Installation & Operations Manual WFC202C Conventional Fire Alarm Control Panel Document : WFC202C Version : WF5.10 Page : 1/33 Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de 2 Zone Conventional Fire Alarm Control Panel WFC202C

Upload: dothuan

Post on 04-Jun-2018

221 views

Category:

Documents


3 download

TRANSCRIPT

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 1/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

2 Zone Conventional Fire Alarm Control Panel

WFC202C

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 2/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

SUMMARY 1- FIRE DETECTION PANEL WFC202C .............................................................3

1-1 INTRODUCTION ............................................................................................3 1-2 WFC202C MODULE ......................................................................................3 1-3 POWER SUPPLY UNIT AND BATTERIES ....................................................3 1-4 TECHNICAL SPECIFICATIONS ....................................................................4 1-4-1 General specifications .................................................................................4 1-4-2 Power supply unit of base module ...............................................................4 1-4-3 Base module of panel..................................................................................5 1-5 BASE MODULE CONSUMPTION ..................................................................6 1-6 OPERATING CHARACTERISTICS OF POWER SUPPLY .............................6 1-7 OPTIONAL EN54 FUNCTIONS ......................................................................6 1-8 EXTRA FUNCTIONS .....................................................................................6 1-9 DIMENSIONS AND INTERNAL VIEW OF WFC202C ....................................7 2- INDICATIONS & COMMANDS ........................................................................7

2-1 CONTROL PANEL .........................................................................................7 2-1-1 A-LED indications of general states of fire panel .........................................8 2-1-2 B-LED indications of faults ..........................................................................8 2-1-3 C-LED indications and general commands ..................................................9 2-1-4 D-LED indications and commands relative to zones ....................................9 2-1-5 E-LED indication of LEVEL 2 ACCESS .......................................................9 3- FUNCTIONS & OPERATIONS ......................................................................10

3-1 PRE-ALARM, ALARM & FAULT OF ZONES ................................................10 3-2 SILENCE BUZZER AND/OR ALARM/FAULT OUTPUTS .............................10 3-3 ENABLE ACCESS LEVEL 2 ........................................................................11 3-4 ENABLE/DISABLE ZONE ............................................................................11 3-5 RESET OF PANEL .......................................................................................11 3-6 AUTORESET OF FIRST ALARM .................................................................12 3-7 ALARM DELAY ............................................................................................12 4- CONFIGURATION OF PANEL ......................................................................12

4-1 ENABLE CONFIGURATION ........................................................................12 4-2 BASE CONFIGURATION .............................................................................14 4-3 VERIFY/MODIFY CONFIGURATION OF ZONES ........................................14 4-4 VERIFY/MODIFY CONFIGURATION OF DELAYS ......................................16 4-5 VERIFY/MODIFY CONFIGURATION OF OPTIONS ....................................18 5- PANEL INSTALLATION AND MOUNTING ...................................................21

5-1 PARTS IDENTIFICATION ............................................................................21 5-2 INSTALLATION ............................................................................................22 5-3 PANEL MOUNTING .....................................................................................22 6- PANEL MAINTENANCE ................................................................................23 7- IMPLANTATION AND TERMINAL BLOCKS ................................................23 7-1 MODULE WFC202C ....................................................................................23 7-1-1 Mains terminal block (MR) .........................................................................25 7-1-2 Batteries connections (red and black cables) ............................................25 7-1-3 Exploitable outputs (CN1) ........................................................................26 7-1-4 Terminal block for connection of zones 1, 2 (M2) ......................................26 7-1-5 Terminal block for connection of actuators (M3) ........................................26 7-2 Connection of alarm actuators ......................................................................27 7-3 Connection of detectors................................................................................28 8- Connection diagram .....................................................................................29

8-1 Connection of detectors WÄCHTER WFD-OC05/WFD-TRC05/WFD-TSC05 to panel ...........................................................................................................................29 8-2 Connection of visual/acoustic indicators to panel..........................................30

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 3/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

1- FIRE DETECTION PANEL WFC202C

1-1 INTRODUCTION

WFC202C is fire detection and indicating panel that uses microprocessor techniques and designed to meet the requirements of standards EN 54-2 and EN 54-4. It is housed in a reduced size plastic box and integrates a control panel (Figure 1) that allows an easy management through signalizations and intuitive commands. The panel manages two zones by the means of monitored bifilar lines balanced with end of line resistors; each detection line can support a maximum of 32 point detectors or manual call point. Each zone has indicators that allow the immediate visualization of the states of alarm, fault and disabled; moreover, commands are available for disabling each single zone. All the signalizations are reported through LED and with the aid of a piezoelectric buzzer. The functions of command are managed through membrane keys and are protected, for the functions of reset and disabling, with an access code.

Figure 1 – WFC202C front panel

1-2 WFC202C BASE MODULE

WFC202C base module consists on a microprocessor board that incorporates and manages all the functions of the fire detection panel: power supply, inputs/outputs interface, command keys and LED. The module is mounted on the front cover with screws and gives access from the external side to LED and functions of command protected by polycarbonate serigraphy. For implantation and connections of the module refers to the appropriate section in par.7-1. 1-3 POWER SUPPLY UNIT AND BATTERIES

The power supply unit is realized in conformity with EN54-4 standard and supplies a D.C. voltage between 21V and 28,5V depending on the operating conditions and the ambient temperature (battery charger compensated in temperature). Power supply unit consists on a linear local power source integrated on the WFC202C module that supplies the primary power source and two sealed lead accumulators batteries that supply the secondary power source in case of lack of mains. The unit is permanently controlled by the electronic of WFC202C which provides a fault condition in case of anomalies like:

Batteries disconnected or FUSE battery fault

Low battery

Battery charging not efficient

mains absent

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 4/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

Output voltage of power supply module is out of the admitted limits (< 21V or > 30V)

1-4 TECHNICAL SPECIFICATIONS 1-4-1 General specifications

NAME EQUIPMENT WFC202C: 2 conventional zones fire detection panel

MANUFACTURE CHARACTERISTICS In agreement with EN54-2 and EN54-4

ENVIRONMENT CONDITIONS -5°C ± 3°C... 40°C +/- 2°C, max humidity 93% with no condensation.

BOX plastic box CMP1 with IP30 Dim 300 x 260 x 125 millimetre

NOMINAL VOLTAGE OF MAINS 230V +10% / -15% ~ 60Hz

MAXIMUM ABSORBED CURRENT FROM MAINS

< 110 mA

OPERATING VOLTAGE OF SYSTEM min. 20,5V D.C, max 30V D.C

1-4-2 Power supply unit of base module

PRIMARY SOURCE INPUT VOLTAGE 230V +10% / -15% ~ 60Hz

TRANSFORMER 15VA primary 230V, secondary 32V

TYPE OF REGULATION Linear with serial regulator

NOMINAL OUTPUT VOLTAGE 27,5V (at 20°C, with batteries connected). The output voltage is stabilized and compensated in temperature in agreement with the characteristics of battery charging

RIPPLE OF VOLTAGE <100 mV pp

CURRENT AVAILABLE FOR EXTERNAL SUPPLYING

0,1A in continuous 0,5A for short periods (30min with charged and connected batteries) NOTA: In order to guarantee 24h autonomy in absence of mains, refer to the data regarding the maximum current in the next section.

MIN/MAX OUTPUT VOLTAGE Min=21V, max=28,5V (voltage available in any operating conditions for panel supplying, external supplying and battery charging).

SAFETY SOURCE

BATTERIES TYPE 2 sealed lead batteries connected in series, type: YUASA NP4-12, 12V 4Ah

CURRENT AVAILABLE FOR EXTERNAL SUPPLYING IN ABSENCE OF PRIMARY SOURCE (current max in

order to guarantee autonomy of 24h)

100mA at 24V nominal (batt.2x12V 4Ah).

DURATION OF CHARGING 24h for 80%, 48h for 100% of the nominal capacity (4Ah).

PERIOD RECOMMENDED FOR SUBSTITUTION

3 years

POWER SOURCE OUTPUTS Distinguished outputs for panel/external power supplying and for battery charging.

PROTECTIONS Fuse 0,25A T for the input of mains, fuse 3,15A T for protection battery, and fuse 1A T for lines and auxiliary outputs. Serial regulator with thermal protection and limitation of current

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 5/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

1-4-3 Base module of panel

INPUTS FOR DETECTORS 2 inputs for bifilar lines supplied with 27V, with line monitoring through end of line resistor (see par.8-1)

TYPE AND NUMBER OF DETECTORS MANAGED FOR EVERY LINES

Max 32 detectors or 32 push-buttons with serial limitation resistor 470Ω¼ W. The detectors must operate correctly in a range of tensions comprised between 12V and 30V D.C and absorbing a current below 60µA.

CONTROL THRESHOLDS LINES (total absorption detector + EOL resistor, at

27V)

Thresholds can be selected at access level 3 through configuration procedure (see par.4-5). This configuration allows panel to recognise pre-alarm/alarm states for several typologies of detectors.

SOUNDERS LINES

- 27V monitored sounders line; it supplies 27,5V max 5A in alarm condition. The monitoring is obtained with end of line resistor 3,9kΩ ¼ W - 27V auto powered sounders line. 27,5V standby voltage becomes 0V in alarm condition. The maximum admissible current of this output must be in agreement with the specificities detailed for the group of power supply.

- Alarm output relay free of voltage contact (30V/1A)

FAULT OUTPUT Fault relay 1A/30V D.C normally excited in standby state (positive safety).

AUXILIARY OUTPUTS

See CN1, par.7-1 fig.6. It makes available: positive and negative (+27,5V max 1A) positive lines (+27V max output current 4mA; disabled in

phase of reset lines) programmable output open collector (max 4mA / 30V).

INPUT OF COMMAND - Input for auxiliary activation of access level 2 (see jumper JP1). - Input for activation of configuration mode (see jumper JP2).

ORGANS OF SIGNALLING

Led and buzzer for the signalling of operating states, functionality, power, deactivation, faults, alarms.

ORGANS OF COMMAND Keys of the front panel are reachable for the function of silence buzzer and protected with access level 2 for the disable functions, reset and outputs management

ORGANS OF PROGRAMMING Led/keys of the panel are reachable in the mode of configuration (protected mode, access level 3 with the opening of the box of panel).

ACCESS LEVELS

Access level 1 is always active. At access level 1 all the indications, the command of silence buzzer and sounders line management are available. Access level 2 is reachable through code or external command. It allows the access to the command of reset, outputs management (alarm/fault) and disable. Access level 3, 4 are reachable with the opening of the box of panel and with specific procedures. They allow the operating configuration of panel.

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 6/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

1-5 BASE MODULE CONSUMPTION

DEVICE: DESCRIPTION: Operating consumption at 24V:

WFC202C Base module in condition of standby with the 2 monitored lines connected

80mA

1-6 OPERATING CHARACTERISTICS OF POWER SUPPLY

PARAMETER OPERATING CONDITIONS MIN TYP MAX UNIT

Mains power supply voltage Mains frequency 60Hz 195 230 250 V

Current absorbed from mains No external supplying Batteries disconnected

32 45 60 mA

Current absorbed from mains Max external supplying

Low batteries connected 75 85 100 mA

Charging batteries voltage 21 27,5 28,5 V

Maximum charging batteries current

Panel powered 0,3 A

Available batteries current Mains absent 1 A

Voltage of power supply group output

- 21 27,5 28,5 V

Current of power supply group output, continuous charging

Batteries disconnected 0,1 A

Current of power supply group output, for short duration

Batteries disconnected 0,2 A

Current of power supply group output, for short duration

Charged batteries connected

0,5 A

1-7 OPTIONAL EN54 FUNCTIONS - Possibility, for each single zone, to manage the delayed alarm. - Management of the outputs (needs a prior configuration) 1-8 ACCESSORY FUNCTIONS

- Possibility to set for every single zone the function of auto reset of the first alarm (the alarm of zone activates the actuators if it is introduced on at least two zones or if the alarm occurs two times on the same zone within a certain time). - Possibility to qualify on every single line the management of the pre alarm threshold (management AND of 2 alarms). - Possibility of activation of the access level 2 through electromechanical setting (the access level 2 is normally obtained through code setting).

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 7/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

1-9 DIMENSIONS AND INTERNAL VIEW OF WFC202C

Measures of panel box WFC202C: CMP1: H300 x L260 x P125 millimetre.

Figure 2 – WFC202C panel: inside disposition of the modules and the batteries 2- INDICATIONS & COMMANDS

2-1 CONTROL PANEL Indications and commands are grouped in logical groups (Figure 3):

Figure 3 - control panel WFC202C

D B C

A

E

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 8/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

2-1-1 A - LED indications of general states of fire panel

LED POWER

Is steady on if the panel is working with the main power source (presence of mains), flashes with a short period of ignition if system lacks mains voltage for less than 20min (working with batteries), it is off if the mains lacks mains voltage for more than 20 minutes (fault) and flashes in normal way if the panel is power supplied by mains but fault is present in the mains (voltage outside from the limits: < 21V or > 30V). LED FAULT It indicates that a condition of fault is present in panel. LED DISABLED If steady on, it indicates that a condition of disabling is present in panel (sounders or zones disabled); it flashes during the phase of reset LED ALARM

If steady on, it indicates that a condition of alarm is present in panel and that the corresponding output is activated. If blinking with long period of ignition and short extinction, it indicates pre alarm or delayed alarm in course. 2-1-2 B - LED indications of faults

LED POWER FAULT

If steady on, it indicates that the power supply of panel is not correct because of one of the following conditions of anomaly:

lack of mains voltage since more than 20 minutes

The local power supply voltage of panel is outside from the limits

the battery is disconnected or inefficient

the circuit of battery charging is out of order Flashing of the led indicates that the power supply is correct but some anomaly conditions had occurred previously (memorised signalling). LED FAULT EARTH

If steady on, it indicates a condition of low isolation between one of the electrical parts and the earth. If flashing, it indicates a correct state but some anomaly conditions had occurred previously (memorised signalling). LED SOUNDERS FAULT If steady on, it indicates the presence of fault on the monitored line that commands the alarm actuators (sounders line balance fault). If flashing, it indicates a correct state but some anomaly conditions had occurred previously (memorised signalling). LED CPU FAULT

It indicates that the microcontroller of panel is temporary or permanently out of control. This type of anomaly can be caused by strong disturbances of electrostatic origin, from an abrupt decrease of the power supply voltage or by a physical anomaly of the board of the panel. In this last case the signal can be shut but it is not resettable. In the other cases it is possible to reset the signalization with the dedicated pushbutton by following the procedure described in the point 3.5; if it has no effect (error in the configuration memory) it is enough to activate and deactivate the configuration procedure as it is described in the point 4.1.

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 9/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

LED FUSE FAULT

If on, it indicates that the fault of the fuse places into protection the outputs of panel (sees F3 par.7-1). 2-1-3 C - LED indications and general commands

LED DISABLE SOUNDERS If steady on, it indicates that the sounders lines have been deactivated. The corresponding key allows (at access level 2) the activation/deactivation of the sounders line. The led is flashing in normal way (alternatively on/off) during the phase of reset. LED SILENCE BUZZER

The ignition of the led indicates that the acoustic signalling of the buzzer, activated as a result of a fault or alarm condition, has been manually silenced by the means of the corresponding key.

NOTA: the pressure of the key at access level 1 (led level 2 off) has effect only on the buzzer. The pressure of the key at access level 2 (led level 2 on), allows to carry out the test of the led and buzzer (simultaneous ignition of the led) and if set in phase of configuration (see par.4-5), executes also the silencing of the outputs of alarm/fault. COMMAND RESET The pressure of the key with active access level 2 (led on) provokes the restoration of the memorised conditions of alarm/fault. The phase of reset is temporised and signalised by simultaneous and regular flashes of the led of disable. 2-1-4 D - LED indications and commands relative to zones

LED ZONE DISABLED If steady on, it indicates that the relative zone is disabled. If the two disable leds of zone are flashing simultaneously and normally, it indicates that the zones are in phase of reset (temporary disabled). The corresponding key allows (access level 2) to activate/deactivate the relative zone. LED ZONE ALARM If steady on, it indicates that the relative zone is in alarm conditions. If it is flashing with long period of ignition and short extinction, it indicates that the zone is found in conditions of pre alarm (zone set in pre alarm mode and line absorption corresponds to pre alarm thresholds). If flashing regularly, it indicates that the zone is in normal state but some anomaly conditions had occurred previously (memorised signalling). LED ZONE FAULT

If steady on, it indicates that the relative zone is in condition of fault (line open or in short circuit). If flashing, it indicates that the zone is in normal state but some anomaly conditions had occurred previously (memorised signalling).

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 10/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

2-1-5 E - LED indication of ACCESS LEVEL 2

If steady on, it indicates that the access level 2 is activated and therefore are available the sounders line management and RESET keys. Moreover, in access level 2, the SILENCE BUZZER key allows carrying out the Led/buzzer test and if so configured, it allows triggering the alarm/fault outputs. The activation of access level 2 is obtained by the means of pressing keys (see par.3-3) or can be activated (optionally) also by the means of a setting of jumper on WFC202C module (see JP1 par.7-1). 3- FUNCTIONS & OPERATIONS 3-1 PRE-ALARM, ALARM & FAULT OF ZONES

Panel manages, for every zone, a physical lines to which are connected the fire detectors to. For each line the panel controls constantly the absorbed current and, according to this, shows the state of the corresponding zone. In particular:

does not appear any signalling of zone if the line is in standby

shows the state of zone fault if the line is cut or short circuited (excessive current or current=0A)

Shows pre alarm or alarm if one or more detectors reveal fire condition (current over the thresholds of pre alarm or alarm).

The pre alarm of zone is a condition that generates the signalling of panel but do not

activate the sounders. Pre alarm mode is set in phase of configuration (see par.4-3), panel will indicate pre alarm state if one detector goes in fire alarm (current over the thresholds of pre alarm and under the threshold of alarm). It is shown by an irregular flash of red led of zone (long ignition/ short extinction) and by the sound of the buzzer. Zone goes in alarm state if a second detector goes in fire alarm, or if push-button is activated (current over the thresholds of alarm) or if the alarm comes from a single detector that belong to a zone not declared as pre alarm. Fire alarm of zone is shown by the ignition of the relative red led and the buzzer if

the zone has not been set in delayed alarm and the delay of alarm actuators is not set. But for delayed zones, in alarm condition the countdown starts until alarm actuators are triggered. Delay is set during configuration (see par.4-4) The fault state is reported in case of short circuit (line current excessive) or in case

of open line (line current insufficient) of the relative line, and it is shown by the ignition of yellow led relative to the corresponding zone. The fixed ignition of the led indicates the current presence of the fault; the flashing of the led indicates a memorised signalling (fault no longer present).

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 11/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

3-2 SILENCE BUZZER AND/OR ALARM/FAULT OUTPUTS

In case of pre alarm, alarm or fault, WFC202C turns the relative Leds and the buzzer on. The acoustic signal can be deactivated without necessity of advanced access level by pressing for a moment SILENCE BUZZER key. At access level 2 and in case of alarm or fault, the key allows deactivation of relative outputs. This action is signalled by ignition of yellow led relative to this key and its effect lasts until reset or until a new alarm/fault state occurs. It is possible anyway to set the panel for an automatic deactivation of buzzer after 10min (see par.4-5) NOTA: Automatic deactivation of buzzer is not applied for CPU Fault, for this fault you need to reset the panel manually. 3-3 ENABLE ACCESS LEVEL 2

All the command available on WFC202C, except from SILENCE BUZZER and manual activation of sounders line (in phase of delayed activation of sounders line), are operative only after activating access level 2. This access level, anticipated for specific users, is signalled by green led and is activated by pressing an access code like detailed next: a) Press and maintain key SILENCE BUZZER. This operation changes the nature of the keys DISABLE of zone and become the following setting keys: Zone 1 = Key 1, Zone 2 = Key 2. b) Press sequence Key 1 and Key 2 (code access level 2) c) Release the key SILENCE BUZZER. If the operation has been executed correctly, green led level 2 will be ignited. This access level 2 remains active for 30s since no key has been pressed during this time. Access level 2 can be optionally activated by the means of mechanical key to be inserted in the panel as well (see par.7-1). 3-4 ENABLE/DISABLE ZONE

Every single zone can be disabled or enabled by following this procedure: a) Activate access level 2 b) Press key ON/OFF relative to the zone you want to disable/enable; if the corresponding led goes yellow on it means that the zone is disabled and if the led is off it means the zone is enabled (pressing the ON/OFF key switches alternatively the zone ENABLE – DISABLE) The deactivation of the zone remains permanent until it is manually activated again. Disabled zones are considered non operative by WFC202C, therefore all alarm or fault signalisations relative to disabled zones are ignored. Disabled zone remains able to analyse the state of its line and keeps on indicating through led the eventual alarms or faults kept in memory.

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 12/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

3-5 RESET OF PANEL

Alarm/fault states that are registered by the panel are memorised through the led or through the alarm actuators. Actions on SILENCE BUZZER are also memorised. In order to get back to normal state after a condition of anomaly it is necessary to carry out a RESET operation. The reset is obtained pressing the dedicated key after having activated the access level 2 (see par. 3-3). Reset takes place in 2 phases and lasts a couple of seconds (programmable). In the first phase, WFC202C cuts the power of the detection lines (physical reset of detectors), in the second phase (post reset) the lines are powered again and WFC202C keeps on ignoring the eventual alarm or fault states coming from zones. The 2 phases of reset are indicated by the blinking of DISABLE leds of zones. 3-6 AUTO RESET OF FIRST ALARM

It is possible, in phase of configuration, to set for each zone the function of auto reset of the first alarm. The auto reset of the first alarm is a filter function that allows ignoring the alarm states that could be false. The principles of the auto reset are following: a) If an alarm occurs on a zone set in auto reset, the alarm is not registered but it generates the activation of a delay of 3 seconds. b) If within this time another alarm occurs on any zone, it will be recognized by the panel as true (AND of two alarms generates true alarm). If no alarm has occurred within these 3 seconds, WFC202C will cut the power of the relative line for a time corresponding to reset allowing physical reset of detector in alarm.

NOTA: the reset does not cancel the eventual memorizations of anomalies registered previously on the led. c) At the end of the time of reset panel begins a 5 minutes countdown. If within this time another condition of alarm occurs on any zone panel will recognise it as true alarm, and will start again 5 minutes countdown. After 5 minutes the function of filter of alarms will be restored. 3-7 ALARM DELAY

It is possible to delay the activation of alarm outputs after an alarm has occurred. This function can be set in phase of configuration (level 3) for every single zone. This setting is permanent until another setting occurs. In case of alarm, the activation of the countdown of delay is indicated by the blinking of the led of general alarm which becomes steady when the countdown ends, then outputs are activated. If another alarm occurs on a normal zone during this delay the countdown is stopped and the alarm outputs are activated immediately. The delay can be set in phase of configuration (sees par.4-4).

NOTA: The alarm delay concerns only the alarm outputs, activation of acoustic and visual indications on panel are immediate.

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 13/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

4- CONFIGURATION OF PANEL

WFC202C is equipped with a non volatile memory on which all the parameters of configuration reside. Some of these parameters can be modified by the installer, in agreement with normative, in order to adapt the panel to the necessities of the installation. 4-1 ENABLE CONFIGURATION The activation of configuration mode is protected (access level 3) and it is

obtained operating like following: a) Remove the screws of the front cover of panel to reach the internal electronic; b) Insert the jumper of configuration JP2 (see Figure 4) on the microprocessor board; c) Push the RESET button P1 on the µP board (see Figure 4) for a short time. The configuration mode is signalled by the blinking of the yellow led of DISABLE and LEVEL 2 (see CF in Figure 5). The following conditions are also present: - All the alarm/fault actuators turn into standby state; - Detection lines are put in condition of reset (Voltage on the lines not present); - Leds and keys have different functions as in normal condition To deactivate configuration mode take jumper JP2 off.

NOTA: If in phase of configuration no key is pressed for more than 10 minutes, buzzer will go on and fault output will be activated.

JP3 P1

Figure 4 – WFC202C module: jumper of configuration

The visualization and/or modification of settings of configuration are carried out through leds and keys that have new meanings during the period of configuration.

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 14/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

Figure 5 - Led and keys of the panel used for configuration The 3 keys RESET, SILENCE BUZZER and DISABLE SOUNDERS become respectively the selection keys of configuration for: zones [SZ], delay [ST], and the options [SO]. FAULT led become the indicators of parameters 1-5 in configuration mode. Led DISABLE and ALARM of zones [A...D] become finally the indicators of the configuration value, and the relative keys ON/OFF [SA, SB] allow modifying the

corresponding positions. All the others led and keys are not significant in configuration mode. For the visualization/modification of each parameter, refer to the next pages. 4-2 BASE CONFIGURATION

The factory configuration of WFC202C complies with EN 54-2. Before carrying out any modification of the configuration it is necessary to refer first to the standard normative in order to avoid an improper operating setting. The factory configuration is following:

Zones/lines:

Zones 1 & 2 are set in instantaneous alarm (no alarm delay), no zone is set in pre alarm mode, and no zone is set in auto reset of first alarm.

Delays:

Minimal duration of pre alarm (if not memorised): 10seconds

Minimal duration of alarm (if not memorised): 30 seconds

Delay of alarm: 60 seconds

Duration of active reset of detectors (detectors not power supplied): 5 seconds

Duration of passive reset of detectors (post-reset): 5 seconds

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 15/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

Options:

Options pre alarm/alarm: - Fault does not active pre alarm. - Alarm output memorised and pre alarm temporised

Earth/buzzer fault: - Earth fault enabled. - Buzzer memorised, sound until the activation of SILENCE BUZZER or RESET.

Aux. Output configuration: - output is active if presence of ENABLE or SILENCE BUZZER.

Several options: - Pre alarm activates alarm delay. - SILENCE BUZZER influences only buzzer. - SILENCE BUZZER does not deactivate automatically after 10mn.

Thresholds/detectors type: WÄCHTER (WÄCHTER detectors range) 4-3 VERIFY/MODIFY CONFIGURATION OF ZONES In order to visualize and/or modify the configuration of the zones activate the configuration mode with jumper JP2 and select with key SZ (key RESET) the parameter to visualize and/or modify.

NOTA: Configuration mode of zones is indicated by the ignition of the leds

corresponding to the parameters 1-3.

1) CONFIGURATION OF THE ZONES IN INSTANTANEOUS: The zones set in instantaneous activate immediately signalizations/outputs of pre alarm or the signalizations/outputs of alarm. The zones that are not set in instantaneous activate the alarm outputs with a delay that starts when the alarm occurs. Delay: 0 to150 seconds (see par.4.4).

SA

SB

SO

ST

SZ

CA

B D

1

2

3

4

5

Select with the keys [SA], [SB] the configuration to be applied to the 2 zones. Led [A] and [B]: if on, it indicates that the zones are set in instantaneous. NOTA: the push-buttons zones are

normally programmed in instantaneous (led on).

2) CONFIGURATION OF ZONES WITH MANAGEMENT OF AUTO RESET OF THE FIRST ALARM:

The zones set in this mode have following principles: a) The first alarm is not registered but activates an internal countdown of 3 seconds. b) If within this time a new alarm occurs on another zone it is registered as a true alarm (AND of two alarms generates true alarm) but if 3 seconds delay has expired WFC202C will apply a reset on detection lines.

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 16/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

c) After reset, a 5 minutes internal countdown will be activated, if within this time an alarm occurs on whichever zones the alarm will be registered as a true alarm. If no alarm occurs within this time the function alarm filter is restored.

SA

SB

SO

ST

SZ

CA

B D

1

2

3

4

5

Select with the keys [SA], [SB] the zones on which you want apply the function of auto reset of the first alarm. Led [A] & [B]: If on, it indicates that the function is applied on the selected zone. NOTA: Avoid applying the function of auto reset of the first alarm on the zones anticipated for push-buttons management.

3) CONFIGURATION OF ZONES WITH MANAGEMENT PRE ALARM MODE: The zones set in pre alarm mode have following principles: a) If an alarm occurs from a single detector (current under the thresholds of alarm and over the threshold of pre alarm; threshold selectable in configuration of options) WFC202C will not register an alarm but a pre alarm. The pre alarm is indicated by the blinking (long ignition/short extinction) of led of alarm of zone and by the sound of the buzzer. In pre alarm conditions the alarm outputs are not activated. If WFC202C has a factory setting (can be modified in par.4-5) the pre alarm will be managed like alarm delayed, it means that after an internal countdown that starts when pre alarm had occurred the pre alarm becomes alarm. b) But if another alarm occurs or a push-button is triggered (current over the threshold of alarm) the alarm outputs are activated directly.

SA

SB

SO

ST

SZ

C A

B D

1

2

3

4

5

4-4 VERIFY/MODIFY CONFIGURATION OF DELAYS

In order to visualize and/or modify the configuration of the delays activate the configuration mode with jumper JP2 and select with key ST (key SILENCE BUZZER) the parameter to visualize and/or modify.

NOTA: Configuration mode of delays is indicated by the blinking of the leds

corresponding to the parameters 1-4

1) CONFIGURATION OF MINIMAL DURATION OF PRE ALARM ACTIVATION:

It is the time that determines the minimal duration of activation of pre alarm (if it is not set in memorised mode)

Select with the keys [SA], [SB] the zones on which you want to apply pre alarm mode. Led [A] & [B]: If on, it indicates that on the corresponding zones the pre

alarm mode is applied.

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 17/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

NOTA: It is possible to set aux. outputs as repetition of pre alarm (see par.4-5)

SA

SB

SO

ST

SZ

C A

B D

1

2

3

4

5

Select with the key [SA], [SB] the time you want to be applied (0 to 150 sec.) Led A on: 10 seconds Led B on: 20 second Led C on: 40 seconds Led D on: 80 seconds The final time is the sum of the times corresponding to the leds that are lit.

2) CONFIGURATION OF MINIMAL DURATION OF ALARM ACTIVATION:

It is the time that determines the minimal duration of activation of the alarm outputs (if they are not set in memorised mode).

SA

SB

SO

ST

SZ

C A

B D

1

2

3

4

5

Select with the keys [SA], [SB] the time you want to be applied (0 to 150 sec.). Led A on: 10 seconds Led B on: 20 seconds Led C on: 40 seconds Led D on: 80 seconds The final time is the sum of the times corresponding to the leds that are lit.

3) TIME OF DELAY ACTIVATION ALARM: It is the time that determines the delay of activation of the alarm outputs in case of an alarm that had occurred in a zone set to this function.

SA

SB

SO

ST

SZ

C A

B D

1

2

3

4

5

Select with the keys [SA], [SB] the delay you want to be applied (0 to 150 sec.). Led A on: 10 seconds Led B on: 20 second Led C on: 40 seconds Led D on: 80 seconds The final time is the sum of the times corresponding to the leds that are lit.

4) DURATION OF ACTIVE PHASE OF RESET LINES/DETECTORS: It determines the duration of the active phase of reset during which reset puts detectors lines out of voltage.

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 18/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

SA

SB

SO

ST

SZ

C A

B D

1

2

3

4

5

Select with the keys [SA], [SB] the time you want to be applied (0 to 75 sec.). Led A on: 5 seconds Led B on: 10 second Led C on: 20 seconds Led D on: 40 seconds The final time is the sum of the times corresponding to the leds that are lit.

NOTA: the active phase of reset is followed by the passive phase of POST-

RESET, during which (voltage present) WFC202C ignores the eventual conditions of alarm and fault. The phase of post-reset can be set at 5 or 15 seconds (see par.4-5) , actually according to EN normative panel must recover its normal state within 20 seconds (end of active reset + post-reset). 4-5 VERIFY/MODIFY CONFIGURATION OF OPTIONS In order to visualize and/or modify the configuration of the options activate the configuration mode with jumper JP2 and select with key SO (key DISABLE SOUNDERS) the parameter to visualize and/or modify.

NOTA: Configuration mode of options is indicated by the blinking of the leds (long ignition / short extinction) corresponding to the parameters 1-5

1) OPTIONS PRE ALARM/ALARM:

SA

SB

SO

ST

SZ

C A

B D

1

2

3

4

5

Through keys [SA], [SB] it is possible to enable/disable the following options: Led A: If on, it indicates that a fault condition (except from CPU fault) will activate general pre alarm (If pre alarm mode is set in temporised mode, WFC202C will activate the countdown corresponding to delay of alarm, so that general alarm will be activated by the end of the countdown). Led B:

If on, it indicates that the pre alarm is not temporised but memorised (only RESET will cancel pre alarm). Led C: If on, it indicates that the alarm outputs are not temporised but memorised (only reset will deactivate the alarm outputs), refer to par.4-4 point 2 to visualize/modify the duration of the alarm outputs activation. Led D: Not used, remains off

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 19/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

NOTA: It is necessary to choose the option C (factory setting) to comply with

EN normative as automatic reset of alarm outputs is prohibited; it is required to reset manually the alarm actuators.

2) OPTION EARTH FAULT:

SA

SB

SO

ST

SZ

C A

B D

1

2

3

4

5

Through keys [SA], [SB] it is possible to enable/disable the following options: Led A: Not used, remains off. Led B:

If on, it indicates that the control of earth fault is disabled. But if it is enabled (factory setting) the corresponding fault led will switch on as soon as one of the parts of the system is found in electrical continuity towards earth. Led C: Not used, remains off. Led D: Not used, remains off.

3) CONFIGURATION OF ELECTRONIC AUXILIARY OUTPUT

SA

SB

SO

ST

SZ

C A

B D

1

2

3

4

5

Through keys [SA], [SB] it is possible to program auxiliary output as repetition of the following conditions:

Led A Led B Led C Formulation:

off off off The output is normally active; it is deactivated if whichever fault conditions occur.

on off off The output repeats the memorised alarm conditions (only manual reset will deactivate the output)

off on off Power/fuse faults activate the output on on off The output is activate if DISABLE (zones or sounders

line) or SILENCE BUZZER occur

off off on the output repeats general pre alarm conditions on off on the output repeats pre alarm/alarm conditions of zone 1

off on on the output repeats pre alarm/alarm conditions of zone 2 on on on Not significant

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 20/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

Led D:

Not significant

4) CONFIGURATION OF PRE ALARM AND SILENCE BUZZER OPTIONS

SA

SB

SO

ST

SZ

C A

B D

1

2

3

4

5

Through keys [SA], [SB] it is possible to enable/disable the following options: Led A:

If on, it indicates that pre alarm condition generates delay of alarm: in pre alarm case the countdown corresponding to delay of alarm starts; alarm is activated by the end of the countdown. If off, it indicates that pre alarm will not generate alarm. Led B:

If on, it indicates that SILENCE BUZZER key affects buzzer only (factory parameter). If off, it indicates the key will affect also the actuator outputs (if temporised). Led C: If on, it indicates that buzzer is automatically deactivated after 10 minutes. Led D: If on, it indicates that the duration of POST-RESET (inhibition of alarm/fault till the end of cycle of reset) is 15 sec. If off, it indicates that the duration is 5 sec. (see par.4-4 point 4)

5) CONFIGURATION OF PRE ALARM/ALARM THRESHOLDS

SA

SB

SO

ST

SZ

CA

B D

1

2

3

4

5

Through keys [SA], [SB] it is possible to enable/disable the following options:

Led A Led B Threshold of pre alarm Threshold of alarm End of line resistor Detectors type

off off 21mA 32mA 3,9Kohm ¼ W WÄCHTER

(WÄCHTER )

on off 21mA 36mA 4,7Kohm ¼ W others

off on 12mA 21mA 4,7Kohm ¼ W others on on Not significant

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 21/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

Led C, D:

Not significant. NOTA: alarm or pre alarm thresholds correspond to the total absorbed current

by the line that activates the associated condition. NOTA: If a zone that is not set in pre alarm mode reaches the pre alarm

threshold, the alarm is activated. 5- PANEL INSTALLATION AND MOUNTING 5-1 PARTS IDENTIFICATION

1

1

4

3

3

2

4

5

7

1

1

6 Inside view of ALPHA 2

2

Legend

PART DESCRIPTION

1 Holes for panel wall mounting

2 Holes for screws of frontal closing

3 Connectors for batteries

4 Batteries (not supplied)

5 Hole for cables entrance

6 Module WFC202C

7 Connecting block for the connection of the mains

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 22/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

5-2 INSTALLATION For a proper installation follow these indications:

Identify the better location for panel, detectors and signalization devices

Fix the panel like indicated further

Proceed to wiring and connection (except from power supply connection).

Maintain separate the high voltage wiring (230V) and the low voltage wiring (27V) in order to prevent accidental contacts between the conductors and others parts of the panel

Verify scrupulously that the connections and their isolation are correct

Connect the mains power supply and batteries

Proceed to the test of the system verifying the operation of the panel and all the detection and indicating system.

NOTA: The installation of the equipment must be carried out by authorized staff, in the respect of the regulation in force (law 46/90). All the materials used for the installation of the system must be conformed to what contents this manual and the regulation in force. 5-3 PANEL MOUNTING

226mm

40mm

3

1 1

2

1

3

1 185mm

PART DESCRIPTION

1 Holes for wall mounting of panel

2 Hole for passage cables

3 Holes for passage cables

For the panel mounting proceed like follow: - Verify that the point of implantation of the panel is free of electrical cables and canalizations - Pierce 4 holes on the wall (according to above measures) for insertion of appropriate supports - Use hole (2) for the passage of connection cables - Use holes (3) for the passage of connection cables

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 23/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

6- PANEL MAINTENANCE Panel needs a periodic maintenance, proceed like follow: Remove eventual dust present with a cloth lightly humid (do not use solvent). Verify that the POWER green led is steady on and that all the others leds are

off. Make verify from qualified staff: Voltage of group of power supply output (in presence of mains and with

batteries connected) that must be between: min. 26,5V and max. 28,5V. Operation of the system in absence of mains: the battery voltage must have a

value ≥ 24V. Operation of all the visual and acoustic signals (activate TEST function) Integrity of the connections and the isolations Operation of the alarm outputs.

Moreover batteries and additional auto powered devices must be replaced within a period of 3 years. 7- IMPLANTATION AND TERMINAL BLOCKS 7-1 MODULE WFC202C

JP3 CONFIG

BZ1

F1

F3

RL1

RL2

RL3

MCU

TR1

JP6 ABIL

1 2 3 4 5

6 7 8 9

10 11 12 13

RV1

L N

MR

M2

F2

1 2 3 4

1AT

3,15AT 250mAT

M3

RED + BATTERY

BLACK

- BATTERY

CN1

NTC

P1 RESET

RL4

16 15 14

M4

fig.6 – WFC202C module MCU: Microprocessor of panel. It controls the operation of panel by the means of

firmware. The panel configuration resides in the MCU. BZ1: Piezoelectric buzzer for local acoustic signalizations. RL1: Alarm relay. It manages the monitored alarm output (terminal 10 and 11). Moreover, through one of the two NC contacts, RL1 manages, for auto powered

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 24/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

sounders, an alarm output that supplies 27V in normal state and 0V in alarm condition (terminal 9). The maximum capacity of this contact is 5A/30V D.C.

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 25/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

RL2: Fault relay. It is normally active and becomes deactivate in fault condition. The

maximum capacity of this contact is 1A/30V D.C. RL3: Battery fault relay. It is normally active and becomes deactivate in battery fault condition. RL4: Alarm output relay, free voltage contact : activation of 1 free voltage contact

on alarm state (30V/1A) (terminal block 14-16) F1: 0,25A temporised fuse (250mAT) for the protection of the mains (230V) power supply input. F2: 3,15A temporised fuse (3,15AT) for the protection of the positive of battery.

F3: 1A temporised fuse (1AT) for the protection of the output lines and the auxiliary

outputs present on main terminal block and on zones terminal block. The burning of this fuse is indicated by the ignition of the corresponding led on the panel. JP1: Connector for external access level 2 activation. The activation of access level 2 is necessary for management of commands of reset, test and deactivation. It is possible to activate the access level 2 in the 2 following ways: - dialling the access code (see par.3-3); - closing JP1 through a free voltage contact (electromechanical key). Access level 2 is indicated by corresponding led (see par.2-1 Figure 3). It is temporised 30 seconds if it is activated through dialling; it is permanent with electromechanical key (as soon as JP1 is no longer closed, panel countdowns 30s and switches into access level if no operation is carried out on panel) JP2: Jumper of activation of configuration mode.

Set JP2 and push P1 button on µP board for a few moment. Panel enters in configuration mode. To leave configuration mode remove JP1.

CN1: Auxiliary outputs connector.

RV1: Potentiometer for calibration of regulated output voltage. Do not modify the

factory adjustment. TR1: Transformer of mains: primary 230V/60Hz, secondary 33V, power 15VA. NTC: Thermo sensitive element for the thermal compensation of the voltage of battery charging. P1: RESET button. Press for hardware reset the panel.

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 26/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

Mains terminal block (MR)

L, N Terminal mains input 230V~ +10%/-15% 60Hz.

Terminal electrical earth

NOTA: the connection of the mains must be executed in conformity with low voltage directives. Following criteria must be respected: a) Respect the connections L and N. b) For the connections use anti flame cables with minimal section of 1,5mm². c) Keep the cables of mains far from the electronics and the low voltage connections d) Verify the earth connection. e) Anticipate, while installation, a bipolar cut and safety device for mains 7-1-2 Batteries connections (red and black cables) Red wire Positive of battery protected by fuse F2 (3,15A T)

Black Negative of battery

The battery connection (batteries not supplied) is carried out like indicated in the following design:

RED +BATTERY

BLACK - BATTERY

+

- +

-

INTERCONNECTION CABLE

fig.7 – cable for batteries connection The BLACK cable is to be connected to the negative pole (-) of the first battery, while the RED cable is to be connected to the positive pole (+) of the second battery. Besides, the first battery is to be connected to the second one by connecting the positive of first battery to negative of second battery. The batteries must be sealed lead type 12V 4Ah.

NOTA: a) Make sure not to invert the battery connections in order not to damage the components of panel and system. b) Connect the batteries to system only when installation is finished and connections of connectors and their isolation are checked. c) Use same type batteries and with envelop flammability class UL94-V2 or better.

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 27/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

7-1-3 Exploitable outputs (CN1)

Connector CN1 (see fig.6); it makes available the following outputs: Pin: Description:

1 Negative.

2 Positive +27V protected with battery fuse F2 (3,15AT).

3 Output VLINEE. Provides in normal condition +27V with serial 4,7k resistor. That voltage becomes null during cycle of line reset. Max admissible current is 4mA

4 Auxiliary programmable electronic output. It is an open collector output that closes to

negative, with serial 4,7kΩ resistor, when active. It can drive a max load of 4mA/30V NOTA: The output is not designed for the direct command of actuator lines. To do

so it is necessary to interface an electronic relay module

7-1-4 Terminal block for connection of zones 1, 2 (M2)

The panel controls 2 lines of absorption detectors. Every physical line corresponds to a zone of panel and consists on 2 conductors on which it is possible to connect up to 32 absorption detectors max. NOTA: the total absorption of the detectors in normal condition does not have to exceed 2mA The 2 lines of panel supply 27V with an output impedance of 390Ω and they are used for powering of detectors in order to reveal the conditions of standby, alarm and fault line. The balance of the line is obtained connecting as end of line element a resistor 3,9 KΩ ¼ W or 4,7 KΩ ¼W according to the type of thresholds selected; see par.4-5.

1 +27,5V; positive protected by fuse F1 (1AT).

2 Input – detector line 2, zone 1 / negative

3 Input + detector line 2, zone 1 (+27V with serial resistor 390 Ω)

4 Input – detector line 1, zone 2 / negative

5 Input + detector line 1, zone 2 (+27V with serial resistor 390 Ω)

For the connection of the detectors to panel refer to relative indications par.7-3.

7-1-5 Terminal block for connection of actuators (M3)

6 Fault common relay contact (RL2).

7 Fault N.C relay contact (RL2, relay normally excited). Max capacity 1A/30V D.C.

8 Fault N.O relay contact (RL2, relay normally excited). Max capacity 1A/30V D.C.

9 Auxiliary alarm output with positive at extinction, not monitored. It supplies +27,5V

in normal condition that becomes null in alarm condition; it can be used for example for command/power of auto powered sounders. Max capacity 1A.

10, 11

Fire alarm output, monitored, for command of sounders. In alarm conditions, terminal 10 is positive terminal (+27,5V) and terminal 11 is negative terminal. In normal condition the voltage on the terminals is inverted. In order to guarantee the balance of the line it is necessary the alarm devices do not absorb current, that why a diode must be inserted in serial with each alarm device (if not already present internally). 3,9 KΩ ¼ W or 4,7 KΩ ¼ W resistor must be present as an end of line element to insure line monitoring (line balance). Max capacity 0,5A. For the connection of alarm devices refer to par.7-2.

12 Negative

13 +27,5V; positive protected with fuse F1 (1AT).

7-1-6 Terminal block for connection of alarm output relay (M4):

14 Alarm output common relay contact (RL4). Max 1A a 30V=.

15 Alarm output N.O relay contact (RL4). Max 1A a 30V=.

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 28/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

16 Alarm output N.C relay contact (RL4). Max 1A a 30V=.

NOTA: Limits of applicable voltage for inputs/outputs: min 0V/max 30V D.C

NOTA: Maximum charges applied on panel must be in accordance with specifications listed par.1-6. The sum of the currents absorbed in continuous by external devices must not exceed 0,1A in continuous and 0,5A for short periods (max 30min. with batteries connected and charged).

7-2 Connection of alarm actuators

The connection of the sounders will be carried out like indicated in the following figure using anti flame cable with section appropriate for actuators/sounders management and according to the length of the line. For the calculation of the section of the conductors refer to the following formula:

Sz= (0, 04 x l x L)/Vl Sz = minimum section in mm² of each of the two conductors of the line

I= maximum total current in ampere absorbed in alarm condition by the actuators/sounders connected to the line

L= total length of the line in meter Vl= maximum falling of voltage in volt on the line (on both conductors). For the

calculation consider a falling of voltage not over 1V. The actuators/sounders will be able to operate with voltage comprised between 20V and 30V D.C and must have a total absorption compatible with the data of panel

(see par.1-4-2).

fig.8 - Connection of a generic sounder to panel WFC202C

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 29/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

7-3 Connection of detectors The connection of the detectors to the lines/zones is carried out with shielded anti flame cables, 2 x 0,5mm² min, with shield connected to earth of panel. 32 detectors or push-buttons max (470 Ω ¼ W limitation resistor in serial for push button). An end of line resistor must be connected to the last detector as element for line balance (monitoring of line). The value of such resistance depends on the selected thresholds and can be 4,7KΩ ¼ W or 3, 9 KΩ ¼ W; see par.4-5.

Refer to the next part CONNECTION DIAGRAM for the exact installation.

NOTA: If a line remains unused it is necessary to terminate the line with an appropriate end of line resistor.

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 30/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

8- Connection diagram 8-1 Connection of detectors WÄCHTER (WÄCHTER ) WFD-OC05 / WFD-TRC05 / WFD-TSC05 to panel

fig.9 - Example of connection of detectors on zone 2 and push-buttons on zone 1.

NOTA: for a correct operation make

sure that Fare thresholds (factory setting) are set (see par.4-5)

32 conventional detectors max [OC05/TRC05/TSC05], with 3,9KΩ ¼ W end of line resistor (orange-white-red-gold)

3,9Kohm

¼ W

Anti flame cable

2 x 0, 5 + shield

N.O. N.O. N.O.

32 push-buttons max with N.O contact and 470 Ω ½ W serial resistor (yellow- purple-brown-gold)

Shield Connected to

earth of panel 470Ω ¼ W

470Ω ¼ W

470Ω ¼ W

1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7

3,9Kohm

¼ W

13

6

5 4

2 1

Zone1

Zone2

+L -L +L -L

WFC-202C terminal blocks

3

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 31/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany Tel: +4951378253079 | Fax: +4951378253083 [email protected] | www.waechtergroup.de

8-2 Connection of visual/acoustic indicators to panel

End of line resistor: 4, 7 KΩ ¼ W or 3, 9 KΩ ¼ W

Powering line, monitored line

FIRE ALARM

Powering line, not monitored line

FIRE ALARM

WFC202C module

1

2 3 4

5

6 7 8 9

10 11 12 13

16

15 14

Figure 10- Connection of sounders to WFC202C panel

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 32/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany

FAST GUIDE These pages resume the main functions of panel. It is therefore advised to detach this section and to conserve it close to panel. The table refers to the following figure. `

Figure 11 – WFC202C panel DESCRIPTION POWER (1) ON indicates the panel is working with the main power source

(presence of mains). OFF indicated that panel is working with only batteries. BLINKING indicates the panel is working with mains source but a fault is present on the group of power source

FAULT (2) ON indicates the presence of fault condition. Verify the other indications to find the cause.

DISABLE (3) ON indicates the presence of a condition of disable. BLINKING in regular way indicates the phase of reset.

ALARM (4) ON indicates the presence of a condition of alarm. BLINKING with long period of ignition and short extinction indicates the phase of delay of alarm in course. BLINKING with regular period indicates that an alarm had occurred previously (memory).

POWER FAULT (6) ON indicates the presence of a condition of fault on group of power source.

EARTH FAULT (7) ON indicates that a condition of low isolation is present.

SOUNDERS FAULT (8) ON indicates the presence of a fault condition on the monitored line that commands the alarm sounders

CPU FAULT (9) ON indicates that the microprocessor is temporary or permanently out of control. This fault can be caused by electrostatic disturbances, an abrupt decrease of voltage or a physical breakdown of the card (in this last case the signalling is not resettable).

FUSES FAULT (10) ON indicates an anomaly on the fuses intended for protection of panel and lines.

ZONES FAULT (15,16) ON indicates the presence of a fault on the relative zone

PRE ALARM/ALARM ZONES (13,14)

ON indicates that the relative zones are in alarm. BLINKING, with a long period of ignition and a short period of extinction, indicates that the zones are found in pre alarm conditions.

DISABLED ZONES (11,12) ON indicates that the relative zones are disabled. BLINKING in regular way indicates that the zones are in phase of reset.

DISABLE SOUNDERS (17) ON indicates the deactivation of the alarm/sounders outputs.

LEVEL 2 (19) ON indicates that the access level 2 is active

SILENCE BUZZER (18) ON indicates that manual silencing of the buzzer is carried out

1

2

3

4

6

7

8

9

10

P3 17

18 P4

P5

19

P3 11 13 15

P2 12 14 16

Installation & Operations Manual

WFC202C Conventional Fire Alarm Control Panel

Document : WFC202C Version : WF5.10 Page : 33/33

Wächter GmbH Sicherheitssysteme | Alte Ricklinger Str. 3, 30823 Garbsen, Germany

NOTA: The regular blinking of a led indicates the memorization of an event that is no longer present. DESCRIPTION OF THE KEY COMMANDS: ENABLE/DISABLE ZONES (P1, P2)

Access level 1: allows to access level 2. Access level 2: enabling/disabling zones.

ACTIVATION/DEACTIVATION OF ALARM OUTPUTS (P3) Access level 1: unused Access level 2: allows activate/deactivate the alarm output.

SILENCE BUZZER AND OUTPUTS (P4) Access level 1: allows the silencing of buzzer. Access level 2: allows to deactivate outputs (*).

RESET (P5) Access level 1: unused. Access level 2: restoration of panel to normal state.

(*) the function is available if set in phase of configuration.

ZONE DESCRIPTION

1

2

TECHNICAL ASSISTANCE FIREMEN