PBTOMM User Manual 1. Contents and General Contents 1. 总总...........................................................1 2. PBTOMM 总总总总总..................................................2 4. PBTOMM 总 PP0 总总总总总总............................................4 5. BTOMM 总 GSD 总总...............................................6 6. (总 总 总 、、)......................................................8 1. General 1.1 Main features of PBTOMM Senlan inverter supporting MODBUS communication can be connected with PROFIBUS-DP through PBTOMM communication module. Thus, the inverter can be controlled and monitored by PROFIBUS. Main features of PROFIBUS communication module are described as follows: (1) One PBTOMM communication module can only connected with one inverter. (2) Power supply: DC24V780mA (3) The address of slave station can be set by the dial switch. (4) ON or OFF of built-in PROFIBUS terminal resistance can be selected through jumper. (5) MODBUS communication error indication and PROFIBUS communication error indication (6) Support the data types of PP01-PP05 in PROFIDRIVE, but not support the definition of “master control word CW” and “master control word SW” in PROFIDRIVE (7) The inverter access parameters can be configured. (8) All inverter parameters can be visited by using PP0 with “parameter zone (PKW)”. 1.2 How to use the Manual For quick use of PBTOMM module, please refer to the following usage mode: (1) Before use this module, please refer to the “inverter parameter addressing method”, “communication parameter 1

Upload: others

Post on 28-Oct-2019

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: file · Web view(6) Support the data types of PP01-PP05 in PROFIDRIVE, but not support the definition of “master control word CW” and “master control word SW” in PROFIDRIVE

PBTOMM User Manual 1. Contents and General

Contents 1. 总述..............................................................................................................................12. PBTOMM 外观及连接..................................................................................................24. PBTOMM 的 PP0 数据类型定义...................................................................................45. BTOMM 的 GSD 文件..................................................................................................66. 一般应用参考(控制变频器启停、复位、给定频率).......................................................8

1. General 1.1 Main features of PBTOMM

Senlan inverter supporting MODBUS communication can be connected with PROFIBUS-DP through PBTOMM communication module. Thus, the inverter can be controlled and monitored by PROFIBUS. Main features of PROFIBUS communication module are described as follows:

(1) One PBTOMM communication module can only connected with one inverter.

(2) Power supply: DC24V780mA

(3) The address of slave station can be set by the dial switch.

(4) ON or OFF of built-in PROFIBUS terminal resistance can be selected through jumper.

(5) MODBUS communication error indication and PROFIBUS communication error indication

(6) Support the data types of PP01-PP05 in PROFIDRIVE, but not support the definition of “master control word CW” and “master control word SW” in PROFIDRIVE

(7) The inverter access parameters can be configured.

(8) All inverter parameters can be visited by using PP0 with “parameter zone (PKW)”.

1.2 How to use the Manual For quick use of PBTOMM module, please refer to the following usage mode:

(1) Before use this module, please refer to the “inverter parameter addressing method”, “communication parameter set numbers corresponding to menu codes” and “list of communication instruction variables” behind the “FF communication parameters” in the “detailed annotation of functional parameters” of “Inverter User Manual”.

(2) Chapters 1, 2, 4, 5 and 6 were extracted from “User Manual of PBTOMM Communication Module”. The original chapter numbers are maintained in “PBTOMM User Manual ”. “User Manual of PBTOMM Communication Module” also includes Chapter 3 “Introduction to PR0FIBUS” and Chapter 7 “Use Examples of PBTOMM Communication Module”.

1

Page 2: file · Web view(6) Support the data types of PP01-PP05 in PROFIDRIVE, but not support the definition of “master control word CW” and “master control word SW” in PROFIDRIVE

(3) Please download the package of “User Manual, Examples and GSD of PBTOMM Communication Module ” on our website: www. Chinavvvf.com .

2

Page 3: file · Web view(6) Support the data types of PP01-PP05 in PROFIDRIVE, but not support the definition of “master control word CW” and “master control word SW” in PROFIDRIVE

PBTOMM User Manual 2. Appearance and Connection of PBTOMM

2. Appearance and Connection of PBTOMM 2.1 Appearance of PBTOMM communication module

(1) Description on PB (green) indicator light: It indicates normal PROFIBUS connection, if the light flickers. It indicates a communication error of PROFIOUS, if the light is off.

(2) Description on MB (red) indicator light: MB will flicker when PB is off (PROFIBUS error). If MB is normally on when PB flickers (PROFIBUS normal), it indicates normal MODBUS data. If MB flickers, it indicates error of some MODBUS data. If MB is off, it indicates totally wrong communication of MODBUS.

(3) Description on port signal

Port Description A (8) PROFIBUS Signal Line A is connected with Pin 8 of

PROFIBUS-DP. B (3) PROFIBUS Signal Line B is connected with Pin 3 of

PROFIBUS-DP. PE Please reliability connect the PE line with the ground. PROFIBUS-DP

PROFIBUS, DB9 port

485- Connect with Inverter 485- 485+ Connect with Inverter 485+ +24V Connect with DC24V power supply GND Connect with DC24V power supply

When a plug terminal is used for connection with PROFITS, please reliably connect the shielding layer of PROFIBUS signal line with the ground. (4) Description on DB9 port signal of PROFIBUS-DP

Signal ConnectorShielded 1 cable shieldB 3 PROFIBUS Signal Line BDGND 5 Data ground, V reference ground VP 6 Supply voltage: 5V

3

Page 4: file · Web view(6) Support the data types of PP01-PP05 in PROFIDRIVE, but not support the definition of “master control word CW” and “master control word SW” in PROFIDRIVE

A 8 PROFIBUS Signal Line A

2.2 Terminal resistance and PROFIBUS address setting PROFIBUS address of PBTOMM communication module defaults to 03H

(OFF). The terminal resistance of built-in PROFIBUS can be selected by jumper. If it is necessary for change, please open the box of PBTOMM communication module. The schematic diagram is shown as follows:

(1) JP1 terminal resistance jumper selection defaults to OFF. If PBTOMM is a terminal device on PROFIBUS bus, the bus terminal resistance must be set. Jumper JP1 can be ON, or external terminal resistance can be used.

(2) PROFIBUS address can be set with the dial switch. The value of R defaults to 03H (OFF). Bit 8 of the dial switch will not be used. Bits 1-7 are corresponding to Bit -Bit-6. ON is 1, and OFF is 0. If the dial switch is used for the first time, please uncover the plastic film on the surface.

Set Value of PROFIBUS Address: 09H (the black block shows the position of the switch)

4

终端电阻跳线 PROFIBUS地址设置拨码开关,1为最低位

Page 5: file · Web view(6) Support the data types of PP01-PP05 in PROFIDRIVE, but not support the definition of “master control word CW” and “master control word SW” in PROFIDRIVE

PBTOMM User Manual 4. Definition of PBTOMM PP0 Data Type

4. Definition of PBTOMM PP0 Data Type See Table 3-1 for the definition of PP0 data of PBTOMM communication

module. Each black cell corresponds to one 16-bit character.

Table 4-1

4.1 Process data zone (PZD)“Process data zone (PZD)” stands for periodic data access, which can be

used to conveniently control the equipment (e.g. operation, stop, reference and fault reset) and quickly read the actual value (e.g. output frequency and output current).

CW Corresponding to inverter MODBUS address: 0×3200; the inverter “control word” can be selected or not selected.

REF Corresponding to inverter MODBUS address: 0×3201; the inverter “given communication frequency”' can be used or not used.

SW Corresponding to inverter MODBUS address: 0×3210; the inverter “master state word” cannot be changed.

ACK Corresponding to inverter MODBUS address: 0×3211; the inverter “operating frequency” cannot be changed.

CPD1-CPD8

To be selected by the user, corresponding to the inverter parameter (such as given PID)

SPD1-SPD8 To be selected by the user, corresponding to the inverter parameter to be read (such as output voltage and output current)

For the inverter MODBUS parameter addressing and the definition of CW and SW, please refer to the “inverter parameter addressing method” and “list of communication instruction variables” below the “FF communication parameters” below the “detailed annotation of functional parameters” of “Inverter User Manual”.

4.2 Parameter zone (PKW)PKW visits the inverter parameters by means of request and response. It

is usually used for non-periodic access of inverter parameters. PKW can be used to access all inverter parameters. Attention shall be paid to many details. Specific definition is shown as follows:

IDMaster to slave (send) Slave to master (receive) 0-no request 0-no response

5

参数区(PKW) 过程数据区(PZD)

数值

Page 6: file · Web view(6) Support the data types of PP01-PP05 in PROFIDRIVE, but not support the definition of “master control word CW” and “master control word SW” in PROFIDRIVE

1-read request 1-data ready

2-write request

0×80+fault code; the fault code is defined as follows: 0: receive data length error; 1: retain; 2: unreasonable data address; 3: data value out of scope; 4: write data failed (write read only parameter or parameter that cannot be modified in the operation); 5: retain; 6: receive data CRC error; 7: receive out of time

INDMaster to slave (send) Slave to master (receive) Parameter address (corresponding MODBUS parameter address)

Parameter address (corresponding to the processed MODBUS parameter address)

Value Master to slave (send) Slave to master (receive) High 16 bits

Low 16 bits High 16 bits

Low 16 bits

Not used (ignore)

Request ID =1: ignoreRequest ID =2: parameter value

Not used (ignore)

Return ID=0: ignore (value not determined); Return ID=1: request ID=1, return parameter value; request ID=2: equal to the written parameter value; Return ID=0x80+fault code: ignore (value not determined)

Attention: In order to protect the data consistency, the following agreement and description is made:

(1) When it is necessary for re-sending if an error code is returned by the slave station, ID shall be cleared. The parameter request shall be sent after “no response” to return.

(2) If the previously sent parameter is different from this parameter, ID may not be cleared after obtaining correct response in the previous time. It shall be directly sent after parameter modification.

(3) The following agreement can be referred when it needs to judge whether the returned data is the response to this request:

1) “Write parameter” is sent: If “IND” and “value” of the return data are consistent with the sent parameter, it is the response to the parameter sent this time.

2) “Read parameter” is sent: If “IND” of the return data is consistent with the sent parameter, it is the response to the parameter sent this time.

(4) When PKW is used to access the inverter parameters, attention shall be paid to the communication response time. It is correlated with PROFIBUS bus Baud rate, number of PROFIBUS slave stations, MODBUS Baud rate and PBTOW response time.

6

Page 7: file · Web view(6) Support the data types of PP01-PP05 in PROFIDRIVE, but not support the definition of “master control word CW” and “master control word SW” in PROFIDRIVE

PBTOMM User Manual 5. GSD File of PBTOMM

5. GSD File of BTOMM GSD file of PBTOMM is PBTOMM.GSD. After PBTOMM.GSD file is

installed in STEP 7, this module will appear under PROFIBUS DP/Additional Field Devices/Gateway (name: PBTOMM).

5-1 CW_REF_CPD1-8_Status, Sir_ACK_SPD1-8_StatusSlot1: CW_REF_CPD1-8_Status and Slot2: SW_ACK_SPD1-8__Status

are preset after adding PBTOMM. See Figure 5-1. It is used to detect MODBUS data communication state between PBTOMM communication module and the inverter. See Table 5-1 for specific definition.

Figure 5-1Slot1: CW_REF_CPD1-8_Status indicates “control parameter” in PBTOMM and the inverter communication state. It is 32-digit data. Bit31-

30Bit29-

28Bit27-

26Bit25-

24Bit23-

22Bit21-

20Bit19-

18Bit17-

16Bit15-

14Bit13-

12Bit11-

0

CW REF CPD1 CPD2 CPD3 CPD4 CPD5 CPD6 CPD7 CPD8 Not used

Slot2: SW_ACK_SPD1-8_Status indicates “state parameter” in PBTOMM and the inverter communication state. It is 32-digit data. Bit31-

30Bit29-

28Bit27-

26Bit25-

24Bit23-

22Bit21-

20Bit19-

18Bit17-

16Bit15-

14Bit13-

12Bit11-

0

SW ACK SPD1 SPD2 SPD3 SPD4 SPD5 SPD6 SPD7 SPD8 Not used

Table 5-1

The parameter of 2’b00= is not used. 2’b11=PBTOMM indicates normal communication of the communication module and the inverter. 2’b01=PBTOMM indicates communication error of the communication module and the inverter.

5.2 Module user parameter setting In Step 7 (hardware configuration), double click PPO in Slot after

selecting the type of the applied PPO, and set the user parameters; Figure 5-2 shows the parameter setting interface of PPO4. See Table 5-2 for the description on parameter setting.

7

SenLan_PBTOMM

Slot Order Number / Designation I Add… Q AddressComment

Page 8: file · Web view(6) Support the data types of PP01-PP05 in PROFIDRIVE, but not support the definition of “master control word CW” and “master control word SW” in PROFIDRIVE

Figure 5-2Parameter name Description FF-0l communication data format

Maintain consistent with FF-01 parameter of the connected inverter

FF-02 communication Baud rate

Maintain consistent with FF-02 parameter of the connected inverter

FF-03 inverter address

Maintain consistent with FF-03 parameter of the connected inverter

CV parameter Corresponding to inverter MODBUS address: 0×3200 (inverter “master control word”); it can be used or not used.

REF parameter Corresponding to inverter MODBUS address: 0×3201 (inverter “given communication frequency”); it can be used or not used.

SPDn parameter set number

Corresponding to high 8 bits of MODBUS address of the inverter parameter to be read

SPDn parameter set serial number

Corresponding to low 8 bits of MODBUS address of the inverter parameter to be read (decimal number)

CPDn parameter set number

Corresponding to high 8 bits of MODBUS address of the inverter parameter to be written

SPDn parameter set serial number

Corresponding to low 8 bits of MODBUS address of the inverter parameter to be written (decimal number)

Table 5-2

The maximum value of n is correlated with the selected PPO. PPO1 and PPO3 have no SPD and CPD parameters for setting. There are four SPD and CPD for PPO2 and PPO4 respectively, and 8 for PPO5.

8

Page 9: file · Web view(6) Support the data types of PP01-PP05 in PROFIDRIVE, but not support the definition of “master control word CW” and “master control word SW” in PROFIDRIVE

PBTOMM User Manual 6. Common Application Reference (Control Inverter Start & Stop, Reset and Given Frequency)

6. Common Application Reference (Control Inverter Start & Stop, Reset and Given Frequency)

The inverter start & stop, reset and given frequency can be controlled through PBTOMM communication module by S7-300 with PROFIBUS bus:

(1) Prepare for the “Inverter User Manual” and refer to “Definition of PBTOMM PPO data” and “GSD file of PPTOMM” in this Manual;

(2) Open the box of PBTOMM communication module and set the address of PROFIBUS according to the actual needs; the default address is 03H (it is also 03H when the dial switch is OFF);

(3) Set the inverter parameters:

1) Given master channel for ordinary operation of F0-01: 1: given communication;

2) Selection of F0-02 run command channel: 2: given communication;

3) For communication resetting, F4-0X (X=5 for SB70 series; X=4 for SB200 series; X=4 for SB-HV series) shall be typed in the terminal. The factory value is 13 (fault reset), which shall be changed into 0 (not connected to the following signal).

(4) During configuration in STEP 7, install PBTOMM.GSD file first; then, this module will appear under PROFIBUS DP/Additional Field Devices/Gateway (name: PBTOMM).

(5) Add onto PBTOMM bus, and set its address as PROFIBUS address set in Step 1

(6) Add the needed type of PPO in Slot with reference to the definition of PPO data in Chapter 4

(7) Double click the newly added PPO and make sure that “FF-01 communication data format”, “FF-02 communication Baud rate” and “FF-03 inverter address” in PPO parameters are consistent with FF parameters of corresponding inverter; set “CW parameter” and “REF parameter” in PPO parameters as “use”; add another CPD and SPD according to the actual needs; for the parameter set number, please refer to the table and description behind the detailed annotation of “FF communication parameters” in the User Manual.

(8) Common flow for inverter start, stop and reset controlled by PLC:

1) For the convenience of description, let’s suppose that MW0 is a temporary variable of CW data. MW0 will be sent to corresponding data zone of “CW parameter”.

2) Initialize MW0 = 0×1E in OB100;

3) Set bit0 of MW0 as 1 when the inverter needs to be started;

4) Set bit0 of MW0 as 0 when the inverter needs to be shut down;

9

Page 10: file · Web view(6) Support the data types of PP01-PP05 in PROFIDRIVE, but not support the definition of “master control word CW” and “master control word SW” in PROFIDRIVE

5) Set bit8 as 1 when the inverter needs to be reset in case of a fault, maintain for T and then set as 0; the minimum value of T is correlated with the communication transmission time. In other words, it cannot be set as 0 unless the inverter obtains the data (namely Bit8 of MW0 as 1).

10