vsd calculator for pumps

10
VS Inputs Nameplate Horsepower Nameplate Efficiency Motor Load at Pump Design GPM Duty Cycle Percent of Capacity Per (cfm) 30 % 50 % 70 % 90 % Outputs Energy and Cost savings Current Annual Energy use VSD Annual Energy Use Annual Energy Savings Annual Cost Savings References and Equations References: • For the energy savings analysis, this tool u the operating characteristics of various fan Westinghouse publication, Bulliten B-851, F/ Final economic analysis should be based on a

Upload: khaldoon-alnashi

Post on 11-Dec-2015

13 views

Category:

Documents


0 download

DESCRIPTION

vsd

TRANSCRIPT

VSD Calculator for Pumps

Inputs

Nameplate Horsepower

Nameplate Efficiency

Motor Load at Pump Design GPM

Duty Cycle

Percent of Capacity Percent of Time at

(cfm) this Capacity

30 % 15 %

50 % 55 %

70 % 25 %

90 % 5 %

Outputs

Energy and Cost savings

Current Annual Energy use kWh/yr

VSD Annual Energy Use kWh/yr

Annual Energy Savings kWh/yr

Annual Cost Savings $/yr

References and Equations

References:

• For the energy savings analysis, this tool used power curves developed from data obtained by measuring

the operating characteristics of various fans and from information provided in "Flow Control", a

Westinghouse publication, Bulliten B-851, F/86/Rev-CMS 8121. The curves are representative, not precise.

Final economic analysis should be based on actual power (kW) measurements of the pumping system.

Constants:

Polynomial Coefficients A1, A2, A3 and A4:

A1 A2 A3 A4

1 55.21240 0.63700 -0.00190 0.00000

2 16.39683 -0.05647 0.01237 -0.00003

3 13.51137 0.34467 0.01269 -0.00007

4 102.00000 0.00000 0.00000 0.00000

VSD 27.44751 -1.00853 0.01762 0.00000

Equations:

Power at Design GPM = Nameplate Horsepower × Conversion Constant (kW/hp) × Motor Load at Design GPM / Nameplate

Efficiency

VSD Power (kW) = Percent of Design kW for VSD × (Power at Design CFM / 100)

VSD Energy (kWh) = VSD Power (kW) × (Percent of time at this Capacity / 100) × Operating Hours

Annual Cost Savings = Annual Energy Savings × Cost of Electricity

AcknowledgementsThis tool was created by the Bonneville Power Administration (BPA). For more information on BPA, visit their website at www.bpa.gov.

Conversion Constant (kW/hp) = 0.746 

Type of Flow Contorl

Computed for each capacity level: 

Percent of Design kW = A1 + (A2 × Capacity) + (A3 × (Capacity2)) + (A4 × (Capacity3)) 

Percent of Design kW for VSD = A1 + (A2 × Capacity) + (A3 × (Capacity2)) + (A4 × (Capacity3))

Current Power (kW) = Percent of Design kW × (Power at Design CFM / 100) 

Current Energy (kWh) = Current Power (kW) × (Percent of time at this Capacity / 100) × Operating Hours 

Current Annual Energy Use = sum of all Current Energy (kWh) 

VSD Annual Energy Use = sum of all VSD Energy (kWh) 

Annual Energy Savings = Current Annual Energy Use – VSD Annual Energy Use 

VSD Calculator for Pumps

hp Annual Operating Hours

% Type of Flow Control

% Cost of Electricity $/kWh

pump_number

###

power of design GPM

###

A values for current fan selection

A1

A2

A3

A4

Percent of design kW

###

###

###

###

###

###

###

###

###

###

###

###

• For the energy savings analysis, this tool used power curves developed from data obtained by measuring ###

the operating characteristics of various fans and from information provided in "Flow Control", a

Westinghouse publication, Bulliten B-851, F/86/Rev-CMS 8121. The curves are representative, not precise. ###

Final economic analysis should be based on actual power (kW) measurements of the pumping system. ###

###

###

Power at Design GPM = Nameplate Horsepower × Conversion Constant (kW/hp) × Motor Load at Design GPM / Nameplate

VSD Energy (kWh) = VSD Power (kW) × (Percent of time at this Capacity / 100) × Operating Hours

This tool was created by the Bonneville Power Administration (BPA). For more information on BPA, visit their website at www.bpa.gov.

)) + (A4 × (Capacity3)) 

)) + (A4 × (Capacity3))

Current Power (kW) = Percent of Design kW × (Power at Design CFM / 100) 

Current Energy (kWh) = Current Power (kW) × (Percent of time at this Capacity / 100) × Operating Hours 

Annual Energy Savings = Current Annual Energy Use – VSD Annual Energy Use 

Instructions for using the VSD Calculator for Pumps Tool1 Select the "Tool" tab located in the bottom left corner of this window highlighted in red.

2 Enter the Nameplate Horsepower, Nameplate Efficiency, Motor Load at Pump Design GPM,

Annual Operating Hours, and Cost of Electricty

3 Select the Type of Flow Control from the drop down list, like the following:

4 Select a standard Duty cycle from the drop down list, like the following:

Alternativly, you can enter your own values into the Percent of Capacity and Percent of time

at this Capacity table.

*Note: If you enter your own values into the Percent of time at this Capacity table, they must

equal 100% for the claculations to continue.

** Note: once you have entered your own values for the "Percent of Time at this Capacity",

if you want to use the generic "High Pump Loading, Low Pump Loading", you

must open a new copy of the workbook downloaded from the wesite.

KeyMotor Load at Design CFM

Cost of Electricity

Duty Cycle

Example, if 80 bhp is required at the design cfm and a 100 hp motor is installed, the motor loading is 80% at pump design cfm.

One method to estimate this would be to take an Amp reading when the fan/pump is operating at design cfm and divide this amp reading by the motor's full load amp value.

The dollar amount per kilowatt hour of power consumed. This value can be found on your utility bill.

The percent of time that the pump spends in an active state. Selecting high and low will populate the table below with standard system specifications. The values in the table are editable. The "low load" duty cycle offers greater ASD energy savings potential than the "high load" duty cycle.

Percent of Capacity This is the estimated percentage of the pump’s design flowrate in cubic feet per minute.

Percent of time at this capacity

This is the estimated percentage of the year that the pump is expected to operate at the flowrate specified in the adjacent column.

Instructions for using the VSD Calculator for Pumps ToolSelect the "Tool" tab located in the bottom left corner of this window highlighted in red.

Enter the Nameplate Horsepower, Nameplate Efficiency, Motor Load at Pump Design GPM,

Select the Type of Flow Control from the drop down list, like the following:

Alternativly, you can enter your own values into the Percent of Capacity and Percent of time

*Note: If you enter your own values into the Percent of time at this Capacity table, they must

** Note: once you have entered your own values for the "Percent of Time at this Capacity",

if you want to use the generic "High Pump Loading, Low Pump Loading", you

must open a new copy of the workbook downloaded from the wesite.

KeyExample, if 80 bhp is required at the design cfm and a 100 hp motor is installed, the motor loading is 80% at pump

One method to estimate this would be to take an Amp reading when the fan/pump is operating at design cfm and divide this amp reading by the motor's full load amp value.

The dollar amount per kilowatt hour of power consumed. This value can be found on your utility bill.

The percent of time that the pump spends in an active state. Selecting high and low will populate the table below with standard system specifications. The values in the table are editable. The "low load" duty cycle offers greater ASD energy savings potential than the "high load" duty

This is the estimated percentage of the pump’s design

This is the estimated percentage of the year that the pump is expected to operate at the flowrate specified in the