w o r k i n g o n b e t t e r s o l u t i o n s1 chroma t&m bu product & marketing div. ~...
TRANSCRIPT
![Page 1: W o r k i n g O n B e t t e r S o l u t i o n s1 Chroma T&M BU Product & Marketing Div. ~ 周晏加 ~ Limits for harmonic current emissions Limits for harmonic](https://reader031.vdocuments.net/reader031/viewer/2022032803/56649e1b5503460f94b09af2/html5/thumbnails/1.jpg)
W o r k i n g O n B e t t e r S o l u t i o n s 1
Chroma T&M BU Product & Marketing Div. ~ 周晏加 ~
Limits for harmonic current emissionsLimits for harmonic current emissions(equipment input current <=16A per phase)(equipment input current <=16A per phase)
![Page 2: W o r k i n g O n B e t t e r S o l u t i o n s1 Chroma T&M BU Product & Marketing Div. ~ 周晏加 ~ Limits for harmonic current emissions Limits for harmonic](https://reader031.vdocuments.net/reader031/viewer/2022032803/56649e1b5503460f94b09af2/html5/thumbnails/2.jpg)
W o r k i n g O n B e t t e r S o l u t i o n s 2
• Background and History• Test instruments• Classification of equipment• Test methods• Test instruments• Limits• Test conditions
OUTLINE
![Page 3: W o r k i n g O n B e t t e r S o l u t i o n s1 Chroma T&M BU Product & Marketing Div. ~ 周晏加 ~ Limits for harmonic current emissions Limits for harmonic](https://reader031.vdocuments.net/reader031/viewer/2022032803/56649e1b5503460f94b09af2/html5/thumbnails/3.jpg)
W o r k i n g O n B e t t e r S o l u t i o n s 3
BackgroundBackground
Too much Harmonic Current pollute Main power
![Page 4: W o r k i n g O n B e t t e r S o l u t i o n s1 Chroma T&M BU Product & Marketing Div. ~ 周晏加 ~ Limits for harmonic current emissions Limits for harmonic](https://reader031.vdocuments.net/reader031/viewer/2022032803/56649e1b5503460f94b09af2/html5/thumbnails/4.jpg)
W o r k i n g O n B e t t e r S o l u t i o n s 4
IEC 555-2 ( ~1/1/2001)IEC 555-2 ( ~1/1/2001)
HistoryHistory
IEC 61000-3-2:IEC 61000-3-2:1995 (1/1/2001 ~1/1/2004)1995 (1/1/2001 ~1/1/2004) IEC 61000-3-2 A14 IEC 61000-3-2 A14 (1/1/2001 ~ )(1/1/2001 ~ )
GGB17625.1-1998 B17625.1-1998 中國中國 33CC 認證項目 認證項目 (1/5/2002 (1/5/2002 開始開始 , 1/5/2003, 1/5/2003 強制 強制 ))
![Page 5: W o r k i n g O n B e t t e r S o l u t i o n s1 Chroma T&M BU Product & Marketing Div. ~ 周晏加 ~ Limits for harmonic current emissions Limits for harmonic](https://reader031.vdocuments.net/reader031/viewer/2022032803/56649e1b5503460f94b09af2/html5/thumbnails/5.jpg)
W o r k i n g O n B e t t e r S o l u t i o n s 5
Chroma Solution for IEC61000-3-2Chroma Solution for IEC61000-3-2
![Page 6: W o r k i n g O n B e t t e r S o l u t i o n s1 Chroma T&M BU Product & Marketing Div. ~ 周晏加 ~ Limits for harmonic current emissions Limits for harmonic](https://reader031.vdocuments.net/reader031/viewer/2022032803/56649e1b5503460f94b09af2/html5/thumbnails/6.jpg)
W o r k i n g O n B e t t e r S o l u t i o n s 6
Voltage accuracy : 2.0 % or better
Frequency accuracy : 0.5 % or better
Power Capacity : 230V x 16A = 3680VA
Voltage Harmonic distortion (With EUT connected): 0.9 % for harmonic of order 3 0.4 % for harmonic of order 5 0.3 % for harmonic of order 7 0.2 % for harmonic of order 9 0.2 % for even harmonic of order from 2 to 10 0.1 % for harmonic of order 11 to 40
AAC Power RequirementsC Power Requirements
![Page 7: W o r k i n g O n B e t t e r S o l u t i o n s1 Chroma T&M BU Product & Marketing Div. ~ 周晏加 ~ Limits for harmonic current emissions Limits for harmonic](https://reader031.vdocuments.net/reader031/viewer/2022032803/56649e1b5503460f94b09af2/html5/thumbnails/7.jpg)
W o r k i n g O n B e t t e r S o l u t i o n s 7
ZZs and Zm are not specified. But have to be s and Zm are not specified. But have to be low to suit the test requirements.low to suit the test requirements.
AC source, Meter and Cable must good.AC source, Meter and Cable must good.
G
Zs
Zm
EUTAC source
Meter
Equipment
AAC Power RequirementsC Power Requirements
![Page 8: W o r k i n g O n B e t t e r S o l u t i o n s1 Chroma T&M BU Product & Marketing Div. ~ 周晏加 ~ Limits for harmonic current emissions Limits for harmonic](https://reader031.vdocuments.net/reader031/viewer/2022032803/56649e1b5503460f94b09af2/html5/thumbnails/8.jpg)
W o r k i n g O n B e t t e r S o l u t i o n s 8
Chroma Programmable AC Source Spec. :
Voltage accuracy : 0.2 % + 0.2 %F.S < 2%
Frequency accuracy : 0.15 % < 0.5%
Power Capacity : For different EUT
For each test, Check Voltage Harmonic Distortion
Model 6560 (6KVA), Model 61505 (4KVA)Model 6560 (6KVA), Model 61505 (4KVA)
Chroma Programmable AC SourceChroma Programmable AC Source
![Page 9: W o r k i n g O n B e t t e r S o l u t i o n s1 Chroma T&M BU Product & Marketing Div. ~ 周晏加 ~ Limits for harmonic current emissions Limits for harmonic](https://reader031.vdocuments.net/reader031/viewer/2022032803/56649e1b5503460f94b09af2/html5/thumbnails/9.jpg)
W o r k i n g O n B e t t e r S o l u t i o n s 9
•Total error in steady-state mode : Shall not exceed 5% of permissible limit or 0.2 % of rated current of EUT
•Maximum relative deviation between f1 and synchronise frequency : Equal to or lower than 0.03 % of f1
•Attenuation of anti-aliasing filter : 50 dB at least
Chroma Power Analyzer 6630Chroma Power Analyzer 6630
![Page 10: W o r k i n g O n B e t t e r S o l u t i o n s1 Chroma T&M BU Product & Marketing Div. ~ 周晏加 ~ Limits for harmonic current emissions Limits for harmonic](https://reader031.vdocuments.net/reader031/viewer/2022032803/56649e1b5503460f94b09af2/html5/thumbnails/10.jpg)
W o r k i n g O n B e t t e r S o l u t i o n s 10
Balancethree-phaseequipment
Y
N
Equipmenthaving special
wave shape andP <= 600 W
Y
N
Lightingequipment Y
N
Portabletools Y
N
N
Class B
*Motordriven
Class C
* Input power > 25W
Class D
* Input power > 75W
Class A
N
Y
IEC 61000-3-2 IEC 61000-3-2 Classification
![Page 11: W o r k i n g O n B e t t e r S o l u t i o n s1 Chroma T&M BU Product & Marketing Div. ~ 周晏加 ~ Limits for harmonic current emissions Limits for harmonic](https://reader031.vdocuments.net/reader031/viewer/2022032803/56649e1b5503460f94b09af2/html5/thumbnails/11.jpg)
W o r k i n g O n B e t t e r S o l u t i o n s 11
Classification A
0.35
![Page 12: W o r k i n g O n B e t t e r S o l u t i o n s1 Chroma T&M BU Product & Marketing Div. ~ 周晏加 ~ Limits for harmonic current emissions Limits for harmonic](https://reader031.vdocuments.net/reader031/viewer/2022032803/56649e1b5503460f94b09af2/html5/thumbnails/12.jpg)
W o r k i n g O n B e t t e r S o l u t i o n s 12
Classification D
0.35
![Page 13: W o r k i n g O n B e t t e r S o l u t i o n s1 Chroma T&M BU Product & Marketing Div. ~ 周晏加 ~ Limits for harmonic current emissions Limits for harmonic](https://reader031.vdocuments.net/reader031/viewer/2022032803/56649e1b5503460f94b09af2/html5/thumbnails/13.jpg)
W o r k i n g O n B e t t e r S o l u t i o n s 13
Class A
Harmonic order
n
Maximum permissibleharmonic current
A
Odd harmonics
Even harmonics
3
5
7
9
11
13
15<= n <=39
2
4
6
8<= n <= 40
2.30
1.14
0.77
0.40
0.33
0.21
0.15 x 15/n
1.08
0.43
0.30
0.23 x 8/n
![Page 14: W o r k i n g O n B e t t e r S o l u t i o n s1 Chroma T&M BU Product & Marketing Div. ~ 周晏加 ~ Limits for harmonic current emissions Limits for harmonic](https://reader031.vdocuments.net/reader031/viewer/2022032803/56649e1b5503460f94b09af2/html5/thumbnails/14.jpg)
W o r k i n g O n B e t t e r S o l u t i o n s 14
Class B, C
Class B : 1.5 times of class A limits
Class C :
Harmonic order
n
Maximum permissible harmonic current expressed as percentage of the input current at the fundamental
frequency%
Odd harmonics only
2
3
5
7
9
11<= n <=39
2
30‧ *
10
7
5
3
* is the circuit power factor
![Page 15: W o r k i n g O n B e t t e r S o l u t i o n s1 Chroma T&M BU Product & Marketing Div. ~ 周晏加 ~ Limits for harmonic current emissions Limits for harmonic](https://reader031.vdocuments.net/reader031/viewer/2022032803/56649e1b5503460f94b09af2/html5/thumbnails/15.jpg)
W o r k i n g O n B e t t e r S o l u t i o n s 15
Class D
Harmonic order
n
Maximum permissible harmonic current per
wattmA/W
Odd harmonics only
3
5
7
9
11
13<= n <=39
3.4
1.9
1.0
0.5
0.35
3.85/n
Maximum perm-issible harmonic
current (A)
2.30
1.14
0.77
0.40
0.33
See class A
![Page 16: W o r k i n g O n B e t t e r S o l u t i o n s1 Chroma T&M BU Product & Marketing Div. ~ 周晏加 ~ Limits for harmonic current emissions Limits for harmonic](https://reader031.vdocuments.net/reader031/viewer/2022032803/56649e1b5503460f94b09af2/html5/thumbnails/16.jpg)
W o r k i n g O n B e t t e r S o l u t i o n s 16
Transitory state
Measure every 16 cycles of fundamental frequency for 2.5 mins
Smoothing the harmonic components by LPF having time constant of 1.5S +- 10%
i
i
16 cycles
2.5 min
Smoothing
![Page 17: W o r k i n g O n B e t t e r S o l u t i o n s1 Chroma T&M BU Product & Marketing Div. ~ 周晏加 ~ Limits for harmonic current emissions Limits for harmonic](https://reader031.vdocuments.net/reader031/viewer/2022032803/56649e1b5503460f94b09af2/html5/thumbnails/17.jpg)
W o r k i n g O n B e t t e r S o l u t i o n s 17
Transitory state
For harmonic order 3-19 and 2-10, if1. T<10% of observation period (15 sec) and2. none of the waveform over 1.5 times limits
It will be considered as pass the limits
2.5 min (150s)
i
Limit
1.5 x Limit
T
![Page 18: W o r k i n g O n B e t t e r S o l u t i o n s1 Chroma T&M BU Product & Marketing Div. ~ 周晏加 ~ Limits for harmonic current emissions Limits for harmonic](https://reader031.vdocuments.net/reader031/viewer/2022032803/56649e1b5503460f94b09af2/html5/thumbnails/18.jpg)
W o r k i n g O n B e t t e r S o l u t i o n s 18
Amendment 14
1. Classification:
Only PC, PC monitor or TV receiver are class D.
1. Measuring time
2. Transitory state