OWNER
YAMHILL CARLTON SCHOOL DISTRICT
120 N LARCH PLACE
YAMHILL, OR 97148
CONTACT: TAMI ZIGLER
YAMHILL CARLTON HIGH SCHOOLVOLUNTARY SEISMIC STRENGTHENING
YAMHILL CARLTON SCHOOL DISTRICT
275 N MAPLE ST
YAMHILL, OR 97148
ARCHITECT
BBL ARCHITECTS
200 NORTH STATE STREET
LAKE OSWEGO, OR 97034
CONTACT: DOUGLASS PRUITT, AIA
G0.1
SHEET
ID
SHEET TITLE
COVER SHEET AND SHEET INDEX
G0.2 ABBREVIATIONS AND SYMBOLS
S2.1 ATTIC/LOW ROOF STRENGTHENING PLAN
LOWER ROOF STRENGTHENING PLAN - BID ALTERNATE
WOOD DETAILS
S2.2
S2.3
S7.1
SHEET INDEX
LEGEND:
ISSUED AS PART OF SET
NOT PART OF ISSUED SET
ISSUED FOR INFORMATION ONLY
DRAWINGS ISSUED
P:\W
RK
2020\20088.00 - Y
am
hill C
arlton H
igh S
chool S
eism
ic R
ehabilitation\C
AD
\20088.00_G
0.1.dw
g 04/29/21 11:37 U
SE
R
drawn by
issue date
revisions
checked by
wrk job number
27
5 N
M
AP
LE
S
T
YA
MH
IL
L, O
R 9
71
48
20088.00
VO
LU
NT
AR
Y S
EIS
MIC
S
TR
EN
GT
HE
NIN
G
YA
MH
IL
L C
AR
LT
ON
H
IG
H S
CH
OO
L
04/29/2021
MM
BID SET
KKS
ROOF STRENGTHENING PLAN
SCALE:
1
VICINITY MAP AND SITE MAP
NTS
NORTH
G0.1
COVER SHEET
AND SHEET
INDEX
SITE LOCATION
D2.2
ROOF PLANA1.1
STRUCTURAL ENGINEER
WRK ENGINEERS, INC.
215 W. 12TH STREET, SUITE 202
VANCOUVER, WA 98660
CONTACT: BRIAN KNIGHT, P.E., S.E.
G0.3 CODE SUMMARY
SPECIAL INSPECTION TABLES
S0.1 GENERAL STRUCTURAL NOTES
NONSTRUCTURAL DETAILSS8.1
LEVEL 2 REFLECTED CEILING DEMOLITION PLAN
D2.1
ELEVATIONSS3.1
PARTIAL BASEMENT NONSTRUCTURAL BRACING PLANS2.4
ATTIC NONSTRUCTURAL BRACING PLANS2.5
WOOD DETAILSS7.2
PARTIAL LEVEL 1 REFLECTED CEILING DEMOLITION PLAN
D2.3
PARTIAL BASEMENT DEMOLITION PLAN
A5.1 DETAILS
S0.2
DEMOLITION ROOF PLAN
D2.4
BID
S
ET
04/2
9/2
02
1
A5.2 DETAILS
G0.4 SITE PLAN
A
MATERIAL TYPES
COMPACTED EARTH
UNDISTURBED EARTH
ROCK FILL, GRAVEL
NON-SHRINK GROUT/SAND
STEEL
LIMITS OF OPENING
SECTION NUMBER
DRAWING WHERE FOUND
LINE OF SECTION CUT
DIRECTION OF VIEW
DETAIL NUMBER
DRAWING WHERE
FOUND
AREA OF DETAIL
AREA OF PARTIAL
PLAN OR PARTIAL
ELEVATION
DIRECTION OF VIEW
ELEVATION NUMBER
DRAWING WHERE ELEVATION
IS FOUND
SECOND FLOOR
EL. XXX'-X"
INDICATES HEIGHT
ABOVE DATUM
DRAWING SIDE
DRAWING WHERE
CONTINUATION IS FOUND
MATCH LINE
SEE SX.XX
EXISTING CONCRETE
INDICATES ORIENTATION
OF PLYWOOD SHEATHING
EXTENT OF SHEATHING
NEW PLYWOOD
NO or # NUMBER
(A) ABOVE
AB ANCHOR BOLT
AC ASPHALT CONCRETE
ACI AMERICAN CONCRETE INSTITUTE
ADDL ADDITIONAL
ADH ADHESIVE
ADJ ADJACENT
AESS ARCHITECTURALLY EXPOSED STRUCTURAL STEEL
AGGR AGGREGATE
AHR ANCHOR
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
AISI AMERICAN IRON AND STEEL INSTITUTE
ALUM ALUMINUM
ALT ALTERNATE
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
APA AMERICAN PLYWOOD ASSOCIATION
APPROX APPROXIMATE
ARCH ARCHITECTURAL
ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
ATC ACOUSTIC TILE CEILING
AVG AVERAGE
AWG AMERICAN WIRE GAUGE
AWPA AMERICAN WOOD PROTECTION ASSOCIATION
AWPB AMERICAN WOOD PRESERVERS BUREAU
AWS AMERICAN WELDING SOCIETY
(B) BELOW
BTWN BETWEEN
BF BRACED FRAME
BLDG BUILDING
BLKG BLOCKING
BM or BMS BEAM or BEAMS
BN BOUNDARY NAILING
BOT BOTTOM
B.O. CONC BOTTOM OF CONCRETE
B.O. FTG BOTTOM OF FOOTING
B.O. SLAB BOTTOM OF SLAB
B.O. STL BOTTOM OF STEEL
BRG BEARING
BS BOTH SIDES
BSMT BASEMENT
C CHANNEL
CG CENTER OF GRAVITY
CGS CENTER OF GRAVITY OF STRAND
CIP CAST-IN-PLACE
CJ CONSTRUCTION JOINT
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL or COLS COLUMN OR COLUMNS
CONC CONCRETE
CONN CONNECTION
CONSTR CONSTRUCTION
CONT CONTINUOUS
CLT CROSS-LAMINATED TIMBER
CSK COUNTERSINK
CTR CENTER
CVN CHARPY V-NOTCH
d PENNY (NAIL SIZE)
DBA DEFORMED BAR ANCHOR
DBL DOUBLE
DBM DROP BEAM
DEG DEGREE
DEMO DEMOLITION
DET or DETS DETAIL OR DETAILS
DF DOUGLAS FIR-LARCH
DIA DIAMETER
DIAG DIAGONAL
DIM or DIMS DIMENSION or DIMENSIONS
DIST DISTANCE
DK or DKG DECK or DECKING
DN DOWN
DO DITTO
DWL or DWLS DOWEL or DOWELS
DWG or DWGS DRAWING or DRAWINGS
(E) EXISTING
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
EMBED EMBEDMENT
EN EDGE NAILING
EOR ENGINEER OF RECORD
EOS EDGE OF SLAB
EQ EQUAL
EQUIP EQUIPMENT
ES EACH SIDE
EV EVERY
EW EACH WAY
EXC EXCAVATION
EXP EXPANSION
EXT EXTERIOR
FA FRAMING ANGLE
FBM FLUSH BEAM
FDN FOUNDATION
FF FAR FACE
FHA FEDERAL HIGHWAY ADMINISTRATION
FIN FINISH
FINF FINISHED FACE
FIN FLR FINISH FLOOR
FLR or FLRS FLOOR or FLOORS
FN FIELD NAILING
FO FACE OF
FOC FACE OF CONCRETE
FOS FACE OF STUDS
FP FIREPROOFING
FRP FIBER REINFORCED POLYMER
FRT FIRE RETARDANT TREATED
FS FAR SIDE
FT FOOT or FEET
FTG or FTGS FOOTING or FOOTINGS
GA GAUGE
GALV GALVANIZED
GLZ GLAZING
GLB GLU-LAMINATED BEAM
GR GRADE
GRND GROUND
GSN GENERAL STRUCTURAL NOTE
GT GIRDER TRUSS
GYP BD GYPSUM BOARD
HDG HOT-DIPPED GALVANIZED
HDR HEADER
HK or HKS HOOK or HOOKS
HORIZ HORIZONTAL
HP HIGH POINT
HSB HIGH STRENGTH BOLTS
HSS HOLLOW STRUCTURAL SECTION
HT HEIGHT
IAPMO INTERNATIONAL ASSOCIATION OF PLUMBING AND
MECHANICAL OFFICIALS
IBC INTERNATIONAL BUILDING CODE
ICC INTERNATIONAL CODE COUNCIL
ID INSIDE DIAMETER
INFO INFORMATION
INT INTERIOR
JST or JSTS JOIST or JOISTS
JT JOINT
KO KNOCK OUT
2L DOUBLE ANGLE
L ANGLE
LB or LBS POUND OR POUNDS
ℓd DEVELOPMENT LENGTH
ℓdb HOOK DEVELOPMENT LENGTH
LFRS LATERAL FORCE RESISTING SYSTEM
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LOC LOCATION
LONG LONGITUDINAL
LPT LOW POINT
ℓs LAP SPLICE LENGTH
LT LIGHT
LVL LAMINATED VENEER LUMBER
LSL LAMINATED STRAND LUMBER
LWC LIGHT WEIGHT CONCRETE
MAX MAXIMUM
MB MACHINE BOLT
MC MISCELLANEOUS CHANNEL
MECH MECHANICAL
MEP MECHANICAL, ELECTRICAL AND PLUMBING DOCUMENTS
MEZZ MEZZANINE
MF MOMENT FRAME
MFR MANUFACTURER
MIA MASONRY INSTITUTE OF AMERICA
MIN MINIMUM
MISC MISCELLANEOUS
MTD MOUNTED
MTL METAL
N NORTH
NF NEAR FACE
NIC NOT IN CONTRACT
NOM NOMINAL
NS NEAR SIDE
NTS NOT TO SCALE
NWC NORMAL WEIGHT CONCRETE
OC ON CENTER
OD OUTSIDE DIAMETER
OPNG OPENING
OPP OPPOSITE
OSB ORIENTED STRAND BOARD
OWSJ OPEN WEB STEEL JOIST
PAF POWDER ACTUATED FASTENER
PC or PCS PIECE OR PIECES
PEF PANEL EDGE FASTENERS
PERP PERPENDICULAR
PJP PARTIAL JOINT PENETRATION
PL PLATE
PLYWD PLYWOOD
PMGT PRE-MANUFACTURED GIRDER TRUSS
PMT PRE-MANUFACTURED TRUSS
PR PAIR
PRCST PRECAST
PLF POUNDS PER LINEAR FOOT
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSL PARALLEL STRAND LUMBER
PT PRESERVATIVE TREATED or POST-TENSIONED
PTI POST-TENSIONING INSTITUTE
PTN PARTITION
PVC POLYVINYL CHLORIDE
R RADIUS
REBAR REINFORCING BAR
REF REFERENCE
REINF REINFORCED or REINFORCING
REQD REQUIRED
RET RETURN
REV REVISE or REVISION
RO ROUGH OPENING
RSJ ROLLED STEEL JOIST
(S) SIMPSON
SAD SEE ARCHITECTURAL DRAWINGS
SCHED SCHEDULE
SECT SECTION
SFRS SEISMIC FORCE RESISTING SYSTEM
SHT SHEET
SHTHG SHEATHING
SIM SIMILAR
SL SLOPE
SMF STEEL MOMENT FRAME
SMS SHEET METAL SCREW
SOG SLAB ON GRADE
SPEC or SPECS SPECIFICATION OR SPECIFICATIONS
SQ SQUARE
SS STAINLESS STEEL
STAG STAGGERED
STD STANDARD
STIF STIFFENER
STL STEEL
STRUCT STRUCTURAL
STS SELF TAPPING SCREW
SUB SUBSTITUTE
SUSP SUSPENDED
SW SHEAR WALL
SYMM SYMMETRY OR SYMMETRICAL
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
TEMP TEMPORARY
THK THICK
THD THREAD or THREADED
THRU THROUGH
TJI WOOD I-JOIST OR TRUSS JOIST
T.O. TOP OF
T.O. CONC TOP OF CONCRETE
T.O. FTG TOP OF FOOTING
T.O. STL TOP OF STEEL
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
URM UN-REINFORCED MASONRY
VENT VENTILATE
VERT VERTICAL
VIF VERIFY IN FIELD
W or WF WIDE FLANGE
W/ WITH
WD WOOD
WHS WELDED HEADED STUD
W/O WITHOUT
WP WORK POINT
WT WEIGHT or WIDE TEE
XS EXTRA STRONG
XXS DOUBLE EXTRA STRONG
X
X
DESCRIPTION
LINE OF DETAIL CUT
DIRECTION OF VIEW
INDICATES EXTENTS OF EXISTING
FRAMING MEMBERS OR OTHER
STRUCTURAL COMPONENTS
INDICATES EXISTING WOOD
POST/COLUMN
INDICATES EXISTING WOOD
POST/COLUMN BELOW
INDICATES EXISTING CONCRETE WALL
INDICATES STRUCTURAL WALL
INDICATES EXISTING WALL BELOW
INDICATES STEP IN SLAB/FRAMING
INDICATES CHANGE IN SLOPE
INDICATES SHEAR WALL HOLDOWN
X
SY.Z
X
SY.Z
X
SY.Z
X
SY.Z
X
SY.Z
SHEAR WALL PER
SCHEDULE
HOLDOWN PER
SCHEDULE
SIDE OF SHEATHING
FOR SHEAR WALL
INDICATES EXTENT
OF WOOD SHEAR
WALL
NEW CONCRETE
REFERENCE SYMBOLS
REVISION NUMBER - SEE
REVISION HISTORY ON TITLE
BLOCK OF EACH DWG.
X
AREA OF REVISION
INDICATES EXISTING WOOD STUD WALL
ABBREVIATIONS
REVISION
GRID LINES
MATCH LINE
ELEVATION
PARTIAL PLAN OR ELEVATION
SECTION
DETAIL
ELEVATION MARKER
PLYWOOD SHEATHING
OPENING
WALL DESIGNATIONS
SHEAR WALL TAG
COLUMN DESIGNATIONS
FRAMING
MISC
GENERAL CONSTRUCTION NOTES
1. UNLESS OTHERWISE APPROVED BY THE DISTRICT, THE CONTRACTOR SHALL PERFORM ALL CONSTRUCTION
BETWEEN 7:00 AM AND 4:00 PM MONDAY THROUGH FRIDAY. NO WORK IS ALLOWED ON PUBLIC HOLIDAYS
OBSERVED BY THE STATE OF OREGON.
2. THE CONTRACTOR SHALL PERFORM ALL WORK NECESSARY TO COMPLETE THE PROJECT IN ACCORDANCE
WITH THE APPROVED PLANS AND SPECIFICATIONS INCLUDING SUCH INCIDENTALS AS MAY BE NECESSARY
TO MEET THE REQUIREMENTS OF THE DISTRICT AND/OR OTHER APPLICABLE AGENCIES FOR A COMPLETE
AND FULLY FUNCTIONAL PROJECT. RESTORATION SHALL BE EQUAL TO OR BETTER THAN THE ORIGINAL
CONDITION, AND TO THE SATISFACTION OF THE DISTRICT.
3. ANY INSPECTION BY THE ENGINEER OF RECORD, THE DISTRICT, OR OTHER AGENCIES SHALL NOT RELIEVE
THE CONTRACTOR IN ANY WAY FROM ANY OBLIGATION TO PERFORM THE WORK IN STRICT COMPLIANCE
WITH THE APPLICABLE REGULATIONS, SPECIFICATIONS, CODES, STANDARDS, AND REQUIREMENTS OF THE
DISTRICT OR OTHER APPLICABLE AGENCIES.
4. THE CONTRACTOR AND/OR SUBCONTRACTOR SHALL HAVE A MINIMUM OF ONE (1) SET OF APPROVED
CONSTRUCTION PLANS, AND CONTRACT SPECIFICATIONS ON THE JOBSITE AT ALL TIMES DURING
CONSTRUCTION.
5. EXISTING CONDITIONS AND UTILITIES ON CONSTRUCTION DOCUMENTS OR THE PLANS ARE SHOWN
WITHOUT GUARANTEE OF ACCURACY. THE CONTRACTOR SHALL NOTIFY THE ENGINEER OF RECORD
IMMEDIATELY IN CASES WHERE ACTUAL LOCATION OR INFORMATION DISCOVERED VARIES, OR NOT SHOWN,
FROM THOSE DEPICTED IN THE CONTRACT DOCUMENTS OR THE PLANS.
6. THE CONTRACTOR SHALL KEEP THE WORKSITE CLEAN, SAFE AND ACCESSIBLE AT THE END OF EACH WORK
DAY. MINIMIZE NOISE LEVEL AT ALL TIMES. DUST CONTROL IS REQUIRED. PROTECT CARPET, FURNITURE,
FIXTURES AND EQUIPMENT AT ALL TIMES. REMOVE, TRANSPORT AND STORE EQUIPMENT AND FURNISHINGS
AS NOTED ON DEMOLITION PLANS OFFSITE AT AS DIRECTED BY THE DISTRICT. REINSTALL THEM FOLLOWING
SEISMIC RETROFIT WORK.
7. ALL EXISTING ROOF AREA SHALL BE PROTECTED. ACCESS TO ROOF AREA ACROSS PARAPETS SHALL BE BY
LADDERS OR LIFTS. CONSTRUCTION MATERIAL ON ROOF AREA SHALL NOT BE OVERLOADED TO CREATE
STRESS AND ROOF COLLAPSE. TEMPORARY PROTECTION ENCLOSURES MUST BE COMPLETED PRIOR TO
THE START OF DEMOLITION OR INTERIOR CONSTRUCTION.
8. THE CONTRACTOR SHALL RECORD ANY APPROVED DEVIATION IN CONSTRUCTION AND AS-BUILT
INFORMATION ON A SET OF THE APPROVED PLANS. THE CONTRACTOR SHALL KEEP THE FIELD RECORD
DRAWINGS UP TO DATE AT ALL TIMES AND SHALL HAVE THEM AVAILABLE FOR INSPECTION BY THE DISTRICT
UPON REQUEST. THE CONTRACTOR SHALL SUBMIT ACCURATE AND COMPLETE AS-BUILT DRAWINGS TO THE
DISTRICT AT THE END OF ALL CONSTRUCTION.
9. THE CONTRACTOR IS RESPONSIBLE FOR MANAGING CONSTRUCTION ACTIVITIES AND TO KEEP THE
DISTRICT'S PROJECT MANAGER AND INSPECTOR INFORMED OF THEIR PROPOSED WORK. PROVIDE WEEKLY
PROJECT SCHEDULES AND TASKS AT WEEKLY CONSTRUCTION MEETINGS WITH THE DISTRICT.
10. THE CONTRACTOR SHALL INFORM THE CITY BUILDING DIVISION FOR ALL REQUIRED INSPECTIONS. THE
CONTRACTOR SHALL ALSO NOTIFY THE DISTRICT'S INDEPENDENT TESTING FIRM AND SPECIALTY
INSPECTOR TO PERFORM TESTS AND STRUCTURAL INSPECTIONS AS SHOWN ON CONSTRUCTION SHEET
S0.2. ALL TESTS SHALL BE WITNESSED BY THE DISTRICT.
INDICATES SHEAR WALL BELOW
EXISTING PLYWOOD
INDICATES EXISTING CONCRETE
COLUMN
G0.2
ABBREVIATIONS
AND SYMBOLS
P:\W
RK
2020\20088.00 - Y
am
hill C
arlton H
igh S
chool S
eism
ic R
ehabilitation\C
AD
\20088.00_G
0.2.dw
g 04/29/21 11:37 U
SE
R
drawn by
issue date
revisions
checked by
wrk job number
27
5 N
M
AP
LE
S
T
YA
MH
IL
L, O
R 9
71
48
20088.00
VO
LU
NT
AR
Y S
EIS
MIC
S
TR
EN
GT
HE
NIN
G
YA
MH
IL
L C
AR
LT
ON
H
IG
H S
CH
OO
L
04/29/2021
MM
BID SET
KKS
EXISTING BRICK OR MASONRY
B
C
6'-3
"
6 5 4 3
70'-6
1
2
"
19'-7
1
4
"
10'-0" 10'-6"
5.5 3.5
19'-9
1
4
"
10'-8"
B.5
12
'-7
"
1
D
20
'-0
"
3
2'-0
"
(E
) R
AM
P
BOILER ROOM
2
P:\W
RK
2020\20088.00 - Y
am
hill C
arlton H
igh S
chool S
eism
ic R
ehabilitation\C
AD
\20088.00_D
2.2.dw
g 04/29/21 11:36 U
SE
R
drawn by
issue date
revisions
checked by
wrk job number
27
5 N
M
AP
LE
S
T
YA
MH
IL
L, O
R 9
71
48
20088.00
VO
LU
NT
AR
Y S
EIS
MIC
S
TR
EN
GT
HE
NIN
G
YA
MH
IL
L C
AR
LT
ON
H
IG
H S
CH
OO
L
04/29/2021
MM
BID SET
KKS
SCALE:
1
PARTIAL BASEMENT DEMOLITION PLAN
1/4"=1'-0"
NORTH
SCALE:
KEYPLAN
NTS
D2.2
PARTIAL
BASEMENT
DEMOLITION
PLAN
PLAN NOTES:
1. EXISTING CONDITIONS ARE SHOWN WITHOUT GUARANTEE OF ACCURACY. NOTIFY THE EOR IF
THE CONDITIONS DISCOVERED IN THE FIELD ARE DIFFERENT THAN THOSE DEPICTED IN THE
CONTRACT DOCUMENTS.
2. THE DRAWINGS CONTAIN REFERENCE TO EXISTING CONDITIONS, MATERIALS, FURNISHINGS,
AND EQUIPMENT. THE INFORMATION IS DEVELOPED FROM EXISTING DRAWINGS AND SITE
AND BUILDING OBSERVATIONS, AND IS PROVIDED FOR REFERENCE ONLY. THE CONTRACTOR
SHALL VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS. IT IS TO BE ASSUMED THE
BUILDING IS NOT LEVEL, SQUARE, OR PLUMB.
3. NOTIFY THE EOR IF DECAY, CORROSION, OR OTHER DAMAGE TO THE EXISTING STRUCTURE
IS DISCOVERED.
4. CONTRACTOR SHALL COORDINATE PROTECTION OF (E) STRUCTURE AND (E) FURNISHING.
TEMPORARY PROTECTION SHALL BE IN PLACE PRIOR TO THE START OF ANY DEMOLITION, OR
INTERIOR CONSTRUCTION.
5. DO NOT REMOVE TEMPORARY PROTECTION UNTIL INTERIOR CONSTRUCTION IS COMPLETED.
6. (E) FURNISHINGS TO BE REMOVED AND STORED OR TEMPORARILY RELOCATED DURING
CONSTRUCTION SHALL BE RETURNED. COORDINATE LOCATION AND CONSTRUCTION
REQUIREMENTS W/ YAMHILL CARLTON SD.
7. FURNITURE SUCH AS STUDENTS DESKS AND CHAIRS, AND MAINTENANCE AND JANITORIAL
EQUIPMENT ARE NOT SHOWN. COORDINATE REMOVAL AND TEMPORARY STORAGE OF THE
ITEMS WITH YAMHILL CARLTON SD.
8. INDICATES AREA OF DEMOLITION.
KEYED NOTES:
1
DEMO (2) LAYERS (E) GYPSUM BOARD CEILING TO PERFORM WORK. REPLACE
W/ (2) LAYERS 5/8" TYPE X GYPSUM BOARD W/ FINISH TO MATCH EXISTING. SEE
SPECIFICATION.
DEMO (E) FURRING WALL TO INSTALL HSS STRONGBACKS. DEMO (E) FLOOR
FINISH AT HSS BASEPLATE, KEEP FLOOR FINISH DEMO EXTENT WITHIN FURRING
WALL WIDTH. REBUILD FURRING WALL ONCE WORK IS COMPLETE. PROVIDE 5/8"
TYPE X GYPSUM BOARD W/ FINISH TO MATCH EXISTING. SEE SPECIFICATION.
DISCONNECT (E) PIPING AS REQUIRED TO INSTALL BOILER ANCHORAGE PER
SHEET S2.4. REINSTALL ONCE WORK IS COMPLETE.
2
3
E
H
F
G
B
C
D
18
'-1
0"
20
'-0
"2
0'-0
"2
0'-0
"1
9'-6
"
20
'-6
1
4
"
13
0'-1
0
1
4
"
70'-6
1
2
"
6 5 4 3
19'-7
1
4
"
10'-0" 10'-6"
5.5 3.5
19'-9
1
4
"
10'-8"
A.5
12
'-0
"
1 1
3
4'-0" 4'-0"
4'-0
"
1
2
2
(E) ATTIC
ACCESS
LADDER
2 2
2'-0"
MIN
2'-0"
MIN
2'-0
"
MIN
2'-0
"
MIN
P:\W
RK
2020\20088.00 - Y
am
hill C
arlton H
igh S
chool S
eism
ic R
ehabilitation\C
AD
\20088.00_D
2.3.dw
g 04/29/21 11:36 U
SE
R
drawn by
issue date
revisions
checked by
wrk job number
27
5 N
M
AP
LE
S
T
YA
MH
IL
L, O
R 9
71
48
20088.00
VO
LU
NT
AR
Y S
EIS
MIC
S
TR
EN
GT
HE
NIN
G
YA
MH
IL
L C
AR
LT
ON
H
IG
H S
CH
OO
L
04/29/2021
MM
BID SET
KKS
SCALE:
1
LEVEL 2 REFLECTED CEILING DEMOLITION PLAN
1/8"=1'-0"
NORTH
SCALE:
KEYPLAN
NTS
D2.3
LEVEL 2
REFLECTED
CEILING
DEMOLITION
PLAN
PLAN NOTES:
1. EXISTING CONDITIONS ARE SHOWN WITHOUT GUARANTEE OF ACCURACY. NOTIFY THE EOR IF
THE CONDITIONS DISCOVERED IN THE FIELD ARE DIFFERENT THAN THOSE DEPICTED IN THE
CONTRACT DOCUMENTS.
2. THE DRAWINGS CONTAIN REFERENCE TO EXISTING CONDITIONS, MATERIALS, FURNISHINGS,
AND EQUIPMENT. THE INFORMATION IS DEVELOPED FROM EXISTING DRAWINGS AND SITE
AND BUILDING OBSERVATIONS, AND IS PROVIDED FOR REFERENCE ONLY. THE CONTRACTOR
SHALL VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS. IT IS TO BE ASSUMED THE
BUILDING IS NOT LEVEL, SQUARE, OR PLUMB.
3. NOTIFY THE EOR IF DECAY, CORROSION, OR OTHER DAMAGE TO THE EXISTING STRUCTURE
IS DISCOVERED.
4. CONTRACTOR SHALL COORDINATE PROTECTION OF (E) STRUCTURE AND (E) FURNISHING.
TEMPORARY PROTECTION SHALL BE IN PLACE PRIOR TO THE START OF ANY DEMOLITION, OR
INTERIOR CONSTRUCTION.
5. DO NOT REMOVE TEMPORARY PROTECTION UNTIL INTERIOR CONSTRUCTION IS COMPLETED.
6. (E) FURNISHINGS TO BE REMOVED AND STORED OR TEMPORARILY RELOCATED DURING
CONSTRUCTION SHALL BE RETURNED. COORDINATE LOCATION AND CONSTRUCTION
REQUIREMENTS W/ YAMHILL CARLTON SD.
7. INDICATES AREA OF DEMOLITION.
KEYED NOTES:
1
REMOVE (E) SUSPENDED CEILING TILE AS REQUIRED AND DEMO (2) LAYERS (E)
GYPSUM BOARD CEILING TO PERFORM WORK. REPLACE GYPSUM BOARD
CEILING W/ 5/8" TYPE X GYPSUM BOARD AND REINSTALL SUSPENDED CEILING
TILES ONCE WORK IS COMPLETED.
WHERE OCCURS, DEMO (2) LAYERS (E) GYPSUM BOARD CEILING TO PERFORM
WORK. REPLACE W/ 5/8" TYPE X GYPSUM BOARD ONCE WORK IS COMPLETED.
DEMO (E) GYPSUM WALLBOARD IN ATTIC SPACE TO PERFORM WORK.
2
3
H
G
20
'-6
1
4
"
103'-6"
6 5 4 3
19'-7
1
4
"
10'-0" 10'-6"
6.5 2.53.55.5
16'-5
3
4
" 19'-9
1
4
"
10'-8"
16'-5
3
4
"
1
4'-0
"
TY
P
3
2 2
3
1
4'-0
"
MIN
4'-0
"
MIN
F
19
'-6
"
P:\W
RK
2020\20088.00 - Y
am
hill C
arlton H
igh S
chool S
eism
ic R
ehabilitation\C
AD
\20088.00_D
2.4.dw
g 04/29/21 11:36 U
SE
R
drawn by
issue date
revisions
checked by
wrk job number
27
5 N
M
AP
LE
S
T
YA
MH
IL
L, O
R 9
71
48
20088.00
VO
LU
NT
AR
Y S
EIS
MIC
S
TR
EN
GT
HE
NIN
G
YA
MH
IL
L C
AR
LT
ON
H
IG
H S
CH
OO
L
04/29/2021
MM
BID SET
KKS
SCALE:
1
PARTIAL LEVEL 1 REFLECTED CEILING DEMOLITION PLAN
1/8"=1'-0"
NORTH
SCALE:
KEYPLAN
NTS
D2.4
PARTIAL LEVEL 1
REFLECTED
CEILING
DEMOLITION
PLAN
KEYED NOTES:
1
DEMO (2) LAYERS (E) GYPSUM BOARD CEILING IN ORDER TO PERFORM WORK.
REPLACE W/ 5/8" TYPE X GYPSUM BOARD ONCE WORK IS COMPLETED.
DEMO (E) DIRECT APPLIED CEILING TILE AS REQUIRED, (2) BAYS MINIMUM, IN
ORDER TO INSTALL TENSION TIE. REPLACE ONCE WORK IS COMPLETED.
APPROXIMATE LOCATION OF NEW ATTIC SHEAR WALL AND TENSION TIE
CONNECTION. SEE DETAIL 3/S7.2 AND ELEVATION 2/S3.1.
2
3
PLAN NOTES:
1. EXISTING CONDITIONS ARE SHOWN WITHOUT GUARANTEE OF ACCURACY. NOTIFY THE EOR IF
THE CONDITIONS DISCOVERED IN THE FIELD ARE DIFFERENT THAN THOSE DEPICTED IN THE
CONTRACT DOCUMENTS.
2. THE DRAWINGS CONTAIN REFERENCE TO EXISTING CONDITIONS, MATERIALS, FURNISHINGS,
AND EQUIPMENT. THE INFORMATION IS DEVELOPED FROM EXISTING DRAWINGS AND SITE
AND BUILDING OBSERVATIONS, AND IS PROVIDED FOR REFERENCE ONLY. THE CONTRACTOR
SHALL VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS. IT IS TO BE ASSUMED THE
BUILDING IS NOT LEVEL, SQUARE, OR PLUMB.
3. NOTIFY THE EOR IF DECAY, CORROSION, OR OTHER DAMAGE TO THE EXISTING STRUCTURE
IS DISCOVERED.
4. CONTRACTOR SHALL COORDINATE PROTECTION OF (E) STRUCTURE AND (E) FURNISHING.
TEMPORARY PROTECTION SHALL BE IN PLACE PRIOR TO THE START OF ANY DEMOLITION, OR
INTERIOR CONSTRUCTION.
5. DO NOT REMOVE TEMPORARY PROTECTION UNTIL INTERIOR CONSTRUCTION IS COMPLETED.
6. (E) FURNISHINGS TO BE REMOVED AND STORED OR TEMPORARILY RELOCATED DURING
CONSTRUCTION SHALL BE RETURNED. COORDINATE LOCATION AND CONSTRUCTION
REQUIREMENTS W/ YAMHILL CARLTON SD.
7. STORAGE OF FURNISHINGS AND OTHER FIXTURES TO BE PROVIDED BY GENERAL
CONTRACTOR.
8. FURNITURE SUCH AS STUDENTS DESKS AND CHAIRS, AND MAINTENANCE AND JANITORIAL
EQUIPMENT ARE NOT SHOWN. COORDINATE REMOVAL AND TEMPORARY STORAGE OF THE
ITEMS WITH YAMHILL CARLTON SD.
9. INDICATES AREA OF DEMOLITION.
GENERAL STRUCTURAL NOTES
1.0 - GENERAL
1. THIS PROJECT CONSISTS OF A VOLUNTARY SEISMIC STRENGTHENING FOR A PORTION OF THE
YAMHILL CARLTON HIGH SCHOOL.
2. MATERIALS AND WORKMANSHIP TO CONFORM WITH THE 2019 EDITION OF THE OREGON
STRUCTURAL SPECIALTY (OSSC) BUILDING CODE, WITH YAMHILL COUNTY AMENDMENTS, THE
REQUIREMENTS OF THE OREGON SEISMIC REHABILITATION GRANT PROGRAM AND THE
REQUIREMENTS OF THE CONTRACT DOCUMENTS.
3. THESE GENERAL NOTES SUPPLEMENT THE REQUIREMENTS OF THE PROJECT SPECIFICATIONS. IN
CASE OF CONFLICT BETWEEN THE PLANS AND SPECIFICATIONS, CONTACT THE OWNER'S
REPRESENTATIVE.
4. REFERENCE TO CODES, RULES, REGULATIONS, STANDARDS, MANUFACTURER'S INSTRUCTIONS OR
REQUIREMENTS OF REGULATORY AGENCIES IS TO THE LATEST PRINTED EDITION OF EACH IN
EFFECT AT THE DATE OF SUBMISSION OF BID UNLESS THE DOCUMENT DATE IS SHOWN.
5. DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION. WHERE CONDITIONS
ARE NOT SPECIFICALLY INDICATED BUT ARE OF SIMILAR CHARACTER TO DETAILS SHOWN, USE
SIMILAR DETAILS OF CONSTRUCTION, SUBJECT TO REVIEW BY THE ENGINEER OF RECORD.
6. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING THE WORK OF ALL TRADES AND FOR
CHECKING DIMENSIONS. NOTIFY THE OWNER'S REPRESENTATIVE OF ANY DISCREPANCIES AND
RESOLVE BEFORE PROCEEDING WITH THE WORK.
7. DO NOT SCALE THE DRAWINGS.
8. PROVIDE MEASURES NECESSARY TO PROTECT THE STRUCTURE DURING CONSTRUCTION. SUCH
MEASURES INCLUDE, BUT MAY NOT BE LIMITED TO, BRACING AND SHORING FOR LOADS DURING
CONSTRUCTION. ADEQUATELY BRACE STRUCTURE AND ALL STRUCTURAL COMPONENTS AGAINST
WIND, LATERAL EARTH AND SEISMIC FORCES UNTIL THE PERMANENT LATERAL-FORCE RESISTING
SYSTEMS HAVE BEEN INSTALLED. RETAIN A REGISTERED CIVIL ENGINEER WHOM IS PROPERLY
QUALIFIED TO DESIGN BRACING, SHORING, ETC. VISITS TO THE SITE BY THE OWNER'S
REPRESENTATIVE WILL NOT INCLUDE OBSERVATION OF THE ABOVE NOTED ITEMS.
9. INFORMATION SHOWN ON THE DRAWINGS RELATED TO EXISTING CONDITIONS REPRESENTS THE
PRESENT KNOWLEDGE, BUT WITHOUT GUARANTEE OF ACCURACY. REPORT CONDITIONS THAT
CONFLICT WITH THE CONTRACT DOCUMENTS TO THE OWNER'S REPRESENTATIVE. DO NOT
DEVIATE FROM THE CONTRACT DOCUMENTS WITHOUT WRITTEN DIRECTION FROM THE OWNER'S
REPRESENTATIVE.
10. REFER TO ARCHITECTURAL DRAWINGS FOR SIZE AND LOCATION OF FLOOR, ROOF AND WALL
OPENINGS NOT SHOWN ON THE STRUCTURAL DRAWINGS. COORDINATE THE SIZE AND LOCATION
OF OPENINGS ASSOCIATED WITH, BUT NOT LIMITED TO, ELECTRICAL, MECHANICAL AND PLUMBING
TRADES. SUBMIT FINAL SIZING AND LOCATION REQUIREMENTS OF OPENINGS TO THE OWNER'S
REPRESENTATIVE FOR REVIEW.
11. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR PROVIDING A SAFE PLACE TO WORK AND
MEETING THE REQUIREMENTS OF ALL APPLICABLE JURISDICTIONS. EXECUTE WORK TO ENSURE
THE SAFETY OF PERSONS AND ADJACENT PROPERTY AGAINST DAMAGE BY FALLING DEBRIS AND
OTHER HAZARDS IN CONNECTION WITH THIS WORK.
12. APPLY, PLACE, ERECT OR INSTALL ALL PRODUCTS AND MATERIALS IN ACCORDANCE WITH THE
MANUFACTURER'S INSTRUCTIONS.
13. ELEMENTS SHOWN, BUT NOTED AS "BY OTHERS", ARE SHOWN FOR COORDINATION PURPOSES
ONLY AND HAVE NOT BEEN DESIGNED BY WRK ENGINEERS. WRK ENGINEERS WILL REVIEW
ELEMENTS DESIGNED BY OTHERS AND SUBMITTED AS A DEFERRED SUBMITTAL ONLY FOR
GENERAL CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS AND PROJECT SPECIFICATIONS.
1.1 - DESIGN CRITERIA
1. APPLICABLE CODE: 2018 IBC, ASCE 41-17 & OSSC 2019
2. SEISMIC DESIGN (LINEAR STATIC PROCEDURE):
PERFORMANCE OBJECTIVE: LIMITED SAFETY FOR BSE-2E SEISMIC HAZARD
WHERE
S
XS
= 0.832
S
X1
= 0.623
S
A
= 0.830
SOIL SITE CLASS "D" (ASSUMED)
BASE SHEAR V = C
1
C
2
C
M
S
A
W = 1.162W
WHERE
C
1
C
2
= 1.4
C
M
= 1.0
2.0 - FOUNDATION AND SITE WORK
1. LOCATE AND PROTECT EXISTING UTILITIES DURING AND/OR AFTER CONSTRUCTION.
2. NOTIFY THE OWNER'S REPRESENTATIVE IF ANY BURIED STRUCTURES NOT INDICATED, SUCH AS
CESSPOOLS, CISTERNS, FOUNDATIONS, ETC., ARE FOUND.
3. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR EXCAVATION PROCEDURES INCLUDING LAGGING,
SHORING, UNDERPINNING AND PROTECTION OF EXISTING CONSTRUCTION.
3.0 - STRUCTURAL STEEL
1. REFERENCE STANDARDS (CURRENTLY ADOPTED EDITIONS)
A. AISC "MANUAL OF STEEL CONSTRUCTION - ALLOWABLE STRESS DESIGN".
B. AISC "CODE OF STANDARD PRACTICE FOR STEEL BUILDING AND BRIDGES".
C. RCSC "SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS".
D. AWS D1.1 "STRUCTURAL WELDING CODE - STEEL".
E. AWS D1.6 "STRUCTURAL WELDING CODE - STAINLESS STEEL".
2. STRUCTURAL STEEL TO CONFORM TO THE FOLLOWING STRUCTURAL STEEL MEMBER TABLE, UNO:
3. HOT DIP GALVANIZE IN ACCORDANCE WITH ASTM A123 AND ASTM A153, CLASS C, STRUCTURAL
STEEL AND FASTENERS THAT ARE PERMANENTLY EXPOSED TO THE WEATHER. REPAIR
GALVANIZING AFTER WELDING IN ACCORDANCE WITH ASTM A780 TO ACHIEVE ORIGINAL
GALVANIZING THICKNESS.
4. STRUCTURAL STEEL AND CONNECTIONS EXPOSED TO VIEW IN THE COMPLETED BUILDING ARE
DESIGNATED ARCHITECTURALLY EXPOSED STRUCTURAL STEEL (AESS).
5. ARC-WELDING ELECTRODES/FILLER METALS TO BE LOW HYDROGEN TYPES E7XTX, E7XTXX OR
E70XXX MINIMUM AS APPLICABLE.
6. WELDERS TO BE CERTIFIED BY AWS AND THE GOVERNING JURISDICTION.
7. WHERE FIELD WELDING IS NOTED, THE DESIGNATION IS GIVEN AS A SUGGESTED CONSTRUCTION
PROCEDURE ONLY. CONTRACTOR SHALL BE SOLEY RESPONSIBLE FOR DETERMINING IF WELDS
ARE PLACED IN SHOP OR FIELD.
8. CONNECT ALL MEMBERS WITH HIGH-STRENGTH BOLTS.
A. BEARING TYPE CONNECTIONS:
a. PROVIDE TYPE X BOLTS AT ALL LOCATIONS.
b. PROVIDE HARDENED WASHERS UNDER ELEMENTS TO BE TIGHTENED. PROVIDE
NUTS & WASHERS IN ACCORDANCE W/ THE STRUCTURAL STEEL MEMBER TABLE.
c. TIGHTEN BOLTS TO A SNUG TIGHT CONDITION.
B. DO NOT WELD HIGH-STRENGTH BOLTS.
9. ALL BOLT HOLES TO BE STANDARD SIZED HOLES UNLESS NOTED OTHERWISE.
10. PROVIDE BEVELED WASHERS AT BOLT HEADS OR NUTS BEARING ON SLOPING SURFACES.
11. CONTRACTOR TO DESIGN AND PROVIDE ERECTION AIDS (BOLTS, CLIPS, SHIMS, SEATS, ETC)
REQUIRED TO FACILITATE CONSTRUCTION.
12. EMBEDDED STEEL ASSEMBLIES: HOT-DIP GALVANIZE WHERE NOTED ON DRAWINGS.
13. APPLY BITUMINOUS ASPHALT COATING TO ALL BURIED STEEL ELEMENTS.
3.1 - PRODUCT APPROVALS
1. FOR ITEMS IN THE CONSTRUCTION DOCUMENTS NOT NOTED WITH A SPECIFIC PRODUCT TYPE OR
MANUFACTURER, THE CONTRACTOR SHALL PROVIDE THE PRODUCT SPECIFIED IN THE TABLE
BELOW.
2. THE FOLLOWING PRODUCTS SHALL BE INSTALLED PER THE REQUIREMENTS OF THE REFERENCED
PRODUCT APPROVALS BELOW, UNO.
3. AT CONTRACTOR'S OPTION, PRODUCTS MAY BE SUBSTITUTED FOR LIKE PRODUCT PER THE
SCHEDULE BELOW IF APPROVED BY THE ENGINEER OF RECORD.
3.2 - POST-INSTALLED ANCHORS
1. INSTALL ACCORDING TO MANUFACTURER'S SPECIFICATIONS.
2. INSTALL WITH IBC SPECIAL INSPECTION ACCORDING TO SPECIAL INSPECTION PROGRAM, SEE
SHEET S0.2.
3. PROVIDE GALVANIZED CARBON STEEL ANCHORS, UNO.
4. LOCATE REINFORCEMENT AND CONFIRM FINAL ANCHOR LOCATIONS PRIOR TO FABRICATING
PLATES, MEMBERS, OR OTHER STEEL ASSEMBLIES ATTACHED WITH POST-INSTALLED ANCHORS.
5. ADHESIVE ANCHORS AND DOWELS INSTALLED INTO CONCRETE AND GROUT-FILLED MASONRY
UNITS SHALL BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
6. ANCHORS AND DOWELS INSTALLED INTO HOLLOW MASONRY UNITS AND UNREINFORCED BRICK
MASONRY (URM) SHALL BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS. USE SCREENS AS
SPECIFIED BY THE MANUFACTURER.
7. THE DIAMETER OF THE HOLES IS PER THE MANUFACTURER'S INSTRUCTIONS.
8. DRILL HOLES FOR ANCHORS AND DOWELS IN UNREINFORCED BRICK MASONRY WITH A NON-IMPACT
ROTARY DRILL.
9. REMOVE GREASE, OIL, RUST, AND OTHER LAITANCE FROM RODS AND DOWELS PRIOR TO
INSTALLATION.
10. PRIOR TO INSTALLING ANCHORS OR DOWELS, WIRE BRUSH HOLES TO REMOVE RESIDUE, BLOW
OUT WITH OIL-FREE COMPRESSED AIR, AND ALLOW HOLE TO DRY.
11. DOWELS: ASTM A615 GRADE 60 REINFORCING STEEL.
12. INSERT THE ANCHOR OR DOWEL IN THE HOLE WITH A TWISTING MOTION TO THE REQUIRED
EMBEDMENT DEPTH. DO NOT PUMP THE ANCHOR OR DOWEL IN AND OUT OF THE HOLE.
13. WEDGE BARS TIGHT AND CENTERED IN THE HOLE WITH WOODEN WEDGES (GOLF TEES) TO HOLD IT
IN PLACE UNTIL THE ADHESIVE SETS.
14. IF REINFORCEMENT IS ENCOUNTERED DURING DRILLING, ABANDON AND SHIFT THE HOLE LOCATION
TO AVOID THE REINFORCEMENT. PROVIDE A MINIMUM OF 2 ANCHOR DIAMETERS OR 1 INCH,
WHICHEVER IS LARGER, OF SOUND CONCRETE BETWEEN THE DOWEL AND THE ABANDONED HOLE.
FILL THE ABANDONED HOLE WITH NON-SHRINK GROUT. IF THE ANCHOR OR DOWEL MAY NOT BE
SHIFTED AS NOTED ABOVE, THE ENGINEER OF RECORD WILL DETERMINE A NEW LOCATION.
15. 5% OF ALL ADHESIVE ANCHORS IN EXISTING URM SHALL BE TENSION TESTED AND 20% OF ALL
ADHESIVE ANCHORS IN EXISTING URM SHALL BE TORQUE TESTED AS FOLLOWS:
NOTE:
SEE 2018 INTERNATIONAL EXISTING BUILDING CODE SECTION A107.4 FOR FURTHER INFORMATION
ON ANCHOR TESTING AS REFERENCED IN ICC-ESR REPORT.
16. REPLACE ANCHORS AND DOWELS THAT FAIL DURING TESTING AND RETEST. IF MORE THAN 10% OF
THE TESTED DOWELS AND ANCHORS FAIL TO ACHIEVE THE SPECIFIED TEST LOAD, TEST 100% OF
THE DOWELS AND ANCHORS INSTALLED IN THE LAST 2 DAYS OF ANCHOR INSTALLATION.
4.0 - ROUGH CARPENTRY
1. FRAMING LUMBER: DOUGLAS FIR (COAST REGION) GRADED AND MARKED IN ACCORDANCE WITH
THE STANDARD GRADING RULES NO. 17 OF THE WEST COAST LUMBER INSPECTION BUREAU
(WCLIB) OR WESTERN LUMBER GRADING RULES, OF THE WESTERN WOOD PRODUCTS ASSOCIATION
(WWPA). USE LUMBER OF THE FOLLOWING GRADES:
2. MAXIMUM MOISTURE CONTENT: 19%
3. PROVIDE SOLID BLOCKING (SAME DEPTH OF MEMBER) AT ALL POINTS OF BEARING (MAXIMUM
SPACING OF 8 FEET OC) AT JOIST WITH A 5:1 OR GREATER DEPTH-TO-THICKNESS RATIO OR WHERE
1 EDGE OF JOIST IS NOT ATTACHED TO SHEATHING, WALLBOARD, BRACING, ETC.
4. DO NOT USE WOOD SHINGLE SHIMS UNDER STUDS, JOISTS, BEAMS, OR POSTS.
5. PANEL SHEATHING: IDENTIFY WOOD STRUCTURAL PANELS WITH THE APPROPRIATE TRADEMARK OF
APA-THE ENGINEERED WOOD ASSOCIATION AND MEET THE REQUIREMENTS OF THE VOLUNTARY
PRODUCT STANDARD PS-1-95 AND APA PRP-108 PERFORMANCE STANDARD.
A. PANEL SHEATHING SHALL BE EXPOSURE 1.
B. PLYWOOD PANELS SHALL BE 5-PLY MINIMUM.
C. PLYWOOD SHALL BE CC GRADE AT LOCATIONS EXPOSED TO WEATHER; CD GRADE
ELSEWHERE.
D. PROVIDE THE FOLLOWING GRADE AND PANEL INDEX RATINGS:
6. SUBSTITUTION OF ORIENTED STRAND BOARD (OSB) FOR PLYWOOD IS ACCEPTABLE IF THE OSB:
A. CONFORMS WITH APA PERFORMANCE STANDARDS FOR WOOD BASED STRUCTURAL USE
PANELS PRP-108 AND UNITED STATES PRODUCT STANDARD PS2-92.
B. IS MANUFACTURED WITH EXTERIOR GLUE.
C. HAS A LOAD/SPAN RATING INDEX EQUAL TO PLYWOOD.
D. BEARS THE APA TRADEMARK.
7. PROVIDE PRESSURE-TREATED PLYWOOD WHERE INDICATED ON DRAWINGS. CONFORM WITH AWPA
STANDARD C11. MARK SHEETS WITH AWPB.
8. PLYWOOD LAYOUT AND INSTALLATION:
A. LAY OUT PLYWOOD SHEATHING WITH END JOINTS STAGGERED, UNLESS NOTED OTHERWISE.
B. LAY OUT PLYWOOD TO ELIMINATE WIDTHS LESS THAN 1 FOOT AT ROOFS, UNLESS ALL
EDGES OF UNDERSIZED PIECES ARE SUPPORTED BY BLOCKING.
C. PROVIDE PANEL SPACINGS ACCORDING TO APA RECOMMENDATIONS.
D. PROTECT FLOOR AND ROOF SHEATHING FROM EXTREME WET CONDITIONS.
E. NAIL ACCORDING TO SCHEDULE AND DRAWINGS.
4.1 - FRAMING CONNECTORS
1. ROUGH HARDWARE:
A. NAILS: COMMON WIRE NAILS, FEDERAL SPECIFICATION FF-N-105, STANDARD LENGTHS UNO.
USE HOT-DIPPED ZINC-COATED GALVANIZED NAILS FOR EXTERIOR INSTALLATIONS AND
WHEN IN CONTACT WITH PRESSURE TREATED OR FIRE-RETARTANT LUMBER.
B. BOLTS AND THREADED RODS: ASTM A307, HEXAGONAL HEAD MACHINE BOLTS WITH ASTM
A563 NUTS. USE MALLEABLE IRON WASHERS UNDER HEAD AND NUT WHEN IN CONTACT
WITH WOOD.
C. LAG SCREWS: ASTM A307, ANSI/ASME STANDARD B18.2.1. USE ANSI B18.22.1 WASHERS
UNDER HEAD WHEN IN CONTACT WITH WOOD.
D. SCREWS: ASTM A307, ANSI/ASME STANDARD B18.6.1. USE CADMIUM-PLATED PAN OR ROUND
HEADED SCREWS AT STEEL-TO-WOOD AND WOOD-TO-WOOD CONNECTIONS.
E. MISCELLANEOUS STEEL: ASTM A36.
F. BOLTS, NUTS, WASHERS, STRAPS AND OTHER HARDWARE EXPOSED TO THE WEATHER OR
PRESERVATIVE TREATED WOOD SHALL BE HOT-DIPPED GALVANIZED OR STAINLESS STEEL.
G. UNO, FRAMING CONNECTIONS SHALL COMPLY WITH THE FOLLOWING NAILING SCHEDULE:
2. NAILING:
A. DRIVE NAILS PERPENDICULAR TO THE GRAIN, UNO.
B. PRE-DRILL HOLES TO
3
4
INCH OF NAIL DIAMETER WHERE SPECIFIED AND WHEN WOOD
TENDS TO SPLIT.
C. AIR-DRIVEN NAILS TO BE FULL-HEADED NAILS. DO NOT OVERDRIVE NAILS.
D. PANEL SHEATHING:
a. AT FLOOR AND ROOF SHEATHING, USE RING SHANK NAILS. USE SMOOTH SHANK
NAILS AT WALLS.
b. USE OF MACHINE NAILING IS SUBJECT TO A SATISFACTORY JOB SITE
DEMONSTRATION FOR EACH PROJECT AND APPROVAL BY THE OWNER'S
REPRESENTATIVE. NAIL HEADS THAT PENETRATE THE OUTER PLY MORE THAN
WOULD BE NORMAL FOR A HAND HAMMER OR IF THE MINIMUM ALLOWABLE EDGE
DISTANCES ARE NOT MAINTAINED THE INSTALLATION IS UNSATISFACTORY.
MACHINE NAILING IS NOT APPROVED IN
5
16
INCH OR LESS SHEATHING.
3. BOLT AND SCREW INSTALLATION:
A. DRILL BOLT HOLES A MAXIMUM OF
1
16
INCH LARGER IN DIAMETER THAN THE BOLT NOMINAL
DIAMETER.
B. DRILL PRE-BORED LEAD HOLES FOR WOOD SCREWS AS FOLLOWS.
a. DRILL LEAD HOLE FOR THE SHANK TO A DEPTH EQUAL TO THE LENGTH OF THE
UNTHREADED PORTION IN THE MAIN MEMBER. USE A DRILL BIT
7
8
INCH THE
DIAMETER OF THE WOOD SCREW.
b. EXTEND THE LEAD HOLE FOR THE THREADED PORTION OF THE SCREW WITH A
DRILL BIT WHOSE DIAMETER IS
7
8
INCH THE DIAMETER OF THE SCREW AT THE ROOT
OF THE THREAD.
c. INSERT THE SCREW INTO LEAD HOLE BY TURNING. DO NOT DRIVE WITH A HAMMER.
d. LUBRICATE WITH SOAP OR BEESWAX TO FACILITATE INSTALLATION.
C. DRILL PRE-BORED LEAD HOLES FOR LAG SCREWS AS FOLLOWS:
a. DRILL LEAD HOLE FOR THE SHANK TO A DEPTH EQUAL TO THE LENGTH OF THE
UNTHREADED PORTION IN THE MAIN MEMBER. USE A DRILL BIT OF THE SAME
DIAMETER AS THE LAG SCREW.
b. EXTEND THE LEAD HOLE FOR THE THREADED PORTION OF THE LAG SCREW WITH A
DRILL BIT WHOSE DIAMETER IS 60% OF THE NOMINAL LAG SCREW DIAMETER.
c. INSERT LAG SCREW INTO LEAD HOLE BY TURNING. DO NOT DRIVE WITH A HAMMER.
LUBRICATE WITH SOAP OR BEESWAX TO FACILITATE INSTALLATION.
4. FRAMING CONNECTORS: SIMPSON STRONG-TIE OR APPROVED.
A. FILL ALL NAIL HOLES WITH NAILS AS SPECIFIED BY THE CONNECTOR MANUFACTURER, UNO.
B. CONNECTIONS IN CONTACT WITH PRESSURE-TREATED LUMBER SHALL BE HOT-DIPPED
ZINC-COATED GALVANIZED.
5.0 - STRUCTURAL TESTS, INSPECTIONS, AND OBSERVATIONS
1. AN INDEPENDENT TESTING AGENCY AND SPECIAL INSPECTORS WILL BE RETAINED BY THE OWNER
TO PERFORM TESTS AND INSPECTIONS AS SHOWN ON SHEET S0.2. PROVIDE ACCESS AND FURNISH
SAMPLES TO THE AGENCY AS REQUIRED BY THE CONTRACT DOCUMENTS.
2. IF INITIAL TESTS OR INSPECTIONS MADE BY THE OWNER'S TESTING AGENCY REVEAL THAT ANY
PORTION OF THE WORK DOES NOT COMPLY WITH THE CONTRACT DOCUMENTS, ADDITIONAL TESTS,
INSPECTIONS, AND NECESSARY REPAIRS WILL BE MADE AT THE CONTRACTOR'S EXPENSE.
3. THE ITEMS IDENTIFIED ON S0.2 REQUIRE TESTS AND INSPECTIONS IN ACCORDANCE WITH THE
"STRUCTURAL TESTS AND INSPECTIONS" REQUIREMENTS OF THE CODE OF THE GOVERNING
JURISDICTION AS NOTED.
4. NOTIFY THE ENGINEER OF RECORD 72 HOURS IN ADVANCE AND PROVIDE ACCESS FOR THE
FOLLOWING STRUCTURAL OBSERVATIONS:
A. WOOD FRAMING
a. GENERAL
b. SHEAR WALLS
c. DIAPHRAGMS AND COLLECTORS
ITEM APPROVED PRODUCTS ICC# IAPMO#
ADHESIVE ANCHOR
TO MASONRY/URM
SIMPSON ET-HP
HILTI HIT-HY
DEWALT AC100+ GOLD
ESR-3638
ESR-4143
ESR-4105
N/A
N/A
N/A
SCREW ANCHOR
TO CONCRETE
SIMPSON TITEN HD
HILTI KWIK HUS EZ
ESR-2713
ESR-3027
N/A
N/A
MEMBER WOOD/GRADE
DIMENSIONAL LUMBER (UNO) DF #2
BEAMS 5
1
2
" AND WIDER
DF SELECT
STRUCTURAL
BEAMS 4
1
2
" AND NARROWER
DF #1
POSTS, 6X6 & LARGER DF SELECT
STRUCTURAL
POSTS, 4X6 & SMALLER DF #1
BACKING, STRIPPING AND
FURRING
CONSTRUCTION
PANEL
THICKNESS
MINIMUM
GRADE
ROOF/FLOOR
RATING
15
32
"
STRUCTURAL 32/16
ROUGH FRAMING CONNECTIONS
CONNECTION NAILS
STUDS TO PLATES - END NAIL (2) 16d COMMON OR (3) 10d
STUDS TO PLATES - TOE NAIL (4) 10d
ROD DIAMETER TENSION TEST LOAD
TORQUE TEST
LOAD
3/4" 1500# 60 FT-LB
TOP PLATES & BOTTOM PLATES -
SPIKE TOGETHER
10d AT 8" OC
LAP AND INTERSECTIONS (4) 10d EACH SIDE JOINT
FLOOR, ROOF, CEILING JOISTS-
TO PLATES OR BEAMS - TOE NAIL
(2) 10d
BLOCKING TO PLATE - TOE NAIL (2) 10d
BLOCKING TO JOISTS - EACH END (2) 10d
CORNER STUDS 10d AT 12" OC
2x LAMINATED BEAMS (2) ROWS STAGGERED 10d
AT 12" OC
MEMBER TABLE
SECTIONS TYPE
ROLLED SHAPES:
CHANNELS, ANGLES, AND
OTHER
ASTM A36
PLATES:
OTHER ASTM A36
COLD FORMED HOLLOW
STRUCTURAL SECTION (HSS)
ASTM A500 GRADE B
CONNECTORS AND STUDS:
HIGH STRENGTH BOLTS A325
MACHINE BOLTS (HEX HEAD) ASTM A307
ANCHOR RODS ASTM F1554, GRADE 36
THREADED AND HANGER
ROD
ASTM A36
HARDENED WASHERS ASTM F436
UN-HARDENDED WASHERS ASTM F844
PLAIN WASHERS ANSI B18.22.1
BEVELED WASHERS ANSI B18.23.1
P:\W
RK
2020\20088.00 - Y
am
hill C
arlton H
igh S
chool S
eism
ic R
ehabilitation\C
AD
\20088.00_S
0.1.dw
g 04/29/21 11:37 U
SE
R
drawn by
issue date
revisions
checked by
wrk job number
27
5 N
M
AP
LE
S
T
YA
MH
IL
L, O
R 9
71
48
20088.00
VO
LU
NT
AR
Y S
EIS
MIC
S
TR
EN
GT
HE
NIN
G
YA
MH
IL
L C
AR
LT
ON
H
IG
H S
CH
OO
L
04/29/2021
MM
BID SET
KKS
S0.1
GENERAL
STRUCTURAL
NOTES
INSPECTION TASKS
INSPECTION TASKS AND DOCUMENTATION FOR SPECIAL INSPECTION SHALL BE PROVIDED BY THE QUALITY
ASSURANCE SPECIAL INSPECTOR AS SHOWN IN TABLE 1 THROUGH TABLE 3. THE FOLLOWING ENTRIES
ARE USED IN THE TABLES:
CONTINUOUS: THE INSPECTOR SHALL BE IN THE AREA OF WORK FULL-TIME, AND SHALL INSPECT IN A
TIMELY MANNER.
PERIODIC: THE INSPECTOR SHALL BE PRESENT IN THE AREA OF WORK PART-TIME. THE INSPECTOR MUST
BE PRESENT INTERMITTENTLY DURING THE WORK, AND AT THE COMPLETION OF THE WORK.
TABLE 1
REQUIRED STRUCTURAL SPECIAL INSPECTIONS
SYSTEM or MATERIAL
INSPECTION
REMARKS
IBC CODE
REFERENCE
CODE or STANDARD
REFERENCE
FREQUENCY
Continuous Periodic
FABRICATORS
FABRICATORS 1704.2.5.2
SPECIAL INSPECTIONS REQUIRED BY SECTION 1705
ARE NOT REQUIRED WHERE THE WORK IS DONE ON
THE PREMISES OF A FABRICATOR REGISTERED AND
APPROVED TO PERFORM SUCH WORK WITHOUT
SPECIAL INSPECTION. APPROVAL SHALL BE BASED
UPON REVIEW OF THE FABRICATOR'S WRITTEN
PROCEDURAL AND QUALITY CONTROL MANUALS
AND PERIODIC AUDITING OF FABRICATION
PRACTICES BY A NATIONALLY RECOGNIZED
ACCREDITING AUTHORITY. AT COMPLETION OF
FABRICATION, THE APPROVED FABRICATOR SHALL
SUBMIT A CERTIFICATE OF COMPLIANCE TO THE
BUILDING OFFICIAL STATING THAT THE WORK WAS
PERFORMED IN ACCORDANCE WITH THE APPROVED
CONSTRUCTION DOCUMENTS.
CONCRETE
INSPECTION OF ANCHORS INSTALLED IN
HARDENED CONCRETE
1909.1
TABLE 1705.3
ACI 318:
3.8.6, 8.1.3, 21.1.8
X
SPECIAL INSPECTIONS APPLY TO ANCHOR PRODUCT
NAME, TYPE, AND DIMENSIONS, HOLE DIMENSIONS,
COMPLIANCE WITH DRILL BIT REQUIREMENTS,
CLEANLINESS OF THE HOLE AND ANCHOR,
ADHESIVE EXPIRATION DATE, ANCHOR/ADHESIVE
INSTALLATION, ANCHOR EMBEDMENT, AND
TIGHTENING TORQUE
P:\W
RK
2020\20088.00 - Y
am
hill C
arlton H
igh S
chool S
eism
ic R
ehabilitation\C
AD
\20088.00_S
0.2.dw
g 04/29/21 11:37 U
SE
R
drawn by
issue date
revisions
checked by
wrk job number
27
5 N
M
AP
LE
S
T
YA
MH
IL
L, O
R 9
71
48
20088.00
VO
LU
NT
AR
Y S
EIS
MIC
S
TR
EN
GT
HE
NIN
G
YA
MH
IL
L C
AR
LT
ON
H
IG
H S
CH
OO
L
04/29/2021
MM
BID SET
KKS
MATERIAL VERIFICATION OF STRUCTURAL
STEEL
1705.2.1
2203.1
TABLE 1705.2
ASTM A6
ASTM STANDARDS
SPECIFIED IN
CONSTRUCTION
DOCUMENTS
AISC 360 N3.2
AISC 360 A3.1
AISC 360 M5.5
X CERTIFIED MILL TEST REPORTS
FOR OTHER STEEL, IDENTIFICATION MARKINGS
TO CONFORM TO ASTM STANDARDS SPECIFIED
IN THE APPROVED CONSTRUCTION DOCUMENTS
TABLE 1705.2
APPLICABLE ASTM
MATERIAL STANDARDS
X MANUFACTURER'S CERTIFIED TEST REPORTS
MATERIAL VERIFICATION OF WELD FILLER
METALS
TABLE 1705.2
AISC 360 N3.2
AISC 360 A3.5
APPLICABLE AWS A5
DOCUMENTS
X MANUFACTURER'S CERTIFICATE OF COMPLIANCE
COMPLETE AND PARTIAL JOINT PENETRATION
GROOVE WELDS
TABLE 1705.2
AWS D1.1
SECTION 6
X ALL WELDS VISUALLY INSPECTED PER AWS D1.1 6.9
SINGLE PASS FILLET WELDS LESS THAN OR
EQUAL TO 5/16"
TABLE 1705.2
AWS D1.1
SECTION 6
X ALL WELDS VISUALLY INSPECTED PER AWS D1.1 6.9
MATERIAL VERIFICATION OF ANCHOR BOLTS
AND THREADED RODS
AISC 360 N3.2
AISC 360 A3.4
ASTM STANDARDS
SPECIFIED IN
CONSTRUCTION
DOCUMENTS
X MANUFACTURER'S CERTIFIED TEST REPORTS
VERIFYING USE OF PROPER WPS'S AISC 360 N3.2 COPY OF WELDING PROCEDURE SPECIFICATIONS
VERIFYING WELDER AND WELDING INSPECTOR
QUALIFICATIONS
1705.2.2.1 X COPY OF QUALIFICATION CARDS
WOOD
FABRICATION OF PREFABRICATED STRUCTURAL
ELEMENTS
1705.5 X
REFER TO INSPECTION OF FABRICATOR
REQUIREMENTS
INSPECTION OF ANCHORS INSTALLED IN
UNREINFORCED MASONRY
3406.1 IEBC A107.4 X
POST INSTALLED ANCHORS
S0.2
SPECIAL
INSPECTION
TABLES
STEEL
FABRICATION OF STRUCTURAL ELEMENTS 1704.2.5.2 AISC 360 N2 X
REFER TO INSPECTION OF FABRICATOR
REQUIREMENTS
APPROVAL BASED ON NATIONALLY RECOGNIZED
ACCREDITING AUTHORITY
MATERIAL VERIFICATION OF HIGH-STRENGTH
BOLTS, NUTS, AND WASHERS
AISC 360 A3.3
AISC 360 N 3.2
ASTM STANDARDS
SPECIFIED IN
CONSTRUCTION
DOCUMENTS
RCSC 2.1
X MANUFACTURER'S CERTIFIED TEST REPORTS
TABLE 2
REQUIRED STRUCTURAL SPECIAL INSPECTIONS
SYSTEM or MATERIAL
INSPECTION
REMARKS
IBC CODE
REFERENCE
CODE or STANDARD
REFERENCE
FREQUENCY
Continuous Periodic
STRUCTURAL WOOD
FIELD GLUING OF DIAPHRAGM AND SHEAR WALL
ELEMENTS FOR SEISMIC
FORCE-RESISTING-SYSTEMS
1705.11.2
X
CONNECTIONS FOR DIAPHRAGM CHORDS,
COLLECTORS, BRACING, AND SHEAR WALL
ANCHORAGE AND HOLDOWNS
X ALL CONNECTIONS VISUALLY INSPECTED
FASTENING OF DIAPHRAGM AND SHEAR WALL
SHEATHING WITH EDGE NAILING < 4"
X
SPECIAL INSPECTION IS NOT REQUIRED WHEN FASTENER
SPACING IS GREATER THAN 4" ON CENTER FOR WOOD SHEAR
WALLS, DIAPHRAGMS, NAILING, BUILDING AND OTHER
COMPONENTS IN THE SEISMIC FORCE-RESISTING SYSTEM.
TABLE 3
REQUIRED SPECIAL INSPECTIONS for SEISMIC RESISTANCE (SEISMIC CATEGORIES C, D, E, F)
SYSTEM or MATERIAL
INSPECTION
REMARKS
IBC CODE
REFERENCE
CODE or STANDARD
REFERENCE
FREQUENCY
Continuous Periodic
E
H
F
G
A
B
C
D
23
'-0
"1
8'-1
0"
20
'-0
"2
0'-0
"2
0'-0
"1
9'-6
"
20
'-6
1
4
"
15
3'-1
0
1
4
"
(E
) 2
x
1
2
A
T
2
4
" O
C
(E
) 2
x
1
2
A
T
2
4
" O
C
(E
) 2
x
1
2
A
T
2
4
" O
C
(E
) 2
x
1
2
A
T
2
4
" O
C
(E
) 2
x
1
2
A
T
2
4
" O
C
70'-6
1
2
"
6 5 4 3
19'-7
1
4
"
10'-0" 10'-6"
MA
TC
HL
IN
E
SE
E S
2.3
MA
TC
HL
IN
E
SE
E S
2.3
A
(E) RIDGE (E) RIDGE
(E
) R
ID
GE
(E) BOWSTRING TRUSS
(E) BOWSTRING TRUSS
(E) BOWSTRING TRUSS
(E) BOWSTRING TRUSS
(E) BOWSTRING TRUSS
A
1
S3.1
12
S7.1
12
S7.1
2
S7.2
2
S7.2
9
S7.1
9
S7.1
1
S7.2
1
S7.2
3.55.5
A.5
12
'-0
"
19'-9
1
4
"
10'-8"
DR
AG
T
RU
SS
DR
AG
T
RU
SS
2
S3.1
2
S3.1
2
(E) ATTIC
ACCESS
LADDER
2
11
(E) RIDGE(E) RIDGE
SIM
LO
W R
OO
FA
TT
IC
SCALE:
1
ATTIC/LOW ROOF STRENGTHENING PLAN
1/8"=1'-0"
NORTH
SCALE:
KEYPLAN
NTS
S2.1
ATTIC/LOW ROOF
STRENGTHENING
PLAN
P:\W
RK
2020\20088.00 - Y
am
hill C
arlton H
igh S
chool S
eism
ic R
ehabilitation\C
AD
\20088.00_S
2.1.dw
g 04/29/21 11:37 U
SE
R
drawn by
issue date
revisions
checked by
wrk job number
27
5 N
M
AP
LE
S
T
YA
MH
IL
L, O
R 9
71
48
20088.00
VO
LU
NT
AR
Y S
EIS
MIC
S
TR
EN
GT
HE
NIN
G
YA
MH
IL
L C
AR
LT
ON
H
IG
H S
CH
OO
L
04/29/2021
MM
BID SET
KKS
PLAN NOTES:
1. EXISTING CONDITIONS ARE SHOWN WITHOUT GUARANTEE OF ACCURACY. NOTIFY THE EOR IF
THE CONDITIONS DISCOVERED IN THE FIELD ARE DIFFERENT THAN THOSE DEPICTED IN THE
CONTRACT DOCUMENTS.
2. THE DRAWINGS CONTAIN REFERENCE TO EXISTING CONDITIONS, MATERIALS, FURNISHINGS,
AND EQUIPMENT. THE INFORMATION IS DEVELOPED FROM EXISTING DRAWINGS AND SITE
AND BUILDING OBSERVATIONS, AND IS PROVIDED FOR REFERENCE ONLY. THE CONTRACTOR
SHALL VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS. IT IS TO BE ASSUMED THE
BUILDING IS NOT LEVEL, SQUARE, OR PLUMB.
3. NOTIFY THE EOR IF DECAY, CORROSION, OR OTHER DAMAGE TO THE EXISTING STRUCTURE
IS DISCOVERED.
4. SEE SHEET S7.1 FOR WOOD DETAILS AND SHEAR WALL SCHEDULE.
5. CONTRACTOR TO PROTECT ALL (E) CONDUIT AND DUCTS.
6. GRIDLINE SHOWN AT FACE OF STUD WALL.
KEYED NOTES:
1
INDICATES (E) PLYWOOD SHTHG OVER (E) 1x DECKING. ADD 10d AT 6" OC PANEL
EDGE NAILING. SEE 2/S7.1 FOR PLYWOOD DIAPHRAGM NAILING.
(E) TRUSS TO RECEIVE PLYWOOD SHEATHING PER 2/S3.1 SHALL BE TRUSS THAT
IS 15'-0" MINIMUM FROM GRIDLINE 3.5 (GRIDLINE 5.5 AT SIM)
2
70'-6
1
2
"
(E) BOWSTRING TRUSS
(E) BOWSTRING TRUSS
(E) BOWSTRING TRUSS
(E) BOWSTRING TRUSS
(
E
)
R
O
O
F
J
O
I
S
T
S
A
T
1
6
"
O
C
(E) BOWSTRING TRUSS
(E
) 2
x
1
2
R
A
F
T
E
R
S
A
T
2
4
" O
C
, T
Y
P
E
H
F
G
A
B
C
D
18
'-1
0"
20
'-0
"2
0'-0
"2
0'-0
"1
9'-6
"
20
'-6
1
4
"
15
3'-1
0
1
4
"
6 5 4 3
10'-0"
MA
TC
HL
IN
E
SE
E S
2.3
MA
TC
HL
IN
E
SE
E S
2.3
(E) RIDGE (E) RIDGE
(E
) R
ID
GE
1
16'-0" 16'-0"
15
'-0
"1
5'-0
"1
2'-0
"
1
11
S7.1
11
S7.1
8
S7.1
8
S7.1
23
'-0
"
19'-7
1
4
"
10'-6"
3.55.5
A.5
12
'-0
"
19'-9
1
4
"
10'-8"
TYP
4
S7.1
TYP
4
S7.1
7
S7.1
TYP
10
S7.1
10
'-6
"
10
'-6
"
SCALE:
1
ROOF STRENGTHENING PLAN
1/8"=1'-0"
NORTH
SCALE:
KEYPLAN
NTS
S2.2
ROOF
STRENGTHENING
PLAN
PLAN NOTES:
1. EXISTING CONDITIONS ARE SHOWN WITHOUT GUARANTEE OF ACCURACY. NOTIFY THE EOR IF
THE CONDITIONS DISCOVERED IN THE FIELD ARE DIFFERENT THAN THOSE DEPICTED IN THE
CONTRACT DOCUMENTS.
2. THE DRAWINGS CONTAIN REFERENCE TO EXISTING CONDITIONS, MATERIALS, FURNISHINGS,
AND EQUIPMENT. THE INFORMATION IS DEVELOPED FROM EXISTING DRAWINGS AND SITE
AND BUILDING OBSERVATIONS, AND IS PROVIDED FOR REFERENCE ONLY. THE CONTRACTOR
SHALL VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS. IT IS TO BE ASSUMED THE
BUILDING IS NOT LEVEL, SQUARE, OR PLUMB.
3. NOTIFY THE EOR IF DECAY, CORROSION, OR OTHER DAMAGE TO THE EXISTING STRUCTURE
IS DISCOVERED.
4. SEE SHEET S7.1 FOR WOOD DETAILS.
5. CONTRACTOR TO PROTECT ALL (E) CONDUIT AND DUCTS.
6. GRIDLINE SHOWN AT FACE OF STUD WALL.
7. INDICATES OUTLINE OF BLOCKED ROOF DIAPHRAGM. PROVIDE BLKG AT PANEL
EDGES.
8. INDICATES BID ALTERNATE SCOPE.
KEYED NOTES:
1
INDICATES (E) PLYWOOD SHTHG OVER (E) 1x DECKING. ADD 10d AT 6" OC PANEL
EDGE NAILING. SEE 2/S7.1 FOR PLYWOOD DIAPHRAGM NAILING.
P:\W
RK
2020\20088.00 - Y
am
hill C
arlton H
igh S
chool S
eism
ic R
ehabilitation\C
AD
\20088.00_S
2.2.dw
g 04/29/21 11:37 U
SE
R
drawn by
issue date
revisions
checked by
wrk job number
27
5 N
M
AP
LE
S
T
YA
MH
IL
L, O
R 9
71
48
20088.00
VO
LU
NT
AR
Y S
EIS
MIC
S
TR
EN
GT
HE
NIN
G
YA
MH
IL
L C
AR
LT
ON
H
IG
H S
CH
OO
L
04/29/2021
MM
BID SET
KKS
8 7 6 5 4 3 2 1
A
B
C
D
211'-6"
25'-0" 29'-0"
19'-7
1
4
"
10'-0" 10'-6" 29'-0" 25'-0"
73
'-1
0"
23
'-0
"1
8'-1
0"
20
'-0
"
MA
TC
HL
IN
E
SE
E S
2.2
MA
TC
HL
IN
E
SE
E S
2.2
(E) RIDGE (E) RIDGE
(E
) R
ID
GE
1
A.5
12
'-0
"
19'-9
1
4
"
10'-8"
16'-5
3
4
" 16'-5
3
4
"
2.53.55.56.5
1
SCALE:
1
LOWER ROOF STRENGTHENING PLAN - BID ALTERNATE
1/8"=1'-0"
NORTH
SCALE:
KEYPLAN
NTS
S2.3
LOWER ROOF
STRENGTHENING
PLAN -
BID ALTERNATE
P:\W
RK
2020\20088.00 - Y
am
hill C
arlton H
igh S
chool S
eism
ic R
ehabilitation\C
AD
\20088.00_S
2.3.dw
g 04/29/21 11:38 U
SE
R
drawn by
issue date
revisions
checked by
wrk job number
27
5 N
M
AP
LE
S
T
YA
MH
IL
L, O
R 9
71
48
20088.00
VO
LU
NT
AR
Y S
EIS
MIC
S
TR
EN
GT
HE
NIN
G
YA
MH
IL
L C
AR
LT
ON
H
IG
H S
CH
OO
L
04/29/2021
MM
BID SET
KKS
PLAN NOTES:
1. EXISTING CONDITIONS ARE SHOWN WITHOUT GUARANTEE OF ACCURACY. NOTIFY THE EOR IF
THE CONDITIONS DISCOVERED IN THE FIELD ARE DIFFERENT THAN THOSE DEPICTED IN THE
CONTRACT DOCUMENTS.
2. THE DRAWINGS CONTAIN REFERENCE TO EXISTING CONDITIONS, MATERIALS, FURNISHINGS,
AND EQUIPMENT. THE INFORMATION IS DEVELOPED FROM EXISTING DRAWINGS AND SITE
AND BUILDING OBSERVATIONS, AND IS PROVIDED FOR REFERENCE ONLY. THE CONTRACTOR
SHALL VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS. IT IS TO BE ASSUMED THE
BUILDING IS NOT LEVEL, SQUARE, OR PLUMB.
3. NOTIFY THE EOR IF DECAY, CORROSION, OR OTHER DAMAGE TO THE EXISTING STRUCTURE
IS DISCOVERED.
4. SEE SHEET S7.1 FOR WOOD DETAILS.
5. CONTRACTOR TO PROTECT ALL (E) CONDUIT AND DUCTS.
6. GRIDLINE SHOWN AT FACE OF STUD WALL.
7. INDICATES BASE BID SCOPE.
KEYED NOTES:
1
INDICATES (E) PLYWOOD SHTHG OVER (E) SKIP 1x SHTHG. ADD 10d AT 6" OC
PANEL EDGE NAILING. SEE 2/S7.1 FOR PLYWOOD DIAPHRAGM NAILING.
B
C
6 5 4 3
70'-6
1
2
"
19'-7
1
4
"
10'-0" 10'-6"
5.5 3.5
19'-9
1
4
"
10'-8"
1
5'-0"
4
D
20
'-0
"6
'-3
"
B.5
12
'-7
"
(E
) R
AM
P
5
BOILER ROOM
3
S3.1
5'-0"
6'-0
"
MA
X
7
S8.1
SIM
3
TYP
3
TYP
2
2
1
11
2'-0
"
TYP
5
S8.1
P:\W
RK
2020\20088.00 - Y
am
hill C
arlton H
igh S
chool S
eism
ic R
ehabilitation\C
AD
\20088.00_S
2.4.dw
g 04/29/21 11:38 U
SE
R
drawn by
issue date
revisions
checked by
wrk job number
27
5 N
M
AP
LE
S
T
YA
MH
IL
L, O
R 9
71
48
20088.00
VO
LU
NT
AR
Y S
EIS
MIC
S
TR
EN
GT
HE
NIN
G
YA
MH
IL
L C
AR
LT
ON
H
IG
H S
CH
OO
L
04/29/2021
MM
BID SET
KKS
SCALE:
1
PARTIAL BASEMENT NONSTRUCTURAL BRACING PLAN
1/4"=1'-0"
NORTH
SCALE:
KEYPLAN
NTS
S2.4
PARTIAL
BASEMENT
NONSTRUCTURAL
BRACING PLAN
PLAN NOTES:
1. EXISTING CONDITIONS ARE SHOWN WITHOUT GUARANTEE OF ACCURACY. NOTIFY THE EOR IF
THE CONDITIONS DISCOVERED IN THE FIELD ARE DIFFERENT THAN THOSE DEPICTED IN THE
CONTRACT DOCUMENTS.
2. THE DRAWINGS CONTAIN REFERENCE TO EXISTING CONDITIONS, MATERIALS, FURNISHINGS,
AND EQUIPMENT. THE INFORMATION IS DEVELOPED FROM EXISTING DRAWINGS AND SITE
AND BUILDING OBSERVATIONS, AND IS PROVIDED FOR REFERENCE ONLY. THE CONTRACTOR
SHALL VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS. IT IS TO BE ASSUMED THE
BUILDING IS NOT LEVEL, SQUARE, OR PLUMB.
3. NOTIFY THE EOR IF DECAY, CORROSION, OR OTHER DAMAGE TO THE EXISTING STRUCTURE
IS DISCOVERED.
4. SEE S8.1 FOR NONSTRUCTURAL DETAILS.
5. CONTRACTOR TO PROTECT ALL (E) CONDUIT AND DUCTS.
6. GRIDLINE SHOWN AT FACE OF STUD WALL.
KEYED NOTES:
1
PROVIDE ANGLE BRACES EA END ALONG SIDE OF (E) BOILER PER DETAIL 8/S8.1.
PROVIDE L6x6x1/2 x 1'-0" W/ (2) 1/4" DIA (S) TITEN-HD AT 9" OC W/ 3" MIN EMBED
INTO (E) HOUSKEEPING PAD. LOCATE ANGLE AS CLOSE TO CENTERLINE OF (E)
BOILER AS POSSIBLE. INSTALL TIGHT TO (E) BOILER.
PROVIDE HSS6x6x1/2 STRONGBACK.
PROVIDE HSS6x6x1/2 STRONGBACK OVER (E) OPENING.
PROVIDE SEISMIC SHUT-OFF VALVE AT (E) NATURAL GAS METER.
2
3
4
5
E
F
G
B
C
D
12
'-0
"1
8'-1
0"
20
'-0
"2
0'-0
"2
0'-0
"1
9'-6
"
11
0'-4
"
70'-6
1
2
"
6 5 4 3
19'-7
1
4
"
10'-0" 10'-6"
A.5
5.5 3.5
19'-9
1
4
"
10'-8"
E
F
G
B
C
D
12
'-0
"1
8'-1
0"
20
'-0
"2
0'-0
"2
0'-0
"1
9'-6
"
11
0'-4
"
70'-6
1
2
"
6 5 4 3
19'-7
1
4
"
10'-0" 10'-6"
A.5
5.5 3.5
19'-9
1
4
"
10'-8"
3
1
3
2
3
33
33
TYP
2
(E) ATTIC
ACCESS
LADDER
(E) ATTIC
ACCESS
LADDER
SCALE:
1
ATTIC NONSTRUCTURAL PIPE BRACING PLAN
1/8"=1'-0"
NORTH
SCALE:
KEYPLAN
NTS
S2.5
PLAN NOTES:
1. EXISTING CONDITIONS ARE SHOWN WITHOUT GUARANTEE OF ACCURACY. NOTIFY THE EOR IF
THE CONDITIONS DISCOVERED IN THE FIELD ARE DIFFERENT THAN THOSE DEPICTED IN THE
CONTRACT DOCUMENTS.
2. THE DRAWINGS CONTAIN REFERENCE TO EXISTING CONDITIONS, MATERIALS, FURNISHINGS,
AND EQUIPMENT. THE INFORMATION IS DEVELOPED FROM EXISTING DRAWINGS AND SITE
AND BUILDING OBSERVATIONS, AND IS PROVIDED FOR REFERENCE ONLY. THE CONTRACTOR
SHALL VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS. IT IS TO BE ASSUMED THE
BUILDING IS NOT LEVEL, SQUARE, OR PLUMB.
3. NOTIFY THE EOR IF DECAY, CORROSION, OR OTHER DAMAGE TO THE EXISTING STRUCTURE
IS DISCOVERED.
4. SEE S8.1 FOR NONSTRUCTURAL DETAILS.
5. INDICATES DIRECTION OF PIPE BRACING.
6. CONTRACTOR TO PROTECT ALL (E) CONDUIT AND DUCTS.
7. GRIDLINE SHOWN AT FACE OF STUD WALL.
ATTIC
NONSTRUCTURAL
BRACING PLAN
KEYED NOTES:
1
PROVIDE SEISMIC BRACING FOR (E) FIRE SUPPRESSION PIPING PER 4/S8.1
(E) CATWALK. DO NOT DISTURB.
(E) SUSPENDED MECH UNIT. BRACE PER DET. 1/S8.1
SCALE:
2
ATTIC NONSTRUCTURAL BRACING PLAN
1/8"=1'-0"
NORTH
2
3
P:\W
RK
2020\20088.00 - Y
am
hill C
arlton H
igh S
chool S
eism
ic R
ehabilitation\C
AD
\20088.00_S
2.5.dw
g 04/29/21 11:38 U
SE
R
drawn by
issue date
revisions
checked by
wrk job number
27
5 N
M
AP
LE
S
T
YA
MH
IL
L, O
R 9
71
48
20088.00
VO
LU
NT
AR
Y S
EIS
MIC
S
TR
EN
GT
HE
NIN
G
YA
MH
IL
L C
AR
LT
ON
H
IG
H S
CH
OO
L
04/29/2021
MM
BID SET
KKS
SCALE:
3
BASEMENT MASONRY WALL ELEVATION
1/2"=1'-0"
(E) STEEL LINTEL
4
6
S8.1
7
S8.1
7
S8.1
4
(E) WOOD POST(E) WOOD POST
6
S8.1
OPP
3456
10'-6"10'-0"
19'-7
1
4
"
70'-6
1
2
"
SCALE:
1
TRUSS ELEVATION - GRIDLINE D
1/4"=1'-0"
3.55.5
10'-8"
19'-9
1
4
"
SCALE:
2
TRUSS ELEVATION
1/4"=1'-0"
G H
1
2
2
6
S7.1
20'-6
1
4
"
VIF
3
5
S7.1
6
S7.1
3
S7.2
SECOND FLOOR
VIF
ATTIC
VIF
LOW ROOF
VIF
5
S7.1
SHEAR WALL
BELOW
SHEAR WALL
BELOW
PLYWOOD INSTALLED
ON OPPOSITE SIDE OF
HOLDOWN, SEE 3/S7.2
S3.1
ELEVATIONS
P:\W
RK
2020\20088.00 - Y
am
hill C
arlton H
igh S
chool S
eism
ic R
ehabilitation\C
AD
\20088.00_S
3.1.dw
g 04/29/21 11:38 U
SE
R
drawn by
issue date
revisions
checked by
wrk job number
27
5 N
M
AP
LE
S
T
YA
MH
IL
L, O
R 9
71
48
20088.00
VO
LU
NT
AR
Y S
EIS
MIC
S
TR
EN
GT
HE
NIN
G
YA
MH
IL
L C
AR
LT
ON
H
IG
H S
CH
OO
L
04/29/2021
MM
BID SET
KKS
KEYED NOTES:
1
(E) ATTIC CATWALK. DO NOT DISTURB.
(E) DUCT, SEE 3/S7.1 WHERE (E) DUCT PENETRATES SHEAR WALL SHEATHING.
SISTER 2x4 TO (E) TRUSS CHORD AND WEB MEMBERS AND INFILL W/ 2x4 STUDS
AT 24" OC MAX AS REQUIRED FOR TYPE "A" SHEAR WALL PANEL EDGE
FASTENING
HSS HORIZONTAL STRONGBACK PER PLAN OVER OPENING. LOCATE
STRONGBACK SO AS TO AVOID CONFLICT WITH (E) MEP
2
ELEVATION NOTES:
1. EXISTING CONDITIONS ARE SHOWN WITHOUT GUARANTEE OF ACCURACY. NOTIFY THE EOR IF
THE CONDITIONS DISCOVERED IN THE FIELD ARE DIFFERENT THAN THOSE DEPICTED IN THE
CONTRACT DOCUMENTS.
2. THE DRAWINGS CONTAIN REFERENCE TO EXISTING CONDITIONS, MATERIALS, FURNISHINGS,
AND EQUIPMENT. THE INFORMATION IS DEVELOPED FROM EXISTING DRAWINGS AND SITE
AND BUILDING OBSERVATIONS, AND IS PROVIDED FOR REFERENCE ONLY. THE CONTRACTOR
SHALL VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS. IT IS TO BE ASSUMED THE
BUILDING IS NOT LEVEL, SQUARE, OR PLUMB.
3. INDICATES OUTLINE OF NEW SHEAR WALL. SEE PLAN FOR SW TYPE, UNO.
SEE 1/S7.1 FOR SHEAR WALL SCHEDULE.
3
4
SCALE:
4
ROOF TO NORTH/SOUTH EXTERIOR WALL
1"=1'-0"
(E) 2x12 AT 1/3RD POINTS
(E) DECKING
(E) 2x12 AT 24" OC
(E) PLYWD SHTHG
(E) 2x12 AT 16" OC
2x6 BLKG W/ (2) ROWS
(S) SDWS22300DB AT
16" OC STAGGERED
(E) STUD WALL
(E) BRICK VENEER
(E) SUSPENDED ATC
CEILING. REMOVE AND
REINSTALL AS REQD.
SEE DEMO PLAN
(E) 2x12 RIM
EN, TYP
SHAPED 3x BLKG
(S) A35
AT 16" OC
1/2" PLYWD W/ 10d AT 4" OC EN, TYP
DEMO (E) LEDGER
TO PERFORM WORK.
REPLACE IN KIND.
(E) PLYWD SHTHG
SCALE:
10
ROOF TO WALL CONNECTION
1"=1'-0"
(E) 2x12 RAFTERS
(E) 2x8 CEILING JSTS
(E) DECKING
(E) PLYWD SHTHG
EN, TYP
(S) A34 AT 24" OC
(E) PLYWD SHTHG
SCALE:
5
ATTIC SHEAR WALL TO (E) SHEAR WALL
1"=1'-0"
4x12 BLKG BTWN (E)
JOISTS
(S) A35 AT 12" OC
(E) SUSPENDED ATC CEILING.
REMOVE AND REINSTALL AS REQD
(2) LAYERS (E) GYP
CEILING
(E) 3x12 TRUSS
BOTTOM CHORD
(E) 3x6 TRUSS WEBS,
TYP
(2) (S) SDS25600
AT 16" OC
EN, TYP
STUD WALL
SW SHTHG PER PLAN
(E) 2x12 CEILING JST
AT 24" OC, TYP
SCALE:
6
ATTIC SHEAR WALL TO (E) ROOF
1"=1'-0"
SCALE:
9
HIGH ROOF TO LOW ROOF CONNECTION
1"=1'-0"
2x12 BLKG
EN, TYP
(E) 2x12 ROOF JOISTS
(E) 1x DECKING
(E) 2x10 TRUSS TOP
PLATES, TYP
(E) 3x12 TRUSS TOP
CHORDS, TYP
(E) DECKING
SW SHTHG PER PLAN
STUD WALL
(S) A35 AT 12" OC
(E) 2x12
AT 24" OC
(E) 2x12
AT 16" OC
(E) 2x12 AT 24" OC
(E) 1x DECKING
(E) PLYWD SHTHG
SCALE:
12
LOW ROOF TO EXT WALL
1"=1'-0"
(E) BRICK VENEER
(E) EXT WALL
SCALE:
8
HIGH ROOF TO LOW ROOF CONNECTION
1"=1'-0"
(E) 2x12 AT 24" OC
(E) STUD WALL
(E) PLYWD SHTHG
(S) A34 AT 24" OC
(E) STUD WALL
(E) BRICK VENEER
2x BLKG
EN, TYP
(E) TRUSS AT 24" OC
(E) 1x DECKING
(E) PLYWD SHTHG
(E) PLYWD SHTHG
(E) 1x DECKING
(E) 2x4 OUTRIGGER
16d AT 6" OC
(E) BLKG
(E) PLYWD SHTHG
SEE DEMO PLAN
TYPE "A" INFILL SW
BTWN (E) FRAMING
(E) PLYWD SHTHG
EN, TYP
(E) STUDWALL(E) STUDWALL
6"
SILL FASTENING PER
SW SCHED
SEE DEMO PLAN
(E) PLYWD SHTHG
16d AT 6" OC
(E) SIDING
(S) A35 BTWN 3x BLKG
AND (E) 2x12 EA END
SCALE:
7
GYM ATTIC SHEAR WALL INFILL - GRIDLINE A.5
1"=1'-0"
(E) PLYWD SHTHG
(E) 1x DECKING
A.5
(E) 2x12 CEILING JOISTS
(2) LAYERS (E) GYP
CEILING
(E) SHEAR WALL
16d AT 6" OC
(E) 2x12 RAFTERS
TYPE "A" SW INFILL
BTWN FRAMING. NOTCH
PLYWD AS REQUIRED.
DEMO (E) GYP BOARD
TO PERFORM WORK
2x6 PL
SHAPED TOP PL
SCALE:
11
ROOF TO EXT WALL
1"=1'-0"
(E) 1x DECKING
(E) PLYWD SHTHG
(E) PLYWD SHTHG (S) SDWS22600DB AT
24" OC
3x BLKG EA STUD
BAY
(S) A35 AT 16" OC W/
#6 x 1/2" SCREWS
INTO PLYWD
(E) 2x12 ROOF
JOISTS, TYP
(E) EXT WALL
(E) 2x12 AT 16" OC
INFILL STUDS TO
MATCH WIDTH OF (E)
WALL BELOW
INFILL STUDS TO
MATCH WIDTH OF (E)
WALL BELOW
INFILL STUDS TO
MATCH WIDTH OF (E)
WALL BELOW
(E) SW
SEE DEMO PLAN
SEE DEMO PLAN
6
3
DD
EN, TYP
G
EN, TYP
TYPE "A" INFILL SW
BTWN (E) FRAMING
G
EN, TYP
H 5.5
3.5
H
NOTES:
1. 10d NAIL = HY-TEK 2 1/4x0.120M OR 3" x 0.128" GALVANIZED BOX.
2. NAIL SIZES SHOWN ARE FOR COMMON NAILS OR GALVANIZED BOX. POWER DRIVEN NAILS SHALL
COMPLY WITH ESR 1539 FOR RECOMMENDED SPACING AND INSTALLATION TO COMPLY WITH
THE ABOVE SHEAR WALL SCHEDULE.
3. FRAMING MEMBERS SHALL NOT BE LESS THAN A SINGLE 3x4 NOMINAL MEMBER OR TWO 2x4
NOMINAL MEMBERS LAMINATED TOGETHER WITH 16d AT 6" OC. WOOD STRUCTURAL PANEL
JOINT AND SILL PLATE NAILING SHALL BE STAGGERED IN ALL CASES. SEE NOTE 7.
4. SHEAR WALL NAILING MUST BE INSTALLED SUCH THAT THE NAIL HEAD OR CROWN IS FLUSH
WITH THE SURFACE OF SHEATHING. OVERDRIVEN OR OVER PENETRATED NAILS WILL NOT BE
ALLOWED OR COUNTED AS APPROPRIATE NAILING.
5. ALL PANEL EDGES SHALL BE BLOCKED AS NOTED.
6. PROVIDE MINIMUM (2) STUDS AT EACH END OF SHEAR WALL UNO BY SHEAR WALL SCHEDULE.
7. FOR PANEL NAILING LESS THAN OR EQUAL TO 4" OC, STAGGER FASTENER 1/2".
SCALE:
1
SHEAR WALL SCHEDULE
NTS
A
EDGE
PANEL NAILING
MARK SHEATHING
SHEAR WALL SCHEDULE
SIDE
SIZE FIELD
ONE 10d 12" OC 3x
15/32" STRUCTURAL I
SHEATHING
VALUE
(PLF)
PANEL
BLOCKING
4" OC 1,530
(S) SDWS22400DB
AT 8" OC
SILL
ANCHOR
SCALE:
2
TYP PLYWOOD DIAPHRAGM NAILING
1/4"=1'-0"
EN AROUND
PENETRATIONS
(TYP)
BLOCK EDGES AS
REQD
FIELD NAIL (TYP)
EN (TYP)
EN
(E) FRAMING
(E) CONT PANEL
SIDE JTS*
EN
(E) BRG/SHEAR
WALL
(E) STAG PANEL
SIDE JTS*
1'-4
"
TY
P
(S) CS20 ES
OF OPNG
DBL TOP PLATE
MECH OPNG
PROVIDE (1) 2x TRIM
STUD AND (1) 2x KING
STUD, WIDTH TO MATCH
WALL FRAMING
3'-6
"
MA
X
(2) 2x8 HEADER
2'-6"
MAX
2'-0"
MIN, TYP
1'-4
"
SCALE:
3
TYP MECHANICAL OPENING IN SHEAR WALL
NTS
(S) CS20, TOP AND
BOT OF OPENING.
PROVIDE BLKG
BELOW STRAP
S7.1
WOOD DETAILS
P:\W
RK
2020\20088.00 - Y
am
hill C
arlton H
igh S
chool S
eism
ic R
ehabilitation\C
AD
\20088.00_S
7.1.dw
g 04/29/21 11:38 U
SE
R
drawn by
issue date
revisions
checked by
wrk job number
27
5 N
M
AP
LE
S
T
YA
MH
IL
L, O
R 9
71
48
20088.00
VO
LU
NT
AR
Y S
EIS
MIC
S
TR
EN
GT
HE
NIN
G
YA
MH
IL
L C
AR
LT
ON
H
IG
H S
CH
OO
L
04/29/2021
MM
BID SET
KKS
SCALE:
1
LOW ROOF TO STUD WALL
1"=1'-0"
(E) 1x DECKING
(E) PLYWD SHTHG
(S) A34 AT 24" OC
(E) PLYWD SHTHG
(E) BLKG (E) 2x4 LEDGER
(E) STUD WALL
(E) BLKG
(E) SIDING
(E) 2x4 RAFTERS
(E) PLYWD SHTHG
SCALE:
3
LOW ROOF CONNECTION TO SECOND FLOOR
1"=1'-0"
ATTIC TRUSS SHEAR
WALL, SEE 2/S3.1
(E) GYP CEILING
(E) FLOOR SHTHG
(E) STEEL JOIST,
TYP
(E) CEILING FINISH
DEMO AS REQD
(E) SHEAR WALL
(2) 2x10 W/ (2) (S) A35
EA SIDE W/ #6x1/2"
SCREWS INTO (E)
FLOOR SHTHG, TYP.
PROVIDE MIN (3) JOIST
BAYS. ALIGN W/ LOWER
ROOF TRUSS
SCALE:
2
LOW ROOF TO STUD WALL
1"=1'-0"
(E) STUDWALL
(E) 1x DECKING
(E) PLYWD SHTHG
EN, TYP
(E) 2x4 RAFTER
(S) SDWS22600DB
AT 12" OC
(E) SIDING. DEMO
AS REQD TO
INSTALL BLKG
(S) A35 AT 16" OC W/
#6 x 1/2" SCREWS
INTO (E) SHTHG
3x BLKG
(E) PLYWD SHTHG
PROVIDE (2) 2x6 BLKG EA STUD
BAY W/ (S) CMST14x10'-0"
INSTALLED OVER PLYWOOD.
ALIGN BLKG W/ HOLDOWN.
(S) HDU5 W/ 5/8" DIA
THRU-BOLT, TYP.
INSTALL OPPOSITE SIDE
OF WALL AS PLYWOOD
PLYWOOD SW W/ 2x STUD
INFILL PER 2/S3.1
AT CONTRACTOR'S
OPTION, PROVIDE (S)
CNW COUPLER
G5.5
3.5
G
S7.2
WOOD DETAILS
P:\W
RK
2020\20088.00 - Y
am
hill C
arlton H
igh S
chool S
eism
ic R
ehabilitation\C
AD
\20088.00_S
7.2.dw
g 04/29/21 11:38 U
SE
R
drawn by
issue date
revisions
checked by
wrk job number
27
5 N
M
AP
LE
S
T
YA
MH
IL
L, O
R 9
71
48
20088.00
VO
LU
NT
AR
Y S
EIS
MIC
S
TR
EN
GT
HE
NIN
G
YA
MH
IL
L C
AR
LT
ON
H
IG
H S
CH
OO
L
04/29/2021
MM
BID SET
KKS
SCALE:
3
ROD STIFFENER
1"=1'-0"SCALE:
1
SUSPENDED MECH UNIT BRACING
1"=1'-0"
PLAN
A
A
NOTE:
SEE 2/S8.1 FOR BRACE CONNECTION TO (E) JOISTS.
P1000 HS, TYP (E) THREADED ROD, TYP
(E) MECH UNIT
BRACE, TYP
A
8"
MA
X
1'-4
" M
AX
TY
P
8"
MA
X
4"
MA
X
SECTION A-A
A
4"
MA
X
P2485 CRADLE
CLIP, TYP
LENGTH OF P1000T
SHALL BE 8" SHORTER
THAN THREADED ROD
(E) ROD
P3008 NUT
3/8"x1" BOLT SNUGGED
AGAINST ROD W/ P3008
NUT
CONNECTION
VARIES
ASSEMBLY VARIES,
SEE PLAN
P1000T UNISTRUT
CHANNEL STIFFENER
SCALE:
5
VERTICAL HSS STRONGBACK CONNECTION
1"=1'-0"
(E) DIAGONAL SHTHG
HE
IG
HT
VA
RIE
S
(E) 2x12 JOISTS AT 24" OC.
LOCATION AND
ORIENTATION MAY VARY
IN FIELD. CONTRACTOR
TO VERIFY
3x12 FLAT BLKG(2) (S) SDS25300
(E) HOLLOW CLAY
TILE WALL
2"
MAX
(E) CONC
FOUNDATION WALL
HSS STRONGBACK
PER PLAN
3/4" DIA ADH AHR
AT 24" OC MAX
(E) CONCRETE SOG
1/2" DIA (S) TITEN-HD W/
2
1
2
" MINIMUM EMBED
PROVIDE 3"x3"
INCOMPRESSIBLE
SHIM AS REQUIRED
SCREEN TUBE PER
MANUF IN 1" DIA
HOLE
AA
AA
PL3/8x6x0'-6"
NOTES:
1. DO NOT LOCATE ANCHOR IN MORTAR JOINT OF MASONRY WALL.
2. LOCATE HOLES TO AVOID MEP CONFLICT.
FIRST FLOOR
VIF
SEE 6/S7.1 FOR
ACCESS HOLE,
TYP
SCALE:
4
SINGLE PIPE SUPPORT WITH SEISMIC BRACING
1 1/2"=1'-0"
4
5
°
±
1
0
°
T
Y
P
4"
MA
X
14
" O
C
MA
X
4
5
°
±
1
0
°
T
Y
P
A
A
SEE 9/S8.1
MASON SCB-2
ADJUSTABLE HINGE
THD ROD
PIPE
HANGER
PIPE CLAMP MAY BE
ROTATED TO GAIN
ACCESS TO STRUCTURE
ABOVE
PIPE CLAMP
PRESTRETCHED
AIRCRAFT CABLE
SEE 9/S8.1
NOTE:
PROVIDE SEISMIC BRACING AT SPACING:
TRANSVERSE : 20'-0" OC MAX
LONG : 40'-0" OC MAX
SEE 9/S8.1
MASON SCB - 2
ADJUSTABLE HINGE, TYP.
LONG BRACING
SHOWN BELOW
(N) OR (E) PIPE
CLEVIS HANGER
SEE 3/S8.1 FOR
ROD STIFFENER
P2486 ROD
STIF AT
14" OC MAX
THD ROD
SEE 9/S8.1
PRESTRETCHED 3/16" DIA.
GALV. AIRCRAFT CABLE,
7x19 TYP.
SECTION A-A
SCALE:
2
BRACING CONNECTION
1 1/2"=1'-0"
SECTION A-A
ROD STIFFENER PER
3/S8.1
SLIP-ON NUT
P1000 HS BRACE, SEE
PLAN FOR LOCATION
SPF 200 W/ (2) 1/2" DIA
BOLTS & CHANNEL NUTS
P1000 HS BRACE, SEE
PLAN FOR LOCATION
AND DIRECTION
(E) ISOLATOR
AS OCCURS
(E) THREADED ROD
(E) MECH UNIT
P1354W W/ 1/2" DIA
THRU-BOLTS AND P1010
CHANNEL NUTS, TYP
BRACE PER 1/S8.1
NOTE:
BRACE ATTACHES TO BOTTOM OF (E) JOIST AS OCCURS.
3x FULL DEPTH BLKG
(E) JOIST, TYP
2
1
2
" 2
1
2
"
EQ
1"
TYP
EQ
PL3/8x6x0'-11"
SECTION A-A
1/4
TYP
SECTION A-A
SCALE:
6
HORIZONTAL HSS STRONGBACK CONNECTION
1 1/2"=1'-0"
NOTE:
DO NOT LOCATE ANCHOR IN MORTAR JOINT OF MASONRY WALL.
2"
TY
P
2"
TYP
(E) WOOD POST
(E) HOLLOW CLAY
TILE WALL
SCREEN TUBE PER
MANUF IN 1" DIA
HOLE
PL3/8x6x0'-6" 3/4" DIA ADH AHR
AT 24" OC FULL
LENGTH OF HSS
A
A
SCALE:
7
(E) HOLLOW CLAY TILE WALL TO (E) POST CONNECTION
1 1/2"=1'-0"
L4x4x
1
4
x0'-4" T&B W/
1/2" DIA THRU-BOLT
1/2" DIA x 4" LAG
SCREW, TYP
1'-0
"
TY
P
2'-0
"
TY
P
L4x4x
1
4x0'-4" W/ 1/2" DIA x 4"
LAG SCREW INTO WOOD
POST, TYP. PROVIDE AT 24"
OC FULL POST HEIGHT.
(E) WOOD POST
3/4" DIA ADH AHR INTO (E)
HOLLOW CLAY TILE WALL,
TYP. SEE 6/S8.1 FOR
ADDITIONAL ANCHOR
INFORMATION
ANGLE OCCURS
BOTH SIDES OF
POST AT SIM
CONDITION.
(E) HOLLOW
CLAY TILE WALL
CJP, TYP
2 1/2" DIA ACCESS
HOLE, TYP
SCALE:
9
TYPICAL PIPE/TRAPEZE CONNECTION
1 1/2"=1'-0"
1
2
" DIA, THRU
BOLT, TYP
L6x3
1
2
x
1
2
x0'-4"
(LLV)
NOTES:
1. PROVIDE ALL BOLTS, NUTS, WASHERS, FITTINGS, ETC, AS RECOMMENDED BY BRACING MANUFACTURER.
2. SEE NONSTRUCTURAL BRACING DETAILS FOR INFORMATION NOT SHOWN OR NOTED.
(E) ROOF SHTHG
5/8" DIA
THRU BOLT
(E) BM/JST
MASON SCB - 2
ADJUSTABLE
HINGE
PRESTRETCHED
AIRCRAFT CABLE
L4x3x
3
8
x0'-8"
MASON
SCB - 2
ADJUSTABLE
HINGE
(E) BM/JST
1
2
" DIA THRU
BOLT, TYP
4"
MA
X
4"
HANGER ROD PER
NONSTRUCTURAL
BRACING DETAILS
4"
MA
X
A
HANGER ROD CONNECTION
B
BRACING PERPENDICULAR TO BEAM/JOIST
C
BRACING PARALLEL TO BEAM/JOIST
PRESTRETCHED
AIRCRAFT CABLE
EQ
EQ
2"
TYP
(E) JOIST OR NEW
BLKG AS REQD
1
2
" MAX
(E) ROOF SHTHG
SCALE:
8
(E) BOILER BRACING
3"=1'-0"
VARIES
VIF
L6x6x
3
8
x0'-6"
(E) BOILER
3" MIN
2"
3
1
2
" V
IF
1/4
1/4
STIFF PL3/8"xREQD
CENTER PL ON L
PL1/2x3x0'-6" W/ (2) 1/4"
DIA (S) TITEN-HD AT 4" OC
(E) CONC SOG
(E) CONC
HOUSEKEEPING
PAD
1
2
"
TY
P
S8.1
NONSTRUCTURAL
DETAILS
P:\W
RK
2020\20088.00 - Y
am
hill C
arlton H
igh S
chool S
eism
ic R
ehabilitation\C
AD
\20088.00_S
8.1.dw
g 04/29/21 11:36 U
SE
R
drawn by
issue date
revisions
checked by
wrk job number
27
5 N
M
AP
LE
S
T
YA
MH
IL
L, O
R 9
71
48
20088.00
VO
LU
NT
AR
Y S
EIS
MIC
S
TR
EN
GT
HE
NIN
G
YA
MH
IL
L C
AR
LT
ON
H
IG
H S
CH
OO
L
04/29/2021
MM
BID SET
KKS