ГОСТ 533-2000 ingl

28

Click here to load reader

Upload: viacheslavverdesh

Post on 29-Sep-2015

219 views

Category:

Documents


1 download

DESCRIPTION

ГОСТ 533-2000 ingl

TRANSCRIPT

533-2000

GOST 533-2000

( 34-3-88)

UDC 621 Group E62

INTERSTATE COUNCIL

ON STANDARDIZATION, METROLOGY AND CERTIFICATION

THE INTERSTATE STANDARD

CARS THE ELECTRIC ROTATING.

TURBOGENERATORS

The general specifications

Rotating electrical machinery. Turbo-generators. General specifications 29.160.20

OKP 33 8300

Date of Introduction 20020101

The foreword

1 it is developed by Interstate technical committee MTK 333 Rotating electric cars, joint-stock company electric power industry Scientific research institute () and electromechanical engineering Scientific research institute () the Russian Federation

It is brought by Gosstandart of Russia

2 it is accepted by Interstate Council about standardization, metrology and certification (the report 17 from June, 22nd, 2000)

For acceptance have voted:StateNational standards body

The Azerbaijan Republic

Republic Armenia

Byelorussia Gosstandart of Belarus

Republic Georgia

Republic Kazakhstan Republic Kazakhstan Gosstandart

The Kirghiz Republic

Republic Moldova

The Russian FederationGosstandart of Russia

Republic Tajikistan

Turkmenistan

Republic Uzbekistan

UkraineGosstandart of Ukraine

3 Sections 1, 5, 6, 7 and 12 this standards represent authentic text 34-388 Rotating electric cars. A part 3: Special requirements for synchronous turbogenerators

On standardization and metrology from April, 2nd, 2001 157-st the interstate standard of GOST 5332000 is installed by 4 Decision of the State committee of the Russian Federation as state standard of the Russian Federation since January, 1st, 2002

5 INSTEAD OF GOST 533-85, GOST 533-93

1 Scope

This standard extends on stationary three-phase synchronous generators capacity of 2500 kw and more with synchronous frequency of rotation of 1500 rpm or 3000 rpm at frequency of a current of 50 Hz and frequency of rotation of 1800 rpm or 3600 rpm at frequency of a current of 60 Hz intended for development of electric energy at connection with steam and gas turbines (turbogenerators).

Standard requirements concern and the generators used as synchronous engines or jacks.

The obligatory requirements shown to turbogenerators, stated in sections 4-13, except 4.2, 4.8, 6.2, 6.13, 7.14, 10.8, 12.3 and appendix A, positions and which requirements are recommended.

The additional requirements reflecting requirements of a national economy, are italicised.

2 Standard references

In this standard references to following standards are used:

GOST 2 Uniform system of the design documentation. Operational documents

GOST 2 Uniform system of the design documentation. Repair documents

GOST 12 Occupational safety standards system. Fire safety. The general requirements

GOST 12 Occupational safety standards system. Products electrotechnical. General safety requirements

GOST 12 Occupational safety standards system. Cars the electric rotating. Safety requirements

GOST 12 Occupational safety standards system. Tests and measurements electric. General safety requirements

GOST 15) System of working out and production statement on manufacture. An industrial and technological production

___________________

1) In territory of the Russian Federation operates with GOST 15.

GOST 27 Reliability in the technician. The basic concepts. Terms and definitions

GOST of 183-74 Cars the electric rotating. The general specifications

GOST of 8865-93 Systems of electric isolation. An estimation and classification

GOST of 10169-77 Cars the electric three-phase synchronous. Test methods

GOST of 11828-86 Cars the electric rotating. The general test methods

GOST of 11929-87 Cars the electric rotating. The general test methods. Noise level definition

GOST of 12969-67 Tablets for cars and devices. Technical requirements

GOST of 12971-67 Tablets rectangular for cars and devices. The sizes

GOST 1419296 Marks of cargoes

GOST of 15150-69 Cars, devices and other technical products. Executions for various climatic areas. Categories, conditions of operation, storage and transportation to parts of influence of climatic factors of an environment

GOST of 15543 Products electrotechnical. The general requirements regarding firmness to climatic external influencing factors

GOST 1650481 System of the state tests of production. Tests and production quality assurance. The basic terms and definitions

GOST of 17494-87 Cars the electric rotating. Classification of degrees of the protection provided with covers of rotating electric cars

GOST of 17516 Products electrotechnical. The general requirements regarding firmness to mechanical external influencing factors

GOST of 21130-75 Products electrotechnical. Clips earthing and grounding signs. A design and the sizes

GOST of 21558-88 Systems of excitation of turbogenerators, hydrogenerators and synchronous jacks. The general specifications

GOST of 23216-78 Products electrotechnical. Storage, transportation, time anticorrosive protection, packing. The general requirements and test methods

GOST 2536497 Units the stationary. Norms of vibration of support of waterpipes and the general requirements to carrying out of measurements

GOST 2594183 ( 34-272, 34-274) Cars the electric rotating. Methods of definition of losses and efficiency

GOST of 26772-85 Cars the electric rotating. A designation of conclusions and a rotation direction

GOST of 27471-87 Cars the electric rotating. Terms and definitions

3 Definitions

In this standard terms in accordance with GOST 27.002, GOST 183, GOST 16504, GOST 27471 are applied.

4 General requirements

Drawing 1

4.1 If another is not stipulated by this standard turbogenerators and their systems of excitation should correspond to the general requirements shown to rotating electric cars in accordance with GOST 183 and GOST 21558.

4.2 Key parametres of the turbogenerators connected to steam and gas turbines, are established on 1) taking into account this standard requirements.

Recommended values of parametres of turbogenerators are resulted in steam turbines in appendix A._____________

1) the agreement between the manufacturer and the basic consumer or the customer Hereinafter means.

4.3 Nominal frequency of rotation 1500 or 3000 rpm at frequency of a current of 50 Hz and 1800 or 3600 rpm at frequency of a current of 60 Hz.

4.4 Cars should suppose long work with rated power and a nominal power factor, and also with the stipulated agreement, section 7 and appendix A, the maximum loadings, at pressure deviations 5 % and frequency 2 % of rating values as it is shown by the shaded area in drawing 1.

Limiting excess of temperature or the limiting temperatures specified in table 1, it is necessary to apply only to an operating mode with nominal pressure and frequency.

Table 1 Limiting temperatures and excess of temperatures

Temperature measurement, (temperature excess,) a method

Parts of turbogenerators or the cooling environmentsopro -

Put in pawn termopreobra -

resistancetermo -

Metresopro -

Put in pawn termopreob-razovatelej resistancetermo -

Metre

Class InClass F

1 Cooling environment on an exit from directly cooled active parts:

Gas (air, hydrogen)110110130130

Water or oil85858585

2 Winding :

At indirect cooling by air(80)(85)(100)(105)

Hydrogen with absolute pressure, :

To 150 .(85)(105)

St. 150 to 200 .(80)(100)

"200 300(78)(98)

"300 400(73)(93)

400(70)(90)

At direct cooling by gas or a liquid120145

3 Winding of a rotor:

At indirect cooling

Air(90)(110)

Hydrogen(85)(105)

At direct cooling by gas (air, hydrogen) and number of zones of release of gas:

1 and 2100115

3 and 4105120

6110125

From 8 to 14 .115130

St. 14120135

4 Active steel of the core 120 (80)120 (80)140 (100)140 (100)

Notes

1 Supposed temperature of a winding of the rotor, measured by a resistance method, at direct cooling by a liquid should be established in the turbogenerator maintenance instruction.

2 Thermoconverters of resistance laid under a grooving wedge, it is supposed to supervise only temperature of windings with liquid cooling.

3 Ventilation of a rotor at direct cooling of a winding by gas is characterised by number of radial zones of an exit of gas on all length of a rotor. Zones of an exit of cooling gas from front parts of a winding on the one hand a rotor should be considered as one zone.

The general zones of an exit of the cooling environment of two axial opposite directed streams should be considered as two zones.

4 Decrease supposed winding temperatures at indirect air or hydrogen cooling for turbogenerators with rated voltage from above 11 in accordance with GOST 183.

5 temperatures of a winding Supposed value at direct cooling by a liquid are established in the turbogenerator maintenance instruction, but no more specified in the table.

Notes

1 In process of increase in a deviation of pressure and frequency from nominal excess of temperatures or temperature can progressively increase. Long work with rated power in some boundary currents of the shaded area can lead to growth temperatures approximately on 10 To.

Cars also should provide rated power at a nominal power factor at pressure change 5 % and frequency from plus of 3 % to a minus of rating values of 5 % as it is defined by external dotted border in drawing 1, however will take place thus the further increases temperatures.

2 For reduction of reduction of service life because of increase of temperatures or temperatures work of the car out of limits of the shaded area should be limited on duration and number of cases As far as possible capacity of the car should decrease or other measures should be undertaken

Turbogenerators should suppose long work with the lowered loading at simultaneous deviations of pressure over 5 %, but no more than to 10 %, and frequency to 2 % of rating values.Safe loads depending on their duration and number of cases of work out of the shaded zone should be specified the manufacturer in the car maintenance instruction3 Operating modes at the raised pressure in a combination to the lowered frequency or at the lowered pressure and the raised frequency are abnormal Thus work in the first of modes can lead to increase in excess of temperature of a winding of excitation. At the operating modes shown in drawing 1, overexcitation or the car and its transformer is not exceeded by 5 %.

4 it is necessary to consider influence of a deviation of frequency from nominal for work of other elements of a turbine unit, for example the turbine and auxiliaries the Manufacturer of the turbine should specify limits of change of frequency and time during which the turbine can work at this frequency. It is necessary to consider also possibility of work of auxiliaries at pressure and frequency change

4.5 Turbogenerators should be made for long typical operating mode S1 in accordance with GOST 183.4.6 Turbogenerators should be made a climatic modification At a category 3 in accordance with GOST 15150. Under the agreement it is supposed to make turbogenerators of other executions and categories.Rating values of climatic factors of an environment in accordance with GOST 15150 and GOST 15543.1 at:To height above sea level no more than 1000 m;The bottom value of temperature of air 5 (for turbogenerators with water or heat exchangers).Environment not explosive, not containing aggressive steams and gases in the concentration destroying metals and isolation, not sated in water steams and a current-carrying dust.Concentration of a dust should not exceed 10 mg/m3.4.7 Direction of rotation of turbogenerators should correspond to the turbine and be specified by the car or in it to the tablet, the sequence of phases by a designation of conclusions in alphabetic order, for example, U1, Vl, W1 in accordance with GOST 26772 besides, should be specified.

4.8 It is supposed to connect a winding in a star or a triangle, and if connection in a triangle winding connection in a star means specially is not specified. In any case if another is not provided by the agreement, the winding should have not less than six conclusions.

4.9 Nominal are those values of a current and pressure of a winding of excitation at which are provided nominal full capacity, pressure and a power factor at nominal frequency and pressure of hydrogen (for cars with hydrogen cooling), and the temperature of a winding of excitation corresponding to temperature of the primary cooling environment for the above-stated conditions of loading at the maximum temperature of the final cooling environment, specified in the standard document on the car.

At presence at the car of contact rings the excitation rated voltage includes also a power failure in the shchetochno-contact device.

4.10 If the agreement does not stipulate other the systems used for windings, on should be not below a class In in accordance with GOST 8865.

The maximum temperatures of conductors of windings, an active steel and the constructive parts of the car adjoining to isolation, at long work with loadings should not be till 4.17 above supposed GOST of 8865 values, according to a class the applied isolation.

Limiting supposed values temperatures or temperatures of active parts in a nominal mode depending on methods of their measurement should be specified the manufacturer and to be no more resulted in table 1.

4.11 Design of a winding a turbogenerator identical electric durability of isolation in front and grooving parts of a winding should be provided.4.12 Resistance of isolation of windings a turbogenerator concerning the case and between windings at temperature 1030 should be not more low 10 on each kilovolt of rated voltage of a winding (at water cooling after a purge and windings air).For more heats supposed resistance of isolation decreases twice on everyone 20 differences between temperature at which measurement is carried out, and 30 .Resistance of isolation of windings in all cases should not be less than 0,5 .4.13 Isolation of windings should pass test for electric durability concerning the case of the car and between windings, and also test isolation in accordance with GOST 183 and GOST 11828.

Isolation of a winding of excitation should be tested for electric durability:

- The test pressure equal to tenfold rated voltage, but not less than 1500 In at rated voltage of a winding of excitation to 500 In;

- The test pressure equal 4000 In, plus the doubled rated voltage at rated voltage of a winding of excitation over 500 Century

4.14 In the car the measures interfering course of currents and their short circuit on the earth should be provided.

The turbogenerator bearing, oil consolidation of a shaft and (in cars with hydrogen cooling), shaft consolidation (in cars with air cooling) from the party opposite to the turbine, bearings of directly attached activators and , and also water supplies to a shaft and reducer bearings (if those are available) should be isolated from base plates and .The electric resistance of this isolation measured by pressure 1000 In, should be not less than 1 . Isolation from currents should be executed so that it could be supervised in the course of car work.

4.15 Rotors of turbogenerators should pass test at the raised frequency of rotation equal of 1,2 nominal frequencies of rotation, within two minutes if other is not established under the agreement.

4.16 Critical frequencies of rotation of a rotor as a part of a turbine unit should not cause emergency operation at operation, change of frequency of a current in the limits specified in 4.4.

4.17 Manufacturer in the maintenance instruction should result the loading diagramme showing limits of work of a turbogenerator on jet loading Q depending on active capacity , caused in admissible temperatures or temperatures, and in necessary cases also static stability of the car. The diagramme result for an operating mode with nominal pressure, frequency of a current, temperatures of cooling environments and pressure of hydrogen (for cars with hydrogen cooling).

On heatings in face zones turbogenerators should suppose work with nominal active loading in a mode of consumption of jet capacity at a power factor equal 0,95.

The typical diagramme is resulted in drawing 2.

Drawing 2

Diagramme borders are defined by following restrictions:

- The curve And corresponds to work with excitation rated current and consequently is characterised approximately by constant excess of temperature of a winding of a rotor;

- The curve In corresponds to work with rated current and is characterised approximately by constant excess of temperature of a winding ;

- The curve With shows a limit caused by local heatings in a face zone or static stability of the car, or a combination of both effects.

To point there corresponds rated power.

Under the agreement between the manufacturer and the customer it is necessary to result as well other diagrammes for working conditions at deviations of pressure and frequency according to 4.4 and parametres of the cooling environments differing from the nominal. The generator should work within diagramme borders under the set conditions on pressure, frequency, to temperatures of cooling environments and pressure of hydrogen. Work out of borders can lead to reduction of service life of the car.

4.18 Turbogenerators should without damages and residual deformations to suppose an overload on a current frequency rate of 1,5 rated currents during:

Two, minutes at indirect cooling of a winding;One minute at direct (gas or a liquid) winding cooling.Rotors of turbogenerators should maintain two-multiple rated current of excitation during not less:50 with for turbogenerators with indirect cooling of a winding of a rotor;20 with for turbogenerators capacity less than 800 with direct cooling of a winding of a rotor;15 with for turbogenerators capacity from 800 to 1200 ;10 with for turbogenerators capacity 1200 and more.Turbogenerators should maintain without damages of an overload with other combination of frequency rate of currents and their duration provided that additional rise in temperature of corresponding windings during an overload remains invariable.

Admissible in emergencies of duration of overloads and a rotor depending on frequency rates of currents in windings should be specified the manufacturer in the car maintenance instruction.

The note At overloads of temperature of windings can exceed reached in a nominal mode, therefore in a machine design should be considered, that number of overloads of limiting duration on the average no more than two in a year.

4.19 Turbogenerators should suppose long work at asymmetrical loading if currents in phases do not exceed rating value, and currents of return sequence do not surpass 10 % of rating value of a current at indirect cooling of a winding of a rotor and 8 % at direct. Rise in temperature of active parts of cars on 5 is thus supposed.4.20 Turbogenerators on thermal firmness of a rotor at short-term work in asymmetrical modes should maintain thermal influences at values of product of a square of a current of return sequence in relative units on a supposed operating time in seconds in an asymmetrical mode not less:

30 with for turbogenerators with indirect cooling of windings;15 with for turbogenerators with indirect cooling of a winding and direct cooling of a winding of a rotor;8 with for turbogenerators capacity to 800 inclusive with direct gas or liquid cooling of windings and a rotor;6 with for turbogenerators capacity from above 800 with direct hydrogen or liquid cooling of windings and a rotor.4.21 Idling with rated voltage at nominal frequency of rotation the factor of telephone harmonics in linear pressure should not exceed 3 % for turbogenerators capacity to 5000 kw inclusive and 1,5 %-for cars capacity more than 5000 kw.

4.22 Turbogenerators should maintain without damage sudden short circuits of any kind on winding conclusions at a rated load and the pressure equal 1,05 nominal, provided that maximum current in a phase is limited by external means and does not surpass the maximum current in a phase at sudden three-phase short circuit. Without damage means, that the damages interfering continuation of operation of the car though some deformations of a winding can take place should not take place.

If test for sudden short circuit spend by the new car it should be carried out after check of isolation of a winding on electric durability full test pressure in accordance with GOST 183.

In a case when the generator is intended for work on the general tyres, test for sudden three-phase short circuit should be spent from an idling mode at rated voltage. Test for sudden short circuit of turbogenerators, which join a power supply system through the transformer or a reactor (usually with the help closed ), spend from a mode of idling by the pressure equal of 70 % nominal, if are not co-ordinated other its lowered value, proceeding from a condition that the current of short circuit of the generator was same, as well as in case of three-phase short circuit on conclusions of the transformer or a reactor from a power supply system at work idling with rated voltage.

Turbogenerator consider passed test for sudden short circuit if the car it is possible at once or after insignificant repair of a winding to include in a network and if the car has passed test of isolation by the pressure equal of 80 % of test pressure, provided GOST 183 for the new generator. Insignificant it is considered small repair of fastening of front parts of a winding or the external insulation layers, not connected with replacement of cores.

The note Is abnormal high currents and the rotating moments can arise in operation in cases of short circuit close to the generator or switching-off and repeated inclusion of the car at more remote damage, and also at erroneous synchronisation. If at such modes splashes in the raised currents it is recommended to check up carefully the car took place, paying special attention on a winding . Before generator introduction in work it is necessary to eliminate any easing of fastening of a winding in order to avoid its possible damage caused by vibration; also it is necessary to check up possible deformations , and bolts .

4.23 Standard minimum values of the relation of short circuit () are resulted in 5.3 and 6.5.

Big minimum values can be established or co-ordinated, but thus some increase in the sizes of the car usually is required.

4.24 Values transitive xd ' and supertransitive xd "inductive resistance on a longitudinal axis should be established or co-ordinated with the account of working conditions of turbogenerators in a power supply system.

It is recommended to establish or co-ordinate the minimum value xd "at the level of saturation corresponding to rated voltage, and the maximum nonsaturated value xd ' at rated current. As xd" and xd ' in degrees are defined by the general magnetic streams it is necessary to mean, that xd "and xd ' are connected with each other and it is impossible to choose the top limit xd" too close to the bottom limit xd '.If another is not stipulated, xd "should be not less than 0,10 . A unit at the level of saturation corresponding to rated voltage.

xd "and xd ' can be established or co-ordinated also at other level of saturation.

If makes a reservation, that xd "and xd ' should be defined by practical consideration tests should be spent according to GOST 10169.

Thus if:

- The limiting values provided by this standard or other limiting values , xd "and xd ' are established or co-ordinated, at the co-ordinated minimum value without the negative admission and the positive admission of 30 %, and at the co-ordinated maximum value without the positive admission and the negative admission of 30 %;

- , xd "and xd ' are established, but their limiting values , xd" and xd ' it is necessary to consider as rating values with the admission 15 % are not defined;

- , xd "and xd ' are not stipulated or are not co-ordinated, they are established by the manufacturer with the admission 15 %.

4.25 Static should not be more low:

1,7 for turbogenerators capacity to 160 ;

1,6 """St. 160 to 800 ;

1,5 """ 800 and more.

Static count under the formula

, (1)

Where an excitation current at a rated load, And;

An excitation current at the established three-phase short circuit and at rated current , And;

cos( a nominal power factor.

4.26 Vibration ( value of vibrating speed) bearings of turbogenerators and the activators jointed with them in the operating modes provided by this standard, should correspond to requirements of GOST 25364.Norms of vibration of the core and front parts of a winding , contact rings of a rotor are established in specifications on turbogenerators of concrete types.4.27 Average level of the sound measured on distance 1 m from an external contour of a turbogenerator and the activator jointed with it, cooled by gas on the opened and closed cycles, or from an external contour corresponding casings (at their presence), should not exceed 90 , and in the absence of the electromachine activator for the closed scheme of ventilation of the generator 85 if under the agreement more rigid norm is not established.4.28 Degrees of protection provided with covers of turbogenerators with air filling or cooling, IP54, with hydrogen cooling IP55, contact rings IP23 in accordance with GOST 17494.4.29 Turbogenerator should keep working capacity after short-term influences of external mechanical factors (emergency and turbines with failure of vacuum, etc.) on group M6 of GOST 17516.1 with restriction of the maximum amplitude of acceleration to 4,9 m/s2 (0,5 g) and to maintain seismic influence not less than 7 points on a scale MOSCOW TIME-64 (i.e. Amplitude of acceleration no more than 0,5 g at installation level).More rigid requirements are established under the agreement4.30 Greasing of bearings of a turbogenerator and activator directly connected to it should be carried out under pressure from the oil pump of the turbine.Oil giving in oil consolidations of a shaft of a turbogenerator with hydrogen cooling should be carried out from system turbines or under the individual scheme.As condensing oil in consolidations of a shaft and lubricant oil in bearings it is necessary to apply turbine oil.Under the agreement it is supposed to apply other lubricant liquid in basic bearings and shaft consolidations.In systems bearings of turbogenerators by capacity 110 and more, connected to the turbines which do not have the main oil pump on to a shaft, and in systems consolidations of a shaft of turbogenerators by capacity 60 and more short-term reservation of giving of oil should be provided at breaks of its receipt and for maintenance emergency without heavy consequences at the termination of receipt of oil from sources .4.31 In branch pipes of bearings of turbogenerators and activator directly connected to it, and also the oil consolidations intended for plum of oil, should be observation ports for supervision over a stream of leaving oil and the device for installation of the temperature indicator. About observation ports places for installation of fixtures should be provided.4.32 In bearings and consolidations of a shaft of a turbogenerator devices for remote measurement of temperature of loose leaves should be established. In bearings of turbogenerators capacity 60 possibility of installation of devices for remote measurement of vibration and the constant control of isolation also should be more provided.At turbogenerators with hydrogen cooling possibilities of joining of gas analyzers for the control over hydrogen leak in bearings and drain shaft consolidations (from the air party), and also branch pipes for giving of inert gas should be provided.4.33 Temperature of the oil leaving bearings of a turbogenerator, should not exceed 65 , and temperature of the loose leaf of the bearing 80 . The temperature of the loose leaf of oil consolidations should not exceed 80 for face types of consolidations and 90 for ring types of consolidation.4.34 For the control over winding temperature in the car should be put in pawn not less than six thermoconverters of resistance.

The general number laid in thermoconverters of resistance for the control of temperature of a winding and an active steel should be not less:9 for turbogenerators capacity less than 32 ;12 for turbogenerators capacity 32 and more.4.35 For measurement of temperature of cooling gas the following number of thermoconverters of resistance should be established:Not less than two ~ in a zone of an input of cooling gas in the car, brought on pipes or from an external cooler;On one or more on an exit of gas from everyone (for turbogenerators with built in );Not less than two in a zone of an exit of hot gas;One or more before or after the compressor.4.36 Turbogenerators in normal conditions of operation include in a network a method of exact synchronisation.4.37 Turbogenerators capacity to 800 (except the cars connected to gas turbines) for all service life should suppose not less than 10000 start-up (inclusions in a network) and no more than 330 in year, and turbogenerators capacities not less than 3600 start-up and no more than 120 in a year.4.38 Turbogenerators (except the cars resulted in rotation by gas turbines) should suppose speed of a set and change of active and jet loadings not less than 6 % nominal in a minute. In emergencies of speed of change of loadings to the generator are not limited.And loadings establish supposed number of dumps in specifications on turbogenerators of concrete types.4.39 Indicators of reliability and durability of turbogenerators are established in specifications on cars of concrete types and should be not below resulted in table 2.

Table 2 reliability IndicatorsThe indicator nameAverage value of an indicator for turbogenerators capacity

To 350 More than 350

Readiness factor 0,9960,995

Time between failures, 2200018000

Resource between major repairs, years 85

The full appointed service life, years4040

5 Turbogenerators with air cooling

5.1 Present section extends on turbogenerators in which active parts are cooled by air directly or indirectly, or the combined way.

5.2 Standard values of a power factor cos is (0,8 and 0,85 (overexcitation).

The note Other values cos can (be co-ordinated, thus it is necessary to mean, that at smaller values the turbogenerator will have the big sizes.

5.3 Measured values at rated voltage and rated current should be equal not less:

0,45 for turbogenerators capacity to 80 inclusive;

0,40 for turbogenerators capacity more than 80 to 150 inclusive.

For turbogenerators more than 150 value is established by capacity under the agreement.

5.4 System of ventilation should be closed. If the opened air system of ventilation in order to avoid a car overheat the measures preventing pollution of its ventilating channels should be provided is defined or co-ordinated.

If application of contact rings measures on prevention of pollution of the generator and the activator a coal dust should be taken is provided.

5.5 Requirements to temperature of a primary coolant, except for the turbogenerators resulted in rotation by gas turbines, in accordance with GOST 183.

If the maximum temperature of air or air temperature on an exit from a cooler air-water (in case of its use) differs from 40 admissible temperatures or excess of temperatures define in accordance with GOST 183.

Special requirements to temperature of a primary coolant for the turbogenerators resulted in rotation by gas turbines, are stated in 7.3 and 7.6.

5.6 If parametres of cooling water are not specified on concrete type of the car air coolers should be executed on temperature of cooling water on an input to 32 and working pressure of water not less than 170 .

Test pressure of air coolers should make not less than 1,5 maximum working pressure of cooling water and should be enclosed within 15 minutes

If pressure of water in an air cooler is supervised by the gate or other device lowering pressure attached to a source of water where pressure above working pressure in an air cooler the air cooler should be executed on more high pressure and it is tested if another is not stipulated, at pressure in 1,5 times above pressure of a source. This raised pressure should be defined the customer or the manufacturer of the car if the system of water supply of air coolers is included into the complete set of delivery of the generator.

Air coolers should be executed so that at a conclusion from operation of its one part for clearing the car could bear, at least, 2/3 (or under the agreement a smaller part) a rated load for a long time without excess of admissible temperature of elements of the car. In these conditions the temperature of primary cooling air can exceed settlement value.

5.7 Turbogenerators with air cooling (or filling) should be equipped by system the sprayed water or inert gas (turbogenerators with the hydrogen cooling, supposing work at air cooling).Degree of automation of system establish in specifications on turbogenerators of concrete types.At manufacturing of turbogenerators from the materials which are not sustaining combustion that should be specially confirmed by the manufacturer, system do not establish.6 Turbogenerators with hydrogen or liquid cooling

6.1 Present section concerns the cars which active parts directly or indirectly cool hydrogen or a liquid, and also at a combination of both ways of cooling. In some designs other gas, instead of hydrogen then if it is possible, apply the same requirements can be applied.

6.2 Manufacturer should specify pressure of hydrogen in the case at which the car gives out rated power.

Following values of superfluous pressure are preferable: 100, 200, 300, 400, 500, 600 .

Nominal superfluous pressure of hydrogen in the case should be not less than 50 .6.3 In turbogenerators with indirect hydrogen cooling cleanliness of hydrogen should be not below 97 %, at direct not below 98 %.Hydrogen leak a day (led to normal conditions) from the case at nominal pressure should not be more, 3:

3 for turbogenerators capacity to 32 ;

7 """St. 32 63 ;

10 """110 ;

12 """800 ;

18 """800 .

6.4 Standard power factor on car conclusions accept equal 0,8 for turbogenerators capacity to BUT and 0,85 or 0,9 (overexcitation) for turbogenerators capacities.

The note other values cos Can be co-ordinated,( thus it is necessary to mean, that at smaller values cos the turbogenerator (will have the big sizes.

6.5 Measured values at rated voltage and rated current should be not less:

0,45 for turbogenerators capacity to 200 inclusive;

0,40 """St. 200 800 0,35 """ 800.

With face boards and covers of coolers at use of hydrogen cooling internal explosion of the formed explosive mix should maintain 6.6 cars Collected the case at atmospheric pressure without danger to attendants. On request of the customer it is necessary to conduct tests by hydraulic pressure for check of durability of the case and boards. Such test should be spent at superfluous pressure 800 within 15 minutes

6.7 car insulators at hydrogen cooling should maintain superfluous pressure of gas not less than 800 .

It is supposed insulators on dielectric durability to test separately from the car. Tests spend on air during 1 mines at pressure not less than 1,5 multiple test pressure of a winding of the car.

The note - When conclusions have liquid cooling connection of liquid cooling is not obligatory at high-voltage test.

6.8 Temperature of primary cooling environments (coolants) of turbogenerators, except resulted in rotation by gas turbines, should correspond to requirements of GOST 183.

The maximum temperatures of primary coolants (hydrogen, a liquid) at nominal or the stipulated maximum loadings can differ from 40 (for example for application of the optimum heat exchanger with the set maximum temperature of a secondary coolant). In this case:

- With indirect cooling it is necessary to apply the corresponding points concerning calculation admissible of temperatures for cars with air cooling to cars;

- With direct cooling the temperatures resulted in table 1 should be applied to cars without changes.

The note to avoid excessive or changes of temperatures, the maximum temperature of a coolant usually should not deviate from 40 more than on 10 To.

Requirements to temperature of a primary coolant for the turbogenerators resulted in rotation by gas turbines, are resulted in 7.3 and 7.8.

6.9 Design of a turbogenerator should allow its use at nominal pressure of gas (superfluous) at height above sea level to 1000 m.

The note Is supposed work of standard cars with rated power at installation at the height exceeding 1000 m above sea level provided that the system of gas cooling provides nominal pressure (absolute) a primary coolant (hydrogen) irrespective of installation height. Thus between the customer and the manufacturer agreements concerning consolidations of a shaft, the case and auxiliary equipment should be reached.

6.10 For cars with direct cooling the temperature measured by built in gauges, does not define temperature of a hot point of a winding . Thus, if the maximum temperatures of a coolant on an exit from the cooled active parts, resulted in table 1, are not exceeded, temperature of a winding do not consider excessive.

The limit of the supposed temperature of a winding on gauges is intended for the prevention of excessive heating of isolation from the core. Indications of the built in temperature gauges can be used for the control of work of system of cooling of a winding.

For turbogenerators with liquid cooling of a winding possibility of the control of heatings of a winding in each parallel branch of a cooling liquid and the control of temperature of the core not less than in six points should be provided.The number of the temperature gauges intended for measurement of temperature of the cooling liquid on an input in the car, should be not less than two.

With direct cooling of a winding the coolant temperature on an exit from a winding should be measured in cars, at least, by three temperature gauges, thus gauges should be in direct contact to a coolant:

At gas cooling of a winding gauges should be established so close from exhaust outlets from cores, how much it is supposed by rules of electric safety;

At water cooling temperature gauges should be established in pipelines in the case of the car or is so close from a place of an exit of a coolant from the case, how much it is practically realizable to avoid a considerable difference between temperature in a point of measurement and temperature at which the coolant leaves a winding.

6.11 Coolers (, heat exchangers) if it is not stipulated differently, should be calculated on temperature of entering water to 32 and working superfluous pressure of water not less than 350 .

Test pressure should be in 1,5 times above the maximum working pressure and is enclosed within 15 minutes

If pressure of water in a cooler supervise by means of the gate or other device lowering pressure which is connected to system of water supply with pressure more than working pressure in a cooler coolers if another is not stipulated, should be executed on pressure in system of water supply and are tested by pressure in 1,5 times big this pressure. The raised pressure in water supply system should be stipulated the customer or is established by the manufacturer if the system of water supply of coolers is included into the complete set of delivery of the generator.

In some operational modes, and also at operations of filling of the case by hydrogen or its clearings of hydrogen, coolers can be exposed to pressure of gas in the absence of pressure of water. Therefore coolers should be carried out taking into account influence of pressure 800 from gas.

Coolers should be executed so that at switching-off of one section, for example for clearing, the turbogenerator could is long to bear not less than 2/3 rated loads (under the agreement with the customer a little smaller loading is supposed) without excess of admissible temperatures of active parts of the car. At work in this mode the temperature of a primary coolant can be above settlement.

6.12 Turbogenerators should be calculated on application of distillate for cooling of windings and a rotor with electric specific resistance not less than 2000 at temperature 25 and should suppose short-term decrease in electric specific resistance of distillate to 500 .6.13 For normal work of the turbogenerators considered in section 6, auxiliary systems (the list of systems is not considered settling, other systems and devices can be applied also) are required:

- System of gas cooling (hydrogen or other gas) with regulators of the control of pressure of gas in the car, with maintenance of possibilities of connection to systems of gas supply and gas;

- System of inert gas for a case purge (usually dioxide of carbon or nitrogen). Possibility of connection of this system to system of gas cooling and safe performance of operations of replacement of hydrogen Should be provided.

If for removal of inert gas after hydrogen replacement use station system of the compressed air which connection should be executed so that air got to the car only at operation of removal of inert gas, for example by use of one rearranged branch pipe;

- Devices for the control and the alarm system of degree of cleanliness of hydrogen in the case, and also cleanliness of inert gas at operations of replacement of hydrogen. It is necessary to use two independent means for the control of degree of cleanliness of hydrogen;

- The equipment for the control of condensing oil and, in case of need, for removal from gas and water oil.

The system emergency the consolidations, joining should be provided automatically at refusal of the basic system ;

- System (or systems) liquid cooling with pumps, coolers, filters and devices of regulation of temperature of a cooling liquid.

At hydrogen cooling use water supply system with pumps, devices of regulation of temperatures of water on an input and hydrogen on an exit;

- Devices for detection of reduction of the expense or the termination of course of a liquid through windings;

- Devices for measurement of electric conductivity of the liquid used for cooling of a winding, and conductivity maintenance at low enough level;

- Devices for indication and the alarm system of functioning of all auxiliaries and liquid occurrence in the car. Possibility of removal of a liquid from the car should be provided.

7 Turbogenerators resulted in rotation by gas turbines

7.1 Present section extends on the turbogenerators resulted in rotation by gas turbines, with the opened system of air cooling, and also with the closed system of cooling by air or hydrogen. As a final coolant water or air can be used.

Requirements concern also the generators disconnected from the turbine working as synchronous jacks.

7.2 Generator resulted in rotation by the gas turbine, should bear loading according to its rated power and loading possibilities under the conditions of operation stipulated by the standard.

7.3 For generators with the opened system of air cooling in temperature of a primary coolant is the temperature of air entering into the car usually corresponding to temperature of air. Limits of change of temperature of entering air are defined by the customer, usual limits of change of temperature are from a minus 5 to plus 40 "With.For cars with the closed system of cooling, temperature of a primary coolant the temperature of air or the hydrogen entering into the car from is. Limits of change of this temperature are defined by the manufacturer for reception of an optimum machine design and the coolers, based on limits of change of temperature of a secondary (final) coolant (air or water) in accordance with GOST 15543.1 or set by the customer.

7.4 Number of start-up in a year with a loading set should not surpass 500.

7.5 Speed of a set of active loading the generator is defined by the turbine.

Speeds of a set and change of active and jet loadings by the generator are not limited.

At the customer's request turbogenerators should provide start-up installations by frequency way at a food from the starting arrangement.7.6 Rated power of the generator is its long full capacity on conclusions to an installation site at nominal pressure and frequency of a current, a power factor and pressure of hydrogen (for cars with hydrogen cooling) at the temperature of a primary coolant equal 40 if another is not co-ordinated.

Rated power of gas turbines define at temperature of entering air 15 , and generator rated power define at temperature of entering cooling air or hydrogen 40 . At identical loading characteristics the gas turbine and the generator have different rated power.

At rated power should not be exceeded temperature or excess of the temperatures, resulted in table 1.

If other is not co-ordinated, generator parametres define with reference to rated power.

7.7 Loading characteristics define the greatest possible full capacity under the co-ordinated conditions of operation.

7.8 Basic capacity define long full capacity on generator conclusions to a place of its installation at nominal frequency of a current, pressure, a power factor and pressure of hydrogen (cars with hydrogen cooling). The range of change of basic capacity corresponds to a range of change of temperature of the final coolant defined for an installation site of the car (7.3). Thus excess of temperatures or temperature should not surpass defined in 7.9.

1 basic capacity; 2 peak capacity; 3 basic and peak capacities for cars with length of an active part of the core less than 2,5 m; 4 basic and peak capacities for cars with length of an active part of the core 2,5 m and more, 5 a rated power point; a scale And temperature of cooling air of cars with the opened system of cooling, a scale In temperature of a final coolant for cars with the closed system of cooling at use of air or hydrogen as a primary coolant

Drawing 3

Notes

1 For the generator with heat exchangers is not obligatory reduction of a scale for temperature of a primary coolant. Two scales for a final coolant are resulted to show forms of diagrammes.

2 At temperatures of a primary coolant more low 10 cars with active length of the core 2,5 m and more work with the fixed limiting excess of temperature. The small increase in capacity of the generator probably because because of decrease in the general temperature decreases resistance of a winding.

Basic capacity of the generator in watts, on car EFFICIENCY, should be equal or should exceed basic capacity of the gas turbine in the co-ordinated range of change of temperature of air on a turbine input on a place of its installation.

The manufacturer of the generator should give a curve of dependence of basic capacity of the car for the co-ordinated range of change of temperature of a final coolant on a generator installation site.

Typical curves of loading possibilities of the generator are resulted in drawing 3.

For cars with the opened air system of cooling the coolant temperature is close to air temperature on an input in the turbine (drawing 3, a scale).As agreed between the manufacturer and the customer it can be accepted, that below some stipulated temperature of air basic capacity of the generator is a little bit less than capacity of the turbine at satisfaction of all other requirements to the generator.

In cars with the closed system of cooling by air or hydrogen at use water the range of change of temperature of water (a final coolant) usually is less, than a range of change of temperature of air on a turbine input.

Hence, at decrease in temperature of air increase of capacity of the generator will be smaller, than at the turbine, and the sizes of the generator will be defined by capacity of the turbine at low temperatures of air that can lead to unfairly overestimated capacity of the generator at usual temperatures of air.

In these conditions the agreement on restriction of loading ability of the generator gets great value in an establishment of the optimum sizes of the car.

In cars with the closed system of cooling there is no idle time or constant dependence between air temperature on an input of the turbine and temperature of cooling water. Therefore in drawing 3 loading ability of the generator is presented depending on temperature of a final coolant (water) on a scale of Century

Taking into account told between the manufacturer and the customer the agreement on degree of conformity of loading abilities of the generator and the turbine should be reached.

7.9 For cars with indirect cooling of excess of temperatures at generator work on an installation site with basic capacity should correspond to table 1 with following changes:

- For temperatures of a primary coolant from 10 to 60 to the values of temperatures established in table 1 to add (40 minus temperature of a primary coolant) To;

- For temperatures of a primary coolant from a minus 20 to plus 10 at length of an active part of the core;

1) less than 2,5 m to the values of temperatures established in table 1 to add 30 To plus 1/2 (10 minus temperature of a primary coolant) To;

2) 2,5 m and more to the values of temperatures established in table 1 to add 30 To;

- For temperatures of a primary coolant more low a minus 20 or above 60 under the agreement between the customer and the manufacturer.

For windings with direct air or hydrogen cooling of temperature at generator work on an installation site should correspond to table 1 with following changes:

- For temperatures of a primary coolant from 10 to 60 without changes;

- For temperatures of a primary coolant from a minus 20 to plus 10 at length of an active part of the core;

1) less than 2,5 m from values of the temperatures established in table 1 to subtract 1/2 (10 minus temperature of a primary coolant) To;

2) 2,5 m and more from values of the temperatures established in table 1 to subtract (10 minus temperature of a primary coolant) To;

- For temperatures of a primary coolant more low a minus 20 or above plus 60 under the agreement between the customer and the manufacturer.

7.10 Peak capacities define long full capacities on generator conclusions to an installation site at nominal frequency of a current, pressure, a power factor and pressure of hydrogen (at its application). The range of change of peak capacities corresponds to a range of change of temperature of the final coolant defined for an installation site of the car (7.3). Thus excess of temperatures or temperature should not surpass the values defined at 7.11.

Positions 7.8 concerning a parity between basic capacities of the generator and the turbine concern also their peak capacities.

7.11 For cars with indirect cooling limiting excess of temperatures for peak capacity can be on 15 To above specified in 7.9.

For cars with direct air or hydrogen cooling of windings limiting temperatures can be on 15 To above specified in 7.9.

The note Work at peak capacity will lead to service life reduction as thermal ageing of isolation will approximately occur in 3 6 times faster, than at the temperature corresponding to base capacity of the generator.

7.12 On the tablet of the car the manufacturer specifies all data according to 12.1 and 12.2, and also peak capacity at temperature of a primary coolant for which the generator rated power is defined.

7.13 Thermal tests should be spent at a rated load and temperature of a primary coolant for which the car rated power is defined. It is supposed under the agreement to conduct thermal tests at any temperature of a primary coolant and corresponding base capacity. Temperature or excess of temperatures should correspond to requirements 7.9 with the amendment, in case of need, a difference in heights of an installation site and a place of tests it agree GOST 183.

7.14 At the customer's request generators should suppose work possibility at a detachment from the turbine in a mode of the synchronous jack. Base and peak capacities in modes of delivery and consumption of jet capacity at work as the jack should be co-ordinated.

8 Safety requirements

8.1 Turbogenerators should correspond to safety requirements of GOST 12.2.007.0, GOST 12.2.007.1 and GOST 12.1.004, including:8.1.1. Resistance of isolation of windings of the generator should correspond 4.128.1.2. Electric durability case and winding isolation in accordance with GOST 183. Isolation of a winding of excitation should pass test till 4.13.8.1.3 In a generator design the measures providing levels of vibration and noise till 4.26 and 4.27 should be provided.8.1.4 Degrees of protection against a touch to the current carrying and moving parts, provided with covers, - till 4.28 and GOST 17494.8.1.5 Contact rings and the device should have a protective casing, and at generators with hydrogen cooling the constructive measures preventing hit of hydrogen from cases of bearings and consolidations to contact rings should be provided.8.1.6 Designs the device and its casing should provide convenience and safety of replacement of brushes and .8.1.7 Durability of the case, insulators and elements systems of generators with hydrogen cooling should correspond to requirements 6.6 and 6.7.8.1.8 Places of a possible congestion of hydrogen (the case of bearings, protective and decorative casings) should have natural or independent ventilation.8.1.9 On the clips which have been put in pawn in the car of thermoconverters of resistance, located on the generator case, protective rated sportsmen should be established.Resistance of isolation of chains of thermoconverters of the resistance, measured pressure 500 In, should be not less than 1 .8.1.10 Case of the generator, base plates and pipelines of systems of cooling should be supplied by grounding elements in accordance with GOST 21130. The case should have two elements of grounding located in opposite places.Resistance between earthing elements and each metal part accessible to a touch which can appear energised, should not exceed 0,1 Ohm.8.1.11 Rotors of turbogenerators should maintain the raised frequency of rotation (4.15) without residual deformations or signs of other defects of its elements.8.1.12 Fire safety of the generator and its elements should be provided both in normal, and in emergency operationSettlement value of probability of occurrence of a fire in (from) the generator () should not exceed 10-6 in a year in accordance with GOST 12.1.004.8.2 At tests and measurements it is necessary to carry out safety requirements in accordance with GOST 12.3.019.9 Completeness

Into the turbogenerator complete set should enter the equipment and devices of systems of excitation, cooling systems, consolidations, the control and automatics diagnostics, spare parts and assembly adaptations in the volume established in specifications on turbogenerators of concrete types and the agreement.Operational and repair documentation should be enclosed to the complete set in accordance with GOST 2.601, GOST 2.602 in the volume established in specifications on turbogenerators of concrete types co-ordinated with the basic consumer or the customer.10 Acceptance procedures

10.1 For check and acknowledgement of conformity of turbogenerators and activators this standard requirements should spend acceptance, qualifying, , certified, periodic and standard tests.Acceptance, qualifying, , periodic and standard tests should spend manufacturer on this standard and GOST 15.001.The test centre (laboratory) accredited on the right of carrying out of specified tests according to standard documents should carry out certified tests of turbogenerators.10.2 tests should be spent on each turbogenerator under the following program:- Measurement of resistance of isolation of windings, concerning the case and between windings;- Measurement of resistance of isolation of the put in pawn thermoconverters of resistance;- Measurement of resistance of windings at a direct current in a cold condition;- Measurement of resistance of thermoconverters of resistance at a direct current in a cold condition;- Definition of the characteristic of the established three-phase short circuit;- Test of isolation of windings and a rotor concerning the case and between windings on electric durability till 4.13:Definition of the characteristic of idling;Check of symmetry of pressure;Rotor test at the raised frequency of rotation;Measurement of vibration of bearings and contact rings;Measurement of resistance of isolation of bearings;Measurement of temperature of oil in bearings;Absence check short circuits in a rotor winding;Test winding isolation in accordance with GOST 183;Check of a condition of consolidations of a shaft in gathering and definition of leak of air at superfluous pressure of air of not less nominal pressure of hydrogen (for cars with hydrogen cooling).The note Tests spend on manufacturer. Separate tests on 10.2 and 10.4 are supposed to be spent in coordination with the consumer on a turbogenerator installation site.

Capacity of 32000 kw and more it is necessary to subject 10.3 Turbogenerators to tests for an installation site upon termination of turbogenerator installation on 10.2, except for rotor tests at the raised frequency of rotation and tests to isolation. Tests of isolation of windings concerning the case and between windings on electric durability spend in the beginning the straightened pressure equal 1,6 from 80 % of th test pressure of an alternating current, established GOST 183, lasting not more than 1 mines, except for those turbogenerators with water cooling of a winding which design does not suppose this test. Test of isolation of windings concerning the case and between windings on electric durability during 1 mines spend the pressure of an alternating current equal of 80 % of test pressure, established GOST 183.Isolation of a winding of a rotor concerning the case is tested pressure 1000 In frequency by of 50 Hz within 1 minuteIn addition spend:- Test for heating (at impossibility of carrying out of tests at a rated load it is supposed to conduct tests at an underload);- Check of work of system of hydrogen cooling and definition of leak of hydrogen from a turbogenerator (for cars with hydrogen cooling);- Check of work of system of liquid cooling (for cars with liquid cooling).10.4 Acceptance tests should be spent on skilled (head) samples of turbogenerators under the program (10.2) tests, including:- Tests for a short-term overload on a current;- Efficiency definition;- Tests for heating in symmetric modes, and under the agreement also in asymmetrical modes till 4.19 and 4.20;- Definition of factor of distortion a curve of linear pressure and factor of telephone harmonics;- Skilled definition of inductive resistance and constants of time of windings;- Measurement of electric pressure between the shaft ends;- Test of mechanical durability at a shock current of short circuit;- Measurement of level of a sound;- Definition of rated current of excitation, nominal change of pressure and the adjusting characteristic of a turbogenerator;- Definition of a current of 3rd harmonic if cars are intended for work with winding connection in a triangle;- Work check systems of hydrogen cooling and definition of leak of hydrogen (for cars with hydrogen cooling);- Check of work of system of liquid cooling (for cars with liquid cooling);- Measurements of vibrations of the core, the case and front parts of a winding .10.5 Periodic tests should be spent not less often than an once in 7 on one turbogenerator under the program 10.4, except for test of mechanical durability at a shock current of short circuit.10.6 Qualifying tests spend at statement on manufacture of turbogenerators, before mastered on other enterprise or produced under licences. The program of qualifying tests is prepared by the manufacturer with attraction of the developer of the car, and it should include tests on 10.4.10.7 Standard tests are necessary for spending at change of a design, materials or technological processes under the program providing definition of those parametres and characteristics which thus can change.10.8 Certified tests are recommended to be spent on a skilled (head) or serial turbogenerator in volume of acceptance tests on 10.4.10.9 Acceptance, , periodic and standard tests of systems of excitation of turbogenerators spend in accordance with GOST 21558.10.10 At manufacturing of head turbogenerators it is necessary to provide their equipment measuring gauges (in addition to the regular control) in the volume co-ordinated with the consumer for carrying out of acceptance or qualifying tests.11 Test methods

11.1 Test methods of turbogenerators in accordance with GOST 11828, GOST 10169, GOST 25364, GOST 25941, GOST 17494.On distance of 1 m from an external contour of the car define 11.2 Average level of a sound a technical method in a free sound field over a plane in accordance with GOST 11929.11.3 Indicators of reliability of turbogenerators should be confirmed by results of the statistical data processing, received of operating experience, with periodicity three years.11.4 Conformity of turbogenerators to firmness requirements to mechanical external influencing factors (including seismic stability) should be confirmed by calculations in accordance with GOST 17516.1.11.5 turbogenerators proves to be true calculations in accordance with GOST 12.1 004.12 Marks, packing, transportation and storage

12.1 On each turbogenerator with air cooling the tablet in accordance with GOST 12869 and GOST 12971, containing should be strengthened:

- Manufacturer trade mark;

- Turbogenerator type;

- Turbogenerator serial number on system of numbering of manufacturer;

- Nominal active capacity, kw;

- Power factor;

- Rated voltage , In;

- Nominal frequency of rotation, rpm;

- Nominal frequency, Hz;

- Number of phases;

- Rated current , And;

- Rotor rated current, And;

- Rotation direction (if left);

- Year of release;

- This standard designation.

12.2 On the tablet of each turbogenerator with hydrogen or vodorodno-liquid cooling nominal working superfluous pressure of hydrogen in should be in addition specified.

12.3 On the tablet of the turbogenerators, passed certification, the conformity Sign can be placed.12.4 Marks of container in accordance with GOST 14192.12.5 If other is not co-ordinated, conditions of transportation of assembly units of turbogenerators regarding influence of mechanical factors "With" in accordance with GOST 23216, and regarding influence of climatic factors same, as conditions 8 in accordance with GOST 15150.12.6 Conditions of storage of assembly units of turbogenerators in accordance with GOST 15150 establish in specifications on turbogenerators of concrete types. A period of storage without represervation 1.12.7 Packing and preservation of components of a turbogenerator (details and assembly units) - in accordance with GOST 23216.

13 Manufacturer's guarantees

The manufacturer guarantees conformity of turbogenerators to this standard requirements at observance of rules of transportation, storage, installation and operation.

The operation warranty period is established under the agreement, but not less than three years from the date of commissioning by interstate deliveries or 1 year from the date of commissioning and no more than three years from the moment of passing through Frontier by deliveries of turbogenerators to export.

APPENDIX A

(Recommended)

Key parametres of turbogenerators to steam turbines

At a rated loadAt the maximum long loading

Active capacity, kwFrequency of rotation, rpmPressure, InFull capacity, Power factor cos(Efficiency, %, not lessThe short circuit relation, Transitive inductive resistance on a longitudinal axis (nonsaturated value), Active capacity, kwPower factor cos(

250030003150,630031250,897,0( 0,47( 0,35

4000500097,3

60006300, 10500750097,4

12001500097,5

3200400098,2384000,85 at tox waters 3(2

63007875098,369300

750000,92 at tox waters (32

1100001050013750098,4(0,451210000,85 at tox waters (32

16000015750, 180001880000,8598,51760000,85 at tox waters (200,9 at tox waters (32

2200001575025880098,6( 0,40242000

3200002000037600098,7352000

50000020000588000( 0,40550000

800000240008889000,998,758800000,9 at tox waters (32

8000000,85 at tox waters (25

10000002400011110011000000,9 at tox waters (32

10000000,85 at tox waters (25

12000002400013300098,813200000,9 at tox waters (32

5000001500200005880000,8598,65500000,85 at tox waters (250,9 at tox waters (32

1000000240001111000,998,7( 0,5011000000,9 at tox waters (32C

10000000,85 at tox waters (25

The note-for turbogenerators with hydrogen cooling by capacity of 63000 kw and more at the maximum long loading pressure of hydrogen in the car case can be raised, its value should be specified in the maintenance instruction

Keywords: turbogenerators, requirements, acceptance, test methods, marks, guarantees

_1275478193.unknown

_1275478194.unknown

_1275478191.unknown

_1275478192.unknown

_1275478190.unknown