wiring std

Upload: chanel-holt

Post on 03-Apr-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 Wiring Std

    1/52

    Standards of Installationfor

    Network Cablingat the

    University of Texas at ArlingtonArlington, Texas

    Campus Network Services

    Created by J ason Ray DuBose, NETWORK SUPPORT SPECIAL IST IIIModified by Brad Samek, NETWORK MANAGER

    Standards as of 01/09/2006Revision - 22.2

  • 7/28/2019 Wiring Std

    2/52

    I. TABLE OF CONTENTS Page 2-4

    II . GENERAL MATERIAL SPECIFICATIONS Page 5

    1.0 Copper Cable Page 51.1 Number of Drops per Room Page 61.2 Network Data Connections Page 61.3 Telecommunications Telephone Page 7

    1.3.1 Telephone Trunk Cables Page 7

    2.0 Telecommunications Room Requirements Page 72.1 Room Design and Requirements Page 72.2 New Installations Page 82.3 Existing Installations Page 8-92.4 Special Installations Page 92.5 Category 5e Patch Panels/Wall Brackets Page 92.6 Electronics Rack Page 102.7 66 - Blocks Telephone Termination Page 11-142.8 Wire Management Page 15-162.9 Transition Between Floors Page 172.10 Patch Cord Colors Page 18

    2.10.1 Patch Cord Specifications and Pin-outs Page 18-19

    II I . GENERAL COPPER REQUIREMENTS Page 20

    3.0 Network Data - Horizontal Cable Page 203.1 Cat 5e Cable Specifications Page 203.2 Cat 6 Cable Installations Page 203.3 Cable Pathways Page 20-23

    4.0 Vertical Wall Drops Page 234.1 Concealed (in-wall) or Flush Mounted Page 234.2 Exposed or Surface Mounted Page 244.3 Copper Terminations Page 25

    4.3.1 RJ -45 Type Page 254.3.2 J ack Colors Page 25

  • 7/28/2019 Wiring Std

    3/52

    5.0 Work Area Outlet (WAO) Office/Classroom Page 255.1 Concealed Page 265.2 Exposed Page 265.3 Faceplate Labels Page 27

    5.4 Zone Cabling Page 285.5 Floor Boxes Page 29

    6.0 Testing and Documentation Twisted Pair Cable Page 30

    IV. FIBER OPTIC CABLE REQUIREMENTS Page 30

    7.0 Fiber Optic Cable Page 307.1 Fiber Optic Cable Construction Page 30

    7.1.1 Outside Plant Fiber Cable Page 307.1.2 EXCLUSIONS: Fiber Specifications not allowed at UTA. Page 317.1.3 Indoor Fiber Cable Page 317.1.4 Standard Fiber Counts for Cables Page 31

    7.2 Wall and Rack Mount Fiber Enclosures Page 31-327.3 Slack Fiber Enclosures Page 327.4 Splices and Splice Enclosures Page 337.5 Fiber Connectors Page 33

    7.5.1 Terminating-Fiber Connectors Page 33

    7.6 Labeling Fiber Optic Cable Page 347.7 Testing and Documentation Fiber Optic Cable Page 34

    7.7.1 Fiber System Loss Budget Calculation Page 357.8 Fiber Splicing Procedures: Page 36

    7.8.1 Fiber Optic Cable Outside Plant Splice Enclosures Page 367.8.2 Testing and Required Documentation for Fiber Splices Page 36

    8.0 Outside Plant Fiber Optic Cable Page 378.1 Outside Fiber Pathways Page 37

    8.2 Outdoor Pull Points Page 37-388.3 Conduits and Inner-ducts for Fiber Optic Cable Page 388.4 Underground Cables Page 38

  • 7/28/2019 Wiring Std

    4/52

    9.0 Building Entrance Point and Inside Fiber Pathways Page 389.1 Inside Fiber Pathways Page 399.2 Indoor Pull Points Page 39

    10.0 Grounding Page 4010.1 Grounding in Telecommunication Rooms Page 41

    V. SAFETY Page 42

    11.0 General Safety Practices Page 4211.1 Asbestos Clearance Page 4211.2 Fire Stopping Page 42-4311.3 Environmental Health & Safety - Attachment 1 Page 44-48

    VI. ADDITIONAL POINTS OF INTEREST Page 49

    12.0 Other Required Campus Notification Page 4912.1 Campus Notification for Core Holes Page 4912.2 After Hours or Holiday Work Page 4912.3 Work in Hazardous or High Liability Areas Page 49

    13.0 GLOSSARY OF TERMS Page 5014.0 IMPORTANT CAMPUS NUMBERS Page 51

  • 7/28/2019 Wiring Std

    5/52

    II . GENERAL MATERIAL SPECIFICATIONS

    1.0 Copper Cable

    NOTE:TIA/EIA 568A Wiring Standardsare the foundation of UTAs Network practices. The followingare specific parts and techniques used in cooperation with the TIA/EIA 568A Cabling Standard. Werequire that installers beBelden Certifiedand followBelden Data-Twist 350 Installation Procedures.

    CABLE TRAUMA: Twisted pair cable can easily be damaged and unravel the pair twist that allows themto pass Cat 5e certification. The cable installers are expected to prevent twisting and kinks duringinstallation. Remember the maximum tension allowed on a twisted pair cable is 25 foot/pounds of force.

    Above that amount and the cable has been damaged.

    FOUR EXAMPLES OF UNACCEPTABLE CABLE TRAUMA

    Photo 1: A kink that has been pulledthrough with excessive force.

    Photo 2: A cable that has beenbent back upon itself.

    Photo 3: Another example of aloop in the cable that has beenforced straight, causing severecable trauma.

    Photo 4: A cable that has beensmashed or crushed. Note thecuts in the outer cable jacket.

  • 7/28/2019 Wiring Std

    6/52

    1.1 Number of Drops per Room

    A standard drop for a new installation will consist of(3) Cat 5e cables. Two of these cables will be terminatedwith a blue jack, denoting use as a data cable. The third Cat 5e cable will be terminated with a yellow jack,denoting use as a telephone jack.

    Faculty/StaffOffices - A minimum of one standard drop will be installed for each 100 square foot of space ieach room.

    Classrooms/Conference Rooms - A minimum of one standard drop will be installed in each room. Lab Space A minimum of 1 standard drop will be installed in each room. Additional wiring infrastructure

    to be determined on a per case basis (i.e. Computer Lab).

    General Space Utilization A minimum of 1 standard drop will be installed in any room that is capable ofbeing utilized as office space.

    Telecommunication Room Cross-connects- A minimum of(2) Cat 5e cross-connect cables will be installebetween telecommunication rooms as stipulated by UTA. These cables will be terminated with orange jacks

    1.2 Network Data Connections

    All cable used for Data Network will be Category 5e, BELDEN, Datatwist350-1701A (for plenuminstallations or as instructed by UTA personnel) andDatatwist350-1700A (for non-plenum installations).

    Unless specifically stated otherwise by UTA, plenum rated cable will beYellow in color and non-plenumrated cable will beBlue in color.

    The cable will be installed under the Belden guidelines for the installation of Datatwist350 Cat 5e cable.

    The cable will be used in reels of 1000' minimum when cable is purchased for the bid project.

    Subsequent shorter runs on the same project will take advantage of short spools of cable.

    A minimum of three (3) Cat 5e cables will be run to each room.

    Cable must be Plenum rated cable unless specifically stated otherwise by UTA. Left over cable will be turned over to the UTA Network Group upon completion of the Project.

    Below is the recommended fill chart for BELDEN Datatwist350 (1701A) Cat 5ecables in areas whereconduits are used. NOTE: These numbers are only valid for cables with outside diameters of approximately0.200 inches. The below chart is based on the NEC at a 40% fill ratio.

    Conduit Fill ChartTrade Size Number ofCable

    1

    1-1/41-1/2 25

    2 422-1/2

    33-1/2 12

    4 161TABLE 1

  • 7/28/2019 Wiring Std

    7/52

    1.3 Telecommunications - Telephone

    All Cable will be Category 5e, BELDEN BrandDatatwist350-1701A (for plenum installations or asinstructed by UTA personnel) andDatatwist350-1700A (for non-plenum installations).

    Unless specifically stated otherwise by UTA, plenum rated cable will beYellow in color and non-plenum

    rated cable will beBlue in color. The cable will be used in reels of 1000' minimum when cable is purchased for the bid project.

    Subsequent shorter runs on the same project will take advantage of the short spools of cable.

    A minimum of one (1) Cat 5e cable run to each room will be designated for telephone.

    Cable must be plenum rated cable unless specifically stated otherwise by UTA.

    Left over cable will be turned over to the UTA Network Group upon completion of the Project.

    1.3.1 TELEPHONE TRUNK CABLES - Cables of 25 pair and up shall be 24 awg, solid conductorcables. Cables shall be in standard increments of 25, 50, 100, 300, 600, 800, 1000 or 1200. The cables will bepunched down on 66 style punch down blocks. Punch-down order should follow traditional USOC color codeorder for multi-pair telephone cables punched on 66-50 Blocks. SeeTable 2on page 13.

    2.0 Telecommunication Room Requirements

    2.1 Room design and Requirements

    All telecommunication rooms use designators in accordance withBICSI TDMM Ch. 7 Equipment RoomsandTIA/EIA 568A Procedures and Guidelines.

    Where possible, telecommunication rooms shall have direct access to the hallway or other such corridor andshould not be shared with other building services, such as Electrical (i.e. electrical distribution panels ortransformers). Supporting codes are found in both BICSI TDMM and the EIA/TIA 568A wiring standard

    unequivocally against multi-use closets. Telecommunication rooms shall not contain any type of sink, be used as Custodial supplies storage or be used

    general storage areas (books, furniture, etc.).

    Floors in telecommunication rooms shall be concrete or tile. Due to the threat of static electricity andresultant potential damage to network distribution equipment, we prefer to avoid carpeted flooring.

    Each telecommunication room will have sleeved core holes between floors as requested by UTA.

    Empty core holes will be properly fire-stopped, preferably with fire pillows.

    A minimum space of 10 X 10 is required for all single floor telecommunication rooms.

    A minimum space of 10 X 15 is required for all multi-floor telecommunication rooms.

    At least one long wall of a telecommunication room will be covered from floor to ceiling in fire-ratedplywood or plywood which is painted with at least two coats of flame retardant white paint.

    All telecommunication rooms will be equipped with a grounding bus bar that is tied back to the buildingsground. The grounding conductor will be attached to an approved electrode per NEC 1999 standards, asreferenced in TIA 607.

    Each telecommunication room will be equipped with a minimum of two (2) 120V-20 amp duplex outlets withindependent circuits (with isolated-ground if possible) on the wall where the plywood is mounted.

  • 7/28/2019 Wiring Std

    8/52

    2.2 New Installations

    NOTE: All installers must bePANDUIT CERTIFIED and properly trained to install these jacks according toPANDUIT specifications.

    Standard Data Termination BluePANDUIT Brand Cat 5e network data jacks (P/N CJ 5E88TBU). Cross-Connect Termination OrangePANDUIT Brand Cat 5e network data jacks (P/N CJ 5E88TOR) shall

    be used to terminate all cross-connect cabling between telecommunication rooms.

    Telephone/voice Termination YellowPANDUIT Brand Cat 5e jacks (P/N CJ 5E88TY L). Faceplate International whitePANDUIT Brand Executive Series 4 port faceplate (P/N CFPE4IW) on in-

    wall installations, PANDUIT Brand Executive Series 6 port (P/N CFPE6IW) or 10 port (P/N CFPE10-2GIW)faceplate may be used where 4 ports is insufficient.

    Surface Mount International whitePANDUIT Brand Surface Mount Box (P/N CBX4IW) on surfaceinstallations, PANDUIT Brand Surface Mount Box (P/N CBX6IW) or 12 port (P/N CBX12IW-A) surfacemount may be used where 4 ports is insufficient.

    2.3 Existing Installations

    Photo 5: The proper way to install DATA-Twist 350 into Panduit Mod-Com Cat 5 jacks.NOTE: The cable jacket is under the stuffer cap of the jack.

    Standard Data Termination - BluePANDUIT Brand Cat 5e network data jacks (P/N CJ 588ABU). Cross-Connect Termination - OrangePANDUIT Brand Cat 5e network data jacks (P/N CJ 588AOR) shall b

    used to terminate all cross-connect cabling between telecommunication rooms. Telephone/Voice Termination - International whitePANDUIT Brand Cat 3 jacks (P/N CJ 88IW).

  • 7/28/2019 Wiring Std

    9/52

    Faceplate International whitePANDUIT Brand Executive Series 4 port Faceplate (P/N CFPE4IW) on inwall or junction box installations, PANDUIT Brand Executive Series 6 port (P/N CFPE6IW) or 10 port (P/NCFPE10IW-2G)faceplate may be used where 4 ports is insufficient.

    Surface Mount International whitePANDUIT Brand 4 port Surface Mount Box (P/N CBX4IW-A) onexposed raceway installations, PANDUIT Brand 6 port Surface Mount Box (P/N CBXD6IW) may be used

    where 4 ports is insufficient.

    2.4 Special Installations

    Keystone Termination (Data) BluePANDUIT Brand Cat 5e network data jacks (P/N KJ 588BU) shall beused to terminate into KI Furnitures PowerUp Classroom style modular furniture using the custom made KImetal adapter fitting.

    Keystone Termination (Phone) If telephone jacks are required,YellowPANDUIT Brand Cat 5e networkdata jacks (P/N KJ 588YL) shall be used to terminate into KI Furnitures PowerUp Classroom style modularfurniture using the custom made KI metal adapter fitting.

    Photo 7: Panduit Keystone Jackin Metal KI PowerUp adapterplate (side view).

    Photo 6: KI PowerUp Module with Panduit Keystone jacksinstalled.

    2.5 Category 5e Patch Panels/Wall Brackets

    Patch Panel - PANDUIT BrandP/N CPP24WBL or P/N CPP48WBL . P/N CPP24WBL will allow the termination of up to 24 MINI-Com TX style modular jacks. P/N CPP48WBL will allow the termination of up to 48 MINI-Com TX style modular jacks.

    Wall Mount Bracket PANDUIT BrandP/N WBH2(2 unit) or P/N WBH4(4 unit) bracket.

  • 7/28/2019 Wiring Std

    10/52

    2.6 Equipment Racks

    Depending on the scope of the job, equipment racks will be either a floor mount or wall mount type.

    Floor Rack Black 7 CHATSWORTH BrandP/N 55053-703will be used for floor mount installations. Th

    rack should be anchored at all four points using a CHATSWORTH BrandP/N 40604-001Concrete Floor Kitof either a or 5/8 size. The bolts should be flush to the base plate of the rack. Also, ablackCHATSWORTH BrandP/N 12100-712 ladder-style cable raceway should be secured to the rack via ablackCHATSWORTH BrandP/N 10595-712rack-to-raceway mounting plate and secured to at least one wall via black CHATWORTH BrandP/N 11421-712wall angle support unit, any exposed ends of the ladder-stylecable raceway should be covered with CHATSWORTH BrandP/N 10642-001end caps. At the discretion ofUTA, one or both sides of the rack should have ablack CHATSWORTH BrandP/N 11374-703cablingmanagement section installed.

    Photo 8. Two rowsof properly mountedChatsworth racks.

    Note: Ladder-stylecable racewayattached to wall toprovide support and

    a cable path betweenracks.

    Wall Mount Enclosure Clear aluminumCHATSWORTH BrandP/N 11348-519will be used for wallmount installations. The unit will ALWAYS be mounted onto a sheet of plywood and will be securedusing at least (#6) 1 to 1 inEVERY hole of the racks mounting surface.

    Wall Mount Enclosure, secured Computer whiteCHATSWORTH BrandP/N 11685-219with a

    CHATSWORTH BrandP/N 11755-003 fan unit will be used in those situations where UTA determines that lockable enclosure is warranted. The unit will ALWAYS be mounted on a sheet of plywood and will besecured using at least (#6) 1 to 1 inEVERY hole of the racks mounting surface.

    Wall Mount Bracket Clear aluminumCHATSWORTH BrandP/N 11583-519wall mount bracket will beused in situations where UTA determines that a smaller rack is suitable.

    Grounding The equipment rack will be properly grounded as specified in Section 10.0 of this document,braided grounding straps will be used to connect separate pieces of ladder-style cable raceway and equipmenracks to form a continuous ground that connects to the telecommunication rooms grounding bus bar.

    1

  • 7/28/2019 Wiring Std

    11/52

    2.7 66-Block Telephone Termination

    Photo 9A: 66 style IDC blocksmounted on plywood backboard.

    Photo 9B: Blow-up of 66 style blockwith clear plastic block covers.

    The standard punch down block for the Office/Classroom cables is a SIEMON Brand pre-wired 66-50termination block (P/N M2-5T-128LR-TP).

    The standard punch down block for the telephone feeder cable is a SIEMON Brand 66-50 termination block(P/N 66M1-50) with a SIEMON Brand wall mount bracket (P/N S-89B).

    Building Feeder cables that enter the building from tunnels or outside of the building shall be properly groundper NEC-1999 Article 800.

    Wire Routing Spools (a.k.a. Mushrooms) will be mounted at the top on both sides of the 66-blocks to alloweasy routing of jumper wire between the Building Feeder cables and the Office/Classroom (W.A.O.) cables.

    Label the Circuit ID on the telephone blocks with a fine point, permanent marker pen on blocks for the

    Office/Classroom (W.A.O.) cables. Cover finished blocks with plastic 66 block covers. Use PANDUIT Brand labels(P/N PLL-24-Y2-1)to prin

    Circuit ID and attach covers.

    When installing Outside Plant (OSP) cable that is filled with water repellent gel in a telecommunication roomthe contractor will properly use cleaning agents (ex. D-gel) to remove the gel filling from the individual cablepairs. Also, any residue or damage incurred during the termination and clean up of the gel filled trunk cableswill be performed by the Contractor before the scope of work is considered complete, to the original or bettercondition. 66-Blocks will be free of any (ikky-pic) gel or D-gel residue.

    1

  • 7/28/2019 Wiring Std

    12/52

    Conceptual Telecommunication Room Layout

    Category 5e wiring

    Patch Panel Rack

    Cable Management

    Cable Management

    Cable Management

    Cable Management

    Cable Management

    Patch Panel (48 pt)

    Patch Panel (48 pt)

    Patch Panel (48 pt)

    Ladder Rack

    Station 66 Blocks(P/N M2-5T-128LR-TP)

    Feeder 66 Blocks(P/N S66M1-50)

    Phone Feede

    Cable

    Yellow Patch Cord

    Cat 5e Data J acks (Blue)CJ 5E88TBU

    Cat 5e Data J acks (Yellow)CJ 5E88TYL

    123-1A

    123-1B

    123-1VA

    DIAGRAM 1: Conceptual Drawing using Cat 5e for the phone, terminated into the equipment rack patch panel.

    Diagram 1 indicates that the designated phone wires will be terminated via a yellow Panduit jack andconnected to the 66 punch down block via a yellow patch cord of the appropriate length.

    The 66 punch down blocks will be located on a suitable wall, mounted to plywood appropriately paintedwith flame retardant paint.

    1

  • 7/28/2019 Wiring Std

    13/52

    ___________________________________________________________________________________________

    Splitting Phone Circuits off a single Cat5e Cable

    Siemon 66 Block(P/N M2-5T-128LR-TP)

    Yellow Cat 5e Patch Cableconencts to patch panel

    Panduit 4 port Exec

    Series Faceplate(P/N CFPE4IW)

    Panduit Cat 5e TXJ ack (Blue)

    P/N CJ5E88TBU

    Panduit Cat 5e TXJ ack (Yellow)

    P/N CJ 5E88TYL

    Panduit Mini-ComBlank Module (White

    P/N CMBIW-X

    Siemon Modular4-Way SplitterP/N YT4-4U1

    RJ -45Connector

    RJ -12Connectors

    YT4-4U1 Pin Out1 2 3 4 5 6 7 8

    J ack 11 2 3 4 5 6

    J ack 21 2 3 4 5 6

    J ack 31 2 3 4 5 6

    J ack 41 2 3 4 5 6

    DIAGRAM 2: Detail for running multiple phone circuits via a single Cat 5E wire.

    Diagram 2 details the methodology for running up to four independent phone circuits via one Cat 5ecable.

    1

  • 7/28/2019 Wiring Std

    14/52

    Terminate punch down blocks following traditional telephone order.

    25 Pair telephone cable(Colors are main color - strip color)

    Pair# Ring Color Tip Color1 White-Blue Blue-White2 White-Orange Orange-White3 White-Green Green-White4 White-Brown Brown-White5 White-Slate Slate-White6 Red-Blue Blue-Red7 Red-Orange Orange-Red8 Red-Green Green-Red9 Red-Brown Brown-Red10 Red-Slate Slate-Red

    11 Black-Blue Blue-Black12 Black-Orange Orange-Black13 Black-Green Green-Black14 Black-Brown Brown-Black15 Black-Slate Slate-Black16 Yellow-Blue Blue-Yellow17 Yellow-Orange Orange-Yellow18 Yellow-Green Green-Yellow19 Yellow-Brown Brown-Yellow20 Yellow-Slate Slate-Yellow21 Violet-Blue Blue-Violet22 Violet-Orange Orange-Violet23 Violet-Green Green-Violet

    24 Violet-Brown Brown-Violet25 Violet-Slate Slate-Violet

    Binder# Color1 White-Blue2 White-Orange3 White-Green4 White-Brown5 White-Slate6 Red-Blue7 Red-Orange8 Red-Green9 Red-Brown

    10 Red-Slate11 Black-Blue12 Black-Orange13 Black-Green14 Black-Brown15 Black-Slate16 Yellow-Blue

    Table 2.

    1

  • 7/28/2019 Wiring Std

    15/52

    2.8 Wire Management

    Vertical Wire Management Black CHATSWORTH BrandP/N 11374-703cable management shall be usedas previously defined in Section 2.4 Equipment Racks under the Floor Rack section, page 10.

    Vertical Patch Cable Management Black PANDUIT BrandP/N E4X4BL66 E slot shall be used

    (typically mounted to the flat surface and aligned with the top of the previously specified CHATSWORTHcable management with either self-tapping CHATSWORTH screws or bolts). Covers for theE4X4BL6Eslot shall beblack PANDUIT BrandP/NC4BL6.

    Photo 10: Proper use of both Vertical and Horizontal Cable Management

    Horizontal Wire Management - Black PANDUIT BrandP/N WMPSE andP/N WMP1 is used where single

    or double spaced, double-sided management is required. The back wire management ensures proper bendradius compliance. For cables coming from the Office/Classroom, the front side is used to manage patch cordfrom the horizontal cabling to the Network Equipment.

    Horizontal Wire Management Black PANDUIT BrandP/NWMPFSE andP/N WMPF1E is used wheresingle or double spaced, front only management is required. This is primarily used to manage patch cordsconnecting to the network distribution equipment.

    1

  • 7/28/2019 Wiring Std

    16/52

    Photo 11. Cables Properly routed in a WMPSE to ensure the Cat 5 Bend Radius.

    Cable Runway - Black CHATSWORTH BrandP/N 10250-712 ladder-style cable raceway shall be used. End Caps Black CHATSWORTH BrandP/N 10642-001end caps should be used on all exposed ends of th

    ladder-style cable raceway. All ends shall be filled down to remove any sharp edges before caps are installed

    Metal Rack and raceway mounting hardware shall all be CHATSWORTH Brand fittings.

    Photo 12. Properlysupported ladder rack.Allowing cable transitionbetween floors.

    Velcro straps are preferred to plastic tie straps in Telecommunication rooms wherever practical. Velcroshould be of sufficient length to wrap around cable bundle twice to accommodate future expansion.

    Tie straps used to dress cable will not be over tightened. Tie straps that deform the outer cable jacket and thacant be slid easily along the length of the cable bundle are too tight.

    Tie straps used in plenum airways must be plenum rated.

    1

  • 7/28/2019 Wiring Std

    17/52

    2.9 Transition Between Floors

    When cables come off a 7 ft. rack and over a ladder way to go down they must be properly secured to thevertical section of ladder rack going to the ground. Use a rounded transition fitting (water-fall, slide) bracketto ensure proper cable management.

    Also cables going through risers between floors must be properly supported for their weight, especially for

    high pair-count telephone feeder cables and large cable bundles. ERICO BrandP/N #CAT600WM wallmount support or #CAT600R strut mount support is suggested.

    Photo 13. Proper use ofwaterfall (rounded transition)fittings for cable changingfrom a horizontal path to avertical one. This maintainsthe minimum bend radius forCat 5 cable.

    Photo 14. Propertransition between floors.Bundles are correctlysecured to vertical laddersections by cable ties orVelcro straps.

    When pulling a cable in conduits between floors replace the pull string or rope for future use.

    1

  • 7/28/2019 Wiring Std

    18/52

    2.10 Patch Cord Colors in Telecommunication Rooms:

    Standard Hub Rooms: use Blue patch cords for new installations. For existing installations, match the colorcurrently in use in the telecommunication room.

    Special Cases: UTA may request that patch cords of differing colors be used to denote special areas

    (differing labs, differing floors, servers, etc.). Available colors are:

    GrayGreenPurpleRed

    Cross-connect Cables: use Orange patch cords for connections between telecommunication rooms.

    Telephone Cables: use Yellow patch cords for connections between patch panels and telephone blocks.

    Cross-over Cables: Black cables are pinned out so that 1 & 3 and 2 & 6 are swapped. These cables are usedto inter-connect the network distribution equipment.

    2.10.1 Patch Cord Specifications and PIN-OUTS: Below is the pin assignment for TIA/EIA 568A compliantpatch cords. All patch cords should be made from a minimum of 4 pair 24AWG stranded cable Cat 5e.

    1

  • 7/28/2019 Wiring Std

    19/52

    USED EXCLUSIVELY AT UTA - Standard EIA/TIA T568A (also called ISDN)

    Pin Wire Color==== ==========

    /---------------T3 1 White/Greenpair 3

    \---------------R3 2 Green/---------------T2 3 White/Orange/ /------R1 4 Blue

    pair 2 pair 1\ \------T1 5 White/Blue\--------------R2 6 Orange/--------------T4 7 White/Brown

    pair 4\--------------R4 8 Brown

    FIGURE 1 T568A

    USED AT UTA FOR CAT 6 INSTAL LATIONS - Standard EIA/TIA T568B (also called AT&T specification)

    Pin Wire Color==== ==========

    /---------------T2 1 White/Orangepair 2

    \---------------R2 2 Orange/---------------T3 3 White/Green/ /------R1 4 Blue

    pair 3 pair 1\ \------T1 5 White/Blue\--------------R3 6 Green

    /--------------T4 7 White/Brownpair 4\--------------R4 8 Brown

    FIGURE 2 T568B

    Cross-over Cable Pin-out (RJ -45 between network distribution equipment)

    FIGURE 3 NOTE: All other pins are terminated straight through.

    1

  • 7/28/2019 Wiring Std

    20/52

    II I. General Copper Requirements

    3.0 Network Data-Horizontal Cable

    3.1 Cat 5e CABLE SPECIFICATIONS

    All cable shall be installed according toBELDEN specifications designated for Data-Twist 350 (1701A)installation. Cable shall be installed when possible in multiple runs from reel jacks designed for the purposeor by pay-out boxes.

    Care shall be taken to prevent nicks, abrasions, burning, and scuffing of cable during installation. Cablesfound to be damaged will be replaced at the contractor's expense regardless of the test results of the cable.SEE CABLE TRAUMA SECTION 1.0

    3.2 Cat 6 CABLE INSTALLATIONS

    Should UTA specify a Cat 6 installation, the cable to be used is theBELDEN brandMedia

    3.3 CABLE PATHWAYS

    Cables shall follow pre-designed, UTA approved pathways. Design of the pathway will follow the standardsset forth in theTIA/EIA 569-A Commercial Building Standard for Telecommunications Pathways andSpacesdocument. Where possible, these pathways will be constructed from Erico brandP/N CAT324Z34 Jhooks hung from ceiling grid wire installed with powder-actuated (ex. Hilti gun) devices. J-Hooks shall beattached to independent grid wire and not attached to the existing drop ceiling grid wiring as the added weigh

    from the cables can cause distortion to the existing grid system. Refer toPhoto 15.

    2

  • 7/28/2019 Wiring Std

    21/52

    Photo 15. Proper use of CADDY J -hooks.

    2

  • 7/28/2019 Wiring Std

    22/52

    EricoP/N CAT425WM Adjustable Cable Support (Caddy Bags) will be used on higher cable count runs,properly mounted per product specifications. They will be secured to the ceiling by either thread all or to I-beams. Grid wireCAN NOT be used with Caddy-Bags due to the cables weight.

    Cable Tray systems can be used when installed as part of a new buildings infrastructure.

    Photo 16. Cable trayinstalled above dropceiling.

    NOTE:1. Finished section going

    into conduits that hasbeen properly bundledto Ladder Tray withVelcro strips.

    2. Conduit bushings onthe end of theconduits to preventthe cable being nickedor abraded on roughconduit edges during

    pulling.

    Some buildings on Campus use ceiling run or slab run conduit systems. When using this type of system, besure to pull a new pull string with the cabling.

    J-Hooks secured to the concrete deck is the preferred method of installation. Ceiling support shall be at amaximum of four (4) foot intervals and should be placed as close to the deck as possible. Cable pathwaysshall be so configured to avoidEMF andRFI interference. Common causes of this interference arefluorescent lighting fixtures, air handling motors and many kinds of electrical controls including starters andpower distribution panels. ALL CABLE RUNS MUST BE A MINIMUM OF 12 FROM ALLFLORECENT LIGHTS and EMF SOURCES. ANY VIOLATIONS OF THIS RULE WILL BE

    CORRECTED AT THE CONTRACTORS EXPENSE.

    Photo 17. There aremultiple problemswith this picture.

    1stthe J-Hooks areattached to the ceilinggrid.

    2nd the cable bundle is

    practically laying inthe fluorescent lightjust left of middle inthe photo.

    Always follow proper procedure to assure the bend radius is not exceeded when branching off to otherareas along a pathway. ALWAYS MAKE THESE BRANCHINGS IMMEDIATELY AFTER THENEARIST J -HOOK . Photo 18.

    2

  • 7/28/2019 Wiring Std

    23/52

    Photo 18. WRONG:Cables should neverbranch out away from asupporting J-hook. Thisplaces undue stress on thecable that might result infuture cable failures.

    Photo 19. WRONG:Cables should never beattached directly to

    electrical conduits or byonly using a tie strap.Shoot a grid wire andattach a J-Hook.

    Never run parallel with electrical conduits and never use them as cable supports.

    Every cable shall be properly supported. This means shooting a dedicated series of grid wires and installingall J-Hooks on an independent cable pathway system. NEVER use the ceiling grid wire system. J-Hooksmust be used, DO NOT wrap bare grid wire around the cable bundle for support.

    Using the ceiling grid system is aviolation of TIA/EIA 569A and NEC requirements. All cable pathways shall keep the cable bundle at least one foot (12 inches) off of the ceiling grid system.

    UTA Network Project Coordinator must approve exceptions. Wherever possible cables shall be grouped together in pathways. Always leave a ten (10) foot service loop a

    each work area outlet. UTA Network Project Coordinator must approve exceptions. Never cinch plastic cable ties overly tight. If it deforms the outer cable jacket it is too tight. The ties should

    be trimmed of any excess length and be snug only. The use of mechanical or powered cable tighteningdevices is strictly prohibited.

    2

  • 7/28/2019 Wiring Std

    24/52

    Always use a J-hook. Never attached cables directly to grid wire with tie straps.

    Cables should be properly supported and not sag between J-hooks. If the cable does sag it means that anadditional J-hook is required for proper support.

    Photo 20. WRONG:1stNever attach cablesdirectly to grid wire.Also the cable hasstress at the point dueto the cable tieviolating the minimbend radius.

    2ndnotice this is a

    ceiling grid wire. Anindependent grid wirewill be installed with a

    J-Hook attached.

    4.0 Vertical Wall Drops

    4.1 Concealed (in-wall) or Flush mounted

    Terminate all jacks according to 568A and PANDUIT PAN-JACK guidelines.

    Concealed (in-wall) drops should be restricted to hollow wall spaces that are made up of sheet rock on at leason side with no fire blocks. Wall openings shall have an ERICO BrandP/N MPLS single gang bracketinstalled for the purpose of mounting the faceplate. The bracket shall be securely fastened to the opening bymeans of sheet rock screws and bracket anchor points at both top and bottom of the bracket to ensure a snugfit. Levels should be used to ensure that faceplates are mounted correctly. Faceplates should be mounted a

    the same height from the floor as electrical outlets, unless otherwise specified. Electronic stud finders will be used at all times and before holes are cut in the sheet rock. This will eliminate

    the hitting of wall studs or problems due to in-wall cross bracing. This will also prevent the installer fromcutting into possibly Asbestos containing wall joint compound.

    2

  • 7/28/2019 Wiring Std

    25/52

    4.2 Exposed or Surface Mounted

    Exposed pathways down walls or columns shall be installed with PANDUIT Brand latch ducts of theappropriate size that will sufficiently accommodate the cables being routed.

    Care should be taken to ensure that cables are not exposed anywhere along the pathway. This means that

    proper fittings are required for all transition points. (I .e. splice covers and drop ceiling fittings.) Double-sided tape alone isnot sufficient to hold the duct and should only be used in conjunction with 1/4"

    anchoring devices mounted a minimum of every (6) six feet. Failure to comply will be corrected at theContractors expense.

    A Minimum of Two (2) - 1/4" anchors shall also be used at every device and/or junction box. Also use #6screws that are at least long. Failure to comply will be corrected at the Contractors expense.

    Photo 21 and 22: Two examples of exposedraceway applications. The one on the left is attached to a pillar.

    The second example is mounted on a non-hallow

    wall above the level of the modularfurniture.

    1/4" anchors shall be used on all fittings for PANDUIT BrandLD-3,LD-5andLD-10 latch duct at aminimum of 2 foot intervals. Failure to comply will be corrected at the Contractors expense.

    A PANDUIT BrandP/N DCF3IW-X, DCF5IW-X or DCF10IW-X ceiling grid/drop ceiling fitting will beused on all new exposed or surface mounted installations.

    Photo 23: An example of aPANDUIT LD-3 Drop CeilingFitting.

    2

  • 7/28/2019 Wiring Std

    26/52

    4.3 Copper Terminations

    4.3.1 RJ -45 Type: All jacks shall be terminated TIA/EIA 568A using the 568-A pin-out and PANDUIT PAN-JACK

    guidelines.

    Standard EIA/TIA T568A (also called ISDN)

    Pin Wire Color==== ==========

    /---------------T3 1 White/Greenpair 3

    \---------------R3 2 Green/---------------T2 3 White/Orange/ /------R1 4 Blue

    pair 2 pair 1

    \ \------T1 5 White/Blue\--------------R2 6 Orange/--------------T4 7 White/Brown

    pair 4\--------------R4 8 Brown

    FIGURE 4

    4.3.2 J ack Colors Standard Category 5e data jacks shall beBLUE in color.

    Voice/telephone Category 5e jacks shall beYELLOW in color.

    Backbone Category 5e data jacks shall beORANGE in color (between telecommunication rooms

    Voice/telephone Category 3 jacks shall beINTERNATIONAL WHITE in color. Blank Inserts shall beINTERNATIONAL WHITE in color.

    5.0 Work Area Outlet (WAO) Office/ClassroomTo determine Drop Locations Circuit ID numbers stand at the rooms main doorway. Label the proposeddrops sequentially from the left and moving around the room in a clockwise fashion. See DIAGRAM 1.

    Countclockwise 211-4

    211-1

    211-3A

    RM 211A

    211-2

    211A-1

    ROOM 211

    DOOR

    Diagram 3:Theproper way toassign Circuit IDNumbers in theroom were cabledrops are beinginstalled.

    2

  • 7/28/2019 Wiring Std

    27/52

    5.1 Concealed

    In areas such as offices that get two data lines and a telephone the faceplate shall be a (4) four portPANDUIT Brand Executive style Mini-Com faceplate (P/N CFPE4IW) unless specified elsewhere.

    In areas where a faceplate needs to be larger than 4 ports and up to six a 6 ports, a six port PANDUIT

    Brand Executive style Mini-Com faceplate (P/N CFP6IW) may be used. When more than 6 ports are required at a location one of the following is acceptable.

    1. Install a second faceplate with the adequate openings required for the number of drops. (Note-Remember this second faceplate will have a separate circuit ID number).

    2. When either a double gang outlet box or a double gang ERICO Brand bracket (P/N MPLS2)hasbeen installed, a PANDUIT Brand Mini-Com 10 port Executive faceplate (P/N CFPR10IW-2G)may be used.

    5.2 Exposed (Possible solutions for exposed Panduit installations)

    A four (4) port Mini-Com surface mount box (P/N CBX4IW-A). A six (6) port Mini-Com surface mount box (P/N CBX6IW-A). A twelve (12) port Mini-Com surface mount box (P/N CBX12IW-A). Use a PANDUIT one-piece surface boxP/N J B1IW-A with a standard four (4) port executive style

    faceplate.

    Photo 24: Example of 4-port

    PANDUIT surface mount box (P/NCBX4IW-A). NOTE: The UTAnetand Circuit ID labels have beenmade with a P-Touch label maker.

    Photo 25: Example of one-piece single gang junction box

    (P/N J B1IW-A) mounted to a power pole to feed the topcaps of modular furniture. Junction boxes are faced withPANDUIT Brand Executivestyle Mini-Com faceplate(P/N CFP6IW).

    2

  • 7/28/2019 Wiring Std

    28/52

    5.3 Faceplate LabelsLabels follow practices set forth in ANSI/TIA/EIA 606A ADMINSTRATION.The UTA Campus Network Services department will generate labels for both the Office/Classroomand telecommunication rooms according to the following criteria: The upper window is a custom designed Campus Network Services logo.

    The lower window is always anArial bold 22 point font (ex. 102A-1). The jack label Mini-Com is PANDUIT Brand white label (P/N PLL-46-Y2-1). The jack label for

    Mod-Com has been changedtoPANDUIT Brand blue label (P/N PDL-411-1BU). The font for thislabel is anArial 10 point (102A-1A, 102A-1B, 102A-1VA, etc.). Use smaller fonts to fit longercircuit ID numbers between black lines.

    Jack labels will be wrapped around the jacks properly.NOTE: Installers will not cut or tear ends off and stick jack labels on while they are snapped inthe panel or faceplate. These labels must be installed centered then wrapped around the jack.Failure to properly install these labels will be repaired by the contractor who will providereplacement labels.

    Each end of the Cat 5e cable will be labeled at approximately 3 to 6 inches from the network data jac

    with a PANDUIT Brand clear cable label (P/N L J SL4-Y3-2.5) usingArial 12 point font. The V in front of a jack letter represents a voice circuit (i.e. 102-1VA). A C would represent a coax circuit (i.e. 102-1CA). Rarely Used. If an office or classroom requires more than a four (4) port faceplate, jacks shall be labeled from uppe

    left to upper right, then lower left to lower right.

    UTAnet x2666

    102-1

    102-1C 102-1VA

    102-1B102-1A

    DIAGRAM 4. Photo 26:Picture of Proper Faceplate Configuration

    2

  • 7/28/2019 Wiring Std

    29/52

    5.4 Zone Cabling Follow rules outlined inTIA TSB-75 for consolidation points and multi-user telecommunications

    outlets for open office areas using modular furniture.

    Photo 27: Example ofsingle gang surfacemount boxes withexecutive faceplatesmounted on a power polefeeding top-caps.

    In the refurbished steel-case style furniture the extended TOP-CAPS must be used to separate the datafrom the bottom channel that contains the AC power for the cubicles. The Network connections willterminate on a power pole or column common to the walls of the modular furniture or on a wall abovethe top of the furniture, 70 from the floor to provide clearance for the removable TOP-CAPS.

    Patch cords will be used to connect the data jacks to the customers workstation, hopefully hiddenunder the Top-Cap and vertically by plastic modular furniture raceway strips supplied by Steel-Case.

    Photo 28: Example of Modular FurnitureTop-Cap installation.

    Photo 29: Example of Top-Caps endview.

    2

  • 7/28/2019 Wiring Std

    30/52

    5.5 Floor Boxes When installing PANDUIT data or telephone jacks in a floor box that was originally intended for

    mounting a 110V duplex power outlet a PANDUIT Brand MINI-COM 106 Duplex Module Fram(P/N CF1064IW) will be used to secure the jacks. This frame will accommodate up to four (4)Mini-Com jacks. Standard color pattern will be used to denote telephone (white) and data (blue).

    Photo 30: Mini-Com 106 Duplex ModuleFrame PANDUIT BrandP/N CF1064IW.

    Photo 31: Two different styles of floor boxes. The one on the left is a round HUBBLE poke-through system. The one on the right is a flip up square floor box with conduits coming from thefloor below. Inside the square box on the right a 106 adapter was used.

    3

  • 7/28/2019 Wiring Std

    31/52

    6.0 Testing and Documentation

    The contractor will perform certification tests on any and all Cat.3, 5, 5e or proposed Cat 6 cablinginstalled at UTA. UTA approved testers are required to handle a minimum level 3 proposed Cat 6 capabltesters, such asPenta-Scanner Plus, LanCAT Level I I Testersor Digital Fluke (DSP-1000, DSP-2000DSP-4000).

    Testing both-ways perTIA/EIATSB #67, Test Chapter Reference in 568A with documentation ismandatory. All testing will adhere to the TIA TSB 67 for certifying Cat 5e installations or the installedmediums required CATEGORY certifications test requirements (i.e. 5e or proposed Cat 6).

    See your UTA project manager for tester set-up instructions.

    Test results and documentation will be provided in bothhard copyandelectronicversions.

    IV. FIBER OPTIC CABLE REQUIREMENTS

    7.0 Fiber Optic CableNote: The TIA/EIA 568A wiring standards are the foundation of UTAs Network installationrequirements. The following are specific parts and techniques used in cooperation with theTIA/EIA 568A cabling standard, including the changes introduced by TIA/EIA TSB-72.

    SAFETY ISSUE: REMEMBER THAT FIBER OPTIC SYSTEMS CAN EMPLOY THEUSE OF LASERS. NEVER LOOK DIRECTLY INTO THE END OF A FIBER SYSTEMUNDER POWER. TAK E ALL RECOMMENDED SAFETY PRECAUTIONS FOR THEINSTALLATION AND TESTING OF FIBER OPTIC SYSTEMS, INCLUDING THEPROPER DISPOSAL OF ALL FIBER SHARDS AND RELATED DEBRIS.

    7.1 Fiber Cable Construction The standard for UTA isCorning. The UTA Network Project Coordinator must approve substitutes. The installation of an outside plant (OSP) cable will have each buffer tube of separate color, followin

    the standard order for fiber colors as set forth in TIA/EIA 568A. The first set of buffer tubes willcontain the Single Mode fibers and the last set of buffer tubes will contain the Multi-Mode fibers.

    7.1.1 OUTSIDE PLANT FIBER CABLE The OSP cable will be of a loose tube type with each tube having an outside diameter of 3.0 mm.

    Each buffer tube will be filled with water blocking gel or dryblock.

    The cable will be flooded with a water blocking gel or use a water-swelling compound system.

    The cable will have a polyethylene outer jacket. Multi-mode will be 62.5/125m graded index and at least FDDI grade fiber.

    Single-mode will be 8.3/125m fiber.

    Also all outside plant (OSP) fiber cable will have armored tape.

    The cable will come with at least one rip cord, preferably two rip cords.

    The cable will have an operating range of 40 to 70 degrees Celsius.

    The only UTA acceptable manufacturer of fiber optic cable isCorning.

    3

  • 7/28/2019 Wiring Std

    32/52

    7.1.2 EXCLUSIONS: FIBER SPECIFICATIONS NOT ALLOWED AT UTA Central tube construction is not used at UTA.

    50/125um multi-mode fiber is not used at UTA.

    7.1.3 INDOOR FIBER CABLE

    Fiber cable will be PLENUM rated unless otherwise noted by the UTA Network ProjectCoordinator.

    Each separate fiber will be 900m tight-buffered 250m fiber.

    Multi-mode will be 62.5/125m graded index and at least FDDI grade fiber.

    Single-mode will be 8.3/125m fiber.

    Will come with at least one ripcord.

    The standard for UTA isCorning. The UTA Network Project Coordinator must approvesubstitutes.

    Fiber Cable Construction Multi-Mode fiber shall be62.5 x 125 micronFDDI grade, 3.0 dB/km @ 850 nm 0.7 dB/km @

    1300 nm Single-Mode fiber shall be8.3 x 125 micron, 0.35 dB/km @1310 nm 0.25 dB/km @1550 nm

    NOTE: 1000Base-SX Multi-Mode Giganet (Gigabit) circuits have a loss budget that will notexceed 7.5 dB and a maximum length of 220 meters.

    7.1.4 Standard Fiber Counts for CablesFIVE basic cables are used at UTA they are:

    CORNING six (6) fiber Multi-Mode plenum rated

    CORNING twelve (12) Multi-Mode/ twelve (12) Single-Mode Plenum Rated Fiber

    CORNING eighteen (18) Multi-Mode/ twelve (12) Single-Mode OSP Rated Fiber CORNING twenty-four (24) Multi-Mode/twelve (12) Single-Mode OSP Rated Fiber

    CORNING thirty-sic (36) Multi-Mode/twenty-four (24) Single-Mode OSP Rated Fiber

    7.2 Wall and Rack Mount Fiber EnclosuresInner-duct will connect the Slack Enclosure to the Wall-Mount Fiber Box in installations where a Wall-Mount Fiber Box is required. Refer toPhoto 32below.The standard port counts of the wall mount fiber distribution centers are:

    6 Port Wall Mount Box

    12 Port Wall Mount Box

    24 Port Wall Mount Box

    48 Port Wall Mount Box

    3

  • 7/28/2019 Wiring Std

    33/52

    Photo 32: 24 port Wall Mount Enclosure and Spare Fiber Enclosure.

    Fiber Distribution Centers shall be installed rack mounted where possible; otherwise a wall mountenclosure will be suitable.

    All wall mount cabinets will be installed on plywood backing unless specifically designated otherwise

    For each cable in a cabinet the Single Mode bulkheads are installed first from left to right followed bythe Multi-Mode bulkheads. In situations where there are multiple cables the next set of Single Modebulkheads go in after the preceding cables Multi-Mode bulkheads.

    Be sure to properly secure the fiberglass center member to the designed anchor points inside the

    enclosures according to the products design. Rack Mount Fiber Enclosures used at UTA are:

    CorningP/N CCH-03U CCH enclosure, 6 slot. CorningP/N CCH-04U CCH enclosure, 12 slot

    Wall Mount Fiber Enclosures used at UTA are:

    CorningP/N WCH-06P CCH enclosure, 6 slot CorningP/N WCH-08P CCH enclosure, 8 slot CorningP/N WCH-12P CCH enclosure, 12 slot

    Both Rack and Wall mount enclosures will be populated with the appropriate bulkheads. CorningbrandP/N CCH-CP06-15T CCH Connectors Panel for Multi-Mode fiber, Corning brand P/N CCH-CP06-19T for single-mode fiber.

    7.3 Slack Fiber Enclosures

    A Fiber slack enclosure will be mounted above the wall-mount fiber boxes or on the wall near the rack-mount fiber enclosures to protect the minimum required amount of slack (25-50 ft.) at each end. THEREWILL BE NO EXCEPTIONS TO THIS MINIMUM FIBER SLACK LENGTH. Be sure to properlysecure the fiberglass center member to the enclosures designed anchor points according to productsdesign.

    3

  • 7/28/2019 Wiring Std

    34/52

    7.4 Splices and Splice Enclosures

    Splices: AMP Corelink Multi-mode mechanical splices (P/N 503901-1) AMP Corelink Single mode mechanical splices (P/N 503577-1)

    Photo 33: CORNING CamSplice Multi-mode (P/N 95-000-04)

    Splice Enclosure: AMP Wall Mount (P/N 502553-1)

    7.5 Fiber ConnectorsUnless specified by the UTA representative, all fiber optic cables will be terminated with SC connectors.Information for the ST equivalents are provided should a job be specified as using ST connectors.

    CORNING brand (P/N 95-100-48) SC connectors for Multi-Mode terminations CORNING brand (P/N 95-200-08) SC connectors for Single-Mode terminations CORNING brand (P/N 95-101-44) ST connectors for Multi-Mode terminations CORNING brand (P/N 95-201-06) ST connectors for Single-Mode terminationsNOTE: These connectors will be polished according to the guidelines outlined by CORNING forpolishing. The end will have a mirror finish and the raw pedestal tip will be completely polishedaway.

    7.5.1 Terminating - Fiber Connectors Fiber shall be terminated by or under close supervision of a certified Fiber Optic Installer. The

    preferred certification is the CORNING S-07 or S-07+. Proof will be required on request.

    Fiber shall be terminated with SC style connectors unless otherwise specified.

    2 part epoxy, such as Lucent or Lok-Tight is preferred.

    All loose buffer tube gel filled cables will have CORNING Brandfan-out kits installed (P/N FANOD25-12) (NO SUBSTITUTIONS).

    A FAN OUT KIT WILL ALWAYS BE USED, NEVER INSTALL FIBER TERMINATORSDIRECTLY ONTO THE LOOSE TUBE FIBER. FAILURE TO COMPLY WILL BE

    CORRECTED AT THE CONTRACTORS EXPENSE. All armored fiber optic cables will have grounding kits (Corning brandP/N FDC-CABLE-GRND

    Armored Cable Grounding Kit) installed at both ends and be properly grounded in thetelecommunication rooms per the TIA/EIA 607 Grounding and Bonding procedures. Also thesecables will be grounding per the guidelines set forth inArticle 250 GroundingandArticle 770-3Fiber Optic Building Entrance Point Grounding located in the 1999 edition of theNationalElectric Code (NEC). Also refer toSection 2.8of this document for further information.

    3

  • 7/28/2019 Wiring Std

    35/52

    7.6 Labeling Fiber Optic Cable

    Labeling on cabinets shall be accomplished by a P-touch (Brother labeler) or similar machine.

    Use black on white tape.

    Labels shall identify the far end location, each bulkhead shall be individually lettered A, B, C, D, etc.

    Labels shall also include the Building and Strand count (refer toDIAGRAM 3). A plastic self laminating 2 X 3.5 tag (PANDUIT Brand P/NPST-FO) with the legendCAUTION

    FIBER OPTIC CABLE will also be placed approximately 2 feet from each end of the fiber cable,outside of the fiber termination box. The proper fiber information (fiber destination and count) will bwritten on the tag with a permanent marker.

    Single-Mode

    Single-Mode

    Multi-Mode

    Multi-Mode

    Single-Mode

    Single-Mode

    Multi-Mode

    Multi-Mode

    Proper Labeling & Bulkhead Layout

    DIAGRAM 5: Notice the order of the Bulkheads in the enclosure.

    7.7 Testing and Documentation - Fiber

    Every fiber shall be tested and documented.

    Every fiber shall be tested with a light source tester; OTDR testing may be required at the UTArepresentatives discretion. Testing with either a light source meter or an OTDR shall be done in bothdirections.

    Locations of any mechanical or fusion splice should be noted in the OTDR information.

    Light meter tests will be Dual wavelength (850nm, 1300nm) Multi-mode. Light meter tests will be Dual wavelength (1310nm, 1550nm) Single mode.

    All tests should be received in a hard copy with a diskette copy of the file.

    All information should be delivered to the UTA Campus Network Services department in an accurateand timely manner.

    A general rule of thumb for acceptable losses are 0.5db for a multimode termination, 0.3db for a singlmode termination and 0.1db for each splice. However, please see section7.8.1 Fiber System LossBudget Calculation as to the preferred method of calculating an acceptable db loss for a circuit.

    3

  • 7/28/2019 Wiring Std

    36/52

    7.7.1 Fiber System Loss Budget Calculation Acceptable Fiber Attenuations:

    Wave Length 850nm 3.50db/kmWave Length 1300nm 1.00db/km

    Wave Length 1310nm 0.40db/kmWave Length 1550nm 0.30db/km

    Acceptable Connector Attenuation: 0.75db/connector link Acceptable Splice Attenuation: 0.10db/splice Formula for calculation:

    (Cable Footage * Fiber Attenuation / 3281 ft) +(#of Connector Pair * 0.75db) +(#of splices * 0.10db)

    Cable Footage is the actual length of the fiber run in feet. Fiber Attenuation / 3281 ft is the Acceptable Fiber Attenuation reference for the

    wavelength being tested divided by 3281 to convert the measurement from kilometers tofeet.

    #of Connector Pairs indicates number of bulkheads a typical install will be 2. #of splices indicate the number of splices of any type, if any, in the fiber path.

    Example Calculation:The job calls for a fiber optic run of 3000 ft. We wish to test it at the 850nm wavelength.This is a single hop test, so there are only 2 connection points, one at either end of the run.There are no splices in the fiber run.The acceptable db loss for this test would be 4.70db.The calculation would be:

    =(3000ft * 3.5db / 3281ft) +(2 [ConnectorPair] * 0.75db) +(0 [no splices] * 0.10db)=(3.20db) +(1.50db) +(0db)=4.70db

    3

  • 7/28/2019 Wiring Std

    37/52

    7.8 Fiber Splicing Procedures:Only Qualified technicians using the proper tools and products rated for the job will perform fiber opticcable splicing at UTA. All splices will be properly tested and documented, noting the point of the splicein all documentation. Technicians will supply all the equipment required to professionally and properlycomplete the splicing work.

    On a composite cable, containing both multi-mode and single mode fiber, the contractor will providethe proper test equipment to completely test both types of fiber.

    This test equipment will be on-site ready for use as soon as the splice has been completed.

    When finished with the splicing work the technician will test the impacted fiber according to the listeddocumentation and test requirements listed in thesection 7.9.1for standard fiber testing at UTA.

    Test results will be provided to the UTA Campus Network Services department in both a hardy copyand electronic format.

    SAFETY ISSUE: REMEMBER THAT FIBER OPTIC SYSTEMS CAN EMPLOY THE

    USE OF LASERS. NEVER LOOK DIRECTLY INTO THE END OF A FIBER SYSTEMUNDER POWER. TAK E ALL RECOMMENDED SAFETY PRECAUTIONS FOR THEINSTALLATION AND TESTING OF FIBER OPTIC SYSTEMS, INCLUDING THEPROPER DISPOSAL OF ALL FIBER SHARDS AND RELATED DEBRIS.

    7.8.1 Fiber Optic Cable Outside Plant Splice Enclosures Outside Plant fiber splice enclosures will be watertight and properly installed to ensure that the

    product remains watertight.

    Spliced fiber will be properly secured in splice trays to ensure reliable operation.

    The remaining slack fiber cable from OSP pull vaults will be properly coiled and replaced intovault.

    Any grounding system disconnected or cut during the course of splicing will be repaired andreconnected. This includes where the metal foil of an armored cable has been cut apart to performthe required splice. It must be restored with its original grounded state. If a cable was notproperly grounded to start with, the contractor should bring this immediately to the UTA NetworkRepresentative or said contractor WILL be held responsible for its repair.

    7.8.2 Testing and Required Documentation for Fiber Splices: The requirements for testing anddocumenting the fiber splices are the same as those found under the section7.8 Testing andDocumentation Fiber found on page 32.

    3

  • 7/28/2019 Wiring Std

    38/52

    8.0 Outside Plant Fiber Optic CableAll Outside Plant Work will follow the guidelines set forth in TIA/EIA-758 Customer-Owned Outside PlantTelecommunications Cabling Standard.

    8.1 Outside Fiber Pathways All outside plant cables shall be installed in schedule 40 or better inner-duct, 1.25" trade size diamete

    rated for outside burial. These inner-ducts shall be color coded by means of a stripe or solid coloringover the outside of the inner-duct.

    A minimum of two spare inner-ducts shall be placed with the inner-duct being used, for future use.

    All spare conduits and inner-ducts will have mule-tape or a pull string provided for future use.

    At points were the inner-duct needs to be spliced proper fittings will be used, either a threaded screwon watertight splice or heat fusion type splice. SeeDIAGRAM 6.

    DIAGRAM 6: Cabletecs 2 piece coupling unit (P/N PE1.660-2)

    All unused conduits in outdoor pull boxes will be properly plugged with removable watertight plugs.

    On this campus, we have an extensive underground tunnel network. In these locations PVC inner-duc1.25" trade size of orange coloring shall be used. This inner-duct shall be supported at a minimum of4 feet intervals.

    All OSP work will be properly documented and the Auto-CADD information including cable depthsand accurate routing will be provided in both electronic and hardcopy form.

    8.2 Out Door Pull Points

    Pull points shall be strategically designed and placed to permit the installation of fiber cables withinthe manufacturer specifications. Pull points will be no further than 400 ft. apart.

    Pull points shall be designed to use a Newbasis Greenline or Quazite hand-hole no smaller than 30" X

    48" X 20" deep with a wire screen bottom. They shall be load rated to 20,000 lb. with bolt down two-piece lids. They shall have a 6" minimum of medium wash rock base. SeeDIAGRAM 7below.

    Where a pathway enters a building above ground there may be placed a 24" X 24" X 12" minimumweather-tight junction box to accommodate the transition and provide pulling access.

    During the pulling of OSP fiber optic the Contractor will use proper figure-8 technique to stage theslack fiber cable between pull points. This shall be done to insure the cable does not get damagedduring installation.

    Contractors will use breakaway swivels rated at no greater than 600 lbs.

    3

  • 7/28/2019 Wiring Std

    39/52

    Diagram 7:Drawing of aQuazite fiber slackenclosure. It isalso used as anoutdoor pull point.

    8.3 Conduits and Inner-ducts for Fiber Optic Cables

    At no place along the pathway should the fiber cable be exposed.

    When outside rated Schedule 40 inner-duct transitions to the thinner wall indoor style inner-duct anoutdoor rated, watertight coupler will be used to connect the two types together.

    All conduits shall be reamed and bushed.

    All conduits shall be installed according to the NEC and any local authority having jurisdiction.

    All spare conduits and inner-ducts will have mule-tape or a pull string provided for future use.

    8.4 Underground Cables

    Cables to be placed underground are to be rated for the purpose. All cable shall be gel filled with anarmored cladding around it. Note:The newer water swelling tape or powder cables can be used ifthey can properly demonstrate at least the same amount of water protection provided by traditionalgel filled OSP cables. SEE SECTION 7.1.1 for OSP fiber construction.

    Cable service loops are required at each hand-hold opening and shall be installed within properdistances:

    100' loop per opening between hand holes.

    9.0 Building Entrance Point and Inside Fiber Pathways: A service loop of 50' will be left at every building entrance.

    At no time shall an Outside Plant rated cable run inside a building further than 50 feet unless it is encasedin rigid metal conduit. Otherwise there must be a transition from outside plant cable to a Plenum ratedfiber cable which will then be run through a Plenum Rated inner-duct. This transition can beaccomplished by a fusion splice, a mechanical splice or by a Fiber Wall Mount Enclosure.

    3

  • 7/28/2019 Wiring Std

    40/52

    9.1 Inside Fiber Pathways

    All pathways will consist of inner-duct, conduit or a combination of both.

    If broken or split, this inner-duct shall be spliced with the proper fittings.

    Inner-duct and fiber cable ran through Plenum airways will be Plenum rated.

    Where it enters a junction box or slack box the inner-duct will be connected to the wall mount boxwith the proper fitting to securely fasten the inner-duct to the enclosure.

    Cables and inner-duct shall be rated according toTIA/EIA andNEC codes for the environment inwhich they are installed.

    Support for inner-duct shall be no greater than 4' intervals.

    All spare inner-duct will have a pull string provided for future use.

    9.2 Indoor Pull-points

    Pull points shall be installed or used at intervals not to exceed the manufacturers specifications for the

    cable being placed. No service loops shall be left at indoor pull points.

    Service loops shall be installed only where a cable leaves a building or is terminated. Those loopsshall be between 12 and 20 feet in length.

    4

  • 7/28/2019 Wiring Std

    41/52

    10.0 Grounding

    All telecommunication rooms will adhere to the grounding guidelines set forth inTIA/EIA-607(COMMERCIAL BUILDING GROUNDING AND BONDING REQUIREMENTS FORTELECOMMUNICATIONS) plus any applicable codes inArticles (250 GROUNDING) and (800 -

    COMMUNICATIONS SYSTEMS) of theNEC 1999.

    For an explanation of what constitutes a proper ground point for the telecommunications bus bar to whichthe equipment will be grounded, seeNEC-1999 Article 800-40. Below are three general possibilities ofacceptable ground points. These ground points must meet all the detailed requirements of the abovementionedTIA/EIA-607 (COMMERCIAL BUIL DING GROUNDING AND BONDINGREQUIREMENTS FOR TELECOMMUNICATIONS) as well as any additional codes inArticles(250 GROUNDING) and(800 - COMMUNICATIONS SYSTEMS) of theNEC 1999.

    1. Attach to Building or Structure grounding system.2. Attach to metallic power service raceway or equipment enclosure.

    3. Attach to an 8 ground rod properly installed in the earth.

    The surface must be prepared to provide a proper path to ground. Any surface that is to be grounded musbe free of paint or other coating that might prevent an effective grounding. Paint should be scraped orfiled away until a metallic surface has been exposed. Then the proper grounding component can beattached to complete the system.

    All system components (i.e. ladder-style cable raceway, equipment racks, etc.) will be connected togetherand will eventually connect to the telecommunication rooms grounding bus bar with at least a #6 solid orstranded copper wire with a green insulation jacket.

    The bus bar will be connected to the building ground system in such a manner so that it meets the abovespecified requirements set forth in TIA/EIA-607 (Commercial Building Grounding and BondingRequirements for Telecommunications) as well as any additional codes in Articles (250 Grounding) and(800 Communications Systems) of the NEC 1999. The telecommunication rooms grounding bus barwill attach to the specified grounding system by a wire that is a minimum of #6 solid or stranded copperwire with a green insulation jacket.

    4

  • 7/28/2019 Wiring Std

    42/52

    10.1 Grounding Procedures in Telecommunication Rooms

    Photo 34: Anexample ofproperlyinstalled groundstraps connectingsections of ladder-way and equipmentracks together.

    All metallic racks, ladder ways and Network/Telecommunications Equipment will be properlyterminated per TIA/EIA 607 and NEC 1999 guidelines and procedures.

    This Equipment will eventually be tied back to the telecommunication rooms Grounding Bus Bar thatties back to the Buildings Grounding System.

    1. The telecommunication rooms Grounding Bus Bar shall be equipped with a grounding conductor that is attached toan approved electrode per NEC 1999 standards by a #6 copper wire with a green colored insulator.

    2. The wire jacket will be rated for the environment that it has been installed in. I.e. if the wire runs back to a groundelectrode in a path through a plenum return airway then the cable should be plenum rated.

    These procedures are Mandatory to the completion of required work in all newNetwork/Telecommunications installations.

    In existing telecommunication rooms that are not up to the required grounding guidelines, the UTANetwork Group will decide if the work will be completed by the Contractor or brought into

    compliance by UTA Network Group Staff. Contractors should bring this question of responsibilityup at the time of the project walk-thru.

    Photo 35: Example of a largegrounding bus bar in atelecommunications room.Note the two connections. Onegoes back to the Buildinggrounding system and the otherwire to the grounded ladder-racks.

    4

  • 7/28/2019 Wiring Std

    43/52

    V. Safety

    11.0 General Safety Practices:

    The Contractor shall conform to all applicable Federal, State and Local Regulations and/or standardspertaining to worker safety; including OSHA standards.

    All workers will use proper safety in performing their installation tasks. I.e. wearing goggles around eyehazards, ladder safety, wearing dust masks under dusty conditions, etc. Contractor injuries should bereported to their supervisors immediately.

    Workers will wear approved safety harnesses when working at dangerous heights in accordance with thefall protection guidelines defined by the OSHA standards.

    All fire or accidents will be reported to the UTA Police Department immediately at (817) 272-3003. To prevent accidents and fire hazards; all construction debris will be cleaned up nightly.

    The Contractor will dispose of all large empty spools of fiber and/or inner-duct in a timely manner (withia week after the job has been completed). Spools blocking hallways or doors are a fire hazard and are no

    permitted.They must be moved immediately.

    11.1 Asbestos Clearance:

    All cabling projects must have an ASB-1 form submitted and approved by the UTA EnvironmentalHealth and Safety Office. This form will explain any possible asbestos risks along the cable path.

    All contractors and employees installing network cabling and/or terminating network cabling at UTAMUST complete a mandatory Asbestos Awareness training courseBEFORE beginning work at UTAThis course is provided by UTA (conducted by a UTA Environmental Health and Safety Officerepresentative) at no charge to the contractor. The contractor is responsible for providing proof of

    each employees completion of this training. Failure to follow this policy will result in thedismissal of the guilty contractor.

    11.2 Fire-stopping:

    All penetrations into fire-walls or core holes between floor must be properly fire-stopped inaccordance with the guidelines inBICSI TDM 95 Chapter 20. Fig. 11 and must also conform toany related NEC requirements for Fire-stopping.

    Penetrations into the surface of any Firewall or presumed Firewall should be only slightly larger thanthe cable or cables that will need to pass through it. This will make Fire-stopping easier and allow the

    wall to maintain a better over all structural integrity. Proper Fire-stopping should be performed on any hole and/or penetration of a firewall or solid wall.

    This may include the Contractor installing Mineral Wool in the space between the sheet rock wall andthen installing a sheet rock patch on both sides before installing the Fire-Stopping Material.

    Fire-stop any transitions between floor using or not using conduit or sleeve. When using Fire-stoppingPutty in a conduit or sleeves between floors a section of Fire-resistant Mineral Wool must be insertedto create the proper base for the putty. Making a form out of cardboard isnot acceptable. Fire-stopping pillows are also acceptable to seal an opening that may need to be reentered at a later time.

    4

  • 7/28/2019 Wiring Std

    44/52

    Photo 36: Properly Fire-stopped using SpecSeal Intumescent Pillows

    4

  • 7/28/2019 Wiring Std

    45/52

    11.3 Environmental Health and Safety Attachment 1.

    ATTACHMENT 1: CAMPUS SAFETY GUIDLINES

    THE UNIVERSITY OF TEXAS AT ARL INGTONEnvironmental Health & Safety

    UNIVERSITY CONSTRUCTION SITEPROCEDURES FOR CONTRACTORS

    DEFINITIONS

    Pollutant, pollution, hazardous waste, hazardous substance, hazardous material, or contaminant, means any toxic

    or harmful substance as defined by CERCLA, SARA, and/or any similar federal, state, or local law, rule, orregulation.

    COMMON PROBLEMS FOR CONTRACTORS

    Equipment CleaningEquipment should be cleaned in a manner that does not create any discharge of cleaning agents, paints, oil, orother pollutants to a storm sewer or waterway. Soaps and detergents should never be discharged to the ground ooff-site. When rinsing painting equipment outside, contain rinse water in a bucket or other container. Waterbased or latex paint rinse water may be discharged to the sanitary sewer. Oil-based paint wastes, includingsolvents & thinners, shouldnotbe disposed of in the sanitary sewer. They must be collected and disposed of

    through the contractors disposal company. Cement handling equipment should be rinsed in a contained area sothere is no drainage off-site.

    Asbestos Containing MaterialsBefore beginning work in any UTA campus buildings, the contractor shall verify that no asbestos containing orsuspect asbestos containing materials will be damaged or disturbed during any portionof the work to beperformed. This can be verified through UTA Environmental Health & Safety (EH&S) Office. If the contractorincidentally damages or disturbs asbestos containing or suspect asbestos containing materials during any portionof the work, the contractor shall immediately stop work in that area, restrict access to the area, and contact EH&SAll personnel working on the campus that may come into contact with suspect asbestos-containing materials musattend a 2-hour asbestos awareness class that will be provided by UTAs Environmental Health & Safety Office.

    The training will be held on the UTA campus at a location yet to be determined. This awareness training will nomeet the OSHA asbestos training requirements for workers removing asbestos containing materials or the traininrequirements for an asbestos competent person.

    Waste DisposalAny trash or debris must be cleaned daily, contained on-site and disposed of in a recycling bin or waste receptaclto prevent wind or rain form carrying it off-site into a storm drain or waterway. Petroleum wastes, such as wasteoil and used oil filters, should be containerized for recycling or disposed by the contractor. Non-hazardous solid

    4

  • 7/28/2019 Wiring Std

    46/52

    wastes, such as general construction debris can be recycled or disposed of in the trash container. Never disposeof liquid wastes of any kind in dumpsters.

    STORM WATER MANAGEMENT

    The University of Texas at Arlington (UTA) has implemented a Storm Water Management Plan covering thatportion of the municipal separate storm water system within the corporate boundary of the city of Arlingtonoperated by UTA. Prior to beginning construction, contractors are required to submit a Storm Water PollutionPrevention Plan for review by the EH&S Office and the Storm Water Management (SWM) Team.

    Erosion/Sediment ControlProper erosion and sedimentation controls must be in place to prevent sediment or silt run-off. The Storm WaterQuality Best Management Practices (BMPs) for Construction Activities Manual produced by the North CentralTexas Council of Governments (NCTCOG) provides appropriate design criteria for permanent and temporarystructural controls. Sediment (including cement) should never be rinsed off the site; instead, it should be cleanedup in a manner that does not allow it to reach a storm drain or waterway. Equipment tires may be rinsed before

    leaving the site to avoid tracking sediment into the roadway or off the site.

    Construction Sites of five (5) or more acresThe contractor will be required to obtain a National Pollutant Discharge Elimination System (NPDES) Permitissued by the Environmental Protection Agency (EPA). Operators of such sites are to implement bestmanagement practices (BMPs) to the maximum extent practicable to minimize the quantity of storm waterpollutants leaving the site. Details for implementing BMPs on site should be described in the Contractors StormWater Pollution Prevention Plan. Site operators and managers should stress and enforce such practices upon thework force, subcontractors and material suppliers in order to avoid the generation of pollutants by wind and stormwater runoff.

    Retain the following documents at the construction site from the date of project initiation to final stabilization.1. SWPPP Storm Water Pollution Prevention Plan2. Reissued NPDES General Permit3. Plan Certification Statement4. NOIs5. EPA DPDES Storm Water Program Notice6. Inspection Reports7. Materials List8. Record of Construction Activities

    Construction Sites of 12,000 feet to five (5) acres, and all Commercial Sites

    Before starting any activity that will disturb an area between 12,000 square feet and five (5) acres of land, thecontractor is required to submit a Storm Water Pollution Prevention Plan to the EH&S Office and SWM Team foreview. For commercial sites, a Storm Water Pollution Prevention Plan is required regardless of the areadisturbed.

    Site De-watering, Tank and Pipe TestingDischarge from de-watering, hydrostatic tank testing or pipe pressure testing must be free from sediment,chemicals, and any other pollutants. Some discharges, such as those from underground storage tank pits, willrequire prior approval from the City of Arlington.

    4

  • 7/28/2019 Wiring Std

    47/52

    PetroleumSpills of hydraulic fluid, oil and other petroleum products should always be immediately cleaned up to preventdischarge of these fluids with storm water run-off. Petroleum contaminated soil should be cleaned up anddisposed of properly. Storage containers should be kept closed, clean, and free of oily residue. Construct a

    liquid-tight bermed area for temporary fuel tanks used during construction.

    Separators or TrapsBefore removing oil/water separators or traps connected to the sanitary sewer, the materials in them must havebeen tested (Toxicity Characteristic Leachate Procedure, or TCLP) within the last two yearsbeforethey arecleaned out. Be aware that this test may take three weeks to complete if a recent test has not been completed, soplan accordingly. Documentation of the test results must be submitted to the EH&S Office for review andapproval beforeemptying or removing the trap.

    SPILL PREVENTION, CLEAN-UP AND DISPOSAL

    Plan AheadIt is cheaper to prevent spills than to clean them up. Be prepared to contain or dike spills to prevent spreading.Small areas are easier to clean than large ones. Keep sorbent materials such as clay (kitty litter), polypropylenebooms and pads, rags and sawdust on hand for clean-up of spilled liquids.

    Clean-upSorbent materials can be used to effectively clean up various materials spilled on pavement, water, and soil. Soilor other media which has been contaminated with petroleum or other pollutants should be excavated orremediated to prevent contaminated discharges to a storm drain or waterway. Excavated contaminated materialsshould be stored in containers or on plastic and covered so that the contamination is not flushed back onto theground during a rainstorm.

    Contaminated Material DisposalProper disposal of waste materials depends partly on the type of contaminant. Hazardous wastes (such asflammable petroleum products and solvents, thinners) and materials contaminated with hazardous wastes, areconsidered regulated wastes, and should be containerized for transport and disposal by a permitted company.Disposal also depends on the amount of contaminant. For information on testing of contaminated soil anddisposal options contact EH&S, 817-272-2185.

    SPILL AND COMPLAINT RESPONSE PROGRAM

    The Universitys Environmental Health & Safety Office has a program to enforce water quality regulations and

    assist you in compliance with those regulations. The EH&S staff respond 24 hours a day, 7 days a week tohazardous materials spills and spills which threaten surface water quality, within the University of Texas atArlington. Investigations are conducted to determine compliance with environmental laws & regulations andensure corrective actions are taken when necessary. Strictly prohibited are discharges of any material orsubstance which will or might cause pollution to surface waters. Staff have specialized training in hazardousmaterials response and spill clean-up regulations. For more information on spill clean-up requirements and otherregulations call 817-272-2185.

    4

  • 7/28/2019 Wiring Std

    48/52

    GENERAL SAFETY

    It is UTAs intention to provide a safe work environment for all individuals at this work site. For this reason, allcontractors performing services on the campus must comply with and enforce all applicable local, state, federal(OSHA regulations), and our campus safety policies. This includes having implemented any required employee

    training and written programs.

    Before providing any services under this contract, the contractor is requested to furnish a copy of all applicablerequired written programs and documentation of training for each employee under their control at the work site.

    The following OSHA regulations may apply to the services being performed and require proper employeetraining, documentation of employee proficiency, and a written program by the contractor:

    LOCKOUT/TAGOUT, 29 CFR 1910.147, Subpart J

    HAZARD COMMUNICATION, 29 CFR 1910.1200 Subpart Z

    RESPIRATOR PROTECTION, 29 CFR 1910.134, Subpart I

    CONFINED SPACE (PERMIT REQUIRED), 29 CFR 1910.146, Subpart J BLOODBORNE PATHOGEN, 29 CFR 1910.1030, Subpart Z

    The following OSHA regulations may apply to the services being performed and require only employee trainingand documentation of employee proficiency by the contractor:

    FALL PROTECTION, 29 CFR 1926.503 Subpart M

    PERSONAL PROTECTIVE EQUIPMENT, 29 CFR 1910.132 Subpart I

    WELDING, CUTTING, BRAZING, 29 CFR 1910.254, Subpart Q

    ELECTRICAL SAFE WORK PRACTICES, 29 CFR 1910.332, Subpart S

    Contractors will: Conduct daily safety inspections of all assigned area

    Identify and correct hazards

    Provide contractor employees with required personal protective equipment

    Establish and maintain an effective Housekeeping Program

    CONTRACTOR REQUIREMENTS AND RESPONSIBILTIES

    The contractor shall maintain a legible copy of a current Material Safety Data Sheet (MSDS) for each hazardouschemical brought to the construction site. MSDS(s) shall be readily available, on request, for review by

    University personnel.

    Contractors are responsible for cleaning up and properly disposing of all spilled pollutants that you brought to thesite, including oil, paint, fuels, antifreeze, solvents, etc. You should keep accurate records (such as receipts,copies of analytical results, etc.) indicating proper disposal of spilled materials. Furthermore, you are responsiblfor ensuring that all discharges from the site are in compliance with all applicable regulations.

    4

  • 7/28/2019 Wiring Std

    49/52

    In general no substance should be dumped or leaked onto the ground or allowed to run-off of a construction sitethat might cause pollution. Be aware that you are responsible for pollutant contaminated run-off and properdisposal of all your waste materials generated as a result of your activities.

    NOTIFICATION REQUIREMENTS AND PROCEDURES

    We should be notified immediatelyin the event of: Any spill that threatens to enter a storm sewer or watercourse.

    All petroleum spills, e.g. hydraulic fluid, transmission fluid, diesel, gasoline, etc.

    Contact with asbestos containing or suspect asbestos containing materials.

    Any hazardous or unknown material spill, e.g. many solvents, cleaners, etc.

    Any discharge from your site which you suspect may be a violation of City Code or state regulations, e.g.discharges which are cloudy, foul-smelling, colored, contain chemicals or heavy sediments loads.

    ENVIRONMENTAL HEALTH & SAFETY - 817-272-2185

    Call this number to contact a representative for information during office hours (8:00 a.m. to 5:00 p.m.).

    (After hours call UTA Police Dispatch, 817-272-3381, who will contact an EH&S representative).

    Revised: August, 200

    END OF SAFETY OFFICE ATTACHMENT

    4

  • 7/28/2019 Wiring Std

    50/52

    VI. ADDITIONAL POINTS OF INTEREST

    12.0 OTHER REQUIRED CAMPUS NOTIFICATION

    12.1 Campus Notification For Core Holes:

    All core holes and permanent modifications to Buildings and other structures must be first reported tothe UTA Physical Plant. This notification must be given in writing before the work is to be done.

    12.2 After-hours or Holiday Work:

    Any work to be performed by the Contractors outside normal University business hours(8:00am-5:00pm Monday - Friday) and/or work to be done duringUniversity Holidaysrequires writtenapproval be granted and access to the area must be scheduled by the University Police department.

    Normally this can be taken care of by the UTA Project Coordinator/Network employee.

    12.3 Work in Hazardous or High Liability Areas

    Certain areas on campus may pose a hazard to Contractors due to the nature of the departmentsresearch. Possible hazards include poisonous animals, high-powered lasers and reactive chemicals.For the safety of the contractors and to limit possible damage to expensive property and equipment,we require a departmental escort to be with the Contractors at all times.Buildings always under these restrictions are the following:

    Basement of the SCIENCE BUILDING

    Basement of the LIFE SCIENCE BUILDING

    Certain areas on campus also use very expensive research equipment. In these areas we will alsorequire the department to provide an escort for the Contractor to ensure nothing is damaged during threquired cabling work in that area. This is to limit the department from coming back later and sayingthe Contractors damaged a piece of expensive equipment.1. Work with a departmental representative to cover any equipment that can be damaged when

    drilling or cutting work is performed near the equipment.2. DO NOT touch or lean against computer or sensitive equipment. If the equipment is in the way o

    the installation make arrangements with a departmental representative to have it relocated to a safeplace until the work has been completed.

    3. Cover machines whenever moving the ceiling tiles above them.4. Clean up any debris and dust caused by the work you have performed.5. Report any damage to furniture or equipment immediately to your foreman or the UTA Project

    Coordinator.

    5

  • 7/28/2019 Wiring Std

    51/52

    13.0 Glossary of Terms:

    Basic Link -This test is only for the horizontal wiring, without the patch cords. This is when thecircuit is being tested by the LanMeter to certify that it meets Cat 5e specifications.Channel -The Channel includes the users patch cord & the TC patch cords that connect the circuit to

    the network electronics. You should see network traffic on this circuit if it is properly working.MM -The abbreviation for multi-mode fiber 62.5 or 50.0m in size operating at 850nm or 1310 nmwavelengths. Multi-mode fiber systems generally use LEDs to transmit data; even so proper safetyprecautions should be taken to prevent permanent eye damage.NEC - The abbreviation for National Electric Code, an international standards-making organizationthat is part of the National Fire Protection Association. They create code practices that must be adherto on any electrical installation including have authority of low voltageOSP -The abbreviation for Out-Side Plant, refers to any cable or work performed between Campusbuildings or off of Campus property. The construction of these products must withstand the elementsand is usually unsuitable for indoor use.OTDR -The abbreviation for Optical Time Domain Reflectometer. This device is used to show

    breaks and loss problems in a fiber optic cable.SM -The abbreviation for single mode fiber 8.3m in size 1330nm or 1550 nm wavelengths. Since uses lasers to transmit data, you must takeproper safety precautions to avoid permanent eye damageTC -The abbreviation forTelecommunications Closet, also called aHub Room. The point at whichcables are terminated to patch panels and connected to network electronics.WAO -The abbreviation for Work Area Outlet. This is the faceplate location at the user site.

    5

  • 7/28/2019 Wiring Std

    52/52

    14.0 Important Campus Numbers:

    CAMPUS NETWORK SERVICESDavid Caldwell (Director - Network Services) (817) 272-3622

    Brad Samek (Network Manager) (817) 272-3633

    TELECOMMUNICATIONSCraig Beal (Director Telecommunications) (817) 272-5011Scott Brasher (PBX Switch Room Operations) (817) 272-2064

    OFFICE OF ENVIROMENTAL HEALTH & SAFETYCraig Powell (Director) (817) 272-2185Shufford Parr (Fire Marshall) (817) 272-4431

    PHYSICAL PLANTJ eff J ohnson (Director) (817) 272-3571Bryan Sims (Associate Director) (817) 272-7000

    CAMPUS POLICEPolice (Emergency) (817) 272-3003Police (Non-Emergency) (817) 272-3381Lt. Nan Rhodes (Building Access) (817) 272-3381

    CAMPUS INFORMATION CENTERInformation (817) 272-2222