vlt 5000 devicenet instructions
TRANSCRIPT
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 1/42
1
VLT ® 5000 Series DeviceNet
Table of Contents
Product Overview 2
Message Groups 6
Device Profile 8
Quick Set-up 8
Cable Lengths/Specifications 8
Bus Termination 11
Physical Connection 12
Configuration Switches 13
Object Modeling 15
Response Time 17
Control Word 19
Status Word 21
Parameter Descriptions 24
User Interface (LEDs) 33
Warnings and Alarms 33
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 2/42
2
VLT ® 5000 Series DeviceNet
The option card is designed to communicate
with other nodes using the DeviceNet defined
standard, this facilitates interoperability or the
ability to communicate with other DeviceNet
certified devices.
The option card allows DeviceNet compatible
masters to control, monitor, and supervise the
VLT ® 5000 adjustable frequency drive. The
option is designed to the DeviceNet System
Protocol for Vendors as a slave device.
The application program has the fol lowing
functions:
1. Support interger parameters through
the dual ported RAM.
2. Manipulate the dual ported RAM
parameters to interface with the CAN.
3. Monitor network activity "watchdog"
function to determine Master Slave
communication continuity.
network management master have a significant
influence on how the node functions on the
network
A DeviceNet network can support up to 64
nodes.
Control and supervision of the VLT 5000 will still
be possible through the standard parameter set.
Overall Function
Limitations
User Profile
Product and
Environment The DeviceNet Option Card is an interface
between the DeviceNet serial communication
bus and the VLT ® 5000 adjustable frequency
drive from Danfoss. The option card will function
as an integrated part of the drive.
DeviceNet is a distributed control network. The
DeviceNet protocol is embedded in the controller
option card and is a communication protocol
conforming to the Open DeviceNet Vendor
Association (ODVA) standard.
The option card allows DeviceNet compatible
controllers, sensors, and network management
tools to control, monitor, and supervise the VLT ®
5000 adjustable frequency drive.
A DeviceNet compatible device has the ability
to perform the following operations with the VLT ®
5000 over the DeviceNet network:
1. Control frequency references and send
drive control commands.
2. Monitor the status of the drive, access
alarm and warning messages, and
monitor drive and motor information.
3. Upload and download drive settings,
configure drives, and also perform the
operations defined in 1 and 2.
Therefore, the level of control and flexibility of
the VLT ® 5000 over the network depends on
the capabilities built into the controlling device.
The VLT ® 5000 will function as a slave on the
DeviceNet network. This depends on how the
system is installed. All addressing and linking to
nodes is done at installation time by a network
manager tool. The network installer and the
The end-user is a network manager programmer
or a controller who see the DeviceNet option
card as a transparent bridge to the VLT 5000.
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 3/42
3
VLT ® 5000 Series DeviceNet
The interface connection to the Dev iceNet
network is implemented through a CAN chip.
The two avai lable Unconnected Message
Manager (UCMM) will receive an explicit
message from the master to establish aconnection through the Connection Object
which directly links to the DeviceNet network.
Af te r th is is es tabl ished, another expl ic it
connection and an I/O connection can be
This interface is implemented through the dual
port RAM specified. The DeviceNet protocol shall
be used to interface with the VLT 5000.
No direct data communication interface (e.g. via
a serial port) other than the DeviceNet interface
and the VLT ® 5000 interface is considered.
Interface toDeviceNet Network
established, through the DeviceNet Predefined
Master/Slave Group 2 Message set. Therefore,
the Danfoss VLT ® 5000 DeviceNet option card
will be capable of establishing two UCMM
explicit message connections, one predefinedMaster/Slave explicit message connection
(Group 2 messages), and one I/O polled
connection (Group 2 messages).
Therefore, VLT ® software changes relating to the
communication and dual ported RAM
interfacing will not be required.
Interface toVLT ® 5000Control Card
DataCommunicationInterface
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 4/42
4
VLT ® 5000 Series DeviceNet
Initialization of
VLT ® 5000 Interface
Watch-dogVLT ® 5000Keep-alive Function
Watch-dogDeviceNet OptionCard Keep-alive
Function
Network VariableHandling
The VLT ® 5000 interface is initialized in three
phases. The first two phases are initiated and
controlled by the VLT ® which will write
commands to the option card through the dual
port RAM.
Phase 1:
Is the initialization of the communication system.
During this phase the option card must respond
correctly to the VLT ® 5000 initialization command
or else the VLT ® will not function and display a
"No Option Init" message.
Phase 2:
Is the interface watchdog function performed
by the option card as the first operational action.
After completion of this phase, data can bepassed between the VLT ® 5000 and the option
card through the command channel in the dual
port RAM.
After initialization of the dual port RAM, this
function must be executed periodically within
100 ms. The watchdog message is a command
to one of the control channels of the dual port
After initialization of the dual port RAM, this
function must be executed periodically within
100 ms. The watchdog message is a command
to one of the control channels of the dual port
The parameter access network variable is a
structure containing parameter number, data,
value, and a function code containing a read or
write command. The application program shall
receive the data, validate the data, convert thedata to the format of the VLT ® 5000 dual port
Phase 3:
The VLT ® 5000 will write to the Initialization
Channel of the dual port RAM which will set the
displacement values of the various channels
(Control Channel, Status Channel, CommandChannel 1, Command Channel 2, Command
Channel 3, Warning Channel, and Spontan
Channel), and the DeviceNet option card
software will read these displacements and
return a response to the VLT ® 5000 notifying
that the initialization was successful or an error
was obtained in the process.
During operation (after initialization) the dual port
RAM interface is supervised by a watch-dog in
the VLT ® 5000. The VLT ® 5000 will be kept "alive"
by cyclic writing to a channel in the dual portRAM by the watch-dog handler of the option
card.
RAM. The watchdog message (any command
channel traffic) is withheld from the VLT ® 5000
after the application program has determined
that there is no network connection.
RAM. The watchdog message (any command
channel traffic) is withheld from the VLT ® 5000
after the application program has determined
that there is no network connection.
RAM, process the read or write of the parameter,
then send the information back in an output
network variable of the same structure. This
output variable would contain the parameter
number, error code information in the event of an exception, and parameter value.
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 5/42
5
VLT ® 5000 Series DeviceNet
DeviceNet NetworkManagementFunctions
The Unconnected Message Manager (UCMM)
provides for the dynamic establishment of
Explicit Messaging Connections. The UCMM
is responsible for processing Unconnected
Explicit Requests and Responses. Support of the UCMM requires a device to screen for the
The option card will stop sending a watchdog
signal to the VLT® 5000 when:
[1] The node has been disconnected from the
network.
[2] A network management tool has the option
card go Off-line.
[3] A hardware fault on the DeviceNet Option
Card PCB prevents reliable operation.
By withholding the watchdog message, the
VLT ® 5000 can detect a "Bus Time-out" and
enter secure, pre-defined state.
For recoverable errors such as [1] and [2] the
option card shall re-send the watchdog
message when the fault or condition has
disappeared such as after re-connection of the
node to the network.
DeviceNet is a low-level network that
standardizes communications between
industrial devices (sensors, limit switches) and
high level devices (controllers). The
communication network can be peer to peer
or master/slave. DeviceNet uses CAN
technology for Media Access Control and
Physical Signaling and it supports up to 64
nodes. DeviceNet also defines device profiles
for devices belonging to specific classes. For
other devices, a custom class must be defined
in order to make it DeviceNet compatible. Thisfurther enhances the interchangeability and
interoperability of the network. Each node on
the network has its own unique media access
control identifier (MAC ID) to distinguish it on
the network. The MAC ID is stored in the header
of the message which is split into four different
message groups. However, DeviceNet only
makes use of three message groups keeping
the fourth one for future use. If two nodes
attempt to get control of the network bus
simultaneously, the CAN protocol resolves the
issue by arbitration. A dominant bit (0) will winarbitration over a recessive bit (1).
Unconnected Explicit Request Message CAN
Identifier from all possible Source MAC IDs. If a
device transmits Unconnected Explicit Request
Messages it must also screen for the
Unconnected Explicit Response CAN Identifierfrom all possible Source MAC IDs.
For unrecoverable errors such as [3] the
application program shall permit logging of
network errors without resetting or restarting the
microprocessor. This will send information to a
network management tool that will allow
appropriate actions to be taken. The only way
to recover from a serious error is to re-initialize
the VLT ®
5000/DeviceNet option card by cyclingpower.
In case of serious VLT ® 5000 fault, the 68HC11
shall hold the CAN chip reset, thereby disabling
any communication to the node until the VLT ®
5000 has been re-initialized.
For the VLT ® 5000 adjustable frequency drive,
the option card will be slave node on the
DeviceNet network. The option card will be a
message server that will request and set
parameters in the VLT via a dual ported RAM
interface. The option card has an embedded
CAN controller that will screen all network
messages with a Mask and Match register. This
feature allows the option card to filter out any
unwanted messages from the network. The
option card will receive group 2 and group 3
messages. Group 2 messages allows the optioncard to use the predefined Master/Slave
connection set which identifies a use for all group
2 message identifiers. The ability to receive Group
3 messages allows the option card to also be an
Unconnected Explicit Message Manager
(UCMM) with the UCMM request and response
message identifier. Explicit message connections
are unconditionally point-to-point. Point-to-point
connections exist between two devices only.
Error Handling
Overall Function
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 6/42
6
VLT ® 5000 Series DeviceNet
The following table describes each message group and their identifier bits. The table doesn't
detail each message identifier for each of the groups.
Identifier Bits Identity Usage Hex Range
10 9 8 7 6 5 4 3 2 1 0
0 Message ID Source MAC ID Message Group 1 000 - 3FF
1 0 MAC ID Mess ID Message Group 2 400 - 5FF
1 1 Mess ID Source MAC ID Message Group 3 600 - 7BF
1 1 1 1 1 Message ID Message Group 4 (Reserved for future use) 7C0 - 7Ef
10 1 1 1 1 1 1 x x x x Invalid CAN identifiers 7F0 - 7FF
in group 1 have highest priority and the
messages in group 4 have the lowest priority.
Group 4 messages are not used at this time by
DeviceNet devices.
most significant bit is always a 0 for group 1
messages making group 1 messages the
highest priority. The group 1 message always
contains the source MAC ID.
Message ID 7 is reserved for the duplicate MACID check. When a connection is established
across group 2, the end point determines if the
source or destination MAC ID should be
specified.
Message ID 6 is used when sending
unconnected explicit messaging requests.
Message ID 6 is used when sending
unconnected explicit messaging requests.
Message ID is invalid and not used.
transmits UCMM it must also screen for the
UCMM response CAN identifier from group 3
messages with message ID 5. Only group 3
messages are capable of receiving or
transmitting UCMM messages.
DeviceNet establishes four message groups
using the 11 bit CAN identifier field. Each
message group has a hex range which also gives
the message its priority on the bus. Messages
DeviceNet does not predefine any use for group
1 messages. Group 1 messages with a lower
message ID will have higher priority than a
message with a greater message ID. The valid
range for group 1 messages is 000 - 3ff, the
Group 2 messages have a range of 400 - 5ff. The two most sign if ican t bi ts in group 2
messages are always 1 and 0. Group 2
messages with message ID 6 and 7 are
predefined. Message ID 6 is reserved for the
master/slave connection management.
Group 3 messages have a range of 600 - 7bf.
Group 3 with messages ID 5, 6 and 7 are
predefined messages. Group 3 message ID 5
is used when sending responses associated with
unconnected explicit messaging requests.
Reserved for future use.
The Unconnected Explicit Message Manager
(UCMM) is responsible for processing UCMM
requests and responses. Support of the UCMM
requires a device to screen for group 3
messages with message ID 6. If a device
Message Groups
Message Group 1
Message Group 2
Message Group 3
Message Group 4
UCMM
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 7/42
7
VLT ® 5000 Series DeviceNet
The Predefined Master/Slave Connection Set Identifier Fields for Group 2 Messages The CAN Identifier Fields associated with the Predefined Master/Slave Connection Set for a group
2 message server are shown in the following table.
Identifier Bits Identity Usage Hex Range
10 9 8 7 6 5 4 3 2 1 0 Group 2 Messages 400 - 5FF
1 0 Source MAC ID 0 0 0 Master's I/O Bit Strobe Command Message
1 0 Source MAC ID 0 0 1 Reserved
1 0 Dest MAC ID 0 1 0 Master's Change of State or Cyclic Acknowledge Message
1 0 Source MAC ID 0 1 1 Slave's Explicit Response Message
1 0 Dest MAC ID 1 0 0 Master's Explicit Request Messages
1 0 Dest MAC ID 1 0 1 Master's I/O Poll Command/Change of State/Cyclic Message
1 0 Dest MAC ID 1 1 0 Group 2 only Unconnected Explicit Request Messages
1 0 Dest MAC ID 1 1 1 Duplicate MAC ID Check Messages
The UCMM Message Group The CAN identifier fields for a UCMM capable device are shown below.
Identifier Bits Identity Usage Hex Range
10 9 8 7 6 5 4 3 2 1 0 Group 3 Messages 600 - 7BF
1 0 Msg ID Source MAC ID Group 3 Messages
1 1 0 0 0 Source MAC ID Undefined
1 1 0 0 1 Source MAC ID Undefined
1 1 0 1 0 Source MAC ID Undefined
1 1 0 1 1 Source MAC ID Undefined
1 1 1 0 0 Source MAC ID Undefined
1 1 1 0 1 Source MAC ID Unconnected Explicit Response Message
1 1 1 1 0 Source MAC ID Unconnected Explicit Request Message
1 1 1 1 1 Source MAC ID
The Poll Predefined Master/Slave Identifier Fields The predefined produced connection id and consumed connection id for a Poll I/O message is
shown below.
Identifier Bits Identity Usage Hex Range
10 9 8 7 6 5 4 3 2 1 0
0 Msg ID Source MAC ID Group 1 Message 000 - 3FF
0 1 1 1 1 Slave's MAC ID Slave's I/O Poll Response Message 3C0 - 3FF
1 0 MAC ID Msg ID Group 2 Message 400 - 5FF
1 0 Slave's MAC ID 1 0 1 Master's I/O Poll Command Message 405 - 5FD
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 8/42
8
VLT ® 5000 Series DeviceNet
#1 Vendor
#2 Device Type
#3 Product Code
#4 Revision - Major, Minor
#5 Status #6 Serial number
#7 Product Name
This object requires no class attr ibutes. Its
instance attributes are the following:
#1 Object List - Number of Classes
Parameter 918:
Set the VLT MAC I.D. from 0 to 63, - one unique
address per VLT.
Parameter 801:
Set the transmission speed in bit/sec. The
default setting is 125 kHz, which means the VLT
automatically detects the transmission speed
of the connected bus. If you set a fixed value it
must be the same as that selected in the master.
Identity Object
Class ID 01hex
This object is used to provide identification and
general information about the device. This object
is required by all DeviceNet products.
This object requires no class attributes. Itsinstance attributes are the following:
The Me ssa ge Ro uter obj ect prov ides a
messaging connection point through which a
Client may address a service to any object class
or instance residing in the physical device.
For how to program the ordinary VLT parameters
refer to the VLT 5000 Series Instruction Manual.
Communication is established by setting the
following parameters:
Parameter 904:
Select the I/O Instance to be applied.
Parameter 502 = "BUS".
Otherwise terminals 12 and 27 of the control
card must be connected, before motor start. In
parameters 502-508 it is possible to define how
to gate the control commands from the
DeviceNet with the equivalent control commands
of the digital inputs.
Message Router
Class ID 02hex
General Information
Quick Setup
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 9/42
9
VLT ® 5000 Series DeviceNet
Cable Lengths Data Rate Trunk Distance Drop Length
Maximum Cumulative
125k baud 500 meters (1640 ft.) 156 meters (512 ft.)
250k baud 250 meters (820 ft.) 6 meters (20 ft.) 78 meters (256 ft.)
500k baud 100 meters (328 ft.) 39 meters (128 ft.)
Physical Characteristics Specification
Two shielded pairs Common axis with drain wire in center
Overall braid shield 65% coverage 36 AWG Cu braid. (individually tinned)
Drain wire #18 (19 x 30 AWG) Copper (individually tinned)
Outside diameter 0.475 ±0.015 inches (round),
roundness - radius delta to be within 15% of 0.5 O.D.*
Jacket insulation * 0.040 inches minimum
Jacket marking Vendor Name & Part # 1 Pr 18 and 1 Pr 15 AWG shielded.
additional markings are acceptable
Electrical Characteristics Specification
DCR (braid+tape+drain) 1.75 Ohms/1000 ft. (nom. @ 20°C)
Applicable Environmental SpecificationCharacteristics
Agency Certifications NEC (UL) type, CL2/CL3 (min.)
(u.s. and Canada)
Bend radius - installation / fixed 20 x diameter / 7 x diameter
Operating ambient temperature 20° to +60°C @ 8 amps; de-rate current linearly to
zero @ 80°C
Storage temperature 40° to +85°C
Pull tension 190 lbs max
Cable Specifications
* Other types of jacket insulation are allowable provided that internal construction and electrical
characteristics adhere to this specification.
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 10/42
10
VLT ® 5000 Series DeviceNet
Drain Wire
DC Power InsulationColor: Black
AL/MYShield
DC Power InsulationColor: Red
Jacket
Data InsulationColor: White
Braid Shield
AL/MYShield
Data InsulationColor: Blue
Cable Cross Section
The screen of the DeviceNet cable must always
be connected to ground at both ends, that
means the screen must be connected to ground
in all stations connected to the DeviceNet
network. It is very important to have a low
impedance ground connection of the screen,
also at high frequencies. This can be obtained
by connecting the surface of the screen to
ground, for example by means of a cable clamp
or a conductive cable gland.
VLT 5000 Ser ies is provided with different
clamps and brackets to enable a proper ground
connection of the DeviceNet cable screen. The
screen connection is shown in the drawing.
It is important that all stations connected to the
DeviceNet network are connected to the same
earth potential. The earth connection must have
a low HF (high frequency) impedance. This canbe achieved by connecting a large surface area
of the cabinet to ground, for example by
mounting the VLT 5000 Series on a conductive
rear plate.
Especially when having long distances between
the stations in a DeviceNet network it can be
necessary to use additional potential equalizing
cables, connecting the individual stations to thesame earth potential.
Connection of theCable Screen
Earth Connection
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 11/42
11
VLT ® 5000 Series DeviceNet
It is essential that the bus line be terminated
properly. A mismatch of impedance may result
in reflections on the line that will corrupt data
transmission.
The DeviceNet Option Card is provided with a
pluggable screw connector.
By using a pluggable screw connector as a
splice between two trunk lines, removal of
devices will not sever the network.
Bus Termination Strain relief, if required, must be provided by
the developer. In current installations of this type
of connector, the strain relief is attached to the
product.
NOTE:
Wires should not be installed while the network
is active. This will prevent problems such as
shorting the network supply or disrupting
communications.
1
2
3
4
5
6
78
ON
5
V +
4
C A
N _ H
3
d r ai n
2
C A
N _ L
1
V –
r e d
w h i t e
b ar e
b l u e
b l a c k
1
2
3
4
5
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 12/42
12
VLT ® 5000 Series DeviceNet
Physical Connection EMC precautions
The fo ll owi ng EMC prec aut ions are
recommended to obtain interference free
operation of the DeviceNet network. Additional
information on EMC can be found in the VLT 5000 Series Instruction Manual.
NOTE:
Relevant national and local regulations, for
example regarding protective earth connection,
must be observed.
If the DeviceNet cable has to cross a motor and
brake resistor cable they must cross each other
at an angle of 90°.
Cable Routing
PLC etc. Panel
PLC
VLT 5000
Output
Contactor
etc.
Cable insulation
stripped
All cable entries in
one side of panel
Motor Cable
AC Line
l1
l2l3
PE
Control Cables
Motor
Ground Rail
Equalizing Cable
PG Cable Gland
The DeviceNet Option Card is connected to the
bus line via MK 1A or 1B, terminals 62 and 63.
It is recommended to use a master with galvanic
isolated bus driver and with over voltageprotection (e.g. zenerdiode).
The DeviceNet communication cable must be
kept away from motor and brake resistor cables
to avoid coupling of high frequency noise from
one cable to the other. Normally a distance of 8inches (200 mm) is sufficient, but it is generally
recommended to keep the greatest possible
distance between the cables, especially where
cables are running in parallel over long
distances.
Min. 8 inches
between
control cable
and line cable
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 13/42
13
VLT ® 5000 Series DeviceNet
ATTENTION:When you make changes to the switch settings, use a pointed instrument such
as a ball point pen. DO NOT use a pencil because damage may occur.
ATTENTION:Unpredictable operation may occur if you fail to check connections and DIP switch
settings for compatibility with your application. Unpredictable operation may resultin death, personal injury, and equipment damage.
ATTENTION:Hazard of injury or equipment damage may occur due to unintended or incorrectmachine motion. When a system is configured for the first time, the motor must
be disconnected from the machine or process during initial system testing.
NOTE: When setting the Communication Module's addressing Dip Switches, you must ensurethat each serial device on the network has a unique address. Also, all devices connected tothe network must be set at the same baud rate.
UnderstandingModuleConfigurationSwitches
The DeviceNet Communication module's DIPswitch settings determine:
DeviceNet node address
DeviceNet baud rate
1 2 3 4 5 6 7 8
ON
DIP Switch
Factory Settings
ON = 0
OFF = 1
1
2
3
4
5
6
7
8
ON
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 14/42
14
VLT ® 5000 Series DeviceNet
Settingthe DeviceNetNode Address
Dip switches 6 through 1 set the module's nodeaddress using binary addressing.
Follow these steps to set the DeviceNet nodeaddress:1. Refer to the table below for the switch
settings of a specific address.
2. Using your finger or a pointed object, slideswitches 6 through 1 to the appropriate
ON/ OFF positions.
DeviceNet Switch DeviceNet Switch DeviceNet Switch DeviceNet SwitchAddress Settings Address Settings Address Settings Address Settings
6 <— 1 6 <— 1 6 <— 1 6 <— 1
0 000000 16 010000 32 100000 48 110000
1 000001 17 010001 33 100001 49 110001
2 000010 18 010010 34 100010 50 110010
3 000011 19 010011 35 100011 51 110011
4 000100 20 010100 36 100100 52 110100
5 000101 21 010101 37 100101 53 110101
6 000110 22 010110 38 100110 54 110110
7 000111 23 010111 39 100111 55 1101118 001000 24 011000 40 101000 56 111000
9 001001 25 011001 41 101001 57 111001
10 001010 26 011010 42 101010 58 111010
11 001011 27 011011 43 101011 59 111011
12 001100 28 011100 44 101100 60 111100
13 001101 29 011101 45 101101 61 111101
14 001110 30 011110 46 101110 62 111110
15 001111 31 011111 47 101111 63 111111
Switch SettingsforDeviceNetNode Addressing
1 2 3 4 5 6 7 8
ON
ON = 0
OFF = 1
DeviceNet Address
000000 - 111111 (0 to 63)
1 2 3 4 5 6 7 8
ON
Use DIP Switchsettings 8 and 7 for
setting the DeviceNet
Baud Rate.
ON = 0
OFF = 1
Setting theBaud Rate
Dip switches 7 and 8 set the baud rate at whichthe Communication Module communicates onthe network.The factory default setting is 125K BPS.
Switch Settings forDeviceNet Module Baud Rate
Baud Switch Switch
Rate Setting Setting8 7
125 kBPS 0 0
250 kBPS 0 1
500 kBPS 1 0
125 kBPS 1 1
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 15/42
15
VLT ® 5000 Series DeviceNet
Object Modeling DeviceNet is defined using object modeling.Object modeling organizes data and proceduresinto one entity: the object.
An object is a collection of related services andattributes. Services are procedures an objectperforms. Attributes are characteristics ofobjects represented by values, which can vary.Typically, attributes provide status informationor govern the operation of an object. The valueassociated with an attribute may or may notaffect the behavior of an object. An object'sbehavior is an indication of how the objectresponds to particular events.
Classes categorize objects. A class defines a
particular type of object and defines thecharacteristics shared by all the objects withina class. For example, the human race could berepresented by the class "Human" with millionsof objects within it.
Objects within a class are called objectinstances. An object instance is the actualrepresentation of a particular object within aclass. Each instance of a class has the same
set of attributes, but has its own set ofattribute values, which makes each instancein the class unique.
Every person in the human race can berepresented by an instance within the class"Human." All humans have the same set ofattributes; eyes, ears age, gender, etc. Yet,because the values of each attribute vary,each of us looks different and performs indistinct ways.
Class Instances Attributes Attribute values
Human Mary Sex Female
Age 31
Joe Sex Male
Age 50
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 16/42
16
VLT ® 5000 Series DeviceNet
A DeviceNet node is modeled as a collection ofobjects. The realization of this abstract objectmodel within a product depends on theimplementation. In other words, a procust
internally maps this object model in a fashionspecific to its implementation.
A Class of Objects within a DeviceNet Node
Each object instance of a Class in aDeviceNet node has the same set ofattributes, but has its own particular set ofattribute values. The figure illustrates, multiple
object instances within a particular class canreside in a DeviceNet node.
DeviceNet Node
Object Instances
A Class of
Objects
Term DefinitionObject An abstract representation of a particular component within a product.Class A set of objects that all represent the same kind of system component. A class isa generalization of an object. All objects in a class are identical in form and behavior,
but may contain different attribute values.Instance A specific and real (physical) occurrence of an object. For example: California isan instance of the object class State. The terms object, instance, and object instance
all refer to a specific Instance.
Attribute A description of an externally visible characteristic or feature of an object. Typically,attributes provide status information or govern the operation of an object. Attributesmay or may not affect the behavior of an object. For example: the ASCII name of
an object; and the repetition rate of a cyclic object.Behavior A specification of how an object acts. Actions result from different events the
object is aware of, such as receiving service requests, detecting internal faults, or elapsingtimers.
Service A function supported by an object and/or object class. DeviceNet defines a set ofcommon services and provides for the definition of object class-specific services.Object-specific services are those which are defined by a particular object class
to perform a required function NOT covered by a common service.
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 17/42
17
VLT ® 5000 Series DeviceNet
VLT ResponseTime
The update time via the DeviceNet connectioncan be divided into two parts:1) The communication time, which is the time it
takes to transmit data from the master to the
slave (VLT with DeviceNet option).2) The internal update time, which is the time it
takes to transmit data between the VLT 5000control card and the DeviceNet option card.
Communication time (tcom
) depends on the actualtransmission speed (baudrate) and the type ofmaster in use. More data or lower transmissionspeed will increase the communication time.
UpdateData time, t
int
Control word/Main reference(part of PPO) 2 msec
Status word/Actual output frequency(part of PPO) 2 msec
Parameter read via PCD-part of PPO
Parameter write via PCD-part of PPO
Parameter read via PCV-part of PPOor FMS read service
Parameter write via PCV-part of PPOor FMS write service
VLT 5000
Control
card
DeviceNet
Option
Master
t int.
t com.
The internal update time (tint
) depends on thetype of data in question as there are differentchannels for the data transfer where time
critical data e.g. control word has highest
priority. The internal update time for thedifferent types of data are stated below.
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 18/42
18
VLT ® 5000 Series DeviceNet
902
900
901
903
20
100
101
102
70
150
151
152
WRITE READValue Decimal Decimal
SPEED
ST AC RefCTW REF
REFCTW 915,1 915,2
915,1 915,2 915,3 915,4
General PurposeDiscrete I/O
The General Purpose Discrete I/O device I/O assemblies consist of:
five predefined input assemblies with single status bits
one product–specific input assembly with a single status bit
five predefine input assemblies with multiple status bits one product–specific input assembly with multiple status bits
five predefined output assemblies
one product–specific output assembly
The I/O Assembly Instance definitions in thissection define the format of the "data" attribute(attribute 3) for I/O Assembly Instances. I/OAssemblies support a hierarchy of motor control
devices. The device hierarchy includes motorstarters, soft starters, AC and DC drives, andservo drives. Assembly Instances are numberedwithin the hierarchy so that each device type isassigned a range of Assembly Instance
numbers, with higher functionality devicessupporting higher instance numbers. Devicesin the hierarchy can choose to supportinstance numbers that are lower than theirs
in the hierarchy. For example an AC drivemay choose to support some I/O Assembliesin the starter profile to make it easier tointerchange starters and drives within thesystem.
General PurposeAnalog I/O
I/O Assembly
Instances
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 19/42
19
VLT ® 5000 Series DeviceNet
Control word as per Profidrive standard(parameter 512 = PROFIDRIVE)The control word is used for transmittingcommands from a master (e.g. a PC) to a slave
(VLT 5000 Series).
Master Slave
Bit Bit = 0 Bit = 1
00 OFF 1 ON 1
01 OFF 2 ON 2
02 OFF 3 ON 3
03 Motor coasting Enable
04 Quick-stop Ramp05 Freeze output frequency Ramp enable
06 Ramp stop Start
07 No function Reset
08 Jog 1 OFF ON
09 Jog 2 OFF ON
10 Data not valid Valid
11 No function Slow down
12 No function Catch
13 Choice of Setup 1 (lsb)
14 Choice of Setup 2 (msb)
15 No function Reversing
Bit 00, OFF1/ON1:An ordinary ramp stop which uses the ramptime in parameters 207/208 or 209/210. Bit00 = "0" leads to a stop and leads to output
relay 01 or 04 being activated, the outputfrequency is 0 Hz, provided Relay 123 hasbeen selected in parameter 323 or 326. Bit00 = "1" means that the adjustable frequencydrive will be able to start if the other conditionsfor starting have been fulfilled.
Bit 01, OFF2/ON2:Coasting stop. Bit 01 = "0" leads to a coastingstop and leads to output relay 01 or 04 beingactivated, when the output frequency is 0 Hz,provided Relay 123 has been selected in
parameter 323 or 326. Bit 01 = "1" meansthat the adjustable frequency drive is able tostart provided the other conditions for startingare fulfilled.
Bit 02, OFF3/ON3:Quick-stop, which uses the ramp time set inparameter 212. Bit 02 = "0" leads to a quickstop and leads to output relay 01 or 04 beingactivated, when the output frequency is 0 Hz,provided Relay 123 has been selected inparameter 323 or 326. Bit 02 = "1" meansthat the adjustable frequency drive is able to
start, provided the other conditions forstarting are fulfilled.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit no.
Controlword
Busreference
Control Word
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 20/42
20
VLT ® 5000 Series DeviceNet
Bit 03, Coasting/enable:Coasting stop. Bit 03 = "0" leads to a stop. Bit03 = "1" means that the adjustable frequencydrive is able to stop, provided the other
conditions for starting are fulfilled. Note: inparameter 502 the choice is made as to how bit03 is to be combined (gated) with thecorresponding function in the digital inputs.
Bit 04, Quick-stop/ramp:Quick-stop which uses the ramp time inparameter 212. Bit 04 = "0" leads to a quick-stop. Bit 04 = "1" means that the adjustablefrequency drive is able to start, provided the otherconditions for starting are fulfilled. Note: Inparameter 503 the choice is made as to how dit
o4 is to be combined (gated) with thecorresponding function on the digital inputs.
Bit 05, Freeze output frequency/ramp enable:Bit 05 = "0" means that the given outputfrequency is maintained even if the reference ischanged. Bit 05 = "1" means that the adjustablefrequency drive is again able to regulate, andthe given reference is followed.
Bit 06, Ramp stop/start:An ordinary ramp stop that uses the ramp timein parameters 207/208 or 209/210; in addition,
output relay 01 or 04 will be activated when theoutput frequency is ) Hz, provided Relay 123 hasbeen selected in parameter 323 or 326. Bit 06= "0" leads to a stop. Bit 06 = '1" means theadjustable frequency drive is able to start,provided the other conditions for starting arefulfilled. In parameter 505 the choice is made as
to how bit 06 is to be combined (gated) with thecorresponding function on the digital inputs.
Bit 07, No function/resetReset of trip. Bit 07 = "0" means that there is no
reset. Bit 07 = "1" means that a trip is reset.
Bit 08, Jog 1 OFF/ON:Activation of pre-programmed speed inparameter 509 (Bus Jog 1). JOG 1 is onlypossible when Bit 04 = "0" and bit 00-03 = "1".
Bit 09, Jog 2 OFF/ON:Activation of pre-programmed speed inparameter 510 (Bus Jog 2). JOG 2 is onlypossible when Bit 04 = "0" and bits 00-03 ="1". If both JOG 1 and JOG 2 are activated (bits
08 and 09 = "1"), JOG 1 has the higher priority,which means that the speed programmed inparameter 509 will be used.
Bit 10, Data not valid/valid:Used for telling VLT 5000 whether the controlword is to be used or ignored. Bit 10 = "0"means that the control word is ignored. Bit
10 = "1" means that the control word is used.This function is relevant because the controlword is always contained in the telegram,regardless of the type of telegram used, i.e.it is possible to disconnect the control wordif it is not to be used in connection withupdating or reading of parameters.
Bit 11, No function/slow down:Used for reducing the speed reference by thevalue in parameter 219. Bit 11 = "0" meansthat there is no change of the reference. Bit
11 = "1" means that the reference is reduced.
Bit 12, No function/catch-up:Used for increasing the speed reference bythe value of parameter 219. Bit 12 = "0"means that the reference is increased. If bothslow down and catch-up are activated (bits11 and 12 = "1"), slow down has the higherpriority, i.e. the speed reference is reduced.
Bits 13/14, Choice of Setup:Bits 13 and 14 are used for choosing amongthe four menu Setups in accordance with:
Setup Bit 14 Bit 13
1 0 0
2 0 1
3 1 0
4 1 1
This function is only possible if Multi-Setupshave been selected in parameter 004.
NOTE: Parameter 507 is used for choosinghow bits 13/14 are to be combined (gated)with the corresponding function on the digitalinputs.
Bit 15, No function/reversing:
Reversing of the direction of rotation of themotor. Bit 15 = "0" leads to no reversing, bit15 = "1" leads to reversing.
Note that as a point of departure reversinghas been selected as Digital in parameter 506.Bit 15 only leads to reversing if bus , logical
or or logical and has been selected (logical
and , however, only together with terminal 19).
NOTE: Unless otherwise mentioned, the
control word bit is combined (gated) with thecorresponding function on the digital inputsas a logical "or" function.
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 21/42
21
VLT ® 5000 Series DeviceNet
Status word (according to Profidrive standard)(parameter 512 = PROFIDRIVE)The status word is used for informing the master(e.g. a PC) of the condition of a slave (VLT 5000
Series).Slave Master
Bit Bit = 0 Bit = 1
00 Control not ready Ready
01 VLT not ready Ready
02 Motor coasting Enable
03 No fault Trip
04 ON 2 OFF 2
05 ON 3 OFF 3
06 Start enable Start disable
07 No warning Warning
08 Speed • reference Speed = ref.
09 Local control Bus control
10 Out of operating range Freq. limit OK
11 Not running Running
12 VLT OK Stalls, auto-start
13 Voltage OK Above limit
14 Torque OK Above limit
15 Timer OK Above limit
Bit 00, Control not ready/ready:Bit 00 = "0" means that bit 00, 01 or 02 of thecontrol word is "0" (OFF1, OFF2 or OFF3), orthat the adjustable frequency drive has tripped.Bit 00 = "1" means that the adjustable frequencydrive is ready, but that there is not necessarilyany supply to the power component (in case ofexternal 24 V supply to the controls).
Bit 01, VLT not ready/ready:Same meaning as bit 00; however, there is alsoa supply to the mains component, and theadjustable frequency drive is ready to run whenit receives the necessary start signals.
Bit 02, Coasting/enable:Bit 02 = "0" means that the control word bit 00,02 or 03 is "0" (OFF1, OFF2, OFF3 or Coasting),or the VLT 5000 Series unit has tripped. Bit 02= "1" means that the control word bits 00, 01,
02 or 03 are "1" and that VLT 5000 Series hasnot tripped.
Bit 03, No fault/trip:
Bit 03 = "0" means that VLT 5000 Series is not
in a fault condition. Bit 03 = "1" means that VLT5000 Series has tripped and needs a reset signalin order to run.
Bit 04, ON2/OFF2:Bit 04 ="0" means that control word bit 01 ="1".Bit 04 ="1" means that control word bit 01 ="0".
Bit 05, ON3/OFF3:Bit 05 ="0" means that control word bit 02 ="1".Bit 05 -"1" means that control word bit 02 ="0".
Bit 06, Start enable/start disable:Bit 06 is always "0" if Danfoss has beenselected in parameter 512. If Profidrive hasbeen selected in parameter 512, bit 06 willbe "1" after reset of a trip, after activation ofOFF2 or OFF3 and after connection of mainsvoltage. Start disable is reset, setting controlword bit 00 to "0" and bits 01, 02 and 10 to
"1".
Bit 07, No warning/warning:Bit 07 = "0" means that there is no unusualsituation. Bit 07 = "1" means that an abnormalcondition has arisen for the VLT 5000 Series.All warnings described in the VLT 5000instruction manual will set bit 07 to "1".
Bit 08, Speed • ref/speed. = ref.:Bit 08 = "0" means that the actual motorspeed is different from the speed referenceset. This can be the case while the speed is
ramped up/down during start/stop. Bit 08 ="1" means that the present motor speedequals the speed reference set.
Bit 09, Local control/Bus control:Bit 09 = "0" means that VLT 5000 Series hasbeen stopped by means of the stop key onthe control panel, or that Local operation hasbeen selected in parameter 002. Bit 09 = "1"means that it is possible to control theadjustable frequency drive via the serial port.
Bit 10, Out of operating range/Freq. limit OK:Bit 10 = "0" means that the output frequencyis out of the range set in parameter 225(Warning: Low frequency) and parameter 226(Warning: High frequency). Bit 10 = "1" meansthat the output frequency lies within thementioned range.
Bit 11, Does not run/runs:Bit 11 = "0" means that the motor is notrunning. Bit 11 = "1" means that VLT 5000Series has a start signal of that the outputfrequency is greater than 0 Hz.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit no.
Statusword
Outputfrequency
Status Word
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 22/42
22
VLT ® 5000 Series DeviceNet
Bit 12, VLT OK/stalling, autostart:Bit 12 = "0" means that there is no temporaryovertemperature on the inverter. Bit 12 = '1"means that the inverter has stopped becauseof overtemperature, but that the unit has nottripped and will continue, once theovertemperature stops.
Bit 13, Voltage OK/above limit:Bit 13 = "0" means that the voltage limits of VLT
5000 Series have not been exceeded. Bit 13 ="1" means that the DC voltage of the VLT 5000Series intermediate circuit is too low or too high.
Control word under VLT standard (parameter
512 = DANFOSS)The control word is used for sending commandsfrom a master (e.g. a PC) to a slave (VLT 5000Series).
Master Slave
Bit Bit = 0 Bit = 1
00 Preset reference choice lsb
01 Preset reference choice msb02 DC brake Ramp
03 Coasting Enable
04 Quick-stop Ramp
05 Hold Ramp enable
06 Ramp stop Start
07 No function Reset
08 No function Jog
09 Ramp 1 Ramp 2
10 Data not valid Valid
11 No function Relay 01 activated
12 No function Relay 04 activated
13 Choice of Setup lsb14 Choice of Setup msb
15 No function Reversing
Bit 00/01:Bits 00 and 01 are used for choosing amongthe four pre-programmed references(parameters 215-218) in accordance with thefollowing table:Preset ref. Parameter Bit 01 Bit 00
1 215 0 0
2 216 0 1
3 217 1 0
4 218 1 1
Bit 14, Torque OK/above limit:Bit 14 = "0" means that the motor current islower than the torque limit selected inparameter 221. Bit 14 = "1" means that the
torque limit in parameter 221 has beenexceeded.
Bit 15, Timers OK/above limit:Bit 15 = "0" means that the timers for themotor thermal protection and VLT thermalprotection, respectively, have not exceeded100%. Bit 15 = "1" means that one of thetimers has exceeded 100%.
NOTE: Parameter 508 is where to choose theway bits 1/12 are to be combined (gated) withthe corresponding function on the digitalinputs.
Bit 02, DC Brake:Bit 02 = "0" leads to DC braking and stop.Braking current and duration are set inparameters 125 and 126. Bit 02 = "1" leadsto ramping.
Bit 08, Activation of Jog speed in parameter213:
Bit 08 = "0": Jog speed not activated. Bit 08= "1" means that the motor is running at Jogspeed.
Bit 09, Choice of ramp 1/2:Bit 09 = "0" means that ramp 1 is active(parameters 207/208). Bit 09 = "1" means that
ramp 2 (parameters 209/210) is active.
Bit 11, Relay 01:Bit 11 = "0": Relay 01 not activated. Bit 11 =1: Relay 01 activated, provided Control word
bit has been chosen in parameter 323.
Bit 12, Relay 04:Bit 12 = "0": Relay 04 has not been activated.Bit 12 = "1": Relay 04 has been activated,provided Control word bit has been chosen inparameter 326>
See the description of other bits under controlword for Profidrive standard.
NOTE: Unless otherwise mentioned, the
control word bit is combined (gated) with the
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit no.
Controlword
Busreference
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 23/42
23
VLT ® 5000 Series DeviceNet
Status word under VLT standard (parameter 512= DANFOSS)The status word is used for informing the master(e.g. a PC) about the condition of the slave (VLT5000 Series).
Slave Master
Bit Bit = 0 Bit = 1
00 Control not ready Ready
01 VLT not ready Ready
02 Coasting Enable
03 No fault Trip
04 Reserved
05 Reserved
06 Reserved
07 No warning Warning
08 Speed • reference Speed = ref.
09 Local control Bus control
10 Out of range Frequency OK
11 Not running Running
12 VLT OK Stalling, auto-start
13 Voltage OK Above limit
14 Torque OK Above limit
15 Timer OK Above limit
Bit 00, Control not ready/ready:Bit 00 = "0" means that the adjustable frequencydrive has tripped.Bit 00 = "1" means that the adjustable frequencydrive controls are ready, but the power
component is not necessarily receiving anypower supply (in case of external 24 V supply tocontrols).
Bit 02, Coasting/enable:Bit 02 = "0" means that the control word bit 03
is "0" (Coasting) or that VLT 5000 Series hastripped.Bit 02 = "1" means that control word bit 03 is"1" and that VLT 5000 Series has not tripped.
See the description of other bits under statusword for the Profidrive standard.
Bus reference value:
Master Slave
The frequency reference value is transmittedto the adjustable frequency drive in the formof a 16-bit word. The value is transmitted as
a whole number (0-32767). 16384 (4000 Hex)corresponds to 100%. (Negative figures areformatted by means of 2's complement.)
The bus reference has the following format:Parameter 203 = "0"
"refMIN – refMAX"0-16384 (4000 Hex) ~ 0-100% ~ ref
MIN- ref
MAX
Parameter 203 = "1"–ref
MIN- +ref
MAX
–16384 (...Hex) - +16384 (4000 Hex) ~ –100 - +100% ~ –ref
MAX- +ref
MAX
Actual output frequency
Slave Master
The value of the actual output frequency ofthe adjustable frequency drive is transmittedin the form of a 16-bit word. The value is
transmitted as a whole number (0-32767).16384 (4000 Hex) corresponds to 100%.(Negative figures are formed by means of2's complement).
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit no.
Busreference
Controlword
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit no.
Outputfrequency
Statusword
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit no.
Statusword
Outputfrequency
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 24/42
24
VLT ® 5000 Series DeviceNet
** Automatic reset to (0)S Only in stop mode (VLT must be stopped in order to change data value.)
Size Conversion Data
PNU Parameter Description Default Value Range Index Index Type
801 Baud rate select 28 –1 3
803 Bus time out 22 –1 3
804 Bus time out function 24 –1 3
805 Bit 10 function 9 –1 6
904 PPO type select 900 900-903 0 0 6
915 PCD config. write 0 0 6
916 PCD config. read 0 0 6
918 Station address 0 0-63 0 0 6
927 Parameter edit With DeviceNet (1) 0-1 0 0 6
928 Process control With DeviceNet (1) 0-1 0 0 6
953 Warning parameter 0 0 35
967 Control word 16 bits 0 0 35968 Status word 16 bits 0 0 35
970 Edit setup Active Setup = P001 0-6 0 0 5
971S Store data values OFF (0) ON/OFF 0 0 5**
980 Defined parameters 0 0 6
981
982
990 Modified parameters 0 0 6
991
992
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 25/42
25
VLT ® 5000 Series DeviceNet
5 Factory setting
Special attention must be given to the followingparameters described in the VLT 5000 SeriesInstruction Manual:• 002: If operation site =Local, then control
via DeviceNet is not possible.• 502-508: Selection of how to gate DeviceNet
control commands with control commandson the digital inputs of the control card.
Selection:125 kBaud (125 KBAUD) [20]250 kBaud (250 KBAUD) [21]500 kBaud (500 KBAUD) [22]
Selection:1 - 99 sec 5 1 sec
• 512: Control word profile, selects a controlword according to DeviceNet or a Danfossspecified control word.
• 515-538: Data read out parameters that can
be used to read various actual data fromthe VLT, as for example actual status onthe analog and digital inputs of the controlcard thus using these as inputs to themaster.
Function:Selec tion of the DeviceNet transmissionspeed. The selection must match thetransmission speed of the master and otherDeviceNet nodes.
Description of selections:• 125 - 500 kBaud : Selection of a fixedbaudrate will reduce the power up time as it
VLT parameters
801Baud rate select
803Bus time out
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 26/42
26
VLT ® 5000 Series DeviceNet
5 Factory setting
804Bus time out function
Selection:5 Off
(OFF) [0]Freeze output frequency
(FREEZE OUTPUT) [1]Stop with auto restart(STOP) [2]Output frequency =JOG freq.(JOGGING) [3]Output frequency =Max, freq.(MAX SPEED) [4]Stop with trip(STOP AND TRIP) [5]Control without DeviceNet(NO DEVICENET CONTROL) [6]Select set-up 4
(SELECT SET UP 4) [7]
Function: The time out counter is triggered at the firstreception of a valid control word i.e. bit 10 =ok, when DP or cyclical FMS communication
is used. Acyclical FMS will not trigger the timeout counter. The time o ut function can beactivated in two different ways:1. CTW is not updated within the specified
time.2. Parameter 805 ="bit 10 =0 time out"
and bit 10 ="0". The VLT remains in time out state until oneof the following four conditions is true:1. Valid control word (Bit 10 =ok) is received
and reset (Bus, terminals or local controlpanel) is activated (reset is only necessary
when the time out functionStop w/ trip isselected) control via DeviceNet is resumedwith the actual control word.
2. Parameter 002 =Local Local control vialocal control panel is enabled.
3. Parameter 928 =Disabled Normal controlvia terminals and RS485 is enabled.
NOTE: The time out counter is reset and must betriggered by a valid control word before a newtime out can be activated.4. Parameter 804 =Off control via DeviceNet
is resumed and the most recent control word
is used.Description of Selections:• Freeze output frequency : Freeze output
frequency until communication is resumed.• Stop with auto restart : Stop with auto restart
when communication is resumed.• Output frequency = JOG freq .: Motor will
run at JOG frequency until communicationisresumed.
• Output frequency = Max. freq .: Motor willrun at max. frequency until communicationisresumed.
• Stop with trip: Motor is stopped, reset neededfor restart, see explanation above.
• Control without DeviceNet : Control viaDeviceNet is disabled and control is possiblevia terminals and/or standard RS485interface, until communication is resumed.
• Selec t set up 4 : Set up 4 is selected inparameter 004 and the settings of set up 4will be used. Parameter 004 is not reset tothe original value when communication isresumed.
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 27/42
27
VLT ® 5000 Series DeviceNet
Function:According to the DeviceNet profile, controlword and speed reference will be ignored if bit 10 of the control word is0 , but parameter
805 lets the user change the function of bit10. This is some times necessary as somemasters are setting all bits to 0 in variousfault situations. In these cases it makessense to change the function of bit 10 sothat the VLT is commanded to stop (coast)when all bits are0 .Description of Selections:• Bit 10 =1 CTW ac tive : Control word and
speed reference is ignored if bit 10 =0.• Bit 10 =0 CTW ac tive : Control word and
speed reference is ignored if bit 10 =1. If
all bits of the control word are 0 the VLTreaction will be coasting.• Bit 10 =0 time out : The time out function
selected in parameter 804 is activated whenbit 10 is0 .
• No function: Bit 10 is ignored, i.e. controlword and speed reference is always valid.
5 Factory setting
805Function of control word bit 10
Selection:No function(NO FUNCTION) [0]
5 Bit 10 = CTW active
(BIT 10 = 1 CTW ACTIVE) [1]Bit 10 = 0 CTW active(BIT 10 = 0 CTW ACTIVE) [2]Bit 10 = 0 time out(BIT 10 = 0 TIME OUT) [3]
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 28/42
28
VLT ® 5000 Series DeviceNet
Function:Parameter 904 will indicate the last PPO typeused for writing when using FMS.Description of Selections:
• PPO type 1: 12 byte PPO with parameterchannel for read and write of parameters and4 bytes of process data (control/status wordand reference/actual output frequency).
• PPO type 2: 20 byte PPO as PPO type 1with 8 additional bytes of selectable processdata
• PPO type 3: 4 byte process data (control/status word and ref./actual outputfrequency).
• PPO type 4: 12 byte process data, asprocess data part of PPO type 2.
5 Factory setting
904PPO type select forDP
Selections:5 PPO type 1 (PPO TYPE 1) 900
PPO type 2 (PPO TYPE 2) 901PPO type 3 (PPO TYPE 3) 902
PPO type 4 (PPO TYPE 4) 903
915PCD config. write
Selections:Sub index 1 Parameter #
Sub index 2 Parameter #Sub index 3 Parameter #Sub index 4 Parameter #
Function:Different parameters can be assigned to PCD
3-10 of the PPO's (the number of PCD'sdepends on the PPO type). The values inPCD 3-10 will be written to the selectedparameters as data values.LCP read only, write access via DeviceNetor standard RS 485.Description of selections: The order of subindexes corresponds to theorder of the PCD's in the PPO, i.e. subindex1 ³ PCD 3, subindex 2 ³ PCD 4 and so on.Each subindex can hold the number of anyof the VLT parameters, but it is only possible
to write 2 byte values (least significant bytes)to parameters with 4 byte data values as 1PCD consists of only 2 bytes.
902
900
901
903
20
100
101
102
70
150
151
152
WRITE READValue Decimal Decimal
SPEED
ST AC RefCTW REF
REFCTW 915,1 915,2
915,1 915,2 915,3 915,4
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 29/42
29
VLT ® 5000 Series DeviceNet
5 Factory setting
916PCD config. read
918MAC I.D.
927Parameter edit
Function:Different parameters can be assigned to PCD3-10 of the PPO's (the number of PCD'sdepends on the PPO type). The PCD 3-10
will hold the actual data value of the selectedparameters.LCP read only, write access via DeviceNetor standard RS 485.Description of selections: The order of subindexes corresponds to theorder of the PCD's in the PPO, i.e. subindex1 ³ PCD 3, subindex 2 ³ PCD 4 and so on.Each subindex can hold the number of anyof the VLT parameters, but it is only possibleto read 2 byte values (least significant bytes)from parameters with 4 byte data values as1 PCD consists of only 2 bytes.
Function:All stations connected to the same bus musthave a unique address. The station addresscan be set in parameter 918 or on a hardwareswitch.
Function:Editing parameters is possible via either
DeviceNet or the standard RS485 interface,but not both at the same time. Parameter readis always possible via the local control panel.Description of selections:• Disabled : Parameter edit via DeviceNet is
disabled. Parameter edit via standardRS485 is possible.• Enabled : Parameter edit via DeviceNet is
enabled. Parameter edit via standard RS485is blocked.
Selections:Sub index 1 (PCD 3) Parameter #Sub index 2 Parameter #Sub index 3 Parameter #
Sub index 4 Parameter #
Selections:0 - 63
5 0
Selections:Disabled [0]
5 Enabled [1]
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 30/42
30
VLT ® 5000 Series DeviceNet
Function:Process control (setting of control word andspeed reference) is possible via eitherDeviceNet or the standard RS485 interface,
but not both at the same time. Local controlis always possible via the local control panel.Control via control card terminals is possiblewith either bus depending on the setting of parameters 502-508.Description of selections:• Disabled : Process control via DeviceNetis disabled. Process control via standardRS485 is possible.• Enabled : Process control via DeviceNet is
enabled. Process control via standardRS485 is blocked.
NOTE: The motor may start without notice whenparameter 928 is changed and startcommands are present.
Function:A 16 bit bitstring where each bit is associatedwith a specific warning according to the listbelow.Bit Bit = "1" when:
0 LSB Connection with DP-master is not ok
1 Connection with FMS-master is not
ok2 FDL (Field-bus Data link Layer) is
not ok
3 Clear data command received
4 Actual value is not updated
5 Spo nta neous messa ge FIFOoverflow
6 DeviceNet ASIC is not transmitting
7 Initializing of DeviceNet option is notok
8 Not used
9 Not used
10 Not used
11 Not used12 Not used
13 Not used
14 Not used
15 MSB Not used
928Process control
953Warning parameter1
Selections:Disabled [0]
5 Enabled [1]
Selections:Read only
No LCP access
5 Factory setting
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 31/42
31
VLT ® 5000 Series DeviceNet
Selections:16 bits binary code
No LCP access
Selections:Read only
No LCP access
Selections:Fac tory set up (FACTORY SET UP) [0]Set up 1 (SET UP 1) [1]Set up 2 (SET UP 2) [2]Set up 3 (SET UP 3) [3]Set up 4 (SET UP 4) [4]
5 Active set up (ACTIVE SET UP) [5]
Selections:5 No action
(NO ACTION) [0]
Store data values(STORE DATA VALUES) [1]
Function:Parameter 967 is devoted to sending a controlword to the VLT when using FMS withacyclical communication (without PPO's). The
control word is sent by means of the FMSwrite service to parameter 967 (index 4967).
Function:Parameter 968 is devoted to reading thestatus word from the VLT when using FMSwith acyclical communication or cyclical readon CR 5 (without PPO's). The status word isread by means of the FMS read service fromparameter 968 (index 4968).
Function:Refer to parameter 005 in the VLT 5000 SeriesInstruction Manual.
Function:Parameter values changed via DeviceNet isonly stored in RAM meaning that the changes
are lost at power down. This parameter is usedto activate a function that stores all parametervalues in the EEPROM thus retainingchanged parameter values at power down.Description of selections:No ac tion : The store function is inactive.Store data values : All parameter values willbe stored in the EEPROM. The value returnsto No action when all parameter values havebeen stored.
967Control Word
968Status word
970Edit set up selection
971Store data values
5 Factory setting
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 32/42
32
VLT ® 5000 Series DeviceNet
980-982Defined parameters
990-992Modified parameters
Function: The three parameters holds a list of all theparameters that are defined in the VLT. Eachof the three parameters can be read as an
array by means of the acyclical FMS readservice with subindex 255. It is also possibleto read single elements of the list by DP andcyclical/acyclical FMS by using thecorresponding subindex. The subindexes startat 1 and follows the order of the parameternumbers.Each parameter holds up to 116 elements(parameter numbers). The number of parameters (980, 981 and 982) in usedepends on the actual VLT configuration.When a 0 is returned as parameter number
the list ends.
Function: The three parameters holds a list of all theVLT parameters that has been changed fromfactory setting. Each of the three parameterscan be read as an array by means of theacyclical FMS read service. It is also possibleto read single elements of the list by DP andcyclical/acyclical FMS by using thecorresponding subindex. The subindexesstarts at 1 and follows the order of the
parameter numbers. Each parameter holdsup to 116 elements (parameter numbers). Thenumber of parameters (990. 991 and 992) inuse depends on how many parameters hasbeen changed from factory setting.Read only parameters, as for example dataread out parameters, will not be registeredas modified even though they are changing.When a 0 is returned as parameter numberthe list ends.
Selections:Read only
Selections:Read only
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 33/42
33
VLT ® 5000 Series DeviceNet
1
2
3
4
5
6
7
8
ON
User Interface The DeviceNet option card contains two bi-color(green/red) LED's for each connector hookupport, to indicate the state of the device andnetwork, respectively.
For the device status LED:1. when the LED is off, the device is off 2. when the LED is green, the device is
operational3. When the LED is flashing green, the device
is in standby4. when the LED is flashing red, the device
detects a minor fault5. when the LED is red, the device detects
an unrecoverable fault6. when the LED is flashing red/green, the
device is self testing
For the network status LED:1. when the LED is off, the network is non-powered/not online
2. when the LED is flashing green, thenetwork is online but not connected
3. when the LED is green, the network isonline and connected
4. when the LED is flashing red, the networkhas a connection time-out
5. when the LED is red, the network has acritical link failure.
No further direct user interface is considered.
LED's
There is a clear distinction between alarms andwarnings. In the case of an alarm, The VLT willenter a fault condition and act as defined in theControl Word. After the cause for the alarm hasbeen cleared, the master will have to
Any warning within the VLT is represented by asingle bit within a warning word. A warning word
is always an action parameter. Bit status FALSE[0] means no warning, while bit status TRUE [1]means warning. To each bit and each bit statusthere is a corresponding text string.
Following an Alarm message the VLT will enterFault condition. Only after the fault has beenalleviated and the master has acknowledged thealarm message by setting bit 7 in the ControlWord, can the VLT resume operation.
acknowledge the alarm message for the VLTto start operating again. A warning on theother hand may come when a warningcondition appears, and disappear whenconditions return to normal without interferingwith the process.
In addition to the warning word message themaster will also be notified through a changeof bit 7 in the Status Word.
Any warning within the VLT is representedby a single bit within a warning word. Awarning word is always an action parameter.Bit status FALSE [0] means no fault, whilebit status TRUE [1] means fault. To each bit
Warning andAlarm Messages
Warnings
Alarms
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 34/42
34
VLT ® 5000 Series DeviceNet
Status messages appear in the 4th line of the
display, see the below example. The status
message will be on the display for
approximately 3 seconds.
Start clockwise/anti-clockwise(START FORW./REV):Input on digital inputs and parameter data are
in conflict.
Slow-down (SLOW DOWN): The output frequency of the VLT adjustable
frequency drive is reduced by the percentage
value chosen in parameter 219.
Catch-up (CATCH UP): The output frequency of the VLT adjustable
frequency drive is increased by the
percentage value chosen in parameter 219.
Feedback high (FEEDBACK HIGH): The FB value is higher than the value set in
parameter 228. This message is only shown
when the motor is running.
Feedback low (FEEDBACK LOW):
The FB value is lower than the value set in
parameter 227. This message is only shown
when the motor is running.
Output frequency high(FREQUENCY HIGH): The output frequency is higher than the value
set in parameter 226. This message is only
shown when the motor is running.
Output frequency low(FREQUENCY LOW): The output frequency is lower than the value
set in parameter 225. This message is only
shown when the motor is running.
Output current high (CURRENT HIGH):
The output current is higher than the value set
in parameter 224. This message is only
shown when the motor is running.
Output current low (CURRENT LOW): The output current is lower than the value set
in parameter 223. This message is only
shown when the motor is running.
Braking max. (BRAKING MAX): The brake is functioning.
Brakes to its maximum when running 100%
duty cycle.
Braking (BRAKING):
The brake is functioning.
Ramp operation (REM/RAMPING):
Remote has been selected in parameter 002
and the output frequency is changed in
accordance with the ramps set.
Ramp operation (LOCAL/RAMPING):
Local has been selected in parameter 002
and the output frequency is changed in
accordance with the ramps set.
Status Messages
SLOW DOWN
FREQUENCY
60.0 HZ 1SETUP
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 35/42
35
VLT ® 5000 Series DeviceNet
Status Messages(continued)
VLT ready, remote control(REM/UNIT READY):
Remote control has been selected in
parameter 002 and Coasting stop inverse in
parameter 304, and there is 0 V on terminal27.
VLT ready, local control(LOCAL/UNIT READY):
Local has been selected in parameter 002
and Coasting inverse in parameter 304, and
there is 0 V on terminal 27.
Quick-stop, remote control(REM/QSTOP):
Remote control has been selected in
parameter 002 and the VLT adjustablefrequency drive has stopped via a quick-stop
signal on terminal 27 (or possibly via the serial
communication port).
Quick-stop, local (LOCAL/QSTOP):
Local has been selected in parameter 002
and the VLT adjustable frequency drive has
stopped via a quick-stop signal on terminal
27 (or possibly via the serial communication
port).
DC stop, remote control
(REM/DC STOP):Remote control has been selected in
parameter 002 and the VLT adjustable
frequency drive has stopped via a DC stop
signal on a digital input (or possibly via the
serial communication port).
DC braking, local (LOCAL/DC STOP):
Local has been selected in parameter 002
and the VLT adjustable frequency drive has
stopped via a DC braking signal on terminal
27 (or possibly via the serial communication
port).
Stop, remote controlled (REM/STOP):
Remote control has been selected in
parameter 202 and the VLT adjustable
frequency drive has stopped via the control
panel or a digital input (or possibly via the
serial communication port).
Stop, local (LOCAL/STOP):
Local has been selected in parameter 002
and the VLT adjustable frequency drive has
stopped via the control panel or the digitalinput (or possibly via the serial communication
port).
Stand by (STAND BY):
Remote control has been selected in
parameter 002. The adjustable frequency
drive will start when it receives a start signal
via a digital input (or the serial communicationport).
Freeze output (FREEZE OUTPUT):
Remote control has been selected in
parameter 002 together with Freeze reference
in parameter 300, 301, 305, 306 or 307, and
the terminal in question (16, 17, 29, 32 or 33)
has been activated (or possibly via the serial
communication port).
Jog operation, remote controlled
(REM/RUN JOG):Remote control has been selected in
parameter 002 and jog in parameter 300,
301, 305, 306 or 307, and the terminal in
question (16, 17, 29, 32 or 33) has been
activated (or possibly via the serial
communication port).
Jog operation, local(LOCAL/RUN JOG):
Local has been selected in parameter 002
and Jog in parameter 300, 301, 305, 306 or
307, and the terminal in question (16, 17, 29,
32 or 33) has been activated (or possibly via
the serial communication port).
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 36/42
36
VLT ® 5000 Series DeviceNet
The display flashes between normal state and
warning. A warning comes up on the first and
second line of the display. See examples
below:
WARN. 1
Under 10 Volts (10 VOLT LOW): The 10 Volts voltage from terminal 50 on the
control card is below 10 Volts.
WARN. 3No motor (NO MOTOR): The motor check function (see parameter 122)
indicates that no motor has been connected
to the output of the VLT adjustable frequency
drive.
WARN. 4Phase fault
(AC LINE PHASE LOSS):One of the three AC line phases is missing.
WARN. 5Voltage warning high(DC LINK VOLTAGE HIGH): The intermediate circuit voltage (DC) is above
the upper voltage limit of the controls (refer tothe table). The VLT adjustable frequency drive
is still active.
WARN. 7Overvoltage (DC LINK OVERVOLT):If the intermediate circuit voltage (DC)
exceeds the inverter overvoltage limit (refer to
the table), the VLT adjustable frequency drive
will trip after the time set in parameter 410
has passed.
Furthermore, the voltage will be stated in the
display.
WARN. 8Undervoltage (DC LINK UNDERVOLT):If the intermediate circuit voltage (DC) drops
below the inverter lower voltage limit (refer to
table), it will be checked whether 24 V power
supply is connected. If no 24 V power supply
is connected, the VLT adjustable frequency
drive will trip after a given time that depends
on the unit.
Furthermore, the voltage will be stated in the
display.
Warnings
Alarm/warning limits:
VLT 5000 Series 3 x 200 - 240 V 3 x 380 - 500 V
[VDC] [VDC]
Undervoltage 211 402
Voltage warning low 222 423
Voltage warning high 384 w/o brake / 405 w/brake 801 w/o brake / 840 w/brake
Overvoltage 425 855
The voltages stated are the intermediate circuit voltage of the VLT adjustable frequency
drive with a tolerance of± 5%. The corresponding AC line voltage is the intermediate circuit
voltage divided by 2 .
NO MOTOR
1SETUPW ARN.3
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 37/42
37
VLT ® 5000 Series DeviceNet
WARN. 25Brake resistor fault (BRAKE RESISTORFAULT): The brake resistor is monitored during
operation and if it short-circuits, the brakefunction is disconnected and the warning
comes up. The VLT adjustable frequency
drive will still be able to work, although
without the brake function.
WARN. 26Brake resistor power 100%(BRAKE PWR WARN 100%)
WARN. 27Brake transistor fault
(BRAKE IGBT FAULT): The brake transistor is monitored during
operation and if short-circuits, the brake
function is disconnected and the warning
comes up. The VLT adjustable frequency
drive will still be able to run, but since the
brake transistor has short-circuited,
substantial power will be transmitted to the
brake resistor, even if it is inactive.
WARNING: There is a risk of substantial power
being transmitted to the brake resistor
if the brake transistor has been
short-circuited.
WARN. 28
Brake resistor power 80%(BRAKE POWER WARN 80%) The power transmitted to the brake resistor is
calculated as a percentage, as a mean value
over the last 120 sec., on the basis of the
resistance value of the brake resistor
(parameter 401) and the intermediate circuit
voltage.
When the calculated mean power exceeds
80% of the monitoring limit for the brake
power (parameter 402), a warning will appear.
If the mean power exceeds 100% and the
power monitoring of the brake resistor is On
(parameter 403), the brake function will be
disconnected.
If power monitoring has been connected (Off),
a warning will come up and the brake function
will still be active, which involves a risk of
overheating the brake resistor.
Warnings(continued)
WARN. 9Inverter overload (INVERTER TIME): The electronic, thermal inverter protection
reports that the Adjustable frequency drive is
about to cut out because of an overload (toohigh current for too long). The counter for
electronic, thermal inverter protection has
reached 98%, where 100% leads to a trip.
WARN. 10Motor overtemperature (MOTOR TIME): According to the electronic thermal protection
(ETR), the motor is too hot. This warning will
only come up if Warning has been selected in
parameter 128.
WARN. 11Motor thermistor (MOTORTHERMISTOR): The thermistor or the thermistor connection
has been disconnected.
WARN. 12Torque limit (TORQUE LIMIT): The torque is higher than the value in
parameter 221 (in motor operation) or the
torque is higher than the value in parameter
222 (in regenerative operation).
WARN. 13Overcurrent (OVERCURRENT): The inverter peak current limit (approximately
250% of the rated current) has been
exceeded.
WARN. 23Fault during brake test (BRAKE TEST
FAILED):If Warning has been selected in parameter
404, the warning will come when the brake
test spots a fault. The brake test runs after
power up and when the motor has stoppedvia one of its functions, coasting stop or
quick-stop. The brake test may fail for the
following reasons:
No brake resistor connected or fault in the
connections; defective brake transistor. This
warning means that the brake will be inactive,
while the VLT adjustable frequency drive will
be able to work without the brake function.
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 38/42
38
VLT ® 5000 Series DeviceNet
Alarm/warning limits:
VLT 5000 Series 3 x 200 - 240 V 3 x 380 - 500 V
[VDC] [VDC]
Undervoltage 211 402
Voltage warning low 222 423
Voltage warning high 384 w/o brake / 405 w/brake 801 w/o brake / 840 w/brake
Overvoltage 425 855
The voltages stated are the intermediate circuit voltage of the VLT adjustable frequency drivewith a tolerance of± 5%. The corresponding AC line voltage is the intermediate circuit voltage
divided by 2 .
The alarm comes up in lines 2 and 3 of the
display, see the example below:
ALARM: 4Phase fault (MAINS PHASE LOSS):
One of the three AC line phases is missing(Trip locked).
ALARM: 7Overvoltage (DC LINK OVERVOLT):If the intermediate circuit voltage (DC) exceeds
the inverter overvoltage limit of the control
card (refer to the table), the VLT adjustable
frequency drive will trip after the time set in
parameter 410 has passed. Furthermore, the
voltage will be stated on the display as TRIP
(RESET).
ALARM: 8Undervoltage (DC LINK UNDERVOLT)
If the intermediate circuit voltage (DC) falls
below the inverter undervoltage limit of the
control card (refer to the table), it will be
checked whether an external 24 V supply has
been connected. If an external 24 V supply
has not been connected, the VLT adjustable
frequency drive will trip after a given time, set
in parameter 410 has passed.
Furthermore, the voltage will be stated on the
display as TRIP (RESET).
ALARM: 9Inverter overtemperature(INVERTER TIME): The electronic, thermal inverter protection
signals that the adjustable frequency drive hascut out because of an overtemperature (too
high current for too long). The counter for
electronic thermal protection has reached
100%. TRIP (RESET) when the counter is
90%).
ALARM: 10Motor overtemperature (MOTOR TIME):
According to the electronic, thermal motor
protection, the motor is too hot. The alarm will
only come on if Warning has been selected in
parameter 128. TRIP (RESET).
ALARM: 11Motor thermistor (MOTOR THERMISTOR) The thermistor or thermistor connection has
been disconnected. TRIP (RESET).
ALARM: 12Torque limit (TORQUE LIM): The motor torque is higher than the value
entered in parameter 221/222. The VLT
adjustable frequency drive will trip after the
trip delay time (parameter 409) has passed.
TRIP (RESET).
ALARM: 13Overcurrent (OVERCURRENT):
The peak current limit of the inverter (approx.
200% of the rated current) has been
exceeded by more than 1-2 seconds. TRIP
(LOCKED).
ALARM: 14Earth fault (EARTH FAULT):
There is a discharge from the output phases
to earth, either in cable between theadjustable frequency drive and the motor or in
the motor itself. TRIP (LOCKED).
Alarm Messages
TRIP (RESET)
1SETUP
TORQUE LIMIT
ALARM xx
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 39/42
39
VLT ® 5000 Series DeviceNet
Alarm Messages(continued)
ALARM: 15Switch mode fault(SWITCH MODE FAULT):Fault in the switch mode power supply
(internal ±14 V supply). TRIP (LOCKED).
ALARM: 16Short-circuiting(CURR.SHORT CIRCUIT): There is short-circuiting on the motor
terminals or in the motor itself. TRIP
(LOCKED).
ALARM: 22AMA fault(AUTO MOTOR ADAPT OK):
A fault has been found during automaticmotor adaptation. The figure shown on
the display indicates a fault report, which
means the following:
1. AMA has found the entered values for
motor voltage, parameter 103, and
motor current , parameter 104, to be
unlikely or unusual in relation to the
motor.
2. AMA has found the entered value for
motor current , parameter 104, unlikely
or unusually low in relation to the
motor.
3. There is an unsymmetrical impedance
in the motor, which can be the result
of a poor motor.
4. The motor is too big in relation to the
VLT adjustable frequency drive.
5. The motor is too small in relation to
the VLT adjustable frequency drive.
6. AMA cannot be carried out because
of a poor motor.
NOTE:
AMA can only be carried out if there are
no alarms during tuning.
ALARM: 23Brake test failed(BRAKETEST FAILED):If Trip has been selected in parameter 404,
the VLT adjustable frequency drive will trip if the brake test spots a fault. The brake test
runs after power-up and when the motor has
stopped via one of the functions coasting
stop or quick-stop. The brake test may fail for
the following reasons:
No brake resistor connected or fault in the
connections, defective brake resistor or
defective brake transistor. The alarm de-
activates the brake, but the VLT adjustable
frequency drive will be able to work after the
alarm has been reset, although without the
brake function. TRIP (RESET).
ALARM: 29Heat sink temperature too high(HEAT SINK OVER TEMP.): The heat sink temperature has exceeded
90°C. The tolerance is ±5°C.
TRIP (LOCKED).
ALARM: 30Motor phase U missing(MISSING MOT. PHASE U):Motor phase U between the VLT adjustable
frequency drive and the motor is missing.
TRIP (LOCKED).
ALARM: 31Motor phase V missing(MISSING MOT. PHASE V):
Motor phase V between the VLT adjustable
frequency drive and the motor is missing.
TRIP (LOCKED).
ALARM: 32
Motor phase W missing(MISSING MOT. PHASE W):Motor phase W between the VLT adjustable
frequency drive and the motor is missing.
TRIP (LOCKED).
ALARM: 33Quick discharge not OK(QUICK DISCHARGE FAIL):Check whether 24 Volts external DC supply
has been connected and check that an
external brake/discharge resistor has been
connected, too. TRIP (RESET).
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 40/42
40
VLT ® 5000 Series DeviceNet
Bit (Hex) Warning word 2
000100 Output current low
000200 Output frequency high
000400 Output frequency low
000800 Brake test ok
001000 Braking max.
002000 Braking
004000 Brake transistor fault
Bit (Hex) Alarm word 1
000001 Brake test failed
000002 Triplock
000004 AMA tuning not OK
000008 AMA tuning OK
000010 Power-up fault
000020 ASIC fault
000040 HPFP bus timeout
000080 Standard bus timeout
000100 Short-circuiting
000200 Switchmode fault
000400 Earth fault
000800 Overcurrent
001000 Torque limit
002000 Motor thermistor
004000 Motor overload
008000 Inverter overload
010000 Undervoltage
020000 Overvoltage
040000 Phase fault
080000 4-20 mA current signal low
100000 Heat sink temperature too high
200000 Motor phase W missing
400000 Motor phase V missing
800000 Motor phase U missing
1000000 Quick discharge not ok
Warning words 1 & 2and Alarm word
Warning words 1 & 2 and alarm word are
shown on the display in Hex format. If there is
more than one warning or alarm, a sum of all
warnings or alarms will be shown. Warning
words 1 & 2 and alarm word can also bedisplayed using the serial bus parameter 540,
541 and 538.
Bit (Hex) Warning word 1
000001 Fault during brake test
000002 EE-prom control card fault
000004 EE-prom power card fault
000008 HPFP bus timeout
000010 Standard bus timeout
000020 Overcurrent
000040 Torque limit
000080 Motor thermistor
000100 Motor overload
000200 Inverter overload
000400 Undervoltage
000800 Overvoltage
001000 Voltage warning low
002000 Voltage warning high
004000 Phase fault
008000 No motor
010000 4-20 mA current signal low
020000 10 Volts low
040000 Brake resistor power 80%
080000 Brake resistor power 100%
100000 Brake resistor fault
200000 Brake transistor fault
Bit (Hex) Warning word 2
000001 Ramping
000002 Aotomatic motor tuning
000004 Start clockwise/anticlockwise
000008 Slow down
000010 Catch-up
000020 Feedback high
000040 Feedback low000080 Output current high
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 41/42
41
VLT ® 5000 Series DeviceNet
eneral Purpose Analog I/O (page 18)
Value Instance WRITE Instance READI/O Assembly
Instances
BUS
REF
BUS
REF
REF
SPEED
102
101
100
20
9024
Byte
9024Byte
9024Byte
9024Byte
CONTROL
WORD
CONTROL
WORD
SecInstance 20
STATUSWORD
STATUSWORD
SecInstance 70
151
152
150
70
916,2
OUTPUTFREQ.
OUTPUTFREQ.
ACTUALSPEED
916,4916,3916,1915,4915,3915,2915,1
Instance Byte
Instance 20
Bit 0Bit 3Bit 4Bit 6 Bit 2Bit 7
FaultReset
RunFwd
20 0
Bit 5
1
2
3
Speed Reference (Low Byte)
Speed Reference (High Byte)
Bit 1
Instance
70
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
FauledRunning1
1
0
2
3
Speed Actual (Low Byte)
Speed Actual (High Byte)
Note: The DeviceNet Option Card is CE pending, consult factory
Instance 70
A P E N D I X
7/27/2019 VLT 5000 DeviceNet Instructions
http://slidepdf.com/reader/full/vlt-5000-devicenet-instructions 42/42
VLT ® 5000 Series DeviceNet
Value Instance WRITE Instance READ
BUS
REF
BUS
REF
REF
SPEED
102
101
100
20
9024Byte
9024
Byte
9024Byte
9024Byte
CONTROL
WORD
CONTROL
WORD
Sec
Instance 20
STATUSWORD
STATUSWORD
SecInstance 70
151
152
150
70
916,2
OUTPUTFREQ.
OUTPUTFREQ.
ACTUALSPEED
916,3915,4915,3915,2915,1
Also refer to pages 18-23.
916,4
Parameter 904 (page 28)
904 Selections: Function:
PPO type select for DP 5PPO type 1 (PPO TYPE 1) 900 Parameter 904 will indicate the last PPO type
PPO type 2 (PPO TYPE 2) 901 used for writing when using FMS.
PPO type 3 (PPO TYPE 3) 902 Description of Selections:
PPO type 4 (PPO TYPE 4) 903
916,1
APENDIX PPO type 1: 12 byte PPO with parameter
channel for read and write of parameters
and 4 bytes of process data (control/statusword and reference/actual output frequency)
PPO type 2: 20 byte PPO as PPO type 1with 8 additional bytes of selectable process data
PPO type 3: 4 byte process data (control/statusword and ref./actual output frequecy)
PPO type 4: 12 byte process data, as process datapart of PPO type 2.