PROJECT TITLE: BTMP-B Fire & Gas Integrity Restoration Project.WORK ORDER NO: TBADATE OF VISIT: 27th December 2012PARTICIPANTS: Eugene Joseph – Jr. Engineer (SES)
Vincent Bising – E&I Supervisor (SES)
PLATFORM INVOLVED: BTMP-B
OBJECTIVE:
To verify and identify the remaining scope of works from previous campaign. To identify hotwork location for next campaign if any and also to highlight any findings or concerns which were encountered during this site visit.
No FINDINGS & RECOMMENDATIONS Action
Drilling Deck1 Remaining scope is to carry out like to like replacement of Infra Red Gas Detector
QZA0321A/B/C/D/E (4 nos). No more hotwork. To check against scope of work on cable replacements scope whether to use existing cables or
new cables. This was highlighted by E&I Supv, Vincent.
INFO
INFO
Production Deck1 Found out during visit, there are not enough spare MCTs for trunk cables from field JB to enter
Control Room. SSB to look into this matter since it might require new MCT to be installed. All trunk cables had been laid from outside of Control Room to its dedicated JBs but pending
penetration to Control Room and glanding & termination at field JB sides.
SSB PE
INFO
1 | P a g e
This spare MCT might be insufficient to accommodate all the new F&G trunk cables.
Trunk cables coiled near field JB. Pending glanding & termination.
No FINDINGS & RECOMMENDATIONS Action
Production Deck2 Below are F&G which still pending mounting pole installation & mounting support installation.
Hotwork & welding habitat required:i. QZA3035(T) – Located at Safe Zone
Below are F&G which still pending mounting pole installation but doesn’t require hotwork because the mounting supports were welded during previous campaign:
i. QZA3004ii. QZA3034 – No support required for this detector as the mounting plate will be
mounted directly to an existing pipe support.
INFO
INFO
3 F&G which requires hotwork & welding habitat for cable saddle installation:i. QZA3031 (R) – Located at safe zone
INFO
2 | P a g e
QZA3034 will be mounted on this pipe support.
Mounting pole to be welded on existing I-beam at this location.
ii. XZA3003 – Located at safe zoneiii. XZA3008 – Located at safe zoneiv. XZA3017 – Located at zone 2v. XZA3015 – Located at zone 2.
No FINDINGS & RECOMMENDATIONS Action
4 All cables from field JBs to F&G devices are not yet install, lay & pull. All F&G Field JBs were installed during previous campaign. Some existing cable trays/ladder already full. Consider some additional cable tray/ladder
during next campaign.
INFOINFOSSB PE
3 | P a g e
Cable saddle to be welded at this location for XZA3003.
Cable saddle to be welded at this location for XZA3015.
Mounting pole for XZA3015 already welded during previous campaign.
Cable saddle to be welded at this location for XZA3017.
Mounting pole for XZA3017 already welded during previous campaign.
No FINDINGS & RECOMMENDATIONS ActionCELLAR DECK
1 Below are F&G Detectors which are still pending mounting pole installation & mounting support installation. Hotwork & welding habitat required:
i. XZA2009 – Safe Zone ii. XZA2010 – Safe Zone
iii. QZA2008 – Safe Zoneiv. QZA2040 – Safe Zone (Also outstanding hotwork for coaming (deck penetration for
cable))v. XZA2015 – Safe Zone
vi. QZA2002 – Safe Zonevii. QZA2001 – Safe Zone
viii. XZA2001 – Safe Zoneix. QZA2003 – Zone 2x. QZA2007 – Zone 2
xi. XZA2002 – Zone 2xii. QZA2006 – Zone 2
xiii. XZA2006 – Zone 2 Below are F&G Detectors which are still pending mounting pole installation but doesn’t
require hotwork because the mounting supports had been welded during previous campaign:i. QZA2032(T)
ii. XZA2004 Layout below show cable trays which are still pending installation (Require both hotwork &
non hotwork). Blue colour show cold work tray installation, red colour shows hotwork tray installation.
For the non hotwork, the cable tray mounting supports had been installed during previous campaign.
INFO
4 | P a g e
Jacket Leg B1
Existing cable tray full.
5 | P a g e
END OF REPORT
Tray supports had been installed. Outstanding cable tray installation. Require cold work only.
Outstanding both cable trays & cable tray supports installation. Hotwork required.