contentsesd.sidsdock.org/.../financial-complex-audit-report-3.docx · web viewde-scale evaporative...

19
Financial Complex

Upload: lykiet

Post on 13-Apr-2018

216 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Contentsesd.sidsdock.org/.../Financial-Complex-Audit-Report-3.docx · Web viewDe-scale evaporative cooled condensers utilizing specialized chemicals. Air Conditioning 7. Service all

Financial Complex

Page 2: Contentsesd.sidsdock.org/.../Financial-Complex-Audit-Report-3.docx · Web viewDe-scale evaporative cooled condensers utilizing specialized chemicals. Air Conditioning 7. Service all

Contents

Chapter 1 - Executive Summary................................................................... 4

Chapter 2 - Facility Description and Findings............................................. 51. Analysis of consumption and load per end use..................................... 72. Benchmark Analysis ................................................................................ 8

Chapter 3 - Energy Efficiency Measures..................................................... 91. Lights ........................................................................................................ 92. Air Conditioning ....................................................................................... 93. Refrigeration..............................................................................................114. Transformers ............................................................................................115. Roof Radiation...........................................................................................116. Renewable Energy Opportunities ...........................................................127. Energy Efficiency Measures with a Payback Period of less than 1 year.............................................................................................................128. Recommended Investment Package.......................................................13

Page 3: Contentsesd.sidsdock.org/.../Financial-Complex-Audit-Report-3.docx · Web viewDe-scale evaporative cooled condensers utilizing specialized chemicals. Air Conditioning 7. Service all

Chapter 1 - Executive Summary

This building recently constructed includes most of the services of the Ministry of Finance, and also the Trade and Consumers Affairs and the Accountant General. These two institutions have been moved from a former site, and therefore are not taken into consideration in any other energy audit, in spite of the fact that they are included in the list of Facilities to be audited.

A summary table of results of recommended energy conservation measures is shown below.

Principal electricity end uses in the facility are:

- Air conditioning for 58%- Lighting for 29%.

Therefore, it is important that strict attention be paid to ensure operation and maintenance for optimum performance of the systems in use.

Based on the energy audit results, we recommend two types of the Energy efficiency (EE) measures to be implemented in order to reduce energy costs, and enhance occupant comfort:

1. “Low cost” EE measures with a payback period of less than one (1) year from energy and maintenance savings. These measures consist in adopting ‘energy efficient’ behaviour mainly by switching off lighting, computers when they are not in use, and air conditioning when space is not occupied.

2. EE measures with longer payback period and more significant investment cost. These measures require some investment on critical consuming points, such as replacing non-efficient equipment by new ones. In addition, we suggest a few measures to reduce the energy consumption by productive installations.

1 It is important to note that the walk-through-audit aims at identifying general efficiency opportunities and does not provide extensive electrical measurements as a detailed or comprehensive energy audit. Hence, it is recommended that additional measurements and analysis be carried out before any major modification or retrofit.2 Exchange rate: 1 US$ = 2.70 EC$3 The Percent Energy Reduction is only based on the “Recommended Investment Package” which does not include the “Low cost” EE measure and the “Other Projects Under Consideration”

Page 4: Contentsesd.sidsdock.org/.../Financial-Complex-Audit-Report-3.docx · Web viewDe-scale evaporative cooled condensers utilizing specialized chemicals. Air Conditioning 7. Service all

Chapter 2 - Facility Description and Findings

This Financial Complex includes all the offices of the Ministry of Finance, and also the Trade and Consumers Affairs and the Accountant General of the State of St Vincent and the Grenadines. The activities include mainly offices, including the Ministry, but also attendance to the public on the ground floor.

The building, recently built, includes 5 floors.

Principal use: administration offices; attendance of public

Date of construction: recently built; around 1990

Area of occupied floors: 5,074m²

Air conditioned area: 5,074m²

Occupancy: 200 to 300 staff + public

Number of rooms: about 60 offices + large open spaces

Daily Hours in Building:

Page 5: Contentsesd.sidsdock.org/.../Financial-Complex-Audit-Report-3.docx · Web viewDe-scale evaporative cooled condensers utilizing specialized chemicals. Air Conditioning 7. Service all

Structure, walls and slabs are in concrete. Windows are single glazed, in aluminum.

Figure 1: Open spaces in the center of the building Figure 2: Typical office at the building periphery

Figure 3:East side of the building Figure 4: West façade of the complex

Page 6: Contentsesd.sidsdock.org/.../Financial-Complex-Audit-Report-3.docx · Web viewDe-scale evaporative cooled condensers utilizing specialized chemicals. Air Conditioning 7. Service all

Analysis of consumption and load per end use

The breakdown of relative energy demand (kVA), consumption (kWh), and costs, of the electrical end uses are presented hereafter. Based on the energy audit, a breakdown of the annual electricity consumption has been reconstituted and is presented in Table 1 and Figure 5.

This diagram reveals that air conditioning and lighting are the primary electrical end uses, with respectively 58% and 29% of total annual electricity consumption.

Figure 5: Breakdown of Estimated Electricity (kWh/year) End Use

Air conditioning consumption is proportionally high because (i) other uses of energy are quite small, and (ii) the whole building is equipped with AC.

Page 7: Contentsesd.sidsdock.org/.../Financial-Complex-Audit-Report-3.docx · Web viewDe-scale evaporative cooled condensers utilizing specialized chemicals. Air Conditioning 7. Service all

Benchmark Analysis

Table 2 summarizes the historical energy consumption and indicates that the average monthly energy use compared to the recommended benchmark is higher than expected. This results in a consumption increase of 31% above the recommended benchmark. This clearly indicates that there is room for energy efficiency improvement, and effort should be made to implement the optimization measures recommended in this report.

Page 8: Contentsesd.sidsdock.org/.../Financial-Complex-Audit-Report-3.docx · Web viewDe-scale evaporative cooled condensers utilizing specialized chemicals. Air Conditioning 7. Service all

Chapter 3 - Energy Efficiency Measures

Lights

We recommend replacing the existing fluorescent tubes (electro static ballasts) with new tubes equipped with electronic ballasts, having negligible losses. Capacity of new tube will be 32W and 15W tubes equipped with electronic ballasts consuming 25% less. Twenty motion sensors will be installed in meeting rooms and little used space. Estimated saving: 5%

It was also discovered that the switch lines do not currently allow switching on or off some specific lights individually. For instance, in one of the visited offices, switching on the light above the desk automatically switches on the whole meeting room which is next door. Therefore a specific budget is reserved in the investment cost for installing new switch lines wherever necessary.

Lux level was also measured in some points: quite often, the light would have been enough with the window natural lighting, but artificial lighting was switched on. So education and awareness of civil officers will have to be addressed.

Figure 6: Fluorescent tubes and fixtures in one open space and in one office

Air Conditioning

Air conditioning is the largest energy end use. We recommend increasing space cooling thermostat settings to 25º C.

The building is not old, but the AC units are inefficient. The second floor, for instance, They could be replaced with new ones rated at minimum energy efficiency ratio (EER) 13 or Coefficient of Performance (COP) of 3.7, whenever they will have to be replaced.

The second option, recommended, is to install a Chiller, a condenser, on the roof and an air handling unit. Two units, 110T each, are proposed, representing each 60% of the total load which is 183T.

Specifications and economics of the new AC plant are given hereafter:

Page 9: Contentsesd.sidsdock.org/.../Financial-Complex-Audit-Report-3.docx · Web viewDe-scale evaporative cooled condensers utilizing specialized chemicals. Air Conditioning 7. Service all

Figure 7: Air handling unit Figure 8: Aero-condenser on the roof Figure 9: very bad condition of the

exchangers

Page 10: Contentsesd.sidsdock.org/.../Financial-Complex-Audit-Report-3.docx · Web viewDe-scale evaporative cooled condensers utilizing specialized chemicals. Air Conditioning 7. Service all

Refrigeration

To optimize refrigeration system efficiency, we recommend that HCFC and HFC refrigerants should be replaced with Hydrocarbon (HC) Refrigerants.

Transformers

All the transformers should be removed and their resistive consumption will be saved. Their use is not necessary as the computers can be switched from 110 V to 230 V.

Roof Radiation

There are important solar radiations coming from the roof. We recommend installing appropriate roof insulation to decrease the sun radiation coming from the roof and reduce the use of air conditioning.

The existing water proof roofing will be removed from the concrete slab of the flat roof. Thermal insulation (mineral wool or polystyrol) will be implemented on the concrete slab before installing the new roofing.

The simple payback of this EE measure is 2.3 years.

It is important to note that savings obtained from the thermal insulation of the roof depends upon the efficiency of the AC plant. The efficiency of the existing AC plant is so low that 2 times more energy is needed, and therefore savings are twice as high. With the new AC plant, the consumption is divided by 2 and the savings also. But the payback remains very good, at 2.3 years.

Figure 10: Existing roofing is in very bad condition Figure 11: Shading effect on the South façade is very good

Page 11: Contentsesd.sidsdock.org/.../Financial-Complex-Audit-Report-3.docx · Web viewDe-scale evaporative cooled condensers utilizing specialized chemicals. Air Conditioning 7. Service all

Renewable Energy Opportunities

The following measures have to be considered but are not recommended at this time, because of their long payback period.

1. Installation of solar photovoltaic (PV) lighting. Not yet cost effective with an estimated payback period of 12 years. Energy efficiency improvements in lighting and air conditioning should first be applied to enable reducing the investment cost for PV installation. This should be reviewed based on PV price reduction.

2. Solar air conditioning with absorption chiller This is technically viable. However the payback period is beyond the 4-year threshold. Presently this is approximately 11-years.

Energy Efficiency Measures with a Payback Period of less than 1 year

We recommend some immediate measures that would make a positive impact on the energy cost reduction effort, and enhance occupant comfort without major capital expense, with a payback period of less than one (1) year from energy and maintenance savings:

General

1. Reduce “phantom loads” by switching off all office equipment. In this specific case, this measure can bring a lot of savings with no cost.

Lighting

2. Turn off the lights in all unoccupied offices and corridors. Same immediate efficiency as above.

3. Disassemble and clean all lighting diffusers.

4. Measure lighting intensity and reduce fluorescent tube quantity where practical.

Refrigeration

5. Retrofit all refrigeration unit compressors with high efficiency (Frigitech) lubricant if the cost is equal to or less than US$50.00/hp/compressor.

6. De-scale evaporative cooled condensers utilizing specialized chemicals.

Air Conditioning

7. Service all split systems

8. Increase space cooling thermostat settings to 25º C

9. De-scale related evaporative cooled condensers utilizing specialized chemicals.

10. Replace the existing inefficient mini-split AC units with new ones rated at minimum energy efficiency ratio (EER) 13 or Coefficient of Performance (COP) of 3.7 whenever one unit has to be replaced.

Page 12: Contentsesd.sidsdock.org/.../Financial-Complex-Audit-Report-3.docx · Web viewDe-scale evaporative cooled condensers utilizing specialized chemicals. Air Conditioning 7. Service all
Page 13: Contentsesd.sidsdock.org/.../Financial-Complex-Audit-Report-3.docx · Web viewDe-scale evaporative cooled condensers utilizing specialized chemicals. Air Conditioning 7. Service all

Recommended Investment Package

The table 3 summarizes all the effective measures which require a payback period of more than one year. The first part, called “Recommended Investment Package”, relates to the most effective measures. The second part, called “Other Projects under Consideration” is a few optional suggestions.

Page 14: Contentsesd.sidsdock.org/.../Financial-Complex-Audit-Report-3.docx · Web viewDe-scale evaporative cooled condensers utilizing specialized chemicals. Air Conditioning 7. Service all

The figure below illustrates the potential effects of the above-proposed, on energy consumption with the “Total Recommended Investment Package” measures.

Figure 12: Potential Effects of Energy Optimization Projects

Note: Energy consumption of the roof has been extracted from the AC value in order to identify the stake of the thermal insulation.