voltage drop calculations
DESCRIPTION
Guideline for Voltage drop calculationTRANSCRIPT
VOLTAGE DROP CALCULATIONSMARCH 12, 2014 MOHAMED A. MOUSSA 2 COMMENTS
Q.Calculate the voltage drop of copper feeder 50 mm2 cable size,
60m length , 20.0 KVA, 230 V,1-phase. (Mention Ref. PLZ).
I(rated)=20,000 (VA)/230V=87 A
V.D% =0.81 (mv/amp/m)* X 87 A X 60 m(length) X 100(%) /230,000 mV
= 1.84% (<3%, acceptable)**.
Q.Calculate the voltage drop of copper feeder 16 mm2 cable size,
60m length , 20.0 KVA, 380 V,3-phase. (Mention Ref. PLZ).
I(rated)=20,000 (VA)/ 400V / 1.732=28.9 A
V.D% =2.2 (mv/amp/m)* X 28.9 AX 60 m(length) X 100(%) / 400,000 mV
X 0.866 = 0.83% (<3% , acceptable)**.
References:
* As per Saudi cable table: (noted that: this table can be usedcommon for
single phase but for three phase multiply by 0.866. Also this values will be
minor changed between companies).
** As per NEC 2011(215.2(A): The voltage drop of a feeder or a branch
circuit is limited to 3 percent. However, the total voltage drop of a branch
circuit plus a feeder can reach 5 percent.
.