![Page 1: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/1.jpg)
NO. 1
TO THE DRAWINGS AND THE PROJECT MANUAL
PROJECT NAME: Aubrey MS Addition
CLIENT NAME: Aubrey ISD
LOCATION: Aubrey, Texas
PROJECT NUMBER: 1780-02-01
PROPOSAL DATE: Tuesday, September, 18, 2018, 2:00 PM
ADDENDUM DATE: Thursday, September, 13, 2018
For additional information regarding this project, contact Ron Rodpracha at 800.687.1229.
THIS ADDENDUM INCLUDES:
Civil Items 1 Pages
Landscape Items - Pages
Structural Items 1 Pages
Architectural Items 1 Pages
Foodservice Items - Pages
Plumbing Items - Pages
Mechanical Items 1 Pages
Electrical Items - Pages
Technology Items 1 Pages
AND ALL ATTACHED REVISED DRAWING REFERENCES IN THE ADDENDUM
���
09/13/2018
![Page 2: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/2.jpg)
Project Name: Aubrey MS Addition Client: Aubrey ISD Aubrey, Texas Project Number: 1780-02-01
Civil Items For Addendum No. #
Page 1 of 1
CIVIL ITEMS FOR ADDENDUM NO. 1 NOTICE TO PROPOSERS:
A. This Addendum shall be considered part of the contract documents for the above-mentioned project as though it had been issued at the same time and incorporated integrally therewith. Where provisions of the following supplementary data differ from those of the original contract documents, this Addendum shall govern and take precedence.
B. Proposers are hereby notified that they shall make any necessary adjustments in their estimate on account of this Addendum. It will be construed that each Proposer’s proposal is submitted with full knowledge of all modifications and supplemental data specified therein. Acknowledge receipt of this addendum in the space provided on the proposal form. Failure to do so may subject Proposer to disqualification.
REFERENCE IS MADE TO THE DRAWINGS AS NOTED: DRAWINGS: AD No 1, Civil Item 1: To the Drawings, Sheet C5.0, “GRADING PLAN,”
1) Grades revised for positive drainage and clarity END OF CIVIL ADDENDUM
![Page 3: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/3.jpg)
RIM=648.1'
UP UP/UG GUY
IVIV
COCO
IV IV IV
GA
TE
TBM MNS654.66'
RIM=654.4'
IVWM
IV
FL 18"RCP =646.8'FL 18"RCP =646.9'
FL 18"RCP =646.6'FL 18"RCP =646.5'
IV
IV
FL 18"RCP =646.4'
FL 18"RCP =646.3'IV
WM
EM
WELL EQUIPMENT
IV
GA
TE
BUILDING CORNERBUILDING CORNER
BUILDING CORNER
RIM=648.3'OU OU OU OU OU OU OU OU OU OU
IVIV
RD
RD
FH
RD
RD
COCOCOGATE7" OAK
IVIV
4" ELM
9" OAK
3" ELM
4" PINE
WVWVWV
FL 12"PVC =653.7'
LP
IV
LEBLEB
COCO
660.2'FINISHED FLOOR
EAVEEAVEEAVE
RD
RDCOCO
RD
RD
RD RD
GI TOP=657.1'FL 15"PVC =655.3'
EAVEEAVEEAVE
EAVE
EAVEEAVE
RD
RDGI TOP=657.6'
FL 15"PVC =655.7'
RD
ROOF DRAIN656.14'
WMWVWVWVWV
LP
4" OAK
IV659.71'
IV659.66'
IVIV
4" ELMIVIV
LEBCOCO
FL 24
"PVC =6
53.5'
FL 24
"PVC =6
53.6'
FL 18"PVC =655.3'
RD
RD
11745
26" COTTONWOOD
EAVEEAVE
EAVE
FL 18"PVC =655.8'
RD RD GP GPRD
RDCO RD
RD
RD
RIM=658.3'
RIM=658.3' RIM=658.5'
RD
COCO
RD RD RD
RD
GMGPGPGP
RD
GATE GATE FDC
RD
RD
RDRD COCOCO
EAVE
EAVE EAVEGP GP GP GP GP
GP
GP657.91'
FL 30"PVC =641.6'
15" PECAN
21" PECAN
18" PECAN
12" PECAN
18" PECAN
16" PECAN
16" PECAN
18" PECAN
IVIVIVBUILDING
BUILDING
BUILDING
CONCRETE
CO
NC
RET
E
CONCRETE
ST
ST
ST
GATE
CONCRETE
GATE
GRAVEL
GRAVEL
645
650
642
643
644
646
647
648
649
645
642
643
644
646
647
648649
641
641
640
638639
639
640
640
645
641
642
643
644
646
646645
644
643
644
645
647
648
647
643
642
649650
650
648
649
651650
651
652
653
654
650
648
649
651
652
653
655654
656
657
660
658
659
661
662
656
657
658
659
660
661 660 65
8
65865
7
658
658
659
656
657
659
655
656 657
658
657657
658
656
655
656
657
65765
8659
658 658
659
652
653
654
655
655
658
659
65965
6
656
658
659
658
659
CONCRETE
CONCRETE
EAV
E
EAV
E
CONCRETE
EAVE
CONCRETE
CONCRETE
EAVE
CONCRETEDRAIN CHANNEL
CONCRETEBLOCKS
(TYPICAL)
CONCRETEDRAIN CHANNEL
BIG D
COMMERCIAL V
ENTURES, LLC,
A TEXAS LIMIT
ED LIABIL
ITY COMPANY
INST. #
2016
-2769
6
O.P.R.D.C.T.
N0
0°5
9'5
2"E
8
16
.8
0'
16' PUBLIC UTILITY EASEMENTCABINET W, SLIDE 232
P.R.D.C.T.
DENNIS COWAN SURVEY
ABSTRACT NO. 3
04
APPROXIMATE LOCATION OF 20' UTILITY EASEMENTGRAPHICALLY DEPICTED ON ADJACENT PLATRECORDED IN CABINET W, SLIDE 232, P.R.D.C.T. ( SEESURVEYOR'S NOTE NO. 5)
APPROXIMATE LIMITS OF ZONE A
APPROXIMATE LIMITS OF ZONE X
(SEE FEMA FLOOD CLASSIFICATION)
APPROXIMATE LIMITS OF ZONE A
(SEE FEMA FLOOD CLASSIFICATION)
(N00
°32'
22"E
817
.32'
)
50' MUTUAL ACCESS, UTILITYAND DRAINAGE EASEMENT
CABINET W, SLIDE 232P.R.D.C.T.
(SEE SURVEYOR'S NOTE NO. 5)
APPROXIMATE LOCATION
OF GEOTHERMAL WELL
APPROXIMATE LOCATION
OF GEOTHERMAL WELL
APPROXIMATE LOCATION
OF GEOTHERMAL WELL
APPROXIMATE LOCATION
OF GEOTHERMAL WELL
APPROXIMATE LOCATION
OF GEOTHERMAL WELL
T
FH
FH
FH
FH
VAN
VA
N
ATHLETIC ADDITION
EXISTING BUILDING
FFE = 655.73
FFE = 658.40
6
5
5
6
5
5
655
TP=651.75
TP=651.65
TP=655.00
TP=655.65
TP=655.60
TP=655.15
FG=655.00FG=655.00
FG=655.00FG=655.00
FG=655.55
TP=655.15
TP=655.60
TP=654.10
TP=654.10
TP=654.00
TP=654.00
TP=653.65
TP=653.65
TP=653.65
TP=653.45
TP=653.10
TP=655.65
TP=655.60
TP=658.36±
MATCH EX.
FG=658.00
Match Ex.
TP=657.90
TP=658.10
TP=657.70
TP=658.15
TC=658.15
TP=657.70
TP=657.65
TC=657.85
TP=657.35
TP=657.75
TP=658.05
TC=657.35
TP=656.85
TP=658.34±
MATCH EX.
TP=657.91±
MATCH EX.
TP=658.19±
MATCH EX.
TP=658.15±
MATCH EX.
TC=658.15
TP=657.75
FG=658.00
MATCH EX.
TP=656.50±
MATCH EX.
TP=655.35
TC=655.75
TP=655.25
TP=654.85
TP=654.80
TC=655.40
TP=654.90
TP=655.40
TP=655.65
TC=655.00
TP = 654.60
TP=655.00
TC=655.50
TP=655.10
TC=655.00
TP=654.50
TP=654.00
TP=656.28±
MATCH EX.
TP=656.28±
MATCH EX.
FG=654.50
FG=654.50
FG=654.50
TC=653.00
TP=652.50
TP=653.60
TP=653.55
TC=658.35
TP=658.00
TP=655.60
TP=655.64
TP=655.65
TP=655.65
6
5
5
6
6
0
6
5
5
TP=655.90
TP=655.20
TP=655.30
6
5
4
TP=655.30
TP=655.55
TP=655.85
TP=656.10
TP=655.20
6
5
5
TP=656.05
6
5
0
655
FFE =
651.50
TP=649.65
TC=654.20
TP=653.70
TC=652.75
TP=652.25
TP=650.35
TP=649.55
TC=654.75
TP=654.25
TC=655.65
TP=655.15
TP=655.70
TP=655.5
TP=655.85
TP=655.90
TC=655.60
TP=655.10
TP=653.55
TP=653.50
TC=654.00
TP=653.50
TC=656.75
TP=656.25
TC=657.30
TP=656.80
TC=656.75
TP=656.25
TC=657.10
TP=656.60
TC=659.90
TP=659.40
TC=662.28±
TP=661.78±
MATCH EX.
TC=662.35±
TP=661.85±
MATCH EX.
TP=659.82±
MATCH EX.
TC=660.14±
TP=659.64±
MATCH EX.
TC=660.75±
TP=660.25±
MATCH EX.
FG=651.9 ±
TP=652.35
TP=653.75
TP=653.65
TC=653.50
TC=654.85
TP=654.40
%5.0MAX
TP=656.89±
MATCH EX.
TP=656.85
TP=656.85±
MATCH EX.
TP=656.65±
MATCH EX.
TC=656.75±
MATCH EX.
TP=656.16±
MATCH EX.
TP=649.00
TP=652.20TP=652.10
TP=649.75
6
5
0
FG=651.00
FG=651.00
FG=651.00
FG=651.00
TP=651.42
6
5
6
6
5
7
6
5
8
6
5
4
6
5
4
6
5
4
6
5
6
6
5
3
6
5
4
655
6
5
2
6
5
1
6
5
2
6
5
4
656
657
6
5
9
6
6
1
6
5
8
6
5
8
65
8
6
5
7
6
5
7
6
5
6
6
5
6
6
5
4
6
5
9
6
57
6
5
5
6
5
6
656
6
5
1
6
5
2
6
5
2
6
5
3
6
5
2
6
5
1
6
5
3
6
5
2
6
5
1
6
5
4
6
5
4
653
6
5
4
6
5
6
656
657
6
5
1
653
652
6
5
2
6
5
1
656
653
6
5
3
65
3
653
6
5
5
6
5
0
TP=654.40
TC=655.50
TP=655.00
TP=655.65
6
5
4
TP=656.30
6
5
3
6
5
3
6
5
3
6
5
4
6
5
5
6
5
9
6
5
4
653
6
5
6
6
5
9
6
5
8
6
5
7
652
TP=651.45
TC=655.05
TP=654.55
TP=655.25
TP=655.45
6
6
0
TP=655.20
TP=655.20
TC=654.60
TP=654.10
TP=652.85
TP=650.5
FG=650.62
TP=654.00
651
650
TC=657.75
TP=657.25
651
650
649
648
647
646
ADJUST TO
FINISHED GRADE
ADJUST TO
FINISHED GRADE
ADJUST TO
FINISHED GRADE
ADJUST TO
FINISHED GRADE
PERFORATED PIPE TO MAINTAIN
CONSTANT ELEVATION OF 55.1
FL 3" = 55.1 ( TOP OF PIPE 55.35)
(BOTTOM OF 4" SIDEWALK 55.4)
FL 3" = 54.90
RIGID PVC
AREA OF <2%
ENERGY DISSIPATION RIP RAP AS
SHOWN. MIN. 24” THICK OF
WELL GRADED 12” AVG DIA STONE
MIXTURE OVER A FILTER BLANKET OR
BEDDING GRADED GRAVEL.
ENERGY DISSIPATION RIP RAP AS
SHOWN. MIN. 24” THICK OF
WELL GRADED 12” AVG DIA STONE
MIXTURE OVER A FILTER BLANKET OR
BEDDING GRADED GRAVEL.
6.0'6.0'
LEGEND
FG=100.50
100
100
PROPOSED CONTOUR
EXISTING CONTOUR
GRADE BREAK
FLOWLINE
ACCESSIBLE ROUTE
SPOT GRADE
PROPOSED FLOW ARROW
FG FINISHED GRADE
TP TOP OF PAVEMENT
TC TOP OF CURB
FL FLOWLINE
FF FINISHED FLOOR
SITE GRADING - IBC REQUIREMENT (SEC. 1804)
· THE GROUND IMMEDIATELY ADJACENT TO THE FOUNDATION
SHALL BE SLOPED AWAY FROM THE BUILDING AT A SLOPE OF NOT
LESS THAN ONE UNIT VERTICAL IN 20 UNITS HORIZONTAL
(5-PERCENT SLOPE) FOR A MINIMUM DISTANCE OF 10-FEET
MEASURED PERPENDICULAR TO THE FACE OF THE WALL.
· IF PHYSICAL OBSTRUCTIONS OR LOT LINES PROHIBIT 10-FEET OF
HORIZONTAL DISTANCE, A 5-PERCENT SLOPE SHALL BE PROVIDED
TO AN APPROVED ALTERNATIVE METHOD OF DIVERTING WATER
AWAY FROM THE FOUNDATION. SWALES USED FOR THIS PURPOSE
SHALL BE SLOPED A MINIMUM OF 2 PERCENT WHERE LOCATED
WITHIN 10-FEET OF THE BUILDING FOUNDATION.
· IMPERVIOUS SURFACES WITHIN 10-FEET OF THE BUILDING
FOUNDATION SHALL BE SLOPED A MINIMUM OF 2-PERCENT AWAY
FROM THE BUILDING.
TBPE Registration #: F-1002
Sheet of
Sheet No.Job. No.
Drawn By:
Date:
Pro
ject:
Re
vis
ion
/ D
ate
Copyright © 2018, Huckabee & Associates, Inc.
This drawing was prepared by Adams Consulting Engineers, Inc.(Adams) as an instrument of service, and shall remain the propertyof Adams. The information hereon shall be used only by the client
to whom the services are rendered and only for the purpose ofconstructing or installing the work as shown at the designated
location and site. Any other use, including (without limitation) anyreproduction or alteration, is strictly prohibited, and the user shallhold harmless and indemnify Adams from all liabilities which may
arise from such unauthorized use.
AU
BR
EY
M
ID
DL
E S
CH
OO
L
AD
DIT
IO
N
FO
R
AU
BR
EY
I.S
.D
.
AU
BR
EY
, T
EX
AS
PACKAGE 1
AUGUST 27, 2018
2018.024
GENERAL SITE GRADING NOTE
· AS PART OF THE BASE BID THE CONTRACTOR SHALL PROVIDE/IMPORTALL SELECT FILL AND TOPSOIL MATERIAL NECESSARY TO ACHIEVE FINALGRADE PER PLAN.
· ALL AREAS WITHIN CONSTRUCTION LIMITS NOT COVERED WITH ANIMPERVIOUS MATERIAL SHALL BE COVERED WITH TOPSOIL. THETOPSOIL SHALL BE IN CONFORMANCE WITH THE TOPSOIL NOTES LISTEDIN THE PLAN SET AND SPECIFICATIONS FOR THIS PROJECT.
· BASE BID SHALL ALSO INCLUDE HAUL OFF OF EXCESS MATERIAL ASNECESSARY.
· ANY FILL PLACED ONSITE SHALL BE TESTED AND APPROVED BY THEPROJECT GEOTECHNICAL ENGINEER AND BE IN CONFORMANCE WITHRECOMMENDATIONS LISTED IN THE SITE GEOTECHNICAL REPORTNO. G18-2113-A AND DATED JULY 2, 2018 OR ANY SUPPLEMENTALADDENDUMS.
STANDARD ACCESSIBILITY REQUIREMENTS
PARKING:
ACCESSIBLE PARKING SPACES SHALL BE AS NOTED TO A MIN. 96" WIDE OR A MIN.
132" WIDE FOR VAN DESIGNATED SPACES WITH A MAXIMUM SLOPE OF 2% (IN ALL
DIRECTIONS). ALL BUILDINGS SHALL CONTAIN AT LEAST ONE VAN ACCESSIBLE
SPACE FOR NO LESS THAN ONE VAN SPACE FOR EVERY 6 ACCESSIBLE SPACES.
EACH ACCESSIBLE PARKING SPACE SHALL HAVE A VERTICALLY MOUNTED (OR
SUSPENDED) SIGN SHOWING THE SYMBOL OF ACCESSIBILITY. APPROPRIATE
VAN ACCESSIBLE SPACES MUST INCORPORATE "VAN-ACCESSIBLE" BELOW THE
SYMBOL OF ACCESSIBILITY. SIGNS SHALL BE LOCATED AS NOTED TO 80" (MIN.)
ABOVE THE ADJACENT PAVED SURFACE TO BOTTOM OF SIGN.
ALL ACCESS AISLES SERVING ACCESSIBLE PARKING SPACES SHALL BE AS NOTED
TO A 60" WIDE MINIMUM.
RAMPS:
RAMPS EXCEEDING 6" IN RISE (EXCLUDING CURB RAMPS) SHALL HAVE
APPROPRIATE EDGE PROTECTION WITH HANDRAILS ON EACH SIDE AT BETWEEN
34" AND 38", AND EXTEND 12" BEYOND THE TOP AND BOTTOM OF RAMP. HANDRAIL
SHALL NOT DIMINISH THE CLEAR AREA REQUIRED FOR TOP AND BOTTOM
LANDINGS SERVING THE RAMPS.
RAMPS SHALL HAVE A SURFACE ARRANGED SO THAT WATER WILL NOT
ACCUMULATE. COLOR OF RAMP FINISH MATERIAL (INCLUDING CONCRETE) SHALL
HAVE A LIGHT AND REFLECTIVE VALUE TO SIGNIFICANTLY CONTRAST FROM
ADJACENT SURFACES OR COLORS ONLY IF REQUIRED BY LOCAL OR STATE
JURISDICTION
LANDINGS FOR RAMPS SHALL BE AS WIDE AS THE RAMP AND 60" LONG MINIMUM
(36" MINIMUM FOR CURB RAMPS)
RAMPS SHALL NOT EXCEED A 1:12 RUNNING SLOPE OR 30" RISE
RAMPS AND LANDINGS SHALL NOT EXCEED 1:48 (2% CROSS SLOPE)
SIDEWALKS AND ACCESSIBLE ROUTES:
SIDEWALKS MUST BE AT LEAST 36" WIDE WITH 5'X5' CLEAR PASSING OPPORTUNITIESIN INCREMENTS LESS THAN 150 LFSIDEWALK CROSS SLOPE SHALL NOT EXCEED 1:48 (2%)
LONGITUDINAL SLOPE OF ANY SIDEWALK (ACCESSIBLE ROUTE)
SHALL NOT EXCEED 1:20 (5%)
A
B
C
D
E
F
G
H
I
J
C5.0MSH
GRADING PLAN
Know what'sbelow.
before you dig.Call
R
THESE PLANS ARE SUBJECT TO REVIEW &
APPROVAL BY JURISDICTIONAL ENTITIES.
THE CONTRACTOR IS SPECIFICALLY CAUTIONED THAT THE LOCATION AND/OR
ELEVATION OF ANY EXISTING UTILITIES AS SHOWN ON THESE PLANS ARE BASED
ON RECORDS OF THE VARIOUS UTILITY COMPANIES, THE GOVERNING
MUNICIPALITY, AND WHERE POSSIBLE, MEASUREMENTS TAKEN IN THE FIELD. THE
INFORMATION PROVIDED IS NOT TO BE RELIED ON AS BEING EXACT OR COMPLETE.
THE CONTRACTOR MUST CALL THE APPROPRIATE UTILITY COMPANY AT LEAST 48
HOURS BEFORE ANY EXCAVATION TO REQUEST EXACT FIELD LOCATION OF
UTILITIES. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO RELOCATE
ALL EXISTING UTILITIES WHICH CONFLICT WITH THE PROPOSED IMPROVEMENTS
SHOWN ON THESE PLANS.
**NOTICE TO CONTRACTORS - UTILITIES**
!!!CAUTION!!!
EXISTING OVERHEAD & UNDERGROUND UTILITIES IN THE VICINITY.
VERIFY LOCATION OF EXISTING UNDERGROUND UTILITIES
BY VACUUM EXCAVATION OR OTHER POTHOLING TECHNIQUES.
** NOTICE TO CONTRACTORS - TOPOGRAPHIC SURVEY **
TOPOGRAPHIC INFORMATION TAKEN FROM A TOPOGRAPHIC SURVEY PERFORMED
BY JPH LAND SURVEYING, INC.. THE CONTRACTOR SHALL NOTIFY THE ENGINEER
IMMEDIATELY, IN WRITING, OF ANY DISCREPANCIES OR OMISSIONS TO THE
TOPOGRAPHIC INFORMATION. THE CONTRACTOR(S) SHALL BE RESPONSIBLE FOR
CONFIRMING THE LOCATION (HORIZONTAL/VERTICAL) OF ANY BURIED CABLES,
CONDUITS, PIPES, AND STRUCTURES (STORM SEWER, SANITARY SEWER, WATER,
GAS, TELEVISION, TELEPHONE, ETC.) WHICH IMPACT THE CONSTRUCTION SITE. THE
CONTRACTOR(S) SHALL NOTIFY THE OWNER AND ENGINEER IF ANY DISCREPANCIES
ARE FOUND BETWEEN THE ACTUAL CONDITIONS VERSUS THE DATA CONTAINED IN
THE CONSTRUCTION PLANS. ANY COSTS INCURRED AS THE RESULT OF NOT
CONFIRMING THE ACTUAL LOCATION (HORIZONTAL/VERTICAL) OF SAID CABLES,
CONDUITS, PIPES, AND STRUCTURES SHALL BE BORNE BY THE CONTRACTOR.
ADDITIONALLY, THE CONTRACTOR(S) SHALL NOTIFY THE OWNER AND ENGINEER IF
ANY ERRORS OR DISCREPANCIES ARE FOUND ON THE CONSTRUCTION DOCUMENTS
(PS&E), WHICH NEGATIVELY IMPACT THE PROJECT. THE ENGINEER AND OWNER
SHALL BE INDEMNIFIED OF PROBLEMS AND/OR COST WHICH MAY RESULT FROM
CONTRACTOR'S FAILURE TO NOTIFY ENGINEER AND OWNER.
GRAPHIC SCALE
FEET0 6030
10
9/1
2/2
01
8A
DD
EN
DU
M #
1
1- REVISED GRADING SPOT
SHOTS/CONTOURS AT SOUTH WEST OF
PARKING LOT
![Page 4: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/4.jpg)
Project Name: Aubrey MS Addition Client: Aubrey ISD Aubrey, Texas Project Number: 1780-02-01
Structural Items For Addendum No. #
Page 1 of 1
STRUCTURAL ITEMS FOR ADDENDUM NO. 1 NOTICE TO PROPOSERS:
A. This Addendum shall be considered part of the contract documents for the above-mentioned project as though it
had been issued at the same time and incorporated integrally therewith. Where provisions of the following supplementary data differ from those of the original contract documents, this Addendum shall govern and take
precedence. B. Proposers are hereby notified that they shall make any necessary adjustments in their estimate on account of this
Addendum. It will be construed that each Proposer’s proposal is submitted with full knowledge of all modifications
and supplemental data specified therein. Acknowledge receipt of this addendum in the space provided on the proposal form. Failure to do so may subject Proposer to disqualification.
REFERENCE IS MADE TO THE DRAWINGS AND THE PROJECT MANUAL AS NOTED:
DRAWINGS: AD No 1, Struct Item 1: To the Drawings, Sheet S2.1, “FOUNDATION & GROUND FLOOR PLAN,”
1) Added section 16/S3.3 at displace cases (2 locations)
AD No 1, Struct Item 2: To the Drawings, Sheet S2.2, “LOW ROOF FRAMING PLAN,”
1) Added section 22/S5.3 at overhead door 2) Updated RTU weights on low roof framing to match mechanical schedule
AD No 1, Struct Item 3: To the Drawings, Sheet S2.3, “HIGH ROOF FRAMING PLAN,”
1) Updated RTU weights on high roof framing to match mechanical schedule
AD No 1, Struct Item 4: To the Drawings, Sheet S3.3, “CONCRETE DETAILS,”
1) New detail, 16/S3.3, at display cases
AD No 1, Struct Item 5: To the Drawings, Sheet S5.3, “ELEVATED FRAMING DETAILS,”
1) Detail 11/S5.3, added notation for connection of WF beam 2) Detail 12/S5.3, revised graphical height of CMU parapet to match architectural and depth of lintel grout to match
scheduled depth
3) Detail 15/S5.3, revised roof edge angle to CMU connection to be consistent with surrounding details 4) New detail, 22/S5.3, at overhead door
END OF STRUCTURAL ADDENDUM
![Page 5: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/5.jpg)
1
12
3
34
5
5
6
6
A A
B
C
D
E
F
G
I
8 3/8"
8 3/
8"
8 3/
8"
TOC 97' - 1 7/16"
TOC 98' - 8"
TOC 100' - 0"
B.1
4.1
7' - 0 1/8"
7 3/8"
8' - 0" 20' - 7" 14' - 2" 19' - 8 1/2" 19' - 8 1/2" 7' - 6"
15' - 7 1/2" 20' - 7" 14' - 3" 10"
84' - 7" 14' - 4 1/4" 50' - 11 1/4" 46' - 0"
8 3/8"
1' -
0"
18' -
1"
19' -
9"
19' -
9"
19' -
9"
19' -
9"
19' -
0"
10"
4' -
2 1
/4"
12' -
8"
23' -
4"
62' -
8"
1' -
0"
4 1/4"
4' -
0"
9' -
5 1
/4"
5' -
7"
8' -
0"
9' -
3"
12' -
8"
17' -
6 3
/4"
18' -
8"
10"
14' - 6" 15' - 4" 15' - 4" 10"
16' -
0"
5' -
0"
16' -
0"
C1
3
S3.2
3
S3.2
11
S3.3
7
S3.2
7
S3.2
4
S3.2
4
S3.2
4
S3.2
4
S3.2
7
S3.2
8
S3.2
6
S3.2
16
S3.2
9
S3.2
5 3/8"
4"
10"
12' -
11
3/4"
12' -
8"
17' -
2"
8' -
1 1
/4"
6' -
11"
4' -
0"
1" E
J
1
S4.2
117'
- 1
1"
195' - 10 1/2"
10" 20' - 5" 20' - 10" 20' - 10" 20' - 10" 10" 14' - 0"
13' - 10"
17
S3.2
GR BM JOG
AT EJ ABUT TO EXIST
14
S3.2
18
S3.2
11
S3.2
12
S3.2
21
S3.2
94' - 0"
P1
94' - 0"
P294' - 0"
P294' - 0"
P294' - 0"
P294' - 0"
P2
94' - 0"
P2
94' - 0"
P2
94' - 0"
P2
94' - 0"
P2
94' - 0"
P2
94' - 0"
P294' - 0"
P294' - 0"
P294' - 0"
P294' - 0"
P2
94' - 8"
P2
94' - 0"
P2
94' - 0"
P2
94' - 0"
P2
94' - 0"
P2
94' - 0"
P2
94' - 0"
P1
94' - 0"
P194' - 0"
P1
94' - 0"
P1
94' - 0"
P194' - 8"
P1
94' - 8"
P1
94' - 8"
P194' - 8"
P1
94' - 8"
P194' - 8"
P1
94' - 8"
P194' - 8"
P1
94' - 8"
P1
94' - 0"
P194' - 0"
P194' - 0"
P1
94' - 0"
P1
94' - 0"
P1
94' - 8"
P2
94' - 8"
P2
94' - 8"
P294' - 8"
P294' - 8"
P294' - 8"
P294' - 8"
P2
94' - 8"
P2
94' - 8"
P2
94' - 0"
P294' - 8"
P294' - 8"
P294' - 8"
P294' - 8"
P2
84' - 7" 14' - 3 1/8" 51' - 0 3/8" 39' - 4" 6' - 8"
EXISTING BUILDING TO REMAIN
94' - 8"
P2
94' - 8"
P2
94' - 8"
P194' - 8"
P1
PRE-MANUFACTURED CANOPY ABOVE
FOUNDATION DESIGN BY CANOPY SUPPLIER
SEE ARCHITECTURAL SITE PLANS/DETAILS
PRE-ENGINEERED CANOPY
ABOVE DESIGNED BY OTHERS
94' - 0"
P1
94' - 0"
P1
2
S4.2
8' -
2 1
/8"
9' -
11
3/4"4 3/
8"4
3/8"
4 3/8"
VOLLEYBALL POST INSERT
SEE ARCH FOR LOCATIONS
SEE TYP24/ S3.1 15
S3.2
15
S3.2
SEE FOR
THICKENED SLAB
BELOW NON-LOAD
BEARING CMU
WALLS TYP
8/ S3.1
ST
EP
BO
GR
BM
SE
E
TY
P13
/ S3.
1
23
S3.2
TYP AT
CANTILEVER GR BM
2
S3.3
22
S3.2
22
S3.2
22
S3.2
STEP BO GR BM
SEE SIM13/ S3.1
7 3/8"
6 3/
8"
6 3/
8"
20
S3.2
20
S3.2
14
S3.3
24
S3.2
24
S3.2
20
S3.2
5 3/
8"
20
S3.2
5 3/
8"
20
S3.2
SIM
1
S3.3
3
S3.3
4
S3.3
20
S3.2
5
S3.3
6
S3.3
AT MOP
SINK
RECESS SLAB
PER
AND SLOPE TO
DRAIN TYP AT
SHOWERS
15/ S3.1
7
S3.3
7
S3.3
7
S3.3
7
S3.3
7
S3.3
22
S3.2
10
S3.3
5 3/8"
9
S3.2
AT
DOORWAY
AT
DOORWAY
AT
DOORWAY
13
S3.3
8
S3.3
TOC 97' - 4"
8' -
8"
1' -
4"
8"10
' - 0
"
PRE-ENGINEERED
CANOPY ABOVE
DESIGNED BY OTHERS
PRE-ENGINEERED
CANOPY ABOVE
DESIGNED BY OTHERS
PRE-ENGINEERED
CANOPY ABOVE
DESIGNED BY OTHERS
6
S3.2
SAWED JOINTS
PER GN TYP
12
S3.3
STEP BL ELEV
SEE ARCH
SAWED JOINTS
PER GN TYP
PRE-ENGINEERED
CANOPY ABOVE
DESIGNED BY OTHERS
4' - 6"
102'
- 1
0 1/
4"
3' -
0"
1' -
0"
4' - 8"
CJ
GR
OU
T S
OLI
D
4' -
11
5/8"
4' - 0"CJ
2' - 0"
2' - 0"
CJ CJ
4' -
0"
CJSIM
TOC 97' - 4"
16
S3.3
TYP
AT
DISPLAY CASE
16
S3.3
AT
DISPLAY CASE
PLAN NOTES: GROUND FLOOR & FOUNDATION
1. FINISH FLOOR ELEVATION IS RELATIVE TO A PROJECT
DATUM ELEVATION. REFER TO GENERAL NOTES.
2. TOP OF CONCRETE SLAB IS FINISH FLOOR UNLESS
INDICATED OTHERWISE.
3. TOP OF PIER ELEVATION RELATIVE TO PROJECT DATUM
100'-0" IS SHOWN ON PLAN.
4. SHEET INDEX:
GENERAL NOTES S1.1
STATEMENT OF SPECIAL INSPECTIONS S1.2
TYPICAL CONCRETE DETAILS S3.1-S3.2
DRILLED PIER SCHEDULE S3.1
TYPICAL CMU DETAILS S4.1
MASONRY WALL SCHEDULE S4.1
TYPICAL STEEL DETAILS S5.1-S5.2
COLUMN SCHEDULE S5.1
5. SEE FOR STORAGE BUILDING FOUNDATION PLAN.21/ S3.3
L.A. FUESS PARTNERS, INC.Structural Engineers3333 Lee Parkway, Suite 300 • Dallas, TX 75219214.871.7010 • www.lafp.com
Sheet No.Job No.
Drawn By:
Date:
Pro
ject
:
Copyright © 2018, Huckabee & Associates, Inc.
PACKAGE #1
LAFP PROJECT NO. 18067 FIRM REG. NO. F-537
AU
BR
EY
MID
DLE
SC
HO
OL
AD
DIT
ION
FO
RA
UB
RE
Y I.
S.D
.A
UB
RE
Y, T
EX
AS
C:\
Tem
p\1
780-
02-0
1 A
UB
RE
Y IN
TE
RM
ED
IAT
E_S
TR
UC
T_a
mcs
wee
ney
.rvt
9/11
/201
8 3:
42:5
6 P
M
LAFP
S2.1
FOUNDATION & GROUND
FLOOR PLAN
8/27/18
1780-02-01
1/8" = 1'-0"
1 FOUNDATION & GROUND FLOOR PLAN - ADDITION
1
1
1
Rev
isio
n /
Dat
e
19
/12
/18
AD
DE
ND
UM
1
![Page 6: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/6.jpg)
1
1
3
3
5
5
6
6
A A
C
D
G
I
1' -
4"
2' -
9"
TY
P
6"
W12
x19
W12
x19
26K622K5
22K5
22K5
22K5
22K5 SP
22K5 SP
22K5
22K5
22K5 SP
22K5 SP
22K5
22K5
22K5
26K6
26K6
26K6
26K6
26K6
26K6
26K6
26K6
26K6
26K6
26K6
26K6
30K10
30K10
30K10
30K10
30K10
30K10
30K10
30K10
30K10
30K10
12K1
12K1
PRE-ENGINEERED CANOPY
BELOW DESIGNED BY OTHERS
B.1
4.1
4.1
TOS 114' - 3 5/8"
TOS 112' - 11 1/2"
TOS 112' - 0"
TOS 112' - 0"
TOS 114' - 0"
5
S5.3
5
S5.36
S5.3
6
S5.3
3' -
3"
6' -
0"
6' -
0"
6' -
0"
6' -
0"
6' -
0"
6' -
0"
6' -
0"
6' -
0"
6' -
0"
6' -
0"
6' -
0"
6' -
0"
6' -
0"
2' -
9 3
/8"
22K5 26K6
15
S5.3
21
S4.1
7
S5.3
11
S5.3
PRE-ENGINEERED CANOPY
DESIGNED BY OTHERS
PRE-ENGINEERED CANOPY
DESIGNED BY OTHERS
22
S4.1
22
S4.1
1
S4.2
RTU APPROX
WT = 1600 LB
RTU
APPROX WT
= 1600 LB
SEE FOR
RTU CURB SUPPORT
TYPICAL
6/ S5.2
84' - 7" 14' - 0" 51' - 3 1/2" 46' - 0"
62' -
8"
23' -
4"
11' -
8"
5' -
2 1
/4"
117'
- 1
1"
PRE-ENGINEERED CANOPY
DESIGNED BY OTHERS
TOS 114' - 3 5/8"
TOS 114' - 0 1/8"
2
S2.2
W12x19
W12x19
W12
x19
12
S5.3
8
S5.3
84' - 7" 14' - 0" 51' - 3 1/2" 46' - 0"
EXISTING BUILDING TO REMAIN
2
S5.3
3
S5.3
4' -
0"
3' -
10
1/4"
W12x19
14
S5.3
PRE-ENGINEERED
CANOPY DESIGNED BY
OTHERS
18
S5.3
WA
LL E
DG
E
GR
OU
T C
ELL
S S
OLI
DU
PT
O 4
' - 0
" F
RO
M
PRE-MANUFACTURED CANOPY
DESIGNED BY OTHERS
SEE ARCHITECTURAL SITE
PLANS/DETAILS
2
S4.2
16
S5.3
W10x12 HIGHTOS 114' - 6"
W10x12 LOWTOS 108' - 6"
19
S5.3
TYP14/ S4.1DECK MARK RA
CONN TYPE 'II'
DECK MARK RA
CONN TYPE 'I'
TY
P
6"
ROOF SCUTTLE
SEE 8/ S5.2
CJ
CJ
CJ
CJ CJ
34' - 8"1' - 0"
20
S5.3
20
S5.3
22
S5.3AT OH
DOOR
PLAN NOTES: ROOF FRAMING
1. TOP OF NEW ROOF STRUCTURE IS SLOPED FOR DRAINAGE. SEE TOP OF STEEL ELEVATIONS
NOTED ON THE FRAMING PLANS. SLOPES SHALL BE UNIFORM BETWEEN COLUMN CENTERLINES
UNLESS SHOWN OTHERWISE.
2. UNLESS NOTED OTHERWISE, STEEL JOISTS/BEAMS SHALL BE CENTERED AND EQUALLY SPACED
BETWEEN COLUMN CENTERLINES.
3. SEE SHEET S1.2 FOR COMPONENT & CLADDING WIND PRESSURES, INCLUDING JOIST NET
UPLIFT DESIGN REQUIREMENTS.
4. JOISTS SUPPORTING MECHANICAL EQUIPMENT SHALL BE DESIGNED FOR TYPICAL ROOF LOADING
SHOWN ON PLANS PLUS A CONCENTRATED LOAD OF 60% OF INDICATED EQUIPMENT WEIGHT
PLACED AT ANY PANEL POINT.
5. SEE OVERALL PLAN AND GENERAL NOTES FOR ROOF DECK TYPE AND DECK CONNECTION.
6. BEAM-COLUMN CONNECTIONS FOR BEAMS ANNOTATED WITH "F=XX KIPS" ARE TO BE DESIGNED
TO TRANSFER THE HORIZONTAL LOAD SHOWN ON PLAN. CONNECTION DESIGNS SHALL BE BY A
LICENSED PROFESSIONAL ENGINEER WORKING FOR THE FABRICATOR AND REGISTERED IN THE
STATE OF THE PROJECT. ALL PROVIDED FORCES ARE FACTORED FOR "LRFD" DESIGN
PROCEDURES.
7. SHEET INDEX:
GENERAL NOTES S1.1
STATEMENT OF SPECIAL INSPECTIONS S1.2
TYPICAL CMU DETAILS S4.1
MASONRY WALL SCHEDULE S4.1
TYPICAL STEEL DETAILS S5.1-S5.2
COLUMN SCHEDULE S5.1
5
A
B
C
B.1
4.1
HSS8 x 6 x 3/8TOS 108' - 9"
HS
S8
x 6
x 3/
8T
OS
108
' - 9
"
2
S5.3
3
S5.3
PRE-ENGINEERED CANOPY
DESIGNED BY OTHERS
11' -
8"
1' -
0"
4' -
2 1
/4"
14' - 0"
L.A. FUESS PARTNERS, INC.Structural Engineers3333 Lee Parkway, Suite 300 • Dallas, TX 75219214.871.7010 • www.lafp.com
Sheet No.Job No.
Drawn By:
Date:
Pro
ject
:
Copyright © 2018, Huckabee & Associates, Inc.
PACKAGE #1
LAFP PROJECT NO. 18067 FIRM REG. NO. F-537
AU
BR
EY
MID
DLE
SC
HO
OL
AD
DIT
ION
FO
RA
UB
RE
Y I.
S.D
.A
UB
RE
Y, T
EX
AS
C:\
Tem
p\1
780-
02-0
1 A
UB
RE
Y IN
TE
RM
ED
IAT
E_S
TR
UC
T_a
mcs
wee
ney
.rvt
9/11
/201
8 3:
42:5
8 P
M
LAFP
S2.2
LOW ROOF FRAMING PLAN
8/27/18
1780-02-01
1/8" = 1'-0"
1 LOW ROOF FRAMING PLAN
1/8" = 1'-0"
2 CANOPY FRAMING PARTIAL PLAN
1
1
1
Rev
isio
n /
Dat
e
19
/12
/18
AD
DE
ND
UM
1
![Page 7: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/7.jpg)
5
5
6
6
A
I
9' -
4"
12' -
0"
12' -
0"
12' -
0"
12' -
0"
12' -
0"
12' -
0"
12' -
0"
12' -
0"
9' -
3"
60DLH16 SP
60DLH16 SP
60DLH16 SP
60DLH16 SP
60DLH16 SP
60DLH16 SP
60DLH16 SP
60DLH16 SP
60DLH16 SP
TOS 131' - 8 1/4"
TOS 131' - 8 1/4"
117'
- 1
1"
84' - 7"
10
S5.3
10
S5.3
9
S5.3
9
S5.3
1
S4.2
84' - 7"
EXISTING BUILDING TO REMAIN
TOS 130' - 0"
TOS 130' - 0"
RT
U A
PP
RO
X
WT
= 2
900
LB
SEE FOR
RTU CURB SUPPORT
TYPICAL
6/ S5.2
RT
U A
PP
RO
X
WT
= 2
900
LB
9/ S5.2
DESIGN JOISTS FOR ADDITIONAL CONCENTRATED LOAD OF 1.5 KIPS
DUE TO BASKETBALL GOAL FRAMING AT CONCENTRATED POINTS
ALONG JOIST BOTTOM CHORD. WHERE GOAL FRAMING DOES NOT
CONNECT TO JOIST BOTTOM CHORD PANEL POINT, SEE
(6 GOAL LOCATIONS TOTAL)
JOIST MFR PROVIDE CAMBER FOR INITIAL CONSTRUCTION DEAD LOAD
OF 8 PSF PLUS JOIST WEIGHT
4/ S5.2
ERECTOR NOTE:
SEE DECK EDGE ANGLE ELEVATION
AFTER JOISTS ARE ERECTED AND
SET TO SELF-WEIGHT DEFLECTED
SHAPE OF ADJACENT JOIST, TYP
EACH SIDE
DECK MARK RB
CONN TYPE 'III'
CJ
PLAN NOTES: ROOF FRAMING
1. TOP OF NEW ROOF STRUCTURE IS SLOPED FOR DRAINAGE. SEE TOP OF STEEL ELEVATIONS
NOTED ON THE FRAMING PLANS. SLOPES SHALL BE UNIFORM BETWEEN COLUMN CENTERLINES
UNLESS SHOWN OTHERWISE.
2. UNLESS NOTED OTHERWISE, STEEL JOISTS/BEAMS SHALL BE CENTERED AND EQUALLY SPACED
BETWEEN COLUMN CENTERLINES.
3. SEE SHEET S1.2 FOR COMPONENT & CLADDING WIND PRESSURES, INCLUDING JOIST NET
UPLIFT DESIGN REQUIREMENTS.
4. JOISTS SUPPORTING MECHANICAL EQUIPMENT SHALL BE DESIGNED FOR TYPICAL ROOF LOADING
SHOWN ON PLANS PLUS A CONCENTRATED LOAD OF 60% OF INDICATED EQUIPMENT WEIGHT
PLACED AT ANY PANEL POINT.
5. SEE OVERALL PLAN AND GENERAL NOTES FOR ROOF DECK TYPE AND DECK CONNECTION.
6. BEAM-COLUMN CONNECTIONS FOR BEAMS ANNOTATED WITH "F=XX KIPS" ARE TO BE DESIGNED
TO TRANSFER THE HORIZONTAL LOAD SHOWN ON PLAN. CONNECTION DESIGNS SHALL BE BY A
LICENSED PROFESSIONAL ENGINEER WORKING FOR THE FABRICATOR AND REGISTERED IN THE
STATE OF THE PROJECT. ALL PROVIDED FORCES ARE FACTORED FOR "LRFD" DESIGN
PROCEDURES.
7. SHEET INDEX:
GENERAL NOTES S1.1
STATEMENT OF SPECIAL INSPECTIONS S1.2
TYPICAL CMU DETAILS S4.1
MASONRY WALL SCHEDULE S4.1
TYPICAL STEEL DETAILS S5.1-S5.2
COLUMN SCHEDULE S5.1 L.A. FUESS PARTNERS, INC.Structural Engineers3333 Lee Parkway, Suite 300 • Dallas, TX 75219214.871.7010 • www.lafp.com
Sheet No.Job No.
Drawn By:
Date:
Pro
ject
:
Copyright © 2018, Huckabee & Associates, Inc.
PACKAGE #1
LAFP PROJECT NO. 18067 FIRM REG. NO. F-537
AU
BR
EY
MID
DLE
SC
HO
OL
AD
DIT
ION
FO
RA
UB
RE
Y I.
S.D
.A
UB
RE
Y, T
EX
AS
C:\
Tem
p\1
780-
02-0
1 A
UB
RE
Y IN
TE
RM
ED
IAT
E_S
TR
UC
T_a
mcs
wee
ney
.rvt
9/11
/201
8 3:
42:5
9 P
M
LAFP
S2.3
HIGH ROOF FRAMING PLAN
8/27/18
1780-02-01
1/8" = 1'-0"
1 HIGH ROOF FRAMING PLAN
1 1
Rev
isio
n /
Dat
e
19
/12
/18
AD
DE
ND
UM
1
![Page 8: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/8.jpg)
21' - 3"
18' -
3"
9' -
1 1
/2"
9' -
1 1
/2"
10' - 7 1/2" 10' - 7 1/2"
10 1/2" 7' - 7" 4' - 4" 7' - 7" 10 1/2"
1' -
2 1
/2"
4' -
5"
7' -
0"
4' -
5"
1' -
2 1
/2" 22
S3.3
22
S3.3
22
S3.3
22
S3.3
23
S3.3
22
S3.3
18
S3.3
18
S3.3
SAW JOINTS
SEE GN
5' - 0" 11' - 3" 5' - 0"
4' -
7 1
/2"
9' -
0"
4' -
7 1
/2"
TO CONC EL
SEE PLAN
8"2'
- 8
"
8 3/8"
8" CMU WALL BELOW WINDOW
REINF W #5 AT 24" OC
DOWELS TO MATCH SIZE &
SPACING OF VERT WALL
REINF
CL GR BM
= CL PIER1' - 8"
TO PIER EL
SEE PLAN
SEE
FOR ADDL INFO4/ S3.2
BB-1 CONT
1' -
4"
1 1/2" 2"
1 1/
2"1/
2"
10"
2' -
0"
BUILDING WALL FRAMING
BY BLDG SUPPLIER
CL AB
FF EL
SEE PLAN
ANCHOR BOLTS BY
BLDG SUPPLIER
REINF W (2) #8 CONT BOTTOM
#4 U-BARS AT 8" OC
#4 (1-6/4-0) AT 12" OC
REINF SLAB W #3 AT
12" OC EW AT SLAB
MID-DEPTH
1 1/2" 7 5/8"
1 1/
2"1/
2"
FF EL
SEE PLAN
1/4"
CONCRETE EDGE
PROFILE AT OH DOOR
SEE
FOR ADDL INFO
22/ S3.3
2' -
0"
FF EL
SEE PLAN
REINF W (2) #8 CONT BOTTOM
#4 U-BARS AT 8" OC
REINF SLAB W #3 AT
12" OC EW AT SLAB
MID-DEPTH
5"
10"
1' - 6" TYP
CONTINUOUS VAPOR
RETARDER OVER PREPARED
SUBGRADE TYPICAL
PLAN NOTES: STORAGE BUILDING FOUNDATION
1. SEE CIVIL FOR FINISH FLOOR ELEVATION. FLOOR
SLAB TO BE LEVEL EXCEPT AS NOTED IN DETAILS.
2. STIFFENED SLAB FOUNDATION SHALL BE CONSTRUCTED
OVER PREPARED SUBGRADE AS DESCRIBED IN THE
GEOTECHNICAL REPORT.
3. FOUNDATION DESIGN IS BASED ON MUELLER BACKYARD
BUILDING KITS: SLAB MOUNTED 18x21 BACKYARD
BUILDING.
4. FOUNDATION DESIGN IS BASED ON THE FOLLOWING
LOADS:
ROOF DEAD LOAD: 10 PSF
ROOF LIVE LOAD: 20 PSF
WALL DEAD LOAD: 100 PLF
FLOOR LIVE LOAD: 100 PSF
5. BUILDING STRUCTURE AND ATTACHMENT TO FOUNDATION
IS BY BUILDING SUPPLIER. ATTACHMENTS SHOWN ARE
AS INDICATED IN PRODUCT LITERATURE AND ARE
SHOWN FOR CONVENIENCE ONLY. ACTUAL CONNECTION
DETAILS MUST BE CONFIRMED BY THE GENERAL
CONTRACTOR BASED ON THE ACTUAL UNIT PURCHASED.
3' - 0"
2' -
0"
8"
D4 AT 18" OC 5" SLAB ON GRADE
SEE GN
REINF
(6) #8 CONT T&B
#4 TIES AT 10" OC
TO CONC EL
SEE PLAN
CL GR BM = CL PIER
TO PIER EL
SEE PLAN
2' - 4"
2' -
0"
8"
TO CONC EL
SEE PLAN
CL GR BM = CL PIER
TO PIER EL
SEE PLAN
SEEPLAN
1' - 1"
SEE
FOR ADDL INFO
24/ S3.2
REINF
(5) #8 CONT T&B
#4 TIES AT 10" OC
2' - 4"
2' -
0"
8"
D4 AT 18" OC 5" SLAB ON GRADE
SEE GN
REINF
(5) #8 CONT T&B
#4 TIES AT 10" OC
TO CONC EL
SEE PLAN
CL GR BM
= CL PIER
TO PIER EL
SEE PLAN
3' - 0"
2' -
0"
8"
D4 AT 18" OC 5" SLAB ON GRADE
SEE GN
REINF
(6) #8 CONT T&B
#4 TIES AT 10" OC
TO CONC EL
SEE PLAN
CL GR BM = CL PIER
TO PIER EL
SEE PLAN
8" LOAD BEARING
CMU WALL SEE GN
FOR WALL REINF &
DOWELSSEE
PLAN
1' - 6"
2' -
0"
8"
TO CONC EL
SEE PLAN
CL GR BM = CL PIER
TO PIER EL
SEE PLAN
6"
SEE
FOR ADDL INFO20/ S3.2
8"
#5 CONT AT CURB
SEE ARCH FOR EXTENTS
CMU "SOAP" TO
MATCH WALL
ABOVE SEE ARCH
1' - 2"
2' -
0"
8"
D4 AT 18" OC
ALTERNATE
DIRECTION
5" SLAB ON GRADE
SEE GN
REINF
(3) #8 CONT T&B
#4 TIES AT 10" OC
TO CONC EL
SEE PLAN
CL GR BM = CL PIER
TO PIER EL
SEE PLAN
NON-LOAD BEARING
CMU WALL SEE ARCH
DOOR SEE ARCH
SEE PLAN
SLOPE
1' - 6"
GR BM REINF
SEE 20/ S3.2
8"2'
- 0
"
D4 AT 18" OC
1/2" COMPR
JOINT FILLER
SITE PAVING
SEE CIVIL
2' -
0"
5" MIN SOG
#3 AT 12" OC EW
CENTER IN SLAB
1' - 8"
SEE CIVIL FOR
TO PAVING EL
#3 (2-0) AT 18" OC
CL GR BM = CL PIER
REINF:
(4) #8 T&B
#4 STIRRUPS AT 10" OC
2' - 0"
2' -
0"
8"
D4 AT 18" OC
ALTERNATE
DIRECTION
5" SLAB ON GRADE
SEE GN
REINF
(6) #8 CONT T&B
#4 TIES AT 10" OC
TO CONC EL
SEE PLAN
CL GR BM = CL PIER
TO PIER EL
SEE PLAN
TO CONC EL
SEE PLAN
D4 AT 18" OC
ALTERNATE DIRECTIONS
8"
2'-8
" A
T S
TE
P D
OW
N
2' -
0"
12" CMU WALL
SEE GN
REINF:
(6) #8 T&B
#4 STIRRUPS AT 10" OC
CL GR BM
= CL PIER
5" SLAB ON GRADE
SEE GN
FF EL
SEE ARCH
TO CONC EL
SEE PLAN
2 9/
16"
5" SLAB ON GRADE
SEE GN
TO PIER EL
SEE PLAN
2' - 0"
FF EL
SEE ARCH
TO CONC EL
SEE PLAN
D4 AT 18" OC
3' -
0"
2' -
8"
12" CMU WALL
SEE GN
CL GR BM
= CL PIER
5" SLAB ON GRADE
SEE GN
TO PIER EL
SEE PLAN
SEE
FOR ADDL INF0
8 3/8" 11 5/8"
3/ S3.2
1' -
4"
1-1/2"x3-1/2" SHEAR
KEY W WATERSTOP
PER ARCH
CJ AT CONTR OPTION
2' - 0"
REINF:
(5) #8 T&B
#4 STIRRUPS AT 10" OC
GROUT CAVITY SOLID
BELOW GRADE
1/2" COMPR
JOINT FILLER
SITE PAVING
SEE CIVIL
# VERT AT 12" OC
EACH WAY EACH FACE
FRENCH DRAIN
REF MEP/CIVIL
FF EL
SEE ARCH
TO CONC EL
SEE PLAN3' -
0"
2' -
8"
12" CMU WALL
SEE GN
CL GR BM
= CL PIER
TO PIER EL
SEE PLAN
SEE
FOR ADDL INF0
8 3/8" 11 5/8"
11/ S3.3
2' - 0"
BL EL
SEE ARCH
#3 U-BARS AT 12" OC
W #4 CONT AT 12" OC
MAX
1' - 6"
2' -
0"
8"
TO CONC EL
SEE PLAN
CL GR BM = CL PIER
TO PIER EL
SEE PLAN
SEEPLAN
SEE
FOR ADDL INFO
20/ S3.2
SLOPE
MASONRY VENEER
W LEDGE LOWER
THAN FF REF ARCH
TO CONC EL
SEE PLAN
12" CMU WALL
SEE GN
CL GR BM
= CL PIER
FF EL
SEE ARCH
TO CONC EL
SEE PLAN
2 9/
16"
TO PIER EL
SEE PLAN
SEE
FOR ADDL INFO6/ S3.2
8" CMU PARTITION
WALL SEE ARCH
SCHEDULED LINTEL
(2) #5 CONT
(1) #5 CONT
DISPLAY CASE
SEE ARCH
NON-STRUCTURAL
CMU INFILL SEE ARCH
L.A. FUESS PARTNERS, INC.Structural Engineers3333 Lee Parkway, Suite 300 • Dallas, TX 75219214.871.7010 • www.lafp.com
Sheet No.Job No.
Drawn By:
Date:
Pro
ject
:
Copyright © 2018, Huckabee & Associates, Inc.
PACKAGE #1
LAFP PROJECT NO. 18067 FIRM REG. NO. F-537
AU
BR
EY
MID
DLE
SC
HO
OL
AD
DIT
ION
FO
RA
UB
RE
Y I.
S.D
.A
UB
RE
Y, T
EX
AS
C:\
Tem
p\1
780-
02-0
1 A
UB
RE
Y IN
TE
RM
ED
IAT
E_S
TR
UC
T_a
mcs
wee
ney
.rvt
9/11
/201
8 3:
43:0
1 P
M
LAFP
S3.3
CONCRETE DETAILS
8/27/18
1780-02-01
1/8" = 1'-0"
21 FOUNDATION PLAN - STORAGE BUILDING -- ADD ALTERNATE 3/4" = 1'-0"
1
3/4" = 1'-0"
22
1 1/2" = 1'-0"
23
3/4" = 1'-0"
18 3/4" = 1'-0"
2
3/4" = 1'-0"
3
3/4" = 1'-0"
4
3/4" = 1'-0"
5
3/4" = 1'-0"
6
3/4" = 1'-0"
7
3/4" = 1'-0"
13
3/4" = 1'-0"
10
3/4" = 1'-0"
8
3/4" = 1'-0"
11
3/4" = 1'-0"
12
3/4" = 1'-0"
14
3/4" = 1'-0"
16 1
Rev
isio
n /
Dat
e
19
/12
/18
AD
DE
ND
UM
1
![Page 9: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/9.jpg)
C 5x6.7 AT
4 FT OC MAX
INFILL W CFMF
SEE ARCH
C 5x6.7 AT
4 FT OC MAX
INFILL W CFMF
SEE ARCH
L 3x3x1/4 BRACE TO
ADJACENT BEAM TOP
FLANGE AT EA C5
L 4x4x1/4 CONT
1/4" STIFF PL AT EA
C5 AND BRACE CONN
CANOPY SUPPORT TUBE
SEE PLAN
SEE ARCH 3"
PRE-ENGINEERED CANOPY
ATTACHMENT TO STRUCTURE
BY CANOPY SUPPLIER
1" 3 3/8"
TOS EL
SEE PLAN
L 4x4x1/4 WELDED CLIP
ANGLE AT EACH VERT C5
TOS EL
SEE PLAN
1 5/8"
L 3x3x1/4 BRACE TO
ADJACENT BEAM TOP
FLANGE AT EA C5
CANOPY SUPPORT TUBE
SEE PLAN
SEE ARCH 3"
PRE-ENGINEERED CANOPY
ATTACHMENT TO STRUCTURE
BY CANOPY SUPPLIER
1" 3 3/8"
TOS EL
SEE PLAN
L 6x4x5/16 CONT
L 4x4x1/4 WELDED CLIP
ANGLE AT EACH VERT C5
SEE
FOR ADDL INFO2/ S5.3
TOS EL
SEE PLAN
BB-1 AT TOP OF WALL
BB-1 CONT BELOW
JOIST BEARING
SEE
L 5x5x5/16 CONT W 1/2" DIA
ADHESIVE OR SCREW
ANCHOR AT 32 IN GROUTED
CELL (4 1/2" EMBED)
CONNECTION PER METAL
DECK CONN SCHED
15/ S4.1
8' CMU WALL
SEE GN
BB-1 AT TOP OF WALL
BB-1 CONT BELOW
DECK BEARING
STEP AS REQD
L 5x5x5/16 CONT W 1/2" DIA
ADHESIVE OR SCREW
ANCHOR AT 32 IN GROUTED
CELL (4 1/2" EMBED)
CONNECTION PER METAL
DECK CONN SCHED
4" M
IN
GR
OU
T S
OLI
D
8' CMU WALL
SEE GN
SET ANGLE ELEVATION AFTER JOISTS
ARE ERECTED AND SET TO SELF-WEIGHT
DEFLECTED SHAPE OF ADJACENT JOIST
8' CMU WALL
SEE GN
EXISTING
EXTERIOR
BUILDING WALL
TO REMAIN
1" EJSEE
FOR ADDL INFO
6/ S5.3
8' CMU WALL
SEE GN
EXISTING
EXTERIOR
BUILDING WALL
TO REMAIN
1" EJSEE
FOR ADDL INFO
6/ S5.3
15/ S4.1JOIST BEARING
SEE
BB-1 CONT BELOW
JOIST BEARING
GR
OU
T S
OLI
D
4" M
IN
BB-2 AT TOP OF WALL
BB-2 CONT BELOW
DECK BEARING
SEE
L 5x5x5/16 CONT W 1/2" DIA
ADHESIVE OR SCREW
ANCHOR AT 32 IN GROUTED
CELL (4 1/2" EMBED)
CONNECTION PER METAL
DECK CONN SCHED
15/ S4.1
12" CMU WALL
SEE GN
BB-2 AT TOP OF WALL
BB-2 CONT BELOW
DECK BEARING
STEP AS REQD
L 5x5x5/16 CONT W 1/2" DIA
ADHESIVE OR SCREW
ANCHOR AT 32 IN GROUTED
CELL (4 1/2" EMBED)
CONNECTION PER METAL
DECK CONN SCHED
4" M
IN
12" CMU WALL
SEE GN
SET ANGLE ELEVATION AFTER
JOISTS ARE ERECTED AND
SET TO SELF-WEIGHT
DEFLECTED SHAPE OF
ADJACENT JOIST
GR
OU
T S
OLI
D
BB-2 CONT BELOW
DECK BEARING
SEE
SEE
AT WF BM CONN
SEE SIM
15/ S4.1
12" CMU WALL
SEE GN
L 5x5 AND EMBED
PER
AT 2'-0" OC
20/ S4.1
9/ S5.3
BL EL
SEE ARCH
13/ S4.1
EXISTING CANOPY
TO BE REMOVED
EXISTING BUILDING TO REMAIN
2" EJ
FV
11 13/16"
SEE
FOR ADDL INFO
10/ S5.3
BB-2 CONT BOTTOM GROUT
3 COURSES SOLID FULL
LENGTH
(2) #5 T&B
CONT
L 5x5x5/16 CONT
(2) #5 W/
STD HOOK
EA END
BB-2 AT TOP
OF WALL
GR
OU
T S
OLI
D
8" CMU WALL
SEE GN
SEE .18/ S4.1
SCHEDULED
LINTEL
SEE
FOR ADDL INFO5/ S5.3
L 5x5 AND EMBED
PER
AT 4'-0" OC MAX23/ S4.1
GR
OU
T S
OLI
D
GR
OU
T S
OLI
D
(2) #5 T&B W/
STD HOOK
EA END
8' CMU WALL
SEE GN
SEE SIM
FOR CANOPY
ATTACHMENT
21/ S4.1
SEE
FOR ADDL INFO6/ S5.3
GR
OU
T S
OLI
D
BB-1
(2) #5 W/ STD
HOOK EA END
WELD TUBE TO DECK AS TYPICAL
SUPPORT CONDITION SEE
GENERAL NOTES
HSS 2 1/2x2 1/2x1/4 CONT
E1 @ 32" O.C.
2 #5 CONT
CUT BLOCK AS REQUIRED
BB-1 CONT
GR
OU
T S
OLI
D
2 #5 T&B W/
STD HOOK
EA END
EXISTING BUILDING
TO REMAIN
20/ S4.1
BOND BM REINF
PER DETAIL
STRUCTURED BRICK
LINTEL BED AT EA
END & AT 24" OC
SEE
BL EL
SEE ARCH
EJ
2" M
IN
MASONRY VENEER
SEE ARCH
BEAM
SEE PLAN
EMBED PL 3/8"x12x12
W (4) 1/2" DIA (0-5) HSA
AT EA BEAM CONN
BB-1 CONT
GR
OU
T S
OLI
D
TYP 1"RET T&B
SEE
FOR ADDL INFO11/ S5.3
BEAM
SEE PLAN
EMBED PL 3/8"x12x12
W (4) 1/2" DIA (0-5) HSA
AT EA BEAM CONN LINTEL SEE
WALL ELEVATIONLINTEL SEE
WALL ELEVATION
TOP OF MASONRY
SEE ARCH
LINTEL EL
SEE ARCH
8" CMU WALL
SEE GN
GR
OU
T S
OLI
D
GR
OU
T S
OLI
D
(2) #5 T&B CONT
w/ STD HOOK
EA END
CONT BB-2
BB-1 CONT BELOW
JOIST BEARING
SEE 15/ S4.1
8' CMU WALL
SEE GN
CUT BLOCK
AS REQUIRED
OFFSET JOIST SEATS
AS NEEDED TO ACHIEVE
REQUIRED BEARING
STAND-OFF BRICK
LINTEL AT CMU
SEE
AT EA END OF OPNG
AND AT 4 FT OC MAX
CMU LINTEL
SEE SCHEDULE
SEE
FOR ADDL INFO
23/ S4.1
5/ S5.3
ROLL-UP OH DOOR
SEE ARCH
L.A. FUESS PARTNERS, INC.Structural Engineers3333 Lee Parkway, Suite 300 • Dallas, TX 75219214.871.7010 • www.lafp.com
Sheet No.Job No.
Drawn By:
Date:
Pro
ject
:
Copyright © 2018, Huckabee & Associates, Inc.
PACKAGE #1
LAFP PROJECT NO. 18067 FIRM REG. NO. F-537
AU
BR
EY
MID
DLE
SC
HO
OL
AD
DIT
ION
FO
RA
UB
RE
Y I.
S.D
.A
UB
RE
Y, T
EX
AS
C:\
Tem
p\1
780-
02-0
1 A
UB
RE
Y IN
TE
RM
ED
IAT
E_S
TR
UC
T_a
mcs
wee
ney
.rvt
9/11
/201
8 3:
43:0
2 P
M
LAFP
S5.3
ELEVATED FRAMING
DETAILS
8/27/18
1780-02-01
3/4" = 1'-0"
2
3/4" = 1'-0"
3
3/4" = 1'-0"
5
3/4" = 1'-0"
6
3/4" = 1'-0"
7
3/4" = 1'-0"
8
3/4" = 1'-0"
9
3/4" = 1'-0"
10
3/4" = 1'-0"
11
3/4" = 1'-0"
12
3/4" = 1'-0"
14
3/4" = 1'-0"
15
3/4" = 1'-0"
18
3/4" = 1'-0"
16
3/4" = 1'-0"
19
3/4" = 1'-0"
20
3/4" = 1'-0"
22
1
1
1
Rev
isio
n /
Dat
e
19
/12
/18
AD
DE
ND
UM
1
![Page 10: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/10.jpg)
Project Name: Aubrey MS Addition
Client: Aubrey ISD
Aubrey, Texas
Project Number: 1780-02-01
Architectural Items For
Addendum No. #
Page 1 of 1
ARCHITECTURAL ITEMS FOR ADDENDUM NO. 1 NOTICE TO PROPOSERS:
A. This Addendum shall be considered part of the contract documents for the above-mentioned project as though it had been issued at the same time and incorporated
integrally therewith. Where provisions of the following supplementary data differ from those of the original contract documents, this Addendum shall govern and take
precedence.
B. Proposers are hereby notified that they shall make any necessary adjustments in their estimate on account of this Addendum. It will be construed that each Proposer’s
proposal is submitted with full knowledge of all modifications and supplemental data specified therein. Acknowledge receipt of this addendum in the space provided
on the proposal form. Failure to do so may subject Proposer to disqualification.
REFERENCE IS MADE TO THE DRAWINGS AND THE PROJECT MANUAL AS NOTED:
PROJECT MANUAL:
AD No 1, Arch. Item 1: To the Project Manual, Sections as listed below, Part 2 – Products;
Products listed herein are considered acceptable for conformance with the design concept of the project and general compliance with the information given in the contract
documents. The manufacturer, supplier and installer are responsible for meeting all requirements given in the contract documents unless specifically noted in the written
approval.
1) To Section 07 2200, “THERMAL INSULATION,”
Add ‘ISO 95+ GL Insulation’ as manufactured by Firestone Building Products
2) To Section 07 5100, “BUILT-UP BITUMINOUS ROOFING,”
Add ‘SBS Premium Torch’ as manufactured by Firestone Building Products
Add ‘Ply VI’ as manufactured by Firestone Building Products
DRAWINGS:
AD No 1, Arch. Item 2: To the Drawings, Sheet A3.2, “DOOR AND WINDOW DETAILS,”
1) DETAIL 9/A3.2: REVISED EMBED PLATE NOTE
AD No 1, Arch. Item 3: To the Drawings, Sheet A6.1, “WALL SECTIONS,”
1) DETAIL 5/A6.1: REVISED NOTE TO READ ‘8” CMU’
AD No 1, Arch. Item 4: To the Drawings, Sheet A6.2, “WALL SECTIONS,”
1) DETAIL 2/A6.2: REVISED BRACING LOCATION
AD No 1, Arch. Item 5: To the Drawings, Sheet A6.6, “WALL SECTION DETAILS,”
1) DETAIL 5/A6.6: CLEANED UP NOTES FOR CLARIFICATION
2) DETAIL 7/A6.6: UPDATED DETAIL TO COORDINATE WITH STRUCTURAL (SHOW CFMF RUNNER IN LIEU OF CHANNEL)
AD No 1, Arch. Item 6: To the Drawings, Sheet A9.1, “TYPICAL DETAILS,”
1) DETAIL 8/A9.1: REVISED PERTAINING TO JOINT SPACING
END OF ARCHITECTURAL ADDENDUM
���
09/13/2018
![Page 11: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/11.jpg)
ASPHALT MASTIC TERMINATOR
CONCRETE MASONRY UNIT
(CMU) - VERIFY DIM. PER PLAN
CONT. SEALANT EA. SIDE
H.M. FRAME AS SCHED. FILL
SOLID W/ MORTAR.
WRAP STL. LINEL W/ METAL
FLASHING. FORM 1/2" DRIP
EDGE AS DETAILED.
WEEPS @ 2'-0" O.C. TYP. PROVIDE 2 WEEPS
PER OPENING MINIMUM.
MASONRY VENEER AT HEAD TO BE
RUNNING BOND, SOLDIER, OR AS NOTED
ON ELEV. AND DTLS.
MORTAR DROPPING COLLECTION
SYSTEM
SELF-ADH. FLASHING. FORM END
DAMS.
WEATHER BARRIER
TYP. EXT. MAS. DOOR HEAD DETAIL
H.M. FRAME AS SCHED. - FILL
SOLID W/MORTAR
JAMB ANCHOR (3 PER JAMB)
CONT. SEALANT EA. SIDE
REF. STRUCT. FOR REINF.
CONCRETE MASONRY UNIT
(CMU) - VERIFY DIM. PER PLAN
CONT. SEALANT - EA. SIDE
FILL COLLAR JOINT W/ MORTAR
FACE BRICK OR CMU - REF.
FLOOR PLAN
WEATHER BARRIER
CONT. INSUL. BD.
CONT. INSUL. BD.
TYP. EXT. MAS. DOOR JAMB DETAIL
TYPICAL EXTERIOR MASONRY DETAILS (T.E.M.) SCALE 1-1/2" = 1'-0
UNLESS NOTED OTHERWISE ALL H.M. FRAMES IN EXTERIOR MASONRY SHALL
CONFORM TO THESE DETAILS
TERMINATION BAR
DRIP FLASHING DETAIL
3" = 1'-0"
SELF-ADH. FLASHING
CONT. SEALANT
PLA
TE
TH
ICK
NE
SS
1/2"
2"
1/2"
1/8"
1/2"
8 3/4"
2" T
YP @
WDW
S &
TRAN
SOM
S
4" T
YP @
DRS
BENT PLATE LINTEL
BOLTED TO CMU WALL-
REF STRUCT
CMU LINTEL AS SCHED - REF
STRUCT
CONT STL GUSSET PLATE
CONT BENT STL ANGLE 2
1/2"x4 1/2" 12 GA GALV @
DOOR ONLY
FLUID APPLIED FLASHING
FLUID APPLIED FLASHING
UNLESS NOTED OTHERWISE ALL H.M. FRAMES IN INTERIOR MASONRY SHALL
CONFORM TO THESE DETAILS
LINTEL AS SCHED. -
REF. STRUCT.
CONCRETE MASONRY
UNIT (CMU) - VERIFY DIM.
PER PLAN
CONT. SEALANT EACH
SIDE
H.M. FRAME AS SCHED.
FILL SOLID W/ GROUT
REF. STRUCT.
FOR REINF.
JAMB ANCHOR
(3 PER JAMB)
TYP. DOOR/WDW HEAD DETAIL TYP. DOOR/WDW JAMB DETAIL
CONT. SEALANT
EACH SIDE
REF. STRUCT. FOR
REINF.
TYP. DOOR/WDW SILL DETAIL
TYPICAL INTERIOR MASONRY DETAILS (T.I.M.) SCALE 1-1/2" = 1'-0
SNAP-IN OR WELD-IN
ANCHOR AT 3'-0" O.C.
BY H.M. MANUF. BED
EACH ANCHOR IN
GROUT
SNAP-IN OR WELD-IN
ANCHOR AT 3'-0" O.C. BY
H.M. MANUF. BED EACH
ANCHOR IN GROUT
CONT. SEALANT
EACH SIDE
REF. STRUCT. FOR
REINF.
SLOPE
WELD MTL. PLATE TO
FRAME. GRIND SMOOTH
FINISH TO CODE 104.
OFFICE KITCHEN
SIM. CONDITION
6 3/4" @ 6" CMU
8 3/4" @ 8" CMU
*HM FRAME MAX WIDTH 8 3/4" FOR 12" CMU OR
DOUBLE WYTHE, SET TO ONE SIDE
FLOOR FIN AS SCHED
F.F.
SEALANT EA. SIDE
SHIM AS REQ'D.
SLOPE @ EXT. ONLY
BACKER ROD
3/8"
1 1/
2"
HM SUB-SILL (.090) SET IN FULL BED
OF MASTIC. (AT EXTERIOR ONLY)
SCREW APPLIED STL. STOP
GLAZING AS SCHED.
EXPANSION ANCHOR @ 1'-4" O.C.
COUNTERSINK, FILL AND GRIND
SMOOTH AND FLUSH.
STL. CRUSH SLEEVE AT EACH
ANCHOR
H.M. FRAME AS SCHED.
EXTERIOR
1/2"
1/2"
MA
X.
1/2"
MA
X.
COMPRESSED FOAM ROD W/
CONT. BED OF SEALANT
TYP. FOR ALUM OR HOLLOW METAL
ALUMINUM THRESHOLD (SET IN
FULL BED OF MASTIC)
S.S. ANCHOR @ 8" O.C.
DOOR BOT. SEAL.
DOOR AS SCHED.
ALTERNATE THRESHOLD
THICK FLOOR FINISH ( Q.T.
TERRAZZO, WALK-OFF MAT
OR OTHER )
WHERE DIFFERENCE IN THICKNESS OF FLOOR FINISHES ON OPPOSITE
SIDES OF THE THRESHOLD EXCEEDS 1/4" PROVIDE HALF SADDLE.
UNLESS NOTED OTHERWISE ALL H.M. FRAMES IN INTERIOR MASONRY SHALL
CONFORM TO THESE DETAILS
LINTEL AS SCHED. -
REF. STRUCT.
CONCRETE MASONRY
UNIT (CMU) - VERIFY DIM.
PER PLAN
CONT SEALANT EA
SIDE
ALUM DOOR FRAME
REF. STRUCT.
FOR REINF.
PROVIDE 3
ANCHORS PER
JAMB MIN
TYP DOOR/WDW HEAD DETAIL TYP DOOR/WDW JAMB DETAIL
CONT. SEALANT
EACH SIDE
TYP DOOR/WDW SILL DETAIL
TYPICAL INTERIOR MASONRY ALUM DETAILS (T.I.M.A.) SCALE 1-1/2" = 1'-0
OFFICE
1"
WINDOW
CONDITION
EASE EDGE BOTH
SIDES
ALUM WINDOW
AS SCHED.
CORR
2" RIGID INSUL.
CMU VERIFY
DIM. PER PLAN.
METAL HOOD
PRE-FIN. MTL. CLOSURE PLATE
O.H. DOOR TRACK (BEYOND)
BY MFR.STL. LINTEL - REF. STRUCT.
FILL SOLID W/ GROUT
3/8" THICK STL. BENT PLATE.
FINISH TO CODE 100.
WEEPS @ 2'-0" O.C. TYP.
PROVIDE 2 WEEPS PER OPENING
MINIMUM.
MASONRY VENEER AT HEAD
TO BE RUNNING BOND, SOLDIER,
OR AS NOTED ON ELEV. AND DTLS.
SELF-ADH. FLASHING W/
FORMED END DAMS- EXTEND
4" BEYOND END OF LINTEL
WEATHER BARRIER
APPLIED TO FACE OF CMU-
FULLY COAT ALL BOLT HEADS
AND CONTINUE OVER TERM BAR
AND SELF-ADH. FLASHING
MORTAR DROPPING COLLECTION
SYSTEM
TERMINATION BAR W/
THERMOPLASTIC SEALANT
2" WALL WIDTH
REF PLAN
FLUID APPLIED FLASHING
4" SPLIT FACE CMU (REF. PLANS
AND ELEVATIONS)
WEATHER BARRIER
2" RIGID INSUL.
CMU VERIFY
DIM. PER PLAN
CONT. SEALANT
EA. SIDE
O.H. DOOR AND
TRACK BY MFR.
FILL COLLAR JOINT W/
GROUT
3/8" THICK STL. BENT PLATE.
FINISH TO CODE 100. WALL WIDTH
FLUID APPLIED
FLASHING
TYPE 'E' STL. GUIDES W/
WEATHER STRIPPING
L 1 1/2" X 1 1/2" X 1/4"X 6" HEADED
STUDS @ 2'-0" O.C. RETURN @
EA. ENDCONC.
SLAB REF.
STRUCT.
FACE BRICK OR
CMU (REF. PLANS
& ELEVATIONS)
STL. PLATE - REF. STRUCT.
GRIND SMOOTH ALL WELDS FIN.
TO CODE 100.
T.O. FIN. LEVEL W/ T.O. STL. ANGLE
SET ANGLE 1/8" ABOVE CONC. TO
FLUSH VCT OR OTHER FLOOR
FINISH.
1/2"
FOUNDATION - REF. STRUCT.
D
4 3/8" 11 5/8"
B.O. CANOPY
107' - 4"
8" CMU
2" RIGID INSUL. BD. (R-20) W/3" 'Z' CLIP OVER CONT.WEATHER BARRIER
PRE-MANUFACTURED
CANOPY
PRE-FIN. MTL. FLASHING
PRE-MANUF. CANOPY
COUNTERFLASHING - REF. A7
SHTS. FOR DTLS.
CANOPY ATTACHMENT -
REF. STRUCT.
CONT. SEALANT EA.
SIDE
1' - 4"
MTL. PANEL CLOSURE
W/ DRIP
METAL WALL PANEL SYS.
MTL SOFFIT PANEL - CONT.SEALANT @ ALL EDGES
ALUM. STOREFRONT
AS SCHED.
8" C.M.U. BOND BEAM W/
REINF. BARS CONT. - FILL
SOLID W/ GROUT
REF. STRUCT.
PRE-FIN. MTL. TRIM
1"
C
FRAME & GLAZING AS SCHED.
REF. A3.1 SHT. FOR CONFIG.
CONT. SEALANT EA. SIDE
FLUID APPLIED FLASHING
C.M.U. LINTEL AS SCHED.
REF. STRUCT.
8" CMU
4" FACE BRICK (FIELD)
2" RIGID INSUL. BD. (R-20)OVER CONT. WEATHER
BARRIER
TERMINATION BAR
MORTAR DROPPING
COLLECTION SYSTEM
WEEPS @ 2'-0" O.C. TYP.
PROVIDE 2 WEEPS PER
OPENING MIN.
WRAP STL. LINTEL W/ METAL
FLASHING. FORM 1/2" DRIP
EDGE AS DETAILED.5" 4 1/2"
BENT PLATE LINTEL
BOLTED TO C.M.U. WALL.
REF. STRUCT.
SELF-ADH. FLASHING
1' - 4"
SIM. TO DRIP GFLASHING
DETAIL @ (T.E.M)
6
1' - 8"
DOOR HEAD
104' - 8"
WRAP STL. LINTEL W/ METAL
FLASHING. FORM 1/2" DRIP
EDGE AS DETAILED
1/2"
8 3/4"
H.M. FRAME AS SCHED.
FILL SOLID W/ MORTAR
CONT. SELANT EA. SIDE
FLUID APPLIED FLASHING
CONT. STL. GUSSET PLATE
C.M.U. LINTEL AS SCHED.
REF. STRUCT..
EMBED PLATE WITH HEADED
STUDS ATTACHED TO C.M.U.
WALL - REF. STRUCT.
WEATHER BARRIER
ASPHALT MASTIC
TERMINATOR
2" RIGID INSUL. BD. (R-20)OVER CONT. WEATHER
BARRIER
?
MORTAR DROP
COLLECTION SYSTEM
WEEPS @ 2'-0" O.C. TYP.
PROVIDE 2 WEEPS PER
OPENING MIN.
COUNTERFLASHING -
REF A7 SHTS. FOR
DTLS
PRE-MANUFACTURED
CANOPY
SELF-ADH. FLASHING
STL. TUBE - REF. STRUCT.
SIM. TO DRIP FLASHING
DTL. ON (T.E.M.)
AS2.1
4
1
2 3/4" MTL. DECK
PER MANUF.
PRE-MANUF. MTL. CANOPY -
REF. EXT. ELEV.
WELDED ENDPLATE
STOREFRONT - REF.
CONFIG. ON A3 SHTS.
CONT. SEALANT EA. SIDE
THRU WALL FLASHING
ALUM. BREAK MTL.
TO MATCH FRAME FINISH
3/4" PLYWOOD (TYP.)
STL. BEAM
REF. STRUCT.
2" CONT. RIGID INSUL. (R-10)
IN BETWEEN STL. BEAM
ATTACHMENTS
STOREFRONT - REF.
CONFIG. ON A3 SHTS.
MTL SOFFIT PANEL CONT. SEALANT
@ ALL EDGES
ALUM. BREAK MTL.
- PAINT TO MATCH FRAME FINISH
@ INTERIOR
CONT. SEALANT EA. SIDE
STOREFRONT ON ALUM
SUBSILL
4 1/2"5"
CONT. SEALANT
EA. SIDESTOREFRONT - REF.
CONFIG. ON A3 SHTS.
5/8" GYP. BD. ON 3 5/8" C.F.M.F. STUDS
@ 1'-4" O.C. (MAX.)
PRE-FIN. MTL. FLASHING
1/8"
GA
P
2" RIGID INSUL. BOARD (R-20)W/ 'Z' CLIP 16" O.C. OVER
CONT. WEATHER BARRIER
METAL WALL PANEL SYS.
10 1/4"
5/8" GYP BD.
3/4" PLYWOOD
WOOD BLOCKING
5/8" GYP. BD.
FIN CLG
112' - 0"
VERT. 'C' CHANNEL -
REF. STRUCT.
BATT INSUL. R-19 (NOT
SHOWN FOR CLARITY) TO
RUN INBETEEN 'C' CHANNELS
ASPHALT MASTIC TERMINATOR
CONCRETE MASONRY UNIT
(CMU) - VERIFY DIM. PER PLAN
CMU LINTEL AS SCHED - REF
STRUCT
CONT. SEALANT EA. SIDE
ALUM FRAME AS SCHED
WRAP STL. LINTEL W/ METAL
FLASHING. FORM 1/2" DRIP
EDGE AS DETAILED.
WEEPS @ 2'-0" O.C. TYP PROVIDE 2 WEEPS
PER OPENING MINIMUM.
FACE BRICK OR ACMU AT HEAD TO BE
RUNNING BOND, SOLDIER, OR AS NOTED
ON ELEV. AND DTLS.
MORTAR DROPPING COLLECTION
SYSTEM
SELF-ADH. FLASHING. FORM END
DAMS.
WEATHER BARRIER
TYP EXT ALUM DOOR HEAD DETAIL
ALUM FRAME AS SCHED
CONT. SEALANT EA. SIDE
REF. STRUCT. FOR REINF.
CONCRETE MASONRY UNIT
(CMU) - VERIFY DIM. PER PLAN
CONT. SEALANT - EA. SIDE
FILL COLLAR JOINT W/ MORTAR
FACE BRICK OR CMU - REF.
FLOOR PLAN
WEATHER BARRIER
2" CONT RIGID INSUL R-10
2" CONT RIGID INSUL R-10
TYP EXT WALL ALUM DOOR JAMB DETAIL
TYPICAL EXTERIOR MASONRY ALUM DETAILS (T.E.M.A.) SCALE 1-1/2" = 1'-0
UNLESS NOTED OTHERWISE ALL H.M. FRAMES IN EXTERIOR MASONRY SHALL
CONFORM TO THESE DETAILS
TERMINATION BAR
DRIP FLASHING DETAIL
3" = 1'-0"
TYP EXT WALL ALUM DOOR SILL DETAIL
SIM. CONDITION
1/2" 4 1/2"
SELF-ADH. FLASHING
CONT. SEALANT
PLAT
E TH
ICKN
ESS
1/2"
5"
1/2"
1/8"
BENT PLATE LINTEL
BOLTED TO CMU WALL-
REF STRUCT
CONT BENT STL ANGLE 2
1/2"x4 1/2" 12 GA GALV @
DOOR ONLY
FLUID APPLIED FLASHING
CONT STL GUSSET PLATE
CONT. SEALANT EA. SIDE
CONCRETE MASONRY UNIT
(CMU) - VERIFY DIM. PER PLAN
ALUM WINDOW AS SCHED.
W/ ALUM SUBSILL
ALUM FLASHING, SET IN BED OF
MASTIC
WEEPS @ 2'-0" O.C. TYP PROVIDE 2
WEEPS PER OPENING MINIMUM.
FILL COLLAR JOINT W/ MORTAR
SELF-ADH. FLASHING
MASONRY VENEER (REF.
PLANS & ELEV'S)
WEATHER BARRIER
CAST STONE SILL
CONC MASONRY UNIT (CMU) -
WALL DIM + 2", DRY PACK &
REINF
5"
FLUID APPLIED FLASHING
FLUID APPLIED FLASHING
GLAZING AS SCHED.
ALUM. FRAME AS SCHED.
ALUMINUM SUB-SILL (.090) AS SPEC'D. SET IN
FULL BED OF MASTIC (NOT REQUIRED FOR
FRAMES INSIDE BLDG.)
FLOOR FIN. AS SCHED.
F.F.
SEALANT AS SPEC'D.,
EA. SIDE
SHIM AS REQ'D.
SLOPE @ EXT. ONLY
4 1/2"
1/2"
ALUM. FRAME AS SCHED.
SEALANT AS SPEC'D. CONT.
EACH SIDE.
WALL LINE
GLAZING AS SCHED.
ALUM. FRAME AS SCHED.
SEALANT AS SPEC'D. CONT.
EACH SIDE.
WALL LINE
GLAZING AS SCHED.
WINDOW CONDITION DOOR CONDITION
4 1/
2"
4 1/
2"
2" 2"
6
1' - 8"
DOOR HEAD
104' - 8"
WRAP STL. LINTEL W/ METAL
FLASHING. FORM 1/2" DRIP
EDGE AS DETAILED
1/2"
8 3/4"
H.M. FRAME AS SCHED.
FILL SOLID W/ MORTAR
CONT. SELANT EA. SIDE
C.M.U. LINTEL AS SCHED.
REF. STRUCT.
BENT PLATE LINTEL
BOLTED TO C.M.U. WALL
REF. STRUCT.
WEATHER BARRIER
ASPHALT MASTIC
TERMINATOR
2" RIGID INSUL. BD. (R-20)OVER CONT. WEATHER
BARRIER
?
MORTAR DROP
COLLECTION SYSTEM
WEEPS @ 2'-0" O.C. TYP.
PROVIDE 2 WEEPS PER
OPENING MIN.
24 GA. PRE-FIN. MTL.
COUNTERFLASHING
PRE-FIN. MTL. FLASHING
4-1/2" PRE-MFG. CANOPY
SELF-ADH. FLASHING
STL. TUBE -
REF. STRUCT.
SIM. TO DRIP FLASHING
DTL. ON (T.E.M.)
AS2.1
4
STL. LINTEL -
REF. STRUCT.
D
CONT. SEALANT EA. SIDE
CONCRETE MASONRY UNIT
(CMU) - VERIFY DIM. PER PLAN
ALUM WINDOW AS SCHED.
W/ ALUM SUBSILL
ALUM FLASHING, SET IN BED OF
MASTIC
WEEPS @ 2'-0" O.C. TYP PROVIDE 2
WEEPS PER OPENING MINIMUM.
FILL COLLAR JOINT W/ MORTAR
SELF-ADH. FLASHING
SPLIT FACE
WEATHER BARRIER
CAST STONE SILL
CONC MASONRY UNIT (CMU) -
WALL DIM + 2", DRY PACK &
REINF
FLUID APPLIED FLASHING
1' - 4"
9 3/8"
Sheet No.Job No.
Drawn By:
Date:
Pro
ject
:
Copyright © 2018, Huckabee & Associates, Inc.
PACKAGE
C:\
Use
rs\r
rod
pra
cha\
Do
cum
ents
\178
0-02
-01
AU
BR
EY
INT
ER
ME
DIA
TE
_AR
CH
_v17
_rro
dp
rach
a.rv
t
9/12
/201
8 4:
29:0
3 P
M
CG
A3.2
DOOR AND WINDOW
DETAILS
8/27/18
1780-02-01
AU
BR
EY
MID
DLE
SC
HO
OL
AD
DIT
ION
FOR
AU
BR
EY
I.S
.D.
AU
BR
EY
, TE
XA
S
1
3" = 1'-0"2DOOR AND WINDOW DETAIL - SILL
6" = 1'-0"1TYP THRESHOLDS
1 1/2" = 1'-0"10HEAD DTL - OH DOOR - CMU / INSUL / BRICK
1 1/2" = 1'-0"7JAMB DTL - OH DOOR - CMU / INSUL / BRICK
1 1/2" = 1'-0"4TYP. O.H. RECESSED SILL
1 1/2" = 1'-0"14SF HEAD @ CANOPY DETAIL AT WEIGHT RM
1 1/2" = 1'-0"12ALUM. WINDOW DETAIL - HEAD
1 1/2" = 1'-0"9H.M. DOOR DETAIL - HEAD
1 1/2" = 1'-0"5DOOR & WINDOW @ CANOPY - SILL/HEAD DTL.
1 1/2" = 1'-0"8CLERESTORY WINDOW DETAIL - HEAD
3" = 1'-0"3DOOR AND WINDOW DETAIL - SILL
3" = 1'-0"6DOOR AND WINDOW DETAIL - JAMB
1 1/2" = 1'-0"13H.M. DOOR DETAIL - HEAD
1 1/2" = 1'-0"11SF SILL @ WEIGHT RM WDW
Rev
isio
n /
Dat
e
10
9/1
2/ 1
8A
DD
EN
DU
M #
1
���
09/13/2018
![Page 12: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/12.jpg)
G
A6.6
9WALL
EXIST.
1" E.J.
7 5/8"
B.O. DECK
ELEV. VARIES112' - 6 7/8"
T.O. WALL
116' - 4"
CONC. FOUNDATION - REF.
STRUCT.
BASE AS SCHED.
8" CMU
STL. JOIST - REF. STRUCT.
4 PLY BUILT-UP ROOFINGASSEMBLY, REFERENCEROOF PLANS.
EXIST. EXTERIOR
WALL
CONT. HORIZ. REINF. @ 16"
O.C. (MAX)
EXIST FIN FLOOR
100' - 0"
METAL WALL PANEL SYS.
7/8" C.F.M.F. HORIZ. HAT CH.@ 1'-4" O.C. (MAX)
WALL MOUNTED
PROJECTOR - REF. A8 SHTS.
V.I.
F.
+/-
3'
- 1
1"
FIN FLOOR
97' - 4"
A6.7
1
1 2
A7.3
10 Sim
A6.6
2
A3.2
T.E.M.
A6.6
5
1' - 4"5' - 4"1' - 4"
DOOR AND FRAME AS
SCHED.
MTL. SOFFIT PANEL -
PROVIDE CONT. SEALANT
@ PERIMETER
4" SPLIT FACE CMU
B.O. LINTEL
106' - 0"
DOOR HEAD
104' - 8"
B.O. DECK
112' - 0"
T.O. WALL
116' - 8"
1/4" / 12"
4 PLY BUILT-UP ROOFINGASSEMBLY, REFERENCEROOF PLANS.
STL. JOIST - REF.
STRUCT.
4" FACE BRICK (FIELD)
CONT. HORIZ. REINF. @
16" O.C.
8" CMU
8" CMU
CONT. HORIZ. REINF. @
16" O.C.
2" RIGID INSUL. BD. (R-20)OVER CONT. WEATHERBARRIER
CONC. FOUNDATION - REF.
STRUCT.
FIN FLOOR
97' - 4"
2" RIGID INSUL. BD. (R-20)OVER CONT. WEATHER
BARRIER
SLOPE
1.02A
CONC. PAVING - REF.
CIVIL
PRE-FIN. MTL. COPING
T.O. CMU
106' - 8"
1
A6.6
2 Sim
A7.3
10 Sim
A3.2
10
B.O. LINTEL
107' - 4"
B.O. DECK
112' - 0"
T.O. WALL
116' - 8"
PRE-FIN. MTL. COPING
4 PLY BUILT-UP ROOFINGASSEMBLY, REFERENCEROOF PLANS.
STL. JOIST - REF.
STRUCT.
8" CMU
4" FACE BRICK (FIELD)
2" RIGID INSUL. BD. (R-20)OVER CONT. WEATHER
BARRIER
CONT. HORIZ. REINF. @
16" O.C.
4" FACE BRICK (FIELD)
CMU LINTEL - REF. STRUCT.
1' - 4"
FIN FLOOR
97' - 4"
O.H. DOOR AS SCHED.
10' -
4"
SO1.03
CONC. FOUNDATION -
REF. STRUCT.CONC. PAVING -
REF. CIVIL
SLOPE
A3.2
4
1/4" / 12"
D
A6.6
1
A7.3
13 Sim
A3.2
14
4 3/8" 11 5/8"
METAL WALL PANEL SYS.
2" RIGID INSUL. BD. (R-20) W/3" 'Z' CLIP OVER CONT.
WEATHER BARRIER
8" CMU
CMU BOND BEAM - REF.STRUCT.
PRE-FIN. MTL. COPING
4 PLY BUILT-UP ROOFINGASSEMBLY, REFERENCEROOF PLANS.
B.O. CANOPY
107' - 4"
DOOR HEAD
107' - 4"
T.O. WALL
116' - 8"
STOREFRONT - REF.
CONFIG. ON A3 SHTS.
SF-C
10"
PRE-MANUF. MTL CANOPY
CONT. HORIZ. REINF.
@ 16" O.C.
B.O. DECK
ELEV. VARIES112' - 6 3/8"
1' - 4"
A3.2
3
4" SPLIT FACE CMU
2" RIGID INSUL. BD. (R-20)OVER CONT. WEATHER
BARRIER
CONT. HORIZ. REINF.
@ 16" O.C. (MAX)
A3.2
11
A6.7
3
8" CMU
1
G F
A7.4
12 Sim
A6.6
9 Sim
FIN FLOOR
97' - 4"
B.O. DECK
ELEV. VARIES112' - 1 1/8"
T.O. WALL
116' - 4"
CONC. PAVING - REF.
CIVIL
4" SPLIT FACE CMU
2" RIGID INSUL. BD. (R-20)OVER CONT. WEATHERBARRIER
8" CMU
CONT. HORIZ. REINF.
@ 16" O.C. (MAX)
WALL
EXIST.
1" E.J.
7 5/8" 8 3/8"
1' - 4"
1" E.J.
1' - 4" STL. JOIST - REF. STRUCT.
T.O. CMU
107' - 4"
A6.7
2
EXIST FIN FLOOR
100' - 0"
B.O. SOFFIT
106' - 0"
MTL SOFFIT PANEL - CONT.SEALANT @ ALL EDGES
SLOPE
REFER TO OTHER A6 SHEETS FOR COMPLETE TYPICAL WALL
SECTION NOTES.
TYPICAL WALL SECTION NOTES APPLY TO ALL WALL SECTIONS
UNLESS NOTED OTHERWISE.
TYPICAL WALL SECTION NOTESAPPPLICABLE TO
ALL A6 SHEETS
Sheet No.Job No.
Drawn By:
Date:
Pro
ject
:
Copyright © 2018, Huckabee & Associates, Inc.
PACKAGE
C:\
Use
rs\r
rod
pra
cha\
Do
cum
ents
\178
0-02
-01
AU
BR
EY
INT
ER
ME
DIA
TE
_AR
CH
_v17
_rro
dp
rach
a.rv
t
9/12
/201
8 4:
29:0
7 P
M
CG
A6.1
WALL SECTIONS
8/27/18
1780-02-01
AU
BR
EY
MID
DLE
SC
HO
OL
AD
DIT
ION
FOR
AU
BR
EY
I.S
.D.
AU
BR
EY
, TE
XA
S
1
1/2" = 1'-0"1WALL SECTION
1/2" = 1'-0"3WALL SECTION
1/2" = 1'-0"4WALL SECTION
1/2" = 1'-0"5WALL SECTION
1/2" = 1'-0"2WALL SECTION
Rev
isio
n /
Dat
e
10
9/1
2/ 1
8A
DD
EN
DU
M #
1
���
09/13/2018
![Page 13: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/13.jpg)
TYPICAL WALL SECTION NOTES
1) REFER ALSO TO A9 SHTS. FOR WALL CONSTRUCTION SECTIONS
AND DETAILS. TYPICAL DETAILS APPLY, AS NEEDED, TO ALL WALL
SECTIONS U.N.O.
2) REINFORCING IN CONCRETE BEAMS, FOOTINGS, AND PIERS HAS
NOT BEEN INDICATED FOR CLARITY. REFER TO STRUCTURAL
DRAWINGS FOR THIS REINFORCING.
3) CONTRACTOR SHALL VERIFY THE DIMENSIONAL CONDITIONS
BETWEEN ALL STRUCTURAL ELEMENTS AND THE ARCHITECTURAL
ELEMENTS FOR CONFLICTS. IF DISCREPANCIES ARE
ENCOUNTERED, NOTIFY THE ARCHITECT IMMEDIATELY.
4) AT ALL EXTERIOR WALLS, PLACE WEATHER BARRIER AT THE
EXTERIOR FACE OF CMU OR SHEATHING. CONTRACTOR TO VERIFY
CHEMICAL COMPATABILITY OF WEATHER BARRIER & SELF-
ADHESIVE FLASHING.
5) PROVIDE 3 STACKED BRICK HEADERS OR ONE SOLID BRICK AT
ALL SOLDIER OUTSIDE CORNERS. (4"X4"X3 5/8")
6) PROVIDE A WEATHERED MORTAR JOINT AT ALL EXTERIOR
CONDITIONS WHERE THE MASONRY COURSE BELOW THE JOINT
PROJECTS BEYOND THE COURSE ABOVE.
7) WHERE CMU IS SHOWN SHADED, FILL CELL SOLID WITH GROUT
UNLESS NOTED IN DETAILS AS MORTAR. COORDINATE ALL
LOCATIONS WITH STRUCTURAL DRAWINGS.
IN CASES OF APPARENT CONFLICT, STRUCTURAL
DRAWINGS SHALL GOVERN DESIGN.
8) FILL ALL OPEN CELLS OF CMU SOLID WITH FOAM INSULATION. AT
ALL EXTERIOR CONDITIONS WHERE RIGID INSULATION IS NOT
APPLIED IN THE CAVITY WALL.
9) PROVIDE THERMAL BATT INSULATION AT ALL EXTERIOR STUD
WALLS AND SOUND BATT INSULATION AT INTERIOR STUD WALLS AS
DESCRIBED IN SECTION 07 2100 OF THE SPECIFICATIONS.
10) REFER TO STRUCTURAL DRAWINGS FOR VERTICAL WALL
REINFORCING.
11) ALL MASONRY WALLS SHALL BE REINFORCED WITH
CONTINUOUS HORIZONTAL BEDJOINT REINFORCING AS SPECIFIED,
AT 1'-4" VERTICAL SPACING. AT VENEER CONDITIONS PROVIDE TIES
AS SPECIFIED AT 1'-4" O.C.E.W.
12) INFORMATION SHOWN BEYOND IN WALL SECTIONS IS PROVIDED
FOR INFORMATION ONLY AND SHALL NOT LIMIT THE SCOPE OF
WORK REQUIRED IN THIS PROJECT.
13) SMALLER SCALE DRAWINGS MAY NOT SHOW ALL CONNECTIONS
AND FINISHES. ALWAYS REFER TO ENLARGED DETAILS, WHERE
PROVIDED, FOR ADDITIONAL INFORMATION. IN CASES OF
APPARENT CONFLICT, THE LARGER SCALED DETAIL SHALL APPLY.
14) INTERIOR WALL FINISHES ARE NOT SHOWN ON WALL SECTIONS
TO AVOID VISUAL CLUTTER. REFER TO FINISH TAGS AND INTERIOR
ELEVATIONS FOR REQUIRED MATERIALS AND MATERIAL PATTERNS.
APPPLICABLE TO
ALL A6 SHEETS
GROUT
CB
A3.2
12
A3.2
8
A3.2
5
A6.6
7 Sim
B.O. CANOPY
108' - 0"
T.O. WALL
116' - 8"
DOOR HEAD
111' - 10"FIN CLG
112' - 0"
DOOR HEAD
107' - 4"
FIN CLG
109' - 4"
4" 10 1/4" 11' - 5 3/4" 1' - 3 5/8"
PRE-MANUF. CANOPY - REF.EXT. ELEV.
METAL WALL PANEL SYS.
2" RIGID INSUL. BOARD (R-20)W/ 'Z' CLIP 16" O.C. OVER
CONT. WEATHER BARRIER
4 PLY BUILT-UP ROOFINGASSEMBLY, REFERENCEROOF PLANS.
5/8" GYP BD.
STOREFRONT - REF.
CONFIG. ON A3 SHTS.
STOREFRONT - REF.
CONFIG. ON A3 SHTS.
PRE-FIN. MTL. COPING
8" CMU
CONT. HORIZ. REINF. @
16" O.C.
2" RIGID INSUL. BD. (R-20)OVER CONT. WEATHER
BARRIER
4" FACE BRICK (FIELD)
LAY-IN CEILING
B.1
10"
B.O. DECK
ELEV. VARIES114' - 2 3/16"
SLOPE
CONC. FOUNDATION - REF.
STRUCTURE
3 5/8" C.F.M.F. STUDS @ 1'-4"O.C. (MAX)
LIGHT FIXTURE - REF. ELEC. STL. BEAM - REF. STRUCT.
CONC. PAVING -
REF. CIVIL
STL. BEAM - REF. STRUCT.
VERT. 'C' CHANNEL - REF.
STRUCT.
STL. ANGLE BRACING -
REF. STRUCT.
SF-A1SF-A
B.O. CANOPY
107' - 0"
2 1/
4"
10"
PRE-FIN. MTL. COPING
FIN FLOOR
97' - 4"
1
B B.1
T.O. CMU
108' - 0"
B.O. CANOPY
108' - 0"
FIN FLOOR
97' - 4"
4" 1' - 4"
8" 8"
MASONRY TIES @ 16"
O.C. (MAX)
STL. COL. - REF.
STRUCT.
STL. BEAM - REF.
STRUCT.
STL. TUBE - REF.
STRUCT.
PRE-MANUF. CANOPY - REF.EXT. ELEV.
10"
4" SPLIT FACE CMU
1 1/2" RIGID INSUL. BOARDOVER CONT. WEATHER
BARRIER
MASONRY TIES @ 16"
O.C. (MAX)
7/8" C.F.M.F. VERT. HAT CH. @1'-4" O.C. (MAX)
METAL WALL PANEL SYS.
1 1/2" RIGID INSUL. BOARD W/'Z' CLIP OVER CONT.WEATHER BARRIER
7/8" C.F.M.F. VERT. HAT CH. @1'-4" O.C. (MAX)
SLOPE
CONC. PAVING -
REF. CIVIL
A6.6
6
STL. COL - REF.
STRUCT.
T.O. WALL
116' - 8"
A6.6
7 Sim
5/8" GYP. SHEATHING
5/8" GYP. SHEATHING
4" FACE BRICK (FIELD)
1 1/2" RIGID INSUL. BOARDOVER CONT. WEATHERBARRIER
5/8" GYP. SHEATHING
FIN CLG
112' - 0"
5/8" GYP BD.
3
A7.3
10 Sim
A6.6
2 Sim
4 PLY BUILT-UP ROOFINGASSEMBLY, REFERENCEROOF PLANS.
1' - 4"
T.O. WALL
108' - 0"
T.O. CMU
107' - 4"
T.O. WALL
116' - 8"
B.O. DECK
112' - 11 1/2"
STL. JOIST - REF.
STRUCT.
4" FACE BRICK (FIELD)
2" RIGID INSUL. BD. (R-20)OVER CONT. WEATHER
BARRIER
8" CMU
4" SPLIT FACE CMU
CONT. HORIZ. REINF. @
16" O.C.
CONC. FOUNDATION -
REF. STRUCT.
6" CMU
PRE-FIN. MTL. COPING
1/4" / 12"
FIN FLOOR
97' - 4"A6.7
3
5
A6.6
11 Sim
A6.6
4
A6.6
3
A6.6
7
A3.2
5
A3.2
8
CONC. FOUNDATION -
REF. STRUCT.
BASE AS SCHED.
CONT. HORIZ. REINF. @
16" O.C. (MAX)
TELESCOPING
BLEACHERS
A4.4
6
STOREFRONT - REF.
CONFIG. ON A3 SHTS.
FIN FLOOR
97' - 4"
B.O. CANOPY
108' - 0"
WDW HEAD
111' - 10"
4 PLY BUILT-UP ROOFINGASSEMBLY, REFERENCEROOF PLANS.
1/4" / 12"
?
5/8" GYP BD.
FIN CLG
112' - 0"
T.O. WALL
134' - 0"
B.O. DECK
131' - 8 1/4"
12" CMU
2" RIGID INSUL. BD. (R-20)OVER CONT. WEATHER
BARRIER
CONT. HORIZ. REINF.
@ 16" O.C.
4" FACE BRICK (FIELD)
4 3/8"1' - 3 5/8"
PRE-FIN. MTL. COPING
4 PLY BUILT-UP ROOFINGASSEMBLY, REFERENCEROOF PLANS.
METAL WALL PANEL SYS.
2" RIGID INSUL. BD. (R-20) W/3" 'Z' CLIP OVER CONT.
WEATHER BARRIER
12" CMU
CONT. HORIZ. REINF. @
16" O.C.
STL. JOIST - REF.
STRUCT.
4.1
T.O. CMU
107' - 4"
8" 2 1/4"
T.O. BRICK
122' - 8"
PRE-MANUF. CANOPY - REF.EXT. ELEV.
4" SPLIT FACE CMU
ACOUSTICAL PANEL
4" FACE BRICK (FIELD)
T.O. BRICK
112' - 8"
B.O. DECK
114' - 3 5/8"
T.O. WALL
116' - 8"
SF-A2
METAL WALL PANEL SYS.
2" RIGID INSUL. BOARD (R-20)W/ 'Z' CLIP 16" O.C. OVER
CONT. WEATHER BARRIER
VERT. 'C' CHANNEL - REF.
STRUCT.
STL. ANGLE BRACING -
REF. STRUCT.
B.O. DECK
114' - 0"
PRE-FIN. MTL. COPING
10"
1/4" / 12"
MTL PANEL WALL SYS.
(BEYOND)
FIN FLOOR
97' - 4"
T.O. CONC
97' - 1 7/16"
Sheet No.Job No.
Drawn By:
Date:
Pro
ject
:
Copyright © 2018, Huckabee & Associates, Inc.
PACKAGE
C:\
Use
rs\r
rod
pra
cha\
Do
cum
ents
\178
0-02
-01
AU
BR
EY
INT
ER
ME
DIA
TE
_AR
CH
_v17
_rro
dp
rach
a.rv
t
9/12
/201
8 4:
29:0
9 P
M
CG
A6.2
WALL SECTIONS
8/27/18
1780-02-01
AU
BR
EY
MID
DLE
SC
HO
OL
AD
DIT
ION
FOR
AU
BR
EY
I.S
.D.
AU
BR
EY
, TE
XA
S
1
1/2" = 1'-0"2WALL SECTION
1/2" = 1'-0"4WALL SECTION
1/2" = 1'-0"1WALL SECTION
1/2" = 1'-0"3WALL SECTION
Rev
isio
n /
Dat
e
10
9/1
2/ 1
8A
DD
EN
DU
M #
1
���
09/13/2018
![Page 14: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/14.jpg)
STL. ANGLE-REF. STRUCT.
TREATED WOOD BLOCKING
CANT STRIP
ROOF MEMBRANE TO EXTEND
TO UNDER FLASHING ABOVE
COUNTER FLASHING REF.
A7 SHTS FOR DTLS.
ROOFING MEMBRANE SHALL
EXTEND UP AND OVER PARAPET
TO FACE SIDE OF WALL
11 5/8"
8 " M
IN.
2" RIGID INSUL. BD. (R-20) W/3" 'Z' CLIP OVER CONT.
WEATHER BARRIER
METAL WALL PANEL SYS.
8" CMU
CONT. HORIZ. REINF.
@ 16" O.C.
8" CMU BOND BEAM W/
REINF. BARS CONT. - FILL
SOLID WITH GROUT -
REF. STRUCT.
B.O. DECK
ELEV. VARIES112' - 6 3/8"
1
STL. ANGLE-REF.
STRUCT.
TREATED WOOD
BLOCKING
CANT STRIP
COUNTER FLASHING REF.
A7 SHTS FOR DTLS.
CONT. HORIZ. REINF. @
16" O.C.
1' - 4"
8" M
IN.
ROOFING MEMBRANE
SHALL EXTEND UP AND
OVER PARAPET TO
FACE SIDE OF WALL
ROOF MEMBRANE TO
EXTEND TO UNDER
FLASHING ABOVE2" RIGID INSUL. BD. (R-20)
OVER CONT. WEATHERBARRIER
4" FACE BRICK (FIELD)
8" CMU
4 PLY BUILT-UP ROOFING
ASSEMBLY OVER 1" PERLITE
BD. ON (2) LAYERS OF 2"
POLYISO INSUL. (R-25ci)
OVER 1 1/2" MTL. DECK
B.O. DECK
REF. SECTION
5
1' - 8"
4" FACE BRICK (FIELD)
2" RIGID INSUL. BD. (R-20)OVER CONT. WEATHER
BARRIER
CONT. HORIZ.
REINF. @ 16" O.C.
WEEPS @ 2'-0" O.C.
MASONRY MORTAR DROPPING
COLLECTION SYSTEM
STL. ANGLE & TUBE - REF. STRUCT.
PRE-FIN COUNTER FLASHING AND
REGLET-REF. TYP. DET ON A7 SHTS.
FLEXIBLE SHEET MEMBRANE
TO EXTEND UNDER FLASHING
ABOVE
PROVIDE THERMOPLASTIC
SEALANT CONT ALONG END
OF SELF-ADH FLASHIN
ALUMINUM TERMINATION BAR
CONT. ALONG END OF SELF-
ADH FLASHING
SELF-ADHESIVE FLASHING
5/8" EXT. GRADE
PLYWOOD SHEATHING
4" CANT STRIP
STL. BEAM - REF.
STRUCT.
12" CMU
CMU BOND BEAM - REF.STRUCT.
CMU BOND BEAM - REF.STRUCT.
4 PLY BUILT-UP ROOFING ASSEMBLY
OVER 1" PERLITE BD. ON (2) LAYERS
OF 2" POLYISO INSUL. (R-25ci) OVER 1
1/2" MTL. DECK 8" M
IN.
STL. ANGLE- REF.
STRUCT.
TREATED WOOD
BLOCKING
B.O. DECK
114' - 3 5/8"
5
1' - 3 5/8"4 3/8"METAL WALL PANEL SYS.
2" RIGID INSUL. BD. (R-20) W/3" 'Z' CLIP OVER CONT.
WEATHER BARRIER
4" FACE BRICK (FIELD)
12" CMU
CONT. HORIZ. REINF.
@ 16" O.C.
MTL. PANEL CLOSURE W/ DRIP
TREATED WOOD BLOCKING
22 GA GALV. CONTINUOUS CLEAT.
SECURE WITH FASTENERS
INSTALLED 6" O.C.
24 GA. PRE-FIN. MTL. FLASHING -
EXTEND UP AND UNDER MTL PANEL
ABOVE
CONT. SEALANT
PROVIDE THERMOPLASTIC SEALANT CONT
ALONG END OF SELF-ADH FLASHING
ALUMINUM TERMINATION BAR CONT
ALONG END OF SELF-ADH FLASHING
EX
IST
.
MA
TC
H
2" RIGID INSUL. BD. (R-20)OVER CONT. WEATHER
BARRIER
1' - 8"
1
MLT. SOFFIT PANEL
PROVIDE CONT. SEALANT
@ PERIMETER
4" FACE BRICK (FIELD)
8" CMU
8" CMU BOND BEAM W/ REINF.
BARS CONT. - FILL SOLID WITH
GROUT - REF. STRUCT.
SELF-ADH. FLASHING
WEEPS @ 2'-0" O.C. TYP.
PROVIDE 2 WEEPS PER
OPENING MIN.
MORTAR DROPPING
COLLECTION SYSTEM
TERMINATION BAR W/
THERMOPLASTIC SEALANT
2" RIGID INSUL. BD. (R-20)OVER CONT. WEATHER
BARRIER
CONT. HORIZ.
REINF. @ 16" O.C.
WRAP STL. LINTEL W/
METAL FLASHING -
FORM TO PROVIDE 1/2"
DRIP AS DETAILED ON
A3.2 T.E.M. DTL.
1/4" MAX.
BENT PLATE LINTEL BOLTED
TO C.M.U. WALL
REF. STRUCT.
4" SPLIT FACE CMU
MTL. TRIM REVEAL
B.O. SOFFIT
106' - 0"
B.O. CMU
106' - 8"
1
A7.4
6 Sim
T.O. WALL
116' - 8"
FLEXIBLE PARAPET MEMBRANE
SHALL EXTEND UP & OVER
PARAPET TO FACE SIDE OF WALL
CANT STRIP
5/8" EXT. GRADE
PLYWOOD SHEATHING
TREATED WOOD
BLOCKING
2" RIGID INSUL. BOARD (R-20)W/ 'Z' CLIP 16" O.C. OVER
CONT. WEATHER BARRIER
METAL WALL PANEL SYS.
STL. BEAM
REF. STRUCT.
STL. BRACING
REF. STRUCT.
5/8" GYP BD.
BATT INSUL. R-19 (NOT
SHOWN FOR CLARITY) TO RUN
INBETEEN 'C' CHANNELS
STL. ANGLE - REF. STRUCT.
VERT. 'C' CHANNEL -
REF. STRUCT.
4 PLY BUILT-UP ROOFING
ASSEMBLY OVER 1" PERLITE BD. ON
(2) LAYERS OF 2" POLYISO INSUL.
(R-25ci) OVER 1 1/2" MTL. DECK
COUNTER FLASHING REF.
A7 SHTS FOR DTLS.
8" M
IN.
5/8" GYP. SHEATHING
B.O. DECK
ELEV. VARIES114' - 0 1/8"
1
A7.3
13 Sim
H
FLEXIBLE PARAPET MEMBRANE
SHALL EXTEND UP & OVER
PARAPET TO FACE SIDE OF WALL
CANT STRIP
TREATED WOOD BLOCKING
STL. ANGLE
REF. STRUCT.
12" CMU
12" CMU BOND BEAM W/
REINF. BARS CONT. - FILL
SOLID WITH GROUT - REF.
STRUCT.
METAL WALL PANEL SYS.
CONT. HORIZ. REINF. @
16" O.C.
4" 11 5/8"
1' - 3 5/8"
T.O. WALL
134' - 0"
4 PLY BUILT-UP ROOFING ASSEMBLY
OVER 1" PERLITE BD. ON (2) LAYERS
OF 2" POLYISO INSUL. (R-25ci) OVER
3" MTL. DECK
2" RIGID INSUL. BD. (R-20) W/3" 'Z' CLIP OVER CONT.
WEATHER BARRIER
COUNTER FLASHING REF.
A7 SHTS FOR DTLS.
8" M
IN.
CONT. HORIZ. REINF. @
16" O.C. (MAX)
B.O. DECK
ELEV. VARIES131' - 5 15/16"
G
8" CMU BOND BEAM W/ REINF.
BARS CONT. - FILL SOLID WITH
GROUT - REF. STRUCT.
FLEXIBLE PARAPET MEMBRANE
SHALL EXTEND UP & OVER
PARAPET TO FACE SIDE OF WALL
CONT. HORIZ. REINF.
@ 16" O.C.
TREATED WOOD
BLOCKING
STL. ANGLE
REF. STRUCT.
CANT STRIP
EXIST. EXTERIOR
WALL
EXISTING WALL 1 7/8"
V.I.F.
+/- 6 3/4"
8" CMU
T.O. WALL
116' - 4"
T.O. EXIST BRK
120' - 8"
EXIST. WALL
1" E.J.
7 5/8"
8" CMU BOND BEAM W/ REINF.
BARS CONT. - FILL SOLID WITH
GROUT - REF. STRUCT.
METAL WALL PANEL SYS.
7/8" C.F.M.F. HORIZ. HAT CH.@ 1'-4" O.C. (MAX)
TREATED WOOD
BLOCKING
NEW THROUGH-WALL
FLASHING TO BE
INSTALLED UNDER
EXIST. MTL. PANEL.
NEW MTL. PANEL
CLOSURE W/ DRIP
MATCH EXIST.
TERMINATION POINT
1" E.J. COVER - REF. DTLS.
ON A7 SHTS
A7.4
13 Sim
4 PLY BUILT-UP ROOFING ASSEMBLY
OVER 1" PERLITE BD. ON (2) LAYERS
OF 2" POLYISO INSUL. (R-25ci) OVER
1 1/2" MTL. DECK
COUNTERFLASHING - REF.
A7 SHTS. FOR DTLS.
8" M
IN.
CONT. WEATHER
BARRIER OVER
EXIST. MASONRYV.I.
F.
+/-
3'
- 1
1"
B.O. DECK
ELEV. VARIES112' - 6 7/8"
H
12" CMU
STL. ANGLE
REF. STRUCT.
TREATED WOOD
BLOCKING
12" C.M.U. BOND BEAM W/
REINF. BARS CONT. - FILL
SOLID W/ GROUT
REF. STRUCT.
EXISTING WALL SYSTEM TO
REMAIN
FLEXIBLE PARAPET MEMBRANE
SHALL EXTEND UP & OVER
PARAPET TO FACE SIDE OF WALL
CANT STRIP
4 PLY BUILT-UP ROOFING ASSEMBLY
OVER 1" PERLITE BD. ON (2) LAYERS
OF 2" POLYISO INSUL. (R-25ci) OVER 1
1/2" MTL. DECK
COUNTER FLASHING REF.
A7 SHTS FOR DTLS.
A7.2
13 Sim
WALL
EXIST.
V.I.F.
+/- 6" 11 5/8"
8" M
IN.
PRE-FIN. MTL. COPING
CONT HORIZ. REINF.
@ 16" O.C. VERT.
REMOVE EXIST. PARAPET CAP AS TO
ALLOW FOR INSTALLATION OF NEW
E.J. COVER
EXISTING ROOF TO REMAIN
EXTEND EXIST. ROOFING
MEMBRANE UP NEW COVER
TREATED WD. BLOCKING
REMOVE PART OF EXIST. MTL.
PANEL AS REQ'D. TO INSTALL
WD. BLOCKING - PROVIDE J-
TRIM CLOSURE AND SEAL TO
ENSURE WATERTIGHT
CONNECTION
2" E.J. COVER - REF. TYP.
DTLS. ON A7 SHTS.
FIN CLG
112' - 0"
LAY-IN CEILING
5/8" GYP BD.
7/8" C.F.M.F. HORIZ. HAT CH.@ 1'-4" O.C. (MAX)
E.J. CLG COVER
A9.3
10 Sim
EXISTING ALUM
STOREFRONT TO REMAIN
20 GA. STL. COPING - COLOR
AS SELECTED BY ARCH
B.O. DECK
ELEV. VARIES114' - 1 5/16"
B
2 3/4" MTL. DECK PER MANUF.
PRE-MANUF. MTL.
CANOPY
WELDED ENDPLATE
MTL SOFFIT PANEL CONT. SEALANT
@ ALL EDGES
1' - 8"4"
2' - 0"
B.O. CANOPY
108' - 0"
MTL. PANEL CLOSURE W/ DRIP
24 GA. PRE-FIN. MTL. FLASHING -
EXTEND UP AND UNDER MTL PANEL
ABOVE
PROVIDE THERMOPLASTIC SEALANT CONT
ALONG END OF SELF-ADH FLASHING
ALUMINUM TERMINATION BAR CONT
ALONG END OF SELF-ADH FLASHING
METAL WALL PANEL SYS.
STL. TUBE - REF.
STRUCT.
4" SPLIT FACE CMU
MASONRY TIES @ 16" O.C.
4" SPLIT FACE CMU
4" FACE BRICK (FIELD)
1 1/2" RIGID INSUL. BOARDOVER CONT. WEATHERBARRIER
5/8" GYP. SHEATHING
1 1/2" RIGID INSUL. BOARDOVER CONT. WEATHERBARRIER
7/8" C.F.M.F. VERT. HAT CH. @1'-4" O.C. (MAX)
I H1' - 8"
8 3/8" 11 5/8"
4" FACE BRICK (FIELD)
12" CMU
WEEPS @ 2'-0" O.C.
MASONRY MORTAR DROPPING
COLLECTION SYSTEM
STL. ANGLE & TUBE -
REF. STRUCT.
PRE-FIN COUNTER FLASHING AND
REGLET-REF. TYP. DET ON A7 SHTS.
PROVIDE THERMOPLASTIC
SEALANT CONT ALONG END
OF SELF-ADH FLASHIN
ALUMINUM TERMINATION BAR
CONT. ALONG END OF SELF-
ADH FLASHING
SELF-ADHESIVE FLASHING
5/8" EXT. GRADE
PLYWOOD SHEATHING
CONT. HORIZ.
REINF. @ 16" O.C.
CMU BOND BEAM - REF.STRUCT.
CMU BOND BEAM - REF.STRUCT.
REMOVE EXIST. PARAPET CAP AS TO
ALLOW FOR INSTALLATION OF NEW
E.J. COVER
TREATED WD. BLOCKING
2" E.J. COVER - REF. TYP.
DTLS. ON A7 SHTS.
20 GA. STL. COPING - COLOR
AS SELECTED BY ARCH
Sheet No.Job No.
Drawn By:
Date:
Pro
ject
:
Copyright © 2018, Huckabee & Associates, Inc.
PACKAGE
C:\
Use
rs\r
rod
pra
cha\
Do
cum
ents
\178
0-02
-01
AU
BR
EY
INT
ER
ME
DIA
TE
_AR
CH
_v17
_rro
dp
rach
a.rv
t
9/13
/201
8 11
:00:
07 A
M
CG
A6.6
WALL SECTION DETAILS
8/27/18
1780-02-01
AU
BR
EY
MID
DLE
SC
HO
OL
AD
DIT
ION
FOR
AU
BR
EY
I.S
.D.
AU
BR
EY
, TE
XA
S
1
1 1/2" = 1'-0"1MID-WALL DETAIL
1 1/2" = 1'-0"2MID-WALL DETAIL
1 1/2" = 1'-0"3MID-WALL DETAIL
1 1/2" = 1'-0"4MID-WALL DETAIL
1 1/2" = 1'-0"5MID-WALL DETAIL
1 1/2" = 1'-0"7WALL SECTION DETAIL
1 1/2" = 1'-0"11WALL SECTION DETAIL
1 1/2" = 1'-0"9WALL SECTION DETAIL
1 1/2" = 1'-0"8WALL SECTION DETAIL
1 1/2" = 1'-0"6WALL SECTION DETAIL
1 1/2" = 1'-0"10WALL SECTION DETAIL
Rev
isio
n /
Dat
e
10
9/1
2/ 1
8A
DD
EN
DU
M #
1
���
09/13/2018
![Page 15: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/15.jpg)
INTERIOR EXTERIOR
ROOF HATCH REF
TYP SECT THIS SHT
WALL BRACKETS
LADDER
WALL LINE
4"X2"X3/16" STD MTL
ANGLE FLR
BRACKET BOLT TO
FLR W/ 1/2" x 4" E.B.
WALL
BRACKETS
LADDER
RETURN RAIL
BACK TO WALL
2" X 3/16" WALL
BRACKET @ 48"
O.C. - ABOVE FIRST
BRACKET
ROOF LINE
EXTEND
ABOVE
PARAPET
WALL
PARAPET
ROOF LINE
WALL LINE
1' - 4
"
7' - 0
" MIN
4' - 0
" O
.C. T
YP
REF
ROO
F PL
AN
4' - 0
"4'
- 0"
7' - 0
"
A7.3
11 Sim
PLAN
SECTION
2' - 8" 4"
3"10
"3"
1' - 4
"
2"1'
- 0"
2"
2' - 8" 4"
5"
3"2"
5"
GALV. L2 X 2 X 3/16 STEEL ANGLES
EACH SIDE WITH 1/4" THICK GALV.
STEEL CHECKER PLATE.
3/4" DIA. STEEL BAR RUNGS AT 12"
O.C. VERTICALLY MAX. VERIFY
NUMBER & SPACING AT EACH
LADDER
2"X1/2" GALV. STEEL PLATE
STRINGERS 18" APART, RADIUS
ENDS
2"x1/2" GALV. STEEL PL BRACKET
AT 48" O.C. MAX EA. SIDE;
PROVIDE 4" BENT LEG W/ 1/2" DIA.
x 6" EXP BOLT
PROVIDE BACKER ROD & SEALANT @
BRICK PENETRATION
2"X1/2" GALV. STEEL PLATE
BRACKET BENT PL TO FIT
AGAINST PARAPET WALL;
ANCHOR TO MASONRY W/ 1/2"
DIA. X 6" EXP. BOLTS; SEAL
WATER-TIGHT.L3 X 5 X 3/8 X 1'-0" (LLH) GALV.
STEEL ANGLE EACH SIDE W/ 1/2" DIA.
X 6" EXP. BOLTS; SEAL WATER-TIGHT.
2"X1/2" GALV. STEEL PLATE
"NOTCHED" PARAPET WALL
BEYOND
2' - 2"
3' - 6
"1'
- 0 1
/4"
1' - 0
"1'
- 7"
TYP
HEIG
HT V
ARIE
S - F
IELD
VER
IFY
6 7/8"
HE
IGH
T V
AR
IES
1'-0
"
EXTERIOR
2 1/2"x2 1/2"x4"x1/4" STEEL CLIP ANGLE ANCHOR,
SECURELY FASTENED TO WALL, PROVIDE STEEL
PLATE 2"x1/2" STRUTS FASTENED STRINGERS,
INSTALL ABOVE ROOF FLASHING
3/4" DIA. STEEL BAR RUNGS AT 12" O.C.
VERTICALLY MAX. VERIFY NUMBER &
SPACING AT EACH LADDER
2"x1/2" STEEL PLATE STRINGERS
18" APART, RADIUS ENDS
1 1/2"x1 1/2"x1/4" STEEL ANGLES EACH SIDE
WITH 1/4" THICK STEEL CHECKER DECK
2"x3/8" STIFFENER BAR AT RADIUS
ELEV. VARIES
MAX
1' - 0
"
TYP
1' - 0
"HE
IGHT
VAR
IES
3' - 6
"
4"6"
4" M
IN
4" 4"
7"
WIDTH VARIES
PARAPET 7"
VA
RIE
S
RAD
IUS
18"
18"
1/2" X 12" LONG
ANCHOR BOLT
@ 48" O.C.
3/8" E.B. X 8" LONG @ 24"
O.C. STAGGERED
24 GA. MITERED, RIVETED & SOLDERED
WATERTIGHT CORNER UNDERPLATEENDWALL CONDITION
INSTALL 1" STANDING SEAM
AT ALL CORNERSNOTE: INSTALL FLEXIBLE VAPOR RETARDER
UNDER CORNERS MIN. 24" EACH WAY
INSTALL A CONTINUOUS BEAD OF SEALANT
UNDER BOTH EDGES OF COVERPLATE.
EXTEND BEAD OF SEALANT DOWN BOTH
VERTICAL FACES OF COPING.
INSTALL MIN. 6" WIDE 24 GA. PREFINISHED
METAL COVER PLATE AT JOINTS OF COPING
CORNER CONDITION
24 GA. MITERED, RIVETED & SOLDERED
WATERTIGHT CORNER UNDERPLATE
VARI
ES
1' - 0" 1' - 0" 2' - 0" 1' - 0" 1' - 0"
FIN GRADE
FIN FLR
PRE-FIN MTL DOWNSPOUT
2"x2" GLAV STL TABS W/ 7/16" HOLE
FOR ATTACHMENT TO FACE OF WALL,
CAULK ALL PENETRATIONS
16 GA GALV STL BOOT, PAINTED
FACE OF WALL
BOTTOM OF STL BOOT 7" ABOVE FIN
GRADE
8" M
IN
8" M
IN
FRONT ELEVATION SIDE ELEVATION
PRE-FAB CONC SPLASH
BLOCK
4' - 0
"
VARI
ES
7"
4'-0
"
PRE-FIN MTL DOWNSPOUT
STL PLATE BOTTOM AT ABOVE
GROUND DISCHARGE
WHERE TRENCH DRAINS
OCCUR, CONT. BOOT - REF
ROOF PLAN AND CIVIL
GALV TABS EA. SIDE
45 DEGREE ANGLE AT ABOVE
GROUND DISCHARGE
D.S. TO FIT INSIDE 16 GA
GALV D.S. BOOT, PAINTED
4x TREATED WOOD MOUNTING
BLOCK. LENGTH AS REQUIRED
LOOSE LAY PROTECTION
PAD ON ROOF
MOP
BLOCK TO
WALK PAD
EXTEND WALK PAD 2" BEYOND
MOUNTING BLOCK ON ALL SIDES
MOP MOUNTING BLOCK TO WALK PAD
SWEEP ALL LOOSE GRAVEL FROM MOUNTING SITE & LAY
PROTECTION PAD LOOSE ON B.U. ROOFING
PLAN
SECTION
3 1/
2"2"
3' - 2"
NOTE: ALL SHT. MTL. COMPONENTS SHOULD
BE DESIGNED TO RESIST VARIOUS
WIND UPLIFT REQUIREMENTS
FASTEN TO WD. NAILER @
24" O.C.
22 GA. GALV. WIND CLIP,
CONT FASTEN AT 6" O.C.
1 LAYER 15# FELT CONT, LAP EA.
JOINT MIN. 6".SEAL ALL JOINTS
W/ MASTIC
CONT SEALANT
6"
2" M
IN
REF WALL SECTION
NOTE: CONTRACTOR SHALL KEEP
CAVITY WATER TIGHT BEFORE AND
AFTER CAP IS INSTALLED
GROUT CELLS SOLID, RENIF
PER STRUCT
REF WALL SECTION FOR
ADDITIONAL INFO
FASTEN TO WD. NAILER @ 24" O.C.
22 GA. GALV. WIND CLIP, CONT
FASTEN AT 6" O.C.
1 LAYER 15# FELT CONT, LAP EA.
JOINT MIN. 6".SEAL ALL JOINTS W/
MASTIC
1 LAYER OF WATERPROOF
MEMBRANE FLASHING, EXTEND
OVER TOP & SIDES OF COPING
1/2" X 6" LONG ANCHOR BOLT @ 48"
O.C. COUNTERSINK HEAD
6"
FLEXIBLE PARAPET MEMBRANE
SHALL EXTEND UP & OVER PARAPET
TO FACE SIDE OF WALL
COMPRESSIVE FIBER
GLASS INSUL.
1" 2" 1"
EXIST MASONRY WALL
BLOCKING & FRAMING TO
REMAIN UNLESS DAMAGED
PROVIDE NEW 24 GA.
GALV SHT MTL EJ COVER
WOOD BLOCKING ASSEMBLY CONSISTING OF 2X TREATED WD. W/ 3/4" EXT GRADE
PLYWD ANCHOR TO WALL W/ FASTNERS @ 24" O.C.
24 GA. STL COPING W/ KYNAR FIN -
COLOR AS SELECTED BY ARCH
EJ
1"
FACE BRICK
FLASH & COUNTERFLASH
4" CMU
4" CANT
ROOFING ASSEMBLY
THRU WALL FLASHING
ICF WALL
ASSEMBLY
5/8" EXT GRADE
PLYWD, ALL WAY
TO INSIDE CORNER
1 LAYER OF 15# FELT
SELF ADH FLASHING
1
2
3
FLASH &
COUNTERFLASH
FLEXIBLE PARAPET
MEMBRANE, ADHEAR
TO COATED
COUNTERFLASHING
CONST SEQUENCE
ROOFING
MEMBRANE
TERM BAR W/ THERMO
PLASTIC SEALANT
TERM BAR W/ THERMO
PLASTIC SEALANT
TERM BAR W/ THERMO
PLASTIC SEALANT
SAW CUT @ EXIST. JOINT. INSTALL
NEW COUNTER FLASHING AND
REGLET. CONT. SEAL
EXTEND ROOFING
MEMBRANE UP WALL AND
UNDER MTL. COPING
CMU SIZE VARIES - REF.
WALL SEC.
WEEPS @ 2'-0" O.C. TYP
NEW SELF-ADH. FLASHING.
TERMINATION BAR
COUNTERFLASHING REF A7
SHTS. FOR TYP. DTLS.
REMOVE & REINSTALL EXIST
VENEER IN SECTIONS AS NEC. TO
ALLOW FOR INSTALLATION OF NEW
THROUGH WALL FLASHING
.
NEW WEATHER BARRIER
EXIST WALL
24 GA. GALV. SHT. MTL.
COVER
TREATED WOOD BLOCKING
24 GA. GALV. SHT. MTL.
COVER
EXTEND ROOFING
MEMBRANE UP WALL AND
UNDER MTL. COPING
CMU SIZE VARIES - REF.
WALL SEC.
TREATED WOOD BLOCKING
THROUGH-WALL
FLASHING W/ DRIP
TERMINATION BAR
EXIST WALL
7/8" C.F.M.F. HORIZ. HAT CH.
@ 1'-4" O.C. (MAX)
MTL. PANEL CLOSURE
MTL. WALL PANEL SYS.
CONT. WEATHER
BARRIER OVER
EXIST. MASONRY
NOTE: ALL SHT. MTL. COMPONENTS SHOULD BE DESIGNED
TO RESIST VARIOUS WIND UPLIFT REQUIREMENTS
FLEXIBLE PARAPET MEMBRANE
SHALL EXTEND UP & OVER
PARAPET TO FACE SIDE OF WALL
5/8" EXT GRADE PLWD SHEATHING
NOTE: CONTRACTOR SHALL KEEP CAVITY WATER
TIGHT BEFORE & AFTER CAP IS INSTALLED
FASTEN TO WD. NAILER @ 24" O.C.
1/2" X 1-1/2" TREATED WD.
BLOCKING, ANCHOR TO PARAPET
@ 16" O.C.
22 GA. GALV. WIND CLIP, CONT.
FASTEN AT 6" O.C.
1 LAYER 15# FELT CONT. - LAP
EA. JOINT MIN. 6" - SEAL ALL
JOINTS W/ MASTIC
WOOD BLOCKING ASSEMBLY
CONSISTING OF 2X TREATED WD. W/ 3/4"
EXT GRADE PLYWD ANCHOR TO WALL W/
FASTNERS @ 24" O.C.
FASTEN TO WD. NAILER @ 24" O.C.
22 GA. GALV. WIND CLIP, CONT
FASTEN AT 6" O.C.
1 LAYER 15# FELT CONT, LAP EA.
JOINT MIN. 6".SEAL ALL JOINTS W/
MASTIC
24 GA. STL COPING W/ KYNAR FIN -
COLOR AS SELECTED BY ARCH
CONT SEALANT
ATTACH WD BLOCKING ASSEMBLY
TO STL CHNL @ 16" O.C. W/ HILTI TI
S-WW 12-24x2-1/2" PFH #4 WINGS
FASTENERS COUNTERSINK AS
REQ'D
VERT STL CHNLS @ 4'-0" O.C., REF
STRUCT, INFILL W/ 6" MTL STUDS @
16" O.C., FILL W/ BATT INSUL
REF WALL SECTION
6"
2" M
IN
6"
2" M
IN
'Z' CLIP @
16" O.C. OVER 2"
RIGID INSUL. (R-20) BOARD.
METAL PANEL SYSTEM
CONT SEALANT
1
1
Sheet No.Job No.
Drawn By:
Date:
Pro
ject
:
Copyright © 2018, Huckabee & Associates, Inc.
PACKAGE
C:\
Use
rs\r
rod
pra
cha\
Do
cum
ents
\178
0-02
-01
AU
BR
EY
INT
ER
ME
DIA
TE
_AR
CH
_v17
_rro
dp
rach
a.rv
t
9/12
/201
8 4:
29:1
7 P
M
CG
A7.4
TYPICAL ROOFING
DETAILS BUILT-UP
ROOFING
8/27/18
1780-02-01
AU
BR
EY
MID
DLE
SC
HO
OL
AD
DIT
ION
FOR
AU
BR
EY
I.S
.D.
AU
BR
EY
, TE
XA
S
1
1/8" = 1'-0"1TYP LADDER ELEVATIONS
1 1/2" = 1'-0"5TYP CONCRETE SPLASH BLOCK
3/4" = 1'-0"2ROOF LADDER DETAIL
3/4" = 1'-0"3TYP LADDER SIDE ELEVATION
1 1/2" = 1'-0"4TYP BOLT PATTERN FOR 2X CAP NAILER
1" = 1'-0"8SHT MTL DOWNSPOUT BOOT ELEV'S @ GRADE
1 1/2" = 1'-0"9TYP DOWNSPOUT BOOT DETAIL (MTL BLDGS)
1 1/2" = 1'-0"7TYP EQUIPMENT SUPPORTS
3" = 1'-0"10PARAPET @ EJ NEW CMU TO EXIST WALL
N.T.S.11
INSIDE CORNER ICF / BRICK 1 1/2" = 1'-0"12EJ @ EXIST HIGH WALL W/ BRICK
1 1/2" = 1'-0"13EJ @ EXIST HIGH WALL W/ METAL PANEL
3" = 1'-0"6TYP PARAPET CAP DETAIL - MTL STUD
Rev
isio
n /
Dat
e
10
9/1
2/ 1
8A
DD
EN
DU
M #
1
���
09/13/2018
![Page 16: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/16.jpg)
8" 8" 8"
MASONRY CONTROL JOINT -
EXTEND AND SEAL FULL HEIGHT OF
WALLCEILING LINE
DOOR REF.
SCHEDULE
DOOR FRAME
REF. SCHEDULE
LOCATION OF MASONRY CONTROL
JOINT IN BRICK CONSTRUCTION
CMU BOND BEAM - FILL W/
GROUT & 2 #5'S BOT. (REF.
TYP. INT. MAS. DOOR HEAD
DETAIL)
CMU - FILL ONE CELL @ EA.
JAMB W/ GROUT & #5 FROM FLR.
TO BOT. OF CMU BOND BEAM.
STOP REINF. 2" BELOW MASONRY
JT. WHERE WINDOW DOES NOT
OCCUR.
PROVIDE CONTROL
JOINTS BELOW
JAMBS AT
BORROWED LITES
AND SIMILAR
OPENINGS.
8"8"
DRYWALL & ICF MASONRY
MASONRY CONTROL JOINT -
EXTEND AND SEAL FULL HEIGHT
OF WALL
CEILING LINE
LOCATION OF MASONRY
CONTROL JOINT IN BRICK
CONSTRUCTION
CMU BOND BEAM - FILL W/
GROUT & 2 #5'S BOT. (REF.
TYP. INT. MAS. DOOR HEAD
DETAIL)
CMU - FILL ONE CELL @ EA.
JAMB W/ GROUT & #5 FROM
FLR. TO BOT. OF CMU BOND
BEAM. STOP REINF. 2" BELOW
MASONRY JT.
PROVIDE CONTROL
JOINTS BELOW
JAMBS AT
BORROWED LITES
AND SIMILAR
OPENINGS.
C.J. @
GYP BOARD (FULL
HEIGHT OF WALL)
CO
NTR
OL
JOIN
T
CO
NTR
OL
JOIN
T
CO
NTR
OL
JOIN
T
CO
NTR
OL
JOIN
T
ROOM TITLE
SIGN
ON LATCH
SIDE OF DOOR
OR ADJACENT
TO ACTIVE
LEAF OF
DOUBLE DOORS
CEILING LINE
DOOR REF.
SCHEDULE
DOOR FRAME
REF. SCHEDULE
3/8"
CR
ITIC
AL
48" M
IN
3/8"
CR
ITIC
AL
9"
60" M
AX T
O B
TM O
F TO
P TE
XT
48" M
IN T
O B
TM O
F TE
XT
CL
60" M
AX
ROOM TITLE SIGN
ON LATCH SIDE
OF DOOR OR
ADJACENT TO
ACTIVE LEAF OF
DOUBLE DOORS
CEILING LINE
DOOR REF.
SCHEDULE
DOOR FRAME
REF. SCHEDULE
3/8"
CR
ITIC
AL
CL
60" M
AX T
O B
TM O
F TO
P TE
XT
48" M
IN T
O B
TM
9"
NOTE: PROVIDE NON-SLIP
FLOORING OR SURFACE
AT ALL RAMPS
1-1/2" STL PIPE WALL
RETURN TYP. EA. END -
REF. TYP. DETAIL THIS SHT
FIN. FLR.
SLOPE
1-1/2" STD. STL. PIPE HANDRAIL - GRIND
ALL WELDS SMOOTH AND PREPARE SURFACE
AS REQ'D FOR FIN CODE 100 FOR
EXTERIOR AND CODE 104 FOR INTERIOR.
/6
A9
.1
1' - 0" REF FLOOR PLAN FOR RAMP LENGTH 1' - 0"
2' - 1
0"
2' - 1
0"
STL WALL MOUNT @ 4'-0" O.C. MAX
LINE OF WALL - REF. FLOOR PLAN
FOR CONSTRUCTION TYPE.
ATTACH TO WALL PER
MANUF. REQUIREMENTS.
1-1/2" STD. STL. PIPE WALL
RETURN FIN. TO
CODE 104.
1-1/2" STD. STL. PIPE HANDRAIL
SMOOTH AND PREPARE SURFACE
AS REQ'D FOR FIN. CODE 104.
/6
A9
.1
2 1/
2"
C L RE
F S
PE
C S
EC
REINF. WALL AS REQ'D. TO
PROPERLY SUPPORT HANDRAIL
-PROVIDE BLOCKING @ DRYWALL
AND GROUT CELLS @ MASONRY
WALLS.
WALL BRACKETS @ 4'-0" O.C. FIN.
TO CODE 104.
HANDRAIL SHALL BE 1-1/2" DIA.
STD. STL. PIPE - FIN. TO CODE
104.
WALL- REF. FLOOR PLAN
FOR CONSTRUCTION TYPE.
0141
00 F
OR
HE
IGH
T
1 1/2"
RUBBER BASE
SERVICE SINK
.075" THICK FIBERGLASS
REINFORCED PLASTIC PANEL ON
CEMENT BACKING BD CONT WITH GYP
BD ABOVE PLASTIC PANEL. INSTALL
PER MFG INSTRUCTIONS W/ ALUM
EDGE AND CORNER
TRIMS AND BULLNOSE TOP TRIM
SERVICE SINK FAUCET.
4"4'
-0"
SEALANT
NOTE:
F.R.P. PANELS NOT REQUIRED
WHEN SERVICE SINK ABUTS
MASONRY WALLS.
HOLD CEMENT BOARD UP 1"
OFF FLOOR IN THIS ROOM AND
PROVIDE SEALANT
PROVIDE SEALANT AT
PERIMETER
FLOORING AS SCHED.
6'-0" 6'-0"
1/2" MIN.
PIPE 1-1/2" STD STL
RAILING CONT, OMIT
HANDRAIL WHERE NOT
REQ'D. GRIND ALL
JOINTS SMOOTH FIN TO
CODE 100
VERT PIPE STANDARDS
@ 4'-0" O.C. MAX
NOTE:
FIN. ALL METAL SURFACES TO CODE
104 (INTERIOR), OR CODE 100
(EXTERIOR) CORE CONC AFTER C.T.,
Q.T. HAVE BEEN INSTALLED. INSTALL
V.C.T. & CARPET AFTER POST
INSTALLED.
6" M
IN2'
- 10"
5"1'
- 0"
6"
1/2" MIN.
6" M
IN4'
- 0"
5"
6"
HANDRAIL GUARDRAIL
PIPE 2" STD STL T&B, REF
ELEV, GRIND ALL JOINTS
SMOOTH FIN TO CODE 100
OR 104
PIPE 3/4" STD STL PICKETS
@ 4 3/4" O.C., REF ELEV'S
2' - 1
0"
1 1/2"
CORE CONC (INSERTS
NOT PERMITTED) &
PROVIDE EPOXY
GROUT BY W.R.
MEADOWS EG-96 HP OR
EQUAL (MOUNDING UP)
ALL AROUND & UNDER
EA VERT PIPE
2"
2"2"
2"2"
ATTACH BRACKET TO PANEL
@ 8" O.C. REINF. PANEL AT
ATTACHMENT FOR PANELS
LARGER THAN 4'-0" X
4'-0". STOP PANEL
BRACKETS 3" SHORT OF
PANEL EACH END.
ACOUSTIC PANEL
LINE OF WALL
WALL BRACKETS MASONRY
WALL :
GYPSUM BOARD PARTITIONS:
Z-BAR BRACKETS
ALL ATHLETIC SPACES:
PROVIDE (2) 2"X2"X6" LONG ALUM.
WALL BRAKETS AT EA.PANEL TO BE
INSTALLED TO PREVENT PANEL
MOVEMENT OR DISLODGING DUE TO
OBJECTS STRIKING PANELS. INSTALL
4" FROM END OF PANEL. PAINT
VERTICAL LEG ALL BRAKETS TO
MATCH ADJACENT WALL SURFACES.
CONTINUOUS .08 THICK X 4"X 1/4"
ALUM. Z-BARS TOP AND BOTTOM
FOR PANELS 4'X4' OR SMALLER.
PROVIDE TOP,INTERMEDIATE AND
BOTTOM Z-BARS FOR PANELS
LARGER THAN 4'X4'. STOP Z-BARS
2" SHORT OF EA. PANEL END AND
PROVIDE Z-BAR END CLOSURES
TO PREVENT PANEL FROM
SLIDING OFF.
SECURE TO WALL W/ 3/8" MIN.
EXPANSION BOLTS NOT TO
EXCEED 12" O.C. ACOUSTICAL
PANELS 48" WIDE REQUIRE
FOUR BOLTS MIN. PER Z-BAR
PROVIDE 1/2" PLYWOOD OR 16
GA. METAL BLOCKING
BETWEEN STUDS @ EA. Z-BAR
FOR SUPPORT OF ACOUSTICAL
PANELS. SCREW Z-BAR TO
BLOCKING AND STUDS @ 12"
O.C. ACOUSTICAL PANELS 48"
WIDE REQUIRE FOUR BOLTS
MIN. PER Z-BAR.
1/4"
1/4"
1/4"
1/4"
HORIZONTAL REINF.
BOND BREAK MATERIAL.
FACE BRICK.
WEATHER BARRIER.
ACMU.
RAKE JOINT BACK 3/8"
AND SEAL WITH
SEALANT.
CMU, FILL INT W/ FOAM
IN PLACE INSUL.
REF PLANS/ELEVS. (OTHERWISE 1'-4")
WEATHER BARRIER
RAKE JOINT BACK 1/2" - PROVIDE BACKER
ROD & CONT SEALANT - (CONT VERT)
PROVIDE BACKER
ROD AND SEALANT
- CONT. VERT.
OFFSET CMU CONTROL JOINT 16" FROM
FACE BRICK E.J. OR AS DIRECTED BY
ARCHITECT
FACE BRICK
REF. STRUCT. FOR REINF.
AND GROUTING
REQUIREMENTS.
KEEP HEAD JOINT @ FACE BRICK
EXPANSION JOINT FREE OF ANY
FOREIGN MATERIAL.(EXCEPTION - FILL
JOINT IN FIREWALL W/ CERAMIC FIBER
BLANKET)
REF
PLAN
1
16" MIN.
REF. PLUMB. FOR ALL FLOW LINE
ELEVATIONS. COORDINATE
WATERPROOFING W/ FOUNDATION.
4" SCH. 40
PERFORATED PIPE -
REF. PLUMB'G & CIVIL
12" DEEP MIN. -
CLEAN COARSE GRAVEL.
DRAINAGE MAT OVER
WATERPROOFING MEMBRANE,
COVER FULL HT OF FOUNDATION
WALL
GEOTECH FILTER FABRIC -
OVERLAP 1'-0" MIN.
BACKFILL BY G.C.
TRENCH BY G.C.
4" SAND CUSHION
Sheet No.Job No.
Drawn By:
Date:
Pro
ject
:
Copyright © 2018, Huckabee & Associates, Inc.
PACKAGE
C:\
Use
rs\r
rod
pra
cha\
Do
cum
ents
\178
0-02
-01
AU
BR
EY
INT
ER
ME
DIA
TE
_AR
CH
_v17
_rro
dp
rach
a.rv
t
9/12
/201
8 4:
29:1
7 P
M
CG
A9.1
TYPICAL DETAILS
8/27/18
1780-02-01
AU
BR
EY
MID
DLE
SC
HO
OL
AD
DIT
ION
FOR
AU
BR
EY
I.S
.D.
AU
BR
EY
, TE
XA
S
1
1/2" = 1'-0"4TYP CONTROL JOINT @ DOOR FRAME- MASONRY
1/2" = 1'-0"9TYP CONTROL JOINT @ WINDOW FRAME - MASONRY, DRYWALL & ICF
1/2" = 1'-0"5TYP SIGNAGE LOCATION
1/2" = 1'-0"10TYP. SIGNAGE LOCATION
1/2" = 1'-0"1TYP. WALL MOUNTED RAMP HANDRAIL ELEV. -STL. PIPE
3" = 1'-0"7TYP. DETAIL OF WALL RETURN - STL. PIPE
3" = 1'-0"6TYP WALL MOUNTED HANDRAIL - STL. PIPE
1/2" = 1'-0"12TYP. WALL FINISH AT SERVICE SINK AT DRYWALL PARTITIONS
1" = 1'-0"2TYP HANDRAIL / GUARDRAIL STL PIPE
3" = 1'-0"3TYP DETAIL OF ACOUSTIC WALL PANEL CONNECTION
3" = 1'-0"11TYPICAL BOND BREAK @ BRICK TO ACMU
1 1/2" = 1'-0"8TYP CMU / BRICK WALL C.J.
Rev
isio
n /
Dat
e
10
9/1
2/ 1
8A
DD
EN
DU
M #
1
1 1/2" = 1'-0"13TYPICAL SUB SOIL DRAIN DETAIL
���
09/13/2018
![Page 17: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/17.jpg)
Project Name: Aubrey MS AdditionClient: Aubrey ISDAubrey, TexasProject Number: 1780-02-01
Mechanical Items ForAddendum No. #
Page 1 of 1
MECHANICAL ITEMS FOR ADDENDUM NO. 1NOTICE TO PROPOSERS:
A. This Addendum shall be considered part of the contract documents for the above-mentioned project as though it had been issued at the same time and incorporated integrally therewith. Where provisions of the following supplementary data differ from those of the original contract documents, this Addendum shall govern and take precedence.
B. Proposers are hereby notified that they shall make any necessary adjustments in their estimate on account of this Addendum. It will be construed that each Proposer’s proposal is submitted with full knowledge of all modifications and supplemental data specified therein. Acknowledge receipt of this addendum in the space provided on the proposal form. Failure to do so may subject Proposer to disqualification.
REFERENCE IS MADE TO THE DRAWINGS AND THE PROJECT MANUAL AS NOTED:
PROJECT MANUAL:
AD No 1, Mech. Item 1: To the Project Manual, Sections as listed below, Part 2 – Products;Products listed herein are considered acceptable for conformance with the design concept of the project and general compliance with the information given in the contract documents. The manufacturer, supplier and installer are responsible for meeting all requirements given in the contract documents unless specifically noted in the written approval.
1) Replace Section 23 0923, “Expansion of Direct Digital Control Systems,”
END OF MECHANICAL ADDENDUM
L
I C E N SE
D
58432
D.J. PENN
S
TATE OF TEXA
S
![Page 18: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/18.jpg)
Aubrey ISD – Aubrey Middle School Addition (1780-02-01)Aubrey, Texas
Image Engineering Group, Ltd. 23 0923 - 1EXPANSION OF EXISTING DIRECT DIGITAL CONTROL SYSTEMS
SECTION 23 0923 EXPANSION TO EXISTING DIRECT DIGITAL CONTROL SYSTEMS
(BY OWNER’S ALLOWANCE)
PART 1. - GENERAL
1.01 GENERAL
A. Refer to Section 23 0500 - GENERAL REQUIREMENTS FOR MECHANICAL Work.
B. Refer To Section 23 0501 for Warranty and Quality Assurance Requirements.
C. Refer to Section 23 7440 for ROOFTOP PACKAGE – GAS HEAT requirements.
1.02 SCOPE OF WORK
A. Expand existing building automation system as required for the installation of a complete electronic system of temperature control for heating, ventilating and air conditioning exclusive of temperature controls specified and furnished with packaged equipment as indicated in the mechanical plans for the addition areas. . The temperature control contractor shall furnish and install all temperature control equipment as described in this specification.
B. Provide system expansion components as required for the full expansion including enclosures, expansion cards and related devices and components.
C. Remove existing control system components and wiring, and install new system devices, temperature sensors, wiring, power supplies, enclosures and all other required system components as needed for a complete system in renovated areas as shown on plans.
D. The system shall be complete with all required wiring, conduit, electric actuators, control dampers, control valves sensors, relays and all other temperature control devices required for a complete and operating system.
E. All controls and accessories shall be installed by the temperature control contractor with the exception of valves, dampers, thermowells, and water taps. Electrical starters and disconnects shall be furnished and installed by other trades per Division 26.
F. Personnel in the direct employ of the temperature controls contractor shall perform all wiring required for the operation of the control system. Supply complete wiring diagrams for the control system and perform all necessary set-up and calibration labor. This work shall include the interlock and control wiring as described herein. All wiring shall conform to the methods and materials described in Section 16 of these specifications and comply with all NEC, state, and local codes included by reference herein.
G. After completion of the installation, the temperature control supplier shall adjust damper actuators, linkages, and other equipment provided under this section, place them in complete operating condition, and demonstrate to the architect and owner that the controls are working satisfactorily. The contractor shall provide 8 hours of instruction for the owner’s personnel in the proper operation of the control system.
![Page 19: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/19.jpg)
Aubrey ISD – Aubrey Middle School Addition (1780-02-01)Aubrey, Texas
Image Engineering Group, Ltd. 23 0923 - 2EXPANSION OF EXISTING DIRECT DIGITAL CONTROL SYSTEMS
H. All products used in this installation shall be new, currently under manufacture, and shall be applied in similar installations for a minimum of 2 years. This installation shall not be used as a test site for any new products unless explicitly approved by the owner's representative in writing. Spare parts shall be available for at least 10 years after completion of this contract
1.03 APPROVED CONTROL SYSTEMS
A. Approved Control Systems:
1. Allerton Controls,a. By Climatec
1.04 QUALITY ASSURANCE
A. System Installer Qualifications
1. The Installer shall have an established working relationship with the Control System Manufacturer of not less than five (5) years.
2. The Installer shall have successfully completed Control System Manufacturer's classes on the control system. The Installer shall present for review the certification of completed training, including the hours of instruction and course outlines upon request.
3. The Installer shall provide 24 hour response in the event of a customer call.
B. Codes and Standards: Meet requirements of all applicable standards and codes, except when more detailed or stringent requirements are indicated by the Contract Documents, including requirement of this Section.
1. Underwriters Laboratories (UL): Products shall be UL-916-PAZX listed.2. National Electrical Code (NEC) - NFPA 70.3. Federal Communications Commission (FCC) - Part J.4. ASHRAE/ANSI 135-1995 (BACnet).
1.05 SUBMITTALS
A. Contractor shall provide shop drawings or other submittals on all hardware and software to be provided. No work may begin on any segment of this project until submittals have been reviewed by the Engineer and Owner for conformity with the plan and specifications design intent. Six (6) copies are required. All shop drawings shall be done on AutoCAD, and provided to the Owner on CD-ROM.
B. Project Record Documents: Upon completion of installation submit three (3) copies of record (as-built) documents. The documents shall be submitted for approval prior to final completion and include:
1. Project Record Drawings - These shall be as-built versions of the submittal shop drawings. One set of magnetic media including CAD .DWG or .DXF drawing files shall also be provided.
2. Testing and Commissioning Report and Checklists.3. Operating and Maintenance (O&M) Manual - These shall be as-built versions of the
submittal product data. In addition to that required for the submittals, the O&M manual shall include:
![Page 20: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/20.jpg)
Aubrey ISD – Aubrey Middle School Addition (1780-02-01)Aubrey, Texas
Image Engineering Group, Ltd. 23 0923 - 3EXPANSION OF EXISTING DIRECT DIGITAL CONTROL SYSTEMS
a. Names, address and 24-hour telephone numbers of Contractors installing equipment, and the control systems and service representative of each.
b. Operators Manual with procedures of operating the control systems including logging on/off, alarm handling, producing point reports, trending data, overriding computer control, and changing set points and other variables.
c. Programming Manual with a description of the programming language including syntax, statement descriptions including algorithms and calculations used, point database creation and modification, program creation and modification, and use of the editor.
d. Engineering, Installation and Maintenance Manual(s) that explains how to design and install new points, panels, and other hardware; preventative maintenance and calibration procedures; how to debug hardware problems; and how to repair or replace hardware.
e. A listing and documentation of all custom software created using the programming language including the point database. One set of magnetic media containing files of the software and database shall also be provided.
f. One set of magnetic media containing files of all color-graphic screens created for the project.
1.06 WARRANTY
A. Warrant all work as follows:
1. Labor and materials for control system specified shall be warranted free from defects for a period of 12 months after final completion acceptance by the Owner. Control System failures during the warranty period shall be adjusted, repaired, or replaced at no charge or reduction in service to the Owner. The Contractor shall respond to the Owner's request for warranty service within 24 hours during customary business hours.
2. All work shall have a single warranted start date even when the Owner received prior benefit due to early start-up. If the work specified is split into multiple contracts or a multi-phase contract, then each contract or phase shall have a separate warranty start date and period.
3. At the end of the final start-up/testing, if equipment and systems are operating satisfactorily to the Owner and Engineer, the Owner shall sign certificates certifying that the control system's operation has been tested and accepted in accordance with the terms of this specification. The date of Owner's acceptance shall be the start of warranty.
4. Operator work-station software, project specific software, graphics, database, and firmware updates shall be provided to the Owner at no charge during the warranty period. Written authorization by owner must, however, be granted prior to the installation of such changes.
PART 2. - PRODUCTS
2.01 COMMUNICATIONS NETWORK, PC, AND MODEM SUPPORT
A. The Communications network between buildings systems must be achieved by utilizing the existing Ethernet TCP/IP infrastructure.
B. Each facility will have a global controller with the communication network.
![Page 21: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/21.jpg)
Aubrey ISD – Aubrey Middle School Addition (1780-02-01)Aubrey, Texas
Image Engineering Group, Ltd. 23 0923 - 4EXPANSION OF EXISTING DIRECT DIGITAL CONTROL SYSTEMS
C. Coordinate with the Owner to obtain a computer (PC). They will provide the PC with a current operating system installed. The PC shall be located at the site. Location shall be as indicated on the plan. The DDC contractor shall install the PC and establish communications with the Global Controller (GC). The GC shall communicate with the stand alone Unitary Controllers (UC) located throughout the facility.
1. Software Configurationa. Remote authorized personal computers shall have access to the automation
system, and shall be able to communicate with and control the remote site even if the on-site PC is turned off or not functioning.
b. Upon failure of the LAN to communicate information, each controller will retain the last legitimate value of its imported network points, and continue to control the systems based on those values. Failure of any controller or any part of a controller on the LAN shall not affect the ability of the LAN to communicate among the remaining controllers.
2.02 GLOBAL CONTROLLER PANELS
A. Provide an independent, stand alone, microprocessor based control panel (Global Controller) for each facility. These panels shall communicate with the operator via the Main Communications Trunk – EIA-232C and/or EIA-485 and/or Ethernet (IEEE.802.2) with TCP/IP, using PC/Graphics Interface Software.
B. The controller shall reside on and communicate on the main LAN using either Ethernet (IEEE.802.3) with TCP/IP and/or EIA-485
C. In addition to main LAN communications, the controller shall support EIA-485 subLANs, PC, modem communications.
D. The controller shall have at least two ports (other than the PC port), which can be configured to BACnet conformance class 3 using TCP/IP or EIA-232 point-to-point communications for interface to other BACnet products
E. The Global Controller panel (GC) shall contain the necessary hardware and firmware to interface the building Unitary Controller Devices with the PC over the Main Communications Trunk, modem interface, existing Ethernet and the Internet (WWW) infrastructure utilizing IEEE.802.3 specifications with TCP/IP for off-site access to data and programming functions. Simply put, the GC controller plugs into the existing 10BaseT Capable Ethernet backbone. Configure the GC with customer provided masking, TCP/IP routers and addresses for each GC; the system works.
F. Each Global Controller panel shall be stand alone in a standard NEMA 1 enclosure. Any panels in cooling tower areas or that are located in chemical treatment areas shall be of stainless steel construction (Fiberglass enclosures rated for outside applications are acceptable). The electrical requirements shall be identified and coordinated by this Contractor. Any 110 VAC requirements are to be coordinated with Division 26 Contractor. 110 VAC power circuits to each panel shall be provided by the division 26 Contractor. Control panels shall be clearly identified by labels (1” lettering). Provide as-built wiring diagrams to indicate the control points on all equipment.
G. Each GC panel shall have a clock with battery back-up. Where there are multiple GC panels, the respective clocks shall be synchronized by the PC or a designated GC.
![Page 22: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/22.jpg)
Aubrey ISD – Aubrey Middle School Addition (1780-02-01)Aubrey, Texas
Image Engineering Group, Ltd. 23 0923 - 5EXPANSION OF EXISTING DIRECT DIGITAL CONTROL SYSTEMS
H. As many GC panels, as required, shall be furnished to provide the monitoring and control functions and capabilities specified. The panel shall be strategically located in areas of the building that are easily accessible for maintenance and repair.
I. The GC panels shall be directly interfaced by the main communications trunk using a peer-to-peer communications protocol or IEEE.802.3 with TCP/IP. The GC panel shall communicate without requiring a PC or remote modem device.
J. The GC panel shall have at least two digital inputs.
K. The trend log, schedules and alarms shall be located in the GC not the PC. The GC should have the capability to log all the information.
L. The GC shall have automatic protection from any power failure of at least twenty-four (24) hours duration.
M. During a power outage situation, the real-time clock continues to operate and the GC automatically restarts upon restoration of power.
N. Any Input, Variable, Schedule point shall have a user-definable, unique, system-wide logical point mnemonic.
2.03 UNITARY CONTROLLER PANELS
A. The manufacturer shall have multiple unitary controllers (UC) specifically designed for HVAC applications. The devices shall be stand-alone. The UC devices shall be able to interface with an operator and interface/room and/or zone sensor devices. The operator interface device shall allow the operator to adjust set points, initiate push-button actions, and receive feedback of temperature and/or status.
2.04 INPUT/OUTPUT (I/O) INTERFACE
A. To gather sensor data and interface with controlled equipment, the UC devices shall use I/O types consistent with the application for which it is designed. This design shall allow different types of points using any of the following input/output options:
B. Input Options (universal; analog or digital) - monitor the open/closed status of dry contacts, monitor analog values of voltages, current and resistance from temperature, pressure, relative humidity, CO2 sensors, etc.
C. Digital Outputs Options - control on/off, start/stop relays.
D. Analog Output Options - supply voltage or current outputs to controlled devices.
E. All I/O points must be universal (i.e. user definable as digital or analog). Dedicated analog/digital points will not be accepted.
F. Any Input, Variable, Schedule point shall have a user-definable, unique, system-wide logical point mnemonic
![Page 23: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/23.jpg)
Aubrey ISD – Aubrey Middle School Addition (1780-02-01)Aubrey, Texas
Image Engineering Group, Ltd. 23 0923 - 6EXPANSION OF EXISTING DIRECT DIGITAL CONTROL SYSTEMS
2.05 UNIVERSAL INPUTS (UI)
A. The Unitary Controller devices shall accept isolated contact closures (either normally open or normally closed contacts).
B. The Unitary Controller devices shall accept analog inputs (DC voltage, DC current, resistance).
C. Analog inputs can be linear or non-linear. Points shall include an A/D converter and an analog power supply. All points shall be wired to the UC device using #18 AWG twisted, shielded pair cables (Belden 8760 or equivalent) or larger or as recommended by the Control Manufacturer.
2.06 DIGITAL OUTPUTS (DO)
A. The digital outputs shall control on/off, start/stop relays which have low voltage coils. Dry contact, two position pilot voltage (0/12vDC), or triac outputs are acceptable. Common ground outputs are acceptable.
2.07 ANALOG OUTPUTS (AO)
A. The analog output supplies voltage or current to the control devices (i.e. damper actuator). All output points to valves and dampers shall read as a percent open. Signal types shall include 4-20 ma (into 1,000 Ohm load), resistance (up to 1,000 Ohms), and voltage (0-10 VDC).
2.08 GC AND UC OPERATOR CONTROL LANGUAGE
A. The Operator Control Language (OCL) will support the concept of output-oriented code allowing many small individual programs to be written and connected to graphic screens. Each output and/or calculation will have its own dedicated program and not be part of one larger program.
B. The DDC system shall have the capacity for timed start/stop on daily schedules, as well as the capability for the owner to develop and run user written application programs. For this, the DDC system shall have a proven OCL which shall be capable of reading the value and/or status of all system points and initiating both analog and digital control actions from any user defined combination of calculations and logical expressions, which shall at a minimum include:
1. Addition, subtraction, multiplication and division.2. Square roots, summations, absolute differences.3. IF THEN ELSE statements.4. Logical “not”, “and”, “or”, “less than”, “greater than”, and “equal to” or their
equivalents.5. Time delays in seconds, minutes or hours.6. Ability to imbed comments in system generated documentation.7. Ability to use time-of-day and day-of year in algebraic calculations.8. Ability to filter continuous small changes in input signals to prevent equally small
increment in output signals from occurring.
C. All of the above functions must be accomplished via software. FIRMWARE BASED FUNCTIONS WILL NOT BE ACCEPTED.
![Page 24: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/24.jpg)
Aubrey ISD – Aubrey Middle School Addition (1780-02-01)Aubrey, Texas
Image Engineering Group, Ltd. 23 0923 - 7EXPANSION OF EXISTING DIRECT DIGITAL CONTROL SYSTEMS
2.09 FROM WITHIN THE OCL PROGRAMMING EDITOR
A. Provide full screen editor to enable editing of the OCL programs source code down to character-by-character changes.
B. Provide the capability in the editor of accepting programs from ASCII files that have been created on other text editors and word processors.
C. If a point name is changed, all occurrences of that will point will automatically be changed, regardless of where the occurrence exists.
D. Provide cutting and pasting functions within editor, such that sections of OCL code from one program can be easily cut and pasted into a different OCL code on residing in another controller.
E. Provide debug utility that will indicate line of OCL containing structural or syntax error.
F. If OCL contains line number, provide automatic renumbering feature to sequentially renumber lines.
G. Provide the capability to automatically view value and/or status of points used within OCL code without exiting editor.
H. Provide at least TEN (10) unique local variables that can be declared for each individual OCL code.
2.10 SOFTWARE
A. The graphic software shall be based on Microsoft Windows 95, 98, ME, XP, 2000 and NT 4.0
B. Basic Interface Description
1. Operator workstation interface software shall minimize operator use and through the use of English language prompting. English language point identification and industry standard PC application software. The software shall provide, as a minimum, the following functionality:a. Real-time graphical viewing and control of environmentb. Scheduling and override of building operationsc. Collection and analysis of historical data and dynamic data (trend plot)d. Definition and construction of dynamic color graphic displays e. Editing, programming, storage and downloading of global controller databases
2. The software shall have a “simulator” mode that allows controllers to be fully programmed off-line without the need of any controller hardware.
3. Alarm reporting, routing, messaging, and acknowledgment4. Provide a graphical user interface that shall minimize the use of keyboard through the
use of a mouse or similar pointing device and “point and click” approach to menu selection.
5. The software shall provide a multi-tasking type environment that allows the user to run several applications simultaneously. The DDC software shall run on Microsoft Windows 95, 98, ME, XP, 2000 or NT 4.0. Other Windows applications shall run simultaneously with the DDC software. The mouse or Keyboard shall be used to quickly select and switch between multiple applications. The operator shall be able to work in Microsoft
![Page 25: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/25.jpg)
Aubrey ISD – Aubrey Middle School Addition (1780-02-01)Aubrey, Texas
Image Engineering Group, Ltd. 23 0923 - 8EXPANSION OF EXISTING DIRECT DIGITAL CONTROL SYSTEMS
Word, Excel, and other Windows based software packages, while concurrently annunciation on-line DDC alarms and monitoring information.
6. Provide functionality such that any of the following may be performed simultaneously on-line, and in any combination, via user-sized windows:a. Dynamic color graphics and graphic controlb. Alarm management, routing to designated locations, and customized messagesc. Week at a Glance Time-of-Day scheduling d. Trend data definition and presentatione. Historical Data Archiving to the local computer hard drivef. Graphic definition and constructiong. Program and point database editing on-lineh. Each system graphic group will accommodate 160 points.
7. Report and alarm printing shall be accomplished via Windows program manager, allowing use of network printers.
8. Provide a security system that prevents unauthorized use unless the operator is logged on. Access shall be limited to the operator’s terminal functions unless the user is logged on.
C. Each operator Terminal shall provide security for 124 users (minimum). Each user shall have an individual password. Each user shall be individually assigned which control functions and menu items the user has access to. All passwords, user names and access assignments shall be adjustable on-line, at the operator’s terminal. Each user shall also have a set security level that defines access to displays and also defines what individual points the user can control.
D. Operator Activity Tracking - An audit trail report to track system changes, accounting for individual user logons shall be printable and archived for future use. The operator activity tracking shall be in a tamper-proof buffer file.
E. Reports shall be generated on demand and directed to Computer workstation displays, printers or disk. As a minimum, the system shall allow the user to easily obtain the following types of reports:
1. A general listing of all or selected points in the networka. List of all points currently in alarmb. List of all points currently in override statusc. List of all disabled pointsd. List of all points currently locked oute. List of user accounts and access levels f. List all weekly schedules g. List of limits and dead-bands h. Excel reports i. System diagnostic reports including, list of DDC panels on line and
communicating, status of all DDC terminal unit device points
F. List of programs
1. Scheduling and override2. Provide a graphical spreadsheet-type format for simplification of time-of-day scheduling
and overrides of building operations. Schedules reside in DDC Global Controller to ensure time equipment scheduling when PC is off-line; PC is not required to execute time scheduling. Provide override access through menu selection or function key. Provide the following spreadsheet graphic types as a minimum:
![Page 26: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/26.jpg)
Aubrey ISD – Aubrey Middle School Addition (1780-02-01)Aubrey, Texas
Image Engineering Group, Ltd. 23 0923 - 9EXPANSION OF EXISTING DIRECT DIGITAL CONTROL SYSTEMS
a. Display of Weekly schedules shall show all information in easy to read 7-day (week) format for each schedule. This includes all on/off times for each day along with all optimum start information.
b. Holiday schedules shall show all dates that are to be holidays. Holidays shall be shown on the terminal in a graphical calendar format showing all scheduled days for a given month. User shall be able to easily scroll through the months for each year. Each day assigned as a holiday shall display as "All Off" or show "Scheduled" for that day.
c. Event schedules shall be shown in the same graphical calendar format and manner as Holiday schedules. Event schedules allow for scheduling of special events. After an event has elapsed, control returns to normal schedule.
d. Operator shall be able to change all information for a given Weekly, Holiday or Event schedule if logged on with the appropriate security access. This includes all information that has to do with optimum start including assignments such as sensors to use and heating/cooling factors.
e. Operator shall be able assign any unit to a group (i.e. classroom wing(s), administration, gym ect.) within the time scheduler. Operator shall also be able to initiate an override for any individual unit from the time scheduler graphic screen regardless of its assigned grouping.
f. Astrological Clock to optimize and control Exterior and Parking Lot Lighting.
G. Collection and Analysis of Historical Data
1. Provide trending capabilities that allow the user to easily monitor and preserve records of system activity over an extended period of time. Any system point may be trended automatically at time-based intervals or change of value, both of which shall be user-definable. Trend data may be stored on hard disk for future diagnostics and reporting. Additionally, trend data may be archived to network drives or removable disk media for future retrieval.
2. Trend data reports shall be provided to allow the user to view all trended point data. Reports may be customized to include individual point or predefined groups of at least six points. Provide additional functionality to allow predefined groups of up to 250 trended points to be easily transferred on-line to Microsoft Excel.
3. A minimum of six points may be graphed, regardless of whether they have been predefined for trending. The dynamic graphs shall continuously update point values. At any time the user may redefine sampling times or range scales for any point. In addition, the user may pause the graph and take “snapshots” of screens to be stored on the workstation disk for future recall and analysis. Exact point values may be viewed and the graphs may be printed.
4. System software shall be capable of graphing the trend log point data. Software shall be capable of creating x-y graphs that display up to 6 points at the same time in different colors. Graphs shall show point value relative to time.
5. Operator shall be able to change trend log setup information as well. This includes information to be trend logged as well as interval at which information is to be logged. All points in the system may be logged. All operations shall be password protected. Setup and viewing may be accessed directly from any and all graphics point is displayed on.
H. Alarm Indication
1. System Terminal shall provide audible, visual and printed means of alarm indication. The Alarm Dialog box shall always become the Top Dialog box regardless of the
![Page 27: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/27.jpg)
Aubrey ISD – Aubrey Middle School Addition (1780-02-01)Aubrey, Texas
Image Engineering Group, Ltd. 23 0923 - 10EXPANSION OF EXISTING DIRECT DIGITAL CONTROL SYSTEMS
application(s) being run at the time (such as a word processor). Printout of alarms shall be sent to the assigned terminal and port.
2. Provide log of alarm messages. Alarm log shall be archived to the hard disk of the system terminal. Each entry shall include point descriptor and address, time and date of alarm occurrence, point value at time of alarm, time and date of point return to normal condition, time and date of alarm acknowledge.
3. Alarm messages shall be in plain English (or specified language) and shall be user definable on site or via remote communication. System shall provide a minimum of 20 user definable messages for each zone controlled.
I. Controller Status
1. Provide means for operator to view communication status of all controllers connected to the system. Display shall include controller, status and error count. Status will show if controller is communicating or not.
J. Configuration/Setup.
1. Provide means for operator to display and change system configuration. This shall include but not be limited to system time, day of the week, date of day light savings set forward/ setback, printer type and port addresses, modem port and speed, etc. Items shall be modified utilizing easy to understand terminology using simple mouse/cursor key movements.
K. Dynamic Color Graphic Displays
1. Create Site Layout Color graphic including building penetration Icons, building floor plan displays with room temperatures and other building sensors values dynamically displayed. Icon links on the floor plans will allow penetration to the building Mechanical equipment. Provide System graphics for each piece of mechanical equipment, including air handling units, chilled and hot water systems as applicable, with dispersed dynamic data as indicated in the system point I/O summary of this specification. Points required by the sequence of operations shall also be displayed even if they are not defined by the I/O schedule to optimize system performance analysis and speed alarm recognition. All points associated with a device shall be able to be changed from its associated graphic screen (set points, time schedules etc.) Provide as a minimum the following graphics.a. Site layoutb. Building Floor plansc. Individual Heat Pump graphics, clicking on the device will display all data
associated with the device.d. EF shall be shown on the floor plans, clicking on the device will display all data
associated with the device. e. All space temperatures (all space temperatures for the entire school will be
displayed on one graphic)f. All status graphic (status of all equipment connected to the system shall be
displayed on one graphic)g. All alarm graphic (all system alarms will be displayed on one graphic screen)h. All graphics will provide in addition to the system points the Outside air
temperaturei. The operator interface shall allow users to access the various system schematics
and floor plans via a graphical penetration scheme, menu selection or text-based
![Page 28: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/28.jpg)
Aubrey ISD – Aubrey Middle School Addition (1780-02-01)Aubrey, Texas
Image Engineering Group, Ltd. 23 0923 - 11EXPANSION OF EXISTING DIRECT DIGITAL CONTROL SYSTEMS
commands. Graphics software shall permit the importing of *.BMP or *.TIF drawings for use in the system.
j. Dynamic temperature values, humidity values, flow values and status indication shall be shown in their actual respective locations and shall automatically update to represent current conditions without operator intervention and without pre-defined screen refresh rates.
k. Analog values displayed in 3 color conventions shall be available for monitor and control of analog values; high and low alarm limit settings shall be displayed on the analog scale or available and displayed separately. The user shall be able to “click and drag” the pointer to change the set point.
2. Provide the user the ability to display blocks of point data by defined point groups; alarm conditions shall be displayed by flashing point blocks.
3. Equipment state can be changed by clicking on the point block or graphic symbol and selecting the new state (on /off) or set point.
4. Colors may be used to indicate status and change as the status of the equipment changes. The state colors shall be user definable. (Example: Red-Alarm, Green-OK).
5. The windowing environment of the PC operator workstation shall allow the users to simultaneously view several applications at a time to analyze total building operation or to allow the display of a graphic associated with an alarm to be viewed without interrupting work in progress.
2.11 TEMPERATURE SENSORS
A. ELECTRONIC SPACE TEMPERATURE SENSORS
1. Electronic space temperature sensors shall be microprocessor based and shall be calibrated to less than or equal to a 1/4 degree F resolution for the specific application.
2. Electronic space temperature sensors shall have a minimum of six programmable buttons and two dedicated buttons for set-point adjustment and a LED display.
3. Electronic space temperature sensors shall have a built-on RJ11 connector that will allow access via laptop computer to the host network.
4. Electronic space temperature sensors shall have the ability to have up to 16 sensors connected to any global controller with all buttons on sensors fully programmable.
B. ELECTRONIC TEMPERATURE SENSORS
1. Temperature sensors shall be thermistors or transducer based and shall be calibrated to less than or equal to a 1/4 degree F resolution for the specific application. The Engineer must approve substitutions. All sensors to be field verified as correct.
2. Provide twisted pair lead wires and shield for input circuit or as otherwise required by the manufacturer.
3. Use insertion elements in ducts not affected by temperature stratification or smaller than one square meter. Use averaging elements where larger or prone to stratification. Sensor length 2.5 m or 5 m as required.
2.12 CO2 SENSORS
A. Electronic space CO2sensors shall be microprocessor based and shall be calibrated to less than or equal to a 5 ppm resolution for the specific application.
B. Electronic space temperature sensors shall have a built-on RJ11 connector that will allow access via laptop computer to the host network.
![Page 29: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/29.jpg)
Aubrey ISD – Aubrey Middle School Addition (1780-02-01)Aubrey, Texas
Image Engineering Group, Ltd. 23 0923 - 12EXPANSION OF EXISTING DIRECT DIGITAL CONTROL SYSTEMS
C. Electronic CO2 sensors shall have the ability to have up to 16 sensors connected to any global controller.
2.13 DAMPER ACTUATORS (Furnished by Controls Contractor, installed by Mechanical Contractor)
A. Damper actuators shall be of the electronic type as manufactured by Siemens. Size actuators for smooth operation and fast response. Where required for the application, furnish spring return actuators.
2.14 PRODUCT OF COMBUSTION DETECTORS (SMOKE DETECTORS)
A. Smoke detectors shall be furnished and installed as part of other Divisions scope of work.
2.15 WELL FIELD WATER TEMPERATURE AND PRESSURE
A. Provide immersion temperature sensors to monitor supply and return water temperature per well field loop.
B. Provide pressure sensors to monitor supply and return water pressure per well field loop.
PART 3. - EXECUTION
3.01 SEQUENCE OF OPERATION (See Part 4)
A. The sequence of operation shall be used in conjunction with the attached Point Input/Output Summary. Points not indicated in the Input/Output Summary but described in the sequence of operation shall be provided.
3.02 SYSTEM PROGRAMMING
A. All programming shall be coordinated with and approved by the owner.
3.03 INSTALLATION
A. Upon completion of installation the temperature control contractor shall make all final adjustments to the system as may be required by actual operating conditions. All throttling range adjustments shall be set as narrow as possible without causing “hunting”.
B. Setpoints and setup amounts shall be such to provide satisfactory operation under load conditions.
C. The operating personnel shall be instructed in the preventive maintenance procedures and in the operating of the control system.
D. The temperature control contractor shall submit a letter stating that the system has been installed under supervision of the temperature control contractor and that the system has been properly adjusted, tested and is fully operational in accordance with the desired sequence of operation.
![Page 30: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/30.jpg)
Aubrey ISD – Aubrey Middle School Addition (1780-02-01)Aubrey, Texas
Image Engineering Group, Ltd. 23 0923 - 13EXPANSION OF EXISTING DIRECT DIGITAL CONTROL SYSTEMS
E. Upon completion of the work and acceptance by the Owner, factory representatives under the direct employment of the temperature control contractor shall provide sixteen hours of instruction to three of the Owner’s operating personnel who responsibility for the mechanical and control systems. Training shall include walk thru focusing on controller locations, a graphic page orientation, as well as an introduction to the project’s specific addressing and scheme and database.
PART 4. - SEQUENCE OF OPERATIONS
1.01 ROOFTOP UNITS
A. Unoccupied Operation: In the unoccupied mode the unit shall be shut off. If the space temperature as sensed by the zone sensor falls above or below the unoccupied set point, the compressor, fan, and reversing valve shall be energized based on the need for either heating or cooling until the unoccupied set point is reached. Outside Air Damper shall be maintained shut at all times during Unoccupied Mode.
B. Night Set Back: Change of operating set points at night/Unoccupied periods when larger extremes of space temperature shall be tolerated to save operating expense. If the zone temperature exceeds either the Unoccupied heating or cooling set point by the allowable deadband for that setpoint, the unit shall attempt to satisfy the unoccupied conditions.
C. Zone Temperature: Each zone sensor offered shall have a microprocessor type element to measure the actual zone temperature.
D. Transition from Unoccupied to Occupied: When the HVAC unit units transition from the Unoccupied mode to the Occupied mode, morning warm-up or morning cool-down and random start programs shall be activated.
E. Morning Warm-up: When there is a call for heating and the zone temperature is 20° F off setpoint, a morning warm-up shall be initiated. The compressor and the fan shall be turned on. When the zone temperature reaches the heating setpoint, the unit shall operate in the Occupied mode.
F. Morning Cool-down: When there is a call for heating and the zone temperature is 20° F off setpoint, a morning cool-down shall be initiated.
G. Random Start: Random start of the unit on electric power up is intended to prevent all units in a building from energizing major loads at the same time. The fan and compressor start shall be delayed from 3 to 32 seconds when power has been either restored after a loss or outage, or after the unit is enabled. If there is no call for cooling or heating, or if no fan operation is required during the delay, the time delay shall be allowed to time out. A random number generator in software shall be used to generate the delay.
H. Occupied Heating/Cooling Operation: The unit shall operate to maintain the setpoint. When there is a call for cooling or heating, the zone temperature shall be compared with the outdoor air temperature.
I. Heat/Cool Setpoint and Mode: The space temperature cooling setpoint shall be determined either by a local setpoint, the unitary controller default setpoint, or BAS control. If the BAS is not communicating, the local zone sensor control. (verify set points with owner)
![Page 31: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/31.jpg)
Aubrey ISD – Aubrey Middle School Addition (1780-02-01)Aubrey, Texas
Image Engineering Group, Ltd. 23 0923 - 14EXPANSION OF EXISTING DIRECT DIGITAL CONTROL SYSTEMS
J. The cooling setpoint shall be limited by adjustable parameters in the unitary controller or the BAS to prevent it from being set too high or low. The heating setpoint shall be a unitary controller calculated setpoint and shall be limited to a value less than or equal to the cooling setpoint. The transition from heat to cool shall be based on the time between setpoint changes. In the Unoccupied mode, the setpoints shall be widened to accommodate night setback and are adjustable. (verify set points with owner)
1. Multiple Units Serving a Single Zone:a. One (lead) unit is in 1st stage cooling, and the other is in fan only.
(1) Both units are in 1st stage cooling. b. One (lead) unit is in 2nd stage cooling, the other is in 1st stage cooling.
(1) Both units are in 2nd stage cooling.
K. Fan Operation:
1. The supply air fan shall operate at the appropriate speed (on, high, or auto) in the Occupied mode. During the Occupied mode if on, low, or high is selected, the fan shall operate continuously. When the fan switch is in the auto position, the fan shall be cycled with compressor operation and shall be turned off 30 seconds after the compressor shuts off (for both Occupied and Unoccupied mode). Units equipped with the fan status option shall shut down the unit and indicate an alarm at the BAS if the fan output and fan status do not match after a verification delay of 30 seconds.
L. Outside Air Damper Operation:
1. Unoccupied Mode: Remains shut at all times during unoccupied mode.2. Occupied Mode: Open when fan is running (energized), closed when fan is not running.
M. Modulating Outside Air Damper Operation: (Cafeteria, Gym, Auditorium Units)
1. Unoccupied Mode: Remains shut at all times during unoccupied mode.2. Occupied Mode: Energized when fan is running (energized), closed when fan is not
running. Damper shall modulated based on signal from CO2 Sensors to maintain level of 1200 ppm (adjustable) maximum in space.
N. Compressor Operation:
1. Compressor operation shall be cycled based upon load conditions as sensed by a zone or discharge air temperature sensor.
O. Reversing Valve Operation:
1. A contact closure output shall be used to control the reversing valve state. The reversing valve shall be energized in the cooling mode. Once the valve is energized for cooling it shall stay energized until a heating cycle is initiated and/or once the valve is energized for heating it shall stay energized until a cooling cycle is called for. The reversing valve operation shall be delayed after compressor shutdown to reduce noise due to refrigerant migration. In the event of a power failure the reversing valve shall fail to the heating mode.
![Page 32: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/32.jpg)
Aubrey ISD – Aubrey Middle School Addition (1780-02-01)Aubrey, Texas
Image Engineering Group, Ltd. 23 0923 - 15EXPANSION OF EXISTING DIRECT DIGITAL CONTROL SYSTEMS
P. Unit Protection: The following shall be provided integral with respective unit, by equipment manufacturer, as standard unit protections as listed:
1. Compressor Cycle Limit a. The compressor operated with minimum 3 minute on and 3 minute off cycles to
maintain oil return for extended life of the compressor.2. Reversing Valve Delay
a. The reversing valve delay is inherent due to the compressor cycle limit. The delay prevents the reversing valve from changing positions against the large differentials in refrigerant pressures during the change from cooling to heating and visa versa, eliminating the noise normally heard due to refrigerant migration.
3. Low Pressure Cutout a. The low-pressure switch is a normally closed switch that opens to lock out the
compressor under low refrigerant circuit pressure conditions (7 psi). On multiple circuit units each circuit has a low-pressure cutout. If a circuit is locked out due to low pressure the remaining circuits shall continue to operate.
4. High Pressure Cutout a. The high-pressure switch is normally a closed switch that opens under high
refrigerant circuit pressure conditions (395 psi), which shall lockout the compressor. The high-pressure switch is wired in series with the compressor contactor coil. On multiple circuit units each circuit has a high-pressure cutout. If a circuit is locked out due to high pressure the remaining circuits shall continue to operate.
5. Freezestat Protection a. The freezestat protection is intended to sense and prevent water coil freeze up for
low water temperature conditions. A low temperature condition is intended to stop and lockout compressor operation until a manual reset of the control is done.
6. Condensate Overflow a. A condensate overflow means the switch in the condensate pan has sensed the
pan is full and requires servicing. When opened, the condensate overflow switch shall lock out the compressor and fan.
7. Compressor Time Delaya. Compressor operation shall be overridden by a preset 3 minute minimum on/off
time delay in order to maintain oil return when the unit is either initially energized, manually reset, switched between modes, or cycled within a single mode.
4.01 EXTERIOR AND PARKING LOT LIGHTING
A. The Exterior and Parking Lot Lighting shall operate on time schedule optimized by an astrological clock.
END OF SECTION
SEE ATTACHED POINT INPUT/OUTPUT SUMMARY
![Page 33: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/33.jpg)
Aubrey ISD – Aubrey Middle School Addition (1780-02-01)Aubrey, Texas
Image Engineering Group, Ltd. 23 0923 - 16EXPANSION OF EXISTING DIRECT DIGITAL CONTROL SYSTEMS
POINT INPUT/OUTPUT SUMMARYPOINT TYPE
NAME FUNCTION DI DO AI AOPackaged Rooftop Unit with Gas Heat
Supply Fan Start/Stop & Status X XCompressor 1 Status XCompressor 2 Status XSupply Air Temperature XSpace Temperature XP.B. Override Status StatusTemperature Set Point Local Adjust XSmoke/High Temp Status X XMin. Outside Air Damper ControlGas Heat Stage 1 Enable & Status X XGas Heat Stage 2 Enable & Status X XBi-Polar Ionizer Status X X
Toilet Exhaust FansFan Start/Stop & Status X X
Outside Lighting Multiple contactors and circuits
X
END OF SUMMARY
![Page 34: 09/13/2018 - Huckabee · NO. 1 TO THE DRAWINGS AND THE PROJECT MANUAL PROJECT NAME: Aubrey MS Addition CLIENT NAME: Aubrey ISD LOCATION: Aubrey, Texas PROJECT NUMBER: 1780-02-01 PROPOSAL](https://reader036.vdocuments.net/reader036/viewer/2022081614/5fc82e3461108b10e005260c/html5/thumbnails/34.jpg)
Project Name: Aubrey MS Addition
Client: Aubrey ISD
Aubrey, Texas
Project Number: 1780-02-01
Technology Items for
Addendum No. 1
Page 1 of 1
TECHNOLOGY ITEMS FOR ADDENDUM NO. 1 NOTICE TO PROPOSERS:
A. This Addendum shall be considered part of the contract documents for the above-mentioned project as though it had been issued at the same time and incorporated
integrally therewith. Where provisions of the following supplementary data differ from those of the original contract documents, this Addendum shall govern and take
precedence.
B. Proposers are hereby notified that they shall make any necessary adjustments in their estimate on account of this Addendum. It will be construed that each Proposer’s
proposal is submitted with full knowledge of all modifications and supplemental data specified therein. Acknowledge receipt of this addendum in the space provided
on the proposal form. Failure to do so may subject Proposer to disqualification.
REFERENCE IS MADE TO THE DRAWINGS AND THE PROJECT MANUAL AS NOTED:
DRAWINGS:
AD No 1, Tech. Item 1: To the Drawings, Sheet T100, “Keynotes,”
1) Below keynotes are applicable only to Sheet T100. Not all keynotes may be utilized.
2)
END OF TECHNOLOGY ADDENDUM