xtreme power conversion tx90/t90 6kva to 40kva · 2019. 7. 30. · approvals ul1778, cul, ce, fcc a...

2
Protect your business. XTREME POWER CONVERSION TX90/T90 6kVA to 40kVA Parallel Scalable System Redundant and scalable UPS with an output up to 40kVA Galvanic isolated systems (TX90) provide full electrical noise isolaon and 120/240V split-phase output Transformerless systems (T90) provide the most economical soluon for 200V, 208V, 220V, 230V, and 240V applicaons Oponal extended baery banks & chargers 0.9 output power factormore waage for high density loads Galvanic isolaon transformer (TX90)—eliminates common mode noise and provides power condioning during nor- mal and bypass operaon 200 amp parallel e panelprovides parallel e and system maintenance bypass for up to four T90/TX90 power modules. Lockable casters— simplify installaon and maintenance Hot swappable internal baery trays—UPS module baeries are easy to replace without interrupng the load UPS module bypassallows individual module repair with internal mainte- nance bypass Extended baery runmesoponal premium internal baeries and external baery cabinets and chargers can be added for extended runme applicaons FEATURES Online scalable UPS for high power and crical N+1 redundant applicaons Xtreme TX90 and T90 parallel N+1 redundant online Uninterrupble Power Supply (UPS) provides the ideal soluon for the most demanding crical power re- quirements. Configuraons up to 40kVA can easily be configured using individual 6kVA or 10kVA modules. Xtreme N+1 configuraons allow complete serviceabil- ity and redundancy. Should an individual UPS require maintenance, the UPS is automacally taken offline. A noficaon is provided to the user from the LCD display and an audible alarm. The failed UPS module may be serviced or replaced without the remaining UPS modules or connected load having to be powered down. PRODUCT SNAPSHOT For single module TX90 6kVA & 10kVA systems, reference www.xpcc.com/tx6-10

Upload: others

Post on 28-Feb-2021

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: XTREME POWER CONVERSION TX90/T90 6kVA to 40kVA · 2019. 7. 30. · APPROVALS UL1778, cUL, CE, FCC A SYSTEM INCLUDES UPS modules with internal batteries, 200A parallel tie panel with

Protect your business.

XTREME POWER CONVERSION TX90/T90 6kVA to 40kVA Parallel Scalable System

› Redundant and scalable UPS with an output up to 40kVA› Galvanic isolated systems (TX90) provide full electrical noise

isolation and 120/240V split-phase output› Transformerless systems (T90) provide the most economical

solution for 200V, 208V, 220V, 230V, and 240V applications› Optional extended battery banks & chargers

0.9 output power factor—more wattage for high density loads

Galvanic isolation transformer (TX90)—eliminates common mode noise and provides power conditioning during nor-mal and bypass operation

200 amp parallel tie panel— provides parallel tie and system maintenance bypass for up to four T90/TX90 power modules.

Lockable casters— simplify installation and maintenance

Hot swappable internal battery trays—UPS module batteries are easy to replace without interrupting the load UPS module bypass— allows individual module repair with internal mainte-nance bypass Extended battery runtimes— optional premium internal batteries and external battery cabinets and chargers can be added for extended runtime applications

FEATURES

Online scalable UPS for high power and critical N+1 redundant applications

Xtreme TX90 and T90 parallel N+1 redundant online Uninterruptible Power Supply (UPS) provides the ideal solution for the most demanding critical power re-quirements. Configurations up to 40kVA can easily be configured using individual 6kVA or 10kVA modules.

Xtreme N+1 configurations allow complete serviceabil-ity and redundancy. Should an individual UPS require maintenance, the UPS is automatically taken offline. A notification is provided to the user from the LCD display and an audible alarm. The failed UPS module may be serviced or replaced without the remaining UPS modules or connected load having to be powered down.

PRODUCT SNAPSHOT

For single module TX90 6kVA & 10kVA systems, reference www.xpcc.com/tx6-10

Page 2: XTREME POWER CONVERSION TX90/T90 6kVA to 40kVA · 2019. 7. 30. · APPROVALS UL1778, cUL, CE, FCC A SYSTEM INCLUDES UPS modules with internal batteries, 200A parallel tie panel with

XPC USA / Denver, CO / [email protected] EMEA / Rotterdam, NL / [email protected]

www.xpcc.com

©2016 Xtreme Power Conversion Corporation. All Rights Reserved. TX90/T90.01U (Rev 6/06/16)

Protect your business.

Xtreme Power 200A Parallel Tie Panel

Maintenance bypass breaker 200ATX90: break-before-makeT90: make-before-break

Output to critical loadsLoad breakers are optionalTX90: 240/120V* (L1, L2, N, G)T90: 208 or 240V (L1, L2, G)

TX90 or T90UPS module

TX90 or T90UPS module

TX90 or T90UPS module

TX90 or T90UPS module

Module output breakers10kVA: 60A6kVA: 40A

Utility Input Panel (provided by others)

Utility input feed

TX90/T90 parallel system diagram

MODEL SELECTION GUIDEMODEL NUMBER (Non-isolated)

MODEL NUMBER (Isolated)T90-06K24

TX90-06K24T90-12K24

TX90-12K24T90-18K24

TX90-18K24T90-24K24

TX90-24K24CAPACITY Power rating 6kVA (5.4kW) 12kVA (10.8kW) 18kVA (16.2kW) 24kVA (21.6kW)

Power rating (redundant) N/A 6kVA (5.4kW) N+1 12kVA (10.8kW) N+1 18kVA (16.2kW) N+1INPUT Voltage 160–280VAC*

Scalable All models are scalable to 24kVA or 18kVA N+1OUTPUT Voltage TX90: 240/120VAC standard (100/110/115/200/208/230VAC are optional)

T90: 208VAC nominal (200/220/230/240VAC selectable)BATTERY Battery runtime (standard models) 7 minutes at 100% load / 21 minutes at 50% load

Battery runtime (TX90-6KXR model) 14 minutes at 100% load / 33 minutes at 50% loadPHYSICAL UPS dimensions (W x D x H) 11.4 x 25.4 x 29.5 in

Number of UPS modules 1 2 3 4Optional external battery cabinets 11.4 x 25.4 x 29.5 in (EBP960, EBP940, EBP920)Tie panel dimensions (W x D x H) 15.5 x 4.5 x 40.5 in

APPROVALS UL1778, cUL, CE, FCC ASYSTEM INCLUDES UPS modules with internal batteries, 200A parallel tie panel with 40A module

output breakers, parallel communication cables.

MODEL NUMBER (Non-isolated)

MODEL NUMBER (Isolated)T90-10K40

TX90-10K40T90-20K40

TX90-20K40T90-30K40

TX90-30K40T90-40K40

TX90-40K40CAPACITY Power rating 10kVA (9kW) 20kVA (18kW) 30kVA (27kW) 40kVA (36kW)**

Power rating (redundant) N/A 10kVA (9kW) N+1 20kVA (18kW) N+1 30kVA (27kW) N+1INPUT Voltage 160–280VAC*

Scalable All models are scalable to 40kVA or 30kVA N+1OUTPUT Voltage TX90: 240/120VAC standard (100/110/115/200/208/230VAC are optional)

T90: 208VAC nominal (200/220/230/240VAC selectable)BATTERY Battery runtime (internal) 4 minutes at 100% load / 13 minutes at 50% load

Battery runtime (TX90-10KXR model) 7 minutes at 100% load / 18 minutes at 50% loadPHYSICAL UPS dimensions (W x D x H) 11.4 x 25.4 x 29.5 in (T90) 11.4 x 25.4 x 34.7 in (TX90)

Number of UPS modules 1 2 3 4Optional external battery cabinets 11.4 x 25.4 x 29.5 in (EBP960, EBP940, EBP920)Tie panel dimensions (W x D x H) 15.5 x 4.5 x 40.5 in

APPROVALS UL1778, cUL, CE, FCC ASYSTEM INCLUDES UPS modules with internal batteries, 200A parallel tie panel with 60A module

output breakers, parallel communication cables.*Depending on load level; **Xtreme parallel tie panel is limited to 160A.