Wood Shear Wall Seismic and Wind Design Example per 2015 WFCM and SDPWS
Lori Koch, P.E.Manager, Educational OutreachAmerican Wood Council
Michelle Kam-Biron, P.E., S.E. S.E.C.BSenior Director, EducationAmerican Wood Council
2W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
COPYRIGHT MATERIALS
This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation without written permission is prohibited.
© American Wood Council 2018
Copyright © 2018 American Wood CouncilAll rights reserved.
2
3W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
DESCRIPTION
Two AWC standards utilized throughout the nation for a code compliant design of wood shear walls are 2015 Wood Frame Construction Manual (WFCM) for One- and Two-Family Dwellings and 2015 Special Design Provisions for Wind and Seismic (SDPWS). The WFCM contains both a prescriptive and engineering design approach. Although the prescriptive design will tend to provide more conservative results than the more efficient engineered design, designers may arrive more readily at a solution. This course will include examples of seismic and wind shear wall designs for segmented and perforated shear walls, utilizing the WFCM and the SDPWS along with a comparison of the results.
4W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
LEARNING OBJECTIVES
At the end of this program, participants will be better able to:
1. Identify and understand the basic shear wall system to resist lateral wind and seismic loads.
2. Understand the differences between segmented and perforated shear wall design.
3. Understand hold down design and special conditions that pertain to seismic and wind hold downs.
4. Be able to identify and analyze shear walls per 2015 WFCM and 2015 SDPWS and understand the differences between them.
Copyright © 2018 American Wood CouncilAll rights reserved.
3
5W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
POLLING QUESTION
1. What is your profession?
a) Architect
b) Engineer
c) Code Official
d) Fire Service Professional
e) Other
6W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
OUTLINE• 2015 IBC/IRC Recognition• Background and Assumptions• Wind Examples
• 2015 WFCM Prescriptive• 2015 WFCM Engineered• 2015 SDPWS
• Seismic Examples • 2015 WFCM Prescriptive• 2015 WFCM Engineered• 2015 SDPWS
Copyright © 2018 American Wood CouncilAll rights reserved.
4
7W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
WFCM AND IRC/IBC
2015 WFCM is referenced in 2015 IRC/IBC
8W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
WFCM AND IRC
IRC R301.1.1 Alternative Provisions
Copyright © 2018 American Wood CouncilAll rights reserved.
5
9W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
WFCM AND IBC
IBC Section 2301.2
10W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
WFCM AND IBC
IBC Section 2309
Copyright © 2018 American Wood CouncilAll rights reserved.
6
11W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
APPLICABILITY LIMITS
12W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
2015 WFCM – NON-RESIDENTIAL
• Applications• Single-story• Slab-on-grade• L and W < 80’• Examples• Commercial/Retail• Restaurants• Office Buildings• Design• Lateral (Wind and Seismic)• Gravity
Copyright © 2018 American Wood CouncilAll rights reserved.
7
1 3W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
2015 WFCM
WFCM p. v
14W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
2015 WFCM
2015 WFCM uses ASCE 7-10 wind and seismic design provisions
What’s Changed
Copyright © 2018 American Wood CouncilAll rights reserved.
8
15W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
SDPWS AND IBC
2015 SDPWS is referenced in 2015 IBC
16W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
SDPWS
• Engineered
• Res and Non-Res
• ASD & LRFD
• Shear wall provisions
• Segmented
• Perforated
• Force Transfer Around Openings
2015 SDPWS
Copyright © 2018 American Wood CouncilAll rights reserved.
9
17W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
SDPWS AND IBC
18W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
MINIMUM DESIGN LOADS
ASCE 7-10 Minimum Design Loads for Buildings and Other Structures
Copyright © 2018 American Wood CouncilAll rights reserved.
10
19W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
OUTLINE• 2015 IBC/IRC Recognition• Background and Assumptions• Wind Examples
• 2015 WFCM Prescriptive• 2015 WFCM Engineered• 2015 SDPWS
• Seismic Examples • 2015 WFCM Prescriptive• 2015 WFCM Engineered• 2015 SDPWS
20W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
SEGMENTED SHEAR WALL (SSW) METHOD
Copyright © 2018 American Wood CouncilAll rights reserved.
11
21W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
PERFORATED SHEAR WALL (PSW) METHOD
22W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
POLLING QUESTION
2. WFCM Prescriptive provisions include which of the following:
a) 110‐195 mph wind loads
b) Exposures B & C
c) Segmented and perforated shear walls
d) All of the above
Copyright © 2018 American Wood CouncilAll rights reserved.
12
23W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
OUTLINE
• 2015 IBC/IRC Recognition• Background and Assumptions• Wind Examples
• 2015 WFCM Prescriptive• 2015 WFCM Engineered• 2015 SDPWS
• Seismic Examples • 2015 WFCM Prescriptive• 2015 WFCM Engineered• 2015 SDPWS
24W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
WFCM PRESCRIPTIVE
WFCM p. 114
Copyright © 2018 American Wood CouncilAll rights reserved.
13
25W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
WFCM PRESCRIPTIVE
•Seismic Design Categories A-D
•Wind Speeds 110-195 mph Exp. B & C
•Segmented & Perforated Shear Walls
•Other Application Limits
26W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
WFCM PRESCRIPTIVE – WIND
Copyright © 2018 American Wood CouncilAll rights reserved.
14
27W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
SDPWS Shear DistributionWFCM PRESCRIPTIVE
28W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
DESIGN EXAMPLE
Design first floor shear wall
Copyright © 2018 American Wood CouncilAll rights reserved.
15
29W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
DESIGN EXAMPLE - WINDAssumptions130 mph (700-yr, 3-second gust) Exposure BL=36’W=30’5/12 roof pitchTop plate to ridge = 6.25’2-story8’ wall height6’8” door height4’ window heightWood Structural Panel Exterior SheathingVary interior walls – with and without gypsumDon’t check deflection
30W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
OUTLINE
• 2015 IBC/IRC Recognition• Background and Assumptions• Wind Examples
• 2015 WFCM Prescriptive• 2015 WFCM Engineered• 2015 SDPWS
• Seismic Examples • 2015 WFCM Prescriptive• 2015 WFCM Engineered• 2015 SDPWS
Copyright © 2018 American Wood CouncilAll rights reserved.
16
31W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
WFCM PRESCRIPTIVE - WIND
2015 WFCM Prescriptive – Segmented Shear Wall
Interpolate = 12.3'
32W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
WFCM PRESCRIPTIVE - WIND
2015 WFCM Prescriptive – Segmented
Interpolate = 0.68Adjusted = 12.3' (0.68) = 8.4'
Copyright © 2018 American Wood CouncilAll rights reserved.
17
33W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
WFCM PRESCRIPTIVE - WIND
2015 WFCM Prescriptive – Segmented – required = 8.4'
4’ + 4’ + 2.5’ + 2.5’ = 13’ > 8.4’ OKAssumes blocked gypsum on interior
34W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
WFCM PRESCRIPTIVE - WIND
2015 WFCM Prescriptive – Segmented
2 Walls having aspect ratios exceeding 1.5:1 shall be blocked shear walls and the maximum aspect ratio shall not exceed 2:1 in accordance with SDPWS Table 4.3.4.
Copyright © 2018 American Wood CouncilAll rights reserved.
18
35W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
WFCM PRESCRIPTIVE - WIND
2015 WFCM Prescriptive – Segmented
What if we don’t count the gypsum on interior?8.4’ x 1.3 = 10.9’
36W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
Segmented shear wall – assuming no interior gypsum4’ + 2.5’ + 2.5’ + 4’ = 13' > 10.9' OK
2015 WFCM Prescriptive Segmented – required = 10.9'
WFCM PRESCRIPTIVE - WIND
Copyright © 2018 American Wood CouncilAll rights reserved.
19
37W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
Segmented shear wall – requires hold downs on each segment
2015 WFCM Prescriptive Segmented – Hold-downsWith and Without Gypsum
WFCM PRESCRIPTIVE - WIND
38W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
% Full-height sheathing8.4' / 36' = 23%Interpolated = 1.868.4'(1.86) = 15.6'w/ blocked gypsum
10.9' / 36' = 30%10.9'(1.72) = 18.7'w/o gypsum
21' Full-height sheathing > 18.7’ OKNote: Max. aspect ratio = 3.5:1 for PSW segments
2015 WFCM Prescriptive – Perforated Shear Wall
WFCM PRESCRIPTIVE - WIND
Copyright © 2018 American Wood CouncilAll rights reserved.
20
3 9W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g nPSW requires fully sheathed wall and hold-downs only at the ends
2015 WFCM Prescriptive – Perforated – Hold-downs
WFCM PRESCRIPTIVE - WIND
40W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
Hold-downs= 3,488 lbsw/ blocked gypsum
3,488 / 1.3= 2,683 lbsw/o gypsum
2015 WFCM Prescriptive – Hold-downs
• Need to combine with top floor hold-down requirements• Based on capacity of first shear wall panel• Does not include dead load
WFCM PRESCRIPTIVE - WIND
Copyright © 2018 American Wood CouncilAll rights reserved.
21
41W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
OUTLINE
• 2015 IBC/IRC Recognition• Background and Assumptions• Wind Examples
• 2015 WFCM Prescriptive• 2015 WFCM Engineered• 2015 SDPWS
• Seismic Examples • 2015 WFCM Prescriptive• 2015 WFCM Engineered• 2015 SDPWS
42W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
WFCM p. 14
WFCM ENGINEERED
Copyright © 2018 American Wood CouncilAll rights reserved.
22
43W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
WFCM ENGINEERED – WIND
2015 WFCM Engineered
wroof = 94 plf
wfloor = 128(0.82)*=105 plf
wtotal = 199 plf
199(30')/2 = 2,985 lbs
*Footnote 2: (H+1)/11adjustment = (8+1)/11
Roof Atrib = gable + ½ wallFloor Atrib = ½ wall + ½ wall
44W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
WFCM ENGINEERED – WIND
2015 WFCM Engineered – Segmented
2 Walls having aspect ratios exceeding 1.5:1 shall be blocked shear walls and the maximum aspect ratio shall not exceed 2:1 in accordance with SDPWS Table 4.3.4.
Copyright © 2018 American Wood CouncilAll rights reserved.
23
45W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
Required Capacity = 2,985 lbs7/16 WSP Capacity = 336 plf1/2” Gypsum Capacity = 100 plf
Total = 436 plf
2,985/436 = 6.8' (w/ blocked gypsum)2,985/336 = 8.9' (w/o gypsum)
2015 WFCM Engineered Segmented
WFCM ENGINEERED – WIND
46W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
2,985 lbs
4’ + 4’ = 8' > 6.8' assuming interior blocked gypsum OK
2015 WFCM Engineered Segmented
WFCM ENGINEERED – WIND
Copyright © 2018 American Wood CouncilAll rights reserved.
24
47W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
2,985 lbs
4’ + 2.5’ + 2.5’ + 4’ = 13' > 8.9' assuming NO interior gypsum OK
2015 WFCM Engineered - Segmented
WFCM ENGINEERED – WIND
48W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
2015 WFCM Engineered - PerforatedReference SDPWS Capacities and AdjustmentsV = 2,985 lbsv = 436 plf (w/ blocked gypsum)v = 336 plf (w/o gypsum)%FHS = Li / LtotLi = 16’ + 2[2(2.5)/8]2.5’ = 19.1’Ltot = 36’%FHS = 19.1’ / 36’ = 53%Interpolated Co Factor = 0.59
436(0.59) = 257 plf2,985/257 = 11.6’ < 21’ (w/ blocked gypsum)
336(0.59) = 198 plf2,985/198 = 15.1’ (w/o gypsum)Note: Li per SDPWS 4.3.4.3 adjustment = 2bs/h
WFCM ENGINEERED – WIND
Copyright © 2018 American Wood CouncilAll rights reserved.
25
49W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
19.1' Effective Full-height sheathing > 15.1' OK
2015 WFCM Engineered - Perforated
WFCM ENGINEERED – WIND
50W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
T = v hv = 436 plf (w/ blocked gypsum)v = 336 plf (w/o gypsum)h = 8’T = 436(8’) = 3,488 lbsT = 336(8’) = 2,688 lbs
2015 WFCM Engineered – Hold-downs
• Need to combine with top floor hold-down requirements• Based on capacity of first shear wall panel• Can account for dead load (WFCM 2.2.4)
WFCM ENGINEERED – WIND
Copyright © 2018 American Wood CouncilAll rights reserved.
26
51W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
POLLING QUESTION
3. The WFCM tabulated hold‐down capacity requirements:
a) Are based on capacity of the first shear wall panel
b) Do not account for dead load unless specified by the designer
c) Are cumulative with floors above
d) All of the above
52W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
OUTLINE
• 2015 IBC/IRC Recognition• Background and Assumptions• Wind Examples
• 2015 WFCM Prescriptive• 2015 WFCM Engineered• 2015 SDPWS
• Seismic Examples • 2015 WFCM Prescriptive• 2015 WFCM Engineered• 2015 SDPWS
Copyright © 2018 American Wood CouncilAll rights reserved.
27
53W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
ASD Capacity = 670/2 = 335 plf
2015 SDPWS – WSP CAPACITY
54W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
ASD Capacity = 200/2 = 100 plf
2015 SDPWS – WSP CAPACITY
Copyright © 2018 American Wood CouncilAll rights reserved.
28
55W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
2015 SDPWS
Adjustment factor(based on stiffness)
SDPWS
56W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
SDPWS - WIND
Required Capacity = 2,985 lbs
WSP = 335 plf
Gypsum = 100 plf
Total = 435 plf
2,985/435 = 6.9' (w/ blocked gypsum)
2,985/335 = 8.9' (w/o gypsum)
2015 SDPWS
Copyright © 2018 American Wood CouncilAll rights reserved.
29
57W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
2,985 lbs
2015 SDPWS – Segmented Shear Wall
4' + 4' = 8' > 6.9' OKassuming interior blocked gypsum
SDPWS - WIND
58W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
2,985 lbs
2015 SDPWS – Segmented Shear Wall
4' + 2.5'(0.625) + 2.5'(0.625) + 4' = 11.1' > 8.9' OKassuming NO interior gypsum
Note: 0.625 per SDPWS 4.3.3.4.1 Exception 1 = 2bs/h
SDPWS - WIND
Copyright © 2018 American Wood CouncilAll rights reserved.
30
59W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
SDPWS - WIND
Shear Capacity Adjustment Factor
h = 8’
Li = 16’ + 2[2(2.5)/8]2.5’ = 19.1’
Ltot = 36’
Ao = 4(4’)(2.5’) + (5’)(6.67’) = 73.4 ft2
r = 0.68
Co = 0.77 (based on total sheathed area)
Comparison: SDPWS/WFCM Engineered (tabulated) Co = 0.59
Note: Li per SDPWS 4.3.4.3 adjustment = 2bs/h
2015 SDPWS – Perforated Shear Wall
60W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
SDPWS - WIND
Co = 0.77w/ blocked gypsum435 (0.77) = 3352,985/335 = 8.9'
w/o gypsum335 (0.77) = 2582,985/258 = 11.6'
19.1' Effective Full-height sheathing > 11.6' OK
2015 SDPWS – Perforated Shear Wall
Copyright © 2018 American Wood CouncilAll rights reserved.
31
61W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
2,985 lbs
2015 SDPWS – Perforated Shear Wall
19.1' Effective Full-height sheathing > 11.6' OK
SDPWS - WIND
62W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
SDPWS - WIND
T = v h
v = 2,985/8' = 347 plf (blocked gyp)
v = 2,985/13' = 230 plf (w/o gyp)
h = 8'
T = 347(8') = 2,985 lbs (blocked gyp)
T = 230(8') = 1,840 lbs (w/o gyp)
2015 SDPWS – Hold-downs (Segmented)
• Need to combine with top floor hold-down requirements• Based on loads• Can account for dead load (4.3.6.4.2)
(4.3-7)
Copyright © 2018 American Wood CouncilAll rights reserved.
32
63W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
SDPWS - WIND
V = 2,985 lbs h = 8'Co = 0.77Li = 16’ + 2[2(2.5)/8]2.5’Li = 19.1'T = 1,624 lbsReq’d Hold-down Capacity = 1624 lbs
2015 SDPWS – Hold-downs (Perforated)
• Need to combine with top floor hold-down requirements• Based on loads• Can account for dead load (4.3.6.4.2)
4.3.4.3…In the design of perforated shear walls, the length of each perforated shear wall segment with an aspect ratio greater than 2:1 shall be multiplied by 2bs/h for the purposes of determining Li and Li
64W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n
AWC Standard Segmented(SSW)
Perforated(PSW) Hold-downs, lbs
2015 WFCM Prescriptive
8.4’ [10.9’] (6/12)
15.6’ [18.8’] (6/12) 3,488 [2,683]
2015 WFCM Engineered
6.8’ [8.9’] (6/12)
11.6’ [15.1’] (6/12)
3,488 [2,683]
2015 SDPWS 6.9’ [8.9’] (6/12)
8.9’ [11.6’] (6/12)
2,985 [1,840] [SSW]1,624 [1,001] [PSW]
2015 WFCM/SDPWS Shear Wall Length Comparison1st of 2-story; W=30'; L = 36’; GSL = 30psf; 130 mph Exposure B
WIND DESIGN EXAMPLE - SUMMARY
Copyright © 2018 American Wood CouncilAll rights reserved.
33
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n65
OUTLINE
• 2015 IBC/IRC Recognition• Background and Assumptions
• Wind Examples
• 2015 WFCM Prescriptive
• 2015 WFCM Engineered
• 2015 SDPWS
• Seismic Examples • 2015 WFCM Prescriptive
• 2015 WFCM Engineered
• 2015 SDPWS
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n66
8’
DESIGN EXAMPLE - SEISMICAssumptionsSeismic Design Category D1
7/16 Wood Structural Panel Exterior Sheathing16” o.c. SPF studs (G=0.42)Ground Snow Load = 30 psfPartial Attic = Roof/Ceiling Dead Load = 25 psfFloor Dead Load = 12 psfPartition Load = 8 psfWall = 110 plfL=36’W=30’L/W=1.22-story8’ wall height6’8” door height4’ window heightDon’t check deflection
Copyright © 2018 American Wood CouncilAll rights reserved.
34
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n67
DESIGN EXAMPLE - SEISMIC
Design first floor shear wall
8’
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n68
OUTLINE
• 2015 IBC/IRC Recognition
• Background and Assumptions
• Wind Examples
• 2015 WFCM Prescriptive
• 2015 WFCM Engineered
• 2015 SDPWS
• Seismic Examples
• 2015 WFCM Prescriptive
• 2015 WFCM Engineered
• 2015 SDPWS
Copyright © 2018 American Wood CouncilAll rights reserved.
35
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n69
WFCM PRESCRIPTIVE - SEISMIC
•Seismic Design Categories A-D
•Segmented & Perforated Shear Walls
•Other Application Limits
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n70
APPLICABILITY LIMITS
Copyright © 2018 American Wood CouncilAll rights reserved.
36
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n71
WFCM PRESCRIPTIVE - SEISMIC
WFCM p. 114
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n72
WFCM p. 123
WFCM PRESCRIPTIVE - SEISMIC
WFCM 3.4.4.2 Exterior Shear Walls
Copyright © 2018 American Wood CouncilAll rights reserved.
37
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n73
WFCM PRESCRIPTIVE - SEISMIC
2015 WFCM Prescriptive – Segmented Shear Wall
Interpolate = 15.8'Required length of full height sheathing (FHS)
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n74
WFCM PRESCRIPTIVE - SEISMIC
2015 WFCM Prescriptive – Segmented
Adjusted = 15.8' (1.2) = 19'Required length of FHS
Copyright © 2018 American Wood CouncilAll rights reserved.
38
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n75
WFCM PRESCRIPTIVE - SEISMIC
2015 WFCM Prescriptive – Segmented
SDPWS adjustment = 2bs/h (for stiffness)
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n76
SDPWS Shear Distribution
WFCM PRESCRIPTIVE - SEISMIC
Copyright © 2018 American Wood CouncilAll rights reserved.
39
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n77
WFCM PRESCRIPTIVE - SEISMIC
2015 WFCM Prescriptive – Segmented – required = 19'
4(4’) + 2(2.5’) = 21’ actual length4(4’)+ 2(2.5’)(2(2.5)/8) = 19.1’ effective lengthEffective length of FHS > 19’ req’d FHS OK
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n78
Segmented shear wall – requires hold downs on each segment
2015 WFCM Prescriptive Segmented – Hold-downs
WFCM PRESCRIPTIVE - SEISMIC
Copyright © 2018 American Wood CouncilAll rights reserved.
40
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n79
% Full-height sheathing19' / 36’ = 53%Interpolated = 1.40
19’(1.40) = 26.6'Req’d length of FHS
19.1' effective FHS < 26.6' req’d FHS NG
2015 WFCM Prescriptive – Perforated Shear WallWFCM PRESCRIPTIVE - SEISMIC
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n80
WFCM PRESCRIPTIVE - SEISMIC
2015 WFCM Prescriptive – Segmented
SDPWS adjustment = 2bs/h (stiffness)
Copyright © 2018 American Wood CouncilAll rights reserved.
41
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n81
With 4/12 nailing19'(0.68) = 12.9' (segmented)
% Full-height sheathing12.9' / 36' = 36%Interpolated = 1.62
12.9'(1.62) = 20.9'Req’d length FHS
19.1' effective FHS < 20.9’ req’d FHS NG
2015 WFCM Prescriptive – Perforated Shear WallWFCM PRESCRIPTIVE - SEISMIC
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n82
WFCM PRESCRIPTIVE - SEISMIC2015 WFCM Prescriptive – Segmented
SDPWS adjustment = 2bs/h
Copyright © 2018 American Wood CouncilAll rights reserved.
42
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n83
With 3/12 nailing19' (0.53) = 10.1' (segmented)
% Full-height sheathing10.1' / 36' = 28%Interpolated = 1.76
10.1’(1.76) = 17.8'Req’d length FHS
19.1' effective FHS > 17.8’ req’d FHS OK
2015 WFCM Prescriptive – Perforated Shear Wall
WFCM PRESCRIPTIVE - SEISMIC
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n84
PSW requires fully sheathed wall• Nailing at 3/12
2015 WFCM Prescriptive – Perforated
WFCM PRESCRIPTIVE - SEISMIC
Copyright © 2018 American Wood CouncilAll rights reserved.
43
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n85
PSW requires hold-downs only at the ends
2015 WFCM Prescriptive – Perforated – Hold-downs
WFCM PRESCRIPTIVE - SEISMIC
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n86
Hold-downs= 1,912 lbsFor segmented wall @ 6/12 nailing
1,912 / 0.53= 3,608 lbsFor PSW @ 3/12 nailing
2015 WFCM Prescriptive – Hold-downs
• Need to combine with top floor hold-down requirements• Based on capacity of first shear wall panel• Does not include dead load
WFCM PRESCRIPTIVE - SEISMIC
Copyright © 2018 American Wood CouncilAll rights reserved.
44
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n E x a m p l e8 7
POLLING QUESTION
4. WFCM Seismic tabulated shear wall values assume which of the following?
a) Studs are spaced at 24”oc max.
b) 19/32” wood structural panels on the exterior
c) 8d common nails at 6”oc panel edges
d) ½” gypsum wallboard capacity
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n88
OUTLINE
• 2015 IBC/IRC Recognition• Background and Assumptions
• Wind Examples
• 2015 WFCM Prescriptive
• 2015 WFCM Engineered
• 2015 SDPWS
• Seismic Examples • 2015 WFCM Prescriptive
• 2015 WFCM Engineered
• 2015 SDPWS
Copyright © 2018 American Wood CouncilAll rights reserved.
45
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n89
WFCM p. 14
WFCM ENGINEERED - SEISMIC
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n90
WFCM ENGINEERED - SEISMIC
WFD2 = 83,680 lbs
VFD2 = 1.1 (83,680) 0.83 / 6.5 = 8,228 lbs
SDS for D1 = 0.83R = 6.51.1 = vertical
force distribution factor
0.7 = ASD load factor
Copyright © 2018 American Wood CouncilAll rights reserved.
46
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n91
WFCM ENGINEERED - SEISMIC COMMENTARY
Simplified Approach ASCE 7-10 Section 12.14.8
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n92
WFCM ENGINEERED - SEISMIC
2015 WFCM Engineered – Segmented
SDPWS adjustment = 2bs/h (for stiffness)
Copyright © 2018 American Wood CouncilAll rights reserved.
47
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n93
Required Capacity = 8,228/2 = 4,114 lbs7/16 WSP Capacity = 239 plf
4,114 lbs / 239 plf = 17.2’Req’d length of FHS
2015 WFCM Engineered Segmented
8,228
4,114
Plan View
4,114
WFCM ENGINEERED - SEISMIC
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n94
4,114 lbs
4(4’) + 2(2.5’) = 21’ actual length4(4’)+ 2(2.5’)(2(2.5)/8) = 19.1’ • Effective length of FHS > 17.2’ req’d FHS OK
2015 WFCM Engineered Segmented
WFCM ENGINEERED - SEISMIC
Copyright © 2018 American Wood CouncilAll rights reserved.
48
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n95
Reference SDPWS Capacities and AdjustmentsV = 4,114 lbsv = 239 plf%FHS = Li / LtotLi = 16’ + 2[2(2.5)/8]2.5’ = 19.1’Ltot = 36’%FHS = 19.1’ / 36’ = 53%Interpolated Co Factor = 0.59
239(0.59) = 141 plf4,114/141 = 29.2’ Req’d FHS
29.2’ > 19.1’ effective FHS NG
2015 WFCM Engineered - Perforated
Note: Li per SDPWS 4.3.4.3 adjustment = 2bs/h
WFCM ENGINEERED - SEISMIC
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n96
WFCM ENGINEERED - SEISMIC2015 WFCM Engineered – Segmented
SDPWS adjustment = 2bs/h for stiffness
Copyright © 2018 American Wood CouncilAll rights reserved.
49
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n97
Reference SDPWS Capacities and AdjustmentsV = 4,114 lbsv = 350 plf%FHS = Li / LtotLi = 16’ + 2[2(2.5)/8]2.5’ = 19.1’Ltot = 36’%FHS = 19.1’ / 36’ = 53%Interpolated Co Factor = 0.59
350(0.59) = 207 plf4,114/207 = 19.9’ Req’d FHS
19.9’ > 19.1’ effective FHS NG
2015 WFCM Engineered - Perforated
Note: Li per SDPWS 4.3.4.3 adjustment = 2bs/h
WFCM ENGINEERED - SEISMIC
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n98
WFCM ENGINEERED - SEISMIC
2015 WFCM Engineered – Segmented
SDPWS adjustment = 2bs/h
Copyright © 2018 American Wood CouncilAll rights reserved.
50
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n99
Reference SDPWS Capacities and AdjustmentsV = 4,114 lbsv = 451 plf%FHS = Li / LtotLi = 16’ + 2[2(2.5)/8]2.5’ = 19.1’Ltot = 36’%FHS = 19.1’ / 36’ = 53%Interpolated Co Factor = 0.59
451(0.59) = 266 plf4,114/266 = 15.5’ Req’d FHS
15.5’ < 19.1’ effective FHS OK
2015 WFCM Engineered - Perforated
Note: Li per SDPWS 4.3.4.3 adjustment = 2bs/h
WFCM ENGINEERED - SEISMIC
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n100
19.1' effective FHS > 15.5' req’d FHS OK
2015 WFCM Engineered - Perforated
WFCM ENGINEERED - SEISMIC
Copyright © 2018 American Wood CouncilAll rights reserved.
51
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n101
T = v hv = 239 plf – segmented @ 6/12v = 451 plf – perforated @ 3/12h = 8’T = 239(8’) = 1,912 lbs - segmentedT = 451(8’) = 3,608 lbs - perforated
2015 WFCM Engineered – Hold-downs
• Need to combine with top floor hold-down requirements• Based on capacity of first shear wall panel• Can account for dead load (WFCM 2.2.4)
WFCM ENGINEERED - SEISMIC
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n E x a m p l e1 0 2
POLLING QUESTION
5. The tabulated perforated shear wall shear capacity adjustment factor is not based on the maximum unrestrained opening height.
FalseTrue or
Copyright © 2018 American Wood CouncilAll rights reserved.
52
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n103
OUTLINE
• 2015 IBC/IRC Recognition
• Background and Assumptions
• Wind Examples
• 2015 WFCM Prescriptive
• 2015 WFCM Engineered
• 2015 SDPWS
• Seismic Examples
• 2015 WFCM Prescriptive
• 2015 WFCM Engineered
• 2015 SDPWS
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n104
SDPWS
• Engineered
• Res and Non-Res
• ASD & LRFD
• Efficiencies in designs
• Shear wall provisions
• Segmented
• Perforated
• Force Transfer Around Openings
2015 SDPWS
Copyright © 2018 American Wood CouncilAll rights reserved.
53
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n105
MINIMUM DESIGN LOADS
ASCE 7-10 Minimum Design Loads for Buildings and Other Structures
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n106
Footnote 1: ASD capacity = half the nominal capacity Footnote 2: use 15/32 capacity for studs at 16” o.c.Footnote 3: SG adjustment factor = 0.92 for SPFASD Capacity = 520 (0.92) / 2 = 239 plf
2015 SDPWS – SEISMIC WSP CAPACITY
Copyright © 2018 American Wood CouncilAll rights reserved.
54
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n107
2015 SDPWSAdjustment factor
(based on stiffness)
SDPWS - SEISMIC
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n108
2015 SDPWS
Aspect Ratio factor(for strength)
SDPWS - SEISMIC
Copyright © 2018 American Wood CouncilAll rights reserved.
55
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n109
SDPWS - SEISMIC
Required Capacity = 4,114 lbs
WSP = 239 plf
Aspect Ratio > 2:1
Adjustment factor (based on stiffness) = 2bs/h
= 2(2.5)/8 = 0.625
Aspect Ratio Factor (strength) = 1.25 - 0.125h/bs
= 1.25 - 0.125(8)/2.5 = 0.84
WSP = 239(0.625) = 149 plf
Shear Distribution
Governs
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n110
239plf(4)(4’) + 149plf(2)(2.5’) = 4569 lbs adjusted capacity 4569 lbs > 4114 lbs (req’d capacity)
4,114 lbs
2015 SDPWS – Segmented Shear Wall
OK
SDPWS - SEISMIC
Copyright © 2018 American Wood CouncilAll rights reserved.
56
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n111
SDPWS - SEISMIC
Required Capacity = 4,114 lbs
239(4)(4’) + 149(2)(x) = 4,114
x = 0.97
Required length FHS = 16’ + 0.97’ = 17.0’
Actual length = 21’
Required Length of FHS
OK
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n112
SDPWS - SEISMIC
Shear Capacity Adjustment Factor
h = 8’
Li = 16’ + 2[2(2.5)/8]2.5’ = 19.1’
Ltot = 36’
Ao = 4(4’)(2.5’) + (5’)(6.67’) = 73.4 ft2
r = 0.68
Co = 0.77 (based on total sheathed area)
Comparison: SDPWS/WFCM Engineered (tabulated) Co = 0.59
Note: Li per SDPWS 4.3.4.3 adjustment = 2bs/h
2015 SDPWS – Perforated Shear Wall
Copyright © 2018 American Wood CouncilAll rights reserved.
57
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n113
SDPWS - SEISMIC
Co = 0.77
239 plf (0.77) = 184 plf
4,114/184 = 22.3’ req’d FHS
22.3’ > 21’ actual FHS
6/12 nail spacing
2015 SDPWS – Perforated Shear Wall
NG
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n114
Footnote 1: ASD capacity = half the nominal capacity Footnote 2: use 15/32 capacity for studs at 16” o.c.Footnote 3: SG adjustment factor = 0.92 for SPFASD Capacity = 760 (0.92) / 2 = 350 plf
2015 SDPWS – SEISMIC WSP CAPACITY
Copyright © 2018 American Wood CouncilAll rights reserved.
58
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n115
SDPWS - SEISMIC
Co = 0.77
350 plf (0.77) = 270 plf
4,114/270 = 15.2’ req’d FHS
15.2’ < 21’ actual FHS OK
4/12 nail spacing
2015 SDPWS – Perforated Shear Wall
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n116
2015 SDPWS – Perforated Shear Wall
4,114 lbs
21’ actual FHS > 15.2' req’d FHS OK
SDPWS - SEISMIC
Copyright © 2018 American Wood CouncilAll rights reserved.
59
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n117
SDPWS - SEISMIC
T = v h
v = 4,114/19.1' = 215 plf
h = 8'
T = 215(8') = 1,723 lbs
2015 SDPWS – Hold-downs (Segmented)
• Need to combine with top floor hold-down requirements• Based on loads• Can account for dead load (4.3.6.4.2)
(4.3-7)
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n118
SDPWS - SEISMIC
V = 4,114 lbs
h = 8'
Co = 0.77
Li = 16’ + 2[2(2.5)/8]2.5’
Li = 19.1'
T = 2,238 lbs
2015 SDPWS – Hold-downs (Perforated)
• Need to combine with top floor hold-down requirements• Based on loads• Can account for dead load (4.3.6.4.2)
4.3.4.3…In the design of perforated shear walls, the length of each perforated shear wall segment with an aspect ratio greater than 2:1 shall be multiplied by 2bs/h for the purposes of determining Li and Li
Copyright © 2018 American Wood CouncilAll rights reserved.
60
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n119
AWC Standard
Segmented(SSW)
Perforated(PSW) Hold-downs, lbs
2015 WFCM Prescriptive
19.0' (6/12)
17.8' (3/12)
1,912 [SSW]3,608 [PSW]
2015 WFCM Engineered
17.2' (6/12)
15.5' (3/12)
1,912 [SSW]3,608 [PSW]
2015 SDPWS 17.0' (6/12)
15.2' (4/12)
1,723 [SSW]2,238 [PSW]
2015 WFCM/SDPWS Shear Wall Length Comparison1st of 2-story; W=30'; L = 36’; GSL = 30psf; SDC D1
Parenthetical values show nail spacing: (edge/field)
SEISMIC DESIGN EXAMPLE - SUMMARY
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n120
AWC Standard Segmented(SSW)
Perforated(PSW) Hold-downs, lbs
2015 WFCM Prescriptive
8.4’ [10.9’] (6/12)
15.6’ [18.8’] (6/12) 3,488 [2,683]
2015 WFCM Engineered
6.8’ [8.9’] (6/12)
11.6’ [15.1’] (6/12)
3,488 [2,683]
2015 SDPWS 6.9’ [8.9’] (6/12)
8.9’ [11.6’] (6/12)
2,985 [1,840] [SSW]1,624 [1,001] [PSW]
Parenthetical values show nail spacing: (edge/field)
2015 WFCM Prescriptive 19.0' (6/12) 17.8' (3/12) 1,912 [SSW]
3,608 [PSW]2015 WFCM Engineered 17.2' (6/12) 15.5' (3/12) 1,912 [SSW]
3,608 [PSW]
2015 SDPWS 17.0' (6/12) 15.2' (4/12) 1,723 [SSW]2,238 [PSW]
WIND & SEISMIC DESIGN EXAMPLE - SUMMARY2015 WFCM/SDPWS Shear Wall Length Comparison
1st of 2-story; W=30'; L = 36’; GSL = 30psf; 130 mph Exposure B; SDC D1
Wind
Seismic
Copyright © 2018 American Wood CouncilAll rights reserved.
61
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n E x a m p l e1 2 1
MORE INFO???
SDPWShttp://awc.org/codes-standards/publications/sdpws-2015
WFCMhttp://awc.org/codes-standards/publications/wfcm-2015
W o o d S h e a r W a l l S e i s m i c a n d W i n d D e s i g n122
RESOURCES
www.apawood.org
Copyright © 2018 American Wood CouncilAll rights reserved.
62
T h i s p r e s e n t a t i o n i s p r o t e c t e d b y U S a n d I n t e r n a t i o n a l C o p y r i g h t l a w s . R e p r o d u c t i o n , d i s t r i b u t i o n , d i s p l a y a n d u s e o f t h e p r e s e n t a t i o n w i t h o u t w r i t t e n p e r m i s s i o n o f A m e r i c a n W o o d C o u n c i l ( A W C ) i s
p r o h i b i t e d . © A m e r i c a n W o o d C o u n c i l 2 0 1 8
in [email protected] | www.awc.org
This concludes the American Institute of Architects Continuing Education Systems Course