3 5 assessment condition of capacitive voltage transformer using tangent delta measurement
TRANSCRIPT
THE CONDITION OF CAPACITOR VOLTAGE THE CONDITION OF CAPACITOR VOLTAGE TRANSFORMER USING TAN DELTA TRANSFORMER USING TAN DELTA
MEASUREMENTMEASUREMENT
Presenter Presenter DimasDimas BangunBangun FiddiansyahFiddiansyah, , SugiyonoSugiyono
©Doble E
ngineeri
ng
22
BACKGROUNDBACKGROUND
CVT Interruption due to insulation failureCVT Interruption due to insulation failureDegradation of Insulation can generally be Degradation of Insulation can generally be restored restored Tan delta measurement is method to Tan delta measurement is method to investigate insulation condition in CVTinvestigate insulation condition in CVT©Do
ble Engin
eering
33
CVT PARTSCVT PARTS
CVT CVD + EMU
Trench Electric
CVD consisted of Capacitor Stacks in series Connection©Do
ble Engin
eering
44
DEFINITIONDEFINITION……..
When tan delta values more increase, When tan delta values more increase, Dissipation power more increaseDissipation power more increase
V
I
δ Ø
DP = Ir2.R = V.I cos ØDP = V.ω.C. sinδ / cos ØDP = V2 . ω . C . Tan δ
IC
©Doble E
ngineeri
ng
55
POWER SYSTEM NETWORK OF POWER SYSTEM NETWORK OF LAMPUNG PROVINCELAMPUNG PROVINCE
©Doble E
ngineeri
ng
66
CVT POPULATION CVT POPULATION IN LAMPUNG PROVINCEIN LAMPUNG PROVINCE
8
15
6 6
35
26
36
21
56
63
6
20
35
0
10
20
30
40
50
60
Tarahan Kotabumi Tegineneng
BALTEAU
ABB
MAGRINIGALILEO
HAEFELYTRENCH
JUMLAHTOTAL
©Doble E
ngineeri
ng
77
TAN DELTA MEASUREMENTTAN DELTA MEASUREMENT
Measurement Method :Measurement Method :Ungrounded Specimen Test (UST)Ungrounded Specimen Test (UST)Grounded Specimen Test (GST)Grounded Specimen Test (GST)Grounded Specimen Test using guard Grounded Specimen Test using guard connection (connection (GSTgGSTg))
Output Parameters :Output Parameters :Capacitance (Total Charging Current)Dielectric LossPower Factor
©Doble E
ngineeri
ng
99
INTERPRETATIONINTERPRETATION
IEC 60044IEC 60044--5 20045 2004--04 Capacitor Voltage 04 Capacitor Voltage Transformer : Rated capacitance Transformer : Rated capacitance --5% to +10%5% to +10%
Tan Tan δδ ≤≤ 5 x 105 x 10--33 at 20at 20ooCC
DobleDoble Test ProcedureTest ProcedureTan Tan δδ ≤≤ 5 x 105 x 10--3 for Oil/ Paper Construction3 for Oil/ Paper Construction
©Doble E
ngineeri
ng
1010
TAN DELTA MEASUREMENT (1)TAN DELTA MEASUREMENT (1)
Tan δ : 5 x 10-3
Ctotal : 6200 (-5 ; +10) %
Tan δ : 5 x 10-3
Ctotal : 6200 (-5 ; +10) %
Tan δ : 5 x 10-3
Ctotal : 6200 (-5 ; +10) % Ph T. 7500–8250 PF
Tan δ : 5 x 10-3
Ctotal : 6200 (-5 ; +10) %
Tan δ : 5 x 10-3
Ctotal : 6200 (-5 ; +10) %
Interpretation
171717
171717
171717
171717
161616
Lifetime(Years)
CVT Replacement5,476,155,53
6114,357009,616629,23
RST
Baturaja(Ln. Bkmng)
Monitoring5,755,665,77
6266,726339,546289,79
RST
Kotabumi(ln. Tgnng 1)
CVT Replacement6,166,883,81
6592,196901,737638,39
RST
Tegineneng(Ln ktbmi 1)
CVT Replacement7,418,957,46
6988,066914,736620,50
RST
Teluk Betung(Ln Natar 1
Monitoring6,696,416,21
6194,056298,746207,58
RST
Tarahan(ln Sutami 1)
RecommendationTan delta(x 10-3)
Capacitance (pF)
PhaseSubstation
©Doble E
ngineeri
ng
1212
Failure CVT FactorFailure CVT FactorTechnical LifetimeTechnical LifetimeOver voltagesOver voltagesHumidityHumidityHigh TemperatureHigh TemperatureMechanical FailureMechanical Failure©Do
ble Engin
eering
1515
TAN DELTA MEASUREMENT TAN DELTA MEASUREMENT ANALYSISANALYSIS
Based on Interpretation stated that :Based on Interpretation stated that :High of Power Factor Values more than 1%, but High of Power Factor Values more than 1%, but Capacitance values still covered in its range, Capacitance values still covered in its range, suggested to Retest in the next 6 month to get suggested to Retest in the next 6 month to get the trending datathe trending dataChanges of CVT Capacitance Values from its Changes of CVT Capacitance Values from its range criteria within range criteria within --5 % to +10% suggested to 5 % to +10% suggested to be Replaced. be Replaced.
©Doble E
ngineeri
ng
1616
CVT monitoring using tan delta CVT monitoring using tan delta measurement is useful in keep sustainability measurement is useful in keep sustainability and reliability of power system network.and reliability of power system network.Failure of CVT Can be effected due to Failure of CVT Can be effected due to Dielectric Insulation FailureDielectric Insulation FailureOperational condition of CVT can be early Operational condition of CVT can be early detected both for normal and abnormal detected both for normal and abnormal conditioncondition
©Doble E
ngineeri
ng
1717
It is important to test CVT Power It is important to test CVT Power Factor & Capacitances through tan Factor & Capacitances through tan delta measurement to get trendings delta measurement to get trendings analisys analisys CVT with Capacitance & tan delta CVT with Capacitance & tan delta values which out of its limit values which out of its limit suggested to be Replacedsuggested to be Replaced