www.newavenergy.com powerscale 10-50kva ed. 02.02.2011 maximize your availability
TRANSCRIPT
www.newavenergy.com
PowerScale
10-50kVAEd. 02.02.2011
Maximize your availability
www.newaveups.com 02.02.2011 2
Contents
• Range
• Features and Performance
• Mechanical Construction
• Battery Configuration
• External Batteries – Battery Cabinet
• Connectivity
• Options and accessories
www.newaveups.com 02.02.2011 3
10kVA 10kVA
15kVA 15kVA
20kVA 20kVA
25kVA 25kVA
30kVA
40kVA
50kVA
345 x 720 x 710 345 x 1045 x 710 440 x 1400 x 910
60-62-64kg 88-90-92-94kg 135-145-150-155kg
RangeTechnology : On-Line, transformer less Power range : 10 ,15, 20, 25,30 ,40,50 kVA (3ph/3ph)Rated at PF : cosphi 0.9
Type B Type CType A
www.newaveups.com 02.02.2011 4
• Generalities
• LCD Display
• Input PFC
• Input THDI
• Efficiency
• Active Power vs cosphi
Features and performance
www.newaveups.com 02.02.2011 5
True on-line double conversion (VFI)
Power Factor 0.9
High efficiency (up to 95.5%)
Input PFC: 0.99 @ 100% load
Input THDi < 3 %
Parallelable up to 20 units
Electronic and manual bypass
Manual/Automatic Battery test
Fan speed temperature regulated
Easy to install, service and manoeuvre
Flexible battery autonomy space within 3 different cabinets size (A,B,C)
Single or Dual input feed
RS 232 + 4 potential free input contacts
SNMP card slot / Pot. Free Output card slot
Multi language LCD display E/S/D/F/P Wide Input voltage windows <@100% load(-23% / +15%)
<@80% load (-30% / +15%) <@60% load (-40% / +15%)
Cab A
Generalities
Features and performance
Cab B
Cab C
www.newaveups.com 02.02.2011 6
ALARM
LINE 2
BATTERY
BY PASS
LINE 1 INV
RESET ENTER
LCD Display ON / OFF
ON / OFF
Most important info available at first glance
LCD Display
Features and performance
www.newaveups.com 02.02.2011 7
Benefits:• No phase compensation filter
required• Respect power grid
regulations• Energy savings
Advanced Booster PFC circuit to provide near-unity Input PF even with partial loads.
0.5
0.6
0.7
0.8
0.9
1
25% 50% 75% 100%
Load (%)
Inp
ut
PF
(%
)
0.990.96 0.985 0.99
Reduced TCO
Input PFC
Features and performance
www.newaveups.com 02.02.2011 8
Benefits:• No gen-set oversizing• Small cable/fuses/breakers
size • No extra heating of
transformers
Input THD versus load
Advanced Booster PFC circuit to provide Flat THDi Curve even with partial loads.
THDi
Unique electrical performance Reduced TCO
Features and performance
www.newaveups.com 02.02.2011 9
Flat Efficiency GraphResults in low losses at PARTIAL and FULL load Redundant UPS Systems operating typically at 25-75% of the rated load.
Efficiency
Features and performance
Energy Savings Reduced TCO
www.newaveups.com 02.02.2011 10
Overview: Cabinet A
Airinlets
Castors
LCD Display
I/O connection
Battery fuse
By-pass fuse
Rectifier fuse
Manual By-pass
UPSdisconnect
• SNMP Card• Pot.free output
contacts (optional)
Mechanical Construction
• RS232• Pot.free
Input contacts
• Multidrop
Parallel kit
www.newaveups.com 02.02.2011 11
Battery bank
CPU board
DisplayBoard
• Rectifier• Booster• Battery charger•Inverter
Overview: Cabinet A
Mechanical Construction
www.newaveups.com 02.02.2011 12
Airinlets
Castors
LCD Display
I/O connection
Battery fuse
By-pass fuse
Rectifier fuse
Manual By-pass
UPSdisconnect
• SNMPCard • Pot.free output contacts (optional)
Overview: Cabinet B
Mechanical Construction
• RS232• Pot.free
Input contacts
• Multidrop
Parallel Kit
www.newaveups.com 02.02.2011 13
Battery bank
CPU board
DisplayBoard
• Rectifier• Booster• Battery charger•Inverter
Overview: Cabinet B
Mechanical Construciton
www.newaveups.com 02.02.2011 14
Removeable Front Panel
Overview: Cabinet C
Mechanical Construciton
Airinlets
Castors
LCD Display
No Access from Rear Side
www.newaveups.com 02.02.2011 15
Overview: Cabinet C
Mechanical Construciton
I/O connection
Battery fuse
By-pass fuse
Rectifier fuse
Manual By-pass
UPSdisconnect
• SNMP• Card and
Pot. Free output contacts
(optional)
RS 232Pot.free
Input ContactsMultidrop
Parall. Kit
www.newaveups.com 02.02.2011 16
Battery Configuration
Battery shelves, trays and links
Power Range kVA/kW
10/915/13.5 20/18
10/915/13.5 20/1825/22.5
25/22.530/2740/3650/45
Maximum Battery Capacity
1 x 48 x 7/9Ah 2 x 48 x 7/9Ah 3 x 48 x 7/9Ah 1 x 48 x 28Ah
Battery shelves and trays
Included Included Optional:2 x 48 x 7/9Ah 04-14753 x 48 x 7/9Ah 04-14761 x 48 x 28Ah 04-1477
Battery links Optional:1 x 48 x 7/9Ah 04-0136
Optional:1 x 48 x 7/9Ah 04-01362 x 48 x 7/9Ah 04-0150
Optional:2 x 48 x 7/9Ah 04-14733 x 48 x 7/9Ah 04-14721 x 48 x 28Ah 04-1474
Type B Type CType A
www.newaveups.com 02.02.2011 17
Shelves (Standard)
Battery Configuration
Battery shelves & traysCabinet C (25, 30,40,50kVA)
2 Shelves are delivered with the empty cabinet
Additional Shelves and Trays are OPTIONAL.
Possible configurations:• 2 x 48 x 7/9Ah• 3 x 48 x 7/9Ah• 1 x 48 x 28Ah
Standard Cabinet C
www.newaveups.com 02.02.2011 18
OPTION 04-1475: Battery shelves and trays for2 x 48 x 7/9Ah
Kit consisting of:
2 x shelves
16 x trays(6 x 7/9Ah batt / tray)
Battery Configuration
Battery shelves & traysCabinet C (25, 30,40,50kVA)
www.newaveups.com 02.02.2011 19
OPTION 04-1476: Battery shelves and trays for3 x 48 x 7/9Ah
Kit consisting of:
4 x shelves
24 x trays(6 x 7/9Ah batt / tray)
Battery Configuration
Battery shelves & traysCabinet C (25, 30,40,50kVA)
www.newaveups.com 02.02.2011 20
OPTION 04-1477: Battery shelves and trays for1 x 48 x 28Ah
Kit consisting of:
2 x shelves
16 x trays(3 x 28Ah batt / tray)
Battery Configuration
Battery shelves & traysCabinet C (25, 30,40,50kVA)
www.newaveups.com 02.02.2011 21
Battery Configuration
Caracteristics (1)
Source: PowerScale Product Specifications Doc: 04-1206_S10_NW_TDSPS_10-50kVA_GB_101021 (2)
www.newaveups.com 02.02.2011 22
Battery Configuration
Caracteristics (2)
www.newaveups.com 02.02.2011 23
Type of Batteries offered by Newave SA 7Ah: Panasonic (normal life)9Ah: YUASA (normal life)28Ah: Panasonic (long life 10Y)
Battery Configuration
How to order INTEGRATED Batteries from Newave
Principles:1. Subsidiaries and Partners calculate
the exact number of battery per string that the application requests and order number of blocks accordingly (minimal number acc to Product Specifications)
PO-Form detail
(per string)
Set Battery Autonomy: mins.
Number of Battery Strings:
Number of Battery Blocks:
Ah:
2. Newave delivers the UPS with integrated batteries mounted and tested, as requested
3. Battery blocks in PowerScale price list include shelves, trays and battery links (items 04-1203; 04-1204; 04-1472; 04-1473; 04-1474)
www.newaveups.com 02.02.2011 24
Battery Configuration
Autonomy Table 10kVA
Note: Backup times are approximate and may vary with battery type, configuration, battery age, temperature etc.
Autonomy (min) 7Ah batt 9Ah batt 7Ah batt 9Ah batt 7Ah batt 9Ah batt6 1 x 24 1 x 20 1 x 32 1 x 22 1 x 34 1 x 248 1 x 28 1 x 22 1 x 38 1 x 26 1 x 42 1 x 28
10 1 x 32 1 x 24 1 x 46 1 x 32 1 x 48 1 x 3412 1 x 40 1 x 28 2 x 26 1 x 36 2 x 30 1 x 4015 1 x 48 1 x 32 2 x 32 1 x 42 2 x 36 1 x 4818 2 x 28 1 x 38 2 x 36 1 x 48 2 x 40 2 x 2820 2 x 30 1 x 40 2 x 40 2 x 28 2 x 44 2 x 3022 2 x 32 1 x 44 2 x 42 2 x 30 2 x 48 2 x 3225 2 x 36 1 x 48 2 x 48 2 x 32 n.a. 2 x 3630 2 x 40 2 x 28 n.a. 2 x 38 n.a. 2 x 4235 2 x 46 2 x 32 n.a. 2 x 42 n.a. 2 x 4840 n.a. 2 x 36 n.a. 2 x 48 n.a. n.a.60 n.a. 2 x 48 n.a. n.a. n.a. n.a.
Min. Nr of Batt Cab AMin. Nr of Batt Cab B
Cabinet A: max 1 x 48 x 7/9Ah batteriesCabinet B: max 2 x 48 x 7/9Ah batteries
6kW 8kW 9kW
Powerscale 10kVA, 9kWLoad Power
16 blocks 20 blocks 24 blocks16 blocks 20 blocks 24 blocks
www.newaveups.com 02.02.2011 25
Battery Configuration
Autonomy Table 15kVA
Note: Backup times are approximate and may vary with battery type, configuration, battery age, temperature etc.
Powerscale 15kVA, 13.5kW
Autonomy (min) 7Ah batt 9Ah batt 7Ah batt 9Ah batt 7Ah batt 9Ah batt6 1 x 40 1 x 28 1 x 48 1 x 32 1 x 348 1 x 48 1 x 34 2 x 28 1 x 40 2 x 34 1 x 42
10 2 x 28 1 x 40 2 x 34 1 x 48 2 x 40 1 x 4812 2 x 34 1 x 48 2 x 40 2 x 28 2 x 4815 2 x 40 2 x 28 2 x 48 2 x 32 n.a. 2 x 3418 2 x 46 2 x 32 n.a. 2 x 38 n.a. 2 x 4220 2 x 48 2 x 36 n.a. 2 x 40 n.a. 2 x 4825 n.a. 2 x 40 n.a. 2 x 48 n.a. n.a.30 n.a. 2 x 48 n.a. n.a. n.a. n.a.35 n.a. n.a. n.a. n.a. n.a. n.a.40 n.a. n.a. n.a. n.a. n.a. n.a.60 n.a. n.a. n.a. n.a. n.a. n.a.
Min. Nr of Batt Cab AMin. Nr of Batt Cab B
Cabinet A: max 1 x 48 x 7/9Ah batteriesCabinet B: max 2 x 48 x 7/9Ah batteries
Load Power
10kW 12kW 13.5kW
24 blocks 30 blocks 34 blocks24 blocks 30 blocks 34 blocks
www.newaveups.com 02.02.2011 26
Battery Configuration
Autonomy Table 20kVA
Note: Backup times are approximate and may vary with battery type, configuration, battery age, temperature etc.
Powerscale 20kVA, 18kW
Autonomy (min) 7Ah batt 9Ah batt 7Ah batt 9Ah batt 7Ah batt 9Ah batt4 1 x 486 1 x 48 1 x 32 2 x 32 1 x 44 2 x 36 1 x 467 1 x 48 2 x 388 2 x 28 1 x 40 2 x 38 2 x 42
10 2 x 34 1 x 48 2 x 46 2 x 32 2 x 48 2 x 3611 2 x 48 n.a. 2 x 3812 2 x 40 2 x 28 n.a. 2 x 36 n.a. 2 x 4015 2 x 48 2 x 32 n.a. 2 x 42 n.a. 2 x 4817 n.a. n.a. 2 x 48 n.a. n.a.18 n.a. 2 x 38 n.a. n.a. n.a. n.a.20 n.a. 2 x 40 n.a. n.a. n.a. n.a.25 n.a. 2 x 48 n.a. n.a. n.a. n.a.30 n.a. n.a. n.a. n.a. n.a. n.a.35 n.a. n.a. n.a. n.a. n.a. n.a.
Min. Nr of Batt Cab AMin. Nr of Batt Cab B
Cabinet A: max 1 x 48 x 7/9Ah batteriesCabinet B: max 2 x 48 x 7/9Ah batteries
30 blocks 40 blocks 46 blocks32 blocks 36 blocks24 blocks
12kW 16kW 18kW
Load Power
www.newaveups.com 02.02.2011 27
Note: Backup times are approximate and may vary with battery type, configuration, battery age, temperature etc.
Battery Configuration
Autonomy Table 25kVA
Powerscale 25kVA, 22.5kW
Autonomy (min) 7Ah batt 9Ah batt 28Ah batt 7Ah batt 9Ah batt 28Ah batt 7Ah batt 9Ah batt 28Ah batt6 2 x 32 1 x 44 2 x 40 2 x 40** 2 x 468 2 x 38 1 x 48 2 x 48 2 x 40** 2 x 48
10 2 x 46 2 x 32 3 x 40** 2 x 40 3 x 46 2 x 4612 2 x 48 2 x 36 3 x 44 2 x 44 3 x 48 2 x 4813 3 x 48 2 x 48 n.a.15 3 x 42 2 x 44 n.a. 3 x 40** n.a.18 3 x 48 2 x 48 1 x 34 n.a. 3 x 42 1 x 40 n.a. 3 x 46 1 x 4820 n.a. 3 x 36 n.a. 3 x 46 n.a. 3 x 48 n.a.22 n.a. 3 x 38 1 x 40 n.a. 3 x 48 1 x 48 n.a. n.a. n.a.24 n.a. n.a. n.a. n.a. n.a. n.a. n.a.25 n.a. 3 x 42 1 x 44 n.a. n.a. n.a. n.a. n.a. n.a.27 n.a. 3 x 48 n.a. n.a. n.a. n.a. n.a. n.a.28 n.a. n.a. 1 x 48 n.a. n.a. n.a. n.a. n.a. n.a.29 n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a.31 n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a.32 n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a.
Min. Nr of Batt Cab B
Min. Nr of Batt Cab C
Cabinet B: max 2 x 48 x 7/9Ah batteriesCabinet C: max 3 x 48 x 7/9Ah batteries
32 blocks 40 blocks 46 blocks
16kW 20kW 22.5kW
Load Power
32 blocks 40 blocks 46 blocks
www.newaveups.com 02.02.2011 28
Battery Configuration
Autonomy Table 30kVA
Powerscale 30kVA, 27kW
Autonomy (min) 7Ah batt 9Ah batt 28Ah batt 7Ah batt 9Ah batt 28Ah batt 7Ah batt 9Ah batt 28Ah batt6 2 x 40 2 x 48 3 x 367 1 x 288 2 x 48 3 x 28 1 x 30
10 2 x 40 2 x 48 3 x 48 1 x 3612 3 x 44 2 x 44 3 x 48 n.a. 1 x 4213 3 x 48 2 x 48 n.a. n.a. 3 x 48 1 x 4415 n.a. n.a. 3 x 48 n.a. n.a. 1 x 4818 n.a. 3 x 42 1 x 40 n.a. n.a. 1 x 48 n.a. n.a. n.a.20 n.a. 3 x 46 n.a. n.a. n.a. n.a. n.a. n.a.22 n.a. 3 x 48 1 x 48 n.a. n.a. n.a. n.a. n.a. n.a.24 n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a.25 n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a.27 n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a.28 n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a.29 n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a.31 n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a.32 n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a.
Min. Nr of Batt Cab C
Cabinet C: max 3 x 48 x 7/9Ah batteries
20kW 24kW 27kW
20 blocks 24 blocks 28 blocks
Load Power
www.newaveups.com 02.02.2011 29
Battery Configuration
Autonomy Table 40kVA
Powerscale 40kVA, 36kW
36kWAutonomy (min) 7Ah batt 9Ah batt 28Ah batt 7Ah batt 9Ah batt 28Ah batt 7Ah batt 9Ah batt 28Ah batt
6 2 x 48 2 x 32 2 x 48 3 x 48 2 x 487 1 x 26 3 x 48 1 x 32 n.a. 3 x 36 1 x 368 3 x 40 2 x 40 n.a. 1 x 34 n.a. 1 x 429 n.a. n.a. 3 x 46 1 x 44
10 3 x 48 2 x 48 1 x 34 n.a. 1 x 40 n.a. 3 x 48 1 x 4812 n.a. 3 x 38 n.a. 3 x 48 1 x 48 n.a. n.a. n.a.13 n.a. 3 x 40 1 x 40 n.a. n.a. n.a. n.a. n.a. n.a.15 n.a. 3 x 44 n.a. n.a. n.a. n.a. n.a. n.a.16 n.a. 3 x 48 1 x 48 n.a. n.a. n.a. n.a. n.a. n.a.18 n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a.20 n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a.
Min. Nr of Batt Cab C
Cabinet C: max 3 x 48 x 7/9Ah batteries
26 blocks 32 blocks 36 blocks
25kW 32kW
Load Power
www.newaveups.com 02.02.2011 30
Battery Configuration
Autonomy Table 50kVA
Powerscale 50kVA, 40kW
45kWAutonomy (min) 7Ah batt 9Ah batt 28Ah batt 7Ah batt 9Ah batt 28Ah batt 7Ah batt 9Ah batt 28Ah batt
6 3 x 48 2 x 48 1 x 34 n.a. n.a.7 n.a. n.a. 3 x 40 1 x 40 n.a. 3 x 46 1 x 448 n.a. 3 x 40 1 x 40 n.a. 3 x 44 n.a. 3 x 48 1 x 489 n.a. n.a. 3 x 48 1 x 48 n.a. n.a. n.a.
10 n.a. 3 x 44 1 x 48 n.a. n.a. n.a. n.a. n.a. n.a.12 n.a. 3 x 48 n.a. n.a. n.a. n.a. n.a. n.a. n.a.13 n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a.15 n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a.16 n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a.18 n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a.20 n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a. n.a.
Min. Nr of Batt Cab C
Cabinet C: max 3 x 48 x 7/9Ah batteries
34 blocks 40 blocks 44 blocks
35kW 40kW
Load Power
www.newaveups.com 02.02.2011 31
External Batteries – Battery Cabinet
Battery Cabinet
In case of external battery requirment, an external battery cabinet will be made available in March 2011.
More information will be available early 2011
www.newaveups.com 02.02.2011 32
Connectivity
Standard - included Optional
• RS232 on Sub-D9 port
• Input Dry Contacts:1. Remote shut down2. Generator ON3. Programable Input: Customer IN14. Temp Sensor for Battery5. 12VDC Source
• RJ 45 for Multidrop
A. SNMP/USHA Card (Slot)
B. Optional Card (Dry contact and USB port: Item nr 00-9737)• Output Dry Contacts:
1.Common Alarm2.Load on Bypass3.Battery low4.Load on Inverster5.Mains Failure
• USB port
www.newaveups.com 02.02.2011 33
SNMP slot card (web enabled)
Shutdown software
Potential free output contact slot card, including USB port
Parallel kit (one additionnel PCB + one parallel adapter)
Parallel cables of different lenghts
Back feed protection
Temperature probe
Options and Accessories
Emergency Shut Down
I/O Transformer for galvanic isolation or voltage adaptation, special I/O configuration
Available in price list
On special request
www.newaveups.com 02.02.2011 34
Sales Availability
Ex Works Availability 10kVA Cabinet A and B 15kVA Cabinet A and B 20kVA Cabinet A and B 25kVA Cabinet B
25kVA Cabinet C 30,40,50kVA Cabinet C
Battery Cabinet
Documentation
1. Sales Presentation2. Product Flyer3. Technical Specifications4. Price List 5. PO-Form 6. User Manual (at delivery)
January 2011
March 2011
www.newaveups.com 02.02.2011 35