- p142 -protection functions - v42_se-en

120
MiCOM P142 Feeder Protection

Upload: iisp-shams

Post on 17-Sep-2015

82 views

Category:

Documents


15 download

DESCRIPTION

manual for micom p142

TRANSCRIPT

  • MiCOM P142Feeder Protection

  • Schneider Electric 2- Energy Automation 09/2010

    30 10 2011 SCHEDULE

    9.00 10.00 INTROUDUCTION ON MICOM P142 SETTING

    10.00 10.30 INTRODUCTION ON MICOM P543 SETTING

    10.30 12.00 PRACTICAL EXERCISES ON MICOM 142 & P543 SETTING

  • Schneider Electric 3- Energy Automation 09/2010

    MiCOM P141 Feeder ProtectionDocument Version

    AVersion Comment Author Date

    First Version F. BROTTET 19/10/09B Schneider Electric Migration S. GASCO 04/11/10

  • Schneider Electric 4- Energy Automation 09/2010

    SYSTEM DATA

  • Schneider Electric 5- Energy Automation 09/2010

    General configuration menus

    Generalities

    4 setting groups

    System Data

  • Schneider Electric 6- Energy Automation 09/2010

    System Data Settings

    Choose between English, French, German and Spanish Selected language will bethe one displayed on LCD front panel

  • Schneider Electric 7- Energy Automation 09/2010

    System Data Settings

    Feeder name (displayedon LCD front panel) Station name (displayed on LCD front panel)

    Frequency : 50Hz or 60Hz

  • Schneider Electric 8- Energy Automation 09/2010

    CB CONTROL

  • Schneider Electric 9- Energy Automation 09/2010

    Disabled Local Remote Local + Remote Opto Opto+ Local Opto+ Remote Opto + Rem + Local

    No manual control of the CB Open/Close commands can beissued only by protection functions(such as autoreclose, trip, )

    Open/Close commands can beissued from front panel using HOT KEYS or via SYSTEM DATA menuCommands can also be issued fromrelay front communication port

    Open/Close commands can be issued from rear communication port

    Open/Close commands can be issued from opto inputs (one opto for open, one opto for close is required)

    CB position contacts should be available on the relay (via opto) when CB control functionis enabled.

    CB Control

    !

  • Schneider Electric 10- Energy Automation 09/2010

    Minimum duration of close command sent to CB

    Minimum duration of open command sent to CB

    It may be necessary to match these values with CB manufacturing data to ensure safeoperation of the CB.

    CB Control

    !

  • Schneider Electric 11- Energy Automation 09/2010

    Time between local close command sent by operator and relay order sent to CB (to go out of the room for safety reasons)

    CB Control

    Waiting time to receive CB Healthy information given by CB. If relay does not receive thisinformation, no more command canbe issued and CB is locked in open position.

    This function requires an opto input connected to relay CB Healthy internal data (via PSL Editor).

    If not, CB Healthy will be set internally at 1, meaning CB always healthy.

    !DDB #037

    Opto Label 06DDB #230CB Healthy

  • Schneider Electric 12- Energy Automation 09/2010

    Operator action (front panel)

    A successful manual close command

    If CB is locked, choose lockout reset by :

    At the end of this timer

    CB Control

    Specify which position contacts are wired to the relay opto : 52A for CB Closed position 52B for CB Open position

  • Schneider Electric 13- Energy Automation 09/2010

    DATE AND TIME

  • Schneider Electric 14- Energy Automation 09/2010

    View / modify date and time (relayfront panel ) When creating setting file, theseare default values

    Date and Time

    Enable / Disable IRIG-B synchronisation

  • Schneider Electric 15- Energy Automation 09/2010

    Reminder : MiCOM S1 Studio

    1

    2

    1. Select relay from Studio Explorer2. Click on Supervise 3. Modify

    3

  • Schneider Electric 16- Energy Automation 09/2010

    Battery Status

    Date and time

    When Alarm is disabled, lowbattery will not generate any alarm

    In case of power supply failure, the battery will savethe date, time, events, disturbance & fault recorder. Settings/PSL are saved in EEPROM memory : no battery is required to save data even without power supply. Battery life time is 1 year if relay is not supplied or 10 years if relay is permanently supplied.

    !

  • Schneider Electric 17- Energy Automation 09/2010

    Allow to set automatic time change (UTC, winter/summer time)

    Date and time

    Winter/Summer time changeovercan be setup accuratelyt

    It is possible to set time shift between UTC and local

  • Schneider Electric 18- Energy Automation 09/2010

    CONFIGURATION

  • Schneider Electric 19- Energy Automation 09/2010

    Configuration

    Restore default settings for whole file or setting group only Available only from front panel

    4 Settings groups available (PSL included) Setting group change over via Menu or Opto

    Enable / Disable protection functions

    Enable one function make it visible in the setting group :

  • Schneider Electric 20- Energy Automation 09/2010

    Configuration

    Display or hide general menus (not protecitonfunctions) Choose display type for settings values (primaryor secondary values)

    Display or hide direct quick access usingHOTKEYS or FUNCTION KEYS Setup relay LCD contrast

  • Schneider Electric 21- Energy Automation 09/2010

    Select via Opto : Active setting group isselected automatically viaOpto1 and Opto2 (onlythese 2 optos).

    Configuration

    Opto 1

    Opto 2Group 1

    0

    Opto 1

    Opto 2Group 2

    0

    1

    0

    Opto 1

    Opto 2Group 3

    0

    1

    Opto 1

    Opto 2Group 4

    1

    1

    Select via Menu : Active setting group isselected by operator action (relay front panel or front/rear communication to PC). Notes : Opto 1 and 2 can be used for otherapplications

    Notes : Opto inputs 1 and 2 must beset in the PSL Setting group change over can be modified only by theseoptos (not through front panel or communication).

    Active setting group is selected via the parameter Active Settings

  • Schneider Electric 22- Energy Automation 09/2010

    It is possible to set up to 4 setting groups. Each setting group can have differentparameters/PSL

    Configuration

    It is advised to disable non-usedsetting groups

    !

  • Schneider Electric 23- Energy Automation 09/2010

    CT AND VT RATIOS

  • Schneider Electric 24- Energy Automation 09/2010

    Main voltage transformer ratio (3 phases)

    Current transformer ratio (3 phases)

    CT and VT Ratios

    Neutral current transfomer ratio used for Earth Fault 1 or REF protection function

    Sensitive neutral currenttransformer ratio used for SEF or REF high impedance protection function

  • Schneider Electric 25- Energy Automation 09/2010

    RECORD CONTROL

  • Schneider Electric 26- Energy Automation 09/2010

    Allow to define which information will be stored in event memory

    Allow to clear disturbance record memory Only from relay front panel

    Record Control

    Allow to prevent one protection signal to appear in the event list

  • Schneider Electric 27- Energy Automation 09/2010

    DISTURB RECORDER

  • Schneider Electric 28- Energy Automation 09/2010

    Configuration of disturbance record duration Selection of operating mode (single or extended)

    Selection of Analog Channelssignals (current, voltage)

    Disturbance Recorder

    Selection of Digital Channelssignals (opto status, output status, start, trip) Selection of trigger for disturbancerecording

  • Schneider Electric 29- Energy Automation 09/2010

    Disturbance Recorder

  • Schneider Electric 30- Energy Automation 09/2010

    Disturbance Recorder

    Trigger Mode Single : anothertrigger is ignored

    Trigger Mode Extended : recordingtime is extended to take into accountsecond trigger

  • Schneider Electric 31- Energy Automation 09/2010

    Disturbance Recorder

    For each digital channel, it is possible to chooseif it is a trigger for disurbance recording :

    yes, on rising edge yes, on falling edge no, not a trigger

    By default, digital channel linked to Output contact R3 (trip contact) is a trigger.

  • Schneider Electric 32- Energy Automation 09/2010

    MEASURET SETUP

  • Schneider Electric 33- Energy Automation 09/2010

    Measurement Setup

    "Standby" display for relay front panel (after 15 min inactivity)

  • Schneider Electric 34- Energy Automation 09/2010

    Measurement Setup

    IA5.62A

  • Schneider Electric 35- Energy Automation 09/2010

    Measurement Setup

    Selected value will be the reference for phase angle calculation

  • Schneider Electric 36- Energy Automation 09/2010

    Measurement Setup

    ui

    ui

    u

    i

    u

    i

    P

    Q

    Mode 1

    P

    Q

    Mode 2

    ui

    ui

    u

    i

    u

    i

    P

    Q

    Mode 3

    ui

    ui

    u

    i

    u

    i

    P

    Q

    Mode 0

    ui

    ui

    u

    i

    u

    i

    Direction of energy displayed on the relay depends on the selected mode

  • Schneider Electric 37- Energy Automation 09/2010

    Measurement Setup

    Average values are calculatedduring this period Display is refreshed after eachperiod

    Average values are calculatedduring the last x sub periods each sub period lasts y minutes Display is refreshed after each sub-period

    For fault location function, select unit for distance and display type for the value.

  • Schneider Electric 38- Energy Automation 09/2010

    CB MONITOR SETUP

  • Schneider Electric 39- Energy Automation 09/2010

    CB Monitor Setup

    Activation of a CB mainenance alarm if limit is reached :

    Total broken currents Number of operations Operating time

    Select 1 for broken current or 2 for broken squared current

  • Schneider Electric 40- Energy Automation 09/2010

    CB Monitor Setup

    Activation of CB lockout (in open position) if the limit is reached :

    Total broken currents Number of operations Operating time Number of operations in a definite time

  • Schneider Electric 41- Energy Automation 09/2010

    OPTO CONFIG

  • Schneider Electric 42- Energy Automation 09/2010

    Opto Configuration

    It is mandatory to select supply voltage for opto:- same voltage for all inputs- customed for each input

    In case no voltage is available, it ispossible to use 48VDC output voltage from the relay to supply opto inputs.

  • Schneider Electric 43- Energy Automation 09/2010

    Opto Configuration

    150 176VDC220 / 250VDC

    75 88VDC110 / 125VDC

    32,4 38,4VDC48 / 54VDC

    20,4 24VDC30 / 34VDC

    16,2 19,2VDC24 / 27VDC

    Undefined rangeVoltage range

    Opto can be damaged if overvoltageoccurs (more than300VDC )

    !

    100%

    0%

    60%

    80%1

    Previous state*

    0

    * Schmitt Trigger

  • Schneider Electric 44- Energy Automation 09/2010

    Opto Configuration

    Each opto input can be filtered. It allows a pre-filteringof half-period wich prevent opto from wiring noise. This filter provide safety but input may be to slow for application such as Intertripping. In this case, we candisable filtering.

    1 = opto filtered response time = 10ms 0 = opto non filtered response time < 5ms

  • Schneider Electric 45- Energy Automation 09/2010

    SYSTEM CONFIG

  • Schneider Electric 46- Energy Automation 09/2010

    System Configuration

    It is possible to block current functionswhen harmonic 2 is present (inrush current) Above the high set of current, blocking iscancelled

    Select phase sequence (usefull in case phases wiring is reversed)

    For each functionbased on current, it ispossible to select the threasholds blocked by 2nd harmonic detection :

  • Schneider Electric 47- Energy Automation 09/2010

    OVERCURRENT (50/51/67)

  • Schneider Electric 48- Energy Automation 09/2010

    Operating time for settings I>1 and I>2 can beswitched between : Definite Time (DT)OR Inverse Time (IEC, IEEE international curves)

    Overcurrent (50/51/67) Elements I>1 and I>2

  • Schneider Electric 49- Energy Automation 09/2010

    Settings I>1 and I>2 can be set to :Non directional

    ORDirectional Forward

    ORDirectional Reverse

    Overcurrent (50/51/67)Elements I>1 and I>2

    Characteristic angle can be set between -95and +95 Angle is same for all elements Minimal polarising voltage is fixed at 0.5 V (synchronouspolarisation is enabled below this threashold)

  • Schneider Electric 50- Energy Automation 09/2010

    Set current threashold and associated timer (or TMS for inverse time curve)

    Overcurrent (50/51/67)Elements I>1 and I>2

    Phase selective

    Any phase

    Start

    PSL :

    It is possible to add a fixed timer(offset) to the inverse time curve

    Phase selective

    Any phase

    Trip

  • Schneider Electric 51- Energy Automation 09/2010

    Timer before threasholdreinitialisation

    Overcurrent (50/51/67) Elements I>1 and I>2

    I>1

    I>1

    TIMER

    TIMER

    TRIP

    TRIP

    tRESET = 0

    tRESET 0

  • Schneider Electric 52- Energy Automation 09/2010

    Elements I>3 and I>4 are onlydefinite time :

    Overcurrent (50/51/67)Elements I>3 and I>4

  • Schneider Electric 53- Energy Automation 09/2010

    Overcurrent (50/51/67)

    All threasholds may be individually blockedfollowing :

    a VT error detected by VT Supervision function (used for direction determination) an inrush current detection (2nd harmonicmethod)

  • Schneider Electric 54- Energy Automation 09/2010

    Overcurrent (50/51/67)

    Action of VT Supervision function for direction determination : ex. of directional forward element when lossof voltage occurs :

    TRIP

    NO TRIP

    NO TRIP

    NO TRIP

    NO TRIP

    NO TRIP

    Reverse Fault

    TRIP

    NO TRIP

    NO TRIP

    NO TRIP

    NO TRIP

    NO TRIP

    Forward Fault

    VT Supervision Blocking

    VT Supervision Indication

    VT Supervision Disabled

  • Schneider Electric 55- Energy Automation 09/2010

    Overcurrent (50/51/67)Action of inrush current blocking (2nd harmonicdetection) :

    Choose blocking for each element Choose blocking operating mode :

    1PH detection blocks 1PHOR1PH detection blocks 3PH

    1PH detection blocks 1PH1PH detection blocks 3PH

  • Schneider Electric 56- Energy Automation 09/2010

    Overcurrent (50/51/67)

    For I>1 and/or I>2 elements, it is possible to reduce threashold when a voltage drop isdetected (function 51V) :for ex. to detect a remote fault

    V1

    Vrms

    k.I>1

  • Schneider Electric 57- Energy Automation 09/2010

    NEG SEQ O/C (46)

  • Schneider Electric 58- Energy Automation 09/2010

    Operating time for settings I2>1 and I2>2 can beswitched between : Definite Time (DT)OR Inverse Time (IEC, IEEE international curves)

    Negative Sequence Overcurrent (46) Elements I2>1 and I2>2

  • Schneider Electric 59- Energy Automation 09/2010

    Settings I2>1 and I2>2 can be set to :Non directional

    ORDirectional Forward

    ORDirectional Reverse

    Negative Sequence Overcurrent (46) Elements I2>1 and I2>2

    Characteristic angle can be set between -95and +95 Angle is same for all elements Minimum polarising voltage (Vi) can be set duringcommissioning : above negative sequence voltage in stable conditions

  • Schneider Electric 60- Energy Automation 09/2010

    Set current threashold and associated timer (or TMS for inverse time curve)

    Negative Sequence Overcurrent (46)Elements I2>1 and I2>2

    It is possible to add a fixed timer(offset) to the inverse time curve

  • Schneider Electric 61- Energy Automation 09/2010

    Timer before threasholdreinitialisation

    Negative Sequence Overcurrent (46) Elements I2>1 and I2>2

    I2>1

    I2>1

    TIMER

    TIMER

    TRIP

    TRIP

    tRESET = 0

    tRESET 0

  • Schneider Electric 62- Energy Automation 09/2010

    Elements I2>3 and I2>4 are onlydefinite time :

    Negative Sequence Overcurrent (46)Elements I2>3 and I2>4

  • Schneider Electric 63- Energy Automation 09/2010

    Negative Sequence Overcurrent (46)

    All threasholds may be individually blockedfollowing :

    a VT error detected by VT Supervision function (used for direction determination) an inrush current detection (2nd harmonicmethod)

  • Schneider Electric 64- Energy Automation 09/2010

    Negative Sequence Overcurrent (46)

    Action of VT Supervision function for direction determination : ex. of directional forward element when lossof voltage occurs :

    TRIP

    NO TRIP

    NO TRIP

    NO TRIP

    NO TRIP

    NO TRIP

    Reverse Fault

    TRIP

    NO TRIP

    NO TRIP

    NO TRIP

    NO TRIP

    NO TRIP

    Forward Fault

    VT Supervision Blocking

    VT Supervision Indication

    VT Supervision Disabled

  • Schneider Electric 65- Energy Automation 09/2010

    Negative Sequence Overcurrent (46)

    Action of inrush current blocking (2nd harmonicdetection) :

    Choose blocking for each element

  • Schneider Electric 66- Energy Automation 09/2010

    BROKEN CONDUCTOR (46BC)

  • Schneider Electric 67- Energy Automation 09/2010

    Define ratio of negative sequence current / positive sequence current and associated timer

    Note : this function guarantees good operationeven with low level of load current (that is differentfrom function 46)

    Broken conductor (46BC)

  • Schneider Electric 68- Energy Automation 09/2010

    EARTH FAULT PROTECTION (50N/51N/67N)

  • Schneider Electric 69- Energy Automation 09/2010

    Earth Fault Protection (50N/51N/67N) 3 types of earth fault protection available

    based on IN measurement

    based on IN calculation

    based on Sensitive IN measurement

  • Schneider Electric 70- Energy Automation 09/2010

    Operating time for settings IN>1 and IN>2 can beswitched between : Definite Time (DT)OR Inverse Time (IEC, IEEE international curves)

    Earth Fault Protection (50N/51N/67N) Elements IN>1 and IN>2

    Note : operation is same for EARTH FAULT 2 and SEF/REF in SEF mode functions

  • Schneider Electric 71- Energy Automation 09/2010

    Settings IN>1 and IN>2 can be set to :

    Non directionalOR

    Directional ForwardOR

    Directional Reverse

    Earth Fault Protection (50N/51N/67N) Elements IN>1 and IN>2

    Characteristic angle can be set between -95and +95 Angle is same for all elements

    Polarisation can be performed using : residual voltage (-3Vo) mandatory for SEF function : we can define minimum voltage for polarisation negative sequence elements : in this case, residual current provides starting and direction isdetermined by negative sequence voltage and current : we can define minimum values for theses elements

  • Schneider Electric 72- Energy Automation 09/2010

    Set current threashold and associated timer (or TMS for inverse time curve)

    Earth Fault Protection (50N/51N/67N)Elements IN>1 and IN>2

    It is possible to add a fixed timer(offset) to the inverse time curve

  • Schneider Electric 73- Energy Automation 09/2010

    Timer before threasholdreinitialisation

    Earth Fault Protection (50N/51N/67N) Elements IN>1 and IN>2

    IN>1

    IN>1

    TIMER

    TIMER

    TRIP

    TRIP

    tRESET = 0

    tRESET 0

  • Schneider Electric 74- Energy Automation 09/2010

    Elements IN>3 and IN>4 are onlydefinite time :

    Earth Fault Protection (50N/51N/67N)Elements IN>3 and IN>4

  • Schneider Electric 75- Energy Automation 09/2010

    Earth Fault Protection (50N/51N/67N)

    All threasholds may be individually blockedfollowing :

    a VT error detected by VT Supervision function (used for direction determination) an inrush current detection (2nd harmonicmethod)

  • Schneider Electric 76- Energy Automation 09/2010

    Earth Fault Protection (50N/51N/67N)

    Action of VT Supervision function for direction determination : ex. of directional forward element when lossof voltage occurs :

    TRIP

    NO TRIP

    NO TRIP

    NO TRIP

    NO TRIP

    NO TRIP

    Reverse Fault

    TRIP

    NO TRIP

    NO TRIP

    NO TRIP

    NO TRIP

    NO TRIP

    Forward Fault

    VT Supervision Blocking

    VT Supervision Indication

    VT Supervision Disabled

  • Schneider Electric 77- Energy Automation 09/2010

    Earth Fault Protection (50N/51N/67N)

    Action of inrush current blocking (2nd harmonicdetection) :

    Choose blocking for each element

  • Schneider Electric 78- Energy Automation 09/2010

    SEF cos(PHI) / sin(PHI)

    Earth Fault Protection (50N/51N/67N) SEF/REF Add-ons

    For specific applications, it may be difficult to discriminate healthy from faulty feeder as the residualcurrent may be similar. We can use Icos characteristicas the faulty feeder will have a higher active component than the healthy.For isolated networks, we prefer using Isin

    WattmetricIt is possible to add a power criteria from existingelements by choosing Wattmetric characteristic

  • Schneider Electric 79- Energy Automation 09/2010

    REF : Restricted Earth Fault

    Earth Fault Protection (50N/51N/67N) SEF/REF Add-ons

    For transformer protection it is advised to use instantaneous protection for earth fault at low voltage side. To ensure stability of the protection in case of external fault, we can use : High impedance method Low impedance method (bias characteristic)

    Note : It is possible to use both low impedance REF and DTS/Wattmetric function whileusing high impedance REF is exclusive

  • Schneider Electric 80- Energy Automation 09/2010

    Earth Fault Protection (50N/51N/67N) High impedance REF operating mode principle

  • Schneider Electric 81- Energy Automation 09/2010

    Earth Fault Protection (50N/51N/67N) Low impedance REF operating mode principle

  • Schneider Electric 82- Energy Automation 09/2010

    RESIDUAL O/V NVD (59N)

  • Schneider Electric 83- Energy Automation 09/2010

    Operating time for element VN>1 can beswitched between :Definite time (DT)

    ORInverse time (IDMT) We can then set the threashold and associatedtimer/TMS

    Residual overvoltage (59N)

    Note : this function is based on calculated VN = VA+VB+VC

    Second element VN>2 is only definite time We just need to set the threashold and associated timer

  • Schneider Electric 84- Energy Automation 09/2010

    Timer before threasholdreinitialisation

    Residual overvoltage (59N) Element VN>1

    TIMER

    TIMER

    TRIP

    TRIP

    tRESET = 0

    tRESET 0

    VN>1

    VN>1

  • Schneider Electric 85- Energy Automation 09/2010

    THERMAL OVERLOAD (49)

  • Schneider Electric 86- Energy Automation 09/2010

    Thermal overload (49)

    Note : Single characteristic (one time constant) isused to protect cables or dry transformers. Dual characteristic (two time constants) isused for oil insulated transformers with naturalair cooling

    one time constant protects againstslow increase of oil temperature one time constant protects against fastincrease of windings temperature

    We define full load current setting (maximum load) It is possible to set an alarm to warn operator of thermal state increase

  • Schneider Electric 87- Energy Automation 09/2010

    NEG SEQUENCE O/V

  • Schneider Electric 88- Energy Automation 09/2010

    Negative sequence overvoltage

    For specific applications where the input voltage must be perfectly balanced (motorsupply), it is advised to use negativesequence overvoltage function Set the threashold and corresponding timer

  • Schneider Electric 89- Energy Automation 09/2010

    COLD LOAD PICKUP

  • Schneider Electric 90- Energy Automation 09/2010

    Cold Load Pickup

    After closing the circuit breaker, it is possible to block phase & earth overcurrent elements, or to define new settings (generally increasethreasholds) during a fix timer. Blocking or new settings will be activatedduring tclp Time Delay after CB closure. Blocking or new settings will also beactivated after tcold Time Delay when CB isopen (load disconnected).

    Note : It is possible to modify the 4 phase overcurrent elements and the first element of earth fault 1 & 2 functions.

  • Schneider Electric 91- Energy Automation 09/2010

    Cold Load Pickup

    If element is set as Enable, the new settings will be applied when function Cold load pickupwill be activated.

    Note : Elements will appear in Cold Load Pickup function only if they are enabled in the relevant PHASE OVERCURRENT & EARTH FAULT functions.

    If element is set as Block, it will not beactive anymore when function Cold loadpickup will be activated.

  • Schneider Electric 92- Energy Automation 09/2010

    Cold Load Pickup

    Cold Load Pickup function activation is linked to circuit breaker position. It is thus necessary to wire CB position on relay digital inputs. CB position is managed by two signals: 52A (CB CLOSED) & 52B (CB OPEN). If only one signal is available, the other one will automatically be calculated by the protection.

    REMINDER : CB position should be defined bothin settings file & PSL file with coherence:

  • Schneider Electric 93- Energy Automation 09/2010

    Cold Load Pickup

    52B

    Functionactivation

    52A

    tclp tcold

    Note : If CB position (52A or 52B) is not available, it is possible to activate the functionusing the signal CLP initiate . Behaviour will be the same as 52B signal (check abovediagram).

    Activation of Cold Load Pickup function

  • Schneider Electric 94- Energy Automation 09/2010

    SELECTIVE LOGIC

  • Schneider Electric 95- Energy Automation 09/2010

    Selective logic

    On specific logic input activation for example it is possible to modify timers of elements 3 & 4 for overcurrent functions(phase & earth)

    Note : It is possible to modify elements 3 & 4 for OVERCURRENT, EARTH FAULT 1 & 2 and SENSITIVE EARTH FAULT (SEF).

  • Schneider Electric 96- Energy Automation 09/2010

    Selective logic

    New timer settings will be applied as long as blocking signals will be active (PSL configuration):

    Note : if Selective Logic function is disabled, signals such as I>3 Timer Block willcompletely block the corresponding element while if Selective Logic function is enabled, element is not blocked anymore but new timer settings will be applied.

  • Schneider Electric 97- Energy Automation 09/2010

    VOLT PROTECTION

  • Schneider Electric 98- Energy Automation 09/2010

    50 V50 V

    No start of element V

  • Schneider Electric 99- Energy Automation 09/2010

    50 V50 V

    No start of element V

  • Schneider Electric 100- Energy Automation 09/2010

    Voltage Protection

    Operating mode:

    Any phase : protection will start if faultappears on any of the three phases Three Phase : protection will start only if fault appears on the three phases

    Note : measurement mode and operating mode are defined for each function UNDER VOLTAGE & OVERVOLTAGE. They will be applied for all elements of each function.

  • Schneider Electric 101- Energy Automation 09/2010

    Voltage Protection

    Function definition

    Settings for a definite time element: Level Timer

    Settings for an inverse time curve element(available only for first element V1):Trev = K / (1 M)with :K = time multiplier setting TMSM = ratio measured voltage / voltage threashold

  • Schneider Electric 102- Energy Automation 09/2010

    Voltage Protection

    Inhibition of Under Voltage protection when CB is open

    It is possible to block undervoltage elements whenCB is open: just enable setting Poledead Inh

  • Schneider Electric 103- Energy Automation 09/2010

    FREQ PROTECTION

  • Schneider Electric 104- Energy Automation 09/2010

    Frequency Protection

    Function definition

    Setting definition: Threashold value Timer

    Note : 4 elements available for UNDER FREQUENCY function and 2 elements for OVER FREQUENCY function.

  • Schneider Electric 105- Energy Automation 09/2010

    Frequency Protection

    Inhibition of Under Frequency protection when CB is open

    It is possible to block underfrequency elementswhen CB is open: just check box Poledead Blk for the required element:

  • Schneider Electric 106- Energy Automation 09/2010

    DF/DT PROTECTION

  • Schneider Electric 107- Energy Automation 09/2010

    df/dt protection

    Function configuration

    Element configuration : Threashold value (df/dt rate in Hz/s) Timer (for trip) Direction:

    Negative for falling frequency conditions operation Positive for rising frequency conditions operation Both

    Note : 4 elements available for DF/DT function

  • Schneider Electric 108- Energy Automation 09/2010

    df/dt protection

    Rate of change of frequency calculation

    Rate of change calculation on 6 cycles will befaster but less accurate than 12 cycles calculation.Maximum fault detection delay is:

    t = 2 x M + 1 (in cycles)where M = df/dt Avg.Cycles

  • Schneider Electric 109- Energy Automation 09/2010

    CB FAIL & I

  • Schneider Electric 110- Energy Automation 09/2010

    Breaker failure

    CB Fail elements are strictlyindependant

    !

    CB Fail stage 1 (re-trip) with correspondingtimer

    CB Fail stage 2 (bad-trip) with correspondingtimer

    Note : after protection trips, if CB is not open before the end of set timer, CB fail elementwill operate

  • Schneider Electric 111- Energy Automation 09/2010

    Breaker failure

    CB Open

    Bfail 1 activation

    Trip

    CB Fail 1 timer

    CB Fail function operation

    CB Open

    Bfail 1 activation

    Trip.

    CB Fail 1 timer

    No Breaker Failure

    Breaker Failure

  • Schneider Electric 112- Energy Automation 09/2010

    Breaker failure

    Acknowledge CB Fail when it has been started by a non current based protection: I< only : When currents drop below the settings I< Current Set & IN< Current Set. CB Open & I< : When currents drop below the settings I< Current Set & IN< Current Set AND protection relay receivesexternal signal for CB open position (fromdigital input). Prot Reset & I< : When currents drop below the settings I< Current Set & IN< Current Set AND started elements has stopped (fault has disappeared)

  • Schneider Electric 113- Energy Automation 09/2010

    Breaker failure

    Acknowledge CB Fail when it has been started by an external protection: I< only : When currents drop below the settings I< Current Set & IN< Current Set. CB Open & I< : When currents drop below the settings I< Current Set & IN< Current Set AND protection relay receivesexternal signal for CB open position (fromdigital input). Prot Reset & I< : When currents drop below the settings I< Current Set & IN< Current Set AND started elements has stopped (fault has disappeared)

    * Requires an opto input assigned to External Trip signal in PSL:

  • Schneider Electric 114- Energy Automation 09/2010

    Breaker failure

    When CB fail acknowledge criteria I< is used, we definelevels of current under which current is considered has disappeared:I< Current Set and IN< Current Set for all functionsbased on current (except SEF) + protections non basedon current + external protectionsISEF< Current for Sensitive Earth Fault protection (SEF)

    It can be interesting to block start signals for first elements I> and IN> when CB fail conditions occurs:when these signals are used to block anotherprotection, CB fail allow to stop blocking it so that it cantrip corresponding CB.

  • Schneider Electric 115- Energy Automation 09/2010

    SUPERVISION

  • Schneider Electric 116- Energy Automation 09/2010

    CT & VT Supervision

    In case of VT failure, VTS can operate as: Indication = an alarm is raised Blocking = optional blocking of voltage dependant protection elements + optionalconversion of directional overcurrentelements to non-directional

    After a VT failure detected by VTS, blockingsignal will be latched after the delay VTS Time Delay VTS Reset Mode: Acknowledgement of blocking can be manual (front panel or communication) or automatic after restorationof the 3 phase voltages (3 V > fix threashold 30V for Vn=100/120V)

    Note : VTS operates when a residual voltage is detected without negative sequencecurrent. In case of loss of voltage on the 3 phases, other calculation will take place to detect VT failure.

  • Schneider Electric 117- Energy Automation 09/2010

    CT & VT Supervision

    It is possible to disable VTS blocking if phase current (or negative seq. current) is above the threashold VTS I> Inhibit (or VTS I2> Inhibit). For example, in case of a close up threephases fault on line energisation, VTS functionshould not block tripping!

  • Schneider Electric 118- Energy Automation 09/2010

    CT & VT Supervision

    CT Supervision activation

    If a zero sequence current appears abovethe CTS IN> Set and the zero sequencevoltage is below the CTS VN< Inhibit, CTS function will operate. An alarm is raised on relay front panel afterCTS Time Delay

    Note : CTS operates when a zero sequence current (calculated) appears when no zerosequence voltage is measured or calculated.When CTS function starts, protection functions based on calculated values (such as Broken Conductor, Earth Fault 2, Negative sequence overcurrent) are automaticallyblocked.Other functions can be blocked by customising the PSL using signals CTS Block -instantaneous or CT Fail Alarm - time delayed:

  • Schneider Electric 119- Energy Automation 09/2010

    FAULT LOCATOR

  • Schneider Electric 120- Energy Automation 09/2010

    Fault locator

    Line length can be set in miles or km:

    Line Impedance: positive sequence line impedance Line Angle: angle of positive sequenceimpedance kZN Residual: zero sequence line impedance kZn Res Angle: angle of zero sequenceimpedance

    Note : distance to fault is displayed in the fault report. It can be displayed as a distance, as an impedance or as % of line length: