zxdu68 t601 product description v1.0 20101221 en
TRANSCRIPT
![Page 1: Zxdu68 t601 product description v1.0 20101221 en](https://reader036.vdocuments.net/reader036/viewer/2022082205/55b72c05bb61ebee4f8b46ac/html5/thumbnails/1.jpg)
Operator Logo
ZXDU68 T601 Product Description
![Page 2: Zxdu68 t601 product description v1.0 20101221 en](https://reader036.vdocuments.net/reader036/viewer/2022082205/55b72c05bb61ebee4f8b46ac/html5/thumbnails/2.jpg)
![Page 3: Zxdu68 t601 product description v1.0 20101221 en](https://reader036.vdocuments.net/reader036/viewer/2022082205/55b72c05bb61ebee4f8b46ac/html5/thumbnails/3.jpg)
ZXDU68 T601 Product Description
ZTE Confidential Proprietary © 2009 ZTE Corporation. All rights reserved. I
ZXDU68 T601 Product Description
Version Date Author Approved By Remarks
V1.0 2009-09-21 Liu Xiaoguang
Wang Dongxu, Li Zhaowei, He Limin, Liu Jiangang, Guo Yubo, Yang Dou
Not open to the Third Party
© 2009 ZTE Corporation. All rights reserved.
ZTE CONFIDENTIAL: This document contains proprietary information of ZTE and is not to be disclosed or used without the prior written permission of ZTE.
Due to update and improvement of ZTE products and technologies, information in this document is subjected to change without notice.
![Page 4: Zxdu68 t601 product description v1.0 20101221 en](https://reader036.vdocuments.net/reader036/viewer/2022082205/55b72c05bb61ebee4f8b46ac/html5/thumbnails/4.jpg)
ZXDU68 T601 Product Description
II © 2009 ZTE Corporation. All rights reserved. ZTE Confidential Proprietary
TABLE OF CONTENTS
1 Overview ................................................................................................................ 1 1.1 System Introduction ................................................................................................. 1 1.2 System Structure ..................................................................................................... 1 1.3 System Configuration .............................................................................................. 1
2 Features ................................................................................................................. 2
3 Functions ............................................................................................................... 4 3.1 Alarm management function .................................................................................... 4 3.2 Battery management function .................................................................................. 4 3.3 Control Functions .................................................................................................... 5 3.4 Three-Remote Functions ......................................................................................... 5 3.5 Man-machine interaction Functions ......................................................................... 5 3.6 Communication Functions ....................................................................................... 5
4 Technical Specifications ....................................................................................... 5
![Page 5: Zxdu68 t601 product description v1.0 20101221 en](https://reader036.vdocuments.net/reader036/viewer/2022082205/55b72c05bb61ebee4f8b46ac/html5/thumbnails/5.jpg)
ZXDU68 T601 Product Description
ZTE Confidential Proprietary © 2009 ZTE Corporation. All rights reserved. III
FIGURES
Figure 1 Cabinet appearance .................................................................................................. 1
TABLES
Table 1 System Configuration ................................................................................................ 1 Table 2 Alarm management function ...................................................................................... 4 Table 3 Environment .............................................................................................................. 5 Table 4 AC Power Distribution ............................................................................................... 6 Table 5 DC Power Distribution ............................................................................................... 6 Table 6 AC Input Alarm and Protection .................................................................................. 7 Table 7 DC Output Alarm and Protectio ................................................................................. 7 Table 8 ZXDU68 T601System Dimensions and Weight .......................................................... 7 Table 9 Others ....................................................................................................................... 8
![Page 6: Zxdu68 t601 product description v1.0 20101221 en](https://reader036.vdocuments.net/reader036/viewer/2022082205/55b72c05bb61ebee4f8b46ac/html5/thumbnails/6.jpg)
![Page 7: Zxdu68 t601 product description v1.0 20101221 en](https://reader036.vdocuments.net/reader036/viewer/2022082205/55b72c05bb61ebee4f8b46ac/html5/thumbnails/7.jpg)
ZXDU68 T601 Product Description
ZTE Confidential Proprietary © 2009 ZTE Corporation. All rights reserved. 1
1 Overview
1.1 System Introduction ZXDU68 T601 system is a 50 A rectifier series power supply system with -48 VDC output. It is an intelligent and unattended power equipment widely used in commutation, microwave, optical transmission equipment and others communication systems.
In full configuration, the system can have twelve ZXD2400 (V4.3) rectifiers, which form a power system with a maximum of 600 A output.
1.2 System Structure
Figure 1 Cabinet appearance
1.3 System Configuration The system configuration is described as below:
Table 1 System Configuration
Component Maximum Configuration
AC Distribution
AC input
There are two AC input modes Single air switch mode: One input air switch (3 phases) Double air switch mode: Two input air switches (3 phases).
AC auxiliary output
Optional: Each phase current should be less than or equal to 16 A.
![Page 8: Zxdu68 t601 product description v1.0 20101221 en](https://reader036.vdocuments.net/reader036/viewer/2022082205/55b72c05bb61ebee4f8b46ac/html5/thumbnails/8.jpg)
ZXDU68 T601 Product Description
2 © 2009 ZTE Corporation. All rights reserved. ZTE Confidential Proprietary
Component Maximum Configuration
DC Distribution
DC Output
Up to 10 load branches are available: 6 LLVD1 load branches (4 branches for the fuses and 2 for the air switches) and 4 LLVD2 load branches. Extended DC output: 7 LLVD1/LLVD2 extended air switch branches ( with at most 150 A total current) or 4 fuse branches (with at most 100 A per branch). The number of LLVD1 and LLVD2 load branches can be flexibly configured according to the user’s requirement.
DC Input Two battery input branches with 500 A fuses Emergency light
Optional configuration
Rectifier 12 sets
Monitoring Unit 1 set
Lightning Arrester
Level C lightning arrester (The lightning arrester should be installed before introducing the AC power supply to the power equipment.) DC surge arrester
Background Monitoring Software
The background monitoring software serves to realize the background monitoring of the power supply system. The system can be connected to the computer where the monitoring software is installed by means of RS232/RS485 interface or other networking modes.
Cabinet Height: 1600 mm (Optional: Add a 400 mm height top cap).
2 Features ZXDU68 T601 system has the following features.
• ZXD2400 (V4.3) rectifier module:
− Input power factor higher than 0.99.
− Rated efficiency higher than 92%.
− Power density up to 854 mW/cm3.
− Power loss during standby mode less than 4 W.
− Electromagnetic compatibility Complying with IEN61000, YD/T983 and standards. Conductive disturbance and radioactive Disturbance complying with EN55022A requirements.
− Complies with GB4943-2001 safety standard requirements.
![Page 9: Zxdu68 t601 product description v1.0 20101221 en](https://reader036.vdocuments.net/reader036/viewer/2022082205/55b72c05bb61ebee4f8b46ac/html5/thumbnails/9.jpg)
ZXDU68 T601 Product Description
ZTE Confidential Proprietary © 2009 ZTE Corporation. All rights reserved. 3
− AC input under/over-voltage protection, PFC output under/over-voltage protection, DC output over-voltage/current protection and over temperature protection.
− Drawer-like structure, convenient for transportation, installation and maintenance.
− The rectifiers are hot-pluggable. In case any rectifier fails, the faulty rectifier automatically stops working.
• Power management features:
− The system operates from three-phase AC power source with a wide input voltage ranging from 80 VAC to 300 VAC, suitable for areas with poor power supply quality.
− Automatic and reliable charging and discharging control function, extending the battery life span.
− LLVD functions (can be configured manually or automatically). These functions can be configured according to the user requirement.
− The system is provided with class C lightning protection, DClightning protection and other lightning protection types, enssuring high reliability of the whole system.
− AC auxiliary output function (optional).
• System features:
− Meets the modern communication technology trend requirements.
− The system adopts modular design and automatic current equalization technology, which make it capable of N+1 backup and easy expansion.
− PC based background monitoring and management functions: remote measurement, remote information, remote control.
− The system has a flexible configuration. Rectifiers can be added/removed while the system is operating.
− High reliability with MTBF greater than or equal to 5 x 106h (N+1 backups; MTTR < 2 h).
− Compact structure. Various units, including AC/DC power distribution unit, rectifiers and the monitoring unit, are built in one chassis. ring
• Intelligent monitoring unit, performing foreground monitor and the following management functions:
− Querying real-time operation information.
− Querying history operation information.
![Page 10: Zxdu68 t601 product description v1.0 20101221 en](https://reader036.vdocuments.net/reader036/viewer/2022082205/55b72c05bb61ebee4f8b46ac/html5/thumbnails/10.jpg)
ZXDU68 T601 Product Description
4 © 2009 ZTE Corporation. All rights reserved. ZTE Confidential Proprietary
− Querying battery discharge record and peak record.
− Setting system parameters.
− Setting battery parameters.
− Setting communication parameters.
− Setting output relay parameters.
− Setting alarm threshold.
3 Functions
3.1 Alarm management function The monitoring unit processes the real-time system data according to the parameters set by users. When a critical fault occurs, it generates an alarm and reports it to background PC automatically. The fault information is then recorded and stored locally. Users can access to alarms information through the monitoring unit directly. The details are shown in the table below:
Table 2 Alarm management function
Button Description
Alarm setting A user can set the upper and lower limits of the system parameters according to the real application requirements.
Alarm management
The system has reliable and real-time alarm management function.
Alarm mode
In case of any alarm, the monitoring unit generates audible and visual signal to inform the maintenance personnel and reports the alarm information to a background PC through its communication interface. Press any key to mute the alarm sound; then the ALM indicator keeps glowing until the fault is eliminated.
3.2 Battery management function The monitoring unit manages storage battery charging in three modes: periodic equalized charging mode, equalized charging mode (after power failure) and floating charging mode.
When the mains supply is cut off, the battery supplies the powerfor load. When the battery is discharged to a certain voltage (user can set this threshold through the monitoring unit), an alarm will be generated.
![Page 11: Zxdu68 t601 product description v1.0 20101221 en](https://reader036.vdocuments.net/reader036/viewer/2022082205/55b72c05bb61ebee4f8b46ac/html5/thumbnails/11.jpg)
ZXDU68 T601 Product Description
ZTE Confidential Proprietary © 2009 ZTE Corporation. All rights reserved. 5
3.3 Control Functions The system is provided with manual /automatic Load Low Voltage Disconnect (LLVD) functions. Users can configure the loads according to the real application requirement. Control the power-on, power-off, the equalized charging and the float charging of the rectifier through the control instruction of the foreground man-machine interaction operation or through the background computer. Adjust the output voltage of the rectifier (-42 V to -58 V, adjustable continuously) according to the user requirements.
3.4 Three-Remote Functions • Remote information.
• Remote control.
• Remote measurement.
3.5 Man-machine interaction Functions The LCD and keys constitute the man-machine interaction, which enables the user to set the system operating parameters and query the related information. The operation is convenient and reliable.
3.6 Communication Functions RS232/RS485 communication interfaces are provided. Centralized monitoring can be realized through other modes.
4 Technical Specifications
Table 3 Environment
Item Specification
Operating temperature –5°C to +45°C ( +15°C to +25°C recommended)
Storage temperature –40°C to +70°C
Relative humidity 10% to 90% without condensation (40% to 60% recommended)
Air pressure 70 KPa to 106 KPa
Other requirements
No conductive dusts or corrosive gases
No explosion hazard, no shake or jolt
![Page 12: Zxdu68 t601 product description v1.0 20101221 en](https://reader036.vdocuments.net/reader036/viewer/2022082205/55b72c05bb61ebee4f8b46ac/html5/thumbnails/12.jpg)
ZXDU68 T601 Product Description
6 © 2009 ZTE Corporation. All rights reserved. ZTE Confidential Proprietary
Item Specification
The floor slope angle is less than or equal to than 5°
Table 4 AC Power Distribution
Item Specification
Input mode Three-phase five-wire (L1, L2, L3, N, PE).
Rated input voltage 220 VAC (phase voltage)
Input voltage range 80 VAC to 300 VAC (phase voltage)
Frequency 45 Hz to 65 Hz
Input power factor ≥ 0.99 (with 100% load)
Level C lightning ≤ 40 kA
Table 5 DC Power Distribution
Item Specification
Rated output voltage -48 VDC
Output voltage range -42 VDC to -58 VDC, adjustable
Output current 0 to 600 A
Regulated voltage precision
≤ 0.6%
Weighted noise voltage < 2 mV
Peak-peak noise voltage ≤ 200 mV (20 MHz bandwidth)
Efficiency ≥ 92% (rated input; full load)
Broad frequency noise voltage
≤ 50 mV (3.4 kHz - 150 kHz)
≤ 20 mV (0.15 MHz - 30 MHz)
Discrete frequencynoise voltage
≤ 5 mV (3.4 kHz - 150 kHz)
≤ 3 mV (150 kHz - 200 kHz)
≤ 2 mV (200 kHz - 500 kHz)
≤ 1 mV (0.5 MHz - 30 MHz)
DC lightning discharge current
≤ 5 kA
![Page 13: Zxdu68 t601 product description v1.0 20101221 en](https://reader036.vdocuments.net/reader036/viewer/2022082205/55b72c05bb61ebee4f8b46ac/html5/thumbnails/13.jpg)
ZXDU68 T601 Product Description
ZTE Confidential Proprietary © 2009 ZTE Corporation. All rights reserved. 7
Table 6 AC Input Alarm and Protection
Item Specification
AC Vol. Max. Default: (286±5) VAC, which can be modified through the monitoring unit.
Threshold of recovery from AC over-voltage alarm
Default: (276±5) VAC, which should be 10 V lower than AC Vol. Max.
AC Vol.Min. Default: (154±5) V VAC, which can be modified through the monitoring unit.
Threshold of recovery from AC under-voltage alarm
Default: (164±5) VAC, which should be 10 V higher than AC Vol.Min.
Table 7 DC Output Alarm and Protectio
Item Specification
DC Vol.Max. Default: (58 ±0.2) VDC, which can be modified through the monitoring unit.
Threshold of recovery from DC over-voltage alarm
Default: (57.5±0.2) VDC, which should be 0.5 V lower than DC Vol.Max.
DC Vol.Min. Default: (48.0 ±0.2) VDC, which can be modified through the monitoring unit.
Threshold of recovery from DC under-voltage alarm
Default: (48.5±0.2) VDC, which should be 0.5 V higher than DC Vol.Min.
1-Shut Vol. Default: (46.0±0.2) VDC, which can be modified through the monitoring unit.
2-Shut Vol. Default: (45.0±0.2) VDC, which can be modified through the monitoring unit.
BatVol Min. Default: (47.0±0.2) VDC, which can be modified through the monitoring unit.
Table 8 ZXDU68 T601System Dimensions and Weight
Item Specification
ZXDU68 T601 main cabinet
Dimensions: 1600 mm × 600 mm × 400 mm (Height × Width × Depth).
Weight: 80 kg (excluding rectifiers and the monitoring unit).
ZXDU68 T601 top cap
Dimensions: 400 mm × 598 mm × 400 mm (Height × Width × Depth).
Weight: 9.5 kg
ZXD2400(V4.3) rectifier Dimensions: 134 mm × 87 mm × 318 mm (Height × Width × Depth).
![Page 14: Zxdu68 t601 product description v1.0 20101221 en](https://reader036.vdocuments.net/reader036/viewer/2022082205/55b72c05bb61ebee4f8b46ac/html5/thumbnails/14.jpg)
ZXDU68 T601 Product Description
8 © 2009 ZTE Corporation. All rights reserved. ZTE Confidential Proprietary
Item Specification
Weight: 3.8 kg
Monitoring unit Dimensions: 134 mm × 87 mm × 310 mm (Height × Monitoring unit Width × Depth).
Weight: 2.2 kg.
Table 9 Others
Item Specification
Noise ≤ 55 dB (A).
MTBF ≥ 5x106 h.(N+1 backups, MTTR < 2 h).
Safety Complies with IEC950 and GB4943-2001 requirements.
EMC Complies with EN61000.
Conductive disturbance and radioactive disturbance Complies with EN55022 level A.
Earthquake resistance Complies with YD 5083-2005 and YD 5096-2005 requirements