14. volume control damper
TRANSCRIPT
Volume Control Damper
Identification* NF/VCD
FRONT VIEW
S T A NDA R D C ONS T R UC T ION
Frame:0.7 - 1.2mm galvanized steel channel provides greaterrigidity and strength.
Blade:Max. 6" spacing galvanized steel 0.7 - 1.0mm design for more strength and overlap coverage. Max. Length = 48".
Linkage:Type NF / VCD formed brackets of 0.7 - 1.0mm galvanized steel.
Bearings:Washer sleeve bearing.
Axles:5/16", 3/8", 1/2" galvanized steel
Sizes:Made to exact size as required.
Dampers less than 9"H made with 3/4" x 3" x 3/4" channel frame.
Hand Quadrant:For manual operation.
Type Of Joint:S&D or TDC joint.
W
H
L
Ø
Volume Control Damper
Identification* NF/VCD
SIDE VIEW
V A R IA T IONS F E A T UR E S
1. Drive Shafts: a. Extendable to 6" beyond frame. b. More than 8" using exterior bearing support.
2. Wider Frames: Frames wider than 4". 3. Axles: Stainless steel.
4. Seals Also available with neoprene side.
5. Bearings: Copper / Bronze sleeze bearing.
6" Max.
Axles 5/16", 3/8", 1/2"Ø
NF / VCD OPPOSED BLADES TYPE
NAM FOONG (M) SDN BHD (8070-T)
ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF VOLUME CONTROL DAMPER
SUPPLIED BY : NAM FOONG (M) SDN BHD (8070-T)TESTED BY : VIPAC ENGINEERS & SCIENTISTS LTDTEST DATE : 30/9/99CLIENT : NAM FOONG (M) SDN BHD (8070-T)UNIT : Volume Control Damper
Size : 610mm x 610mm Neck (To Fit Nominal 24" x 24" Duct)Damper Position : FULLY OPEN
TEST CONDITIONS SOUND POWER LEVEL, dB re 1E-12 WOCTAVE BAND CENTRE FREQUENCY (Hz)
Qs 125 250 500 1000 2000 4000 8000(l/s)
760 <47.0 <36.5 <29.8 26.6 23.5 <18.3 <18.0900 <47.3 <37.6 <32.2 30.8 27.7 21.3 <19.31270 <50.3 43.4 40.9 38.6 35.8 30.4 26.11610 54.1 49.3 47.5 44.7 42.1 37.5 33.72070 59.8 54.8 54.7 50.7 47.5 43.4 39.6
ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF VOLUME CONTROL DAMPER
SUPPLIED BY : NAM FOONG (M) SDN BHD (8070-T)TESTED BY : VIPAC ENGINEERS & SCIENTISTS LTDTEST DATE : 30/9/99CLIENT : NAM FOONG (M) SDN BHD (8070-T)UNIT : Volume Control Damper
Size : 610mm x 610mm Neck (To Fit Nominal 24" x 24" Duct)Damper Position : CLOSE 1
TEST CONDITIONS SOUND POWER LEVEL, dB re 1E-12 WOCTAVE BAND CENTRE FREQUENCY (Hz)
Qs 125 250 500 1000 2000 4000 8000(l/s)
760 <48.1 <38.6 <31.0 26.5 21.3 <16.6 <17.6900 <49.1 <39.4 35.1 32.1 26.9 19.3 <18.61180 <51.2 44.7 42.5 39.3 34.5 26.9 <21.81470 56.1 50.2 48.7 44.8 40.6 34.2 29.31870 62.3 55.7 55.4 51.1 46.7 40.0 33.6
LEGEND
Qs - Primary Air Flow Rate (l/s)Ps - Supply Static Pressure (Pa)< - Insufficient margin above background noise to allow accurate determination
Ps(Pa)
79172641
Ps(Pa)
1319304572
NAM FOONG (M) SDN BHD (8070-T)
ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF VOLUME CONTROL DAMPER
SUPPLIED BY : NAM FOONG (M) SDN BHD (8070-T)TESTED BY : VIPAC ENGINEERS & SCIENTISTS LTDTEST DATE : 30/9/99CLIENT : NAM FOONG (M) SDN BHD (8070-T)UNIT : Volume Control Damper
Size : 610mm x 610mm Neck (To Fit Nominal 24" x 24" Duct)Damper Position : CLOSE 2
TEST CONDITIONS SOUND POWER LEVEL, dB re 1E-12 WOCTAVE BAND CENTRE FREQUENCY (Hz)
Qs 125 250 500 1000 2000 4000 8000(l/s)
680 <46.7 <38.0 <32.7 27.2 19.9 <15.3 <17.2810 <48.9 <41.2 39.3 33.9 28.6 23.0 <20.4960 <51.2 45.8 45.1 40.1 33.4 24.4 <19.41180 55.1 50.3 50.6 45.9 39.9 31.8 22.91420 60.0 54.1 55.0 51.2 45.8 38.4 29.7
ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF VOLUME CONTROL DAMPER
SUPPLIED BY : NAM FOONG (M) SDN BHD (8070-T)TESTED BY : VIPAC ENGINEERS & SCIENTISTS LTDTEST DATE : 30/9/99CLIENT : NAM FOONG (M) SDN BHD (8070-T)UNIT : Volume Control Damper
Size : 610mm x 610mm Neck (To Fit Nominal 24" x 24" Duct)Damper Position : CLOSE 3
TEST CONDITIONS SOUND POWER LEVEL, dB re 1E-12 WOCTAVE BAND CENTRE FREQUENCY (Hz)
Qs 125 250 500 1000 2000 4000 8000(l/s)
570 <47.2 <39.1 34.8 28.6 20.9 <15.2 <17.1670 <49.2 <41.4 40.9 34.7 27.6 <17.8 <17.4810 <51.2 45.9 46.7 41.1 34.1 24.6 <18.8985 54.5 50.0 51.7 47.4 40.9 32.2 22.21160 59.4 53.6 55.4 52.4 47.1 38.7 29.3
LEGEND
Qs - Primary Air Flow Rate (l/s)Ps - Supply Static Pressure (Pa)< - Insufficient margin above background noise to allow accurate determination
Ps(Pa)
2030436184
Ps(Pa)
2434486993
NAM FOONG (M) SDN BHD (8070-T)
ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF VOLUME CONTROL DAMPER
SUPPLIED BY : NAM FOONG (M) SDN BHD (8070-T)TESTED BY : VIPAC ENGINEERS & SCIENTISTS LTDTEST DATE : 30/9/99CLIENT : NAM FOONG (M) SDN BHD (8070-T)UNIT : Volume Control Damper
Size : 610mm x 610mm Neck (To Fit Nominal 24" x 24" Duct)Damper Position : CLOSE 4
TEST CONDITIONS SOUND POWER LEVEL, dB re 1E-12 WOCTAVE BAND CENTRE FREQUENCY (Hz)
Qs 125 250 500 1000 2000 4000 8000(l/s)
570 <48.9 <41.1 39.7 33.4 26.7 <17.1 <17.3670 <50.8 44.5 45.4 40.4 34.1 23.9 <18.0800 54.3 48.8 50.5 46.7 40.5 31.4 <21.5980 58.0 52.9 54.8 52.0 47.0 38.5 28.5
LEGEND
Qs - Primary Air Flow Rate (l/s)Ps - Supply Static Pressure (Pa)< - Insufficient margin above background noise to allow accurate determination
6896
Ps(Pa)
3448
NAM FOONG (M) SDN BHD (8070-T) ______________________________________________________________________________________
PERFORMANCE NOTES • Units are tested accordance with the Air Diffusion Council (USA) Equipment
Test Code 1062 : GRD-84. Measurements were taken in general accordance with the following standards :-
ACOUSTICS International Standard ISO 3741 Clause 8.3 (Method 11) “Acoustics – Determination of Sound Power Levels of Noise Sources – Precision Methods for Broad-Band Sources in Reverberation Rooms”. AIRFLOW Air Diffusion Council (USA) Equipment Test Code 1062 : GRD-84. THROW AND STATIC PRESSURE DROP
Air Diffusion Council (USA) Equipment Test Code 1062 : GRD-84. TEST SET UP AND PROCEDURE Reverberation Test Room has a volume of 170m3 has been qualified in accordance with the procedures in ISO 3741 for determination of sound power in octave bands with Centre Frequencies from 125 Hz to 8000 Hz. The Units under test were set up in the Air Distribution (Reverberation) Test Chamber and connected to a quiet air supply. The units were supplied with ambient temperature air at the specified airflow. The environmental test conditions in the reverberation chamber varied for each test within the following ranges : - Test Air Temperature 18 degrees C ± 2.0 degree C Room Air Temperature 20 degrees C ± 2.0 degree C Barometric Pressure 1040 millibar ± 5 millibar Relative Humidity 60 ± 10%
NAM FOONG (M) SDN BHD (8070-T) ______________________________________________________________________________________ DAMPER BLADES (SIDE VIEW) DAMPER BLADES
1 2 3
PLAN VIEW OF DAMPER FOR EACH DAMPER SETTING, THE MEASURED APPARENT BLADE WIDTHS WERE AS FOLLOWS :- Apparent width of each damper blade, as measured from plan
view (mm) Damper Setting 1 2 3
Fully Open 38 27 33 Close 1 90 80 80 Close 2 115 115 110 Close 3 134 130 125 Close 4 145 145 142
Volume Control Damper Blade Settings
width blade