    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    III.4 ADRESSABLE FIRE ALARM SYSTEM (CLOSED

    LOOP SYSTEM) BLOCK-A

    1 182 Supply and installation of photo electric analogaddressable optical smoke detectors ( multi sensor )

    suitable for detecting a wide range of smoke from slow

    smoldering and fast flaming fire. The detectors shall

    have following features and also including supply of all

    fixing materials complete as required

    Each

    Solid state addressing arrangement in combination

    with a hand held programmer to configure the sensor

    address.

    Electronics free mounting baseTwin alarm LED's for 360 degree viewing and shall

    have blinking LED facility.

    Photo electric sensor shall have a removable chamber

    for ease of cleaning or replacement.

    Automatic compensation for smoke sensor

    contamination.

    Shall have a built in test facility which allows the fire

    alarm control panel to adjust the alarm threshold levels

    to compensate for contamination and shall have a

    maintenance alarm display when threshold can no

    longer be adjusted.

    Operating Temp Range: 10 deg C to 59 deg C and

    Humidity : 95% RH non-condensing.

    2 5 Supply and installation of optical type duct detectors

    same as no 2 above but inside a air sampling chamber

    to be located inside the AC return air duct including

    supply o all fixing materials.

    Each

    3 3 Supply and installation of analog addressable heat

    detector. The detector shall have the following features

    :

    Each

    Page 1 of 32

  • 7/29/2019 Works for Addressable

    2/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    Solid state addressing arrangement in combination

    with a hand held programmer to configure the sensor

    address.

    Electronics free mounting base

    Twin alarm LED's for 360 degree viewing and shall

    have blinking LED facility.

    Simple anti tamper locking mechanism

    4 110 Supply and installation of visual type response

    indicators with LED indicating lamp, housed in suitable

    MS enclosure with acrylic cover fixed in flush with wall

    to operate in conjunction with smoke / heat detectors

    operating on 24VDC installed above the false ceiling

    or below the false floor, complete with all accessories

    and fixing materials as required and as directed by

    Engineer in charge.

    Each

    5 4 Supply and installation of addressable manual call

    stations with in build monitor module and press /

    break and resettable capability constructed of high

    impact LEXAN sheet with clearly visible operating

    instructions on the cover and the word Fire shall

    appear on front and suitable for surface mounting /

    flush mounting and complete as required.

    Each

    6 14 Supply and installation of short circuit isolator, analog

    addressable type for isolating analog devices from

    short circuit, fault isolating module shall have LED that

    is to indicate a short on the loop. This device shall

    automatically determining an return to normal

    condition of the loop and restore the isolated

    segments.

    Each

    7 4 Supply and installation of loop powered base

    addressable sounders complete with all fixing material

    complete as required

    Set

    Page 2 of 32

  • 7/29/2019 Works for Addressable

    3/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    8 5 Supply and installationof addressable control modules

    for providing tripping contacts for the AHUs ( This shall

    be wired in the loop and located near the AHUs )

    including supply and fixing of all fixing materials asrequired.

    Set

    9 1 Supply, installation, testing and commissioning of

    micro processor based digital distributed processing

    real time multitasking and multi user type loop analog

    addressable type fire alarm control panel FACP and

    control panel shall have the following features

    including supply of all fixing materials interconnections

    earthing complete as required. ( 2 LOOP PANEL)

    Set

    FACP shall be suitable for 230 V 50hz AC supply and

    smoke detectors shall be powered using FACP based

    smoke detection circuits. Devices shall receive power

    and communication for the same pair of conductors.

    FACP shall provide for resetting smoke detectors fault

    isolation and sensor loop operation.

    FACP shall be suitable for mixing different fire devices

    and beam smoke detectors within the same loop to

    optimize field wiring.

    FACP shall have alarm indication of individualsensors

    detectors trouble alarm indication for dust

    accumulation The panel shall check detectors once in

    every 24 hours for contamination for this purpose.

    The FACP shall regularly supervise all the sensors and

    devices on the loop and initiate fire or trouble alarm

    whenever required.

    FACP shall have 2 wire circuit to connect 126

    addressable devices per loop

    Page 3 of 32

  • 7/29/2019 Works for Addressable

    4/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    FACP shall be with repeater interface and suitable 24

    batter with built in software and 2 x 40 character

    alphanumeric LCD display and necessary front panel

    control keys, FACP shall display the date time anddescription for analog sensors to indicate alarms and

    trouble situations.

    FACP switches shall allow authorized personnel to

    accomplish the following

    Initiate a general alarm condition

    Silence the local audible

    Silence the alarm signals

    Reset all zones / points

    FACP shall have walk test facility

    Shall have facility for programming from the key boardor utilizing PC set up software via laptop / desk top

    computer

    Shall have memory data for panel configuration and

    operation reside in non volatile memory ( EPROM )

    All addressable units shall be connected to the FACP

    through the loop cards and shall be addressed

    through individualized numbers. The FACP shall be

    able to obtain analog value for all detectors in the

    circuit through a pulsed digitized current data. The

    FACP shall be able to analyze all analog inputs from al

    addressable units and through its own software and

    ambient level screening the FACP shall be able to

    identify fire, possible fire or fault condition. The unit

    supervision shall be dynamic and continuous

    The FACP shall itself have all loop cards in it. No

    isolated motherboard or transponder shall be

    considered.

    Page 4 of 32

  • 7/29/2019 Works for Addressable

    5/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    Short/ open circuit units shall also be reported at the

    FACP in such cases the system through the use of

    fault isolators shall be able to isolate that segment

    between the two fault isolators. The missing detectors/ devices shall also be reported to the FACP with

    identification of the location.

    The FACP shall have the facility to set smoke sensor

    sensitivityremotely to either high sensitivitymanuallyor

    on a pre programmed sequence ( ie day/ night ) period

    When an alarm condition is sensed at the FACP from

    a smoke or heat detector, a delay time / alarm

    verificationperiod shall be stated. If the sensor is still in

    alarm after the delay time expired , an alarm condition

    is reported. The delay time shall be adjustable from 0

    to 990 seconds.

    FACP shall have either an in built or external printer

    coupled to the FACP, which shall log all events with

    time. The printout shall clearly indicate the event fire /

    Pre alarm / Fault etc. with the unit address and time.

    The FACP shall also be able to discriminate between

    false alarms and fire conditions as well as priority

    selection of alarm in case alarm activates in two or

    more remotely located units simultaneously. In such

    cases the manual call stations shall have the highest

    priority.

    The FACP also be able to actuate switches

    automaticallyin case of fire condition that of AHUs and

    power supply or other system such as piped

    pressurized gas supply.

    Page 5 of 32

  • 7/29/2019 Works for Addressable

    6/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    The system shall be fail safe and adequate safe

    guards should be under taken that in the event of al

    failure of a part of the system it shall not handicap the

    complete system. The loop cards shall be of Modularconstruction.

    The FACP shall have its own battery backup of a

    minimum of 48 hrs in normal run and then half an hour

    in alarm condition. The back up time calculation shall

    be done as per TAC standards. The batteryshall be 2

    x 12 V ( 24 V ) DC and of sealed maintenance free

    type, housed inside the FACP.

    It shall be able to with stand temp variations from 0deg C to 55 deg C. Further RH up to 93 % shall not

    hamper its performance. The voltage rating shall be

    from 17 VDC to 31 VDC, though the voltage may be

    change depending upon the working voltages of a

    proprietary FACP

    The FACP shall be totally enclosed dust and vermin

    proof type made of minimum 16 gauge dust inhibited

    sheet with even baked finish. The FACP shall be of

    completely solid stage design.

    The logic circuitry shall be based on high noiseimmunity solid state hardware employing modular

    construction. Logic cards shall be of epoxy fiber glass

    construction.

    The FACP shall have EN54 / UL / FM approval

    The panel shall have an extra loop card to serve as

    standby in case of burnout or malfunctioning of any

    operating loop cards.

    The FACP shall be capable of being networked (

    future expansion ) with other similar FACPs located at

    different part of the premises through a single RS 485bus.

    Page 6 of 32

  • 7/29/2019 Works for Addressable

    7/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    The FACP shall have provision for interfacing with the

    public address system.

    10 1 Supply and installation of repeater panels which

    display fire / fault message simultaneously with the

    FACP. It shall be capable of interfacing with the FACP

    on a single RS485 bus. The panel shall be capable of

    operating on 24 VDC supply

    Each

    The panel shall have 2 x 40 characters backlit display

    which shall displaydate time and description of alarm /

    trouble events are that displayed in the FACP with in

    built buzzer to indicate fault / fire alarm.

    The panel shall be powered from the FACP

    It shall have control keys for sound silence mute and

    to reset the FACP from the repeater stations.

    The repeater panel shall have the following LEDs

    indications like supply , fault, mute, silent, disabled,

    fire.

    11 2200 Supply and wiring with 2C x 1,5sqmm FRLS twisted

    pair shielded,1.1KV grade PVC insulated unarmoured

    copper conductor cable , PVC overall sheathed cable

    in already embedded conduit with ISI certification

    mark, interconnections complete as required and as

    directed by EIC.

    Mtrs

    12 100 Supply ands wiring with 4C x 1.5 sqmm FRLS twisted

    pair shielded, 1.1 KV grade PVC insulated unarmored

    copper conductor cable PVC overall sheathed cable in

    already embedded conduit with ISI certification mark ,

    interconnections complete as required and as directed

    by EIC

    mtrs

    Page 7 of 32

  • 7/29/2019 Works for Addressable

    8/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    BLOCK-B

    1 130 Supply and installation of photo electric analog

    addressable optical smoke detectors ( multi sensor )

    suitable for detecting a wide range of smoke from slow

    smoldering and fast flaming fire. The detectors shall

    have following features and also including supply of all

    fixing materials complete as required

    Each

    Solid state addressing arrangement in combination

    with a hand held programmer to configure the sensor

    address.

    Electronics free mounting base

    Twin alarm LED's for 360 degree viewing and shall

    have blinking LED facility.

    Photo electric sensor shall have a removable chamberfor ease of cleaning or replacement.

    Automatic compensation for smoke sensor

    contamination.

    Shall have a built in test facility which allows the fire

    alarm control panel to adjust the alarm threshold levels

    to compensate for contamination and shall have a

    maintenance alarm display when threshold can no

    longer be adjusted.

    Operating Temp Range: 10 deg C to 59 deg C and

    Humidity : 95% RH non-condensing.

    2 6 Supply and installation of optical type duct detectorssame as no 2 above but inside a air sampling chamber

    to be located inside the AC return air duct including

    supply o all fixing materials.

    Each

    3 2 Supply and installation of analog addressable heat

    detector. The detector shall have the following features

    :

    Each

    Solid state addressing arrangement in combination

    with a hand held programmer to configure the sensor

    address.

    Electronics free mounting base

    Twin alarm LED's for 360 degree viewing and shall

    have blinking LED facility.

    Simple anti tamper locking mechanism

    Page 8 of 32

  • 7/29/2019 Works for Addressable

    9/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    4 67 Supply and installation of visual type response

    indicators with LED indicating lamp, housed in suitable

    MS enclosure with acrylic cover fixed in flush with wall

    to operate in conjunction with smoke / heat detectorsoperating on 24VDC installed above the false ceiling

    or below the false floor, complete with all accessories

    and fixing materials as required and as directed by

    Engineer in charge.

    Each

    5 4 Supply and installation of addressable manual call

    stations with in build monitor module and press /

    break and resettable capability constructed of high

    impact LEXAN sheet with clearly visible operating

    instructions on the cover and the word Fire shall

    appear on front and suitable for surface mounting /

    flush mounting and complete as required.

    Each

    6 11 Supply and installation of short circuit isolator, analog

    addressable type for isolating analog devices from

    short circuit, fault isolating module shall have LED that

    is to indicate a short on the loop. This device shall

    automatically determining an return to normal

    condition of the loop and restore the isolated

    segments.

    Each

    7 4 Supply and installation of loop powered base

    addressable sounders complete with all fixing materialcomplete as required

    Set

    8 6 Supply and installationof addressable control modules

    for providing tripping contacts for the AHUs ( This shall

    be wired in the loop and located near the AHUs )

    including supply and fixing of all fixing materials as

    required.

    Set

    9 1 Supply, installation, testing and commissioning of

    micro processor based digital distributed processing

    real time multitasking and multi user type loop analog

    addressable type fire alarm control panel FACP and

    control panel shall have the following features

    including supply of all fixing materials interconnections

    earthing complete as required.( 2 LOOP PANEL )

    Set

    Page 9 of 32

  • 7/29/2019 Works for Addressable

    10/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    FACP shall be suitable for 230 V 50hz AC supply and

    smoke detectors shall be powered using FACP based

    smoke detection circuits. Devices shall receive power

    and communication for the same pair of conductors.

    FACP shall provide for resetting smoke detectors fault

    isolation and sensor loop operation.

    FACP shall be suitable for mixing different fire devices

    and beam smoke detectors within the same loop to

    optimize field wiring.

    FACP shall have alarm indication of individualsensors

    detectors trouble alarm indication for dust

    accumulation The panel shall check detectors once inevery 24 hours for contamination for this purpose.

    The FACP shall regularly supervise all the sensors and

    devices on the loop and initiate fire or trouble alarm

    whenever required.

    FACP shall have 2 wire circuit to connect 126

    addressable devices per loop

    FACP shall be with repeater interface and suitable 24

    batter with built in software and 2 x 40 character

    alphanumeric LCD display and necessary front panel

    control keys, FACP shall display the date time and

    description for analog sensors to indicate alarms andtrouble situations.

    FACP switches shall allow authorized personnel to

    accomplish the following

    Initiate a general alarm condition

    Silence the local audible

    Silence the alarm signals

    Reset all zones / points

    FACP shall have walk test facility

    Shall have facility for programming from the key board

    or utilizing PC set up software via laptop / desk top

    computer

    Page 10 of 32

  • 7/29/2019 Works for Addressable

    11/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    Shall have memory data for panel configuration and

    operation reside in non volatile memory ( EPROM )

    All addressable units shall be connected to the FACP

    through the loop cards and shall be addressed

    through individualized numbers. The FACP shall be

    able to obtain analog value for all detectors in the

    circuit through a pulsed digitized current data. The

    FACP shall be able to analyze all analog inputs from al

    addressable units and through its own software and

    ambient level screening the FACP shall be able to

    identify fire, possible fire or fault condition. The unit

    supervision shall be dynamic and continuous

    The FACP shall itself have all loop cards in it. No

    isolated motherboard or transponder shall be

    considered.

    Short/ open circuit units shall also be reported at the

    FACP in such cases the system through the use of

    fault isolators shall be able to isolate that segment

    between the two fault isolators. The missing detectors

    / devices shall also be reported to the FACP with

    identification of the location.

    The FACP shall have the facility to set smoke sensorsensitivityremotely to either high sensitivitymanuallyor

    on a pre programmed sequence ( ie day/ night ) period

    When an alarm condition is sensed at the FACP from

    a smoke or heat detector, a delay time / alarm

    verificationperiod shall be stated. If the sensor is still in

    alarm after the delay time expired , an alarm condition

    is reported. The delay time shall be adjustable from 0

    to 990 seconds.

    FACP shall have either an in built or external printer

    coupled to the FACP, which shall log all events with

    time. The printout shall clearly indicate the event fire /

    Pre alarm / Fault etc. with the unit address and time.

    Page 11 of 32

  • 7/29/2019 Works for Addressable

    12/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    The FACP shall also be able to discriminate between

    false alarms and fire conditions as well as priority

    selection of alarm in case alarm activates in two or

    more remotely located units simultaneously. In suchcases the manual call stations shall have the highest

    priority.

    The FACP also be able to actuate switches

    automaticallyin case of fire condition that of AHUs and

    power supply or other system such as piped

    pressurized gas supply.

    The system shall be fail safe and adequate safe

    guards should be under taken that in the event of al

    failure of a part of the system it shall not handicap the

    complete system. The loop cards shall be of Modular

    construction.

    The FACP shall have its own battery backup of a

    minimum of 48 hrs in normal run and then half an hour

    in alarm condition. The back up time calculation shall

    be done as per TAC standards. The batteryshall be 2

    x 12 V ( 24 V ) DC and of sealed maintenance free

    type, housed inside the FACP.

    It shall be able to with stand temp variations from 0

    deg C to 55 deg C. Further RH up to 93 % shall not

    hamper its performance. The voltage rating shall be

    from 17 VDC to 31 VDC, though the voltage may be

    change depending upon the working voltages of a

    proprietary FACP

    The FACP shall be totally enclosed dust and vermin

    proof type made of minimum 16 gauge dust inhibited

    sheet with even baked finish. The FACP shall be of

    completely solid stage design.

    The logic circuitry shall be based on high noise

    immunity solid state hardware employing modular

    construction. Logic cards shall be of epoxy fiber glass

    construction.

    The FACP shall have EN54 / UL / FM approval

    The panel shall have an extra loop card to serve as

    standby in case of burnout or malfunctioning of any

    operating loop cards.

    Page 12 of 32

  • 7/29/2019 Works for Addressable

    13/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    The FACP shall be capable of being networked (

    future expansion ) with other similar FACPs located at

    different part of the premises through a single RS 485

    bus.

    The FACP shall have provision for interfacing with the

    public address system.

    10 1 Supply and installation of repeater panels which

    display fire / fault message simultaneously with the

    FACP. It shall be capable of interfacing with the FACP

    on a single RS485 bus. The panel shall be capable of

    operating on 24 VDC supply

    Each

    The panel shall have 2 x 40 characters backlit display

    which shall displaydate time and description of alarm /

    trouble events are that displayed in the FACP with in

    built buzzer to indicate fault / fire alarm.

    The panel shall be powered from the FACP

    It shall have control keys for sound silence mute and

    to reset the FACP from the repeater stations.

    The repeater panel shall have the following LEDs

    indications like supply , fault, mute, silent, disabled,

    fire.

    11 1700 Supply and wiring with 2C x 1,5sqmm FRLS twisted

    pair shielded,1.1KV grade PVC insulated unarmoured

    copper conductor cable , PVC overall sheathed cable

    in already embedded conduit with ISI certification

    mark, interconnections complete as required and as

    directed by EIC.

    Mtrs

    12 100 Supply ands wiring with 4C x 1.5 sqmm FRLS twisted

    pair shielded, 1.1 KV grade PVC insulated unarmored

    copper conductor cable PVC overall sheathed cable in

    already embedded conduit with ISI certification mark ,

    interconnections complete as required and as directed

    by EIC

    mtrs

    Page 13 of 32

  • 7/29/2019 Works for Addressable

    14/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    BLOCK-C

    1 210 Supply and installation of photo electric analog

    addressable optical smoke detectors ( multi sensor )

    suitable for detecting a wide range of smoke from slow

    smoldering and fast flaming fire. The detectors shall

    have following features and also including supply of all

    fixing materials complete as required

    Each

    Solid state addressing arrangement in combination

    with a hand held programmer to configure the sensor

    address.

    Electronics free mounting base

    Twin alarm LED's for 360 degree viewing and shall

    have blinking LED facility.Photo electric sensor shall have a removable chamber

    for ease of cleaning or replacement.

    Automatic compensation for smoke sensor

    contamination.

    Shall have a built in test facility which allows the fire

    alarm control panel to adjust the alarm threshold levels

    to compensate for contamination and shall have a

    maintenance alarm display when threshold can no

    longer be adjusted.

    Operating Temp Range: 10 deg C to 59 deg C and

    Humidity : 95% RH non-condensing.

    2 6 Supply and installation of optical type duct detectorssame as no 2 above but inside a air sampling chamber

    to be located inside the AC return air duct including

    supply o all fixing materials.

    Each

    3 5 Supply and installation of analog addressable heat

    detector. The detector shall have the following features

    :

    Each

    Solid state addressing arrangement in combination

    with a hand held programmer to configure the sensor

    address.

    Electronics free mounting base

    Page 14 of 32

  • 7/29/2019 Works for Addressable

    15/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    Twin alarm LED's for 360 degree viewing and shall

    have blinking LED facility.

    Simple anti tamper locking mechanism

    4 130 Supply and installation of visual type response

    indicators with LED indicating lamp, housed in suitable

    MS enclosure with acrylic cover fixed in flush with wall

    to operate in conjunction with smoke / heat detectors

    operating on 24VDC installed above the false ceiling

    or below the false floor, complete with all accessories

    and fixing materials as required and as directed by

    Engineer in charge.

    Each

    5 4 Supply and installation of addressable manual call

    stations with in build monitor module and press /

    break and resettable capability constructed of high

    impact LEXAN sheet with clearly visible operatinginstructions on the cover and the word Fire shall

    appear on front and suitable for surface mounting /

    flush mounting and complete as required.

    Each

    6 16 Supply and installation of short circuit isolator, analog

    addressable type for isolating analog devices from

    short circuit, fault isolating module shall have LED that

    is to indicate a short on the loop. This device shall

    automatically determining an return to normal

    condition of the loop and restore the isolated

    segments.

    Each

    7 4 Supply and installation of loop powered base

    addressable sounders complete with all fixing material

    complete as required

    Set

    8 6 Supply and installationof addressable control modules

    for providing tripping contacts for the AHUs ( This shall

    be wired in the loop and located near the AHUs )

    including supply and fixing of all fixing materials as

    required.

    Set

    Page 15 of 32

  • 7/29/2019 Works for Addressable

    16/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    9 1 Supply, installation, testing and commissioning of

    micro processor based digital distributed processing

    real time multitasking and multi user type loop analog

    addressable type fire alarm control panel FACP andcontrol panel shall have the following features

    including supply of all fixing materials interconnections

    earthing complete as required. (2 LOOP PANEL )

    Set

    FACP shall be suitable for 230 V 50hz AC supply and

    smoke detectors shall be powered using FACP based

    smoke detection circuits. Devices shall receive power

    and communication for the same pair of conductors.

    FACP shall provide for resetting smoke detectors faultisolation and sensor loop operation.

    FACP shall be suitable for mixing different fire devices

    and beam smoke detectors within the same loop to

    optimize field wiring.

    FACP shall have alarm indication of individualsensors

    detectors trouble alarm indication for dust

    accumulation The panel shall check detectors once in

    every 24 hours for contamination for this purpose.

    The FACP shall regularly supervise all the sensors and

    devices on the loop and initiate fire or trouble alarm

    whenever required.

    FACP shall have 2 wire circuit to connect 126

    addressable devices per loop

    FACP shall be with repeater interface and suitable 24

    batter with built in software and 2 x 40 character

    alphanumeric LCD display and necessary front panel

    control keys, FACP shall display the date time and

    description for analog sensors to indicate alarms and

    trouble situations.

    FACP switches shall allow authorized personnel to

    accomplish the followingInitiate a general alarm condition

    Silence the local audible

    Page 16 of 32

  • 7/29/2019 Works for Addressable

    17/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    Silence the alarm signals

    Reset all zones / points

    FACP shall have walk test facility

    Shall have facility for programming from the key board

    or utilizing PC set up software via laptop / desk top

    computer

    Shall have memory data for panel configuration and

    operation reside in non volatile memory ( EPROM )

    All addressable units shall be connected to the FACP

    through the loop cards and shall be addressed

    through individualized numbers. The FACP shall be

    able to obtain analog value for all detectors in the

    circuit through a pulsed digitized current data. The

    FACP shall be able to analyze all analog inputs from al

    addressable units and through its own software and

    ambient level screening the FACP shall be able toidentify fire, possible fire or fault condition. The unit

    supervision shall be dynamic and continuous

    The FACP shall itself have all loop cards in it. No

    isolated motherboard or transponder shall be

    considered.

    Short/ open circuit units shall also be reported at the

    FACP in such cases the system through the use of

    fault isolators shall be able to isolate that segment

    between the two fault isolators. The missing detectors

    / devices shall also be reported to the FACP withidentification of the location.

    The FACP shall have the facility to set smoke sensor

    sensitivityremotely to either high sensitivitymanuallyor

    on a pre programmed sequence ( ie day/ night ) period

    Page 17 of 32

  • 7/29/2019 Works for Addressable

    18/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    When an alarm condition is sensed at the FACP from

    a smoke or heat detector, a delay time / alarm

    verificationperiod shall be stated. If the sensor is still in

    alarm after the delay time expired , an alarm conditionis reported. The delay time shall be adjustable from 0

    to 990 seconds.

    FACP shall have either an in built or external printer

    coupled to the FACP, which shall log all events with

    time. The printout shall clearly indicate the event fire /

    Pre alarm / Fault etc. with the unit address and time.

    The FACP shall also be able to discriminate between

    false alarms and fire conditions as well as priority

    selection of alarm in case alarm activates in two ormore remotely located units simultaneously. In such

    cases the manual call stations shall have the highest

    priority.

    The FACP also be able to actuate switches

    automaticallyin case of fire condition that of AHUs and

    power supply or other system such as piped

    pressurized gas supply.

    The system shall be fail safe and adequate safe

    guards should be under taken that in the event of al

    failure of a part of the system it shall not handicap the

    complete system. The loop cards shall be of Modular

    construction.

    The FACP shall have its own battery backup of a

    minimum of 48 hrs in normal run and then half an hour

    in alarm condition. The back up time calculation shall

    be done as per TAC standards. The batteryshall be 2

    x 12 V ( 24 V ) DC and of sealed maintenance free

    type, housed inside the FACP.

    Page 18 of 32

  • 7/29/2019 Works for Addressable

    19/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    It shall be able to with stand temp variations from 0

    deg C to 55 deg C. Further RH up to 93 % shall not

    hamper its performance. The voltage rating shall be

    from 17 VDC to 31 VDC, though the voltage may bechange depending upon the working voltages of a

    proprietary FACP

    The FACP shall be totally enclosed dust and vermin

    proof type made of minimum 16 gauge dust inhibited

    sheet with even baked finish. The FACP shall be of

    completely solid stage design.

    The logic circuitry shall be based on high noise

    immunity solid state hardware employing modular

    construction. Logic cards shall be of epoxy fiber glass

    construction.

    The FACP shall have EN54 / UL / FM approval

    The panel shall have an extra loop card to serve as

    standby in case of burnout or malfunctioning of any

    operating loop cards.

    The FACP shall be capable of being networked (

    future expansion ) with other similar FACPs located at

    different part of the premises through a single RS 485

    bus.

    The FACP shall have provision for interfacing with the

    public address system.

    10 1 Supply and installation of repeater panels whichdisplay fire / fault message simultaneously with the

    FACP. It shall be capable of interfacing with the FACP

    on a single RS485 bus. The panel shall be capable of

    operating on 24 VDC supply

    Each

    The panel shall have 2 x 40 characters backlit display

    which shall displaydate time and description of alarm /

    trouble events are that displayed in the FACP with in

    built buzzer to indicate fault / fire alarm.

    The panel shall be powered from the FACP

    It shall have control keys for sound silence mute andto reset the FACP from the repeater stations.

    Page 19 of 32

  • 7/29/2019 Works for Addressable

    20/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    The repeater panel shall have the following LEDs

    indications like supply , fault, mute, silent, disabled,

    fire.

    11 2600 Supply and wiring with 2C x 1,5sqmm FRLS twisted

    pair shielded,1.1KV grade PVC insulated unarmoured

    copper conductor cable , PVC overall sheathed cable

    in already embedded conduit with ISI certification

    mark, interconnections complete as required and as

    directed by EIC.

    Mtrs

    12 100 Supply ands wiring with 4C x 1.5 sqmm FRLS twisted

    pair shielded, 1.1 KV grade PVC insulated unarmored

    copper conductor cable PVC overall sheathed cable in

    already embedded conduit with ISI certification mark ,

    interconnections complete as required and as directedby EIC

    mtrs

    BLOCK-D

    1 260 Supply and installation of photo electric analog

    addressable optical smoke detectors ( multi sensor )

    suitable for detecting a wide range of smoke from slow

    smoldering and fast flaming fire. The detectors shall

    have following features and also including supply of all

    fixing materials complete as required

    Each

    Solid state addressing arrangement in combination

    with a hand held programmer to configure the sensor

    address.

    Electronics free mounting base

    Twin alarm LED's for 360 degree viewing and shall

    have blinking LED facility.

    Photo electric sensor shall have a removable chamber

    for ease of cleaning or replacement.

    Automatic compensation for smoke sensor

    contamination.

    Page 20 of 32

  • 7/29/2019 Works for Addressable

    21/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    Shall have a built in test facility which allows the fire

    alarm control panel to adjust the alarm threshold levels

    to compensate for contamination and shall have a

    maintenance alarm display when threshold can nolonger be adjusted.

    Operating Temp Range: 10 deg C to 59 deg C and

    Humidity : 95% RH non-condensing.

    2 11 Supply and installation of optical type duct detectors

    same as no 2 above but inside a air sampling chamber

    to be located inside the AC return air duct including

    supply o all fixing materials.

    Each

    3 5 Supply and installation of analog addressable heat

    detector. The detector shall have the following features

    :

    Each

    Solid state addressing arrangement in combination

    with a hand held programmer to configure the sensor

    address.

    Electronics free mounting base

    Twin alarm LED's for 360 degree viewing and shall

    have blinking LED facility.

    Simple anti tamper locking mechanism

    4 155 Supply and installation of visual type response

    indicators with LED indicating lamp, housed in suitable

    MS enclosure with acrylic cover fixed in flush with wall

    to operate in conjunction with smoke / heat detectors

    operating on 24VDC installed above the false ceilingor below the false floor, complete with all accessories

    and fixing materials as required and as directed by

    Engineer in charge.

    Each

    5 6 Supply and installation of addressable manual call

    stations with in build monitor module and press /

    break and resettable capability constructed of high

    impact LEXAN sheet with clearly visible operating

    instructions on the cover and the word Fire shall

    appear on front and suitable for surface mounting /

    flush mounting and complete as required.

    Each

    Page 21 of 32

  • 7/29/2019 Works for Addressable

    22/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    6 18 Supply and installation of short circuit isolator, analog

    addressable type for isolating analog devices from

    short circuit, fault isolating module shall have LED that

    is to indicate a short on the loop. This device shallautomatically determining an return to normal

    condition of the loop and restore the isolated

    segments.

    Each

    7 6 Supply and installation of loop powered base

    addressable sounders complete with all fixing material

    complete as required

    Set

    8 11 Supply and installationof addressable control modules

    for providing tripping contacts for the AHUs ( This shall

    be wired in the loop and located near the AHUs )

    including supply and fixing of all fixing materials asrequired.

    Set

    9 1 Supply, installation, testing and commissioning of

    micro processor based digital distributed processing

    real time multitasking and multi user type loop analog

    addressable type fire alarm control panel FACP and

    control panel shall have the following features

    including supply of all fixing materials interconnections

    earthing complete as required.(3LOOP PANEL )

    Set

    FACP shall be suitable for 230 V 50hz AC supply andsmoke detectors shall be powered using FACP based

    smoke detection circuits. Devices shall receive power

    and communication for the same pair of conductors.

    FACP shall provide for resetting smoke detectors fault

    isolation and sensor loop operation.

    FACP shall be suitable for mixing different fire devices

    and beam smoke detectors within the same loop to

    optimize field wiring.

    Page 22 of 32

  • 7/29/2019 Works for Addressable

    23/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    FACP shall have alarm indication of individualsensors

    detectors trouble alarm indication for dust

    accumulation The panel shall check detectors once in

    every 24 hours for contamination for this purpose.

    The FACP shall regularly supervise all the sensors and

    devices on the loop and initiate fire or trouble alarm

    whenever required.

    FACP shall have 2 wire circuit to connect 126

    addressable devices per loop

    FACP shall be with repeater interface and suitable 24

    batter with built in software and 2 x 40 character

    alphanumeric LCD display and necessary front panel

    control keys, FACP shall display the date time and

    description for analog sensors to indicate alarms and

    trouble situations.

    FACP switches shall allow authorized personnel to

    accomplish the following

    Initiate a general alarm condition

    Silence the local audible

    Silence the alarm signals

    Reset all zones / points

    FACP shall have walk test facility

    Shall have facility for programming from the key board

    or utilizing PC set up software via laptop / desk top

    computer

    Shall have memory data for panel configuration and

    operation reside in non volatile memory ( EPROM )

    All addressable units shall be connected to the FACP

    through the loop cards and shall be addressed

    through individualized numbers. The FACP shall be

    able to obtain analog value for all detectors in the

    circuit through a pulsed digitized current data. The

    FACP shall be able to analyze all analog inputs from al

    addressable units and through its own software and

    ambient level screening the FACP shall be able to

    identify fire, possible fire or fault condition. The unit

    supervision shall be dynamic and continuous

    Page 23 of 32

  • 7/29/2019 Works for Addressable

    24/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    The FACP shall itself have all loop cards in it. No

    isolated motherboard or transponder shall be

    considered.

    Short/ open circuit units shall also be reported at the

    FACP in such cases the system through the use of

    fault isolators shall be able to isolate that segment

    between the two fault isolators. The missing detectors

    / devices shall also be reported to the FACP with

    identification of the location.

    The FACP shall have the facility to set smoke sensor

    sensitivityremotely to either high sensitivitymanuallyor

    on a pre programmed sequence ( ie day/ night ) period

    When an alarm condition is sensed at the FACP from

    a smoke or heat detector, a delay time / alarm

    verificationperiod shall be stated. If the sensor is still in

    alarm after the delay time expired , an alarm condition

    is reported. The delay time shall be adjustable from 0

    to 990 seconds.

    FACP shall have either an in built or external printer

    coupled to the FACP, which shall log all events with

    time. The printout shall clearly indicate the event fire /

    Pre alarm / Fault etc. with the unit address and time.

    The FACP shall also be able to discriminate between

    false alarms and fire conditions as well as priority

    selection of alarm in case alarm activates in two or

    more remotely located units simultaneously. In such

    cases the manual call stations shall have the highest

    priority.

    The FACP also be able to actuate switches

    automaticallyin case of fire condition that of AHUs and

    power supply or other system such as piped

    pressurized gas supply.

    Page 24 of 32

  • 7/29/2019 Works for Addressable

    25/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    The system shall be fail safe and adequate safe

    guards should be under taken that in the event of al

    failure of a part of the system it shall not handicap the

    complete system. The loop cards shall be of Modularconstruction.

    The FACP shall have its own battery backup of a

    minimum of 48 hrs in normal run and then half an hour

    in alarm condition. The back up time calculation shall

    be done as per TAC standards. The batteryshall be 2

    x 12 V ( 24 V ) DC and of sealed maintenance free

    type, housed inside the FACP.

    It shall be able to with stand temp variations from 0

    deg C to 55 deg C. Further RH up to 93 % shall nothamper its performance. The voltage rating shall be

    from 17 VDC to 31 VDC, though the voltage may be

    change depending upon the working voltages of a

    proprietary FACP

    The FACP shall be totally enclosed dust and vermin

    proof type made of minimum 16 gauge dust inhibited

    sheet with even baked finish. The FACP shall be of

    completely solid stage design.

    The logic circuitry shall be based on high noise

    immunity solid state hardware employing modularconstruction. Logic cards shall be of epoxy fiber glass

    construction.

    The FACP shall have EN54 / UL / FM approval

    The panel shall have an extra loop card to serve as

    standby in case of burnout or malfunctioning of any

    operating loop cards.

    The FACP shall be capable of being networked (

    future expansion ) with other similar FACPs located at

    different part of the premises through a single RS 485

    bus.

    The FACP shall have provision for interfacing with thepublic address system.

    Page 25 of 32

  • 7/29/2019 Works for Addressable

    26/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    10 1 Supply and installation of repeater panels which

    display fire / fault message simultaneously with the

    FACP. It shall be capable of interfacing with the FACP

    on a single RS485 bus. The panel shall be capable ofoperating on 24 VDC supply

    Each

    The panel shall have 2 x 40 characters backlit display

    which shall displaydate time and description of alarm /

    trouble events are that displayed in the FACP with in

    built buzzer to indicate fault / fire alarm.

    The panel shall be powered from the FACP

    It shall have control keys for sound silence mute and

    to reset the FACP from the repeater stations.

    The repeater panel shall have the following LEDs

    indications like supply , fault, mute, silent, disabled,

    fire.

    11 3100 Supply and wiring with 2C x 1,5sqmm FRLS twisted

    pair shielded,1.1KV grade PVC insulated unarmoured

    copper conductor cable , PVC overall sheathed cable

    in already embedded conduit with ISI certification

    mark, interconnections complete as required and as

    directed by EIC.

    Mtrs

    12 100 Supply ands wiring with 4C x 1.5 sqmm FRLS twisted

    pair shielded, 1.1 KV grade PVC insulated unarmoredcopper conductor cable PVC overall sheathed cable in

    already embedded conduit with ISI certification mark ,

    interconnections complete as required and as directed

    by EIC

    mtrs

    Page 26 of 32

  • 7/29/2019 Works for Addressable

    27/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    CONNECTING CORRIDOOR FOR 4BLOCKS

    1 115 Supply and installation of photo electric analog

    addressable optical smoke detectors ( multi sensor )

    suitable for detecting a wide range of smoke from slow

    smoldering and fast flaming fire. The detectors shall

    have following features and also including supply of all

    fixing materials complete as required

    Each

    Solid state addressing arrangement in combination

    with a hand held programmer to configure the sensor

    address.

    Electronics free mounting base

    Twin alarm LED's for 360 degree viewing and shall

    have blinking LED facility.

    Photo electric sensor shall have a removable chamberfor ease of cleaning or replacement.

    Automatic compensation for smoke sensor

    contamination.

    Shall have a built in test facility which allows the fire

    alarm control panel to adjust the alarm threshold levels

    to compensate for contamination and shall have a

    maintenance alarm display when threshold can no

    longer be adjusted.

    Operating Temp Range: 10 deg C to 59 deg C and

    Humidity : 95% RH non-condensing.

    2 10 Supply and installation of short circuit isolator, analog

    addressable type for isolating analog devices from

    short circuit, fault isolating module shall have LED that

    is to indicate a short on the loop. This device shall

    automatically determining an return to normal

    condition of the loop and restore the isolated

    segments.

    Each

    Page 27 of 32

  • 7/29/2019 Works for Addressable

    28/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    3 1 Supply, installation, testing and commissioning of

    micro processor based digital distributed processing

    real time multitasking and multi user type loop analog

    addressable type fire alarm control panel FACP andcontrol panel shall have the following features

    including supply of all fixing materials interconnections

    earthing complete as required.( 2 LOOP PANEL )

    Set

    FACP shall be suitable for 230 V 50hz AC supply and

    smoke detectors shall be powered using FACP based

    smoke detection circuits. Devices shall receive power

    and communication for the same pair of conductors.

    FACP shall provide for resetting smoke detectors faultisolation and sensor loop operation.

    FACP shall be suitable for mixing different fire devices

    and beam smoke detectors within the same loop to

    optimize field wiring.

    FACP shall have alarm indication of individualsensors

    detectors trouble alarm indication for dust

    accumulation The panel shall check detectors once in

    every 24 hours for contamination for this purpose.

    The FACP shall regularly supervise all the sensors anddevices on the loop and initiate fire or trouble alarm

    whenever required.

    FACP shall have 2 wire circuit to connect 126

    addressable devices per loop

    FACP shall be with repeater interface and suitable 24

    batter with built in software and 2 x 40 character

    alphanumeric LCD display and necessary front panel

    control keys, FACP shall display the date time and

    description for analog sensors to indicate alarms and

    trouble situations.

    FACP switches shall allow authorized personnel to

    accomplish the following

    Page 28 of 32

  • 7/29/2019 Works for Addressable

    29/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    Initiate a general alarm condition

    Silence the local audible

    Silence the alarm signals

    Reset all zones / points

    FACP shall have walk test facility

    Shall have facility for programming from the key board

    or utilizing PC set up software via laptop / desk top

    computer

    Shall have memory data for panel configuration and

    operation reside in non volatile memory ( EPROM )

    FACP shall have facility for speech processor ( to

    record pre recorded message of 20 S ) and also have

    auto dialer facility ( can dial up to 8 different lines )

    All addressable units shall be connected to the FACP

    through the loop cards and shall be addressed

    through individualized numbers. The FACP shall be

    able to obtain analog value for all detectors in the

    circuit through a pulsed digitized current data. The

    FACP shall be able to analyze all analog inputs from al

    addressable units and through its own software and

    ambient level screening the FACP shall be able to

    identify fire, possible fire or fault condition. The unit

    supervision shall be dynamic and continuous

    The FACP shall itself have all loop cards in it. No

    isolated motherboard or transponder shall be

    considered.

    Short/ open circuit units shall also be reported at the

    FACP in such cases the system through the use of

    fault isolators shall be able to isolate that segment

    between the two fault isolators. The missing detectors

    / devices shall also be reported to the FACP with

    identification of the location.

    Page 29 of 32

  • 7/29/2019 Works for Addressable

    30/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    The FACP shall have the facility to set smoke sensor

    sensitivityremotely to either high sensitivitymanuallyor

    on a pre programmed sequence ( ie day/ night ) period

    When an alarm condition is sensed at the FACP from

    a smoke or heat detector, a delay time / alarm

    verificationperiod shall be stated. If the sensor is still in

    alarm after the delay time expired , an alarm condition

    is reported. The delay time shall be adjustable from 0

    to 990 seconds.

    FACP shall have either an in built or external printer

    coupled to the FACP, which shall log all events with

    time. The printout shall clearly indicate the event fire /

    Pre alarm / Fault etc. with the unit address and time.

    The FACP shall also be able to discriminate between

    false alarms and fire conditions as well as priority

    selection of alarm in case alarm activates in two or

    more remotely located units simultaneously. In such

    cases the manual call stations shall have the highest

    priority.

    The FACP also be able to actuate switches

    automaticallyin case of fire condition that of AHUs and

    power supply or other system such as pipedpressurized gas supply.

    The system shall be fail safe and adequate safe

    guards should be under taken that in the event of al

    failure of a part of the system it shall not handicap the

    complete system. The loop cards shall be of Modular

    construction.

    Page 30 of 32

  • 7/29/2019 Works for Addressable

    31/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    The FACP shall have its own battery backup of a

    minimum of 48 hrs in normal run and then half an hour

    in alarm condition. The back up time calculation shall

    be done as per TAC standards. The batteryshall be 2x 12 V ( 24 V ) DC and of sealed maintenance free

    type, housed inside the FACP.

    It shall be able to with stand temp variations from 0

    deg C to 55 deg C. Further RH up to 93 % shall not

    hamper its performance. The voltage rating shall be

    from 17 VDC to 31 VDC, though the voltage may be

    change depending upon the working voltages of a

    proprietary FACP

    The FACP shall be totally enclosed dust and vermin

    proof type made of minimum 16 gauge dust inhibited

    sheet with even baked finish. The FACP shall be of

    completely solid stage design.

    The logic circuitry shall be based on high noise

    immunity solid state hardware employing modular

    construction. Logic cards shall be of epoxy fiber glass

    construction.

    The FACP shall have EN54 / UL / FM approval

    The panel shall have an extra loop card to serve as

    standby in case of burnout or malfunctioning of any

    operating loop cards.

    The FACP shall be capable of being networked (

    future expansion ) with other similar FACPs located at

    different part of the premises through a single RS 485

    bus.

    The FACP shall have provision for interfacing with the

    public address system.

    Page 31 of 32

  • 7/29/2019 Works for Addressable

    32/32

    Package-I Part-III Electrical Works- Addressble Fire Alarm System

    Sl. NO QUANTITY DESCRIPTION UNITS RATE

    (IN FIGURES

    & WORDS)

    AMOUNT

    4 1 Supply and installation of repeater panels which

    display fire / fault message simultaneously with the

    FACP. It shall be capable of interfacing with the FACP

    on a single RS485 bus. The panel shall be capable ofoperating on 24 VDC supply

    Each

    The panel shall have 2 x 40 characters backlit display

    which shall displaydate time and description of alarm /

    trouble events are that displayed in the FACP with in

    built buzzer to indicate fault / fire alarm.

    The panel shall be powered from the FACP

    It shall have control keys for sound silence mute and

    to reset the FACP from the repeater stations.

    The repeater panel shall have the following LEDs

    indications like supply , fault, mute, silent, disabled,

    fire.

    5 1300 Supply and wiring with 2C x 1,5sqmm FRLS twisted

    pair shielded,1.1KV grade PVC insulated unarmoured

    copper conductor cable , PVC overall sheathed cable

    in already embedded conduit with ISI certification

    mark, interconnections complete as required and as

    directed by EIC.

    Mtrs

    6 120 Supply ands wiring with 4C x 1.5 sqmm FRLS twisted

    pair shielded, 1.1 KV grade PVC insulated unarmored

    copper conductor cable PVC overall sheathed cable inalready embedded conduit with ISI certification mark,

    interconnections complete as required and as directed

    by EIC

    mtrs

    TOTAL Rs