07 b- emcp ii quick reference

18

Click here to load reader

Upload: suhailtambal

Post on 12-Dec-2015

122 views

Category:

Documents


50 download

DESCRIPTION

07 B- EMCP II Quick Reference

TRANSCRIPT

Page 1: 07 B- EMCP II Quick Reference

SDLCSDLC PSDPSD--FTPFTP

Power System Power System –– Fast Fast Training ProgramTraining Program

Inst. Ahmed Inst. Ahmed M. A/HafeezM. A/Hafeez

Page 2: 07 B- EMCP II Quick Reference

PHASEPHASESELECTSELECT

ENGINEENGINEMETERMETER

LAMPLAMPTESTTEST

ALARMALARMCODECODE EXITEXIT

SERVICESERVICEMODEMODE

SCROLLSCROLLRIGHTRIGHT

SCROLLSCROLLUPUP

SCROLLSCROLLDOWNDOWN

SELECTSELECT ENTERENTER

OP1

OP2-0

OP3

FAULT LOG VIEWING

Engine/Generator Setpoint Viewing

PASSWORD ENTRY

13231

OP4

OP5-0

OP6

OP7

OP8

OP9

OP10

Fault log clearing

Engine Generator programming

Spare Input/Output programming

Hour meter programming

Voltmeter/Ammeter programming

Engine setpoint verification

AC offset adjustment - calibration

OP5-1

OP5-2

OP5-3

Protective relaying programming

Factory use only

Synchronization setpoint programming

OP11 Synchronization setpoint tuning

OP2-1

OP2-2

OP2-3

Protective Relaying Setpoint Viewing

AC Factory Calibration Setpoint Viewing

Synchronization Setpoints

Page 3: 07 B- EMCP II Quick Reference

OP1, Fault log viewing OP2-0, Engine/Generator setpoint viewing OP2-1, Protective relaying setpoint viewing OP2-2, AC factory calibration setpoint viewing

OP2-3, Synchronization setpoints (1)

OP3, Password entry OP4, Fault log clearing OP5-0, Engine/Generator programming OP5-1, Protective relaying programming OP5-2, For factory use, not accessible by the user.

OP5-3, Synchronization setpoint programming (1) OP6, Spare Input/Output programming OP7, Hourmeter programming OP8, Voltmeter/Ammeter programming OP9, Engine setpoint verification OP10, AC offset adjustment

OP11, Synchronization setpoint tuning (1)

13231

Page 4: 07 B- EMCP II Quick Reference

Setpoint

Name Description Range Of Value Factory Default

0 - ETR fuel solenoid1 - ETS fuel solenoid

0 - English units (psi, degrees F)1 - Metric units (kPa, degrees C) 0 - engine shutdown1 - alarm only (shutdown override, no engine shutdown) 0 - alarm only (shutdown override, no engine shutdown)1 - for engine shutdown

0 - generator sets without sensor1 - generator sets with sensor 0 - engine shutdown1 - alarm only (shutdown override, no engine shutdown.)

P007 System Voltage 24 Or 32 Volts

System voltage (battery voltage) of the generator set. (Determined by application or customer.)

24 or 32 24

P008 N/A This setpoint is not currently being used by the GSC+ and cannot be programmed.

N/A N/A

95 to 350 teethin increments of 1 500 to 4330 rpmin increments of 10 100 to 1000 rpmin increments of 10 400 to 1800 rpmin increments of 10

34 to 420 kPa (5 to 61 psi)in increments of 1

20 to 336 kPa (3 to 49 psi)in increments of 1

85 to 123°C (185 to 253°F)in increments of 1

OP5-0 Setpoints - Engine/Generator Programming (1)

P001 Fuel Solenoid Type

Type of fuel system solenoid used on the generator set. All Larne-built generators covered by this maual are ALWAYS programmed as ETR (0), even if the generator has an ETS fuel solenoid.

0

P002 Units Shown Type of measurement units shown on the GSC+ display.

0

P003 Shutdown Override For Engine Fault

GSC+ responds to a low engine oil pressure or high coolant temperature fault. (Determined by application or customer.)

0

P004 Shutdown Enable For Sensor Fault

GSC+ responds to a diagnostic fault with the engine oil pressure sensor, coolant temperature sensor, oil temperature sensor, sensor power supply or coolant loss sensor. (Determined by application or customer.)

0

P005 Coolant Loss Sensor Installed

Tells whether or not the optional engine coolant loss sensor is installed on the generator set.

0

P006 Shutdown Override For Coolant Loss Fault

GSC+ responds to an engine coolant loss fault. (Determined by application or customer.)

0

P009 Number Of Ring Gear Teeth

Number of teeth on the ring gear engine. Used by the GSC+ to determine engine speed.

136 teeth for MUI and PEEC

P010 Engine Overspeed

Engine speed used by the GSC+ to declare that an engine overspeed fault exists. The engine overspeed

2120 rpm

P011 Crank Terminate Speed

Engine speed used by the GSC+ to disengage the starting motor during engine cranking.

400 rpm

P012 (2) Oil Step Speed Engine speed used by the GSC+ for distinguishing between rated speed and idle speed when a low oil

1350 rpm

P013 (3) Low Oil Pressure Shutdown At Rated Speed

Oil pressure used by the GSC+ to declare that a low oil pressure shutdown fault exists with engine at rated speed (the engine must have exceeded the oil step speed for at least nine seconds).

205 kPa (30 psi)

P014 (3) Low Oil Pressure Shutdown At Idle Speed

Oil pressure used by the GSC+ to declare that a low oil pressure shutdown fault exist with the engine at idle speed (the engine must have been running for at least nine seconds and the engine speed must be less than oil step speed).

70 kPa (10 psi)

P015 (4) High Water Temperature Shutdown

Coolant temperature used by the GSC+ to declare a high coolant temperature shutdown fault exists (after a 10 second delay).

107°C (225°F)

Page 5: 07 B- EMCP II Quick Reference

0 to 36°C (32 to 97°F)in increments of 1

Cycle crank time used by the GSC+ to declare that an overcrank fault exists.

5 to 360 seconds

(Determined by application or customer.) in increments of 1 5 to 300 secondsin increments of 1 0 to 30 minutesin increments of 1

P020 (5) AC Voltage Full scale AC voltage of the generator. The GSC+ measures the AC voltage and shows it on the display. (Determined by application or customer.)

700, 150, 300, 500, 600, 750, 3.0k, 4.5k, 5.25k, 9.0k, 15.0k, 18.0k, 30.0k

700

P021 AC Current Full Scale

AC current full scale is the ratio of the current transformers (CT) based on a 5A secondary. It does not represent the maximum AC current of the generator. The GSC+ measures the current and shows it on the display.

75, 100, 150, 200, 300, 400, 600, 800, 1000, 1200, 1500, 2000, 2500, 3000, 4000A

600A

P022 (6) GSC+ Engine Number

Informs other devices on the CAT Data Link (for example, CCM) of the engine number for the GSC+ (Determined by application or customer).

01 through 08 01

0 to 20 secondsin increments of 1 0 - generator sets without an oil temperature sensor1 - generator sets with an oil temperature sensor

85 to 123°C (185 to 253°F)in increments of 1 0 - alarm only (shutdown override, no engine shutdown)1 - engine shutdown 100V to 25kVin increments of 1 0 to 4000Ain increments of 1 0 through 10MWin increments of 1kW

P031 Rated Frequency

Nominal frequency rating of generator set. 50, 60 or 400Hz 60Hz

0 - wye1 - delta 0 through 254in increments of 2

P016 Low Water Temperature Alarm

Coolant temperature used by the GSC+ to declare that a low temperature alarm fault exists (after a 2 second delay). (Determined by application or customer.)

21°C (70°F)

P017 Total Cycle Crank Time

90 seconds

P018 Cycle Crank Time

Amount of time the GSC+ cranks and then rests the starting motor during a single crank cycle.

10 seconds

P019 Cooldown Time Amount of time the GSC+ allows the engine to run after a normal shutdown is initiated. (Determined by application or customer.)

5 minutes

P023 Engine Type Identifies the engine as a mechanical unit injector (MUI) diesel, spark ignited (gas), or electronic unit injector (EUI) diesel engine.

0 - MUI diesel1 - Gas2 - EUI diesel

P024 (7) Crank Time Delay Amount of time the GSC+ delays activation of the fuel control relay (FCR) during a crank cycle. This

5 seconds

P025 Oil Temperature Sensor Installed

Tells whether or not the optional engine oil temperature sensor is installed on the generator set.

0

P026 High Oil Temperature Shutdown

Oil temperature used by the GSC+ to declare a high oil temperature shutdown fault exists (after a 10 second delay).

107°C (225°F)

P027 Shutdown Override For High Oil Temperature Fault

GSC+ responds to an engine high oil temperature fault. (Determined by application or customer.)

0

P028 Nameplate Voltage

Rated voltage of the generator. This setpoint is used for protective relaying functions.

480V

P029 Nameplate Current

Rated current output of the generator. 600A

P030 Nameplate Power

Rated power capability of the generator. 400kW

P032 Connection Configuration Of

Wye or delta configuration of generator. 0

P033 (8) Number Of Generator Poles.

Number of generator poles. 4

Page 6: 07 B- EMCP II Quick Reference

Setpoint Name Description Range Of Value Factory Default

0 - disabled

1 - enabled

P102 Overvoltage Alarm Threshold

Voltage the GSC+ uses to issue an overvoltage alarm.

100 to 125% of nameplate voltage in increments of 1%

105%

P103 Overvoltage Alarm Time Delay

Amount of time the GSC+ waits before issuing an overvoltage alarm.

0 to 120 seconds (2) in increments of 1

10 seconds

0 - disabled

1 - enabled

P105 Overvoltage Shutdown Threshold

Voltage the GSC+ uses to issue an overvoltage shutdown.

100 to 125% of nameplate voltage in increments of 1%

110%

P106 Overvoltage Shutdown Time Delay

Amount of time the GSC+ waits before inssuing an overvoltage shutdown.

0 to 120 seconds (2) in increments of 1

10 seconds

0 - disabled

1 - enabled

P108 Undervoltage Alarm Threshold

Voltage the GSC+ uses to issue an undervoltage alarm.

60 to 100% of nameplate voltage in increments of 1%

90%

P109 Undervoltage Alarm Time Delay

Amount of time the GSC+ waits before inssuing an undervoltage alarm.

0 to 120 seconds (2) in increments of 1

10 seconds

0 - disabled

1 - enabled

P111 Undervoltage Shutdown Threshold

Voltage the GSC+ uses to issue an undervoltage shutdown.

60 to 100% of nameplate voltage in increments of 1%

85%

P112 Undervoltage Shutdown Time Delay

Amount of time the GSC+ waits before issuing an undervoltage shutdown.

0 to 120 seconds (2) in increments of 1

15 seconds

0 - disabled

1 - enabled

50 to 60, for 50 Hz Gen 53 Hz

60 to 70, for 60 Hz Gen 63 Hz

400 to 480, for 400 Hz Gen

422 Hz

P115 Overfrequency Alarm Time Delay

Amount of time the GSC+ waits before issuing an overfrequency alarm.

0 to 120 seconds (2) in increments of 1

10 seconds

0 - disabled

1 - enabled

50 to 60, for 50 Hz Gen 55Hz

PEEC and EUI Engines: 60 to 70, for 60Hz Gen 66 Hz MUI Engines: 60 to 70, for 60 Hz Gen 63 Hz

PEEC and EUI Engines: 400 to 480, for 400 Hz Gen 440 Hz MUI Engines: 400 to 480, for 400 Hz Gen 422 Hz

P118 Overfrequency Shutdown Time Delay

Amount of time the GSC+ waits before issuing an overfrequency shutdown.

0 to 120 seconds (2) in increments of 1

10 seconds

0 - disabled

1 - enabled

MUI Engines: 30 to 50, for 50 Hz Gen

45 Hz

PEEC and EUI Engines: 30 to 50, for 50 Hz Gen 47 Hz MUI Engines: 36 to 60, for 60 Hz Gen 54 Hz PEEC and EUI Engines: 36 to 60, for 60 Hz Gen 57 Hz MUI Engines: 240 to 400, for 400 Hz Gen 360 Hz

PEEC and EUI Engines: 240 to 400, for 400 Hz Gen 378 Hz

P120 Underfrequency Alarm Threshold

Frequency the GSC+ uses to issue an underfrequency alarm.

P119 Underfrequency Alarm Enable

The GSC+ enables or disables the generator underfrequency alarm function.

1

1

P117 Overfrequency Shutdown Threshold

Frequency the GSC+ uses to issue an overfrequency shutdown.

P114 Overfrequency Alarm Threshold

Frequency that the GSC+ uses to issue an overfrequency alarm.

P116 Overfrequency Shutdown Enable

The GSC+ enables or disables the generator overfrequency shutdown function.

P113 Overfrequency Alarm Enable

The GSC+ enables or disables the generator overfrequency alarm function.

1

P110 Undervoltage Shutdown Enable

The GSC+ enables or disables the generator undervoltageshutdown function.

1

P107 Undervoltage Alarm Enable

The GSC+ enables or disables the generator undervoltage alarm function.

1

P104 Overvoltage Shutdown Enabled

The GSC+ enables or disables the generator overvoltage shutdown function.

1

OP5-1 Setpoints (1) - Protective Relaying Programming

P101 Overvoltage Alarm Enable

The GSC+ enables or disables the generator overvoltage alarm function.

1

Page 7: 07 B- EMCP II Quick Reference

P121 Underfrequency Alarm Time Delay

Amount of time the GSC+ waits beforeissuing an underfrequency alarm.

0 to 120 seconds (2) in increments of 1

10 seconds

0 - disabled

1 - enabled

30 to 50, for 50 Hz Gen 45 Hz36 to 60, for 60 Hz Gen 54 Hz240 to 400, for 400 Hz Gen

360 Hz

P124 Underfrequency Shutdown Time Delay

Amount of time the GSC+ waits before issuing an underfrequency shutdown.

0 to 120 seconds (2) in increments of 1

15 seconds

0 - disabled1 - enabled

P126 Reverse Power Shutdown Threshold

Level of reverse power the GSC+ uses to issue a reverse power shutdown.

0 to 20% of nameplate power in increments of 1%

15%

P127 Reverse Power Shutdown Time Delay

Amount of time the GSC+waits before issuing a reverse power shutdown.

0 to 30 seconds (2) in increments of 1

10 seconds

0 - disabled1 - enabled

P129 Phase Overcurrent Alarm Threshold

Level of current the GSC+ uses to issue a phase overcurrent alarm.

100 to 160% of nameplate current in increments of 5%

105%

P130 Phase Overcurrent Alarm Time Delay

Amount of time the GSC+ waits before issuing a phase overcurrent alarm.

0 to 250 seconds (2) in increments of 1

20 seconds

P131 Total Overcurrent Alarm Threshold

Level of current the GSC+ uses to issue a total overcurrent alarm.

100 to 160% of three times nameplate current in increments of 5%

105%

P132 Total Overcurrent Alarm Time Delay

Amount of time the GSC+ waits before issuing a total overcurrent alarm.

0 to 250 seconds (2) in increments of 1

20 seconds

0 - disabled1 - enabled

P134 Phase Overcurrent Shutdown Threshold

Level of current the GSC+ uses to issue a phase overcurrent shutdown.

100 to 160% of nameplate current in increments of 5%

110%

P135 Phase Overcurrent Shutdown Time Delay

Amount of time the GSC+ waits before issuing a phase overcurrent shutdown.

0 to 250 seconds (2) in increments of 1

30 seconds

P136 Total Overcurrent Shutdown Threshold

Level of current the GSC+ uses to issue a total overcurrent shutdown.

100 to 160% of three times nameplate current in increments of 5%

110%

P137 Total Overcurrent Shutdown Time Delay

Amount of time the GSC+ waits before issuing a total overcurrent shutdown.

0 to 250 seconds (2) in increments of one.

30 seconds

0 - disabled1 - enabled

P139 KW Level Relay Threshold

Level of power the GSC+ uses to activate the kW level relay function.

0 to 110% of nameplate power in increments of 1%

105%

P140 KW Level Relay Time Delay

Amount of time the GSC+ waits before activating the kW relay function.

0 to 120 seconds (2) in increments of 1

0 seconds

P141 KW Level Relay Disengage Threshold

Level of power the GSC+ uses deactivate the kW level relay function.

0 to 110% of nameplate power in increments of 1%

100%

P142 KW Level Relay Disengage Time Delay

Amount of time the GSC+ waits before deactivating the kW level relay function.

0 to 120 seconds (2) in increments of 1

10 seconds

P122 Underfrequency Shutdown Enable

The GSC+ enables or disables the generator underfrequency shutdown function.

1

P123 Underfrequency Shutdown Threshold

Frequency the GSC+ uses to issue an underfrequency shutdown.

P125 Reverse Power Shutdown Enable

The GSC+ enables or disables the generatorreverse power shutdown function.

1

P128 Overcurrent Alarm Enable

The GSC+ enables or disables the overcurrent alarm.

1

P133 Overcurrent Shutdown Ecable

The GSC+ enables or disables the overcurrent shutdown.

1

P138 KW Level Relay Enable

The GSC+ enables or disables the kW level relay function.

1

Page 8: 07 B- EMCP II Quick Reference

Setpoint Name Description Range Of Value

Factory Default

0 - disabled

1 - Woodward

P302 Breaker Coil Time Limit

The maximum amount of time the breaker coil can be energized without damaging the coil.

0.2 to 5.0 seconds in increments of 0.1 second

1.0 second

0 - disabled

1 - enabled

P304 Voltage Limit The maximum acceptable difference between the bus voltage and the oncoming voltage, expressed as a percentage of bus voltage.

1% to 15 % in increments of 1%

1%

P305 (1) Phase Tolerance Limit

The maximum phase angle magnitude allowed for breaker closure

1 to 25 degrees in increments of 1 degree

5 degrees

P306 (1) Dwell Time The time during which the phase angle between the generator and the bus during synchronization.

0.1 to 1.0 seconds in increments of 0.1 second

0.5 second

P307 (1) (2) Speed Control Gain

Controls how fast the engine speed will change during synchronization.

0.0% to 100.0% in increments of 0.1%

50.0%

P308 (1) (2) Speed Control Rate

Controls the rate of change of the phase angle differencebetween the generator and the bus during synchronization.

0.0% to 100.0% in increments of 0.1%

50.0%

P309 (1) (2) Speed Control Damping

Controls the amount of overshoot and settling time of engine speed during synchronization.

0.0% to 100.0% in increments of 0.1%

0.0%

1 - enabled (3)

0 - disabled

P311 Dead Bus Limit

The maximum acceptable voltage for the bus to be considered dead, as a percent of rated voltage.

5% to 50% in increments of 1%

20%

P312 Dead Bus On Time Delay

The amount of time the GSC+P waits before closing to a dead bus.

0 to 120 seconds in increments of 1 second

0 seconds

P313 Frequency Match Notification Time

The amount of time before notification of possible synchronization failure. Must not be greater than the Maximum Synchronization Time.

5 to 1000 seconds in increments of 1 seconds

20 seconds

P314 Maximum Synchronization Time

The maximum amount of time to spend attempting to synchronize before setting the Synchronization Time-out Alarm

5 to 1000 seconds in increments of 1 second

30 seconds

OP5-3 Setpoints - Paralleling Programming

P301 Synchronization Enable

Enables or disables the synchronization function, and specifies the type of Load Share control being driven.

0

P303 Voltage Limit Enable

Enables or disables the generator/bus voltage checking during automatic synchronization

1

P310 Dead Bus Closure Enable

Enables or disables automatic closing to a dead bus.

0

Page 9: 07 B- EMCP II Quick Reference

Setpoint Name Description Range Of Value Factory Default Spare Input 1 0 - active low

Active State 1 - active high Spare input 1 0 - shutdownResponse 1 - alarm Spare Input 1 0 to 250 seconds

Time Delay in increments of 1 Spare Input 2 0 - active low

Active State 1 - active high Spare Input 2 0 - shutdownResponse 1 - alarm Spare Input 2 0 to 250 seconds

Time Delay in increments of 1 Spare Input 3 0 - active low

Active State 1 - active high Spare Input 3 0 - shutdownResponse 1 - alarm Spare Input 3 0 to 250 seconds

Time Delay in increments of 1 Spare Input 4 0 - active low

Active State 1 - active high Spare Input 4 0 - shutdownResponse 1 - alarm Spare Input 4 0 to 250 seconds

Time Delay in increments of 1 Spare Output 0 - active low

Response 1 - active high Spare Relay Output 0 - relay inactive when triggeredResponse 1 - relay active when triggered Spare Output 0 - unusedTrigger Condition 1 - active SP1 fault (2)

2 - active SP2 fault (2)

3 - active SP3 fault (2)

4 - active SP4 fault (2)

5 - any combination of active SP1, SP2, SP3 or SP4 faults (2)

6 - any active shutdown fault (AL1 - AL14, SP1 - 4, or CID FMI)7 - any active alarm or shutdown fault (AL1 - 15, SP1 - 4, or CID FMI)8 - cooldown mode9 - coolant loss fault (2)

10 - high oil temperature fault (2)

Spare Relay Output 11 - CCM control (3)

Trigger Condition Spare Indicator 1 0 - unusedTrigger Condition 1 - active SP1 fault (2)

2 - active SP2 fault (2)

3 - active SP3 fault (2)

4 - active SP4 fault (2)

5 - any combination of active SP1, SP2, SP3 or SP4 faults (2)

Spare Indicator 2 6 - coolant loss fault (2)

Trigger Condition 7 - high oil temperature fault (2) Spare Indicator 3

Trigger Indicator

OP6-0 Setpoints (1) - Spare Input/Output Programming

SP01 Input state used by the GSC+ to declare that a SP1 fault exists.

0

SP02 GSC+ response to a SP1 fault. 0

SP03 Amount of time the GSC+ waits before responding to a SP1 fault.

0 seconds

SP04 Input state used by the GSC+ to declare that a SP2 fault exists.

0

SP05 GSC+ response to a SP2 fault 0

SP06 Amount of time the GSC+ waits before responding to a SP2 fault.

0

SP07 Input state used by the GSC+ to declare that a SP3 fault exists.

0

SP08 GSC+ response to a SP3 fault. 0

SP09 Amount of time the GSC+ waits before responding to a SP3 fault.

0 seconds

SP10 Input state used by the GSC+ to declare that a SP4 fault exist.

0

SP11 GSC+ response to a SP4 fault. 0

SP12 Amount of time the GSC+ waits before responding to a SP4 fault.

0 seconds

SP13 GSC+ response to the spare output trigger condition.

0

SP15 GSC+ response to the spare relay trigger condition.

1

SP14 The condition used by the GSC+ to trigger the spare output trigger response.

8

SP16 The condition used by the GSC+ to trigger the spare relay.

SP17 The condition used by the GSC+ to trigger spare indicator 1.

0

SP18 The condition used by the GSC+ to trigger Spare Indicator 2.

SP19 The condition used by the GSC+ to trigger spare indicator 3.

Page 10: 07 B- EMCP II Quick Reference

Hourmeter Programming OP7

OP7 is used in order to program the hours that are on the hourmeter.

Note: The hours can be increased but not decreased.

Note: The following procedure is applicable only to MUI or PEEC engines when the GSC+/GSC+P determines the value of the hourmeter on the display. The setpoint P023 is programmed to 0 or 1 and OP7 is available for programming. When setpoint P023 is programmed to 2(EUI engines) the value is determined by the engine ECM and OP7 is not available for programming.

The hours of a new GSC+ can be changed in order to match the hours of the former GSC+. OP7 allows the hours on a new GSC+ to exactly match the hours of the previous GSC+. This improves the tracking of engine maintenance when the GSC+ is replaced.

If the hourmeter shows all dashes, the hours can not be reprogrammed. See CID 268 if the hourmeter shows all dashes instead of a reasonable numeric value. CID 268 is within Testing And Adjusting, "Diagnostic Troubleshooting Codes".

Procedure For Hourmeter Programming

A new GSC+ w ith 0 hours is used as an example in the follow ing procedure. The example sets the hours to a value of 1234. If the value of the hours is increased, this procedure is valid.Note: Service Mode cannot be entered w hen the engine control sw itch (ECS) is in the AUTO position.

1. Turn the ECS to the STOP position in order to shut dow n the engine. Enter service mode and enter the passw ord. "OP 4" is show ing on the low er display. See System Operations, "Passw ord Entry OP3".2. Press the "SCROLL UP" key four times. "OP 7" is show ing on the low er display.

3. Press the "SELECT" key. The present hourmeter value is show ing. 0 is the hourmeter value in this example.

4. Press the "SELECT" key. "000000" is show ing. The first digit is f lashing.

5. Press the "SCROLL RIGHT" key tw o times. "000000" is show ing. The third digit is f lashing.

6. Press the "SCROLL UP" key. "001000" is show ing. The third digit is f lashing.

7. Press the "SCROLL RIGHT" key. "001000" is show ing. The fourth digit is f lashing.

8. Press the "SCROLL UP" key tw o times. "001200" is show ing. The fourth digit is f lashing.

9. Press the "SCROLL RIGHT" key. "001200" is show ing. The fifth digit is f lashing.

10. Press the "SCROLL UP" key three times. "001230" is show ing. The fifth digit is f lashing.

11. Press the "SCROLL RIGHT" key. "001230" is show ing. The sixth digit is f lashing.

12. Press the "SCROLL UP" key four times. "001234" is show ing. The sixth digit is f lashing.

13. Press the "ENTER" key. "001234" f lashes on the low er display and "ArE YOU SUrE" is show ing on the upper display.

For yes, press "ENTER" key. "001234" stops f lashing.

For no, press "SELECT" key. "000000" is show ing. The first digit is f lashing. Repeat this procedure to program the hourmeter again.

Note: The original hourmeter value can be stored in the GSC+ memory. When the display show s "ArE YOU SUrE", press the "EXIT" key tw ice for a normal display. The original hourmeter display remains in the GSC+.Note: Entering less hours into the GSC+ memory is not allow ed. The display w ill briefly show "ErrOr". The display then show s the original hours that are stored in the GSC+. The f irst digit w ill be f lashing.14. Press "EXIT" key. "OP 1" is show ing on the low er display.

15. Press "EXIT" key. The display returns to normal mode. As the engine data scrolls, the programmed value should show on the

low er display.

Page 11: 07 B- EMCP II Quick Reference

Setpoint Name Description Range Of Value

Factory Default

AC01 Phase A (VA) Voltage Calibration

Calibration value used by the GSC+ to compensate for the characteristics of the phase A voltage transformer within the ATB+.

0 to 255 in increments of 1

0

AC02 Phase B (VB) Voltage Calibration

Calibration value used by the GSC+ to compensate for the characteristics of the phase B voltage transformer within the ATB+.

0 to 255 in increments of 1

0

AC03 Phase C (VC) Voltage Calibration

Calibration value used by the GSC+ to compensate for the characteristics of the phase C voltage transformer within the ATB+.

0 to 255 in increments of 1

0

AC04 Phase A (IA) Current Calibration

Calibration value used by the GSC+ to compensate for the characteristics of the phase A current transformer within the ATB+.

0 to 255 in increments of 1

0

AC05 Phase B (IB) Current Calibration

Calibration value used by the GSC+ to compensate for the characteristics of the phase B current transformer within the ATB+.

0 to 255 in increments of 1

0

AC06 Phase C (IC) Current Calibration

Calibration value used by the GSC+ to compensate for the characteristics of the phase C current transformer within the ATB+.

0 to 255 in increments of 1

0

AC07 (2) Phase A (VA) Voltage Calibration of BTB+

Calibration value used by the GSC+ to compensate for the characteristics of the phase A voltage transformer within the BTB+.

0 to 255 in increments of one.

0

OP8 Setpoints (1) - Voltmeter Ammeter Programming

Page 12: 07 B- EMCP II Quick Reference

OP9 Engine Setpoint Verification

OP9 is the option for verifying that the EMCP II+ operates correctly

when a fault occurs with low oil pressure, high coolant temperature or

engine overspeed. An engine overspeed fault causes the GSC+ to shut

off the engine. When a low oil pressure or a high water temperaturefault is

detected the GSC+ will shut off the engine or sound the alarm according to

the programmed setpoint P003.

OP9 is only for verification of certain engine setpoints. OP5-0 is used for the actual programming of these setpoints. The setpoints that are verified by this procedure are listed below.

P003 Shutdown Override For Engine Fault - P003 is the GSC+ response to a low engine oil pressure. P003 is also the response to a high coolant temperature fault. 0 is for engine shutdown. If P003 is set to 1 then the alarm responds only. The GSC+ will over

P010 Engine Overspeed

P013 Low Oil Pressure Shutdown At Rated Speed

Note: When the oil pressure drops to a level that is within 34 kPa (5 psi) of the P013 setpoint, a low oil pressure alarm is issued by the GSC+ and the optional alarm module.

P015 High Water Temperature Shutdown

Note: A high water coolant temperature alarm is issued by the GSC+ when the coolant temperature rises to a level that is within 6°C (11°F) of the P015

The following conditions are required before the engine setpoints are verified.

The previously listed setpoints must be correct for the engine application. See System Operation, "Service Mode" in order to view a list of the setpoints. See System Operation, "Setpoint Programming OP5" in order to program the setpoints.

The engine is checked at idle and rated speed. No faults should be present at the initial starting. If necessary, troubleshoot and correct any fault.

Page 13: 07 B- EMCP II Quick Reference

Setpoint

Name Description Range Of Value

Factory Default

PH A Phase A Voltage Adjustment

Value used by the GSC+ in order to offset the voltmeter (for the phase A to neutral reading) from the actual voltage measurement.

-5.0% to +5.0% of measured voltage in increments of 0.04%

0

PH B Phase B Voltage Adjustment

Value used by the GSC+ to offset the voltmeter (for the phase B to neutral reading) from the actual voltage measurement.

-5.0% to +5.0% of measured voltage in increments of 0.04%

0

PH C Phase C Voltage Adjustment

Value used by the GSC+ to offset the voltmeter (for the phase C to neutral reading) from the actual voltage measurement.

-5.0% to +5.0% of measured voltage in increments of 0.04%

0

PH A-B

Phase A-B Voltage Adjustment

Value used by the GSC+ to offset the voltmeter (for the phase A to phase B reading) from the actual voltage measurement.

-5.0% to +5.0% of measured voltage in increments of 0.04%

0

PH B-C

Phase B-C Voltage Adjustment

Value used by the GSC+ to offset the voltmeter (for the phase B to phase C reading) from the actual voltage measurement.

-5.0% to +5.0% of measured voltage in increments of 0.04%

0

PH C-A

Phase C-A Voltage Adjustment

Value used by the GSC+ to offset the voltmeter (for the phase C to phase A reading) from the actual voltage measurement.

-5.0% to +5.0% of measured voltage in increments of 0.04%

0

OP10 Setpoints ( 1) - AC Offset Adjustment

Page 14: 07 B- EMCP II Quick Reference

OP11 Parallel Setpoint TuningOP11 is the option for programming some of the Synchronization

setpoints. For more information, refer to Systems Operation, "Synchronization

Tuning Procedure". P305, P306, P307, P308, and P309 are the setpoints that

are affected by this procedure. The setpoints are described in "Parallel

Programming OP5-3"

Procedure For Programming Synchronization Setpoints

The generator set must be operating at rated speed when the technician is performing this

procedure. The parallel functions are available in OP11 by using the Parallel Mode Switch.

Note: If a parallel function is requested with the Parallel Mode Switch, the OP11 display will be

replaced by the display of the synchroscope while the synchronization is being performed. After

synchronization, the display will return to OP11.

1. Start the engine and run the engine at rated speed. Enter Service Mode and enter the

password. For more information, see Systems Operation, "Password Entry - OP3". "OP9"

should now be showing on the lower display.

2. Press the "SCROLL UP" key twice. OP11 is showing on the lower display.

3. Press the "SELECT". "P305" is showing on the lower display.

4. Press the "SCROLL UP" key or the "SCROLL DOWN" key. The next setpoint and the

value of the setpoint is showing. Repeat this step until the desired setpoint is showing.

5. Press the "SELECT" key. The value of this setpoint is showing.

6. Press the "SCROLL UP" key or the "SCROLL DOWN" key in order to adjust the value of the setpoint. In order to rapidly scroll through a large range of values, press the appropriate "SCROLL" key and hold the key.

7. Press the "ENTER key". The value of the setpoint stops flashing.

8. Repeat Steps 2, 3, 4, 5, 6, and 7 until all of the desired setpoints are adjusted.

9. Press the "EXIT" key. OP1 is showing on the lower display.

10. Press the "EXIT" key. The display returns to the Normal Mode.

Page 15: 07 B- EMCP II Quick Reference

AL Fault Code

Description Troubleshooting

High Water Temperature AlarmCoolant temperature increases to within6°C (11°F) of setpoint P015. Low Engine Coolant Temperature AlarmCoolant temperature decreases to setpoint P016. Low Engine Oil Pressure AlarmOil pressure drops to within34 kPa (5 psi) of the P013 or P014 setpoint. Fault Detected By Engine ECMThe engine ECM detects an alarm fault or a shutdown fault. Low Engine Coolant Level FaultCoolant level drops below the probe of the coolant loss sensor. High Engine Oil Temp FaultOil temperature increases to within6°C (11°F) of setpoint P026. Generator Overvoltage FaultLine to line voltages rises above the P102 or P105 setpoints. Generator Undervoltage FaultLine to line voltage drops below the P108 or the P111 setpoints. Generator Overfrequency FaultFrequency rises above the P114 or P117 setpoints. Generator Underfrequency FaultFrequency drops below the P120 or P123 setpoints. Generator Reverse Power FaultReverse power rises above the P126 setpoint. Generator Phase Overcurrent Fault Check for a cause of the overcurrent.Phase current rises above the P129 or P134 setpoints.

Check setpoint P029 and setpoints P128 through P135.

Generator Total Overcurrent FaultTotal current rises above the P131 or P136 setpoints. Phase A No Voltage Input FaultPhase A voltage not being received at GSC+ input. GSC+ Configuration ErrorFrequency of generator output voltage does not match engine speed.

Incorrect Phase SequenceThe generator and the bus have a phase mismatch. Improper generator or bus voltage 1. The generator voltage and the bus voltage must be above 10% of the

nameplate voltage in P028 when setpoint P020 is set to 700. Generator voltage and bus voltage must be above 50% of the nameplate voltage in P028 when setpoint P020 is set to any other v

The generator voltage or the bus voltage are either too low or the voltages do not match.

2. Check Setpoints P303 and P304 in order to determine whether the generator voltage and the bus voltage match within the tolerance that is specified.

Synchronizer Time-OutThe GSC+P is unable to complete automatic synchronization or dead bus paralleling within the time allowed in P314.

AL18 Check for cause of synchronization time-out. Ensure that the engine is responding properly to the GSC+P Speed Adjust 1 Output signal. Check for wiring errors. Check setpoints P313 and P314 for proper values. Increase the values, if necessary.

Additional AL Fault Codes (for GSC+P) AL16 Check for the cause of the phase sequence mismatch. Check wiring to

the bus transformer box (BTB +) and the AC transformer box (ATB +).

AL17

AL14 Check for an open circuit on the wire that is connected to the GSC+ connector contact 10. Check for a short on the wire that is connected to the GSC+ connector contact 10. See the Testing And Adjusting,

AL15 Check setpoints P009 and P033. Setpoint P009 represents the number of ring gear teeth. Setpoint P033 represents the number of generator poles. Correct the setpoint value, if necessary.

AL11 Refer to the engine service manual for a cause of lost engine power. Check setpoints P125 through P127.

AL12

AL13 Check for a cause of the overcurrent. Check setpoint P029 and setpoints P128 through P137.

AL9 See the Troubleshooting, "Indicator For Engine Overspeed". Check setpoints P113 through P118.

AL10 Refer to the engine service manual for a cause of low engine speed. If engine speed is reduced and the ECS is NOT in STOP, the GSC+ will issue this fault. Check setpoints P119 through P124.

AL7 Refer to the service manual for the voltage regulator that is being used. Check P101 through P106 setpoints.

AL8 Refer to the service manual for the voltage regulator that is being used. Check P107 through P112 setpoints. Refer to the engine service manual for the cause of low engine speed. If engine speed is reduced

AL5 Check level of engine coolant. The level of engine coolant must be above the probe of the sensor. Check for CID 111 faults. Perform the electrical connector inspection test. Refer to the Testing and

AL6 Check level of engine coolant. The level of engine coolant must be above the probe of sensor. Check fan belt, etc. Check P026 setpoint.

AL3 See the Troubleshooting, "Troubleshooting Dedicated Shutdown Indicators".

AL4 Refer to the appropriate engine troubleshooting service manual.

AL Fault Code Troubleshooting

AL1 See the Troubleshooting, "Troubleshooting Dedicated Shutdown Indicators".

AL2 See the Troubleshooting, "Troubleshooting Dedicated Shutdown Indicators".

Page 16: 07 B- EMCP II Quick Reference

CID No. / FMI No. Description FMI 12 Failed component

FMI 2 Incorrect signal FMI 3 Voltage above normal FMI 12 Failed component FMI 4 Voltage below normal

FMI 12 Failed component FMI 2 Incorrect signal FMI 3 Voltage above normal FMI 12 Failed component FMI 4 Voltage below normal

FMI 3 Voltage above normal FMI 3 Voltage above normal FMI 4 Voltage below normal

FMI 3 Voltage above normal FMI 12 Failed component FMI 4 Voltage below normal

FMI 7 Improper mechanical response

FMI 2 Incorrect signal FMI 3 Voltage above normal FMI 9 Abnormal update FMI 4 Voltage below normal

FMI 9 Abnormal update FMI 2 Incorrect signal FMI 3 Voltage above normal FMI 3 Voltage above normal

FMI 4 Voltage below normal FMI 9 Abnormal update

FMI 3 Voltage above normal FMI 2 Incorrect signal FMI 4 Voltage below normal

FMI 3 Voltage above normal FMI 3 Voltage above normal FMI 4 Voltage below normal FMI 4 Voltage below normal

FMI 3 Voltage above normal FMI 4 Voltage below normal FMI 4 Voltage below normal

FMI 3 Voltage above normal FMI 3 Voltage above normal FMI 4 Voltage below normal FMI 4 Voltage below normal

FMI 2 Incorrect signal FMI 2 Undefined state

FMI 2 Incorrect siganl FMI 12 Failed component FMI 4 Voltage below normal

FMI 8 Abnormal signal FMI 12 Failed component

FMI 3 Voltage above normal FMI 12 Failed component ( 1 )

For troubleshooting, see the procedure with the same CID And FMI No.

( 2 ) Parallelling Applications Only

FMI 12 Failed component

Diagnostic Codes (1)

CID 100 - Pressure Sensor (Engine Oil):

CID 110 - Temperature Sensor (Engine Coolant):

CID 269 - Sensor Power Supply:

CID 333 - Alarm Module Control:

CID 111 - Fluid Level Sensor (Engine Coolant):

CID 168 - Electrical System Voltage:

CID 175 - Temperature Sensor (Engine Oil):

CID 190 - Speed Sensor (Engine):

CID 443 - Crank Termination Relay:

CID 444 - Starting Motor Relay:

CID 445 - Run Relay:

CID 446 - Air Shutoff Relay:

CID 334 - Spare Output:

CID 336 - Switch (Engine Control):

CID 441 - Electronic Governor Relay:

CID 442 - Generator Fault Relay:

CID 248 - CAT Data Link:

CID 268 - EMCP Electronic Control (Generator

CID 447 - Fuel Control Relay:

CID 448 - Programmable Spare Relay:

CID 475 - Relay Driver Module:

CID 500 - EMCP Electronic Control (Generator

CID 566 - Unexpected Shutdown:

CID 590 - Engine Electronic Control Module:

CID 770 - Customer Communication Module

CID 858 - Generator Close Breaker: ( 2)

CID 1169 - AC Transformer Box Sensor:

CID 1170 - Bus Transformer Box Sensor:

CID 1178 - Pressure Sensor For Machine

CID 859 - Kilowatt Level Output:

CID 1038 - Governor Adjust Analog Output:

CID 1167 - EPG Circuit Breaker:

CID 1168 - Dead Bus Sensor:

Page 17: 07 B- EMCP II Quick Reference

Typical Generator AbbreviationsA - Ammeter ACT - Actuator ADS - Engine Combustion Air Damper Position Switch AFCR - Auxiliary Fuel Control Valve ALM - Alarm Module ALS - Alarm Silence Push Button ALT - Alternator AR - Arming Relay ASOS - Air Shutoff Solenoid ASR - Air Shutoff Relay ASSV - Air Start Solenoid Valve ATB - AC Transformer Box AUX - Auxiliary Terminal Strip AUXREL - Auxiliary Relay (Crank Termination) AWG - American Wire Gauge BATT - Battery BCF - Battery Charger Failure Switch BTB - Bus Transformer Box C - Common CAM - Custom Alarm Module CAR - Custom Alarm Relay CB - Circuit Breaker CCM - Customer Communication Module CDM - Engine Cooldown Timer Module CIM - Customer Interface Module CID – Code or Component IdentifierCT - Current Transformer CTR - Crank Termination Relay D - Diode DCV - DC Voltmeter DIAG – Diagnostic or Diagram DS - Disconnect Switch ECLC - Engine Coolant Loss Sensor Connector ECLS - Engine Coolant Loss Sensor ECS - Engine Control Switch ECTS - Engine Coolant Temperature Sensor EFCR - Emergency Fuel Control Relay EFL - Emergency Fuel Light EG - Electronic Governor (Speed Sensing) EGA - Electronic Governor Actuator EGR - Electronic Governor Relay EHC - Ether Hold-In Coil EHS - Ether Hold-In Switch ENFR - Engine Failure Relay EOTC - Engine Oil Temperature Sensor Connector EOTS - Engine Oil Temperature Sensor EOPS - Engine Oil Pressure Sensor EPC - Ether Pull-In Coil EPS - Ether Pull-In Switch ES - Ether Solenoid ESPB - Emergency Stop Push Button

ESL - Emergency Stop Light F - Fuse FCR - Fuel Control Relay FCTM - Fuel Control Timer Module FMI – Failure Mode IdentifierFRB - Fuel Rupture Basin FS - Fuel Solenoid FSOS - Fuel Shutoff Solenoid GFR - Generator Fault Relay GOL - Generator On Load GOV - Governor GPHI - Ground Post (High Voltage) GPLO - Ground Post (Low Voltage) GS - Governor Switch GSC - Generator Set Control GSM - Governor Synchronizing Motor GSOV - Gas Shutoff Valve HZ - Frequency Meter KWR - Kilowatt Level Relay IC - Remote Start/Stop Initiate Contact L - Load Leads LFL - Low Fuel Level Light LFLAS - Low Fuel Level Alarm Switch LFS - Latching Fuel Control Solenoid LOLAS - Low Oil Level Alarm Switch LWLAS - Low Water Level Alarm Switch LWTL - Low Water Temperature Light MAN - Manual MPU - Magnetic Speed Pickup NC - Normally Closed NO - Normally Open OCL - Overcrank Light OCR - Overcurrent Relay OCT - Overcrank Timer OP - Oil Pressure OPG - Oil Pressure Gauge OPL - Oil Pressure Light OSL - Overspeed Light OSR - Oil Step Relay OVR - Overvoltage Relay PEEC - Programmable Electronic Engine Control PL - Panel Illumination Light PLS - Panel Light Switch POS - Positive POT - Potentiometer PP - Prelube Pump PPMS - Prelube Pump Magnetic Switch PPPS - Prelube Pump Oil Pressure Switch PR - PreregulatorPS - Pinion Solenoid PWM - Electrical Converter (Pulse Width Modulated)

Page 18: 07 B- EMCP II Quick Reference

RAN - Remote AnnunciatorRDM - Relay Driver Module RPL - Reverse Power Light RPR - Reverse Power Relay RPSR - Reverse Power Slave Relay RR - Run Relay SASV - Start Aid Solenoid Valve SATS - Start Aid Temperature Switch SAS - Starting Aid Switch SEC - Second SHTC - Circuit Breaker Shunt Trip Coil SIG - Signal SL - Synchronizing Light SLM - Synchronizing Light Module SLR - Synchronizing Light Resistor SM - Starting Motor SMMS - Starting Motor Magnetic Switch SMR - Starting Motor Relay SP - Speed Adjust Potentiometer SPM - Synchronizing Parallel Module SR - Slave Relay SS - Synchronizing Switch T - Generator Line Leads TD - Time Delay Relay TSC - Transfer Switch Position Indicating Contact V - AC Voltmeter VAR - Voltage Adjust Rheostat VR - Voltage Regulator WT - Water Temperature WTG - Water Temperature Gauge WTL - Water Temperature Light XDUCER - Transducer Z - Zener Diode

DATE NOTES