LV circuit breakersEasyPact from 15 A to 250 A 0

0

Catalogue

2005

Page 2: 01_3 EasyPact 15-250A En

545E1003TDM_Ver1.0.fm/125 novembre 2004 10:36

EasyPact General contents 0

Presentation 545E1003TDM

Circuit breakers 545E2003TDM

Busbars 545E3003TDM

Installation guide 545E4003TDM

Page 3: 01_3 EasyPact 15-250A En

545E1003_Ver4.0.fm/2 9 février 2005 13:41

EasyPact Follow the wayto simplicity

With only two sizes of circuit breakers, the EasyPact system is the simple and universal solution to fit all the needs in terms of low voltage protection.

EasyPact range complies to worldwide standards

b IEC 60947-2b JIS 8370b JIS 8201-2-1 A1 / A2b GB 14048-2b Nema-AB1b UL508b CSA22-2b IACS for Merchant Marine.(International Association of ClassificationSocieties: Veritas, Germanisher Lloyd's,Rina, USSR, Lloyd's Register)

with international certifications and approuvalsby independant LaboratoriesASEFA, KEMA, TILVA, TÜV, UL.

EZ

C10

0-28

EZ

C25

0-37

DB

1064

79D

B10

6478

TM

Page 4: 01_3 EasyPact 15-250A En

545E1003_Ver4.0.fm/39 février 2005 13:41

0

Easy to chooseEasyPact brings you easy solutionsb from 15 A to 250 Ab up to 36 kA at 415 Vb in only two frame sizesb with a complete range of auxiliaries

and accessories.

Easy to installb common installation dimensions

- same depth- same panel cut-out.

b the smallest depth (60 mm) b no settings, no adjustmentsb field-installable auxiliaries and accessoriesb bare cables connected through cable lugs,

screwed inside the breaker.

Easy to useb a thermal calibration suitable for use

at 50°C without deratingb safe and reliable

with positive contact indication(no risk for maintenance: when green flag is visible, main contacts of the breakers are effectively opened, and not welded).

DB

1064

80D

B10

6481

75 mm105 mm60 mm

50 mm

DB

1064

82

Page 5: 01_3 EasyPact 15-250A En

545E1003_Ver4.0.fm/4 9 février 2005 13:41

Page 6: 01_3 EasyPact 15-250A En

545E2003TDM_Ver1.0.fm/114 décembre 2004 09:58

EasyPact Circuit breakers

General characteristics 545E2003/2

Characteristics 545E2003/4

Catalogue numbers 545E2003/6EZC100B 7.5 kA (400 V AC) 545E2003/6EZC100F 10 kA (400 V AC) 545E2003/6EZC100N 15 kA (400 V AC) 545E2003/7EZC100H 30 kA (400 V AC) 545E2003/8EZC250F 18 kA (400 V AC) 545E2003/9EZC250N 25 kA (400 V AC) 545E2003/9EZC250H 36 kA (400 V AC) 545E2003/10

Electrical and mechanical accessories overview 545E2003/11EasyPact EZ100 545E2003/11EasyPact EZ250 545E2003/12

Electrical auxiliaries 545E2003/13

Direct rotary handle 545E2003/15

Extended rotary handle 545E2003/16

Power connections and cable lugs 545E2003/17

Power connections and insulation of live parts 545E2003/18

DIN rail adaptor, padlocking, sealing screws 545E2003/19

Page 7: 01_3 EasyPact 15-250A En

545E

Circuit breakers General characteristics 0

DB

1062

05

DB

1062

06

EZC100H EZC250H

DB

1062

07

Standardised characteristics indicated on the rating plate:Ui: rated insulation voltageUimp: rated impulse withstand voltageIcu: ultimate breaking capacity, for various

values of the rated operational voltage Ue

Cat: utilisation categoryIcs: service breaking capacity

suitable for isolation

EZ

101P

R-2

0

EZ

101P

R-2

8

18~277/480Y

~

JIS C 8370 220 ~ 100NEMA-AB1 240 ~ 100(HIC)

380/400 ~ 30 / 15220/240 50 / 25110/130 ~ 100 / 50

415 ~ 30 / 7.5

Icu / Ics(kA)Ue(V)IEC947-2

Ui=690V Uimp=6kVCat.A 50/60Hz

TH01

285

550 ~ 10 / 2.5

EZC100H 100A

Compliance with standardsEasyPact circuit breakers and auxiliaries comply with the following international standards:b IEC 60947-1 - general rulesb IEC 60947-2 - low-voltage switchgear and controlgear, part 2 (circuit breakers)b European (EN 60947-1 and EN 60947-2) and the corresponding national standardsb GB 14048-2b JIS C 8370: Japanese industrial standard for molded case circuit breakerb JIS C 8201-2-1 Annex 1 and Annex 2b NEMA AB1 (High Interrupting Capacity): American standardb UL508/CSA 22-2 No. 14.

Approvals and Certficationsb IEC certfication by independent laboratories (ASEFA, KEMA, TÜV)

b e marking

b certified by third party Tilva

b certified by third party Underwriter Laboratories as a "Manual Motor Controller" (approval pending for EZC100).

Vibration and shock withstand testEasyPact circuit breakers resist mechanical vibrations and shocks. Tests are carried out in compliance with standard IEC 60068-2-6 for the levels required by merchant-marine inspection organisation IACS: International Association of Classification Societies (Veritas, Germanisches Lloyd’s, Rina, USSR, Lloyd’s Register).b 2 to 13.2 Hz: amplitude ± 1 mm13.2 to 100 Hz: acceleration 0.7g.

Pollution degreeEasyPact circuit breakers are certified for operation in pollution-degree III environments as defined by IEC standard 60947 (industrial environments).

TropicalisationEasyPact circuit breakers have successfully passed the tests prescribed by the following standards for extreme atmospheric conditions:b IEC 60068-2-1 - dry cold (- 55 °C)b IEC 60068-2-2 - dry heat (+ 85 °C)b IEC 60068-2-30 - damp heat (95% relative humidity at 55 °C)b IEC 60068-2-52 - salt mist (severity level 2).

Positive contact indicationAll EasyPact circuit breakers are suitable for isolation as defined in IEC standard 60947-2:b the isolation position corresponds to the O (OFF) positionb the operating handle cannot indicate the O (OFF) position (“green colour” visible) unless the contacts are effectively openb padlocks may not be installed unless the contacts are openb installation of a rotary handle does not alter the reliability of the position-indication system.The isolation function is certified by tests guaranteeing:b the mechanical reliability of the position indication systemb the absence of leakage currentsb overvoltage withstand capacity between upstream and downstream connections.

Environmental protectionEasyPact circuit breakers take into account important concerns for environmental protection. Most components are recyclable and the parts are marked as specified in applicable standards.

2003_Ver5.0.fm/2 13 avril 2005 18:27

Page 8: 01_3 EasyPact 15-250A En

Circuit breakers General characteristics 0

Ambient temperatureb EasyPact has been particularly designed to hold 100% In at 50 °C without tripping in normal conditionb EasyPact circuit breakers may be used between - 25 °C and + 70 °Cb the permissible storage-temperature range for EasyPact circuit breakers in the original packing is - 35 °C to + 85 °C.

DB

1060

03 InstallationEasyPact circuit breakers are designed for easy installation in the various types of switchboards. They may be mounted vertically, horizontally or flat on their back without any derating of characteristics

Installation positions

DB

1060

37 Power supplyEasyPact circuit breaker can be supplied from either the top or the bottom (reverse feeding) without any reduction in performance. This capability facilitates connection when installed in a switchboard.

Degree of protectionAs per standards IEC 60529 (IP degree of protection) and EN 50102 (IK degree of protection against external mechanical impacts).

Reverse feeding

Bare circuit breaker with terminal shields

DB

1060

13

With toggle IP20 IK07

DB

1060

14

With direct rotary handle standard IP40 IK07

Circuit breaker installed in a switchboard

DB

1060

15

DB

1060

35

With toggle IP40 IK07

DB

1060

16

With direct rotary handle standard/VDE MCC

IP54 IK07

DB

1060

17

With extended rotary handle IP54 IK08

545E2003_Ver5.0.fm/313 avril 2005 18:27

Page 9: 01_3 EasyPact 15-250A En

545E

Circuit breakers Characteristics 0

EZ

110P

-34

EZC100

EasyPact circuit breakersNumber of polesRated current (A) In at 40 °C

Rated insulation voltage (V) UiRated impulse withstand voltage (kV) UimpRated operational voltage (V) Ue AC 50/60 Hz

DC

Electrical characteristics as per IEC 60947-2 and EN 60947-2Ultimate breaking capacity (kA rms) Icu AC 50/60 Hz 110/130 V

220/230/240 V

380 V400/415 V440 V

550 VDC 125 V (1P)

250 V (2P in series)

Rated service breaking capacity Ics % Icu 110-400 V

PB

1012

10-2

7

EZC250

415-550 VSuitability for isolationUtilisation category

Pollution degreeEndurance (C-O cycles) Mechanical

Electrical In/415 V

Electrical characteristics as per JIS C8370Breaking capacity (kA) Icn AC 50/60 Hz 130 V

220 V460 V

Electrical characteristics as per NEMA-AB1Breaking capacity (kA) HIC AC 50/60 Hz 240 V

277/480Y V

Protection

Overload protection BimetalInstantaneous protection Magnetic

AuxiliariesIndication contacts Auxiliary switch AX

Alarm switch AL

Combined AX + AL AXALVoltage releases Shunt trip release SHT

Undervoltage release UVR

InstallationConnection Crimp lugs/bars

Accessories Box lugs for bare cablesRotary handles direct

extended

Terminal extensionsSpreadersPhase barriers

Terminal shieldsPadlocking systemDIN rail plate

Dimension and weightDimensions (mm) D x H

WWeight (kg)

2003_Ver5.0.fm/4 13 avril 2005 18:27

Page 10: 01_3 EasyPact 15-250A En

Circuit breakers Characteristics 0

EZC100B EZC100F EZC100N EZC100H EZC250F EZC250N EZC250H3 3 1 3 1 2-3 3 3 2-315, 20, 25, 30, 40, 50, 60

15, 20, 25, 30, 40, 50, 60, 75, 80, 100

15, 20, 25, 30, 40, 50, 60, 75, 80, 100

15, 20, 25, 30, 40, 50, 60, 75, 80, 100

15, 20, 25, 30, 40, 50, 60, 75, 80, 100

15, 20, 25, 30, 40, 50, 60, 75, 80, 100

100, 125, 150, 160, 175, 200, 225, 250

100, 125, 150, 160, 175, 200, 225, 250

100, 125, 150, 160, 175, 200, 225, 250

690 690 690 690 690 690 690 690 690

6 6 6 6 6 6 6 6 6550-

550250

550250

550250

550250

550250

550250

550250

550250

10 25 25 25 50 100 25 50 8510 25 18 25 25 100 (1) 25 50 857.5 10 2.5 18 5 30 18 25 36

7.5 10 2.5 15 5 30 18 25 365 7.5 - 10 - 20 15 20 252.5 5 - 5 - 10 5 8 10

- 55

5-

55

10-

1010

55

2020

3030-

25% 50% 50% 50% 50% 50% 50% 50% 50%25% 50% 50% 50% 50% 25% 50% 50% 50%

A A A A A A A A A3 3 3 3 3 3 3 3 3

8 500 8 500 8 500 8 500 8 500 8 500 10 000 10 000 10 0001 500 1 500 1 500 1 500 1 500 1 500 5 000 5 000 5 000

10 25 15 25 30 100 30 50 8510 25 - 25 - 100 30 50 85

5 7.5 - 10 - 25 15 25 35

- - 10 25 18 100 25 50 85- - 10 (2) 10 18 (2) 18 (3) 15 18 25 (3)

fixed fixed fixed fixed fixed fixed fixed fixed fixedfixed fixed fixed fixed fixed fixed fixed fixed fixed

- -

- -- -- -

- -

- - (3)

- - (3)

- - - - - -

- - (3)

- - -

60 x 130 60 x 130 60 x 130 60 x 130 60 x 130 60 x 130 60 x 165 60 x 165 60 x 16575 75 25 75 25 50 (2P), 75 (3P) 105 105 1050.78 0.78 0.28 0.78 0.28 0.6(2P), 0.78(3P) 1.3 1.3 1.1 (2P), 1.3 (3P)

(1) 50 kA for 2 poles(2) for 277 V only(3) for 3 poles only

545E2003_Ver5.0.fm/513 avril 2005 18:27

Page 11: 01_3 EasyPact 15-250A En

545E

Circuit breakers Catalogue numbers 0

EZC100B 7.5 kA (400 V AC)EZC100F 10 kA (400 V AC)

EZ

104P

-20

EZC100B 3 poles

EZC100B 15 to 60 A

Designation EZC100BCurrent rating (A) 15 - 20 - 25 - 30 - 40 - 50 - 60Number of poles 3PBreaking capacities (kA rms) as per IEC 60947-2

Ue (V) Icu (kA) Ics (% Icu)Ue = 550 V AC 220/230/240 10 25%Ui = 690 V 380/400/415 7.5 25%

Uimp = 6 kV 440 5 25%550 2.5 25%

Breaking capacities (kA rms) as per JIS C8370Ue (V) Icn (kA)

AC 220 10460 5

Rating Cat. Nb 3P15 A EZC100B301520 A EZC100B302025 A EZC100B302530 A EZC100B303040 A EZC100B304050 A EZC100B305060 A EZC100B3060

EZ

105P

-19

EZC100F 3 poles

EZC100F 15 to 100 A

Designation EZC100FCurrent rating (A) 15 - 20 - 25 - 30 - 40 - 50 - 60 - 75 - 80 - 100Number of poles 3PBreaking capacities (kA rms) as per IEC 60947-2

Ue (V) Icu (kA) Ics (% Icu)Ue = 550 V AC 220/230/240 25 50%Ui = 690 V 380/400/415 10 50%

Uimp = 6 kV 440 7.5 50%550 5 50%

DC 125 (1P) 5 50%

250 (2P) 5 50%Breaking capacities (kA rms) as per JIS C8370

Ue (V) Icn (kA)AC 220 25

460 7.5Rating Cat. Nb 3P15 A EZC100F301520 A EZC100F302025 A EZC100F302530 A EZC100F303040 A EZC100F304050 A EZC100F305060 A EZC100F306075 A EZC100F307580 A EZC100F3080100 A EZC100F3100

2003_Ver5.0.fm/6 13 avril 2005 18:27

Page 12: 01_3 EasyPact 15-250A En

Circuit breakers Catalogue numbers 0

EZC100N 15 kA (400 V AC)

EZ

106P

-10

EZC100N 1 pole

EZ

101P

-19

EZC100N 3 poles

EZC100N 15 to 100 A

Designation EZC100NCurrent rating (A) 15 - 20 - 25 - 30 - 40 - 50 - 60 - 75 - 80 - 100Number of poles 1P and 3PBreaking capacities (kA rms) as per IEC 60947-2

Ue (V) Icu (kA) Ics (% Icu)1P 3P 1P - 3P

Ue = 550 V AC 110/130 25 - 50%Ui = 690 V 220/230/240 18 25 50%Uimp = 6 kV 380 2.5 18 50%

400/415 2.5 15 50%440 - 10 50%550 - 5 50%

DC 125 (1P) 5 5 50%250 (2P) - 5 50%

Breaking capacities (kA rms) as per JIS C8370Ue (V) Icn (kA)

AC 110/130 15 -220 - 25460 - 10

Breaking capacities (kA rms) as per NEMA-AB1Ue (V) HIC (kA)

AC 240 - 25277 10 -480 - 10

Rating Cat. Nb 1P Cat. Nb 3P15 A EZC100N1015 EZC100N301520 A EZC100N1020 EZC100N302025 A EZC100N1025 EZC100N302530 A EZC100N1030 EZC100N303040 A EZC100N1040 EZC100N304050 A EZC100N1050 EZC100N305060 A EZC100N1060 EZC100N306075 A EZC100N1075 EZC100N307580 A EZC100N1080 EZC100N3080100 A EZC100N1100 EZC100N3100

545E2003_Ver5.0.fm/713 avril 2005 18:27

Page 13: 01_3 EasyPact 15-250A En

545E

Circuit breakers Catalogue numbers 0

EZC100H 30 kA (400 V AC)

E

Z10

8P-1

1

EZC100H 1 pole

EZ

101P

-40

EZC100H 2 poles

EZC100H 15 to 100 A

Designation EZC100HCurrent rating (A) 15 - 20 - 25 - 30 - 40 - 50 - 60 - 75 - 80 - 100Number of poles 1P, 2P and 3PBreaking capacities (kA rms) as per IEC 60947-2

Ue (V) Icu (kA) Ics (% Icu)

1P 2P 3P 1P 2P - 3P Ue = 550 V AC 110/130 50 100 - 50% 50%Ui = 690 V 220/230/240 25 50 100 50% 50%

EZ

110P

-34

EZC100H 3 poles

Uimp = 6 kV 380/400/415 5 30 30 50% 50%440 - 20 20 - 25%550 - 10 10 - 25%

DC 125 (1P) 10 10 10 - -250 (2P) - 5 10 - -

Breaking capacities (kA rms) as per JIS C8370Ue (V) Icn (kA)

AC 110/130 30 - -220 - 100 100460 - 25 25

Breaking capacities (kA rms) as per NEMA-AB1Ue (V) HIC (kA)

AC 240 - 100 100277 18 - -480 - 18

Rating Cat. Nb 1P Cat. Nb 2P Cat. Nb 3P15 A EZC100H1015 EZC100H2015 EZC100H301520 A EZC100H1020 EZC100H2020 EZC100H302025 A EZC100H1025 EZC100H2025 EZC100H302530 A EZC100H1030 EZC100H2030 EZC100H303040 A EZC100H1040 EZC100H2040 EZC100H304050 A EZC100H1050 EZC100H2050 EZC100H305060 A EZC100H1060 EZC100H2060 EZC100H306075 A EZC100H1075 EZC100H2075 EZC100H307580 A EZC100H1080 EZC100H2080 EZC100H3080100 A EZC100H1100 EZC100H2100 EZC100H3100

2003_Ver5.0.fm/8 13 avril 2005 18:27

Page 14: 01_3 EasyPact 15-250A En

Circuit breakers Catalogue numbers 0

EZC250F 18 kA (400 V AC)EZC250N 25 kA (400 V AC)

PB

1012

08-2

7

EZC250F 3 poles

EZC250F 100 to 250 A

Designation EZC250FCurrent rating (A) 100 - 125 - 150 - 160 - 175 - 200 - 225 - 250Number of poles 3PBreaking capacities (kA rms) as per IEC 60947-2

Ue (V) Icu (kA) Ics (% Icu)Ue = 550 V AC 220/230/240 25 50%Ui = 690 V 380/400/415 18 50%

Uimp = 6 kV 440 15 50%550 5 50%

DC 125 (1P) 10 50%

250 (2P) 10 50%Breaking capacities (kA rms) as per JIS C8370

Ue (V) Icn (kA)AC 220 30

460 15Breaking capacities (kA rms) as per NEMA-AB1

Ue (V) HIC (kA)AC 240 25

277/480 15 -

Rating Cat. Nb 3P100 A EZC250F3100125 A EZC250F3125150 A EZC250F3150160 A EZC250F3160175 A EZC250F3175200 A EZC250F3200225 A EZC250F3225250 A EZC250F3250

PB

1012

09-2

7

EZC250N 3 poles

EZC250N 100 to 250 A

Designation EZC250NCurrent rating (A) 100 - 125 - 150 - 160 - 175 - 200 - 225 - 250Number of poles 3PBreaking capacities (kA rms) as per IEC 60947-2

Ue (V) Icu (kA) Ics (% Icu)Ue = 550 V AC 220/230/240 50 50%

Ui = 690 V 380/400/415 25 50%Uimp = 6 kV 440 20 50%

550 8 50%

DC 125 (1P) 20 50%250 (2P) 20 50%

Breaking capacities (kA rms) as per JIS C8370Ue (V) Icn (kA)

AC 220 50460 25

Breaking capacities (kA rms) as per NEMA-AB1Ue (V) HIC (kA)

AC 240 50

277/480 18 -Rating Cat. Nb 3P100 A EZC250N3100125 A EZC250N3125150 A EZC250N3150160 A EZC250N3160175 A EZC250N3175200 A EZC250N3200225 A EZC250N3325250 A EZC250N3250

545E2003_Ver5.0.fm/913 avril 2005 18:27

Page 15: 01_3 EasyPact 15-250A En

545E2

Circuit breakers Catalogue numbers 0

EZC250H 36 kA (400 V AC)

PB

1012

11-2

7

EZC250H 2 poles

EZC250H 100 to 250 A

Designation EZC250HCurrent rating (A) 100 - 125 - 150 - 160 - 175 - 200 - 225 - 250Number of poles 2P and 3PBreaking capacities (kA rms) as per IEC 60947-2

Ue (V) Icu (kA) Ics (% Icu)2P 3P

Ue = 550 V AC 220/230/240 85 85 50%

Ui = 690 V 380/400/415 36 36 50%Uimp = 6 kV 440 25 25 50%

550 10 10 50%

DC 125 (1P) 30 30 50%250 (2P) 30 30 50%

PB

1012

10-2

7

EZC250H 3 poles

Breaking capacities (kA rms) as per JIS C8370Ue (V) Icn (kA)

2P 3PAC 220 85 85

460 35 35Breaking capacities (kA rms) as per NEMA-AB1

Ue (V) HIC (kA)2P 3P

AC 240 85 85277/480 - 25 -

Rating Cat. Nb 2P Cat. Nb 3P100 A EZC250H2100 EZC250H3100125 A EZC250H2125 EZC250H3125150 A EZC250H2150 EZC250H3150160 A EZC250H2160 EZC250H3160175 A EZC250H2175 EZC250H3175200 A EZC250H2200 EZC250H3200225 A EZC250H2225 EZC250H3225250 A EZC250H2250 EZC250H3250

003_Ver5.0.fm/10 13 avril 2005 18:27

Page 16: 01_3 EasyPact 15-250A En

Circuit breakers Electrical and mechanical accessories overview 0

EasyPact EZ100

EasyPact circuit breaker EZ100 comes with a full range of accessories to fulfill different application requirements and make it easy for the end-user.

DB

1060

47-1

20

Phase barriers

Terminal shield

Sealing screw

Cable lugs

Spreaders

DIN rail adaptor

Auxiliary switch,

Cable lugs

Phase barriers

Sealable terminal shield

Extended rotary

Direct rotary handle

Padlocking device

Shunt trip,Undervoltage release

Spreadershandle

Sealing screw

Alarm switch,Auxiliary/Alarm switch

545E2003_Ver5.0.fm/1113 avril 2005 18:27

Page 17: 01_3 EasyPact 15-250A En

545E2

Circuit breakers Electrical and mechanical accessories overview 0

EasyPact EZ250

EasyPact circuit breaker EZ250 comes with a full range of accessories to fulfill different application requirements and make it easy for the end-user.

DB

1060

02-1

40

Phase barriers

Terminal shield

Cable lugs

Spreaders

Shunt trip

Cable lugs

Phase barriers

Extended rotary

Direct rotary

Padlocking device

Auxiliary switch,

Undervoltage release

Spreaders

handle

Terminalextensions

Terminal shield

Terminalextensions

handle

Alarm switch,Auxiliary/Alarm switch

003_Ver5.0.fm/12 13 avril 2005 18:27

Page 18: 01_3 EasyPact 15-250A En

Circuit breakers Electrical auxiliaries 0

Indication contactsCommon-point changeover contacts provide remote circuit breaker status information. They can be used for indications, electrical locking, relaying, etc..b Auxiliary switch AX (ON/OFF) indicates the position of the circuit breaker contacts.b Alarm switch AL (trip indication) indicates that the circuit breaker has tripped due to:v an overloadv a short-circuitv operation of a voltage releaseIt returns to de-energised state when the circuit breaker is reset.

Characteristics

Electrical auxiliaries can be installed in either location (left or right) regardless of the function (AX - AL - AXAL)

PB

1012

19-2

7P

B10

1220

-27

Electrical auxiliaries are pre-wired

PB

1012

23-1

5

PB

1012

26-1

5

Auxiliary switch (AX)EZAUX10

Auxiliary switch (AX)EZEAX

ContactsRated thermal current (A) 5Minimum load 10 mA at 24 V

Utilisation category (IEC 60947-5-1) AC12 AC15 DC12 DC14Operational current (A) 24 V 5 5 4 3

48 V 5 5 2.5 1

125 V 5 3 0.4 0.4250 V 3 2 0.2 0.2

ConnectionsConnection wire length 500 mmCross-section EZC100: 1 mm2, EZC250: 1.5 mm2

DB

1060

33

Designation Cat. number Cat. numberEZC100 EZC250

Auxiliary switch (AX) EZAUX10 EZEAXAlarm switch (AL) EZAUX01 EZEALAuxiliary/Alarm switch (AX/AL) EZAUX11 EZEAXAL

All EasyPactelectrical auxiliairesare "snapped in place"

545E2003_Ver5.0.fm/1313 avril 2005 18:27

Page 19: 01_3 EasyPact 15-250A En

545E2

Circuit breakers Electrical auxiliaries 0

Remote trippingShunt Trip (SHT) or Under Voltage Release (UVR).

bbbb Shunt Trip (SHT)v this release trips the circuit breaker when the control voltage rises above 0.7 x Unv control signals can be of the impulse type (> 20 ms) or maintained.

b Under Voltage Release (UVR)v this release trips the circuit breaker when the control voltage drops below a tripping thresholdv tripping threshold between 0.35 and 0.7 times the rated voltagev circuit breaker closing is possible only if the voltage exceeds 0.85 times the rated voltagev circuit breaker tripping by an UVR release meets the requirements of standard IEC 60947-2.

bbbb OperationWhen the circuit breaker has been tripped by an UVR or SHT release, it must be reset locally:v UVR or SHT tripping takes priority over manual closingv in the presence of a standing trip order, closing of the contacts, even temporary, is not possible.

Characteristics

bbbb Installationv EZC100 SHT and UVR: internal mounting (left or right side)v EZC250: - SHT: internal mounting (right side)

- UVR: external mounting (right side).

PB

1012

22-2

7

SHT (MX) and UVR (MN) voltage release on EZC100

PB

1012

21-2

9

SHT (MX) and UVR (MN) voltage release on EZC250

Mechanicalmechanical endurance 10% of MCCB mechnical endurance

Electrical EZC100 EZC250AC DC

SHT pick-up consumption response time

< 30 VA< 50 ms

< 30 VA< 50 ms

< 35 W< 100 ms

UVR seal-in consumption response time

< 5 VA< 50 ms

< 5 VA< 50 ms

< 10 W< 100 ms

Connections EZC100 EZC250SHT pre-wired (1 mm2) pre-wired (0.5 mm2)

UVR pre-wired (1 mm2) screws (< 2 mm2)

PB

1012

29-1

5

PB

1012

31-1

5

Shunt TripEZASHT

Shunt TripEZESHT

PB

1012

30-1

5

PB

1012

32-1

5

Under Voltage ReleaseEZAUVR

Under Voltage ReleaseEZEUVR

Designation Cat. number Cat. numberEZC100 EZC250

Shunt Trip 100-130 V AC EZASHT100AC 100-120 V AC EZESHT100ACRelease (SHT) 120-130 V AC EZESHT120AC

200-277 V AC EZASHT200AC 200-240 V AC EZESHT200AC277 V AC EZESHT277AC

380-480 V AC EZASHT380AC 380-440 V AC EZESHT400AC440-480 V AC EZESHT440AC

24 V DC EZASHT024DC 24 V DC EZESHT024DC48 V DC EZASHT048DC 48 V DC EZESHT048DC

Under Voltage 110-130 V AC EZAUVR110AC 110-130 V AC EZEUVR110ACRelease (UVR) 200-240 V AC EZAUVR200AC 200-240 V AC EZEUVR200AC

277 V AC EZAUVR277AC 277 V AC EZEUVR277AC380-415 V AC EZAUVR380AC 380-415 V AC EZEUVR400AC440-480 V AC EZAUVR440AC 440-480 V AC EZEUVR440AC24 V DC EZAUVR024DC 24 V DC EZEUVR024DC48 V DC EZAUVR048DC 48 V DC EZEUVR048DC125 V DC EZAUVR125DC 125 V DC EZEUVR125DC

003_Ver5.0.fm/14 13 avril 2005 18:27

Page 20: 01_3 EasyPact 15-250A En

Circuit breakers Direct rotary handle 0

Direct rotary handle suitable for Motor Control Centre (MCC) switchboardsb Degree of protection IP40 or IP54, IK07 (IP54 with gasket provided with the EZAROTDS and EZEROTDS).

b The direct rotary handle maintains:v suitability for isolationv indication of the three positions O (OFF), I (ON) and trippedv circuit breaker locking capability in the OFF position by one to three padlocks, (padlock not supplied) shackle diameter Ø 5 for EZC100, Ø 8 for EZC250v door opening disabled when the circuit breaker is ONv circuit breaker closing is disabled if the door is open.

PB

1012

33-4

0

Direct rotary handle for EZC100

IP40 or IP54

PB

1012

34-4

0

DB

1060

05

DB

1060

06

Direct rotary handle for EZC250 EZC100 EZC250

gasketfor IP54

gasketfor IP54

Padlocking

DB

1060

07

DB

1060

08

EZC100 EZC250

Designation Cat. number Cat. numberEZC100 EZC250

Direct rotary handle standard EZAROTDS EZEROTDS

545E2003_Ver5.0.fm/1513 avril 2005 18:27

Page 21: 01_3 EasyPact 15-250A En

545E2

Circuit breakers Extended rotary handle 0

Extended rotary handleThis handle makes it possible to operate circuit breakers installed at the back of switchboards, from the switchboard front.

b Degree of protection IP40 or IP54, IK08(with gasket provided with the EZAROTE and EZEROTE)

b The extended rotary handle maintains:v suitability for isolationv indication of the three positions O (OFF), I (ON) and trippedv circuit breaker locking capability in the OFF position by one to three padlocks, (padlock not supplied) shackle diameter: Ø 5 for EZC100, Ø 8 for EZC250v door opening disabled when the circuit breaker is ON.

b The extended rotary handle is made up of:v a unit on the front cover of the circuit breaker (secured by screws)v an assembly (handle and front plate) on the door that is always secured in the same position, whether the circuit breaker is installed vertically or horizontallyv an extension shaft that must be adjusted to the distance (min/max distance between back of circuit breaker and door is 145/422 mm).

PB

1012

35-4

0

Extended rotary handle for EZC100

IP40 or IP54

PB

1012

36-4

0

DB

1062

81

DB

1062

82

Extended rotary handle for EZC250 EZC100 EZC250

Padlocking

DB

1060

28

Designation Cat. number Cat. numberEZC100 EZC250

Extended rotary handle EZAROTE EZEROTE

003_Ver5.0.fm/16 13 avril 2005 18:27

Page 22: 01_3 EasyPact 15-250A En

Circuit breakers Power connections and cable lugs0

Nota : For EZC250, when cable lugs are used on upstream side, breaking capacity is limited to 50 % of rated value.

DB

1060

29

EZC100 with M5 / M8 screws

All EasyPact circuit breakers are supplied with terminal screws15 to 50 A Screw M5

E88

221

60 to 100 A Screw M8

E88

222

100 to 250 A Screw M8D

B10

6044

Connection of insulated bars or cables with lugsEZC100 EZC250

DB

1060

18

Bars L (mm) < 17 < 25

E50

702

l (mm) d + 10 d + 10d (mm) < 7 < 8e (mm) < 6 < 6

Ø (mm) < 50 A 5.5 -> 50 A 8.5 9

Crimp lugs L (mm) < 17 < 25

d (mm) < 9 < 8Ø (mm) < 50 A 5.5 -

> 50 A 8.5 9

Tightening torque (N.m) < 50 A 2 N.m -> 50 A 5.5 N.m 13 N.m

L

Ø

e

dl

400

L

Connection of bare cables with cable lugsThis connector screws directly to the standard connectors. It is used to connect:< 50 A (EZC100) > 50 A (EZC100) > 100 A (EZC250)

E88

190

E88

189

DB

1060

45

cables from 2.5 to 16 mm2 cables from 10 to 50 mm2 cables from 42.2 to 150 mm2

DB

1060

32

Designation Cat. number Cat. numberEZC100 EZC250

Cable lug up to 50 A (set of 2) EZALUG0502 -Cable lug up to 50 A (set of 3) EZALUG0503 -Cable lug from 60 A up to 100 A (set of 2) EZALUG1002 -Cable lug from 60 A up to 100 A (set of 3) EZALUG1003 -Cable lug from 100 A up to 250 A (set of 3) - EZELUG2503

545E2003_Ver5.0.fm/1713 avril 2005 18:27

Page 23: 01_3 EasyPact 15-250A En

545E2

Circuit breakers Power connections and insulation of live parts 0

SpreaderIncreases the pitch of the circuit breaker terminals:b EZC100 from 25 mm to 35 mmb EZC250 from 35 mm to 45 mm.

Terminal extensionsAdditional terminal extensions are available for EZC250.

Phase barriersb safety accessories for maximum insulation at the power connection pointsb slide easily onto the circuit breakerb usable with all other connection accessories, except terminal shieldsb each breaker is delivered with a set of 2 phase barriers for a 3 poles breaker and1 phase barrier for a 2 poles breakerb an additional set of phase barriers is available for insulation between 2 side by side mounted breakers or outgoings.

Terminal shieldb insulating accessories used for protection against direct contact with power circuitsb designed for front connection only (long terminal shield)b designed for 3 poles base only.

PB

1012

40-2

5

Spreader

PB

1012

41-2

5

Terminal extensionsD

B10

6041

DB

1060

46

Designation Cat. number Cat. numberEZC100 EZC250

Spreader (1 set of 3) EZASPDR3P EZESPDR3PTerminal Extensions (1 set of 3) EZETEX

PB

1012

43-2

0

Phase barriers

DB

1060

21

DB

1060

22

Designation Cat. number Cat. numberEZC100 EZC250

Phase barriers (set of 2) EZAFASB2 EZEFASB2

PB

1012

44-2

5

PB

1012

45-2

5

Terminal shield (3P only) for EZC100

Terminal shield for EZC250

DB

1060

26

Designation Cat. number Cat. numberEZC100 EZC250

Terminal shield for 3P only (set of 2) EZATSHD3P EZETSHD3P

003_Ver5.0.fm/18 13 avril 2005 18:27

Page 24: 01_3 EasyPact 15-250A En

Circuit breakers DIN rail adaptor, padlocking, sealing screws 0

DIN rail adaptorMounting on a DIN rail is possible using a special adaptor (for EZC100 only).

Padlocking systemLocking in the OFF position guarantees isolation as per IEC 60947-2.Padlocking system can receive: b up to 2 padlocks Ø 5 mm (padlocks not supplied) for EZC100b up to 3 padlocks Ø 8 mm for EZC250 (padlocks not supplied)

Sealing screws

PB

1012

46-2

5

DIN rail adaptorD

B10

6011

Mounting on DIN rail (optional)

Designation Cat. number Cat. numberEZC100 EZC250

DIN rail adaptor EZADINR -

PB

1012

47-2

5

PB

1012

48-2

5

DB

1060

10

DB

1060

09

Padlocking device for EZC100

Padlocking device for EZC250

Toggle locking using a removable device :for EZC100 for EZC250

Designation Cat. number Cat. numberEZC100 EZC250

Padlocking system EZALOCK EZELOCK

PB

1012

49-2

5

Sealing screws (set of 2)

DB

1060

27

Designation Cat. number Cat. numberEZC100 EZC250

Sealing screws (set of 2) EZASSCR -

545E2003_Ver5.0.fm/1913 avril 2005 18:27

Page 25: 01_3 EasyPact 15-250A En

545E2

003_Ver5.0.fm/20 13 avril 2005 18:27
Page 26: 01_3 EasyPact 15-250A En

545E3003TDM_Ver1.0.fm15 novembre 2004 08:02

EasyPact Busbars

Introduction 545E3003/2

Busbars characteristics 545E3003/4

Main busbars and extension 545E3003/5

Accessories 545E3003/6

Page 27: 01_3 EasyPact 15-250A En

545E3003_Ver1.0.fm/2 17 décembre 2004 09:39

Busbars Introduction 0

DB

1060

19

Page 28: 01_3 EasyPact 15-250A En

545E3003_Ver1.0.fm/317 décembre 2004 09:39

Busbars Introduction 0

The EasyPact Busbar - engineered and certified together with the EasyPact MCCB to provide superior performance, flexibility and value. Simply the best solution for your distribution panel needs:b available for 250 A, 400 A or 630 A main incoming currentb available for 4, 6, 8, 10 or 12 Ways (3 poles) EasyPact 100 A (max.) outgoing MCCB’sb 400 A and 630 A systems can accept an additional 2 or 4 EasyPact 250 or Compact NS/NB160/250 A outgoing MCCB’sb designed and tested to meet IEC 60439-1 requirementsb completely assembled in ISO certified facility for easy installation into locally made enclosures.

EZ

116P

-70

Premium Materials make a premium busbar system:b solid copper busbars and connectors for cool, care-free operationb electro-tin plating on all busbars and connectors for corrosion resistance in all environmentsb fiberglass reinforced nylon bus supports for strength and dimensional stabilityb molded thermoplastic phase barriers to maintain alignment and ensure electrical isolation between phasesb a nameplate with Schneider Electric on the bottom line - stands for quality and reliability.

Page 29: 01_3 EasyPact 15-250A En

545E3003_Ver1.0.fm/4 17 décembre 2004 09:39

Busbars Busbars characteristics 0

Compliance with standardsThe EasyPact Busbar System is designed and certified to meet all international requirements specified in IEC 60439-1 relating to construction of Low Voltage switchgear and controlgear assemblies, including:b verification of temperature - rise limitsb verification of dielectric propertiesb verification of short-circuit withstand strengthb verification of clearances and creepage distances.In addition, the system has been type-tested in ASTA labs to confirm the short-circuit and short-time withstand ratings.

EZ

148P

-60

Enclosed 10 ways Busbar 250 A with 250 A main incomer

EasyPact Busbar System EZB250 EZB400 EZB630Number of outgoing MCCB’s EasyPact 100 A (max.) 4

Ways6 Ways

8Ways

10 Ways

12 Ways

4 Ways

6 Ways

8Ways

10 Ways

12 Ways

4 Ways

6 Ways

8Ways

10 Ways

12 Ways

1P 12 18 24 30 36 12 18 24 30 36 12 18 24 30 36

2P 6 8 12 14 18 6 8 12 14 18 6 8 12 14 183P 4 6 8 10 12 4 6 8 10 12 4 6 8 10 12

EZ/NS/NB branch breaker No extension Yes (2 or 4 Ways) Yes (2 or 4 Ways)

Electrical characteristicsRated incoming current (A) 250 400 630Rated operational voltage (V) AC 50/60 Hz 550 550 550Rated insulation voltage (V) 690 690 690Breaking capacity Refer to cascading tables page 17

Rated short-time withstand current (kA rms)

1 sec. 30 40 40

DimensionsDimensions (mm) L x W x D 4 Ways 268.5 x 416 x 82.5 290 x 416 x 107 290 x 416 x 107

6 Ways 343.5 x 416 x 82.5 365 x 416 x 107 365 x 416 x 1078 Ways 418.5 x 416 x 82.5 440 x 416 x 107 440 x 416 x 10710 Ways 493.5 x 416 x 82.5 515 x 416 x 107 515 x 416 x 107

12 Ways 568.5 x 416 x 82.5 590 x 416 x 107 590 x 416 x 107

Page 30: 01_3 EasyPact 15-250A En

545E3003_Ver1.0.fm/517 décembre 2004 09:39

Busbars Main busbars and extension 0

EZ

149P

-60

Main busbarThe core of the EasyPact Busbar System includes the main busbars and outgoing connectors for EasyPact MCCB’s.

Designation Cat. numberType EZB250 EZB 400 EZB630Main busbar current rating 250 A 400 A 630 A

# Branch Ways (3 poles EasyPact MCCB’s)4 Ways EZB250W04 EZB400W04 EZB630W046 Ways EZB250W06 EZB400W06 EZB630W068 Ways EZB250W08 EZB400W08 EZB630W0810 Ways EZB250W10 EZB400W10 EZB630W1012 Ways EZB250W12 EZB400W12 EZB630W12

EasyPact Busbar EZB250W08

DB

1060

04

4 Ways with 3 poles

DB

1060

20

6 Ways with 3 polesD

B10

6023

8 Ways with 3 poles

DB

1060

24

10 Ways with 3 poles

DB

1060

25

12 Ways with 3 poles

DB

1063

06

6 Ways with 1 pole

DB

1063

07

6 Ways with 1 pole

E88

637-

60

EasyPact and Compact NS/NB branch extensionFor applications calling for larger than 100 A outgoing MCCB’s, EasyPact Busbar rated 400 A and 630 A can accept the 2 Ways or 4 Ways EasyPact and Compact NS/NB branch extension for up to four additional 250 A max. outgoing circuits.EasyPact and Compact NS/NB branch extensions simply connect directly to the terminals provided on the EZB400 and EZB630 EasyPact Busbar.

Designation Cat. numberEZ/NS/NB branch breaker extention

2 Ways EZBNS24 Ways EZB2NS2

EasyPact and Compact NS/NB branch breaker extension 2 Ways

Page 31: 01_3 EasyPact 15-250A En

545E3003_Ver1.0.fm/6 17 décembre 2004 09:39

Busbars Accessories 0

E88

301-

50

D

B10

6042

....

...

Main incoming connectionsIncoming cables with crimped lugs can connect directly to the terminals provided.

EZ

117P

-60

Main connectorsFor installing a main disconnect device (EasyPact or Compact NS/NB MCCB or INS switch) ahead of EasyPact Busbar, use the tin-plated copper connector kits below.

Designation Cat. numberMain Busbar current rating 250 A 400 A 630 A

Main disconnect device for EasyPact or Compact NS/NB or INS switch

EZB250MCNS EZB400MCNS EZB630MCNS

E88

309-

50

Mechanical lugsFor incoming cables without crimped lugs, use the mechanical lug kits below. Each kit contains three aluminium lugs suitable for copper or aluminium cables.

Designation Cat. numberMain Busbar current rating 250 A 400 A 630 A

Incoming cable size 16-150 mm2 35-300mm2 25-240 mm2

2 cables per phaseLug kit EZB250MLUG EZB400MLUG EZB630MLUG

DB

1060

43

E88

310-

54

Connector capsConnector caps are available to isolate the ends of connectors in positions where branch breakers are not installed.Mounting screws are provided for an insulating barrier (locally provided) to cover the branch connectors when IP2X finger safety is specified.

Designation Cat. numberConnector caps (set of 3)

EasyPact branch MCCB EZB100CAPEasyPact or Compact NS/NB branch MCCB

EZB250CAP

DB

1063

9

= =

≤37

>10

DB

1062

09

Page 32: 01_3 EasyPact 15-250A En

545E4003TDM_Ver1.0.fm/117 décembre 2004 09:47

EasyPact Installation guide

Dimensions 545E4003/2EasyPact 100 545E4003/2EasyPact 250 545E4003/3Busbar EZB250 545E4003/8Busbars EZB400/630 545E4003/9EasyPact or Compact NS/NB branch extensions layout 545E4003/10

Safety clearances and minimum distances 545E4003/11

Temperature derating 545E4003/12

Tripping curves 545E4003/13

Current-limiting curves 545E4003/15

Cascading 545E4003/16

Cascading tables 545E4003/17

Motor protection 545E4003/18

Capacitor protection 545E4003/20

Page 33: 01_3 EasyPact 15-250A En

545E4003_Ver5.0.fm/2 13 avril 2005 17:43

Installation guide Dimensions 0

EasyPact 100

Dimensions1P 2P 3P

DB

1060

57

DB

1060

59

DB

1060

60

DB

1060

58Mounting on plate1P 2P 3P

DB

1060

61

DB

1060

62

DB

1060

95

Mounting on DIN rail

DB

1060

96

DB

1060

97

E88

494

Page 34: 01_3 EasyPact 15-250A En

545E4003_Ver5.0.fm/313 avril 2005 17:43

Installation guide Dimensions 0

EasyPact 250

Dimensions2P, 3P

DB

1061

33

DB

1061

34

Mounting on plate2P, 3P

DB

1061

35

Page 35: 01_3 EasyPact 15-250A En

545E4003_Ver5.0.fm/4 13 avril 2005 17:43

Installation guide Dimensions 0

EasyPact 100

Door cut-out (small)1P, 3P 2P

DB

1060

98

DB

1060

99

DB

1061

19

Door cut-out (large)1P 2P

DB

1061

18

DB

1060

99

DB

1061

00

3P

DB

1061

01

Page 36: 01_3 EasyPact 15-250A En

545E4003_Ver5.0.fm/513 avril 2005 17:43

Installation guide Dimensions 0

EasyPact 250

Door cut-out (small)2P, 3P

DB

1061

36

DB

1061

37

Door cut-out (large)2P, 3P

DB

1061

38

DB

1061

39

Page 37: 01_3 EasyPact 15-250A En

545E4003_Ver5.0.fm/6 13 avril 2005 17:43

Installation guide Dimensions 0

EasyPact 100

Terminal shield

DB

1061

12

DB

1061

13

3P

Phase barrier

DB

1061

09

DB

1061

10

2P

DB

1061

11

3P

Direct rotary handleDimensions Door cut-out

DB

1061

14

DB

1061

15

DB

1061

16

Extended rotary handleDimensions Door cut-out

DB

1061

17

DB

1061

15

DB

1061

16

Page 38: 01_3 EasyPact 15-250A En

545E4003_Ver4.0.fm/728 février 2005 16:07

Installation guide Dimensions 0

EasyPact 250

Terminal shield Phase barrier

DB

1061

40

DB

1061

41

DB

1061

42

DB

1061

43

Direct rotary handle

DB

1061

44

DB

1061

45

DB

1061

46

Extended rotary handle

DB

1061

47

DB

1061

45

DB

1061

46

Page 39: 01_3 EasyPact 15-250A En

545E4003_Ver5.0.fm/8 13 avril 2005 17:43

Installation guide Dimensions 0

Busbar EZB250

Layout installation EZB250Panel layout using the EasyPact Busbar is simple using the guides below. In addition to the mounting locations for the busbar and main disconnect components (if required), make note of the minimum clearances required to the top, bottom and sides of the enclosure.

DB

1061

02

DB

1060

53

EZB250 - 250 A main busbar rating

DB

1061

20

Trim cut-outA B C D E F G H I

EZ250 incomer

187.4 52 92.7 24 109.5 126

NS/NB incomer

182.4 76 90.2 29 108 125

4 ways 268.5 225 1476 ways 343.5 300 222

8 ways 418.5 375 29710 ways 493.5 450 37212 ways 568.5 525 447

Page 40: 01_3 EasyPact 15-250A En

545E4003_Ver5.0.fm/913 avril 2005 17:43

Installation guide Dimensions 0

Busbars EZB400/630

Layout installation EZB400/630

Nota : to avoid excess temperature rise on incoming MCCB terminals, panels using 630 A main breaker with these minimum enclosure dimensions require a 7000 mm2 ventilation opening (after subtracting effects of screening) at each of the 4 corners of the enclosure.

DB

1061

03

DB

1060

52

EZB400 and EZB630 - 400 A and 630 A main busbar ratings

DB

1061

32

Trim cut-outA B C

4 ways 290 225 147

6 ways 365 300 2228 ways 440 375 29710 ways 515 450 372

12 ways 590 525 447

Page 41: 01_3 EasyPact 15-250A En

45E4003_Ver5.0.fm/10 13 avril 2005 17:43

Installation guide Dimensions 0

EasyPact or Compact NS/NB branch extensions layout

Layout installation for EasyPact or Compact NS/NB branch extensions

DB

1061

04

DB

1060

54

EZBNS2 and EZBNS4 Compact NS/NB branch breaker extension.

A B C D E F G HEZBNS2 270 175 NAEZBNS4 384 275 85.5

EZC250 90.5 57.5 24 61 52 249NS/NB250 85.5 78.5 29 45.5 76 232

DB

1065

69

Trim cut-out

Page 42: 01_3 EasyPact 15-250A En

545E4003_Ver5.0.fm/1113 avril 2005 17:43

Installation guide Safety clearances and minimum distances 0

EasyPactWhen installing a circuit breaker, minimum distances (safety clearances) must be maintained between the device and panels, bars and other protection devices installed nearby. These distances, which depend on the ultimate breaking capacity, are defined by tests carried out in accordance with standard IEC 60947-2.If installation conformity is not checked by type tests, it is also necessary to:b use insulated bars for circuit-breaker connectionsb block off the busbars using insulating screens.For EasyPact breaker, terminal shields, inter-phase barriers or an insulation isolator are recommended and may be mandatory depending on the utilisation voltage and the type of installation.

Minimal distance between two adjacent circuit breakers

E88

230

Minimal distance between the circuit breaker and top, bottom or side panels

Minimal distance between the circuit breaker and front or rear panels

DB

1060

55

DB

1065

70

Dimensions (mm) Bare or painted sheet metal;insulated bars

Bare busbar under voltage

EasyPact circuit breaker C1 D1 D2 D1 D2 EEZC100B/F/N 40 45 45 75 45 40EZC100H 40 60 45 75 45 40EZC250F/N 50 60 45 140 45 42.5

EZC250H 50 80 45 140 45 42.5The mandatory distances when installing EasyPact circuit breakers are calculated from the device case, not taking into account the terminal shields or the inter-phase barriers.

E44

458

Installation in an enclosureEasyPact circuit breakers can be installed in a metal enclosure together with other devices (contacts, motor-protection circuit breakers, LEDs, etc.).

Minimum enclosure dimensionsCircuit breakers Height (mm) Depth (mm) (*) Width (mm)

EZC100B/F/N 200 90 155EZC100H 215 90 155

EZC250F/N 270 90 205EZC250H 290 90 205

Installation in an enclosure (*) with front door

H

W D

Page 43: 01_3 EasyPact 15-250A En

45E4003_Ver5.0.fm/12 13 avril 2005 17:43

Installation guide Temperature derating 0

Ambient temperatureEasyPact devices are equipped with fixed thermal-magnetic trip units.b EasyPact has been particularly designed to hold 100% In at 50 °C without tripping in normal conditionb EasyPact circuit breakers may be used between - 25 °C and + 70 °Cb EasyPact circuit breakers should be put into service under normal ambient operating temperature conditions. Exceptionally, the circuit breaker may be put into service when the ambient temperature is between - 35 °C and - 25 °Cb the permissible storage-temperature range for EasyPact circuit breakers in the original packing is - 35 °C to + 85 °C.

To determine tripping times using time/current curves, use Ir values corresponding to the thermal setting on the device, corrected as indicated in the tables below. Breaker Amperage 25 °C 40 °C 45 °C 50 °C 55 °C 60 °C 65 °C 70 °CEZC10015 17.0 15.7 15.3 15.0 14.7 14.6 14.2 13.820 21.8 20.4 20.2 20.0 19.7 19.2 18.9 18.525 26.9 25.7 25.3 25.0 24.7 24.5 24.3 24.0

30 34.5 31.4 30.7 30.0 29.4 29.1 28.5 28.040 42.8 40.9 40.4 40.0 39.5 38.0 37.6 37.150 54.2 52.1 51.0 50.0 49.3 48.1 47.3 46.6

60 64.4 61.8 60.9 60.0 59.0 57.5 56.6 55.775 78.6 76.8 75.9 75.0 73.5 70.4 69.8 69.180 84.4 82.2 81.1 80.0 78.6 77.3 76.7 76.1

100 108.8 102.6 101.3 100.0 99.2 94.2 93.5 92.7

EZC250100 116.3 106.8 103.5 100.0 96.4 92.7 88.8 84.7125 148.4 134.9 130.0 125.0 119.8 114.3 108.5 102.5

150 174.0 160.0 155.1 150.0 144.7 139.3 133.6 127.6160 186.0 170.9 165.5 160.0 154.3 148.3 142.1 135.6175 206.7 188.3 181.8 175.0 167.9 160.6 152.9 144.7

200 235.8 215.0 207.6 200.0 192.0 183.8 175.1 165.9225 269.0 243.5 234.5 225.0 215.1 204.8 193.9 182.3250 298.9 270.6 260.5 250.0 239.0 227.5 215.4 202.6

Page 44: 01_3 EasyPact 15-250A En

545E4003_Ver4.0.fm/1328 février 2005 16:07

Installation guide Tripping curves 0

EasyPact 100 TM magnetic trip units15 A 20 A 25 A

DB

1061

21

DB

1061

22

DB

1061

23

30 A 40 A 50 A

DB

1061

24

DB

1061

25

DB

1061

26

60 A 75 A 80 A

DB

1061

27

DB

1061

28

DB

1061

29

Page 45: 01_3 EasyPact 15-250A En

45E4003_Ver5.0.fm/14 13 avril 2005 17:43

Installation guide Tripping curves 0

EasyPact 100 TM magnetic trip units (cont.)100 A

DB

1061

30

EasyPact 250 TM magnetic trip units100-125 A 150-160-175-200 A 225-250 A

DB

1061

48

DB

1061

49

DB

1061

50

Page 46: 01_3 EasyPact 15-250A En

545E4003_Ver5.0.fm/1513 avril 2005 17:43

Installation guide Current-limiting curves 0

The exceptional limiting capacity of the EasyPact range greatly reduces the forces created by fault currents in devices.The result is a major increase in breaking performance.

The Ics value, defined by IEC standard 60947-2, is guaranteed by tests comprising the following operations:b break three times consecutively a fault current equal from 25% to 100% of Icub check that the device continues to function normally:v it conducts the rated current without abnormal temperature risesv protection functions perform within the limits specified by the standardv suitability for isolation is not impaired.

Longer service life of electrical installationsCurrent-limiting circuit breakers greatly reduce the negative effects of short-circuits on installations.Thermal effectsLess temperature rise in conductors, therefore longer service life for cables.Mechanical effectsReduced electrodynamic forces, therefore less risk of electrical contacts or busbars being deformed or broken.Electromagnetic effectsLess disturbances for measuring devices located near electrical circuits.

Economy by means of cascadingCascading is a technique directly derived from current limiting. Circuit breakers with breaking capacities less than the prospective short-circuit current may be installed downstream of a limiting circuit breaker. The breaking capacity is reinforced by the limiting capacity of the upstream device.It follows that substantial savings can be made on downstream equipment and enclosures.

Current-limiting curvesThe current-limiting capacity of a circuit breaker is expressed by two curves which are a function of the prospective short-circuit current (the current which would flow if no protection devices were installed):b the actual peak current (limited current),b thermal stress (A2s), i.e. the energy dissipated by the short-circuit in a conductor with a resistance of 1 Ω.

The limiting capacity of a circuit breaker is its aptitude to limit short-circuit currents.

DB

1060

49

Current limiting curves 380/415 V AC Thermal-stress curves 380/415 V AC

DB

1061

51

DB

1061

52

Page 47: 01_3 EasyPact 15-250A En

45E4003_Ver5.0.fm/16 13 avril 2005 17:43

Installation guide Cascading 0

What is cascading?Cascading is the use of the current limiting capacity of circuit breakers at a given point to permit installation of lower-rated and therefore lower-cost circuit breakers downstream.The upstream compact circuit breakers acts as a barrier against short-circuit currents. In this way, downstream circuit breakers with lower breaking capacities than the prospective short-circuit (at their point of installation) operate under their normal breaking conditions.Since the current is limited throughout the circuit controlled by the limiting circuit breaker, cascading applies to all switchgear downstream. It is not restricted to two consecutive devices.

General use of cascadingWith cascading, the devices can be installed in different switchboards. Thus, in general, cascading refers to any combination of circuit breakers where a circuit breaker with a breaking capacity less than the prospective Isc at its point of installation can be used. Of course, the breaking capacity of the upstream circuit breaker must be greater than or equal to the prospective short-circuit current at its point of installation.The combination of two circuit breakers in cascading configuration is covered by the following standards:b IEC 60947-2 (construction)b NF C 15-100, § 434.3.1 (installation).

Coordination between circuit breakersThe use of a protective device possessing a breaking capacity less than the prospective short-circuit current at its installation point is permitted as long as another device is installed upstream with at least the necessary breaking capacity.In this case, the characteristics of the two devices must be coordinated in such a way that the energy let through by the upstream device is not more than that which can be withstood by the downstream device and the cables protected by these devices without damage.Cascading can only be checked by laboratory tests and the possible combinations can be specified only by the circuit breaker manufacturer.

220/240 V network downstream from a 380/415 V networkFor 1P + N or 2P circuit breakers connected between the phase and neutral on a 380/415 V network, with a TT or TNS neutral system, consult the 220/240 V cascading table to determine cascading possibilities between upstream and downstream circuit breakers.

Economy by means of cascadingThanks to cascading, circuit breakers with breaking capacities less than the prospective short-circuit current may be installed downstream from a current limiting circuit breaker.It follows that substantial savings can be made on downstream switchgear and enclosures.

Cascading tablesMerlin Gerin cascading tables are:b drawn up on the basis of calculations (comparison between the energy limited by the upstream device and the maximum permissible thermal stress for the downstream device)b verified experimentally in accordance with IEC standard 60947-2.For distribution systems with 220/240 V, 380/415 V and 440 V between phases, the tables of the following pages indicate cascading possibilities between upstream Compact/EasyPact and downstream Multi 9 and EasyPact circuit breakers.

DB

1060

51

Page 48: 01_3 EasyPact 15-250A En

545E4003_Ver5.0.fm/1713 avril 2005 17:43

Installation guide Cascading tables 0

DB

1061

06

Network 220/240 VUpstream EZC100F EZC100N EZC100HBreaking capacity kA rms 25 25 100Downstream Enhanced breaking capacityNC45 6 10 10 15NC45N 10 15 15 25NC45H 15 25 25 50C60a 10 25 25 50C60N 20 25 25 65C60H 30 65QO-E 10 25 25 50

Upstream EZC250F EZC250N EZC250H NS250HBreaking capacity kA rms 25 50 85 100Downstream Enhanced breaking capacityEZC100B 10 15 20EZC100F 25 30 30 50EZC100N 25 30 36 50EZC100H 100

Upstream NB400/630 NS400/630N NS400/630HBreaking capacity kA rms 85 85 100Downstream Enhanced breaking capacityEZC100B 10 20 20 20EZC100F 25 50 50 50EZC100N 25 50 50 50EZC100H 100EZC250F 25 50 50 50EZC250N 50EZC250H 85

Network 380/415 VUpstream EZC100F EZC100N EZC100HBreaking capacity kA rms 10 15 30

DB

1061

60

Downstream Enhanced breaking capacityNC45 5 6 8 15NC45N 8 10 10 15NC45H 10 15 15C60a 6 10 15 15C60N 10 15 15C60H 15 15QO-E 5 10 15 15GV2M 15

Upstream EZC250F EZC250N EZC250H NS250HBreaking capacity kA rms 18 25 36 70Downstream Enhanced breaking capacityEZC100B 7.5 15EZC100F 10 15 15 30EZC100N 15 20 20 50EZC100H 30 36 70

Upstream NB400/630 NS400/630N NS400/630HBreaking capacity kA rms 30 50 70Downstream Enhanced breaking capacityEZC100B 7.5EZC100F 10EZC100N 15 20 20 30EZC100H 30 45 50EZC250F 18 20 20 20EZC250N 25 30 36 40EZC250H 36 45 50

Network 440 VUpstream EZC250F EZC250N EZC250HBreaking capacity kA rms 15 20 25Downstream Enhanced breaking capacityEZC100B 5EZC100F 7.5EZC100N 10 15 15EZC100H 20

Upstream NB400/630 NS400/630N NS400/630HBreaking capacity kA rms 30 42 65Downstream Enhanced breaking capacityEZC100B 5EZC100F 7.5EZC100N 10 15 15 25EZC100H 20 30 30 30EZC250F 15EZC250N 20 25 25 30EZC250H 25 30 30 30

Page 49: 01_3 EasyPact 15-250A En

45E4003_Ver5.0.fm/18 13 avril 2005 17:43

Installation guide Motor protection 0

A circuit supplying a motor may include one, two, three or four switchgear or controlgear devices fulfilling one or more functions.When a number of devices are used, they must be coordinated to ensure optimum operation of the motor.Protection of a motor circuit involves a number of parameters that depend on:b the application (type of machine driven, operating safety, starting frequency, etc.)b the level of service continuity imposed by the load or the applicationb the applicable standards to ensure protection of life and property.The necessary electrical functions are of very different natures:b short circuit protectionb overload protection dedicated for motorb control (generally with high endurance levels)b isolation.

Protection functionsDisconnection functions:Isolate a motor circuit prior to maintenance operations.

Short-circuit protection:Protect the starter and the cables against major overcurrents (> 10 In).

Control:Start and stop the motor and, if applicable:b gradual accelerationb speed control.

Overload protection:Protect the starter and the cables against minor overcurrents (< 10 In).

Additional specific protection:b limitative fault protection (while the motor is running)b preventive fault protection (monitoring of motor insulation with motor off).

Overloads (I < 10 In)An overload may be caused by:b an electrical problem, for instance on the mains (loss of a phase, voltage outside tolerances, etc.)b a mechanical problem, for instance excessive torque due to abnormally high demands by the process or motor damage (bearing vibrations, etc.).A further consequence of these two origins is excessively long starting.

Impedance short-circuit (10 < I < 50 In)Deterioration of motor-winding insulation is the primary cause.

Short-circuit (I > 50 In)This type of fault is relatively rare. A possible cause may be a connection error during maintenance.

Overload protectionThermal relays provide protection against this type of fault. They may be:b integrated in the short-circuit protective deviceb separate.

Short-circuit protectionThis type of protection is provided by a circuit breaker.

Protection against insulation faultsThis type of protection may be provided by:b a residual current device (RCD)b an insulation monitoring device (IMD).

DB

1061

08

DB

1061

07

DB

1060

50

Page 50: 01_3 EasyPact 15-250A En

545E4003_Ver5.0.fm/1913 avril 2005 17:43

Installation guide Motor protection 0

Motor protection - circuit breaker selectionP (kW) 220/230 V

I (A)240 V I (A)

Circuit breaker rating (In)

380/400 VI (A)

415 V I (A)

Circuit breaker rating (In)

440 V I (A)

Circuit breaker rating (In)

0.37 2 1.8 20 1.2 1.1 20 1 200.55 2.8 2.6 20 1.6 1.5 20 1.4 20

0.75 3.5 3.2 20 2 1.8 20 1.7 201.1 5 4.5 20 2.8 2.6 20 2.4 201.5 6.5 6 20 3.7 3.4 20 3.1 20

2.2 9 8 20 5.3 4.8 20 4.5 203 12 11 20 7 6.5 20 5.8 204 15 14 20 9 8.2 20 8 20

5.5 21 19 30 12 11 20 10.5 207.5 28 25 40 16 14 20 13.7 209 - - - 19 17 25 16.9 25

10 36 33 50 21 19 30 19 3011 39 36 50 23 21 30 20 3015 52 48 75/80 30 28 40 26.5 40

18.5 63 59 75/80 37 34 50 33 5022 75 70 100 - 40 50 39 5022 - - - 43 - 60 - -

25 - - - - 47 60 - -30 100 95 125 59 55 75/80 51 75/8037 125 115 150 - 66 80 64 75/80

37 - - - 72 - 100 - -45 150 140 170 85 80 100 76 10055 180 170 225 105 100 125 90 125

75 250 235 - 138 135 150 125 15090 300 270 170 165 175 146 175

110 360 330 - 205 200 225 178 225

Page 51: 01_3 EasyPact 15-250A En

545E4003_Ver5.0.fm/20 13 avril 2005 17:43

Installation guide Capacitor protection 0

EasyPact circuit breaker is suitable for capacitor protection following the rules below:

bbbb Inc = Nominal current from the capacitor

b Inb = Nominal current for the circuit breaker protection (EZC)v Inb = 1.36 x Inc for standard equipmentv Inb = 1.5 x Inc for overrated type equipmentv Inb = 1.19 x Inc for detuned type equipment: 3.8 tuningv Inb = 1.31 x Inc for detuned type equipment: 4.3 tuningv Inb = 1.12 x Inc for detuned type equipment: 2.7 tuningv the short-circuit (magnetic) protection-setting thresholds must enable passage of the energising transients: 10 x Inc for standard, overrated and detuned type equipment.b short-circuit level is given by the installation.

Example:Table at 400 V AC - 3 phases 50 Hz for standard equipment.

Thanks to its small size and short-circuit capacity, EasyPact circuit breaker is the most compact solution for any capacitor protection (eg: for each step of capacitor bank from 7.5 kVAR to 50 kVAR).

EZ

101P

R-2

5

EZC100 EZC250

EZ

151D

EZ

152P

-50

Inc = Nominal Current Capacitor (A)Qc = Reactive power (kVAR)U = Nominal Voltage (V)

Reactive power Inc Inb Breaking capacity to Circuit Breaker(kVAR) (A) (A) 15 kA 30 kA7.5 11 15 EZC100N3015 EZC100H301510 14 20 EZC100N3020 EZC100H302015 22 30 EZC100N3030 EZC100H303020 29 40 EZC100N3040 EZC100H304030 43 60 EZC100N3060 EZC100H306040 58 80 EZC100N3080 EZC100H308050 72 100 EZC100N3100 EZC100H310060 87 118 EZC250F3125 EZC250H312575 108 147 EZC250F3150 EZC250H3150100 144 196 EZC250F3200 EZC250H3200

IncQc

U 3------------=

Page 52: 01_3 EasyPact 15-250A En

545E5100_Ver1.2.fm/2

Catalogue numbers EZC100N/H 1P/2P 0

Circuit breaker

EasyPact EZC100N 1P 18 kA 220/240 VWith thermal magnetic trip unit

DB

1008

18

Rating 1P 1d

15 A EZC100N101520 A EZC100N102025 A EZC100N102530 A EZC100N103040 A EZC100N104050 A EZC100N105060 A EZC100N106075 A EZC100N107580 A EZC100N1080100 A EZC100N1100

EasyPact EZC100H 1P 25 kA - 2P 50 kA 220/240 VWith thermal magnetic trip unit

DB

1008

18

1P

2P

Rating 1P 1d 2P 2d15 A EZC100H1015 EZC100H201520 A EZC100H1020 EZC100H202025 A EZC100H1025 EZC100H202530 A EZC100H1030 EZC100H203040 A EZC100H1040 EZC100H204050 A EZC100H1050 EZC100H205060 A EZC100H1060 EZC100H206075 A EZC100H1075 EZC100H207580 A EZC100H1080 EZC100H2080100 A EZC100H1100 EZC100H2100

DB

1008

19

Page 53: 01_3 EasyPact 15-250A En

545E5100_Ver1.2.fm/3

Catalogue numbers EZC100N/H/B/F 3P 0

Circuit breaker

EasyPact EZC100B 3P 7.5 kA 400/415 VWith thermal magnetic trip unit

DB

1008

20

Rating 3P 3d

15 A EZC100B301520 A EZC100B302025 A EZC100B302530 A EZC100B303040 A EZC100B304050 A EZC100B305060 A EZC100B3060

EasyPact EZC100F 3P 10 kA 400/415 VWith thermal magnetic trip unit

DB

1008

20

Rating 3P 3d15 A EZC100F301520 A EZC100F302025 A EZC100F302530 A EZC100F303040 A EZC100F304050 A EZC100F305060 A EZC100F306075 A EZC100F307580 A EZC100F3080100 A EZC100F3100

EasyPact EZC100N 3P 15 kA 400/415 VWith thermal magnetic trip unit

DB

1008

20

Rating 3P 3d15 A EZC100N301520 A EZC100N302025 A EZC100N302530 A EZC100N303040 A EZC100N304050 A EZC100N305060 A EZC100N306075 A EZC100N307580 A EZC100N3080100 A EZC100N3100

EasyPact EZC100H 3P 30 kA 400/415 VWith thermal magnetic trip unit

DB

1008

20

Rating 3P 3d

15 A EZC100H301520 A EZC100H302025 A EZC100H302530 A EZC100H303040 A EZC100H304050 A EZC100H305060 A EZC100H306075 A EZC100H307580 A EZC100H3080100 A EZC100H3100

Page 54: 01_3 EasyPact 15-250A En

545E5100_Ver1.2.fm/4

Catalogue numbers EZC100N/H/B/F 0

Accessories

Connection accessories Cable lugs

DB

1008

21

y 50 A Cables from 2.5 to 16 mm2 Set of 2 EZALUG0502Set of 3 EZALUG0503

DB

1008

22

> 50 A Cables from 10 to 50 mm2 Set of 2 EZALUG1002Set of 3 EZALUG1003

Spreader

DB

1008

23

EZASPDR3P (*)

Terminal shield

DB

1008

24

Terminal shield for 3-pole breaker Set of 2 EZATSHD3P

Sealing screws

DB

1008

25

Set of 2 EZASSCR

Phase barriers

DB

1008

26

Set of 2 EZAFASB2

Electrical auxiliariesIndication contacts

DB

1008

27

Auxiliary switch (AX) EZAUX10

DB

1008

28

Alarm switch (AL) EZAUX01

DB

1008

29

Aux. switch/Alarm switch (AX/AL) EZAUX11

(*) Consult us.

Page 55: 01_3 EasyPact 15-250A En

545E5100_Ver1.2.fm/5

Catalogue numbers EZC100N/H/B/F 0

Accessories

Electrical auxiliaries (cont.)

Voltage releases

DB

1008

30

Shunt trip (SHT)

Under voltage release (UVR)

AC Voltage MX/SHT MN/UVR

100-130 V EZASHT100AC110-130 V EZAUVR110AC200-240 V EZAUVR200AC200-277 V EZASHT200AC277 V EZAUVR277AC380-415 V EZAUVR380AC380-480 V EZASHT380AC440-480 V EZAUVR440AC

DB

1008

31

DC Voltage MX/SHT MN/UVR

24 V EZASHT024DC EZAUVR024DC48 V EZASHT048DC EZAUVR048DC125 V EZAUVR125DC

Rotary handlesDirect rotary handle

DB

1008

32

Standard handle EZAROTDS

Extended rotary handle

DB

1008

33

Extended handle EZAROTE

LocksPadlocking system

DB

1008

34

EZALOCK

Installation accessoryDin rail adaptor

DB

1008

35

For 2 x 1 pole or 1 x 2 pole or 1 x 3 pole breaker EZADINR

Page 56: 01_3 EasyPact 15-250A En

545E5100_Ver1.2.fm/6

Catalogue numbers EasyPact Busbar 0

"Type-tested solution IEC 60439"

Main Busbar# Branch Ways (3-pole EasyPact MCCB’s) 250 A 400 A 630 A

DB

1008

36

4 ways (3-pole)

8 ways (3-pole)

4 ways EZB250W04 EZB400W04 EZB630W046 ways EZB250W06 EZB400W06 EZB630W068 ways EZB250W08 EZB400W08 EZB630W0810 ways EZB250W10 EZB400W10 EZB630W1012 ways EZB250W12 EZB400W12 EZB630W12

DB

1008

37

Compact NS/NB branch extension

DB

1008

38

4 ways (3-pole)

2 ways EZBNS24 ways EZBNS4

Main incoming connectionsMain connectors 250 A 400 A 630 A

DB

1008

39

To connect the main incomer to EasyPact busbar (Compact NS/NB or INS switch)

EZB250MCNS EZB400MCNS EZB630MCNS

Mechanical lugs 250 A 400 A 630 A

DB

1008

40

Incoming cable size 16-150 mm2 35-300 mm2 25-240 mm2

2 cables per phaseLug kit for bare incoming cables EZB250MLUG EZB400MLUG EZB630MLUG

Connector caps

DB

1008

41

EasyPact branch MCCB Set of 3 EZB100CAPCompact NS/NB branch MCCB Set of 3 EZB250CAPTo isolate connections when branch breaker not installed

Page 57: 01_3 EasyPact 15-250A En

AR

T00

000

© 2

004

- S

chne

ider

Ele

ctric

- A

ll rig

hts

rese

rved

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.

Publication: Schneider Electric SASPrinting:

Schneider Electric Industries SAS

545E-ABTED0000000EN 10-2004