wavelet based noise cancellation technique for fault location on underground power cables

Upload: shimaa-barakat

Post on 14-Apr-2018

227 views

Category:

Documents


1 download

TRANSCRIPT

  • 7/29/2019 Wavelet Based Noise Cancellation Technique for Fault Location on Underground Power Cables

    1/14

    Electric Power Systems Research 77 (2007) 13491362

    Wavelet based noise cancellation technique forfault location on underground power cables

    C.K. Jung a,, J.B. Lee a, X.H. Wang b, Y.H. Song c

    a Department of Electrical Engineering, Wonkwang University, 344-2, Shinyong-dong, I ksan, Republic of Koreab School of Computing and Information System, Kingston University, Kingston upon Thames, Surrey KT1 2EE, London, UK

    cDepartment of Computing and Information System, Brunel University, Middlesex UB8 3PH, London, UK

    Received 29 December 2005; received in revised form 18 September 2006; accepted 16 October 2006

    Available online 16 November 2006

    Abstract

    This paper describes a new algorithm to identify the reflective waves for fault location in noisy environment. The new algorithm is based on the

    correlation of detail components at adjacent levels of stationary wavelet transform of current signal from one end of the cable. The algorithm is

    simple and straightforward. Simulation results based on a real power transmission system proved it can detect and locate the fault in very difficult

    situations.

    2006 Elsevier B.V. All rights reserved.

    Keywords: Fault location; Fault classification; Underground power cable system; Stationary wavelet transform

    1. Introduction

    Thepotential benefits of applying wavelet transform in powercable fault location have been recognized by many researchers

    [19]. The wavelet transform has the ability to localize the

    signals in both time and frequency domains. This makes it par-

    ticularly useful in capturing the transients at one end or both

    ends of the cable and locate the fault position. This refers to

    single-ended or double-ended fault location. Between these two

    approaches, single-ended approach is less expensive and more

    reliable as it does not need communication link between the ends

    of the cable and requires only one equipment to operate rather

    than two at both ends. This reduces the errors caused by the

    different equipment and synchronization of time at both ends.

    Therefore, single-ended approach is more practical and accurate

    in fault location.

    The single-ended approach uses reflected transients from

    either the fault or other end to locate the fault. This raises some

    problems of detecting the reflected transients on underground

    power cable system. If the reflections are from fault point, they

    will be very weak because part of the signals will transmit to

    Corresponding author. Tel.: +82 63 850 6735; fax: +82 63 850 6735.

    E-mail address: [email protected] (C.K. Jung).

    the other end from fault point. If the reflections are from the

    other end, same problem still exists as part of the signals will

    reflect back. At the same time, the signal will travel a long wayto reach the measurement end. Since the high frequency tran-

    sients have a very high attenuation in the cables, the reflection

    will become weak after the long way traveling. It is clear that

    the magnitudes of the reflections are much smaller than the first

    transient. In addition, the measurement will be noisy. Some-

    times the noise level may be higher than the reflections. Then

    how to discriminate the weak reflection from the noise is a big

    issue.

    Thetransients have many irregular signals, andall of them are

    useable signal. However, only transients at specific frequency

    are useful to locate the fault. The rest are useless. Therefore,

    this paper considers unnecessary signals as noise. In this paper,

    a new algorithm was proposed to discriminate the reflected sig-

    nals from noise and thus locate the fault. The algorithm is based

    on the correlation of the wavelet coefficients at multi-scales.

    For wavelet transform, the stationary wavelet transform (SWT)

    is introduced instead of conventional discrete wavelet trans-

    form (DWT). Stationary wavelet transform uses upsampling at

    each level of decomposition that causes redundancy. In wavelet

    transform, thenumber of elements perscaleand location is fixed-

    independent of scale. The redundancy increases the elements per

    scale and location at coarse scales. In term of denoising, there

    0378-7796/$ see front matter 2006 Elsevier B.V. All rights reserved.

    doi:10.1016/j.epsr.2006.10.005

    mailto:[email protected]://localhost/var/www/apps/conversion/tmp/scratch_3/dx.doi.org/10.1016/j.epsr.2006.10.005http://localhost/var/www/apps/conversion/tmp/scratch_3/dx.doi.org/10.1016/j.epsr.2006.10.005mailto:[email protected]
  • 7/29/2019 Wavelet Based Noise Cancellation Technique for Fault Location on Underground Power Cables

    2/14

    1350 C.K. Jung et al. / Electric Power Systems Research 77 (2007) 13491362

    is an advantage in having more orientations than necessary at

    coarse scales. It is better in noisy signal processing [10,11].

    After brief review of the stationary wavelet transform in sec-

    ond section, fault classification algorithm and noise cancellation

    technique for fault location will be discussed in Sections 4 and

    5, based on a real cable system described in Section 3. The algo-

    rithms will be tested by simulations in Section 6. Thelast section

    concludes the paper.

    2. Stationary wavelet transform

    In this section, the basic principles of the SWT method will

    be presented. In summery, the SWT method can be described

    as at each level, when the high and low pass filters are applied

    to the data, the two new sequences have the same length as the

    original sequences. To do this, the original data is not decimated.

    However, the filters at each level are modified by padding them

    out with zeros.

    Supposing a function f(x) is projected at each step j on the

    subset Vj (. . . V3 V2 V1 V0). This projection is definedby the scalar product cj,k of f(x) with the scaling function (x)

    which is dilated and translated:

    cj,k = f(x), j,k(x) (1)

    j,k(x) = 2j(2jx k) (2)

    where(x) is the scaling function, which is a low-pass filter. cj,k,

    is also called a discrete approximation at the resolution 2j.

    If(x) is the wavelet function, the wavelet coefficients are

    obtained by:

    j,k = f(x), 2j(2jx k) (3)

    where j,k is called the discrete detail signal at the resolution 2j.

    As the scaling function (x) has the property:

    1

    2x

    2

    =n

    h(n)(x n),

    where h(n) is the low-pass filter. cj+1,k can be obtained by direct

    computation from cj,k

    cj+1,k =n

    h(n 2k)cj,n and1

    2x

    2

    =n

    g(n)(xn)

    (4)

    where g(n) is the high-pass filter.The scalar products f(x),2(j+1)(2(j+1)x k) are com-

    puted with:

    j+1,k =n

    g(n 2k)cj,n (5)

    Eqs. (4) and (5) are the multi-resolution algorithm of the

    traditional discrete wavelet transform. In this transform, a down-

    sampling algorithm is used to perform the transformation. That

    is one point out of two is kept during transformation. Therefore,

    the whole length of the function f(x) will reduce by half after the

    transformation. This process continues until the length of the

    function becomes one.

    However, for stationary or redundant transform, instead of

    downsampling, an upsampling procedure is carried out before

    performingfilterconvolution at eachscale. The distance between

    samples increases by a factor of 2 from scale j to the next. cj+1,kis obtained by:

    cj+1,k = l

    h(l)cj,k+2jl (6)

    and the discrete wavelet coefficients:

    j+1,k =l

    g(l)cj,k+2jl (7)

    where l indicates the finite length.

    3. Model system

    The diagram of a real power cable system to be discussed in

    this paper is shown in Fig. 1. It is a single core cable transmission

    system with the voltage of 154 kV. The total length of the cableis 6.284 km. It consists of five crossbonded major sections with

    three minor sections foreach major section. As usual,the sheaths

    are jointed and crossbonded between two sections.

    In this paper, the single line to ground fault is considered

    in real power cable system to test the proposed algorithm and

    Alternative Transient Programs (ATP) program is used for sys-

    temmodelingand simulation. Thesampling frequency is 1 MHz,

    the propagation velocities of traveling wave on power cable sys-

    tem is 1.67487 105 km/s. The applied fault inception angle is

    0, 45, 60 and 90, respectively. In order to calculate the dis-

    tance to fault point, single line to ground fault is supposed to

    occur at 13 km from A S/S. Fault resistance is assumed to be

    0, 0.5 and 1, respectively.

    4. Algorithm for fault classification

    Wavelet transform decomposes the signal into approxima-

    tion and detail coefficients, forming approximations and details.

    The approximations are the high-scale, low-frequency com-

    ponents of the signal, while the details are the low-scale,

    high-frequency components. The decomposition process can be

    iterated.

    Normally the first level detail in wavelet transform contains

    the information to detect the fault. In order to detect the fault,

    threshold is set. If the signal exceeds the threshold, then it issupposed that a fault has occurred. However, the spike can be

    detected on all phases. It is difficult to discriminate on which

    phase the fault is. For many signals, the low frequency contents

    are the most important parts. They give the signal their identities

    to some extents. For SWT decomposition, the approximation

    contains the low frequency components. The more levels the

    signals are decomposed, the lower frequency the components

    will be.

    For fault detection and classification, the 4th level approxi-

    mations of current on phasesAC will be used. If thefault occurs

    on phase A, the magnitude of approximation on phases B and C

    are very low comparing to that on phase A after some delayed

  • 7/29/2019 Wavelet Based Noise Cancellation Technique for Fault Location on Underground Power Cables

    3/14

    C.K. Jung et al. / Electric Power Systems Research 77 (2007) 13491362 1351

    Fig. 1. Underground power cable system.

    Fig. 2. Flow chart for fault detection and classification.

    sampling time from the fault inception. Then an algorithm is

    established to classify the fault.

    For every sampling point exceeding the threshold on the first

    detail, approximations of the three-phase currents on 4th level

    are calculated as A4j, where j = 1, 2 and 3 for three phases.

    The maximum approximation among three phases is denoted

    as Amax. Then the absolute ratio of the approximations on each

    single phase to the maximum approximation is calculated. The

    ratio on the faulty phase should be unity since its approximation

    is equal to the maximum value, while the ratios on the other two

    phases are near zero because of the weak signals. Therefore, if

    two ratios are near zero, it can deduce that a fault has occurred,

    and the faulty phase can be classified as the one whose ratio is

    equal to unity. A simple flow chart of the procedure is shown is

    Fig. 2.

    Faults on phase A were applied for testing the fault detection

    and classification algorithm. However, an extensive investiga-

    tion has been carried out to study the fault with various condi-

    tions which include the different positions, inception angles andfault resistance. The calculated ratios are shown in Table 1. The

    ratios on all faulty phases show unity because its approximation

    is equal to the maximum value regardless of fault conditions,

    while the ratios on other two phases are near zero. From these

    results, the fault on which phase will be easily identified.

    5. Noise cancellation technique

    After applying the wavelet transform the details of the first

    level are shown in Figs. 3 and 4 in case of fault at 1 and 2 km.

    As shown in these figures, many spikes appeared because of the

    reflected transients from both fault point and other end of thecable including many noises.

    Therefore, it is very difficult to discriminatewhichtransient is

    the fault generated. This makes the fault location by the wavelet

    transformation impossible.

    How to remove the noise interference is a big issue and up to

    date no solutions have been provided. A new solution based on

    correlation of multiple scales of the transients will be presented.

    As shown in Figs. 3 and 4, it is very difficult to discriminate

    the fault transients by the first level details. However, only one

    Table 1

    Ratio under different fault conditions

    Fault conditions = 0 = 45 = 60 = 90

    Fault

    resistance ()

    Fault distance

    (km)

    ra rb rc ra rb rc ra rb rc ra rb rc

    0 1 1.000 0.0537 0.0513 1.000 0.0513 0.0512 1.000 0.0519 0.04 1.000 0.0436 0.0407

    2 1.000 0.0459 0.0447 1.000 0.0460 0.0446 1.000 0.0447 0.0435 1.000 0.0355 0.0337

    3 1.000 0.0436 0.0362 1.000 0.04 0.04360 1.000 0.0426 0.0355 1.000 0.0341 0.0242

    0.5 1 1.000 0.0505 0.0485 1.000 0.0483 0.0482 1.000 0.0466 0.0449 1.000 0.0487 0.0456

    2 1.000 0.0433 0.0421 1.000 0.03 0.0409 1.000 0.04091 0.0385 1.000 0.0402 0.0386

    3 1.000 0.0409 0.0337 1.000 0.0398 0.0324 1.000 0.0374 0.0279 1.000 0.0378 0.0279

    1 1 1.000 0.0449 0.0431 1.000 0.0429 0.0431 1.000 0.0397 0.0385 1.000 0.0456 0.0419

    2 1.000 0.0376 0.0367 1.000 0.0367 0.0358 1.000 0.0326 0.0321 1.000 0.0369 0.0355

    3 1.000 0.0352 0.0280 1.000 0.0343 0.03 1.000 0.0308 0.0343 1.000 0.0343 0.0254

  • 7/29/2019 Wavelet Based Noise Cancellation Technique for Fault Location on Underground Power Cables

    4/14

    1352 C.K. Jung et al. / Electric Power Systems Research 77 (2007) 13491362

    Fig. 3. First level details of the wavelet transform at 1 km fault according to fault resistance (fault inception angle: 0): (a) fault resistance: 0 ; (b) fault resistance:

    0.5; (c) fault resistance: 1 .

    transient is significant with the high value while the magnitudes

    of the other transients are relatively low. It is discovered that the

    wavelet maxima at a scale 2j will propagate to another maxima

    at the coarser scale 2j+1 if both maxima belong to the same

    maxima line [12]. For the white noises, on average, the number

    of maxima decreases by a factor of 2 when the scale increases by

    2. Half of the maxima do not propagate from the scale 2j to the

    scale 2j+1. We adopted a simple algorithm to remove the noise

    relied on the variations in the scale of the wavelet transform data

    of the signal by using direct multiplication of the wavelet data at

    adjacent scales [13]. Our approach to detect the fault transients

    and locate the fault also bases on the variation of the wavelet

    data at adjacent scales by using the direct multiplication. It is

    simple, quick and straightforward.

    Supposingthe signalis decomposed by thewavelet at n levels,

    the detail coefficients will be D1, D2, . . ., Dn. Then the details

    at first two scales will be multiplied directly, give a correlation

    Corr1 as in Eq. (8). Next the correlation is rescaled to the first

    detail by Eq. (9).

    Corr1 = D1D2 (8)

    Corr new1 = Corr1

    PD1

    PCorr12n (9)

  • 7/29/2019 Wavelet Based Noise Cancellation Technique for Fault Location on Underground Power Cables

    5/14

    C.K. Jung et al. / Electric Power Systems Research 77 (2007) 13491362 1353

    Fig. 4. First level details of the wavelet transform at 2 km fault according to fault resistance (fault inception angle: 45): (a) fault resistance: 0 ; (b) fault resistance:

    0.5; (c) fault resistance: 1.

    where PD1 =

    D21 and PCorr1 =

    Corr12 are the powers of

    detail D1 and Corr1. n is iteration number.

    Next is to compare the absolute value of Corr new1 and D1.

    Values where D1 is more than Corr new1 are identified and

    stored in a new variable. This one is regarded as the new detail

    at level one, D1 new1.

    Then the Corr new1 and D3 will be multiplied directly, give

    a correlation2 Corr2 such as Eq. (10). Next the correlation is

    rescaled to the first detail by Eq. (11):

    Corr2 = Corr new1D3 (10)

    Corr new2 = Corr2

    PCorr new1

    PCorr22n (11)

    where PCorr new1 =

    Corr new12 and PCorr2 =

    Corr22 are

    the powers of Corr new1 and Corr2 and n is iteration number.

    As the first procedure, to compare the absolute value of

    Corr new1 and Corr new2, the values where Corr new1 more

    than Corr new2 are identified and stored in a new variable. This

    one is D1 new2.

    Finally, Corr new2 and D4 will be multiplied directly, giving

    a correlation Corr3 and rescaled Corr new3 as in Eqs. (12)

  • 7/29/2019 Wavelet Based Noise Cancellation Technique for Fault Location on Underground Power Cables

    6/14

    1354 C.K. Jung et al. / Electric Power Systems Research 77 (2007) 13491362

    and (13) as the same as above, and D1 new3 will be stored as

    usual:

    Corr3 = Corr new2D4 (12)

    Corr new3 = Corr3PCorr new2PCorr3

    2n (13)

    If at this stage, more than two fault transients can be detected

    at D1 new3, then locate the fault using the absolute value of D1new3 and stop the algorithm. If only one fault transient can be

    detected at D1 new3, then the algorithm will be repeated at the

    next iteration and finished when the signal detection is satis-

    fied. The whole procedure can be described by the flowchart in

    Fig. 5.

    Fig. 6. Lattice diagram in case of near half fault.

    Fig. 5. Flow chart of noise cancellation procedure for fault location.

  • 7/29/2019 Wavelet Based Noise Cancellation Technique for Fault Location on Underground Power Cables

    7/14

    C.K. Jung et al. / Electric Power Systems Research 77 (2007) 13491362 1355

    Fig. 7. Noise cancellation procedure at the 1 km fault (fault resistance: 0, fault inception angle: 90, n = 1): (a) D1; (b) D1 new1; (c) D1 new2; (d) abs(D1 new3).

  • 7/29/2019 Wavelet Based Noise Cancellation Technique for Fault Location on Underground Power Cables

    8/14

    1356 C.K. Jung et al. / Electric Power Systems Research 77 (2007) 13491362

    Fig. 8. Noise cancellation procedure at the 1 km fault (fault resistance: 0.5, fault inception angle: 45, n = 1): (a) D1; (b) D1 new1; (c) D1 new2; (d) abs(D1 new3).

  • 7/29/2019 Wavelet Based Noise Cancellation Technique for Fault Location on Underground Power Cables

    9/14

    C.K. Jung et al. / Electric Power Systems Research 77 (2007) 13491362 1357

    Fig. 9. Noise cancellation procedure at the 2km fault (fault resistance: 0.5, fault inception angle: 90, n = 1): (a) D1; (b) D1 new1; (c) D1 new2; (d) abs(D1 new3).

  • 7/29/2019 Wavelet Based Noise Cancellation Technique for Fault Location on Underground Power Cables

    10/14

    1358 C.K. Jung et al. / Electric Power Systems Research 77 (2007) 13491362

    Fig. 10. Noise cancellation procedure at the 2km fault (fault resistance: 0.5, fault inception angle: 90, n = 2): (a) D1; (b) D1 new1; (c) D1 new2; (d) abs(D1 new3).

  • 7/29/2019 Wavelet Based Noise Cancellation Technique for Fault Location on Underground Power Cables

    11/14

    C.K. Jung et al. / Electric Power Systems Research 77 (2007) 13491362 1359

    Fig. 11. Noise cancellation procedure at the 2 km fault (fault resistance: 1, fault inception angle: 45, n = 3): (a) D1; (b) D1 new1; (c) D1 new2; (d) abs(D1 new3).

  • 7/29/2019 Wavelet Based Noise Cancellation Technique for Fault Location on Underground Power Cables

    12/14

    1360 C.K. Jung et al. / Electric Power Systems Research 77 (2007) 13491362

    Fig. 12. Noise cancellation procedure at the 3km fault (fault resistance: 0.5, fault inception angle: 90, n = 2): (a) D1; (b) D1 new1; (c) D1 new2; (d) abs(D1 new3).

  • 7/29/2019 Wavelet Based Noise Cancellation Technique for Fault Location on Underground Power Cables

    13/14

    C.K. Jung et al. / Electric Power Systems Research 77 (2007) 13491362 1361

    6. Simulation results

    In this section, the noise cancellation technique is applied for

    fault location on underground power cable system. In order to

    test this algorithm, the faults on the first half, at 13 km from A

    S/S, are only to be considered.

    Fig. 6 shows the lattice diagram of the characteristic of travel-

    ing wave as the ground fault occurs on the first half. In this case,

    after the arrival time of the first and second reflections at A S/S

    are successfully detected using noise cancellation technique, the

    distance(X) to fault point can be calculated by Eq. (14):

    X =c(TP2 Tp2)

    2(14)

    where c is the propagation velocity on underground power

    cable system, and Tp1 and Tp2 are the arrival times of first and

    the second transients, respectively.

    Fig. 7 shows the noise cancellation procedure when the

    ground fault occurred at 1 km. In this case, fault resistance is

    0 and fault inception angle is 90. As shown in the figure,at the first level detail (Fig. 7(a)), it is hard to discriminate the

    reflected points because of the noises. However, after rescal-

    ing using multiple scales correlation, the noise is significantly

    removed. As shown in D1 new2 (Fig. 7(c)) the reflected point

    at A S/S can be easily detected. Finally, the distance to fault

    point can be calculated using the absolute value of D1 new3

    (Fig. 7(d)). In this case, the first and the second arrival times

    are 0.016667 and 0.016678 s, and the propagation velocity is

    1.67487 105 km/s as discussed in Section 3. The calculated

    distance is 0.921 km which is very close to the exact fault dis-

    tance of 1 km.

    In terms of fault at 1 km with fault resistance of 0.5 andfault inception angel of 45, the noise cancellation procedure is

    shown in Fig. 8. Many noises in D1 are gradually removed from

    D1 new1 to D1 new3. From these results, the distance to fault

    point can be calculated using the absolute value of D1 new3. In

    Fig. 8(d), the first and the second reflection time are 0.014587

    and 0.014599 s. The calculated distance is 1.005 km which is

    also very close to the exact fault distance of 1 km.

    In case of fault at 2 km with fault resistance of 0.5 and

    fault inception angel of 90, as shown in Fig. 9, the distance

    cannot be calculated because D1 new2 and D1 new3 have just

    one reflection signal at the first iteration (n = 1). In this case,

    algorithm will automatically go to the next step, n = 2. Fig. 10

    shows thenoise cancellationresult at the second iteration (n =2).

    In Fig. 10(d), the time of first and second reflections are easily

    detected at 0.016673 and 0.016697 s. Therefore, the calculated

    distance to fault point is 2.009 km. It is quite accurate.

    Figs. 11 and 12 show the noise cancellation results when

    the ground fault occurred at 2 and 3 km, respectively. In these

    two figures, the appropriate signals for fault location can be

    detected at the third iteration (n = 3) and the second iteration

    (n = 2), respectively.

    In Fig. 11(d), the arrival times of the two reflections are

    0.014593 and 0.014618 s. Therefore, the calculated distance to

    fault point is 2.093 km. The arrival times of reflected signals

    in Fig. 12(d) are 0.016679 and 0.016715 s, and its distance is3.014 km.

    The criterion used for evaluating the algorithm is the location

    error which is defined as:

    Error (%) =|actual location-calculated location|

    total line length 100 (15)

    This algorithm has been tested for a variety of simulated fault

    conditions which include changing fault resistance from 0 to 1,

    fault inception angle from 0 to 90 and fault location between

    1 to 3 km. The maximum location error is less than 3% and the

    average error is 1.132%. The errors for fault location in all faultconditions are shown in Table 2.

    As shown in Figs. 712 and Table 2, it is possible to discrim-

    inate the reflected signal from noises by the application of the

    algorithm proposed in this paper. This method is very useful in

    detecting the fault in noisy environment.

    Table 2

    Errors for fault location in different fault conditions

    Fault distance

    [km]

    Fault inception

    angle

    Fault resistance []

    0 0.5 1

    Calculated

    distance [km]

    n Error [%] Calculated

    distance [km]

    n Error [%] Calculated

    distance [km]

    n Error [%]

    1 0 0.921 1 1.257 1.005 1 0.079 1.005 2 0.079

    45 1.005 1 0.079 1.005 1 0.079 1.005 1 0.079

    60 1.005 1 0.079 1.005 1 0.079 1.005 1 0.079

    90 0.921 1 1.257 0.921 1 1.257 0.921 1 1.257

    2 0 2.093 3 1.479 2.093 3 1.479 2.093 3 1.479

    45 2.093 2 1.479 2.093 2 1.479 2.093 3 1.479

    60 2.009 1 0.143 2.093 2 1.479 2.093 2 1.479

    90 2.009 1 0.143 2.009 2 0.143 2.093 2 1.479

    3 0 3.182 3 2.896 3.182 3 2.896 3.182 4 2.896

    45 3.098 3 1.559 3.098 3 1.559 3.098 4 1.559

    60 3.098 3 1.559 3.098 3 1.559 3.098 4 1.559

    90 3.098 3 1.559 3.014 2 0.222 3.098 4 1.559

    Average error [%]: 1.132.

  • 7/29/2019 Wavelet Based Noise Cancellation Technique for Fault Location on Underground Power Cables

    14/14

    1362 C.K. Jung et al. / Electric Power Systems Research 77 (2007) 13491362

    7. Conclusions

    Fault location on underground power cable system is very

    difficult because the measurements include many noises. In this

    paper, in order to detect, classify the fault and discriminate the

    transients and the reflected signal from noise, a new algorithm

    based on multiple scale correlation of wavelet transform was

    presented using current signal from one end. By this algorithm,

    faulty phase can be detected and classified by the approximation

    components of three phases on 4th level. Then the details at

    first level are rescaled until the clear transients are identified.

    It proved that the noises can be significantly removed by the

    proposed algorithm.

    The algorithm was validated by simulation on real power

    cable system. From these results, the faults can be detected and

    located even in very difficult situations, such as at inception

    angles of 0 and 90.

    Acknowledgements

    This work has been supported by KESRI (R-2003-B-274),

    which is funded by Ministry of Commerce, Industry and Energy

    (MOCIE).

    References

    [1] X.H. Wang, Y.H. Song, C. Ferguson, Wave propagation characteristics

    on crossbonded underground power transmission cables and sheath fault

    location, Eur. Trans. Electric Power (ETEP) 13 (2) (2003) 127131.

    [2] X.H. Wang, Y.H. Song, Sheath fault detection and classification based on

    wavelet analysis, Eur. Trans. Electric Power (ETEP) 16 (4) (2006) 327

    344.

    [3] F.H. Magnago, A. Abur, Fault location using wavelets, IEEE Trans. Power

    Deliv. 13 (October (4)) (1998) 14751480.

    [4] E. Styvaktakis, M.H.J. Bollen, I.Y.H. Gu, A fault location technique using

    high frequency fault clearing transients, IEEE Power Eng. Rev. 19 (May

    (5)) (1999) 5060.

    [5] M.M. Tawfik, M.M. Morcos, A novel approach for fault location ontransmission lines, IEEE Power Eng. Rev. 18 (November (11)) (1998)

    5860.

    [6] A.M. Gaouda, S.H. Kanoun, M.M.A. Salama, A.Y. Chikhani, Generation,

    wavelet-based signal processing for disturbance classification and mea-

    surement, IEE Proc. Transm. Distrib. 149 (May (3)) (2002) 310318.

    [7] I.K. Yu, Y.H. Song, Wavelet transform and neural network approach to

    developing adaptive single-pole auto-reclosingschemesfor EHV transmis-

    sion systems, IEEE Power Eng. Rev. 18 (November (11)) (1998) 6264.

    [8] F.N.Chowdhury, J.L.Aravena, A modularmethodologyfor fastfault detec-

    tionand classificationin power systems,IEEE Trans.ControlSyst.Technol.

    6 (September (5)) (1998) 623634.

    [9] Z.Q. Bo, M.A. Redfern, G.C. Weller, Positional protection of transmission

    line using fault generated high frequency transient signal, IEEE Trans.

    Power Deliv. 15 (3) (2000) 888894.

    [10] X.H. Wang, R.S.H. Istepanian, Y.H. Song, Microarray image de-noisingusing stationary wavelet transform, in: Proceedings of the 4th IEEE Con-

    ference on Information Technology Applications, 2003, pp. 1518.

    [11] H. Ye, G. Wang, S.X. Ding, A new fault detection approach based on

    parity relation and stationary wavelet transform, in: IEEE Proceeding of

    the American Control Conference, June 2003, pp. 29912996.

    [12] Stephane Mallat, Wen Liang Hwang, Singularity detection and processing

    with wavelet, IEEE Trans. Inform. Theory 38 (2) (1992) 617643.

    [13] Y. Xu, J.B. Weaver, D.M. Healy, J. Lu, Wavelet transform domain filters:

    a spatially selective noise filtration technique, IEEE Trans. Image Process.

    3 (6) (1994) 747758.