zxdu68 t601 product description v1.0 20101221 en

14
Operator Logo ZXDU68 T601 Product Description

Upload: adeepcdma

Post on 28-Jul-2015

263 views

Category:

Technology


13 download

TRANSCRIPT

Page 1: Zxdu68 t601 product description v1.0 20101221 en

Operator Logo

ZXDU68 T601 Product Description

Page 2: Zxdu68 t601 product description v1.0 20101221 en
Page 3: Zxdu68 t601 product description v1.0 20101221 en

ZXDU68 T601 Product Description

ZTE Confidential Proprietary © 2009 ZTE Corporation. All rights reserved. I

ZXDU68 T601 Product Description

Version Date Author Approved By Remarks

V1.0 2009-09-21 Liu Xiaoguang

Wang Dongxu, Li Zhaowei, He Limin, Liu Jiangang, Guo Yubo, Yang Dou

Not open to the Third Party

© 2009 ZTE Corporation. All rights reserved.

ZTE CONFIDENTIAL: This document contains proprietary information of ZTE and is not to be disclosed or used without the prior written permission of ZTE.

Due to update and improvement of ZTE products and technologies, information in this document is subjected to change without notice.

Page 4: Zxdu68 t601 product description v1.0 20101221 en

ZXDU68 T601 Product Description

II © 2009 ZTE Corporation. All rights reserved. ZTE Confidential Proprietary

TABLE OF CONTENTS

1 Overview ................................................................................................................ 1 1.1 System Introduction ................................................................................................. 1 1.2 System Structure ..................................................................................................... 1 1.3 System Configuration .............................................................................................. 1

2 Features ................................................................................................................. 2

3 Functions ............................................................................................................... 4 3.1 Alarm management function .................................................................................... 4 3.2 Battery management function .................................................................................. 4 3.3 Control Functions .................................................................................................... 5 3.4 Three-Remote Functions ......................................................................................... 5 3.5 Man-machine interaction Functions ......................................................................... 5 3.6 Communication Functions ....................................................................................... 5

4 Technical Specifications ....................................................................................... 5

Page 5: Zxdu68 t601 product description v1.0 20101221 en

ZXDU68 T601 Product Description

ZTE Confidential Proprietary © 2009 ZTE Corporation. All rights reserved. III

FIGURES

Figure 1 Cabinet appearance .................................................................................................. 1

TABLES

Table 1 System Configuration ................................................................................................ 1 Table 2 Alarm management function ...................................................................................... 4 Table 3 Environment .............................................................................................................. 5 Table 4 AC Power Distribution ............................................................................................... 6 Table 5 DC Power Distribution ............................................................................................... 6 Table 6 AC Input Alarm and Protection .................................................................................. 7 Table 7 DC Output Alarm and Protectio ................................................................................. 7 Table 8 ZXDU68 T601System Dimensions and Weight .......................................................... 7 Table 9 Others ....................................................................................................................... 8

Page 6: Zxdu68 t601 product description v1.0 20101221 en
Page 7: Zxdu68 t601 product description v1.0 20101221 en

ZXDU68 T601 Product Description

ZTE Confidential Proprietary © 2009 ZTE Corporation. All rights reserved. 1

1 Overview

1.1 System Introduction ZXDU68 T601 system is a 50 A rectifier series power supply system with -48 VDC output. It is an intelligent and unattended power equipment widely used in commutation, microwave, optical transmission equipment and others communication systems.

In full configuration, the system can have twelve ZXD2400 (V4.3) rectifiers, which form a power system with a maximum of 600 A output.

1.2 System Structure

Figure 1 Cabinet appearance

1.3 System Configuration The system configuration is described as below:

Table 1 System Configuration

Component Maximum Configuration

AC Distribution

AC input

There are two AC input modes Single air switch mode: One input air switch (3 phases) Double air switch mode: Two input air switches (3 phases).

AC auxiliary output

Optional: Each phase current should be less than or equal to 16 A.

Page 8: Zxdu68 t601 product description v1.0 20101221 en

ZXDU68 T601 Product Description

2 © 2009 ZTE Corporation. All rights reserved. ZTE Confidential Proprietary

Component Maximum Configuration

DC Distribution

DC Output

Up to 10 load branches are available: 6 LLVD1 load branches (4 branches for the fuses and 2 for the air switches) and 4 LLVD2 load branches. Extended DC output: 7 LLVD1/LLVD2 extended air switch branches ( with at most 150 A total current) or 4 fuse branches (with at most 100 A per branch). The number of LLVD1 and LLVD2 load branches can be flexibly configured according to the user’s requirement.

DC Input Two battery input branches with 500 A fuses Emergency light

Optional configuration

Rectifier 12 sets

Monitoring Unit 1 set

Lightning Arrester

Level C lightning arrester (The lightning arrester should be installed before introducing the AC power supply to the power equipment.) DC surge arrester

Background Monitoring Software

The background monitoring software serves to realize the background monitoring of the power supply system. The system can be connected to the computer where the monitoring software is installed by means of RS232/RS485 interface or other networking modes.

Cabinet Height: 1600 mm (Optional: Add a 400 mm height top cap).

2 Features ZXDU68 T601 system has the following features.

• ZXD2400 (V4.3) rectifier module:

− Input power factor higher than 0.99.

− Rated efficiency higher than 92%.

− Power density up to 854 mW/cm3.

− Power loss during standby mode less than 4 W.

− Electromagnetic compatibility Complying with IEN61000, YD/T983 and standards. Conductive disturbance and radioactive Disturbance complying with EN55022A requirements.

− Complies with GB4943-2001 safety standard requirements.

Page 9: Zxdu68 t601 product description v1.0 20101221 en

ZXDU68 T601 Product Description

ZTE Confidential Proprietary © 2009 ZTE Corporation. All rights reserved. 3

− AC input under/over-voltage protection, PFC output under/over-voltage protection, DC output over-voltage/current protection and over temperature protection.

− Drawer-like structure, convenient for transportation, installation and maintenance.

− The rectifiers are hot-pluggable. In case any rectifier fails, the faulty rectifier automatically stops working.

• Power management features:

− The system operates from three-phase AC power source with a wide input voltage ranging from 80 VAC to 300 VAC, suitable for areas with poor power supply quality.

− Automatic and reliable charging and discharging control function, extending the battery life span.

− LLVD functions (can be configured manually or automatically). These functions can be configured according to the user requirement.

− The system is provided with class C lightning protection, DClightning protection and other lightning protection types, enssuring high reliability of the whole system.

− AC auxiliary output function (optional).

• System features:

− Meets the modern communication technology trend requirements.

− The system adopts modular design and automatic current equalization technology, which make it capable of N+1 backup and easy expansion.

− PC based background monitoring and management functions: remote measurement, remote information, remote control.

− The system has a flexible configuration. Rectifiers can be added/removed while the system is operating.

− High reliability with MTBF greater than or equal to 5 x 106h (N+1 backups; MTTR < 2 h).

− Compact structure. Various units, including AC/DC power distribution unit, rectifiers and the monitoring unit, are built in one chassis. ring

• Intelligent monitoring unit, performing foreground monitor and the following management functions:

− Querying real-time operation information.

− Querying history operation information.

Page 10: Zxdu68 t601 product description v1.0 20101221 en

ZXDU68 T601 Product Description

4 © 2009 ZTE Corporation. All rights reserved. ZTE Confidential Proprietary

− Querying battery discharge record and peak record.

− Setting system parameters.

− Setting battery parameters.

− Setting communication parameters.

− Setting output relay parameters.

− Setting alarm threshold.

3 Functions

3.1 Alarm management function The monitoring unit processes the real-time system data according to the parameters set by users. When a critical fault occurs, it generates an alarm and reports it to background PC automatically. The fault information is then recorded and stored locally. Users can access to alarms information through the monitoring unit directly. The details are shown in the table below:

Table 2 Alarm management function

Button Description

Alarm setting A user can set the upper and lower limits of the system parameters according to the real application requirements.

Alarm management

The system has reliable and real-time alarm management function.

Alarm mode

In case of any alarm, the monitoring unit generates audible and visual signal to inform the maintenance personnel and reports the alarm information to a background PC through its communication interface. Press any key to mute the alarm sound; then the ALM indicator keeps glowing until the fault is eliminated.

3.2 Battery management function The monitoring unit manages storage battery charging in three modes: periodic equalized charging mode, equalized charging mode (after power failure) and floating charging mode.

When the mains supply is cut off, the battery supplies the powerfor load. When the battery is discharged to a certain voltage (user can set this threshold through the monitoring unit), an alarm will be generated.

Page 11: Zxdu68 t601 product description v1.0 20101221 en

ZXDU68 T601 Product Description

ZTE Confidential Proprietary © 2009 ZTE Corporation. All rights reserved. 5

3.3 Control Functions The system is provided with manual /automatic Load Low Voltage Disconnect (LLVD) functions. Users can configure the loads according to the real application requirement. Control the power-on, power-off, the equalized charging and the float charging of the rectifier through the control instruction of the foreground man-machine interaction operation or through the background computer. Adjust the output voltage of the rectifier (-42 V to -58 V, adjustable continuously) according to the user requirements.

3.4 Three-Remote Functions • Remote information.

• Remote control.

• Remote measurement.

3.5 Man-machine interaction Functions The LCD and keys constitute the man-machine interaction, which enables the user to set the system operating parameters and query the related information. The operation is convenient and reliable.

3.6 Communication Functions RS232/RS485 communication interfaces are provided. Centralized monitoring can be realized through other modes.

4 Technical Specifications

Table 3 Environment

Item Specification

Operating temperature –5°C to +45°C ( +15°C to +25°C recommended)

Storage temperature –40°C to +70°C

Relative humidity 10% to 90% without condensation (40% to 60% recommended)

Air pressure 70 KPa to 106 KPa

Other requirements

No conductive dusts or corrosive gases

No explosion hazard, no shake or jolt

Page 12: Zxdu68 t601 product description v1.0 20101221 en

ZXDU68 T601 Product Description

6 © 2009 ZTE Corporation. All rights reserved. ZTE Confidential Proprietary

Item Specification

The floor slope angle is less than or equal to than 5°

Table 4 AC Power Distribution

Item Specification

Input mode Three-phase five-wire (L1, L2, L3, N, PE).

Rated input voltage 220 VAC (phase voltage)

Input voltage range 80 VAC to 300 VAC (phase voltage)

Frequency 45 Hz to 65 Hz

Input power factor ≥ 0.99 (with 100% load)

Level C lightning ≤ 40 kA

Table 5 DC Power Distribution

Item Specification

Rated output voltage -48 VDC

Output voltage range -42 VDC to -58 VDC, adjustable

Output current 0 to 600 A

Regulated voltage precision

≤ 0.6%

Weighted noise voltage < 2 mV

Peak-peak noise voltage ≤ 200 mV (20 MHz bandwidth)

Efficiency ≥ 92% (rated input; full load)

Broad frequency noise voltage

≤ 50 mV (3.4 kHz - 150 kHz)

≤ 20 mV (0.15 MHz - 30 MHz)

Discrete frequencynoise voltage

≤ 5 mV (3.4 kHz - 150 kHz)

≤ 3 mV (150 kHz - 200 kHz)

≤ 2 mV (200 kHz - 500 kHz)

≤ 1 mV (0.5 MHz - 30 MHz)

DC lightning discharge current

≤ 5 kA

Page 13: Zxdu68 t601 product description v1.0 20101221 en

ZXDU68 T601 Product Description

ZTE Confidential Proprietary © 2009 ZTE Corporation. All rights reserved. 7

Table 6 AC Input Alarm and Protection

Item Specification

AC Vol. Max. Default: (286±5) VAC, which can be modified through the monitoring unit.

Threshold of recovery from AC over-voltage alarm

Default: (276±5) VAC, which should be 10 V lower than AC Vol. Max.

AC Vol.Min. Default: (154±5) V VAC, which can be modified through the monitoring unit.

Threshold of recovery from AC under-voltage alarm

Default: (164±5) VAC, which should be 10 V higher than AC Vol.Min.

Table 7 DC Output Alarm and Protectio

Item Specification

DC Vol.Max. Default: (58 ±0.2) VDC, which can be modified through the monitoring unit.

Threshold of recovery from DC over-voltage alarm

Default: (57.5±0.2) VDC, which should be 0.5 V lower than DC Vol.Max.

DC Vol.Min. Default: (48.0 ±0.2) VDC, which can be modified through the monitoring unit.

Threshold of recovery from DC under-voltage alarm

Default: (48.5±0.2) VDC, which should be 0.5 V higher than DC Vol.Min.

1-Shut Vol. Default: (46.0±0.2) VDC, which can be modified through the monitoring unit.

2-Shut Vol. Default: (45.0±0.2) VDC, which can be modified through the monitoring unit.

BatVol Min. Default: (47.0±0.2) VDC, which can be modified through the monitoring unit.

Table 8 ZXDU68 T601System Dimensions and Weight

Item Specification

ZXDU68 T601 main cabinet

Dimensions: 1600 mm × 600 mm × 400 mm (Height × Width × Depth).

Weight: 80 kg (excluding rectifiers and the monitoring unit).

ZXDU68 T601 top cap

Dimensions: 400 mm × 598 mm × 400 mm (Height × Width × Depth).

Weight: 9.5 kg

ZXD2400(V4.3) rectifier Dimensions: 134 mm × 87 mm × 318 mm (Height × Width × Depth).

Page 14: Zxdu68 t601 product description v1.0 20101221 en

ZXDU68 T601 Product Description

8 © 2009 ZTE Corporation. All rights reserved. ZTE Confidential Proprietary

Item Specification

Weight: 3.8 kg

Monitoring unit Dimensions: 134 mm × 87 mm × 310 mm (Height × Monitoring unit Width × Depth).

Weight: 2.2 kg.

Table 9 Others

Item Specification

Noise ≤ 55 dB (A).

MTBF ≥ 5x106 h.(N+1 backups, MTTR < 2 h).

Safety Complies with IEC950 and GB4943-2001 requirements.

EMC Complies with EN61000.

Conductive disturbance and radioactive disturbance Complies with EN55022 level A.

Earthquake resistance Complies with YD 5083-2005 and YD 5096-2005 requirements