    C264 Expert Utilisation

    PACiS

  • 8/20/2019 YANN C264 Commissioning

    2/44

    > L2 4A C264 Expert utilisation 02 2  2

    C264 Expert C264 Expert C264 Expert C264 Expert 

    1 ) Hardware installation & Commissioning

    2 ) Computer’s basic settings 

    3 ) Software Installation 

    4 ) Download DataBase and Switch

    5 ) Communication Testing 

  • 8/20/2019 YANN C264 Commissioning

    3/44

    > L2 4A C264 Expert utilisation 023 3

    C264 Expert C264 Expert C264 Expert C264 Expert 

    1) Requirement 

    2) Checks Power Off Hardware configuration (CORTEC) 

    3) Checks/install only Power Software Version Ethernet/Front port 

    Database Version Hardware Self tests 

    4) Checks with I/O IED Communication 

    DB 

    Installation / CommissioningInstallation / CommissioningInstallation / CommissioningInstallation / Commissioning

  • 8/20/2019 YANN C264 Commissioning

    4/44

    > L2 4A C264 Expert utilisation 024 4

    1.1) Set-up Requirements 

    1) Adapted DC Power supply (protected)

    2) Personal Computer (WINDOWS 2000 administrator)

    3) RS232C Null Modem Cable

    4) Ethernet cable (cross if not hub/switch)

    5) Screw-driver (Torque 10, POZ 1) extractor

    19200 baudsNo parity 8 bit1 stopNo flow control

  • 8/20/2019 YANN C264 Commissioning

    5/44

    > L2 4A C264 Expert utilisation 025 5

    1.2 ) C264 Requirement 

    MANDATORY

    From Business Ordering

    1) C264 Delivery Form

    2) C264 Hardware Version (kind of CPU, Power Supply)3) C264 Software Version + System Release Note

    4) C264 Business IP, Net name

    5) C264 Business Board ConfigurationCORTEC

    Kind by Slot, Voltage, BIU port

    6) C264 Business Data Bag

  • 8/20/2019 YANN C264 Commissioning

    6/44

    > L2 4A C264 Expert utilisation 026 6

    2 ) Checks Power OFF 

    2 ) Power Off Hardware Checks 

    2.1) C264 Package Reception

    2.2) Front panel Removal Check Hardware configuration 

    Boards location and Voltage 

    2.3) Optional Bus removal Check BIU ports jumpers 

    2.4) Mechanical Mounting 

    2.5) Wiring installation Shield 

  • 8/20/2019 YANN C264 Commissioning

    7/44

    > L2 4A C264 Expert utilisation 027 7

    2.1 ) Delivery reception 

    1) Packing inspection and opening

    2) Delivery Form checking / acceptance

    3) Delivery Form Storage in Business Hardware Binder

    4) Checking Front Panel Sticker

    5) Opening Record Sheet

  • 8/20/2019 YANN C264 Commissioning

    8/44

    > L2 4A C264 Expert utilisation 028 8

    2.2) Front Panel Removing 

    Front Panel removal POZ 1

    Rack mounting

  • 8/20/2019 YANN C264 Commissioning

    9/44

    > L2 4A C264 Expert utilisation 029 9

    2.2 ) Checking Boards Slot / Voltage 

    Remove front panel and check boards location / Slot

    BIU

    CPU

    DIU DOU CCU  AIU

    Board Number  Board Name

  • 8/20/2019 YANN C264 Commissioning

    10/44

    > L2 4A C264 Expert utilisation 0210 10

    2.2 ) Checking Boards Slot / Voltage 

    Remove front panel and check VoltagesBIU / DIU / CCU

    Sticker 

    A01 24 V

    A02 48VA03 110/125VA04 220V

  • 8/20/2019 YANN C264 Commissioning

    11/44

    > L2 4A C264 Expert utilisation 0211 11

    2.3 ) BIU Port Setting 

    0) Check no power on BIU, get anti-static Brace

    1) Get HW chapter (hardware)2) Remove BUS with finger starting from left

    3) Remove Torque Screw (Board + ruler)

    4) Extract board with dedicated extractor tool

    5) Checking PORT 1/2 setting via jumpers

    6) Put Back Board / screws / Bus

  • 8/20/2019 YANN C264 Commissioning

    12/44

    > L2 4A C264 Expert utilisation 0212 12

    2.4 ) Mechanical Mounting 

    Front Panel ReinstallC264 mechanical fixation (19” rack or other)

  • 8/20/2019 YANN C264 Commissioning

    13/44

    > L2 4A C264 Expert utilisation 0213 13

    2.5 ) Wiring Check (still no power) 2.5 ) Wiring Check (still no power) 2.5 ) Wiring Check (still no power) 2.5 ) Wiring Check (still no power) 

    1) Shield wiring2) Power supply wiring (BIU + neutral policy)

    3) I/O board wiring4) Ethernet Networks wiring5) Serial TBUS/LBUS network wiring

    Refer to “CONNECTIONS” chapter(“C264_EN CO” documentation)

    Good Practices Shield Schemewire color/diameter policy naming e.g. DIU200_2_DWrite name on connector

  • 8/20/2019 YANN C264 Commissioning

    14/44

    > L2 4A C264 Expert utilisation 0214 14

    3 ) Checks Power ON on BIU only 

    3 ) Checks on Computer’s basic settings 

    3.1) Run-time Requirements 

    3.2) C264 power up sequence 

    3.3) Setting commands

    2.3) Checking default settings 2.4 ) Input new settings 

  • 8/20/2019 YANN C264 Commissioning

    15/44

    > L2 4A C264 Expert utilisation 0215 15

    3.1) Run-time Requirement 

     ALSTOM

    Serial link

    RS232

    >p CR 

    The following informationshould be displayed:

    “bootdevice :tffs=0,0

    “processor number :0

    “hostname :

    “file name :/flash/bin/vxWorks

    “inetonethernet :

    “ineton backplane :CR 

    “hostinet :

    “gateway inet :0.0.0.0

    “user :

    “ftp password :

    “flags : 0x0

    “targetname :

    “s tar tup s cri p t :

    “other :motfec

    1) Connection IP, Serial link 2) Launch HyperTerminal on the PC3) Launch CMT and WFTP

    4) Power up delivered MiCOM C264

  • 8/20/2019 YANN C264 Commissioning

    16/44

    > L2 4A C264 Expert utilisation 0216 16

    3.2 ) C264 Starting 

    1) Pre boot

    First Count Down [VxWorks]

    2) Booting Software(network, flash)

    Second Count Down ->

    3) Starting Software

    4) Loading Data Base

  • 8/20/2019 YANN C264 Commissioning

    17/44

    > L2 4A C264 Expert utilisation 0217 17

    3.3 ) settings commands 

    BASIC COMMANDS

    Default settings visualization :

     VxWorks level > use “p” command

    application level > use “bootChange” command

    Default settings setup :

     VxWorks level > use “c” commandapplication level > use “bootChange” command

    Reboot the computer :

     VxWorks level > use “^X” “@” commandapplication level > use “reboot” command

    power off - power on

  • 8/20/2019 YANN C264 Commissioning

    18/44

    > L2 4A C264 Expert utilisation 0218 18

    3.3 ) Checking default settings 3.3 ) Checking default settings 3.3 ) Checking default settings 3.3 ) Checking default settings 

    >p CR or bootChange (CR)

    The following information should be displayed:

    “boot device : tffs=0,0

    “processor number : 0

    “host name :

    “file name : /flash/bin/vxWorks

    “inet on ethernet :

    “inet on backplane : CR “host inet :

    “gateway inet : 0.0.0.0

    “user :

    “ftp password :

    “flags : 0x0

    “target name :

    “startup script :

    “other : motfec

    Tffs=0,0 boot from flash

    motfec=0 boot from PC

    c264_cpu0 cpu 8mega flash-old LCD

    c264_cpu1 cpu 16mega flash-old LCD

    c264_cpu2 cpu 16mega flash-new LCD

  • 8/20/2019 YANN C264 Commissioning

    19/44

    > L2 4A C264 Expert utilisation 0219 19

    4 ) Computer’s Software Installation

    3 ) Computer’s Software Installation on PC 

    3.1 ) Computer’s Software Installation Requirements

    3.2 ) Install computer’s software on the PC 

    3 ) Computer’s Software Installation on C264 

    3.3 ) Transfer computer’s software on the C264 

    3.4 ) Input settings for Software Installation 

    3.5 ) Transfer computer’s software on the C264 

    3.6 ) Change settings after Software Installation 

  • 8/20/2019 YANN C264 Commissioning

    20/44

    > L2 4A C264 Expert utilisation 02 20  20

    4.1 ) Computer’s Software InstallationRequire ments 

    Requirements for new software installation

    Ethernet link

    Serial link cable for “HyperTerminal” application

    Ethernet Connection may be direct or via Ethernet switch

    Use a crossed Ethernet cable for direct connection

    COM1orCOM29600/19200

    8 bitno parity TTY

    mode

  • 8/20/2019 YANN C264 Commissioning

    21/44

    > L2 4A C264 Expert utilisation 02 21  21

    4.2 ) Install computer’s software on the PC 

    Step 1 : agreement acceptance

  • 8/20/2019 YANN C264 Commissioning

    22/44

    > L2 4A C264 Expert utilisation 02 22  22

    Install computer’s software on the PC (next)

    Step 2 : choose default directories “recommendedrecommendedrecommendedrecommended”

    CAUTION : Computer’s software and FTP server are configured to beinstalled to the default directories. If you don’t choose default directories« FTP server » must be reconfigured.

  • 8/20/2019 YANN C264 Commissioning

    23/44

    > L2 4A C264 Expert utilisation 02 23  23

    Install computer’s software on the PC(next)

    Step 3 : Don’t choose “FTP server” if is not the first

    installation via the Personal Computer 

  • 8/20/2019 YANN C264 Commissioning

    24/44

    > L2 4A C264 Expert utilisation 02 24  24

    4.3 ) Transfer computer’s software on the C264 

    0) if already loaded CLEAN_DB

    1) Change to motfec, start wftp, reboot

    loading software from network to RAM2) cleaning flash by eraseFlash + reboot

    3) stop 2nd count down Stop Computer with CMT

    4) bootInstallcopy from RAM to flash

    5) change to tffs=0,0, stop wftp, reboot

    loading software from flash

    6) Check Software version LCD, VERSION with front link 

  • 8/20/2019 YANN C264 Commissioning

    25/44

    > L2 4A C264 Expert utilisation 02 25  25

    4.4 ) Input settings for Software Installation 

    ->c CR (or bootChange CR)

    “boot device : tffs=0,0 enter CR

    “processor number : 0 CR 

    “host name : CR 

    “file name : /flash/bin/vxWorks enter CR

    “inet on ethernet : xxx.xxx.xxx.xxx> CR (@IP change if needed)

    “inet on backplane : CR  

    “host inet : xxx.xxx.xxx.xxx> CR (@IP change if needed)

    “gateway inet : 0.0.0.0 CR 

    “user : c264_cpu2(or c264_cpu1) CR

    “ftp password : vxworks CR“flags : 0x0 CR 

    “target name : CR 

    “startup script : CR 

    “other : motfec CR 

    ->@ CR (or reboot CR)

    Change settings for new software installation

  • 8/20/2019 YANN C264 Commissioning

    26/44

    > L2 4A C264 Expert utilisation 02 26  26

    4.5 ) Transfer computer 4.5 ) Transfer computer 4.5 ) Transfer computer 4.5 ) Transfer computer’ ’’ ’s software on the C264 s software on the C264 s software on the C264 s software on the C264 

    1) Launch FTP server on your PC

    2) Reboot the computer 

    3 ) hit “CR ” on the “HyperTerminal” after loading C264 software

    4 ) enter “eraseFlash”+ “CR ”

    5 ) Reboot the computer

    6 ) enter “bootInstall” + “CR ” after loading C264 software (cantake some minutes)

    If the computer can’t loading C264 software checkEthernet link and verify settings with “p” or

    “bootChange” command

  • 8/20/2019 YANN C264 Commissioning

    27/44

    > L2 4A C264 Expert utilisation 02 27  27

    Transfer computer’s software on the C264(next)

    1) At the end of software installation reboot thecomputer 

    2 ) select the “service panel” and check the version of

    the new software

    3 ) The computer must be in “maintenance mode”

    4 ) Check software installed version

  • 8/20/2019 YANN C264 Commissioning

    28/44

    > L2 4A C264 Expert utilisation 02 28  28

    4.6 ) Change settings after Software Installation 

    -> c CR (or bootChange CR)

    “boot device : motfec0 enter < tffs=0,0 > CR“processor number : 0 CR 

    “host name : CR 

    “file name : vxworks enter CR

    “inet on ethernet : xxx.xxx.xxx.xxx> CR 

    “inet on backplane : CR “host inet : xxx.xxx.xxx.xxx> CR 

    “gateway inet : 0.0.0.0 CR 

    “user : CR 

    “ftp password : CR 

    “flags : 0x0 CR “target name : CR 

    “startup script : CR 

    “other : motfec CR 

    ->@ CR (or reboot CR)

    Change settings for taking in account the new software

  • 8/20/2019 YANN C264 Commissioning

    29/44

    > L2 4A C264 Expert utilisation 02 29  29

    4.7) Checking Software version 

    S E R V . I N F O

    C O M P U T E R S E R I A L N B :

    S O F T W A R E V E R S I O N :

    D A T A B A S E 1 V E R S & S T A T E :

    D A T A B A S E 2 V E R S & S T A T E :

    O P E R A T I N G H O U R S :

    O P E R A T I N G M O D E :

    R E D U N D A N C Y M O D E :

    Check software version via the service panel

    Purchased version

    No data base

  • 8/20/2019 YANN C264 Commissioning

    30/44

    > L2 4A C264 Expert utilisation 0230 30

    4.8) Database Downloading 

    Checking connectionLoading DB under SMTDownload DB unto C264Switch to downloaded data base

  • 8/20/2019 YANN C264 Commissioning

    31/44

    > L2 4A C264 Expert utilisation 0231 31

    5 ) Communications Testing 

    5 ) Communications Testing 5.1 ) Communications Testing Requirements 

    5.2 ) Debug port testing 

    5.3 ) IED communication testing 

    5.4 ) IED communication Debug commands 

    5.5 ) Printer communication testing 

    5.6 ) Ethernet Communication testing 

  • 8/20/2019 YANN C264 Commissioning

    32/44

    > L2 4A C264 Expert utilisation 0232 32

    5.1 ) Communications ports 

    Ethernet port

    Scc1 port (serial link RS232 or RS485)

    Scc2 port (serial link RS232 or RS485)

    Scc3 port (serial link RS232)

    Scc4 port (serial link RS232)

    Debug port (serial link)

  • 8/20/2019 YANN C264 Commissioning

    33/44

    > L2 4A C264 Expert utilisation 0233 33

    5.2) Communications Testing Requirements 

    Computer must be in operational mode (SCE DB loaded)

    Ethernet link

    Serial link cable for “HyperTerminal” application

    Ethernet Connection may be direct or via Ethernet Hub

    Use a crossed Ethernet cable for direct connection

    Printer cable

  • 8/20/2019 YANN C264 Commissioning

    34/44

    > L2 4A C264 Expert utilisation 0234 34

    5.3 ) Debug port testing 

    Serial link cable for “HyperTerminal” application

    COM1orCOM29600 / 19200

    8 bitno parity 

    TTY mode

    No Communication check :> serial cable

    > check PC COMx settings

    >p CR 

    The following informationshould be displayed:

    “bootdevice :tffs=0,0

    “processor number :0

    “hostname :

    “file name :/flash/bin/vxWorks

    “inetonethernet :

    “ineton backplane :CR 

    “hostinet :

    “gateway inet :0.0.0.0

    “user :

    “ftp password :

    “flags : 0x0

    “targetname :

    “s tar tup s cri p t :

    “other :motfec

    5 4 ) E h C i i i

  • 8/20/2019 YANN C264 Commissioning

    35/44

    > L2 4A C264 Expert utilisation 0235 35

    5.4 ) Ethernet Communication testing 

    If no communication :•check IP addresses settings/Mask/Negotiation of both equipment

    •use “ping” command via MS-DOS window

    •Launch the CMT

    Ethernet link

    Ethernet Connection may be direct or via Ethernet switch

    Use a crossed Ethernet cable for direct connection

    5 4 ) S i l i ti t ti

  • 8/20/2019 YANN C264 Commissioning

    36/44

    > L2 4A C264 Expert utilisation 0236 36

    5.4 ) Serial communication testing 

    Use theUse theUse theUse the ““““TEST_COMTEST_COMTEST_COMTEST_COM”””” debug command to send a framedebug command to send a framedebug command to send a framedebug command to send a framefrom one port to the other from one port to the other from one port to the other from one port to the other 

    Transmitter port

    Receiver port 0=RS232,1=RS485  ASCII string

     Always=1

    Use theUse theUse theUse the ““““S_APICOM_ShowConfigS_APICOM_ShowConfigS_APICOM_ShowConfigS_APICOM_ShowConfig”””” debug command todebug command todebug command todebug command to verify the business DB port setting (and if initialized) verify the business DB port setting (and if initialized) verify the business DB port setting (and if initialized) verify the business DB port setting (and if initialized)

    5 4 ) IED i ti t ti

  • 8/20/2019 YANN C264 Commissioning

    37/44

    > L2 4A C264 Expert utilisation 0237 37

    5.4 ) IED communication testing 

    1 ) Link together scc1 and Scc2 as follow 2 )Via the HyperTerminal launch the TEST_COMcommand

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    21

    22

    23

    24

    Scc2 T-

    GND

    Scc2 T+

    GND

    Scc1 T+

    Scc1 T-

      BIU 200

    connector

    example “ TEST_COM (1,2,1,”test port 1 to 2”,1)example “ TEST_COM (2,1,1,”test port 2 to 1”,1)

    5 4 ) IED i ti t ti

  • 8/20/2019 YANN C264 Commissioning

    38/44

    > L2 4A C264 Expert utilisation 0238 38

    5.4 ) IED communication testing 

    1 ) Link together scc3 and Scc4 as follow 2 )Via the HyperTerminal launch the command“test_com” to send frame from one port to another

    example “ TEST_COM (3,4,0,”test port 3 to 4”,1)example “ TEST_COM (4,3,0,”test port 4 to 3”,1)

    12

    3

    4

    5

    6

    78

    9

    1

    2

    3

    4

    5

    6

    7

    8

    9

    Scc3 Scc4

    5 5 ) IED communication Debug commands

  • 8/20/2019 YANN C264 Commissioning

    39/44

    > L2 4A C264 Expert utilisation 0239 39

    5.5 ) IED communication Debug commands

    >p CR 

    The following informationshould be displayed:

    “bootdevice :tffs=0,0

    “processor number :0

    “hostname :

    “file name :/flash/bin/vxWorks

    “inetonethernet :

    “ineton backplane :CR 

    “hostinet :

    “gateway inet :0.0.0.0

    “user :

    “ftp password :

    “flags : 0x0

    “targetname :

    “s tar tup s cri p t :

    “other :motfec

    Frame : C264 to IED

    Frame : IED response

    RS485 RS232

    No Communication with the IED : check C264 configuration

    and IED settings, check wiring with the IED

    Debug CommandsDebug CommandsDebug CommandsDebug CommandsTraces_scc1=16Traces_scc1=16Traces_scc1=16Traces_scc1=16Traces_scc2=16Traces_scc2=16Traces_scc2=16Traces_scc2=16

    -> traces_scc1=16traces_scc1 = 0x516fd8: value = 16 = 0x100x1274568 (T35IECM20): 0065ms -->P=1 L=5 :10 5B 02 5D 160x1274568 (T35IECM20): 0015ms

  • 8/20/2019 YANN C264 Commissioning

    40/44

    > L2 4A C264 Expert utilisation 0240 40

    IED communication - frames IEC

    IEC 60870-5-103 Frames

    ->-> traces_scc1=16traces_scc1 = 0x516fd8: value = 16 = 0x10

    0x1274568 (T35IECM20): 0065ms -->P=1 L=5 :10 5B 02 5D 160x1274568 (T35IECM20): 0015ms

  • 8/20/2019 YANN C264 Commissioning

    41/44

    > L2 4A C264 Expert utilisation 0241 41

    IED communication framesModBus

    ModBus Frames-> traces_scc2=16traces_scc2 = 0x516fdc: value = 16 = 0x100x129d068 (T42MBM21): 0025ms -->P=2 L=8 :02 02 00 00 00 10 79 F5

    0x129d068 (T42MBM21): 0020ms

  • 8/20/2019 YANN C264 Commissioning

    42/44

    > L2 4A C264 Expert utilisation 0242 42

    5.6 ) Printer communication testing 

    Scc1 & Scc2 port (serial link RS232 or RS485)

    Scc3, Scc4 used (usually) for printer orSCADA link (protocols ModBus, IEC

    60870-5-101)

    CentralProcessing Unitboard

    CPU260

    PIN

    RJ-45(female)

    1 2 3 4 5 6 7 8

    P3

    RJ-45(female)

    1 2 3 4 5 6 7 8

    RS232/

    RS485

    #

    Serial

    link 1GND

    TXD / T+

    RXD / T-

    DCD

    RTS

    CTS8

    7

    5

    3

    2

    1

    10/100 BaseT

    Ethernet-based link

    P2

    RJ-45(female)

    1 2 3 4 5 6 7 8

    RS232/

    RS485

    #

    Serial

    link 2GND

    TXD / T+

    RXD / T-

    DCD

    RTS

    CTS8

    7

    5

    3

    2

    1

    OPTIONNAL LINKS:

    Printer’s communication

  • 8/20/2019 YANN C264 Commissioning

    43/44

    > L2 4A C264 Expert utilisation 0243 43

    Printer s communication

    SS WESPEELAR CAS 36 - C264WESP 02/01/8809:07:37.890

    * 02/01/88 09:07:37.890 C264 WESPELAART3 REENCL ES NON BLSet* 02/01/88 09:07:37.890 WESPELAAR /DV SPS REENCL EN NBSet

    * 02/01/88 09:07:37.890 WESPELAAR /DV AR BLOCKINGReset* 02/01/88 09:07:38.079 WESPELAAR /IN FROM COM TRAN UHT< ET UMT<Reset* 02/01/88 09:07:38.094 WESPELAAR /IN FROM COM TRAN UHT >Set* 02/01/88 09:07:38.094 WESPELAAR /IN FROM COM TRAN UMT>

    Set* 02/01/88 09:07:40.521 WESPELAAR /P142 TPR GenStartReset* 02/01/88 09:07:40.798 WESPELAAR /INP FROM SYN RTU ENCL/DECL MAN DVOpen* 02/01/88 09:07:40.924 WESPELAAR /sd SPS DEVERROUILLA Reset* 02/01/88 09:07:40.924 WESPELAAR TC EN COURS

    Set* 02/01/88 09:07:40.940 WESPELAAR /DV+ SPS DECL PH CSet

    If no printing check : printers settings and C264 DB

    settings