Assemblies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32-33
Ester Based Mud Resistant Cable . . . . . . . . . 30-31
General Information• Ampacity Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . 1• Bend Radius . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1• Hawke Gland Types . . . . . . . . . . . . . . . . . . . . . . . . . . 1• Gexol Cable Stranding Profile . . . . . . . . . . . . . . . . . . 2
Instrumentation Cable. . . . . . . . . . . . . . . . . . . . 15-18• Individually Shielded Pairs. . . . . . . . . . . . . . . . 15 - 16• Individually Shielded Triads . . . . . . . . . . . . . . . 17 - 18
Multi-Conductor Control Cable . . . . . . . . . . . . 13-14
Power Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12• Single Conductor . . . . . . . . . . . . . . . . . . . . . . . . 3 - 4• Two Conductor . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 6• Three Conductor . . . . . . . . . . . . . . . . . . . . . . . . . 7 - 8• Four Conductor . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 10• Five Conductor. . . . . . . . . . . . . . . . . . . . . . . . . 11 - 12
Type MMV Medium Voltage Power Cable . . 21-29
Type VFD Power Cable• Standard Gexol Insulated VFD Cable . . . . . . . . 19-20• MMV VFD Cable. . . . . . . . . . . . . . . . . . . . . . . . . 27-28
Assembly Solutions . . . . . . . . . . . . . . . . . . . . . . . . . 32
®
AmerCable believes the information presented throughout this catalog to be reliable and current. All information is subject to change without notice. The information listedis approximate, and is presented only as a guide for product selection. We make no claims or warranties for the suitability of any product for any particular application.
� Fastest Lead Times• Standard 6 - 8 weeks• Emergency 2 - 4 weeks
� Best On-Time Delivery Rate*
� Highest Ampacity Ratings• DNV: 95°C• ABS: 100°C• Lloyd’s: 95°C
� Extremely Flexible
*Visit www.AmerCable.com for our most current on time delivery rate
Flame RetardantCertified to IEC 92-3 (332-3A)
and IEEE 1580
Severe Cold DurabilityExceeds CSA Cold Bend / Cold Impact (-40°C/-35°C)
Oil ResistantDrilling Mud Resistant
Gexol® is a registered trademark of AmerCable Incorporated. Registered in the U.S. Patent and Trademark Office. © 2009 AmerCable Incorporated
1
Diameter Conversion ➡ (inches to millimeters): Multiply by 25.4
Bend RadiusUnarmored Armored Armored & Sheathed
IEEE 45 6X Diameter 8X Diameter 8X Diameter
IEC 92 <1" (25mm) 6X Diameter 8X Diameter4 x Diameter>1" (25mm)6X Diameter
Transport <1" (25mm) 6X Diameter 6X DiameterCanada 4X Diameter
>1" (25mm)6X Diameter
Gexol® Insulated Oil & Gas Cables are the industry’s standard for premiumpower, control and instrumentationperformance. Gexol cables prove their value daily in the punishing operatingenvironments of offshore drilling andpetroleum facilities around the world.
Offshore applications challenge cableconstruction with relentless heat,vibration, salt corrosion, drilling mud and mechanical stress. And reliability is a huge issue – because it’s a long,long way to the nearest cable warehouse. You can depend on Gexol Insulated Oil & Gas cables for safe, reliable performance in theharshest operating conditions.
HawkeGland Types Unarmored Armored & SheathedIndustrial & Safe Area (IP68) 121 153-XIncreased Safety 501/421 501/453/U“EExe”Explosion Proof 710 753
Class I, Div. 2 Class I, Div. 1Class I, Zone 2 Class I, Zone 1 & 2
Flameproof 501/421 501/453/U“EExd” Zone 1 & 2 (2 liter or < enclosures)
ICG 653/U(2 liter or > enclosures)
Zone 1 & 2
Hawke Gland Types
110°C (Free Air) Ratings Based on IEEE Std. 835-1994 for isolated cables in freeair with full sun, 2 ft/s air movement, and a 45°C ambient.
110°C Ratings Based on IEEE Std. 45 with a 45°C ambient and arranged in a single bank per hanger. For those instances where cable must be double banked, the 110°C ampacities should be multiplied by 0.8.
100°C Ratings Based on IEEE Std. 45 with a 45°C ambient and arranged in a single bank per hanger. For those instances where cable must be double banked, the 100°C ampacities should be multiplied by 0.8.
95°C Ratings Based on Table 4/3C.10 of the 1997 ABS MODU rules and a 45°C ambient.
• Ampacities for four conductor cables are based on one conductor not acting as a normal current-carrying conductor (e.g., grounded neutral or grounding conductor).
• For free air ratings, the IEEE Std. 45 numbers can be divided by 0.85
Ampacity Ratings
®
Oil & Gas Cables
Individual Closest Equivalent UninsulatedSize Number Strand Dia. IEEE 45 Metric Size Conductor
AWG/kcmil of Strands (inches) Std. Size (mm2) Dia. (inches)
181614121086421
1/02/03/04/0
262313373444535646777
1111
19191919373761
133133209266342418532646777925
11101332159119242745
0.0100 0.0117 0.0147 0.01850.01670.0201 0.0201 0.01770.0223 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.02010.0201 0.0201 0.0201 0.0201 0.0201
2346
101626416683
106133168212262313373444535646777
1111
0.96 1.32 2.083.29 5.23 7.57
12.49 21.11 33.51 42.7954.45 70.01 85.57
108.91 132.25159.06 189.36227.23272.68325.70393.87561.94
0.0490.059 0.0740.093 0.113 0.1360.1750.2580.3240.361 0.4070.4610.510 0.5750.6540.720 0.7850.8600.9411.0291.1321.354
Gexol Insulated Power, Control andInstrumentation Cable
SSttrraannddiinngg PPrrooffiillee
Gexol Insulated Power, Control andInstrumentation Cable
SSttrraannddiinngg PPrrooffiilleeOil & Gas Cables
2
Flame RetardantCertified to IEC 92-3 (332-3A)
and IEEE 1580
Severe Cold DurabilityExceeds CSA Cold Bend / Cold Impact (-40°C/-35°C)
Oil ResistantDrilling Mud Resistant
HawkeGland Types Unarmored Armored & Sheathed
Industrial & Safe Area (IP68) 121 153-XIncreased Safety 501/421 501/453/U“EExe”Explosion Proof 710 753
Class I, Div. 2 Class I, Div. 1Class I, Zone 2 Class I, Zone 1 & 2
Flameproof 501/421 501/453/U“EExd” Zone 1 & 2 (2 liter or < enclosures)
ICG 653/U(2 liter or > enclosures)
Zone 1 & 2
3
37-102
Single Conductor Power CableGexol® InsulatedExtremely Flexible • 600V or 2kV • Rated 110°C
www. amercable.com • e-mail: [email protected]
Ratings & Approvals (Other certifications pending)
� 110˚C Temperature Rating� NVE 95/1696, FAL� Transport Canada 8700-20-2� Det Norske Veritas (DNV)
E-6669, E-6388, E-6390, E-6391� Lloyd’s Register of Shipping (LRS) 91/60333 (E6)� American Bureau of Shipping (ABS) 99-BT5905-X� UL Listed as Marine Shipboard Cable (E111461) � United States Coast Guard November 2, 1987 / 9304� CSA listed as Marine Shipboard Cable (82346)
ApplicationDesigned and constructed for the demanding environments of offshore drilling and petroleum facilities located throughout the world.
Features� High strand count conductors make this product much
more flexible, easier to install and more resistant to vibration than Type MC, IEC spec or commercial cables.
� Gexol’s lower dielectric constant and higher insulationresistance reduces electrical losses.
� Gexol’s excellent resistance to moisture produces stableelectrical properties throughout the life of the cable.
� In a fire condition, Gexol’s nonchlorinated flame retardantsystem produces less toxic and less corrosive gases.
� Dual certified IEEE 1580 Type P and UL 1309/CSA 245 Type X110.
� Highest ampacity ratings: ABS 100˚C, DNV 95˚C, LRS 95˚C, Transport Canada 95˚C.
� Severe cold durability: exceeds CSA cold bend/cold impact (-40˚C/-35˚C).
� Flame retardant: IEC 332-3 Category A and IEEE 1202.� Suitable for use in Class I, Division 1 and Zone 1
environments (armored and sheathed).� Optional braid armor of bronze or tinned copper.
Insulation/JacketGEXOL® cross-linked flame retardant polyolefin, meeting the requirements for Type P of IEEE 1580 and Type X110 of UL 1309/CSA 245.2000V/IEC 1000V.
Armor (Optional)Basket weave wirearmor per IEEE 1580 and UL1309/CSA 245. Bronze standard.Tinned copperavailable by request.
ConductorSoft annealedflexible strandedtinned copper perIEEE 1580 Table 11.
Sheath (Optional)A black, arctic grade,flame retardant, oil,abrasion, chemical and sunlight resistantthermosetting compound meeting UL 1309/CSA 245 andIEEE 1580.
®
Oil & Gas Cables
Size Unarmored Inductive Voltage Drop DC Resistance AC Resistance at AmpacityAWG/ Part No. Diameter Weight Reactance at 110°C at 25°C 110°C, 60 Hz Free Airkcmil 37-102 (inches) (lbs/MFt.) (Ohms/k ft.) (Volts/Amp/kft.) (Volts/Amp/kft.) (Ohms/k ft.) 110°C 110°C 100°C 95°C18 -151 0.143 16 0.046 13.560 7.210 9.763 30 17 16 2016 -153 0.153 18 0.044 8.516 4.520 6.121 35 25 23 2314 -154 0.168 25 0.041 5.383 2.850 3.859 41 40 37 3212 -156 0.187 32 0.038 3.394 1.790 2.424 64 48 45 3810 -158 0.207 51 0.036 2.155 1.130 1.530 85 62 58 518 -159 0.255 71 0.036 1.338 0.694 0.940 112 77 72 686 -160 0.295 108 0.034 0.852 0.436 0.590 148 103 96 914 -162 0.377 173 0.030 0.583 0.286 0.399 196 137 128 1212 -164 0.443 242 0.029 0.368 0.175 0.244 259 181 169 1621 -165 0.484 335 0.029 0.301 0.140 0.195 298 208 194 187
1/0 -166 0.548 420 0.029 0.246 0.111 0.156 344 243 227 2172/0 -167 0.615 494 0.028 0.202 0.089 0.125 396 281 262 2503/0 -168 0.663 734 0.028 0.167 0.070 0.100 457 321 300 289
600VUnarmored
(2kV on next page)
4
GEXO
L®is
a re
gist
ered
trad
emar
k of
Am
erCa
ble
Inco
rpor
ated
Man
ufac
ture
d by
Am
erCa
ble
Inco
rpor
ated
• 80
0-50
6-94
73 •
713-
896-
5800
• Fa
x: 7
13-8
49-9
009
1063
3 W
est L
ittle
Yor
k • B
ldg.
#1
• Sui
te #
100
• Hou
ston
, TX
7704
1 • w
ww
. am
erca
ble.
com
*Una
rmor
ed 3
/0 a
nd s
mal
ler h
as a
jack
et p
er U
L130
9 &
IEEE
1580
Cabl
e di
amet
ers
show
n as
nom
inal
are
sub
ject
to a
±5%
man
ufac
turin
g to
lera
nce
Orde
ring
Gexo
l Oil
& G
as C
able
sEx
ampl
e:
• Sin
gle
cond
ucto
r pow
er c
able
• 2kV
100
%• 5
35 k
cmil
• bro
nze
arm
ored
& s
heat
hed
Amer
Cabl
e Ge
xol
Oil &
Gas
Pre
fixSp
ecifi
c Ca
ble
Num
ber
(from
cha
rts)
Arm
or R
equi
rem
ent
BS –
arm
ored
&sh
eath
edBl
ank
– no
arm
or
37–1
02–
124
BS
See
page
2 fo
r Stra
ndin
g Pr
ofile
37-1
02
Sing
le C
ondu
ctor
Pow
er C
able
Gexo
l®In
sula
ted
Extre
mel
y Fl
exib
le •
2kV
• Rat
ed 1
10°C
2kV
– Fl
exib
le P
ower
Cab
le –
Sin
gle
Cond
ucto
rAr
mor
ed a
ndUn
arm
ored
Arm
ored
(B)
Shea
th (B
S)Si
zeUn
arm
ored
Diam
eter
Nom
inal
Nom
inal
Indu
ctiv
eVo
ltage
Dro
pDC
Res
ista
nce
AC R
esis
tanc
e at
Ampa
city
AWG/
Part
No.
Diam
eter
Wei
ght
Unde
r Arm
orW
eigh
t Di
amet
erW
eigh
tDi
amet
erW
eigh
tRe
acta
nce
at 1
10°C
at
25°
C11
0°C,
60 H
zFr
ee A
irkc
mil
mm
237
-102
(inch
es)
(lbs/
MFt
.)(in
ches
)(lb
s/M
Ft.)
(inch
es)
(lbs/
MFt
.)(in
ches
)(lb
s/M
Ft.)
(Ohm
s/10
00 ft
.)(V
olts
/Am
p/10
00 ft
.)(O
hms/
1000
ft.)
(Ohm
s/10
00 ft
.)11
0°C
110°
C10
0°C
95°C
181.
0-1
010.
232*
290.
143
160.
193
290.
324
380.
065
13.5
807.
210
9.76
330
1716
2016
1.3
-102
0.24
5*34
0.15
318
0.20
332
0.33
442
0.06
28.
535
4.52
06.
121
3525
2323
142.
1-1
050.
259*
420.
168
250.
218
450.
349
600.
057
5.40
12.
850
3.85
941
4037
3212
3.3
-106
0.28
1*53
0.18
732
0.23
758
0.36
880
0.05
33.
410
1.79
02.
424
6448
4538
105.
2-1
080.
302*
680.
207
510.
257
930.
388
127
0.05
02.
170
1.13
01.
530
8562
5851
87.
6-1
090.
354*
950.
255
710.
305
116
0.43
615
90.
048
1.35
10.
694
0.94
011
277
7268
612
.5-1
100.
384*
130
0.29
510
80.
345
155
0.47
620
40.
045
0.86
40.
436
0.59
014
810
396
914
21-1
120.
484*
210
0.37
717
30.
427
230
0.55
829
60.
039
0.59
30.
286
0.39
919
613
712
812
12
34-1
140.
576*
314
0.44
324
20.
493
303
0.62
436
50.
037
0.37
60.
175
0.24
425
918
116
916
21
43-1
150.
629*
393
0.48
433
50.
534
406
0.66
546
80.
036
0.30
70.
140
0.19
529
820
819
418
71/
054
-116
0.68
7*48
50.
548
420
0.59
849
40.
729
571
0.03
50.
253
0.11
10.
156
344
243
227
217
2/0
70-1
170.
737*
596
0.61
549
40.
665
579
0.79
666
20.
034
0.20
80.
089
0.12
539
628
126
225
03/
086
-118
0.78
8*70
90.
663
627
0.71
377
60.
886
900
0.03
40.
174
0.07
00.
100
457
321
300
289
4/0
109
-119
0.81
082
00.
810
820
0.86
088
91.
038
1036
0.03
30.
145
0.05
60.
080
528
376
351
335
262
132
-120
0.88
894
50.
888
945
0.93
811
471.
111
1295
0.03
40.
127
0.04
60.
067
599
436
407
382
313
159
-121
0.95
411
130.
954
1113
1.00
413
321.
177
1491
0.03
30.
112
0.03
80.
056
604
487
455
427
373
189
-122
1.01
814
191.
018
1419
1.06
815
761.
241
1741
0.03
20.
099
0.03
20.
047
674
553
516
476
444
227
-123
1.09
415
781.
094
1578
1.14
418
161.
317
1992
0.03
10.
089
0.02
70.
041
750
630
588
531
535
273
-124
1.21
219
761.
212
1976
1.26
222
461.
435
2425
0.03
10.
081
0.02
20.
035
839
709
630
597
646
326
-126
1.30
023
481.
300
2348
1.35
025
591.
523
2757
0.03
10.
073
0.01
90.
030
937
783
731
671
777
394
-127
1.39
527
951.
395
2795
1.44
530
131.
618
3205
0.03
00.
067
0.01
50.
026
1048
881
822
753
1111
562
-129
1.66
839
821.
668
3982
1.71
841
291.
954
4484
0.03
00.
056
0.01
10.
018
1303
1098
1025
937
Oil &
Gas
Cab
les
5
37-102
Two Conductor Power CableGexol® InsulatedExtremely Flexible • 0.6/1kV • Rated 110°C
www. amercable.com • e-mail: [email protected]
Ratings & Approvals (Other certifications pending)
� 110˚C Temperature Rating� American Bureau of Shipping (ABS)
99-BT5905-X� Transport Canada 8700-20-2� Det Norske Veritas (DNV)
E-6669, E-6388, E-6390, E-6391� Lloyd’s Register of Shipping (LRS)
91/60333 (E6)� NVE 95/1696, FAL� UL Listed as Marine Shipboard Cable
(E111461) � United States Coast Guard
November 2, 1987 / 9304� CSA listed as Marine Shipboard Cable (82346)
JacketA black, arctic grade,flame retardant, oil,abrasion, chemical and sunlight resistantthermosettingcompound meeting UL 1309/CSA 245 andIEEE 1580.
InsulationGEXOL® cross-linkedflame retardant polyolefin, meeting the requirements for Type P of IEEE 1580 and Type X110 of UL 1309/CSA 245.Color code:Black-White
ConductorSoft annealedflexible strandedtinned copper perIEEE 1580 Table 11.
Sheath (Optional)A black, arctic grade,flame retardant, oil,abrasion, chemical and sunlight resistantthermosetting compoundmeeting UL 1309/CSA 245 and IEEE 1580.
Armor (Optional)Basket weave wire armorper IEEE 1580 and UL1309/CSA 245. Bronzestandard. Tinned copperavailable by request.
ApplicationDesigned and constructed for the demandingenvironments of offshore drilling and petroleumfacilities located throughout the world.
Features� High strand count conductors make this
product much more flexible, easier to installand more resistant to vibration than Type MC,IEC spec or commercial cables.
� Gexol’s lower dielectric constant and higherinsulation resistance reduces electrical losses.
� Gexol’s excellent resistance to moistureproduces stable electrical properties throughoutthe life of the cable.
� In a fire condition, Gexol’s nonchlorinated flameretardant system produces less toxic and lesscorrosive gases.
� Dual certified IEEE 1580 Type P and UL 1309/CSA 245 Type X110.
� Highest ampacity ratings: ABS 100˚C, DNV95˚C, LRS 95˚C, Transport Canada 95˚C.
� Severe cold durability: exceeds CSA coldbend/cold impact (-40˚C/-35˚C).
� Flame retardant: IEC 332-3 Category A and IEEE 1202.
� Suitable for use in Class I, Division 1 and Zone 1 environments (armored and sheathed).
� Optional braid armor of bronze or tinned copper.
®
Oil & Gas Cables
HawkeGland Types Unarmored Armored & Sheathed
Industrial & Safe Area (IP68) 121 153-XIncreased Safety 501/421 501/453/U“EExe”Explosion Proof 710 753
Class I, Div. 2 Class I, Div. 1Class I, Zone 2 Class I, Zone 1 & 2
Flameproof 501/421 501/453/U“EExd” Zone 1 & 2 (2 liter or < enclosures)
ICG 653/U(2 liter or > enclosures)
Zone 1 & 2
6
GEXO
L®is
a re
gist
ered
trad
emar
k of
Am
erCa
ble
Inco
rpor
ated
Cab
le d
iam
eter
s sh
own
as n
omin
al a
re s
ubje
ct t
o a
±5%
man
ufac
turin
g to
lera
nce
Arm
ored
and
Unar
mor
edAr
mor
ed (B
)Sh
eath
(BS)
Size
Nom
inal
Nom
inal
Nom
inal
AC R
esis
tanc
eIn
duct
ive
Volta
ge D
rop
AWG/
Part
No.
Diam
eter
Wei
ght
Diam
eter
Wei
ght
Diam
eter
Wei
ght
DC R
esis
tanc
e at
110°
C, 6
0 Hz
Reac
tanc
e11
0°C
Ampa
city
kcm
ilm
m2
37-1
02(in
ches
)(lb
s/M
Ft.)
(inch
es)
(lbs/
MFt
.)(in
ches
)(lb
s/M
Ft.)
25°C
(Ohm
s/10
00 ft
.)(O
hms/
1000
ft.)
(Ohm
s /1
000
ft.)
(Vol
ts/A
mp/
1000
ft.)
110°
C10
0°C
95°C
161.
3-5
010.
350
750.
400
141
0.54
020
24.
610
6.12
10.
039
8.51
120
1920
142.
1-5
070.
380
840.
430
165
0.56
123
02.
907
3.85
90.
036
5.37
933
3127
123.
3-5
150.
420
111
0.47
019
00.
601
263
1.82
62.
424
0.03
43.
390
4340
3210
5.2
-553
0.46
014
60.
510
230
0.64
130
71.
153
1.53
00.
032
2.15
153
4943
87.
6-2
090.
600
221
0.65
032
70.
781
416
0.70
80.
940
0.03
41.
336
6964
586
12.5
-210
0.68
030
80.
730
424
0.90
355
90.
445
0.59
00.
032
0.85
091
8577
421
-594
0.88
751
60.
937
664
1.11
083
50.
300
0.39
90.
029
0.58
211
811
010
31/
054
-216
1.24
311
281.
293
1334
1.46
615
620.
117
0.15
60.
028
0.24
521
319
918
44/
010
9-2
191.
593
2003
1.64
322
711.
878
2680
0.05
90.
080
0.02
60.
138
329
307
285
37-1
02
Two
Cond
ucto
r Pow
er C
able
Gexo
l®In
sula
ted
Extre
mel
y Fl
exib
le •
0.6/
1kV
• Rat
ed 1
10°C
Man
ufac
ture
d by
Am
erCa
ble
Inco
rpor
ated
• 80
0-50
6-94
73 •
713-
896-
5800
• Fa
x: 7
13-8
49-9
009
1063
3 W
est L
ittle
Yor
k • B
ldg.
#1
• Sui
te #
100
• Hou
ston
, TX
7704
1 • w
ww
. am
erca
ble.
com
Flex
ible
Pow
er C
able
– T
wo
Cond
ucto
r
Orde
ring
Gexo
l Oil
& G
as C
able
sEx
ampl
e:
• 2 c
ondu
ctor
pow
er c
able
• 0.6
/1kV
• #4
AWG
• bro
nze
arm
ored
& s
heat
hed
Amer
Cabl
e Ge
xol
Oil &
Gas
Pre
fixSp
ecifi
c Ca
ble
Num
ber
(from
cha
rts)
Arm
or R
equi
rem
ent
BS –
arm
ored
&sh
eath
edBl
ank
– no
arm
or
37–1
02–
594
BS
Oil &
Gas
Cab
les
See
page
2 fo
r St
rand
ing
Prof
ile
7
37-102
Three Conductor Power CableGexol® InsulatedExtremely Flexible • 0.6/1kV • Rated 110°C
www. amercable.com • e-mail: [email protected]
Ratings & Approvals (Other certifications pending)
� 110˚C Temperature Rating� American Bureau of Shipping (ABS)
99-BT5905-X� Transport Canada 8700-20-2� Det Norske Veritas (DNV)
E-6669, E-6388, E-6390, E-6391� Lloyd’s Register of Shipping (LRS)
91/60333 (E6)� NVE 95/1696, FAL� UL Listed as Marine Shipboard Cable
(E111461) � United States Coast Guard
November 2, 1987 / 9304� CSA listed as Marine Shipboard Cable (82346)
JacketA black, arctic grade,flame retardant, oil,abrasion, chemical and sunlight resistantthermosetting compound meeting UL 1309/CSA 245 and IEEE 1580.
Sheath (Optional)A black, arctic grade,flame retardant, oil,abrasion, chemical and sunlight resistantthermosetting compoundmeeting UL 1309/CSA 245 and IEEE 1580.
ConductorSoft annealed flexiblestranded tinned copperper IEEE 1580 Table 11.
InsulationGEXOL® cross-linkedflame retardantpolyolefin, meeting the requirements for Type P of IEEE 1580and Type X110 of UL 1309/CSA 245.Color code:Black-White-Red
Armor (Optional)Basket weave wirearmor per IEEE 1580and UL 1309/CSA 245.Bronze standard.Tinned copperavailable by request.
ApplicationDesigned and constructed for the demandingenvironments of offshore drilling and petroleumfacilities located throughout the world.
Features� High strand count conductors make this
product much more flexible, easier to installand more resistant to vibration than Type MC,IEC spec or commercial cables.
� Gexol’s lower dielectric constant and higherinsulation resistance reduces electrical losses.
� Gexol’s excellent resistance to moistureproduces stable electrical properties throughoutthe life of the cable.
� In a fire condition, Gexol’s nonchlorinated flameretardant system produces less toxic and lesscorrosive gases.
� Dual certified IEEE 1580 Type P and UL 1309/CSA 245 Type X110.
� Highest ampacity ratings: ABS 100˚C, DNV95˚C, LRS 95˚C, Transport Canada 95˚C.
� Severe cold durability: exceeds CSA coldbend/cold impact (-40˚C/-35˚C).
� Flame retardant: IEC 332-3 Category A and IEEE 1202.
� Suitable for use in Class I, Division 1 and Zone 1 environments (armored and sheathed).
� Optional braid armor of bronzeor tinned copper.
An uninsulated ground conductormay be incorporated on a
make-to-order basis.
®
Oil & Gas Cables
HawkeGland Types Unarmored Armored & Sheathed
Industrial & Safe Area (IP68) 121 153-XIncreased Safety 501/421 501/453/U“EExe”Explosion Proof 710 753
Class I, Div. 2 Class I, Div. 1Class I, Zone 2 Class I, Zone 1 & 2
Flameproof 501/421 501/453/U“EExd” Zone 1 & 2 (2 liter or < enclosures)
ICG 653/U(2 liter or > enclosures)
Zone 1 & 2
8
37-1
02
Thre
e Co
nduc
tor P
ower
Cab
leGe
xol®
Insu
late
dEx
trem
ely
Flex
ible
• 0.
6/1k
V • R
ated
110
°C
Man
ufac
ture
d by
Am
erCa
ble
Inco
rpor
ated
• 80
0-50
6-94
73 •
713-
896-
5800
• Fa
x: 7
13-8
49-9
009
1063
3 W
est L
ittle
Yor
k • B
ldg.
#1
• Sui
te #
100
• Hou
ston
, TX
7704
1 • w
ww
. am
erca
ble.
com
Flex
ible
Pow
er C
able
– T
hree
Con
duct
or
Cab
le d
iam
eter
s sh
own
as n
omin
al a
re s
ubje
ct t
o a
±5%
man
ufac
turin
g to
lera
nce
GEXO
L®is
a re
gist
ered
trad
emar
k of
Am
erCa
ble
Inco
rpor
ated
Arm
ored
and
Unar
mor
edAr
mor
ed (B
)Sh
eath
(BS)
Size
Nom
inal
Nom
inal
Nom
inal
AC R
esis
tanc
eIn
duct
ive
Volta
ge D
rop
Opt.
Unin
sula
ted
AWG/
Part
No.
Diam
eter
Wei
ght
Diam
eter
Wei
ght
Diam
eter
Wei
ght
DC R
esis
tanc
e at
110°
C, 6
0 Hz
Reac
tanc
e11
0°C
Grou
ndin
g Co
nd.
Ampa
city
kcm
ilm
m2
37-1
02(in
ches
)(lb
s/M
Ft.)
(inch
es)
(lbs/
MFt
.)(in
ches
)(lb
s/M
Ft.)
25°C
(Ohm
s/10
00 ft
.)(O
hms/
1000
ft.)
(Ohm
s /1
000
ft.)
(Vol
ts/A
mp/
1000
ft.)
Size
AW
G11
0°C
100°
C95
°C16
1.3
-502
0.36
965
0.41
912
70.
519
181
4.61
06.
121
0.03
98.
511
–17
1616
142.
1-5
080.
401
102
0.45
117
60.
583
228
2.90
73.
859
0.03
65.
379
–27
2522
123.
3-5
160.
445
133
0.49
521
20.
626
276
1.82
62.
424
0.03
43.
390
–33
3127
105.
2-3
080.
488
189
0.53
828
10.
669
352
1.15
31.
530
0.03
22.
151
–44
4136
87.
6-3
090.
637
274
0.68
738
50.
818
477
0.70
80.
940
0.03
41.
336
–56
5248
612
.5-3
100.
723
390
0.77
351
90.
946
650
0.44
50.
590
0.03
20.
850
875
7064
421
-312
0.94
267
80.
992
843
1.16
510
040.
300
0.39
90.
029
0.58
28
9992
852
34-3
141.
084
987
1.13
411
601.
307
1374
0.18
40.
244
0.02
80.
366
613
112
211
31
43-3
151.
206
1234
1.25
614
581.
431
1675
0.14
70.
195
0.02
80.
299
615
314
313
11/
054
-316
1.32
614
481.
376
1781
1.55
020
150.
117
0.15
60.
028
0.24
56
176
164
152
2/0
70-3
171.
422
1945
1.47
220
821.
645
2424
0.09
30.
125
0.02
70.
200
620
118
817
53/
086
-318
1.52
823
791.
578
2720
1.81
431
060.
074
0.10
00.
027
0.16
64
234
218
202
4/0
109
-319
1.76
528
641.
815
3233
2.05
036
520.
058
0.08
00.
026
0.13
84
270
252
235
262
132
-320
1.98
034
522.
030
3880
2.26
644
340.
048
0.06
70.
026
0.11
93
315
294
267
313
159
-321
2.13
140
232.
181
4434
2.41
849
190.
040
0.05
60.
026
0.10
53
344
321
299
373
189
-322
2.23
147
722.
281
5219
2.51
757
180.
034
0.04
70.
025
0.09
23
387
361
334
444
227
-323
2.39
456
702.
444
6176
2.68
068
640.
028
0.04
10.
025
0.08
32
440
411
372
535
273
-324
2.63
767
842.
687
7492
2.98
682
500.
024
0.03
50.
026
0.07
52
498
443
418
646
326
-326
2.95
879
613.
008
8414
3.30
192
580.
020
0.03
00.
026
0.06
81
553
516
470
777
394
-327
3.16
895
733.
218
1006
53.
511
1094
50.
016
0.02
60.
026
0.06
31
602
562
529
Orde
ring
Gexo
l Oil
& G
as C
able
sEx
ampl
e:
• 3 c
ondu
ctor
pow
er c
able
• 0.6
/1kV
• bro
nze
arm
ored
& s
heat
hed
• with
gro
und
Amer
Cabl
e Ge
xol
Oil &
Gas
Pre
fixSp
ecifi
c Ca
ble
Num
ber
(from
cha
rts)
Arm
or R
equi
rem
ent
BS –
arm
ored
&sh
eath
edBl
ank
– no
arm
or
Grou
nd C
ondu
ctor
G –
with
gro
und
Blan
k –
no g
roun
d
37–1
02–
320
BSG
Oil &
Gas
Cab
les
See
page
2 fo
r St
rand
ing
Prof
ile
9
37-102
Four Conductor Power CableGexol® InsulatedExtremely Flexible • 0.6/1kV • Rated 110°C
www. amercable.com • e-mail: [email protected]
Ratings & Approvals (Other certifications pending)
� 110˚C Temperature Rating� American Bureau of Shipping (ABS)
99-BT5905-X� Transport Canada 8700-20-2� Det Norske Veritas (DNV)
E-6669, E-6388, E-6390, E-6391� Lloyd’s Register of Shipping (LRS)
91/60333 (E6)� NVE 95/1696, FAL� UL Listed as Marine Shipboard Cable
(E111461) � United States Coast Guard
November 2, 1987 / 9304� CSA listed as Marine Shipboard Cable (82346)
JacketA black, arctic grade, flame retardant, oil,abrasion, chemical andsunlight resistantthermosetting compoundmeeting UL 1309/CSA 245and IEEE 1580.
InsulationGEXOL® cross-linkedflame retardant polyolefin,meeting the requirementsfor Type P of IEEE 1580and Type X110 of UL 1309/CSA 245. Color code:Black-White-Red-Green
ConductorSoft annealed flexiblestranded tinnedcopper per IEEE 1580Table 11.
Sheath (Optional)A black, arctic grade,flame retardant, oil,abrasion, chemical and sunlight resistantthermosetting compoundmeeting UL 1309/CSA245 and IEEE 1580.
ApplicationDesigned and constructed for the demandingenvironments of offshore drilling and petroleumfacilities located throughout the world.
Features� High strand count conductors make this
product much more flexible, easier to installand more resistant to vibration than Type MC,IEC spec or commercial cables.
� Gexol’s lower dielectric constant and higherinsulation resistance reduces electrical losses.
� Gexol’s excellent resistance to moistureproduces stable electrical properties throughoutthe life of the cable.
� In a fire condition, Gexol’s nonchlorinated flameretardant system produces less toxic and lesscorrosive gases.
� Dual certified IEEE 1580 Type P and UL 1309/CSA 245 Type X110.
� Highest ampacity ratings: ABS 100˚C, DNV95˚C, LRS 95˚C, Transport Canada 95˚C.
� Severe cold durability: exceeds CSA coldbend/cold impact (-40˚C/-35˚C).
� Flame retardant: IEC 332-3 Category A and IEEE 1202.
� Suitable for use in Class I, Division 1 and Zone 1 environments (armored and sheathed).
� Optional braid armor of bronze or tinned copper.
Armor (Optional)Basket weave wire armorper IEEE 1580 and UL1309/CSA 245. Bronzestandard. Tinned copperavailable by request.
An uninsulated ground conductormay be incorporated on a
make-to-order basis.
®
Oil & Gas Cables
HawkeGland Types Unarmored Armored & Sheathed
Industrial & Safe Area (IP68) 121 153-XIncreased Safety 501/421 501/453/U“EExe”Explosion Proof 710 753
Class I, Div. 2 Class I, Div. 1Class I, Zone 2 Class I, Zone 1 & 2
Flameproof 501/421 501/453/U“EExd” Zone 1 & 2 (2 liter or < enclosures)
ICG 653/U(2 liter or > enclosures)
Zone 1 & 2
10
37-1
02
Four
Con
duct
or P
ower
Cab
leGe
xol®
Insu
late
dEx
trem
ely
Flex
ible
• 0.
6/1k
V • R
ated
110
°C
Man
ufac
ture
d by
Am
erCa
ble
Inco
rpor
ated
• 80
0-50
6-94
73 •
713-
896-
5800
• Fa
x: 7
13-8
49-9
009
1063
3 W
est L
ittle
Yor
k • B
ldg.
#1
• Sui
te #
100
• Hou
ston
, TX
7704
1 • w
ww
. am
erca
ble.
com
Flex
ible
Pow
er C
able
– F
our C
ondu
ctor
Cab
le d
iam
eter
s sh
own
as n
omin
al a
re s
ubje
ct t
o a
±5%
man
ufac
turin
g to
lera
nce
GEXO
L®is
a re
gist
ered
trad
emar
k of
Am
erCa
ble
Inco
rpor
ated
Arm
ored
and
Unar
mor
edAr
mor
ed (B
)Sh
eath
(BS)
Size
Nom
inal
Nom
inal
Nom
inal
AC R
esis
tanc
eIn
duct
ive
Volta
ge D
rop
Opt.
Unin
sula
ted
AWG/
Part
No.
Diam
eter
Wei
ght
Diam
eter
Wei
ght
Diam
eter
Wei
ght
DC R
esis
tanc
e at
110°
C, 6
0 Hz
Reac
tanc
e11
0°C
Grou
ndin
g Co
nd.
Ampa
city
kcm
ilm
m2
37-1
02(in
ches
)(lb
s/M
Ft.)
(inch
es)
(lbs/
MFt
.)(in
ches
)(lb
s/M
Ft.)
25°C
(Ohm
s/10
00 ft
.)(O
hms/
1000
ft.)
(Ohm
s /1
000
ft.)
(Vol
ts/A
mp/
1000
ft.)
Size
AW
G11
0°C
100°
C95
°C16
1.3
-529
0.40
299
0.45
215
40.
583
221
4.61
06.
121
0.04
28.
514
–17
1616
142.
1-5
090.
438
126
0.48
821
30.
619
262
2.90
73.
859
0.03
95.
382
–27
2522
123.
3-5
170.
486
168
0.53
625
60.
668
323
1.82
62.
424
0.03
73.
393
–33
3127
105.
2-4
080.
553
243
0.60
331
30.
734
390
1.15
31.
530
0.03
52.
154
–44
4136
87.
6-4
090.
698
355
0.74
846
60.
921
591
0.70
80.
940
0.03
71.
339
–56
5248
612
.5-4
100.
794
533
0.84
466
91.
017
808
0.44
50.
590
0.03
50.
853
875
7064
421
-412
1.03
587
91.
085
1062
1.25
812
360.
300
0.39
90.
032
0.58
58
9992
852
34-4
141.
194
1120
1.24
413
451.
417
1677
0.18
40.
244
0.03
00.
369
613
112
211
31
43-4
151.
332
1602
1.38
219
091.
555
2144
0.14
70.
195
0.03
10.
302
615
314
313
11/
054
-416
1.46
519
071.
515
2180
1.75
024
340.
117
0.15
60.
030
0.24
86
176
164
152
2/0
70-4
171.
573
2535
1.62
326
651.
859
3050
0.09
30.
125
0.03
00.
203
620
118
817
53/
086
-418
1.75
432
061.
804
3578
2.04
040
030.
074
0.10
00.
029
0.16
84
234
218
202
4/0
109
-419
1.96
437
652.
014
4214
2.24
946
700.
058
0.08
00.
029
0.14
04
270
252
235
262
132
-420
2.20
546
252.
255
4795
2.49
056
100.
048
0.06
70.
029
0.12
23
315
294
267
313
159
-421
2.37
453
672.
424
5868
2.65
963
950.
040
0.05
60.
028
0.10
73
344
321
299
373
189
-422
2.49
564
622.
545
6853
2.83
875
760.
034
0.04
70.
028
0.09
53
387
361
334
444
227
-423
2.65
375
602.
703
7987
3.00
287
600.
028
0.04
10.
028
0.08
62
440
411
372
535
273
-424
2.98
992
843.
039
9762
3.33
810
570
0.02
40.
035
0.02
80.
077
246
344
341
864
632
6-4
263.
277
1057
13.
327
1094
63.
620
1184
00.
020
0.03
00.
029
0.07
11
553
516
470
Orde
ring
Gexo
l Oil
& G
as C
able
sEx
ampl
e:
• 4 c
ondu
ctor
pow
er c
able
• 0.6
/1kV
• #6
AWG
• bro
nze
arm
ored
& s
heat
hed
• with
gro
und
Amer
Cabl
e Ge
xol
Oil &
Gas
Pre
fixSp
ecifi
c Ca
ble
Num
ber
(from
cha
rts)
Arm
or R
equi
rem
ent
BS –
arm
ored
&sh
eath
edBl
ank
– no
arm
or
Grou
nd C
ondu
ctor
G
– w
ith g
roun
d Bl
ank
– no
gro
und
37–1
02–
410
BSG
Oil &
Gas
Cab
les
See
page
2 fo
r St
rand
ing
Prof
ile
11
37-102
Five Conductor Power CableGexol® InsulatedExtremely Flexible • 0.6/1kV • Rated 110°C
www. amercable.com • e-mail: [email protected]
Ratings & Approvals (Other certifications pending)
� 110˚C Temperature Rating� American Bureau of Shipping (ABS)
99-BT5905-X� Transport Canada 8700-20-2� Det Norske Veritas (DNV)
E-6669, E-6388, E-6390, E-6391� Lloyd’s Register of Shipping (LRS)
91/60333 (E6)� NVE 95/1696, FAL� UL Listed as Marine Shipboard Cable
(E111461) � United States Coast Guard
November 2, 1987 / 9304� CSA listed as Marine Shipboard Cable (82346)
JacketA black, arctic grade,flame retardant, oil,abrasion, chemical and sunlight resistantthermosetting compound meeting UL 1309/CSA 245 andIEEE 1580.
InsulationGEXOL® cross-linkedflame retardant polyolefin,meeting the requirementsfor Type P of IEEE 1580and Type X110 of UL 1309/CSA 245. Color code:Black-White-Red-Green-Orange
ConductorsSoft annealed flexiblestranded tinned copperper IEEE 1580 Table 11.
Sheath (Optional)A black, arctic grade,flame retardant, oil,abrasion, chemical and sunlight resistantthermosetting compoundmeeting UL 1309/CSA245 and IEEE 1580.
Armor (Optional)Basket weave wirearmor per IEEE 1580and UL 1309/CSA 245.Bronze standard. Tinned copper available by request.
ApplicationDesigned and constructed for the demandingenvironments of offshore drilling and petroleumfacilities located throughout the world.
Features� High strand count conductors make this
product much more flexible, easier to installand more resistant to vibration than Type MC,IEC spec or commercial cables.
� Gexol’s lower dielectric constant and higherinsulation resistance reduces electrical losses.
� Gexol’s excellent resistance to moistureproduces stable electrical properties throughoutthe life of the cable.
� In a fire condition, Gexol’s nonchlorinated flameretardant system produces less toxic and lesscorrosive gases.
� Dual certified IEEE 1580 Type P and UL 1309/CSA 245 Type X110.
� Highest ampacity ratings: ABS 100˚C, DNV95˚C, LRS 95˚C, Transport Canada 95˚C.
� Severe cold durability: exceeds CSA coldbend/cold impact (-40˚C/-35˚C).
� Flame retardant: IEC 332-3 Category A and IEEE 1202.
� Suitable for use in Class I, Division 1 and Zone 1 environments (armored and sheathed).
� Optional braid armor of bronze or tinned copper.
®
Oil & Gas Cables
HawkeGland Types Unarmored Armored & Sheathed
Industrial & Safe Area (IP68) 121 153-XIncreased Safety 501/421 501/453/U“EExe”Explosion Proof 710 753
Class I, Div. 2 Class I, Div. 1Class I, Zone 2 Class I, Zone 1 & 2
Flameproof 501/421 501/453/U“EExd” Zone 1 & 2 (2 liter or < enclosures)
ICG 653/U(2 liter or > enclosures)
Zone 1 & 2
12
Arm
ored
and
Unar
mor
edAr
mor
ed (B
)Sh
eath
(BS)
Size
Nom
inal
Nom
inal
Nom
inal
AC R
esis
tanc
eIn
duct
ive
Volta
ge D
rop
AWG/
Part
No.
Diam
eter
Wei
ght
Diam
eter
Wei
ght
Diam
eter
Wei
ght
DC R
esis
tanc
e at
110°
C, 6
0 Hz
Reac
tanc
e11
0°C
Ampa
city
kcm
ilm
m2
37-1
02(in
ches
)(lb
s/M
Ft.)
(inch
es)
(lbs/
MFt
.)(in
ches
)(lb
s/M
Ft.)
25°C
(Ohm
s/10
00 ft
.)(O
hms/
1000
ft.)
(Ohm
s /1
000
ft.)
(Vol
ts/A
mp/
1000
ft.)
110°
C10
0°C
95°C
181.
0-5
580.
418
950.
468
165
0.59
921
47.
350
9.76
30.
044
13.5
5811
1011
161.
3-5
590.
437
110
0.48
718
90.
619
264
4.61
06.
121
0.04
28.
514
1413
1314
2.1
-510
0.47
914
90.
529
234
0.66
030
12.
907
3.85
90.
039
5.38
221
2018
123.
3-5
600.
550
196
0.60
026
60.
744
334
1.82
62.
424
0.03
73.
393
2725
2210
5.2
-561
0.60
429
60.
654
406
0.78
549
41.
153
1.53
00.
035
2.15
435
3329
87.
6-5
620.
765
453
0.81
556
90.
988
704
0.70
80.
940
0.03
71.
339
4542
386
12.5
-563
0.91
465
30.
964
813
1.13
797
30.
445
0.59
00.
035
0.85
360
5651
421
-565
1.13
710
731.
187
1292
1.36
014
810.
300
0.39
90.
032
0.58
579
7468
234
-566
1.31
513
611.
365
1637
1.53
818
560.
184
0.24
40.
030
0.36
910
598
901
43-5
671.
470
2130
1.52
021
921.
756
2482
0.14
70.
195
0.03
10.
302
122
114
105
1/0
54-5
681.
618
2550
1.66
827
461.
903
3108
0.11
70.
156
0.03
00.
248
140
131
122
2/0
70-5
691.
802
2954
1.85
233
012.
088
3734
0.09
30.
125
0.03
00.
203
161
150
140
4/0
109
-746
2.16
736
152.
217
3955
2.45
345
920.
058
0.08
00.
029
0.14
021
620
218
8
37-1
02
Five
Con
duct
or P
ower
Cab
leGe
xol®
Insu
late
dEx
trem
ely
Flex
ible
• 0.
6/1k
V • R
ated
110
°C
Man
ufac
ture
d by
Am
erCa
ble
Inco
rpor
ated
• 80
0-50
6-94
73 •
713-
896-
5800
• Fa
x: 7
13-8
49-9
009
1063
3 W
est L
ittle
Yor
k • B
ldg.
#1
• Sui
te #
100
• Hou
ston
, TX
7704
1 • w
ww
. am
erca
ble.
com
Flex
ible
Pow
er C
able
– F
ive
Cond
ucto
r
Cab
le d
iam
eter
s sh
own
as n
omin
al a
re s
ubje
ct t
o a
±5%
man
ufac
turin
g to
lera
nce
GEXO
L®is
a re
gist
ered
trad
emar
k of
Am
erCa
ble
Inco
rpor
ated
Orde
ring
Gexo
l Oil
& G
as C
able
sEx
ampl
e:
• 5 c
ondu
ctor
pow
er c
able
• 0.6
/1kV
• #2
AWG
• bro
nze
arm
ored
& s
heat
hed
Amer
Cabl
e Ge
xol
Oil &
Gas
Pre
fixSp
ecifi
c Ca
ble
Num
ber
(from
cha
rts)
Arm
or R
equi
rem
ent
BS –
arm
ored
&sh
eath
edBl
ank
– no
arm
or
37–1
02–
566
BS
Oil &
Gas
Cab
les
See
page
2 fo
r St
rand
ing
Prof
ile
13
37-102
Multi-Conductor Control CableGexol® InsulatedExtremely Flexible • 0.6/1kV • Rated 110°C
www. amercable.com • e-mail: [email protected]
Ratings & Approvals (Other certifications pending)
� 110˚C Temperature Rating� American Bureau of Shipping (ABS)
99-BT5905-X� Transport Canada 8700-20-2� Det Norske Veritas (DNV)
E-6669, E-6388, E-6390, E-6391� Lloyd’s Register of Shipping (LRS)
91/60333 (E6)� NVE 95/1696, FAL� UL Listed as Marine Shipboard Cable
(E111461) � United States Coast Guard
November 2, 1987 / 9304� CSA listed as Marine Shipboard Cable (82346)
InsulationGEXOL® cross-linked,flame retardant polyolefin, meeting the requirements for Type P of IEEE 1580 and Type X110 of UL 1309/CSA 245.
JacketA black, arctic grade,flame retardant, oil,abrasion, chemicaland sunlight resistantthermosettingcompound meeting UL 1309/CSA 245 and IEEE 1580. Color code:IEEE 1580 Table 22
ConductorsSoft annealed flexiblestranded tinned copperper IEEE 1580 Table 11.
Sheath (Optional)A black, arctic grade, flame retardant, oil, abrasion, chemical and sunlight resistantthermosetting compound meeting UL 1309/CSA 245 and IEEE 1580. Color code: IEEE 1580 Table 22
Armor (Optional)Basket weave wirearmor per IEEE 1580and UL 1309/CSA 245.Bronze standard.Tinned copper available by request.
ApplicationDesigned and constructed for the demandingenvironments of offshore drilling and petroleumfacilities located throughout the world.
Features� High strand count conductors make this
product much more flexible, easier to installand more resistant to vibration than Type MC,IEC spec or commercial cables.
� Gexol’s lower dielectric constant and higherinsulation resistance reduces electrical losses.
� Gexol’s excellent resistance to moistureproduces stable electrical properties throughoutthe life of the cable.
� In a fire condition, Gexol’s nonchlorinated flameretardant system produces less toxic and lesscorrosive gases.
� Dual certified IEEE 1580 Type P and UL 1309/CSA 245 Type X110.
� Highest ampacity ratings: ABS 100˚C, DNV95˚C, LRS 95˚C, Transport Canada 95˚C.
� Severe cold durability: exceeds CSA coldbend/cold impact (-40˚C/-35˚C).
� Flame retardant: IEC 332-3 Category A and IEEE 1202.
� Suitable for use in Class I, Division 1, and Zone 1 environments (armored and sheathed).
� Optional braid armor of bronze or tinned copper.
®
Oil & Gas Cables
HawkeGland Types Unarmored Armored & Sheathed
Industrial & Safe Area (IP68) 121 153-XIncreased Safety 501/421 501/453/U“EExe”Explosion Proof 710 753
Class I, Div. 2 Class I, Div. 1Class I, Zone 2 Class I, Zone 1 & 2
Flameproof 501/421 501/453/U“EExd” Zone 1 & 2 (2 liter or < enclosures)
ICG 653/U(2 liter or > enclosures)
Zone 1 & 2
37-102
Multi-Conductor Control CableGexol® InsulatedExtremely Flexible • 0.6/1kV • Rated 110°C
Manufactured by AmerCable Incorporated • 800-506-9473 • 713-896-5800 • Fax: 713-849-900914
GEXOL® is a registered trademark of AmerCable Incorporated
Armored andUnarmored Armored (B) Sheath (BS)
Nominal Nominal NominalSize Number of Part No. Diameter Weight Diameter Weight Diameter Weight AmpacityAWG Conductors 37-102 (inches) (lbs/MFt.) (inches) (lbs/MFt.) (inches) (lbs/MFt.) 110°C 100°C 95°C16 4 -529 0.402 99 0.452 154 0.583 227 17 16 1616 5 -559 0.437 110 0.487 189 0.619 264 14 13 1316 7 -505 0.475 155 0.525 255 0.656 330 12 11 1116 8 -503 0.531 164 0.581 265 0.712 340 12 11 1116 10 -504 0.631 206 0.681 366 0.812 445 9 8 1116 16 -546 0.719 299 0.769 465 0.942 602 9 8 1116 20 -687 0.794 360 0.844 560 1.017 724 9 8 1116 24 -525 0.923 462 0.973 718 1.146 809 8 7 1116 37 -526 1.048 658 1.098 819 1.271 989 6 6 816 44 -577 1.173 807 1.223 980 1.396 1175 6 6 816 60 -527 1.298 1053 1.348 1256 1.521 1496 6 6 816 91 -581 1.548 1595 1.598 1896 1.833 2181 6 6 814 4 -509 0.438 126 0.488 213 0.619 262 27 25 2214 5 -510 0.479 149 0.529 234 0.660 301 21 20 1814 6 -511 0.539 182 0.589 264 0.720 335 21 20 1814 7 -521 0.539 205 0.589 297 0.720 377 19 18 1514 10 -512 0.691 280 0.741 406 0.914 515 14 13 1514 12 -585 0.713 307 0.763 428 0.936 558 14 13 1514 14 -523 0.749 415 0.799 540 0.972 665 14 13 1514 20 -513 0.916 560 0.966 812 1.139 876 14 13 1514 24 -571 1.013 615 1.063 892 1.236 1132 12 11 1514 30 -573 1.071 780 1.121 965 1.294 1180 12 11 1314 37 -514 1.153 876 1.203 1135 1.376 1405 11 10 1314 44 -574 1.293 1087 1.343 1260 1.516 1477 10 9 1114 91 -582 1.775 2200 1.825 2465 2.060 2855 10 9 1112 4 -517 0.486 168 0.536 256 0.668 323 33 31 2712 5 -560 0.550 196 0.600 266 0.744 334 27 25 2212 6 -547 0.611 280 0.661 405 0.792 500 27 25 2212 10 -518 0.771 369 0.821 500 0.994 629 17 16 1912 20 -519 1.022 701 1.072 890 1.245 1055 17 16 1912 24 -572 1.133 861 1.183 1167 1.356 1468 15 14 1912 37 -520 1.293 1262 1.343 1467 1.516 1677 13 12 16
Cable diameters shown as nominal are subject to a ±5% manufacturing tolerance
Flexible Control Cable – Multi-Conductor
Ordering Gexol Oil & Gas CablesExample:
• Multi-Conductor control cable• 0.6/1kV• #12 AWG• bronze armored & sheathed
AmerCable Gexol Oil & Gas Prefix
Specific Cable Number(from charts)
Armor RequirementBS – armored &
sheathedBlank – no armor
37–102 – 519 BS
Oil & Gas Cables
See page 2 for Stranding Profile
15
GEXOL® is a registered trademark of AmerCable Incorporated
37-102
Shielded Pairs InstrumentationCable – Gexol® InsulatedExtremely Flexible • Individually Shielded Pairs • 0.6/1kV • Rated 110°C
www. amercable.com • e-mail: [email protected]
Ratings & Approvals (Other certifications pending)
� 110˚C Temperature Rating� American Bureau of Shipping (ABS)
99-BT5905-X� Transport Canada 8700-20-2� Det Norske Veritas (DNV)
E-6669, E-6388, E-6390, E-6391� Lloyd’s Register of Shipping (LRS)
91/60333 (E6)� NVE 95/1696, FAL� UL Listed as Marine Shipboard Cable
(E111461) � United States Coast Guard
November 2, 1987 / 9304� CSA listed as Marine Shipboard Cable (82346)
ApplicationDesigned and constructed for the demandingenvironments of offshore drilling and petroleumfacilities located throughout the world.
Features� High strand count conductors make this
product much more flexible, easier to installand more resistant to vibration than Type MC,IEC spec or commercial cables.
� Gexol’s lower dielectric constant and higherinsulation resistance reduces electrical losses.
� Gexol’s excellent resistance to moistureproduces stable electrical properties throughoutthe life of the cable.
� In a fire condition, Gexol’s nonchlorinated flameretardant system produces less toxic and lesscorrosive gases.
� Dual certified IEEE 1580 Type P and UL 1309/CSA 245 Type X110.
� Highest ampacity ratings: ABS 100˚C, DNV95˚C, LRS 95˚C, Transport Canada 95˚C.
� Severe cold durability: exceeds CSA coldbend/cold impact (-40˚C/-35˚C).
� Flame retardant: IEC 332-3 Category A and IEEE 1202.
� Suitable for use in Class I, Division 1 and Zone 1 environments (armored and sheathed).
� Optional braid armor of bronzeor tinned copper.
ConductorSoft annealed flexiblestranded tinned copperper IEEE 1580 Table 11.
Armor (Optional)Basket weave wirearmor per IEEE 1580and UL 1309/CSA245. Bronze standard.Tinned copperavailable by request.
InsulationGEXOL® cross-linkedflame retardant polyolefin,meeting the requirementsfor Type P of IEEE 1580 and Type X110 of UL 1309/CSA 245.
JacketA black, arctic grade,flame retardant, oil,abrasion, chemical andsunlight resistantthermosetting compound meeting UL 1309/CSA 245 andIEEE 1580.
PairsEach pair is twisted with a bare tinned drain wire.Each pair is shielded withpolyester-backed aluminum foil tape toafford 100% coverage.Pair to pair isolation plusoverall shield is provided.Pair color code:Black-White
Sheath (Optional)A black, arctic grade,flame retardant, oil,abrasion, chemical and sunlight resistantthermosetting compoundmeeting UL 1309/CSA 245and IEEE 1580.
Cable available with blue jacket or stripe to signify
intrinsically safe circuit.
®
Oil & Gas Cables
HawkeGland Types Unarmored Armored & Sheathed
Industrial & Safe Area (IP68) 121 153-XIncreased Safety 501/421 501/453/U“EExe”Explosion Proof 710 753
Class I, Div. 2 Class I, Div. 1Class I, Zone 2 Class I, Zone 1 & 2
Flameproof 501/421 501/453/U“EExd” Zone 1 & 2 (2 liter or < enclosures)
ICG 653/U(2 liter or > enclosures)
Zone 1 & 2
GEXOL® is a registered trademark of AmerCable Incorporated
37-102
Shielded Pairs InstrumentationCable – Gexol® InsulatedExtremely Flexible • Individually Shielded Pairs • 0.6/1kV • Rated 110°C
Manufactured by AmerCable Incorporated • 800-506-9473 • 713-896-5800 • Fax: 713-849-900916
Armored andUnarmored Armored (B) Sheath (BS)
Nominal Nominal NominalSize Number of Part No. Diameter Weight Diameter Weight Diameter WeightAWG Pairs 37-102 (inches) (lbs/MFt.) (inches) (lbs/MFt.) (inches) (lbs/MFt.)18 1 -601 0.336 63 0.386 123 0.486 17618 2 -602 0.551 131 0.601 204 0.732 33518 3 -603 0.581 163 0.631 265 0.762 34318 4 -604 0.630 195 0.680 317 0.801 41018 5 -605 0.685 243 0.735 395 0.900 51118 7 -606 0.742 340 0.792 457 0.957 57518 8 -607 0.800 388 0.850 521 1.015 75218 10 -608 0.976 495 1.026 699 1.199 87418 12 -609 1.011 581 1.061 780 1.234 98218 16 -645 1.121 748 1.171 833 1.344 118218 18 -641 1.181 824 1.231 1050 1.404 130018 24 -646 1.382 1069 1.432 1151 1.605 172016 1 -610 0.356 77 0.406 120 0.507 20316 2 -611 0.565 160 0.615 249 0.751 37716 3 -612 0.617 200 0.667 311 0.785 41016 4 -613 0.671 239 0.721 389 0.886 56916 5 -614 0.730 297 0.780 483 0.945 60916 7 -615 0.792 416 0.842 559 1.007 70316 8 -616 0.896 475 0.946 638 1.119 80316 10 -617 1.047 606 1.097 787 1.270 109816 12 -618 1.081 711 1.131 923 1.304 113816 16 -619 1.207 948 1.257 1231 1.422 151716 18 -626 1.265 1100 1.315 1260 1.488 157016 20 -688 1.327 1215 1.377 1476 1.552 189416 24 -699 1.482 1510 1.532 1625 1.767 206514 1 -620 0.386 97 0.436 151 0.537 19914 2 -621 0.621 202 0.671 315 0.802 48114 3 -622 0.658 251 0.708 391 0.881 51514 4 -623 0.721 301 0.771 469 0.944 63314 5 -624 0.791 374 0.841 608 1.013 78714 7 -625 0.905 524 0.955 704 1.128 88614 8 -630 0.979 498 1.029 803 1.202 101114 10 -627 1.148 747 1.198 1003 1.371 119614 12 -628 1.186 896 1.236 1203 1.409 1434
Cable diameters shown as nominal are subject to a ±5% manufacturing tolerance
Flexible Instrumentation Cable – Individually Shielded Pairs
Ordering Gexol Oil & Gas CablesExample:
• Instrumentation cable• 0.6/1kV• #14 AWG• bronze armored & sheathed
AmerCable Gexol Oil & Gas Prefix
Specific Cable Number(from charts)
Armor RequirementBS – armored &
sheathedBlank – no armor
37–102 – 620 BS
VALUES:
#18 PairsCapacitance (nF/1000 feet) = 28Inductance (mH/1000) = 0.22Resistance (Ohms/1000 feet) = 7.21 (@ 20°C)
#16 PairsCapacitance (nF/1000 feet) = 32Inductance (mH/1000) = 0.20Resistance (Ohms/1000 feet) = 4.52 (@ 20°C)
#14 PairsCapacitance (nF/1000 feet) = 37Inductance (mH/1000) = 0.19Resistance (Ohms/1000 feet) = 2.85 (@ 20°C)
See page 2 for Stranding
Profile
Oil & Gas Cables
17
37-102
Shielded Triads InstrumentationCable – Gexol® InsulatedExtremely Flexible • Individually Shielded Triads • 0.6/1kV • Rated 110°C
www. amercable.com • e-mail: [email protected]
Ratings & Approvals (Other certifications pending)
� 110˚C Temperature Rating� American Bureau of Shipping (ABS)
99-BT5905-X� Transport Canada 8700-20-2� Det Norske Veritas (DNV)
E-6669, E-6388, E-6390, E-6391� Lloyd’s Register of Shipping (LRS)
91/60333 (E6)� NVE 95/1696, FAL� UL Listed as Marine Shipboard Cable
(E111461) � United States Coast Guard
November 2, 1987 / 9304� CSA listed as Marine Shipboard Cable (82346)
ApplicationDesigned and constructed for the demandingenvironments of offshore drilling and petroleumfacilities located throughout the world.
Features� High strand count conductors make this
product much more flexible, easier to installand more resistant to vibration than Type MC,IEC spec or commercial cables.
� Gexol’s lower dielectric constant and higherinsulation resistance reduces electrical losses.
� Gexol’s excellent resistance to moistureproduces stable electrical properties throughoutthe life of the cable.
� In a fire condition, Gexol’s nonchlorinated flameretardant system produces less toxic and lesscorrosive gases.
� Dual certified IEEE 1580 Type P and UL 1309/CSA 245 Type X110.
� Highest ampacity ratings: ABS 100˚C, DNV95˚C, LRS 95˚C, Transport Canada 95˚C.
� Severe cold durability: exceeds CSA coldbend/cold impact (-40˚C/-35˚C).
� Flame retardant: IEC 332-3 Category A and IEEE 1202.
� Suitable for use in Class I, Division 1, and Zone 1 environments (armored and sheathed).
� Optional braid armor of bronzeor tinned copper.
ConductorSoft annealed flexiblestranded tinned copperper IEEE 1580 Table 11.
Armor (Optional)Basket weave wirearmor per IEEE 1580and UL 1309/CSA245. Bronze standard.Tinned copperavailable by request.
InsulationGEXOL® cross-linked, flame retardant polyolefin,meeting the requirementsfor Type P of IEEE 1580and Type X110 of UL 1309/CSA 245.
JacketA black, arctic grade,flame retardant, oil,abrasion, chemical andsunlight resistantthermosettingcompound meeting UL 1309/CSA 245 andIEEE 1580.
TriadsEach triad is twisted witha bare tinned drain wire.Each triad is shieldedwith polyester-backed aluminum foil tape toafford 100% coverage.Triad to triad isolationplus overall shieldingis provided.Triad color code:Black-White-Red
Sheath (Optional)A black, arctic grade,flame retardant, oil,abrasion, chemical and sunlight resistantthermosetting compound meeting UL 1309/CSA 245 and IEEE 1580. Cable available with
blue jacket or stripe to signify intrinsically safe circuit.
®
Oil & Gas Cables
HawkeGland Types Unarmored Armored & Sheathed
Industrial & Safe Area (IP68) 121 153-XIncreased Safety 501/421 501/453/U“EExe”Explosion Proof 710 753
Class I, Div. 2 Class I, Div. 1Class I, Zone 2 Class I, Zone 1 & 2
Flameproof 501/421 501/453/U“EExd” Zone 1 & 2 (2 liter or < enclosures)
ICG 653/U(2 liter or > enclosures)
Zone 1 & 2
37-102
Shielded Triads InstrumentationCable – Gexol® InsulatedExtremely Flexible • Individually Shielded Triads • 0.6/1kV • Rated 110°C
Manufactured by AmerCable Incorporated • 800-506-9473 • 713-896-5800 • Fax: 713-849-900918
GEXOL® is a registered trademark of AmerCable Incorporated
#18 Triads
Capacitance – (nF/1000 feet) = 28
Inductance – (mH/1000) = 0.22
Resistance – (Ohms/1000 feet) = 7.21 (@ 20°C)
#16 TriadsCapacitance – (nF/1000 feet) = 32
Inductance – (mH/1000) = 0.20
Resistance – (Ohms/1000 feet) = 4.52 (@ 20°C)
VALUES:
Armored andUnarmored Armored (B) Sheath (BS)
Nominal Nominal NominalSize Number of Part No. Diameter Weight Diameter Weight Diameter WeightAWG Triads 37-102 (inches) (lbs/MFt.) (inches) (lbs/MFt.) (inches) (lbs/MFt.)18 1 -647 0.354 75 0.404 144 0.504 19918 2 -681 0.649 183 0.699 290 0.872 38018 3 -648 0.688 190 0.738 305 0.911 39318 4 -682 0.755 281 0.805 408 0.978 55118 5 -649 0.871 286 0.921 419 1.094 56118 7 -650 0.947 409 0.997 565 1.170 72418 8 -683 1.026 515 1.076 680 1.249 87018 12 -640 1.244 766 1.294 965 1.467 119516 1 -668 0.376 86 0.426 155 0.558 21316 3 -669 0.735 218 0.785 338 0.958 46616 4 -698 0.807 410 0.857 530 1.030 70016 6 -676 1.012 630 1.062 750 1.235 95516 7 -670 1.012 710 1.062 835 1.235 105016 8 -677 1.090 729 1.140 876 1.330 1103
Cable diameters shown as nominal are subject to a ±5% manufacturing tolerance
Flexible Instrumentation Cable – Individually Shielded Triads
Ordering Gexol Oil & Gas CablesExample:
• Instrumentation cable• 0.6/1kV • #18 AWG• bronze armored & sheathed
AmerCable Gexol Oil & Gas Prefix
Specific Cable Number(from charts)
Armor RequirementBS – armored &
sheathedBlank – no armor
37–102 – 682 BS
Oil & Gas Cables
See page 2 for Stranding Profile
Termination KitsAmerCable Systems offers pre-sized and pre-formed termination kit packages specificallyfor VFD cable constructions
37-102VFD
Type VFD Power CableGexol® InsulatedThree Conductor • 2kV • Rated 110°C
www. amercable.com • e-mail: [email protected] 19
ApplicationA flexible, braid and foil shielded, 2kV powercable specifically engineered for use in variablefrequency AC motor drive (VFD) applications.
Features� Specially engineered cable design produces
a longer cable life in VFD applications.� Overall braid and foil shield provides 100%
coverage containing VFD EMI emissions.� Symmetrical insulated ground conductors
reduce induced voltage imbalances and carry common mode noise back to the drive.
� High strand count conductors and braid shield design is much more flexible, easier to install and more resistant to vibration than Type MC cable.
� Gexol’s lower dielectric constant (standardXLPEs, EPRs and other Type P insulationmaterials have higher dielectric constants)reduces reflected wave peak voltage magnitudes. This allows for longer output cable distances and minimizes the effect of high frequency noise induced into the plant ground system.
� 2kV insulation thickness resists the repetitive 2x voltage spikes from 600V VFDs and reduces drive over current trip problems due to cable charging current.
� Dual certified IEEE 1580 Type P and UL 1309/CSA 245 Type X110.
� Highest ampacity ratings: ABS 100˚C, DNV95˚C, LRS 95˚C, Transport Canada 95˚C.
� Severe cold durability: exceeds CSA coldbend/cold impact (-40˚C/-35˚C).
� Flame retardant: IEC 332-3 Category A and IEEE 1202.
� Suitable for use in Class I, Division 1 and Zone 1 environments (armored and sheathed).
� Optional braid armor of bronze or tinned copper.
Insulation (2kV)Gexol® cross-linked flameretardant polyolefin, meeting the requirements for Type P of IEEE 1580 and Type X110 of UL 1309/CSA 245. Color: Gray with
printed phase I.D.(Black-White-Red)
JacketA black, arctic grade, flameretardant, oil, abrasion,chemical and sunlight resistant thermosetting compound meeting UL1309/CSA 245 and IEEE 1580.
Power Conductors (x3)Soft annealed flexiblestranded tinned copperper IEEE 1580 Table 11.
Ground Conductors (x3)Soft annealed flexible stranded tinned copper per IEEE 1580 Table 11.Gexol® insulation sized per UL 1277.Color: Green
Armor (Optional)Basket weave wirearmor per IEEE 1580and UL 1309/CSA 245.Bronze standard. Tinned copper available by request.
ShieldOverall tinned copperbraid plus aluminum/polyester tape providing100% coverage.
Sheath (Optional)A black, arctic grade, flame retardant, oil, abrasion, chemical and sunlight resistant thermosetting compound meeting UL 1309/CSA 245 and IEEE 1580.
Ratings & Approvals (Other certifications pending)
� 110˚C Temperature Rating� American Bureau of Shipping (ABS): 99-BT5905-X� Transport Canada: 8700-20-2� Det Norske Veritas (DNV): E-6669, E-6388, E-6390,
E-6391� Lloyd’s Register of Shipping (LRS): 91/60333 (E6)� NVE: 95/1696, FAL� UL Listed as Marine Shipboard Cable: (E111461)� UL Listed as Type TC (E123629) available by request� United States Coast Guard: November 2, 1987 / 9304� CSA listed as Marine Shipboard Cable (82346)
Gexol insulation has lowcapacitance for superior
performance in VFD
®
Oil & Gas Cables
37-102VFD
Type VFD Power CableGexol® InsulatedThree Conductor • 2kV • Rated 110°C
Manufactured by AmerCable Incorporated • 800-506-9473 • 713-896-5800 • Fax: 713-849-900920
GEXOL® is a registered trademark of AmerCable Incorporated
SSiizzee NNoommiinnaall WWeeiigghhtt NNoommiinnaall WWeeiigghhtt NNoommiinnaall WWeeiigghhttAAWWGG// PPaarrtt NNoo.. DDiiaammeetteerr PPeerr PPaarrtt NNoo.. DDiiaammeetteerr PPeerr PPaarrtt NNoo.. DDiiaammeetteerr PPeerrkkccmmiill 3377--110022 IInncchheess** 11000000 FFtt.. 3377--110022 IInncchheess** 11000000 FFtt.. 3377--110022 IInncchheess** 11000000 FFtt.. SSiizzee ((AAWWGG)) 111100˚̊CC 110000˚̊CC 9955˚̊CC 9900˚̊CC 7755˚̊CC
14 -508VFD 0.540 194 -508BVFD 0.590 281 -508BSVFD 0.725 356 18 27 25 22 - 18
12 -516VFD 0.590 224 -516BVFD 0.646 321 -516BSVFD 0.772 401 18 33 31 27 - 24
10 -308VFD 0.633 308 -308BVFD 0.694 412 -308BSVFD 0.820 497 14 44 41 36 - 33
8 -309VFD 0.764 441 -309BVFD 0.820 565 -309BSVFD 0.988 702 14 56 52 48 - 43
6 -310VFD 0.865 570 -310BVFD 0.925 708 -310BSVFD 1.090 865 12 75 70 64 93 58
4 -312VFD 1.072 886 -312BVFD 1.125 1061 -312BSVFD 1.295 1243 12 99 92 85 122 79
2 -314VFD 1.215 1421 -314BVFD 1.271 1618 -314BSVFD 1.440 1822 10 131 122 113 159 105
1 -315VFD 1.340 1517 -315BVFD 1.395 1743 -315BSVFD 1.560 1966 10 153 143 131 184 121
1/0 -316VFD 1.443 1803 -316BVFD 1.493 2027 -316BSVFD 1.666 2327 10 176 164 152 211 145
2/0 -317VFD 1.572 2153 -317BVFD 1.622 2399 -317BSVFD 1.854 2840 10 201 188 175 243 166
4/0 -319VFD 2.053 3463 -319BVFD 2.103 3785 -319BSVFD 2.335 4347 8 270 252 235 321 223
262 -320VFD 2.193 4175 -320BVFD 2.243 4522 -320BSVFD 2.475 5120 6 315 294 267 365 254
313 -321VFD 2.370 4727 -321BVFD 2.420 5104 -321BSVFD 2.652 5747 6 344 321 299 408 287
373 -322VFD 2.501 5415 -322BVFD 2.551 5809 -322BSVFD 2.845 6674 6 387 361 334 451 315
444 -323VFD 2.670 6707 -323BVFD 2.721 7141 -323BSVFD 3.014 8059 6 440 411 372 499 350
535 -324VFD 2.972 7483 -324BVFD 3.022 7966 -324BSVFD 3.316 8981 6 498 443 418 - 390
646 -326VFD 3.164 8916 -326BVFD 3.214 9428 -326BSVFD 3.508 10504 4 553 516 470 - 431
777 -327VFD 3.388 10395 -327BVFD 3.438 10940 -327BSVFD 3.732 12088 4 602 562 529 473
*Cable diameters are subject to a +/- 5% manufacturing tolerance
GGrreeeenn IInnssuullaatteeddGGrroouunnddiinngg
CCoonndduuccttoorr ((xx33))
andhas a
low capacitance for superior performance in
VFD applications!
Gexolis
flexible
110°C RatingsBased on IEEE Std. 45 with a 45°C ambient and arranged in a single bank per hanger. For thoseinstances where cable must be double banked, the 110°C ampacities should be multiplied by 0.8.
100°C Ratings Based on IEEE Std. 45 with a 45°C ambient and arranged in a single bank per hanger. For thoseinstances where cable must be double banked, the 100°C ampacities should be multiplied by 0.8.
95°C Ratings Based on 4-3-4/Table 10 of the 2001 ABS MODU rules and a 45°C ambient.
90°C Ratings Based on ICEA S-75-381 Table H-1 for a single isolated cable in air with a 40°C ambient. Thisampacity is typically used for mining and other portable applications.
75°C Ratings Based on Table B.310.1 of the 2005 NEC for cables in raceway and a 30°C ambient.
VFD Cable Ampacity Ratings
Unarmored ArmoredArmored &
Sheathed (BS)
Ampacity
Oil & Gas Cables
See page 2 for Stranding Profile
37-105
Type MMV Medium Power CableSingle Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°CMulti-Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°C
www. amercable.com • e-mail: [email protected]
ApplicationsAmerCable’s Type MMV marine mediumvoltage cables are for use aboard commercial ships, mobile offshoredrilling units (MODUs), and fixed orfloating offshore facilities.
Features� These cables utilize flexible
stranded conductors, braided shieldsand a braided armor (when armored)which make them very suitable forapplications involving repeated flexingand high vibration.
� These cables have a small minimumbending radius (6xOD for unarmoredcables and 8xOD for armored cables) for easy installation.
� Optional uninsulated groundingconductors sized per UL 1072.
� The increased flexibility of this cableallows for termination of one end and coiling on multiple module offshore platforms. Then coiling andterminating other end when modulesare mated at sea thereby reducinginstallation time.
� Passes IEC 332-3 Category A and IEEE 1202 flame tests.
Conductor ShieldA combination of semi-conducting tape andextruded thermosetting semi-conductingmaterial meeting UL 1309, IEEE 1580, ICEA S-68-516 and UL1072.
Armor (optional)(Optional) 0.0126" bronze braid providing 88%minimum coverage meeting UL 1309 and IEEE Std. 45-1998.
JacketA black, arctic grade, flame retardant, oil, abrasion,chemical and sunlight resistant thermosetting compound meeting UL 1309, IEEE 1580, ICEA S-68-516 and UL 1072. Colored jackets for signifyingdifferent voltage levels are also available on specialrequest (ie. yellow = 5kV, orange = 8kV and red = 15kV).
Sheath (optional)A black, arctic grade, flame retardant, oil, abrasion,chemical, and sunlight resistant thermosetting compound meeting UL 1309, IEEE 1580, ICEA S-68-516 and UL 1072. Colored jackets forsignifying different voltage levels is also availableon special request (ie. yellow = 5kV, orange = 8kv and red = 15kV).
Metallic ShieldComposite shieldconsisting of 0.0126"tinned copper braided with nylonproviding 60% copper Shieldedcoverage meetingUL 1309, IEEE Std.1580, ICEA S-68-516 and UL 1072.The nylon is coloredfor easy phase identification (threeconductor = black,blue, red) withoutthe need to removethe shield to find anunderlying coloredtape.
Insulation ShieldSemi-conducting tape, with overlap, for fastand easy termination meeting UL 1309, IEEE 1580, ICEA S-68-516 and UL 1072.
ConductorsSoft annealed flexiblestranded tinned copperper IEEE 1580 Table 11.
InsulationExtruded thermosetting90°C Ethylene PropyleneRubber (EPR), meetingUL 1309 (Type E), IEEE 1580 (Type E),ICEA S-68-516 and UL 1072.
Grounding Conductor (optional)One uninsulated soft annealed flexible strandedtinned copper conductor per ASTM B 33 andsized according to Table 21.1 of UL 1072.
Ratings & Approvals� UL Listed as Marine Shipboard Cable (E111461)� American Bureau of Shipping (ABS)� Det Norske Veritas (DNV) Pending� Lloyd’s Register of Shipping (LRS) Pending� 90˚C Temperature Rating� Voltage Rating – 5kV to 15kV
(25kV available on request)
Termination KitsAmerCable recommendsRaychem’s HVT seriesterminations for single conductorconstructions and HVT-M seriesterminations for multi-conductorconstructions.
®
Oil & Gas Cables
21
HawkeGland Types Unarmored Armored & Sheathed
Industrial & Safe Area (IP68) 121 153-XIncreased Safety 501/421 501/453/U“EExe”Explosion Proof 710 753
Class I, Div. 2 Class I, Div. 1Class I, Zone 2 Class I, Zone 1 & 2
Flameproof 501/421 501/453/U“EExd” Zone 1 & 2 (2 liter or < enclosures)
ICG 653/U(2 liter or > enclosures)
Zone 1 & 2
37-105
Type MMV Medium Voltage CableSingle Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°CMulti-Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°C
Inductive Voltage Inductive Voltage Single DC ACSize Part Nominal Weight Reactance Drop Nominal Weight Reactance Drop In Free Triangular Banked Resistance Resistance
AWG/ No. Diameter (Lbs./ (ohms/ (Volts/amp/ Diameter (Lbs./ (ohms/ (Volts/amp/ Air Configuration in Tray at 25°C at 90°C, 60 Hzkcmil mm2 37-105 (inches) 1000 ft.) 1000 ft.) 1000 ft.) (inches) 1000 ft.) 1000 ft.) 1000 ft.) (amps) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.)
86421
1/02/03/04/0
262313373444535646777
1111
7.612.5
213443547086
109132159189227273326394562
-101-102-103-104-105-106-107-108-109-110-111-112-113-114-115-116-117
0.5640.6040.6860.7500.7900.8770.9370.9801.0421.1211.1871.2521.3271.4081.4961.5991.883
204252344449528659787910
108612721467169219682294267231544414
1.2820.8220.5660.3610.2960.2450.2020.2780.1410.1220.1080.0950.0860.0770.0700.0650.054
0.0540.0500.0440.0410.0400.0390.0380.0370.0350.0340.0330.0320.0320.0310.0300.0300.029
0.7510.8360.9180.9811.0641.1081.1681.2121.2741.3531.4191.4841.5591.7061.7931.8812.169
401502622748894
100411601298149617081926217424762949336138595255
0.0610.0580.0510.0470.0470.0450.0430.0420.0400.0380.0370.0360.0350.0350.0340.0330.033
1.2880.8300.5730.3670.3030.2500.2070.1730.1460.1270.1120.0990.0900.0820.0750.0690.057
80107141186214247285328381435486544606682767865
1084
6992
121159184212244281325371413460510570635709853
6891
120158182210242279324370413462515580652735921
0.6940.4360.2860.1750.1400.1110.0890.0700.0560.0460.0380.0320.0270.0220.0190.0150.011
0.8850.5560.3760.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.0330.0280.0250.017
Unarmored
Single Conductor Type MMV Marine Medium Voltage – 5kV, 100/133% Insulation LevelArmored &
Sheathed (BS) Ampacity
Inductive Voltage Inductive Voltage Single DC ACSize Part Nominal Weight Reactance Drop Nominal Weight Reactance Drop In Free Triangular Banked Resistance Resistance
AWG/ No. Diameter (Lbs./ (ohms/ (Volts/amp/ Diameter (Lbs./ (ohms/ (Volts/amp/ Air Configuration in Tray at 25°C at 90°C, 60 Hzkcmil mm2 37-105 (inches) 1000 ft.) 1000 ft.) 1000 ft.) (inches) 1000 ft.) 1000 ft.) 1000 ft.) (amps) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.)
6421
1/02/03/04/0
262313373444535646777
1111
12.5213443547086
109132159189227273326394562
-118-119-120-121-122-123-124-125-126-127-128-129-130-131-132-133
0.6560.7380.8010.8840.9290.9891.0321.0941.1731.2391.3041.3791.4601.5481.6511.935
283378486604702835956
113513241522175020292359274131864498
0.8240.5670.3620.2980.2460.2030.1690.1420.1230.1090.0960.0870.0780.0710.0660.055
0.0520.0460.0430.0420.0410.0390.0380.0360.0350.0340.0330.0330.0320.0310.0300.030
0.8880.9701.0331.1081.1601.2201.2641.3261.4051.4711.5361.6031.7461.8331.9492.233
549673806942
107212261363156317791999225025383012342839445388
0.0590.0520.0480.0470.0460.0440.0430.0410.0390.0380.0370.0360.0360.0350.0340.033
0.8310.5740.3680.3040.2510.2080.1740.1470.1280.1130.1000.0910.0820.0750.0700.058
107141186214247285328381435486544606682767865
1084
92121159184212244281325371413460510570635709853
91120158182210242279324370413462515580652735921
0.4360.2860.1750.1400.1110.0890.0700.0560.0460.0380.0320.0270.0220.0190.0150.011
0.5560.3760.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.0330.0280.0250.017
Unarmored
Single Conductor Type MMV Marine Medium Voltage – 8kV, 100% Insulation LevelArmored &
Sheathed (BS) Ampacity
®
Oil & Gas Cables
22 Manufactured by AmerCable Incorporated • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
See page 29 for MMV
Stranding Profile
www. amercable.com • e-mail: [email protected] 23
Inductive Voltage Inductive Voltage Single DC ACSize Part Nominal Weight Reactance Drop Nominal Weight Reactance Drop In Free Triangular Banked Resistance Resistance
AWG/ No. Diameter (Lbs./ (ohms/ (Volts/amp/ Diameter (Lbs./ (ohms/ (Volts/amp/ Air Configuration in Tray at 25°C at 90°C, 60 Hzkcmil mm2 37-105 (inches) 1000 ft.) 1000 ft.) 1000 ft.) (inches) 1000 ft.) 1000 ft.) 1000 ft.) (amps) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.)
6421
1/02/03/04/0
262313373444535646777
1111
12.5213443547086
109132159189227273326394562
-134-135-136-137-138-139-140-141-142-143-144-145-146-147-148-149
0.7100.7920.8980.9380.9831.0431.0861.1481.2271.2931.3581.4331.4601.6021.7671.989
317417565648751884
1007118913811584181320952359281433764587
0.8260.5690.3650.3000.2470.2040.1710.1430.1240.1100.0970.0880.0780.0720.0670.055
0.0540.0470.0450.0440.0420.0400.0390.0380.0360.0350.0340.0330.0320.0320.0320.031
0.9421.0161.1291.1701.2141.2741.3181.3801.4591.5241.5821.7191.7581.8882.0652.275
603725916
1022114012931432163518542081231827343034352941815470
0.0600.0530.0500.0490.0470.0450.0440.0420.0400.0390.0380.0380.0360.0360.0360.034
0.8320.5750.3700.3050.2520.2090.1750.1480.1290.1140.1010.0930.0830.0760.0710.058
107141186214247285328381435486544606682767865
1084
92121159184212244281325371413460510570635709853
91120158182210242279324370413462515580652735921
0.4360.2860.1750.1400.1110.0890.0700.0560.0460.0380.0320.0270.0220.0190.0150.011
0.5560.3760.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.0330.0280.0250.017
Unarmored
Single Conductor Type MMV Marine Medium Voltage – 8kV, 133% Insulation LevelArmored &
Sheathed (BS) Ampacity
Inductive Voltage Inductive Voltage Single DC ACSize Part Nominal Weight Reactance Drop Nominal Weight Reactance Drop In Free Triangular Banked Resistance Resistance
AWG/ No. Diameter (Lbs./ (ohms/ (Volts/amp/ Diameter (Lbs./ (ohms/ (Volts/amp/ Air Configuration in Tray at 25°C at 90°C, 60 Hzkcmil mm2 37-105 (inches) 1000 ft.) 1000 ft.) 1000 ft.) (inches) 1000 ft.) 1000 ft.) 1000 ft.) (amps) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.)
21
1/02/03/04/0
262313373444535646777
1111
3443547086
109132159189227273326394562
-150-151-152-153-154-155-156-157-158-159-160-161-162-163
1.0501.0881.1331.1911.2361.2981.3971.4631.5281.6031.7421.8301.9652.187
692778883
10241154134315681778201523132762316537294930
0.3690.3030.2510.2080.1740.1460.1280.1130.1000.0910.0820.0750.0700.057
0.0490.0470.0450.0440.0420.0400.0390.0380.0370.0360.0360.0350.0340.033
1.2691.3081.3521.4101.4561.5181.6161.7441.8091.8842.0242.1122.2462.468
10881186130114621608181720772422268530143520396045785870
0.0530.0510.0490.0470.0460.0440.0420.0420.0410.0400.0390.0380.0370.036
0.3730.3080.2550.2120.1780.1500.1310.1170.1040.0950.0860.0790.0730.060
186214247284327378431481536598672754848
1061
164189217250288332377418464514574638709857
158182210241278321366409456508571641721902
0.1750.1400.1110.0890.0700.0560.0460.0380.0320.0270.0220.0190.0150.011
0.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.0330.0280.0250.017
Unarmored
Single Conductor Type MMV Marine Medium Voltage – 15kV, 100% Insulation LevelArmored &
Sheathed (BS) Ampacity
Ordering Type MMV Medium Voltage CablesExample:
• 3 conductor power cable• 8kV 100%• #2 AWG• ground• bronze armored & sheathed
AmerCable TypeMMV Prefix
Specific Cable Number(from charts)
Armor RequirementBS – armored &
sheathedBlank – no armor
Ground ConductorG – with groundBlank – no ground
37–105 – 319 BS G
37-105
Type MMV Medium Voltage CableSingle Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°CMulti-Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°C
®
Oil & Gas Cables
See page 29 for MMV
Stranding Profile
37-105
Type MMV Medium Voltage CableSingle Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°CMulti-Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°C
Inductive Voltage Inductive Voltage Single DC ACSize Part Nominal Weight Reactance Drop Nominal Weight Reactance Drop In Free Triangular Banked Resistance Resistance
AWG/ No. Diameter (Lbs./ (ohms/ (Volts/amp/ Diameter (Lbs./ (ohms/ (Volts/amp/ Air Configuration in Tray at 25°C at 90°C, 60 Hzkcmil mm2 37-105 (inches) 1000 ft.) 1000 ft.) 1000 ft.) (inches) 1000 ft.) 1000 ft.) 1000 ft.) (amps) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.)
21
1/02/03/04/0
262313373444535646777
1111
3443547086
109132159189227273326394562
-164-165-166-167-168-169-170-171-172-173-174-175-176-177
1.1321.1701.2151.2731.3381.4001.4791.5451.6101.7471.8241.9442.0472.269
771863970
11121267146116701884213225412889335038705083
0.3700.3050.2520.2090.1760.1480.1290.1140.1010.0930.0840.0770.0710.058
0.0500.0490.0470.0450.0440.0420.0400.0390.0380.0380.0370.0360.0350.034
1.3521.3901.4341.4921.5581.6201.7611.8271.8922.0292.1062.2262.3292.551
11941299141615781756197123202561283633013680419147536057
0.0550.0530.0510.0490.0470.0460.0440.0430.0420.0410.0400.0390.0380.036
0.3750.3090.2560.2130.1790.1510.1330.1180.1050.0960.0870.0800.0740.061
186214247284327378431481536598672754848
1061
164189217250288332377418464514574638709857
158182210241278321366409456508571641721902
0.1750.1400.1110.0890.0700.0560.0460.0380.0320.0270.0220.0190.0150.011
0.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.0330.0280.0250.017
Unarmored
Single Conductor Type MMV Marine Medium Voltage – 15kV, 133% Insulation LevelArmored &
Sheathed (BS) Ampacity
Single InductiveSize Nominal Weight Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Voltage Drop Optional
AWG/ Part No. Diameter (Lbs./ Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (ohms/ (Volts per amp Groundingkcmil mm2 37-105 (inches) 1000 ft.) (inches) 1000 ft.) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) per 1000 ft.) Conductor
86421
1/02/03/04/0
262313373444535646777
7.612.5
213443547086
109132159189227273326394
-301-302-303-304-305-306-307-308-309-310-311-312-313-314-315-316
1.1371.2261.4021.5381.6261.7831.9132.0072.1402.3102.4532.5892.8182.9743.1643.385
781955
1307169019742423288433153937461953196107728084639814
11526
12181424182423722692323237494220489956546549740286849964
1140713226
1.3691.4571.6251.8241.9112.0812.2102.3052.4382.6082.7963.0003.1613.3173.5073.729
6688
116152175201232266306348386429455528584647
567599
129149171197226260296328365387449496550
0.7080.4450.3000.1840.1470.1170.0930.0740.0580.0480.0400.0340.0280.0240.0200.016
0.8850.5560.3760.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.0330.0280.025
0.0480.0440.0390.0360.0350.0340.0330.0320.0310.0300.0290.0290.0280.0280.0270.027
1.2750.8150.5600.3560.2910.2390.1960.1630.1360.1180.1040.0920.0830.0740.0670.062
866644433322111
1/0
Unarmored
Three Conductor Type MMV Marine Medium Voltage – 5kV, 100/133% Insulation LevelArmored &
Sheathed (BS) Ampacity
Manufactured by AmerCable Incorporated • 800-506-9473 • 713-896-5800 • Fax: 713-849-900924
®
Oil & Gas Cables
See page 29 for MMV
Stranding Profile
v2.08.1
www. amercable.com • e-mail: [email protected] 25
Single InductiveSize Nominal Weight Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Voltage Drop Optional
AWG/ Part No. Diameter (Lbs./ Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (ohms/ (Volts per amp Groundingkcmil mm2 37-105 (inches) 1000 ft.) (inches) 1000 ft.) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) per 1000 ft.) Conductor
6421
1/02/03/04/0
262313373444535646
12.5213443547086
109132159189227273326
-332-333-334-335-336-337-338-339-340-341-342-343-344-345
1.4541.6301.8291.9162.0122.1412.2362.3692.5392.6802.8853.0363.2103.400
1249163921622467283833273763441751335870688479599167
10554
189623592964330637174259473454436422722783409491
1078212261
1.7401.9162.1142.2022.2972.4272.5212.6542.8883.0313.2353.3803.5523.742
88116152175201232266306348386429455528584
7599
129149171197226260296328365387449496
0.4450.3000.1840.1470.1170.0930.0740.0580.0480.0400.0340.0280.0240.020
0.5560.3760.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.0330.028
0.0480.0430.0400.0380.0370.0360.0350.0330.0320.0320.0310.0300.0300.029
0.8200.5640.3590.2940.2420.1990.1660.1390.1210.1060.0940.0850.0760.069
66644433322111
Unarmored
Three Conductor Type MMV Marine Medium Voltage – 8kV, 133% Insulation LevelArmored &
Sheathed (BS) Ampacity
Single InductiveSize Nominal Weight Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Voltage Drop Optional
AWG/ Part No. Diameter (Lbs./ Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (ohms/ (Volts per amp Groundingkcmil mm2 37-105 (inches) 1000 ft.) (inches) 1000 ft.) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) per 1000 ft.) Conductor
6421
1/02/03/04/0
262313373444535646777
12.5213443547086
109132159189227273326394
-317-318-319-320-321-322-323-324-325-326-327-328-329-330-331
1.3381.5141.6501.8001.8952.0252.1192.2522.4222.5652.7042.9303.0963.2673.512
1094146219702263261731003531416248645581639275828806
1013711959
158921342725305434543989445851405913688477609059
103661178013708
1.5611.7991.9982.0852.1812.3102.4042.5372.7072.9143.0543.2803.4393.6113.855
88116152175201232266306348386429455528584647
7599
129149171197226260296328365387449496550
0.4450.3000.1840.1470.1170.0930.0740.0580.0480.0400.0340.0280.0240.0200.016
0.5560.3760.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.0330.0280.025
0.0460.0410.0380.0370.0360.0340.0330.0320.0310.0300.0300.0290.0290.0280.028
0.8180.5620.3570.2930.2410.1980.1650.1380.1190.1050.0930.0840.0750.0680.063
66644433322111
1/0
Unarmored
Three Conductor Type MMV Marine Medium Voltage – 8kV, 100% Insulation LevelArmored &
Sheathed (BS) Ampacity
37-105
Type MMV Medium Voltage CableSingle Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°CMulti-Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°C
®
Oil & Gas Cables
Ordering Type MMV Medium Voltage CablesExample:
• 3 conductor power cable• 8kV 100%• #2 AWG• ground• bronze armored & sheathed
AmerCable TypeMMV Prefix
Specific Cable Number(from charts)
Armor RequirementBS – armored &
sheathedBlank – no armor
Ground ConductorG – with groundBlank – no ground
37–105 – 319 BS G
See page 29 for MMV
Stranding Profile
37-105
Type MMV Medium Voltage CableSingle Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°CMulti-Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°C
Single InductiveSize Nominal Weight Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Voltage Drop Optional
AWG/ Part No. Diameter (Lbs./ Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (ohms/ (Volts per amp Groundingkcmil mm2 37-105 (inches) 1000 ft.) (inches 1000 ft.) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) per 1000 ft.) Conductor
21
1/02/03/04/0
262313373444535
3443547086
109132159189227273
-346-347-348-349-350-351-352-353-354-355-356
2.1572.2392.3352.4612.5592.6912.7492.8813.0213.1833.357
27593073346639914466515057496483733183809599
3697404544775242576465137348818488569983
11285
2.4432.5242.6202.8102.9103.0413.1523.2873.3653.5273.701
156178205234269309352389432456528
133151174199229263299331367388449
0.1840.1470.1170.0930.0740.0580.0480.0400.0340.0280.024
0.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.033
0.0420.0400.0390.0370.0360.0350.0340.0330.0320.0310.031
0.3610.2960.2440.2010.1680.1410.1220.1070.0950.0860.077
64443332211
Unarmored
Three Conductor Type MMV Marine Medium Voltage – 15kV, 100% Insulation LevelArmored &
Sheathed (BS) Ampacity
Single InductiveSize Nominal Weight Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Voltage Drop Optional
AWG/ Part No. Diameter (Lbs./ Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (ohms/ (Volts per amp Groundingkcmil mm2 37-105 (inches) 1000 ft.) (inches) 1000 ft.) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) per 1000 ft.) Conductor
21
1/02/03/04/0
262313373444535
3443547086
109132159189227273
-357-358-359-360-361-362-363-364-365-366-367
2.3342.4162.5122.6372.8422.9762.9893.0913.2043.3473.521
3125347038744411520659306412699078978879
10144
413745155150574866407430783185299510
1056011910
2.6192.7012.8612.9873.1923.3253.3403.3943.5483.6903.865
156178205234269309352389432456528
133151174199229263299331367388449
0.1840.1470.1170.0930.0740.0580.0480.0400.0340.0280.024
0.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.033
0.0440.0430.0410.0390.0380.0370.0350.0340.0340.0330.033
0.3640.2990.2460.2030.1700.1420.1240.1090.0970.0880.079
64443332211
Unarmored
Three Conductor Type MMV Marine Medium Voltage – 15kV, 133% Insulation LevelArmored &
Sheathed (BS) Ampacity
Manufactured by AmerCable Incorporated • 800-506-9473 • 713-896-5800 • Fax: 713-849-900926
Ordering Type MMV Medium Voltage CablesExample:
• 3 conductor power cable• 8kV 100%• #2 AWG• ground• bronze armored & sheathed
AmerCable TypeMMV Prefix
Specific Cable Number(from charts)
Armor RequirementBS – armored &
sheathedBlank – no armor
Ground ConductorG – with groundBlank – no ground
37–105 – 319 BS G
®
Oil & Gas Cables
See page 29 for MMV
Stranding Profile
v2.08.1
www. amercable.com • e-mail: [email protected] 27
®
Oil & Gas Cables
v2.08.1
37-105VFD
Type MMV-VFDPower CableThree Conductor: 8kV –15kV • 133% Insulation Level • Rated 90°C
ApplicationsA flexible, braid and foil shielded,power cable specifically engineered for use in medium voltage variable frequency AC drive (VFD) applications.
Features� Flexible stranded conductors,
braided shields and a braided armor(when armored). Suitable for applications involving repeated flexing and high vibration.
� Small minimum bending radius (6xOD for unarmored cables and 8xODfor armored cables) for easy installation.
� Insulation resists the repetitive 3x voltage spikes from VFDs and reducesdrive over current trip problems due to cable charging current.
� Overall braid and foil shield provides100% coverage containing VFD EMI emissions.
� Symmetrical insulated ground conductors reduce induced voltageimbalances and carry common mode noise back to the drive.
� High strand count conductors andbraid shield design is much more flexible, easier to install and moreresistant to vibration than Type MC cable.
� Severe cold durability: exceeds CSA cold bend/cold impact (-40˚C/-35˚C).
� Flame retardant: IEC 332-3 Category A and IEEE 1202.
� Suitable for use in Class I, Division 1and Zone 1 environments (armoredand sheathed).
Conductor ShieldA combination of semi-conducting tape andextruded thermosetting semi-conductingmaterial meeting UL 1309, IEEE 1580, ICEA S-68-516 and UL1072.
Armor (optional)Basket weave wire armor per IEEE 1580 and UL 1309/CSA 245. Bronze standard. Tinned copper available by request.
JacketA black, arctic grade, flame retardant, oil, abrasion,chemical and sunlight resistant thermosetting compound meeting UL 1309/CSA 245, IEEE 1580,and UL 1072. Colored jackets for signifying differentvoltage levels are also available on special request(orange = 8kV and red = 15kV).
Sheath (optional)A black, arctic grade, flame retardant, oil, abrasion,chemical and sunlight resistant thermosetting compound meeting UL 1309/CSA 245, IEEE 1580,and UL 1072. Colored jackets for signifying differentvoltage levels are also available on special request(orange = 8kV and red = 15kV).
Insulation ShieldComposite shieldconsisting of 0.0126"tinned copper braidedwith nylon providing60% copper Shieldedcoverage meeting UL1309, IEEE Std. 1580,ICEA S-68-516 and UL1072. The nylon iscolored for easy phase identification (threeconductor = black, blue,red) without the need toremove the shield to findan underlying coloredtape.
Insulation ShieldSemi-conducting layer meeting UL 1309, IEEE 1580, ICEA S-68-516 and UL 1072.
EMI ShieldOverall tinned copperbraid plus aluminum/polyester tape providing100% coverage
Conductors (3)Soft annealed flexiblestranded tinned copperper IEEE 1580 Table 11.
InsulationExtruded thermosetting90°C Ethylene PropyleneRubber (EPR), meetingUL 1309 (Type E), IEEE 1580 (Type E),ICEA S-68-516 and UL 1072.
Symmetrical InsulatedGrounding Conductors (3)Soft annealed flexible stranded tinned copperconductor per IEEE 1580 Table 11. Gexol Insulationsized per Table 23.2 of UL1072. Color: Green
Ratings & Approvals� UL Listed as Marine Shipboard
Cable (E111461)� American Bureau of Shipping (ABS)� Det Norske Veritas (DNV) Pending� Lloyd’s Register of Shipping (LRS)
Pending� 90˚C Temperature Rating� Voltage Rating – 8kV to 15kV
(25kV available on request)
Termination Kits
AmerCableSystems offers
pre-sized and pre-formed termination kit
packages specifically for
VFD cable constructions
Low smoke halogen-free jacket available on request.
Manufactured by AmerCable, Incorporated • (870) 862-4919 • (800) 643-1516 • Fax (870) 862-961328
37-105VFD
Type MMV-VFDPower CableThree Conductor: 8kV –15kV • 133% Insulation Level • Rated 90°C
Single Inductive Voltage Green InsulatedSize Nominal Weight Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Drop Grounding
AWG/ Part No. Diameter (Lbs./ Part No. Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (ohms/ (Volts per amp Conductor (3x)kcmil mm2 37-105 (inches) 1000 ft.) 37-105 (inches) 1000 ft.) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) per 1000 ft.) Size (AWG)
6421
1/02/03/04/0262313373444535
12.5213443547086
109132159189227273
-332VFD-333VFD-334VFD-335VFD-336VFD-337VFD-338VFD-339VFD-340VFD-341VFD-342VFD-343VFD-344VFD
-332BSVFD-333BSVFD-334BSVFD-335BSVFD-336BSVFD-337BSVFD-338BSVFD-339BSVFD-340BSVFD-341BSVFD-342BSVFD-343BSVFD-344BSVFD
1.5411.7281.9392.0312.1332.2692.3702.5112.6912.8413.0583.2183.403
1349177023352664306535934064477055446340743585969900
20482548320135704014460051135878693678059007
102501164
1.8792.0692.2832.3782.4812.6212.7232.8663.1193.2733.4943.6503.836
88116152175201232266306348386429455528
7599
129149171197226260296328365387449
0.4450.3000.1840.1470.1170.0930.0740.0580.0480.0400.0340.0280.024
0.5560.3760.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.033
0.0480.0430.0400.0380.0370.0360.0350.0330.0320.0320.0310.0300.030
0.8200.5640.3590.2940.2420.1990.1660.1390.1210.1060.0940.0850.076
1010108886666444
Unarmored
Three Conductor Type MMV-VFD Marine Medium Voltage – 8kV • 133% Insulation LevelArmored &
Sheathed (BS) Ampacity
Single Inductive Voltage Green InsulatedSize Nominal Weight Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Drop Grounding
AWG/ Part No. Diameter (Lbs./ Part No. Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (ohms/ (Volts per amp Conductor (3x)kcmil mm2 37-105 (inches) 1000 ft.) 37-105 (inches) 1000 ft.) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) per 1000 ft.) Size (AWG)
21
1/02/03/04/0262313373444
3443547086
109132159189227
-357VFD-358VFD-359VFD-360VFD-361VFD-362VFD-363VFD-364VFD-365VFD-366VFD
-357BSVFD-358BSVFD-359BSVFD-360BSVFD-361BSVFD-362BSVFD-363BSVFD-364BSVFD-365BSVFD-366BSVFD
2.4742.5612.6632.7953.0133.1553.1683.2763.3963.548
3375374841844764562264046925754985299589
44684876556262087171802484579211
1027111405
2.8292.9173.0903.2263.4473.5913.6073.6663.8323.985
156178205234269309352389432456
133151174199229263299331367388
0.1840.1470.1170.0930.0740.0580.0480.0400.0340.028
0.2300.1840.1470.1170.0940.0750.0630.0530.0450.039
0.0440.0430.041
0.0390.038
0.0370.0350.0340.0340.033
0.3640.2990.2460.2030.1700.1420.1240.1090.0970.08
10888666644
Unarmored
Three Conductor Type MMV-VFD Marine Medium Voltage – 15kV • 133% Insulation LevelArmored &
Sheathed (BS) Ampacity
Ordering Type MMV-VFD Medium Voltage CablesExample:
• 3 conductor MMV-VFD power cable• 15kV• #2 AWG• bronze armored & sheathed
AmerCable Type MMV-VFD Prefix
Specific CableNumber (from charts)
37–105 – 357BSVFD
Ordering Type MMV-VFD Medium Voltage CablesExample:
• 3 conductor MMV-VFD power cable• 8kV• #6 AWG• Unarmored
AmerCable Type MMV-VFD Prefix
Specific CableNumber (from charts)
37–105 – 332VFD
®
Oil & Gas Cables
www. amercable.com • e-mail: [email protected] 29
Ampacities are based on API RP 14F (June 1999)Table 4 or 5 for single conductor cables and Table3 for multi-conductor cables. The notes to thesetables are also applicable. Ampacities are alsobased on a 90°C conductor temperature and a45°C ambient temperature.Inductive reactance and voltage drop values are based on a 90°C conductor temperature and 60 Hz operation. Values for single conductor cables are based on a symmetrical triangular configuration.Please consult AmerCable on values for other configurations.
MMV Ampacities & Electrical Data
Individual Closest Equivalent UninsulatedSize Number Strand Dia. IEEE 45 Metric Size Conductor
AWG/kcmil of Strands (inches) Std. Size (mm2) Dia. (inches)
86421
1/02/03/04/0
262313373444535646777
1111
3761
133133209266342418532646777925
11101332159119242745
0.0201 0.0201 0.0177 0.0223 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201
1626416683
106133168212262313373444535646777
1111
7.57 12.49 21.11 33.51 42.79 54.45 70.01 85.57
108.91 132.25 159.06 189.36 227.23 272.68 325.70 393.87 561.94
0.136 0.175 0.258 0.324 0.361 0.407 0.461 0.510 0.575 0.654 0.720 0.785 0.860 0.941 1.029 1.132 1.354
MMV Bend RadiusUnarmored Armored Armored & Sheathed
IEEE 45 6X Diameter 8X Diameter 8X Diameter
IEC 92 <1" (25mm) 6X Diameter 8X Diameter4 x Diameter>1" (25mm)6X Diameter
Transport <1" (25mm) 6X Diameter 6X DiameterCanada 4X Diameter
>1" (25mm)6X Diameter
37-105
Type MMV Medium Voltage CableSingle Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°CMulti-Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°C
MMV Stranding Profile
®
Oil & Gas Cables
Designed to deliver outstanding performance in the harshest operating conditions – specifically in high temperature Ester Based drilling muds.
Designed to deliver outstanding performance in the harshest operating conditions – specifically in high temperature Ester Based drilling muds.
30
Ester Based Mud ResistantJacketed Cables110°C • UL Marine Shipboard Cable
A swollen orsplit cable
jacket due to drillingmud exposure
is a productivity
killer.
AmerCableoffers three
levels of mudresistance tomatch youroperating
conditions:
Standard, Advanced and
Ester Based Mud Resistant
www. amercable.com • e-mail: [email protected] 31
1 All results representative of finished cables (6 3/C, 14 7/C and 18 7 PR). Test data on file at AmerCable
Aging Requirements 90°C Rated Jacket121±1°C Air Oven 240 Hours
Oil ExposureResistanceAfter Oil Immersion at121±1°C 18 Hours
Jacket Type Type N Type N Mud Resistant Jacket
Tensile Strength, Min, PSI 1800 1800 Pass
300 300 Pass
20 20 Pass
Elongation at Rupture, Min, %
Set, Max, %
Tensile Strength,Minimum
900 psi 900 psi Pass
50%Actual
50%Actual
Pass
80 80 Pass
60 60 Pass
100 130 Pass
Elongation at Rupture, %
Tensile Strength, % Retentionof Unaged, Min
Elongation at Rupture, %Retention of Unaged, Min
Mechanical WaterAbsorption mg / in2
Weatherometer TestNo
RequirementPass PassPer UL 1581
Tear NoRequirement
35 Passlb/in Thickness, Min
FT4/IEEE 1202 FlameExposure (UL-1685)
Pass Pass Pass–
IEC 332-3 FlameExposure
NoRequirement
No Requirement Pass–
Table ISpecifications UL-1309
Table 4IEEE 1580Table 5-7
AmerCable TestingProgram1
World Class Mud ResistantJacket
PhysicalRequirements –Unaged
When standard mud resistance isn’t enough, AmerCable has aWorld Class Mud Resistant cable jacket designed to deliveroutstanding performance in the harshest operating conditions.Designed specifically for exposure to high temperature ESTERBASED drilling muds, this cable meets all the performancerequirements of industry standards UL 1309 and IEEE 1580for Type N jackets. When tested for prolonged exposure to themost aggressive ester based drilling muds, it easily passes the mud resistance requirements of NEK 606.
AmerCable’s ester based mud resistant cables were also testedagainst the requirements of UL 1309 and IEEE 1580 and theresults are shown in Table I.1 This product easily passed allthe requirements. Table II shows the results of this cablewhen aged in Baroid Petrofree® (Ester Based) drilling mud perNEK 606. All aging requirements were met. Additional testingdone on these cables show the jacket to pass cold impact at -20°C and cold bend at -40°C.
Table II
MUD Resistant –NEK 606
Note: Tested forChanges in Each ListedRequirement
70°C, 56 Days
Elongation at Break ±25% Baroid Petrofree® (Ester Based) Pass
Tensile Strength ±25% Baroid Petrofree® (Ester Based) Pass
Volume Swelling Max 20% Baroid Petrofree® (Ester Based) Pass
Weight Increase Max 15% Baroid Petrofree® (Ester Based)
Baroid Petrofree® (Ester Based)
Pass
Oxygen Index Min 25% Pass
Requirements Mud Type Results
Ester Based Mud ResistantJacketed Cables110°C • UL Marine Shipboard Cable
®
Oil & Gas Cables
v2.08.1
The Assembly Application ProfessionalsThe Assembly Application Professionals
CableASSEMBLIESCableASSEMBLIES
Precision Engineered
Turn-key cable assembly solutions for hazardous
and industrial environments
Constructions:� 300V – 15kV AC� DC Power� Composite Power
& Control� Instrumentation� Thermocouple� Fiber Optic� Electro-Optic
Applications:� Service Loops� Driller’s Console� Mud Pump Controls� 15kV Bridle Assembly� Tender-to-Platform Bridle� Ship-to-Shore Power� Portable Power Generation� Zone 1 (EX) Rated
Cable Assemblies
32
(800) 506-9473
Cable Assemblies from AmerCable Systems
save you time & money!
� Fast Delivery� Job-site application evaluation
and consultation� Highly reliable cable assemblies
custom built and tested to spec
Fiber OpticSolutions
Top DriveService Loops
9_09© 2009, AmerCable Incorporated
10633 West Little York • Building #1 • Suite #100 • Houston, TX 77041 800-506-9473 • 713-896-5800 • Fax: 713-849-9009 • e-mail: [email protected] • www.amercable.com
®
Low smokehalogen-freefire resistantor flameretardant Type P cables.
SHF1, SHF2and NEK 606IEC cables
Precisionengineered cableassembliesfor hazardousand industrialapplications.
Top DriveServiceLoops
VFDCABLES
Crush andImpactResistant Type P cableswithoutexternalarmoring.
Foil shielded,power cablesengineered for use in variablefrequency AC driveapplications.
Available in severalconstructions
AmerCable is an ISO 9001 certified cable manufacturerthat combines leading-edge manufacturing technology,
innovative thinking, and high quality service to deliver the finest oil & gas cable andengineered cable assemblies available.
AmerCable serves the world from our Oil & Gas Group headquarters in Houston, Texas. Ourprofessional field engineers and sales force work withyou to create innovative, cost-effective project solutions.
What can you expect from AmerCable?� Fastest Lead Times in the Industry
� On-Time Delivery
� Professional Sales, Support and Service
� Productivity Solutions
� Global Cable Management
AmerCable’s manufacturing facility in El Dorado, Arkansas.