Ulazni podaci - Konstrukcija
Izometrija
Dimenzionisanje (celik)STAP 4-10CROSS-SECTION: L 60x60x6JUS
CROSS-SECTION PROPERTIES
z
y
6 0
60
1 6 .9
16
.9
6
[m m ]
T
Ax = 6.910 cm2 Ay = 3.600 cm2 Az = 3.600 cm2 Iξ = 36.100 cm4 Iη = 9.430 cm4 Iz = 22.765 cm4 Iy = 22.765 cm4 Ix = 0.860 cm4 Wy = 5.282 cm3
UTILISATION RATIO FOR LOADING COMBINATIONSTower - 3D Model Builder 6.0 Registered to Nenad Dimitrijevic Radimpex - www.radimpex.rs
4. γ=0.53 3. γ=0.00
KONTROLA DEFORMACIJA
Maksimalni ugib stapa u = 0.769 mm(load 4, at 42.8 cm from the start of the member)
SLUCAJ OPTERECENJA: 4FAKTOR SIGURNOSTI : 1.50DOPUSTENI NAPON : 10.45MERODAVNI UTICAJI (pocetak stapa)
The axial force design value N = -1.078 kNThe bending mom.design value(y-y) My = -0.489 kNmThe shear force design value(z-z) Tz = 3.531 kNSystem length L = 107.00 cmDuzina izvijanja oko z ose li,z = 107.00 cmDuzina izvijanja oko y ose li,y = 107.00 cmKriva izvijanja za z osu CKriva izvijanja za y osu C
MEMBER SUBJECT TO AXIAL COMPRESSION AND BENDING
KONTROLA STAB.PRI EKSC. PRITISKU JUS U.E7.096
Radius of gyration i,z = 2.286 cmRadius of gyration i,y = 1.168 cmSlenderness λz = 46.813Slenderness λy = 91.594Non-dimensional slenderness λ'z = 0.407Non-dimensional slenderness λ'y = 0.797Relativni napon σ' = 0.015Koef.zavisan od oblika Mz β = 1.000Bezdimenzionalni koeficijent κ,z = 0.894Bezdimenzionalni koeficijent κ,y = 0.664Koeficijent povecanja uticaja Kmz = 1.000Koeficijent povecanja uticaja Kmy = 1.010Uticaj ukupne imperfekc. stapa Knz = 1.102Uticaj ukupne imperfekc. stapa Kny = 1.295Poluprecnik inercije prit.zone i_prit = 1.732 cmLength between lateral restr.points L_lat. = 107.00 cmDuzina pritisnute zone L_prit. = 21.795 cmUsv. razmak bocno nepomer. tacaka
L_lat. = 21.795 cm
Slenderness λ,y = 12.583Granicna vitkost λ,cr = 48.969 λ,y < λ,crGranicni napon izvijanja σ_d = 15.680 kN/cm2Koef.povecanja ut. od b.i. θ = 1.000Normalni napon od N σ(N) = 0.156 kN/cm2Normalni napon od My σ(My) = 5.132 kN/cm2Maksimalni napon σ_max = 5.383 kN/cm2Dopusteni napon σ_dop = 10.453 kN/cm2
Stress control: σ_max <= σ_dop
Smicuci napon τ = 0.981 kN/cm2Dopusteni smicuci napon τ_dop = 6.035 kN/cm2
Stress control: τ <= τ_dop
COMPARATIVE STRESS CONTROLTower - 3D Model Builder 6.0 Registered to Nenad Dimitrijevic Radimpex - www.radimpex.rs
Normalni napon σ = 5.288 kN/cm2Smicuci napon τ = 0.981 kN/cm2Maximal comparative stress σ,up = 5.554 kN/cm2Dopusteni napon σ_dop = 10.453 kN/cm2Stress control: σ,up <= σ_dop
SLUCAJ OPTERECENJA: 4FAKTOR SIGURNOSTI : 1.50DOPUSTENI NAPON : 10.45MERODAVNI UTICAJI (na 42.8 cm od pocetka stapa)
The axial force design value N = -1.078 kNThe bending mom.design value(y-y) My = 0.351 kNmThe shear force design value(z-z) Tz = 0.706 kNSystem length L = 107.00 cm
KONTROLA STABILNOSTI NA IZBOC.LIMOVA JUS U.E7.121Izbocavanje nozice valj.L preseka
Dimenzije lima a/b/t = 107/6/0.6 (cm)Nacin oslanjanja: BOdnos a/b α = 17.833 Ivicni normalni napon u limu σ1 = -6.797 kN/cm2Ivicni normalni napon u limu σ2 = 2.448 kN/cm2Odnos σ1/σ2 Ψ = -0.360 Koeficijent izbocavanja k_σ = 5.719 Ojlerov napon izbocavanja lima σ_E = 189.80 kN/cm2Kriticni napon izbocavanja σ_cr = 1085.5 kN/cm2Relativna vitkost ploce λ'pσ = 0.120 Bezdim. koef. izbocavanja κ_pσ = 1.000 Korekcioni faktor c_σ = 1.250 Korekcioni faktor f = 0.000 Relativni granicni napon σ'u = 1.000 Granicni napon izbocavanja σ_u = 15.680 kN/cm2Faktorisani napon pritiska σ = 10.195 kN/cm2
Stress control: σ <= σ_u
Koeficijent izbocavanja k_τ = 5.353 Ojlerov napon izbocavanja lima σ_E = 189.80 kN/cm2Kriticni napon izbocavanja τ_cr = 1015.9 kN/cm2Relativna vitkost ploce λ'pτ = 0.094 Bezdim. koef. izbocavanja κ_pτ = 1.000 Korekcioni faktor c_τ = 1.250 Kriticni napon izbocavanja τ_cr = 1015.9 kN/cm2Relativni granicni napon τ'u = 1.000 Granicni napon izbocavanja τ_u = 9.053 kN/cm2Faktorisani smicuci napon τ = 0.294 kN/cm2
Stress control: τ <= τ_u
Kombinovano naponsko stanje σ'2 = 0.424
Stress control: σ'2 <= 1