DAIKIN ONE+ TRANSLATION ADAPTOR INSTALLATION INSTRUCTIONS Only personnel that have been trained to install, adjust, service or repair (hereinafter, “service”) the equipment specified in this manual should service the equipment. The manufacturer will not be responsible for any injury or property damage arising from improper service or service procedures. If you service this unit, you assume responsibility for any injury or property damage which may result. In addition, in jurisdictions that require one or more licenses to service the equipment specified in this manual, only licensed personnel should service the equipment. Improper installation, adjustment, servicing or repair of the equipment specified in this manual, or attempting to install, adjust, service or repair the equipment specified in this manual without proper training may result in product damage, property damage, personal injury or death. WARNING WARNING PROP 65 WARNING FOR CALIFORNIA CONSUMERS Cancer and Reproductive Harm - www.P65Warnings.ca.gov 0140M00517-A WARNING HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Safety Precautions 1. Only qualified personnel can carry out the equipment installation. 2. Make sure to turn off the power supply before starting the wiring work and do not turn on until the work is completed. Read the installation manual and wiring diagram of the indoor unit when carry out the work. 3. Make sure to securely connect the connectors, unse- cured connections may result in improper communi- cation and/or malfunction. 4. Do not splice wires. © 2020 19001 Kermier Rd. Waller, TX 77484 www.daikincomfort.com P/N: IOD-7134 Date: July 2020 Items in the packaging Item Translation Adaptor with power supply wire P1P2 connector (removable) Thermostat connector (removable) Front cover Adaptor mounting plate Screws Adhesive tape Qty. 1 1 1 1 1 4 1 Image Item Daikin One+ Thermostat Thermostat terminal plate Thermostat mounting plate S21 wiring cable Welcome documents Qty. 1 1 1 1 1 Image S21 Only

Upload: others

Post on 14-Aug-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: WARNING - daikinone.com · P/N: IOD-7134 Date: July 2020. Items in the packaging. Item Translation Adaptor with power supply wire P1P2 connector (removable) Thermostat connector (removable)

DAIKIN ONE+TRANSLATION ADAPTORINSTALLATION INSTRUCTIONS

Only personnel that have been trained to install, adjust, service or repair (hereinafter, “service”) the equipment specified in this manual should service the equipment. The manufacturer will not be responsible for any injury or property damage arising from improper service or service procedures. If you service this unit, you assume responsibility for any injury or property damage which may result. In addition, in jurisdictions that require one or more licenses to service the equipment specified in this manual, only licensed personnel should service the equipment. Improper installation, adjustment, servicing or repair of the equipment specified in this manual, or attempting to install, adjust, service or repair the equipment specified in this manual without proper training may result in product damage, property damage, personal injury or death.

WARNING

WARNING

PROP 65 WARNING FOR CALIFORNIA CONSUMERS

Cancer and Reproductive Harm -www.P65Warnings.ca.gov

0140M00517-A

WARNING

HIGH VOLTAGEDISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.

Safety Precautions

1. Onlyqualifiedpersonnelcancarryouttheequipmentinstallation.

2. Makesuretoturnoffthepowersupplybeforestartingthewiringworkanddonotturnonuntiltheworkiscompleted.Readtheinstallationmanualandwiringdiagramoftheindoorunitwhencarryoutthework.

3. Makesuretosecurelyconnecttheconnectors,unse-cured connections may result in improper communi-cationand/ormalfunction.

4. Do not splice wires.

© 2020 19001 Kermier Rd. Waller, TX 77484 www.daikincomfort.com P/N: IOD-7134 Date: July 2020

Items in the packaging

ItemTranslation Adaptor with power supply

wire

P1P2 connector

(removable)

Thermostat connector

(removable)Front cover

Adaptor mounting

plateScrews Adhesive

tape

Qty. 1 1 1 1 1 4 1

Image

Item Daikin One+ Thermostat

Thermostat terminal plate

Thermostat mounting plate

S21 wiring cable

Welcome documents

Qty. 1 1 1 1 1

Image

S21 O

nly

Page 2: WARNING - daikinone.com · P/N: IOD-7134 Date: July 2020. Items in the packaging. Item Translation Adaptor with power supply wire P1P2 connector (removable) Thermostat connector (removable)

2

Product Overview

TheDaikinOne+TranslationAdaptorisusedtoconnecttheDaikinOne+thermostatwithDaikinVRV,SkyAir, Single-ZoneandMulti-zonesystems.

S21 Terminal P1P2 Terminal Power Indicator

ThermostatTerminal

S21/P1P2 Wiring Slot

TheDaikinOne+SmartThermsostatcannotusetogetherwithotherwirelessorwiredremotecontrollers.Forretro-fitproject,pleaseremoveanyotherremotecontroller(s)beforeinstallation.

Not Compatible

Not Compatible

Dimension Drawings

1. Translation Adaptor

2. Mounting Plate

Specification

DTST-ONE-ADA-ADaikin One+ Smart Thermostat for VRV and Ductless Products1 for S21 Indoor Units (1 remote controller group) (cannot use together with another wireless remote controller or wired remote controller)16 for P1P2 Indoor Units (1 remote controller group) (cannot use together with another wireless remote controller or wired remote controller)

Power Wire 5.5 ft (included)

Thermostat Wire 125 ft (Field-supplied, 18AWG, 4-conductor non-shielded stranded wire)

S21 Communication Wire 6 ft (included)

P1P2 Communication Wire

6 ft* for the wire between the Translation Adaptor and the indoor unit terminal block (Field-supplied, 18AWG, 2-conductor non-shielded stranded wire)

Thermostat Obtained from the Translation Adaptor

Translation Adaptor 110-240 VACThermostat 6.8" x 3.4" x 0.8"Thermostat Adaptor 2.72" x 7.26" x 0.43"Thermostat 10.5 ozThermostat Adaptor 18.4 oz

32°F to 120°FThermostat 32°F to 120°FThermostat Adaptor -40°F to 150°F

20 to 95% RH (non-condensing)*P1P2 wire has a maximum wiring length of 1640 feet

Dimensions

Weight

Operation TemperatureHumidity

Storage Temperature

Model

Description

Power Supply

Max Wiring Length

Maximum Connections

S21 O

nly

Page 3: WARNING - daikinone.com · P/N: IOD-7134 Date: July 2020. Items in the packaging. Item Translation Adaptor with power supply wire P1P2 connector (removable) Thermostat connector (removable)

3

Selection of Mounting Location

TherecommendedmountinglocationandapproachvaryfordifferentDaikinindoorunittypes.

1. Wall-mounted unitApplicablemodels:CTXS,FAQ,FTK_N,FTX_N,FTX_U,FTXG,FTXR,FTXS,FXAQForwall-mountedunits,iftherefrigerantpipingisinstalledontherightsideandtherefrigerantpipingchaseinsidetheindoorunitisnotoccupied,itis recommendedtomounttheTranslationAdaptor insidetheindoorunitsothattheAdaptoris concealed.Otherwise,theAdaptorwillneedtobemountedoutsideoftheindoorunit.• Mountinginsidetheindoorunitpipingchase.○Makeuseoftheextraspaceleftbytheindoor

unitmountingplate,mountthebackplateoftheAdaptortothewall.Theextraspacevariesfordifferentindoorunitmodels,usethelargestavailablespaceformounting.MakesurethehighvoltagepowersideoftheAdaptorisfacingtowardstheindoorunitelectricalbox.Wheninstalledinsidethepipingchase,thefrontcoverisoptional.Forsomeofthewallmountunits,removalofthefrontplatemayberequiredtofitinsidethepipingchase.

○IftheAdaptorismountedinsidetheunit,thereisnoneedtoinstalltheAdaptorcover.

Indoor unit moun�ng plate

Translator Box (remove front cover)

• Mountingoutsideoftheindoorunit○Iftherefrigerantpipingisleft-sideinstalledand

thepipingchaseisoccupiedbytherefriger-antpiping,theTranslationAdaptorneedstobemountedoutsidetheindoorunit.Selectalocationthatwillprovideaccesstotheindoorunitelectricalbox,sothattheviewofboththeAdaptorandthewiringcablescanbeminimized

2. DuctedandAirHandlerUnitApplicablemodels:CDXS,CXTQ,FBQ,FDMQ,FDXS,FTQ,FXDQ,FXMQ,FXSQ,FXTQFortheductedindoorunit,theTranslationAdaptorcanbemountedtothesideoftheindoorunitorontopoftheindoorunitbytheadhesivetape.Thetranslatorboxcanalsobemountedtoanearbysur-facethatissturdyenoughtoholdtheAdaptor.Selectalocationthatwillprovideaccesstotheindoorunitelectricalbox

3. CeilingCassetteUnitsApplicablemodels:FCQ,FFQ,FXEQ,FXFQ,FXZQFortheceilingcassetteindoorunit,theTranslationAdaptorcanbemountedontoporthesideoftheindoorunitbytheadhesivetape.Thetranslatorboxcanalsobemountedonasurfaceabovetheceilingusingtheprovidedscrews.Selectalocationthatwillprovideaccesstotheindoorunitelectricalbox.

4. CeilingsuspendedUnitsApplicablemodels:FHQ,FXHQ,FXUQFortheceilingsuspendedindoorunits,theTransla-tionAdaptorcanbemountedontopoftheindoorunitbytheadhesivetape(forFXUQ).TheAdaptorcanalsobemountedabovetheceiling.Selectalocationthatwillprovideaccesstotheindoorunitelectricalbox.

5. Floor-mountedandFloorStandingUnitsApplicablemodels:FVXS,FXLQ,FXMQ,FXNQForthefloor-mountedandfloorstandingunit,thetranslatorboxshallbemountedbythesideoftheindoorunit.SelectalocationthatminimizestheviewoftheAdaptorandthewiring,aswellas,provideaccesstotheindoorunitelectricalbox.

.S21 O

nly

Page 4: WARNING - daikinone.com · P/N: IOD-7134 Date: July 2020. Items in the packaging. Item Translation Adaptor with power supply wire P1P2 connector (removable) Thermostat connector (removable)

4

Mounting

TheTranslationAdaptorprovidestwomountingapproach-es.Forthewall-mountedunit,thefrontcoverisoptionaliftheadaptorismountedinsidethepipingchase.

1. MountwithtwoscrewsScrews(provided)areusedtomounttheAdaptortotheavailablewallsurface.DonotusescrewstomounttheAdaptordirectlytotheindoorunit.Usethetwoscrewstomountthebackplateontotheselectedsurface.

Front Cover (Op�onal for small wall-mount unit)

Adaptor

Screws

Moun�ng plate

2. Mountwithdouble-sidedadhesivetapeDouble-sidedadhesivetapeisusedtomountthetranslatorboxontotheindoorunitdirectly.Themountingplatehasarecesstoplacetheadhesivetapetominimizethegapbetweenthemountingplateandthemountingsurface.Usethetext“APPLYOPTIONALADHESIVESTRIPHERE”toidentifythebacksideofthemountingplate.Toensureexcellentdurabilityperformanceoftheadhesivetape,thefollowingstepsarerequiredinapplyingthisadhesivetape:• Makesurethemountingsurfaceisclean.Itis suggestedtousea50:50mixtureofisopropyl alcoholandwatertocleanthesurfacetoremoveanydustoroils.Ifthesurfaceisnotproperlycleaned,theadhesivewillnotcreateachemicaladhesivebond.

• Forflatsurface,usetheadhesivetapethatis providedinthepackage.Firmapplicationpressurefor30secondsdevelopsbetteradhesive contactandhelpsimproveadhesivechemicalbondstrength.

• Fornon-flatsurfaceapplications,theinstallermayneedtousethickeradhesivetapesuchas3MSuperStrengthMoldingTape03609inordertoprovide more contact compliance on curved surfaces.

Front Cover

Adaptor

Moun�ng plate

Adhesive tape

S21 O

nly

Page 5: WARNING - daikinone.com · P/N: IOD-7134 Date: July 2020. Items in the packaging. Item Translation Adaptor with power supply wire P1P2 connector (removable) Thermostat connector (removable)

5

Thermostat terminal plate Transla�on adaptor Indoor unit power supply terminal (110-230VAC)

S21 connector on the indoor unit/Interface Adaptor

• ForS21IndoorUnits

• ForP1P2IndoorUnits

Thermostat terminal plate Transla�on adaptor Indoor unit power supply terminal (110-230VAC)

Indoor unit terminal block

Thewiringrequirementislistedinthefollowingtable:

Wire Name Type Connected to Max LengthHigh-Voltage Power Line 3-wire, Included in the package Indoor unit power terminal or

external power source5 1/2 ft

Thermostat Wire Field-supplied, 18 AWG, 4-conductor non-shielded stranded wire

Daikin One+ Thermostat 125 ft

S21 Communication Wire 5-conductor wire with connectors, included in the package

S21 Terminal on the indoor unit PCB or S21 Terminal on the Interface adaptor

6 ft

P1P2 Communication Wire Field-supplied, 18 AWG, 2-conductor non-shielded stranded wire

P1P2 Terminal on the indoor unit 6 ft*

*Max P1P2 wire length is 1640 ft

Wiring

1. OverviewThetranslatorboxisconnectedbetweentheindoorunitandtheDaikinOne+Thermostat.Itobtainspowerfromtheindoorunitpowerterminationorexternalpowersource.Thefollowingfiguresgiveanoverviewofthewiring.

S21 O

nly

Page 6: WARNING - daikinone.com · P/N: IOD-7134 Date: July 2020. Items in the packaging. Item Translation Adaptor with power supply wire P1P2 connector (removable) Thermostat connector (removable)

6

2. ThermostatWiringTheDaikinOne+SmartThermostatobtainspowerfromtheadaptordirectly.Itisrecommendedtowirethether-mostatwirefirstbeforewiringtheS21orP1P2communicationwire.Thethermostatterminal(D1,D2,C,R)ontheadaptorshallbeconnecttothe(1,2,C,R)terminalsonterminalplateoftheDaikinOne+Thermostatby18AWG4-conductornon-shieldedstrandedwire.Makesuretheterminationcombinationsintheimagebelowarefollowed.

Terminals Plate for the thermostat

Thermostat Terminal on the Adaptor

Removable for Easy installa�on

3. S21CommunicationWiringS21CommunicationterminalisusedforS21indoorunits(SingleandMulti-splits)only.TheS21wiringcableisin-cludedinthepackage.TheS21wiringcableshallmakeuseofthe2anchorsandtheS21/P1P2wiringslottoroutewiringcabletowardsthehighvoltagesideoftheAdaptor.

Onlyoneofthecommunicationterminalsshallbeusedperindoorunit.Never use the S21 terminal and the P1P2 terminal at the same time.Thefollowingtableliststhecommunicationterminalforeachindoorunitmodel.

Indoor Unit Model Communication TerminalCDXS, CTXS, FDXS, FTK_N, FTX_N, FTX_U, FTXG, FTXR, FTXS, FVXS S21 TerminalCXTQ, FAQ, FBQ, FDMQ, FTQ, FCQ, FHQ, FFQ, FXAQ, FXDQ, FXEQ, FXFQ, FXHQ, FXLQ, FXMQ, FXNQ, FXSQ, FXTQ, FXUQ, FXZQ

P1P2 Terminal

S21 O

nly

Page 7: WARNING - daikinone.com · P/N: IOD-7134 Date: July 2020. Items in the packaging. Item Translation Adaptor with power supply wire P1P2 connector (removable) Thermostat connector (removable)

7

TheS21wiringcableisconnectedtotheS21connectorontheindoorunitPCBortotheS21connectorontheIn-terfaceAdaptor(dependentuponindoorunitmodel).RefertotheindoorunitinstallationmanualonhowtofindandaccesstheS21connector.Someofthesingle-zoneandmulti-zoneindoorunitsdonothaveanS21connectorontheindoorunitPCB.Forthoseindoorunits,anInterfaceAdaptorneedstobeorderedseparately.ThefollowingtablesummarizestheindoorunitmodelsthatrequireanInterfaceAdaptorandthemodelnumberoftherequiredinterfaceadaptor.

Indoor Unit Models Required Interface AdaptorFTX09NMVJU, FTX12NMVJU, FTK09NMVJU, FTK12NMVJU, KRP067A41EFTX15NMVJU, FTX18NMVJU, FTX24NMVJU, FTK18NMVJU, FTK24NMVJU KRP980B2E

4. P1P2 Communication WiringTheP1P2CommunicationterminalisusedforP1P2indoorunitsonly.Use18-2-non-shieldedstrandedwiretoconnecttheP1P2terminalontheAdaptortotheP1P2terminaloftheapplicableindoorunit.DonotusetheS21terminalifP1P2terminalisused.

5. PowerSupplyTheP1P2CommunicationterminalisusedforP1P2indoorunitsonly.Use18-2-non-shieldedstrandedwiretoconnecttheP1P2terminalontheAdaptortotheP1P2terminaloftheapplicableindoorunit.DonotusetheS21terminalifP1P2terminalisused.

Removable for Easy installa�on

WARNING

HIGH VOLTAGEDISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.

S21 O

nly

Page 8: WARNING - daikinone.com · P/N: IOD-7134 Date: July 2020. Items in the packaging. Item Translation Adaptor with power supply wire P1P2 connector (removable) Thermostat connector (removable)

8

6. CheckPowerIndicatorsOncethewiringandinstallationiscomplete,turnonpowertotheindoorunit.UsethepowerindicatorontheAdap-tortoconfirmwhetherthewiringissuccessfulornot.TheLEDlightfor‘Power’indicatesthepowerisconnectedsuccessfully.IftheindoorunithastheS21termination,the‘S21’LEDwillbeon;IftheindoorunithastheP1P2termination,the‘P1P2’LEDwillbeon.OncepowerandcommunicationhasbeenverifiedusetherubbergrommettocovertheLEDs.ThiswillpreventtheLEDlightfrombleedingthroughtheindoorunitwhentheindoorunitandadaptor are completely installed.

LED lights status for S21 units LED lights status for P1P2 units

Forsomewall-mountedunits,thefrontcovershallberemovedtofitinsidethepipingchase.Forotherunits,putthefrontcoverbackontothetranslatorboxandpressdownuntilitsnapsintoplace.

S21 O

nly

Page 9: WARNING - daikinone.com · P/N: IOD-7134 Date: July 2020. Items in the packaging. Item Translation Adaptor with power supply wire P1P2 connector (removable) Thermostat connector (removable)

9

CUSTOMER FEEDBACKDaikin is very interested in all product comments.Pleasefilloutthefeedbackformonthefollowinglink:https://daikincomfort.com/contact-usYoucanalsoscantheQRcodeontherighttobedirectedtothefeedbackpage.

Our continuing commitment to quality products may mean a change in specifications without notice. © 2020

19001 Kermier Rd. Waller, TX 77484www.daikincomfort.com