water cooled freecooling chiller kw 39÷634

6
39÷634 kW General Tetris W FC/NG is a freecooling chiller for indoor in- stallation that integrates decoupling exchanger, 3-way modulating valve, inverter pump on source side and ad- vanced software to manage the system and remote air cooled exchanger. Configurations Base: unit with a Total Freecooling Temperaure of -2°C HE: unit with a Total Freecooling Temperaure of +1°C Pump and integrated buffer tank available as option Tetris W FC/NG Water cooled freecooling chiller Bullet points Plug and play indoor freecooling unit Hybrid freecooling: capability, in the mid seasons, to operate in mixed mode freecoling/chiller Full completely integrated control for managing chil- ler, freecooling system and remote air cooled exchan- ger High efficiency in summer mode Two levels of freecooling efficiency and payback time Designed for easy indoor installation Glycol free on user side Wide capacity range

Upload: others

Post on 02-Feb-2022

8 views

Category:

Documents


0 download

TRANSCRIPT

Blue Box Group S.r.l.Via Valletta, 5 - 30010 Cantarana di Cona, (VE) Italywww.bluebox.it - [email protected] +39 0426 921111 - Fax +39 0426 302222

39÷6

34 k

WGeneral

Tetris W FC/NG is a freecooling chiller for indoor in-stallation that integrates decoupling exchanger, 3-way modulating valve, inverter pump on source side and ad-vanced software to manage the system and remote air cooled exchanger.

Configurations

Base: unit with a Total Freecooling Temperaure of -2°CHE: unit with a Total Freecooling Temperaure of +1°CPump and integrated buffer tank available as option

Tetris W FC/NGWater cooled freecooling chiller

Bullet points

► Plug and play indoor freecooling unit

► Hybrid freecooling: capability, in the mid seasons, to operate in mixed mode freecoling/chiller

► Full completely integrated control for managing chil-ler, freecooling system and remote air cooled exchan-ger

► High efficiency in summer mode

► Two levels of freecooling efficiency and payback time

► Designed for easy indoor installation

► Glycol free on user side

► Wide capacity range

Indoor freecoolingThe ultimate freecooling experience

Supplied with

dedicated dry cooler

optimized for the unit.

+1°C100% FC

externaltemperature

Nominal cooling capacity [kW]

Nominal cooling capacity [kW]

-2°C

TFT (100% FC)STD version

TFT (100% FC)HE version

STD

HE

T STD: 8°C*A

T HE: 9°C*A

+1°C

T ext air

Freecooling mode

Chiller mode

T ext airHYBRID FREECOOLING

HYBRID FREECOOLING

Partial Freecooling

Tota

l en

erg

y co

nsu

mp

tio

n [

kWh

]

External air temperature [C°]

Example for Stockholm

Low billsLow carbon emission

TETRIS W FC/NG HE 26.4

41%Energy saving=0

5000

10000

15000

20000

25000

-25 -22 -19 -16 -13 -10 -7 -4 -1 2 5 8 11 14 17 20 23 26 29 32

Chiller + Freecooling mode

Chiller mode only

year

winter winter

Nominal cooling capacity [kW]

Freecooling mode ON Freecooling mode OFFPartial Freecooling

summer

modespring summer autumn

averageEER 4,7*

High partialhybrid freecooling mode

Here are a number illustrating the energy savings for Stockholm, in terms of energy consumption, achieved using TETRIS W FC/NG HE, in compari-son to a water cooled standard unit, assuming that the cooling need is constant throughout the year.

Tetris W FC / NG combines all the advantages of high ef-ficiency water-cooled chiller (Tetris W range) with the hybrid freecooling integrated system

•Hybrid free CoolingUnit performs full nominal capa-city with compressors operating at part load with reduced power consumption.

• 100% Free Cooling (Winter)Unit performs full nominal capa-city only using Dry Cooler fans and with compressors OFF.

HYBRID FREE COOLING

* Evaporator inlet-outlet water temperature 15-10°C; condenser inlet-outlet water temperature 30-35°C (e.g. 30%)

NOT ONLY FREECOOLINGHigh efficiency in summer mode

Thanks to high performan-ce of the chiller side, Tetris W FC/NG ensures high ef-ficiency of the plant during all the year. The product adapts and optimises itself to the seasons, providing a high return all year round.

EASYINSTALLATIONTetris W FC / NG provides a lot pof op-tions and pumping configurations to suit every requirements. The footprint is designed for indoor in-stallation (max width below 900 mm). The structure provides also the division in two section for sizes long over 5 me-ters to allow an easy movement in inte-rior spaces. This means:• Less design time• Quicker and less cost for installa-

tion team• Few connections

INVERTER DRIVEN PUMP ON SOURCE SIDEInverter driven pump on source side as standard:• Reduced energy consumption• Greater control of condensing tempe-

rature in partial freecooling.

FULL INTEGRATEDCONTROL SYSTEMAdvanced built-in control to manage the 3-way modulating valve, inverter driven pump on the source side and the fan speed adjuster of the dry cooler.No need additional cost for controls in-tegration.

GLYCOL FREE Thanks to the built-in decoupling heat exchanger Tetris W FC/NG is Glycol free on user side. This means:• more efficiency on user side with only

water• the plant doesn’t need to be monitored

(ethylene glycol is poisonous for hu-mans)

usersourceGly

col

No

Gly

col

INOUT

Unit Size 3.2 4.2 5.2 6.2 7.2 8.2 9.2 10.2 12.2 13.2 15.2 17.2 19.2 20.2 24.2 27.2

CoolingNominal cooling capacity (1),(6) kW 39 45 52 57 66 74 85 103 117 135 150 166 188 206 229 258

EER (1) 4,69 4,66 4,74 4,77 4,72 4,73 4,78 4,79 4,78 4,79 4,82 4,79 4,76 4,67 4,66 4,69

EER (EN 14511-3:2011) (1),(6) 4,10 4,01 4,14 4,18 4,20 4,09 4,17 4,23 4,31 4,26 4,29 4,23 4,24 4,17 4,26 4,23

Basic unit size and weightsLenght mm 1633 1633 1633 1633 1633 1633 1633 1633 3300 3300 3300 3300 3300 3300 3300 3300

Width mm 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800

Height mm 1880 1880 1880 1880 1880 1880 1880 1880 1880 1880 1880 1880 1880 1880 1880 1880

Unit Size 30.3 34.3 40.3 18.4 20.4 24.4 26.4 30.4 34.4 38.4 40.4 48.4 54.4 56.6 60.6

CoolingNominal cooling capacity (1),(6) kW 328 370 414 169 204 233 263 297 331 377 423 468 527 563 634

EER (1) 4,81 4,84 4,86 4,74 4,72 4,77 4,77 4,78 4,75 4,72 4,73 4,62 4,70 4,73 4,73

EER (EN 14511-3:2011) (1),(6) 4,37 4,35 4,36 4,22 4,33 4,34 4,23 4,39 4,23 4,29 4,23 4,28 4,29 4,28 4,28

Basic unit size and weightsLenght mm 4505 4505 4505 3685 3685 4502 4502 4502 4502 2820 + 2930 3320 + 2930

Width mm 880 880 880 880 880 880 880 880 880 880 880 880 880 880 880

Height mm 1880 1880 1880 1880 1880 1880 1880 1880 1880 1880 1880 1880 1880 1880 1880

(1) Evaporator inlet-outlet water temperature 15-10°C; Condenser inlet-outlet water temperature 30-35°C (e.g.30%)(6) Values conform to EN 14511-3:2011This board reports the feature data of the base and standard versions; for details, refer to the specific documentation.

Hotel Sail CityBremerhaven - GermanyIndoor freecooling system -> 2 water cooled chiller + 2 water cooled freecooling chillerSupply -> 1 MW

Blue Box Group S.r.l.Via Valletta, 5 - 30010 Cantarana di Cona, (VE) Italywww.bluebox.it - [email protected] +39 0426 921111 - Fax +39 0426 302222

Zeta Echos FC > 44÷143 kW

Tetris FC series > 97÷518 kW

Kappa V Evo FC > 325÷1178 kW

Tetris W FC/NG > 39÷634 kW

Kappa Rev HEi & XEi > 286÷1451 kW

High efficiency air cooled freecooling chillers. Patented system.

High efficiency air cooled modular freecooling chillers.

High efficiency air cooled freecooling chillers.

High efficiency water cooled freecooling chillers with integrated hydronic module.