30

00

.30

0—

——

0.4

38

0.6

00

80

88

.92

.13

.05

.55

.57.

67.

611

.115

.2

3 ½

4.0

00

0.0

83

0.1

20

——

—0

.22

60

.22

6—

0.3

180

.318

——

——

—9

010

1.6

2.1

3.0

5.7

5.7

8.1

8.1

Page 204: Victaulic I-100 Field Installation Handbook.pdf

Siz

e

Nom

inal

Siz

ein

ches

/mm

Act

ual

Out

side

Dia

met

erin

ches

/mm

Sch

. 5

SS

ch.

10S

Sch

. 10

Sch

. 30

Std

.S

ch.

60

Ext

raStr

ong

Sch

. 8

0S

ch.

100

Sch

.S

ch.

Sch

.16

0XX

Str

ong

44

.50

00

.08

30

.12

0—

——

0.2

37

0.2

37

—0

.33

70

.33

7—

0.4

38

—0

.531

0.6

7410

011

4.3

2.1

3.0

6.0

6.0

8.6

8.6

11.1

13.5

17.1

55

.56

30

.10

90

.13

4—

——

0.2

58

0.2

58

—0

.37

50

.37

5—

0.5

00

—0

.62

50

.75

012

514

1.3

2.8

3.4

6.6

6.6

9.5

9.5

12.7

15.9

19.1

66

.62

50

.10

90

.13

4—

——

0.2

80

0.2

80

—0

.43

20

.43

2—

0.5

62

—0

.719

0.8

64

150

168

.32

.83

.47.

17.

111

.011

.014

.318

.321

.9

88

.62

50

.10

90

.14

8—

0.2

50

0.2

77

0.3

22

0.3

22

0.4

06

0.5

00

0.5

00

0.5

94

0.7

190

.812

0.9

06

0.8

75

20

021

9.1

2.8

3.8

6.4

7.0

8.2

8.2

10.3

12.7

12.7

15.1

18.3

20

.62

3.0

22

.2

1010

.75

00

.13

40

.16

5—

0.2

50

0.3

07

0.3

65

0.3

65

0.5

00

0.5

00

0.5

94

0.7

190

.84

41.

00

01.

125

1.0

00

25

02

73

.03

.44

.26

.47.

89

.39

.312

.712

.715

.118

.321

.42

5.4

28

.62

5.4

1212

.75

00

.15

60

.18

0—

0.2

50

0.3

30

0.3

75

0.4

06

0.5

62

0.5

00

0.6

88

0.8

44

1.0

00

1.12

51.

312

1.0

00

30

03

23

.94

.04

.66

.48

.49

.510

.314

.312

.717

.521

.42

5.4

28

.63

3.3

25

.4

14 O

D14

.00

00

.15

60

.18

80

.25

00

.312

0.3

75

0.3

75

0.4

38

0.5

94

0.5

00

0.7

50

0.9

38

1.0

94

1.2

50

1.4

06

—3

55

.64

.04

.86

.47.

99

.59

.511

.115

.112

.719

.12

3.8

27.

831

.83

5.7

16 O

D16

.00

00

.16

50

.18

80

.25

00

.312

0.3

75

0.3

75

0.5

00

0.6

56

0.5

00

0.8

44

1.0

311.

219

1.4

38

1.5

94

—4

06

.44

.24

.86

.47.

99

.59

.512

.716

.712

.721

.42

6.2

31.0

36

.54

0.5

18 O

D18

.00

00

.16

50

.18

80

.25

00

.312

0.4

38

0.3

75

0.5

62

0.7

50

0.5

00

0.9

38

1.15

61.

37

51.

56

21.

78

1—

45

7.0

4.2

4.8

6.4

7.9

11.1

9.5

14.3

19.1

12.7

23

.82

9.4

34

.93

9.7

45

.2

20

OD

20

.00

00

.18

80

.218

0.2

50

0.3

75

0.5

00

0.3

75

0.5

94

0.8

120

.50

01.

031

1.2

81

1.5

00

1.7

50

1.9

69

—5

08

.04

.85

.56

.49

.512

.79

.515

.12

0.6

12.7

26

.23

2.5

38

.14

4.5

50

.0

22

OD

22

.00

00

.18

80

.218

0.2

50

0.3

75

0.5

00

0.3

75

—0

.87

50

.50

01.

125

1.3

75

1.6

25

1.8

75

2.1

25

—5

59

.04

.85

.56

.49

.512

.79

.52

2.2

12.7

28

.63

4.9

41.3

47.

65

4.0

24

OD

24

.00

00

.218

0.2

50

0.2

50

0.3

75

0.5

62

0.3

75

0.6

88

0.9

69

0.5

00

1.21

91.

531

1.8

122

.06

22

.34

4—

610

.05

.56

.46

.49

.514

.39

.517

.52

4.6

12.7

31.0

38

.94

6.0

52

.45

9.5

Page 205: Victaulic I-100 Field Installation Handbook.pdf

I-100_198

Siz

e

Nom

inal

Siz

ein

ches

/mm

Act

ual

Out

side

Dia

met

erin

ches

/mm

Sch

. 5

SS

ch.

10S

Sch

. 10

Sch

. 30

Std

.S

ch.

60

Ext

raStr

ong

Sch

. 8

0S

ch.

100

Sch

.S

ch.

Sch

.16

0XX

Str

ong

26

OD

26

.00

0—

—0

.312

0.5

00

—0

.37

5—

—0

.50

01.

313

——

——

—6

60

.47.

912

.79

.512

.73

3.4

28

OD

28

.00

0—

—0

.312

0.5

00

0.6

25

0.3

75

——

0.5

00

——

——

——

711

.07.

912

.715

.99

.512

.7

30

OD

30

.00

00

.25

00

.312

0.3

120

.50

00

.62

50

.37

5—

—0

.50

0—

——

——

—7

62

.06

.47.

97.

912

.715

.99

.512

.7

32

OD

32

.00

0—

—0

.312

0.5

00

0.6

25

0.3

75

0.6

88

—0

.50

0—

——

——

—8

13.0

7.9

12.7

15.9

9.5

17.5

12.7

34

OD

34

.00

0—

—0

.312

0.5

00

0.6

25

0.3

75

0.6

88

—0

.50

0—

——

——

—8

63

.67.

912

.715

.99

.517

.512

.7

36

OD

36

.00

0—

—0

.312

0.5

00

0.6

25

0.3

75

0.7

50

—0

.50

0—

——

——

—9

14.0

7.9

12.7

15.9

9.5

19.1

12.7

42

OD

42

.00

0—

——

0.3

75

——

——

0.5

00

——

——

——

106

7.0

9.5

12.7

Page 206: Victaulic I-100 Field Installation Handbook.pdf

I-100_199

Fraction ininches

DecimalEquivalent

inches

DecimalEquivalentmillimeters

Fraction ininches

DecimalEquivalent

inches

DecimalEquivalentmillimeters

1⁄64 0.016 0.397 33⁄64 0.516 13.097

1⁄32 0.031 0.794 17⁄32 0.531 13.494

3⁄64 0.047 1.191 35⁄64 0.547 13.891

1⁄16 0.063 1.588 9⁄16 0.563 14.288

5⁄64 0.781 1.984 37⁄64 0.578 14.684

3⁄32 0.094 2.381 19⁄32 0.594 15.081

7⁄64 0.109 2.778 39⁄64 0.609 15.478

1⁄8 0.125 3.175 5⁄8 0.625 15.875

9⁄64 0.141 3.572 41⁄64 0.641 16.272

5⁄32 0.156 3.969 21⁄32 0.656 16.669

11⁄64 0.172 4.366 43⁄64 0.672 17.066

3⁄16 0.188 4.763 11⁄16 0.688 17.463

13⁄64 0.203 5.159 45⁄64 0.703 17.859

7⁄32 0.219 5.556 23⁄32 0.719 18.256

15⁄64 0.234 5.953 47⁄64 0.734 18.653

¼ 0.250 6.350 ¾ 0.750 19.050

17⁄64 0.266 6.747 49⁄64 0.766 19.447

9⁄32 0.281 7.144 25⁄32 0.781 19.844

19⁄64 0.297 7.541 51⁄64 0.797 20.241

5⁄16 0.313 7.938 13⁄16 0.813 20.638

21⁄64 0.328 8.334 53⁄64 0.828 21.034

1⁄3 0.333 8.467 27⁄32 0.844 21.431

11⁄32 0.344 8.731 55⁄64 0.859 21.828

23⁄64 0.359 9.128 7⁄8 0.875 22.225

3⁄8 0.375 9.525 57⁄64 0.891 22.622

25⁄64 0.391 9.922 29⁄32 0.906 23.019

13⁄32 0.406 10.319 59⁄64 0.922 23.416

27⁄64 0.422 10.716 15⁄16 0.938 23.813

7⁄16 0.438 11.113 61⁄64 0.953 24.209

29⁄64 0.453 11.509 31⁄32 0.969 24.606

15⁄32 0.469 11.906 63⁄64 0.984 25.003

½ 0.500 12.700 1 1.000 25.400

Min. Deg. Min. Deg. Min. Deg. Min. Deg.1 .0166 16 .2666 26 .4333 36 .6000

2 .0333 17 .2833 27 .4500 37 .6166

3 .0500 18 .3000 28 .4666 38 .6333

4 .0666 19 .3166 29 .4833 39 .6500

5 .0833 20 .3333 30 .5000 40 .6666

6 .1000 21 .3500 41 .6833 51 .8500

7 .1166 22 .3666 42 .7000 52 .8666

8 .1333 23 .3833 43 .7166 53 .8833

9 .1500 24 .4000 44 .7333 54 .9000

10 .1666 25 .4166 45 .7500 55 .9166

11 .1833 31 .5166 46 .7666 56 .9333

12 .2000 32 .5333 47 .7833 57 .9500

13 .2166 33 .5500 48 .8000 58 .9666

14 .2333 34 .5666 49 .8166 59 .9833

15 .2500 35 .5833 50 .8333 60 1.0000

Page 207: Victaulic I-100 Field Installation Handbook.pdf

Pounds PerSquare Inch

Pounds PerSquare Inch

1 2.31 100 230.90

2 4.62 110 253.93

3 6.93 120 277.07

4 9.24 130 300.16

5 11.54 140 323.25

6 13.85 150 346.34

7 16.16 160 369.43

8 18.47 170 392.52

9 20.78 180 415.61

10 23.09 200 461.78

15 34.63 250 577.24

20 46.18 300 692.69

25 57.72 350 808.13

30 69.27 400 922.58

40 92.36 500 1154.48

50 115.45 600 1385.39

60 138.54 700 1616.30

70 161.63 800 1847.20

80 184.72 900 2078.10

90 207.81 1000 2309.00

Pounds PerSquare Inch

Pounds PerSquare Inch

1 0.43 100 43.31

2 0.87 110 47.64

3 1.30 120 51.97

4 1.73 130 56.30

5 2.17 140 60.63

6 2.60 150 64.96

7 3.03 160 69.29

8 3.46 170 76.63

9 3.90 180 77.96

10 4.33 200 86.62

15 6.50 250 108.27

20 8.66 300 129.93

25 10.83 350 151.58

30 12.99 400 173.24

40 17.32 500 216.55

50 21.65 600 259.85

60 25.99 700 303.16

70 30.32 800 346.47

80 34.65 900 389.78

90 39.98 1000 433.00

Page 208: Victaulic I-100 Field Installation Handbook.pdf

The following table provides a listing of products and installation information. If you need

additional copies of any installation information, contact Victaulic at 1-800-PICK VIC.

If two sources of instructions are referenced in this index, Victaulic recommends

the use of both to ensure proper product installation.

Product Where to Find Instructions

AquaFlex® Products Instructions Shipped with Product

Aquamine® Spline Couplings I-Aquamine

Depend-O-Lok Type Couplings Instructions Shipped with Coupling

FireLock® Automatic Sprinkler Products I-40

FireLock Fire Protection Valves and

AccessoriesManual Shipped with Valve or Accessory

PermaLynx™ Permanent

Push-to-Connect System ProductsI-PermaLynx and I-600

Pipe Preparation Tools Manual Shipped with Tool

Pressfit® System Products I-500

Vic-Press Schedule 10S System Products I-P500

Series 247 FireLock Residential Zone

Control Riser Module AssemblyI-247

Series 317 AWWA Check Valve I-317

Series 365 AWWA Vic-Plug® Valve

(3 – 12-inch/88.9 – 323.9-mm Sizes)I-365/366/377.3-12

Series 377 Vic-Plug Balancing Valve I-365/366/377.3-12

Series 608 Copper Connection Butterfly

ValveI-600

Series 700 Butterfly Valve Manual Shipped with Valve and I-100

Series 702 Butterfly Valve I-702.GO

Series 705 FireLock Butterfly Valve I-765/705

Series 707C Supervised Closed Butterfly

ValveI-766/707C

Series 712/712S Swinger® Check Valve I-100

Series 713 Swinger Check Valve I-100

Series W715 AGS Dual-Disc

Vic-Check ValveI-100

Series 716H/716 Vic-Check® Valve I-100

Series 717H/717 Check Valve I-100

Series 717HR/717R Check Valve I-100

Series 722 Brass Body Ball Valve I-100

Series 723/723S Diverter Ball Valve I-100

Series 726/726S Vic-Ball® Valve I-100

Series 728 FireLock Ball Valve I-728

Series 730 Vic-Strainer® Tee Type I-730/732/AGS

Series W730 AGS Vic-Strainer Tee Type I-730/732/AGS

Page 209: Victaulic I-100 Field Installation Handbook.pdf

Product Where to Find Instructions

Series 731-D Suction Diffuser I-731D

Series 731-I Suction Diffuser (Europe Only) I-731I/W731I

Series W731-I AGS Suction Diffuser

(Europe Only)I-731I/W731I

Series 732 Vic-Strainer Wye Type I-730/732/AGS

Series W732 AGS Vic-Strainer Wye Type I-730/732/AGS

Series 747M FireLock Zone Control Riser

Module AssemblyI-747M

Series 761 Vic-300 MasterSeal®

Butterfly ValveI-VIC300MS and I-100

Series W761 AGS Vic-300 Butterfly Valve I-AGS.GO and I-100

Series 763 Butterfly Valve I-100

Series 765 FireLock Butterfly Valve I-765/705

Series 766 Butterfly Valve with Supervised-

Closed SwitchesI-766/707C

Series 779 Venturi Check Valve I-100

Series 782/783 TA Bypass Instructions Shipped with Valve

Series 785 TA TBVS Sweated-End Mini

Circuit Balancing ValveInstructions Shipped with Valve

Series 786 TA STAS Soldered-End Circuit

Balancing ValveInstructions Shipped with Valve

Series 787 TA STAD NPT Female Threaded

Circuit Balancing ValveInstructions Shipped with Valve

Series 788 TA STAF Flanged-End Circuit

Balancing ValveInstructions Shipped with Valve

Series 789 TA STAG Grooved-End Circuit

Balancing ValveInstructions Shipped with Valve

Style 005 FireLock Rigid Coupling I-100

Style 009H/009/009V FireLock EZ™ Rigid

CouplingI-009H/009/009V and I-100

Style 07 Zero-Flex® Rigid Coupling

(1 – 12-inch/33.7 – 323.9-mm Sizes)I-100

Style 07 Zero-Flex Rigid Coupling

(14 – 24-inch/355.6 – 610-mm Sizes)IT-07 and I-100

Style W07 AGS Rigid Coupling I-W07/W77 and I-100

Style 22 Coupling for Vic-Ring Adapters

and Shouldered-End PipeI-6000

Style 31 Coupling for AWWA Ductile Iron I-300

Style 31 Coupling for Vic-Ring Adapters

and Shouldered-End PipeI-6000

Style 41 Coupling for Vic-Ring Adapters

and Shouldered-End PipeI-6000

Style 44 Coupling for Vic-Ring Adapters

and Shouldered-End PipeI-6000

Style 72 Outlet Coupling I-100

Style 75 Flexible Coupling I-100

Page 210: Victaulic I-100 Field Installation Handbook.pdf

Product Where to Find Instructions

Style 77/77A/77S Flexible Coupling I-100

Style 77DX Flexible Stainless Steel

Coupling for Duplex and Super Duplex PipeI-100

Style W77 AGS Flexible Coupling I-W07/W77 and I-100

Style 78/78A Snap-Joint® Coupling I-100

Style 89 Rigid Coupling for Stainless Steel IT-89 and I-100

Style W89 AGS Rigid Coupling for Stainless

SteelI-W89

Style 99 Roust-A-Bout Coupling for Plain-

End SteelIT-99 and I-100

Style 107H/107 QuickVic® Rigid Coupling

for Steel PipeI-107H/107 and I-100

Style 150 Mover® Expansion Joint Submittal 09.06

Style 155 Expansion Joint Submittal 09.06

Style W155 AGS Expansion Joint Submittal 09.06

Style 177 QuickVic Flexible Coupling for

Steel PipeI-177 and I-100

Style 307 Coupling for Grooved NPS Steel

to Grooved AWWA Ductile IronI-300

Style 341 Vic-Flange Adapter for AWWA

Ductile IronI-300

Style 441 Vic-Flange for Stainless Steel I-441 and I-100

Style 475 Lightweight, Flexible Stainless

Steel CouplingI-100

Style 475DX Flexible Stainless Steel

Coupling for Duplex and Super Duplex PipeI-100

Style 489 Rigid Coupling for Stainless Steel

(11 ⁄2 – 4-inch/48.3 – 114.3-mm Sizes)IT-489.2-4 and I-100

Style 489 Rigid Coupling for Stainless Steel

(6 – 12-inch and 139.7 – 318.5-mm Metric

and JIS Sizes)

IT-489 and I-100

Style 489DX Stainless Steel Coupling for

Duplex and Super Duplex PipeI-100

Style 606 Rigid Coupling for Copper Tubing I-600

Style 607 QuickVic® Rigid Coupling for

Copper TubingI-607 and I-600

Style 622 Mechanical-T® Bolted Branch

Outlet for Copper TubingI-622 and I-600

Style 641 Vic-Flange Adapter for Copper

TubingI-600

Style 707-IJ Transition Coupling for NPS

to JISI-100

Style 720 TestMaster™ II Alarm Test

ModuleI-720

Style 720 TestMaster II Alarm Test Module

with Pressure Relief OptionI-720PR

Page 211: Victaulic I-100 Field Installation Handbook.pdf

Product Where to Find Instructions

Style 735 Fire Pump Test Meter I-100

Style 738 TA Portable Differential Meter Instructions Shipped with Meter

Style 739 Portable Master Meter Instructions Shipped with Meter

Style 740 TA CBI Meter Instructions Shipped with Meter

Style 741 NPS and Metric Vic-Flange

AdapterI-100

Style W741 AGS Vic-Flange Adapter IT-W741 and I-100

Style 743 Vic-Flange Adapter I-100

Style 744 FireLock Flange Adapter I-100

Style 750 Reducing Coupling I-100

Style 770 Large-Diameter Coupling IT-770 and I-100

Style 791 Vic-Boltless® Coupling I-100

Style 808 Duo-Lock Coupling I-808

Style 912 FireLock Low-Profile

Sprinkler-Tee (Europe Only)I-912 and I-100

Style 920 and 920N Mechanical-T Outlets I-920/920N and I-100

Style 922 FireLock Outlet-T I-922 and I-100

Style 923 Vic-Let Strapless Outlet I-923 and I-100

Style 924 Vic-O-Well Strapless

Thermometer OutletI-100

Style 926 Mechanical-T Spigot Assembly I-926 and I-100

Style 931 Vic-Tap II Mechanical-T VT-II

Style 994 Vic-Flange Adapter for HDPE IT-994 and I-900

Style 995 Coupling for Plain-End NPS and

Metric HDPEIT-995 and I-900

Style 997 Transition Coupling for HDPE

to SteelIT-997 and I-900

Style 2970 Aquamine Coupling for Plain-

end NPS PVCIT-2970

Style 2971 Aquamine Transition Coupling

for Plain-End NPS PVC to Plain-End HDPEIT-2971

Style 2972 Aquamine Transition Coupling

for Plain-End NPS PVC to Grooved NPS

Steel

IT-2972

Style HP-70 Rigid Coupling

(2 – 12-inch/60.3 – 323.9-mm Sizes)I-100

Style HP-70 Rigid Coupling

(14 – 16-inch/355.6 – 406.4-mm Sizes)IT-70 and I-100

Style HP-70ES Rigid Coupling

with EndSeal® Gasket

(2 – 12-inch/60.3 – 323.9-mm Sizes)

I-100

Page 212: Victaulic I-100 Field Installation Handbook.pdf

Product DataThe following information contains center-to-end, end-to-end, take-out, and similar

overall dimensions for couplings, flange adapters, fittings, valves, and accessories. Refer

to the current Victaulic submittal for complete dimensional information and for products

not listed in this section.

NOTICE

Page 213: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

SizeNo. 10 No. 11

½

No. 13 11¼

Nominal Size

inches or mm

Actual Pipe Outside

Diameter inches/mm

C to E inches/mm

C to Einches/mm

C to Einches/mm

C to Einches/mm

C to Einches/mm

C to Einches/mm

¾1.050 2.25 1.50 1.63 sw 1.38 sw

— —26.9 57 38 41 35

11.315 2.25 1.75 3.25 @ 1.38 sw

— —33.7 57 44 83 35

1 ¼1.660 2.75 1.75 1.75 1.38 sw

— —42.4 70 44 44 35

1 ½1.900 2.75 1.75 1.75 1.38 sw

— —48.3 70 44 44 35

22.375 3.25 2.00 3.75 @ 1.38 4.38 2.75 60.3 83 51 95 35 111 70

2 ½2.875 3.75 2.25 4.00 @ 1.50 5.13 3.0073.0 95 57 102 38 130 76

76.1 mm3.000 3.75 2.25 2.24 1.50

— —76.1 95 57 57 38

33.500 4.25 2.50 4.50 @ 1.50 5.88 3.3888.9 108 64 114 38 149 86

3 ½4.000 4.50 2.75 2.50 sw 1.75 sw

— —101.6 114 70 64 44

44.500 5.00 3.00 2.88 1.75 7.50 4.00114.3 127 76 73 44 191 102

108.0 mm4.250 5.00 3.00

— — — —108.0 127 76

4 ½5.000 5.25 sw 3.13 sw 3.50 1.88 sw

— —127.0 133 79 89 48

55.563 5.50 3.25 2.88 sw 2.00 sw

+ +141.3 140 83 73 51

133.0 mm5.250 5.50 3.25

— — — —133.0 140 83

139.7 mm5.500 5.50 3.25 2.87 2.00

— —139.7 140 83 73 51

66.625 6.50 3.50 6.25 @ 2.00 10.75 5.50168.3 165 89 159 51 273 140

159.0 mm6.250 6.50 3.50

— — — —159.0 165 89

¼

½

Cto E

C to EC to E

C to E

E to E

½

C to E

C to EC to E

¼

Page 214: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

SizeNo. 10 No. 11

½

No. 13 11¼

Nominal Size

inches or mm

Actual Pipe Outside

Diameter inches/mm

C to E inches/mm

C to Einches/mm

C to Einches/mm

C to Einches/mm

C to Einches/mm

C to Einches/mm

165.1 mm6.500 6.50 3.50 3.13 2.00 10.75 5.50165.1 165 89 79 51 273 140

88.625 7.75 4.25 7.75 @ 2.00 14.25 7.25219.1 197 108 197 51 362 184

1010.750 9.00 4.75 4.38 sw 2.13 sw 15.00 6.25273.0 229 121 111 54 381 159

1212.750 10.00 5.25 4.88 sw 2.25 sw 18.00 7.50323.9 254 133 124 57 457 191

14 #14.000 14.00 5.75 5.00 sw 3.50 sw 21.00 s 8.75 s355.6 355.6 146 127 89 533 222

377.0 mm †14.843 14.84 6.15

— — — —377.0 376.9 156.2

16 #16.000 16.00 6.63 5.00 sw 4.00 sw 24.00 s 10.00 s406.4 406.4 168 127 102 610 254

426.0 mm †16.772 16.77 6.95

— — — —426.0 426.0 176.5

18 #18.000 18.00 7.46 5.50 sw 4.50 sw 27.00 s 11.25 s457.0 457.2 189 140 114 686 286

480.0 mm †18.898 18.90 7.83

— — — —480.0 480.0 198.8

20 #20.000 20.00 8.28 6.00 sw 5.00 sw 30.00 s 12.50 s508.0 508.0 210 152 127 762 318

530.0 mm †20.866 20.87 8.64

— — — —530.0 530.0 219.4

24 #24.000 24.00 9.94 7.00 sw 6.00 sw 36.00 s 15.00 s610.0 609.6 252 178 152 914 381

630.0 mm †24.803 24.80 10.27

— — — —630.0 630.0 261.0

14 – 24

@ Gooseneck design, end-to-end dimension

# For use on cut-grooved systems only. For roll grooved systems, Victaulic offers the Advanced Groove System (AGS).

† Chinese standard sizes

All fittings are ductile iron unless noted otherwise with an “sw” or “s”. SW = Segmentally Welded, S = Carbon Steel

Cto E

C to EC to E

C to E

E to E

½

C to E

C to EC to E

¼

Page 215: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

With added wall thickness at bend for abrasive services

Size

No. 100-3D No. 110-3D

Nominal Size inches

Actual Pipe Outside Diameter

inches/mmC to E

inches/mmC to E

inches/mm

22.375 10.00 6.5060.3 254 165

33.500 13.00 7.7588.9 330 197

44.500 16.00 9.00114.3 406 229

66.625 24.00 13.50168.3 610 343

All fittings are ductile iron unless noted otherwise with an “sw” or “s”. SW = Segmentally Welded, S = Carbon Steel

C to E

No. 100-3D

C to E

No. 110-3D

Size

Nominal Size inches/Actual mm

C to E inches/mm

H inches/mm

B Diameter

inches/mm

6 ×

4 9.00 1.25 1.50168.3 114.3 229 32 38

×5 9.00 1.50 1.50

141.3 229 38 38

8 ×

6 10.50 2.13 1.50219.1 168.3 267 54 38

10×

8 12.00 2.40 1.50273.0 219.1 305 61 38

All fittings are ductile iron unless noted otherwise with an “sw” or “s”. SW = Segmentally Welded, S = Carbon Steel

C to E

H

B Dia.

C to E

H

B Dia.

Page 216: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

SizeNo. 18 No. 19

Nominal Size

inches

Actual Pipe Outside

Diameter inches/mm

inches/mm

C to TE inches/mm

inches/mm

C to TE inches/mm

¾1.050 2.25 2.25 1.50 1.5026.9 57 57 38 38

11.315 2.25 2.25

— —33.7 57 57

1 ¼1.660 2.75 2.75

— —42.4 70 70

1 ½1.900 2.75 2.75 1.75 1.7548.3 70 70 44 44

22.375 3.25 4.25

— —60.3 83 108

2 ½2.875 3.75 3.75 2.25 2.2573.0 95 95 57 57

33.500 4.25 6.00 2.50 4.2588.9 108 152 64 108

3 ½4.000 4.50 6.25 5.25 5.25101.6 114 159 133 133

66.625 6.50 6.50 3.50 3.50168.3 165 165 89 89

@ Available with British Standard Pipe Threads. Specify “BSPT” clearly on order.

All fittings are ductile iron unless noted otherwise with an “sw” or “s”. SW = Segmentally Welded, S = Carbon Steel

C toTE

C toGE C to

GE

C toTE

Page 217: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

C to E

CtoE

C to EC to LE

C toSE

C toGE

C to TE

Size

TeeNo. 35 No. 33

Branch

Nominal Size

inches or mm

Actual Pipe Outside

Diameter inches/mm

C to E inches/mm

C to E inches/mm

C to LE inches/mm

C to SE inches/mm

inches/mm

C to TE inches/mm

¾1.050 2.25 2.25

— —2.25 2.25

26.9 57 57 57 57

11.315 2.25 2.25 2.25 2.25 2.25 2.2533.7 57 57 57 57 57 57

1 ¼1.660 2.75 2.75 2.75 2.50 2.75 2.7542.4 70 70 70 64 70 70

1 ½1.900 2.75 2.75 2.75 2.75 2.75 2.7548.3 70 70 70 70 70 70

22.375 3.25 3.25 3.25 2.75 3.25 4.2560.3 83 83 83 70 83 108

2 ½2.875 3.75 3.75 3.75 3.00 3.75 3.7573.0 95 95 95 76 95 95

76.1 mm3.000 3.75

— — —3.75 3.75

76.1 95 95 95

33.500 4.25 4.25 4.25 3.25 4.25 6.0088.9 108 108 108 83 108 152

3 ½4.000 4.50 (sw) 4.50 4.50 3.50 4.50 4.50101.6 114 114 114 89 114 114

108.0 mm4.250 5.00

— — —5.00 5.00

108.0 127 127 127

44.500 5.00 5.00 5.00 3.75 5.00 7.25114.3 127 127 127 95 127 184

4 ½5.000 5.25 (sw) 5.25

— —5.25 5.25

127.0 133 133 133 133

133.0 mm5.250 5.50

— — —5.50 5.50

133.0 140 140 140

139.7 mm5.500 5.50

— — —5.50 5.50

139.7 140 140 140

55.563 5.50 5.50 5.50 4.00 5.50 5.50141.3 140 140 140 102 140 140

159.0 mm6.250 6.50

— — —6.50 6.50

159.0 165 165 165

165.1 mm6.500 6.50 6.50

— —6.50 6.50

165.1 165 165 165 165

66.625 6.50 6.50 6.50 4.50 6.50 6.50168.3 165 165 165 114 165 165

88.625 7.75 7.75 7.75 6.00 7.75 7.75219.1 197 197 197 152 197 197

Page 218: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

TeeNo. 35 No. 33

Branch

Nominal Size

inches or mm

Actual Pipe Outside

Diameter inches/mm

C to E inches/mm

C to E inches/mm

C to LE inches/mm

C to SE inches/mm

inches/mm

C to TE inches/mm

1010.750 9.00 9.00 9.00 6.50 9.00 9.00273.0 229 229 229 155 229 229

1212.750 10.00 10.00 10.00 7.00 10.00 10.00323.9 254 254 254 178 254 254

14 #14.000 11.00 11.00 11.00 7.50

— —355.6 279 279 279 191

377.0 mm14.000 11.00

— — — — —355.6 279

16 #16.000 12.00 12.00 12.00 8.00

— —406.4 305 305 305 203

426.0 mm †16.000 12.00

— — — — —406.4 305

18 #18.000 14.00 15.50 15.50 8.50

— —457.0 356 394 394 216

480.0 mm†18.000 14.00

— — — — —457.0 356

20 #20.000 15.00 17.25 17.25 9.00

— —508.0 381 438 438 229

530.0 mm †20.000 15.00

— — — — —508.0 381

24 #24.000 17.00 20.00 20.00 10.00

— —610.0 432 508 508 254

630.0 mm †24.000 17.00

— — — — —610.0 432

14 – 24

# For use on cut grooved systems only. For roll grooved systems, Victaulic offers the Advanced Groove System (AGS).

† Chinese standard sizes

All fittings are ductile iron unless noted otherwise with an “sw” or “s”. SW = Segmentally Welded, S = Carbon Steel

Fittings in sizes 26 – 48 inches/660.0 – 1219.0 mm are available roll grooved for installation with Style 770 Large Diameter Couplings. Contact Victaulic for details.

C to E

CtoE

C to EC to LE

C toSE

C toGE

C to TE

Page 219: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Std.

Nominal Size inches/Actual mm

C to E inches/mm

C to E inches/mm

¾+ +

33.7 33.7 26.9

1 ¼×

1 ¼×

1+ +

42.4 42.4 33.7

1 ½×

1 ½×

¾+ +

48.3 48.3 26.9

1+ +

33.7

1 ¼+ +

42.4

¾ 3.25 3.2560.3 60.3 26.9 83 83

1 3.25 3.2533.7 83 83

1 ¼+ +

42.4

1 ½ 3.25 3.25 (sw)48.3 83 83

2 ½×

2 ½×

¾+ +

73.0 73.0 26.9

1 3.75 3.75 (sw)33.7 95 95

1 ¼+ +

42.4

1 ½ 3.75 3.7548.3 95 95

2 3.75 3.75 (sw)60.3 95 95

¾+ +

88.9 88.9 26.9

1 4.25 4.2533.7 108 108

1 ¼+ +

42.4

1 ½ 4.25 4.25 (sw)48.3 108 108

2 4.25 4.25 (sw)60.3 108 108

2 ½ 4.25 4.25 (sw)73.0 108 108

C to E

CtoE

C to E

CtoE

Page 220: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Std.

Nominal Size inches/Actual mm

C to E inches/mm

C to E inches/mm

¾+ +

114.3 114.3 26.9

1 5.00 5.0033.7 127 127

1 ¼+ +

42.4

1 ½ 5.00 5.0048.3 127 127

2 5.00 5.0060.3 127 127

2 ½ 5.00 5.0073.0 127 127

3 5.00 5.0088.9 127 127

1+ +

141.3 141.3 33.7

1 ½+ +

48.3

2 5.50 (sw) 5.50 (sw)60.3 140 140

2 ½ 5.50 5.50 (sw)73.0 140 140

3 5.50 5.50 (sw)88.9 140 140

4 5.50 5.50 (sw)114.3 140 140

1+ +

168.3 168.3 33.7

1 ½+ +

48.3

2 6.50 6.5060.3 165 165

2 ½ 6.50 6.5073.0 165 165

3 6.50 6.5088.9 165 165

4 6.50 6.50114.3 165 165

5 6.50 6.50141.3 165 165

6 ½×

6 ½×

3 6.50 6.50 (sw)165.1 165.1 88.9 165 165

4 6.50 6.50 (sw)114.3 165 165

C to E

CtoE

C to E

CtoE

Page 221: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Std.

Nominal Size inches/Actual mm

C to E inches/mm

C to E inches/mm

1 ½+ +

219.1 219.1 48.3

2 7.75 (sw) 7.75 (sw)60.3 197 197

2 ½+ +

73.0

3 7.75 (sw) 7.75 (sw)88.9 197 197

4 7.75 7.75114.3 197 197

5 7.75 (sw) 7.75 (sw)141.3 197 197

6 7.75 7.75168.3 197 197

165.1 mm

7.75 (sw) 7.75 (sw)197 197

10×

10×

1 ½+ +

273.0 273.0 48.3

2 9.00 (sw) 9.00 (sw)60.3 229 229

2 ½+ +

73.0

3+ +

88.9

4 9.00 (sw) 9.00 (sw)114.3 229 229

5 9.00 (sw) 9.00 (sw)141.3 229 229

6 9.00 (sw) 9.00 (sw)168.3 229 229

8 9.00 (sw) 9.00 (sw)219.1 229 229

12×

12×

1+ +

323.9 323.9 33.7

2+ +

60.3

2 ½+ +

73.0

3 10.00 (sw) 10.00 (sw)88.9 254 254

4 10.00 (sw) 10.00 (sw)114.3 254 254

5 10.00 (sw) 10.00 (sw)141.3 254 254

6 10.00 (sw) 10.00 (sw)168.3 254 254

8 10.00 (sw) 10.00 (sw)219.1 254 254

10 10.00 (sw) 10.00 (sw)273.0 254 254

C to E

CtoE

C to E

CtoE

Page 222: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Std.

Nominal Size inches/Actual mm

C to E inches/mm

C to E inches/mm

# 14×

14×

4+ +

355.6 355.6 114.3

6+ +

168.3

8 11.00 11.00219.1 279 279

10 11.00 11.00273.0 279 279

12 11.00 11.00323.9 279 279

# 16×

16 ×

4+ +

406.4 406.4 114.3

6+ +

168.3

8 12.00 12.00219.1 305 305

10 12.00 12.00273.0 305 305

12 12.00 12.00323.9 305 305

14+ +

355.6

# 18×

18 ×

4+ +

457.0 457.0 114.3

6+ +

168.3

8+ +

219.1

10 15.50 15.50273.0 394 394

12 15.50 15.50323.9 394 394

14 15.50 –355.6 394 –

16 15.50 –406.4 394 –

# 20×

20×

6+ +

508.0 508.0 168.3

8+ +

219.1

10+ +

273.0

12+ +

323.9

14 17.25—

355.6 438

16 17.25—

406.4 438

18 17.25—

457.0 438

C to E

CtoE

C to E

CtoE

Page 223: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Std.

Nominal Size inches/Actual mm

C to E inches/mm

C to E inches/mm

# 24×

24×

8 20.00 20.00610.0 610.0 219.1 508 508

10 20.00 20.00273.0 508 508

12 20.00 20.00323.9 508 508

14 § 20.00—

355.6 508

16 20.00—

406.4 508

18 § 20.00—

457.0 508

20 20.00—

508.0 508

14 – 24355.6 – 610.0

+ Contact Victaulic for details.

All fittings are ductile iron unless noted otherwise with an “sw” or “s”. SW = Segmentally Welded, S = Carbon Steel

No. 29T Threaded Branches are supplied standard with NPT threads. British Standard Pipe Threads are available. Specify “BSPT” clearly on order.

# For use on cut grooved systems only. For roll grooved systems, Victaulic offers the Advanced Groove System (AGS).

§ Cast fitting available. Contact Victaulic for details.

C to E

CtoE

C to E

CtoE

Page 224: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Standpipe Tee

Nominal Size inches/Actual mm

inches/mm

C to EOB inches/mm

2 ½ 3.25 4.00114.3 114.3 73.0 83 102

2 ½ 3.25 5.13168.3 168.3 73.0 83 130

Available with British Standard Pipe Threads. Specify “BSPT” clearly on order.

All fittings are ductile iron unless noted otherwise with an “sw” or “s”. SW = Segmentally Welded, S = Carbon Steel

Size

Bullhead Tee

Nominal Size inches/Actual mm

inches/mm

C to EOB inches/mm

8 7.75 5.50141.3 141.3 219.1 197 140

8 7.75 6.50168.3 168.3 219.1 197 165

All fittings are ductile iron unless noted otherwise with an “sw” or “s”. SW = Segmentally Welded, S = Carbon Steel

SizeNo. 61

Nominal Size inches

Actual Pipe Outside Diameter

inches/mmE to E

inches/mm

22.375 4.0060.3 102

2 ½2.875 5.0073.0 127

33.500 6.0088.9 152

44.500 7.00114.3 178

55.563 8.00141.3 203

66.625 10.00168.3 254

No. 61 Bull Plugs should be used in vacuum services with Style 72 Outlet Couplings and Style 750 Reducing Couplings

All fittings are ductile iron unless noted otherwise with an “sw” or “s”. SW = Segmentally Welded, S = Carbon Steel

C toEOB

C toEOR

C toEOB

C toEOR

E to E

No. 61

Page 225: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

SizeNo. 30

Nominal Size inches or mm

Actual Pipe Outside Diameter

inches/mmC to LE

inches/mmC to SE

inches/mm

¾1.050 4.50 2.0026.9 114 51

11.315 5.00 2.2533.7 127 57

1 ¼1.660 5.75 2.5042.4 146 64

1 ½1.900 6.25 2.7548.3 159 70

22.375 7.00 2.7560.3 178 70

2 ½2.875 7.75 3.0073.0 197 76

76.1 mm3.000 8.50 3.2576.1 216 83

33.500 8.50 3.2588.9 216 83

3 ½4.000 10.00 3.50101.6 254 89

44.500 10.50 3.75114.3 267 95

55.563 12.50 4.00141.3 318 102

165.1 mm6.500 14.00 4.50165.1 356 114

66.625 14.00 4.50168.3 356 114

88.625 18.00 6.00219.1 457 152

1010.750 20.50 6.50273.0 521 165

1212.750 23.00 7.00323.9 584 178

14 #14.000 26.50 7.50355.6 673 191

16 #16.000 29.00 8.00406.4 737 203

18 #18.000 32.00 8.50457.0 813 216

20 #20.000 35.00 9.00508.0 889 229

24 #24.000 40.00 10.00610.0 1016 254

14 – 24

# For use on cut grooved systems only. For roll grooved systems, Victaulic offers the Advanced Groove System (AGS).

All fittings are ductile iron unless noted otherwise with an “sw” or “s”. SW = Segmentally Welded, S = Carbon Steel

C to LE

C toLE

C toSE

No. 30

Page 226: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size inches/ Actual mm

C to LE inches/mm

C to SE inches/mm

3x

3x

2 8.50 3.2588.9 88.9 60.3 216 83

2 ½ 8.50 3.2573.0 216 83

4x

4x

2 10.50 3.75114.3 114.3 60.3 267 95

2 ½ 10.50 3.7573.0 267 95

3 10.50 3.7588.9 267 95

5x

5x

2 12.50 4.00141.3 141.3 60.3 318 102

3 12.50 4.0088.9 318 102

4 12.50 4.00114.3 318 102

6x

6x

3 14.00 4.50168.3 168.3 88.9 356 114

4 14.00 4.50114.3 356 114

5 14.00 4.50141.3 356 114

8x

8x

4 18.00 6.00219.1 219.1 114.3 457 152

5 18.00 6.00141.3 457 152

6 18.00 6.00168.3 457 152

10x

10x

4 20.50 6.50273.0 273.0 114.3 521 165

5 20.50 6.50141.3 521 165

6 20.50 6.50168.3 521 165

8 20.50 6.50219.1 521 165

12x

12x

5 23.00 7.00323.9 323.9 141.3 584 178

6 23.00 7.00168.3 584 178

8 23.00 7.00219.1 584 178

10 23.00 7.00273.0 584 178

C to LE

C toLE

C toSE

Page 227: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size inches/ Actual mm

C to LE inches/mm

C to SE inches/mm

# 14x

14x

4 26.50 7.50355.6 355.6 114.3 673 191

6 26.50 7.50168.3 673 191

8 26.50 7.50219.1 673 191

10 26.50 7.50273.0 673 191

12 26.50 7.50323.9 673 191

# 16x

16x

6 29.00 8.00406.4 406.4 168.3 737 203

8 29.00 8.00219.1 737 203

10 29.00 8.00273.0 737 203

12 29.00 8.00323.9 737 203

14 29.00 8.00355.6 737 203

# 18x

18x

6 32.00 8.50457.0 457.0 168.3 813 216

8 32.00 8.50219.1 813 216

12 32.00 8.50323.9 813 216

14 32.00 8.50355.6 813 216

16 32.00 8.50406.4 813 216

# 20x

20x

12 35.00 9.00508.0 508.0 323.9 889 229

14 35.00 9.00355.6 889 229

16 35.00 9.00406.4 889 229

# 24x

24x

16 40.00 10.00610.0 610.0 406.4 1016 254

20 40.00 10.00508.0 1016 254

14 – 24355.6 – 610.0

# For use on cut grooved systems only. For roll grooved systems, Victaulic offers the Advanced Groove System (AGS).

All fittings are ductile iron unless noted otherwise with an “sw” or “s”. SW = Segmentally Welded, S = Carbon Steel

C to LE

C toLE

C toSE

Page 228: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size inches/Actual mm

inches/

mm

H inches/

mm

E1 inches/

mm

E inches/

mm

2 2.75 7.00 9.00 4.6360.3 60.3 60.3 70 178 229 118

2 ½×

2 ½×

2 ½ 3.00 7.75 10.50 5.7573.0 73.0 73.0 76 197 267 146

3 3.25 8.50 11.50 6.5088.9 88.9 88.9 83 216 292 165

3 ½×

3 ½×

3 ½ 3.25 10.00 13.00 7.75101.6 101.6 101.6 89 254 330 197

4 3.75 10.50 13.63 8.13114.3 114.3 114.3 95 267 346 207

5 4.00 12.50 16.13 10.00141.3 141.3 141.3 102 318 410 254

6 4.50 14.00 18.25 11.50168.3 168.3 168.3 114 356 464 292

8 6.00 18.00 23.25 15.25219.1 219.1 219.1 152 457 591 387

10×

10×

10 6.50 20.50 27.25 18.00273.0 273.0 273.0 165 521 692 457

12×

12×

12 7.00 23.00 31.00 20.50323.9 323.9 323.9 178 584 787 521

All fittings are ductile iron unless noted otherwise with an “sw” or “s”. SW = Segmentally Welded, S = Carbon Steel

H

G

E2

E1

Page 229: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size inches/Actual mm

inches/

mm

H inches/

mm

E1 inches/

mm

E inches/

mm

3 3.50 9.50 10.75 5.75114.3 88.9 88.9 89 241 273 146

4 3.75 10.50 13.63 8.13114.3 95 267 346 206

3 3.75 10.50 12.88 7.88114.3 114.3 88.9 95 267 327 200

3 1.25 9.75 11.50 7.63141.3 88.9 88.9 32 248 292 194

5 4.00 12.50 16.13 11.13141.3 102 318 410 283

3 1.88 9.13 11.88 6.88141.3 114.3 88.9 48 232 302 175

4 1.88 9.13 12.75 7.25114.3 48 232 324 184

3 4.00 12.50 14.25 9.25141.3 141.3 88.9 102 318 362 235

4 4.00 12.50 15.13 9.63114.3 102 318 384 245

6 4.50 14.00 18.25 11.50168.3 114.3 168.3 114 356 464 292

3 1.25 10.75 13.00 8.00168.3 141.3 88.9 32 273 330 203

4 1.25 10.75 13.88 8.38114.3 32 273 352 213

3 4.50 14.00 15.31 10.31168.3 168.3 88.9 114 356 389 262

4 4.50 14.00 16.25 10.75114.3 114 356 413 273

5 4.50 14.00 17.25 11.13141.3 114 356 438 283

4 1.00 12.00 14.75 9.25219.1 168.3 114.3 25 304 375 235

8 6.00 18.00 23.25 15.25219.1 152 457 591 387

G

H E2

E1

Page 230: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size inches/Actual mm

inches/

mm

H inches/

mm

E1 inches/

mm

E inches/

mm

3 6.00 18.00 18.19 13.19219.1 219.1 88.9 152 457 462 335

4 6.00 18.00 19.00 13.50114.3 152 457 483 343

5 6.00 18.00 20.00 13.88141.3 152 457 508 352

6 6.00 18.00 21.13 14.38168.3 152 457 537 365

10×

10×

3 6.50 20.50 19.88 14.88273.0 273.0 88.9 165 521 505 378

4 6.50 20.50 20.75 15.25114.3 165 521 527 387

5 6.50 20.50 21.88 15.75141.3 165 521 556 400

10×

10×

6 6.50 20.50 22.88 16.13273.0 273.0 168.3 165 521 581 410

8 6.50 20.50 27.25 19.25219.1 165 521 692 489

All fittings are ductile iron unless noted otherwise with an “sw” or “s”. SW = Segmentally Welded, S = Carbon Steel

G

H E2

E1

Page 231: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size inches

Actual Pipe Outside Diameter

inches/mmE to E

inches/mm

¾1.050 3.0026.9 76

11.315 3.0033.7 76

1¼ 1.660 4.0042.4 102

1½1.900 4.0048.3 102

22.375 4.0060.3 102

2½2.875 4.0073.0 102

33.500 4.0088.9 102

3½4.000 4.00101.6 102

44.500 6.00114.3 152

55.563 6.00141.3 152

66.625 6.00168.3 152

88.625 6.00219.1 152

1010.750 8.00273.0 203

1212.750 8.00323.9 203

Available with British Standard Pipe Threads. Specify “BSPT” clearly on order. For pump package nipples with a 1 ½-inch/38-mm hole cut to receive Style 923 Vic-Let Strapless Outlets or Style 924 Vic-O-Well Strapless Thermometer Outlets, special No. 40, No. 42, or No. 43 Adapter Nipples must be used. Specify No. 40-H, 42-H, or 43-H clearly on order. NOTE: An 8-inch/203-mm minimum length is required for 4 – 12-inch/114.3 – 323.9-mm sizes. # For use on cut grooved systems only. For roll grooved systems, Victaulic offers the Advanced Groove System (AGS).

All fittings are ductile iron unless noted otherwise with an “sw” or “s”. SW = Segmentally Welded, S = Carbon Steel

E to E

E to E

E to E

Page 232: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

SizeNo. 60

Cap

Nominal Size inches or mm

Actual Pipe Outside Diameter

inches/mm

T

inches/mm

¾1.050 0.8826.9 22

11.315 0.8833.7 22

1 ¼1.660 0.8842.4 22

1 ½1.900 0.8848.3 22

22.375 0.8860.3 22

2 ½2.875 0.8873.0 22

76.1 mm3.000 0.8876.1 22

33.500 0.8888.9 22

3 ½4.000 0.88101.6 22

108.0 mm4.250 1.00108.0 25

44.500 1.00114.3 25

133.0 mm5.250 1.00133.0 25

139.7 mm5.500 1.00 139.7 25

55.563 1.00141.3 25

159.0 mm6.250 1.00159.0 25

165.1 mm6.500 1.00165.1 25

66.625 1.00168.3 25

88.625 1.19219.1 30

1010.750 1.25273.0 32

1212.750 1.25323.9 32

T

No. 60

Page 233: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

SizeNo. 60

Cap

Nominal Size inches or mm

Actual Pipe Outside Diameter

inches/mm

T

inches/mm

14 # (s)14.000 9.50355.6 241

16 # (s)16.000 10.00406.4 254

18 # (s)18.000 11.00457.0 279

20 # (s)20.000 12.00508.0 305

24 # (s)24.000 13.50610.0 343

14 – 24

* Steel dish caps are available through 24 inches/610.0 mm. Contact Victaulic for details.

No. 60 Caps are not suitable for use in vacuum services with Style 72 Outlet Couplings or Style 750 Reducing Couplings. No. 61 Bull Plugs should be used for this application.

# For use on cut grooved systems only. For roll grooved systems, Victaulic offers the Advanced Groove System (AGS).

NOTE: All fittings are ductile iron unless noted otherwise with an “sw” or “s”. SW = Segmentally Welded, S = Carbon Steel

T

No. 60

Page 234: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

E to E E to E E to E E to E E to E

Size

Flanged Adapter Nipple

ANSI 150 Flanged

ANSI 300 Flanged

Nominal Size inches

Actual Pipe Outside Diameter

inches/mmE to E

inches/mmE to E

inches/mmE to E

inches/mm

¾1.050 3 3 326.9 76 76 76

11.315 3 3 333.7 76 76 76

1¼1.660 4 4 442.4 102 102 102

1½1.900 4 4 448.3 102 102 102

22.375 4 4 460.3 102 102 102

2½2.875 4 4 473.0 102 102 102

33.500 4 4 488.9 102 102 102

3½4.00 4 4 4101.6 102 102 102

44.500 6 6 6114.3 152 152 152

55.563 6 6 6141.3 152 152 152

66.625 6 6 6

168.3 152 152 152

8 8.625 6 6 6219.1 152 152 152

10 10.750 8 8 8273.0 203 203 203

12 12.750 8 8 8

323.9 203 203 203

Page 235: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Flanged Adapter Nipple

ANSI 150 Flanged

ANSI 300 Flanged

Nominal Size inches

Actual Pipe Outside Diameter

inches/mmE to E

inches/mmE to E

inches/mmE to E

inches/mm

14 #14.000 8 8 8

355.6 203 203 203

16 #16.000 8 8 8

406.4 203 203 203

18 #18.000 8 8 8

457.0 203 203 203

20 #20.000 8 8 8

508.0 203 203 203

24 #24.000 8 8 8

610.0 203 203 203

14 – 24

+ Contact Victaulic for details. Flanged adapter nipples are supplied with original groove system roll grooves. Standard cut grooves or machining for rubber lining are available as options. Contact Victaulic for details. # For use on cut grooved systems only. For roll grooved systems, Victaulic offers the Advanced Groove System (AGS). NOTE: All fittings are ductile iron unless noted otherwise with an “sw” or “s”. SW = Segmentally Welded, S = Carbon Steel

E to E E to E E to E E to E E to E

Page 236: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

E to E E to E E to E

No. 53 No. 55

Size

Nominal Size inches/Actual mm

E to E inches/mm

2 ×

1 6.5060.3 33.7 165

1 ¼ 6.5042.4 165

1 ½ 6.50 48.3 165

2 ½ ×

1 7.00 73.0 33.7 178

1 ¼ 7.0042.4 178

1 ½ 7.0048.3 178

2 7.0060.3 178

3 × 1 8.0088.9 33.7 203

1 ¼ 8.0042.4 203

1 ½ 8.0048.3 203

2 8.0060.3 203

2 ½ 8.0073.0 203

3 ½ ×

3 8.00101.6 88.9 203

4 ×

1 9.00114.3 33.7 229

1 ¼ 9.0042.4 229

1 ½ 9.0048.3 229

2 9.0060.3 229

Size

Nominal Size inches/Actual mm

E to E inches/mm

2 ½ 9.00114.3 73.0 229

3 9.00114.3 88.9 229

3 ½ 9.00101.6 229

5 ×

2 11.00 141.3 60.3 279

3 11.0088.9 279

4 11.00114.3 279

6 ×

1 12.00168.3 33.7 305

1 ¼ 12.0042.4 305

1 ½ 12.00 48.3 305

2 12.0060.3 305

2 ½ 12.0073.0 305

3 12.0088.9 305

3 ½ 12.00101.6 305

4 12.00114.3 305

4 ½ 12.00 127.0 305

5 12.00 141.3 305

8 ×

6 +

219.1 168.3

+ Contact Victaulic for details.

All fittings are ductile iron unless noted otherwise with an “sw” or “s”. SW = Segmentally Welded, S = Carbon Steel

Page 237: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

No. 80 Female Threaded

Adapter

Nominal Size inches

Actual Pipe Outside Diameter

inches/mmE to E

inches/mm

¾1.050 2.0026.9 51

11.315 2.0633.7 52

1 ¼1.660 2.31 (sw)42.4 59

1 ½1.900 2.31 (sw)48.3 59

22.375 2.5060.3 64

2 ½2.875 2.7573.0 70

33.500 2.7588.9 70

44.500 3.25114.3 83

Available with British Standard Pipe Threads. Specify “BSPT” clearly on order. All fittings are ductile iron unless noted otherwise with an “sw” or “s”.

SW = Segmentally Welded, S = Carbon Steel

E to E

No. 80

Page 238: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size inches

Actual Pipe Outside Diameter

inches/mmE to E

inches/mm

¾1.050 3.1226.9 79

11.315 3.3833.7 86

1 ¼1.660 3.8842.4 98

1 ½1.900 3.8848.3 98

22.375 4.5060.3 114

2 ½2.875 5.3873.0 137

33.500 5.7588.9 146

44.500 7.00114.3 178

55.563 8.75141.3 222

66.625 10.12168.3 257

88.625 11.88219.1 302

1010.750 12.50273.0 318

1212.750 14.50323.9 368

All fittings are ductile iron unless noted otherwise with an “sw” or “s”. SW = Segmentally Welded, S = Carbon Steel

E to E

Page 239: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

No. 50 Concentric

No. 51 Eccentric

Nominal Size inches/Actual mm

E to E inches/mm

E to E inches/mm

1 ¼×

¾+ —

42.4 26.9

1+ —

33.7

1 ½ ×

¾+

— 48.3 26.9

1* 2.50 8.50 (SW)33.7 64 216

1 ¼* 2.50—

42.4 64

2 ×

¾* 2.50 9.00 (SW)60.3 26.9 64 229

1* 2.50 9.00 (SW)33.7 64 229

1 ¼* 2.50 9.00 (SW)42.4 64 229

1 ½* 3.50 3.5048.3 89 89

2 ½ ×

¾+ +

73.0 26.9

1* 2.50 9.5033.7 64 241

1 ¼* 3.50 3.5042.4 89 89

1 ½* 2.50 9.50 (SW)48.3 64 241

2* 2.50 9.50 (SW)60.3 64 241

3 ×

¾*+ +

88.9 26.9

1* 2.50 9.50 (SW)33.7 241 241

1 ¼* 2.50+

42.4 64

1 ½* 2.50 9.50 (SW)48.3 64 241

2* 2.50 3.50 60.3 64 89

2 ½* 2.50 3.5073.0 64 89

76.1 mm

2.50 —

64

Size

No. 50 Concentric

No. 51 Eccentric

Nominal Size inches/Actual mm

E to E inches/mm

E to E inches/mm

3 ½×

3 2.50 9.50 (SW)101.6 88.9 64 241

4 ×

1* 3.00 13.00 (SW)114.3 33.7 76 330

1 ¼+ —

42.4

1 ½* 3.00 (SW) 10.00 (SW)48.3 76 254

2* 3.00 4.0060.3 76 102

2 ½* 3.00 4.0073.0 76 102

3* 3.00 4.0088.9 76 102

3 ½ 3.00 10.00 (SW)101.6 76 254

5 ×

2 11.00 (SW) 11.00 (SW)141.3 60.3 279 279

2 ½ 4.00 11.00 (SW)73.0 102 279

3 4.00 11.00 (SW)88.9 102 279

4* 3.50 5.00114.3 89 127

6 ×

1* 4.00 11.50 (SW)168.3 33.7 102 292

1 ½+ +

48.3

2* 4.00 11.50 (SW)60.3 102 292

2 ½* 4.00 11.50 (SW)73.0 102 292

3* 4.00 5.5088.9 102 140

4* 4.00 5.50114.3 102 140

5* 4.00 5.50141.3 102 140

8 ×

2 ½* 16.00 12.00 (SW) 219.1 73.0 406 305

3 5.00 12.00 (SW)88.9 127 305

Eto E

E to E

No. 50 No. 51

Page 240: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

No. 50 Concentric

No. 51 Eccentric

Nominal Size inches/Actual mm

E to E inches/mm

E to E inches/mm

8 ×

4 5.00 12.00 (SW)219.1 114.3 127 305

5 5.00 12.00 (SW)141.3 127 305

6 5.00 6.00168.3 127 152

10 ×

4 6.00 13.00 (SW)273.0 114.3 152 330

5+ +

141.3

6 6.00 13.00 (SW)168.3 152 330

8 6.00 7.00219.1 152 178

12 ×

4+

14.00 (SW)323.9 114.3 356

6 7.00 14.00 (SW)168.3 178 356

8 7.00 14.00 (SW)219.1 178 356

10 7.00 14.00 (SW)273.0 178 356

# 14×

6 13.00 13.00355.6 168.3 330 330

8 13.00 13.00219.1 330 330

10 13.00 13.00273.0 330 330

12 13.00 13.00323.9 330 330

# 16×

8 14.00 14.00406.4 219.1 356 355

10 § 14.00 14.00273.0 356 355

12 14.00 14.00323.9 356 355

14 14.00 14.00355.6 356 355

Size

No. 50 Concentric

No. 51 Eccentric

Nominal Size inches/Actual mm

E to E inches/mm

E to E inches/mm

# 18×

10 15.00 15.00457.0 273.0 381 381

12 15.00 15.00323.9 381 381

14 15.00 15.00355.6 381 381

16 15.00 15.00406.4 381 381

# 20×

10 20.00 20.00508.0 273.0 508 508

12 20.00 20.00323.9 508 508

14 20.00 20.00355.6 508 508

16 20.00 20.00406.4 508 508

18 20.00 20.00457.0 508 508

# 24×

10 20.00 20.00610.0 273.0 508 508

12 20.00 20.00323.9 508 508

14 20.00 20.00355.6 508 508

16 20.00 20.00406.4 508 508

18 20.00 20.00457.0 508 508

20 20.00 20.00508.0 508 508

14 – 24 350 – 600

section.

All fittings are ductile iron unless noted otherwise with an “sw” or “s”. SW = Segmentally Welded, S = Carbon Steel

Eto E

E to E

No. 50 No. 51

+ Contact Victaulic for details. * Available as a small male threaded reducer. Refer to the No. 52 section. Steel eccentric reducers are available through 30 inches/762.0 mm. Contact Victaulic for dimensions. # For use on cut grooved systems only. For roll grooved systems, Victaulic offers the Advanced Groove System (AGS). § Cast fitting available for JIS size. Contact Victaulic for details.

Page 241: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Eto E

Eto E

Size

Nominal Size inches/Actual mm

E to E inches/mm

E to E inches/mm

1 ½×

1 2.50—

48.3 33.7 64

1 ¼ 2.50—

42.4 64

2 ×

¾ 2.50—

60.3 26.9 64

1 2.50—

33.7 64

1 ¼ 2.50—

42.4 64

1 ½ 2.50—

48.3 64

2 ½ ×

1 2.50—

73.0 33.7 64

1 ¼ 2.50 (sw)—

42.4 64

1 ½ 2.50 (sw)—

48.3 64

2 3.00—

60.3 76

76.1 mm × 48.3 63.5 63.5

60 — 63.5

3 ×

¾+ (sw) —

88.9 26.9

1 2.50—

33.7 64

1 ¼ 2.50—

42.4 64

1 ½ 2.50 (sw)—

48.3 64

2 2.50—

60.3 64

2 ½ 2.50—

73.0 64

88.9 mm × 42.4 63.5 63.5

48.3 63.5 63.5

60 — 63.5

1 3.00—

114.3 33.7 76

1 ½ 3.00—

48.3 76

2 3.00—

60.3 76

Size

Nominal Size inches/Actual mm

E to E inches/mm

E to E inches/mm

2 ½ 3.00—

114.3 73.0 76

3 3.00—

88.9 76

108.0 mm × 42.4 76.2 76.2

48.3 76.2 76.2

60 — 76.2

114.3 mm × 42.4 76.2 76.2

48.3 76.2 76.2

60 — 76.2

5 ×

4+ —

141.3 100

133.0 mm × 60 — 114.3

139.7 mm × 60 — 114.3

6 ×

1 4.00—

168.3 33.7 102

2 4.00—

60.3 102

2 ½ 4.00—

73.0 102

3 4.00—

88.9 102

4 + (sw) —

114.3

5 + (sw) —

141.3

159.0 mm x 42.4 114.3 114.3

48.3 114.3 114.3

60 — 114.3

165.1 mm x 42.4 101.6 101.6

48.3 101.6 101.6

60 — 101.6

8 ×

2 16.00—

219.1 60.3 406

2 ½ 16.00—

73.0 406

+ Contact Victaulic for details. All fittings are ductile iron unless noted

otherwise with an “sw” or “s”. SW = Segmentally Welded, S = Carbon Steel

Page 242: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

CtoE

C to E

C to E

C to E

CtoE

C to EC to E

CtoE

No. 63-ES No. 35-ES

Size No. 63-ES No. 35-ES *

Nominal Size inches

Actual Pipe Outside Diameter

inches/mmC to E

inches/mmC to E

inches/mmC to E

inches/mmC to E

inches/mm

22.375 3.25 2.00 3.25 3.2560.3 83 51 83 83

2 ½2.875 3.75 2.25 3.75 3.7573.0 95 57 95 95

33.500 4.25 2.50 4.25 4.2588.9 108 64 108 108

44.500 5.00 3.00 5.00 5.00114.3 127 76 127 127

6 †6.625 6.50 3.50 6.50 6.50168.3 165 89 165 165

*Steel Fabricated – Cast Full Flow

† For sizes to 12 inches/323.9 mm, contact Victaulic.

Steel full-flow elbows are available with longer center-to-end dimensions. Contact Victaulic for details.

Fitting Size Mated C to E Header Tee

Nominal Size inches

Actual Pipe Outside Diameter

inches/mmC to E

inches/mm

2 – 32.375 4.2560.3 108

2 – 42.375 5.0060.3 127

C to E

CtoE

Page 243: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

CtoE

C to E

C to E

C to E

C to E

C to E

C to E

C to E

Size

Nominal Size inches

Actual Pipe Outside Diameter

inches/mmC to E

inches/mmC to E

inches/mmC to E

inches/mmC to E

inches/mm

¾1.050 2.25 * 1.50 * 1.63 1.3826.9 57 38 41 35

11.315 2.25 * 1.75 * 1.63 1.3833.4 57 44 41 35

1 ¼1.660 2.75 * 1.75 * 1.75 1.3842.4 70 44 44 35

1 ½1.900 2.75 * 1.75 * 1.75 1.3848.3 70 44 44 35

22.375 3.25 * 2.00 * 1.88 1.38 *60.3 83 51 48 35

2 ½2.875 3.75 * 2.25 * 2.00 * 1.5073.0 95 57 51 38

33.500 4.25 * 2.50 * 2.25 * 1.50 *88.9 108 64 57 38

3 ½4.000 4.50 * 2.75 * 2.50 1.75101.6 114 70 64 44

44.500 5.00 * 3.00 * 2.88 1.75 *114.3 127 76 73 44

55.563 5.50 * 3.25 * 2.88 2.00141.3 140 83 73 51

66.625 6.50 * 3.50 * 3.13 2.00 *168.3 165 89 80 51

88.625 7.75 * 4.25 * 3.88 2.00219.1 197 108 99 51

1010.750 9.00 * 4.75 * 4.38 2.13273.0 229 121 111 54

1212.750 10.00 * 5.25 * 4.88 2.25323.9 254 133 124 57

1414.000 11.00 * 6.00 * 5.00 3.50355.6 279 152 127 89

1616.000 12.00 * 7.25 * 5.00 4.00406.4 305 184 127 102

1818.000 15.50 8.00 5.50 4.50457.2 394 203 140 114

2020.000 17.25 9.00 6.00 5.00508.0 438 229 152 127

2424.000 20.00 11.00 7.00 6.00609.6 508 279 178 152

* Available in Victaulic full flow cast design

Page 244: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

TeeCrossTrue Wye

CtoE

C to EC to E

CtoE

C to LE

C to SE C to LE

C toLE

C toSE

Tee Cross True Wye

Size Tee Cross True Wye

Nominal Size

inches

Actual Pipe Outside

Diameter inches/mm

C to E inches/mm

C to LE inches/mm

C to E inches/mm

C to SE inches/mm

C to LE inches/mm

C to SE inches/mm

¾1.050 2.25 * 2.25 2.25 2.00 4.50 2.0026.9 57 57 57 51 114 51

11.315 2.25 * 2.25 2.25 * 2.25 * 5.00 2.2533.4 57 57 57 57 127 51

1 ¼1.660 2.75 * 2.75 2.75 2.50 5.75 2.5042.4 70 70 70 64 146 64

1 ½1.900 2.75 * 2.75 2.75 2.75 6.25 2.7548.3 70 70 70 70 159 70

22.375 3.25 * 3.25 * 3.25 2.75 7.00 2.7560.3 83 83 83 70 178 70

2 ½2.875 3.75 * 3.75 3.75 3.00 7.75 3.0073.0 95 95 95 76 197 76

33.500 4.25 * 4.25 * 4.25 3.25 8.50 * 3.25 *88.9 108 108 108 83 216 83

3 ½4.000 4.50* 4.50 4.50 3.50 10.00 3.50101.6 114 114 114 89 254 89

44.500 5.00 * 5.00 * 5.00 3.75 10.50 * 3.75 *114.3 127 127 127 95 267 95

55.563 5.50 * 5.50 5.50 4.00 12.50 4.00141.3 140 140 140 102 318 102

66.625 6.50 * 6.50 6.50 4.50 14.00 4.50168.3 165 165 165 114 356 114

88.625 7.75 * 7.75 7.75 6.00 18.00 6.00219.1 197 197 197 152 457 152

1010.750 9.00 * 9.00 9.00 6.50 20.50 6.50273.0 229 229 229 165 521 165

1212.750 10.00 * 10.00 10.00 7.00 23.00 7.00323.9 254 254 254 178 584 178

1414.000 11.00 11.00 11.00 7.50 26.50 7.50355.6 279 279 279 191 673 191

1616.000 12.00 12.00 12.00 8.00 29.00 8.00406.4 305 305 305 203 737 203

1818.000 15.50 15.50 15.50 8.50 32.00 8.50457.2 394 394 394 216 813 216

2020.000 17.25 17.25 17.25 9.00 35.00 9.00508.0 438 438 438 229 889 229

2424.000 20.00 20.00 20.00 10.00 40.00 10.00609.6 508 508 508 254 1016 254

* Available in Victaulic full flow cast design

Page 245: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

C to E

Cto E

C to EC

to E

CtoE

T

No. 001 No. 003 No. 006

SizeNo. 001 No. 003

Straight TeeNo. 006

Cap

Nominal Size inches or mm

Actual Pipe Outside

Diameter inches/mm

C to E inches/mm

C to E inches/mm

C to E inches/mm

inches/mm

1 ¼1.660

— — —0.8

42.4 21

1 ½1.900

— — —0.82

48.3 21

22.375 2.75 2.00 2.75 0.8860.3 70 51 70 22

2 ½2.875 3.00 2.25 3.00 0.8873.0 76 57 76 22

76.1 mm3.000 3.00 2.25

— —76.1 76 57

33.500 3.38 2.50 3.38 0.8888.9 86 64 86 22

108 mm4.250 4.00 3.00 4.00

—108.0 102 76 102

44.500 4.00 3.00 4.00 1.00114.3 102 76 102 25

55.563 4.88 3.25 4.88 1.00141.3 124 83 124 25

159 mm6.250 5.50 3.50 5.50

—158.8 140 89 140

66.625 5.50 3.50 5.50 1.00168.3 140 89 140 25

88.625 6.81 4.25 6.94 1.13219.1 173 108 176 29

Page 246: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Cto E

C to E

C to E

C to E

CtoE

T

No. 10-A No. 11-A No. 60-A

SizeNo. 10-A No. 11-A

TeeNo. 60-A

Nominal Size inches

Actual Pipe Outside

Diameter inches/mm

C to Einches/mm

C to Einches/mm

C to Einches/mm inches/mm

11.315 2.25 1.75 2.25 0.8833.7 57 45 57 22

1 ½1.900 2.75 1.75 2.75 0.8848.3 70 45 70 22

22.375 3.25 2.00 3.25 0.8860.3 83 51 83 22

2 ½2.875 3.75 2.25 3.75 0.8873.0 95 57 95 22

33.500 4.25 2.50 4.25 0.8888.9 108 64 108 22

44.500 5.00 3.00 5.00 1.00114.3 127 76 127 25

55.563 5.50 3.25 5.50 1.00141.3 140 83 140 25

66.625 6.50 3.50 6.50 1.00168.3 165 89 165 25

88.625 7.75 4.25 7.75 1.19219.1 197 108 197 30

† Cap does not extend beyond coupling when assembled.

Page 247: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size inches

Actual Pipe Outside Diameter

inches/mm inches/mm

11.315 3.0033.7 76

1 ½1.900 4.0048.3 102

22.375 4.0060.3 102

2 ½2.875 4.0073.0 102

33.500 4.0088.9 102

44.500 6.00114.3 152

55.563 6.00141.3 152

66.625 6.00168.3 152

88.625 6.00219.1 152

* Made of standard-weight aluminum pipe.

† Other lengths available. Contact Victaulic for details.

No. 40-A Grooved X Threaded Adapter Nipples are supplied NPT and are available with British Standard Pipe Threads (BSPT). For British Standard Pipe Threads, specify “BSPT” clearly on order.

E to E

E to E

E to E

Page 248: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size E to E

Nominal Sizeinches/Actual mm inches/mm

1 ½x

1 2.5048.3 33.7 64

2x

1 2.5060.3 33.7 64

1 ½ 2.5048.3 64

3x

1 2.5088.9 33.7 64

2 2.5060.3 64

2 ½ 2.5073.0 64

4x

2 3.00114.3 60.3 76

2 ½ 3.0073.0 76

3 3.0088.9 76

6x

3 4.00168.3 88.9 102

4 4.00114.3 102

8x

4 5.00219.1 114.3 127

6 5.00168.3 127

Eto E

No. 50-A

Page 249: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

VICTAULIC

No.W10C

to E

C to E

VICT

AULIC

No.W11

C toE

C to E

C to E VICTAULIC

No.W100

C to E

Cto E VI

CTAU

LIC

No.W11

0

C toE

No. W10 No. W11 No. W13 No. W100 No. W110

Size No. W10 No. W11No. W13

No. W100 No. W110

Nominal Size inches

Actual Pipe Outside

Diameter inches/mm

C to E inches/

mm

C to E inches/

mm

C to E inches/

mm

C to E inches/

mm

C to E inches/

mm

C to E inches/

mm

1414.000 14.00 5.80 5.00 3.50 21.00 8.75355.6 356 147 127 89 533 222

1616.000 16.00 6.63 5.00 4.00 24.00 10.00406.4 406 168 127 102 610 254

1818.000 18.00 7.46 5.50 4.50 27.00 11.25457.0 457 189 140 114 686 286

2020.000 20.00 8.28 6.00 5.00 30.00 12.50508.0 508 210 152 127 762 318

2424.000 24.00 9.94 7.00 6.00 36.00 15.00610.0 610 252 178 152 914 381

All fittings are ductile iron unless noted otherwise with an “sw”. SW = Segmentally Welded

Page 250: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

VICTAULICNo.W20

C toE

C toE

VICTAULICNo.W35

C to E

VICTAULIC

No.W33

C toLE

C toSE

No. W35 No. W33

Size

Nominal Size inches

Actual Pipe Outside

Diameter inches/mm

C to E inches/mm

C to E inches/mm

C to LE inches/mm

C to SE inches/mm

1414.000 11.00 11.00 11.00 7.50355.6 279 279 279 191

1616.000 12.00 12.00 12.00 8.00406.4 305 305 305 203

1818.000 13.50 13.50 13.50 8.50457.0 343 343 343 216

2020.000 15.00 15.00 15.00 9.00508.0 381 381 381 229

2424.000 17.00 17.00 17.00 10.00610.0 432 432 432 254

All fittings are ductile iron unless noted otherwise with an “sw”. SW = Segmentally Welded

Page 251: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Segmentally-Welded Steel

Size

Nominal Sizeinches/Actual mm

C to E inches/mm

C to LE inches/mm

C to SE inches/mm

14×

14×

6—

11.00 9.38355.6 355.6 168.3 279 238

8—

11.00 9.75219.1 279 248

10—

11.00 10.12273.0 279 257

12—

11.00 10.62323.9 279 270

14 11.00— —

355.6 279

16 ×

16×

6—

12.00 10.38406.4 406.4 168.3 305 264

8—

12.00 10.75219.1 305 273

10—

12.00 11.12273.0 305 282

12—

12.00 11.62323.9 305 295

14—

12.00 12.00355.6 305 305

16 12.00— —

406.4 305

18×

18×

6—

13.50 11.38457.0 457.0 168.3 343 289

8—

13.50 11.75219.1 343 298

10—

13.50 12.12273.0 343 308

12—

13.50 12.62323.9 343 321

14—

13.50 13.00355.6 343 330

16—

13.50 13.00406.4 343 330

18 13.50— —

457.0 343

VICTAULICNo.W20

C toE

C to E

VICTAULICNo.W25

C toLE

C toSE

Page 252: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Sizeinches/Actual mm

C to E inches/mm

C to LE inches/mm

C to SE inches/mm

20 ×

20×

6—

15.00 12.38508.0 508.0 168.3 381 314

8—

15.00 12.75219.1 381 324

10—

15.00 13.12273.0 381 333

12—

15.00 13.62323.9 381 346

14 *—

15.00 14.00355.6 381 356

16 *—

15.00 14.00406.4 381 356

18—

15.00 14.50457.0 381 368

20 15.00— —

508.0 381

24 ×

24×

6—

17.00 14.38610.0 610.0 168.3 432 365

8—

17.00 14.75219.1 432 375

10—

17.00 15.12273.0 432 384

12—

17.00 15.62323.9 432 397

14—

17.00 16.00355.6 432 406

16—

17.00 16.00406.4 432 406

18—

17.00 16.50457.0 432 419

20—

17.00 17.00508.0 432 432

24 17.00— —

610.0 432

Outlets in sizes 12 inch/323.9 mm and smaller are provided with original groove system roll or cut grooves that are suitable for use with standard Victaulic grooved pipe couplings in that size range.

VICTAULICNo.W20

C toE

C to E

VICTAULICNo.W25

C toLE

C toSE

Page 253: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Segmentally-Welded Steel

Size No. W30

Nominal Size inches

Actual Pipe Outside Diameter

inches/mmC to LE

inches/mmC to SE

inches/mm

1414.000 26.50 7.50355.6 673 191

1616.000 29.00 8.00406.4 737 203

1818.000 32.00 8.50457.0 813 216

2020.000 35.00 9.00508.0 889 229

2424.000 40.00 10.00610.0 1016 254

VICTA

ULIC

No.W30

C to LE

C toLE

C toSE

No. W30

Page 254: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Segmentally-Welded Steel

Size

Nominal Size inches/Actual mm

C to LE inches/mm

C to SE inches/mm

14×

14×

4 26.50 7.50355.6 355.6 114.3 673 191

6 26.50 7.50152.4 673 191

8 26.50 7.50219.1 673 191

10 26.50 7.50273.0 673 191

12 26.50 7.50323.9 673 191

16×

16×

6 29.00 8.00406.4 406.4 152.4 737 203

8 29.00 8.00219.1 737 203

10 29.00 8.00273.0 737 203

12 29.00 8.00323.9 737 203

14 29.00 8.00355.6 737 203

18 ×

18×

6 32.00 8.50457.0 457.0 152.4 813 216

8 32.00 8.50219.1 813 216

12 32.00 8.50323.9 813 216

14 32.00 8.50355.6 813 216

16 32.00 8.50406.4 813 216

20×

20×

12 35.00 9.00508.0 508.0 323.9 889 229

14 35.00 9.00355.6 889 229

16 35.00 9.00406.4 889 229

24×

24×

16 40.00 10.00610.0 610.0 406.4 1016 254

20 40.00 10.00508.0 1016 254

Outlets in sizes 12 inch/323.9 mm and smaller are provided with original groove system roll or cut grooves that are suitable for use with standard Victaulic grooved pipe couplings in that size range.

VICTA

ULIC

No.W30-R

C toLE

C toSE

C to LE

Page 255: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Steel

Size

Nominal Size inches

Actual Pipe Outside Diameter

inches/mmE to E

inches/mm

1414.000 8.00355.6 203

1616.000 8.00406.4 203

1818.000 8.00457.0 203

2020.000 8.00508.0 203

2424.000 8.00610.0 203

E to E

E to E

E to E

Steel

Size

Nominal Size inches

Actual Pipe Outside Diameter

inches/mmE to E

inches/mm

1414.000 8.00355.6 203

1616.000 8.00406.4 203

1818.000 8.00457.0 203

2020.000 8.00508.0 203

2424.000 8.00610.0 203

E to E

Steel

Size No. W60

Nominal Size inches

Actual Pipe Outside Diameter

inches/mm

T

inches/mm

1414.000 6.50355.6 165

1616.000 7.00406.4 178

1818.000 8.00457.0 203

2020.000 9.00508.0 229

2424.000 10.50610.0 267

VICTA

ULIC

No.W60

T

No. W60

Page 256: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size No. W50 No. W51

Nominal Size inches/Actual mm

E to E inches/mm

E to E inches/mm

14×

6 13.00 13.00355.6 168.3 330 330

8 13.00 13.00219.1 330 330

10 † 13.00 13.00273.0 330 330

12 † 13.00 13.00323.9 330 330

16 ×

8 14.00 14.00406.4 219.1 356 356

10 14.00 14.00273.0 356 356

12 † 14.00 14.00323.9 356 356

14 † 14.00 14.00355.6 356 356

18 ×

10 15.00 15.00457.0 273.0 381 381

12 15.00 15.00323.9 381 381

14 † 15.00 15.00350 381 381

16 † 15.00 15.00400 381 381

20 ×

12 20.00 20.00500 300 508 508

14 20.00 20.00350 508 508

16 † 20.00 20.00400 508 508

18 † 20.00 20.00450 508 508

24 ×

16 20.00 20.00600 400 508 508

18 † 20.00 20.00450 508 508

20 † 20.00 20.00500 508 508

† Standard as cast ductile iron. Contact Victaulic for details.

Outlets in sizes 12 inch/323.9 mm and smaller are provided with original groove system roll or cut grooves that are suitable for use with standard Victaulic grooved pipe couplings in that size range.

VICTAULICNo.W50

Eto E

No. W50

VICTAULICNo.W51E to E

No. W51

Page 257: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size No. 10 No. 11

Tee

NominalSize

mm/inches mm/inchesC to E

mm/inchesC to E

mm/inchesC to E

mm/inches

200A 216.3 197 108 1978 8.515 7.75 4.25 7.75

250A 267.4 229 121 22910 10.528 9.00 4.75 9.00

300A 318.5 254 133 25412 12.539 10.00 5.25 10.00

Fittings made to US standard sizes are available from 200A – 600A, which are compatible with JIS standards. Contact Victaulic for details.

C to E

CtoE

SizeC to EBranch

Nominal Sizemm/inches

mm/inches

mm/inches

mm/inches

200Ax

200Ax

165 216.3x

216.3x

165.1 198.1 198.18 8 6 ½ 8.515 8.515 6.500 7.8 7.8

250Ax

250Ax

200A 267.4x

267.4x

216.3 228.6 228.610 10 8 10.528 10.528 8.515 9.0 9.0

300Ax

300Ax

250A 318.5x

318.5x

267.4 254.0 254.012 12 10 12.539 12.539 10.528 10.0 10.0

Fittings made to US standard sizes are available from 200A – 600A, which are compatible with JIS standards. Contact Victaulic for details.

Size E to E

Nominal Sizemm/inches mm/inches

mm/inches

200Ax

165 216.3x

165.1 127.08 6 ½ 8.515 6.500 5.00

250Ax

200A 267.4x

216.3 152.410 8 10.528 8.515 6.00

300Ax

250A 318.5x

267.4 177.812 10 12.539 110.528 7.00

Fittings made to US standard sizes are available from 200A – 600A, which are compatible with JIS standards. Contact Victaulic for details.

Eto E

No. 50

Cto E

C to E

C to E

No. 10 No. 11

C to E

CtoE

Page 258: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

NOTICE

Y Y Y

Style 009H

Size

Nominal Size inches or mm

Actual Pipe Outside Diameter

inches/mm Style 009H

1¼1.660 4.77 – –42.4 121 – –

1½1.900 4.97 – –48.3 126 – –

22.375 5.53 5.75 5.5960.3 140 146 142

2½2.875 6.09 6.26 6.13

73.0 155 159 156

76.1 mm3.000 6.31 6.39 6.31

76.1 160 162 160

33.500 6.70 7.36 7.05

88.9 170 187 179

44.500 7.82 8.39 8.24

114.3 199 213 209

139.7 mm5.500 – 9.60 9.52

139.7 – 244 242

55.563 – 9.72 9.66

141.3 – 247 245

165.1 mm6.500 – 11.32 –

165.1 – 288 –

66.625 – 11.32 11.14

168.3 – 288 283

88.625 – 13.56 13.56

219.1 – 344 344

The “Y” dimensions, listed above, apply to the pre-assembled, installation-ready condition.

Page 259: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

NOTICE

Y Y Y

Y

Style 005

Size

Nominal Size inches or mm

Actual Pipe Outside

Diameter inches/mm Style 005

11.315 – 4.22 –33.7 – 107 –

1 ¼1.660 4.50 4.62 –42.4 114 117 –

1 ½1.900 4.75 5.81 –48.3 121 148 –

22.375 5.25 5.78 6.68 60.3 133 147 168

2 ½2.875 5.75 6.38 7.1373.0 146 162 181

76.1 mm3.000 5.75 6.61 –76.1 146 168 –

33.500 6.13 6.81 7.7588.9 156 173 197

44.500 7.25 8.21 9.63114.3 184 209 245

108.0 mm4.250 7.25 7.98 –108.0 184 203 –

55.563 9.00 9.89 –141.3 229 251 –

133.0 mm5.250 9.00 9.60 –133.0 229 244 –

139.7 mm5.500 9.00 9.82 –139.7 229 249 –

66.625 10.00 10.83 12.68168.3 254 275 321

Page 260: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size inches or mm

Actual Pipe Outside

Diameter inches/mm Style 005

159.0 mm6.250 10.00 10.54 –159.0 254 268 –

165.1 mm6.500 10.00 10.84 –165.1 254 275 –

88.625 13.14 13.74 15.00219.1 334 349 381

10 §10.750 – 16.98 17.25273.0 – 431 438

12 §12.750 – 18.88 19.13323.9 – 480 486

14 †14.000 – – 22.00323.9 – – 559

16 †16.000 – – 24.13406.4 – – 613

Y Y Y

Y

Style 005

Page 261: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size

inches/Actual mm inches/mm inches/mm

1 ½×

½ 2.63 4.5048.3 21.3 67 114

¾ 2.63 4.5026.9 67 114

1 2.63 4.5033.7 67 114

½ 3.03 5.0060.3 21.3 77 127

¾ 3.03 5.0026.9 77 127

1 3.03 5.0033.7 77 127

2 ½×

½ 3.13 6.0073.0 21.3 79 152

¾ 3.13 6.0026.9 79 152

1 3.13 6.0033.7 79 152

1 ¼ 3.69 6.8842.4 94 175

1 ½ 3.69 6.8848.3 94 175

¾ 3.31 7.0088.9 20 84 178

1 4.75 8.0033.7 121 203

1 ¼ 4.75 8.0042.4 121 203

1 ½ 4.25 8.0048.3 108 203

¾ 3.81 8.38114.3 20 97 213

1 3.81 8.3833.7 97 213

1 ½ 4.59 9.0048.3 117 229

2 4.59 9.0060.3 117 229

1 6.88 12.00168.3 33.7 175 305

1 ½ 6.88 12.0048.3 175 305

2 6.06 12.0060.3 154 305

§ Center of run to end of fitting The No. 60 Cap is not suitable for use in vacuum services with Style 72 Outlet Couplings. For

this type of service, No. 60 Bull Plugs should be used.

Y

V

Page 262: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Y Y Y Y Y

mm

559.0-mm

610.0-mm

Size

Nominal Size inches or mm

Actual Pipe Outside Diameter

inches/mm

¾1.050 – 4.00 – 3.89 3.3126.9 – 102 – 99 84

11.315 4.27 4.12 4.12 4.50 4.0433.7 108 105 105 114 103

1¼1.660 4.61 5.00 4.91 4.79 4.3742.4 117 127 125 122 111

1½1.900 4.82 5.38 5.23 4.80 4.4348.3 122 137 133 122 113

22.375 5.22 5.88 5.77 5.33 5.0060.3 133 149 147 135 127

57.0 mm2.664 – 5.73 – – –57.0 – 146 – – –

2½2.875 5.68 6.50 6.38 5.79 5.5073.0 144 165 162 147 140

76.1 mm3.000 5.90 6.63 – – –76.1 150 168 – – –

33.500 7.00 7.13 7.04 6.99 6.3888.9 178 181 179 178 162

3½4.000 7.50 8.25 – – –101.6 191 210 – – –

44.500 8.03 8.88 8.78 9.00 8.50114.3 204 226 223 229 216

108.0 mm4.250 7.79 8.63 – – –108.0 198 219 – – –

4½5.000 9.43 – – – –127.0 240 – – – –

55.563 10.07 10.65 10.47 – –141.3 256 270 266 – –

133.0 mm5.250 9.37 10.38 – – –133.0 238 264 – – –

139.7 mm5.500 9.59 10.65 – – –139.7 244 270 – – –

152.4 mm6.000 10.48 – – – –152.4 266 – – – –

66.625 11.07 11.88 11.77 11.06 11.04168.3 281 302 299 281 280

159.0 mm6.250 10.49 11.50 – – –159.0 266 292 – – –

Page 263: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size inches or mm

Actual Pipe Outside Diameter

inches/mm

165.1 mm6.500 – 11.63 – – –165.1 – 295 – – –

203.2 mm8.000 13.33 – – – –203.2 339 – – – –

8 §8.625 13.97 14.75 14.73 14.74 –219.1 355 375 374 374 –

254.0 mm10.000 15.81 – – – –254.0 402 – – – –

10 §10.750 – 17.13 – 17.33 –273.0 – 435 – 440 –

304.8 mm12.000 17.69 – – – –304.8 449 – – – –

12 §12.750 – 19.25 19.15 19.15 –323.9 – 489 486 486 –

14 ‡14.000 – 19.88 – 20.44 –355.6 – 505 – 519 –

377.0 mm #14.842 – 20.96 – – –377.0 – 531 – – –

16 ‡16.000 – 22.13 – 22.52 –406.4 – 562 – 572 –

426.0 mm #16.772 – 22.92 – – –426.0 – 581 – – –

18 ‡18.000 – 24.50 – 24.62 –457.0 – 622 – 625 –

480.0 mm #18.898 – 25.86 – – –480.0 – 655 – – –

20 ‡20.000 – 27.25 – – –508.0 – 692 – – –

530.0 mm #20.866 – 27.80 – – –530.0 – 704 – – –

22 ‡22.000 – 29.50 – – –559.0 – 749 – – –

580.0 mm #22.835 – 30.01 – – –580.0 – 762 – – –

24 ‡24.000 – 31.25 – – –609.6 – 794 – – –

630.0 mm #24.803 – 32.16 – – –630.0 – 817 – – –

§ Style 77 Standard Flexible Couplings in 8, 10, 12-inch/219.1, 273.0, 323.9-mm sizes are available to JIS standards. ‡ For use on cut grooved systems only. For roll grooved systems, Victaulic offers the Advanced Groove System (AGS). # CIS size product is designed with two housings.

Y Y Y Y Y

mm

559.0-mm

610.0-mm

Page 264: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size

inches

Actual Pipe Outside

Diameter inches/mm

11.315 3.25 –33.7 83 –

1 ¼1.660 3.75 –42.2 95 –

1 ½1.900 4.50 –48.3 114 –

22.375 4.75 4.8860.3 121 124

2 ½2.875 5.88 –73.0 149 –

33.500 6.25 –88.9 159 –

44.500 7.75 –114.3 197 –

55.563 9.50 –141.3 241 –

66.625 10.63 –168.3 270 –

88.625 13.00 –219.1 330 –

1010.750 – 15.60273.0 – 396

Refer to the installation instructions in this manual for locking handle clearance dimensions.

Y

Page 265: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Y Y Y Y Y

Style 89 Styles

Style

Size

Nominal Size inches or mm

Actual Pipe Outside Diameter

inches/mmStyle 89

Style Style Style Style

11.315 – 4.36 3.98 – –33.7 – 111 101 – –

1 ¼1.660 – 4.67 4.45 – –42.4 – 119 113 – –

1 ½1.900 – 4.74 4.52 4.42 –48.3 – 120 115 118 –

22.375 6.68 5.03 5.03 5.19 6.6860.3 168 128 128 132 168

2 ½2.875 7.13 5.59 5.59 5.62 7.1373.0 181 142 142 143 181

76.1 mm3.000 7.25 5.73 5.73 5.72 7.2576.1 184 146 146 145 184

33.500 7.75 6.67 6.67 6.78 7.7588.9 197 169 169 172 197

44.500 9.63 7.96 7.96 7.90 9.63114.3 245 202 202 201 245

139.7 mm5.500 10.63 8.97 – 11.13 10.63139.7 270 228 – 283 270

55.563 10.63 – – – –141.3 270 – – – –

165.1 mm6.500 12.38 10.53 – 12.68 12.38165.1 314 268 – 321 314

66.625 12.68 – – 12.68 12.68168.3 321 – – 321 321

216.3 mm8.515 15.25 – – 15.00 –216.3 387 – – 381 –

88.625 15.25 – – 15.00 15.25219.1 387 – – 381 387

267.4 mm10.528 17.00 – – 17.25 –267.4 432 – – 438 –

1010.750 17.25 – – 17.25 17.25273.0 438 – – 438 438

318.5 mm12.539 19.63 – – 19.13 –318.5 499 – – 486 –

1212.750 19.63 – – 19.13 19.63323.9 499 – – 486 499

Page 266: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size inches/Actual mm inches/mm

1 5.2860.3 33.7 134

1 ½ 5.2848.3 134

2 ½×

2 5.9373.0 60.3 151

76.1 mm× 2 6.63

60.3 168

2 7.1388.9 60.3 181

2 ½ 7.1373.0 181

88.9 mm × 76.1 mm7.13181

2 8.90114.3 60.3 226

2 ½ 8.9073.0 226

3 8.9088.9 226

114.3 mm × 76.1 mm8.90226

4 10.70141.3 114.3 272

4 11.90168.3 114.3 302

5 11.90141.3 302

165.1 mm× 4 11.90

114.3 302

6 14.88219.1 168.3 378

219.1 mm × 165.1 mm14.88378

10×

8 17.26273.0 219.1 438

The No. 60 Cap is not suitable for use in vacuum services with Style 750 Reducing Couplings. For this type of service, No. 61 Bull Plugs should be used.

Y

Page 267: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

YY

Y

Size

Nominal Size inches

Actual Pipe Outside Diameter

inches/mm

22.375 – 4.7160.3 – 120

2 ½2.875 – 5.4873.0 – 139

33.500 – 6.1588.9 – 156

44.500 – 7.62114.3 – 194

66.625 – 10.18168.3 – 259

88.625 – 12.50219.1 – 318

2626.000 34.25 –660.4 870 –

2828.000 36.33 –711.0 923 –

3030.000 38.32 –762.0 973 –

3232.000 40.43 –813.0 1027 –

3636.000 44.33 –914.0 1126 –

4242.000 51.56 –1067.0 1310 –

For Style 791 Vic-Boltless Couplings, refer to the installation instructions in this manual for Style 792 Assembly Tool clearance dimensions.

Page 268: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size inches

Actual Pipe Outside Diameter

inches/mm Style W89

1414.000 20.59 21.38355.6 523 543

1616.000 23.51 23.50406.4 597 597

1818.000 25.53 25.63457.0 648 651

2020.000 27.13 27.63508.0 689 702

2424.000 32.31 32.00610.0 821 813

2626.000 35.23 –660.4 895 –

2828.000 37.22 –711.2 945 –

3030.000 39.64 –762.0 1007 –

3232.000 41.74 –812.8 1060 –

3636.000 45.72 –914.4 1161 –

4040.000 50.51 –1016.0 1283 –

4242.000 52.50 –1066.8 1334 –

4646.000 56.48 –1168.4 1435 –

4848.000 58.47 –1219.2 1485 –

5454.000 65.16 –1371.6 1655 –

5656.000 67.65 –1422.2 1718 –

6060.000 72.13 –1524.0 1832 –

Y

Y

Y

Y

Y

Style W89

Page 269: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

YY

YY Y

Style 005

Nominal Size Style 005

200A 216.3 337 346 349 374 3568 8.515 13.25 13.62 13.75 14.72 14.02

250A 267.4 – 431 – 433 42210 10.528 – 16.97 – 17.05 16.61

300A 318.5 – 480 – 486 47512 12.539 – 18.90 – 19.13 18.70

Couplings made to US standard sizes are available from 200A – 600A, which are compatible with JIS standards. Contact Victaulic for details.

Page 270: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

W W W W W

610.0-mm

Size

Nominal Size inches or mm

Actual Pipe Outside

Diameter inches/mm

22.375 6.84 6.75 7.70 6.7560.3 174 172 196 172

2 ½2.875 7.72 7.87 8.61 7.8873.0 196 200 219 200

33.500 8.22 8.29 9.48 8.4488.9 209 211 241 214

44.500 9.72 9.87 11.35 9.94114.3 247 251 288 252

55.563 – 10.90 12.31 11.00141.3 – 277 313 279

66.625 11.78 11.90 13.77 12.00168.3 299 302 350 305

165.1 mm6.500 – 11.92 – –165.1 – 303 – –

88.625 – 14.50 16.68 14.63219.1 – 368 424 372

1010.750 – 17.24 19.25 –273.0 – 438 489 –

1212.750 – 20.25 22.25 –323.9 – 514 565 –

14 #14.000 – 24.50 – –355.6 – 622 – –

16 #16.000 – 27.12 – –406.4 – 689 – –

18 #18.000 – 29.00 – –457.0 – 737 – –

20 #20.000 – 31.50 – –508.0 – 800 – –

24 #24.000 – 36.00 – –610.0 – 914 – –

# For cut-grooved systems only. For 14 - 24-inch/355.6 - 610.0-mm roll-grooved systems, the Style W741 AGS Vic-Flange Adapter is used. The Style 741 is not compatible with the AGS system.

Page 271: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size mm

Actual Pipe Outside

Diameter mm/inches and PN16

Australian Standard

5060.3 177 1652.375 6.97 6.50

76.176.1 208 –

3.000 8.19 –

8088.9 218 200

3.500 8.58 7.87

100114.3 251 2514.500 9.88 9.87

139.7139.7 274 –5.500 10.79 –

159.0159.0 307 –6.250 12.09 –

165.1165.1 303 3036.500 11.93 11.92

150168.3 302 2866.625 11.89 11.25

200219.1 368 # 3688.625 14.49 14.50

250273.0 437 § –10.750 17.20 –

300323.9 478 ‡ –12.750 18.82 –

# PN16 dimensions (mm/inches): W = 360/14.17 § PN16 dimensions (mm/inches): W = 438/17.24 ‡ PN 16 dimensions (mm/inches): W = 478/18.82

Size

Nominal Size mm

Actual Pipe Outside

Diameter mm/inches

6576.3 208

3.000 8.20

7373.0 200

2.880 7.87

8089.1 211

3.500 8.29

100114.3 2514.500 9.87

141.3141.3 2775.560 10.90

165.1165.1 3026.500 11.90

150165.2 3026.625 11.90

W

W

Page 272: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size inches

Actual Pipe Outside Diameter

inches/mm

1414.000 24.50355.6 622

1616.000 27.12406.4 688

1818.000 29.00457.0 737

2020.000 31.50508.0 800

2424.000 36.00610.0 914

W

Page 273: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size inches or mm

Actual Pipe Outside Diameter

inches/mm Style 99

11.315 4.2533.7 108

1 ½1.900 5.5048.3 140

22.375 6.7560.3 171

2 ½2.875 7.1373.0 181

76.1 mm3.000 6.2576.1 159

33.500 8.5088.9 216

3 ½4.000 9.25101.6 235

44.500 10.00114.3 254

139.7 mm5.500 10.75139.7 260

55.563 11.38141.3 289

66.625 13.38168.3 340

165.1 mm6.500 13.25165.1 337

88.625 14.38219.1 365

1010.750 16.38273.0 416

1212.750 19.63323.9 499

1414.000 20.75355.6 527

1616.000 22.63406.4 575

1818.000 23.50457.0 597

Y

Style 99

Y

Style 99

Y

Style 99

Page 274: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size inches or mm

Actual Pipe Outside

Diameter inches/mm

AEnd-to-End

BOverall Height*

22.375 3.21 5.6260.3 82 143

2 ½2.875 3.77 6.3573.0 96 161

76.1 mm3.000 3.77 6.3576.1 96 161

33.500 3.77 6.8588.9 96 174

44.500 4.63 8.13114.3 118 207

108.0 mm †4.250 4.63 8.13108.0 118 207

55.563 5.88 9.59141.3 149 244

133.0 mm †5.250 5.88 9.59133.0 149 244

139.7 mm5.500 5.88 9.59139.7 149 244

66.625 5.88 10.58168.3 149 269

159.0 mm †6.250 5.88 10.58159.0 149 269

165.1 mm6.500 5.88 10.58165.1 149 269

88.625 5.33 13.00219.1 135 330

1010.750 6.40 15.88273.0 163 403

1212.750 6.50 17.88323.9 165 454

† Contact Victaulic for availability * The “B” Overall Height dimension is given for a bare valve and is for reference only. Refer to Victaulic publication 08.20 for dimensions with gear operator and handle options. DO NOT attempt to operate the valve without a gear operator or handle installed.

2 – 8-inch/60.3 – 219.1-mm sizes are ISO Flange Designation F07; 10 – 12-inch/273.0 – 323.9-mm sizes are ISO Flange Designation F10

A

B

Page 275: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size inches or mm

Actual Pipe Outside

Diameter inches/mm

AEnd-to-End

BOverall Height

1 ½1.900 3.38 6.0748.3 86 154

22.375 3.19 6.5860.3 81 167

2 ½2.875 3.81 7.8173.0 97 198

33.500 3.81 8.3788.9 97 213

44.500 4.56 10.19114.3 116 259

55.563 5.81 12.25141.3 148 311

66.625 5.81 13.28168.3 148 337

165.1 mm6.500 5.81 13.28165.1 148 337

Size

Nominal Size inches or mm

Actual Pipe Outside

Diameter inches/mm

AEnd-to-End

BOverall Height

2 ½2.875 6.00 9.8073.0 152 249

76.1 mm3.000 6.00 9.8076.1 152 249

33.500 6.25 10.4888.9 159 266

44.500 6.63 11.89114.3 168 302

66.625 7.00 13.74168.3 178 349

88.625 8.00 16.92219.1 203 430

1010.750 8.00 19.18273.0 203 487

A

B

B

A

Page 276: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

A

B

Size

Nominal Size inches or mm

Actual Pipe Outside Diameter

inches/mmA

End-to-EndB

Overall Height

22.375 4.25 8.6960.3 108 221

2½2.875 3.77 9.8273.0 96 249

76.1 mm3.000 3.77 9.8276.1 96 249

33.500 3.77 10.3288.9 96 262

108.0 mm4.250 4.63 11.69108.0 118 297

44.500 4.63 11.69114.3 118 297

133.0 mm5.250 5.88 14.23133.0 149 361

139.7 mm5.500 5.88 14.23139.7 149 361

55.563 5.88 14.23141.3 149 361

159.0 mm6.250 5.88 15.22159.0 149 387

165.1 mm6.500 5.88 15.22165.1 149 387

66.625 5.88 15.22168.3 149 387

88.625 5.33 18.60219.1 135 472

10 *10.750 6.40 22.01273.0 163 559

12 *12.750 6.50 24.00323.9 165 610

* Series 707C and Series 766 Butterfly Valves are not available in 10-inch/273.0-mm and 12-inch/323.9-mm sizes.

Page 277: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal AWWA Size

inches

Actual AWWA Pipe Outside

Diameter inches/mm

AEnd-To-End

33.960 8.00100.6 203

44.800 9.00121.9 229

66.900 10.50175.3 267

89.050 11.50229.9 292

1011.100 13.00281.9 330

1213.200 14.00335.3 356

Refer to Victaulic publication 08.12 for additional dimensions with gear operator and handle options.

Size

Nominal Size inches

Actual Pipe Outside

Diameter inches/mm

AEnd-To-End

BOverall Height

2 §2.375 9.00 6.6960.3 229 170

2 ½2.875 9.25 7.7573.0 235 197

33.500 10.75 8.2588.9 273 210

44.500 12.00 11.01114.3 305 280

§ The Series 712S and Series 731 are available only in the 2-inch/60.3-mm size.

A

SEAT END

B

A

Page 278: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size inches

Actual Pipe Outside

Diameter inches/mm

AEnd-To-End

BOverall Width

22.375 8.66 6.4650.8 220 164

2 ½2.875 9.37 6.9473.0 238 176

76.1 mm3.000 9.37 6.9476.1 238 176

33.500 9.62 7.4488.9 244 189

44.500 9.63 6.00114.3 245 152

139.7 mm5.500 10.50 6.80139.7 267 173

55.563 10.50 6.80141.3 267 173

165.1 mm6.500 11.50 8.00165.1 292 203

66.625 11.50 8.00168.3 292 203

88.625 14.00 9.88219.1 356 251

1010.750 17.00 12.00273.0 432 305

1212.750 19.50 14.00323.9 495 356

Size

Nominal Size inches

Actual Pipe Outside

Diameter inches/mm

AEnd-To-End

BOverall Height

44.500 9.63 7.38114.3 245 187

139.7 mm5.500 10.50 8.75139.7 267 222

55.563 10.50 8.75141.3 267 222

165.1 mm6.500 11.50 9.50165.1 292 241

66.625 11.50 9.50168.3 292 241

88.625 14.00 11.74219.1 356 298

1010.750 17.00 13.80273.0 432 351

1212.750 19.50 15.74323.9 495 400

A

B

B

A

Page 279: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size inches

Actual Pipe Outside

Diameter inches/mm

AEnd-To-End

BOverall Width

2 ½2.875 3.88 4.2673.0 99 108

76.1 mm3.000 3.88 4.2676.1 99 108

33.500 4.25 5.0688.9 108 129

44.500 9.63 6.00114.3 245 152

139.7 mm5.500 10.50 6.80139.7 267 173

55.563 10.50 6.80141.3 267 173

165.1 mm6.500 11.50 8.00165.1 292 203

66.625 11.50 8.00168.3 292 203

88.625 14.00 9.88219.1 356 251

1010.750 17.00 12.00273.0 432 305

1212.750 19.50 14.00323.9 495 356

Size

Nominal Size inches

Actual Pipe Outside

Diameter inches/mm

AEnd-To-End

B *Overall Width

2 †2.375 8.66 11.7360.3 220 298

2 ½ †2.875 9.37 13.8173.0 238 351

76.1 mm †3.000 9.37 13.8176.1 238 351

3 †3.500 9.62 14.3188.9 244 363

4 #4.500 9.63 25.50114.3 245 648

139.7 mm #5.500 10.50 27.50139.7 267 699

5 #5.563 10.50 27.50141.3 267 699

165.1 mm #6.500 11.50 28.50165.1 292 724

6 #6.625 11.50 28.50168.3 292 724

8 #8.625 14.00 29.88219.1 356 759

† The Series 717HR is available only in 2 – 3-inch/60.3 – 88.9-mm sizes. # The Series 717R is available only in 4 – 8-inch/114.3 – 219.1-mm sizes. * The “B” dimension includes the Victaulic Riser Check Kit

A

B

A

B(Handle Open)

A

B(Handle Open)

Page 280: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size inches

Actual Pipe Outside

Diameter inches/mm

AEnd-to-End

¼0.540 1.5413.7 39

3⁄80.675 1.7717.1 45

½0.084 2.1321.3 54

¾1.050 2.4426.7 62

11.315 2.9533.4 75

1 ¼1.660 3.3142.2 84

1 ½1.900 3.6648.3 93

22.375 4.2160.3 107

Size

Nominal Size inches

Actual Pipe Outside

Diameter inches/mm

AEnd-to-End

22.375 6.5060.3 165

Size

Nominal Size inches or mm

Actual Pipe Outside

Diameter inches/mm

AEnd-to-End

1 ½1.900 5.1248.3 130

22.375 5.5060.3 140

2 ½2.875 6.2573.0 159

76.1 mm3.000 6.25

76.1 159

33.500 6.5688.9 167

44.500 8.25114.3 210

66.625 10.10168.3 257

A

A

A

Page 281: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size inches/Actual mm

AEnd-to-End

BOverall Height

1 Thd. x Thd. 2.84 4.7433.7 Thd. x Thd. 72 120

1¼ Thd. x Thd. 3.31 4.9542.4 Thd. x Thd. 84 126

1½ Thd. x Thd. 3.66 5.1348.3 Thd. x Thd. 93 130

2 Thd. x Thd. 4.33 5.4960.3 Thd. x Thd. 110 139

1¼ Grv. x Grv. 7.25 4.9542.4 Grv. x Grv. 184 126

1½ Grv. x Grv. * 7.25 5.1748.3 Grv. x Grv. * 184 131

2 Grv. x Grv. * 7.25 5.4760.3 Grv. x Grv. * 184 139

Size

Nominal Size inches or mm

Actual Pipe Outside

Diameter inches/mm

AEnd-to-End

BOverall Height*

22.375 3.20 6.2660.3 81 159

2 ½2.875 3.77 6.8573.0 96 174

76.1 mm3.000 3.77 6.8576.1 96 174

33.500 3.77 7.5788.9 96 192

44.500 4.64 8.47114.3 118 215

165.1 mm6.500 5.88 12.01165.1 149 305

66.625 5.88 12.01168.3 149 305

88.625 5.32 14.30219.1 135 363

1010.750 6.40 17.14273.0 163 435

* The “B” Overall Height dimension is given for a bare valve and is for reference only. Refer to Victaulic publication 17.23 for dimensions with gear operator and handle options. DO NOT attempt to operate the valve without a gear operator or handle installed.

B

A

B

A

Page 282: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Triple Service Valve AssembliesB

A

B

A

SEAT END

B

ASEAT END

B

A

MasterSeal Handle-Operated

Valve and Series

3-inch/88.9-

Vic-Plug Valve

Coupling

Vic-Plug Valve

Coupling

Size

Nominal Size inches

or mm

Actual Pipe Outside

Diameter inches/mm

AEnd-to-End

AEnd-to-EndHandle Operator Handle Operator

2 ½2.875 7.75 8.01 9.41

— — —73.0 197 203 239

76.1 mm76.1 7.75 8.01 9.41

— — —3.000 197 203 239

33.500 8.12 8.63 10.03 12.25 12.00 16.1388.9 206 219 255 311 305 410

44.500 14.38 10.88 12.28 18.62 13.19 17.31114.3 365 276 312 473 335 440

55.536 16.50 12.50 14.43

— — —141.3 419 318 367

139.7 mm139.7 16.50 12.50 14.43

— — —5.500 419 318 367

66.625 17.50 13.38 15.31 22.00 15.56 19.31168.3 444 340 389 559 395 490

165.1 mm165.1 17.50 13.38 15.31

— — —6.500 444 340 389

88.625 19.50 15.63 17.68 25.50

—23.97

219.1 495 397 449 648 609

1010.750 23.50

—22.31 30.00

—30.63

273.0 597 567 762 778

1212.750 26.12

—24.25 33.50

—34.00

323.9 663 616 851 864

Page 283: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size inches

Actual Pipe Outside

Diameter inches/mm

AEnd-to-End

BOverall Height

1414.000 10.00 24.45355.6 254 621

1616.000 10.50 27.14406.4 267 689

1818.000 11.00 29.56457.0 279 751

2020.000 11.50 32.64508.0 292 829

2424.000 12.00 38.89610.0 305 988

Size

Nominal Size inches

Actual Pipe Outside

Diameter inches/mm

AEnd-to-End

BOverall Width

1414.000 10.75 16.93355.6 273 430

1616.000 12.00 19.88406.4 305 505

1818.000 14.25 21.54457.0 362 547

2020.000 14.50 24.75508.0 368 628

2424.000 15.50 28.81610.0 394 732

A

B

Vic-300

A

B

Page 284: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size inches or mm

Actual Pipe Outside

Diameter inches/mm

L - Length

Minimum

L - Length

Maximum

22.375 11.88 14.8860.3 302 378

76.1 mm3.000 12.13 15.1376.1 308 384

33.500 12.13 15.1388.9 308 384

44.500 14.13 17.13114.3 359 435

139.7 mm5.50 14.13 17.13139.7 359 435

55.563 14.13 17.13141.3 359 435

165.1 mm6.50 16.00 19.00165.1 406 483

66.625 16.00 19.00168.3 406 483

Size

Coupling Style

Nominal Size

inches

Actual Pipe Outside

Diameter inches/mm

L - Length

Compressed

L - Length

Expanded

¾1.050

7726.25 28.13

26.7 667 715

11.315

7726.25 28.13

33.7 667 715

1 ¼1.660

7728.25 30.13

42.4 718 765

1 ½1.900

7728.25 30.13

48.3 718 765

22.375

7528.25 30.13

60.3 718 765

2 ½2.875

7528.25 30.13

73.0 718 765

33.500

7528.25 30.13

88.9 718 765

3 ½4.000

7528.25 30.13

101.6 718 765

44.500

7526.25 28.00

114.3 667 711

55.563

7526.25 28.00

141.3 667 711

66.625

7526.25 28.00

168.3 667 711

88.625

7528.50 30.25

219.1 724 768

1010.750

7732.50 34.25

273.0 826 870

1212.750

7732.50 34.25

323.9 826 870

L min.L max.

Style 150

L

Style 155

Page 285: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size inches

Actual Pipe Outside

Diameter inches/mm

L - Length

Compressed

L - Length

Expanded

1414.000 30.00 31.75355.6 762 806

1616.000 30.00 31.75406.4 762 806

1818.000 30.00 31.75457.0 762 806

2020.000 30.00 31.75508.0 762 806

2424.000 30.00 31.75610.0 762 806

L

Style W155

Page 286: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Assembly

Size

Nominal Size

inches

Actual Pipe Outside

Diameter inches/mm Drain Size

AEnd-to-End

BOverall Height

11.315 1 11.45 13.4833.4 33 291 342

1 ¼1.660 1 11.45 13.4842.2 33 291 342

1 ½1.900 1 11.45 13.6148.3 33 291 346

22.375 1 11.45 13.9160.3 33 291 353

Size

Nominal Size

inches

Actual Pipe Outside

Diameter inches/mm Drain Size

AEnd-to-End

BOverall Height

1 ¼1.660 1 11.45 12.9742.2 33 291 329

1 ½1.900 1 11.45 13.0948.3 33 291 332

22.375 1 11.45 13.3260.3 33 291 338

2 ½2.875 1 ¼ 12.00 14.5973.0 42 305 371

33.500 1 ¼ 12.00 15.6088.9 42 305 396

44.500 2 12.00 17.15114.3 60 305 436

66.625 2 12.00 19.16168.3 60 305 487

A

B

A

B

Page 287: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

FULL DRAINPOSITION

CLOSEDPOSITION

DC

B

A

DC

B

A

FULL DRAINPOSITION

CLOSEDPOSITION

DC

GB

I A H

FULL DRAINPOSITION

CLOSEDPOSITION

Threaded Ends

Size

Nominal Sizeinches

Actual Pipe Outside

Diameter inches/mm A B C D H I

STYLE 720 GROOVED ENDS

1 ¼1.660 3.15 2.90 5.47 6.43

— — —42.4 80 74 139 163

1 ½1.900 3.65 3.06 5.47 6.51

— — —48.3 93 78 139 165

22.375 3.65 3.06 5.47 6.51

— — —60.3 93 78 139 165

STYLE 720 THREADED ENDS

11.315 3.00 2.38 5.47 6.43

— — —33.4 76 61 139 163

1 ¼*1.660 3.00 2.38 5.47 6.43

— — —42.2 76 61 139 163

1 ½*1.900 3.63 2.38 5.47 6.51

— — —48.3 92 61 139 165

22.375 3.63 2.38 5.47 6.51

— — —60.3 92 61 139 165

STYLE 720 WITH PRESSURE RELIEF VALVE

11.315 3.00 2.38 5.47 6.43 3.90 4.95 4.0033.4 76 61 139 163 99 126 102

1 ¼1.660 3.00 2.38 5.47 6.43 3.90 4.95 4.0042.2 76 61 139 163 99 126 102

1 ½1.900 3.63 2.38 5.47 6.51 4.09 4.95 4.0048.3 92 61 139 165 104 126 102

22.375 3.63 2.38 5.47 6.51 4.09 4.95 4.0060.3 92 61 139 165 104 126 102

* Not available in Canada

Page 288: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size inches

Actual Pipe Outside Diameter

inches/mm E to E

47-GT Grooved X Threaded

11.315 4.0033.7 102

1 ¼1.660 4.0042.4 102

1 ½1.900 4.0048.3 102

22.375 4.0060.3 102

2 ½2.875 6.0073.0 152

33.500 6.0088.9 152

3 ½4.000 6.00101.6 152

44.500 6.00114.3 152

47-TT Threaded X Threaded

½0.840 3.0021.3 76

¾1.050 3.0026.7 76

11.315 4.0033.7 102

1 ¼1.660 4.0042.4 102

1 ½1.900 4.0048.3 102

22.375 4.0060.3 102

2 ½2.875 6.0073.0 152

33.500 6.0088.9 152

3 ½4.000 6.00101.6 152

44.500 6.00114.3 152

E to E

E to E

Page 289: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

SizeDimensions inches/mm

Nominal Size inches

Actual Pipe Outside Diameterinches/mm

E to E

22.375 2.125 4.1960.3 54.0 106

2 ½2.875 2.625 6.1973.0 66.7 157

33.500 3.125 6.1988.9 79.4 157

44.500 4.125 6.19114.3 104.8 157

55.563 5.125 6.19141.3 130.2 157

66.625 6.125 6.19168.3 155.6 157

88.625 8.125 6.19219.1 206.4 157

Size inches/mm

Nominal Size inches

Actual Pipe Outside Diameter

inches/mm End-to-End

2 ½2.875 4.0073.0 102

33.500 4.2588.9 108

44.500 3.75114.3 95

55.563 5.00141.3 127

66.625 6.00168.3 152

88.625 7.00219.1 178

1010.750 8.00273.0 203

1212.750 12.00323.9 305

E to E

Page 290: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size inches

Actual Pipe Outside

Diameter inches/mm

AEnd-to-End

C

Clearance

1 ½1.900 5.50 4.0048.3 140 102

22.375 6.50 5.0060.3 165 127

2 ½2.875 7.50 5.0073.0 191 127

33.500 8.50 6.0088.9 216 152

44.500 10.00 7.00114.3 254 178

55.563 11.00 8.00141.3 279 203

66.625 13.00 10.00168.3 330 254

88.625 15.50 12.00219.1 394 305

1010.750 18.00 14.00273.0 457 356

1212.750 20.00 16.00323.9 508 406

Size

Nominal Size inches or mm

Actual Pipe Outside

Diameter inches/mm

AEnd-to-End

C

Clearance

22.375 9.75 8.0060.3 248 203

2 ½2.875 10.75 9.0073.0 273 229

76.1 mm3.000 10.75 10.0076.1 273 254

33.500 11.75 10.0088.9 299 254

44.500 14.25 12.00114.3 362 305

55.563 16.50 14.00141.3 419 356

165.1 mm6.500 18.50 16.00165.1 470 406

66.625 18.50 16.00168.3 470 406

88.625 24.00 20.00219.1 610 508

1010.750 27.00 24.00273.0 686 610

1212.750 30.00 28.00323.9 762 711

AC

C

A

Page 291: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

OAL

CLR

Nominal Size inches/Actual mm

Inlet x Outlet OAL - Overall Length

76.1 mm x2 12.25 14.00

60.3 311 356

3x

2 12.25 14.0088.9 60.3 311 356

2½ 12.25 14.0073.0* 311 356

76.1 mm*12.25 14.00311 356

3 14.50 16.0088.9 368 406

4x

2 12.25 14.00114.3 60.3 311 356

2½ 12.25 14.0073.0* 311 356

76.1 mm*12.25 14.00311 356

3 14.50 16.0088.9 368 406

4 16.00 18.00114.3 406 457

139.7 mm x 76.1 mm*12.25 14.00311 356

3 14.50 16.0088.9 368 406

4 16.00 18.00114.3 406 457

139.7 mm*18.50 20.00470 508

5x

3 14.50 16.00141.3 88.9 368 406

4 16.00 18.00114.3 406 457

5 18.50 20.00141.3* 470 508

* Does not conform to Australian Standard sizes. All sizes are available with either an ANSI Class 150 or 300 flange, except for the following

configurations: 88.9 x 76.1; 114.3 x 76.1; 139.7 x 76.1; 139.7 x 139.7; 165.1 x 139.7; 168.3 x 139.7; 219.1 x 139.7; 219.1 x 165.1; and 273.0 x 165.1.

All sizes conform to PN 10 and PN 16 sizes, except for the following configurations: 88.9 x 73.0; 114.3 x 73.0; 141.3 x 73.0; 141.3 x 88.9; 141.3 x 141.3; 168.3 x 141.3; and 219.1 x 141.3.

All sizes conform to JIS 10K sizes, except for the following configurations: 139.7 x 139.7; 165.1 x 139.7; 168.3 x 139.7; 219.1 x 139.7; 273.0 x 273.0; 323.9 x 273.0; and 323.9 x 323.9. Table continued on the following page.

Page 292: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Nominal Size inches/Actual mm

Inlet x Outlet OAL - Overall Length

165.1 mm x3 14.50 16.00

88.9 368 406

4 16.00 18.00114.3 406 457

139.7 mm*18.50 20.00470 508

6x

3 14.50 16.00168.3 88.9 368 406

4 16.00 18.00114.3 406 457

139.7 mm*18.50 20.00470 508

5 18.50 20.00141.3* 470 508

6 22.25 24.00

168.3 565 610

8x 139.7 mm*

18.50 20.00

219.1 470 508

5 18.50 20.00141.3* 470 508

165.1 mm22.25 24.00565 610

6 22.25 24.00

168.3 565 610

8 26.00 27.00219.1 660 686

10x 165.1 mm

22.25 24.00

273.0 565 610

6 22.25 24.00168.3 565 610

8 26.00 27.00219.1 660 686

10 29.00 30.00273.0* 737 762

12x

8 26.00 27.00323.9 219.1 660 686

10 29.00 30.00273.0* 737 762

12 37.25 37.00323.9* 946 940

OAL

CLR

Refer to notes on the previous page.

Page 293: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

CLR

SERIES 731D

6⁄168,3

4⁄114

.3

OAL

Size

System Side Pump Side Flange

OALOverall Length

Nominal Sizeinches/Actual mm

2 11.00 8.0088.9 60.3 279 203

2 ½ 11.00 8.0073.0 279 203

3 11.00 8.0088.9 279 203

2 ½ 13.00 9.50114.3 73.0 330 241

3 13.00 9.5088.9 330 241

4 13.00 9.50114.3 330 241

3 15.00 10.00141.3 88.9 381 254

4 15.00 10.00114.3 381 254

5 15.00 10.00141.3 381 254

4 16.00 11.50168.3 114.3 406 292

5 15.80 11.50141.3 406 292

6 15.80 11.50168.3 406 292

5 19.00 14.00219.1 141.3 483 356

6 19.00 14.00168.3 483 356

8 19.00 14.00219.1 483 356

10×

6 23.00 18.00273.0 168.3 584 457

8 22.50 18.00219.1 584 457

10 22.50 18.00273.0 584 457

12×

8 27.00 20.00323.9 219.1 686 508

10 26.84 20.00273.0 686 508

12 26.84 20.00323.9 686 508

Page 294: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

CLR

SERIES 731D

6⁄168,3

4⁄114

.3

OAL

Size mm/inches

System Side Pump Side Flange

OALOverall Length

millimeters/inches

76.1 mm ×50 279 2032 11.00 8.00

80×

50 279 2033 2 11.00 8.00

76.1 mm279 203

11.00 8.00

80 279 2033 11.00 8.00

100×

330 2414

76.1 mm13.00 9.50

80 330 2413 13.00 9.50

100 330 2414 13.00 9.50

139.7 mm × 76.1 mm381 254

15.00 10.00

80 381 2543 15.00 10.00

100 381 2544 15.00 10.00

139.7 mm381 254

15.00 10.00

125 × 80 381 2545 3 15.00 10.00

100 381 2544 15.00 10.00

125 381 2545 15.00 10.00

150×

100 406 2926 4 16.00 11.50

139.7 mm 406 29216.00 11.50

125 406 2925 16.00 11.50

150 406 2926 16.00 11.50

200× 139.7 mm

483 3568 19.00 14.00

125 483 3565 19.00 14.00

150 483 3566 19.00 14.00

200 483 3568 19.00 14.00

Page 295: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size mm/inches

System Side Pump Side Flange

OALOverall Length

millimeters/inches

250×

150 584 45710 6 23.00 18.00

200 584 4578 23.00 18.00

250 584 45710 23.00 18.00

300×

200 686 50812 8 27.00 20.00

250 686 50810 27.00 20.00

300 686 50812 27.00 20.00

CLR

SERIES 731D

6⁄168,3

4⁄114

.3

OAL

Page 296: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

CLR

SERIES 731D

6⁄168,3

4⁄114

.3

OAL

Size mm/inches

System Side Pump Side Flange

OALOverall Length

millimeters/inches

×50 279 203

76.1 mm2 11.00 8.00

80×

50 279 2033 2 11.00 8.00

279 20376.1 mm

11.00 8.00

80 279 2033 11.00 8.00

100×

330 2414

76.1 mm13.00 9.50

80 330 2413 13.00 9.50

100 330 2414 13.00 9.50

×381 267

139.7 mm 76.1 mm15.00 10.50

80 381 2673 15.00 10.50

100 381 2674 15.00 10.50

381 267139.7 mm

15.00 10.50

150 × 100 406 2926 4 16.00 11.50

406 292139.7 mm

16.00 11.50

125 406 2925 16.00 11.50

150 406 2926 16.00 11.50

200 × 483 3568

139.7 mm19.00 14.00

125 483 3565 19.00 14.00

150 483 3566 19.00 14.00

200 483 3568 19.00 14.00

250 × 150 584 45710 6 23.00 18.00

200 584 4578 23.00 18.00

250 584 45710 23.00 18.00

Page 297: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size mm/inches

System Side Pump Side Flange

OALOverall Length

millimeters/inches

300 × 200 686 50812 8 27.00 20.00

250 686 50810 27.00 20.00

300 686 50812 27.00 20.00

CLR

SERIES 731D

6⁄168,3

4⁄114

.3

OAL

Page 298: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

CLR

SERIES 731D

6⁄168,3

4⁄114

.3

OAL

Size

System Side Pump Side Flange

OALOverall Length

millimeters/inches

×50A 279 203

76.1 mm2 11.00 8.00

80A×

50A 279 2033 2 11.00 8.00

279 20376.1 mm

11.00 8.00

80A 279 2033 11.00 8.00

100A×

330 2414

76.1 mm13.00 9.50

80A 330 2413 13.00 9.50

100A 330 2414 13.00 9.50

×381 254

139.7 mm 76.1 mm15.00 10.00

125A×

381 2545

76.1 mm15.00 10.00

80A 381 2543 15.00 10.00

100A 381 2544 15.00 10.00

125A 381 2545 15.00 10.00

150A×

100A 406 2926 4 16.00 11.50

406 292139.7 mm

16.00 11.50

125A 406 2925 16.00 11.50

150A 406 2926 16.00 11.50

200A×

483 3568

139.7 mm19.00 14.00

125A 483 3565 19.00 14.00

150A 483 3566 19.00 14.00

200A 483 3568 19.00 14.00

Page 299: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

System Side Pump Side Flange

OALOverall Length

millimeters/inches

250A×

150A 584 45710 6 23.00 18.00

200A 584 4578 23.00 18.00

250A 584 45710 23.00 18.00

300A×

200A 686 50812 8 27.00 20.00

250A 686 50810 27.00 20.00

300A 686 50812 27.00 20.00

CLR

SERIES 731D

6⁄168,3

4⁄114

.3

OAL

Page 300: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

CLR

SERIES 731D

6⁄168,3

4⁄114

.3

OAL

Size mm/inchesSystem Side Pump Side

Flange OALOverall Length

millimeters/inches

×50 279 203

76.1 mm2 11.00 8.00

80×

50 279 2033 2 11.00 8.00

279 20376.1 mm

11.00 8.00

80 279 2033 11.00 8.00

100×

330 2414

76.1 mm13.00 9.50

80 330 2413 13.00 9.50

100 330 2414 13.00 9.50

125 × 80* 381 2545 3 15.00 10.00

100 381 2544 15.00 10.00

125 381 2545 15.00 10.00

150 × 100* 406 2926 4 16.00 11.50

125 406 2925 16.00 11.50

150 406 2926 16.00 11.50

200×

125* 483 3568 5 19.00 14.00

150 483 3566 19.00 14.00

200 483 3568 19.00 14.00

250 × 150* 584 45710 6 23.00 18.00

200 584 4578 23.00 18.00

250 584 45710 23.00 18.00

300 × 200* 686 50812 8 27.00 20.00

250 686 50810 27.00 20.00

300 686 50812 27.00 20.00

* Available with No. 50 Concentric Reducer and appropriate coupling. Contact Victaulic.

Page 301: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Size

Nominal Size inches

Actual Pipe Outside

Diameter inches/mm

AEnd-to-End

C

Clearance

1414.000 22.00 30.00355.6 559 762

1616.000 24.00 32.00406.4 610 813

1818.000 31.00 35.00457.0 787 889

2020.000 34.50 38.00508.0 876 965

2424.000 40.00 44.00610.0 1016 1118

Size

Nominal Size inches

Actual Pipe Outside

Diameter inches/mm

AEnd-to-End

C

Clearance

1414.00 34.00 30.00

355.60 863.6 762

1616.00 37.00 32.00

406.40 939.8 813

1818.00 40.51 35.00457.20 1028.9 889

A

C

A

C

Page 302: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

OAL

CLR

Nominal Size inches/Actual mm

Inlet x OutletOAL

Overall Length

12x

8 26.00 27.00323.9 219.1 660 686

10 29.00 30.00273.0 737 762

12 37.25 37.00323.9 946 940

14x

10 29.00 30.00355.6 273.0 737 762

12 37.25 37.00323.9 946 940

14 40.56 41.00355.6 1030 1041

16x

12 37.25 37.00406.4 323.9 946 940

14 40.56 41.00355.6 1030 1041

18x

16 44.50 45.00

457.0 406.4 1130 1143

24x

20 54.25 57.00610.0 508.0 1378 1448

Page 303: Victaulic I-100 Field Installation Handbook.pdf
Page 304: Victaulic I-100 Field Installation Handbook.pdf

Product Data and

ProductsThe following information contains take-out dimensions, overall dimensions, and hole

sizes for Victaulic hole-cut products. Refer to the current Victaulic product submittal for

complete dimensional information.

NOTICE

Page 305: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Nominal Size inches/ Actual mm

1x

½ 3.7233.7 21.3 94

1 ¼x

½ 4.1242.4 21.3 105

1 ½x

½ 4.3248.3 21.3 110

Nominal Sizeinches/Actual mm

V

1 ¼X

½ 1.83 3.8742.4 21.3 46.5 98.3

¾ 1.83 3.8726.9 46.5 98.3

1 2.18 3.8733.7 55.4 98.3

1 ½X

½ 1.95 4.0848.3 21.3 49.5 103.6

¾ 1.95 4.0826.9 49.5 103.6

1 2.30 4.0833.7 58.4 103.6

2X

½ 2.19 4.6060.3 21.3 55.6 116.8

¾ 2.19 4.6026.9 55.6 116.8

1 2.54 4.6033.7 64.5 116.8

2 ½X

½ 2.44 5.4073.0 21.3 62.0 137.2

¾ 2.44 5.4026.9 62.0 137.2

1 2.79 5.4033.7 70.9 137.2

76.1 mm X½ 2.44 5.50

21.3 62.0 139.7

¾ 2.44 5.5026.9 62.0 139.7

1 2.79 5.5033.7 70.9 139.7

† Victaulic female threaded products are designed to accommodate standard NPT or BSPT (optional) male pipe threads only. Use of male threaded products with special features, such as probes, dry pendent sprinkler heads, etc., should be verified as suitable for use with this Victaulic product. Failure to verify suitability in advance may result in assembly problems or leakage.

Y

V

Y

Page 306: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

X

Y

X

Y

Nominal Sizeinches/Actual mm

X

4 – 8 x ½ 3.00 3.09114.3 – 219.1 15 76 78

x ¾ 3.00 3.0920 76 78

10 and Larger x ½ 3.00 3.00273.0 and Larger 15 76 76

x ¾ 3.00 3.0020 76 76

***Width of collar as supplied. The width will change due to deformation of the collar during assembly. DUE TO DEFORMATION OF THE COLLAR, STYLE 923 VIC-LET STRAPLESS OUTLETS SHOULD NOT BE RE-USED AFTER INITIAL INSTALLATION.

Nominal Sizeinches/Actual mm

X

4 – 8 for 6-inch Stem † 7.09 3.09114.3 – 219.1 for 152.4-mm Stem 180 78

10 and Larger for 6-inch Stem † 7.09 3.09273.0 and Larger for 152.4-mm Stem 180 78

***Width of collar as supplied. The width will change due to deformation of the collar during assembly. DUE TO DEFORMATION OF THE COLLAR, STYLE 924 VIC-O-WELL THERMOMETER OUTLETS SHOULD NOT BE RE-USED AFTER INITIAL INSTALLATION. † 1 ¼-inch outlet – 1 ¼ – NEF18 – 2B

Page 307: Victaulic I-100 Field Installation Handbook.pdf

I-100_300

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Y

V T

Y

V

Threaded Outlet

SizeStyle

Number

X Branch T** Fem. Thd.Nominal inches/Actual mm

2x

½ (a)920N

2.00 2.53—

5.3560.3 21.3 51 64 136

¾ (a)920N

1.97 2.53—

5.3526.9 50 64 136

1 (a)920N

1.85 2.53—

5.3533.7 47 64 136

1 ¼ (a)920N

2.05 2.75 3.00 5.3542.4 52 70 76 136

1 ½ (a)920N

2.03 2.75 3.12 5.3548.3 52 70 79 136

2 ½x

½ (a)920N

2.21 2.74—

5.6473.0 21.3 56 70 143

¾ (a)920N

2.18 2.74—

5.6426.9 55 70 143

1 (a)920N

2.06 2.74—

5.6433.7 52 70 143

1 ¼ † (a)920N

2.30 3.00 3.25 6.2942.4 58 76 83 160

1 ½ † (a)920N

2.28 3.00 3.25 6.2648.3 58 76 83 159

76.1 mm x½ (a)

920N2.22 2.75

—6.46

21.3 56 70 164

¾ (a)920N

2.19 2.75—

6.4626.9 56 70 164

1 (a)920N

2.07 2.75—

6.4633.7 53 70 164

1 ¼ † (a)920N

2.30 3.00 3.31 6.2942.4 58 76 84 160

1 ½ (a)920N

2.28 3.00 3.31 6.2948.3 58 76 84 160

3x

½ (a)920N

2.52 3.05—

6.1588.9 21.3 64 78 156

¾ (a)920N

2.49 3.05—

6.1526.9 63 78 156

1 (a)920N

2.38 3.06—

6.1533.7 61 78 156

1 ¼ † (a)920N

2.55 3.25 3.56 6.1542.4 (b) 65 83 90 156

1 ½ † (a)920N

2.78 3.50 3.56 6.1548.3 (b) 71 89 90 156

2 (a)920N

2.75 3.50 3.56 6.7560.3 70 89 90 172

Page 308: Victaulic I-100 Field Installation Handbook.pdf

I-100_301

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

SizeStyle

Number

X Branch T** Fem. Thd.Nominal inches/Actual mm

3 ½x

2920N

3.00—

3.75 6.72101.6 60.3 76 95 171

4x

½ (a)920N

3.03 3.56—

7.01114.3 21.3 77 90 178

¾ (a)920N

3.00 3.56—

7.0126.9 76 90 178

1 (a)920N

2.88 3.56—

7.0133.7 73 90 178

1 ¼ † (a)920N

3.08 3.78 4.00 7.0142.4 (b) 78 96 102 178

1 ½ † (a)920N

3.28 4.00 4.00 7.0148.3 (b) 83 102 102 178

2 † (a)920N

3.25 4.00 4.00 7.0160.3 83 102 102 178

2 ½ † (a)920

2.88 4.00 4.00 7.3473.0 73 102 102 186

76.1 mm 9202.88

—4.00 7.34

73 102 186

3 † (a)920

3.31 4.50 4.12 7.7388.9 84 114 105 196

108.0 mm x1 ¼ (a)

920N3.08 3.78

—7.64

42.4 78 96 194

1 ½ (a)920N

3.28 4.00—

7.6448.3 88 102 194

2 (a)920N

3.25 4.00—

7.6460.3 83 102 194

76.1 mm 9202.88 4.00 4.00 7.6473 102 102 194

3 (a)920

3.31 4.50 4.50 7.6388.9 84 114 114 194

5x

1 ½ † (a)920

4.03 4.75 4.75 9.70141.3 48.3 102 121 121 246

2 † (a)920

4.00 4.75 4.75 9.7060.3 102 121 121 246

2 ½ † (a)920

3.63 4.75 4.75 9.7073.0 92 121 121 246

76.1 mm 9203.75

—4.75 9.70

95 121 246

3 † (a)920

3.81 5.00 4.63 9.7088.9 97 127 118 246

Y

V T

Y

V

Threaded Outlet

Page 309: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

SizeStyle

Number

X Branch T** Fem. Thd.Nominal inches/Actual mm

133.0 mm x2

920N3.75 4.50

—8.00

60.3 95 114 203

3920

3.81 5.00—

9.4688.9 97 127 240

139.7 mm x1 ½ †

920N3.78 4.50

—8.23

48.3 96 114 209

2 †920N

3.75 4.50—

8.2360.3 95 114 209

6x

1 ¼920N

4.43 5.13 5.13 9.15168.3 42.4 113 130 130 232

1 ½ † (a)920N

4.40 5.13 5.13 9.1548.3 (b) 112 130 130 232

2 † (a)920N

4.38 5.13 5.13 9.1560.3 111 130 130 232

76.1 mm (a) (b) 920

4.15—

5.21 10.51105 132 267

3 † (a)920

4.31 5.50 5.13 10.5188.9 110 140 130 267

4 † (a)920

3.81 5.75 5.38 10.51114.3 97 146 137 267

159.0 mm x1 ½ (a)

920N4.41 5.13

—9.40

48.3 112 130 239

2 (a)920N

4.38 5.13—

9.4060.3 111 130 239

76.1 mm 9204.38 5.50 5.13 9.40111 140 130 239

3920

4.31 5.50 5.13 9.4088.9 110 140 130 239

108.0 mm 9204.45

—5.38 9.40

113 137 239

4920

3.81 5.75—

9.40114.3 97 146 239

Y

VT

Y

V

Threaded Outlet

Page 310: Victaulic I-100 Field Installation Handbook.pdf

I-100_303

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

SizeStyle

Number

X Branch T** Fem. Thd.Nominal inches/Actual mm

165.1 mm x1

920N3.88 4.56

—9.34

33.7 99 116 237

1 ¼920N

4.43 5.13—

9.3442.4 113 130 237

1 ½ † (a)920N

4.41 5.13 5.13 9.3448.3 112 130 130 237

2 † (a)920N

4.38 5.13 5.13 9.3460.3 111 130 130 237

76.1 mm (a) (b) 920

4.01 5.13 5.21 10.51102 130 132 267

3 † (a)920

4.31 5.50 5.13 10.5188.9 110 140 130 267

4 † (a)920

3.81 5.75 5.38 10.51114.3 97 146 137 267

8x

2 (a)920

5.44 6.19 6.25 12.42219.1 60.3 138 157 159 316

2 ½ † (a)920

5.07 6.19 6.19 12.4273.0 129 157 157 316

76.1 mm 9205.25

—6.25 12.42

133 159 316

3 † (a)920

5.31 6.50 6.50 12.4288.9 135 165 165 316

4 † (a)920

4.81 6.75 6.38 12.42114.3 122 172 162 316

** Center of run engaged pipe end for female threaded outlets only (dimensions are approximate) † Available with grooved outlet or female threaded outlet ‡ Center of run to end of fitting # Female threaded outlets are available to NPT and BSPT specifications (a) British Standard female pipe threaded outlet is available (b) For 76.1-mm threaded outlets, specify 2 ½-inch BSPT

Style 920 and Style 920N housings cannot be mated to each other to achieve cross connections.

Y

VT

Y

V

Threaded Outlet

Page 311: Victaulic I-100 Field Installation Handbook.pdf

Always refer to the current Victaulic submittal publication in the G-100 General Catalog or on the website www.victaulic.com for the most up-to-date dimensional information.

Minimum Hole Size

inches/mm

Maximum Hole Size

inches/mm

Minimum Hole Size

inches/mm

Maximum Hole Size

inches/mm

Minimum Hole Size

inches/mm

Maximum Hole Size

inches/mm

All Sizes15⁄16 1 1 3⁄16 1 ¼ 1 ½ 1 9⁄1624 25 30 32 38 40

NOTICE

SizeHole Dimensions

inches/mmNominal

Outlet Sizeinches

Actual mm

Minimum HoleDiameter/Hole

Maximum

Diameter

All ½-inch/21.3 Outlets1 ½ 1 5⁄838 41

All ¾-inch/26.9 Outlets1 ½ 1 5⁄838 41

All 1-inch/33.7 Outlets1 ½ 1 5⁄838 41

All 1 ¼-inch/42.4 Outlets1 ¾ 1 7⁄844 48

All 1 ½-inch/48.3 Outlets2† 2 1⁄851 54

All 2-inch/60.3 Outlets2 ½‡ 2 5⁄864 67

All 2 ½-inch/73.0 Outlets2 ¾ 2 7⁄870 73

All 76.1-mm Outlets2 ¾ 2 7⁄870 73

All 3-inch/88.9 Outlets3 ½ 3 5⁄889 92

All 4-inch/114.3 Outlets4 ½ 4 5⁄8114 118

All 108.0-mm Outlets4 ½ 4 5⁄8114 118

† 2 x 1 ½-inch/60.3 x 48.3-mm Style 920N products require a 1 ¾-inch/44-mm hole.

‡ 8 x 2-inch/219.1 x 60.3-mm Style 920 products require a 2 ¾-inch/70-mm size hole.

Style 920 and Style 920N housings CANNOT be mated to each other to achieve cross connections.

Page 312: Victaulic I-100 Field Installation Handbook.pdf

I-100FIELD INSTALLATION HANDBOOK

VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.

© 2012 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.

VICTAULIC GLOBAL CONTACT INFORMATION

US & WORLD HEADQUARTERS

P.O. Box 31Easton, PA 18044-0031 USA

4901 Kesslersville RoadEaston, PA 18040 USA

1-800-PICK-VIC(+1-800-742-5842)(within North America)+1-610-559-3300+1-610-250-8817 (fax)[email protected]

CANADA

123 Newkirk RoadRichmond Hill, ON L4C 3G5+1-905-884-7444+1-905-884-9774 (fax)[email protected]

CENTRAL AND SOUTH AMERICA

P.O. Box 31Easton, PA 18044-0031 USA

4901 Kesslersville RoadEaston, PA 18040 USA

+1-610-559-3300+1-610-559-3608 (fax)[email protected]

UNITED KINGDOM

Units B1 & B2, SG1 Industrial ParkCockerell CloseGunnels Wood RoadStevenageHertfordshire SG1 2NB (UK)

+44-(0)-1438-310-690+44-(0)-1438-310-699 (fax)0124-60219 (direct to Irelandwithin the UK)[email protected]

EUROPE

Prijkelstraat 369810 Nazareth, Belgium

+32-9-381-15-00+32-9-380-44-38 (fax)[email protected]

MIDDLE EAST

P.O. Box 17683Unit XB 8Jebel Ali Free ZoneDubaiUnited Arab Emirates

+971-4-883-88-70+971-4-883-88-60 (fax)

ASIA

Unit 06-10, Floor 3AA Mansion 291 Fumin RoadShanghai, China 200031

+86-21-6170-1222+86-21-6170-1221 (fax)

[email protected]

AUSTRALIA AND NEW ZEALAND

7 Chambers RoadUnit 1Altona North, VictoriaAustralia 3025

1-300-PIC-VIC(+1-300-742-842)+61-3-9392-4000+61-3-9392-4096 (fax)[email protected]

www.victaulic.com