Page1 Holding company ”EMZ” Head office and Factory: Aradippou Industrial and Commercial Estate, 7105 Larnaca, Cyprus RN HE 132211; IN 9.84 TRANSFORMER TEST VAN TransLAB-3 The transformer test van performs the following functions: 1. Automatic Tangent Delta Testing 2. Three Phase Transformer Turns Ratio Testing 3. Transformer Resistance Testing 4. Sweep Frequency Response Analyzing 5. Insulation Resistance Testing 6. Winding resistance testing; 7. Short circuit testing 8. AC/DC 100/80 kV Tester A. Main Equipment 1 Central Control Operating Unit The entire operation control of the mobile cable test van is performed via a central operating unit and controls for the individual high voltage operating modes. The unit and its controls are laid out centrally in the operator’s field of vision. All operation modes, techniques and safety control are fully integrated in the system. 2 CDS-6000 Fully automatic 12 kV insulation power factor / dissipation factor (tan ∂) test set designed for condition assessment of electrical insulation in high voltage apparatus such as transformers, bushings, circuit breakers, cables, lightning arresters and rotating machinery. Number ФПА (VAT) 10132211L

Upload: trinhdieu

Post on 09-Mar-2018

245 views

Category:

Documents


15 download

TRANSCRIPT

Page 1: TRANSFORMER TEST VAN TransLAB-3 - · PDF fileTRANSFORMER TEST VAN TransLAB-3 . The transformer test van performs the following functions: 1. Automatic Tangent Delta Testing 2. Three

Page

1

Holding company ”EMZ” Head office and Factory:

Aradippou Industrial and Commercial Estate, 7105 Larnaca, Cyprus

RN HE 132211; IN 9.84

TRANSFORMER TEST VAN TransLAB-3

The transformer test van performs the following functions:

1. Automatic Tangent Delta Testing 2. Three Phase Transformer Turns Ratio Testing 3. Transformer Resistance Testing 4. Sweep Frequency Response Analyzing 5. Insulation Resistance Testing 6. Winding resistance testing; 7. Short circuit testing 8. AC/DC 100/80 kV Tester

A. Main Equipment

1 Central Control Operating Unit

The entire operation control of the mobile cable test van is performed via a central operating unit and controls for the individual high voltage operating modes. The unit and its controls are laid out centrally in the operator’s field of vision. All operation modes, techniques and safety control are fully integrated in the system.

2 CDS-6000

Fully automatic 12 kV insulation power factor / dissipation factor (tan ∂) test set designed for condition assessment of electrical insulation in high voltage apparatus such as transformers, bushings, circuit breakers, cables, lightning arresters and rotating machinery.

Number ФПА (VAT) 10132211L

Page 2: TRANSFORMER TEST VAN TransLAB-3 - · PDF fileTRANSFORMER TEST VAN TransLAB-3 . The transformer test van performs the following functions: 1. Automatic Tangent Delta Testing 2. Three

Page

2

CDF-6000 provides the most accurate test results for power apparatus. CDF-6000 incorporates breakthrough technology and design that gives accurate and reliable results over time.

Specifications: Input: 180-270V, 50/60Hz

Output: Test Voltage: 0.5 ~12kV selectable Test current: 200mA max Meas range: 3pF ~ 0.05μF @ 12kV

60pF ~ 1μF @ 0.5kV Accuracy:

Capacitance ±1% of reading +1pF Tangent ±1% of reading +0.0004 Voltage: ±1% of reading

3 FRAX-150 Sweep Frequency Response Analyzer

Power transformers are some of the most vital components in today’s transmission and distribution infrastructure. Transformer failures cost enormous amounts of money in unexpected outages and unscheduled maintenance. It is important to avoid these failures and make testing and diagnostics reliable and efficient.

The FRAX 150 Sweep Frequency Response Analyser (SFRA) detects potential mechanical and electrical problems that other methods are unable to detect. Major utilities and service companies have used the FRA method for more than a decade. The measurement is easy to perform and will capture a unique “fingerprint” of the transformer. The measurement is compared to a reference “fingerprint” and gives a direct answer if the mechanical parts of the transformer are unchanged or not. Deviations indicate geometrical and/or electrical changes within the transformer.

Page 3: TRANSFORMER TEST VAN TransLAB-3 - · PDF fileTRANSFORMER TEST VAN TransLAB-3 . The transformer test van performs the following functions: 1. Automatic Tangent Delta Testing 2. Three

Page

3

4 MTO-330 Transformer Ohmmeter Test Set

The MTO series delivers full eight-terminal/six-winding resistance measurement capability. It is designed to save time by testing all six windings without having to disconnect and reconnect leads. Also, the simultaneous winding magnetization (SWM) method gives fast and reliable measurements even on large transformers with delta configuration on the low voltage side.

Additionally, the MTO series leads are interchangeable with the Megger TTR series of three-phase turns ratio instruments which eliminates additional connecting time for turns ratio measurements. The MTO330 offers the same functionality as the MTO300. However, it is equipped with an onboard computer featuring full QWERTY keyboard and navigational pushbuttons as displayed on an 8.4 inch full-color VGA transflective screen viewable in bright sunlight.

5 TTR-330

The TTR300 Series of three-phase transformer turns ratio test sets are designed to measure the turns ratio of power, instrument, and distribution transformers in a substation or manufacturing environment. A rugged and robust design makes these instruments well suited for use in a variety of harsh environments. Our leads are specially designed to provide the necessary flexibility needed in cold weather.

The TTR300 Series are ideal for use by power transformer manufacturers. Their unique testing procedures and storage capability allows an operator to set up and test difficult three-phase transformers (with multiple tap changers and bushing CTs) in a fraction of the time than it used to take with other TTRs. This test also includes a pass/fail limit of individual ratios. The TTR300 Series also measure the phase deviation of the transformer primary versus secondary. This quickly indicates problems in the transformer such as partial shorted turns and core faults. This measurement is also useful in verifying phase errors in all types of PTs and CTs.

Page 4: TRANSFORMER TEST VAN TransLAB-3 - · PDF fileTRANSFORMER TEST VAN TransLAB-3 . The transformer test van performs the following functions: 1. Automatic Tangent Delta Testing 2. Three

Page

4

6 Insulation Resistance Tester – MIT-1025

The new insulation resistance tester MIT1025 is available up 20 TΩ for the 10 kV model. The new instrument is smaller and lighter than previous models yet offer advanced features and rapid charge capability. A key productivity feature is the ability to take measurements when connected to line power/mains with a dead battery. Intelligent battery charging ensures the optimum charge rate as a function of battery level, resulting in minimum charge times. The rugged, unique dual case design provides the ultimate protection for a portable instrument and a clip-on lead pouch ensures that leads remain with the instrument at all times. The case lid is removable for improved terminal access. IP rating is IP65 with the case closed preventing water/dust ingress. High reliability and safety are built in; all models are safety rated to CATIV 600 V and are double insulated.

Five preset voltage ranges are provided in insulation test mode, plus a user settable lock voltage range. Any selectable test voltage may be locked and restored via the selector switch, thereby increasing efficiency of commissioning and repetitive tests. Preconfigured diagnostic tests include Polarization Index (PI), Dielectric Absorption Ratio (DAR), dielectric discharge (DD), Step Voltage (SV) and ramp test.

B. Portable Equipment

7 TRT-27-20

Transformer Resistance Tester ‘TRT-27-20’ has already been in use in the field of the electric power system .To enhance the instrument’s performance and make the test check quickly, the ‘TRT-27-20’ is a high precision, new generation, light weight, large output test current and micro-processor controlled tester. ‘TRT-27-20’ adopts advanced switch power technology. It can output various test currents with a wide test range. The instrument is controlled by a high-speed micro-processor. It has a built-in printer to save results.

Page 5: TRANSFORMER TEST VAN TransLAB-3 - · PDF fileTRANSFORMER TEST VAN TransLAB-3 . The transformer test van performs the following functions: 1. Automatic Tangent Delta Testing 2. Three

Page

5

Specifications: Input Power: 230V ± 10%; 50 Hz Maximum power dissipation:

500W @ 20A

Testing current: 1A / 5A / 10A / 20A Measuring Range: 1 uΩ- 20Ω (1A)

1 uΩ- 4Ω (5A) 1 uΩ- 2Ω (10A) 1 uΩ- 1Ω (20A)

Accuracy: ± 0.2% full scale ± 3digits Resolution: 0.1uΩ Data storage: 255 Display: LCD screen; resistance

display in 4. digits Environmental temp: 0 to 40 deg C Environmental humidity:

<90%RH, non condensing

FEATURES • New switching power supply, output current steady, great power • Advanced signal measurement circuit, low noise, reliable test results • Automatic discharge and discharge indicator • Compact structure , small size, light weight, more suitable for field use • Multi-range output current provides wider range

8 OTSA-100

Insulating oil being an efficient cooling medium with high dielectric strength has been a recognized insulating medium in electrical equipment. Degradation of oil takes place due to acids, oxidation, sludge, gas and water absorption. A dielectric strength test shows the changes caused in oil due to these processes. OTSA-100 insulating oil testers are fully automatic microcontroller based testers completely self-contained with built-in printer.

Specifications: Test Voltage: 0-100kV Capacity: 100kV:2 kVA Resolution: 0.1 kV Accuracy: 2% Time of Breakdown: <10 milliseconds Rate of rise of Voltage:

0.5 to 5 kV adjustable per second ± 20%

Display: LCD screen; resistance display in 4. digits

Environmental temp: 0 to 40 deg C Environmental humidity:

<85%RH, non condensing

Page 6: TRANSFORMER TEST VAN TransLAB-3 - · PDF fileTRANSFORMER TEST VAN TransLAB-3 . The transformer test van performs the following functions: 1. Automatic Tangent Delta Testing 2. Three

Page

6

FEATURES • Tests as per international standards • Auto / Manual mode • 100 test result storage capacity • Large LCD display • Built in printer • User Friendly RS 232 Interface • Safety protection • Accurate performance

9 High voltage testing block HV-100M

HV functions: • High voltage DC test up to 80 kV of gap,

cable routes and other with leakage current control in the range of 0.2 мА. 2 мА, 20 мА.

• High voltage AC testing to 100kV outputs, dielectrics, as well as voltage limiter with the conduction current in the range of 2 мА. 20 мА. 200 мА.

• While high voltage DC testing of dischargers and etc with small capacitors the sliding compensator of 0.4uF is used

10 Testing voltage source TTO - 100/80

The maximum AC testing voltage is 100kV. The maximum DC testing voltage is 80kV at the maximum current 200 mА

Manage system integrate in control panel of the laboratory.

Page 7: TRANSFORMER TEST VAN TransLAB-3 - · PDF fileTRANSFORMER TEST VAN TransLAB-3 . The transformer test van performs the following functions: 1. Automatic Tangent Delta Testing 2. Three

Page

7

C. CONNECTING DEVICES

11 Cable Drum Racks

External connections for the L.V. cable test van are provided with a power feeding cable drum, a grounding cable drum and an output voltage cable drum.

• drum with LV main cable, 230Vac, 50Hz, length of cable 25m; • drum with grounding cable with a cross-section 25 mm2, length

of cable 25m; • drums with output cables, length of cable 25m; • drum with auxiliary ground cable, length of cable 15 m.

D. ELECTRICAL SAFETY SYSTEM

12 Electrical Safety Check System

The electrical safety system provides protection to the operating personnel as follows:

• monitoring the potential on the car (switching off if the potential is higher than 24V)

• monitoring the earth resistance (switching off if the resistance is higher than 25 Ohm)

• monitoring the door of the high voltage compartment (switching off the equipment if doors are opened)

• Emergency Switch to shut down the equipment in case of hazard

• Visible break load switch • Beacon and warning siren

Page 8: TRANSFORMER TEST VAN TransLAB-3 - · PDF fileTRANSFORMER TEST VAN TransLAB-3 . The transformer test van performs the following functions: 1. Automatic Tangent Delta Testing 2. Three

Page

8

E. PROTECTIVE EQUIPMENT

13 Voltage Detector -

Voltage Detectors are used to verify live or de-energized conductors. These testers may be used with rubber insulating gloves or hot sticks using the splined universal end fitting. Testers indicate the presence of voltage with an extra bright LED light and a distinctive audible signal. It is recommended that the tester be moved closer to conductor until warning is indicated, or it touches conductor, apparatus, or test point. Test the unit on a nearby energized conductor.

14 Personnel Protective Equipment / Tool Kit

1 Grounding rod 1 unit 2 3

Hot stick Dielectric gloves

1 unit 2 pair

4 Dielectric boots 1 pair 5 Protective helmet 2 units 6 7 8

Tool Kit Fire extinguishers Reflecting triangle

1 unit 2units 2units

F. VEHICLE

15 IVECO DAILY

TECHNICAL SPECIFICATIONS Engine: FIC E048IL/E3 – 4 STROKE -

2998cc, Εuro 3 Rated Output: 146HP @ 3000rpm Rated Torque: 350Nm @ 1400-2750 rpm Engine Details: Turbo Intercooler, Common Rail

Injection system Transmission:

IVECO 2840.6 6+1 Speed Manual synchronized. @ GVW 3500kg: Maximum Geared Speed 130 km/h, Gradeability 40%.

Suspension:

Front: Independent with Torsion Bar. Back: Parabolic springs Shock Absorbers: 2 front and rear Front and Rear Stabilizer bar Power steering

Wheels/Tires: 195/75R16 Michelin tubeless. Spare wheel located under the cargo area

Page 9: TRANSFORMER TEST VAN TransLAB-3 - · PDF fileTRANSFORMER TEST VAN TransLAB-3 . The transformer test van performs the following functions: 1. Automatic Tangent Delta Testing 2. Three

Page

9

22 VEHICLE BODY

Manufacturer can replace equipment and change design according to the equipment that

customers require to be included in the laboratory.

Page 10: TRANSFORMER TEST VAN TransLAB-3 - · PDF fileTRANSFORMER TEST VAN TransLAB-3 . The transformer test van performs the following functions: 1. Automatic Tangent Delta Testing 2. Three

Page

10

The transformer test van is designed to be easy to operate and service. It is equipped with high quality insulated wall panelling and air conditioning. The body is divided into technical and operator compartments separated by a partition wall. The technical compartment includes all the necessary tools and equipment for carrying out testing and inspections. Safety is an important feature of the laboratories and hence all equipment is properly mounted and secured for transit. The operator compartment provides a pleasant environment to work in with more room and plenty of storage. It is equipped with cabinetry and workbenches that increase the operators’ efficiency and productivity. Features

• Air conditioner • Internal lighting 230 VAC & 12V DC • Insulated walls and roof for thermal and noise • Special antistatic floor in operator area • Special aluminium tread plate suitable for rough loading in high voltage area • Partition wall, Operating desk & chair • Drawers for storage of accessories

G. DOCUMENTATION

23 Included one full set of laboratory documentation.

H. TRAINING

24 Full training is provided for the laboratory personnel. The training includes the full use of the

equipment and covers the basic laboratory operations such as safety management, routine and preventative maintenance of equipment.

I. WARRANTY

25 Our laboratories are covered by a warranty for a period of two year. At the end of this period, the

manufacturer can provide upon order an after-sales service of the equipment.

Page 11: TRANSFORMER TEST VAN TransLAB-3 - · PDF fileTRANSFORMER TEST VAN TransLAB-3 . The transformer test van performs the following functions: 1. Automatic Tangent Delta Testing 2. Three

Page

11

Contact information: Tel.: +357 24821788 Fax: +357 24821787 Mob.: + 357 99556229

E-mail: [email protected] Factory: 35 Everest Street, Aradippou Industrial and Commercial Estate, P.C. 7105 Larnaca,

Cyprus For letter: P.O.Box 410163, 6308, Larnaca, Cyprus

www.vitaldrive.net