SECTION 16000 MULTIPLE DWELLING UNIT SYSTEMS Display hidden notes to specifier. (Don't know how? Click Here ) Copyright 2017 - 2019 ARCAT, Inc. - All rights reserved PART 1 GENERAL 1.1 SECTION INCLUDES A. Multiple dwelling unit systems including the following: 1. Home systems/audio-visual. 2. Integrated wiring devices. 3. Wiring devices. 4. Lighting controls. 5. Under-cabinet lighting systems. 6. Commercial floor boxes. 7. Fire classified floor boxes. 8. Recessed outlet poke-thru devices. 9. Meeting room solutions. 10. Plugmold. 11. Residential floor boxes. 12. Open space power and communications delivery 13. Productivity products. 1.2 RELATED SECTIONS A. Section 16050 - Basic Electrical Means and Methods. 1.3 SUBMITTALS A. Submit under provisions of Section 01300. B. Product submittals: 1. Provide an electronic Submittal Log matrix, listing each of the components to be used. a. Submittal Log fields to include referenced specification section, manufacturer, component description and part number. 2. Provide manufacturer's cut sheet of each of the components to be used. a. Specified component to be clearly designated on the manufacturer's cut sheet. b. Manufacturer cut sheets to include detailed component 16000-1

Upload: hadan

Post on 01-Aug-2019

217 views

Category:

Documents


0 download

TRANSCRIPT

Page 1:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

SECTION 16000MULTIPLE DWELLING UNIT SYSTEMS

Display hidden notes to specifier. (Don't know how? Click Here)

Copyright 2017 - 2019 ARCAT, Inc. - All rights reserved

PART 1 GENERAL

1.1 SECTION INCLUDES

A. Multiple dwelling unit systems including the following:1. Home systems/audio-visual.2. Integrated wiring devices.3. Wiring devices.4. Lighting controls.5. Under-cabinet lighting systems.6. Commercial floor boxes.7. Fire classified floor boxes.8. Recessed outlet poke-thru devices.9. Meeting room solutions.10. Plugmold.11. Residential floor boxes.12. Open space power and communications delivery13. Productivity products.

1.2 RELATED SECTIONS

A. Section 16050 - Basic Electrical Means and Methods.

1.3 SUBMITTALS

A. Submit under provisions of Section 01300.

B. Product submittals:1. Provide an electronic Submittal Log matrix, listing each of the components to be used.

a. Submittal Log fields to include referenced specification section, manufacturer, component description and part number.

2. Provide manufacturer's cut sheet of each of the components to be used.a. Specified component to be clearly designated on the manufacturer's cut sheet.b. Manufacturer cut sheets to include detailed component performance

parameters.

C. Shop drawing submittals:1. Provide shop drawings that have been coordinated with field conditions and the work

of other trades.2. Submit shop drawings for review and acceptance prior to commencement of work.

D. Seismic and bracing documentation for the structural bracing and support of telecommunications equipment:1. Refer to Structural design documents for seismic requirements for non-structural

components for all structural bracing and support of telecommunications equipment.

16000-1

Page 2:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

2. Provide seismic design calculations and seismic design sketches prepared by the Contractor's California Certified structural engineer for coordination and approval by the Owner's Representative prior to fabricating or installing any supports. Any proposed reinforcement to be the responsibility of the Contractor. Coordinate seismic design with other trades, fire protection and site conditions.

E. As-built documentation submittals:1. Provide as-built documentation of all telecommunications pathway systems under this

section utilized throughout the site for review, acceptance and future reference.2. As-built documentation to include:

a. Record Drawings.b. Database matrix of components used.

F. Warranty documentation:1. Submit manufacturers extended warranty certification after the warranty acceptance

by the manufacturer. It shall be the contractor's responsibility to facilitate the manufacturer specific warranty requirements.

G. Selection Samples: For each finish product specified, two complete sets of color chips representing manufacturer's full range of available colors and patterns.

H. Verification Samples: For each finish product specified, two samples, minimum size 6 inches (150 mm) square representing actual product, color, and patterns.

1.4 QUALITY ASSURANCE

A. Manufacturer Qualifications: Minimum 5 year experience manufacturing similar products.

B. Installer Qualifications: Minimum 2 year experience installing similar products.

C. Product Qualifications:1. National Electric Code Compliance: Comply with all NEC articles that apply to

construction and installation practices applicable to this section2. ANSI/TIA: Comply with all ANSI/TIA articles that apply to construction and installation

practices applicable to this section3. UL Compliance: Provide products that are UL and or cUL-classified.4. NFPA Compliance: Comply with NFPA 70.5. Items of a given type shall be the products of the same manufacturer.6. Supply equipment and accessories new and free from defects.

D. Mock-Up: Provide a mock-up for evaluation of surface preparation techniques and application workmanship.1. Finish areas designated by Architect.2. Do not proceed with remaining work until workmanship is approved by Architect.3. Refinish mock-up area as required to produce acceptable work.

1.5 PRE-INSTALLATION MEETINGS

A. Convene minimum two weeks prior to starting work of this section.

1.6 DELIVERY, STORAGE, AND HANDLING

A. Deliver and store products in manufacturer's unopened packaging bearing the brand name and manufacturer's identification until ready for installation.

B. Handling: Handle materials to avoid damage.

1.7 PROJECT CONDITIONS

16000-2

Page 3:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

A. Maintain environmental conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer's recommended limits.

1.8 SEQUENCING

A. Ensure that products of this section are supplied to affected trades in time to prevent interruption of construction progress.

PART 2 PRODUCTS

2.1 MANUFACTURERS

A. Acceptable Manufacturer: Legrand, which is located at: 60 Woodlawn St.; West Hartford, CT 06110; Toll Free Tel: 877-295-3472; Tel: 860-233-6251; Fax: 860-232-2062; Email:request info ([email protected]); Web:http://www.legrand.us/wiremold.aspx

B. Substitutions: Not permitted.

C. Requests for substitutions will be considered in accordance with provisions of Section 01600.

2.2 HOME SYSTEMS/AUDIO-VISUAL

A. Residential Multimedia Panel (MMP):1. Acceptable manufacturers: On-Q/Legrand2. Designed to provide a central distribution point for home or small office technologies,

the enclosures accommodate the distribution of voice, data, video, audio, security, and control applications.

3. Cutout pattern in bottom accommodates single gang or full width AC power modules and Mini and Universal DC power supplies. Designed to accommodate high-quality hospital-grade power module with surge suppression.

4. Mounting slots on the enclosure simplify adjustment for different sheetrock depths5. Sheetrock depth marks of 1/2 inch, 5/8 inch and 3/4 inch (13 mm, 16 mm, 19 mm) on

the enclosure simplify alignment.6. Lance slots provide clean cable management within the enclosure.7. Flush-mount cover overlaps 3/4 inch (19 mm) to hide possible uneven drywall cuts

around the MMP.8. Provided with a cardboard insert to help prevent drywall debris or paint over-spray

from entering the MMP during the rough-in stage of installation.9. Mounting hook on the cover aligns screw holes for easier installation.10. Multiple knockouts on the top and bottom support conduit up to 2 inches (51 mm) in

diameter and facilitate cable routing and entry11. Self-healing foam grommets protect cable bundles.12. Holds 1/4, 1/2 and full-width expansion modules with the ability to mount most

modules vertically or horizontally.13. The structured media enclosure shall be a one-piece (excluding cover) box, made of

18-gauge, white, powder-coated steel. It shall flush-mount with four wood screws (provided) on standard 16 inches (406 mm) center wall studs prior to dry wall.

14. Includes a secure, hinged cover with lock and key set.15. The enclosure shall include installation hardware.16. Provide for bonding and grounding to meet TIA/EIA 606 Standards.17. UL Listed.18. Comply with all TIA/EIA 568-A and TIA/EIA 570-A requirements.19. Meet FCC part 68.20. Finish: Powder coated white.21. Finish: Powder coated almond.

16000-3

Page 4:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

22. Finish:23. Enclosure size, data module, voice module, and video module will depend on

application variables, such as Fiber or Copper, Cat5e or Cat6, size of residence, etc. As such, provide the following in each unit on this project:

24. Minimum dimension of 14 inches h x 14.38 inches w x 3.6 inches d (356 mm x 365 mm x 91 mm) with (8) module capacity.a. Product: EN1400: 14 inches (356 mm) Enclosure W/ Screw-On Cover.b. Product: EN1450: 14 inches (356 mm) Enclosure W/ Hinged Cover and Lock.c. Product: EN1480: 14 inches (356 mm) Enclosure, No Cover.d. Product: EN1460: 14 inches (356 mm) Hinged Cover and Lock.e. Product: EN1420: 14 inches (356 mm) Screw-On Cover.f. Product: EN1485: Stackable 14-Inches (356 mm) Enclosure with Knock-Outs,

No Cover.25. Minimum dimension of 20 Inches (508 mm):

a. Product: EN2000: 20 Inches (508 mm) Enclosure W/ Screw-On Cover.b. Product: EN2050: 20 Inches (508 mm) Enclosure W/ Hinged Cover and Lock.c. Product: EN2080: 20 Inches (508 mm) Enclosure, No Cover.d. Product: EN2060: 20 Inches (508 mm) Hinged Cover and Lock.e. Product: EN2020: 20 Inches (508 mm) Screw-On Cover.f. Product: EN2085: Stackable 20 Inches (508 mm) Enclosure with Knock-Outs,

No Cover.26. Minimum dimension of 28 inches h x 14 inches w x 3.6 inches d (711 mm x 356 mm x

91 mm) with (12) module capacity.a. Product: EN2800: 28 inches (711 mm) Enclosure W/ Screw-On Cover.b. Product: EN2850: 28 inches (711 mm) Enclosure W/ Hinged Cover and Lock.c. Product: EN2880: 28 inches (711 mm) Enclosure, No Cover.d. Product: EN2860: 28 inches (711 mm) Hinged Cover and Lock.e. Product: EN2820: 28 inches (711 mm) Screw-On Cover.f. Product: EN2885: Stackable 28-Inch Enclosure with Knock-Outs, No Cover.

27. Minimum dimension of 42 inches h x 14.38 inches w x 3.6 inches d (1067 mm x 365 mm x 91 mm) with (18) module capacity.a. Product: EN4200: 42 inches (1067 mm) Enclosure W/ Screw-On Cover.b. Product: EN4250: 42 inches (1067 mm) Enclosure W/ Hinged Cover and Lock.c. Product: EN4260: 42 inches (1067 mm) Hinged Cover and Lock.d. Product: EN4220: 42 inches (1067 mm) Screw-On Cover.e. Product: EN4285: Stackable 42-Inch Enclosure with Knock-Outs, No Cover.

B. Wired Network:1. Enclosure-Mounted Routers and Switches: Gigabit Ethernet (Throughput up to 1000

Mbps).a. Product: DA1054 4-Port Gigabit Router/Switch.b. Product: DA1458 8-Port Gigabit Switch with 4-Ports PoE.c. Product: DA1008 8-Port Gigabit Switch.

2. Enclosure-Mounted Routers and Switches: Fast Ethernet (Throughput up to 100 Mbps).a. Product: DA1004 4-Port Fast Ethernet Router/Switch.b. Product: DA1002 5-Port Fast Ethernet Network Switch.

3. Switches:a. Product: DA1015-V1 Desktop 5-Port Gigabit Ethernet Switch.b. Product: DA1018-V1 Desktop 8-Port Gigabit Ethernet Switch.

4. Power Over Ethernet (POE) Injectors:a. Product: 4-Port Power Over Ethernet Injector (802.3af compliant, fast ethernet

speeds).b. Product: 4-Port High Power, Power Over Ethernet Injector (802.3at compliant,

gigabit speeds).c. Product: AC1025 Power over Ethernet Mounting Plate.

16000-4

Page 5:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

C. Wireless Network:1. Wireless Access Points:

a. Product: DA1101 802.11n Wireless Access Point (speeds up to 300Mbps).b. Product: DA2131-V1 802.11n Outdoor Wireless Access Point (speeds up to

150Mbps).c. Product: DA2155-V1 802.11n Wireless Desktop Repeater/Access Point

(speeds up to 150Mbps).2. Wireless Desktop Router:

a. Product: DA2154-V1 802.11n Wireless Desktop 4-Port Router (speeds up to 300Mbps).

D. Powerline Network:1. Network Adapters:

a. Product: DA2301-V1 One-Port Powerline Network Adapter (gigabit port - 500Mbps homeplug AV).

b. Product: DA2304-V1 4-Port Powerline Network Adapter ( port gigabit switch - 500Mbps homeplug AV).

2. Adapter Kit:a. Product: DA2300-V1 Powerline Network Adapter Kit (10/100 fast ethernet ports

500Mbps homeplug AV).

E. COAX Network:1. Network Adapter:

a. Product: DA2204-V1 4-Port Coax Network Adapter.2. Digital Cable Splitter:

a. Product: VM2202-V1 2-Way Digital Cable Splitter with Coax Network Support.b. Product: VM2203-V1 3-Way Digital Cable Splitter with Coax Network Support.c. Product: VM2204-V1 4-Way Digital Cable Splitter with Coax Network Support.

3. Accessories:a. Product: VM2200-V1 Coax Network Signal Blockerb. Product: VM2201-V1 Single-Port Digital Cable Amplifier with Coax Network

Support.

F. Value Line Structured Wiring Solution:1. Kit:

a. Product: EN0802: 8-Inch MDU Enclosure Kit (6 phone, 4 video).2. Components:

a. Product: EN0800: 8-Inch MDU Enclosure and Cover.b. Product: EN0801: 8-Inch MDU Enclosure Cover.c. Product: EN0806: 8-Inch MDU Enclosure Bulk Pack (6).d. Product: TM0106: 1X6 Telephone Board (For use with EN0800).e. Product: TM0404: Combo 1x4 Phone / 4 Port Cat5e Data Board (For use with

EN0800).f. Product: VM0104:4 Way Vertical 1Ghz Splitter (For use with EN0800).g. Product: VM0106:6 Way Vertical 1Ghz Splitter (For use with EN0800).h. Product: VM0108:8 Way Vertical 1Ghz Splitter (For use with EN0800).i. Product: VM0204:4 Way Vertical 2Ghz Splitter (For use with EN0800).j. Product: VM0206:6 Way Vertical 2Ghz Splitter (For use with EN0800).k. Product: VM0208:8 Way Vertical 2Ghz Splitter (For use with EN0800).

G. Enclosure Power Management:1. Receptacles:

a. Product: F7526:AC Power Kit (Electrical Box, White Duplex Receptacle, White Faceplate).

b. Product: 364569-02-V1: Surge Protected Duplex Outlet Kit.2. Power Distribution:

16000-5

Page 6:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

a. Product: AC1031: Enclosure Power Strip Module - Half Width.

H. Video/Voice:1. Combo Video/Voice:

a. Product: CO1045:10x8 Combo Module, RJ45 Connections w/ RJ31X.b. Product: CO1110:10x8 Combo Module, 110 Punchdown Connections w/

RJ31X.2. Voice:

a. Product: TM1110:4x10 Telecom Module,110 Punchdown Connections w/ RJ31X.

b. Product: TM1045:4x10 RJ45 Telecom Module w/ RJ31X.c. Product: 1267062-01-V1:1x6 Basic Telecom Module.

3. Video:a. Product: VM1000:1X4 Enhanced Passive Video Splitter/Combiner, DC

Passing, 1Ghz.b. Product: VM1002:1X8 Enhanced Passive Video Splitter/Combiner, DC

Passing, 1Ghz.

I. Passive Data / Patch Panel:1. Product: AC1012:6-Port CAT5E Network Interface Module W/2 Keystone Openings.2. Product: AC1013:6-Port CAT6 Network Interface Module W/2 Keystone Openings.3. Product: AC1014:12-Port CAT5E Network Interface Module.4. Product: AC1000:6 Port Network Interface Module with RJ45 Inserts.5. Product: 363486-01:8 Port Network Interface Module.

J. Keystone Wall Plate:1. 1-Port:

a. Product: WP3401-BK: Single Gang Wall Plate, 1-Port, Black.b. Product: WP3401-BR: Single Gang Wall Plate, 1-Port, Brown.c. Product: WP3401-GY: Single Gang Wall Plate, 1-Port, Gray.d. Product: WP3401-IV: Single Gang Wall Plate, 1-Port, Ivory.e. Product: WP3401-LA: Single Gang Wall Plate, 1-Port, Light Almond.f. Product: WP3401-LA-10: Single Gang Wall Plate, 1-Port, 10-pk, Light Almond.g. Product: WP3401-LA-25: Single Gang Wall Plate, 1-Port, 25-pk, Light Almond.h. Product: WP3401-SS: Single Gang Wall Plate, 1-Port, Stainless Steel.i. Product: WP3401-WH: Single Gang Wall Plate, 1-Port, White.j. Product: WP3401-WH-10: 1-Gang, 1-Port Wallplate, 10-pk, White.k. Product: WP3401-WH-25: Single Gang Wall Plate, 1-Port, 25-pk, White.

2. 2-Port:a. Product: WP3402-BK: Single Gang Wall Plate, 2-Port, Black.b. Product: WP3402-BR: Single Gang Wall Plate, 2-Port, Brown.c. Product: WP3402-GY: Single Gang Wall Plate, 2-Port, Gray.d. Product: WP3402-IV: Single Gang Wall Plate, 2-Port, Ivory.e. Product: WP3402-LA: Single Gang Wall Plate, 2-Port, Light Almond.f. Product: WP3402-LA-10: Single Gang Wall Plate, 2-Port, 10-pk, Light Almond.g. Product: WP3402-LA-25: Single Gang Wall Plate, 2-Port, 25-pk, Light Almond.h. Product: WP3402-SS: Single Gang Wall Plate, 2-Port, Stainless Steel.i. Product: WP3402-WH: Single Gang Wall Plate, 2-Port, White.j. Product: WP3402-WH-10: Single Gang Wall Plate, 2-Port, 10-pk, White.k. Product: WP3402-WH-25: Single Gang Wall Plate, 2-Port, 25-pk, White.

3. 3-Port:a. Product: WP3403-BK: Single Gang Wall Plate, 3-Port, Black.b. Product: WP3403-BR: Single Gang Wall Plate, 3-Port, Brown.c. Product: WP3403-GY: Single Gang Wall Plate, 3-Port, Gray.d. Product: WP3403-IV: Single Gang Wall Plate, 3-Port, Ivory.e. Product: WP3403-LA: Single Gang Wall Plate, 3-Port, Light Almond.

16000-6

Page 7:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

f. Product: WP3403-SS: Single Gang Wall Plate, 3-Port, Stainless Steel.g. Product: WP3403-WH: Single Gang Wall Plate, 3-Port, White.h. Product: WP3403-WH-10: Single Gang Wall Plate, 3-Port, 10-pk, White.

4. 4-Port:a. Product: WP3404-BK: Single Gang Wall Plate, 4-Port, Black.b. Product: WP3404-BR: Single Gang Wall Plate, 4-Port, Brown.c. Product: WP3404-GY: Single Gang Wall Plate, 4-Port, Gray.d. Product: WP3404-IV: Single Gang Wall Plate, 4-Port, Ivory.e. Product: WP3404-LA: Single Gang Wall Plate, 4-Port, Light Almond.f. Product: WP3404-SS: Single Gang Wall Plate, 4-Port, Stainless Steel.g. Product: WP3404-WH: Single Gang Wall Plate, 4-Port, White.h. Product: WP3404-WH-10: Single Gang Wall Plate, 4-Port, 10-pk, White.

5. 6-Port:a. Product: WP3406-BK: Single Gang Wall Plate, 6-Port, Black.b. Product: WP3406-BR: Single Gang Wall Plate, 6-Port, Brown.c. Product: WP3406-GY: Single Gang Wall Plate, 6-Port, Gray.d. Product: WP3406-IV: Single Gang Wall Plate, 6-Port, Ivory.e. Product: WP3406-LA: Single Gang Wall Plate, 6-Port, Light Almond.f. Product: WP3406-SS: Single Gang Wall Plate, 6-Port, Stainless Steel.g. Product: WP3406-WH: Single Gang Wall Plate, 6-Port, White.

6. 12-Port:a. Product: WP3212-IV: Two Gang Wall Plate 12-Port - Ivory.b. Product: WP3212-LA: Two Gang Wall Plate 12-Port - Light Almond.c. Product: WP3212-WH: Two Gang Wall Plate 12-Port - White.

K. Pre-Molded Straps:1. Coax:

a. Product: 26CATVI:1 GHz Coax F Connector Decorator Strap, Ivory.b. Product: 26CATVLA:1 GHz Coax F Connector Decorator Strap, Light Almond.c. Product: 26CATVW:1 GHz Coax F Connector Decorator Strap, White.

2. Phone:a. Product: 26TE14I:2 Line Telephone Decorator Strap (4 Conductor), Ivory.b. Product: 26TE14LA:2 Line Telephone Decorator Strap (4 Conductor), Light

Almond.c. Product: 26TE14W:2 Line Telephone Decorator Strap (4 Conductor), White.d. Product: 26TE16I:3 Line Telephone Decorator Strap (6 Conductor), Ivory.e. Product: 26TE16W:3 Line Telephone Decorator Strap (6 Conductor), White.

L. Pre-Molded Wall Plates:1. Coax:

a. Product: TPCATV2: Dual 1 GHz Coax F Connector Wall plate, Brown.b. Product: TPCATV2BK: Dual 1 GHz Coax F Connector Wall plate, Black.c. Product: TPCATV2I: Dual 1 GHz Coax F Connector Wall plate, Ivory.d. Product: TPCATV2LA: Dual 1 GHz Coax F Connector Wall plate, Light Almond.e. Product: TPCATV2W: Dual 1 GHz Coax F Connector Wall plate, White.f. Product: TPCATV: 1 GHz Coax F Connector Wall plate, Brown.g. Product: TPCATVBK: 1 GHz Coax F Connector Wall plate, Black.h. Product: TPCATVI: 1 GHz Coax F Connector Wall plate, Ivory.i. Product: TPCATVLA: 1 GHz Coax F Connector Wall plate, Light Almond.j. Product: TPCATVW: 1 GHz Coax F Connector Wall plate, White.k. Product: WP2008-LA-V1: 3GHz Coax Wall plate, Light Almond.l. Product: WP2008-WH-V1: 3GHz Coax Wall plate, White.m. Product: WP2009-LA-V1: 3GHz Dual Coax Wall plate, Light Almond.n. Product: WP2009-WH-V1: 3GHz Dual Coax Wall plate, White.

2. Phone:a. Product: TPTE1: 2 Line Telephone Wall plate (4 Conductor), Brown.

16000-7

Page 8:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

b. Product: TPTE1BK: 2 Line Telephone Wall plate (4 Conductor), Black.c. Product: TPTE1I: 2 Line Telephone Wall plate (4 Conductor), Ivory.d. Product: TPTE1LA: 2 Line Telephone Wall plate (4 Conductor), Light Almond.e. Product: TPTE1W: 2 Line Telephone Wall plate (4 Conductor), White.f. Product: TPTE2: Dual 2 Line Telephone Wall plate (4 Conductor), Brown.g. Product: TPTE2BK: Dual 2 Line Telephone Wall plate (4 Conductor), Black.h. Product: TPTE2I: Dual 2 Line Telephone Wall plate (4 Conductor), Ivory.i. Product: TPTE2LA: Dual 2 Line Telephone Wall plate (4 Conductor), Light

Almond.j. Product: TPTE2W: Dual 2 Line Telephone Wall plate (4 Conductor), White.

3. Hanging Phone:a. Product: WMTE14I: 2 Line Telephone Wall Mount Wall plate (4 Conductor),

Ivory.b. Product: WMTE14LA: 2 Line Telephone Wall Mount Wall plate (4 Conductor),

Light Almond.c. Product: WMTE14W: 2 Line Telephone Wall Mount Wall plate (4 Conductor),

White.4. Coax & Phone:

a. Product: TPTELTV: 2 Line Telephone/1 GHz Coax F Wall plate, Brown.b. Product: TPTELTVBK: 2 Line Telephone/1 GHz Coax F Wall plate, Black.c. Product: TPTELTVI: 2 Line Telephone/1 GHz Coax F Wall plate, Ivory.d. Product: TPTELTVLA: 2 Line Telephone/1 GHz Coax F Wall plate, Light

Almond.e. Product: TPTELTVW: 2 Line Telephone/1 GHz Coax F Wall plate, White.

M. Cat 5e Quick Connect Inserts:1. Product: WP3475-BE: Quick Connect Cat5e RJ45 Keystone Insert, Blue.2. Product: WP3475-BE-50: Quick Connect Cat5e RJ45 Keystone Insert, 50-pk, Blue.3. Product: WP3475-BK: Quick Connect Cat5e RJ45 Keystone Insert, Black.4. Product: WP3475-BR: Quick Connect Cat5e RJ45 Keystone Insert, Brown.5. Product: WP3475-GN: Quick Connect Cat5e RJ45 Keystone Insert, Green.6. Product: WP3475-GY: Quick Connect Cat5e RJ45 Keystone Insert, Grey.7. Product: WP3475-IV: Quick Connect Cat5e RJ45 Keystone Insert, Ivory.8. Product: WP3475-LA: Quick Connect Cat5e RJ45 Keystone Insert, Light Almond.9. Product: WP3475-LA-10: Quick Connect Cat 5e RJ45 Keystone Insert, 10-pk, Light

Almond.10. Product: WP3475-LA-50: Quick Connect Cat 5e RJ45 Keystone Insert, 50-pk, Light

Almond.11. Product: WP3475-OR: Quick Connect Cat5e RJ45 Keystone Insert, Orange.12. Product: WP3475-RE: Quick Connect Cat5e RJ45 Keystone Insert, Red.13. Product: WP3475-WH: Quick Connect Cat5e RJ45 Keystone Insert, White.14. Product: WP3475-WH-10: Quick Connect RJ45 Cat 5e Keystone Insert, 10-pk, White.15. Product: WP3475-WH-100: Quick Connect RJ45 Cat 5e Keystone Insert, 100-pk,

White.16. Product: WP3475-WH-50: Quick Connect RJ45 Cat 5e Keystone Insert, 50-pk, White.17. Product: WP3475-YE: Quick Connect Cat5e RJ45 Keystone Insert, Yellow.

N. Cat 6 Quick Connect Insert:1. Product: WP3476-BE: Quick Connect Cat6 RJ45 Keystone Insert, Blue.2. Product: WP3476-BE-50: Quick Connect Cat6 RJ45 Keystone Insert, 50-pk, Blue.3. Product: WP3476-BK: Quick Connect Cat6 RJ45 Keystone Insert, Black.4. Product: WP3476-BR: Quick Connect Cat6 RJ45 Keystone Insert, Brown.5. Product: WP3476-GY: Quick Connect Cat6 RJ45 Keystone Insert, Grey.6. Product: WP3476-IV: Quick Connect Cat6 RJ45 Keystone Insert, Ivory.7. Product: WP3476-LA: Quick Connect Cat6 RJ45 Keystone Insert, Light Almond.8. Product: WP3476-LA-10: Quick Connect Cat6 RJ45 Keystone Insert, 10-pk, Light

16000-8

Page 9:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

Almond.9. Product: WP3476-LA-50: Quick Connect Cat6 RJ45 Keystone Insert, 50-pk, Light

Almond.10. Product: WP3476-OR: Quick Connect Cat6 RJ45 Keystone Insert, Orange.11. Product: WP3476-RE: Quick Connect Cat6 RJ45 Keystone Insert, Red.12. Product: WP3476-WH: Quick Connect Cat6 RJ45 Keystone Insert, White.13. Product: WP3476-WH-10: Quick Connect Cat6 RJ45 Keystone Insert, 10-pk, White.14. Product: WP3476-WH-100: Quick Connect Cat6 RJ45 Keystone Insert, 100-pk,

White.15. Product: WP3476-WH-50: Quick Connect Cat6 RJ45 Keystone Insert, 50-pk, White.

O. Cat 6a Quick Connect Insert:1. Product: WP346A-BE: Quick Connect Cat 6a RJ45 Keystone Insert, Blue.2. Product: WP346A-BK: Quick Connect Cat 6a RJ45 Keystone Insert, Black.3. Product: WP346A-BR: Quick Connect Cat 6a RJ45 Keystone Insert, Brown.4. Product: WP346A-GN: Quick Connect Cat 6a RJ45 Keystone Insert, Green.5. Product: WP346A-GY: Quick Connect Cat 6a RJ45 Keystone Insert, Grey.6. Product: WP346A-IV: Quick Connect Cat 6a RJ45 Keystone Insert, Ivory.7. Product: WP346A-LA: Quick Connect Cat 6a RJ45 Keystone Insert, Light Almond.8. Product: WP346A-OR: Quick Connect Cat 6a RJ45 Keystone Insert, Orange.9. Product: WP346A-RE: Quick Connect Cat 6a RJ45 Keystone Insert, Red.10. Product: WP346A-WH: Quick Connect Cat 6a RJ45 Keystone Insert, White.11. Product: WP346A-YE: Quick Connect Cat 6a RJ45 Keystone Insert, Yellow.

P. Coax Inserts:1. Recessed:

a. Product: WP3480-BK: Gold Recessed 3 GHz Keystone F-Connector, Black.b. Product: WP3480-BR: Gold Recessed 3 GHz Keystone F-Connector, Brown.c. Product: WP3480-IV: Gold Recessed 3 GHz Keystone F-Connector, Ivory.d. Product: WP3480-LA: Gold Recessed 3 GHz Keystone F-Connector, Light

Almond.e. Product: WP3480-WH: Gold Recessed 3 GHz Keystone F-Connector, White.f. Product: WP3481-BK: Nickel Recessed 3 GHz Keystone F-Connector, Black.g. Product: WP3481-BR: Nickel Recessed 3 GHz Keystone F-Connector, Brown.h. Product: WP3481-GY: Nickel Recessed 3 GHz Keystone F-Connector, Gray.i. Product: WP3481-IV: Nickel Recessed 3 GHz Keystone F-Connector, Ivory.j. Product: WP3481-LA: Nickel Recessed 3 GHz Keystone F-Connector, Light

Almond.k. Product: WP3481-LA-10: Nickel Recessed 3 GHz Keystone F-Connector, 10-

pk, Light Almond.l. Product: WP3481-WH: Nickel Recessed 3 GHz Keystone F-Connector, White.m. Product: WP3481-WH-10: Nickel Recessed 3 GHz Keystone F-Connector, 10-

pk, White.n. Product: WP3481-WH-50: Nickel Recessed 3 GHz Keystone F-Connector, 50-

pk, White.o. Product: WP3482-BK: Gold Recessed 1 GHz Self-Terminating Keystone F-

Connector, Black.p. Product: WP3482-BR: Gold Recessed 1 GHz Self-Terminating Keystone F-

Connector, Brown.q. Product: WP3482-IV: Gold Recessed 1 GHz Self-Terminating Keystone F-

Connector, Ivory.r. Product: WP3482-LA: Gold Recessed 1 GHz Self-Terminating Keystone F-

Connector, Lt Almond.s. Product: WP3482-WH: Gold Recessed 1 GHz Self-Terminating Keystone F-

Connector, White.2. Non-Recessed:

16000-9

Page 10:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

a. Product: WP3479-BK: Non-Recessed Nickel 1 GHz F-Connector - Black.b. Product: WP3479-BR: Non-Recessed Nickel 1 GHz F-Connector - Brown.c. Product: WP3479-GY: Non-Recessed Nickel 1 GHz F-Connector - Gray.d. Product: WP3479-IV: Non-Recessed Nickel 1 GHz F-Connector - Ivory.e. Product: WP3479-LA: Non-Recessed Nickel 1 GHz F-Connector - Light

Almond.f. Product: WP3479-LA-10: Non-Recessed Nickel 1 GHz F-Connector - 10-pk -

Light Almond.g. Product: WP3479-LA-50: Non-Recessed Nickel 1 GHz F-Connector - 50-pk -

Light Almond.h. Product: WP3479-WH: Non-Recessed Nickel 1 GHz F-Connector - White.i. Product: WP3479-WH-10: Non-Recessed Nickel 1 GHz F-Connector - 10-pk -

White.j. Product: WP3479-WH-50: Non-Recessed Nickel 1 GHz F-Connector - 50-pk -

White.

Q. LV Brackets:1. Product: AC1009-11: Single Gang LV Bracket Face Mount New Construction (Box of

24).2. Product: AC1009-02: Dual Gang LV Bracket Face Mount New Construction (Box of

12).3. Product: AC1010-01: Single Gang LV Bracket Retrofit (Box of 24).4. Product: AC1010-02: Dual Gang LV Bracket Retrofit (Box of 12).5. Product: AC1010-03: Triple Gang LV Bracket Retrofit (Box of 12).

R. Patch Panel:1. Product: WP24RM:24-Port Keystone Rack Mount Patch Panel.2. Product: WP48RM:48-Port Keystone Rack Mount Patch Panel.3. Product: 24845C5E:24-Port Cat 5e Rack Mount Patch Panel.4. Product: 48845C5E:48-Port Cat 5e Rack Mount Patch Panel.5. Product: 24845CC6:24-Port Cat 6 Rack Mount Patch Panel.6. Product: 48845CC6:48-Port Cat 6 Rack Mount Patch Panel.

S. Flat Panel TV Pre-Wire:1. Power and Cable Kits:

a. Product: HT2102-WH-V1: White Flat Panel TV Connection Kit.b. Product: HT2103-WH-V1: White Home Theater Connection Kit.c. Product: AC2102: Recessed Box New Construction Bracket (Works w/ HT2103

& HT2102).2. HDMI Kits:

a. Product: HT2000-WH-V1: Basic in-Wall HDMI Signal Distribution Kit.b. Product: HT2001-WH-V1: Premium in-Wall HDMI Signal Distribution Kit, White

(Consumer Pkg), includes 1 HDMI strap, 1 cable access strap, 2 wall plates, 9 feet (2743 mm) in-wall rated HDMI cable.

c. Product: HT2002-WH-V1: Component Video Wall Mount Distribution Kit, White (Consumer Pkg), includes 2 CVDA straps, 2 wall plates, 9 feet (2743 mm) in-wall rated patch cable.

d. Product: HT2004-WH-V1: HDTV In-Wall Cable Connection Kit - White (Consumer Pkg) includes 2 cable access straps w/wall plates & in-wall strap mounting clips.

3. HDMI Cable - CL3 In-Wall Rated:a. Product: AC2M00-BK: 0.7m (2.3 feet) HS HDMI w/Ethernet CL3 Cable.b. Product: AC2M01-BK: 1m (3.3 feet) HS HDMI w/Ethernet CL3 Cable.c. Product: AC2M02-BK: 2m (6.6 feet) HS HDMI w/Ethernet CL3 Cable.d. Product: AC2M03-BK: 3m (9.8 feet) HS HDMI w/Ethernet CL3 Cable.e. Product: AC2M04-BK: 4m (13.1 feet) HS HDMI w/Ethernet CL3 Cable.

16000-10

Page 11:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

f. Product: AC2M05-BK: 5m (16.4 feet) HS HDMI w/Ethernet CL3 Cable.g. Product: AC2M07-BK: 7.5m (24.6 feet) HS HDMI w/Ethernet CL3 Cable.h. Product: AC2M10-BK: 10m (32.8 feet) HS HDMI w/Ethernet CL3 Cable.i. Product: AC2M15-BK: 15m (49.2 feet') HS HDMI w/Ethernet CL3 Cable.j. Product: AC2M20-BK: 20m (65.6 feet) HS HDMI w/Ethernet CL3 Cable.

4. Bullnose Wall Plates:a. Product: WP9001-BK: Single Gang Hinged Bull Nose Wall plate - Black.b. Product: WP9001-WH: Single Gang Hinged Bull Nose Wall plate - White.c. Product: WP9002-BK: Double Gang Hinged Bull Nose Wall plate - Black.d. Product: WP9002-WH: Double Gang Hinged Bull Nose Wall plate - White.

2.3 INTEGRATED WIRING DEVICES

A. Product Family: Integrated solution from Adorne by Legrand.

B. Outlets:1. Pop-Out Outlets:

a. General: Outlets comply with UL 498.b. Pop-Out Outlet, 1-Gang: adorne™ Part No. ARPTR151G2; rated 15 amps, 125

volts; NEMA Configuration 5-15R; tamper-resistant; includes 1-gang frame for installation; cannot be paired with other switches, dimmers, outlets, or accessories; white or magnesium finish; UL Listed.

c. Pop-Out Outlet, 2-Gang: adorne™ Part No. ARPTR152G2; rated 15 amps, 125 volts; NEMA Configuration 5-15R; tamper-resistant; includes one (1) Pop-Out Outlet and 2-gang frame for installation; use to pair Pop-Out Outlets with other switches, dimmers, outlets, or accessories; white or magnesium finish; UL Listed.

2. Tamper-Resistant Outlets:a. General: Outlets comply with UL 498.b. Tamper-Resistant Outlet, 2-Module: adorne Part No. ARTR152; rated 15 amps,

125 volts; NEMA Configuration 5-15R; pair with a 1-Module NightLight, Paddle Switch, or USB outlet for greater functionality in a 1-gang, 3-Module wall plate; outlet comes with patented shutter system to prevent children from pushing small objects into the outlet; white or magnesium finish; UL Listed.

c. Tamper-Resistant Outlet, 2-Module: adorne Part No. ARTR202; rated 20 amps, 125 volts; NEMA Configuration 5-20R; pair with a 1-Module NightLight, Paddle Switch, or USB outlet for greater functionality in a 1-gang, 3-Module wall plate; outlet comes with patented shutter system to prevent children from pushing small objects into the outlet; white or magnesium finish; UL Listed.

d. Tamper-Resistant Outlet, 3-Module: adorne Part No. ARTR153; rated 15 amps, 125 volts; NEMA Configuration 5-15R; compatible with a 1-gang, 3-Module wall plate only; cannot be used in multi-gang installations; outlet comes with patented shutter system to prevent children from pushing small objects into the outlet; white or magnesium finish; UL Listed.

e. Tamper-Resistant GFCI Outlet, 2-Module: adorne Part No. AGFTR2152; rated 15 amps, 125 volts; NEMA Configuration 5-15R; protects against serious injury due to electric shock; required by National Electrical Code in kitchens, bathrooms, and outdoor locations; outlet comes with patented shutter system to prevent children from pushing small objects into the outlet; white or magnesium finish; UL Listed.1) Self-test: Automatic test is conducted every three seconds, ensuring it's

always ready to protect. If device fails the test, the indicator light flashes to signal that the GFCI should be replaced and power to the receptacle will be disconnected.

f. Tamper-Resistant GFCI Outlet, 2-Module: adorne Part No. AGFTR2202; rated 20 amps, 125 volts; NEMA Configuration 5-20R; protects against serious injury

16000-11

Page 12:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

due to electric shock; required by National Electrical Code in kitchens, bathrooms, and outdoor locations; outlet comes with patented shutter system to prevent children from pushing small objects into the outlet; white or magnesium finish; UL Listed.1) Self-test: Automatic test is conducted every three seconds, ensuring it's

always ready to protect. If device fails the test, the indicator light flashes to signal that the GFCI should be replaced and power to the receptacle will be disconnected.

g. Tamper-Resistant GFCI Outlet, 3-Module: adorne Part No. AGFTR2153; rated 15 amps, 125 volts; NEMA Configuration 5-15R; protects against serious injury due to electric shock; required by National Electrical Code in kitchens, bathrooms, and outdoor locations; compatible with a 1-gang, 3-Module wall plate only; cannot be used in multi-gang installations; outlet comes with patented shutter system to prevent children from pushing small objects into the outlet; white or magnesium finish; UL Listed.1) Self-test: Automatic test is conducted every three seconds, ensuring it's

always ready to protect. If device fails the test, the indicator light flashes to signal that the GFCI should be replaced and power to the receptacle will be disconnected.

3. USB Outlets:a. General: Outlets ETL tested and labeled for compliance with UL 1310.b. USB Outlet, 1-Module (Half-Size): adorne Part No. ARUSB; rated 2.1 amps, 5

volts DC, 11 watts; charges mobile devices such as phone and tablets; pair with a 1-module switch or second USB outlet in a 1-gang, 2-Module wall plate or with a 1-gang, 3-Module wall plate for more functionality in one box; white or magnesium finish; ETL Listed.

4. Energy-Saving ON/OFF Outlets:a. General: Outlets comply with UL 498.b. Energy-Saving ON/OFF Outlet, 2-Module: adorne Part No. ARPS152; rated 15

amps, 125 volts, with built-in manual switch; NEMA Configuration 5-15R; promotes saving energy and stopping flow of power without unplugging devices; for use in kitchens, bathrooms, and computer rooms; white or magnesium finish; UL Listed.

5. Wireless ON/OFF Outlets:a. General: Outlets comply with UL 498.b. Wireless ON/OFF Outlet: adorne Part No. ARPS15RF2; rated 15 amps, 125

volts; NEMA Configuration 5-15R; controls plug load from a new location without running additional wires when paired with adorne™ sofTap Wireless Master Switch; on/off switch allows the user to save energy and stop flow of power to outlet without unplugging the device; white or magnesium finish; UL Listed.

C. Switches:1. General: Switches comply with UL 20 or UL 508.2. 1-Module (Half-Size) Paddle Switches: adorne™ Part No. ASPD1531; single-pole, 3-

way; rated 15A, 120 VAC; 1/2-hp; white or magnesium finish; compatible with all types of loads; features a simple up and down motion, permitting easy on-off control of lighting; UL Listed.a. Locator Status Light: adorne Part No. AALSL6; light is on when load is off and

off when load is on; simplifies finding the switch in a dark room.3. Two-Module Paddle Switches:

a. Single-Pole, Three-Way: adorne Part No. ASPD1532; single-pole, 3-way; rated 15A, 120 VAC; 1/2-hp; white or magnesium finish; compatible with all types of loads; features a simple up and down motion, permitting easy on-off control of lighting; UL Listed.

b. Single-Pole, Three-Way: adorne Part No. ASPD2032; single-pole, 3-way; rated

16000-12

Page 13:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

20A, 120 VAC; 1/2-hp; white or magnesium finish; compatible with all types of loads; features a simple up and down motion, permitting easy on-off control of lighting; UL Listed.

c. Four-Way: adorne Part No. ASPD2042; pair with two (2) 3-way switches; rated 20A, 120 VAC; 1/2-hp; white or magnesium finish; compatible with all types of loads; features a simple up and down motion, permitting easy on-off control of lighting; UL Listed.1) Locator Status Light: adorne Part No. AALSL6; light is on when load is

off and off when load is on; simplifies finding the switch in a dark room.4. Whisper Switches: adorne™ Part No. ASWR1532; single-pole, 3-way; rated 15A, 120

VAC; 1/2-hp; white or magnesium finish; compatible with all types of loads; features a slim rocker switch with classic, elegant lines and a silent, fluid motion; UL Listed.a. Locator Status Light: adorne Part No. AALSL6; light is on when load is off and

off when load is on; simplifies finding the switch in a dark room.5. Push Switches: adorne™ Part No. ASPU1532; single-pole, 3-way; rated 15A, 120

VAC; 1/2-hp; white or magnesium finish; compatible with all types of loads; features a simple push-button motion to turn lights on and off; UL Listed.a. Locator Status Light: adorne Part No. AALSL6; light is on when load is off and

off when load is on; simplifies finding the switch in a dark room.6. sofTap Switches:

a. Single-Pole, Three-Way: adorne Part No. ASTP1532; single-pole, 3-way; rated 15A, 120 VAC, 1/2-hp; white or magnesium finish; compatible with all types of loads; uses micro-movement to turn lights on and off with a soft tap of the finger; UL Listed.

b. Wifi-Ready Wireless Master: adorne Part No. ASTP155RM; wireless master, wifi-ready; white or magnesium finish; compatible with all types of loads; features a simple up and down motion, permitting easy on-off control of lighting with RF communication up to 100 feet from master location (hard wired to load), 300 feet with repeater; UL Listed.

c. Wifi-Ready Wireless Remote: adorne Part No. ASTPRR; wireless remote, wifi-ready; white or magnesium finish; compatible with all types of loads; features a simple up and down motion, permitting easy on-off control of lighting with RF communication up to 100 feet from remote locations, 300 feet with repeater; UL Listed.

7. SensaSwitches:a. Switches use passive-infrared (PIR) sensor technology to automatically turn

lights on and off when leaving a room; includes micro movement technology to manually turn lights on and off with a soft touch of the finger and occupancy sensor. The occupancy sensor, vacancy sensor, and dimmer each have a maximum coverage range of 180 degrees and coverage area of 600 sq ft (56 sq. m).

b. Single-Pole, Three-Way: adorne Part No. ASOS32; single-pole, single-pole, three-way when paired together on the same circuit; rated 600W, 120 VAC, 60 Hz, 1/6-hp; white or magnesium finish; compatible with all types of loads; auto-ON/auto-OFF; 5-30 minute time delay; UL Listed.

c. Multi-Way: adorne Part No. ASOS32; rated 600W, 120 VAC, 60 Hz, 1/6-hp; white or magnesium finish; compatible with all types of loads; auto-ON/auto-OFF; 30 second-30 minute time delay; UL Listed; CA Title 20/24 Compliant.

d. Single-Pole, Multi-Way: adorne Part No. ASVS12; single-pole, three-way; rated 600W, 120 VAC, 60 Hz, 1/6-hp; white or magnesium finish; compatible with all types of loads; manual-ON/auto-OFF; 5-30 minute time delay; UL Listed; CA Title 24 compliant.

e. Multi-Way: adorne Part No. ASVS12; single-pole, three-way; rated 600W, 120 VAC, 60 Hz, 1/6-hp; white or magnesium finish; compatible with all types of loads; manual-ON/auto-OFF; 30 second-30 minute time delay; UL Listed; CA Title 20/24 compliant.

16000-13

Page 14:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

f. Single-Pole, Multi-Way: adorne Part No. ASTM2; single-pole, three-way; rated 600W, 120 VAC, 60 Hz, 1/6-hp; white or magnesium finish; compatible with all types of loads; manual-ON/timed-OFF, selectable times of 10, 20, 30 or 60 minutes with a soft touch of the finger; UL Listed.

g. Single-Pole, Multi-Way: adorne Part No. ASM703H; single-pole, three-way; rated 600W, 120 VAC, 60 Hz; white or magnesium finish; compatible with incandescent, LED and CFL; selectable auto/manual-ON; daylight hold-off 30 second-30 minute time delay; UL Listed.

8. Touch Switches:a. General: Switches comply with UL 508.b. Single-Pole, Three-Way: adorne Part No. ASTH1532; single-pole, 3-way; rated

15A, 120 VAC, 60 Hz, 1/2-hp; white or magnesium finish; compatible with all types of loads; features translucent face; operates by a touch of the finger on a circle to turn lights on and off; UL Listed.

c. Wifi-Ready Wireless Master: adorne Part No. ASTH155RM; wireless master, wifi-ready; white or magnesium finish; compatible with all types of loads; features translucent face; operates by a touch of the finger on a circle to turn lights on and off; RF communication up to 30 feet (9144 mm) from master location; UL Listed.

d. Wifi-Ready Wireless Remote: adorne Part No. ASTHRR; wireless remote, wifi-ready; white or magnesium finish; compatible with all types of loads; features translucent face; operates by a touch of the finger on a circle to turn lights on and off; RF communication up to 30 feet (9144 mm) from remote location; UL Listed.

9. Wave Switches:a. General: Comply with UL 508.b. Single-Pole, Three-Way: adorne Part No. ASWV1532; single-pole, 3-way; rated

15A, 120 VAC, 1/2-hp; white or magnesium finish; compatible with all types of loads; features innovative technology combined with sleek, contemporary design; operates by a wave of the hand in front of the switch to turn lights on and off; sensor distance preset at four inches (102 mm), adjustable from one to six inches (25 mm to 152 mm) in front of switch; UL Listed.

D. Dimmers:1. General: Dimmers comply with UL 1472.2. Paddle Dimmers:

a. Single-Pole, Three-Way: adorne Part No. ADPD703H; single-pole, 3-way, 2-wire; rated 25W - 700W; compatible with incandescent and halogen lamps; white or magnesium finish; features a simple up and down motion, permitting easy on-off control of lighting; includes slider for dimming lights; UL Listed.

b. Single-Pole, Three-Way: adorne Part No. ADPD1103H; single-pole, 3-way, 2-wire; rated 25W - 1100W; compatible with incandescent and halogen lamps; white or magnesium finish; features a simple up and down motion, permitting easy on-off control of lighting; includes slider for dimming lights; UL Listed.

c. Single-Pole, Three-Way: adorne Part No. ADPD453L; single-pole, 3-way, 2-wire; rated 25W - 450W for CFL and LED lamps and 600W for incandescent and halogen lamps; white or magnesium finish; features a simple up and down motion, permitting easy on-off control of lighting; includes slider for dimming lights; UL Listed.

3. Whisper Dimmers:a. Single-Pole, Three-Way: adorne Part No. ADWR703H; single-pole, 3-way, 2-

wire; rated 25W - 700W; compatible with incandescent and halogen lamps; white or magnesium finish; features classic, elegant lines and a fluid motion, permitting easy on-off control of lighting; includes slider for dimming lights; UL Listed.

b. Single-Pole, Three-Way: adorne Part No. ADWR1103H; single-pole, 3-way, 2-

16000-14

Page 15:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

wire; rated 25W - 1100W; compatible with incandescent and halogen lamps; white or magnesium finish; features classic, elegant lines and a fluid motion, permitting easy on-off control of lighting; includes slider for dimming lights; UL Listed.

4. sofTap Dimmers:a. Single-Pole, Three-Way, True Universal: adorne Part No. ADTP703TU; single-

pole, 3-way, 3-wire; rated 700W; compatible with incandescent, halogen, forward and reverse-phase ELV, MLV, fluorescent, CFL, and LED lamps; white or magnesium finish; features innovative micro-movement that turns lights on and off with just a soft tap of the finger; includes unique paddle to adjust light levels; UL Listed.

b. Single-Pole, Three-Way: adorne Part No. ADTP703H; single-pole, 3-way, 2-wire; rated 700W; compatible with incandescent and halogen lamps; white or magnesium finish; features innovative micro-movement that turns lights on and off with just a soft tap of the finger; includes unique paddle to adjust light levels; UL Listed.

c. Single-Pole, Three-Way: adorne Part No. ADTP1103H; single-pole, 3-way, 2-wire; rated 1100W; compatible with incandescent and halogen lamps; white or magnesium finish; features innovative micro-movement that turns lights on and off with just a soft tap of the finger; includes unique paddle to adjust light levels; UL Listed.

5. sofTap Dimmers, Wifi-Ready Wireless:a. Wireless Master, Wifi-Ready: adorne Part No. ADTP600RMH; 2-wire; rated

600W; compatible with incandescent and halogen lamps; white or magnesium finish; features classic, elegant lines and a fluid motion, permitting easy on-off control of lighting; includes slider for dimming lights; UL Listed.

b. Wireless Master, Wifi-ready, Tru-Universal: adorne Part No. ADTP700RMTU; 3-wire; rated 450W for CFL, LED, and reverse-phase ELV lamps, rated 700W for incandescent, halogen, forward-phase ELV, MLV, and fluorescent lamps; white or magnesium finish; features classic, elegant lines and a fluid motion, permitting easy on-off control of lighting; includes slider for dimming lights; UL Listed.

c. Wireless Remote, Wifi-ready: adorne Part No. ADTPRR; compatible with all loads; white or magnesium finish; UL Listed.

6. SensaDimmers, Auto-ON, Auto-OFF:a. Single-Pole, Three-Way: adorne Part No. ADSM703H; single-pole, 3-way, 3-

wire; rated 700W; adjustable from 5-30 minutes; compatible with incandescent and halogen lamps; white or magnesium finish; features passive infrared (PIR) sensor technology, automatically turns lights on or off when someone enters or leaves a room; includes a dimming occupancy sensor; UL Listed.

b. Single-Pole, Three-Way: adorne Part No. ADSM703H; single-pole, 4-way, 3-wire; rated 700W; adjustable from 5-30 minutes; compatible with CFL and 450-watt LED lamps; white or magnesium finish; features passive infrared (PIR) sensor technology, automatically turns lights on or off when someone enters or leaves a room; includes a dimming occupancy sensor; UL Listed.

7. Touch Dimmers, Wifi-Ready Wireless:a. Wireless Master, Wifi-Ready: adorne Part No. ADTH600RMH; 2-wire; rated

600W; compatible with incandescent and halogen lamps; white or magnesium finish; features translucent face and operates just like an iPhone® - touch a finger on the circle to turn lights on and off; includes arrows on right side of switch for dimming; UL Listed.

b. Wireless Remote, Wifi-Ready: adorne Part No. ADTHRR; compatible with all loads; white or magnesium finish; UL Listed.

c. Wireless Master, Wifi-Ready, True Universal: adorne Part No. ADTH700RMTU; 3-wire; rated 450W for CFL, LED, and reverse-phase ELV lamps, rated 700W for incandescent, halogen, forward-phase ELV, MLV, and fluorescent lamps;

16000-15

Page 16:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

white or magnesium finish; features translucent face and operates just like an iPhone® - touch a finger on the circle to turn lights on and off; includes arrows on right side of switch for dimming; UL Listed.

8. Paddle Fan Speed Controls:a. General: Fan speed controls comply with UL 1917.b. Four-Speed De-hummer Controls: adorne Part No. AAFN4S16A; rated 1.6

amp, 120 volts AC; compatible with paddle-type ceiling fans; white or magnesium finish; features a simple up and down motion, permitting easy on-off control of lighting; includes slider for adjusting fan speed; UL Listed.

E. Accessories:1. Nightlights:

a. General: ETL tested and listed for compliance with UL 1786.b. Nightlight, 1-Module: adorne Part No. AANLM14; ambient light level sensor,

soft, glowing LED light; pairs with a switch or outlet in a 1-gang, 3-module plate; light levels include: "always off," "low," "medium," and "high".

c. Nightlight, 2-Module: adorne Part No. AANLM24; ambient light level sensor, soft, glowing LED light; light levels include: "always off," "low," "medium," and "high".

d. Portable Nightlight/Flashlight: adorne Part No. AARNL2; ambient light level sensor, soft, glowing LED light; push nightlight to remove it from wall for use as a flashlight, device recharges while mounted in wall and operates for up to 10 hours during a power failure; light levels include: "always off," "low," "medium," "high," and "flashlight".

2. Accent Nightlights:a. General: ETL tested and listed for compliance with UL 514D.b. General: The accent nightlight can be added to any adorne product and is

compatible with 1- to 4-gang wall plates. Device is invisible once installed and can be activated by placing a finger under the wall plate. This causes the light to cycle through several light level options including: Daytime "Auto-OFF" and "Always ON", Night Time "high," "medium," "low," "ultra-low," and "OFF."

c. Accent Nightlight, 1-Gang: adorne Part No. AAAL1G4.d. Accent Nightlight, 2-Gang: adorne Part No. AAAL2G2.e. Accent Nightlight, 3-Gang: adorne Part No. AAAL3G2.f. Accent Nightlight, 4-Gang: adorne Part No. AAAL4G2.

3. Locator Status Lights:a. General: A small locator light can be added to a Paddle, Whisper, or Push

switch or dimmer; standard feature on sofTap, SensaSwitch, Touch, and Wave switches and dimmers. Facilitates locating the switch or dimmer in the dark. Locator light is on when the load is off and off when the load is on.

b. Locator Status Light: adorne Part No. AALSL6; ETL Listed.4. Blank Modules:

a. General: ETL and UL listed for compliance with UL 514D.b. General: Blank inserts can be paired with other 1-module devices such as the

Nightlight, Paddle Switch, or USB, in a 1-gang wall plate to provide a complete, finished appearance.

c. Blank, 1-Module: adorne Part No. AABK1; white or magnesium finish.5. Keystone Frames:

a. General: Keystone frames enable audio, video, and data connectivity in an adorne wall plate. Pair and keystone insert with a 1-port, 2-port, or 4-port frame and then mount in an adorne™ wall plate for a complete installation.

b. 1-Port Frame: adorne Part No. AC1PF; white or magnesium finish.c. 2-Port Frame: adorne Part No. AC2PF; white or magnesium finish.d. 4-Port Frame: adorne Part No. AC4PF; white or magnesium finish.e. In-Wall Cable Access Port: adorne Part No. ACBRSTP; white or magnesium

finish.

16000-16

Page 17:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

6. Keystone Inserts:a. Cat 5e RJ45 Data/Phone Insert: adorne Part No. AC5ERJ45; white or

magnesium finish.b. Cat 5e RJ45 Data Coupler Insert: adorne Part No. AC5ERJ45C; white or

magnesium finish.c. Cat 6 RJ45 Data Insert: adorne Part No. AC6RJ45; white or magnesium finish.d. RJ25 Phone Jack: adorne Part No. ACRJ45; white or magnesium finish.e. Component Video RCA to F Kit: adorne Part No. ACRGBRCAF; white or

magnesium finish.f. Composite Video RCA to F-Connector: adorne Part No. ACYRCAF; white or

magnesium finish.g. HDMI Keystone Coupler: adorne Part No. ACHDMI; white or magnesium finish.h. Single Keystone Speaker Connector: adorne Part No. ACSSI; white or

magnesium finish.i. Speaker Binding Post: adorne Part No. ACABP; white or magnesium finish.j. Subwoofer RCA to F-Connector: adorne Part No. ACPRCAF; white or

magnesium finish.k. Video F-Connector: adorne Part No. ACNRFC; white or magnesium finish.l. Blank Keystone Insert: adorne Part No. ACBLK; white or magnesium finish;

four (4) pack.

F. Wall Plates:1. Wall Plates, General: Single and combination types matching corresponding wiring

devices.a. Available in one through six gang sizes to complement adorne switches,

dimmers, outlets, and accessories. Collection includes variety of finishes, including cast metals, real materials, and plastic. Each wall plate comes with a metal frame to enable easy installation when paired with a device. Plates are screw less and snap onto the metal frame. All wall plates are UL and ETL-approved.

2. Wall plates are ETL and UL tested and listed for compliance with UL 514D.3. Wall Plates, Cast Metals: adorne Part No.___________

a. Finish and Color: Aged Bronze, Antique Bronze, Antique Nickel, Brushed Brass, Brushed Pewter, Brushed Stainless, Steel, Dark Burnished Pewter, Oil-Rubbed Bronze, Satin Bronze, Satin Nickel. Refer to Drawings or Schedule for finish.

4. Wall Plates, Real Materials: adorne Part No. _______a. Finish and Color: Black Leather, Brushed Stainless, French Oak, Mirror Black,

Mirror White, Wenge Wood, Custom with Magnesium Trim, Custom with White Trim. Refer to Drawings or Schedule for finish.

5. Wall Plates, Plastics: adorne Part No. _________).a. Finish and Color: Bronze, Cherry, Gloss White, Graphite Honey, Lichen Green,

Pale Blue, Plum Satin, Light Almond, Soft Touch Felt Green, Soft Touch Moss Grey, Soft Touch Russet, Titanium Turquoise Blue. Refer to Drawings or Schedule for finish.

2.4 INTEGRATED WIRING DEVICES

A. Product Family: Radiant Series by Pass & Seymour.

B. Convenience Receptacles 125 V, 15 and 20 A:1. Comply with NEMA WD 1, NEMA WD 6 configurations 5-15R and 5-20R, UL 498 and

Federal Specification W-C-596. Prewired pigtail connectors that accommodate Fed Spec receptacles are approved. Required to be a crimped and welded terminal with right angle application connector.

2. Products: Pass & Seymour, 885 (15A duplex).

16000-17

Page 18:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

3. Products: Pass & Seymour, 885S (15A duplex, self-grounding).

C. Tamper-Resistant Convenience Receptacles, 125V, 15 and 20 A:1. Comply with NEMA WD1, NEMA WD6 configurations 5-15R and 5-20R, UL498 and

Federal Specification W-C-596. Prewired pigtail connectors that accommodate Fed Spec receptacles are approved. Required to be a crimped and welded terminal with right angle application connector.

2. Products: Pass & Seymour, 885TR (15A duplex).3. Products: Pass & Seymour, TR26352R (20A duplex).

D. Duplex GFCI Convenience Receptacles, 125 V, 15 and 20 A:1. PlugTail receptacle connectors meet Fed Spec GFCI receptacle approval. Right-angle

connectors feature pre-stripped leads. Connector contacts are crimped and welded.2. Products: Pass & Seymour, 1597 (15A duplex).3. Products: Pass & Seymour, 2097 (20A duplex).4. Products: Pass & Seymour, 2097NA (20A duplex, NAFTA-Compliant).5. Products: Pass & Seymour, PT1597 (15A duplex, PlugTail).6. Products: Pass & Seymour, PT1597NA (15A duplex, PlugTail, NAFTA-Compliant).7. Products: Pass & Seymour, PT2097 (20A duplex, PlugTail).8. Products: Pass & Seymour, PT2097NA (20A duplex, PlugTail, NAFTA-Compliant).9. Products: Pass & Seymour, 2087 (20A duplex, dead front).

E. Hospital-Grade, Duplex GFCI Convenience Receptacles, 125 V, 15 and 20 A:1. Comply with NEMA WD1, NEMA WD6 configurations 5-15R and 5-20R, UL 498

Supplement SD and Federal Specification W-C-596. Prewired pigtail connectors that accommodate Fed Spec GFCI receptacles are approved. Shall be crimped and welded terminal right angle application connector.

2. Products: Pass & Seymour, 1597HG (15A duplex).3. Products: Pass & Seymour, 2097HG (20A duplex).4. Products: Pass & Seymour, 2097HGNA (20A duplex, NAFTA-Compliant).5. Products: Pass & Seymour, PT1597HG (15A duplex, PlugTail).6. Products: Pass & Seymour, PT2097HG (20A duplex, PlugTail).7. Products: Pass & Seymour, PT2097HGNA (20A duplex, PlugTail, NAFTA-compliant).

F. Tamper-Resistant GFCI Convenience Receptacles, 125 V, 15 and 20 A:1. Comply with NEMA WD1, NEMA WD6 configurations 5-15R and 5-20R, UL 498

Supplement SD, Federal Specification W-C-596 and UL943, Class A, and include indicator light that is lighted when device is tripped. Prewired pigtail connectors that accommodate Fed Spec GFCI receptacles are approved. Shall be crimped and welded terminal right angle application connector

2. Products: Pass & Seymour, 1597TR (15A duplex, tamper resistant).3. Products: Pass & Seymour, 1597TRA (15A duplex, tamper resistant, audible alarm).4. Products: Pass & Seymour, 1597SWTTR (15A duplex, tamper resistant, combination

switch/GFCI receptacle).5. Products: Pass & Seymour, 1597NTLTR (15A duplex, tamper resistant, combination

night light/GFCI receptacle).6. Products: Pass & Seymour, 1597TRWR (15A duplex, weather resistant).7. Products: Pass & Seymour, 1597TRR (15A duplex, tamper resistant, RoHS-

Compliant).8. Products: Pass & Seymour, 1597IGTR (15A duplex, tamper resistant, isolated

ground).9. Products: Pass & Seymour, 1597TRNA (15A duplex, tamper resistant, NAFTA-

Compliant).10. Products: Pass & Seymour, 1597TRWRNA (15A duplex, tamper resistant, weather

resistant, NAFTA-Compliant).11. Products: Pass & Seymour, 2097TR (20A duplex, tamper resistant).

16000-18

Page 19:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

12. Products: Pass & Seymour, 2097TRA (20A duplex, tamper resistant, audible alarm).13. Products: Pass & Seymour, 2097NTLTR (20A duplex, tamper resistant, combination

night light/GFCI receptacle).14. Products: Pass & Seymour, 2097TRWR (20A duplex, weather resistant).15. Products: Pass & Seymour, 2097TRRI (20A duplex, tamper resistant, RoHS-

Compliant).16. Products: Pass & Seymour, 2097IGTR (20A duplex, tamper resistant, isolated

ground).17. Products: Pass & Seymour, 2097TRNA (20A duplex, tamper resistant, NAFTA-

Compliant).18. Products: Pass & Seymour, 2097TRWRNA (20A duplex, tamper resistant, weather

resistant, NAFTA-Compliant).19. Products: Pass & Seymour, PT1597TR (15A duplex, PlugTail, tamper resistant).20. Products: Pass & Seymour, PT1597NTLTRNAW (15A duplex, PlugTail, combination

night light/GFCI receptacle, NAFTA-Compliant).21. Products: Pass & Seymour, PT2097TR (20A duplex, PlugTail, tamper resistant).22. Products: Pass & Seymour, PT2097NTLTR (20A duplex, PlugTail, tamper resistant,

combination night light/GFCI receptacle).23. Products: Pass & Seymour, PT2097TRNA (20A duplex, PlugTail, tamper resistant,

NAFTA-Compliant).24. Products: Pass & Seymour, PT2097NTLTRNA (20A duplex, PlugTail, combination

night light/GFCI receptacle, NAFTA-Compliant).

G. Tamper-Resistant, Hospital-Grade, Duplex GFCI Convenience Receptacles, 125 V, 15 and 20 A:1. Comply with UL 498 Supplement SD and Federal Specification W-C-596. Prewired

pigtail connectors that accommodate Fed Spec GFCI receptacles are approved. Shall be crimped and welded terminal right angle application connector.

2. Products: Pass & Seymour, 1597HGTR (15A duplex).3. Products: Pass & Seymour, 1597IGHGTRO (15A duplex, isolated ground).4. Products: Pass & Seymour, 1597HGNTLTR (15A duplex, combination night

light/GFCI receptacle).5. Products: Pass & Seymour, 1597HGTRA (15A duplex, audible alarm).6. Products: Pass & Seymour, 2097HGTR (20A duplex).7. Products: Pass & Seymour, 2097IGHGTR (20A duplex, isolated ground.8. Products: Pass & Seymour, 2097HGNTLTR (20A duplex, combination night

light/GFCI receptacle).9. Products: Pass & Seymour, 2097HGTRA (20A duplex, audible alarm).10. Products: Pass & Seymour, 2097HGTRNA (20A duplex, NAFTA-Compliant).11. Products: Pass & Seymour, PT1597HGTR (15A duplex, PlugTail).12. Products: Pass & Seymour, PT1597HGNTLTR (15A duplex, PlugTail, combination

night light/GFCI receptacle).13. Products: Pass & Seymour, PT2097HGTR (20A duplex, PlugTail).14. Products: Pass & Seymour, PT2097HGNTLTR (20A duplex, PlugTail, combination

night light/GFCI receptacle).15. Products: Pass & Seymour, PT2097HGTRNA (20A duplex, PlugTail, NAFTA-

compliant).16. Products: Pass & Seymour, PT2097HGNTLTRNAI (20A duplex, PlugTail, combination

night light/GFCI receptacle, NAFTA-compliant).

H. Quad USB Charging Receptacles:1. Comply with UL 1310 and cULus.2. Products: Pass & Seymour, TM8USB4.

I. USB Chargers with Duplex Tamper-Resistant Receptacles:1. Comply with UL 498, UL 1310, CSA C22.2 No. 42, CSA C22.2 No. 223, and cULus.

16000-19

Page 20:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

2. Products: Pass & Seymour, TM826USB.

J. Toggle Switches, 120/277 V:1. Prewired pigtail connectors that accommodate Fed Spec switches are approved. Shall

be crimped and welded terminal right angle application connector.2. Products: Pass & Seymour, RCD11 (15A, combination, two single pole).

a. Snap-In Light Module: Pass & Seymour, RCDLM.3. Products: Pass & Seymour, RCD33 (15A, combination, two single pole, three-way).

a. Snap-In Light Module: Pass & Seymour, RCDLM.4. Products: Pass & Seymour, RCD113 (15A, combination, two single pole and single

pole/three-way).a. Snap-In Light Module: Pass & Seymour, RCDLM.

5. Products: Pass & Seymour, RCD38TR (15A, combination, single pole/three-way and tamper resistant outlet).a. Snap-In Light Module: Pass & Seymour, RCDLM.

K. Illuminated Switches, 15 and 20A for 120/277V:1. Description: Neon-lighted handle, illuminated when switch is "OFF."2. Products: Pass & Seymour, TM870_SL (15A, single pole).3. Products: Pass & Seymour, TM873_SL (15A, three-way).4. Products: Pass & Seymour, TM874_SL (15A, four-way).

L. Incandescent Lamp Dimmers, 120 V:1. Control shall follow square-law dimming curve. On-off switch positions shall bypass

dimmer module. Dimmers shall require no de-rating when ganged with other devices2. Illuminated when "OFF."3. Products: 700 W - Pass & Seymour, RH703P (single pole and three-way).4. Products: 1100 W - Pass & Seymour, RH1103P (single pole and three-way).

M. Fluorescent Lamp Dimmer Switches:1. Modular; compatible with dimmer ballasts; trim potentiometer to adjust low-end

dimming; dimmer-ballast combination capable of consistent dimming with low end not greater than 20 percent of full brightness

2. Products: 8A, 120V - Pass & Seymour, RHFB83P (single pole and three-way).

N. Modular Fan Speed Controls, 120-V:1. Full-wave, solid-state units with integral, quiet on-off switches and audible frequency

and EMI/RFI filters. Comply with UL 1917.2. Products: Pass & Seymour RHDH163PW.3. Products: Pass & Seymour RHDH163PTC

O. Residential Vacancy Sensors (PIR):1. Manual ON - Auto-ON (selectable): Pass & Seymour, RRW600UTC (Occupancy

sensor).2. Manual ON - Auto-ON (selectable): Pass & Seymour, RRW600VTC (Vacancy

sensor).

P. Night Light Devices:1. Compliant with NEMA WD-1 and WD-6, and cULus listed.2. Product: Pass & Seymour, NTL885TR (Tamper resistant, adjustable light levels).3. Product: Pass & Seymour, NTL873 (Adjustable light settings).4. Product - Full Night Light: Pass & Seymour, NTLFULL (Adjustable light settings).

Q. Screwless Wall Plates:1. Compliance: UL 514.2. Material: Polycarbonate.3. Product: Pass & Seymour, RWP26 (One-gang).

16000-20

Page 21:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

4. Product: Pass & Seymour, RWP262 (Two-gang).5. Product: Pass & Seymour, RWP263 (Three-gang).6. Product: Pass & Seymour, RWP264 (Four-gang).7. Product: Pass & Seymour, RWP265 (Five-gang).8. Product: Pass & Seymour, RWP266 (Six-gang).

2.5 WIRING DEVICES

A. Outlets:1. Commercial Specification Grade Receptacles

a. General: UL Listed, File Number E140596, Standard UL498, CSA/CUL approved, Standard CSA-C22.2 No. 42. Conforms to NEMA WD-1 and WD-6.

b. Grade: Commercial Grade 15 and 20 amp, 125 VAC.c. Compliant: Tamper-resistant complies with 2014 NEC Article 406.12.d. Series: TR15 and TR20 as manufactured by Pass and Seymour.e. Type: Duplex Receptacle; NEMA 5-15R and NEMA 5-20R.f. Color: Brown, Black, Ivory, Light Almond, Gray, Red, White. Refer to Drawing

schedule.2. Commercial Specification Grade Tamper Resistant Receptacles

a. General: UL Listed, File Number E140596, Standard UL498, CSA/CUL approved, Standard CSA-C22.2 No. 42. Conforms to NEMA WD-1 and WD-6.

b. Grade: Commercial Grade 15 and 20 amp, 125 VAC.c. Compliant: Tamper-resistant complies with 2014 NEC Article 406.12.d. Series: TR5252 and TR5352 as manufactured by Pass and Seymour.e. Type: Duplex Receptacle; NEMA 5-15R and NEMA 5-20R.f. Color: Brown, Black, Ivory, Light Almond, Gray, Red, White. Refer to Drawing

schedule.3. Commercial Specification Grade Tamper Resistant Decorator Receptacles

a. General: UL Listed, File Number E140596, Standard UL498, CSA Certified, File Number LR16063, Standard CSA-C22.2 No. 42. Conforms to NEMA WD-1 and WD-6.

b. Grade: Commercial Grade 15 and 20 amp, 125 VAC.c. Compliant: Tamper-resistant complies with 2014 NEC Article 406.12.d. Series: TR26242 and TR26342 as manufactured by Pass and Seymour.e. Type: Duplex Receptacle; NEMA 5-15R and NEMA 5-20R.f. Color: Brown, Black, Ivory, Light Almond, Gray, Red, White. Refer to Drawing

schedule.4. Commercial Specification Grade Tamper Resistant Decorator Receptacles

a. General: UL Listed, File Number E140596, Standard UL498, CSA Certified, File Number LR16063, Standard CSA-C22.2 No. 42. Conforms to NEMA WD-1 and WD-6.

b. Grade: Commercial Grade 15 and 20 amp, 125 VAC.c. Compliant: Tamper-resistant complies with 2014 NEC Article 406.12.d. Series: TR26252 and TR26352 as manufactured by Pass and Seymour.e. Type: Duplex Receptacle; NEMA 5-15R and NEMA 5-20R.f. Color: Brown, Black, Ivory, Light Almond, Gray, Red, White. Refer to Drawing

schedule.

B. PlugTail Devices:1. Factory-terminated devices and connectors.2. PlugTail Devices - Decorator Switches:

a. General: cULus Listed, File Number E140597, UL20, Standard CSA-C22.2 No. 111, General Use Snap Switches. Federal Specification WS896. Conforms to NEMA WD-1 and WD-6.

b. Grade: Specification Grade 15 and 20 amp, 120/277 VAC.c. Series: PT26 as manufactured by Pass and Seymour.

16000-21

Page 22:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

d. Connectors: PlugTail Connector in stripped 6 inches (152 mm) solid or stranded.

e. Type: Single Pole Decorator Switches.f. Type: Single Pole Illuminated Decorator Switches.g. Type: Three-Way Decorator Switches.h. Type: Three-Way Illuminated Decorator Switches.

3. PlugTail Devices - Switches:a. General: cULus Listed, File Number LR17446, Standard CSA-C22.2 No. 111,

General Use Snap Switches. Federal Specification WS896. Conforms to NEMA WD-1 and WD-6.

b. Grade: Specification Grade 15 and 20 amp, 120/277 VAC.c. Series: PT15 and PT20 series as manufactured by Pass and Seymour.d. Connectors: PlugTail Connector in stripped 6 inches (152 mm) solid or

stranded.e. Type: Single Pole Toggle Switches.f. Type: Single Pole Illuminated Toggle Switches.g. Type: Three-Way Toggle Switches.h. Type: Three-Way Illuminated Toggle Switches.

4. PlugTail Devices - Extra Heavy Duty Outlets:a. General: cULus Listed, File Number E140596, Standard UL498. Federal

Specification WC596, Hospital Grade Conforms to NEMA WD-1 and WD-6.b. Grade: Hospital Grade 15 and 20 amp, 125 VAC. 2 Pole, 3 Wire Grounding.c. Series: PT8 as manufactured by Pass and Seymour.d. Connectors: PlugTail Connector in stripped 6 inches (152 mm) solid or

stranded.e. Type: Duplex Receptacle; NEMA 5-15R and NEMA 5-20R.f. Type: Duplex Illuminated Receptacle; NEMA 5-15R and NEMA 5-20R.

5. PlugTail Devices - Heavy Duty Compact Outlets:a. General: cULus Listed, File Number E140596, Standard UL498. UN SPSC:

3912406. Federal Specification WC596, Hospital Grade, CSA Listing: C22.2 No. 42.

b. Grade: Hospital Grade 15 and 20 amp, 125 VAC.c. Series: PT8200H and PT8300H as manufactured by Pass and Seymour.d. Connectors: PlugTail Connector in stripped 6 inches (152 mm) solid or

stranded.e. Type: Duplex Receptacle; NEMA 5-15R and NEMA 5-20R.f. Type: Duplex Illuminated Receptacle; NEMA 5-15R and NEMA 5-20R.

6. PlugTail Devices - Extra Heavy Duty Tamper Resistant Outlets:a. General: cULus Listed, File Number E140596, Standard UL498. Federal

Specification WC596, Hospital Grade.b. Grade: Hospital Grade 15 and 20 amp, 125 VAC.c. Series: PTT62H and PTTR63H as manufactured by Pass and Seymour.d. Connectors: PlugTail Connector in stripped 6 inches (152 mm) solid or

stranded.e. Type: Duplex Receptacle; NEMA 5-15R and NEMA 5-20R.

7. PlugTail Devices - Isolated Ground Outlets:a. General: cULus Listed, File Number E140596, Standard UL498. Federal

Specification WC596, Hospital Grade.b. Grade: Specification 15 and 20 amp, 125 VAC.c. Series: PTIG8200 and PTIG8300 as manufactured by Pass and Seymour.d. Connectors: PlugTail Connector in stripped 6 inches (152 mm) solid or

stranded.e. Type: Duplex Receptacle; NEMA 5-15R and NEMA 5-20R.

8. PlugTail Devices - Hospital Grade Isolated Ground Surge Protective Outlets:a. General: UL Listed, File Number E140596, Standard UL498, Attachment Plugs

and Receptacles UL1449 Transient Voltage Surge Suppressor. Federal

16000-22

Page 23:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

Specification WC596. CSA Certified, File Number LR16063, Standard CSA-C22.2 No. 42, ANSI/EEE C62.41 (Formerly IEEE 587), ANSI/IEEE C62.45 Installation Categories "A" (Ring Wave) "B" (Unidirectional Impulse). Complies with NEC 410-56(c) and 250-74 exception 4. Conforms to NEMA WD-1 and WD-6.

b. Grade: Hospital Grade 15 and 20 amp, 125 VAC. 2 Pole, 3 Wire Grounding.c. Series: PTIG8200SP and PTIG8300SP as manufactured by Pass and

Seymour.d. Connectors: PlugTail Connector in stripped 6 inches (152 mm) solid or

stranded.e. Type: Duplex Receptacle; NEMA 5-15R and NEMA 5-20R.

9. PlugTail Devices - Extra Heavy-Duty Hospital Grade Surge Protective Outlets:a. General: UL Listed, File Number E140596, Standard UL498, Attachment Plugs

and Receptacles UL1449 Transient Voltage Surge Suppressor. Federal Specification WC596. CSA Certified, File Number LR16063, Standard CSA-C22.2 No. 42, ANSI/EEE C62.41 (Formerly IEEE 587), ANSI/IEEE C62.45 Installation Categories "A" (Ring Wave) "B" (Unidirectional Impulse). Complies with NEC 410-56(c) and 250-74 exception 4. Conforms to NEMA WD-1 and WD-6.

b. Grade: Hospital Grade 15 and 20 amp, 125 VAC. 2 Pole, 3 Wire Grounding.c. Series: PT8200SP and PT8300SP as manufactured by Pass and Seymour.d. Connectors: PlugTail Connector in stripped 6 inches (152 mm) solid or

stranded.e. Type: Duplex Receptacle; NEMA 5-15R and NEMA 5-20R.

10. PlugTail Devices - Extra Heavy-Duty Surge Protective Outlets:a. General: cULus Listed, File Number E140596, Standard UL498. Federal

Specification WC596.b. Grade: Specification Grade 15 and 20 amp, 125 VAC. 2 Pole, 3 Wire

Grounding.c. Series: PT5262SP and PT5362SP as manufactured by Pass and Seymour.d. Connectors: PlugTail Connector in stripped 6 inches (152 mm) solid or

stranded.e. Type: Duplex Receptacle; NEMA 5-15R and NEMA 5-20R.

11. PlugTail Devices - Isolated Ground Surge Protective Outlets:a. General: UL Listed, File Number E140596, Standard UL498, Attachment Plugs

and Receptacles UL1449 Transient Voltage Surge Suppressor. Federal Specification WC596. CSA Certified, File Number LR16063, Standard CSA-C22.2 No. 42, ANSI/EEE C62.41 (Formerly IEEE 587), ANSI/IEEE C62.45 Installation Categories "A" (Ring Wave) "B" (Unidirectional Impulse). Complies with NEC 410-56(c) and 250-74 exception 4. Conforms to NEMA WD-1 and WD-6.

b. Grade: Specification Grade 15 and 20 amp, 125 VAC. 2 Pole, 3 Wire Grounding.

c. Series: PTIG5262SP and PTIG5362SP as manufactured by Pass and Seymour.

d. Connectors: PlugTail Connector in stripped 6 inches (152 mm) solid or stranded.

e. Type: Duplex Receptacle; NEMA 5-15R and NEMA 5-20R.12. PlugTail Devices - Tamper-Resistant Surge Protective Outlets:

a. General: UL Listed, File Number E140596, Standard UL498, Attachment Plugs and Receptacles UL1449 Transient Voltage Surge Suppressor. Federal Specification WC596. CSA Certified, File Number LR16063, Standard CSA-C22.2 No. 42, ANSI/EEE C62.41 (Formerly IEEE 587), ANSI/IEEE C62.45 Installation Categories "A" (Ring Wave) "B" (Unidirectional Impulse). Complies with NEC 410-56(c) and 250-74 exception 4. Conforms to NEMA WD-1 and WD-6.

16000-23

Page 24:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

b. Grade: Specification Grade 15 and 20 amp, 125 VAC. 2 Pole, 3 Wire Grounding.

c. Series: PTTR5262SP and PTTR5362SP as manufactured by Pass and Seymour.

d. Connectors: PlugTail Connector in stripped 6 inches (152 mm) solid or stranded.

e. Type: Duplex Receptacle; NEMA 5-15R and NEMA 5-20R.13. PlugTail Devices - Split Circuit Outlets:

a. General: cULus Listed, File Number E140596, Standard UL498. Federal Specification WC596. Conforms to NEMA WD-1 and WD-6.

b. Grade: Specification Grade 15 and 20 amp, 125 VAC.c. Series: PT5262SC and PT5362SC as manufactured by Pass and Seymour.d. Connectors: PlugTail Connector in stripped 6 inches (152 mm) solid or

stranded.e. Type: Duplex Receptacle; NEMA 5-15R and NEMA 5-20R.

14. PlugTail Devices - Tamper Resistant Outlets:a. General: cULus Listed, File Number E140596, Standard UL498. Federal

Specification WC596. Conforms to NEMA WD-1 and WD-6.b. Grade: Specification Grade 15 and 20 amp, 125 VAC.c. Tamper Resistant Series: PTTR5262 and PTTR5362 as manufactured by Pass

and Seymour.d. Tamper Resistant/ Split Circuit Series: PTTR5262SC and PTTR5362SC as

manufactured by Pass and Seymour.e. Connectors: PlugTail Connector in stripped 6 inches (152 mm) solid or

stranded.f. Type: Duplex Receptacle; NEMA 5-15R and NEMA 5-20R.

15. PlugTail Devices - GFCI:a. General: cULus Listed File Number E42190 and E140596, Standard UL498

Attachment Plugs and Receptacles, UL943 GFCIs. Federal Specification WC596, Hospital Grade. Standard CSA C22.2 No. 42 General Use. Receptacles, CSA C22.2 No. 144 GFCIs. Conforms to NEMA WD-1 and WD-6.

b. Grade: Hospital Grade 15 and 20 amp, 125 VAC.c. Series: PT15 and PT20 as manufactured by Pass and Seymour.d. Connectors: PlugTail Connector in stripped 6 inches (152 mm) solid or

stranded.e. Type: GFCI; NEMA 5-15R and NEMA 5-20R.f. Type: GFCI Tamper Resistant (TR); NEMA 5-15R and NEMA 5-20R.g. Type: GFCI Tamper Nightlight (NTL) + Resistant (TR); NEMA 5-15R and

NEMA 5-20R.h. Supplied with TP26 Decorator nylon wall plate.

16. PlugTail Devices - GFCI:a. General: cULus Listed File Number E42190 and E140596, Standard UL498

Attachment Plugs and Receptacles, UL943 GFCIs. Federal Specification WC596, Hospital Grade. Standard CSA C22.2 No. 42 General Use Receptacles, CSA C22.2 No. 144 GFCIs. Conforms to NEMA WD-1 and WD-6.

b. Grade: Specification Grade 15 and 20 amp, 125 VAC.c. Series: PT15 and PT20 as manufactured by Pass and Seymour.d. Connectors: PlugTail Connector in stripped 6 inches (152 mm) solid or

stranded.e. Type: GFCI; NEMA 5-15R and NEMA 5-20R.f. Type: GFCI Tamper Resistant (TR); NEMA 5-15R and NEMA 5-20R.g. Type: GFCI Tamper Nightlight (NTL) + Resistant (TR); NEMA 5-15R and

NEMA 5-20R.h. Supplied with TP26 Decorator nylon wall plate.

C. Plug Load Control Devices / Decorative Receptacle:

16000-24

Page 25:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

1. General: UL Listed, File Number E140596, Standard UL498, Fed Spec WC596 , CSA C22.2 No. 42, CSA/CUL approved, File Number LR16063, Standard CSA-C22.2 No. 42.

2. Controlled receptacle marking is NEMA-approved and compliant with 2014 NEC.3. Grade: 15 and 20 amp, 125 VAC.4. Split Circuit Series: 26252CH, 26352CH as manufactured by Pass and Seymour.5. Dual Circuit Series: 26252CD, 26352CD as manufactured by Pass and Seymour.6. Type: Duplex Receptacle NEMA 5-15R and NEMA 5-20R.7. Color: Brown, Black, Ivory, Light Almond, Gray, Red, Green, White. Refer to Drawing

schedule.

D. Plug Load Control Devices / Receptacle:1. General: UL Listed, File Number E140596, Standard UL498, Fed Spec WC596,

CSAcertified File Number LR16063, Standard CSA-C22.2 No. 42. General Use Receptacles. Conforms to NEMA WD-1 and WD-6.

2. Controlled receptacle marking is NEMA-approved and compliant with 2014 NEC, CA Title 24, and ASHRAE Energy Efficiency Standard 90.1.

3. Grade: 15 and 20 amp, 125 VAC.4. Split Circuit Series: 5262CH, 5362CH as manufactured by Pass and Seymour.5. Dual Circuit Series: 5262CD, 5362CD as manufactured by Pass and Seymour.6. Type: Duplex Receptacle NEMA 5-15R and NEMA 5-20R.7. Color: Brown, Black, Ivory, Light Almond, Gray, Red, Green, White. Refer to Drawing

schedule.

E. Plug Load RF Control Devices / Receptacle:1. General: RF Receptacles: UL listed to Standards: 498B, 498, 244A, Fed Spec WC-

596. CSA C22.2 No. 42. Conforms to NEMA WD-1 and WD-6; Title 24 Compliant.2. RF Signal Pack: Transmitter in compliance with Part 15 of FCC Rules, Class B.

Tested to UL 244A.3. Controlled receptacle marking is NEMA-approved and compliant with 2014 NEC, CA

Title 24, and ASHRAE Energy Efficiency Standard 90.1.4. Grade: 15 and 20 amp, 125 VAC.5. Split Circuit Series: RF26252CH, RF26352CH as manufactured by Pass and

Seymour.6. Dual Circuit Series: RF26252CD, RF26352CD as manufactured by Pass and

Seymour.7. Type: Duplex Receptacle NEMA 5-15R and NEMA 5-20R.8. Color: Brown, Black, Ivory, Light Almond, Gray, Green, White. Refer to Drawing

schedule.9. RF Signal Pack (RFP) and 24 VDC power pack (PWP120277).

F. USB Charging Devices:1. Product: Quad USB Model TM8USB4 as manufactured by Pass and Seymour.

a. Voltage: 15 A and 20 A 125 VAC.b. Charging Capacity: 4.2 amps.c. Description: Four 5-volt DC USB ports that work with USB 2.0 & 3.0 compatible

devices.d. Color: Black, Ivory, Light Almond, Nickel, White. Refer to Drawing schedule.

2. Product: USB Duplex Receptacle:a. Voltage: 15 A and 20 A 125 VAC.b. Grade: UL Federal Specification - Tamper Resistant.c. Compliant: cULus Listed, UL Fed Spec Listed. Complies with test requirements

UL 498, UL 1310, Fed Spec WC596 , CSA C22.2 No. 42, CSA C22.2 No. 223.d. Series: TR5262USB and TR5362USB as manufactured by Pass and Seymour.e. Charging Capacity: 3.1 amps.f. Description: USB charging capability. Combination AC duplex receptacles

16000-25

Page 26:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

include two 5-volt DC USB ports that work with USB 2.0 & 3.0 compatible devices.

g. Color: Brown, Black, Ivory, Light Almond, Nickel-plated, Gray, Red, Green, White. Refer to Drawing schedule.

3. Product: Decorator Duplex USB Chargera. Voltage: 15 A 125 VAC.b. Compliant: cULus listed. Complies with test requirements UL 498, UL 1310,

CSA C22.2 No. 42, CSA C22.2 No. 223.c. Model: TM826USB as manufactured by Pass and Seymour.d. Charging Capacity: 3.1 amps.e. Description: USB charging capability. Combination AC duplex receptacles

include two 5-volt DC USB ports that work with USB 2.0 & 3.0 compatible devices.

f. Color: Black, Ivory, Light Almond, Nickel-plated, White. Refer to Drawing schedule.

G. Dimmers:1. Product: Radiant Tru-Universal Dimmer as manufactured by Legrand.

a. Description: Self-calibrating technology automatically sets the minimum voltage of the lamp. Combines On/Off Decorator switch with separate slider for dimming control. Green White LED glows when off to make dimmer easy to find in the dark.

b. Rating: Incandescent, Halogen & ELV: 700W, MLV: 50VA, LED/CFL: 450W (not compatible with 0-10V LED drivers), EFL: 5.5A.

c. Compliant: cULus Listed.d. Voltage: 120VAC, 60 HZ.e. Preset, Single Pole and 3-Way.

2. Product: Titan Series Lighting and Fan Controls as manufactured by Pass and Seymour.a. Description: Trim potentiometer to adjust minimum light level to account for

variations in electronic dimmable fluorescent ballasts. Built-in label holder.b. Compliant: cULus Listed, File Number E95219 Standard UL1472 Solid State

Dimming Controls, Standard C22.2. No. 184-1; File Number E109655 Standard UL1917 Solid State Fan Controls, Standard C22.2 No. 156. Conforms to NEMA WD-1 and WD-6. California Title 24 Compliant.

c. 2 Wire Fluorescent:1) Device: CDFB5* 2 Wire, Electronic, Single Pole, Slide-to-OFF 5A, 120V

Narrow.2) Device: CDFB8* 8A, 120V Narrow.3) Device: CDFB10* 10A, 120V Wide.4) Device: CDFB16* 16A, 120V Wide.5) Device: PCDFB7277* 7A, 277V Wide.6) Device: CDFB10-277* 10A, 277V Wide.7) Device: CDFB53P* 2 Wire, Electronic, Single Pole/3-Way, Preset 5A,

120V Narrow.8) Device: CDFB83P* 8A, 120V Narrow.9) Device: CDFB103P* 10A, 120V Wide.10) Device: CDFB163P* 16A, 120V Wide.11) Device: CDFB73P277* 7A, 277V Wide.12) Device: CDFB103P277* 10A, 277V Wide.

d. 3 Wire Fluorescent:1) Device: CD3FB16* 3 Wire, Electronic, Single Pole, Slide-to-OFF 16A,

120V Narrow.2) Device: CD3FB10277* 10A, 277V Narrow.3) Device: CD3FB163P* 3 Wire, Electronic, Single Pole/3-Way, Preset 16A,

120V Narrow.

16000-26

Page 27:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

4) Device: CD3FB103P277* 10A, 277V Wide.e. 4 Wire Fluorescent: Requires PWP120277 Power Pack.

1) Device: CD4FB* 4 Wire, Electronic, Single Pole, Slide-to-OFF 24VDC Narrow.

2) Device: CD4FB3P* 4 Wire, Electronic, Single Pole/3-Way, Preset 24VDC Narrow.

f. Adaptor Kit:1) Device: CDADAPTORKIT* Decorator Device Adaptor Kit - Narrow.

g. *Color Designation: I Ivory, - Brown, BK Black, W White, GRY Gray, LA Light Almond.

3. Product: Titan Series Lighting and Fan Controls as manufactured by Pass and Seymour.a. Description: Incandescent/Magnetic Low Voltage/Fan Control. adjustable limit

control in incandescent dimmers saves energy and extends lamp life - reduces maximum output by up to 10 percent.. Built-in label holder.

b. Compliant: cULus Listed, File Number E95219 Standard UL1472 Solid State Dimming Controls, Standard C22.2. No. 184-1; File Number E109655 Standard UL1917 Solid State Fan Controls, Standard C22.2 No. 156. Conforms to NEMA WD-1 and WD-6. California Title 24 Compliant.

c. Incandescent:1) CD700* Single Pole, Slide-to-Off 700W Narrow2) CD1100* 1100W Narrow3) CD1600* 1600W Wide4) CD2000* 2000W Wide5) PCD703-P* Single Pole/3-Way, Preset 700W Narrow6) CD1103-P* 1100W Narrow7) CD1603-P* 1600W Wide8) CD2003-P* 2000W Wide

d. Magnetic Low Voltage:1) CDLV700-* Single Pole, Slide-to-Off 700VA Narrow2) CDLV1100-* 1100VA Narrow3) CDLV1600-* 1600VA Wide4) CDLV703-P* Single Pole/3-Way, Preset 700VA Narrow5) CDLV1103-P* 1100VA Narrow6) CDLV1603-P* 1600VA Wide

e. Fan Speed Control:1) CDSC6-* Variable Speed 6A Narrow2) CDSC12-* 12A Wide3) CDDH16-* Dehummer, 4-Speed 1.6A Narrow

f. Adaptor Kit:1) CDADAPTORKIT* Decorator Device Adaptor Kit - Narrow

g. *Color Designation: I Ivory, - Brown, BK Black, W White, GRY Gray, LA Light Almond.

H. Recessed Television Box:1. Product: Model TV2MW - New Work Metal Television Box 2 Gang.2. Compliant: cUlus listed. Low voltage and line voltage partitioning.3. Application: Designed to provide a snug-to-wall placement for new-work applications

in the hospitality, education, commercial, and residential environments.4. Construction: Factory-assembled steel containing integral 35 cubic inch electrical box.

Provided with an adjustable trim ring that accommodates various thicknesses of wall board. Devices not included.

2.6 LIGHTING CONTROLS

A. System Description & Operation:

16000-27

Page 28:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

1. The Lighting Control and Automation system as defined under this section covers the following equipment:a. Digital Occupancy Sensors - Self-configuring, digitally addressable and

calibrated occupancy sensors with LCD display and two-way active infrared (IR) communications.

b. Digital Switches - Self-configuring, digitally addressable pushbutton on/off, dimming, and scene switches with two-way active infrared (IR) communications.

c. Handheld remotes for personal control - One-button dimming, two-button on/off, or five-button scene remotes provide control using infrared communications. Remote may be configured in the field to control selected loads or scenes without special tools.

d. Digital Daylighting Sensors - Single-zone closed loop, multi-zone open loop and single-zone dual-loop daylighting sensors with two-way active infrared (IR) communications can provide switching, bi-level, tri-level or dimming control for daylight harvesting.

e. Digital Room Controllers - Self-configuring, digitally addressable one, two or three relay plenum-rated controllers for on/off control. Selected models include 0-10 volt or line voltage forward phase control dimming outputs and integral current monitoring capabilities.

f. Digital Plug-Load Controllers - Self-configuring, digitally addressable, single relay, plenum-rated application-specific controllers. Selected models include integral current monitoring capabilities.

g. Configuration Tools - Handheld remote for room configuration and relay panel programming provides two way infrared (IR) communications to digital devices and allows complete configuration and reconfiguration of the device / room from up to 30 feet away. Unit to have Organic LED display, simple pushbutton interface, and allow bi-directional communication of room variables and occupancy sensor settings. Computer software also customizes room settings.

h. Digital Lighting Management (DLM) local network - Free topology, plug-in wiring system (Cat 5e) for power and data to room devices.

i. Digital Lighting Management (DLM) segment network - Linear topology, BACnet MS/TP network (1.5 twisted pair, shielded,) to connect multiple DLM local networks for centralized control

j. Network Bridge - provides BACnet MS/TP-compliant digital networked communication between rooms, panels and the Segment Manager or building automation system (BAS) and automatically creates BACnet objects representative of connected devices.

k. Segment Manager - provides web browser-based user interface for system control, scheduling, power monitoring, room device parameter administration and reporting.

l. Programming and Configuration software - Optional PC-native application capable of accessing DLM control parameters within a room, for the local network, via a USB adapter, or globally, for many segment networks simultaneously, via BACnet/IP communication.

m. LMCP Digital Lighting Management Relay Panel - provides up to 8, 24, or 48 mechanically latching relays. Relays include a manual override and a single push-on connector for easy installation or removal from the panel. Panel accepts program changes from handheld configuration tool for date and time, location, holidays, event scheduling, button binding and group programming. Provides BACnet MS/TP-compliant digital networked communication between other lighting controls and/or building automation system (BAS).

n. Emergency Lighting Control Unit (ELCU) - allows a standard lighting control device to control emergency lighting in conjunction with normal lighting in any area within a building

16000-28

Page 29:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

B. Lighting Control Applications:1. Unless relevant provisions of the applicable local Energy Codes are more stringent,

provide a minimum application of lighting controls as follows:a. Space Control Requirements - Provide occupancy/vacancy sensors with

Manual- or Partial-ON functionality in all spaces except toilet rooms, storerooms, library stacks, or other applications where hands-free operation is desirable and Automatic-ON occupancy sensors are more appropriate. Provide Manual-ON occupancy/vacancy sensors for any enclosed office, conference room, meeting room, open plan system and training room. For spaces with multiple occupants, or where line-of-sight may be obscured, provide ceiling- or corner-mounted sensors and Manual-ON switches.

b. Bi-Level Lighting - Provide multi-level controls in all spaces except toilet rooms, storerooms, library stacks, or applications where variable dimming is used.

c. Task Lighting / Plug Loads - Provide automatic shut off of non-essential plug loads and task lighting in all spaces except toilet rooms and storerooms. Provide Automatic-ON of plug loads whenever spaces are occupied. For spaces with multiple occupants a single shut off consistent with the overhead lighting may be used for the area.

d. Daylit Areas - Provide daylight-responsive automatic control in all spaces (conditioned or unconditioned) where daylight contribution is available as defined by relevant local building energy code:1) All luminaires within code-defined daylight zones shall be controlled

separately from luminaires outside of daylit zones.2) Daytime setpoints for total ambient illumination (combined daylight and

electric light) levels that initiate dimming shall be programmed in compliance with relevant local building energy codes.

3) Multiple-leveled switched daylight harvesting controls may be utilized for areas marked on drawings.

4) Provide smooth and continuous daylight dimming for areas marked on drawings. Daylighting control system may be designed to turn off electric lighting when daylight is at or above required lighting levels, only if system functions to turn lamps back on at dimmed level, rather than turning full-on prior to dimming.

e. Conference, meeting, training, auditoriums, and multipurpose rooms shall have controls that allow for independent control of each local control zone. Rooms larger than 300 square feet (28 sq. m) shall instead have at least four pre-set lighting scenes unless otherwise specified. Occupancy / vacancy sensors shall be provided to extinguish all lighting in the space. Spaces with up to four moveable walls shall include controls that can be reconfigured when the room is partitioned.

C. Acceptable Manufacturer: Legrand, which is located at: 60 Woodlawn St.; West Hartford, CT 06110; Toll Free Tel: 877-295-3472; Tel: 860-233-6251; Fax: 860-232-2062; Email:request info ([email protected]); Web:http://www.legrand.us/wiremold.aspx1. System: Digital Lighting Management(DLM).

D. Digital Lighting Controls:1. Furnish the Manufacturer's system which accommodates the square-footage

coverage requirements for each area controlled, utilizing room controllers, digital occupancy sensors, switches, daylighting sensors and accessories which suit the lighting and electrical system parameters.

E. Digital Wall Switch Occupancy Sensors:1. Wallbox mounted passive infrared PIR or dual technology (passive infrared and

ultrasonic) digital occupancy sensor with 1 or 2 switch buttons.2. Digital Occupancy Sensors shall provide scrolling LCD display for digital calibration

16000-29

Page 30:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

and electronic documentation. Features include the following:a. Digital calibration and pushbutton configuration for the following variables:

1) Sensitivity - 0-100% in 10% increments2) Time delay - 1-30 minutes in 1 minute increments3) Test mode - Five second time delay4) Detection technology - PIR, Dual Technology activation and/or re-

activation.5) Walk-through mode6) Load parameters including Auto/Manual-ON, blink warning, and daylight

enable/disable when photo sensors are included in the DLM local network.

b. Programmable control functionality including:1) Each sensor may be programmed to control specific loads within a local

network.2) Sensor shall be capable of activating one of 16 user-definable lighting

scenes.3) Adjustable retrigger time period for manual-on loads. Load will retrigger

(turn on) automatically during the configurable period of time (default 10 seconds) after turning off.

4) On dual technology sensors, independently configurable trigger modes are available for both Normal (NH) and After Hours (AH) time periods. The retrigger mode can be programmed to use the following technologies:a) Ultrasonic and Passive Infraredb) Ultrasonic or Passive Infraredc) Ultrasonic onlyd) Passive Infrared only

c. Independently configurable sensitivity settings for passive infrared and ultrasonic technologies (on dual technology sensors) for both Normal (NH) and After Hour (AH) time periods.

d. Two RJ-45 ports for connection to DLM local network.e. Two-way infrared (IR) transceiver to allow remote programming through

handheld configuration tool and control by remote personal controls.f. Device Status LEDs including:

1) PIR detection2) Ultrasonic detection3) Configuration mode4) Load binding

g. Assignment of occupancy sensor to a specific load within the room without wiring or special tools.

h. Assignment of local buttons to specific loads within the room without wiring or special tools

i. Manual override of controlled loads.j. All digital parameter data programmed into an individual wall switch sensor

shall be retained in non-volatile FLASH memory within the wall switch sensor itself. Memory shall have an expected life of no less than 10 years.

3. BACnet object information shall be available for the following objects:a. Detection state.b. Occupancy sensor time delay.c. Occupancy sensor sensitivity, PIR and Ultrasonic.d. Button state.e. Switch lock control.f. Switch lock status.

4. Units shall not have any dip switches or potentiometers for field settings.5. Multiple occupancy sensors may be installed in a room by simply connecting them to

the free topology DLM local network. No additional configuration will be required.

16000-30

Page 31:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

6. Two-button wall switch occupancy sensors, when connected to a single relay dimming room controller, shall operate in the following sequence as a factory default:a. Left button:

1) Press and release - Turn load on.2) Press and hold - Raise dimming load.

b. Right button:1) Press and release - Turn load off.2) Press and hold - Lower dimming load.

7. Low voltage momentary pushbuttons shall include the following features:a. Load/Scene Status LED on each switch button with the following

characteristics:1) Bi-level LED.2) Dim locator level indicates power to switch.3) Bright status level indicates that load or scene is active.

b. The following button attributes may be changed or selected using a wireless configuration tool:1) Load and Scene button function may be reconfigured for individual

buttons (from Load to Scene, and vice versa).2) Individual button function may be configured to Toggle, On only or Off

only.3) Individual scenes may be locked to prevent unauthorized change.4) Fade Up and Fade Down times for individual scenes may be adjusted

from 0 seconds to 18 hours.5) Ramp rate may be adjusted for each dimmer switch.6) Switch buttons may be bound to any load on a room controller and are

not load type dependent; each button may be bound to multiple loads.8. WattStopper Part Numbers: LMPW, LMDW. Available in white, light almond, ivory,

grey, red and black; compatible with wall plates with decorator opening.

F. Digital Wall and Ceiling Mounted Occupancy Sensor:1. Wall and ceiling mounted (to suit installation) passive infrared (PIR), ultrasonic or dual

technology digital (passive infrared and ultrasonic) occupancy sensor.2. Digital Occupancy Sensors shall provide graphic LCD display for digital calibration

and electronic documentation. Features include the following:a. Digital calibration and pushbutton configuration for the following variables:

1) Sensitivity - 0-100% in 10% increments.2) Time delay - 1-30 minutes in 1 minute increments.3) Test mode - Five second time delay.4) Detection technology - PIR, Ultrasonic or Dual Technology activation

and/or re-activation.5) Walk-through mode.6) Load parameters including Auto/Manual-ON, blink warning, and daylight

enable/disable when photo sensors are included in the DLM local network.

b. Programmable control functionality including:1) Each sensor may be programmed to control specific loads within a local

network.2) Sensor shall be capable of activating one of 16 user-definable lighting

scenes.3) Adjustable retrigger time period for manual-on loads. Load will retrigger

(turn on) automatically within a configurable period of time (default 10 seconds) after turning off.

4) On dual technology sensors, independently configurable trigger modes are available for both Normal (NH) and After Hours (AH) time periods. The retrigger mode can be programmed to use the following technologies:

16000-31

Page 32:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

a) Ultrasonic and Passive Infrared.b) Ultrasonic or Passive Infrared.c) Ultrasonic only.d) Passive Infrared only.

c. Independently configurable sensitivity settings for passive infrared and ultrasonic technologies (on dual technology sensors) for both Normal (NH) and After Hour (AH) time periods.

d. One or two RJ-45 port(s) for connection to DLM local network.e. Two-way infrared (IR) transceiver to allow remote programming through

handheld commissioning tool and control by remote personal controls.f. Device Status LEDs, which may be disabled for selected applications,

including:1) PIR detection.2) Ultrasonic detection.3) Configuration mode.4) Load binding.

g. Assignment of occupancy sensor to a specific load within the room without wiring or special tools.

h. Manual override of controlled loads.i. All digital parameter data programmed into an individual occupancy sensor

shall be retained in non-volatile FLASH memory within the sensor itself. Memory shall have an expected life of no less than 10 years.

3. BACnet object information shall be available for the following objects:a. Detection state.b. Occupancy sensor time delay.c. Occupancy sensor sensitivity, PIR and Ultrasonic.

4. Units shall not have any dip switches or potentiometers for field settings.5. Multiple occupancy sensors may be installed in a room by simply connecting them to

the free topology DLM local network. No additional configuration will be required.6. WattStopper Product Numbers: LMPX, LMDX, LMPC, LMUC, LMDC.

G. Digital Wall Switches:1. Low voltage momentary pushbutton switches in 1, 2, 3, 4, 5 and 8 button

configuration. Wall switches shall include the following features:a. Two-way infrared (IR) transceiver for use with personal and configuration

remote controls.b. Removable buttons for field replacement with engraved buttons and/or

alternate color buttons. Button replacement may be completed without removing the switch from the wall.

c. Configuration LED on each switch that blinks to indicate data transmission.d. Load/Scene Status LED on each switch button with the following

characteristics:1) Bi-level LED.2) Dim locator level indicates power to switch.3) Bright status level indicates that load or scene is active.

e. Dimming switches shall include seven bi-level LEDs to indicate load levels using 14 steps.

f. Programmable control functionality including:1) Button priority may be configured to any BACnet priority level, from 1-16,

corresponding to networked operation allowing local actions to utilize life safety priority.

2) Scene patterns may be saved to any button other than dimming rockers. Once set, buttons may be digitally locked to prevent overwriting of the preset levels.

g. All digital parameter data programmed into an individual wall switch shall be retained in non-volatile FLASH memory within the wall switch itself. Memory

16000-32

Page 33:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

shall have an expected life of no less than 10 years.2. BACnet object information shall be available for the following objects:

a. Button state.b. Switch lock control.c. Switch lock status.

3. Two RJ-45 ports for connection to DLM local network.4. Multiple digital wall switches may be installed in a room by simply connecting them to

the free topology DLM local network. No additional configuration shall be required to achieve single-pole, three-way switching.

5. The following switch attributes may be changed or selected using a wireless configuration tool:a. Load and Scene button function may be reconfigured for individual buttons

(from Load to Scene, and vice versa).b. Individual button function may be configured to Toggle, On only or Off only.c. Individual scenes may be locked to prevent unauthorized change.d. Fade Up and Fade Down times for individual scenes may be adjusted from 0

seconds to 18 hours.e. Ramp rate may be adjusted for each dimmer switch.f. Switch buttons may be bound to any load on a room controller and are not load

type dependant; each button may be bound to multiple loads.6. WattStopper Product Numbers: LMSW-101, LMSW-102, LMSW-103, LMSW-104,

LMSW-105, LMSW-108, LMDM-101.7. Available in white, light almond, ivory, grey, red and black; compatible with wall plates

with decorator opening.

H. Handheld Remote Controls:1. Battery-operated handheld devices in 1, 2 and 5 button configurations for remote

switching or dimming control. Remote controls shall include the following features:a. Two-way infrared (IR) transceiver for line of sight communication with DLM

local network within up to 30 feet (9144 mm).b. LED on each button confirms button press.c. Load buttons may be bound to any load on a room controller and are not load

type dependant; each button may be bound to multiple loads.d. Inactivity timeout to save battery life.

2. A wall mount holster and mounting hardware shall be included with each remote control.

3. WattStopper Part Numbers: LMRH-101, LMRH-102, LMRH-105.

I. Digital Partition Controls:1. Partition controls shall enable manual or automatic coordination of lighting controls in

flexible spaces with up to four moveable walls by reconfiguring the connected digital switches and occupancy sensors.

2. Four-button low voltage pushbutton switch for manual control.a. Two-way infrared (IR) transceiver for use with configuration remote control.b. Removable buttons for field replacement with engraved buttons and/or

alternate color buttons. Button replacement may be completed without removing the switch from the wall.

c. Configuration LED on each switch that blinks to indicate data transmission.d. Each button represents one wall; Green button LED indicates status.e. Two RJ-45 ports for connection to DLM local network.f. WattStopper part number: LMPS-104. Available in white, light almond, ivory,

grey and black; compatible with wall plates with decorator opening.3. Contact closure interface for automatic control via input from limit switches on

movable walls (by others).a. Operates on Class 2 power supplied by DLM local network.b. Includes 24VDC output and four input terminals for maintained third party

16000-33

Page 34:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

contract closure inputs.1) Input max. sink/source current: 1-5mA.2) Logic input signal voltage High: > 18VDC.3) Logic input signal voltage Low: < 2VDC.

c. Four status LEDs under hinged cover indicate if walls are open or closed; supports LMPS-104 as remote status indicator.

d. Two RJ-45 ports for connection to DLM local network.e. WattStopper Part Number: LMIO-102.

J. Digital Daylighting Sensors:1. Digital daylighting sensors shall work with room controllers to provide automatic

switching, bi-level, or tri-level or dimming daylight harvesting capabilities for any load type connected to a room controller. Daylighting sensors shall be interchangeable without the need for rewiring.a. Closed loop sensors measure the ambient light in the space and control a

single lighting zone.b. Open loop sensors measure incoming daylight in the space, and are capable of

controlling up to three lighting zones.c. Dual loop sensors measure both ambient and incoming daylight in the space to

insure that proper light levels are maintained as changes to reflective materials are made in a single zone.

2. Digital daylighting sensors shall include the following features:a. The sensor's internal photodiode shall only measure light waves within the

visible spectrum. The photodiode's spectral response curve shall closely match the entire photopic curve. The photodiode shall not measure energy in either the ultraviolet or infrared spectrums. The photocell shall have a sensitivity of less than 5% for any wavelengths less than 400 nanometers or greater than 700 nanometers.

b. Sensor light level range shall be from 1-6,553 foot-candles (fc).c. The capability of ON/OFF, bi-level or tri-level switching, or dimming, for each

controlled zone, depending on the selection of room controller(s) and load binding to room controller(s).

d. For switching daylight harvesting, the photosensor shall provide a field-selectable deadband, or a separation, between the "ON Setpoint" and the "OFF Setpoint" that will prevent the lights from cycling excessively after they turn off.

e. For dimming daylight harvesting, the photosensor shall provide the option, when the daylight contribution is sufficient, of turning lights off or dimming lights to a field-selectable minimum level.

f. Photosensors shall have a digital, independently configurable fade rate for both increasing and decreasing light level in units of percent per second.

g. Photosensors shall provide adjustable cut-off time. Cut-off time is defined by the number of selected minutes the load is at the minimum output before the load turns off. Selectable range between 0-240 minutes including option to never cut-off.

h. Optional wall switch override shall allow occupants to reduce lighting level to increase energy savings or, if permitted by system administrator, raise lighting levels for a selectable period of time or cycle of occupancy.

i. Integral infrared (IR) transceiver for configuration and/or commissioning with a handheld configuration tool, to transmit detected light level to wireless configuration tool, and for communication with personal remote controls.

j. Configuration LED status light on device that blinks to indicate data transmission.

k. Status LED indicates test mode, override mode and load binding.l. Recessed switch on device to turn controlled load(s) ON and OFF.m. BACnet object information shall be available for the following daylighting sensor

objects, based on the specific photocell's settings:

16000-34

Page 35:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

1) Light level2) Day and night set points.3) Off time delay.4) On and off set point.5) Up to three zone set points.6) Operating mode - on/off, bi-level, tri-level or dimming.

n. One RJ-45 port for connection to DLM local network.o. A choice of accessories to accommodate multiple mounting methods and

building materials. The photo sensors may be mounted on a ceiling tile, skylight light well, suspended lighting fixture or back box. Standard tube photo sensors accommodate mounting materials from 0-0.62" thickness (LMLS-400, LMLS-500). Extended tube photo sensors accommodate mounting materials from 0.62"-1.25" thickness (LMLS-400-L, LMLS-500-L). Mounting brackets are compatible with J boxes (LMLS-MB1) and wall mounting (LMLS-MB2). LMLS-600 photosensor to be mounted on included bracket below skylight well.

p. Any load or group of loads in the room can be assigned to a daylighting zoneq. Each load within a daylighting zone can be individually enabled or disabled for

discrete control (load independence).r. All digital parameter data programmed into a photosensor shall be retained in

non-volatile FLASH memory within the photosensor itself. Memory shall have an expected life of no less than 10 years.

3. Closed loop digital photo sensors shall include the following additional features:a. An internal photodiode that measures light in a 100-degree angle, cutting off

the unwanted light from bright sources outside of this cone.b. Automatic self-calibration, initiated from the photosensor, a wireless

configuration tool or a PC with appropriate software.c. Automatically establishes application-specific set points following self-

calibration. For switching operation, an adequate deadband between the ON and OFF set points shall prevent the lights from cycling; for dimming operation a sliding setpoint control algorithm with separate Day and Night set points shall prevent abrupt ramping of loads.

d. WattStopper Product Number: LMLS-400, LMLS-400-L.4. Open loop digital photo sensors shall include the following additional features:

a. An internal photodiode that measures light in a 60-degree angle cutting off the unwanted light from the interior of the room.

b. Automatically establishes application-specific set points following manual calibration using a wireless configuration tool or a PC with appropriate software. For switching operation, an adequate deadband between the ON and OFF set points for each zone shall prevent the lights from cycling; for dimming operation, a proportional control algorithm shall maintain the design lighting level in each zone.

c. Each of the three discrete daylight zones can include any non overlapping group of loads in the room.

d. WattStopper Product Number: LMLS-500, LMLS-500-L.5. Dual loop digital photo sensors shall include the following additional features:

a. Close loop portion of dual loop device shall have an internal photodiode that measures light in a 100 degree angle, cutting off the unwanted light from sources outside of this con

b. Open loop portion of dual loop device shall have an internal photodiode that can measure light in a 60 degree angle, cutting off the unwanted light from the interior of the room.

c. Automatically establishes application-specific set-points following self-calibration. For switching operation, an adequate deadband between the ON and OFF set points shall prevent the lights from cycling; for dimming operation a sliding setpoint control algorithm with separate Day and Night set points shall prevent abrupt ramping of load.

16000-35

Page 36:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

d. Device shall reference closed loop photosensor information as a base line reference. The device shall be able to analyze the open loop photosensor information to determine if an adjustment in light levels is required.

e. Device shall be able to automatically commission set points each night to provide adjustments to electrical lighting based on changes in overall lighting in the space due to changes in reflectance within the space or changes to daylight contribution based on seasonal changes.

f. Device shall include extendable mounting arm to properly position sensor within a skylight well.

g. WattStopper Product Number LMLS-600

K. Digital Room Controllers And Plug-Load Controllers1. Digital controllers for lighting and plug loads automatically bind the room loads to the

connected devices in the space without commissioning or the use of any tools. Room and plug load controllers shall be provided to match the room lighting and plug load control requirements. The controllers will be simple to install, and will not have dip switches or potentiometers, or require special configuration for standard Plug n' Go applications. The control units will include the following features:a. Automatic room configuration to the most energy-efficient sequence of

operation based upon the devices in the room.b. Simple replacement - Using the default automatic configuration capabilities, a

room controller may be replaced with an off-the-shelf.c. Multiple room controllers connected together in a local network shall

automatically prioritize each room controller, without requiring any configuration or setup, so that loads are sequentially assigned using room controller device ID's from highest to lowest.

d. Device Status LEDs to indicate:1) Data transmission.2) Device has power.3) Status for each load.4) Configuration status.

e. Quick installation features including:1) Standard junction box mounting.2) Quick low voltage connections using standard RJ-45 patch cable.

f. Based on individual configuration, each load shall be capable of the following behavior on power up following the loss of normal power:1) Turn on to 100%.2) Remain off.3) Turn on to last level.

g. Each load shall be configurable to operate in the following sequences based on occupancy:1) Auto-on/Auto-off (Follow on and off).2) Manual-on/Auto-off (Follow off only).

h. The polarity of each load output shall be reversible, via digital configuration, so that on is off and off is on.

i. BACnet object information shall be available for the following objects:1) Load status.2) Electrical current.3) Total watts per controller.4) Schedule state - normal or after-hours.5) Demand response control and cap level.6) Room occupancy status.7) Total room lighting and plug loads watts.8) Total room watts/sq ft.9) Force on/off all loads.

j. UL 2043 plenum rated.

16000-36

Page 37:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

k. Manual override and LED indication for each load.l. Dual voltage (120/277 VAC, 60 Hz), or 347 VAC, 60 Hz (selected models only).

120/277 volt models rated for 20A total load, derating to 16A required for some dimmed loads (forward phase dimming); 347 volt models rated for 15A total load; plug load controllers carry application-specific UL 20 rating for receptacle control.

m. Zero cross circuitry for each load.n. All digital parameter data programmed into an individual room controller or plug

load controller shall be retained in non-volatile FLASH memory within the controller itself. Memory shall have an expected life of no less than 10 years.

2. On/Off Room Controllers shall include:a. One or two relay configuration.b. Efficient 150 mA switching power supply.c. Three RJ-45 DLM local network ports with integral strain relief and dust cover.d. WattStopper product numbers: LMRC-101, LMRC-102.

3. On/Off/Dimming enhanced Room Controllers shall include:a. Real time current monitoring.b. Multiple relay configurations.

1) One, two or three relays (LMRC-21x series).2) One or two relays (LMRC-22x series).

c. Efficient 250 mA switching power supply.d. Four RJ-45 DLM local network ports with integral strain relief and dust cover.e. One Dimming Output Per Relay:

1) 0-10V Dimming - Where indicated, one 0-10 volt analog output per relay for control of compatible ballasts and LED drivers. The 0-10 volt output shall automatically open upon loss of power to the Room Controller to assure full light output from the controlled lighting. (LMRC-21x series).

2) Line Voltage, Forward Phase Dimming - Where indicated, one forward phase control line voltage dimming output per relay for control of compatible two-wire or three-wire ballasts, LED drivers, MLV, forward phase compatible ELV, neon/cold cathode and incandescent loads. (LMRC-22x series).

3) Each dimming output channel shall have an independently configurable minimum and maximum calibration trim level to set the dimming range to match the true dynamic range of the connected ballast or driver.

4) The LED level indicators on bound dimming switches shall utilize this new maximum and minimum trim.

5) Each dimming output channel shall have an independently configurable minimum and maximum trim level to set the dynamic range of the output within the new 0-100% dimming range defined by the minimum and maximum calibration trim.

6) Calibration and trim levels shall be set per output channel.7) Devices that set calibration or trim levels per controller are not

acceptable.8) All configuration shall be digital. Devices that set calibration or trim levels

per output channel via trim pots or dip-switches are not acceptable.f. Each load shall have an independently configurable preset on level for Normal

Hours and After Hours events to allow different dimmed levels to be established at the start of both Normal Hours and After Hours events.

g. Fade rates for dimming loads shall be specific to bound switch buttons, and the load shall maintain a default value for any bound buttons that do not specify a unique value.

h. The following dimming attributes may be changed or selected using a wireless configuration tool:1) Establish preset level for each load from 0-100%.2) Set high and low trim for each load.

16000-37

Page 38:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

3) Set lamp burn in time for each load up to 100 hours.i. Override button for each load provides the following functions:

1) Press and release for on/off control.2) Press and hold for dimming control.

j. WattStopper Product Numbers: LMRC-211, LRMC-212, LRMC-213, LMRC-221, LMRC-222

4. Plug Load Room Controllers Shall Include:a. One relay configuration with additional connection for un-switched load.b. Configurable additive time delay to extend plug load time delay beyond

occupancy sensor time delay (e.g. a 10 minute additive delay in a space with a 20 minute occupancy sensor delay ensures that plug loads turn off 30 minutes after the space is vacated).

c. Factory default operation is Auto-on/Auto-off, based on occupancyd. Real time current monitoring of both switched and un-switched load (LMPL-201

only)e. Efficient switching power supply

1) 150mA (LMPL-101).2) 250mA (LMPL-201).

f. RJ-45 DLM local network ports1) Three RJ-45 ports (LMPL-101).2) Four RJ-45 ports (LMPL-201).

g. WattStopper Product Numbers: LMPL-101, LMPL-201.

L. DLM Local Network (Room Network):1. The DLM local network is a free topology lighting control physical connection and

communication protocol designed to control a small area of a building.2. Features of the DLM local network include:

a. Plug n' Go automatic configuration and binding of occupancy sensors, switches and lighting loads to the most energy-efficient sequence of operation based upon the device attached.

b. Simple replacement of any device in the network with a standard off the shelf unit without requiring commissioning, configuration or setup.

c. Push n' Learn configuration to change the automatic configuration, including binding and load parameters without tools, using only the buttons on the digital devices in the local network.

d. Two-way infrared communications for control by handheld remotes, and configuration by a handheld tool including adjusting load parameters, sensor configuration and binding, within a line of sight of up to 30 feet (9144 mm) from a sensor, wall switch or IR receiver.

3. Digital room devices connect to the local network using pre-terminated Cat 5e cables with RJ-45 connectors, which provide both data and power to room devices. Systems that utilize RJ-45 patch cords but do not provide serial communication data from individual end devices are not acceptable.

4. If manufacture's pre-terminated Cat5e cables are not used for the installation, the contractor is responsible for testing each cable following installation and supplying manufacturer with test results.

5. WattStopper Product Number: LMRJ-Series.

M. DLM SEGMENT NETWORK (Room To Room Network):1. The segment network shall be a linear topology, BACnet-based MS/TP subnet to

connect DLM local networks (rooms) and LMCP relay panels for centralized control.a. Each connected DLM local network shall include a single network bridge

(LMBC-300), and the network bridge is the only room-based device that is connected to the segment network.

b. Network bridges, relay panels and segment managers shall include terminal blocks, with provisions for separate "in" and "out" terminations, for segment

16000-38

Page 39:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

network connections.c. The segment network shall utilize 1.5 twisted pair, shielded, cable supplied by

the lighting control manufacturer. The maximum cable run for each segment is 4,000 feet (1219 m). Conductor-to-conductor capacitance of the twisted pair shall be less than 30 pf/ft and have a characteristic impedance of 120 Ohms.

d. Network signal integrity requires that each conductor and ground wire be correctly terminated at every connected device.

e. Substitution of manufacturer-supplied cable shall be pre-approved: Manufacturer shall not certify network reliability, and reserves the right to void warranty, if non-approved cable is installed, and if terminations are not completed according to manufacturer's specific requirements.

f. Segment networks shall be capable of connecting to BACnet-compliant BAS (provided by others) either directly, via MS/TP, or through NB-ROUTERs, via BACnet/IP or BACnet/Ethernet. Systems whose room-connected network infrastructure require gateway devices to provide BACnet data to a BAS are unacceptable.

2. WattStopper Product Number: LM-MSTP, LM-MSTP-DB.

N. Configuration Tools1. A wireless configuration tool facilitates optional customization of DLM local networks

using two-way infrared communications, while PC software connects to each local network via a USB interface.

2. Features and functionality of the wireless configuration tool shall include but not be limited to:a. Two-way infrared (IR) communication with DLM IR-enabled devices within a

range of approximately 30 feet (9144 mm).b. High visibility organic LED (OLED) display, pushbutton user interface and

menu-driven operation.c. Shall be able to read and modify parameters for room controllers, occupancy

sensors, wall switches, daylighting sensors, network bridges and relay panels, and identify room devices by type and serial number.

d. Save up to eight occupancy sensor setting profiles, and apply profiles to selected sensors.

e. Temporarily adjust light level of any load(s) on the local network, and incorporate those levels in scene setting. Set room mode for testing of Normal Hours (NH) and After Hours (AH) parameter settings.

f. Adjust or fine-tune daylighting settings established during auto-configuration, and input light level data to complete configuration of open loop daylighting controls.

g. Set room mode for testing of Normal Hours (NH) and After Hours (AH) parameter settings.

h. Verify status of building level network devices.3. WattStopper Product Numbers: LMCT-100, LMCI-100/LMCS-100.

O. Network Bridge:1. The network bridge module connects a DLM local network to a BACnet-compliant

segment network for communication between rooms, relay panels and a segment manager or BAS. Each local network shall include a network bridge component to provide a connection to the local network room devices. The network bridge shall use industry standard BACnet MS/TP network communication and an optically isolated EIA/TIA RS-485 transceiver.a. The network bridge shall be provided as a separate module connected on the

local network through an available RJ-45 port.b. Provide Plug n' Go operation to automatically discover room devices connected

to the local network and make all device parameters visible to the segment manager via the segment network. No commissioning shall be required for set

16000-39

Page 40:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

up of the network bridge on the local network.c. The network bridge shall automatically create standard BACnet objects for

selected room device parameters to allow any BACnet-compliant BAS to include lighting control and power monitoring features as provided by the DLM room devices on each local network. BACnet objects will be created for the addition or replacement of any given in-room DLM device for the installed life of the system. Products requiring that an application-specific point database be loaded to create or map BACnet objects are not acceptable. Systems not capable of providing BACnet data for control devices via a dedicated BACnet Device ID and physical MS/TP termination per room are not acceptable. Standard BACnet objects shall be provided as follows:1) Read/write the normal or after hours schedule state for the room.2) Read the detection state of each occupancy sensor.3) Read the aggregate occupancy state of the room.4) Read/write the On/Off state of loads.5) Read/write the dimmed light level of loads.6) Read the button states of switches.7) Read total current in amps, and total power in watts through the room

controller.8) Read/write occupancy sensor time delay, PIR sensitivity and ultrasonic

sensitivity settings.9) Activate a preset scene for the room.10) Read/write daylight sensor fade time and day and night set points.11) Read the current light level, in foot candles, from interior and exterior

photo sensors and photocells.12) Set daylight sensor operating mode.13) Read/write wall switch lock status.14) Read watts per square foot for the entire controlled room.15) Write maximum light level per load for demand response mode.16) Read/write activation of demand response mode for the room.17) Activate/restore demand response mode for the room.

2. WattStopper Product Numbers: LMBC-300.

P. Segment Manager:1. For networked applications, the Digital Lighting Management system shall include at

least one segment manager to manage network communication. It shall be capable of serving up a graphical user interface via a standard web browser utilizing either unencrypted TCP/IP traffic via a configurable port (default is 80) or 256 bit AES encrypted SSL TCP/IP traffic via a configurable port (default is 443).

2. Each segment manager shall have integral support for at least three segment networks. Segment networks may alternately be connected to the segment manger via external routers and switches, using standard Ethernet structured wiring. Each router shall accommodate one segment network. Provide the quantity of routers and switches as shown on the plans.

3. Operational features of the Segment Manager shall include the following:a. Connection to PC or LAN via standard Ethernet TCP/IP via standard Ethernet

TCP/IP with the option to use SSL encrypted connections for all traffic.b. Easy to learn and use graphical user interface, compatible with Internet

Explorer 8, or equal browser. Shall not require installation of any lighting control software to an end-user PC.

c. Log in security capable of restricting some users to view-only or other limited operations.

d. Automatic discovery of DLM devices and relay panels on the segment network(s). Commissioning beyond activation of the discovery function shall not be required to provide communication, monitoring or control of all local networks and lighting control panels.

16000-40

Page 41:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

e. After discovery, all rooms and panels shall be presented in a standard navigation tree format. Selecting a device from the tree will allow the device settings and operational parameters to be viewed and changed by the user.

f. Ability to view and modify room device operational parameters. It shall be possible to set device parameters independently for normal hours and after hours operation including sensor time delays and sensitivities, and load response to sensor including Manual-On or Auto-On.

g. Ability to set up schedules for rooms and panels, view and override current status of panel channels and relays, and assign relays to groups. Schedules shall automatically set controlled zones or areas to either a normal hours or after hours mode of operation. Support for a minimum of 100 unique schedules, each with up to four time events per day. Support for annual schedules, holiday schedules and unique date-bound schedules.

h. Ability to group rooms and loads for common control by schedules, switches or network commands.

i. Ability to monitor connected load current and display power consumption for areas equipped with room controllers incorporating the integral current monitoring feature.

j. Provide capabilities for integration with a BAS via BACnet protocol. At a minimum, the following points shall be available to the BAS via BACnet IP connection to the segment manager: room occupancy state; room schedule mode; room switch lock control; individual occupancy sensor state; room lighting power; room plug-load power; load ON/OFF state; load dimming level; panel channel schedule state; panel relay state; and Segment Manager Group schedule state control.

k. The Segment Manager shall allow access and control of the overall system database via Native Niagara AX FOX connectivity. Systems that shall utilize a Tridium Niagara controller in addition to the programming, scheduling and configuration server are not acceptable.

4. Segment Manager shall support multiple DLM rooms as follows:a. Support up to 120 network bridges and 900 digital in-room devices (LMSM-3E).b. Support up to 300 network bridges and 2,200 digital in room devices,

connected via network routers and switches (LMSM-6E).5. WattStopper Product Numbers: LMSM-3E, LMSM-6E, NB-ROUTER, NB-SWITCH,

NB-SWITCH-8, NB-SWITCH-16.

Q. Programming, Configuration And Documentation Software:1. PC-native application for optional programming of detailed technician-level parameter

information for all DLM products, including all parameters not accessible via BACnet and the handled IR configuration tool. Software shall be capable of accessing room-level parameter information locally within the room when connected via the optional LMCI-100 USB programming adapter, or globally for many segment networks simultaneously utilizing standard BACnet/IP communication.a. Additional parameters exposed through this method include but are not limited

to:1) Occupancy sensor detection LED disable for performance and other

aesthetic spaces where blinking LEDs present a distraction.2) Six occupancy sensor action behaviors for each controlled load,

separately configurable for normal hours and after hours modes. Modes include: No Action, Follow Off Only, Follow On Only, Follow On and Off, Follow On Only with Override Time Delay, Follow Off Only with Blink Warn Grace Time, Follow On and Off with Blink Warn Grace Time.

3) Separate fade time adjustments per load for both normal and after hours from 0 - 4 hours.

4) Configurable occupancy sensor re-trigger grace period from 0 - 4 minutes separate for both normal hours and after hours.

16000-41

Page 42:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

5) Separate normal hours and after hours per-load button mode with modes including: Do nothing, on only, off only, on and off.

6) Load control polarity reversal so that on events turn loads off and vice versa.

7) Per-load DR (demand response) shed level in units of percent.8) Load output pulse mode in increments of 1second.9) Fade trip point for each load for normal hours and after hours that

establishes the dimmer command level at which a switched load closes its relay to allow for staggered On of switched loads in response to a dimmer.

b. Generation of reports at the whole file, partial file, or room level. Reports include but are not limited to:1) Device list report: All devices in a project listed by type.2) Load binding report: All load controller bindings showing interaction with

sensors, switches, and daylighting.3) BACnet points report: Per room Device ID report of the valid BACnet

points for a given site's BOM.4) Room summary report: Device manifest for each room, aggregated by

common BOM, showing basic sequence of operations.5) Device parameter report: Per-room lists of all configured parameters

accessible via hand held IR programmer for use with O&M documentation.

6) Scene report: All project scene pattern values not left at defaults (i.e. 1 = all loads 100%, 2 = all loads 75%, 3 = all loads 50%, 4 = all loads 25%, 5-16 = same as scene 1).

7) Occupancy sensor report: Basic settings including time delay and sensitivity(ies) for all occupancy sensors.

c. Network-wide programming of parameter data in a spreadsheet-like programming environment including but not limited to the following operations:1) Set, copy/paste an entire project site of sensor time delays.2) Set, copy/paste an entire project site of sensor sensitivity settings.3) Search based on room name and text labels.4) Filter by product type (i.e. LMRC-212) to allow parameter set by product.5) Filter by parameter value to search for product with specific

configurations.d. Network-wide firmware upgrading remotely via the BACnet/IP network.

1) Mass firmware update of entire rooms.2) Mass firmware update of specifically selected rooms or areas.3) Mass firmware upgrade of specific products.

2. WattStopper Product Number: LMCS-100, LMCI-100.

R. LMCP Lighting Control Panels:1. Provide lighting control panels in the locations and capacities as indicated on the

plans and schedules. Each panel shall be of modular construction and consist of the following components:a. Enclosure/Tub shall be NEMA 1, sized to accept an interior with 1 - 8 relays, 1 -

24 relays and 6 four-pole contactors, or 1 - 48 relays and 6 four-pole contactors.

b. Cover shall be configured for surface or flush wall mounting of the panel as indicated on the plans. The panel cover shall have a hinged and lockable door with restricted access to line voltage section of the panel.

c. Interior assembly shall be supplied as a factory assembled component specifically designed and listed for field installation. The interior construction shall provide total isolation of high voltage (Class 1) wiring from low voltage (Class 2) wiring within the assembled panel. The interior assembly shall include intelligence boards, power supply, DIN rails for mounting optional Class 2

16000-42

Page 43:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

control devices, and individually replaceable latching type relays. The panel interiors shall include the following features:1) Removable, plug-in terminal blocks with connections for all low voltage

terminations.2) Individual terminal block, override pushbutton, and LED status light for

each relay.3) Direct wired switch inputs associated with each relay shall support 2-wire

momentary switches only.4) Digital inputs (four RJ-45 jacks) shall support 1-, 2-, 3-, 4-, and 8-button

digital switches; digital IO modules capable of receiving 0-5V or 0-10V analog photocell inputs; digital IO modules capable of receiving momentary or maintained contact closure inputs or analog sensor inputs; digital daylighting sensors; and digital occupancy sensors. Inputs are divided into two separate digital networks, each capable of supplying 250mA to connected devices.

5) True relay state shall be indicated by the on-board LED and shall be available to external control devices and systems via BACnet.

6) Automatically sequenced operation of relays to reduce impact on the electrical distribution system when large loads are controlled simultaneously.

7) Group and pattern control of relays shall be provided through a simple keypad interface from a handheld IR programmer. Any set of relays can be associated with a group for direct on/off control or pattern (scene) control via a simple programming sequence using the relay override pushbuttons and LED displays for groups 1-8 or a handheld IR programmer for groups 1-99.

8) Relay group status for shall be provided through LED indicators for groups 1-8 and via BACnet for groups 1-99. A solid LED indicates that the last group action called for an ON state and relays in the group are on or in a mixed state.

9) Single-pole latching relays with modular plug-in design. Relays shall provide the following ratings and features:a) Electrical:

1) 30 amp ballast at 277V.2) 20 amp ballast at 347V.3) 20amp tungsten at 120V.4) 30 amp resistive at 347V.5) 1.5 HP motor at 120V.6) 14,000 amp short circuit current rating (SCCR) at 347V.7) Relays shall be specifically UL 20 listed for control of plug-

loads.b) Mechanical:

1) Replaceable, 1/2 inch (13 mm) KO mounting with removable Class 2 wire harness.

2) Actuator on relay housing provides manual override and visual status indication, accessible from Class 2 section of panel.

3) Dual line and load terminals each support two #14 - #12 solid or stranded conductors.

4) Tested to 300,000 mechanical on/off cycles.d. Isolated low voltage contacts provide for true relay status feedback and pilot

light indication.e. Power supply shall be a multi-voltage transformer assembly with rated power to

supply all electronics, occupancy sensors, switches, pilot lights, and photocells as necessary to meet the project requirements. Power supply to have internal over-current protection with automatic reset and metal oxide varistor protection.

16000-43

Page 44:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

f. Where indicated, lighting control panels designated for control of emergency lighting shall be provided with factory installed provision for automatic by pass of relays controlling emergency circuits upon loss of normal power. Panels shall be properly listed and labeled for use on emergency lighting circuits and shall meet the requirements of UL924 and NFPA 70 - Article 700.

g. Integral system clock shall provide scheduling capabilities for panel-only projects without DLM segment networks or BAS control.1) Each panel shall include digital clock capability able to issue system wide

automation commands to up to eleven other panels for a total of twelve networked lighting control panels. The clock shall provide capability for up to 254 independent schedule events per panel for each of the ninety-nine system wide channel groups.

2) The clock capability of each panel shall support the time-based energy saving requirements of applicable local energy codes.

3) The clock module shall provide astronomic capabilities, time delays, blink warning, daylight savings, and holiday functions and will include a battery back up for the clock function and program retention in non-volatile FLASH memory. Clocks that require multiple events to meet local code lighting shut off requirements shall not be allowed.

4) The clock capability of each panel shall operate on a basis of ON/OFF or Normal Hours/After Hours messages to automation groups that implement pre-configured control scenarios. Scenarios shall include:a) Scheduled ON / OFF.b) Manual ON / Scheduled OFF.c) Astro ON / OFF (or Photo ON / OFF).d) Astro and Schedule ON / OFF (or Photo and Schedule ON / OFF).

5) The user interface shall be a portable IR handheld remote control capable of programming any panel in the system (LMCT-100).

6) The clock capability of each panel shall employ non-volatile memory and shall retain user programming and time for a minimum of 10 years.

7) Schedules programmed into the clock of any one panel shall be capable of executing panel local schedule or Dark/Light (photocell or Astro) events for that panel in the event that global network communication is lost. Lighting control panels that are not capable of executing events independently of the global network shall not be acceptable.

h. The lighting control panel can operate as a stand-alone system, or can support schedule, group, and photocell control functions, as configured in a Segment Manager controller, via a segment network connection.

i. The lighting control panel shall support digital communications to facilitate the extension of control to include interoperation with building automation systems and other intelligent field devices. Digital communications shall be RS485 MS/TP-based using the BACnet protocol.1) The panel shall have provision for an individual BACnet device ID and

shall support the full 222 range (0 - 4,193,304). The device ID description property shall be writable via the network to allow unique identification of the lighting control panel on the network.

2) The panel shall support MS/TP MAC addresses in the range of 0 - 127 and baud rates of 9600k, 38400k, 76800k, and 115.2k bits per second.

3) Lighting control relays shall be controllable as binary output objects in the instance range of 1 - 64. The state of each relay shall be readable and writable by the BAS via the object present value property.

4) Lighting control relays shall report their true on/off state as binary input objects in the instance range of 1 - 64.

5) The 99 group Normal Hours/After Hours control objects associated with the panel shall be represented by binary value objects in the instance range of 201 - 299. The occupancy state of each channel group shall be

16000-44

Page 45:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

readable and writable by the BAS via the object present value property. Commanding 1 to a channel group will put all relays associated with the channel into the normal hours mode. Commanding 0 or NULL shall put the relays into the afterhours mode.

6) Setup and commissioning of the panel shall not require manufacturer-specific software or a computer. All configuration of the lighting control panel shall be performed using standard BACnet objects or via the handheld IR programming remote. Provide BACnet objects for panel setup and control as follows:a) Binary output objects in the instance range of 1 - 64 (one per

relay) for on/off control of relays.b) Binary value objects in the instance range of 1 - 99 (one per

channel) for normal hours/afterhours schedule control.c) Binary input objects in the instance range of 1 - 64 (one per relay)

for reading true on/off state of the relays.d) Analog value objects in the instance range of 101 - 199 (one per

channel group) shall assign a blink warn time value to each channel. A value of 5 shall activate the blink warn feature for the channel and set a 5-minute grace-time period. A value of 250 shall activate the sweep feature for the channel and enable the use of sweep type automatic wall switches.

7) The description property for all objects shall be writable via the network and shall be saved in non-volatile memory within the panel.

8) The BO and BV 1 - 99 objects shall support BACnet priority array with a relinquish default of off and after hours respectively. Prioritized writes to the channel BV objects shall propagate prioritized control to each member relay in a way analogous to the BACnet Channel object described in addendum aa. (http://www.bacnet.org/Addenda/Add-135-2010aa.pdf).

9) Panel-aggregate control of relay Force Off at priority 2 shall be available via a single BV5 object. Force On at priority 1 shall be available via a single BV4 object.

10) Lockout of all digital switch buttons connected to a given panel shall be command-able via a single BV2 object. The lock status of any connected switch station shall be represented as BV101-196.

j. WattStopper Product Number: LMCP8, LMCP24 or LMCP48.2. User Interface: Each lighting control panel system shall be supplied with at least one

handheld configuration tool (LMCT-100). As a remote programming interface the configuration tool shall allow setup, configuration, and diagnostics of the panel without the need for software or connection of a computer. The user interface shall have the following panel-specific functions as a minimum:a. Set network parameters including panel device ID, MS/TP MAC address, baud

rate and max master range.b. Relay Group creation of up to 99 groups. Group creation shall result in

programming of all seven key relay parameters for member relays. The seven parameters are as follows: After-hours Override Time Delay, Normal Hours Override Time Delay, Action on Transition to Normal Hours, Action on Transition to After Hours, Sensor Action During Normal Hours, Sensor Action During After Hours, Blink-Warn Time for After Hours.

c. Program up to 254 separate scheduled events. Events shall occur on seven day intervals with each day selectable as active or inactive, and shall be configurable as to whether the event is active on holidays. Holidays are also defined through the User Interface.

d. Program up to 32 separate Dark/Light events. Events shall have a selectable source as either calculated Astro with delay, or a digital IO module with an integral 0-5V or 0-10V analog photocell. Dark/Light events shall occur on seven

16000-45

Page 46:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

day intervals with each day selectable as active or inactive, and shall be configurable as to whether the event is active on holidays.

e. Button binding of digital switches to groups shall be accessible via the handheld IR remote and accomplished from the digital switch station.

f. Programming of panel location information shall be accomplished by the handheld IR remote and include at a minimum LAT, LON, DST zone, and an approximate city/state location.

g. An additional handheld IR remote may optionally be specified to be permanently mounted to the panel interior via a retractable anti-theft lanyard to allow for convenient programming of the panel while assuring that the handheld programmer is always present at that panel. An unlimited number of handheld IR remotes may also be purchased for facilities staff as determined by the end user's representative.

h. WattStopper Product Number: LMCT-100.

S. Emergency Lighting Control Devices:1. Emergency Lighting Control Unit - A UL 924 listed device that monitors a switched

circuit providing normal lighting to an area. The unit provides normal ON/OFF control of emergency lighting along with the normal lighting. Upon normal power failure the emergency lighting circuit will close, forcing the emergency lighting ON until normal power is restored. Features include:a. 120/277 volts, 50/60 Hz, 20 amp ballast rating.b. Push to test button.c. Auxiliary contact for remote test or fire alarm system interface.

2. WattStopper Product Numbers: ELCU-100, ELCU-200.

T. Contractor Installation and Services:1. Contractor to install all devices and wiring in a professional manner. All line voltage

connections to be tagged to indicate circuit and switched legs.2. Contractor to install all room/area devices using manufacturer's factory-tested Cat 5e

cable with pre-terminated RJ-45 connectors. If pre-terminated cable is not used for room/area wiring, the contractor is responsible for testing each field-terminated cable following installation, and shall supply the lighting controls manufacturer with test results. Contractor to install any room to room network devices using manufacturer-supplied LM-MSTP network wire. Network wire substitution is not permitted and may result in loss of product warranty per DLM SEGMENT NETWORK section of specification. Low voltage wiring topology shall comply with manufacturer's specifications. Contractor shall route network wiring as shown in submittal drawings as closely as possible, and shall document final wiring location, routing and topology on as built drawings.

3. Install the work of this Section in accordance with manufacturer's printed instructions unless otherwise indicated. Before start up, contractor shall test all devices to ensure proper communication.

4. Calibrate all sensor time delays and sensitivity to guarantee proper detection of occupants and energy savings.a. Adjust time delay so that controlled area remains lighted while occupied.

5. Provide written or computer-generated documentation on the configuration of the system including room by room description including:a. Sensor parameters, time delays, sensitivities, and daylighting set points.b. Sequence of operation, (e.g. manual ON, Auto OFF. etc.)c. Load Parameters (e.g. blink warning, etc.)

6. Post start-up tuning - After 30 days from occupancy contractor shall adjust sensor time delays and sensitivities to meet the Owner's requirements. Provide a detailed report to the Architect / Owner of post start-up activity.

2.7 UNDER-CABINET LIGHTING SYSTEMS

16000-46

Page 47:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

A. Under-cabinet lighting system: Modular, fully customizable system of components that can be either hard-wired or plugged into any home wiring configuration. Designed for use in kitchens, offices, hospitality, and healthcare applications.

B. Modular Tracks:1. 12 inches (305 mm) Modular Track: adorne Part No. APMT12TM2; 12 inches length

includes one outlet module and one blank module; capable of supporting up to two LED lights; provides 120V power via 15A outlet modules and 20A pass-through; module openings on 6 inches (152 mm) centers; outlets are tamper resistant and ETL Listed.

2. 18 inches (457 mm) Modular Track: adorne Part No. APMT18TM4; 18 inches length includes one outlet module and one blank module; capable of supporting up to two LED lights; provides 120V power via 15A outlet modules and 20A pass-through; module openings on 9 inches (229 mm) centers; outlets are tamper resistant and ETL Listed.

3. 27 inches (686 mm) Modular Track: adorne Part No. APMT27TM2; 27 inches length includes two outlet modules and one blank module; capable of supporting up to three LED lights; provides 120V power via 15A outlet modules and 20A pass-through; module openings on 9 inches (229 mm) centers; outlets are tamper resistant and ETL Listed.

4. Short Modular Track: adorne Part No. APST9TM1; for use with narrow single cabinets; back feed power from in-wall wiring; 10-1/4 inches (260 mm) length with end caps; tamper resistant; ETL Listed.

5. 18 inches (457 mm) Modular Track Extender: adorne Part No. APME18TM2; 18 inches length blank module enables a perfect fit in any room; cut to length (minimum of six inches (152 mm)); attach to end of modular track; does not contain any module openings; ETL Listed.

6. Modular Track Corner Connector: adorne Part No. APCCTM4; use with installations that include a right-angle corner to connect two modular tracks; allow 3 inches (76 mm) on each side for installations with corner connectors; ETL Listed.

C. Control Boxes:1. Control Box with Paddle Dimmer: adorne Part No. APCB1TM4; connects to existing

in-wall wiring; fits onto end of modular track, adding 5 inches (127 mm) onto system length; includes adorne™ Paddle Dimmer Part No. ADPD453LM2 rated for 450W CFL/LED; GFCI protection shall be provided at electrical panel; ETL Listed.

2. Control Box with Paddle Dimmer and 15A GFCI: adorne Part No. APCB2TM2; connects to existing in-wall wiring; fits onto end of modular track, adding 5-1/4 inches (133 mm) onto system length; includes adorne™ Paddle Dimmer Part No. ADPD453LM2 rated for 450W CFL/LED and 15A tamper-resistant GFCI outlet adorne™ Part No. AGFTR153M4; ETL Listed.

3. Plug-In Control Box: adorne Part No. APCB3TM4; snaps into any module opening on track and plugs into an existing outlet to provide system power; cord length of 24 inches (610 mm) can easily be shortened to match distance from outlet to modular track; ETL Listed.

4. One-Gang Control Box, No Devices: adorne Part No. APCB5TM1; connects to existing in-wall wiring; fits onto end of modular track, adding five inches (127 mm) onto system length; customizes with choice of adorne™ dimmers, switches, or outlets; ETL Listed.

5. Two-Gang Control Box, No Devices: adorne Part No. APCB4TM1; connects to existing in-wall wiring; fits onto end of modular track, adding 5-1/4 inches (133 mm) onto system length; customizes with choice of adorne™ dimmers, switches, or outlets; ETL Listed.

6. Direct Wire Connector: adorne Part No. APDWCTM1; enables direct wire feed of power from in-wall wiring, eliminating need for a control box; connector is 6 inches (152 mm) in length; ETL Listed.

16000-47

Page 48:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

D. LED Lights:1. LED Puck Light: adorne Part No. ALPKLEDTM4; 7 watts, 240 lumens; Correlated

Color Temperature - 3000 degrees Kelvin, Color Rendering Index - 95; can be paired with adorne™ Part No. ADPD453L CFL/LED Paddle Dimmer to enable dimming; ETL Listed.

2. LED Linear Light: adorne Part No. ALLNLEDTM4; 8 watts, 280 lumens; Correlated Color Temperature - 3000 degrees Kelvin, Color Rendering Index - 95; Energy Star Certified; can be paired with adorne™ Part No. ADPD453L CFL/LED Paddle Dimmer to enable dimming; ETL Listed.

3. Light Extender: adorne Part No. ALEXTLEDTM4; enables adorne™ LED lights to be mounted up to 22 inches (559 mm) from backsplash by extending cord length beyond default 11 inches (279 mm); ideal for corner cabinet installations; ETL Listed.

E. Modules and Accessories:1. 15A Outlet Module: adorne Part No. APTR15TM4; provides two power outlets by

snapping into any module opening; tamper-resistant outlet designed with patented shutter system; included with 12-inches (305 mm), 18-inches (457 mm), and 27-inches (686 mm) module tracks; rated 15A, 120V; ETL Listed.

2. USB Outlet Module: adorne Part No. APUSB3TM4; provides two USB charging ports for devices such as mobile phones and tablets by snapping into any module opening; does not include charging cable; rated 3.1A, 5V; ETL Listed.

3. Mobile Phone Cradle: adorne Part No. AAPCTM4; attaches anywhere along track to hold a mobile phone; use with USB outlet mobile while charging devices.

4. Tablet Cradle: adorne Part No. AATCTM4; attaches anywhere along track to hold a tablet; use with USB outlet mobile while charging devices.

5. Digital Music Kit: adorne Part No. AUDMTM1; includes two full range drivers; digital signal processing for full, rich sound; Bluetooth® wireless technology is A2DP compatible; also includes USB charging capability; ETL Listed.

F. Installation:1. Strictly comply with manufacturer's installation instructions and recommendations,

Legrand Document No. 1 010 776R1 05/13. Coordinate installation with adjacent work to ensure proper clearances and to prevent electrical hazards.

2. The Modular Track requires three separate circuits from the electrical service panel. The receptacle circuit, the lighting circuit, and an accessory circuit.a. The receptacle circuit: 20 amps, using number 12 wire, and GFCI protected.b. The lighting and accessory circuits: Minimum 15 amps each and using number

14 wire.3. Install under-cabinet lighting system at underside of wall-mounted cabinets and in

front of wall finishes, unless indicated otherwise.a. Do not install under-cabinet lighting system directly above any direct heat or

open flame source.b. Do not install under-cabinet lighting system in a high moisture content

environment.

2.8 COMMERCIAL FLOOR BOXES

A. Electrical Floor Boxes and Components: Comply with requirements of applicable local codes, NEC, UL, and NEMA Standards pertaining to floor boxes and components. Meet or exceed UL Fire Classification requirements, where scheduled or required, for recessed and flush style boxes. Listed and labeled in accordance with NFPA 70, Article 100.

B. Accessibility Compliance: Design device flange to meet ADA Accessibility Guidelines as to changes in floor and ground surface levels. Bevel flanges so the slope is no greater than 1:2.

C. Floor Boxes: 861 Series as manufactured by Legrand / Wiremold.1. Classification and Use: Floor boxes shall have been examined and tested by

16000-48

Page 49:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

Underwriters Laboratories Inc. to meet UL514A and UL514C and Canadian Standard C22.2 and bear the U.S. and Canadian UL Listing Mark. Floor boxes shall also have been tested by Underwriters Laboratories Inc. and classified for tile, terrazzo, and scrub water exclusion test for carpet and wood floors and bear the U.S. and Canadian UL Classification Mark.

2. Floor Boxes, General: 861 Series Floor Boxes for use in both raised and wood-constructed floors. Boxes shall be compatible with manufacturer's flush-style poke-thru cover assemblies in dedicated power, communication or pass-through versions. Boxes will also accept 895 and 896 Series Single Service Covers. Floor boxes bring power or communication services directly to the point-of-use for open space applications.

3. Raised Floor Boxes: 861 Series Floor Boxes; consisting of a die cast aluminum alloy frame, stamped spring steel retainer clip, and a disposable molded nylon pre-activation cover. Box shall be round in shape and available in a single-gang configuration. Minimum depth of deep boxes shall be 3-3/8 inches (85.7 mm). Provide box with three 1/2 inch (13 mm) trade size knockouts, two on the sides and one on the bottom. Spring steel retainer clip holds box in floor without additional fasteners.

4. Covers and Flanges: All floor box options shall accept brass, nonmetallic and single service flush flanges. Flanges shall mount directly to floor box and allow for various types of floor coverings to be used.a. Brass Covers: Brass flanges made of solid brass forgings. Each part shall have

a brushed appearance and be protected by a lacquer finish. Brass flanges shall be approved for carpet, wood, or tile floor applications. Brass flanges shall accommodate duplex and GFCI receptacles or communication cable pass-through services. The carpet flange shall be 5-1/2 inches (140 mm) and the tile flange shall be 4-1/4 inches (108 mm) in diameter.

b. Aluminum Covers: Aluminum flanges made from die-cast aluminum. Each part shall have a brushed appearance and be protected by a lacquer finish or powder-coated finish. Powder-coated aluminum flanges shall be available in black, brass, nickel, bronze, or gray colors. Aluminum flanges shall accommodate duplex and GFCI receptacles or communication cable pass-through services. Carpet flange shall be 5-1/2 inches (140 mm) and tile flange shall be 4-1/4 inches (108 mm) in diameter.

c. Nonmetallic Covers: Manufacture from polycarbonate material in black, brown, bronze or aluminum colors. Covers shall be approved for carpet, wood or tile floors. Covers shall accommodate duplex receptacles or allow for communication pass-through services. Flange shall be 5-1/2 inches (140 mm) in diameter.

d. Quad Power Activation Covers: Manufacture trim flange from die-cast aluminum alloy. Covers shall be capable of being powder-coated or plated. Coated finish to be textured, two-stage epoxy paint in gray, black, or ivory. Attach a gasket to underside of trim flange to maintain scrub water tightness. Trim flange shall also be available in a solid brass forging and die-cast brushed aluminum finish. Brass and aluminum finish shall have a lacquer sealant coating. The activation cover shall be 7 inches (178 mm) in diameter. The activation slide cover shall be 5 inches (127 mm) in diameter.1) Manufacture activation cover from textured polycarbonate or PVC in

black, gray, ivory or brass color. Slide holder assembly shall be flush with floor and provide "dead-front" protection that allows receptacle cover to snap back into place when receptacle is not in use. Attach a gasket to underside of cover assembly to maintain scrub water tightness by preventing water, dirt and debris from entering power compartment.

e. Communications Activation Cover: Manufacture trim flange from die-cast aluminum alloy. Covers shall be capable of being powder coated or plated. Coated finish to be textured, two-stage epoxy paint in gray, black, or ivory. Attach a gasket to underside of trim flange to maintain scrub water tightness.

16000-49

Page 50:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

Trim flange shall also be available in a solid brass forging and a die cast brush aluminum finish. Brass and aluminum finish shall have a lacquer sealant coating. The activation cover shall be 7 inches (178 mm) in diameter. The activation slide cover shall be 5 inches (127 mm) in diameter.1) Manufacture activation cover from textured polycarbonate or PVC in

black, gray, ivory or brass color. Slide holder assembly shall be flush with floor. Attach a gasket to underside of cover assembly to maintain scrub water tightness by preventing water, dirt and debris from entering communication compartments. The device shall also have accommodations for up to two (2) dual Category 6 modular inserts. Cover shall have individual slides that allow access to the communication connectors and will close over the connectors when not in use. Each activation cover shall also provide locations to adhere labels to identify communication circuits.

f. Furniture Feed Activation Cover: Manufacture trim flange from die-cast aluminum alloy. Covers shall be capable of being powder coated or plated. Coated finish is to be textured, two-stage epoxy paint in gray, black, or ivory. Attach a gasket to the underside of the trim flange to maintain scrub water tightness. Trim flange shall also be available in a solid brass forging and a die cast brush aluminum finish. Brass and aluminum finish shall have a lacquer sealant coating. The activation cover shall be seven (7) inches (178mm) in diameter. The activation slide cover shall be five (5) inches (127 mm) in diameter. Cover shall have two (2) 1/2-inch trade size conduit openings and one (1) 3/4-inch trade size conduit opening for feeding cables or wires through floor.

D. Floor Boxes: 880 Series as manufactured by Legrand / Wiremold.

E. Floor Boxes: 880W Series as manufactured by Legrand / Wiremold.1. Classification and Use: Floor boxes shall have been examined and tested by

Underwriters Laboratories Inc. to meet UL514A, UL514C, UL514D, and Canadian Standard C22.2 and bear the U.S. and Canadian UL Listing Mark. Floor boxes are approved for use in wood frame floor construction and meet and exceed the UL scrub water exclusion test.

2. Floor Boxes, General: One-, two-, or three-gang configurations. Boxes shall be rectangular in shape. Boxes shall consist of a stamped steel body, applicable stamped steel barriers, and stamped steel mounting brackets for flanges. Boxes shall have an overall depth of 3-7/16 inches (87 mm). Boxes shall provide a mounting mechanism to attach the floor box to the wood subfloor.

3. Floor Boxes for Wood Floors: 880W Series Wood Floor Boxes for use in wood-constructed floors. Boxes shall provide interface between power, communication, and/or audio/video services in a wood floor and workstation or activation location where power, communication, and/or audio/video device outlets are required. Boxes shall provide flush device outlets that will not obstruct the floor area.a. One-Gang Boxes: 4-15/16 inches (125 mm) W by 3-3/4 inches (95 mm) L.

Boxes shall provide for three 1/2-inch (12.7 mm) knockouts, five 3/4-inch (19.1 mm) knockouts, and two 1 inch (25 mm) knockouts to feed cabling to the floor box. Boxes shall provide a total of 53 cubic inches (869 ml) of Device Wiring Chamber volume.

b. Two-Gang Boxes: 4-15/16 inches (125 mm) W by 7-7/8 inches (200 mm) L. Boxes shall provide six 1/2 inch (12.7 mm) knockouts, eight 3/4 inch (19.1mm) knockouts, and two 1 inch (25 mm) knockouts to feed cabling to the floor box. Boxes shall provide a total of 117 cubic inches (1918 ml) of Device Wiring Chamber volume. Each box shall provide a total of 58 cubic inches (951 ml) of volume in one gang and 59 cubic inches (967 ml) of volume in the second gang.

16000-50

Page 51:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

c. Three-Gang Boxes: 4-15/16 inches (125 mm) W by 12 inches (305 mm) L. Boxes shall provide nine 1/2 inch (12.7 mm) knockouts, eleven 3/4 inch (19.1 mm) knockouts, and two 1 inch (25 mm) knockouts to feed cabling to the floor box. Boxes shall provide a total of 180 cubic inches (2951 ml) of Device Wiring Chamber volume. Each box shall provide a total of 56 cubic inches (918 ml) of volume in each outside gang and 68 cubic inches (1115 ml) of volume in the center gang.

4. Covers and Flanges:a. All floor box options shall accept brass, aluminum, and nonmetallic cover plates

and flanges. Flanges for brass, aluminum, and nonmetallic cover plates shall designed to install on one-, two-, or three-gang boxes. Aluminum flanges and cover plates shall be available in a brushed finish or powder-coated finish. Powder-coated finish shall be available in black, brass, nickel, gray, or bronze colors. Each flange shall provide 1/2 inch (12.7 mm) of adjustment to accommodate various floor covering thicknesses.1) Brass, Aluminum, and Nonmetallic Flanges and Cover Plates: Flange

dimensions shall be as follows:a) One Gang Brass Finish:

1) Width: 5.060 in (128.524 mm).2) Length: 6.080 in (154.432 mm).

b) One Gang Aluminum Finish:1) Width: 4.920 in (124.968 mm).2) Length: 5.940 in (150.876 mm).

c) One Gang Nonmetallic Finish:1) Width: 4.750 in (121.000 mm).2) Length: 5.750 in (146.000 mm).

d) Two Gang Brass Finish:1) Width: 9.185 in (233.299 mm).2) Length: 6.080 in (154.432 mm).

e) Two Gang Aluminum Finish:1) Width: 9.045 in (229.743 mm).2) Length: 5.940 in (150.876 mm).

f) Two Gang Nonmetallic Finish:1) Width: 8.875 in (225.000 mm).2) Length: 5.750 in (146.000 mm).

g) Three Gang Brass Finish:1) Width: 13.310 in (338.074 mm).2) Length: 6.080 in (154.432 mm).

h) Three Gang Aluminum Finish:1) Width: 13.170 in (334.518 mm).2) Length: 5.940 in (150.876 mm).

i) Three Gang Nonmetallic Finish:1) Width: 13.000 in (330.000 mm).2) Length: 5.750 in (146.000 mm).

2) All brass, aluminum, and nonmetallic flanges shall be approved for use on carpet, tile, or wood covered floor applications. Brass flanges and covers plates shall have a buffed appearance and be protected with a lacquer finish. Aluminum flanges and cover plates shall be offered in a buffed appearance with a lacquer finish, and shall be offered with a black, brass, bronze, nickel, and gray powder coated finishes. Nonmetallic flanges and cover plates shall be provided in a black, brown, or gray finish. All flanges shall also accommodate Ortronics workstation connectivity outlets and modular inserts, and Wiremold Connectivity Modular Insert System. Modular inserts shall snap directly into each flange through use of a mounting adapter.

3) Aluminum and nonmetallic cover plate options shall seat inside either the

16000-51

Page 52:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

aluminum or nonmetallic flanges and be flush with the finished floor. Aluminum and nonmetallic cover plate dimensions shall be 3.29 inches (83.566 mm) W x 4.310 inches (109.474 mm) L. Brass cover plate dimensions are 3.156 inches (80.162 mm) W x 4.182 inches (106.223 mm) L. Brass cover plates shall seat inside only brass flanges and be flush with the finished floor. All cover plate options shall provide for both power and communication services. Communication covers shall accommodate Ortronics workstation connectivity outlets and modular inserts, and Wiremold Connectivity Modular Insert System.

5. Communication Devices and Accessoriesa. The floor box manufacturer shall have available a complete line of Ortronics

Workstation Connectivity Outlets and Modular Inserts, and Activate™ Communication Connectivity outlets and modular inserts for UTP, Fiber Optic, Coaxial, and other cabling types with faceplates and bezels to facilitate mounting.

F. Raised floor box shall be manufactured by Walker Systems, Inc. -- A Wiremold Company.1. The raised floor box provides the interface between power and communication cabling

beneath a raised floor, and the workstation where recessed power and communication device outlets are required.

2. The unwired raised floor box is designed for indoor, dry location applications only, and shall have been examined and tested by Underwriters Laboratories Inc., to their Standard UL514A and to Canadian Standard C22.2, No. 18-22, and bear the Listing Mark. The box shall be suitable for use in air handling spaces in accordance with Sec. 300-22(C) of the National Electrical Code and in raised floor plenums.

3. Box Size 8 inches x 8 inches x (4 inches or 5 inches) (203 mm x 203 mm x 102 mm or 127mm):a. The panel opening shall be 8 inches x 8 inches (203 mm x 203 mm) and have

an overall module depth of either 4 inches or 5 inches (102 mm or 127 mm). The box shall provide a total Device Wiring Chamber volume of at least 64 cubic inches (1047 ml) for the 4 inches (102 mm) deep box, and at least 97 cubic inches (1593 ml) for the 5 inches (127 mm) deep box. The total Box Volume capacity shall have a minimum of 152 cubic inches (2490 ml) for the 4 inches (102 mm) box and at least 199 cubic inches (3264 ml) for the 5 inches (127 mm) box.

b. The box lid shall be constructed of die-cast zinc material, and shall also be removable and 180 degree reversible. The lid shall provide a removable cable guard for egress of power and communication workstation cables. The cable guard, when in use, shall extend above the surface of the lid for the purpose of added protection of the workstation cables.

c. The wiring chamber shall provide two separate compartments to accommodate power wiring on one side of the box and communication wiring on the other side. The chamber shall also provide complete access to the communication wiring plate, which will allow for removal of the wiring plate, without the need to disconnect the wiring of any communication device outlets. All 4 inches (102 mm) deep boxes shall be supplied with a power plate, which shall have two duplex receptacle knockouts. All 5 inches (127 mm) deep boxes shall be supplied with a power plate that shall have four duplex receptacle knockouts.

d. The box shall be secured to the raised floor by the use of two locking toggles. The locking toggles shall be integral to the box and adjusted by use of their locking screws.

4. Box Size 8 inches x 10 inches x (4 inches or 5 inches) (203 mm x 254 mm x 102 mm or 127 mm):a. The panel opening shall be 8 inches x 10 inches (203 mm x 254 mm) and have

an overall module depth of either 4 inches or 5 inches (102 mm or 127 mm). The box shall provide a total Device Wiring Chamber volume of at least 77

16000-52

Page 53:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

cubic inches (1260 ml) for the 4 inches (102 mm) deep box, and at least 111 cubic inches (1820 ml) for the 5 inches (127 mm) deep box. The total Box Volume capacity shall have a minimum of 201 cubic inches (3295 ml) for the 4 inches (102 mm) box and at least 262 cubic inches (4309 ml) for the 5 inches (127 mm) box.

b. The box lid shall be constructed of die-cast zinc material, and shall also be removable and 180 degree reversible. The lid shall provide a removable cable guard for egress of power and communication workstation cables. The cable guard, when in use, shall extend above the surface of the lid for the purpose of added protection of the workstation cables.

c. The trim flange shall be constructed of die-cast zinc material and have a minimum overall dimension of 9-1/4 inches x 11-1/4 inches (235 mm x 285 mm) for both the 4 inches and 5 inches (102 mm or 127 mm).

d. The wiring chamber shall provide two separate compartments to accommodate power wiring on one side of the box and communication wiring on the other side. The chamber shall also provide complete access to the communication wiring plate, which will allow for removal of the communication plate without the need to disconnect the wiring of any communication device outlets. All 4 inches (102 mm) deep boxes shall be supplied with a power plate, which shall have two duplex receptacle knockouts. All 5 inches (127 mm) deep boxes shall be supplied with a power plate that shall have four duplex receptacle knockouts.

e. The box shall be secured to the raised floor by the use of two locking toggles. The locking toggles shall be integral to the box and adjusted by use of their locking screws.

5. Box Size 10 inches x 10 inches x 5 inches (254 mm x 254 mm x 127 mm):a. The panel opening shall be 10 inches x 10 inches (254 mm x 254 mm) and

have an overall module depth of 5 inches (127 mm). The box shall provide a total Device Wiring Chamber volume of at least 115 cubic inches (1884 ml). The total Box Volume capacity shall have a minimum of 358 cubic inches (5865 ml).

b. The box lid shall be constructed of die-cast zinc material, and shall also be removable and 180 degree reversible. The lid shall provide a removable cable guard for egress of power and communication workstation cables. The cable guard, when in use, shall extend above the surface of the lid for the purpose of added protection of the workstation cables.

c. The trim flange shall be constructed of die-cast zinc material and have a minimum overall dimension of 11-1/2 inches x 11-1/2 inches (288 mm x 288 mm).

d. The wiring chamber shall provide two separate compartments to accommodate power wiring on one side of the box and communication wiring on the other side. The chamber shall also provide complete access to the communication wiring plate, which will allow for removal of the communication plate, without the need to disconnect the wiring of any communication device outlets. The box shall be supplied with a power plate which shall have four duplex receptacle knockouts.

e. The box shall be secured to the raised floor by the use of two locking toggles. The locking toggles shall be integral to the box and adjusted by use of their locking screws.

G. Raised floor box shall be manufactured by Walker Systems, Inc. -- A Wiremold Company.1. The raised floor box provides the interface between power and communication cabling

beneath a raised floor, and the workstation where recessed power and communication device outlets are required. The box is available in both an unwired version and a prewired version that interfaces with a flexible wiring system. Only power devices are prewired.

2. The raised floor box is designed for indoor, dry location applications only, and shall

16000-53

Page 54:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

have been examined and tested by Underwriters Laboratories Inc., to their standard UL514A and to Canadian Standard C22.2, No. 18-22, and bear the Listing Mark. The box shall be suitable for use in air handling spaces in accordance with Sec. 300-22(C) of the National Electrical Code and for use in raised floor plenums.

3. Box size - 8 inches x 6 inches x 5 inches (203 mm x 152 mm x 127 mm) (AF1 & AF2 Series):a. The panel opening shall be 8 inches x 6 inches (203 mm x 152 mm) and have

an overall module depth of 5 inches (127 mm). The box shall provide a total activation chamber volume of at least 130 cubic inches (2130 ml). The total Box Volume capacity shall have a minimum of 208 cubic inches (3418 ml).

b. The box lid shall be constructed of polycarbonate material, available in standard colors of black, brown and gray. The lid shall provide a removable cable guard for egress of power and communication workstation cables. The cable guards shall hold workstation cables in place with the lid either in the open or closed position.

c. The trim flange shall be constructed of polycarbonate material and have a minimum overall dimension of 8-3/4 inches x 6-3/4 inches (222 mm x 171 mm). The hinged lid and trim flange shall be available for either carpet or tile floor applications.

d. The wiring chamber shall provide a minimum of three separate compartments to accommodate a combination of both power and communication wiring. The compartments shall be separated by use of die cast aluminum built in dividers.

e. If a prewired flexible wiring system is specified, the same manufacturer shall supply the box, and the flexible wiring system. The box shall contain integral connectors to mate with the flexible wiring system. The box shall be capable of disconnecting from the flexible wiring system directly at the box. The prewired box shall be able to contain up to three separate circuits, utilizing up to an 8 conductor MC cable assembly.

f. The box shall be secured to the raised floor by the use of two locking tabs. The locking tabs shall be integral to the box and adjusted by use of their locking screws.

4. Box size - 8 inches x 10 inches x 5 inches (203 mm x 254 mm x 127 mm) (AF3 & AF4 Series):a. The panel opening shall be 8 inches x 10 inches (203 mm x 254 mm) and have

an overall module depth of 5 inches (127 mm). The box shall provide a total Device Wiring Chamber volume of at least 220 cubic inches (3604 ml). The total Box Volume capacity shall have a minimum of 300 cubic inches (4915 ml).

b. The box lid shall be a hinged style and constructed of polycarbonate material, available in standard colors of black, brown and gray. The lid shall provide a minimum of three removable cable guards for egress of power and communication workstation cables. The cable guards shall hold workstation cables in place with the lid either in the open or closed position.

c. The trim flange shall be constructed of polycarbonate material and have a minimum overall dimension of 9-1/8 inches x 11 inches (232 mm x 279 mm). The hinged lid and trim flange shall be available for either carpet or tile floor applications.

d. The wiring chamber shall provide an upper and a lower compartment. The top compartment shall be divided into three separate compartments to accommodate a combination of both power and communication wiring. These compartments shall be separated by use of integral; die cast aluminum built in dividers. The bottom compartment shall be available for either all power or all communication wiring.

e. If a prewired flexible wiring system is specified, the same manufacturer shall supply the box, and the flexible wiring system. The box shall contain integral connectors to mate with the flexible wiring system. The box shall be capable of disconnecting from the flexible wiring system directly at the box. The prewired

16000-54

Page 55:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

box shall be able to contain up to three separate circuits, utilizing up to an 8 conductor MC cable assembly.

f. The box shall be secured to the raised floor by the use of two locking tabs. The locking tabs shall be integral to the box and adjusted by use of their locking screws.

5. Communication Devices and Accessories:a. Box size - 8 inches x 10 inches x 2-1/2 inches (203 mm x 254 mm x 64 mm)

(SAF21/2 Series) The panel opening shall be 8 inches x 10 inches (203 mm x 254 mm) and have overall depth of 2-1/2 inches (64 mm). The box shall provide a total Device Wiring Chamber volume of at least 18.5 cubic inches (303 ml). The total Box Volume capacity shall have a minimum of 29 cubic inches (475 ml).

b. The box lid shall be a hinged style and constructed of polycarbonate material, available in standard colors of black, brown and gray. The lid shall provide a minimum of three removable cable guards for egress of power and communication workstations cables. The cable guards shall hold workstation cables in place with the lid either in the open or closed position.

c. The trim flange shall be constructed of polycarbonate material and have a minimum overall dimension of 9-1/8 inches x 11 inches (232 mm x 279 mm). The hinged lid and trim flange shall be available for either carpet or tile floor applications.

d. The wiring chamber shall provide two compartments to accommodate power and communication wiring. The box shall be secured to the raised floor by two set screws on sides of box.

6. Prewired Boxa. Installation drawings shall be furnished showing the appropriate power layouts

where the raised floor box and flexible wiring system is to be used. The installation shall be represented on the layout drawing in the form of a legend. The legend shall contain a catalog number and a description describing the components use. Installer shall comply with detailed manufacturer's installation instruction sheets that accompany the raised floor box. All equipment shall be warranted for one year from the date of final acceptance.

H. Floor boxes for round recessed raised and wood floor boxes shall be CRFB Series floor boxes manufactured by Legrand/Wiremold.1. Classification and Use: Floor boxes shall have been examined and tested by

Underwriters Laboratories Inc. to comply with UL514A and/or UL514C and Canadian Standard C22.2, No. 18-98 and bear the U.S. and Canadian UL Listing Mark. Fire classified floor boxes shall also have been tested by UL and classified for fire resistance and bear the U.S. and Canadian UL Classification Mark. The floor boxes shall conform to the standards set forth in the National Electrical Code, Section 300-21.

2. Floor boxes shall have been evaluated by UL to meet the applicable U.S. and Canadian safety standards for scrub water exclusion when used on tile, terrazzo, wood, and carpet covered floors.

3. These devices are not suitable for wet or damp locations, or other areas subject to saturation with water or other liquids such as commercial kitchens.

4. Floor boxes shall be suitable for use in air handling spaces in accordance with Section 300-22C of the National Electrical Code.

5. Round Recessed Raised and Wood Floor Boxes: Model No. CRFB4 Round Recessed Raised and Wood Floor Boxes manufactured by Legrand/Wiremold:a. Round recessed raised and wood floor boxes provide an interface between

power, communication and audio/visual (A/V) cabling in a raised or wood floor and at the workstation or activation location where power, communication and/or A/V device outlets are required. These devices provide flush and recessed outlets that will not obstruct the floor area. Refer to the Drawings for

16000-55

Page 56:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

types.b. Round recessed raised and wood floor boxes shall be compatible with the

complete line of Ortronics workstation connectivity outlets and modular inserts.c. Round recessed raised and wood floor boxes shall be round in shape and

available in a four-gang configuration. Boxes shall also include a removable barrier between the individual compartments for greater capacity when required. Boxes shall have a 1-inch (25 mm) trade size knockout installed in the barriers to allow cables to be passed through from one compartment to the next. Supply boxes with grommets to be installed into the knockout area to prevent the cables from being damaged when passing through openings. Supply boxes with a tunneling feature to allow the two outer compartments to be utilized separately from the two center compartments. Two of the four compartments shall have a minimum capacity of 23.5 cu. in. (385 ml), one compartment shall have a minimum capacity of 17.5 cu. in. (287 ml), and one compartment shall have a minimum capacity of 32.8 cu. in. (537 ml).1) Body: Manufacture box body from die-cast aluminum with stamped steel

base. Boxes shall be available in a four-gang configuration. Overall box dimensions are 8-1/4 inches (210 mm) diameter x 6-1/2 inches (165 mm) H. Provide the box with the following trade size knockouts: three 1/2-inch / 3/4-inch (13 mm / 19 mm) concentric knockouts, three 3/4-inch / 1-inch (19 mm / 25 mm) concentric knockouts, one 1-1/4 inches (32 mm) knockout, and one 2 inches (51 mm) knockout.

6. Activation Covers:a. CRFB, CRFBCTC, and CRFBBTC Series Covers: Manufacture from die-cast

aluminum with black powder coat, gray powder coat, brass powder coat, nickel powder coat, bronze powder coat finish as indicated or scheduled. Provide cover assemblies with capability to accept tile or carpet inserts or solid covers. Provide cover assembly with gasketing to maintain scrub water tightness. The cover shall be 9-1/4 inches (235 mm) diameter. Provide covers with a 1/4 turn locking feature.1) Cover assembly shall be tamper-resistant.

b. 8CT Series Covers: Manufacture from die-cast aluminum alloy with black powder coat, gray powder coat, brass powder coat, nickel powder coat, bronze powder coat finish as indicated or scheduled. Provide cover assemblies with capability to accept tile or carpet inserts. Provide covers with two gaskets (one for carpet and one for tile) to go under the trim flange to maintain scrub water tightness. The activation cover shall be 9-1/4 inches (235 mm) diameter. The carpet covers shall be surface mounted and the tile covers shall be flush with the finished floor covering. The cover shall have spring loaded slides to allow cables to egress out of the unit and maintain as small an egress opening as possible.

7. Communication Modules Mounting Accessories:a. The floor box manufacturer shall provide a complete line of faceplates and

bezels to facilitate mounting of UTP, STP (150 ohm), fiber optic, coaxial, and communication devices. The box shall provide a series of device mounting plates that will accommodate Ortronics workstation connectivity outlets and modular inserts, Wiremold Connectivity Modular Insert System, and Extron Electronics MAAP devices.

I. Electrical shallow floor boxes shall be Resource CAF series floor boxes manufactured by Legrand/Wiremold.1. Floor Boxes General: CAF3 Series Floor Boxes: Manufactured from stamped steel

and approved for use on above grade floors.2. Dimensions (L x W x H): 5-7/8 x 7-1/8 x 3 inches (333 x 165 x 87 mm). Provide the

box with three independent wiring compartments that allow capacity for up to two duplex receptacles, communication and audio/video services. The box shall permit

16000-56

Page 57:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

tunneling from end power compartment to end power compartment. Provide each of the three compartments with a minimum wiring capacity of 50 cu in (819 cu ml). Three compartments shall have a minimum of three inches of space behind the device plates. The box shall include the following number of conduit knockouts: two 1/2 inch (13 mm) and two 3/4 inch (19 mm). The box shall be fully adjustable, providing a maximum of 1-3/8 inch (35 mm) pre-pour adjustment, and a maximum of 3/4 inch (19 mm) after-pour adjustment. The box shall include a series of device mounting plates that will accept both duplex power devices as well as plates that will accommodate Ortronics workstation connectivity outlets and modular adapters, Legrand AVIP audio/video device plates, and other open system devices.

3. Activation Covers: FloorPort FPCTC and FPBTC Series Covers.a. Manufactured of die-cast aluminum or die-cast zinc. Activation covers shall be

available in flanged versions. The cover's hinge shall allow for the cover to open 180 degrees. The covers shall have been evaluated by UL to meet the applicable U.S. and Canadian safety standards for scrub water exclusion when used on tile, terrazzo, wood, and carpet covered floors.1) Finish: Brushed aluminum.2) Powder coat finish color shall be aluminum, black, gray, brass, nickel,

bronze.4. Communications Modules Mounting Accessories: The floor box manufacturer shall

provide a complete line of faceplates and bezels to facilitate mounting of UTP, STP (150 ohm), fiber optic, coaxial, and communication devices. The box shall provide a series of device mounting plates that will accommodate Ortronics workstation connectivity outlets and modular adapters, and other open system devices.

J. Electrical floor boxes and fittings shall be Evolution Series as manufactured by Legrand/Wiremold.1. Classification and Use: Floor boxes shall have been examined and tested by

Underwriters Laboratories Inc. to meet UL514A and/or UL514C and Canadian Standard C22.2, No. 18.1-04 and 18.2-06 and bear the U.S. and Canadian UL Listing Mark. Floor boxes shall also have been tested by Underwriters Laboratories Inc. and classified for fire resistance and bear the U.S. and Canadian UL Classification Mark. Devices shall be classified for use in 2-hour rated, unprotected reinforced concrete floors and 2-hour rated floors employing unprotected steel floor units and concrete toppings (D900 Series Designs) or concrete floors with suspended ceilings (fire resistive designs with suspended ceilings shall have provisions for accessibility in the ceiling below the floor boxes). Floor boxes shall also conform to the standards set in Section 300-21 of the National Electrical Code. Floor boxes shall meet UL scrub water requirements, but are not suitable for wet or damp locations, or other areas subject to saturation with water or other liquids such as commercial kitchens. Floor boxes shall also have been evaluated by UL to meet the applicable U.S. and Canadian safety standards for scrub water exclusion when used on tile, bare concrete, terrazzo, wood, and carpet covered floors. Floor boxes shall be suitable for use in air handling spaces in accordance with Section 300-22 (C) of the National Electrical Code.

2. Floor Boxes, General: Evolution Series Floor Boxes for use on above grade concrete floors, raised floors or wood floors. Provide boxes with a component to permit installation in polished concrete or terrazzo floors. Boxes shall be compatible with complete line of Ortronics workstation connectivity outlets and modular inserts.a. Floor boxes provide the interface between power, communication and

audio/video (A/V) cabling in above-grade floors, on-grade concrete floors, raised floors, wood floors, and fire-classified floors and the workstation or activation location where power and communication and/or A/V device outlets are required. Boxes shall provide recessed device outlets that will not obstruct the floor area. Refer to Drawings for size and types.

b. Floor boxes shall permit all wiring to be completed at floor level. The FC models shall be used as defined by the UL Fire Resistance Directory at a minimum

16000-57

Page 58:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

spacing of 2 feet (610 mm) on center.3. Model EFB45S Floor Boxes:

a. Manufactured from stamped steel approved for use on above grade concrete floors, raised floors and wood floors with the same product. Boxes shall have the ability to accept a component (EFB45-CTR) that will allow the box to be installed in polished concrete or terrazzo floors. Boxes shall have a polyester based backed white enamel finished interior. Dimensions (L x W x H): 12-1/16 x 9-3/16 x 5-15/16 inches (306 x 233 x 151 mm). Provide boxes with provisions that enable installation into concrete floors, raised floors, or wood floors without having to purchase additional components or accessories. Provide boxes with four independent wiring compartments that allow for up to four receptacles, communication and/or audio/video services. Boxes shall have the ability to expand to five independent wiring compartments by changing out the mounting brackets module. Boxes shall accept standard size single gang; 2-3/4 x 4-1/2 inch (70 x 114 mm), double gang; 4-9/16 x 4-1/2 inch (116 x114 mm), and triple gang; 6-3/8 x 4-1/2 inch (162 x 114 mm) wall plates. Boxes shall permit feed to adjacent compartments. Each of the two outer compartments shall have a minimum wiring capacity of 28 cu in (459 ml). Each of the two center compartments shall have a minimum wiring capacity of 34 cu in (557 ml). Each of the four compartments shall have a minimum depth of 3-1/2 inch (89 mm) behind the plate. Provide boxes with a removable compartment to facilitate installation and moves, additions, and changes. The compartments shall be removable from the top and back of the floor box. Provide boxes with two cable guides to organize and maintain the cables egress out of the box. Provide boxes with removable knockout plates to allow for the maximum cable pass-through area. The cable pass-through area shall be a minimum of 11-5/8 sq in (7500 sq mm). The box shall contain the following number of knockouts: four 3/4 inch (19 mm) trade size, four 1 inch (25 mm) trade size, three 1-1/4 inch (32 mm) trade size, and one 2 inch (51 mm) trade size. Boxes shall be fully adjustable, accommodating a maximum 2 inch (51 mm) pre-concrete pour and a maximum 1/2 inch (13 mm) post-concrete pour adjustment. Equip boxes with toggle clamps to allow box to be secured to raised and wood floors. Include mounting brackets with the boxes that will accommodate 15 amp, 20 amp straight blade, 20 amp turn loc, 30 amp straight blade and 30 amp turn loc receptacles. Boxes shall have the ability to accommodate a bracket (EFB-50A) allowing for one 50 amp receptacle. Boxes shall also accommodate Ortronics workstation connectivity and modular adapters, a variety of audio/video devices from most manufacturers, and other open system devices.

4. Model EFB45S-OG Floor Boxes:a. Manufactured from stamped steel approved for use in above grade and on-

grade floor applications. Boxes shall have the ability to accept a component (EFB45-CTR) that will allow the box to be installed in polished concrete or terrazzo floors. Boxes shall be painted with a fusion-bonded epoxy designed for use on metal reinforcement bar and related accessories before encapsulation in concrete, and be approved for use on-grade and above grade floors. Dimensions (L x W x H): 12-1/16 x 9-3/16 x 5-15/16 inches (306 x 233 x 151 mm). Provide boxes with four independent wiring compartments that allow for up to four duplex receptacles, communication and/or audio/video services. Box shall have the ability to expand to five independent wiring compartments by changing out the mounting brackets module. Boxes shall have removable and relocatable dividers to permit custom configuration of compartments as well as permit feed to adjacent compartments. Each of the two outer compartments shall have a minimum wiring capacity of 28 cu in (455 ml). Each of the two center compartments shall have a minimum wiring capacity of 34 cu in (557 ml). Each of the four compartments shall have a minimum depth of 3-1/2 inch (89 mm) behind the plate. Provide boxes with removable compartments to

16000-58

Page 59:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

facilitate installation. The compartments shall be removable from the top of the floor box. Provide boxes with two cable guides to organize and maintain the cables egress out of the box. The box shall contain the following number of knockouts: six 1 inch (25 mm) trade size, three 1-1/4 inch (32 mm) trade size, and two 2 inch (51 mm) trade size. Boxes shall be fully adjustable, accommodating a maximum 2 inch (51 mm) pre-concrete pour and a maximum 1/2 inch (13 mm) post-concrete pour adjustment. Boxes shall accept standard size single gang; 2-3/4 x 4-1/2 inch (70 x 114 mm), double gang; 4-9/16 x 4-1/2 inch (116 x114 mm), and triple gang; 6-3/8 x 4-1/2 inch (162 x 114 mm) wall plates. Include mounting brackets with the boxes that will accommodate 15 amp, 20 amp straight blade, 20 amp turn loc, 30 amp straight blade and 30 amp turn loc receptacles. Boxes shall have the ability to accommodate a bracket (EFB-50A) allowing for one 50 amp receptacle. Boxes shall also accommodate Ortronics workstation connectivity and modular adapters, a variety of audio/video devices from most manufacturers, and other open system devices.

5. Model EFB45S-FC Floor Boxes:a. Manufactured from stamped steel approved for use in 2-hour fire-rated

concrete floors. Boxes shall have the ability to accept a component (EFB45-CTR) that will allow the box to be installed in polished concrete or terrazzo floors. Boxes shall have a polyester based backed white enamel finished interior. Dimensions (L x W x H): 12-1/16 x 9-3/16 x 5-15/16 inches (306 x 233 x 151 mm). Provide boxes with a sheet metal concrete pan to ensure that 3-1/4 inches (83 mm) of concrete surrounds the box. Concrete Pan Dimensions (L x W x H): 18-11/16 x 16-3/8 x 15-1/16 inches (475 x 416 x 383 mm). Provide boxes with four independent wiring compartments that allow for up to four receptacles, communication and/or audio/video services. Box shall have the ability to expand to five independent wiring compartments by changing out the mounting brackets module. Boxes shall have removable and repositionable dividers to permit feed to adjacent compartments and reconfiguration of devices. Each of the compartments shall have a minimum wiring capacity of 53 cu in (868 ml). Each of the four compartments shall have a minimum depth of 3-1/2 inch (89 mm) behind the plate. Provide boxes with two cable guides to organize and maintain the cables egress out of the box. Provide boxes with four intumescent services feed stems with a 1-1/4 inch (32 mm) pass-through channel that allows the pathway to close off during a fire. Boxes shall be fully adjustable, accommodating a maximum 3 inch (76 mm) pre-concrete pour and a maximum 1/2 inch (13 mm) post-concrete pour adjustment. Boxes shall accept standard size single gang; 2-3/4 x 4-1/2 inch (70 x 114 mm), double gang; 4-9/16 x 4-1/2 inch (116 x114 mm), and triple gang; 6-3/8 x 4-1/2 inch (162 x 114 mm) wall plates. Include mounting brackets with the boxes that will accommodate 15 amp, 20 amp straight blade, 20 amp turn loc, 30 amp straight blade and 30 amp turn loc receptacles. Boxes shall have the ability to accommodate a bracket (EFB-50A) allowing for one 50-amp receptacle. Boxes shall also accommodate Ortronics workstation connectivity and modular adapters, a variety of audio/video devices from most manufacturers, and other open system devices.

6. Model EFB45S-FC12 Floor Boxes:a. Manufactured from stamped steel approved for use in 2-hour fire-rated

concrete floors. Boxes shall have the ability to accept a component (EFB45-CTR) that will allow the box to be installed in polished concrete or terrazzo floors. Boxes shall have a polyester based backed white enamel finished interior. Dimensions (L x W x H) 12-1/16 x 9-3/16 x 5-15/16 inches (306 x 233 x 151 mm). Provide boxes with a sheet metal concrete pan to ensure that 3-1/4 inches (83 mm) of concrete surrounds the box. Concrete Pan Dimensions (L x W x H): 18-11/16 x 16-3/8 x 15-1/16 inches (475 x 416 x 383 mm). Provide

16000-59

Page 60:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

boxes with four independent wiring compartments that allow for up to four receptacles, communication and/or audio/video services. Box shall have the ability to expand to five independent wiring compartments by changing out the mounting brackets module. Boxes shall have removable and repositionable dividers to permit feed to adjacent compartments and reconfiguration of devices. Each of the compartments shall have a minimum wiring capacity of 53 cu in (868 ml). Each of the four compartments shall have a minimum depth of 3-1/2 inch (89 mm) behind the plate. Provide boxes with two cable guides to organize and maintain the cables egress out of the box. Provide boxes with four intumescent services feed stems. Two of the intumescent service feed stems shall have a 1-1/4 inch (32 mm) pass-through channel and two intumescent service feed stems shall have a 2 inch (51mm) pass - through channel that allows the pathway to close off during a fire. Boxes shall be fully adjustable, accommodating a maximum 3 inch (76 mm) pre-concrete pour and a maximum 1/2 inch (13 mm) post-concrete pour adjustment. Boxes shall accept standard size single gang; 2-3/4 x 4-1/2 inch (70 x 114 mm), double gang; 4-9/16 x 4-1/2 inch (116 x114 mm), and triple gang; 6-3/8 x 4-1/2 inch (162 x 114 mm) wall plates. Include mounting brackets with the boxes that will accommodate 15 amp, 20 amp straight blade, 20 amp turn loc, 30 amp straight blade and 30 amp turn loc receptacles. Boxes shall have the ability to accommodate a bracket (EFB-50A) allowing for one 50-amp receptacle. Boxes shall also accommodate Ortronics workstation connectivity and modular adapters, a variety of audio/video devices from most manufacturers, and other open system devices.

7. Model EFB6S Floor Boxes:a. Manufactured from stamped steel approved for use on above grade concrete

floors, raised floors and wood floors with the same product. Boxes shall have the ability to accept a component (EFB610-CTR) that will allow the box to be installed in polished concrete or terrazzo floors. Boxes shall have a polyester based backed enamel finished interior (white). Boxes shall be 15-3/16 inches L x 13-7/8 inches W x 4-3/16 inches H (385 mm x 351 mm x 107 mm). Provide boxes with provisions that enable installation into concrete floors, raised floors, or wood floors without having to purchase additional components or accessories. Provide boxes with six independent wiring compartments that allow for up to six receptacles, communication and/or audio/video services. Boxes shall have removable and relocatable dividers to permit custom configuration of compartments as well as permit feed to adjacent compartments. Boxes shall permit feed to compartments on the opposite side of the box through a tunnel. Each of the four outer compartments shall have a minimum wiring capacity of 32-in3 (524 ml). Each of the two center compartments shall have a minimum wiring capacity of 38.5-in3 (630 ml). Each of the six compartments shall have a minimum depth of 3-7/8 inches (98 mm) behind the plate. Provide boxes with removable compartments to facilitate installation and moves, additions, and changes. The compartments shall be removable from the top and back of the floor box. Provide boxes with two cable guides to organize and maintain the cables egress out of the box. Provide boxes with removable knockout plates to allow for the maximum cable pass-through area. The cable pass-through area shall be a minimum of 6-15/16 in2 (176 mm2). The box shall contain the following number of knockouts: Ten 1 inch (25 mm) trade size, six 1-1/4 inches (32 mm) trade size, six 3/4 inch (19 mm) trade size, and two 2 inches (51 mm) trade size. Boxes shall be able to accept up to six 2 inches (51 mm) trade size conduit feeds in the sides of the boxes, through the use of the EFB6S-2HUB and maintain a 4 inches (102 mm) deep concrete pour. Boxes shall be fully adjustable, accommodating a maximum 2 inches (51 mm) pre-concrete pour and a maximum 1/2 inch (13 mm) post-concrete pour adjustment. Equip boxes with toggle clamps to allow

16000-60

Page 61:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

box to be secured to raised and wood floors. The box shall be able to accept 2-3/4 inches x 4-1/2 inches (70 mm x 114 mm) standard size wall plates. Include mounting brackets with the boxes that will accommodate 15 amp, 20 amp straight blade, 20 amp turn-loc, 30 amp straight blade and 30 amp turn-loc receptacles, Ortronics workstation connectivity and modular adapters, a variety of audio/video devices from most manufacturers, and other open system devices.

8. Model EFB6S-OG Floor Boxes:a. Manufactured from stamped steel approved for use in above grade and on-

grade floor applications. Boxes shall have the ability to accept a component (EFB610-CTR) that will allow the box to be installed in polished concrete or terrazzo floors. Boxes shall be painted with a fusion-bonded epoxy designed for use on metal reinforcement bar and related accessories before encapsulation in concrete, and be approved for use on-grade and above grade floors. Boxes shall be 15-3/16 inches L x 13-7/8 inches W x 4-3/16 inches H (385 mm x 351 mm x 107 mm). Provide boxes with six independent wiring compartments that allow for up to six duplex receptacles, communication and/or audio/video services. Boxes shall have removable and relocatable dividers to permit custom configuration of compartments as well as permit feed to adjacent compartments. Boxes shall permit feed to compartments on the opposite side of the box through a tunnel. Each of the four outer compartments shall have a minimum wiring capacity of 32 in3 (524 ml). Each of the two center compartments shall have a minimum wiring capacity of 38.5 in3 (630 ml). Each of the six compartments shall have a minimum depth of 3-7/8 inches (98 mm) behind the plate. Provide boxes with removable compartments to facilitate installation. The compartments shall be removable from the top of the floor box. Provide boxes with two cable guides to organize and maintain the cables egress out of the box. The box shall contain the following number of knockouts: Ten 1 inch (25.4 mm) trade size, six 1-1/4 inches (32 mm) trade size, six 3/4 inch (19 mm) trade size, and two 2 inches (51 mm) trade size. Boxes shall be able to accept up to six 2 inches (51 mm) trade size conduit feeds in the sides of the boxes, through the use of the EFB6S-2HUB and maintain a 4 inches (102 mm) deep concrete pour. Boxes shall be fully adjustable, accommodating a maximum 2 inches (51 mm) pre-concrete pour and a maximum 1/2 inches (12.7 mm) post-concrete pour adjustment. The box shall be able to accept 2-3/4 inches x 4-1/2 inches standard size wall plates. Include mounting brackets with the boxes that will accommodate 15 amp, 20 amp straight blade, 20 amp turn loc, 30 amp straight blade and 30 amp turn loc receptacles, Ortronics workstation connectivity and modular adapters, a variety of audio/video devices from most manufacturers, and other open system devices.

9. Model EFB6S-FC Floor Boxes:a. Manufactured from stamped steel approved for use in 2-hour fire-rated

concrete floors. Boxes shall have the ability to accept a component (EFB610-CTR) that will allow the box to be installed in polished concrete or terrazzo floors. Boxes shall have a polyester based backed enamel finished interior (white). Boxes shall be 15-3/16 inches L x 13-7/8 inches W x 4-3/16 inches H (385 mm x 351 mm x 107 mm). Provide boxes with a 21-3/4 inches L x 17-1/4 inches W x 6-1/2 inches H (552 mm x 438 mm x 165 mm) sheet metal concrete pan to ensure that 3-1/4 inches (83 mm) of concrete surrounds the box. Provide boxes with six independent wiring compartments that allow for up to six receptacles, communication and/or audio/video services. Boxes shall permit feed to adjacent compartments. Boxes shall permit feed to compartments on the opposite side of the box through a tunnel. Each of the four outer compartments shall have a minimum wiring capacity of 32 in3 (524 ml). Each of the two center compartments shall have a minimum wiring capacity of 38.5 in3 (630 ml). Each of the six compartments shall have a minimum depth of 3-7/8

16000-61

Page 62:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

inches (98 mm) behind the plate. Provide boxes with two cable guides to organize and maintain the cables egress out of the box. Provide boxes with four intumescent services feed stems with a 1-1/4 inches (32 mm) pass-through channel that allows the pathway to close off during a fire. Boxes shall be fully adjustable, accommodating a maximum 2-1/2 inches (64 mm) pre-concrete pour and a maximum 1/2 inch (12.7 mm) post-concrete pour adjustment. The box shall be able to accept 2-3/4 inches x 4-1/2 inches standard size wall plates. Include mounting brackets with the boxes that will accommodate 15 amp, 20 amp straight blade, 20 amp turn loc, 30 amp straight blade and 30 amp turn loc receptacles, Ortronics workstation connectivity and modular adapters, a variety of audio/video devices from most manufacturers, and other open system devices.

10. Model EFB8S Floor Boxes:a. Manufactured from stamped steel approved for use on above grade concrete

floors, raised floors and wood floors with the same product. Boxes shall have the ability to accept a component (EFB610-CTR) that will allow the box to be installed in polished concrete or terrazzo floors. Boxes shall have a polyester based backed enamel finished interior (white). Boxes shall be 15-3/16 inches L x 12-3/4 inches W x 6-1/16 inches H (385 mm x 324 mm x 154 mm). Provide boxes with provisions that enable installation into concrete floors, raised floors, or wood floors without having to purchase additional components or accessories. Provide boxes with eight independent wiring compartments that allow for up to eight receptacles, communication and/or audio/video services. Boxes shall accept standard size single gang (2-3/4 inches x 4-1/2 inches (70 mm x114 mm)), double gang (4-9/16 inches x 4-1/2 inches (116 mm x 114 mm)), and triple gang (6-3/8 inches x 4-1/2 inches (162 mm x 114 mm) wall plates. Boxes shall permit feed to adjacent compartments. Boxes shall permit feed to compartments on the opposite side of the box through a tunnel. Each of the four outer compartments shall have a minimum wiring capacity of 28 in3 (455 ml). Each of the four center compartments shall have a minimum wiring capacity of 34 in3 (524 ml). Each of the eight compartments shall have a minimum depth of 3-1/2 inches (89 mm) behind the plate. Provide boxes with removable compartments to facilitate installation and moves, additions, and changes. The compartments shall be removable from the top and back of the floor box. Provide boxes with two cable guides to organize and maintain the cables egress out of the box. Provide boxes with removable knockout plates to allow for the maximum cable pass-through area. The cable pass-through area shall be a minimum of 11-5/8 in2 (7500 mm2). The box shall contain the following number of knockouts: four 3/4 inch (19 mm) trade size, eight 1-inch (25 mm) trade size, six 1-1/4 inches (32 mm) trade size, and two 2 inches (51 mm) trade size. Boxes shall be fully adjustable, accommodating a maximum 2-inch (51mm) pre-concrete pour and a maximum 1/2 inch (12.7 mm) post-concrete pour adjustment. Equip boxes with toggle clamps to allow box to be secured to raised and wood floors. Include mounting brackets with the boxes that will accommodate 15 amp, 20 amp straight blade, 20 amp turn loc, 30 amp straight blade and 30 amp turn loc receptacles. Boxes shall have the ability to accommodate a bracket (EFB-50A) allowing for one 50-amp receptacle. Boxes shall also accommodate Ortronics workstation connectivity and modular adapters, a variety of audio/video devices from most manufacturers, and other open system devices.

b. Model EFB8S-OG Floor Boxes: Manufactured from stamped steel approved for use in above grade and on-grade floor applications. Boxes shall have the ability to accept a component (EFB610-CTR) that will allow the box to be installed in polished concrete or terrazzo floors. Boxes shall be painted with a fusion-bonded epoxy designed for use on metal reinforcement bar and related accessories before encapsulation in concrete, and be approved for use on-

16000-62

Page 63:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

grade and above grade floors. Boxes shall be 15-3/16 inches L x 12-5/8 inches W x 6-1/16 inches H (385 mm x 321 mm x 154 mm). Provide boxes with eight independent wiring compartments that allow for up to eight duplex receptacles, communication and/or audio/video services. Boxes shall have removable and relocatable dividers to permit custom configuration of compartments as well as permit feed to adjacent compartments. Boxes shall permit feed to compartments on the opposite side of the box through a tunnel. Each of the four outer compartments shall have a minimum wiring capacity of 28 in3 (455 ml). Each of the four center compartments shall have a minimum wiring capacity of 34 in3 (455 ml). Each of the eight compartments shall have a minimum depth of 3-1/2 inches (89 mm) behind the plate. Provide boxes with removable compartments to facilitate installation. The compartments shall be removable from the top of the floor box. Provide boxes with two cable guides to organize and maintain the cables egress out of the box. The box shall contain the following number of knockouts: Twelve 1-inch (25 mm) trade size, six 1-1/4 inches (32 mm) trade size, and four 2 inches (51 mm) trade size. Boxes shall be fully adjustable, accommodating a maximum 2 inches (51 mm) pre-concrete pour and a maximum 1/2 inch (12.7 mm) post-concrete pour adjustment. The box shall be able to accept standard size single gang (2-3/4 inches x 4-1/2 inches (70 mm x114 mm)), double gang (4-9/16 inches x 4-1/2 inches (116 mm x 114 mm)), and triple gang (6-3/8 inches x 4-1/2 inches (162 mm x 114 mm) wall plates. Include mounting brackets with the boxes that will accommodate 15 amp, 20 amp straight blade, 20 amp turn loc, 30 amp straight blade and 30 amp turn loc receptacles. Boxes shall have the ability to accommodate a bracket (EFB-50A) allowing for one 50-amp receptacle. Boxes shall also accommodate Ortronics workstation connectivity and modular adapters, a variety of audio/video devices from most manufacturers, and other open system devices.

c. Model EFB8S-FC Floor Boxes: Manufactured from stamped steel approved for use in 2-hour fire-rated concrete floors. Boxes shall have the ability to accept a component (EFB610-CTR) that will allow the box to be installed in polished concrete or terrazzo floors. Boxes shall have a polyester based backed enamel finished interior (white). Boxes shall be 15-3/16 inches L x 13-7/8 inches W x 4-3/16 inches H (385 mm x 351 mm x 107 mm). Provide boxes with a 21-3/4 inches L x 17-1/4 inches W x 6-1/2 inches H (552 mm x 438 mm x 165 mm) sheet metal concrete pan to ensure that 3-1/4 inches (83 mm) of concrete surrounds the box. Provide boxes with eight independent wiring compartments that allow for up to eight receptacles, communication and/or audio/video services. Boxes shall have removable and repositionable dividers to permit feed to adjacent compartments and reconfiguration of devices. Boxes shall permit feed to compartments on the opposite side of the box through a tunnel. Each of the compartments shall have a minimum wiring capacity of 53 in3 (860 ml). Each of the eight compartments shall have a minimum depth of 3-1/2 inches (89 mm) behind the plate. Provide boxes with two cable guides to organize and maintain the cables egress out of the box. Provide boxes with removable compartments to facilitate installation. Provide boxes with four intumescent services feed stems with a 1-1/4 inches (32 mm) pass-through channel that allows the pathway to close off during a fire. Boxes shall be fully adjustable, accommodating a maximum 2-1/2 inches (64 mm) pre-concrete pour and a maximum 1/2 inch (12.7 mm) post-concrete pour adjustment. The box shall be able to accept standard size single gang (2-3/4 inches x 4-1/2 inches (70 mm x114 mm)), double gang (4-9/16 inches x 4-1/2 inches (116 mm x 114 mm)), and triple gang (6-3/8 inches x 4-1/2 inches (162 mm x 114 mm) wall plates. Include mounting brackets with the boxes that will accommodate 15 amp, 20 amp straight blade, 20 amp turn loc, 30 amp straight blade and 30 amp turn loc receptacles. Boxes shall have the ability to accommodate a

16000-63

Page 64:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

bracket (EFB-50A) allowing for one 50-amp receptacle. Boxes shall also accommodate Ortronics workstation connectivity and modular adapters, a variety of audio/video devices from most manufacturers, and other open system devices.

11. Model EFB10S Floor Boxes:a. Manufactured from stamped steel approved for use on above grade concrete

floors, raised floors and wood floors with the same product. Boxes shall have the ability to accept a component (EFB610-CTR) that will allow the box to be installed in polished concrete or terrazzo floors. Boxes shall have a polyester based backed enamel finished interior (white). Boxes shall be 15-3/16 inches L x 12-3/4 inches W x 6-1/16 inches H (385 mm x 324 mm x 154 mm). Provide boxes with provisions that enable installation into concrete floors, raised floors, or wood floors without having to purchase additional components or accessories. Provide boxes with ten independent wiring compartments that allow for up to ten receptacles, communication and/or audio/video services. Boxes shall permit feed to adjacent compartments. Boxes shall permit feed to compartments on the opposite side of the box through a tunnel. Six of the ten compartments shall have a minimum wiring capacity of 23-1/2 in3 (597 ml). Four of the ten compartments shall have a minimum wiring capacity of 27 in3 (686 ml). Each of the ten compartments shall have a minimum depth of 3-1/2 inches (89 mm) behind the plate. Provide boxes with removable compartments to facilitate installation and moves, additions, and changes. The compartments shall be removable from the top and back of the floor box. Provide boxes with two cable guides to organize and maintain the cables egress out of the box. Provide boxes with removable knockout plates to allow for the maximum cable pass-through area. The cable pass-through area shall be a minimum of 11-5/8 in2 (7500 mm2). The box shall contain the following number of knockouts: four 3/4-inch trade size, ten 1-inch (25.4) trade size, eight 1-1/4 inches (32 mm) trade size, and two 2 inches (51 mm) trade size. Boxes shall be fully adjustable, accommodating a maximum 2-inch (51mm) pre-concrete pour and a maximum 1/2 inch (12.7 mm) post-concrete pour adjustment. Equip boxes with toggle clamps to allow box to be secured to raised and wood floors. Include mounting brackets with the boxes that will accommodate 15 amp, 20 amp straight blade, 20 amp turn loc, 30 amp straight blade and 30 amp turn loc receptacles. Boxes shall have the ability to accommodate a bracket (EFB-50A) allowing for one 50-amp receptacle. Boxes shall also accommodate Ortronics workstation connectivity and modular adapters, a variety of audio/video devices from most manufacturers, and other open system devices.

b. Model EFB10S-OG Floor Boxes: Manufactured from stamped steel approved for use in above grade and on-grade floor applications. Boxes shall have the ability to accept a component (EFB610-CTR) that will allow the box to be installed in polished concrete or terrazzo floors. Boxes shall be painted with a fusion-bonded epoxy designed for use on metal reinforcement bar and related accessories before encapsulation in concrete, and be approved for use on-grade and above grade floors. Boxes shall be 15-3/16 inches L x 12-5/8 inches W x 6-1/16 inches H (385 mm x 321 mm x 154 mm). Provide boxes with ten independent wiring compartments that allow for up to ten duplex receptacles, communication and/or audio/video services. Boxes shall have removable and relocatable dividers to permit custom configuration of compartments as well as permit feed to adjacent compartments. Boxes shall permit feed to compartments on the opposite side of the box through a tunnel. Six of the ten compartments shall have a minimum wiring capacity of 23-1/2 in3 (597 ml). Four of the ten compartments shall have a minimum wiring capacity of 27 in3 (686 ml). Each of the ten compartments shall have a minimum depth of 3-1/2 inches (89 mm) behind the plate. Provide boxes with removable compartments to facilitate installation. The compartments shall be removable from the top of

16000-64

Page 65:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

the floor box. Provide boxes with two cable guides to organize and maintain the cables egress out of the box. The box shall contain the following number of knockouts: Fourteen 1 inch (25.4 mm) trade size, six 1-1/4 inches (32 mm) trade size, and four 2 inches (51 mm) trade size. Boxes shall be fully adjustable, accommodating a maximum 2 inches (51mm) pre-concrete pour and a maximum 1/2 inch (12.7 mm) post-concrete pour adjustment. Include mounting brackets with the boxes that will accommodate 15 amp, 20 amp straight blade, 20 amp turn loc, 30 amp straight blade and 30 amp turn loc receptacles. Boxes shall have the ability to accommodate a bracket (EFB-50A) allowing for one 50-amp receptacle. Boxes shall also accommodate Ortronics workstation connectivity and modular adapters, a variety of audio/video devices from most manufacturers, and other open system devices.

c. Model EFB10FC Floor Boxes: Manufactured from stamped steel approved for use in 2-hour fire-rated concrete floors. Boxes shall have the ability to accept a component (EFB610-CTR) that will allow the box to be installed in polished concrete or terrazzo floors. Boxes shall have a polyester based backed enamel finished interior (white). Boxes shall be 15-3/16 inches L x 13-7/8 inches W x 4-3/16 inches H (385 mm x 351 mm x 107 mm). Provide boxes with a 21-3/4 inches L x 17-1/4 inches W x 6-1/2 inches H (552 mm x 438 mm x 165 mm) sheet metal concrete pan to ensure that 3-1/4 inches (83 mm) of concrete surrounds the box. Provide boxes with ten independent wiring compartments that allow for up to ten receptacles, communication and/or audio/video services. Boxes shall have removable and repositionable dividers to permit feed to adjacent compartments and reconfiguration of devices. Boxes shall permit feed to compartments on the opposite side of the box through a tunnel. Each of the compartments shall have a minimum wiring capacity of 53 in3 (860 ml). Each of the ten compartments shall have a minimum depth of 3-1/2 inches (89 mm) behind the plate. Provide boxes with two cable guides to organize and maintain the cables egress out of the box. Provide boxes with removable compartments to facilitate installation. The compartments shall be removable from the top of the floor box. Provide boxes with four intumescent services feed stems with a 1-1/4 inches (32 mm) pass-through channel that allows the pathway to close off during a fire. Boxes shall be fully adjustable, accommodating a maximum 2-1/2 inches (64 mm) pre-concrete pour and a maximum 1/2 inch (12.7 mm) post-concrete pour adjustment. Include mounting brackets with the boxes that will accommodate 15 amp, 20 amp straight blade, 20 amp turn loc, 30 amp straight blade and 30 amp turn loc receptacles. Boxes shall have the ability to accommodate a bracket (EFB-50A) allowing for one 50-amp receptacle. Boxes shall also accommodate Ortronics workstation connectivity and modular adapters, a variety of audio/video devices from most manufacturers, and other open system devices.

12. Model EFBFF Floor Boxes:a. Manufactured from stamped steel approved for use on above grade concrete

floors, raised floors and wood floors with the same product. Boxes shall have the ability to accept a component (FP-CTR) that will allow the box to be installed in polished concrete or terrazzo floors. Boxes shall be 7-1/16 inches L x 6-5/8 inches W x 4-1/8 inches H (179 mm x 168 mm x 105 mm). Provide boxes with provisions that enable installation into concrete floors, raised floors, or wood floors without having to purchase additional components or accessories. Provide boxes with two independent wiring compartments that allow for power, communication and/or audio/video services. Each of the two wiring compartments shall have a minimum wiring capacity of 64-1/2 in3 (1056 ml). The box shall be equipped with a metal divider to separate the services and maintain code requirements. The box shall contain the following number of knockouts: four 1/2 inch trade size, four 3/4 inch (19 mm) trade size, one 1 inch (12,7 mm) trade size, six 1-1/4-inches (32 mm) trade size, one 1-1/2-inches (38

16000-65

Page 66:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

mm) trade size, and two 2 inches (51 mm). Boxes shall be fully adjustable, accommodating a maximum 2 inches (51 mm) pre-concrete pour and a maximum 1/2 inch (12.7 mm) post-concrete pour adjustment. Equip boxes with toggle clamps to allow box to be secured to raised and wood floors.

b. Model EFBFF-OG Floor Boxes: Manufactured from stamped steel approved for use in above grade and on-grade floor applications. Boxes shall have the ability to accept a component (FP-CTR) that will allow the box to be installed in polished concrete or terrazzo floors. Boxes shall be painted with a fusion-bonded epoxy designed for use on metal reinforcement bar and related accessories before encapsulation in concrete, and be approved for use on-grade and above grade floors. Boxes shall be 7-1/16 inches L x 6-5/8 inches W x 4-1/8 inches H (179 mm x 168 mm x 105 mm). Provide boxes with provisions that enable installation into concrete floors, raised floors, or wood floors without having to purchase additional components or accessories. Provide boxes with two independent wiring compartments that allow for power, communication and/or audio/video services. Each of the two wiring compartments shall have a minimum wiring capacity of 64-1/2 in3 (1056 ml). The box shall be equipped with a metal divider to separate the services and maintain code requirements. The box shall contain the following number of knockouts: four 1/2 inch (12.7 mm) trade size, four 3/4 inch (19 mm) trade size, one 1-inch (25.4 mm) trade size, six 1-1/4 inches 932 mm) trade size, one 1-1/2 inches (38 mm) trade size, and two 2 inches (51 mm). Boxes shall be fully adjustable, accommodating a maximum 2 inches (51 mm) pre-concrete pour and a maximum 1/2 inch (12.7 mm) post-concrete pour adjustment.

13. Activation Covers:a. Evolution EFB45BT and EFB45CT Series Covers: Manufactured of die-cast

aluminum. Activation covers shall be available in surface mount and flush versions. Provide covers with two gaskets (one for carpet and one for tile) to go under the trim flange to maintain scrub water tightness. Covers shall be 13-7/8 x 9-15/16 x 3/16 inches (352 x 252 x 4 mm). Covers shall be available with a carpet recess area or a solid lid. Secure the cover to the flange and enable cover to rotate greater than 180 degrees to reduce trip hazards and provide maximum amount of working space. Provide covers with spring-loaded self-closing slide egress doors to reduce egress opening when cables are exiting and reduce trip hazards. Each of the two egress openings shall have a minimum of 2 sq in (1290 sq mm), or a minimum of 4 sq in (2581 sq mm) per cover assembly.1) Powder coat finish, color shall be aluminum, black, gray, brass, nickel,

bronze.b. Evolution EFB610BT and EFB610CT Series Covers: Manufactured of die-cast

aluminum. Activation covers shall be available in surface mount and flush versions. Provide covers with two gaskets (one for carpet and one for tile) to go under the trim flange to maintain scrub water tightness. Covers shall be 16-15/16 inches x 12-1/2 inches x 3/16 inch (430 mm x 318 mm x 4 mm). Covers shall be available with a carpet recess area or a solid lid. Secure the cover to the flange and enable cover to rotate greater than 180 degrees to reduce trip hazards and provide maximum amount of working space. Provide covers with spring-loaded self-closing slide egress doors to reduce egress opening when cables are exiting and reduce trip hazards. Each of the two egress openings shall have a minimum of 4 in2 (102 mm2), or a minimum of 8 in2 (203 mm2) per cover assembly.1) Powder coat finish, color shall be aluminum, black, gray, brass, nickel,

bronze.c. FloorPort FPFFTC Series Covers: Manufactured of die-cast aluminum or die-

cast zinc, and available in brushed aluminum finish and powder-coated paint finishes. Activation covers shall be available in flanged version. Covers shall

16000-66

Page 67:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

come equipped with one 1 inch (25.4 mm) trade size screw plug opening and one combination 1-1/4 inches (32 mm) and 2 inches (51 mm) trade size screw plug.1) Flanged covers shall be 7-3/4 inches L x 6-9/16 inches W (197 mm x 167

mm).a) Powder coat finish, color shall be black, gray, brass, nickel,

bronze.

K. Electrical floor boxes and fittings shall be manufactured by Legrand/Wiremold.1. Classification and Use: Floor boxes shall have been examined and tested by

Underwriters Laboratories Inc. to meet UL514A, UL514C, UL514D and Canadian Standard C22.2 and bear the U.S. and Canadian UL Listing Mark. Floor boxes shall also have been tested by Underwriters Laboratories Inc. and classified for fire resistance and bear the U.S. and Canadian UL Classification Mark.

2. Floor Boxes, General: Omnibox Series Floor Boxes for use on above-grade and on- or below-grade concrete floors. Boxes shall be compatible with complete line of Ortronics® workstation connectivity outlets and modular inserts.a. Floor boxes provide the interface between power, communication and

audio/video (A/V) cabling in above-grade and on-grade concrete floors and the workstation or activation location where power and communication and/or A/V device outlets are required. Boxes shall provide flush device outlets that will not obstruct the floor area. Refer to Drawings for size and types.

b. Floor boxes shall be available in one-, two-, or three-gang configurations and in stamped-steel and cast-iron versions. Boxes shall be rectangular in shape and available in deep and shallow versions. All boxes shall also provide 1-3/4 inches (44 mm) pre-pour and 1/2 inch (12.7 mm) post-pour adjustment. Provide boxes with a removable barrier between individual compartments for greater capacity when required.

c. The minimum concrete pour depth shall be 2-1/2 inches (64 mm) for the shallow versions and 3-1/2 inches (89 mm) for the deep versions. Each box shall contain four locations to accommodate leveling for pre-concrete pour adjustment. Provide each box with four leveling screws for pre-pour adjustment.

3. Cast-Iron Floor Boxes: Series 880C Floor Boxes; manufactured from cast-iron and approved for use in above grade and on-grade floor applications. Paint interior and exterior of boxes. Minimum depth of deep boxes shall be 3-7/16 inches (87 mm). Minimum depth of shallow boxes shall be 2-7/16 inches (62 mm). Overall box dimensions for both shallow and deep boxes shall be as follows:a. One Gang (W x L): 5-3/16 x 4-3/8 inches (132 x 111 mm).b. Two Gang (W x L): 5-3/16 x 8-1/2 inches (132 x 216 mm).c. Three Gang (W x L): 5-3/16 x 12-1/2 inches (132 x 318 mm).d. One-gang deep boxes shall provide at least 48 cubic inches (787 ml) of Device

Wiring Chamber volume. One-gang shallow boxes shall provide at least 34 cubic inches (557 ml) of Device Wiring Chamber volume. Both versions shall provide at least four 1 inch (25.4 mm) threaded conduit openings to feed cabling to the floor box.

e. Two-gang deep boxes shall provide at least a total of 94 cubic inches (1541 ml) of Device Wiring Chamber volume. This total volume shall be divided between the two gangs with 45 cubic inches (738 ml) of volume in the first gang and 49 cubic inches (803ml) of volume in the second gang.1) Version shall provide at least six 1 inch (25.4 mm) threaded conduit

openings to feed cabling to the floor box.f. Two-gang shallow boxes shall provide at least a total of 76 cubic inches (1246

ml) of Device Wiring Chamber volume. This total volume shall be divided between the two gangs with 36 cubic inches (590 ml) of volume in the first gang and 40 cubic inches (656 ml) of volume in the second gang.1) Version shall provide at least six 1 inch (25.4 mm) threaded conduit

16000-67

Page 68:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

openings to feed cabling to the floor box.g. Three-gang deep boxes shall provide at least a total of 160 cubic inches (2623

ml) of Device Wiring Chamber volume. This total volume shall be divided among the three gangs with 53 cubic inches (869 ml) of volume in each of the outside gangs and 54 cubic inches (885 ml) of volume in the center gang.1) Version shall provide at least six 1 inch (25.4 mm) threaded conduit

openings to feed cabling to the floor box.h. Three-gang shallow boxes shall provide at least a total of 118 cubic inches

(1934ml) of Device Wiring Chamber volume. This total volume shall be divided among the three gangs with 39 cubic inches (639 ml) of volume in each of the outside gangs and 40 cubic inches (656 ml) of volume in the center gang.1) Version shall provide at least six 1 inch (25.4 mm) threaded conduit

openings to feed cabling to the floor box.4. Stamped Steel Floor Boxes: Series 880 Floor Boxes; concrete-tight construction,

manufactured from stamped steel and approved for use on above grade concrete floors. Minimum depth of deep boxes shall be 3-15/32 inches (88 mm). Minimum depth of shall boxes shall be 2-15/32 inches (63 mm). Overall box dimensions for both shallow and deep boxes shall be as follows:a. One Gang (W x L): 4-13/16 x 3-23/32 inches (122 x 94 mm).b. Two Gang (W x L): 4-13/16 x 7-15/16 inches (122 x 202 mm).c. Three Gang (W x L): 4-13/16 x 12 inches (122 x 305 mm).d. One-gang deep boxes shall provide at least 53 cubic inches (869 ml) of Device

Wiring Chamber volume. The deep version shall provide at least three 1/2 inch (12.7 mm), five 3/4 inch (19.1 mm) and two 1 inch (25.4 mm) conduit knockout locations to feed cabling to the floor box.

e. One-gang shallow boxes shall provide at least 37 cubic inches (607 ml) of Device Wiring Chamber volume. The shallow version shall provide at least five 1/2 inch (12.7 mm) and five 3/4 inch (19.1 mm) conduit knockout locations to feed cabling to the floor box.

f. Two-gang deep boxes shall provide at least a total of 117 cubic inches (1918 ml) of Device Wiring Chamber volume. This total volume shall be divided between the two gangs with 58 cubic inches (951 ml) of volume in the first gang and 59 cubic inches (967 ml) of volume in the second gang. The deep version shall provide at least four 1/2 inch (12.7 mm), eight 3/4 inch (19.1 mm) and four 1 inch (25.4 mm) conduit knockout locations to feed cabling to the floor box.

g. Two-gang shallow boxes shall provide at least a total of 80 cubic inches (1312 ml) of Device Wiring Chamber volume. This total volume shall be divided between the two gangs with 40 cubic inches (656 ml) of volume in each gang. The shallow version shall provide at least eight 1/2 inch (12.7 mm) and eight 3/4 inch (19.1 mm) conduit knockout locations to feed cabling to the floor box.

h. Three-gang deep boxes shall provide at least a total of 180 cubic inches (2951 ml) of Device Wiring Chamber volume. This total volume shall be divided among the three gangs with 56 cubic inches (918 ml) of volume in each of the outside gangs and 68 cubic inches (1115 ml) of volume in the center gang. The deep version shall provide at least five 1/2 inch (12.7 mm), eleven 3/4 inch (19.1 mm), and six 1 inch (25.4 mm) conduit knockout locations to feed cabling to the floor box.

i. Three-gang shallow boxes shall provide at least a total of 126 cubic inches (2065 ml) of Device Wiring Chamber volume. This total volume shall be divided among the three gangs with 39 cubic inches (639 ml) of volume in each of the outside gangs and 48 cubic inches (787 ml) of volume in the center gang. The shallow version shall provide at least eleven 1/2 inch (12.7 mm) and eleven 3/4 inch (19.1 mm) conduit knockout locations to feed cabling to the floor box.

5. Covers and Flanges:a. All floor box options shall accept brass, brushed aluminum, powder coated

aluminum, and nonmetallic cover plates and flanges. Flanges for brass,

16000-68

Page 69:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

brushed aluminum, powder coated aluminum, and nonmetallic shall be available for one, two, or three gang applications and install on the boxes. Each flange shall provide 1/2 inch (12.7 mm) of adjustment to accommodate various floor covering and concrete pour depths. All cover assemblies shall have an integral design which keeps out water, dirt, and debris from the power and communication components.

b. Brass, Brushed Aluminum, Powder coated aluminum, and Nonmetallic Flanges and Cover Plates: Flange dimensions shall be as follows:1) One Gang Brass Finish:

a) Width: 5.060 in (128.524 mm).b) Length: 6.080 in (154.432 mm).

2) One Gang Aluminum Finish:a) Width: 4.920 in (124.968 mm).b) Length: 5.940 in (150.876 mm).

3) One Gang Powder Coated Finish:a) Width: 4.920 in (124.968 mm).b) Length: 5.940 in (150.876 mm).

4) One Gang Nonmetallic Finish:a) Width: 4.750 in (121.000 mm).b) Length: 5.750 in (146.000 mm).

5) Two Gang Brass Finish:a) Width: 9.185 in (233.299 mm).b) Length: 6.080 in (154.432 mm).

6) Two Gang Aluminum Finish:a) Width: 9.045 in (229.743 mm).b) Length: 5.940 in (150.876 mm).

7) Two Gang Powder Coated Finish:a) Width: 9.045 in (229.743 mm).b) Length: 5.940 in (150.876 mm).

8) Two Gang Nonmetallic Finish:a) Width: 8.875 in (225.000 mm).b) Length: 5.750 in (146.000 mm).

9) Three Gang Brass Finish:a) Width: 13.310 in (338.074mm).b) Length: 6.080 in (154.432 mm).

10) Three Gang Aluminum Finish:a) Width: 13.170 in (334.518 mm).b) Length: 5.940 in (150.876 mm).

11) Three Gang Powder Coated Finish:a) Width: 13.170 in (334.518 mm).b) Length: 5.940 in (150.876 mm).

12) Three Gang Nonmetallic Finish:a) Width: 13.000 in (330.000 mm).b) Length: 5.750 in (146.000 mm).

c. All brass, brushed aluminum, powder coated aluminum, and nonmetallic flanges shall be approved for use on carpet, tile, or wood covered floor applications. Brass and brushed aluminum flanges and cover plates shall have a buffed appearance and be protected with a lacquer finish. Powder coated aluminum flanges are available in black, brass, nickel, bronze, and gray finishes. Nonmetallic flanges and cover plates shall be provided in a black, brown, or gray finish. All flanges shall also accommodate Ortronics workstation connectivity outlets and modular inserts, and Wiremold Connectivity Modular Insert System. Modular inserts shall snap directly into each flange through use of a mounting bezel.

d. Brushed aluminum, powder coated aluminum, and nonmetallic cover plate options shall seat inside either the aluminum or nonmetallic flanges and be

16000-69

Page 70:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

flush with the finished floor. Aluminum and nonmetallic cover plate dimensions shall be 3.29 inches (83.566 mm) W x 4.310 inches (109.474 mm) L. Brass cover plate dimensions shall be 3.156 inches (80.162 mm) W x 4.182 inches (106.223 mm) L. Brass cover plates shall seat inside only brass flanges and be flush with the finished floor. All cover plate options shall provide for both power and communication services. Communication covers shall accommodate Ortronics workstation connectivity outlets and modular inserts, and Wiremold Connectivity Modular open adapter system.

6. Communication Devices and Accessories:a. The floor box manufacturer shall have available a complete line of Ortronics

workstation connectivity outlets and modular inserts, and Activate Connectivity Modular Inserts for UTP (including Cat 5), fiber optic, coaxial, and other cabling types with faceplates and bezels to facilitate mounting.

L. Floor boxes and fittings shall be Resource RFB Floor Box Series manufactured by Legrand/Wiremold.1. Floor Box:

a. RFB2 Series Floor Boxes: Manufactured from stamped steel and approved for use on above grade floors. The box shall be 13-1/8 inches L x 6-1/2 inches W x 3-7/16 inches H (333 mm x 165 mm x 87 mm). Provide the box with two independent wiring compartments that allow capacity for up to two duplex receptacles, communication and audio/video services. The box shall permit tunneling from end power compartment to end power compartment. Provide each of the two compartments with a minimum wiring capacity of 50 cu in (822 ml3). Two (compartments shall have a minimum of 3 inches (76 mm) of space behind the device plates. The box shall include the following number of conduit knockouts: two 1/2 inch (12.7 mm), six 3/4 inch (19.1 mm), two 1-inch (25.4 mm) and four 1-1/4 inches (32 mm). The box shall be fully adjustable, providing a maximum of 1-3/8 inches (35 mm) pre-pour adjustment, and a maximum of 3/4 inch (19.1 mm) after-pour adjustment. The box shall include a series of device mounting plates that will accept both duplex power devices as well as plates that will accommodate Ortronics workstation connectivity outlets and modular adapters, Legrand AVIP audio/video device plates, and other open system devices.

b. RFB2-SS Series Floor Boxes: Manufactured from stamped steel and approved for use on above grade floors. The box shall be 13-1/8 inches L x 6-1/2 inches W x 2-5/8 inches H (333 mm x 165 mm x 67 mm). Provide the box with two independent wiring compartments that allow capacity for up to two duplex receptacles, communication and/or audio/video services. The box shall permit tunneling from end power compartment to end power compartment. Provide each of the two compartments with a minimum wiring capacity of 38 cu in (622 ml3). Two compartments shall have a minimum of 3 inches (76 mm) of space behind the device plates. The box shall contain the following number of conduit knockouts: two 1/2-inch (12.7 mm) and twelve 3/4-inch (19.1 mm). The box shall be fully adjustable, providing a maximum of 1-3/8 inches (35 mm) pre-pour adjustment, and a maximum of 3/4 inch (19.1 mm) after-pour adjustment. The box shall include a series of device mounting plates that will accept both duplex power devices as well as plates that will accommodate Ortronics workstation connectivity outlets and modular adapters, Legrand AVIP audio/video device plates, and other open system devices.

c. RFB2-OG Series Floor Boxes: Manufactured from stamped steel and painted with a fusion-bonded epoxy designed for use on metal reinforcement bar and related accessories before encapsulation in concrete, and be approved for use on grade and above grade floors. The box shall be 13-1/8 inches L x 6-1/2 inches W x 3-7/16 inches H (333 mm x 165 mm x 87 mm). Provide the box with two independent wiring compartments that allow capacity for up to two duplex

16000-70

Page 71:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

receptacles, communication and/or audio/video services. The box shall permit tunneling from end power compartment to end power compartment. Provide each of the two compartments with a minimum wiring capacity of 50 cu in (822 ml3). Two compartments shall have a minimum of 3 inches (76 mm) of space behind the device plates. The box shall include the following number of conduit knockouts: two 1/2 inch (12.7 mm), six 3/4 inch (19.1mm), two 1 inch (25.4 mm) and four 1-1/4 inches (32 mm). The box shall be fully adjustable, providing a maximum of 1-3/8 inches (35 mm) pre-pour adjustment, and a maximum of 3/4 inch (19.1 mm) after-pour adjustment. The box shall include a series of device mounting plates that will accept both duplex power devices as well as plates that will accommodate Ortronics workstation connectivity outlets and modular adapters, Legrand AVIP audio/video device plates, and other open system devices.

d. RFB4 and RFB4-4DB Series Floor Boxes: Manufactured from stamped steel and approved for use on above grade floors. The box shall be 12-3/4 inches L x 10 inches W x 3-7/16 inches H (324 mm x 254 mm x 87 mm). Provide the box with four independent wiring compartments that allow capacity for up to four duplex receptacles, communication and/or audio/video services. The RFB4 Series Box shall permit tunneling from end power compartment to end power compartment. The RFB4-4DB Series Box shall permit tunneling from adjacent or opposite compartments. Two of the four compartments shall have a minimum wiring capacity of 16.4 cu in (269 cu cm), one compartment shall have a minimum capacity of 32.3 cu in (529 cu cm), and one compartment shall have a minimum capacity of 50 cu in (820 cu cm). Four compartments shall have a minimum of 2 inches (51 mm) of space behind the device plates. The box shall include the following number of conduit knockouts: one 1/2 inch (12.7 mm), three 1 inch (25.4 mm), six 3/4 inch (19.1 mm), and six 1-1/4 inches (32 mm). The box shall be fully adjustable, providing a maximum of 1-7/8 inches (47.7 mm) pre-pour adjustment, and a maximum of 3/4 inch (19.1 mm) after-pour adjustment. The box shall include a series of device mounting plates that will accept both duplex power devices as well as plates that will accommodate Ortronics workstation connectivity outlets and modular adapters, Legrand AVIP audio/video device plates, and other open system devices.

e. RFB4-CI-1 and RFB-CI-NA Series Floor Boxes: Manufactured from cast-iron and approved for use on grade and above grade floors. The box shall be 14-1/2 inches L x 11-7/8 inches W x 3-7/16 inches H (368 mm x 302 mm x 87 mm). Provide the box with four independent wiring compartments that allow capacity for up to four duplex receptacles and/or communication services. The box shall permit tunneling from adjacent or opposite compartments. Two of the four compartments shall have a minimum wiring capacity of 27 cu in (443cu cm) and two compartments shall have a minimum wiring capacity of 36 cu in (590cu cm). Four compartments shall have a minimum of 2 inches (51 mm) of space behind the device plates. The box shall include the following number of conduit hubs: four 1-inch (25.4 mm) and four 1-1/4 inches (32 mm). The box shall be fully adjustable, providing a maximum of 1-7/8 inches (48 mm) pre-pour adjustment, and a maximum of 3/4 inch (19.1 mm) after-pour adjustment. The box shall include a series of device mounting plates that will accept both duplex power devices as well as plates that will accommodate Ortronics workstation connectivity outlets and modular adapters, Legrand AVIP audio/video device plates, and other open system devices.

f. RFB4-SS Series Floor Boxes: Manufactured from stamped-steel and approved for use on above grade floors. The box shall be 13-5/8 inches L x 10 inches W x 2-7/16 inches H (346 mm x 254 mm x 62 mm). Provide the box with four independent wiring compartments that allow capacity for up to four duplex receptacles, communication and/or audio/video services. The box shall permit feed through tunneling from adjacent compartments. Two of the four

16000-71

Page 72:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

compartments shall have a minimum wiring capacity of 15.7 cu in (257 cu cm) and two compartments shall have a minimum wiring capacity of 31.2 cu in (511 cu cm). Four compartments shall have a minimum of 2 inches (51 mm) of space behind the device plates. The box shall contain the following number of conduit knockouts: two 1/2 inch (12.7 mm), six 3/4 inch (19.1 mm), and eight 1 inch (25.4 mm). The box shall be fully adjustable, providing a maximum of 1-7/8 inches (48 mm) pre-pour adjustment, and a maximum of 3/4 inch (19.1 mm) after-pour adjustment. The box shall include a series of device mounting plates that will accept both duplex power devices as well as plates that will accommodate Ortronics workstation connectivity outlets and modular adapters, Legrand AVIP audio/video device plates, and other open system devices.

g. RFB4E Series Floor Boxes: Manufactured from stamped steel and approved for use on above grade floors. The box shall be 13-1/8 inches L x 13-1/8 inches W x 4-1/16 inches H (333 mm x 333 mm x 103 mm). Provide the box with four independent wiring compartments that allow capacity for up to four duplex receptacles, communication and/or audio/video services. The box shall permit feed through removable barriers from adjacent compartments. Four compartments shall have a minimum wiring capacity of 75 cu in (1230 cu cm). Four compartments shall have a minimum of 3-1/2 inches (89 mm) of space behind the device plates. The box shall contain the following number of conduit knockouts: six 3/4 inch (19.1 mm), ten 1 inch (25.4 mm), and eight 1-1/4 inches (32 mm). The box shall have two removable knockout plates that can be replaced with a 2 inches (51 mm) trade size conduit hub (2HUB). The box shall be fully adjustable, providing a maximum of 2 inches (35 mm) pre-pour adjustment, and a maximum of 3/4 inch (19.1 mm) after-pour adjustment. The box shall include a series of device mounting plates that will accept both duplex power devices as well as plates that will accommodate Ortronics workstation connectivity outlets and modular adapters, Legrand AVIP audio/video device plates, and other open system devices.

h. RFB4E-OG Series Floor Boxes: Manufactured from stamped steel and painted with a fusion-bonded epoxy designed for use on metal reinforcement bar and related accessories before encapsulation in concrete, and approved for use on grade and above grade floors. The box shall be 13-1/8 inches L x 13-1/8 inches W x 4-1/16 inches H (333 mm x 333 mm x 103 mm). Provide the box with four independent wiring compartments that allow capacity for up to four duplex receptacles, communication and/or audio/video services. The box shall permit feed through removable barriers from adjacent compartments. Four compartments shall have a minimum wiring capacity of 75 cu in (1230 cu cm). Four compartments shall have a minimum of 3-1/2 inches (89 mm) of space behind the device plates. The box shall contain the following number of conduit knockouts: six 3/4 inch (19.1 mm), ten 1 inch (25 mm), and eight 1-1/4 inches (32 mm). The box shall have two removable knockout plates that can be replaced with a 2 inches (51 mm) trade size conduit hub (2HUB). The box shall be fully adjustable, providing a maximum of 2 inches (51 mm) pre-pour adjustment, and a maximum of 3/4 inch (19.1 mm) after-pour adjustment. The box shall include a series of device mounting plates that will accept both duplex power devices as well as plates that will accommodate Ortronics workstation connectivity outlets and modular adapters, Legrand AVIP audio/video device plates, and other open system devices.

i. RFB6 Series Floor Boxes: Manufactured from stamped steel and approved for use on above grade floors. The box shall be 13-1/8 inches L x 12-1/2 inches W x 3-1/4 inches H (333mm x 317mm x 83mm). Provide the box with six independent wiring compartments that allow capacity for up to six duplex receptacles, communication and/or audio/video services. The box shall permit feed through tunneling from adjacent compartments. Two of the six compartments shall have a minimum wiring capacity of 23 cu in (376 cu cm)

16000-72

Page 73:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

and four compartments shall have a minimum wiring capacity of 52 cu in (850 cu cm). Four of the six compartments shall have a minimum of 3-1/4 inches of space behind the device plates and two of the six compartments shall have a minimum of 2-3/8 inches (60 mm) of space behind the device plates. The box shall contain the following number of conduit knockouts: twelve 3/4 inch (19.1 mm), four 1 inch (25 mm), and twelve 1-1/4 inches (32 mm). The box shall be fully adjustable, providing a maximum of 1-3/8 inches (35 mm) pre-pour adjustment, and a maximum of 3/4 inch (19.1 mm) after-pour adjustment. The box shall include a series of device mounting plates that will accept both duplex power devices as well as plates that will accommodate Ortronics workstation connectivity outlets and modular adapters, Legrand AVIP audio/video device plates, and other open system devices.

j. RFB6-OG Series Floor Boxes: Manufactured from stamped steel and painted with a fusion-bonded epoxy designed for use on metal reinforcement bar and related accessories before encapsulation in concrete, and approved for use on grade and above grade floors. The box shall be 13-1/8 inches L x 12-1/2 inches W x 3-1/4 inches H (333 mm x 317 mm x 83 mm). Provide the box with six independent wiring compartments that allow capacity for up to six duplex receptacles, communication and/or audio/video services. The box shall permit feed through tunneling from adjacent compartments. Two of the six compartments shall have a minimum wiring capacity of 23 cu in (376 cu cm) and four compartments shall have a minimum wiring capacity of 52 cu in (850 cu cm). Four of the six compartments shall have a minimum of 3-1/4 inches (83 mm) of space behind the device plates and two of the six compartments shall have a minimum of 2-3/8 inches (60 mm) of space behind the device plates. The box shall contain the following number of conduit knockouts: twelve 3/4 inch (19.1 mm), four 1 inch (25.4 mm), and twelve 1-1/4 inches (32 mm). The box shall be fully adjustable, providing a maximum of 1-3/8 inches (35 mm) pre-pour adjustment, and a maximum of 3/4 inch (19.1 mm) after-pour adjustment. The box shall include a series of device mounting plates that will accept both duplex power devices as well as plates that will accommodate Ortronics workstation connectivity outlets and modular adapters, Legrand AVIP audio/video device plates, and other open system devices.

k. RFB6E Series Floor Boxes: Manufactured from stamped steel and approved for use on above grade floors. The box shall be 13-1/8 inches L x 12-1/2 inches W x 4 inches H (333 mm x 317 mm x 102 mm). Provide the box with six independent wiring compartments that allow capacity for up to six duplex receptacles, communication and/or audio/video services. The box shall permit feed through tunneling from adjacent compartments through 1-1/4 inches grommet openings. Two of the six compartments shall have a minimum wiring capacity of 23 cu in (376 cu cm) and four compartments shall have a minimum wiring capacity of 52cu in (850 cu cm). Four of the six compartments shall have a minimum of 3-1/4 inches (83 mm) of space behind the device plates and two of the six compartments shall have a minimum of 2-3/8 inches (60 mm) of space behind the device plates. The box shall contain the following number of conduit knockouts: twelve 3/4-inch (19.1 mm), four 1 inch (25.4 mm), and twelve 1-1/4 inches (32 mm). The box shall be fully adjustable, providing a maximum of 1-3/8 inches (35 mm) pre-pour adjustment, and a maximum of 3/4-inch (19.1 mm) after-pour adjustment. The box shall include a series of device mounting plates that will accept both duplex power devices as well as plates that will accommodate Ortronics workstation connectivity outlets and modular adapters, Legrand AVIP audio/video device plates, and other open system devices.

l. RFB6E-OG Series Floor Boxes: Manufactured from stamped steel and painted with a fusion-bonded epoxy designed for use on metal reinforcement bar and related accessories before encapsulation in concrete, and approved for use on

16000-73

Page 74:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

grade and above grade floors. The box shall be 13-1/8 inches L x 12-1/2 inches W x 4 inches H (333 mm x 317 mm x 102 mm). Provide the box with six independent wiring compartments that allow capacity for up to six duplex receptacles, communication and/or audio/video services. The box shall permit feed through tunneling from adjacent compartments. Two of the six compartments shall have a minimum wiring capacity of 23 cu in (376 cu cm) and four compartments shall have a minimum wiring capacity of 52cu in (850 cu cm). Four of the six compartments shall have a minimum of 3-1/4 inches (83 mm) of space behind the device plates and two of the six compartments shall have a minimum of 2-3/8 inches (60 mm) of space behind the device plates. The box shall contain the following number of conduit knockouts: twelve 3/4-inch (19.1 mm), four 1-inch (25.4 mm), and twelve 1-1/4 inches (32 mm). The box shall be fully adjustable, providing a maximum of 1-3/8 inches (35 mm) pre-pour adjustment, and a maximum of 3/4 inch (19.1 mm) after-pour adjustment. The box shall include a series of device mounting plates that will accept both duplex power devices as well as plates that will accommodate Ortronics workstation connectivity outlets and modular adapters, Legrand AVIP audio/video device plates, and other open system devices.

2. Activation Covers:a. FloorPort FPCT, FPBT, and FPFFT Series Covers: Manufactured of die-cast

aluminum or die-cast zinc, and available in brushed aluminum finish and powder-coated paint finishes (black, gray, bronze, nickel and brass). Activation covers shall be available in flanged and flangeless versions. Covers shall be available with options for tile or carpet inserts, or flush covers. The cover's hinge shall allow for the cover to open 180 degrees. The furniture feed covers shall come equipped with one 1-inch trade size screw plug opening and one combination 1-1/4 inches and 2-inches (32 mm and 51 mm) trade size screw plug.1) Flanged covers shall be 7-3/4 inches L x 6-9/16 inches W (197 mm x 167

mm).2) Flangeless covers shall be 6-3/4 inches L x 5-9/16 inches W (171 mm x

142 mm).b. 6CT, 6CTC, 6CFFTC, 8CTC, and 8CT Series Covers: Manufactured of die-cast

aluminum alloy and available in powder-coated gray, black, brass, nickel or bronze finish. The covers shall be available in carpet and tile versions. Provide covers with two gaskets (one for carpet and one for tile) to go under the trim flange to maintain scrub water tightness. The activation cover for the 8CTC and 8CT series shall be 9-1/4 inches (235 mm) in diameter. The activation cover for the 6CT and 6CTC series shall be 7-1/4 inches (184 mm) in diameter and the activation cover for the 6CFFTC series shall be 7-3/4 inches (197 mm) in diameter. The carpet covers shall be surface mounted and the tile covers shall be flush with the finished floor covering. The covers shall have spring loaded slides to allow cables to egress out of the unit and maintain as small an egress opening as possible.

c. The covers shall have been evaluated by UL to meet the applicable U.S. and Canadian safety standards for scrub water exclusion when used on tile, terrazzo, wood, and carpet covered floors.

3. Communication Modules Mounting Accessories:a. The floor box manufacturer shall provide a complete line of faceplates and

bezels to facilitate mounting of UTP, STP (150 ohm), fiber optic, coaxial, and communication devices. The box shall provide a series of device mounting plates that will accommodate Ortronics workstation connectivity outlets and modular adapters, and other open system devices.

b. Provide a minimum concrete pour depth of 3-7/16 inches (87 mm) plus 1/16 inch (1.6 mm) above the top of the box for the RFB4, RFB4-4DB, RFB2, and the RFB2-OG Series Boxes; 2-7/16 inches (62 mm) plus 1/16 inch (1.6 mm) for

16000-74

Page 75:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

the RFB4-SS and RFB2-SS Series Boxes; and 3-7/16 inches (87 mm) plus 13/16 inch (21 mm) above the top of the box for the RFB4-CI-1, RFB6, and RFB6-OG Series Boxes; and 4-1/16 inches (103 mm) above the top of the RFB4E and RFB4E-OG Series Boxes; and 4 inches (102 mm) above the top of the RFB6E and RFB6E-OG Series Boxes. Provide the box with four locations to accommodate leveling for pre-concrete pour adjustment and include four leveling screws for the pre-pour adjustment.

2.9 FIRE CLASSIFIED FLOOR BOXES

A. Fire classified floor boxes and fittings shall be manufactured by Legrand/Wiremold.

B. Classification and Use: Fire classified floor boxes shall have been examined and tested by Underwriters Laboratories Inc. to meet UL514A, UL514C, UL514D, UL263, and Canadian Standard C22.2 and bear the U.S. and Canadian UL Listing Mark. Floor boxes are approved for use in recessed and flush floor construction and meet and exceed the UL scrub water exclusion test.1. Floor boxes shall be classified for use in 1, 1-1/2, 2, or 3-hour rated floors and 1, 1-

1/2, 2, or 3-hour rated floors employing unprotected steel floor units and concrete toppings (D900 Series designs), or concrete floors with suspended ceilings. Fire resistive designs with suspended ceilings shall have provisions for accessibility in the ceiling below the floor boxes.

2. These devices are not suitable for wet or damp locations, or other areas subject to saturation with water or other liquids such as commercial kitchens.

3. Floor boxes shall be suitable for use in air handling spaces in accordance with Section 300-22(c) of the National Electrical Code.

4. Fire Classified Floor Boxes: 8801S-FC, 8801S-FC2, 8802S-FC, 8802S-FC12, 8803S-FC, 8803S-FC12, RFB2S-FC, RFB2S-FC12, RFB4S-FC, RFB4S-FC12, 880MPFC, 881FC, EFB6S-FC, EFB6S-FC1122, EFB6S-FC2222, EFB8S-FC, EFB8S-FC1122, EFB8S-FC2222, EFB10S-FC, EFB10S-FC1122, EFB10S-FC2222 Fire Classified Floor Boxes manufactured by Legrand/Wiremold.a. Fire classified floor boxes provide an interface between power, communication

and audio/visual (A/V) cabling in an above grade concrete floor and the workstation or activation location where power, communication and/or A/V device outlets are required. These devices provide flush and recessed outlets that will not obstruct the floor area. Refer to the Drawings for types.

b. Fire classified floor boxes shall be compatible with the complete line of Ortronics workstation connectivity outlets and modular inserts, and Wiremold's CM series open system adapters.

c. Floor boxes shall be suitable for use in air handling spaces in accordance with Section 300-22(c) of the National Electrical Code.

5. Omnibox 880 Series Fire Classified Floor Boxes: Boxes shall be available in one-, two-, or three-gang configurations and available in a stamped-steel version. Boxes shall be rectangular in shape and provide pre- and post-pour adjustment. The two- and three-gang boxes shall also provide a removable barrier between the individual compartments for greater capacity when required.a. Body: Boxes shall be manufactured from stamped steel and formed. Boxes

shall be available in one-, two-, or three-gang configurations. The 8801S-FC, 8802S-FC, and 8803S-FC shall have a minimum concrete depth of 2 inches (51 mm) and a maximum concrete depth of 5-1/4 inches (133 mm). The 880S1-FC2, 8802S-FC12, & 8803S-FC12 shall have a minimum concrete depth of 2 inches (51 mm) and a maximum concrete depth of 6-1/2 inches (165 mm). Overall box dimensions shall be as follows:1) One-gang: 4-13/16 inches (122 mm) W x 3-23/32 inches (94 mm) L.2) Two-gang: 4-13/16 inches (122 mm) W x 7-15/16 inches (20 2mm) L.3) Three-gang: 4-13/16 inches (122 mm) W x 12 inches (305 mm) L.

16000-75

Page 76:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

b. One-gang Boxes: Item No. 8801S-FC and 8801S-FC2; shall provide at least 53 cu in (869 ml) of device wiring chamber volume. The 8801S-FC boxes shall include one (intumescent stem with a 1-1/4 inches (31 mm) diameter pass-through channel that allows the pathway to close off during a fire. The 8801S-FC2 boxes shall include one intumescent stem with a 2 inches (51 mm) diameter pass-through channel that allows the pathway to close off during a fire. The 8801S-FC shall be fire classified to restore the fire rating of the floor structure for up to 2 hours. The 8801S-FC2 floor boxes shall be fire classified to restore the fire rating of the floor structure for up to 3 hours. Provide boxes with a 14-1/2 inches L x 11-3/8 inches W x 3-1/2 inches H (367 mm x 289 mm x 90 mm) sheet metal concrete pan to ensure that 3-1/4 inches (83 mm) of concrete surrounds the box.

c. Two-gang Boxes: Item No. 8802S-FC and 8802S-FC12; shall provide at least a total of 117 cu in (1918 ml) of device wiring chamber volume. This total volume shall be divided evenly between the two gangs with 58.5 cu in (958 ml) of volume in each gang. The 8802S-FC boxes shall include two intumescent stems with a 1-1/4 inches (31 mm) diameter pass-through channel that allows the pathway to close off during a fire. The 880S2-FC12 boxes shall include two intumescent stems with one stem with a 1-1/4 inches (31 mm) diameter pass-through channel and one stem with a 2 inches (51 mm) diameter pass-through channel that allows the pathway to close off during a fire. The 8801S-FC shall be fire classified to restore the fire rating of the floor structure for up to 2 hours. The 8801S-FC2 floor boxes shall be fire classified to restore the fire rating of the floor structure for up to 3 hours. Provide boxes with a 14-1/2 inches L x 11-3/8 inches W x 3-1/2 inches H (367 mm x 289 mm x 90 mm) sheet metal concrete pan to ensure that 3-1/4 inches (83 mm) of concrete surrounds the box.

d. Three-gang Boxes: Item No. 8803S-FC and 8803S-FC12; shall provide at least a total of 180 cu in (2951 ml) of device wiring chamber volume. This total volume shall be divided among the three gangs with 54 cu in (885 ml) of volume in each of the outside gangs and 67.5 cu in (1106 ml) of volume in the center gang. The 8803S-FC boxes shall include three intumescent stems with a 1-1/4 inches (31 mm) diameter pass-through channel that allows the pathway to close off during a fire. The 8803S-FC12 boxes shall include three intumescent stems, one with a 1-1/4 inches (31 mm) diameter pass-through channel and two with 2-inches (51 mm) diameter pass-through channels that allows the pathway to close off during a fire. Provide boxes with a 20 inches L x 11-3/8 inches W x 3-1/2 inches H (507 mm x 289 mm x 90 mm) sheet metal concrete pan to ensure that 3-1/4 inches (83 mm) of concrete surrounds the box.

e. Activation Cover: All floor box options shall accept brass and aluminum cover plates and flanges. Flanges for brass and aluminum shall be available for one-, two-, or three-gang applications and install on the previously mentioned boxes. The aluminum flanges and covers are available in a brushed aluminum finish and five powder-coated colors (black, brass, nickel, bronze, and gray). Each flange shall provide 1/2 inch (12.7 mm) of adjustment to accommodate various floor covering and concrete pour depths.

f. Communication covers shall accommodate Ortronics workstation connectivity outlets and modular inserts, and Wiremold Connectivity Modular Insert System.

g. Flanges: Brass and aluminum flanges shall be approved for use on carpet, tile, or wood covered floor applications. Brass and aluminum flanges and cover plates shall have a buffed appearance and be protected with a lacquer finish. Aluminum cover plate dimensions shall be 3.29 inches (83.566 mm) W x 4.310 inches (109.474 mm) L. Aluminum cover plates shall seat inside only aluminum and be flush with the finish floor. Brass cover plate dimensions shall be 3.156 inches (80.162 mm) W x 4.182 inches (106.223 mm) L. Brass cover plates shall

16000-76

Page 77:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

seat inside only brass flanges and be flush with the finished floor. All cover plate options shall provide for both power and communication services.1) Flanges shall also accommodate Ortronics workstation connectivity

outlets and modular inserts and Wiremold Open Modular Inserts. Modular inserts shall snap directly into each flange through use of mounting adapters.

2) Flange Dimensions: Aluminum and brass flange dimensions shall be as follows:a) One Gang Brass Finish:

1) Width: 5.060 in (128.524 mm).2) Length: 6.080 in (154.432 mm).

b) One Gang Aluminum Finish:1) Width: 4.920 in (124.968 mm).2) Length: 5.940 in (150.876 mm).

c) Two Gang Brass Finish:1) Width: 9.185 in (233.299 mm).2) Length: 6.080 in (154.432 mm).

d) Two Gang Aluminum Finish:1) Width: 9.045 in (229.743 mm).2) Length: 5.940 in (150.876 mm).

e) Three Gang Brass Finish:1) Width: 13.310 in (338.074 mm).2) Length: 6.080 in (154.432 mm).

f) Three Gang Aluminum Finish:1) Width: 13.170 in (334.518 mm).2) Length: 5.940 in (150.876 mm).

3) Communication Modules Mounting Accessories: Flanges shall also accommodate Ortronics workstation connectivity outlets and modular inserts, and Techchoice™ Category 6 discrete keystone connectors. Modular inserts shall snap directly into each flange through use of mounting adapters.

6. Fire Classified Resource RFB Series: Boxes shall be available in two-, or four-gang configurations and in a stamped-steel version. All boxes shall provide pre- and post-pour adjustment. All boxes shall also provide a removable barrier and tunnels between the individual compartments for greater capacity when required.a. Floor Box:

1) RFB2S-FC and RFB2S-FC12 Series Floor Box: Manufactured from stamped steel and approved for use on above grade floors. The box shall be 13-1/8 inches L x 6-1/2 inches W x 3-7/16 inches H (333 mm x 165 mm x 87 mm). Provide boxes with a 20 inches L x 13-3/8 inches W x 3-1/2 inches H (507 mm x 339 mm x 90 mm) sheet metal concrete pan to ensure that 3-1/4 inches (83 mm) of concrete surrounds the box. Boxes shall have the ability to accept a component (FP-CTR) that will allow the box to be installed in polished concrete or terrazzo floors. There shall be two independent wiring compartments that allow capacity for up to two duplex receptacles and/or communication services. The RFB2 Series Box shall permit tunneling from end power compartment to end power compartment. Each of the two compartments shall have a minimum wiring capacity of 50 cu in (822 ml3). The RFB2S-FC box shall include two intumescent stems with a 1-1/4 inches (32 mm) diameter pass-through channel that allows the pathway to close off during a fire. The RFB2S-FC shall be fire classified to restore the fire rating of the floor structure for up to 2 hours. The RFB2S-FC12 box shall include two intumescent stems, one with a 1-1/4 inches (32 mm) diameter pass-through channel and one with a 2 inches (51 mm) diameter pass-through channel that allows the pathway to close off during a fire. The RFB2S-

16000-77

Page 78:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

FC12 shall be fire classified to restore the fire rating of the floor structure for up to 3 hours. The RFB2S-FC box shall be fully adjustable, providing a minimum pour height of 2 inches (51 mm) and a maximum of 5-1/4 inches (133 mm) pre-pour adjustment, and a maximum of 3/4 inch (19.1 mm) after-pour adjustment. The RFB2S-FC12 box shall be fully adjustable, providing a minimum pour height of 2 inches (51 mm) and a maximum of 6-1/2 inches (165 mm) pre-pour adjustment, and a maximum of 3/4 inch (19.1 mm) after-pour adjustment. The boxes shall provide a series of device mounting plates that will accept both duplex power devices, as well as plates that will accommodate Ortronics workstation connectivity outlets and modular inserts, and other open system devices.

2) RFB4S-FC and RFB4S-FC12 Series Floor Boxes: Manufactured from stamped steel and approved for use on above grade floors. The box shall be 12-3/4 inches L x 10 inches W x 3-7/16 inches H (324 mm x 254 mm x 87 mm). Provide boxes with a 20 inches L x 16-5/8 inches W x 3-1/2 inches H (507 mm x 422 mm x 90 mm) sheet metal concrete pan to ensure that 3-1/4 inches (83 mm) of concrete surrounds the box. Boxes shall have the ability to accept a component (FP-CTR) that will allow the box to be installed in polished concrete or terrazzo floors. There shall be four independent wiring compartments that allow capacity for up to four duplex receptacles and/or communication services. The RFB4 Series Box shall permit tunneling from end power compartment to end power compartment. The RFB4S-FC Series Box shall permit tunneling from adjacent or opposite compartments. Two of the four compartments shall have a minimum wiring capacity of 22.5 cu in (369 ml), one compartment shall have a minimum capacity of 25.5 cu in (418 ml), and one compartment shall have a minimum capacity of 43.5 cu in (713 ml). The RFB4S-FC box shall include two intumescent stems with a 1-1/4inches (32 mm) diameter pass-through channel that allows the pathway to close off during a fire. The RFB4S-FC shall be fire classified to restore the fire rating of the floor structure for up to 2 hours. The RFB4S-FC12 box shall include two intumescent stems, one with a 1-1/4 inches (32 mm) diameter pass-through channel and one with a 2 inches (51 mm) diameter pass-through channel that allows the pathway to close off during a fire. The RFB4S-FC12 shall be fire classified to restore the fire rating of the floor structure for up to 3 hours. The RFB4S-FC box shall be fully adjustable, providing a minimum pour height of 2 inches (51 mm) and a maximum of 5-1/4 inches (133 mm) pre-pour adjustment, and a maximum of 3/4 inch (19.1 mm) after-pour adjustment. The RFB4S-FC12 box shall be fully adjustable, providing a minimum pour height of 2 inches (51 mm) and a maximum of 6-1/2 inches (165 mm) pre-pour adjustment, and a maximum of 3/4 inch (19.1 mm) after-pour adjustment. The box shall provide a series of device mounting plates that will accept both duplex power devices, as well as plates that will accommodate Ortronics workstation connectivity outlets and modular inserts, and other open system devices.

b. Activation Cover: Manufactured of die-cast aluminum or die-cast zinc, and finished in (brushed aluminum) (plated brass) (powder-coated paint). Covers shall be available with options for tile or carpet inserts, flush covers. The activation cover shall have been evaluated by UL to meet the applicable U.S. and Canadian safety standards for scrub water exclusion when used on tile, terrazzo, wood, and carpet covered floors.1) Flanged Cover Size: 7-3/4 inches L x 6-9/16 inches W (197 mm x 167

mm).7. Fire Classified Nonmetallic Floor Boxes: Boxes shall be manufactured through the use

16000-78

Page 79:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

of injection molded Geon M3900 PVC material. The box shall be round or rectangular in shape. Box shall also have concrete depth markings on the exterior of the box to indicate box depth at the time of the pour. Box shall also provide graduated cubic inch markings on the interior of the box to indicate volume capacity at the appropriate box depth. Boxes shall include intumescent material on the inside of the box to maintain the fire classification of the floor. Box shall accommodate concrete depths from 3-1/2 inches (89 mm) minimum to 6 inches (152 mm) maximum.a. Floor Box:

1) Rectangular floor boxes shall provide two 1-inch (25.4 mm) conduit openings to feed cabling to the box. Round floor boxes shall provide four 1-inch (25.4 mm) conduit openings to feed cabling to the box. Box shall provide the means to reduce this opening to fit 3/4 inch (19 mm) and 1/2-inch (13 mm) conduit sizes. Equip boxes with a high impact mudcap to protect the box from damage and prevent concrete entry during the pour and debris entry after the pour. The mudcap shall withstand loads up to 700 lbs over a 2 inches (51 mm) diameter. Box shall also be provided with ratchet teeth along interior box walls to attach cover. Box shall include internal spacer to prevent deformation of the box sidewalls when high temperature additives are used in the concrete pour.

2) Adjusting rings shall be used to attach flanges and covers to the floor box body. Adjusting ring shall have ratchet teeth to align with the teeth on box wall to connect box body without the use of adhesive or mechanical fasteners. Adjusting ring shall provide for 10 degrees of adjustment after concrete pour to adjust to various concrete conditions and floor finishes. Provide brass inserts to mount finish flanges to box body. Adjusting ring shall also provide for grounding locations using brass inserts.

3) Adjusting ring shall provide the ability to accept a modular connectivity system. Modular communication inserts shall snap directly into the adjusting ring openings. Adjusting ring for the rectangular box shall provide a fiber storage loop to maintain proper fiber optic bend radius control and excess fiber storage. Each adjusting ring shall except up to six connectivity activation locations. Adjusting ring shall allow modular connectivity inserts to be mounted recessed and protected when not in use.

4) Covers and Flanges: Floor box options shall accept brass and brushed aluminum cover plates and flanges. Rectangular flanges for brass and brushed aluminum cover plates shall be available in a one-gang application. Round flanges for brass and brushed aluminum covers plates shall be available in single application. Each flange shall provide 1/2 inch (12.7 mm) of adjustment to accommodate various floor coverings and concrete depths.

5) Flanges shall accommodate connectivity outlets and modular inserts.6) Modular inserts shall snap directly into each flange using a mounting

bezel.8. Model EFB6S-FC, EFB6S-FC1122, and EFB6S-FC2222 Floor Boxes: Manufactured

from stamped steel approved for use in 2 hour (EFB6S-FC), and 3 hour (EFB6S-FC1122, and EFB6S-FC2222) fire-rated concrete floors. Boxes shall have the ability to accept a component (EFB610-CTR) that will allow the box to be installed in polished concrete or terrazzo floors. Boxes shall have a polyester based backed enamel finished interior (white). Boxes shall be 15-3/16 inches L x 13-11/16 inches W x 4-1/8 inches H (385 mm x 347 mm x 104 mm). Provide boxes with a 21-3/4 inches L x 17-1/4 inches W x 4-3/16 inches H (552 mm x 438 mm x 106 mm) sheet metal concrete pan to ensure that 3-1/4 inches (83 mm) of concrete surrounds the box.a. Provide boxes with six independent wiring compartments that allow for up to six

receptacles, communication and/or audio/video services. Boxes shall permit feed to adjacent compartments. Boxes shall permit feed to compartments on

16000-79

Page 80:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

the opposite side of the box through a tunnel. Each of the four outer compartments shall have a minimum wiring capacity of 32 in3 (524 ml). Each of the two center compartments shall have a minimum wiring capacity of 38.5 in3 (630 ml). Each of the six compartments shall have a minimum depth of 3-7/8 inches (98 mm) behind the plate. Provide boxes with two cable guides to organize and maintain the cables egress out of the box.

b. Provide EFB6S-FC boxes with four intumescent services feed stems with a 1-1/4 inches (32 mm) pass-through channel that allows the pathway to close off during a fire.

c. Provide EFB6S-FC1122 boxes with four intumescent services feed stems, two with a 1-1/4 inches (32 mm) pass-through channel and two with a 2 inches (51 mm) pass-through channel that allows the pathway to close off during a fire.

d. Provide EFB6S-FC2222 boxes with four intumescent services feed stems with a 2 inches (51 mm) pass-through channel that allows the pathway to close off during a fire. The EFB6S-FC box shall be fully adjustable, providing a minimum pour height of 2 inches (51 mm) and a maximum of 5-1/4 inches (133 mm) pre-pour adjustment, and a maximum of 1/2-inch (12.7 mm) after-pour adjustment.

e. The EFB6S-FC1122 and EFB6S-FC2222 boxes shall be fully adjustable, providing a minimum pour height of 2 inches (51 mm) and a maximum of 6-1/2 inches (165 mm) pre-pour adjustment, and a maximum of 1/2 inch (12.7 mm) after-pour adjustment. The box shall be able to accept 2-3/4 inches x 4-1/2 inches standard size wall plates.

f. Include mounting brackets with the boxes that will accommodate 15 amp, 20 amp straight blade, 20 amp turn loc, 30 amp straight blade and 30 amp turn loc receptacles, Ortronics workstation connectivity and modular adapters, a variety of audio/video devices from most manufacturers, and other open system devices.

9. Model EFB8S-FC, EFB8S-FC1122, and EFB8S-FC2222 Floor Boxes: Manufactured from stamped steel approved for use in 2 hour (EFB8S-FC) and 3 hour (EFB8S-FC1122 and EFB8S-FC2222) fire-rated concrete floors. Boxes shall have the ability to accept a component (EFB610-CTR) that will allow the box to be installed in polished concrete or terrazzo floors. Boxes shall have a polyester based backed enamel finished interior (white). Boxes shall be 15-3/16 inches L x 12-5/8 inches W x 6-1/16 inches H (385 mm x 320 mm x 153 mm). Provide boxes with a 21-3/4 inches L x 17-1/4 inches W x 6-1/8 inches H (552 mm x 438 mm x 155 mm) sheet metal concrete pan to ensure that 3-1/4 inches (83 mm) of concrete surrounds the box. Provide boxes with eight independent wiring compartments that allow for up to eight receptacles, communication and/or audio/video services.a. Boxes shall have removable and repositionable dividers to permit feed to

adjacent compartments and reconfiguration of devices. Boxes shall permit feed to compartments on the opposite side of the box through a tunnel. Each of the compartments shall have a minimum wiring capacity of 53 in3 (860 ml).

b. Each of the eight compartments shall have a minimum depth of 3-1/2 inches (89 mm) behind the plate. Provide boxes with two cable guides to organize and maintain the cables egress out of the box. Provide boxes with removable compartments to facilitate installation.

c. Provide EFB8S-FC boxes with four intumescent services feed stems with a 1-1/4 inches (32 mm) pass-through channel that allows the pathway to close off during a fire.

d. Provide EFB8S-FC1122 boxes with four intumescent services feed stems, two with a 1-1/4 inches (32 mm) pass-through channel and two with a 2 inches (51 mm) pass-through channel that allows the pathway to close off during a fire.

e. Provide EFB8S-FC2222 boxes with four intumescent services feed stems with a 2 inches (51 mm) pass-through channel that allows the pathway to close off during a fire.

f. The EFB8S-FC box shall be fully adjustable, providing a minimum pour height

16000-80

Page 81:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

of 2 inches (51 mm) and a maximum of 5-1/4 inches (133 mm) pre-pour adjustment, and a maximum of 1/2 inch (12.7 mm) after-pour adjustment.

g. The EFB8S-FC1122 and EFB8S-FC2222 boxes shall be fully adjustable, providing a minimum pour height of 2 inches (51 mm) and a maximum of 6-1/2 inches (165 mm) pre-pour adjustment, and a maximum of 1/2 inch (12.7 mm) after-pour adjustment. The box shall be able to accept standard size single gang (2-3/4 inches x 4-1/2 inches (70 mm x 114 mm)), double gang (4-9/16 inches x 4-1/2 inches (116 mm x 114 mm)), and triple gang (6-3/8 inches x 4-1/2 inches (162 mm x 114 mm)) wall plates. Include mounting brackets with the boxes that will accommodate 15 amp, 20 amp straight blade, 20 amp turn loc, 30 amp straight blade and 30 amp turn loc receptacles. Boxes shall have the ability to accommodate a bracket (EFB-50A) allowing for one 50-amp receptacle. Boxes shall also accommodate Ortronics workstation connectivity and modular adapters, a variety of audio/video devices from most manufacturers, and other open system devices.

10. Model EFB10FC, EFB10S-FC1122, and EFB10S-FC2222 Floor Boxes: Manufactured from stamped steel approved for use in 2 hour (EFB10S-FC) and 3 hour (EFB10S-FC1122 and EFB10S-FC2222) fire-rated concrete floors. Boxes shall have the ability to accept a component (EFB610-CTR) that will allow the box to be installed in polished concrete or terrazzo floors. Boxes shall have a polyester based backed enamel finished interior (white). Boxes shall be 15-3/16 inches L x 12-5/8 inches W x 6-1/16 inches H (385 mm x 320 mm x 153 mm). Provide boxes with a 21-3/4 inches L x 17-1/4 inches W x 6-1/8 inches H (552 mm x 438 mm x 155 mm) sheet metal concrete pan to ensure that 3-1/4 inches (83 mm) of concrete surrounds the box. Provide boxes with ten independent wiring compartments that allow for up to ten receptacles, communication and/or audio/video services. Boxes shall have removable and repositionable dividers to permit feed to adjacent compartments and reconfiguration of devices. Boxes shall permit feed to compartments on the opposite side of the box through a tunnel. Each of the compartments shall have a minimum wiring capacity of 53 in3 (860 ml). Each of the ten compartments shall have a minimum depth of 3-1/2 inches (89 mm) behind the plate. Provide boxes with two cable guides to organize and maintain the cables egress out of the box. Provide boxes with removable compartments to facilitate installation. The compartments shall be removable from the top of the floor box.a. Provide EFB10S-FC boxes with four intumescent services feed stems with a 1-

1/4 inches (32 mm) pass-through channel that allows the pathway to close off during a fire. Provide EFB10S-FC1122 boxes with four intumescent services feed stem) with a 1-1/4 inches (32mm) pass-through channel and two with a 2 inches (51 mm) pass-through channels that allows the pathway to close off during a fire.

b. Provide EFB10S-FC2222 boxes with four intumescent services feed stems with a 2 inches (51 mm) pass-through channel that allows the pathway to close off during a fire. The EFB10S-FC box shall be fully adjustable, providing a minimum pour height of 2 inches (51 mm) and a maximum of 5-1/4 inches (133 mm) pre-pour adjustment, and a maximum of 1/2 inch (12.7 mm) after-pour adjustment.

c. The EFB10S-FC1122 and EFB10S-FC2222 boxes shall be fully adjustable, providing a minimum pour height of 2 inches (51 mm) and a maximum of 6-1/2 inches (165 mm) pre-pour adjustment, and a maximum of 1/2 inch (12.7 mm) after-pour adjustment. Include mounting brackets with the boxes that will accommodate 15 amp, 20 amp straight blade, 20 amp turn loc, 30 amp straight blade and 30 amp turn loc receptacles. Boxes shall have the ability to accommodate a bracket (EFB-50A) allowing for one 50-amp receptacle. Boxes shall also accommodate Ortronics workstation connectivity and modular adapters, a variety of audio/video devices from most manufacturers, and other open system devices.

16000-81

Page 82:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

d. Activation Covers: Evolution EFB610BT and EFB610CT Series Covers:1) Manufactured of die-cast aluminum. Activation covers shall be available

in surface mount and flush versions.2) Provide covers with two gaskets (one for carpet and one for tile) to go

under the trim flange to maintain scrub water tightness.3) Covers shall be 16-15/16 inches x 12-1/2 inches x 3/16 inches (430 mm

x 318 mm x 4 mm).4) Covers shall be available with a carpet recess area or a solid lid.5) Secure the cover to the flange and enable cover to rotate greater than

180 degrees to reduce trip hazards and provide maximum amount of working space.

6) Provide covers with spring-loaded self-closing slide egress doors to reduce egress opening when cables are exiting and reduce trip hazards.

7) Each of the two egress openings shall have a minimum of 4 in2 (102 mm2), or a minimum of 8 in2 (203 mm2) per cover assembly. Cover finish shall be as indicated or as scheduled.

2.10 RECESSED OUTLET POKE-THRU DEVICES

A. Electrical Poke-Thru Devices and Components: Comply with requirements of applicable local codes, NEC, UL, and NEMA Standards pertaining to poke-thru devices and components. Listed and labeled in accordance with NFPA 70, Article 100.

B. Accessibility Compliance: Design device flange to meet ADA Accessibility Guidelines as to changes in floor and ground surface levels. Flanges shall be beveled so the slope is no greater than 1:2.

C. Recessed Outlet Poke-Thru Devices as manufactured by Legrand/Wiremold. Poke-thru devices shall be compatible with the complete line of Ortronics workstation connectivity outlets and modular inserts, Wiremold's CM open system adapters, or a variety of audio/video devices from most manufacturers, and other open system devices.1. Classification and Use: Poke-thru device shall have been examined and tested by

Underwriters Laboratories Inc. to comply with UL514A and/or UL514C and Canadian Standard C22.2, No. 18-98 and bear the U.S. and Canadian UL Listing Mark. Poke-thru device shall also have been tested by UL and classified for fire resistance and bear the U.S. and Canadian UL Classification Mark. The poke-thru device shall conform to the standards set in the National Electrical Code, Section 300-21.a. Poke-thru devices shall be classified for use in 1, 1-1/2, or 2-hour rated floors

and 1, 1-1/2, or 2 hour rated floors employing unprotected steel floor units and concrete toppings (D900 Series designs), or concrete floors with suspended ceilings. Fire resistive designs with suspended ceilings shall have provisions for accessibility in the ceiling below the poke-thru device fittings.

b. Poke-thru device shall have been evaluated by UL to meet the applicable U.S. and Canadian safety standards for scrub water exclusion when used on tile, terrazzo, wood, and carpet covered floors.

c. These devices are not suitable for wet or damp locations, or other areas subject to saturation with water or other liquids such as commercial kitchens.

d. Poke-thru device shall be suitable for use in air handling spaces in accordance with Section 300-22C of the National Electrical Code.

2. 6AT Poke-Thru Assembly: Poke-thru device assemblies shall consist of an insert and an activation cover. Assembly length: 16-3/4 inches (425 mm).a. Insert: Insert body shall recess the devices a minimum of 2-3/4 inches (69 mm)

and have a polyester based backing enamel finished interior; ivory color. Furnish with necessary channels to provide complete separation of power and communication services. Provide three compartments that allow for up to three duplex receptacles that can be wired as a standard receptacle or isolated

16000-82

Page 83:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

ground and/or 12 communication ports and/or 10 Legrand AVIP AV devices or 10 Extron Electronics MAAP and/or two AAP devices.1) Body consists of an intumescent firestop material to maintain fire rating

of the floor slab. Hold intumescent material securely in place in insert body. Intumescent material will not have to be adjusted to maintain fire rating of the unit and the floor slab. Provide insert with a retaining feature to hold the poke-thru device in the floor slab without additional fasteners. Poke-thru insert shall also consist of a 3/4 inch (19 mm) trade size conduit stub that is connected to the insert body and a 24.5 cu in (401 ml) stamped steel junction box for wire splicing and connections. Stamped steel junction box shall also contain the means necessary to electrically ground the poke-thru device to the system ground.

b. Activation Cover: Manufactured of die-cast aluminum alloy. Provide with two gaskets, (one for surface and one for flush) to go under the trim flange to maintain scrub water tightness. Activation cover is 7-1/4 inches (184 mm) in diameter. Provide cover with spring-loaded slides to allow cables to egress out of the unit and maintain as small an egress opening as possible.1) Powder coat finish, color shall be aluminum, black, gray, brass, nickel,

bronze.c. Communication Modules Mounting Accessories: Provide activation unit with

three locations to mount communication connectors. Mount connectors using a mounting bracket capable of accepting up to 12 Ortonics TracJack Category 6 insert modules or TechChoice Category 6 discrete keystone connectors. Also provide unit with two Category 6 discrete keystone connectors and two industry standard keystones and accommodate a mechanism to permit protection of communication cabling. Fabricate mechanism from stamped steel construction. Mechanism shall accept both flexible and rigid 3/4 inch (19 mm) , 1-1/4 inch (32 mm) or 2 inch (51 mm) trade size conduit.

3. 8AT Poke-Thru Assembly: Poke-thru device assemblies shall consist of an insert and an activation cover. Assembly length: 16-3/4 inches (425 mm).a. Insert: Insert body shall recess the devices a minimum of 2-3/4 inches (69 mm)

and have a polyester based backing enamel finished interior; ivory color. Furnish with necessary channels to provide complete separation of power and communication services. Provide five compartments that allow for up to five duplex receptacles that can be wired as a standard receptacle or isolated ground and/or 22 communication ports and/or 16 Legrand AVIP AV devices or 16 Extron Electronics MAAP and/or four AAP devices.1) Body consists of an intumescent firestop material to maintain fire rating

of the floor slab. Hold intumescent material securely in place in insert body. Intumescent material will not have to be adjusted to maintain fire rating of the unit and the floor slab. Provide insert with a retaining feature to hold the poke-thru device in the floor slab without additional fasteners. Poke-thru insert shall also consist of a 3/4 inch (19 mm) trade size conduit stub that is connected to the insert body and a 24.5 cu in (401 ml) stamped steel junction box for wire splicing and connections. Stamped steel junction box shall also contain the means necessary to electrically ground the poke-thru device to the system ground.

b. Activation Cover: Manufactured of die-cast aluminum alloy. Provide with two gaskets (one for carpet and one for tile) to go under the trim flange to maintain scrub water tightness. Activation cover is 9-1/4 inches (235 mm) in diameter. Provide cover with spring-loaded slides to allow cables to egress out of the unit and maintain as small an egress opening as possible.1) Powder coat finish, color shall be aluminum, black, gray, brass, nickel,

bronze.c. Communication Modules Mounting Accessories: Provide activation unit with

three locations to mount communication connectors. Mount connectors using a

16000-83

Page 84:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

mounting bracket capable of accepting up to 12 Ortonics TracJack Category 6 insert modules or TechChoice Category 6 discrete keystone connectors. Also provide unit with two Category 6 discrete keystone connectors and two industry standard keystones and accommodate a mechanism to permit protection of communication cabling. Fabricate mechanism from stamped steel construction. Mechanism shall accept both flexible and rigid 3/4 inch (19 mm) , 1-1/4 inch (32 mm) or 2 inch (51 mm) trade size conduit.

4. 6AFF Poke-Thru Assembly: Poke-thru device assemblies shall consist of an insert and an activation cover. Assembly length: 16-3/4 inches (425 mm).a. Insert: Insert body shall have the necessary channels to provide complete

separation of power and communication services. Provide two channels that allow up to 10, No. 10 AWG conductors in the power channel and 28 Category 6A data cables in the communication channel.1) Body consists of an intumescent firestop material to maintain fire rating

of the floor slab. Hold intumescent material securely in place in insert body. Intumescent material will not have to be adjusted to maintain fire rating of the unit and the floor slab. Provide insert with a retaining feature to hold the poke-thru device in the floor slab without additional fasteners. Poke-thru insert shall also consist of a 3/4 inch (19 mm) trade size conduit stub that is connected to the insert body and a 24.5 cu in (401 ml) stamped steel junction box for wire splicing and connections. Stamped steel junction box shall also contain the means necessary to electrically ground the poke-thru device to the system ground.

b. Activation Cover: Manufactured of die-cast aluminum alloy. Provide with two gaskets (one for carpet and one for tile) to go under the trim flange to maintain scrub water tightness. Activation cover is 7-3/4 inches (196 mm) in diameter. Provide cover with one 3/4-inch (19 mm) trade size opening for power and one 1-1/4 to 2 inch (32 to 51 mm) combination trade size opening for communications.1) Provide surface mounted activation cover that accommodates a carpet

floor finish.2) Powder coat finish, color shall be aluminum, black, gray, brass, nickel,

bronze.5. 10AT Poke-Thru Assembly: Poke-thru device assemblies shall consist of an insert

and an activation cover. Assembly length: 11-3/4 inches (286 mm).a. Insert: Insert body shall recess the devices a minimum of 4-1/2 inches (114

mm) and have a polyester based backing enamel finished interior; ivory color. Furnish with necessary channels to provide complete separation of power, communication, and audio/video (A/V) services. Provide eight compartments (four internal and four external) that allow for up to eight duplex receptacles that can be wired as a standard receptacle or isolated ground and/or 32 communication ports and/or 24 Legrand AVIP A/V devices or 24 Extron Electronics MAAP and/or eight AAP devices. The four internal compartments shall have a volume of 19 cu in (311 ml) each. The four external compartments shall have a minimum volume of 14 cu in (232 ml) each.1) Body consists of an intumescent firestop material to maintain fire rating

of the floor slab. Hold intumescent material securely in place in insert body. Intumescent material will not have to be adjusted to maintain fire rating of the unit and the floor slab. Provide insert with a retaining feature to hold the poke-thru device in the floor slab without additional fasteners. Poke-thru insert shall also consist of a 3/4 inch (19 mm) trade size conduit stub that is connected to the insert body to feed the power services. The intumescent body shall be listed and classified as an electrical enclosure allowing for electrical connections to be made within the poke-thru body without the need for an external junction box.

b. Activation Cover: Manufactured of die-cast aluminum alloy. Provide with two

16000-84

Page 85:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

gaskets (one for carpet and one for tile) to go under the trim flange to maintain scrub water tightness. Activation cover is 11-1/4 inches (283 mm) in diameter. Provide cover with spring-loaded slides to allow cables to egress out of the unit and maintain as small an egress opening as possible.1) Provide surface mounted activation cover that accommodates a carpet

floor finish.2) Provide flush activation cover that accommodates a tile floor finish.3) Powder coat finish, color shall be aluminum, black, gray, brass, nickel,

bronze.c. Communication Modules Mounting Accessories: Provide activation unit with

three locations to mount communication connectors. Mount connectors using a mounting bracket capable of accepting up to 32 Ortonics TracJack Category 6 insert modules or TechChoice Category 6 discrete keystone connectors. Also provide unit with two Category 6 discrete keystone connectors and two industry standard keystones and accommodate a mechanism to permit protection of communication cabling. Fabricate mechanism from stamped steel construction. Mechanism shall accept both flexible and rigid 3/4 inch (19 mm), 1-1/4 inch (32 mm) or 2 inch (51 mm) trade size conduit.

6. Copper Wire Cross Sectional Area:a. Commonly Used conductors

1) Size No. 24: .00032 sq in (0.206 sq mm).2) Size No. 22: .00050 sq in (0.322 sq mm)3) Size No. 14: .00323 sq in (2.083 sq mm)4) Size No. 12: .00512 sq in (3.303 sq mm)5) Size No. 10: .00815 sq in (5.258 sq mm)6) Size No. 8: .01296 sq in (8.361 sq mm).

b. Maximum copper cross sectional area for 6AT outer compartment only is .0154 sq in (9.9 sq mm). Maximum copper cross sectional area for the center compartment only is .0387 sq in (24.9 sq mm).

c. Maximum copper cross sectional area for 6ATCFF power compartment only is .0815 sq in (52.6 sq mm). Maximum copper cross sectional area for the center communication compartment only is .0686 sq in (44.3 sq mm). The maximum copper cross sectional area for the outside communication compartment only is .0187 sq in (12.1 sq mm).

d. Maximum copper cross sectional area for 8AT outer compartment only is .0154 sq in (9.9 sq mm). Maximum copper cross sectional area for the center compartment only is .0775 sq in (16.6 mm).

e. Maximum copper cross sectional area for 10AT outer compartment only is .0288 sq in (18.6 sq mm). Maximum copper cross sectional area for the center compartment only is .0960 sq in (61.9 sq mm).

2.11 MEETING ROOM SOLUTIONS

A. Integrating A/V with the Collaborative Space:1. Product: InteGreat Series from Legrand.2. Components:

a. AVIP Device Plates - Audio video interface plates and devices mounted in InteGreat A/V Table Box.

b. InteGreat A/V Table Box - Provides unique work surface solution to deliver devices access on the table surface and is fed from InteGreat™ UTCM system.

c. InteGreat Cable Retractors - Protects and organizes cabling while keeping table surface free of excess cabling.

d. InteGreat Under Table Cable Management - Provides clean cable management for power, communication and A/V cables on the underside of the table.

e. InteGreat Transition Channel - Connects with Poke-Thru devices or OFR Series Overfloor Raceway to transition cables from the floor to the underside of

16000-85

Page 86:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

the table.f. OFR Series Overfloor Raceway - Feeds power, communication and A/V cabling

from wall to the underside of meeting table when feeding through the floor is not possible.

g. Evolution Series Poke-Thru Device - Delivers power, communication and A/V cabling through the floor.

h. Evolution Series A/V Wall Box - Provides power, communication and A/V services to flat screen monitors, while allowing the monitor to sit flush against the wall.

i. Evolution Series Ceiling Box - Fully finished enclosure designed to manage and store A/V and IT equipment in an air handling plenum space above a false ceiling.

2.12 PLUGMOLD

A. The surface metal raceway system and/or multi-outlet system specified herein for branch circuit wiring and convenience power outlets shall be the 2000 Base and Blank Cover, the 2000 Plugmold Multi-outlet, and the 2000 Plugmold with Snapicoil System as manufactured by The Wiremold Company.1. This specification covers a surface metal raceway and multi-outlet system to provide

branch wiring and convenience power outlets. The surface metal raceway shall consist of a base, blank cover, and appropriate fittings to complete the installation per the electrical drawings. The multi-outlet system shall consist of a base, pre-punched cover, wired receptacle harness, and appropriate fittings for a complete installation per the electrical drawings.a. Classification and Use: Surface metal raceway is to be utilized in dry interior

locations only as covered in Article 386 of the National Electrical Code, as adopted by the National Fire Protection Association and as approved by the American National Standards Institute and Section 12-1600 of the Canadian Electrical Code. The Wiremold Company 2000 Raceway System is listed by Underwriters Laboratories under File No. E4376 Guide RJBT and E41751 Guide RJPR and CSA certified under File 350.

b. The multi-outlet system is to be utilized in dry interior locations only as covered in Article 380 of the National Electrical Code, as adopted by the National Fire Protection Association and as approved by the American Standards Institute and meets Section 12-3032 of the Canadian Electrical Code. The Wiremold Company Plugmold 2000 Multioutlet System is listed by Underwriters Laboratories under File Nos. E15191 Guide PVGT and CSA certified under File 28650.

c. Materials; The raceway and all system components shall be UL listed and CSA certified. The base and cover shall be manufactured of steel, finished in ivory ScuffCoatSYMBOL 228 "Symbol" 10 (a polyester topcoat over an ivory base), gray enamel or custom colors and suitable for field repainting.

2. Raceway: The raceway shall be a two-piece design with a base and cover. Total width shall be 1.28 inches by 0.75 inches (32.51 mm by 19.05 mm) deep with a cross sectional area of 0.80 square inches (516 mm2). The 2000 Series cover shall be a minimum thickness of .025 inch (6.35mm), the base a thickness of .040 inch (1.01mm). The 2000 Raceway base and cover shall be available in 5 feet (1.52m) lengths. The 2000 Plugmold Multioutlet System shall be available in standard lengths of 3 feet, 5 feet and 6 feet (.91 m, 1.52 m, and 1.82 m).a. The 2000 Plugmold with Snapicoil harness shall be available in standard

lengths of 48 feet and 50 feet (14.63 m and 15.24 m).b. The 2000 Series base shall have random start 1/2 inch (12.7 mm) trade size

knockouts on 8 inches (203.2 mm) centers for feeding the system.c. The 2000 Series cover shall be available as a blank or with pre-punched

holecuts for receptacles on 6 inches, 9 inches, 12 inches and 18 inches (152.4

16000-86

Page 87:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

mm, 228 mm, 304.8 mm and 457.2 mm) centers for Plugmold 2000 outlet strips or with 6 inches, 9 inches, 12 inches and 18 inches, 30 inches and 60 inches (152.4 mm, 304.8 mm, 457.2 mm 762 mm and 1524 mm) centers for Plugmold 2000 with Snapicoil harness. A hand operated cutting tool shall be available for the base and cover to ensure clean, square cuts.

3. Fittings: A full compliment of fittings shall be available including but not limited to couplings, flat, internal and external elbows, tees, entrance end fittings, blank end fittings, cover clips, and bushings. The fitting covers shall be painted with an enamel finish to match the raceway. All fittings shall be supplied with a base where applicable. Transition fittings shall be available to adapt to an existing flush wall box and to other raceways series manufactured by The Wiremold Company.

4. Device and Extension Boxes: Device boxes shall be available to mount standard devices and device faceplates in single-gang and two-gang configurations. Device boxes shall function as an extension box by removal of a rectangular knockout (1.656 inches W x 2.906 inches L (42.06 mm W x 73.81 mm L) in the base. The boxes shall be available in 1 3/4 inches (44.45 mm) depth and painted to match the raceway.

5. Multi-outlet Wiring Harnesses: Multi-outlet wiring harnesses shall consist of 15 Amp 125 Volt NEMA 5-15R specification grade receptacles conforming to NEMA specification WD 1-7.01 to 7.10 "heavy duty general use 15A, 125V grounding receptacles". Receptacles shall be UL listed and be in compliance with UL-498. The harnesses shall be available in single circuit (2 conductor plus ground), two circuit (3 conductor plus ground) alternating wire configuration and a single circuit (2 conductor plus isolated ground) wire configuration isolated ground version. The wires shall be #12 AWG solid type THHN conductors, factory assembled to the receptacles.a. The Plugmold 2000 Multioutlet system shall have a factory installed wiring

harness with available receptacle spacings of 6 inches, 9 inches, 12 inches and 18 inches (152.4 mm, 228 mm, 304.8 mm and 457.2 mm) centers.

b. The Plugmold 2000 with Snapicoil shall have a field installed harnesses with available receptacle spacings of 6 inches, 9 inches, 12 inches and 18 inches, 30 inches and 60 inches (152.4 mm, 304.8 mm, 457.2 mm 762 mm and 1524 mm) centers. The Snapicoil harness shall be available on reels in standard lengths of 48 feet or 50 feet (16.63 m or 15.24 m). Harness lengths up to 240 feet (73.15 m) shall be available for receptacle spacings of 6 inches, 9 inches, 12 inches and 18 inches (152.4 mm, 228 mm, 304.8 mm and 457.2 mm) centers; and in lengths up to 500 feet (152.4 m) for receptacle spacings of 30 inches and 60 inches (762mm and 1524mm) centers.

6. Communication Devices and Accessories: The raceway manufacturer will provide a complete line of connectivity outlets and modular inserts for UTP/STP, Fiber Optic, Audio, Video and other cabling types with faceplates and bezels to facilitate mounting. A complete line of preprinted station and port identification labels, snap-in icon buttons as well as write-on station identification labels shall be available.

B. The surface steel raceway system specified herein for branch circuit wiring convenience power outlets and voice/data devices shall be the V2400BD Base and Blank Cover as manufactured by The Wiremold Company.1. This specification covers a surface steel raceway to provide branch wiring and

convenience power outlets. The surface steel raceway shall consist of a divided base, blank cover, and appropriate fittings to complete installation per electrical and/or telecom drawings.

2. Classification and Use: Surface steel raceway is to be utilized in dry interior locations only as covered in Article 386 of the National Electrical Code, as adopted by the National Fire Protection Association and as approved by the American National Standards Institute. The Wiremold Company V2400BD raceway system is listed by Underwriters Laboratories (US/C Canadian Listed) under File No. E4376 Guide RJBT and E41751 Guide RJPR. (Also covers Canadian listing).

3. Materials: The raceway and all system components shall be US/C Listed. The base

16000-87

Page 88:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

and cover shall be manufactured of steel, finish in ivory ScuffCoatSYMBOL 212 "Symbol" 10 (a polyester topcoat over an ivory base) or custom colors and suitable for field repainting.

4. Raceway: The raceway shall be a two-piece design with a base divided into two compartments of 1/3 and 2/3 the width of raceway base and snap-on cover. Total width shall be 1.90 inches x 0.88 inch (48 mm x 22 mm) deep with a cross sectional area of 0.374 square inches (241 mm2) for the 1/3 compartment and 0.866 square inches (559 mm2) for the 2/3 compartment. The base and cover shall be a minimum thickness of 0.040 inch (1mm). The V2400BD raceway base shall be available in 10 feet (3.050m) lengths and the cover shall be available in 5 feet (1.525m) lengths.

5. Fittings: A full complement of fittings shall be available including, but not limited to, couplings, flat, internal and external elbows, entrance end fittings, blank end fittings, cover clips and wire clips. The fitting covers shall be manufactured of steel and be painted with an enamel finish or a rigid plastic compound that exhibits nonflammable self-extinguishing characteristics tested to comparable specifications of UL94V-0. All fittings shall be supplied with a base where applicable. Transition fittings shall be available to adapt to V4000 Series raceway manufactured by The Wiremold Company.

6. Device and Extension Boxes: Device boxes shall be available to mount standard devices and Activate inserts by The Wiremold Company with faceplates in single and two gang configurations. Device bases shall be available for over-the-raceway mounting feature with twist-outs that allow for access into either raceway compartment. The boxes shall be available in 2 3/4 inches (70 mm) depth and painted to match the raceway.

7. Communication Devices and Accessories: The raceway manufacturer will provide a complete line of connectivity outlets and modular inserts for UTP/STP, Fiber Optic, Coaxial and other cabling types with faceplates and bezels to facilitate mounting. A complete line preprinted station and port identification labels, snap-in icon buttons as well as write-on station identification labels shall be available.

C. Mechanical Security: All raceway systems shall be mechanically continuous and connected to all electrical outlets, boxes, cabinets, in accordance with manufacturer's installation sheets.

D. Electrical Security: All metal raceway shall be electrically continuous and bonded in accordance with the National Electric Code for proper grounding.

E. Raceway Support: Raceway shall be securely supported at intervals not exceeding 10 feet (3.048m) or in accordance with manufacturer's installation sheets.

2.13 RESIDENTIAL FLOOR BOXES

A. Wood Floor Boxes:1. WMFB Series Boxes and covers shall be listed by Underwriters Laboratories Inc. to

their standards UL514A, 514C, and 514D, and to Canadian standard C22.2.a. Model: WMFB1SRKS1B Single-Gang Floor Box Assembly.

1) Includes single-gang box, divider, one 15A receptacle, one opening for communication device, and brass cover with two screw plugs.

b. Model WMFB1DRN Single-Gang Floor Box Assembly.1) Includes single-gang box, one 15A, 125V tamper-resistant duplex

receptacle, and nickel cover with two screw plugs.c. Model: WMFB1SRKS1N Single-Gang Floor Box Assembly.

1) Includes single-gang box, divider, one 15A receptacle, one opening for communication device, and nickel cover with two screw plugs.

d. Model: WMFB1SRB Single-Gang Floor Box Assembly1) Includes single-gang box, one 15A, 125V tamper-resistant single

receptacle, and brass cover with one screw plug.

16000-88

Page 89:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

e. Model: WMFB1DRB Single-Gang Floor Box Assembly1) Includes single-gang box, one 15A, 125V tamper-resistant duplex

receptacle, and brass cover with two screw plugs.f. Model: WMFB1SRN Single-Gang Floor Box Assembly.

1) Includes single-gang box, one 15A, 125V tamper-resistant single receptacle, and nickel cover with one screw plug.

g. Model: WMFB2DR2B Dual-Gang Floor Box Assembly.1) Includes dual-gang box, two 15A, 125V tamper-resistant duplex

receptacles, and brass cover with four screw plugs.h. Model: WMFB1KS2N Single-Gang Floor Box Assembly.

1) Includes single-gang box, device plate with two openings for communication devices, and nickel cover with one screw plug.

i. Model: WMFB2DR2N Dual-Gang Floor Box Assembly.1) Includes dual-gang box, two 15A, 125V tamper-resistant duplex

receptacles, and nickel cover with four screw plugs.j. WMFB1KS4B Single-Gang Floor Box Assembly.

1) Includes single-gang box, 106 adapter with four openings for communication devices, and brass cover with two screw plugs.

k. Model: WMFB1KS2B Single-Gang Floor Box Assembly.1) Includes single-gang box, device plate with two openings for

communication devices, and brass cover with one screw plug.l. Model: WMFB1KS4N Single-Gang Floor Box Assembly.

1) Includes single-gang box, 106 adapter with four openings for communication devices, and nickel cover with two screw plugs.

m. Model: WMFB2DRKS4B Dual-Gang Floor Box Assembly.1) Includes dual-gang box, one 15A, 125V tamper-resistant duplex

receptacle, 106 adapter with four openings for communication devices, and brass cover with four screw plugs.

n. Model: WMFB2KS8B Dual-Gang Floor Box Assembly.1) Includes dual-gang box, two 106 adapters with eight openings for

communication devices, and brass cover with four screw plugs.o. Model: WMFB2DRKS4N Dual-Gang Floor Box Assembly.

1) Includes dual-gang box, one 15A, 125V tamper-resistant duplex receptacle, 106 adapter with four openings for communication devices, and nickel cover with four screw plugs.

p. Model: WMFB2KS8N Dual-Gang Floor Box Assembly.1) Includes dual-gang box, two 106 adapters with eight openings for

communication devices, and nickel cover with four screw plugs.

B. Round Floor Boxes For Retrofit Residential Wood Floor Applications:1. Boxes and covers shall be listed by Underwriters Laboratories Inc. to their standard

UL514A, 514C, 514D, and Canadian standard C22.2.2. Product: Wiremold 863 Series Residential Wood Floor Boxes.

a. Model: 863DPCOM Dual Service Box Kit.1) Includes round PVC floor box, one 15A, 125V tamper-resistant duplex

receptacle, one coax F connector, one RJ45 Category 5e connector, and brass duplex opening cover plate with two flip lids.

b. Model: 863DRGFICOM Dual Service Box Kit.1) Includes round PVC floor box, one 15A, 125V tamper-resistant decorator

style duplex receptacle, one coax F connector, one RJ45 Category 5e connector, and brass duplex opening cover plate with single flip lid.

2.14 OPEN SPACE POWER AND COMMUNICATIONS DELIVERY

A. The system specified herein for branch circuit wiring, convenience power outlets, and data network, voice, video, and other low-voltage wiring shall be the Vista System as

16000-89

Page 90:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

manufactured by The Wiremold Company.

B. Scope: This specification covers vertical chase, and multi-outlet systems in steel and aluminum, used to provide branch wiring, convenience power outlets, and multi-media low voltage communications. The assembly shall consist of modular vertical channels, and appropriate fittings to complete installation per electrical drawings. The system shall consist of a pre-punched support, aluminum end covers and a metallic center panel, which can be finished with laminate products. Furniture feed or wired receptacle harnesses, and appropriate fittings complete the installation per electrical and communications drawings.1. Communication Devices and Accessories: The assembly manufacturer will provide a

complete line of connectivity outlets and modular inserts for UTP, STP Fiber Optic, Coaxial and other cabling types with faceplates and bezels to facilitate mounting.

C. Classification and Use: The multi-outlet assembly is to be utilized in dry interior locations only as covered in Article 380 of the National Electrical Code, as adopted by the National Fire Protection Association and as approved by the American National Standards Institute. The Wiremold Company multi-outlet assemblies are listed by Underwriters Laboratories Inc. c(UL)us under the following file number: E15191.

D. Components:1. Frame: The frame shall be mill finished 6063-T6 aluminum with snap on steel and/or

aluminum covers and satin anodized aluminum end caps. Covers and access panels may also be painted over and are suitable for field painting.a. The frame shall be a four-piece design with two center supports and snap-on

covers and end caps, yielding a total of three useable wire and cable channels. The product will be available in two sizes -- small and large. Total small width shall be 8.9 inches (226 mm) by 3.8 inches (96 mm) deep. The large size will be 13.4 inches (340 mm) wide by 3.8 inches (96 mm) deep. The aluminum extrusions will be a minimum thickness of 0.06 inch (1.5mm), and steel covers .040 inch (1.0 mm). The system shall be available in 10 feet-6 inches (3.2 m) height. The system shall be available with an extension kit that includes aluminum tubes to allow for varying ceiling heights up to 15 feet (4.5 m). Access panels and covers up to a height of 30 inches (762 mm) above finished floor will provide access to wiring and devices.

b. The frame supports shall be available with factory pre-punched hole cuts for communication receptacles and trade knockouts for electrical terminations.

2. Center Panels: The center panel shall be constructed of painted steel, aluminum or stainless steel in 96 inches (2.4 m), 30 inches (762 mm), 24 inches (609 mm), and 6 inches (152 mm) heights. A large assortment of center panel adornments shall be available. These finishes shall include wood laminate, metal laminate, nonmetallic laminate, fabric, and a painted surface. Perforated metal in painted steel and glass panels shall be available for the upper sections. An open center option is also offered. This option consists of a metallic panel from the floor to 30 inches (762mm) high. The remainder of the center section is open to the ceiling.

3. Lighting: A bracket shall be available to affix commercially available light fixtures up to 10 lbs. (4.5 kg).

4. Fittings: A full complement of fittings shall be available including, but not limited to, internal braces with knockouts, snap-in dividers and wire clips, ceiling and carpet trim pieces. The fittings shall be manufactured of extruded aluminum, galvanized steel, and/or plastic.

5. Multi-Outlet Wiring Harnesses: Multi-outlet wiring harnesses shall consist of 20 Amp 125 Volt NEMA 5-20R specification grade receptacles. The harnesses shall be available in single circuit (2 conductor plus ground) and alternating two circuit (3 conductor plus ground) wiring configurations. The wires shall be #12 AWG solid type THHN conductors, factory assembled to the receptacles.

6. Furniture Feed: A plate with openings and knockouts shall be provided. The plate will

16000-90

Page 91:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

provide the openings necessary for the Vista Power and Communications Delivery to feed a modular furniture system.

7. Columns: Wiremold Vista Point5 Architectural Columns.a. Compliant: cULus Listed Multioutlet Assemblies. File E15191, Guide PVGT.

Meets Article 380 of NEC.b. Product: VSP5662345 Small Profile Point5 as manufactured by Legrand.

1) Column - Small profile 36 inches (914 mm) high column.2) Anodized aluminum frame with round end channels. Includes four

adapters for Pass & Seymour Activate inserts, Wiremold CM Series Open System communication modules, or Ortronics® TracJack or Series II devices.

3) Includes two 20A duplex receptacles located 32-1/2 inches (819mm) above floor.

c. Product: VLP5662345 Large Profile Point5 as manufactured by Legrand.1) Column: Large profile 36 inches (914 mm) high column.2) Anodized aluminum frame with round end channels. Includes two

adapters for Pass & Seymour Activate inserts, Wiremold CM Series Open System communication modules, or Ortronics® TracJack or Series II devices.

3) Includes four 20A duplex receptacles located 32-1/2 inches (819mm) above floor.

d. Datacom Connectivity: Provide required devices by the following manufacturer.1) Ortronics TracJack® and Series II Modular Connectivity Solutions.2) Pass & Seymour Activate Modular Inserts3) Open System Communication Modules.

8. Mechanical Security: All systems shall be mechanically continuous and connected to all electrical outlets, boxes, and cabinets, in accordance with manufacturer's installation sheets.

9. Electrical Security: The system shall be electrically continuous and bonded in accordance with the National Electric Code for proper grounding.

10. System Support: System shall be securely supported at the ceiling and the floor in accordance with manufacturer's installation sheets.

11. Completeness: All systems shall be installed complete, including insulating bushings and inserts where required by manufacturer's installation sheets. All unused openings where wire is exposed shall be closed.

2.15 PRODUCTIVITY PRODUCTS

A. FAS Power (Prefabricated Assemblies for Concrete Block):1. Product: FB816 as manufactured by Legrand Cabofil.2. Design: Each FB816 is shipped pre-wired, fully assembled and ready for rough-in.

Each assembly comes with a clear cover to protect pre-wired P&S PlugTail connectors during construction and painting. Adjustable mounting frame assembly fits within the concrete block cavity to keep assembly in place during joint mortaring process.

3. Assembly: Model numbering system ("Bracket"-"Wiring Component"-"Attachment").a. Bracket #: FB816.b. Wiring Component RPT: Plugtail for receptacle.c. Wiring Component RRPT: Plugtails for 2 receptacles.d. Wiring Component SPT: Plugtails for SP switch.e. Wiring Component SSPT: Plugtails for 2 SP switches.f. Wiring Component S3PT: Plugtail for 3-way switch.g. Wiring Component S3S3PT: Plugtails for 2 3-way switches.h. Wiring Component SS3PT: Plugtails for SP switch and 3 way.i. Wiring Component S3SPT: Plugtails for SP switch and 3-way.j. Wiring Component D: 1-Gang ring only.

16000-91

Page 92:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

k. Wiring Component DD: 2-Gang ring only.l. Wiring Component DGP: 1-Gang ring with ground wire.m. Wiring Component DDGP: 2-Gang ring with ground wire.n. Wiring Component JGP: 3-O ring with ground wire.o. Attachment 12CON: 1/2 inch (13 mm) EMT compression connector.p. Attachment 34CON: 3/4 inch (19 mm) EMT compression connector.q. Attachment CON: 1 inch (25 mm) EMT compression connector.r. Attachment 12EMT02: 1/2 inch (13 mm) EMT connector with 2 feet (610 mm)

stub.s. Attachment 34EMT02: 3/4 inch (19 mm) EMT connector with 2 feet (610 mm)

stub.t. Attachment 1EMT02: 1 inch (25 mm) EMT connector with 2 feet (610 mm) stub.

PART 3 EXECUTION

3.1 EXAMINATION

A. Do not begin installation until substrates have been properly prepared.

3.2 HOME SYSTEMS/AUDIO-VISUAL - GENERAL

A. Leftover construction dust, metal filings and debris from drilling, cutting, sawing and any other construction activity can be detrimental to electronic equipment in production technology room environments. The Contractor shall be required to place dust protective plastic covers at all times over HVAC systems, UPS power systems and any other equipment or furniture that is occupying the space during construction when the Contractor is doing construction work in the immediate vicinity of this equipment. This will prevent dust, metal filings and debris collection in the equipment during construction. Dust protection covers to be approved by the Owner prior to installation.

B. The Contractor shall do vacuuming, mopping and cleaning of immediate environment around any area where drilling, cutting, and sawing and any other construction activity is taking place at the same time of the construction activity.

C. The Contractor shall do vacuuming, mopping and cleaning of the entire technology room environment prior to termination of cabling and prior to electronic hardware being installed inside the technology rooms.

3.3 HOME SYSTEMS/AUDIO-VISUAL INSTALLATION

A. Cabinets, racks, frames and enclosures shall be located and installed as indicated in the specifications and on the drawings.

B. Follow installation guidelines as per the requirements specified by the manufacturer.

C. Seismic bracing:1. Provide seismic support and bracing for all cabinets, racks, frames and enclosures

installed under this work as required by local building code requirements and to project structural requirements.

2. Seismic bracing shall not obstruct or interfere with needed access clearances and cable bend radius requirements.

D. Provide the necessary clearances in the front and rear of cabinets, racks, frames and enclosures so that the technology hardware and cabling infrastructure can be accessed without obstruction by other utilities or architectural components.

E. All cabinets, racks, frames and enclosures shall be grounded to the telecommunications ground bus bar.

16000-92

Page 93:   · Web viewProduct submittals: Provide an electronic Submittal Log matrix, listing each of the components to be used. Submittal Log fields to include referenced specification section,

F. Mounting screws not used for installing patch panels and other hardware shall be bagged and left within a well-marked container upon completion of the installation.

3.4 HOME SYSTEMS/AUDIO-VISUAL CLOSEOUT AND ACCEPTANCE

A. No additional burden to the Owner regarding costs, network down-time and/or end user interruption shall result from the re-installation of specified components. Scheduling for reinstallation work shall be coordinated, in writing, with the Owner prior to beginning the work.

B. All specified Communications systems indicated on the drawings and specifications shall be complete.

C. Specified shop drawings and product submittals shall have been submitted for review and all review comments and deficiencies shall have been resolved. Final shop drawings and product submittals shall have been submitted, reviewed and found to meet the requirements of the specifications.

D. Issues and deficiencies identified in field reports and punch lists shall have been resolved. Final as-built drawings shall have been submitted, reviewed and found to meet the requirements of the specifications.

E. Contractor shall provide written notice of final completion of the telecom infrastructure. Upon receipt, the Owner's Representative will review/observe the completed installation. Once the Owner's Representative is satisfied that all work is in accordance with the Contract Documents, the Contractor will be notified in writing.

F. If substrate preparation is the responsibility of another installer, notify Architect of unsatisfactory preparation before proceeding.

3.5 PREPARATION

A. Clean surfaces thoroughly prior to installation.

B. Prepare surfaces using the methods recommended by the manufacturer for achieving the best result for the substrate under the project conditions.

3.6 INSTALLATION

A. Install in accordance with manufacturer's instructions.

3.7 PROTECTION

A. Protect installed products until completion of project.

B. Touch-up, repair or replace damaged products before Substantial Completion.

END OF SECTION