VRV Outdoor Unit - Models RXYQ / REYQ
Daikin is launching its new 6-Ton VRV outdoor units in Heat Pump (RXYQ72MTJU) and Heat Recovery (REYQ72MTJU) configurations. This unit extends the range of condensing units now allowing the combination from 6 Tons to 16 Tons, making the VRV system more flexible than ever. Featuring R-410A and inverter “variable speed” compressor, higher energy efficiency is achieved as well as a lower installation cost. Combined with the wide range of Daikin indoor units, the VRV system provides absolute comfort to offices, retail stores, restaurants, hotels and beyond.
Inverter Heat Pump and Heat Recovery Units6 / 8 / 12 / 14 / 16 Tons Inverter Heat Pump units allow for either cooling or heating from one system.
Inverter Heat Recovery units provide simultaneous operation of heating and cooling with greater energy efficiency.
Up to 20 indoor zones can be controlled from a single outdoor unit using a dual compressor outdoor unit comprised of Daikin’s “inverter” variable speed and
fixed speed scroll compressors.
Continuous operation 0°F DB (-5°F WB) - 64°F DB (60°F WB) in heating mode and 23°F DB - 110°F DB in cooling mode.
Daikin’s optimized scroll compressor designed for R-410A provides a quiet, reliable energy efficient operation.
Daikin’s oil-equalizing technology assures maximum reliability and flexibility to the VRV system with piping lengths of up to 492 ft., for a total networked length of up to 1,000 ft.
All VRV condensing units are connectable to the complete line of VRV indoor units including 8 different styles for a total of 36 individual units.
Anticorrosion treatment standard on exterior metal parts and heat exchanger.
Available in 208-230V / 3-phase power.
Fully compatible with the complete Daikin control suite including Intelligent Touch controller, and the LonWorks® and BACnet® gateways1.
INVERTER
R-410A
12/14/16 Tons
48-7/8” 48-7/8” 30-1/8”
64”
6/8 Tons
48-7/8” 30-1/8”
64”
1. LONWORKS® and LON® are registered trademarks of Echelon Corporation. BACnet® is a Data Communication Protocol for Building Automation and Control Networks, developed under the auspices of the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this brochure without notice and without incurring any obligations.)
Daikin AC (Americas), Inc. 1645 Wallace Drive, Suite 110 Carrollton, TX 75006 866-4DAIKIN www.daikinac.com
#VRV6T SS 07/06
Outdoor Unit Combination Capabilities
Models Included
Cooling CapacityCooling Input PowerHeating CapacityHeating Input PowerOperating Range - CoolingOperating Range - HeatingPowerSound Pressure Level @ 3ft.Airflow H/LVertical Pipe LengthActual Pipe LengthEquivalent Pipe LengthTotal Pipe LengthMax. No. Of Indoor UnitsCinnection RatioWeightDimensions (H x W x D)
Models Included
Cooling CapacityCooling Input PowerHeating CapacityHeating Input PowerOperating Range - CoolingOperating Range - HeatingPowerSound Pressure Level @ 3ft.Airflow H/LVertical Pipe LengthActual Pipe LengthEquivalent Pipe LengthTotal Pipe LengthMax. No. Of Indoor UnitsConnection RatioWeightDimensions (H x W x D)
Btu/h kW
Btu/hkW (Btu/h)
°FDB°FDB/°FWB
V/Ph/HzdB(A)cfmft.ft.ft.ft.
%lbs. in.
RXYQ72MTJU
72,0005.7
80,0006.6 (22,519)
23 - 1100 - 64/-5 - 60208-230/3/60
607,400164492575
1,00013
70-130666
64 x 48 7/8 x 30 1/8
RXYQ96MTJU
96,0008.67
108,0009.19 (31,356)
23 - 1100 - 64/-5 - 60208-230/3/60
607,400164492575
1,00016
50-130666
64 x 48 7/8 x 30 1/8
RXYQ72MTJU +RXYQ72MTJU
144,00011.4
160,00013.2 (45,038)
23 - 1100 - 64/-5 - 60208-230/3/60
637,400 + 7,400
164492575
1,00020
70-130666 + 666
64 x 48 7/8 (x2) x 30 1/8
RXYQ72MTJU +RXYQ96MTJU
168,00014.4
188,00015.8 (53,910)
23 - 1100 - 64/-5 - 60208-230/3/60
637,400 + 7,400
164492575
1,00020
70-130666 + 666
64 x 48 7/8 (x2) x 30 1/8
RXYQ96MTJU +RXYQ96MTJU
192,00017.3
216,00018.4 (62,781)
23 - 1100 - 64/-5 - 60208-230/3/60
637,400 + 7,400
164492 575
1,00020
50-130666 + 666
64 x 48 7/8 (x2) x 30 1/8
Outdoor Unit - Heat Pump
Outdoor Unit - Heat Recovery
6.0 Ton 8.0 Ton 12.0 Ton 14.0 Ton 16.0 Ton
Btu/h kW
Btu/hkW (Btu/h)
°FDB°FDB/°FWB
V/Ph/HzdB(A)cfmft.ft.ft.ft.
%lbs. in.
REYQ72MTJU
72,0005.7
80,0006.6 (22,519)
23 - 1100 - 64/-5 - 60208-230/3/60
607,400164492575
1,00013
70-130666
64 x 48 7/8 x 30 1/8
REYQ96MTJU
96,0008.67
108,0009.19 (31,356)
23 - 1100 - 64/-5 - 60208-230/3/60
607,400164492575
1,00016
50-130666
64 x 48 7/8 x 30 1/8
REYQ72MTJU +REYQ72MTJU
144,00011.4
160,00013.2 (45,038)
23 - 1100 - 64/-5 - 60208-230/3/60
637,400 + 7,400
164492575
1,00020
70-130666 + 666
64 x 48 7/8 (x2) x 30 1/8
REYQ72MTJU +REYQ96MTJU
168,00014.4
188,00015.8 (53,910)
23 - 1100 - 64/-5 - 60208-230/3/60
637,400 + 7,400
164492575
1,00020
70-130666 + 666
64 x 48 7/8 (x2) x 30 1/8
REYQ96MTJU +REYQ96MTJU
192,00017.3
216,00018.4 (62,781)
23 - 1100 - 64/-5 - 60208-230/3/60
637,400 + 7,400
164492575
1,00020
50-130666 + 666
64 x 48 7/8 (x2) x 30 1/8
6.0 Ton 8.0 Ton 12.0 Ton 14.0 Ton 16.0 Ton
11 3/4 or more
11 3/4 or more
11 3/4 or more
Front
Front
Front
Front
19 5/8 or more
19 5/8 or more
19 5/8 or more
23 5/8 or more
3/4 or more 3/8 or more
3/8 or more3/8 or more
(in.)
(in.)
(in.)
3/8 or more
3/8 or more 3/8 or more
3/8 or more 3/4 or more
3/4 or more
3/4 or more
Installation Space Branch Selector
Please refer to the installation manual for detailed instructions.
Up to 3.0 Ton Up to 5.0 Ton
ModelConnection Capacity
Weight lbs.Dimensions in.
5/8” Flare (Suction Gas)1/2” Flare (Discharge Gas)
3/8” Flare (Liquid)5/8” Flare (Gas)
3/8” Flare (Liquid)
BSVQ36MVJU36,000 Btu/h
BSVQ60MVJU60,000 Btu/h
187 1/4 x 12 1/4 x 11
187 1/4 x 12 1/4 x 11
Pipe WorkConnections
Outdoor UnitSide
(For use with REYQ Condensing Units)
Indoor UnitSide
For more information, please refer to the VRV catalogue and Engineering Data manual available.
For more information, please refer to the VRV brochure and Engineering Data Manuals available.