Drayton Beaumont Services Ltd. Newstead Trading Estate, Trentham, Stoke-on-Trent, Staffordshire. ST4 8HX Office Line: +44 (0) 1782 645170 Fax Line: +44 (0) 1782 645171 Website: www.draytonbeaumontservices.com email: [email protected] Page 1 of 3 TECHNICAL SUBMISSION Technical Submission Ref. : DBS-507-TSM-013 Revision : A Technical Submission Title : Pressurisation Unit & Expansion Vessel Project Number : DBS 507 Project Name : New Training Centre & Restaurant, Slimming World Completed By : J.Burns Issued To (Name / Company) : Scott Churchill / Morgan Sindall Construction Manufacturer Model No. Of DutyPoint Systems Quantum QP-35 Pressurisation Unit 1 DutyPoint Systems Zilmet 200ltr Expansion Vessel 2 General Description of Equipment: The proposed pressurisation equipment shall be supplied by Duty Points Systems Ltd and shall be the Quantum range of pressurisation units, model QP-35. The pressurisation unit shall be installed with 2no. 200ltr Zilmet expansion vessels supplied by Duty Points Systems Ltd. The unit has the following features: Floor mounted configuration unit with base frame and steel enclosure. 10ltr polyethylene break tank with lid, WRAS approved ball float and valve, type AB air gap to BS13077, 22mm overflow and suction strainer. Drain valve and isolation valves will be installed across all components. Run and standby pumps with electrical starters. Pumps fitted with non-return valves. Pressure transducer control. The unit is suitable for connection to a local BMS and the integral controls are provide the following functions; system fill mode, system leak detection, adjustable pressure differential. Front LED display facia with high pressure, low pressure, pump trip warnings, power on indication, fault indications. VFC’s available to integration with BMS for the following; pump 1 run, pump 1 fail/trip, pump 2 run, pump 2 fail/trip, low pressure, high pressure, excess starts, low water, boiler interlock. Pumps capable for continuous running for system filling.

Upload: others

Post on 01-Jan-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: tomrobbo.comtomrobbo.com/dbsinfo/designstuff/DBS-507-TSM-013... · Web viewThese are capable of a maximum cold pressure of 3.2bar. Expansion vessels shall be the floor standing vertical

Drayton Beaumont Services Ltd.Newstead Trading Estate, Trentham, Stoke-on-Trent, Staffordshire. ST4 8HXOffice Line: +44 (0) 1782 645170 Fax Line: +44 (0) 1782 645171Website: www.draytonbeaumontservices.com email: [email protected]

Page 1 of 3 TECHNICAL SUBMISSION

Technical Submission Ref. : DBS-507-TSM-013 Revision : A

Technical Submission Title : Pressurisation Unit & Expansion Vessel

Project Number : DBS 507

Project Name : New Training Centre & Restaurant, Slimming World

Completed By : J.Burns

Issued To (Name / Company) : Scott Churchill / Morgan Sindall Construction

Manufacturer Model No. Of

DutyPoint Systems Quantum QP-35 Pressurisation Unit 1

DutyPoint Systems Zilmet 200ltr Expansion Vessel 2

General Description of Equipment:

The proposed pressurisation equipment shall be supplied by Duty Points Systems Ltd and shall be the Quantum range of pressurisation units, model QP-35. The pressurisation unit shall be installed with 2no. 200ltr Zilmet expansion vessels supplied by Duty Points Systems Ltd.

The unit has the following features:

Floor mounted configuration unit with base frame and steel enclosure. 10ltr polyethylene break tank with lid, WRAS approved ball float and valve, type AB air gap

to BS13077, 22mm overflow and suction strainer. Drain valve and isolation valves will be installed across all components. Run and standby pumps with electrical starters. Pumps fitted with non-return valves. Pressure transducer control. The unit is suitable for connection to a local BMS and the integral controls are provide the

following functions; system fill mode, system leak detection, adjustable pressure differential.

Front LED display facia with high pressure, low pressure, pump trip warnings, power on indication, fault indications.

VFC’s available to integration with BMS for the following; pump 1 run, pump 1 fail/trip, pump 2 run, pump 2 fail/trip, low pressure, high pressure, excess starts, low water, boiler interlock.

Pumps capable for continuous running for system filling. Be installed complete with an expansion vessel(s) suitable for operating up to 10bar at a

temperature of 100oC.

The system will be installed with 2no. 200ltr expansion vessels also supplied by DutyPoint systems. These are capable of a maximum cold pressure of 3.2bar. Expansion vessels shall be the floor standing vertical type.

Page 2: tomrobbo.comtomrobbo.com/dbsinfo/designstuff/DBS-507-TSM-013... · Web viewThese are capable of a maximum cold pressure of 3.2bar. Expansion vessels shall be the floor standing vertical

Drayton Beaumont Services Ltd.Newstead Trading Estate, Trentham, Stoke-on-Trent, Staffordshire. ST4 8HXOffice Line: +44 (0) 1782 645170 Fax Line: +44 (0) 1782 645171Website: www.draytonbeaumontservices.com email: [email protected]

Drayton Beaumont Services Ltd.Newstead Trading Estate, Trentham, Stoke-on-Trent, Staffordshire. ST4 8HXOffice Line: +44 (0) 1782 645170 Fax Line: +44 (0) 1782 645171Website: www.draytonbeaumontservices.com email: [email protected]

Page 2 of 3 TECHNICAL SUBMISSION

Please see attached calculations which shows the rationale for the expansions vessel sizing.

Please refer to system schematic (when available) which shows pipework configuration and general system layout.

Equipment Literature Attached ☒ Not Applicable ☐Equipment Schedule Attached ☒ Not Applicable ☐

Specification By : CPW Consulting

Specification Title :Slimming World Cotes Park New Build, 16113, Mechanical Services Performance Specification & Tender Analysis, Rev T1 (22.06.16)

Equipment Compliant with Specification? Yes ☒ No ☐

Reason For Non Compliance (if required):

Note the following discrepancies against the specification which have been noted below but which do not represent a non-compliance against the performance specification:

The unit has a corrosion resistant steel finish and is not painted.

Note also that no equipment manufacturer is specified within the CPW specification.

Issued Date : 10/05/2017

Page 3: tomrobbo.comtomrobbo.com/dbsinfo/designstuff/DBS-507-TSM-013... · Web viewThese are capable of a maximum cold pressure of 3.2bar. Expansion vessels shall be the floor standing vertical

Drayton Beaumont Services Ltd.Newstead Trading Estate, Trentham, Stoke-on-Trent, Staffordshire. ST4 8HXOffice Line: +44 (0) 1782 645170 Fax Line: +44 (0) 1782 645171Website: www.draytonbeaumontservices.com email: [email protected]

Drayton Beaumont Services Ltd.Newstead Trading Estate, Trentham, Stoke-on-Trent, Staffordshire. ST4 8HXOffice Line: +44 (0) 1782 645170 Fax Line: +44 (0) 1782 645171Website: www.draytonbeaumontservices.com email: [email protected]

Page 3 of 3 TECHNICAL SUBMISSION

Approval / Comments Required Date : 24/05/2017

Approval / Comments Received Date :

Status A - Approved ☐Status B – Approved With Comments ☐Status C – Re-Submission Required ☐

Comments: