  • 7/23/2019 3 IEC61850-Engineering in DIGSI.pdf

    1/12

    02/2007 1

    Power Transmission and Distribution

    Power Automation

    Progress Its that simple

    Power Transmission and Distribution

    Communication in Substations with IEC 61850

    Engineering in DIGSI

    Markus Spangler, Siemens AG, PTD EA 13

  • 7/23/2019 3 IEC61850-Engineering in DIGSI.pdf

    2/12

    05/2007 2

    Power Transmission and Distribution

    Power Automation

    Progress Its that simple

    Source-column in Matrix

    The engineering is done in the configuration matrix.

    To allocate information, DIGSI provides one column as sourcefor the system interface

    S System Interface

  • 7/23/2019 3 IEC61850-Engineering in DIGSI.pdf

    3/12

    05/2007 3

    Power Transmission and Distribution

    Power Automation

    Progress Its that simple

    Structural elements of the IEC 61850

    Which types of information should be allocated to source S

    All Commands with or without feedback C x

    Single point indication SP (from information catalog) x (only report

    External Single point indication ExSP x

    External Double point indication ExDI,ExDI_S x

    External operating value MVU x

  • 7/23/2019 3 IEC61850-Engineering in DIGSI.pdf

    4/12

    05/2007 4

    Power Transmission and Distribution

    Power Automation

    Progress Its that simple

    Destination-columns in Matrix

    The engineering is done in the configuration matrix.To allocate information, DIGSI provides two columns as

    destination for the system interface

    S System Interface with default protection indications (app.10%)

    and control indications assigned to logical nodes

    X Extended system interface with additional SIPROTEC-

    information (app. 90%) and user defined information

    (Recommendation) embedded in logical nodes

  • 7/23/2019 3 IEC61850-Engineering in DIGSI.pdf

    5/1205/2007 5

    Power Transmission and Distribution

    Power Automation

    Progress Its that simple

    Destination-columns in Matrix

    Which indication/information will be configured with which destination column?

    indications/informations described by standard:1.) predefined:

    will be configured to Systeminterface S (and cant also be deleted or changed)additionally a configuration to Extended Systeminterface X is possible (so all

    indications appear in logical device EXT)

    2.) user specific:

    will be configured to Systeminterface S, automatically to logical device CTRL,

    Extended Systeminterface X is not possible

    indications/informations described out of standard:

    1.) predefined:will be configured to Extended Systeminterface X, Systeminterface S

    is not possible

    2.) user specific:will be configured to Systeminterface S, automatically to logical device CTRL

    and Logical node GGIO, Extended Systeminterface X is not possible

  • 7/23/2019 3 IEC61850-Engineering in DIGSI.pdf

    6/1205/2007 6

    Power Transmission and Distribution

    Power Automation

    Progress Its that simple

    Structural elements of the IEC 61850

    Description of the Siprotec devices with 5 logical devices:

    PROT Protection

    CTRL Control

    MEAS Measurement DR Disturbance Recorder

    EXT extended

    Manufacturer-spanning, unique and complete!

    Where will I find my allocated information within the

    system configurator...

  • 7/23/2019 3 IEC61850-Engineering in DIGSI.pdf

    7/1205/2007 7

    Power Transmission and Distribution

    Power Automation

    Progress Its that simple

    Structural elements of the IEC 61850

    All information with destination X

    can be found under

    EXT extended

    All information with destination Scan be found under

    PROT Protection or

    CTRL Control or

    MEASMeasurement or

    DR Disturbance Recorder

  • 7/23/2019 3 IEC61850-Engineering in DIGSI.pdf

    8/1205/2007 8

    Power Transmission and Distribution

    Power Automation

    Progress Its that simple

    Structural elements of the IEC 61850

    Which types of information should be allocated to destination S X

    Single point indication SP (default) x

    Single point indication SP (from information catalog) xOutput Indication OUT x x

    Internal single point indication IntSP (default) x

    Double point indication DP,DP_I x

    Value Indication VI x

    Measurement value MV xMetered value of measured value MVMV x

    Measured value with time MVT x

    Limit values LV x

    Pulse metered value PMV x

  • 7/23/2019 3 IEC61850-Engineering in DIGSI.pdf

    9/1205/2007 9

    Power Transmission and Distribution

    Power Automation

    Progress Its that simple

    Structural elements of the IEC 61850

    The allocated indications can be found in the system configurator via thelogical devicesand have to be assigned to sourceand destination

  • 7/23/2019 3 IEC61850-Engineering in DIGSI.pdf

    10/1205/2007 10

    Power Transmission and Distribution

    Power Automation

    Progress Its that simple

    Application-specific interconnection lists

    Interconnections arealways combined in

    applications. This is

    ideal to keep the

    overview even in the

    case of a huge

    amount of inter-

    connected information.

  • 7/23/2019 3 IEC61850-Engineering in DIGSI.pdf

    11/1205/2007 11

    Power Transmission and Distribution

    Power Automation

    Progress Its that simple

    Standard and SIPROTEC text

    We pick up the user in his/her usual world:

    Apart from the standard text, he/she also sees the

    text of the assigned SIPROTEC object or at least a

    text in accordance with the SIPROTEC language

    world.

    Power Transmission and Distribution

  • 7/23/2019 3 IEC61850-Engineering in DIGSI.pdf

    12/1205/2007 12

    Power Automation

    Progress Its that simple

    Thank you very much for your attention.