Anthony Fang Kirsten Rice Viv Pitter Ryan Williams Jeremy Molayem WATER SUPPLY AND SEWER SYSTEM DESIGN

Upload: jeremy-molayem

Post on 15-Nov-2014

317 views

Category:

Engineering


10 download

DESCRIPTION

 

TRANSCRIPT

Page 1: Water Supply and Sewerage Design

Anthony FangKirsten RiceViv PitterRyan WilliamsJeremy Molayem

WATER SUPPLY AND SEWER SYSTEM

DESIGN

Page 2: Water Supply and Sewerage Design

ZONE AREAS

A

Page 3: Water Supply and Sewerage Design

Residential Area: 66.281 acres Population Density: 40 people/acre Population: 2652 people

Industrial Area: 3.2881 acres Population Density: 20 people/acre Population: 66 people

Commercial Area: 5.3375 acres Use: 10 hours per weekday

ZONE POPULATION

Page 4: Water Supply and Sewerage Design

I. WATER SUPPLY SYSTEM

Page 5: Water Supply and Sewerage Design

Residential Average consumption: 2.652 x 105 gpd Peak day consumption: 5.304 x 105 gpd Peak hour consumption: 1.608 x 106 gpd

Industrial Weekday consumption: 1.44 x 106 gal/day Peak hour consumption:1.8 x 105 gal/hr

Commercial Average flow rate: 17.5 gpm Peak day flow rate: 35 gpm

DEMAND

Page 6: Water Supply and Sewerage Design

Fire flow is calculated based on the equation NFF=(Oi)(Ci)[1.0+(X+P)i]

Q = 5200 gpm (10 hour duration) = 3.124 x 106 gpd

Total flow for max day and Fire flowQ tota l = 2.38x106 + 3.124x106 = 5.50 x 106 gpd

FIRE FLOW

Page 7: Water Supply and Sewerage Design

WATER DISTRIBUTION MAP WITH OUTFALLS

Page 8: Water Supply and Sewerage Design

DISTRIBUTION LAYOUT

Page 9: Water Supply and Sewerage Design

System B – Pumping station to major center of demand with an elevated storage tank between the supply and demand

Average Day = 1.7 mgd.Max Day = 1.7 mgd x 1.5 = 2.55 mgdPeak hour = 2.55 mgd x 1.5 = 3.83 mgdMax day + Fire flow = 5.5 mgd

DISTRIBUTION STORAGE

Page 10: Water Supply and Sewerage Design

DISTRIBUTION STORAGE

Demand Rate Calculation Pumping Head

Average Day (1.7 mgd)

115 + (0.67 x 19) 128 ft

Max. Day. (2.55 mgd)

115 + (1.42 x 19) 142 ft

Max. Hour. (3.83 mgd)

115 + (3.0 x 19) 172 ft

Max day + fire = (5.5 mgd)

115 + (6.1 x 19) 231 ft

Page 11: Water Supply and Sewerage Design

Total Length of Pipe ~ 19,000 feetPipe Material = ductile iron (C = 140)Diameter: 12-14 inWater Tower Head – 310 ftPump Head – 305 ft

Worst Case: Pump Failure Pressure low: 28.84 psi, high: 40.21 psi

PIPING SYSTEM INFORMATION

Page 12: Water Supply and Sewerage Design

HP=QxH/(3960*n)

Q= 3606 GPMH=305ftn=65%

HP=427.28 500 HP pump needed. Two pumps (one standby)

PUMP DESIGN

Page 13: Water Supply and Sewerage Design

Fire hydrants are to be located 300 feet apart on each street and 150 feet apart in high value zones.

FIRE HYDRANT LOCATIONS

Page 14: Water Supply and Sewerage Design

II. SEWER SYSTEM

Page 15: Water Supply and Sewerage Design

SEWER DESIGN

Page 16: Water Supply and Sewerage Design

For Commercial and Residential 25 F.U. => 40 gpm x 3 (Restaurants) = 120 gpm 10 F.U. => 30 gpm x 2 (Offi ces) = 60 gpm Total = 180 gpm

For Industry = (3000gpm) x (70%) = 2100 gpm

For Residential = (Max Hourly Use) x 70% = Sewage Flow

SEWER DESIGN

Page 17: Water Supply and Sewerage Design

Summary

SEWER DESIGN

Pipe Material PVCMin. Velocity 2 ft/sMax Velocity 10 ft/sRoughness (n) 0.015Min Ground Cover 6 ftPercentage Full 50%Min. Pipe Diameter 8 in.Max Pipe Diameter 50 inMax Velocity (Actual) 7.7 ft/sMax Depth 22 ft.

Page 18: Water Supply and Sewerage Design

III. STORMWATER SYSTEM

Page 19: Water Supply and Sewerage Design

STORM DATA

Duration, Min Intensity, In/Hr5 7

10 5.515 520 4.325 3.930 3.7535 3.540 3.3545 3.250 3.1555 3.12560 3.1

Page 20: Water Supply and Sewerage Design

STORM SEWER DESIGN

Design Criteria Value (Minimum) Value (Maximum)  

Flow Velocity 3 ft/s 15 ft/s  

Slope 0.02% 10%  

Depth of Cover 5 ft below surface N/A  

Diameter 1 ft N/A  

Roughness Coefficient N/A N = 0.013  

Capacity* N/A ¾, 0.75  

Horizontal Distance from Drinking Water Lines**

10 ft N/A  

Vertical Distance from Utilities**

1 ft    

 Pipe Material  PVC for Diameter les    

*ratio of flow depth to full depth**from Haestad Methods, Stormwater Conveyance Modeling and DesignDesign Restrictions•Hydraulic Gradient Line should be below surface elevation at all times.•Curved Storm Sewers are unacceptable (maintenance problems)Depth of cover should be at least 5 ft in order to prevent crushing of pipes due to loads.

Page 21: Water Supply and Sewerage Design

CONDUITS EXCEEDING DESIGN CAPACITY

Page 22: Water Supply and Sewerage Design

CONDUITS OVERCAPACITY AT 21 INCHES

Page 23: Water Supply and Sewerage Design

CONDUITS OVERCAPACITY AT 24 INCHES

Page 24: Water Supply and Sewerage Design

CONDUITS OVERCAPACITY AT 27 INCHES

Page 25: Water Supply and Sewerage Design

DESIGN SATISFIED, ALL CAPACITY < 0.75

Page 26: Water Supply and Sewerage Design

DESIGN CRITERION: 3FPS < VELOCITY <15FPS

Page 27: Water Supply and Sewerage Design

DESIGN CRITERION, 0.2% < SLOPE <10%

Page 28: Water Supply and Sewerage Design

CONDUIT DIAMETER

Page 29: Water Supply and Sewerage Design

CONDUIT FLOW

Page 30: Water Supply and Sewerage Design

HYDRAULIC PROFILES

Page 31: Water Supply and Sewerage Design

HYDRAULIC PROFILES

Page 32: Water Supply and Sewerage Design

HYDRAULIC PROFILES

Page 33: Water Supply and Sewerage Design

SUMMARY

Pipe Material PVC or Reinforced Concrete (D>1ft)Min. Velocity 3.72 fpsMax. Velocity 12.3 fpsRoughness n=0.013Min Ground Cover 5 ftMax Capacity 75% fullnessMin. Pipe Diameter 12 inchesMax. Pipe Diameter 27 inchesMax Depth 22 ft

Page 34: Water Supply and Sewerage Design

Worst Case ScenarioPump Failure, distribution only from water tower

Water tower height 310 ft Pump head = 0 ft

Pressure High- 40.21 psi Low- 28.84 psi

DISTRIBUTION DESIGN (SCENARIO 1)

Page 35: Water Supply and Sewerage Design

Water Tower Failure, supply only from pump Water tower head = 0 ft Pump head = 305 ft

Pressure High: 44.99 psi Low: 30.52 psi

DISTRIBUTION DESIGN (SCENARIO 2)

Page 36: Water Supply and Sewerage Design

Best Case Elevated Storage Tank -310 ft Pumping Reservoir- Total head about 305 ft

Pressure- High- 45.89 psi Low- 33.01 psi

DISTRIBUTION DESIGN (SCENARIO 3)