VOLTEX® & VOLTEX DS®
BENTONITE GEOTEXTILE WATERPROOFING SYSTEM
For Cast-in-place Concrete Applications
PRODUCT MANUAL
www.cetco.com
VOLTEX® & VOLTEX DS® BENTONITE GEOTEXTILE WATERPROOFING
PRODUCT MANUAL
- 2 -
CONTENTSWHAT IS SODIUM BENTONITE?PRODUCT DESCRIPTIONASSOCIATED SYSTEM PRODUCTSACCESSORIESLIMITATIONS
INSTALLATION GUIDELINESSECTION 1: UNDERSLAB INSTALLATION 1.1 Substrate Preparation 1.2 Installation 1.3 Pile Caps & Ground Beams 1.4 Slab Penetrations 1.5 Elevator Pits 1.6EdgeofSlab,BackfilledWalls 1.7EdgeofSlab,PropertyLineWalls SECTION 2: PROPERTY LINE CONSTRUCTION 2.1 Property Line Installation Guidelines 2.2 Soldier Pile & Lagging 2.3SteelSheetPilingRetainingWall 2.4 Earth Formed Shotcrete Retention 2.5Secant/ContiguousPiledRetentionWall SECTION 3: BACKFILLED WALLS 3.1 Surface Preparation 3.2 Installation 3.3BackfilledWallPenetrations 3.4 Terminations 3.5MasonryBlockWalls SECTION 4: SPECIAL CONDITIONS 4.1 Precast Concrete Construction 4.2 Contaminated Conditions
THIS MANUAL CONTAINS THE INSTALLATION GUIDE-LINES FOR THE VOLTEX® AND VOLTEX DS® WATER-PROOFING SYSTEM FOR CAST-IN-PLACE CONCRETE APPLICATIONS, INCLUDING UNDERSLAB, PROP-ERTY LINE WALLS, AND BACKFILLED WALLS. THIS MANUAL DOES NOT COVER SHOTCRETE, MASONRY BLOCK, OR PRECAST CONCRETE APPLICATIONS. FOR APPLICATIONS NOT COVERED IN THIS MANU-AL, CONTACT CETCO FOR SPECIFIC INSTALLATION GUIDELINES. BEFORE INSTALLATION, READ THIS MANUAL TO GAIN FAMILIARITY WITH SPECIFIC PRO-CEDURES AND APPLICATIONS. IN THIS MANUAL THE PRODUCT NAME “VOLTEX” IS USED GENERICALLY FOR ALL VOLTEX® PRODUCT TYPES.
WHAT IS SODIUM BENTONITE?
Sodium bentonite is a non-toxic material of volcanic origin which can be found in various geographical locations. Bentonite is specially processed by CETCO to achieve the highest possible performance for all of our waterproofing products. CETCO also manufacturers a contaminant resistant bentonite to assure optimum performance in moderate saline or contaminated water. Bentonite prevents wa-ter intrusion by forming a dense monolithic membrane upon contact with water. The specially processed bentonite expands under con-finement,forminganimperviousmembranethatwillbemaintainedfor the life of the structure.
PRODUCT DESCRIPTIONVOLTEX®isahighlyeffectivewaterproofingcompositecomprisedoftwopolypropylene geotextiles and sodium bentonite. The two geotextiles are interlocked by a patented needlepunching process which encapsulates andconfinesthebentonite.VOLTEXDS® integrates a polymer liner bond-ed to the outside surface of the nonwoven geotextile. The polymer liner provides extremely low permeabilities for water vapour transmission.
Figure 1 – Cross section illustration of VOLTEX®waterproofingmembranemechanicallybondedtoconcrete
Concrete
Needlepunched geotextilefibres
Granular sodium bentonite
Nonwoven geotextile
VOLTEX® forms a continuous mechanical bond to concrete. This bond is created when VOLTEX®’s strong geotextilefibresareencapsulated by poured concrete as shown in the illustration
Wovengeotextile
www.cetco.com
Installation of VOLTEX® is fast and easy. Simply position the product into place and fasten. VOLTEX® can be installed on green concrete, in virtually any weather, without the need for primers or adhesives. VOLTEX® can be easily cut on site to form around corners and pene-trations. The result is always a consistent self-sealing membrane.
DURABILITYThe VOLCLAY® sodium bentonite in VOLTEX® is uniformly encapsu-lated between two high-strength woven and non-woven geotextiles. CETCO’s state-of-the-art needlepunching process interlocks the geotextiles, preventing the displacement of bentonite prior to, dur-ing, and after installation. The geotextiles provide superior protection from inclement weather and construction-related damage, without requiring to use a protection course.
SUPERIOR ADHESIONWhenconcreteispouredagainstVOLTEX®, a tenacious mechanical bond is created with VOLTEX®’s high strength geotextile. Independent laboratorytestingconductedinaccordancewithASTMD903(mod.)(Peel Adhesion to Concrete), yields an average adhesion value of2.6 kN/m. The mechanical bond will hold VOLTEX® in intimate contact with the concrete should any ground settlement occur, thereby pre-ventingwatermigrationbetweenthewaterproofingandtheconcrete.
COST EFFECTIVE AND TIME EFFICIENTVOLTEX® is designed to be installed on a properly prepared subgrade, withouttheneedtopouraworkingslab.Theproduct’sinherentflex-ibility allows for easy installation on irregular surfaces and rough property line forming. VOLTEX® can be installed as soon as the forms are stripped; there is no waiting for the concrete to cure.
ASSOCIATED SYSTEM PRODUCTSWATERSTOP-RX® – expanding concrete joint waterstop used around penetrations and applicable concrete joints. Swells upon hy-dration.AQUADRAIN – foundation drainage composite consisting of amouldedprofilecoreandafilterfabric.Includessheetdrainageandbase drain collection.
ACCESSORIESBENTOSEAL® – trowel grade mastic used to detail around penetra-tions, corner transitions and terminations. CETSEAL – single-component polyether general sealant and adhesive.VOLCLAY GRANULES® – active granular material used at detail areas that require additional protection.SEAMTAPE® – premium tape used to seal overlapped membrane edg-esofVOLTEXDS®. AKWASWELL – caulk grade hydrophilic waterstop.
TERMINATION BAR – Min. 25 mm wide aluminum or stainless steel barwithpre-punchedholeson300mmcentringforfastening.CEMENTITIOUS BOARD – 12 mm thick cementitious wall board forprotectionofwaterproofingduringtheremovalofsteelsoldierpilecap and top lagging boards. CETBIT 300 – self-adhering flashingmembraneused for ground levelflashing.TB-BOOT – pre-formed, single piece cover for tie-back heads and soilnails.Threesizesavailable:TB-6SN,TB-8&TB-10.
LIMITATIONSVOLTEX® should only be installed after substrate preparation has been properly completed and is suitable to receive the waterproof-ing system. Concrete work should use conventional cast-in-place forms that produce a smooth surface. Do not use stay-in-placeconcrete forming; use removeable forming products only.
VOLTEX® is designed for below-ground waterproofing applica-tionswhere the product is properly confined. VOLTEX® products should not be installed in standing water or over ice. If ground water contains strong acids, alkalies, or is of a conductivity of 2,500μmhos/cmorgreater,watersamplesshouldbesubmittedto the manufacturer for compatibility testing. ULTRASEAL may be required if contaminated ground water or saltwater conditions exist.
VOLTEX® is designed for use under reinforced concrete slabs 100mmthickorgreateronacompactedearth/gravelsubstrate.VOLTEX® requiresaminimum150mmthickreinforcedconcreteslab if installed over concrete blinding. VOLTEX® is not designed for split-slab plaza deck construction.
VOLTEX® is not designed to waterproof expansion joints. Do not use VOLTEX® on masonry block foundation walls. Consult CETCO for special installation guidelines that ap-ply to shotcrete and precast concrete construction.
In this manual, the product name “VOLTEX” is used generi-cally in the installation and application guidelines for the applicable products: VOLTEX®, VOLTEX CR®, VOLTEX DS® and VOLTEX DSCR®. Refer to the table on the back page for product descriptions and roll sizes. Illustrations are not shown to scale.
VOLTEX® & VOLTEX DS® BENTONITE GEOTEXTILE WATERPROOFING
PRODUCT MANUAL
- 4 -
INSTALLATION GUIDELINES
Before installing VOLTEX® read this installation manual to gain fa-miliaritywithspecificproceduresandapplications.Forapplicationsnotcovered in thismanual, contactCETCO forspecific installationguidelines.
VOLTEX® is engineered for use under reinforced concrete slabs 100mm thick or greater on a compacted earth/gravel substrate.VOLTEX®requiresaminimum150mmthickreinforcedconcreteslabif installed over concrete blinding. VOLTEX CR®orVOLTEXDSCR® is used in contaminated conditions as determined by a CETCO water sample test.
For hydrostatic conditions, VOLTEX® should be installed under footings and ground beams as shown in Figures 1.6, 1.7 and 1.8. For non-hydrostatic conditions, VOLTEX® should be installed around footingsandgroundbeamsasshowninFigures1.9,1.10and1.11.
Prior to installing VOLTEX® the substrate must be properly prepared. Complete all required elevator pit, sump pit, ground beam and pil-ing work prior to installing VOLTEX® under main slab area. These ar-easmustbecorrectlytiedintotheunderslabwaterproofingtoforma monolithic seal.
1.1 SUBSTRATE PREPARATIONSubstrate may be concrete, earth, sand, or crushed stone. Earth and sandsubstratesshouldbecompactedtoaminimum85%ModifiedProctordensity.Crushedstoneshouldbenolargerthan19mminsize.Substrateshouldbesmoothandwithoutsharpdeflectionsorpockets.
1.2 INSTALLATIONInstall VOLTEX®orVOLTEXDS® over the properly prepared substrate with thedarkgray (woven)geotextilesideup.Overlapalladjoiningedgesaminimumof100mmandstaggersheetendsaminimumof300mm(Figure1.1).Nailorstapleedges togetheras requiredto prevent any displacement before and during concrete placement (Figure1.2).
Whentheslabispouredinsections,VOLTEX® should extend a mini-mum 300 mm beyond the slab edge (Figure 1.3). This enables VOLTEX® to be properly overlapped for subsequent slab section pours. WATERSTOP-RX® should be installed in all applicable slab con-structionjoints(Figure1.3).
SECTION 1 UNDERSLAB INSTALLATION
Figure 1.2 – Secure overlaps together with fasteners
Figure 1.1 – Overlap edges 100mmwith seams staggered 300mm
VOLTEX®
Overlap 100mm Min.
Stagger300mm
DARK GRAY (WOVEN) GEOTEXTILE SIDE UP
Overlap 100mmmin.
Reinforced concrete slab
300mmmin VOLTEX®
WATERSTOP-RX® min. 75 mm coverage
Figure 1.3 – Extend VOLTEX® a minimum 300mm beyond slab edge. Install WATERSTOP-RX® in joint
www.cetco.com
WATERSTOP-RX® 75 mm min. coverage
Reinforced concrete slab aminimum100mmthick
VOLTEX®
Compacted Substrate
DARK GRAY (WOVEN) GEOTEXTILE SIDE UP
Figure 1.4 – VOLTEX®installeddirectlyovercompactedearth/gravelsubstraterequiresaminimum100mmslab
Reinforced concrete slab aminimum150mmthick
VOLTEX®
Compacted Substrate
Concrete blinding
Figure 1.5 – VOLTEX®installedoverconcreteblindingrequiresaminimum150mmthickreinforcedslab
WATERSTOP-RX® 75 mm min. coverage
DARK GRAY (WOVEN) GEOTEXTILE SIDE UP
VOLTEX® & VOLTEX DS® BENTONITE GEOTEXTILE WATERPROOFING
PRODUCT MANUAL
- 6 -
HYDROSTATIC CONDITIONS NON-HYDROSTATIC CONDITIONS
VOLTEX®
VOLTEX®
BENTOSEAL® FILLET (min38mmx38mm)
Figure1.6–Slabonfootingdetail(hydrostatic)
WATERSTOP-RX® 75 mm min. coverage
VOLTEX®
BENTOSEAL®
BENTOSEAL® FILLET (min38mmx38mm)
VOLTEX®
Concrete Blinding
Figure1.7–Raisedslabdetailwithconcreteblinding(hydrostatic)
WATERSTOP-RX® 75 mm min. coverage
VOLTEX®
BENTOSEAL®
VOLTEX®
Concrete Blinding
Figure1.10–Raisedslabdetailwithconcreteblinding(non-hydrostatic)
WATERSTOP-RX® 75 mm min. coverage
VOLTEX®
VOLTEX®
Figure1.8–Flushslabdetailpropertylinewall(hydrostatic)
WATERSTOP-RX® 75 mm min. coverage
VOLTEX®
Term Bar & BENTOSEAL®
300mm
Figure1.11–Flushslabdetailbackfilledwall(non-hydrostatic)
WATERSTOP-RX® 75 mm min. coverage
VOLTEX®
BENTOSEAL® FILLET (min38mmx38mm)
Figure1.9–Slabonfootingdetail(non-hydrostatic)
WATERSTOP-RX® 75 mm min. coverage
Term bar and BENTOSEAL®
www.cetco.com
1.3 PILE CAPS AND GROUND BEAMS
VOLTEX® is typicallynot installedoverpilecapsbutcut tofit tight-ly around pile caps. Then apply a minimum 19mm thick fillet of BENTOSEAL® at intersection of VOLTEX® and the piling (Figure1.12)withVOLCLAY GRANULES under VOLTEX® at the piling edge. BENTOSEAL® should extend onto VOLTEX® and piling a minimum of 50mmat19mmthickness.WATERSTOP-RX® should be installed on topsurfaceofpilecaparoundreinforcingsteel(Figure1.12).
Detailgroundbeamsthesameaspilecaps(Figure1.14)withanon-hydrostatic condition. For hydrostatic conditions, VOLTEX® should be installedundertheentiregroundbeam(Figure1.15).Linethegroundbeam formwork with VOLTEX® prior to placement of reinforcing steel. Leaveaminimum300mmofVOLTEX® at the top of the form to tie intobelowslabwaterproofing.
Figure1.12–PileCapDetail(Hydrostaticcondition)
Figure1.13–PileCapDetail(Non-hydrostaticcondition)
Figure1.14–GroundBeam(Non-hydrostaticcondition) Figure1.15–GroundBeam(Hydrostaticcondition)
WATERSTOP-RX®
Concrete pile
BENTOSEAL®
VOLTEX®
VOLCLAY GRANULES
WATERSTOP-RX®
Steel I-beam
VOLTEX®
WATERSTOP-RX®
50mmthickfilletofBENTOSEAL®
VOLCLAY GRANULES
WATERSTOP-RX® VOLCLAY GRANULES
VOLTEX®
BENTOSEAL®
Pile cap
BENTOSEAL®
Pile
WATERSTOP-RX® Reinforcing steel BENTOSEAL®
VOLTEX®
Ground beam
50mmthick filletof VOLCLAY GRANULES
Ground beam
Reinforcing steelWATERSTOP-RX®
VOLTEX®
VOLTEX® & VOLTEX DS® BENTONITE GEOTEXTILE WATERPROOFING
PRODUCT MANUAL
- 8 -
1.4 SLAB PENETRATIONS
Cut VOLTEX®tocloselyfitaroundpenetrations(Figure1.16).Trowelaminimum19mmthickfilletofBENTOSEAL® around the penetration tocompletelyfillanyvoidareabetweenVOLTEX® and the penetra-tion(Figure1.16).TheBENTOSEAL® should extend up the penetra-tion about 38 mm and extend onto VOLTEX®. In areas where multiple
penetrations are close together, it may be impractical to cut VOLTEX® to fit around each penetration. Pour VOLCLAY GRANULES a mini-mum 6 mm thick around the penetrations covering the entire sub-stratearea.Withgravelsubstrate,installminimum200mmcollarof VOLTEX® around penetration prior to placing VOLCLAY GRANULES. Then apply a thick layer of BENTOSEAL® around each penetration as detailed(Figure1.18).
Figure 1.16 – BENTOSEAL® troweled around penetrations Figure 1.17 – Slab penetration cross section detail
Figure 1.18 – Multiple pipe penetrations. Trowel BENTOSEAL® around pipes and covering area between the pipes
VOLTEX®
Pipe
BENTOSEAL®
DARK GRAY (WOVEN) GEOTEXTILE SIDE UP
VOLTEX®
VOLCLAY GRANULES
BENTOSEAL®
WATERSTOP-RX® 75 mm min. coverage Pipe
Concrete Blinding Substrate Compacted Earth or Gravel Substrate
Concrete Blinding
WATERSTOP-RX®
BENTOSEAL®
Continue VOLTEX® between pipes VOLTEX®
VOLCLAY GRANULESConcrete blinding substrate
Continue VOLTEX® between pipes
WATERSTOP-RX®
BENTOSEAL®
Gravel substrate
VOLTEX® collar VOLCLAY GRANULES
www.cetco.com
1.5 ELEVATOR PITS
VOLTEX® should be placed on vertical surfaces and on the substrate below the slab to form a continuous envelope around the elevator pit (Figure1.19). If the vertical soil cut is smoothand stable, VOLTEX®
may be installed directly against the soil. Contain unstable soils with concrete backblinding. Install VOLTEX® directly against the concrete backblinding.Duetovariouselevatorpistonplungerdesigns,consultCETCOforspecific installationanddetailing forpistonplungers thatpenetrate the pit slab.
Figure1.19–VOLTEX® under elevator pit slab and on excavation cut walls
1.6 EDGE OF SLAB, BACKFILLED WALLSWhentheinstallationreachestheouteredgeoftheslab,continueVOLTEX®uptothetopedgeoftheformsinsidesurface(Figure1.20)or extend the VOLTEX® sheet out the top of the form a minimum of 300mm (Figure1.21).At theslabcorner,VOLTEX® should remain in contact with the substrate and the inside surface of the concrete form.
When the slab edge form is removed, any undamaged portion of VOLTEX® extended outside the form should be positioned and se-
curedtothetopoftheconcretefooting.Damagedmaterialoutsidethe form should be cut off and disposed of. Overlap the secured VOLTEX® edgeon topof the footingaminimum150mmwith thesucceedingwallwaterproofing.InstallBENTOSEAL®fillet(min38mmx38mm)atwall-to-footingcornerpriortoinstallingoverlappingwallwaterproofing.
WATERSTOP-RX® should be installed in the perimeter wall/slab inter-section joint as illustrated in Figure 1.22.
Figure1.20–VOLTEX® turned up and secured at top of concrete form Figure 1.21 – Extra tail of VOLTEX® extended out of form and later cut off after concrete pour
300mm min.
VOLTEX®
Compacted substrate
VOLTEX® VOLTEX® secured to top of form before concrete pour
Slab edge form
Compacted substrate
VOLTEX®
Extra tail of VOLTEX® extended out of form. Cut off damaged areas before installing VOLTEX® overlap
Slab edge form
Compacted substrate
WATERSTOP-RX® 75 mm min. coverage
VOLTEX® & VOLTEX DS® BENTONITE GEOTEXTILE WATERPROOFING
PRODUCT MANUAL
- 10 -
1.7 EDGE OF SLAB, PROPERTY LINE CONSTRUCTIONWherepropertylineretainingwalls,suchassoldierpileandlagging,are used as the outside form, continue the underslab VOLTEX® instal-lationuptheretainingwallaminimum300mmabovethetopedgeoftheslaborfooting(Figure1.22).Theextra300mmsheetextensionis very important since there is no access to the outer edge of the footing after it is poured.
Slab to Wall Corner Transition: Install VOLTEX®orVOLTEXDS® sheethorizontallyoriented(darkgraywovengeotextilefacinginstall-er)withaminimum300mmofthesheetextendingoutontothehori-zontal substrate. The top edge of the sheet must extend a minimum 300mmabovethefinishedslabsurface.SecureVOLTEX® sheet to laggingwallwithwasher-headfastenermaximum600mmoncentre.Overlap edges of adjacent VOLTEX®sheetsaminimum100mm.
If theslab thickness isgreater than600mm, installasecond fullsheet or cut strip of VOLTEX®, horizontally oriented, to meet the 300mmrequirementabovetheslab.Overlaptopedgeofprevioussheetandedgesofadjacentsheetsaminimum100mm.
Base Wall Course:InstallfirstVOLTEX® sheet course on the shoring wallhorizontallyoriented(darkgreywovengeotextilefacinginstaller)over the corner transition sheet, with the bottom edge extending down to the wall/slab transition corner as shown in Figure 1.22. Se-cure VOLTEX® sheet to lagging wall with washer-head fasteners maxi-mum600mmoncentre.OverlapedgesofadjacentVOLTEX® sheets aminimum100mm.
Install underslab VOLTEX® membrane extending to corner transition, overlappingthe300mmsheettailofthecornertransitionsheetin-stalledatthewallbase.Securecorneredgewithfasteners300mmon centre.
Forsteelsheetpilingshoringwalls,first install theVOLTEX® corner transition sheet horizontally oriented with the bottom edge extending minimum300mmoutontothesubstrate.Cutthebottomedgeofthecorner transition sheet at piling transition angles to allow the bottom edgetolayflatontothesubstrate.Pour38mmcontinuousfilletofVOLCLAY GRANULES along base of shoring wall. Then install under-slab VOLTEX®sheetcuttofitcontoursofsteelsheetpiling.Finally,install the base shoring wall VOLTEX® sheet (horizontally oriented)overlapping the corner transition sheet.
Figure1.22–SLAB-TO-WALLTRANSITION–VOLTEX® corner transition sheet should extend past the height of the top of the finishedslablevelaminimum300mmandextendunder theslab300mm
Figure 1.23 – AQUADRAIN100BDDISCHARGEPIPE–Connect AQUADRAIN100BDtowaterdischargepipesusing100BD accessory connections
VOLTEX® under slabVOLTEX® transition sheet at corner installed horizontally oriented
Cast-in-place concrete wall
VOLTEX® base course installed horizontally oriented
Woodlagging
300mm min.
VOLTEX® base course installed horizontally oriented
AQUADRAIN SheetDrain
Woodlagging
300mm min.
AQUADRAIN100BDbasedrainconnected to discharge pipes
VOLTEX® transition sheet at corner installed horizontally oriented
VOLTEX®
DischargePipe
WATERSTOP-RX® 75 mm min. coverage
WATERSTOP-RX® 75 mm min. coverage
300mmBENTOSEAL®
www.cetco.com
The use of construction techniques described in this section al-low the exterior building dimensions to coincide with the prop-erty line, thereby maximizing use of available land for building. VOLTEX®/VOLTEXDS® has been proven to be one of the most effec-tiveandwidelyusedmeansforwaterproofingpropertylineconstruc-tion. Cast-in-place property line construction methods include soldier pile & lagging, steel sheet piling, earth formed shotcrete retention walls, and secant / contiguous piled walls.
For all property line construction methods, VOLTEX® is in-stalled to the shoring wall prior to concrete placement.Install VOLTEX® or VOLTEX DS® with the dark grey (woven) geotextile inward, facing the installer, away from the shoring wall. Refer to each applicable construction method in Sec-tion 2 for specific substrate preparation and detailing instal-lation guidelines.
AQUADRAINsheetand100BDbasedraincompositesystemshouldbeconnectedtoanoperativewaterdischargesystem(sumppumporgravitytodaylightdischarge).
Protectbentonitewaterproofingproductsfromhydratingbeforema-terial iscontainedwithconcreteorbackfill.Afteranyprecipitation,standingwatershouldbepumpedoffwaterproofingassoonaspos-sible.
Shoring Wall: Excavation work should provide shoring wall in good condition to receive waterproofing system. Wood lagging shoringshould extend to the lowest level of thewaterproofing installationwithanyvoidsorcavitiesexteriorofthelaggingfilledwithcompactedsoil or cementitious grout. Voids or cavities at tie-backs should be filledwithgroutorcompactedsoilprior toVOLTEX® installation. In-terior surface of lagging timbers should be monolithic and tight to-gether with gaps less than 25 mm. Gaps in excess of 25 mm should becompletelyfilledwithcementitiousgroutorothersolidmaterial.
Cut rock excavations and concrete secant / contiguous piled retain-ingwallsmustbesufficientlyplanar. Typicallya shotcreteor groutlayer is required to provide acceptable surface to install VOLTEX®.
Employ constructionmethods to stop water flowing through shor-ingwallpriortowaterproofinginstallation.Ifonlywaterseepage,in-stall polyethylene sheeting over the seepage area prior to installing VOLTEX®. Polyethylene sheeting should extend from seepage eleva-tiontobaseofwalltoprotectentirewaterproofinginstallationatthatarea.
SECTION 2 PROPERTY LINE CONSTRUCTION
Figure1.24–RAISEDSLABCONDITION– Connect AQUADRAIN100BDtowaterdischargepipesusing 100BDaccessoryconnectors
Figure 1.25 – Steel sheet piling to slab transition detail
Cast-in-place concrete wall
AQUADRAIN
VOLTEX®Wood lagging
BENTOSEAL® FILLET (min38mmx38mm)
VOLTEX®
Dischargepipe
AQUADRAIN100BDbasedrainconnected to discharge pipes
VOLTEX® underslab
300mmmin.
VOLCLAY GRANULESfilletin corner over VOLTEX® corner transition sheet
Steel sheetpiling
VOLTEX® base layer horizontally oriented
WATERSTOP-RX® 75 mm min. coverage
WATERSTOP-RX® 75 mm min. coverage
BENTOSEAL®
Retained earth
VOLTEX® corner transition sheet horizontally oriented(installfirst)
VOLTEX® corner transition sheet horizontally oriented(slicedto contour sheet piling)
VOLTEX® cut tofitcontoursof sheet pilesConcrete
blinding
INSTALL VOLTEX® OR VOLTEX DS® WITH DARK GRAY (WOVEN) GEOTEXTILE SIDE FACING INSTALLER
VOLTEX® & VOLTEX DS® BENTONITE GEOTEXTILE WATERPROOFING
PRODUCT MANUAL
- 12 -
2.1 PROPERTY LINE WALL INSTALLATION GUIDELINESAfter the slab-to-wall corner transition sheet and bottom wall sheet course have been installed per Section 1.7 Page 10, VOLTEX® sheets can be installed either vertically or horizontally oriented. Fasten the VOLTEX® into position with washer-head fasteners maxi-mum600mmoncentrearoundthesheetedge.Installsucceeding VOLTEX®sheetoverlappingtheprevioussheetedge100mm.(Note:Shingle lap seams so that the bottom edge of the upper sheet is over thelowersheetstopedge).
Continue installation up wall until ground level termination detail, or asspecified,staggeringallsheetendsofadjacentrollsaminimum300mm.Donotallowsheetoverlapjointstooccuratsameelevationas concrete construction joints. Plan by chalk lining the location of construction joints.
Penetrations: Install a cut collar of VOLTEX® tightly around the pen-etration;extendingaminimum300mmradius.ApplyBENTOSEAL® over VOLTEX® collar around penetration; extending BENTOSEAL® a minimum 75 mm radius at 6mm thickness. Then install main course of VOLTEX® membrane tightly around the penetration. Finally, detail around penetrationwith 19mm thick fillet ofBENTOSEAL®. Withsleevedpipes,theconcreteworkshouldincludefillingthegapbetween the pipe and the sleeve with non-shrink cementitious grout, mechanical seal by others and install WATERSTOP-RX® to outside of sleeve.
Tie-Back Covers:SelectappropriatesizeTB-Boottofitovertie-backplate and allow proper cast-in-place concrete coverage per project re-quirements.TB-Bootshouldfitoverentiretie-backheadwithoutthetie-back plate or cables in direct contact with the TB-Boot. Prior to TB-Bootinstallation,fillvoidsinretentionwallsubstrateandtie-backheadassemblywithsprayfoam(min.1.38bar)ornon-shrinkgrout.For non-hydrostatic conditions, install and secure AQUADRAIN drain-age composite course per manufacturer’s guidelines to soil reten-tion wall prior to installing TB-Boot. For hydrostatic conditions, install TB-Boot prior to VOLTEX®membrane.Withsoldierpiles, strippileswithwaterproofingmembranepriortoTB-Bootplacement.
Fill pre-formed shape of TB-Boot with 2-part urethane spray foam (min. 1.38 bar) and place over tie-back head before foam setsup. Secure TB-Boot to soil retention system using washer head fasteners along the outside edge of the flat base. Apply 6mmthick by minimum 75 mm wide continuous ring of BENTOSEAL® ontotheflatbasejustoutsideofthe12mmraisedcollar.Install1.2 m by 1.2 m piece of VOLTEX® (withprecuthole incentre tofittightaroundthe12mmraisedcollar)overtheentireflatbasewith outside edges fastened to the retaining wall. Secure inside VOLTEX® edge around raised collar with washer-head fasten-ers that pass through the BENTOSEAL® ring; typical fastener spacing 150mm. Do not install fasteners or puncture TB-Bootinside of the 12 mm raised collar. Apply counter flashing of BENTOSEAL® along VOLTEX® sheet edge around raised collar. Then install VOLTEX® field sheet overlapping outer membraneedgeminimum100mm.
Figure2.1–WALLPENETRATION–CutandsecureVOLTEX® tightly around penetrations and then apply BENTOSEAL®19mmringaroundpenetration and extend over membrane a minimum 75 mm radius at minimum 6 mm thickness
Figure2.2–SLEEVEDWALLPENETRATION–CutandsecureVOLTEX® tightly around penetrations and then apply BENTOSEAL® 19mmringaroundpenetrationandextendovermembrane a min. 75 mm
300mm min.
Woodlagging
300mmVOLTEX® collar around pipe penetration
19mmBENTOSEAL®fillet
WATERSTOP-RX®
Pipe
Cast-in-place concrete wall
VOLTEX®
AQUADRAINSheetDrain
300mm min.
Woodlagging
300mmVOLTEX® collar around pipe penetration
19mmBENTOSEAL®fillet
WATERSTOP-RX®
Pipe
VOLTEX®
AQUADRAINSheetDrain
Pipesleeve,filledwith non-shrink grout
Cast-in-place concrete wall
BENTOSEAL® ring 6 mm x 75 mm min.
BENTOSEAL® ring 6mm x 75 mm min.
Mechanical seal by others
www.cetco.com
Soldier Pile Stripping: Install a strip of VOLTEX® over all soldier piles with raised lagging hanger bolts, form tie rods, or other irregular surface. VOLTEX®stripshouldextendaminimum150mmtobothsides of the piling. Apply BENTOSEAL®6mmx50mmtoVOLTEX® stripsurfacealongbothedgesofeachsoldierpile(Figure2.6).
Cementitious Board: Prior to installing VOLTEX®/VOLTEXDS® to finishedground level, install12mmthickcementitiouswallboardcentredoversteelsoldierpilefromfinishedgroundelevationtospec-ifieddepththatthetopofsteelsoldierpileandwoodlaggingwillberemoved(Figure2.10).
Ground Termination: Terminate VOLTEX®membrane300mmbe-lowfinishedgroundelevationwithwasher-headfastenersmaximum300mmoncentre.InstallCETBIT300flashingtoprimedconcretesubstrate with bottom edge overlapping top edge of VOLTEX® mem-braneminimum100mm.Overlapallrollendsaminimum100mm
toformacontinuousflashing.Heightofflashingshallbeperprojectdetailsandspecifications.InstallarigidterminationbaralongtopedgeofCETBIT300;fastenedmaximum300mmoncentre.Com-plete ground level termination detail with tooled bead of CETSEAL alongthetopedge,atallpenetrationsthroughtheflashing,andallexposed overlap seams.
Wherelaggingtimbersandthetopendofsteelsoldierpilesarere-moved, repair any waterproofing damaged by the excavation andremoval of the retention wall system. Secure all excavated VOLTEX® overlapseamswithwasher-head fastenersmaximum600mmoncentre;withVOLTEXDS® also apply Seamtape centred along over-lapseams.Backfillshallbeplacedandcompactedtominimum85%Modified Proctor density promptly after waterproofing installation.Backfill should consist of compactable soil or angular aggregate19mmorless)freeofdebris,sharpobjects,andstoneslargerthan19mm.Seeterminationdetails(Figures3.11and3.12,page22).
Figure2.3:TIE-BACKDETAIL–InstallTB-Bootcentredovertie-backthen install main course of VOLTEX® with BENTOSEAL®detailing.Donot fasten boot inside of raised collar around centre formed area
Shoring wall
VOLTEX®
AQUADRAIN sheet drain
2-part urethane expanding spray foam (min.1.38bar)
Soldier pile
Fastener
Use spray foamtofillall voids behind tie-back
Donotfasten boot inside of raised collar
Tie-back head with cables
CETCO pre-formed TB-Boot
BENTOSEAL® 6 mm X 75 mm min. VOLTEX®
Field Sheet
Concrete wall
Fastener
Raised collar
Figure2.3a:TIE-BACKDETAIL–InstallTB-Bootcentredover tie-back then install VOLTEX® with BENTOSEAL®detailing.Donot fasten boot inside of raised collar around centre formed area
Shoring wallSoldier pileFastener
VOLTEX® pile strip
VOLTEX®
Raised collar
TB-Boot
Fastener
Soldier pile
VOLTEX® fieldsheet
Use spray foamtofillall voids behind tie-back
Donotfasten boot inside of raised collar
VOLTEX® pile strip
VOLTEX® pile strip
Tie-back head with cables
CETCO pre-formed TB-Boot
2-part urethane expanding spray foam (min.1.38bar)
VOLTEX®fieldsheet
BENTOSEAL® 6 mm X 75 mm min.
NON-HYDROSTATIC CONDITIONS HYDROSTATIC CONDITIONS
BENTOSEAL®
Soldier pile
AQUADRAIN
BENTOSEAL®
BENTOSEAL®
BENTOSEAL®
VOLTEX® & VOLTEX DS® BENTONITE GEOTEXTILE WATERPROOFING
PRODUCT MANUAL
- 14 -
2.2 SOLDIER PILE & LAGGING RETAINING WALL
Verify the following substrate preparation work has been completed. Then install VOLTEX® following the property line installation guide-lines in Section 2.1 on page 12 and 13.
Preparation: Gaps between the wood lagging must be no wider than 25 mm. If the gaps between lagging are in excess of 25 mm, thegapsshouldbecompletelyfilledwithcementitiousgrout,wood,extrudedpolystyrene(min.2.75bar)orcompactedsoil(Figure2.4).Ifwaterisflowingthroughthelagging,athinpolyethylenesheetingcanbe installed over the area before VOLTEX® is installed.
In areas with large gaps (up to 63 mm) between lagging, AQUADRAIN sheet drainage composite can be installed over the lag-ging to provide a uniform surface to mount VOLTEX®(Figure2.5).Se-curely fasten AQUADRAIN to the lagging surface with washerhead nails before installing VOLTEX®. Gaps larger than 63 mm between lagging shouldbecompletelyfilledwithgrout,wood,extrudedpolystyrene (min.2.75bar)orcompactedsoilevenifAQUADRAIN is installed prior to VOLTEX®.Donotuseplywoodorothersurfacetreatmentoverlargelagginggapsthatleavesthecavityvoid.Details2.7through2.9onpage 15 illustrate the installation of VOLTEX® over the different wood lagging positions relative to the soldier piling.
Figure 2.4 – VOLTEX® installed directly to wood lagging with gapsfilled.(Cast-in-place concretewall)
Figure 2.5 – AQUADRAIN used to cover gaps in lagging less than63mm.(Cast-in-placeconcretewall)
Woodlagging
VOLTEX®
Grout caps larger than 25 mm
WATERSTOP-RX®
Woodlagging
VOLTEX®
AQUADRAIN
WATERSTOP-RX®
Figure 2.6 – Install VOLTEX® onto soldier pile and wood lagging retaining wall prior to cast-in-place concrete wall
BENTOSEAL® troweled over surface of VOLTEX® strip at both edges of the soldier pile
VOLTEX® strip centred over soldier pile BENTOSEAL®
TB-Boot over tie-back plate
VOLTEX® corner transition sheet installed horizontally oriented
VOLTEX® base wall course installed horizontally oriented
Wood lagging
Tie-back head
Soldier pile
100mm
INSTALL VOLTEX® OR VOLTEX DS® WITH DARK GRAY (WOVEN) GEOTEXTILE SIDE FACING INSTALLER
www.cetco.com
Wood lagging
Steel piling
VOLTEX® main course
VOLTEX® strip over pile prior to main course
WATERSTOP-RX® (75mmmin. coverage)
BENTOSEAL®
Cast-in-place concrete wall
Woodlagging
Steel piling
Retained earth
VOLTEX® main course
BENTOSEAL® between sheets of VOLTEX®
VOLTEX® strip over pile prior to main course
Fill gap with solid material
Cast-in-place concrete wall
Plate & bolts secure lagging
WATERSTOP-RX® (75mmmin. coverage)
Figure2.8–Laggingsecuredtoinsidesurfaceoffrontpileflange.Install VOLTEX® strip to cover mounting plates and bolts prior to maincourse(PlanView)
Figure2.7–Laggingsecuredtooutsidesurfaceoffrontpileflangeprovidingsmoothsurface(PlanView)
Figure2.9–Laggingsecuredtoinsidesurfaceofbackpileflange. Install BENTOSEAL® and VOLTEX® strip prior to main VOLTEX® course and inward BENTOSEAL®fillet.(PlanView)
Steel piling
Woodlagging
VOLTEX® main courseBENTOSEAL®,applytwofillets–onebefore VOLTEX® strip and one after main course
Cast-in-place concrete wall
WATERSTOP-RX® to exterior of cut rebar hole in steel piling
Rebar
VOLTEX® strip over pile prior to main VOLTEX® course
Anyvoidareamustbefilledwithwoodor solid material
WATERSTOP-RX® (75mmmin. coverage)
Figure2.10–WALLEXCAVATIONATGROUNDLEVEL–Cementitiousboardprotectswaterproofingduringexcavationandremovalofsteelpile top and wood lagging
VOLTEX® Cementitious board
Woodlagging
SteelH-pile,topremoved with excavation work
AQUADRAIN sheet drainCast-in-place concrete wall
VOLTEX® & VOLTEX DS® BENTONITE GEOTEXTILE WATERPROOFING
PRODUCT MANUAL
- 16 -
Figure 2.11 – Sheet pile interlock detail
Figure 2.12 – Install VOLTEX® onto steel sheet piling retaining wall with washer-head fasteners
2.3 STEEL SHEET PILING RETAINING WALL
Verify the following substrate preparation work has been completed. Then install VOLTEX® following the property line installation guide-lines in Section 2.1 on page 12 and 13. Special knurled washer-head fasteners are recommended to secure VOLTEX® to the steel sheet piling.
Preparation: Trowel a 12 mm thick layer of BENTOSEAL® along all sheet piling knuckles. Fill voids or cavities at tieback plates with ce-mentitious grout or compacted soils. If excessive water is penetrating the sheet piling knuckles, BENTOGROUT® can be injected to the out-sideoftheknuckletostopwaterflow(Figure2.11).ConsultCETCOfor BENTOGROUT® applications and installation guidelines.
Alternate Plywood MethodAlternatively, 12 mm plywood may be fastened to the sheet piling to createaflatsurfaceuponwhichVOLTEX® is fastened. All void spaces betweentheplywoodandsheetpilingmustbefilledwithcompactedearth or concrete. Apply VOLTEX® to plywood following “Property Line Construction” Guidelines in Section 2, Page 11.
BENTOGROUT® injected to exterior sideofsheetpileinterlock(perprojectrequirements)
Retained earth
Sheet piling
VOLTEX®BENTOSEAL®Sheet pile interlock
Cast-in-place concrete wall
VOLTEX® vertical seams should not occur at interlocking of sheet piling
VOLTEX®
WATERSTOP-RX® (75mmmin.coverage)
Retained earth
Steel sheet piling
Completelyfillareabehind plywood with compacted soil or concrete
Optional technique: plywood fastened to sheet piling to form flatsurfacetomountVOLTEX®
INSTALL VOLTEX® OR VOLTEX DS® WITH DARK GRAY (WOVEN) GEOTEXTILE SIDE FACING INSTALLER
www.cetco.com
2.4 EARTH FORMED SHOTCRETE RETAINING WALLVerify the following substrate preparation work has been completed. Then install VOLTEX® following the property line installation guide-lines in Section 2.1 on page 12 and 13.
Preparation: The surface of the earth formed diaphragm wall must besufficientlyplanartoprovideanadequatelysmoothsurfacetoap-ply VOLTEX®. VOLTEX® can be applied over large, relatively shallow indentations. The surface should not contain voids or sharp protru-sions in excess of 25 mm. Fill all voids with cementitious grout and remove protrusions prior to installing VOLTEX®(Figure2.15).
Figure 2.14 – Earth formed concrete retention wall with concretepilesupports(PlanView)
Figure 2.15 – VOLTEX® installation over an earth formed shotcrete retention wall prior to cast-in-place concrete wall
Figure 2.13 – Grout void area and remove protrusions to provide smooth surface for VOLTEX®
WATERSTOP-RX® 75 mm min. coverage)
Grout irregular areas
VOLTEX®
Cast-in-place concrete wall
Shotcrete retaining wall (non-structural)
Shotcrete retaining wall (non-structural)
VOLTEX®
WATERSTOP-RX®
Cast-in-place concrete wall
Retained earth Concrete pile
Retained earth
Shotcrete retaining wall (non-structural)
VOLTEX®
VOLTEX® corner transition sheet horizontally oriented
Grouted depressions and irregular surfaces
100mm
100mmINSTALL VOLTEX® OR VOLTEX DS® WITH DARK GRAY (WOVEN) GEOTEXTILE SIDE FACING INSTALLER
VOLTEX® & VOLTEX DS® BENTONITE GEOTEXTILE WATERPROOFING
PRODUCT MANUAL
- 18 -
Figure2.16–CutRockexcavationwithshotcreteappliedtoprovideasmoothsurfaceforwaterproofinginstallation
2.5 SECANT / CONTIGUOUS PILED WALLSVerify the following substrate preparation work has been completed. Then install VOLTEX® following the property line installation guide-lines in Section 2.1 on page 12 and 13.
Preparation: The surface of secant / contiguous piled and cut rock excavationwallsmustbesufficientlyplanartoprovideanadequately
smooth surface to apply VOLTEX®. VOLTEX® can be applied over large, relatively shallow indentations where VOLTEX® can conform tight against the surface. The surface should not contain voids or sharp protrusions in excess of 25 mm. Fill all large recesses between piles with cementitious grout prior to installing VOLTEX®(Figure2.17).Cutrock excavations typically require shotcrete or grout work to provide acceptable surface to install VOLTEX®(Figure2.16).
Figure 2.17 – Fill in recesses between cast piles with grout toprovidesmoothsurface(PlanView)
Retained earth side Pile caisson
VOLTEX® Grout recesses
Cut rock formation from excavation
Shotcrete applied to cut rock surface(non-structural)
VOLTEX® TB-6SNVOLTEX®
WATERSTOP-RX®
BENTOSEAL® detailing
Contiguous piled wall
VOLTEX® fastened to face of piled wall
INSTALL VOLTEX® WITH DARK GREY (WOVEN) GEOTEXTILE FACING INSTALLER
Reinforced concrete wall (min150mmthick)
WATERSTOP-RX®101 (min75mmcover)
BENTOSEAL® fillet (38mmx38mm)
Concrete blinding
Figure2.18–PropertyLineContiguousPiledWallDetail
www.cetco.com
Install VOLTEX®orVOLTEXDS®withthedarkgray(woven)geotextileside against the concrete wall on cast-inplace concrete foundation walls prior to backfilling. VOLTEX® may be applied as soon as the forms are removed. It is not necessary to wait for the concrete to completely cure. Use VOLTEX® with concrete cast with conventional forms that produce smooth surface.
3.1 SURFACE PREPARATIONFooting should be swept clean of silt, rocks and debris to provide VOLTEX® with direct contact to the concrete in the application area. The wall surface must be properly prepared before VOLTEX® is in-stalled.Areasofsurfacehoneycombingorvoidsshouldbefilledwithcementitious grout or BENTOSEAL®. Protrusions of over 6 mm should be knocked off smooth with the concrete surface. Concrete work should includecompletelyfilling taper-tieholeswithnon-shrinkce-mentitious grout and a piece of WATERSTOP-RX® centred in the wall (Figure3.1).ApplyBENTOSEAL® over exterior grouted surface of all formtieholes(Figure3.1).
3.2 INSTALLATIONBeforeinstallingthefirstcourseofVOLTEX®,installBENTOSEALfillet(min38mmx38mm)atthewall/footinginsidecorner(Figure3.2).
Beginning at the bottom corner of the wall, install VOLTEX® horizon-tally oriented with 1.5 m on one wall and the remainder around the cornerontheotherwallsurface(Figure3.2).CutthebottomedgeofVOLTEX®at thecorneraminimumof150mmsothatVOLTEX® can be extended onto the footing. Fasten VOLTEX® into position with washerheadfastenersmaximum600mmoncentre.Thencutandinstall a VOLTEX® section over the uncovered footing corner area. Apply BENTOSEAL® at the VOLTEX® section to VOLTEX®overlaps.(Figure3.2).
Install adjacent VOLTEX® rolls of the bottom course horizontally ori-ented.Eachrollshouldoverlaptheprecedingrollaminimum100mmandshouldextendontothefootingaminimum150mm.Atverticalinsidecornersapplyacontinuous19mmfilletofBENTOSEAL® di-rectly in the corner prior to installing VOLTEX®(Figure3.3).Staggerallverticaloverlapjointsaminimumof300mm(Figure3.4).Whenhy-drostatic conditions exist, the vertical wall VOLTEX® should cover the entire footingandoverlap theunderslabwaterproofingaminimum150mm(Figure3.6).TapeallVOLTEXDS® membrane overlap seams with CETCO Seamtape.
SECTION 3 BACKFILLED WALLS
Figure 3.2 – Start VOLTEX® at the corner horizontally. Place cut sec-tion at corner and apply BENTOSEAL® at overlaps
Figure 3.1 – Concrete form tie details
Figure3.3–ApplyfilletofBENTOSEAL® to inside corner
Snap-Tie Taper-Tie
Non-shrink groutConcrete Tile BENTOSEAL® exterior
face of form tie
Non-shrink grout
VOLTEX®
Install VOLTEX® around corner
BENTOSEAL®filletunder VOLTEX®
VOLTEX®
BENTOSEAL®
Install VOLTEX® to fitcorner
Install VOLTEX® to fitcorner
19mmfilletofBENTOSEAL®
Inside corner of cast-in-place concrete wall
WATERSTOP-RX®
VOLTEX® & VOLTEX DS® BENTONITE GEOTEXTILE WATERPROOFING
PRODUCT MANUAL
- 20 -
Figure 3.4 – VOLTEX®installedoncast-in-placebackfilledwall,overlapedges100mmandstaggerverticalendlaps
Backfill: Theexcavatedareashouldbebackfilledandcompactedpromptly after VOLTEX®isinstalled.Useplacedbackfillasaplatformin applying succeeding VOLTEX®courses.Thebackfillmustbecom-pactedtoaminimum85%ModifiedProctordensity.Backfillshouldconsistofcompactiblesoilsorangularaggerate(19mmorless)freeofdebris,sharpobjects,andstonelargerthan19mm.Whenbackfillcannot be placed immediately protect membrane from precipitation and debris by sealing edges to concrete substrate with CETCO SEAMTAPE or tooled bead of CETSEAL. This temporary temination can be left in place covered by subsequent membrane overlap.
Figure3.6–Stepbystepdetailofoutsidewallbasecornerinstallation(hydrostaticcondition)
Figure3.5–MinimumVOLTEXDS®overlapdetail;tapeVOLTEXDS® seams
Min. 100mm
Cast-in-place concrete wall
Washer-headmechanicalfastener
VOLTEXDS®
CETCO Seamtape
Step 1. Step 2.
Step 3. Step 4.
VOLTEX® turned up from underslab
Trowel BENTOSEAL® at corner
CutandfoldfirstVOLTEX® section
Cut and fold second VOLTEX® section
Place third VOLTEX® piece over the previous two sections
Trowel BENTOSEAL® over grouted form-tie holes
VOLTEX®
BENTOSEAL®filletplacedunder VOLTEX® at transition at footing
Stagger end seams a minimum 300mm
Mechanically fasten VOLTEX® maximum 600 mm on centre
Install CETCO Seamtape atVOLTEXDS® membrane overlaps
100mmoverlap
WATERSTOP-RX® (min.75mmcoverage)
150mm
INSTALL VOLTEX® OR VOLTEX DS® WITH DARK GRAY (WOVEN) GEOTEXTILE SIDE AGAINST THE CONCRETE WALL
Term bar and BENTOSEAL®
www.cetco.com
3.3 BACKFILLED WALL PENETRATIONS
Cut VOLTEX® to closely fit around penetrations. After installing VOLTEX®,trowelaminimum19mmthickfilletofBENTOSEAL® around thepenetrationtocompletelyfillanyspacebetweenthepenetrationand the VOLTEX® edge. The BENTOSEAL® should extend onto the penetration 38 mm and cover VOLTEX®’sedge(Figure3.7).Inareaswhere multiple penetrations are close together, it may be impracti-cal to cut VOLTEX®tofitaroundbaseofeachpenetration.Therefore,applya19mmthickfilletofBENTOSEAL® around each penetration andcovertheentiresurfacebetweenthepenetrations(Figure3.8).Extend BENTOSEAL® 38 mm onto the penetrations.
Figure 3.7 – Single penetration cast-in-place wall detail
Figure3.10–InstallVOLTEX® between penetrations with accessibility. Trowel BENTOSEAL® around penetrations
Figure 3.8 – Cut VOLTEX®tofitaroundpenetrations
Figure3.9–Closemultiplepenetrations.TrowelBENTOSEAL® around and between penetrations
VOLTEX®
Cast-in-place concrete wall
BENTOSEAL® troweled around penetration
Pipe
WATERSTOP-RX® (min.75mmcoverage)
VOLTEX® Apply BENTOSEAL® to cut out area
VOLTEX® cut out around multiple penetrations
WATERSTOP-RX®
VOLTEX®
BENTOSEAL®
Pipe
BENTOSEAL®
Pipe
VOLTEX®
WATERSTOP-RX®
WATERSTOP-RX®
VOLTEX®
BENTOSEAL®
Pipe
BENTOSEAL®
VOLTEX®
BENTOSEAL®
Pipe
VOLTEX®
WATERSTOP-RX®
VOLTEX® & VOLTEX DS® BENTONITE GEOTEXTILE WATERPROOFING
PRODUCT MANUAL
- 22 -
3.4 GROUND LEVEL TERMINATIONS
Terminate VOLTEX®membrane300mmbelow finished ground el-evationwithwasher-head fastenersmaximum300mmoncentre.InstallCETBIT300flashingtoprimedconcretesubstratewithbottom
edge overlapping top edge of VOLTEX®membraneminimum100mm.Overlapallrollendsaminimum100mmtoformacontinuousflash-ing.Heightofflashingshallbeperprojectdetailsandspecifications.InstallarigidterminationbaralongtopedgeofCETBIT300;fastenedmaximum300mmoncentre.Completegroundlevelterminationde-tail with tooled bead of CETSEAL along the top edge, at all penetra-tionsthroughtheflashing,andallexposedoverlapseams.Groundlevel terminations are illustrated in Figures 3.11 and 3.12.
3.5 MASONRY BLOCK WALLSVOLTEX®isnotrecommendedforwaterproofingmasonryblockwalls.Consult with CETCO regarding recommended products and installa-tion guidelines for masonry block walls.
4.1 PRECAST CONCRETE CONSTRUCTIONConsult CETCO regarding products and special installation guidelines for precast concrete plank decks, precast earth covered roofs, and precast wall construction.
4.2 CONTAMINATED CONDITIONSWhere contaminated ground-water conditions exist, use VOLTEX CR®/VOLTEX DSCR® with contaminant resistant sodium bentonite. VOLTEX CR®/VOLTEXDSCR® resist higher levels of the fol-lowing contaminants: nitrates, phosphates, chlorides, sulfates, lime and organic solvents. Verify suitability of product by submitting a site watersampletoCETCOforWaterCompatibilityTestingpriortoinstal-lation. Contact CETCO for further details.
Forcompatibilitytesting,providetwo(2)litresofsitegroundwaterina clean, unbreakable container. Ship water sample to: Birkenhead Road,Wallasey,UKCH447UB(OR)Szczytno12-100,Korpele13A–Strefa,Poland (OR)Cheste (Valencia)46380,Crta.CV-50,Spain,ATTN: BMG Field Services. Upon analysis, CETCO will provide a writ-ten report evaluating the water’s compatibility with VOLTEX® and rec-ommend any special product and/or installation requirements.
SECTION 4 SPECIAL CONDITIONS
IMPORTANT NOTICEFOR SHOTCRETE, PRECAST CONCRETE, EXPANSION JOINTS AND OTHER APPLICATIONS NOT COVERED IN THIS MANUAL, CONTACT CETCO FOR TECHNICAL ASSIS-TANCE AND INSTALLATION GUIDELINES.
Figure3.11–Terminationatfinishedgroundlevel
CETBIT300
CETBIT300
VOLTEX®
Compactedbackfill see CETCO technical data sheets for guidelines
CETCO approved protection course
Tooled CETSEAL bead
Fasten300mmMAXOC
INSTALL VOLTEX® WITH DARK GRAY (WOVEN) GEOTEXTILE AGAINST CONCRETE
Figure 3.12 – Termination at ground level with brick skin
Cavitytray(byothers)
BENTOSEAL®fillet (5mmx75mm)
Compactedbackfill see CETCO technical data sheets for guidelines
VOLTEX®
Termination bar fasten300mmc/c
DPC(byothers) lapped150mm over VOLTEX®
150mm
150mm
150mm
INSTALL VOLTEX® WITH DARK GRAY (WOVEN) GEOTEXTILE AGAINST CONCRETE
150mmmin
www.cetco.com
The information and data contained herein is believed to be accurate and reliable.Specificationsandotherinformationcontainedhereinsupersedeall previously printed material and are subject to change without notice. Manufacturer’s warranty of installed system is available. Contact seller for terms and sample documents including all limitations. All goods sold by seller are warranted to be free from defects in material and workmanship. The foregoing warranty is in lieu of and excludes all other warranties not expressly set forth herein, whether expressed or implied by operation of law or otherwise including but not limited to any implied warranties of mer-chantabilityorfitness.Seller shall not be liable for incidental or consequential losses, damages or expenses, directly or indirectly arising from the sale, handling or use of the goods, or from any other cause relating thereto, and seller’s liability hereunderinanycaseisexpresslylimitedtothereplacement(intheform
originallyshipped)ofgoodsnotcomplyingwiththisagreementoratseller’selection, to the repayment of, or crediting buyer with, an amount equal to the purchase price of such goods, whether such claims are for breach of warranty or negligence.Any claim by buyer with reference to the goods sold hereunder for any cause shall be deemed waived by buyer unless submitted to seller in writ-ingwithinthirty(30)daysfromthedatebuyerdiscoveredorshouldofdis-covered, any claimed breach. Materials should be inspected and tested by purchaser prior to their use if productqualityissubjecttoverificationaftershipment.Performanceguar-antees are normally supplied by the applicator.
Note: VOLTEX®waterproofingsystemisnotanexpansionjointmaterial.
LIMITED WARRANTY
PRODUCT TABLEPRODUCT DESCRIPTION
VOLTEX® Bentonitegeotextilewaterproofingmembranewithstandardsodiumbentonite
VOLTEX CR® Bentonitegeotextilewaterproofingmembranewithcontaminantresistantsodiumbentonite
VOLTEXDS® Bentonitegeotextilewaterproofingmembranewithstandardsodiumbentoniteandapolyethylenelinercomponent
VOLTEXDSCR® Bentonitegeotextilewaterproofingmembranewithcontaminantresistantsodiumbentoniteandapolyethylenelinercomponent
IMPORTANT NOTICEContact CETCO for verification of specification and instal-lation requirements to comply for eligibility of HydroShield Warranty.
IMPORTANT: The information contained herein supersedes all previous printed versions, and is believed to be accurate and reliable. For the most up-to-date information, please contact CETCO sales team. CETCO accepts no responsibility for the results obtained through application of this product. CETCO reserves the right to update information without notice.
FORM:PM_VOLTEX_EMEA_EN_201605_V6
www.cetco.com | [email protected]
UPDATED:MAY2016
www.cetco.com
86/1650
1488-CPR-0030/Z1035-CPD-018658
EN13491:2004+EN13491:2004/A1:2006