Action Pumps Ltd Tel: 023 9226 8511 1" BSPF to be piped to drain Top floor WASP cold water riser system saver Water Air Surge Protection valve · Automatic Surge Protection The unique WASP valve incorporates as standard, three design features to automatically protect building risers under all operating conditions, from the destructive surge and water hammer phenomena. These features are independent of any mechanical devices ensuring reaction in a very low milli second time span. · Vacuum Protection The WASP valve utilises the large orifice to admit air in the riser thus preventing vacuum occurring when the booster set is down (powered off). · Effective Air Release During filling, air is forced through an "Anti-Surge” orifice resulting in the deceleration of the approaching water column due to the resistance of rising air pressure in the valve. This dampens potential pressure transients when the air valve closes. The WASP valve design, ensures effective de-aeration under all pipeline flow and operating conditions, via either one of three discharge orifices. PIPE SYSTEM PROTECTOR! Dampens effect of Water-Hammer at pump start-up Provides Vacuum Protection when the pump stops and the riser drains TYPICAL ARRANGEMENT The WASP valve must be installed at the top of each riser to ensure adequate water-hammer protection. An isolating valve should be installed to facilitate maintenance. IMPORTANT NOTE To ensure proper operation the system must be thoroughly flushed prior to the installation of the WASP valve.

Upload: letruc

Post on 19-May-2018

254 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: WASP cold water riser system saver ater ir Surge ... · WASP cold water riser system saver ... air is forced through an "Anti-Surge” ... The WASP valve offers air,surge and vacuum

Action Pumps LtdTel: 023 9226 8511

1" BSPF to bepiped to drain

Top floor

WASP cold water riser system saverWater Air Surge Protection valve

· Automatic Surge ProtectionThe unique WASP valve incorporates as standard,three design features to automatically protectbuilding risers under all operating conditions, fromthe destructive surge and water hammerphenomena.These features are independent of any mechanicaldevices ensuring reaction in a very low milli secondtime span.· Vacuum ProtectionThe WASP valve utilises the large orifice to admitair in the riser thus preventing vacuum occurringwhen the booster set is down (powered off).· Effective Air ReleaseDuring filling, air is forced through an "Anti-Surge” orifice resulting in the deceleration of theapproaching water column due to the resistance ofrising air pressure in the valve. This dampenspotential pressure transients when the air valvecloses. The WASP valve design, ensures effectivede-aeration under all pipeline flow and operatingconditions, via either one of three dischargeorifices.

PIPE SYSTEM PROTECTOR!Dampens effect of Water-Hammer at pump start-upProvides Vacuum Protection when the pump stopsand the riser drains

TYPICAL ARRANGEMENTThe WASP valve must be installed at the top of each riser to ensureadequate water-hammer protection.An isolating valve should be installed to facilitate maintenance.

IMPORTANT NOTETo ensure proper operation the system must be thoroughly flushed prior tothe installation of the WASP valve.

richard.malec
Text Box
The WASP valve offers air,surge and vacuum protection as a custom built solution for installation at the top of a riser in a building to reduce the potential for hydraulic shock.
Page 2: WASP cold water riser system saver ater ir Surge ... · WASP cold water riser system saver ... air is forced through an "Anti-Surge” ... The WASP valve offers air,surge and vacuum

Action Pumps LtdTel: 023 9226 8511

A

D

C

B

E

Size—mm/in. 25 / 1”

Pressure rating PN10*

A 337mm

B 317mm

C 95mm

D 1” BSPF

E 1” BSPF

Weight 4.6 kg

Max. riser pipe diameter 200mm**

WRAS No. 0904082

Min. pressure 0.3 Bar

Max. temperature 70°C/158°F

Min. temperature 4°C/40°F

* Versions rated at higher pressures up to PN40 available on request.** The design, size and use of every cold water riser /distribution laterals is different for all buildings, hence to size awater / air surge protection valve correctly, the system should be evaluated to determine the maximum flow rate ofair entering the system under vacuum conditions. In reality this is virtually impossible to estimate, so the figurestated is based on a maximum vacuum not exceeding 0.1 bar (riser draw down flow rate of approximately 55m³/hr.System fill - We strongly recommend that all booster pump set control systems utilise a “system fill” feature to assist with controlled slow filling of a system after a power failure or if the system pressure drops below a pre-determinedthreshold.