zones software what needs to happen? intelligent devices with intelligent control panels, allow...

Download ZONES SOFTWARE What needs to happen? Intelligent devices with intelligent control panels, allow almost unlimited flexibility through the use of Software

If you can't read please download the document

Upload: phoebe-jennings

Post on 24-Dec-2015

213 views

Category:

Documents


0 download

TRANSCRIPT

  • Slide 1
  • Slide 2
  • ZONES SOFTWARE
  • Slide 3
  • What needs to happen?
  • Slide 4
  • Intelligent devices with intelligent control panels, allow almost unlimited flexibility through the use of Software Zones!
  • Slide 5
  • WHAT IS A SOFTWARE ZONE? FIRST LETS DISCUSS WHAT ITS NOT! A software zone is not a group of devices specifically wired together to form a WIRED ZONE A software zone is not a geographical zone such as a BUILDING OR A FLOOR ZONE
  • Slide 6
  • A SOFTWARE ZONE IS: A function within the control panel that allows the programming of a variety of output responses based on various initiating events known as: CBEs (Control By Event)
  • Slide 7
  • Word Association HOT TRUE ON HIGH ONE (1) ACTIVE COLD FALSE OFF LOW ZERO (0) INACTIVE
  • Slide 8
  • A SOFTWARE ZONE HAS JUST TWO STATES: ACTIVE or INACTIVE
  • Slide 9
  • The control panel operates CBEs through Lists of ZONES.
  • Slide 10
  • A ZONE becomes listed when it is added to a device points ZONE map through POINT PROGRAMMING
  • Slide 11
  • These lists are associations between INPUTS and OUTPUTS.
  • Slide 12
  • A zone (ZONE 47) mapped to a smoke detectors CBE list and the same zone (ZONE 47) mapped to a NACs CBE list constitute an association. BASIC EXAMPLE
  • Slide 13
  • Now, lets assume that the detectors goes into alarm. ZONE 47
  • Slide 14
  • The control panel during its polling cycle determines that the detector is in alarm. ZONE 47
  • Slide 15
  • THE ZONE(s) IN THE DETECTORS CBE LIST NOW BECOME ACTIVE. ZONE47
  • Slide 16
  • The control panel checks to see if there are any devices that have ZONE (Z47) mapped to their CBE lists. The control panel identifies the NAC as having ZONE (Z47) in its CBE list.
  • Slide 17
  • The control panel activates the NAC. 47 ZONE
  • Slide 18
  • (Note: The ZONE (Z47) did not activate the NAC)
  • Slide 19
  • Please note: THE DETECTOR AND THE NAC DO NOT HAVE TO BE ON THE SAME (SIGNALING LINE CIRCUIT) SLC!!!!
  • Slide 20
  • INPUT / OUTPUT ASSOCIATION -- -- -- -- -- 01
  • Slide 21
  • Slide 22
  • 9901
  • Slide 23
  • GENERAL ZONES THE NFS2-640 SUPPORTS 100 GENERAL ZONES
  • Slide 24
  • THE NFS2-3030 SUPPORTS 1000 GENERAL ZONES GENERAL ZONES
  • Slide 25
  • ZONE 00 GENERAL ALARM ZONE -- -- -- -- -- 0003
  • Slide 26
  • 0003
  • Slide 27
  • HOW MANY ZONES CAN BE PLACED IN A POINTS CBE LIST?
  • Slide 28
  • NFS2-640 = FIVE NFS2-3030 = TEN
  • Slide 29
  • CBE LIST 5 POSITIONS NFS2-640
  • Slide 30
  • CBE LIST - 10 POSITIONS NFS2-3030
  • Slide 31
  • CBE List Activation! -- -- -- -- -- 90030925030834
  • Slide 32
  • NFS2-640 10 SPECIAL ZONES
  • Slide 33
  • ZF0INPUT OR OUTPUT PRESIGNAL (TIME) ZF1OUTPUT - SYS TROUBLE (NOT AC LOSS) ZF2OUTPUT - SYS TRBL AC LOSS OR BROWNOUT ZF3OUTPUT - SECURITY INPUT ACTIVE ZF4OUTPUT SUPERVISORY INPUT ACTIVE ZF5INPUT SWITCHES TO OCCUPIED LEVEL ZF6 ZF7HOLIDAY LIST ZF8OUTPUT MARCH OR TEMPORAL CODE ZF9PRE-ALARM
  • Slide 34
  • NFS2-3030 13 SPECIAL ZONES
  • Slide 35
  • ZF0INPUT OR OUTPUT PRESIGNAL (TIME) ZF1OUTPUT - SYS TROUBLE (NOT AC LOSS) ZF2OUTPUT - SYS TRBL AC LOSS OR BROWNOUT ZF3OUTPUT - SECURITY INPUT ACTIVE ZF4OUTPUT SUPERVISORY INPUT ACTIVE ZF5INPUT SWITCHES TO OCCUPIED LEVEL ZF9PRE-ALARM (ALERT/ACTION) ZF10ALARM VERIFICATION ZF11DRILL ACTIVE NORMAL AFTER RESET ZF12ACKNOWLEDGE 2 SECONDS NORMAL ZF13SIGNAL SILENCE 2 SECONDS NORMAL ZF14SYSTEM RESET 10 SECONDS NORMAL ZF15DISABLED EVENTS NORMAL AFTER ALL CLEARED
  • Slide 36
  • Practice Session