wfc sc 20
DESCRIPTION
xTRANSCRIPT
-
WATER FIRED CHILLER WFC-SC 20
www.maya-airconditioning.com
Item WFC-SC 20 Cooling capacity kW 70
C
h
i
l
l
e
d
w
a
t
e
r
Temperature Inlet C 12,5
Outlet C 7
Evaporator pressure loss kPa 65,8
Maximun operating pressure kPa 588 Flow rate l/s 3,06 Water retention volume l 47
C
o
o
l
i
n
g
w
a
t
e
r
Heat rejection kW 171
Temperature Inlet C 31 Outlet C 35 Absorber/condenser pressure loss kPa 45,3 Coil fouling factor M2hrK/kW 0,086 Maximun operating pressure kPa 588 Flow rate l/s 10,2 Water retention volume l 125
H
e
a
t
m
e
d
i
u
m
Heat input kW 100,4
Temperature Inlet C 88 Outlet C 83 Range C Min. 70 Max 95
Generatoer pressure loss kPa 46,4 Maximun operating pressure kPa 588 Flow rate l/s 4,8 Water retention volume l 54
Electical Power supply 400V 3 fasi 50Hz Consumption W 260 Current A 0,92
Control Cooling ON - OFF Dimensions
Width mm 1060 Depth mm 1300 Height (includes fixing plate) mm 2030
Weight Dry kg 930 Operating kg 1156 Acoustics Noise level dB(A) 49
Piping diameter Chilled water mm 50 Cooling water mm 50 Heat medium mm 50
Cabinet and finish
Weatherproof cabinet suitable for indoor or outdoor application comprising silver metallic pre-painted hot dip zinc coated sheet steel exterior panels