Israel Electric Corp. Ltd. Marketing Division National Network Unit Overhead Lines Department Edition no.: 26 Issued date: 30.7.15 Specification K-2545 Wood poles for overhead power lines Page no. :1 of 22 Specification for: Wood poles for overhead power lines Prepared by: Eng. David Chen (-signed-) Approved by: Eng. Yeheskel Samoocha (-signed-)

Upload: others

Post on 29-Dec-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Wood poles for overhead power lines - Flanders State of

Israel Electric Corp. Ltd. Marketing Division

National Network Unit Overhead Lines Department

Edition no.: 26 Issued date: 30.7.15

Specification K-2545 Wood poles

for overhead power lines Page no. :1 of 22

Specification for:

Wood poles for overhead power lines

Prepared by: Eng. David Chen (-signed-) Approved by: Eng. Yeheskel Samoocha (-signed-)

Page 2: Wood poles for overhead power lines - Flanders State of

Israel Electric Corp. Ltd. Marketing Division

National Network Unit Overhead Lines Department

Edition no.: 26 Issued date: 30.7.15

Specification K-2545 Wood poles

for overhead power lines Page no. :2 of 22

Contents:

No. Of Para. Page No. 1. General 3 2. Threshold conditions 3 3.Documents for the proposal 3 4. Manufacturing standards 3 5. Technical requirements 5.1 Material 5.2 Preparation of poles 5.3 Dimensions of poles 5.4 Ultimate loads 5.5 Drilling of holes 5.6 Preservation

4 - 8 4 - 6

6 6 7 7 8

6. Marking 6.1 stainless steel tags 6.2 bottom end 6.3 top end

8 – 9 8 9 9

7. Acceptance tests 7.1 Visual inspection 7.2 Bending tests 7.3 Preservation inspection 7.4 Recording

9 – 11 9

10-11 11 11

8.Packing 11-12 9. Quality control 12 10. Delivery approval conditions 12 11. Summary of data 13 12. Revisions 14 - 15

Appendix Page No. 1. Drawing NCD 4725 – Wood poles 9, 10, 12, 14, 16 m – geometry, holes location and marking.

16

2. Drawing HOME 593 – Measurement of sweep and short crook in wood poles.

17

3. Test forms for wood pole. 18 - 21 4. I.E.C quality specification - Q – APP –02 22

Page 3: Wood poles for overhead power lines - Flanders State of

Israel Electric Corp. Ltd. Marketing Division

National Network Unit Overhead Lines Department

Edition no.: 26 Issued date: 30.7.15

Specification K-2545 Wood poles

for overhead power lines Page no. :3 of 22

1. GENERAL This specification covers wood poles for electrical overhead lines 9, 10, 12, 14, 16 m. length. 2. THRESHOLD CONDITIONS According to attached documents of the "supply and storage division" of I.E.C (Israel Electric Corp.).

3. DOCUMENTS FOR THE PROPOSAL The bidder shall submit together with his offer the following information and documents from the manufacturers: 3.1 Wood pole manufacturer's experience period in manufacturing scots pine wood poles. 3.2 Wood pole manufacturer's supply history: what types of wood poles were supplied, to whom, quantities and dates (during the last five years). 3.3 Preservation manufacturer's experience period in preservation of scots pine wood poles with the proposed impregnation substance. 3.4 Preservation manufacturer's supply history: what type of wood poles were supplied, impregnation substance, to whom, quantities and dates (during the last five years). 3.5 Complete filled summary of data for each proposed item (para. 11). 3.6 I.E.C drawing NCD 4725, signed by the bidder (appendix 1). 3.7 Manufacturer part number of the items. 3.8 The manufacturer trade mark. 3.9 The name of the impregnation material and it's components. 3.10 Bending test report example of one wood pole produced by the manufacturer, according to standard BS 1990. 3.11 A full description of manufacturer quality control actions. The above mentioned documents will be in English or Hebrew. Bidder which will not submit all the above will be disqualified. 4. MANUFACTURING STANDARDS The poles shall be manufactured and supplied in accordance with the requirements of the latest relevant published standards BS 1990 : part 1, BS EN 335, BS EN 351.1, BS EN 599.1. The bidder is entitled to propose industrial standard acceptable in his own country, for I.E.C approval. In addition, the poles will fulfill the requirements which are stated in this specification. If a conflict should arise between the standards and this specification, the I.E.C specification will prevail.

Page 4: Wood poles for overhead power lines - Flanders State of

Israel Electric Corp. Ltd. Marketing Division

National Network Unit Overhead Lines Department

Edition no.: 26 Issued date: 30.7.15

Specification K-2545 Wood poles

for overhead power lines Page no. :4 of 22

5. TECHNICAL REQUIREMENTS 5.1 MATERIAL 5.1.1 Species The poles shall be made from scots pine (redwood, pinus sylvestris). 5.1.2 Felling The trees shall be felled between 1 November and the following 31 March. 5.1.3 Sources Poles shall not be manufactured from trees subjected to snow breakage, frost damage, windfall or from forests damaged by fire. 5.1.4 Straightness Short crook (natural deviation of the axis of the pole occurring on a length less than 1.5 m) shall not be permitted. Double sweep or reverse sweep shall not be permitted. Single sweep (only one bend) shall be permitted to the extent that a straight line from the centre of the top to the centre of the pole 1.5 m from the butt remains within the pole. See drawing HOME 593 in appendix 2. 5.1.5 Slope of grain The slope of grain shall not exceed aslope of 1 in 6. A significant change in the slope of grain is not permitted. 5.1.6 Spiral grain (twist grain) Maximum 1 complete twist in any 5 m is permitted. 5.1.7 Rate of growth The average rate of growth measured on the butt, in the outer 5 cm of poles having a diameter of 30 cm or less at 1.5 m from butt, and in the outer 8 cm of poles having a diameter of more than 30 cm at 1.5 m from butt, shall be not less than 6 rings per 2.5 cm. 5.1.8 Decay and insects Poles shall be sound and free from decay and attack by insects. Minor insect holes are acceptable providing these are, either, not larger than 1.5 mm in diameter and do not exceed 5 in number, or not larger than 1.0 mm in diameter and do not exceed 20 in number, evenly distributed in any 100 mm length of pole. All other forms of insect damage are prohibited.

Page 5: Wood poles for overhead power lines - Flanders State of

Israel Electric Corp. Ltd. Marketing Division

National Network Unit Overhead Lines Department

Edition no.: 26 Issued date: 30.7.15

Specification K-2545 Wood poles

for overhead power lines Page no. :5 of 22

5.1.9 Knots The diameter of any single knot shall not exceed 1/6 of the circumference where the knot occurs, or the limits of table 1, whichever is smaller. At any cross section along the pole, the sum of knot diameters at the cross section shall not exceed 1/4 of the circumference. The sum of knot diameters in any 300 mm length of the pole section shall not exceed 1/3 of the circumference of the pole at the mid point of the 300 mm length. The dimension of a knot or knot cluster shall be measured as the diameter of a knot measured on the surface of the pole and perpendicular to the axis of the pole. Knot clusters shall be treated as a single knot.

Table 1

Length of pole

[m]

Maximum diameter of any single knot

[cm]

Lower half of length 5 9, 10, 12,14 Upper half of length 10 Lower half of length 10 16 Upper half of length 15

5.1.10 cross cracks cracks across the pole and the grain is not permitted. 5.1.11 Fissures Seasoning fissures along the grain are expected and are not recognized as defects providing they do not have a depth greater than half the diameter at one point along the pole or does not exceed 50% of the length of the pole. 5.1.12 Ring and star shakes The tip shall be free from ring or star shakes. One complete ring or one star shake is acceptable at the butt, provided that no part extends to within 50 mm from the periphery (circumference). If they extend to the periphery, they shall not extend along the pole more than 500 mm from the butt, and shall not have an opening wider than 3 mm. 5.1.13 Dead streaks Dead streaks are not permitted.

Page 6: Wood poles for overhead power lines - Flanders State of

Israel Electric Corp. Ltd. Marketing Division

National Network Unit Overhead Lines Department

Edition no.: 26 Issued date: 30.7.15

Specification K-2545 Wood poles

for overhead power lines Page no. :6 of 22

5.1.14 Mechanical damage Mechanical damage shall not extend the maximum dimensions: a. Length: 4 X minimum diameter of pole, at the cross section where the damage occurs. b. Width: 0.5 X minimum diameter of pole, at the cross section where the damage occurs. c. Depth: 5% of the minimum diameter of pole, at the cross section where the damage occurs. The maxima shall only be permitted for one measurement, with half the value given for the other two. No more than two occurrences of mechanical damage shall be permitted and no part of these shall be less than 500 mm apart. 5.1.15 Bark pockets and ring galls No more than two Bark pockets or ring galls shall be permitted. Maximum dimensions and position shall not exceed those given for mechanical damage (see para. 5.1.14). 5.2 PREPARATION OF POLES The poles shall be trimmed using a mechanical peeling machine so that the outer and inner bark shall be removed until the outer ring. The top end of the pole shall be prepared in gable shape. The butt shall be cut perpendicular to the longitudinal axis of the pole and shall have chamfered edges. 5.3 DIMENSIONS OF POLES 5.3.1 Length: The nominal lengths of the poles are given in table 2. The tolerance of pole’s length shall not exceed ±75 mm. 5.3.2 Diameter: The dimensional tolerances of nominal diameter at the top of the pole and at 1.5 meters from the bottom are given in table 2. Nominal diameter is the minimum diameter of the pole section (in case of elliptical cross section).

Page 7: Wood poles for overhead power lines - Flanders State of

Israel Electric Corp. Ltd. Marketing Division

National Network Unit Overhead Lines Department

Edition no.: 26 Issued date: 30.7.15

Specification K-2545 Wood poles

for overhead power lines Page no. :7 of 22

Table 2 Dimensions of poles

Nominal length

L

[m]

Nominal diameter at top

T

[mm]

Nominal diameter at 1.5 m from butt

end B

[mm]

Class of poles according to

standard BS 1990 : Part 1

I.E.C Catalogue

no.

min max min 4451126 9 150 180 220 Medium poles 4451142 10 150 185 230 Medium poles 4451167 12 190 250 305 Stout poles 4451183 14 195 255 335 Stout poles 4451191 16 200 265 365 Stout poles

5.4 ULTIMATE LOADS The wood poles (after preservation) will be able to withstand, without breaking , a ultimate load ( according to table 3) applied 0.60 meter from the top , perpendicular to the axis of the pole, while held rigid 1.5 meter from the bottom end.

Table 3

Ultimate loads at 0.6 m from poles top

Nominal length of pole L [m]

9 10 12 14 16

[kg]

450 600 900 900 900 Ultimate load at 0.6 m from

pole top p

[kN] 4.41 5.88 8.83 8.83 8.83

DRILLING HOLES 5. 5

Holes shall be drilled in 12&14 meter wooden poles as follows: a) The first hole 21 mm + 0.5 mm / -0.0 mm diameter, with center at 150 mm ± 10 mm from the top end of the pole. b) The second hole 21 mm + 0.5 mm / -0.0 mm diameter, with center located at 400 mm ± 1 mm from the center of the first hole, directly in line. See drawing NCD 4725 in appendix 1.

Page 8: Wood poles for overhead power lines - Flanders State of

Israel Electric Corp. Ltd. Marketing Division

National Network Unit Overhead Lines Department

Edition no.: 26 Issued date: 30.7.15

Specification K-2545 Wood poles

for overhead power lines Page no. :8 of 22

5.6 PRESERVATION The wood poles shall be treated, for preservation, by pressure impregnating, with impregnation substance that is not prohibited by Israel ministry of environmental protection. The wood poles shall be treated by a waterborne wood preservative. The wood poles shall not be treated by CCA (copper, chromium, arsenic) compound. The preservative treatment shall be according to relevant BS EN standards. All dressing, notching, pre-cutting and drilling shall be completed before preservative treatment. Prior to preservative treatment, the moisture content of the poles shall be at or below their fiber saturation point (25%). 5.6.1 Penetration All sapwood shall be completely penetrated with preservative. 5.6.2 Net retention The preservation shall be suitable for Hazard class 4 in BS EN 335 standard. The net retention of the impregnation substance shall be based on BS EN 351.1 and BS EN 599.1 standards (Hazard class 4). The minimum net retention of Celcure AC 800 – 36 kg/m3. The minimum net retention of Tanalith E 3492 – 16 kg/m3. The minimum net retention of another impregnation substance shall be according the above standards, approved by I.E.C in advance.

6. MARKING The marking shall be clearly visible and readable. See drawing NCD 4725 in appendix 1. The poles shall be marked in the following manner: 6.1 STAINLESS STEEL TAGS At a distance of 4.00±0.2 meters from the bottom end and on the bottom end, 1 mm thickness and approximately 50 mm diameter stainless steel tag shall be affixed with four stainless steel nails. Each tag shall include: a. The manufacturer trade mark. b. The nominal length of pole (m). c. The year of preservation. d. The code letters denoting the impregnation material used for preservation. e. I.E.C Catalogue no. (see table 2). The above marking shall be engraved or embossed.

Page 9: Wood poles for overhead power lines - Flanders State of

Israel Electric Corp. Ltd. Marketing Division

National Network Unit Overhead Lines Department

Edition no.: 26 Issued date: 30.7.15

Specification K-2545 Wood poles

for overhead power lines Page no. :9 of 22

6.2 BOTTOM END The bottom end of the poles shall be marked as follow: a. Stainless steel tag according to para. 6.1. b The nominal length of the pole (m) shall be painted by black color. c. Each pole shall be numbered with a different serial number from 1 to 999. The pole number (1- 999) shall be painted by green paint.

TOP END .36 The top end of the poles shall be painted with green color paint. The painting shall be on the top area and on 2 cm circumference strip.

ACCEPTANCE TESTS. 7 The tests shall be made by the supplier in accordance with the wood poles standards BS 1990 : part 1, EN 335, EN 351.1, EN 599.1 and K-2545 specification.

Representatives of Israel Electric Corporation, shall be invited at least 1 month in advance, to be present in the acceptance tests. The loading tests of the poles shall be performed in the manufacturer's facility. The manufacture shall ensure that all facilities, equipment and instruments are made readily available. The instruments shall be calibrated by authoritative laboratory. The accuracy of load-monitoring device shall be +/- 1% of actual reading. The accuracy of deflection measurements shall be +/- 5 mm. The manufacturer have the right to perform the acceptance tests at a known lab, approved by I.E.C. The poles to be tested (acceptance tests) shall be preservative treated (after preservation treatment). The moisture content of the poles to be tested shall be at or above their fiber saturation point (25%). The measurement of moisture content shall be made with a resistance-type moisture meter equipped with insulated electrodes. These measurements shall be taken at middle length of the pole. The inspection and tests shall be according to standard BS 1990 and K-2545 specification. All tests, including the wood poles that were tested and destructed, and all inspection procedures, will be at no additional cost to I.E.C.

ectionVisual insp 1.7

. before delivery,poles allon by the supplier This inspection shall be performed The following shall be checked: a. Pole material according to the requirements in para. 5.1. b. Dimensions of the pole – length, diameters at tip and butt (see table 2). c. Location and diameter of drilling holes (see para. 5.5 and drawing NCD 4725 in appendix 1).

Page 10: Wood poles for overhead power lines - Flanders State of

Israel Electric Corp. Ltd. Marketing Division

National Network Unit Overhead Lines Department

Edition no.: 26 Issued date: 30.7.15

Specification K-2545 Wood poles

for overhead power lines Page no. :10 of 22

d. Pole marking (see para. 6 and drawing NCD 4725 in appendix 1).

The results of visual inspection shall be recorded by the supplier on the form of appendix 3. The results shall be presented to I.E.C representative.

testsendingB .27

The number of wood poles to be selected for the tests, from the delivery for I.E.C order (with the same length), shall be according to column 2 in Table 4. The poles shall be selected randomly, by I.E.C. representative.

4Table

3

Number of wood poles selected for the

tests in case of failure

2 Number of wood poles

selected for the tests

1 Number of wood poles

in the delivery (with the same length)

2 1 Up to 60 4 2 61 to 120 6 3 121 to 200

If at least one pole failed the tests, another amount of wood poles, according to column 3 in table 4, shall be selected from the same delivery (with the same length) , and the poles shall be tested. If in the second testing group, at least one pole failed the tests, the all delivery (with the same length) shall be rejected. 7.2.1 Preparation Prior to bending tests, the poles shall be visual inspected according to para. 7.2.1 and the following data shall be measured and recorded: a. Moisture content at middle length of the pole. b. Length of the pole [m]. c. Weight of the pole [kg]. d. butt diameter [mm]. e. Diameter at 1.5 m from butt [mm]. f. Diameter at midpoint of the pole length [mm]. g. Diameter at point of application of the test load [mm]. h. tip diameter [mm]. 7.2.2 Procedure The bottom section of the pole under test shall be rigidly clamped up to 1.5 m from

Page 11: Wood poles for overhead power lines - Flanders State of

Israel Electric Corp. Ltd. Marketing Division

National Network Unit Overhead Lines Department

Edition no.: 26 Issued date: 30.7.15

Specification K-2545 Wood poles

for overhead power lines Page no. :11 of 22

the butt. A load shall be applied 0.6 m from the tip of the pole in a direction perpendicular to the original axis of the pole. The pole shall be gradually loaded (in steps of 100 kg) until the ultimate load is reached (see table 3).The ultimate load shall be maintained for 5 minutes. Failure shall not be permissible at load less than the ultimate load. On completion of loading the ultimate load, loading shall be continued until pole destruction. During the loading process a current record shall be made of the force and the corresponding deflection at pole tip, for each load step. After testing, the moisture content shall be measured close to the position of failure. The moisture content and the location shall be recorded. The poles that have been tested for bending (para. 7.2.2) shall not be supplied to I.E.C. 7.3 preservation inspection Preservation inspection shall be made on all destructed wood poles of bending tests, according to column 2 in table 4. Net retention and full penetration of sapwood shall be certified by a known laboratories approved by I.E.C. If the above results will not compliance with the requirements according to para. 5.6.1, 5.6.2 of this specification, the all batch shall be rejected. Poles shall be clean and dry to the touch at the time of delivery. Poles that bleed preservative at the plant or at delivery shall be rejected. Pole may be retreated only once. 7.4 Recording The acceptance tests shall be recorded on the forms of appendix 3 in this specification, for each tested pole.

PACKING. 8 The wooden poles shall be supplied properly bound to prevent the possible damages during shipment and storage. Each pole type (according to length & I.E.C. catalogue no.) shall be bounded separately. Each bounded package, of 9 m and 10 m poles length, shall contain 10 poles. Each bounded package, of 12 m and 14 m poles length, shall contain 5 poles. Each bounded package, of 16 m poles length, shall contain 4 poles.

Page 12: Wood poles for overhead power lines - Flanders State of

Israel Electric Corp. Ltd. Marketing Division

National Network Unit Overhead Lines Department

Edition no.: 26 Issued date: 30.7.15

Specification K-2545 Wood poles

for overhead power lines Page no. :12 of 22

Each package shall be bounded by two safety synthetic strips with upper loops, for lifting by fork- lift rods from the loops. The distance between the two strips shall be 2 m. The two strips shall be located symmetric to the middle length of poles.

Each delivery shall have packing list and in addition, shall be marked with the following information: a. supplier's name and address. b. Manufacturer's name and address. c. Descriptive name of the wooden poles (nominal length (m), species). d. I.E.C catalogue number. e. I.E.C order number f. Quantity. g. Gross weight. h. Gross volume. 9. QUALITY CONTROL Quality control requirements shall be according to I.E.C standard Q-APP-02. 10. DELIVERY APPROVAL CONDITIONS 10.1 The certificates of preservation inspection, according to para. 7.3, shall be attached to the documents for each delivery. 10.2 Manufacturer's declaration about poles species, period dates of felling and that the poles have been manufactured according to BS 1990 part 1: 1984 standard, shall be attached to the documents for each delivery. 10.3 Before each delivery, acceptance tests shall be made, according to para. 7. 10.4 I.E.C reserves the right to verify the compliance of the delivered wood poles with this specification. 10.5 Delivery which will not pass acceptance test according to para.7 and / or the documents according to para.10.1 and 10.2 will be missed or not satisfying, will be rejected.

Page 13: Wood poles for overhead power lines - Flanders State of

Israel Electric Corp. Ltd. Marketing Division

National Network Unit Overhead Lines Department

Edition no.: 26 Issued date: 30.7.15

Specification K-2545 Wood poles

for overhead power lines Page no. :13 of 22

11. SUMMARY OF DATA FOR WOODEN POLES Name of the Bidder ______________________ Nominal length of pole L [m] ________________ I.E.C catalogue no. (see table 2) ____________________ (Insert all data in this column)

1. Wood pole Manufacturer’s name and address.

2. Preservation manufacturer’s name and address.

3. Wood pole Manufacturer’s experience period in manufacturing scots pine wood poles. [years]

4. Is wood pole Manufacturer’s supply history attached? (Yes/No)

5. Preservation manufacturer’s experience period in preservation of scots pine wood poles with the proposed impregnation substance. [years]

6. Is preservation manufacturer’s supply history attached? (Yes/No)

7. Is the drawing NCD 4725, with the bidder signature, attached? (Yes/No)

8. Is the markings accordance with this specification? (Yes/No)

9. Manufacturer part no. 10. Manufacturer trade mark. 11. Please state the manufacturing standards of wooden poles.

12.1 12.2

12. Material 12.1 Pole species 12.2 Impregnation substance. 12.3 The ultimate load (after preservation) [kg] 12.3

13.1 13.Tests 13.1.Which test standards does the wooden poles comply with? 13.2 Are the test example, according to para. 3.10, attached? (Yes/No)

13.2

14.1 14.2

14. Packing and shipping data 14.1. Quantity [pcs] 14.2. Weight [ kg] 14.3. Volume [m3] 14.3

Page 14: Wood poles for overhead power lines - Flanders State of

Israel Electric Corp. Ltd. Marketing Division

National Network Unit Overhead Lines Department

Edition no.: 26 Issued date: 30.7.15

Specification K-2545 Wood poles

for overhead power lines Page no. :14 of 22

12. REVISION: 1. Changed format of specification. 2. Cancellation of 12.0 meters thick pole. 3. Addition of preliminary acceptance conditions: - Quality system ISO 9002. - At least two years of manufacturing experience. 4. Addition of paragraphs 4, 8 and 9. 5. Changed summary of data. 10. Changed I.E.C. cat no. and identification for 9 m poles. 6/97 11. Deleted IS0 9002 10/98 12. Changing in para 3, 5 and the sequence of the para. Add. Standard quality assurance requirements. Add ISO 9002 5/00 13. Changing in para 2 “threshold condition” 5/03 14 Change in para 3 and 5.6 (impregnation demands) 11/03 15 Chang in para 2, 3, 5.6, 9, 12. 16. Changing of para. 2, 3, 4, 6, 7, 11, 12 of revision no. 15. 03/2007 * The threshold conditions will be in the documents of I.E.C "supply and storage division". * The requirement for ISO 9002 or ISO 9001:2000 was deleted. * The proven experience was changed to two years. * The standard SFS 2662 was deleted. * added black painted marking on the top an on center of gravity of poles. * para. 9. was deleted. 17. Changing of para. 5.3, 7 of revision no. 16. 06/2007 * IEC Catalogue no. was changed (table 1 in para. 5.3). * Tag and nails material was changed to stainless steel (para. 7.1). * IEC Catalogue no. marking was added to aluminum tag (para. 7.1). * The year marking was changed to preservation year (para. 7.1). * The bottom end marking was changed (para. 7).

Page 15: Wood poles for overhead power lines - Flanders State of

Israel Electric Corp. Ltd. Marketing Division

National Network Unit Overhead Lines Department

Edition no.: 26 Issued date: 30.7.15

Specification K-2545 Wood poles

for overhead power lines Page no. :15 of 22

* The painting of top end and center of gravity was changed to green (para.7) 18. Changing of para. 7.4, 10.1, 11 of revision no. 17. 07/2007 * para. 3.1.4 was added. * The green painted marking on the center of gravity of poles was deleted (para. 7.4). * The requirement for submitting detailed drawing for I.E.C approval, prior to commencement, was deleted (Para 10.1). * The summary of data was updated (para. 11). * Drawing NCD 4725 was added (appendix 1). 19. General changing of the all specification. 1/2008 20. * Para. 3.10 of revision no.19 was deleted. 5/2008 * The prohibition of CCA compound in the treatment was added (para. 5.6). 21. * Table 2 (in para. 5.3) was changed according to table 1 of standard BS 1990 : Part 1. * Para 7.2 was updated. * The summary of data was updated (para. 11). 22. * Para. 5.7, 7.2.4 of revision no.21 was deleted. 12/2008 * Para. 7.2, 7.2.3, 10 were updated. * Appendix 3 was updated. 23. * Para. 5.6 was updated. 24. Drawing NCD 4725 of appendix 1 was updated (table). 1/2011 25. * Para. 5.6, 7.1, 7.2.2.2, 8, 10 were updated. 6/2011 * Appendix 4 was updated. 26. * Para. 3, 7, 10, 11 were updated. 7/2015 * Appendix 3 was updated. * Para. 7.1 of revision no.25 was deleted.

Page 16: Wood poles for overhead power lines - Flanders State of

Israel Electric Corp. Ltd. Marketing Division

National Network Unit Overhead Lines Department

Edition no.: 26 Issued date: 30.7.15

Specification K-2545 Wood poles

for overhead power lines Page no. :16 of 22

Appendix 1

Page 17: Wood poles for overhead power lines - Flanders State of

Israel Electric Corp. Ltd. Marketing Division

National Network Unit Overhead Lines Department

Edition no.: 26 Issued date: 30.7.15

Specification K-2545 Wood poles

for overhead power lines Page no. :17 of 22

Appendix 2

Page 18: Wood poles for overhead power lines - Flanders State of

Israel Electric Corp. Ltd. Marketing Division

National Network Unit Overhead Lines Department

Edition no.: 26 Issued date: 30.7.15

Specification K-2545 Wood poles

for overhead power lines Page no. :18 of 22

Appendix 3

TEST FORMS FOR WOOD POLE (Appendix to specification K-2545)

I.E.C order number: ____________________________ Date of test: ___________________________________ Serial number of the pole: ________________________ Supplier's name: _______________________________ Manufacturer's name: ___________________________ Nominal length of pole L [m]: ____________________ I.E.C catalogue no.:_____________________________ Certificates of preservation inspection are the certificates of preservation inspection according to para. 7.3 submitted by the manufacturer? _______________________ Are the results of net retention and penetration compliance with the requirements according to para.5.6.1, 5.6.2 ?_____________________ Visual inspection on the pole intended to bending test a. Length of pole L [m]: ____________________ b. Diameter at 1.5 m from butt end B [mm]: ________________ c. Diameter at top T [mm]: ____________________ d. Are the holes in the proper place and with proper diameter? ___________ e. Is the pole marked properly? _____________ f. Are the following conformed to para. 5.1? Species _____________ Felling ____________ Straightness __________ Slop of grain ______________ Spiral grain ___________ Rate of growth ________________ Decay and insects ____________ Knots ___________ Cross cracks _____________ Fissures ____________ Ring and star shakes ___________ Dead streaks ____________ Mechanical damage _____________ Bark pockets and ring galls ___________

Page 19: Wood poles for overhead power lines - Flanders State of

Israel Electric Corp. Ltd. Marketing Division

National Network Unit Overhead Lines Department

Edition no.: 26 Issued date: 30.7.15

Specification K-2545 Wood poles

for overhead power lines Page no. :19 of 22

bending test a. Preparation Moisture content at middle length of the pole [%]: ____________ Length of pole [m]: _______________ Weight of pole [kg]: _________________ Butt diameter [mm]: ________________ Diameter at 1.5 m from butt [mm]: _____________ Diameter at midpoint of the pole length [mm]: _____________ Diameter at point of application of the test load [mm]: _______________ Tip diameter [mm]: ________________ Figure 2 – bending test position of a wood pole

Order number: _______________________ Date of test: _________________________ Serial number of the pole: ______________ Supplier name: ___________________

Page 20: Wood poles for overhead power lines - Flanders State of

Israel Electric Corp. Ltd. Marketing Division

National Network Unit Overhead Lines Department

Edition no.: 26 Issued date: 30.7.15

Specification K-2545 Wood poles

for overhead power lines Page no. :20 of 22

b. Loading the pole in stages up till destruction

2. Continuation of Loading in stages up till destruction

Deflection at pole top

Remarks

Net deflection

Ai - Ao

[mm]

Ai [mm]

Force at 0.6 m from

pole top

P [kg]

Measurements after destruction: a. The distance of the failure position from butt [m]: ________________ b. Moisture content close to the position of failure [%]: ______________

1. Loading in stages up till ultimate load Ultimate load = _______ [kg] (see table 3) A0 = _________ [mm]

Deflection at pole top

Remarks

Net deflection

Ai - Ao

[mm]

Ai [mm]

Force at 0.6 m from

pole top

P [kg]

A0= 0

Order number: _______________________ Date of test: _________________________ Nominal length of pole L [m]:___________ Serial number of the pole: ______________ Supplier name: ___________________

Page 21: Wood poles for overhead power lines - Flanders State of

Israel Electric Corp. Ltd. Marketing Division

National Network Unit Overhead Lines Department

Edition no.: 26 Issued date: 30.7.15

Specification K-2545 Wood poles

for overhead power lines Page no. :21 of 22

Form for visual inspection of the all poles, before delivery I.E.C order number: ____________________________ Date of visual inspection: ________________________ Supplier's name: _______________________________ Manufacturer's name: ___________________________ Nominal length of pole L [m]: ____________________ I.E.C catalogue no.:_____________________________ Date of preservation treatment: ____________________

Serial number of the pole

length of pole

L [m]

Diameter at 1.5 m from butt

end

B [mm]

Diameter at top

T [mm]

Are the holes in

the proper place and

with proper

diameter?[yes/no]

Is the pole marked

properly?

[yes/no]

Are the material

conformed to para.

5.1?

[yes/no]

Page 22: Wood poles for overhead power lines - Flanders State of

Israel Electric Corp. Ltd. Marketing Division

National Network Unit Overhead Lines Department

Edition no.: 26 Issued date: 30.7.15

Specification K-2545 Wood poles

for overhead power lines Page no. :22 of 22

Appendix 4

I.E.C quality specification

Q – APP – 02 /4